CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

42
08--00--1 Vol. 1 REV 56, Jan 31/03 ENVIRONMENTAL CONTROL SYSTEM Table of Contents Flight Crew Operating Manual CSP A--013 MASTER CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM Page TABLE OF CONTENTS 08--00 Table of Contents 08--00--1 INTRODUCTION 08--10 Introduction 08--10--1 AIR-CONDITIONING SYSTEM 08--20 Air--ConditioningSystem 08--20--1 Packs 08--20--4 Temperature Control 08--20--9 Ram Air Ventilation 08--20--9 Conditioned Air Distribution 08--20--9 System Circuit Breakers 08--20--10 AVIONICS COOLING SYSTEM 08--30 Avionics Cooling System 08--30--1 System Circuit Breakers 08--30--8 AFT CARGO BAY VENTILATION SYSTEM 08--40 Cargo Compartment Air System 08--40--1 System Circuit Breakers 08--40--5 LAVATORY AND GALLEY VENTILATION SYSTEM 08--50 Galley Heating System 08--50--1 System Circuit Breakers 08--50--4 PRESSURIZATION SYSTEM 08--60 Pressurization System 08--60--1 Outflow Valves 08--60--7 Cabin Pressure Controllers 08--60--7 Automatic Pressurization Modes 08--60--7 Manual Pressurization Modes 08--60--8 Differential Pressure Control 08--60--9 Cabin Altitude Limitation 08--60--9 Emergency Depressurization 08--60--9 Cabin Pressure Monitoring 08--60--9 System Circuit Breakers 08--60--10

Transcript of CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

Page 1: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--00--1Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Table of Contents

Flight Crew Operating ManualCSP A--013

MASTER

CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

Page

TABLE OF CONTENTS 08--00Table of Contents 08--00--1

INTRODUCTION 08--10Introduction 08--10--1

AIR-CONDITIONING SYSTEM 08--20Air--Conditioning System 08--20--1

Packs 08--20--4Temperature Control 08--20--9Ram Air Ventilation 08--20--9Conditioned Air Distribution 08--20--9System Circuit Breakers 08--20--10

AVIONICS COOLING SYSTEM 08--30Avionics Cooling System 08--30--1

System Circuit Breakers 08--30--8

AFT CARGO BAY VENTILATION SYSTEM 08--40Cargo Compartment Air System 08--40--1

System Circuit Breakers 08--40--5

LAVATORY AND GALLEY VENTILATION SYSTEM 08--50Galley Heating System 08--50--1

System Circuit Breakers 08--50--4

PRESSURIZATION SYSTEM 08--60Pressurization System 08--60--1Outflow Valves 08--60--7Cabin Pressure Controllers 08--60--7

Automatic Pressurization Modes 08--60--7Manual Pressurization Modes 08--60--8Differential Pressure Control 08--60--9Cabin Altitude Limitation 08--60--9Emergency Depressurization 08--60--9Cabin Pressure Monitoring 08--60--9System Circuit Breakers 08--60--10

Page 2: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--00--2ENVIRONMENTAL CONTROL SYSTEM

Table of Contents

MASTERFlight Crew Operating ManualCSP A--013

LIST OF ILLUSTRATIONS

INTRODUCTIONFigure 08--10--1 Simplified Block Diagram 08--10--2

AIR-CONDITIONING SYSTEMFigure 08--20--1 Air Conditioning System 08--20--2Figure 08--20--2 Air Conditioning Pack 08--20--5Figure 08--20--3 Air Conditioning System -- Controls 08--20--6Figure 08--20--4 Air Conditioning -- EICAS Messages 08--20--7Figure 08--20--5 Air Conditioning System -- Synoptic

Page Indications 08--20--8

AVIONICS COOLING SYSTEMFigure 08--30--1 Avionics Cooling -- CRT Display Supply 08--30--2Figure 08--30--2 Avionics Cooling -- ARINC Supply 08--30--3Figure 08--30--3 Avionics Cooling -- Controls 08--30--4Figure 08--30--4 Avionics Cooling -- Exhaust System 08--30--5Figure 08--30--5 Avionics Cooling -- EICAS Indications 08--30--6Figure 08--30--6 Display Overtemperature Indications 08--30--7

