charge fail, emergency stop, low oil pressure, high engine temperature, fail to start, low/high DC...

4
® SPECIFICATION DC SUPPLY 8V to 35V continuous CRANKING DROPOUTS Able to survive 0V for 50mS, providing supply was at least 10V before dropout and supply recovers to 5V. This is achieved without the need for internal batteries MAXIMUM OPERATING CURRENT 460mA at 12V. 245mA at 24V MAXIMUM STANDBY CURRENT 375mA at 12V. 200mA at 24V ALTERNATOR INPUT RANGE 15V(L-N) to 333V AC (L-N) absolute maximum ALTERNATOR INPUT FREQUENCY 50Hz - 60Hz at rated engine speed (Minimum: 15V AC L-N) MAGNETIC PICK-UP VOLTAGE RANGE +/- 0.5V to 70V Peak MAGNETIC INPUT FREQUENCY 10,000 Hz (max) START RELAY OUTPUT 15A DC at supply voltage FUEL RELAY OUTPUT 15A DC at supply voltage AUXILIARY RELAY OUTPUTS Three outputs 2A DC at supply voltage Two outputs volt free 2A at 250V AC DIMENSIONS 240mm x 172mm x 57mm 9.4” x 6.8” x 2.2” PANEL CUTOUT 220mm x 160mm 8.7” x 6.3” CHARGE FAIL/EXCITATION RANGE 0V to 35V BUILT IN GOVERNOR CONTROL Fully Isolated Minimum Load Impedence: 1000Gain Volts 0V - 10V DC Offset Volts + / - 10V DC BUILT IN AVR CONTROL Fully Isolated Minimum Load Impedence: 1000Gain Volts 0V - 10V DC Offset Volts + / - 10V DC ENCLOSURE PROTECTION (front of module) IP65 (with optional gasket) IP42 (without gasket) The DSE7510 is an Automatic Engine Control Module, designed to provide advanced load share functionality for diesel and gas generating sets that include non- electronic and electronic engines. The module also provides excellent engine monitoring and protection features. The module’s load share functions include automatic synchronising with built in synchroscope and closing onto dead bus. Direct and flexible outputs from the module are provided to allow connection to the most commonly used speed governors and automatic voltage regulators (AVRs). The module has been designed to combine a maximum of 16 generators and 16 mains (utility) supplies up to a maximum of 20 in one system, e.g. 16 generators and 4 mains (utility) supplies – DSE7560 required to synchronise with the mains (utility). The module has the ability to monitor generator under/over volts, over current, generator under/over frequency, under speed, over speed, charge fail, emergency stop, low oil pressure, high engine temperature, fail to start, low/high DC battery volts, fail to stop, generator short circuit protection, reverse power, generator phase rotation error, earth fault protection, loss of speed signal, fail to open, fail to close, out of sync, open circuit failure, negative phase sequence and loss of excitation. FEATURES Electronic engine capability RS232 or RS485 remote communications Modbus RTU Pin number protected front panel programming Exercise timer Back-lit LCD 4-line text display Multiple display languages Voltage measurement Configurable inputs (9) Configurable outputs (5) Automatic start Manual start Audible alarm LED indicators Built-in governor and AVR control Engine history event log Engine protection Fault condition notification to a designated PC Front panel mounting PC configuration Bus failure detection Configurable alarm timers Configurable start & stop timers Automatic load transfer SMS alert messaging Remote monitoring Magnetic pick-up KW overload alarms Engine temperature alarms LOAD SHARE FEATURES No-break transfer Peak shaving/peak lopping Sequential set start KW on mains (utility) level Mains (utility) decoupling test mode Manual speed/frequency adjust Phase locking Bus coupler control ROCOF & vector shift Generator load demand Automatic hours run balancing Dead bus sensing Existing load share line interfacing (P123 required) Direct governor & AVR communication Volts & frequency matching KW and Kvar load sharing Manual voltage adjust Auto ID negotiation BENEFITS Sends SMS messages to engineers to notify specific engine problems (GSM Modem and SIM card required) On-site and remote (modem required) module configuration In-built engine diagnostics removes the requirement for service equipment Full engine protection & instrumentation without the need for additional senders (Electronic engines only) Remote monitoring of the module using comprehensive DSE PC software License free PC software DSE POWER ® SHARING WITH SIMPLICITY. DSE7510 AUTO START CONTROL MODULE ELECTRONIC ENGINE CAPABILITY NEW RELEASE