AFT CARGO BAY VENTILATION SYSTEMFigure 08--40--1 Cargo Compartment Air System with Air

Conditioning -- Schematic <0013><0034>< 0074> 08--40--2Figure 08--40--2 Cargo Compartment Ventilation

System -- Schematic <0043><0053><0059> 08--40--3Figure 08--40--3 Cargo Compartment Air/Ventilation System 08--40--4

LAVATORY AND GALLEY VENTILATION SYSTEMFigure 08--50--1 Galley heating System 08--50--2Figure 08--50--2 Galley heating System -- Control Switches 08--50--3

PRESSURIZATION SYSTEMFigure 08--60--1 Pressurization Control System -- Schematic 08--60--2Figure 08--60--2 Pressurization Control Panel 08--60--3Figure 08--60--3 Pressurization -- EICAS Messages 08--60--4Figure 08--60--4 Pressurization Synoptic Page Indications 08--60--6

Page 3: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--10--1Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Introduction

Flight Crew Operating ManualCSP A--013

MASTER

1. INTRODUCTION

The environmental control system (ECS) provides temperature and pressure regulated airfor heating, ventilating and pressurizing the flight and passenger compartments. Exhaustair, from the compartments, is used to ventilate the avionics and cargo compartments,before being dumped overboard through two outflow valves.

For ground operations, pneumatic air to operate the ECS can be obtained from:

S A ground air supply cart connected to the aircraft

S The auxiliary power unit (APU)

S Either or both engines.

During flight, the engines normally supply bleed air for operating the air-conditioning,pressurization, and avionics cooling systems.

ECS warnings and cautions are displayed on the engine indication and crew alerting system(EICAS) primary page. ECS advisory and status messages are displayed on the EICASstatus page. Views of the aircraft ECS temperature, pressure, valve positions and systemstatus indications are displayed on the EICAS ECS synoptic page.

Page 4: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--10--2ENVIRONMENTAL CONTROL SYSTEM

Introduction

MASTERFlight Crew Operating ManualCSP A--013

Simplified Block DiagramFigure 08---10---1

RAMAIR

DISTRIBUTION MANIFOLD

LEFTPACK

RIGHTPACK

LP GROUNDCONDITIONEDAIR

OUTFLOWVALVES (2)

AFT PRESSUREBULKHEADPASSENGER CABIN

RAM AIRINLET

(HIGH PRESSUREPNEUMATIC SUPPLY)

Pressurized andconditioned by airconditioningsystem.

Pressurized by airexhausted fromcockpit/cabinno temperaturecontrol.Heated by exhaustair fromelectronicschassis.

Unpressurized

LEGEND

FLIGHTCOMPARTMENT

CONNECTION

GROUNDPOWERUNIT

AUXILIARYPOWERUNIT

GASPERSYSTEM

SOV

POSITIONVALVE

DUAL

PACKPRSOV’s

10 THSTAGE

10 THSTAGE

R/HSOV

ISOLL/HSOV

Page 5: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--20--1Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Air--Conditioning System

Flight Crew Operating ManualCSP A--013

MASTER

1. AIR--CONDITIONING SYSTEM

There are two air-conditioning systems, which can be operated separately or in parallel, tosupply conditioned air to the flight and passenger compartments. Each system consists ofan air-conditioning unit or package (PACK), a temperature controller and ducting. Ram air isprovided for pack cooling and ventilation. The temperature controllers also control theengine 10th stage bleed air supply to the system (see Chapter 19).

Page 6: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--20--2ENVIRONMENTAL CONTROL SYSTEM

Air--Conditioning System

MASTERFlight Crew Operating ManualCSP A--013

Air Conditioning SystemFigure 08---20---1 Sheet 1

Page 7: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--20--3Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Air--Conditioning System

Flight Crew Operating ManualCSP A--013

MASTER

Air Conditioning SystemFigure 08---20---1 Sheet 2

Page 8: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--20--4ENVIRONMENTAL CONTROL SYSTEM

Air--Conditioning System

MASTERFlight Crew Operating ManualCSP A--013

A. Packs

The packs are located in the aft equipment compartment. They provide cooling of theengine or APU bleed air supplies for distribution to the flight and passengercompartments. 10th stage bleed air to each pack is regulated to a constant 30 psi byrespective pressure regulator and shutoff valves (PRSOV). For single pack operation,the PRSOV will regulate the pressure to 41 psi. Each pack consists of an air cyclemachine and heat exchanger which are used to decrease the temperature and watercontent of the bleed air used in the conditioning process. Normally, the right packsupplies the passenger compartment and the left pack supplies the flight compartment.If a pack fails, the remaining pack can supply conditioned air to both compartments.

Page 9: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--20--5Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Air--Conditioning System

Flight Crew Operating ManualCSP A--013

MASTER

Air Conditioning PackFigure 08---20---2

A

A

Page 10: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--20--6ENVIRONMENTAL CONTROL SYSTEM

Air--Conditioning System

MASTERFlight Crew Operating ManualCSP A--013

Air Conditioning System --- Controls <MST>Figure 08---20---3

Used to control operation of air conditioningpacks.When pressed in, associated packpressure regulating/shut--off valve opens,permitting airflow into pack. OFF (white)light goes out.When pressed out, associated packpressure regulating/shut--off valve closes,shutting down airflow into pack. OFF (white)light comes on and EICAS displays L/RPACK OFF status message.Amber FAULT light comes on:When overpressure occurs betweenprimary heat exchanger and compressorsection of pack.

RAM AIR VentilationSwitch/Light(Guarded)Used when both packs fail. Provides ambient air toleft conditioned air (cockpit) supply duct.When pressed in, ram air vent valve opens andsupplies air into cockpit supply duct. OPEN (white)light comes on. EICAS displays RAM AIR OPENstatus message and ECS page indicates valveposition.When pressed out, ram air valve closes andOPEN light goes out. EICAS ECS page indicatesvalve at closed position.

Control Switch/LightUsed to select manualmode temperature control.When pressed in, selectsmanual control and lightcomes on green andEICAS indicates CKPT/CABIN TEMP MAN.When pressed out, selectsautomatic control and lightgoes out.

Manual Mode -- Temperature

Air--Conditioning PanelOverhead Panel

Left and Right PACKSwitch/Lights

<0013><0034><0074>

<0043><0053><0059>

Page 11: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--20--7Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Air--Conditioning System

Flight Crew Operating ManualCSP A--013

MASTER

Air Conditioning --- EICAS Messages <MST>Figure 08---20---4

Primary Page

<0039>

<0006>

PACK OFF L/Rstatus (white)Comes on to indicate that respectiveair conditioning pack has been shutdown. Corresponds to PACK L/Rswitch/lights indicating OFF (white).

RAM AIR OPENstatus (white)Comes on to indicate that ram airvalve has been selected open.Corresponds to RAM AIR switch/lightindicating OPEN (white).

Status Page

<0039>

<0039>

PACK HI PRESS L/Rcaution (amber)Comes on when a high pressure(51 psi) is sensed in respectiveair conditioning pack’s outlet duct.Corresponds to PACK L/R switch/lightsindicating FAULT (amber).

Page 12: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--20--8ENVIRONMENTAL CONTROL SYSTEM

Air--Conditioning System

MASTERFlight Crew Operating ManualCSP A--013

Air Conditioning System --- Synoptic Page Indications <MST>Figure 08---20---5

Environmental ControlSystem Page

OvertemperatureCaution message (amber)Indicates high temperaturesensed in respective airconditioning pack’s outletcorresponds toPACK HI TEMP L, R cautionon primary page, and PACKswitch/light indicating FAULT.

10th Stage BleedPressure (white)

MANUAL message(white)Comes on to indicatethat the respectiveCKPT/CABIN MANswitch/light is selected.

OverpressureCaution message (amber)Indicates high pressuresensed in respectivepacks outlet, correspondsto PACK HI PRESS L, Rcaution on primary pageand PACK switch/lightindicating FAULT.

<0039>

Page 13: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--20--9Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Air--Conditioning System

Flight Crew Operating ManualCSP A--013

MASTER

B. Temperature Control

The flight compartment and the passenger compartments have identical butindependently-operated temperature control systems. Each controller subsystem isdedicated to an air-conditioning pack. Temperature control, in automatic mode, isprovided by CKPT and CABIN selector knobs on the air conditioning panel. Control inmanual mode is provided by left and right pack MAN switchlights and HOT/COLDswitches on the same panel. The individual packs can be manually turned OFF byselecting the respective L or R PACK switchlight on the air conditioning panel.