Transcript of charge fail, emergency stop, low oil pressure, high engine temperature, fail to start, low/high DC...

Page 1: charge fail, emergency stop, low oil pressure, high engine temperature, fail to start, low/high DC battery volts, fail to stop, generator short circuit protection, reverse power, generator

®

SPECIFICATION

DCSUPPLY8V to 35V continuous

CRANKINGDROPOUTSAble to survive 0V for 50mS, providing supplywas at least 10V before dropout and supplyrecovers to 5V. This is achieved without theneed for internal batteries

MAXIMUMOPERATINGCURRENT460mA at 12V. 245mA at 24V

MAXIMUMSTANDBYCURRENT375mA at 12V. 200mA at 24V

ALTERNATOR INPUT RANGE15V(L-N) to 333V AC (L-N) absolute maximum

ALTERNATOR INPUT FREQUENCY50Hz - 60Hz at rated engine speed (Minimum:15V AC L-N)

MAGNETIC PICK-UP VOLTAGERANGE+/- 0.5V to 70V Peak

MAGNETIC INPUT FREQUENCY10,000 Hz (max)

START RELAYOUTPUT15A DC at supply voltage

FUEL RELAYOUTPUT15A DC at supply voltage

AUXILIARY RELAYOUTPUTSThree outputs 2A DC at supply voltageTwo outputs volt free 2A at 250V AC

DIMENSIONS240mm x 172mm x 57mm9.4” x 6.8” x 2.2”

PANEL CUTOUT220mm x 160mm8.7” x 6.3”

CHARGE FAIL/EXCITATION RANGE0V to 35V

BUILT IN GOVERNORCONTROLFully IsolatedMinimum Load Impedence:1000ΩGain Volts 0V - 10V DCOffset Volts + / - 10V DC

BUILT IN AVRCONTROLFully IsolatedMinimum Load Impedence:1000ΩGain Volts 0V - 10V DCOffset Volts + / - 10V DC

ENCLOSURE PROTECTION(front of module)IP65 (with optional gasket)IP42 (without gasket)

The DSE7510 is an AutomaticEngine Control Module, designedto provide advanced load sharefunctionality for diesel and gasgenerating sets that include non-electronic and electronic engines.The module also providesexcellent engine monitoring andprotection features.

The module’s load share functionsinclude automatic synchronisingwith built in synchroscope andclosing onto dead bus. Direct andflexible outputs from the moduleare provided to allow connectionto the most commonly used speedgovernors and automatic voltageregulators (AVRs).

The module has been designed tocombine a maximum of 16generators and 16 mains (utility)supplies up to a maximum of 20 inone system, e.g. 16 generatorsand 4 mains (utility) supplies –DSE7560 required to synchronisewith the mains (utility).

The module has the ability tomonitor generator under/over volts,over current, generator under/overfrequency, under speed, over speed,charge fail, emergency stop, low oilpressure, high engine temperature,fail to start, low/high DC batteryvolts, fail to stop, generator shortcircuit protection, reverse power,

generator phase rotation error, earthfault protection, loss of speed signal,fail to open, fail to close, out of sync,open circuit failure, negative phasesequence and loss of excitation.