AUTOMATIC MODE -- Operating Range MANUAL MODE -- Operating Range

14.5_C to 28_C (58_F to 82_F) 1.7_C to 71_C (35_F to 160_F)

NOTE

Manual mode temperature below 3_C (37_F) mayresult in icing of the pack water separator andsubsequent cycling of the pack output.

C. Ram Air Ventilation

The cooling air for the left and right heat exchangers is supplied from a ram air intake,located on the upper aft fuselage. During normal operation, the ram air is exhaustedthrough an exhaust duct in the lower aft fuselage, after passing over the heatexchangers. The ram air intake duct also provides cooling air to the hydraulic systemsheat exchanger to cool the hydraulic fluid. (Refer to Chapter 14).

Ram air ventilation is used only when the air conditioning packs fail (unpressurized).Operating the (guarded) RAM AIR, switchlight on the air--conditioning panel, opens thenormally closed ram air valve. Ram air then enters the left (flight compartment) supplysystem. Ram air also flows through the distribution manifold to the passengercompartment.

D. Conditioned Air Distribution

Conditioned air, from the left and right air-conditioning packs, is routed throughseparate ducting systems through a distribution manifold to the flight compartment andthe passenger compartments.

Conditioned air, to the passenger compartment, is distributed from ducts along eachside of the aircraft. Passenger compartment exhaust air is routed underfloor to theoutflow valves on the aft pressure bulkhead.

Conditioned air, to the flight compartment, is distributed to the side console panels,gaspers and vents, and avionics units within the instrument panel. Dedicated fans andducts direct conditioned air over the flight compartment display units. Flightcompartment exhaust air is routed underfloor through the avionics compartment to theoutflow valve at the aft pressure bulkhead.

Page 14: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--20--10ENVIRONMENTAL CONTROL SYSTEM

Air--Conditioning System

MASTERFlight Crew Operating ManualCSP A--013

E. Low Pressure Ground Air Connection <0007>

An external ground air connector, located on the right aft fuselage, is provided forground air-conditioning. Low pressure compressed air from a ground air conditioningcart can be supplied directly into flight and passenger compartment distributionsystems.

F. System Circuit Breakers

SYSTEM SUB--SYSTEM CB NAME BUS BAR CBPANEL

CBLOCATION

NOTES

Left Pack L AIR CONDUNIT J1

AirC diti i C k it

CKPTTEMP/CONT DC BUS 1

1J2

Conditioning-- FlightCompartment

CockpitTemperatureControl

CKPTTEMP/CONTMAN

1

J3

CKPT FAN AC BUS 1 C8

Ram Air RAM AIR SOV DC BAT P5

Right Pack R AIR CONDUNIT J1

Air

CABINTEMP/CONT DC BUS 2

2J2

AirConditioning-- Cabin

CabinTemperatureControl

CABINTEMP/CONTMAN

2

J3Control

GALLEY FANAC BUS 2

C5

CABIN FANAC BUS 2

C8

Page 15: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--30--1Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Avionics Cooling System

Flight Crew Operating ManualCSP A--013

MASTER

1. AVIONICS COOLING SYSTEM

The electronic flight instruments in the flight compartment instrument panel, control panelsand display units in the center pedestal, and electronic units in the left and right portions ofthe underfloor avionics bay are cooled during on-ground and flight operations.

The cockpit displays are cooled with air from two display fans located under the flightcompartment floor. Fan control is provided by a DSPLY FAN selector knob on the avionicscooling panel. Normally, only one fan operates at a time (controlled by WOW). In flight, onlyfan 1 is powered and on the ground, only fan 2 is powered. When powered, the respectivefan draws in recirculated air from the flight compartment and mixes it with conditioned airthen supplies the air to the backs of each display. In the event of a fan failure, the alternatefan can be powered by selecting the FLT ALTN or GND ALTN position. If both fans fail,selecting STDBY permits conditioned air to ventilate the displays. A low flow sensormonitors the air flow to ensure adequate cooling. Check valves prevent loss of cooling air orreverse flow.

Two ARINC cooling fans are installed under the flight compartment floor. The fans are usedto provide recirculated cabin air to the left and right avionics equipment racks. Fan control isprovided by an ARINC FAN selector knob on the avionics cooling panel. In the NORMposition, only one fan operates at a time (controlled by WOW). In flight, only fan 1 ispowered and on the ground, only fan 2 is powered. In the event of a fan failure, thealternate fan can be powered by selecting the FLT ALTN or GND ALTN position.

The avionics exhaust system consists of an exhaust fan, an inboard exhaust valve and anoutboard exhaust valve. The exhaust fan is installed in the avionics compartment andoperates whenever AC BUS 1 is powered. The fan is used to remove warm air from theCRT displays, pedestal panels and the left and right avionics equipment racks, then direct itto the exhaust valves. When either the passenger door or service door is open, the inboardvalve is closed and the outboard valve is open to exhaust the air to the wing root area.When the passenger and service doors are closed, the outboard valve is closed and theinboard valve is open to exhaust the air to the rear lower fuselage where it is dumpedoverboard through the outflow valves.

Page 16: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--30--2ENVIRONMENTAL CONTROL SYSTEM

Avionics Cooling System

MASTERFlight Crew Operating ManualCSP A--013

Avionics Cooling --- CRT Display SupplyFigure 08---30---1

Avionics Cooling Fan Selector PanelCenter Pedestal

STANDBY FAN

RECIRCULATEDAIR FROM FLIGHTCOMPARTMENT

COCKPIT DISPLAY COOLINGSHUT--OFF VALVE

CONDITIONED AIRFROM ACU NO.1

FAN 2(LOWER)

DISPLAY SUPPLYFAN AND CHECKVALVE

FAN 1(UPPER)

EXHAUSTFROM CRT

TO AVIONICSEXHAUST FAN

CRT--DISPLAYLOW--FLOWDETECTOR

CRT COOLINGSYSTEM

6 WAY DUCT (REF)

CRTDISPLAYS

COCKPITGASPERS INLET FROM FLIGHT

COMPARTMENT

FROMACUNO.1

Page 17: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--30--3Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Avionics Cooling System

Flight Crew Operating ManualCSP A--013

MASTER

Avionics Cooling --- ARINC SupplyFigure 08---30---2

RECIRCULATEDCABIN AIR

CHECKVALVE

ARINCSUPPLYFAN 2(FLT ALTN)

ARINCSUPPLYAIRFILTER

ARINC SUPPLYFAN 1 (GND ALTN)

ARINC LOWFLOW DETECTOR

ARINC CHASSIS (RACK)

ARINC CHASSIS (RACK)

Page 18: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--30--4ENVIRONMENTAL CONTROL SYSTEM

Avionics Cooling System

MASTERFlight Crew Operating ManualCSP A--013

Avionics Cooling --- ControlsFigure 08---30---3

DISPLAY FAN SELECTORNORM -- Fans in EFIS/EICAS display ductoperate in automatic mode providing airflowthrough flight compartment displays:Fan 1 during flight, andFan 2 during ground operations.

FLT ALTN -- Selects flight alternate (fan 2) asthe reversionary fan.GND ALTN -- Selects ground alternate (fan 1)as the reversionary fan.STBY -- Select standby fan as thereversionary fan.

Reversionary mode selected when DISPLAYCOOL caution (amber) indicated on EICAS.

AVIONICSCOOLINGDISPLAY FAN 1AC ESS BUS

AVIONICSCOOLINGARINC FAN 1AC ESS BUS

AVIONICSCOOLINGARINC FAN 2AC BUS 2

AVIONICSCOOLINGDISPLAY FAN 2AC BUS 1

AVIONICSCOOLINGDISPLAY FANSTBYAC ESS BUS

Avionics Cooling FanSelector Panel

Center Pedestal

ARINC FAN SELECTORNORM -- Fans in ARINC chassissupply duct operate in automatic modeproviding airflow through ARINC chassis:Fan 1 during flight,Fan 2 during ground operations.