FEATURES• Electronic engine capability• RS232 or RS485 remotecommunications

• Modbus RTU• Pin number protected front panelprogramming

• Exercise timer• Back-lit LCD 4-line text display• Multiple display languages• Voltage measurement• Configurable inputs (9)• Configurable outputs (5)• Automatic start• Manual start• Audible alarm• LED indicators• Built-in governor and AVR control• Engine history event log• Engine protection• Fault condition notification to adesignated PC

• Front panel mounting• PC configuration• Bus failure detection• Configurable alarm timers• Configurable start & stop timers• Automatic load transfer• SMS alert messaging• Remote monitoring• Magnetic pick-up• KW overload alarms• Engine temperature alarms

LOAD SHARE FEATURES• No-break transfer• Peak shaving/peak lopping• Sequential set start• KW on mains (utility) level• Mains (utility) decoupling test mode• Manual speed/frequency adjust• Phase locking• Bus coupler control• ROCOF & vector shift• Generator load demand• Automatic hours run balancing• Dead bus sensing• Existing load share line interfacing(P123 required)

• Direct governor & AVRcommunication

• Volts & frequency matching• KW and Kvar load sharing• Manual voltage adjust• Auto ID negotiation

BENEFITS• Sends SMS messages toengineers to notify specificengine problems (GSM Modemand SIM card required)

• On-site and remote (modemrequired) module configuration

• In-built engine diagnosticsremoves the requirement forservice equipment

• Full engine protection &instrumentation without the needfor additional senders (Electronicengines only)

• Remote monitoring of the moduleusing comprehensive DSE PCsoftware

• License free PC software

DSEPOWER®

SHARINGWITHSIMPLICITY.DSE7510AUTOSTARTCONTROLMODULE

ELECTRONICENGINECAPABILITY

NEWRELEASE

Page 2: charge fail, emergency stop, low oil pressure, high engine temperature, fail to start, low/high DC battery volts, fail to stop, generator short circuit protection, reverse power, generator

TIMERS & INPUT FUNCTIONSThe module has been designed to include the following timers and input functions:

• Start delay timer• Stop delay timer• Crank timer• Crank rest timer• Engage attempt & manual crank limit timers• Safety on delay timer• Warm up timer• Cooling timer• Energise to stop hold timer• Pre-heat timer• Pre-heat bypass timer• Smoke limiting control timer• Fail to stop timer• Over speed over shoot timer• Breaker pulse control timers• DC battery alarm delay timers• Sync/fail to sync timer

BUILT-IN FUNCTIONS• Alternator under/over volts• Alternator under/over frequency• Warning or shutdown on engine temperature, over/under speed, oilpressure

• Warning, shutdown or electrical trip on battery volts or over current• Shutdown or electrical trip on reverse power, phase rotation or shortcircuit fault

• Earth fault shutdown• Adjustable crank cycle/attempts• Full remote control and telemetry• 9 configurable digital inputs• 5 configurable and 2 fixed relay/FET outputs• System lock input• Load switching control push-button inputs• ROCOF/vector shift (mains/utility decoupling)• Negative phase sequence• Loss of excitation• PIN number

INSTRUMENTATION ANDALARMSThe DSE7510 module provides advanced metering and alarm functionalityvia the LCD display. The information can be accessed using the display scrollpush buttons. The table below shows the instrumentation and alarm featuresthe module provides.

Generator Volts L1-N, L2-N, L3-NGenerator Volts L1-L2, L2-L3, L3-L1Generator Amps L1, L2, L3Generator Frequency HzGenerator kVA L1, L2, L3, TotalGenerator kW L1, L2, L3, TotalGenerator pf L1, L2, L3, AverageGenerator kVAr L1, L2, L3, TotalGenerator KWhGenerator KVAhGenerator KVArhGenerator Phase SequenceSynchroscope DisplayEngine Speed RPMEngine Oil PressureEngine TemperaturePlant Battery VoltsCharge Alternator VoltsFuel LevelGenerator Earth CurrentBus Volts (L-L&LN)Bus Frequency (Hz)Bus Phase SequenceEngine Hours RunNumber of Start AttemptsMaintenance DisplayEngine ECU diagnostics information via industry standard CAN interfaceEnhanced metering via CAN when connected to an electronic engine

TELEMETRYThe module gives the user fulltelemetry facilities when using theoptional communications software.The module can be connected to aPC using the DSE810 PC interfaceor by using a suitable modem.

The PC software is MicrosoftWindows™ based. All access intothe module can be configured tobecome password protected toprevent unauthorised entry. The PCsoftware allows the module to becontrolled from a remote location.

COMMUNICATIONSThe DSE7510 has a number ofdifferent communication capabilities:-

SMSMessagingWhen the module detects an alarmcondition, it has the ability to sendan SMS message to a dedicatedmobile number, notifying an engineerof the problem. (GSM Modem anddata enabled SIM Card required).

Remote CommunicationsWhen the module detects analarm condition, it dials out to a PCnotifying the user of the exact alarmcondition (modem required).

BuildingManagementThe module has been designed tobe integrated with new and existingbuilding management systems.

SCADA/PC SoftwareThe module has the ability to beconfigured and monitored from aremote PC, using the DSE810interface.

EVENT LOGThe module includes acomprehensive event log thatshows the 25 most recent alarmconditions and the date and timethat they occurred.This function assists the user whenfault finding and maintaining thegenerating set.

EXPANSIONMODULESDSE123 Load Share Lines InterfaceModuleDSE157 Relay Output ExpansionModuleDSE545 & DSE548 RemoteAnnunciation Expansion ModuleDSE130 Input Expansion Module

ELECTRONIC ENGINECOMPATIBILITY• Cummins• Deutz• John Deere• MTU• Perkins• Scania• Volvo• Generic• Plus additional manufacturers

TYPICAL LOAD SHAREAPPLICATION

LOAD

G1

G2

G3

ELECTROMAGNETIC CAPABILITYBS EN 61000-6-2EMC Generic Emission Standard for theIndustrial EnvironmentBS EN 61000-6-4EMC Generic Emission Standard for theIndustrial Environment

ELECTRICAL SAFETYBS EN 60950Safety of Information Technology Equipment,including Electrical Business Equipment

TEMPERATUREBS EN 60068-2-2Test Ab to +70oC 60067-2-2 HotTest Ab to -30oC 60068-2-1 Cold

VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn

HUMIDITYBS 2011 part 2.1 60068-2-30Test Cb Ob Cyclic93% RH @ 40oC for 48 hours

SHOCKBS EN 60068-2-27Three shocks in each of three major axes15gn in 11mS

ENVIRONMENTAL TESTINGSTANDARDS

OPERATIONThe module is operated using thefront STOP/RESET, MANUAL, AUTOand START push buttons. Three ofthese push buttons include an LEDindicator. Additional push buttonsprovide LCD display scroll, lamp test,mute functionality and breaker control.

Page 3: charge fail, emergency stop, low oil pressure, high engine temperature, fail to start, low/high DC battery volts, fail to stop, generator short circuit protection, reverse power, generator

®

DSE7510

BATTERY

-VE

+V

E CH

GA

LT

CO

MM

ON

GR

OU

ND

FUE

LLE

VE

L(F

LEX

IBLE

)

WA

TE

RT

EM

P

OIL

PR

ES

SU

RE

9 INPUTSPLANT +VE

CLOSE GENOUTPUT D

OUTPUT C

3 OUTPUTSENGINE ECU

MSC

SCR H L

AVR

O/PB A

GOVERNOR

O/PB A

SCR H L

120 R TERMINATING RESISTORMAY BE REQUIRED EXTERNALLYSEE ENGINE MANUFACTURERSLITERATURE

CT1 CT2 CT3 CT4 COML1S1 L2S1 L3S1 NS2

U V W NL1 L2 L3

51

1 2 3 4 5 16 17 18 15 6 60 61 62 63 64 65 66 67 68 8 9 10 35347 36 37 38 27 25 26