FLT ALTN -- Selects flight alternate (fan 2) asthe reversionary fan.GND ALTN -- Selects ground alternate (fan 1)as the reversionary fan.

Reversionary mode selected when ARINCCOOL caution (amber) indicated on EICAS.

Page 19: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--30--5Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Avionics Cooling System

Flight Crew Operating ManualCSP A--013

MASTER

Avionics Cooling --- Exhaust SystemFigure 08---30---4

TO WINGROOT AREA

CRTDISPLAYEXHAUST

AVIONICSEQUIPMENTRACKS

AVIONICEXHAUSTLOW--FLOWDETECTOR

AVIONICSEXHAUSTFAN

OVERBOARDEXHAUSTVALVE

ARINC

TO REARLOWERFUSELAGEINBOARD

EXHAUSTVALVE

ARINC

Page 20: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--30--6ENVIRONMENTAL CONTROL SYSTEM

Avionics Cooling System

MASTERFlight Crew Operating ManualCSP A--013

Avionics Cooling --- EICAS Indications <MST>Figure 08---30---5

Primary Page

<0039>

Status Page

<0039>

<0039>

OVBD COOL FAIL status (white)Comes on during ground operations, ifthe overboard avionics cooling SOVhas failed closed with passenger doorunlatched (10 secs. time delay).

INBD COOL FAIL status (white)Inboard avionics cooling SOV not openwith the passenger door closed (10 secs.time delay).

NOTEThe inboard cooling shut--off valve (INBDCOOL SOV) is used during flight to flushcool the avionics system equipment. Thevalve is normally closed on the groundand open during flight.

CKPT COOL FAIL status (white)Avionics cooling SOV not in correctposition (closed on ground or openduring flight).COOL EXHAUST FAIL status (white)Exhaust fan failed or low flow from coolingexhaust (10 secs. time delay).

OVBD COOL caution (amber)Overboard avionics cooling SOV not closed withthe passenger door and service door closed(10 secs. time delay).

NOTEThe avionics cooling overboard shut--off valve(OVBD COOL SOV) is used during groundoperations to flush cool the avionics system anddump hot air overboard. The valve is normallyopen on the ground and closed during flight. Theairplane will not pressurize to normal levels if theoverboard cooling shut--off valve is failed open.

<0006>

DISPLAY COOL caution (amber)Low airflow is detected in cockpit display coolingduct (due to duct disconnection, duct blockage)or display fan 1 or 2, or standby fan has failed(10 secs. time delay).

ARINC COOL caution (amber)Low airflow is detected in ARINC unit coolingduct (due to duct disconnection, duct blockage)or avionics cooling fan 1 or 2 has failed (10 secs.time delay).

Page 21: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--30--7Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Avionics Cooling System

Flight Crew Operating ManualCSP A--013

MASTER

Display Overtemperature IndicationsFigure 08---30---6

Display Overtemperaturewarning (red)Indicates an approaching thermalshutdown of MFD.

Display Overtemperaturewarning (red)Indicates an approaching thermalshutdown of PFD.Sky and ground raster isremoved (to delay thermal

Multifunction DisplayPilot’s and Copilot’s Instrument Panels

Primary Flight DisplayPilot’s and Copilot’s Instrument Panels

shutdown).

Page 22: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--30--8ENVIRONMENTAL CONTROL SYSTEM

Avionics Cooling System

MASTERFlight Crew Operating ManualCSP A--013

A. System Circuit Breakers

SYSTEM SUB--SYSTEM CB NAME BUS BAR CBPANEL

CBLOCATION

NOTES

DISPLAYFAN 1 AC ESS 3 C9

Display Fans

DISPLAYFAN 2 AC BUS 1 1 D2

Display FansDISPLAYFAN STBY AC ESS 3 C6

Avionics

EXHAUSTFAN AC BUS 1 1 C5

AvionicsCoolingS t

ARINC ARINC FAN 1 AC ESS 3 C12gSystem

ARINCChassis Fans ARINC FAN 2 AC BUS 2 D2

CONT22

L2

CKPT SOV DC BUS 22

L3

Controller andSh ff V l

I/B SOV L4Shutoff Valves O/B SOV DC BUS 1 1 L4

AVIONICSCONT 1 DC ESS 4 C4

Page 23: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--40--1Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Aft Cargo Bay Ventilation System