52 53 55 54 43 44 45 46 41 42 24 22 23 4039 56 57 47 48 49 50 33 31 32

R S T NL1 L2 L3

GEN VOLTS BUS VOLTS

SCR

MPUGEN CURRENT

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

A

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

B

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

C

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

D

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

E

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

F

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

G

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

H

US

ER

CO

NFI

GU

RA

BLE

+V

EO

UT

PU

TE

US

ER

CO

NFI

GU

RA

BLE

+V

EO

UT

PU

TF

US

ER

CO

NFI

GU

RA

BLE

+V

EO

UT

PU

TG

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

I

2 AMPFUSES

2 AMPFUSES

CT’s 1 AMP OR 5 AMPSECONDARY

PROTECTION CLASS

P1 P2

S1 S2

L3

N

L2

L1

TOLOAD

FROMGENERATOR

FUE

L

CR

AN

K

RS485

RS232

SCR

B

A

MODULE 7510

AUTOMATIC MCCBAUTOMATIC ACBor CONTACTOR

3 or 4 POLE

MPU

TO

GE

NS

WIT

CH

ING

DE

VIC

EC

IRC

UIT

RY

TO ALL OTHER 7510 AND 7560MSC CONNECTIONS

MAX 250 METERS120 OHM SCREENED CABLE

THE FIRST AND LASTUNITS MSC MUST BE FITTEDWITH A 120 OHM RESISTOR

ACROSS H AND L

157

P810

RE

MO

VE

LIN

KFO

RU

PT

O32

AM

PS

FUS

EFO

RR

EM

OT

EE

MS

TO

P

MIN

2A

MP

SM

AX

20A

MP

AN

TI-

SU

RG

EFU

SE

TO

FUE

LS

OLE

NO

IDM

AX

16A

MP

OU

TP

UT

A

TO

CR

AN

KS

OLE

NO

IDM

AX

16A

MP

OU

TP

UT

B

LOW

OIL

PR

ES

SU

RE

HIG

HC

OO

LAN

TT

EM

P

FUE

LT

EM

P

TO

EN

GIN

EE

AR

TH

CH

AR

GE

ALT

ER

NA

TO

R

BA

TT

ER

Y+

VE

(12

OR

24V

DC

)

BA

TT

ER

Y-V

E

CO

NE

CT

SC

RE

EN

AT

GE

NE

RA

TO

RO

NLY

SCREEN EARTHEDAT THIS END ONLY

TOGOVERNOR

TOAVR

CO

NE

CT

SC

RE

EN

AT

GE

NE

RA

TO

RO

NLY

RELATEDMATERIALSTITLE PART NO’SDSE7510 Manual 057-088DSE7510 Installation Instructions 053-052DSE75xx PC Software Manual 057-078DSE7520 Data Sheet 055-066DSE7560 Data Sheet 055-067DSE123 Data Sheet 055-044DSE810 Manual 057-052Load Share Design and Commissioning 057-047Guide to Synchronising and LoadSharing 057-045/6CAN and DSE Wiring Guide 057-004DSE850 Comms Software Data Sheet 055-072

Page 4: charge fail, emergency stop, low oil pressure, high engine temperature, fail to start, low/high DC battery volts, fail to stop, generator short circuit protection, reverse power, generator

®

DEEP SEA ELECTRONICS INC3230 Williams AvenueRockfordIL 61101-2668 USA

TELEPHONE+1 (815) 316 8706

FACSIMILE+1 (815) 316 8708

[email protected]

WEBSITEwww.deepseausa.com

DEEP SEA ELECTRONICS PLCHighfield HouseHunmanby Industrial EstateHunmanby, North YorkshireYO14 0PH England

TELEPHONE+44 (0)1723 890099

FACSIMILE+44 (0)1723 893303

[email protected]

WEBSITEwww.deepseaplc.com