Flight Crew Operating ManualCSP A--013

MASTER

1. CARGO COMPARTMENT AIR SYSTEM

The cargo compartment air system allows the flight crew to control the ventilation air withinthe cargo compartment. The system consists of a recirculation air shut--off valve,recirculation fan and an exhaust air shut--off valve. <0043><0059>

The cargo compartment conditioned air system allows the flight crew to control theventilation air and temperature within the cargo compartment. The system consists of arecirculation air shut--off valve, recirculation fan, heater and an exhaust air shut--off valve.<0013><0034>

The system is controlled by a 2--position CARGO, OFF/FAN switch on the air-conditioningpanel. In the OFF position, both shut--off valves are closed and the system is disabled. Inthe FAN position, both shut--off valves open and the fan is powered to blow recirculatedcabin air into the cargo compartment to maintain the compartment temperature abovefreezing. <0043><0059>

The system is controlled by a CARGO, 3--position, OFF/FAN/AIR COND switch on theair-conditioning panel. In the OFF position, both shut--off valves are closed and the systemis disabled. In the FAN position, both shut--off valves open and the recirculation fan ispowered to blow recirculated cabin air into the cargo compartment to maintain thecompartment temperature above freezing. In the COND AIR position, both shut--off valvesare open, the heater is enabled and the recirculation fan is powered to blow heated air intothe cargo compartment. The heater is controlled by a temperature control switch in theexhaust duct which will cycle the heater ON and OFF as necessary to maintain the cargocompartment temperature between 21_C and 27_C (70_F and 80_F). <0013><0034>

An overheat switch in the exhaust duct provides overtemperature protection by removingpower to the heater when the exhaust duct temperature exceeds 49_C (120_F). A signal isalso sent to the EICAS to display a CARGO OVHT caution message. The switch will resetwhen the temperature decreases below 29_C (85_F). <0013><0034>

A duct overheat switch is installed in the heater outlet. If the heater discharge temperatureexceeds 49_C (120_F) power is removed from the heater. The switch will reset when thetemperature decreases below 38_C (104_F). <0013><0034>

The system interacts with the cargo bay smoke detectors and fire extinguishing system (SeeChapter 10, Fire Protection). When smoke is detected, the shut-off valves automaticallyclose to isolate the cargo compartment. <0043><0059>

The system interacts with the cargo bay smoke detectors and fire extinguishing system (SeeChapter 10, Fire Protection). When smoke is detected, the heater power is removed and theshut-off valves automatically close to isolate the cargo compartment. <0013><0034>

NOTE

For ground operations with the cargo compartmentdoor open, the CARGO switch may be set to CONDAIR. For ambient temperatures above 30_C (86_F),this may result in a cargo overheat caution message.The cargo switch must be reset to the FAN positionafter the cargo door has been closed. <0013><0034>

Page 24: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--40--2ENVIRONMENTAL CONTROL SYSTEM

Aft Cargo Bay Ventilation System

MASTERFlight Crew Operating ManualCSP A--013

Cargo Compartment Air System with Air Conditioning --- Schematic <0013><0034>Figure 08---40---1

RECIRCULATION FAN

CONDITIONEDAIR

DISTRIBUTIONMANIFOLD

CONDITIONED--AIRSHUT--OFF VALVE

RECIRCULATEDCABIN AIR

CARGOCOMPARTMENTEXHAUSTINTAKE

TEMPERATURECONTROLSWITCH

OVERHEATSWITCH

EXHAUST AIRSHUT--OFFVALVE

EXHAUST AIRTO AFT ECSCOMPARTMENT

HEATERASSEMBLY

CARGOCOMPARTMENTSUPPLY

RECIRCULATED--AIRSHUT--OFF VALVE

DUCTOVERHEATSWITCH

Page 25: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--40--3Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Aft Cargo Bay Ventilation System

Flight Crew Operating ManualCSP A--013

MASTER

Cargo Compartment VentilationSystem --- Schematic <0043><0059>Figure 08---40---2

RECIRCULATION FAN

RECIRCULATEDCABIN AIR

EXHAUSTINTAKE

EXHAUST AIRSHUT--OFFVALVE

EXHAUST AIRTO AFT ECSCOMPARTMENT

CARGOCOMPARTMENTSUPPLY

RECIRCULATED--AIRSHUT--OFF VALVE

Page 26: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--40--4ENVIRONMENTAL CONTROL SYSTEM

Aft Cargo Bay Ventilation System

MASTERFlight Crew Operating ManualCSP A--013

Cargo Compartment Air/ventilation System <MST>Figure 08---40---3

CARGO SOV FAIL status (white)Comes on to indicate that air supply shut--offvalve has failed (either open or closed).

CARGO FAN FAIL status (white)Comes on to indicate low air flow at cargobay recirculation fan.

Status Page

Primary Page

Air--Conditioning PanelOverhead Panel

BAGGCOMPTCONTDC BUS 1

BAGGCOMPTFANAC BUS 1

BAGGCOMPTSOVDC ESS

Cargo Bay Air ConditioningSwitchUsed to select to system mode.COND AIR -- Temperaturecontrolled airflow providedto cargo bay area.FAN -- Recirculated cabinexhaust air provided to cargobay area.OFF -- Shuts off airflow to thecargo bay area.

<0006><0039>

Cargo Bay Mode SwitchUsed to select to system mode.FAN -- Recirculated cabinexhaust air provided to cargobay area.OFF -- Shuts off airflow to thecargo bay area.

<0039>

<0013><0034><0074>

<0043><0053><0059>

<0039>

<0013><0034><0074>

<0013><0034><0074>

<0043><0053><0059>

Page 27: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--40--5Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Aft Cargo Bay Ventilation System

Flight Crew Operating ManualCSP A--013

MASTER

A. System Circuit Breakers

SYSTEM SUB--SYSTEM CB NAME BUS BAR CBPANEL

CBLOCATION

NOTES

Controller BAGG COMPTCONT DC BUS 1 1 L3

Cargo BayConditionedAir System

Heater BAGG COMPTHEATER AC BUS 1 1 B8

<0013><0034><0074>Air System

Fan BAGG COMPTFAN AC BUS 1 1 D5

Shutoff Valve BAGG COMPTSOV DC ESS 4 A12

Page 28: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--40--6ENVIRONMENTAL CONTROL SYSTEM

Aft Cargo Bay Ventilation System

MASTERFlight Crew Operating ManualCSP A--013

THIS PAGE INTENTIONALLY LEFT BLANK

Page 29: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--50--1Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEMLavatory and Galley Ventilation System

Flight Crew Operating ManualCSP A--013

MASTER

Effectivity:

S Aircraft 7002, 7050 and subsequent.

S Aircraft 7003 to 7010, 7015,7016, 7019 to 7021, 7023 to 7025, 7032, 7033, 7036, 7039,7040 incorporating SB 601R--25--012.

1. GALLEY HEATING SYSTEM

The galley is heated with two 500 watt heaters to provide supplementary heat to the galley andservice door area. One heater uses the air from the right exhaust riser duct and the secondheater warms conditioned air from the right gasper supply duct. The heaters are controlled byswitchlights on the Flight Attendants panel. There is no EICAS display for the galley heatingsystem.

Each heater incorporates an internal overtemperature switch that removes power to the heaterwhen the heater outlet temperature becomes excessive. The heater also incorporates aninternal, overheat protection switch which disables the heater when the internal temperatureexceeds a preset limit. Heater #1 has a fan which can be used in conjunction with or separatefrom the heaters.

System test is accomplished using the SYSTEM 1 & 2 TEST switchlight on the FlightAttendants panel as follows:

Latch the FAN and HTR 1 and 2 switchlights and check that:

S The FAN and HRT 1 and 2 lights illuminate green.

Press the TEST switchlight and hold; check that:

S The FAN FAIL and HTR 1 and 2 INOP lights illuminate (amber), and

S The FAN and HRT 1 and 2 green lights go out.

Release the TEST switchlight and check that:

S The HTR 2 INOP light goes out, and

S The FAN FAIL and HTR 1 INOP lights remain ON.

Unlatch the FAN and HTR 1 and 2 switchlights and check that:

S All galley heating panel lights are off.

Page 30: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--50--2ENVIRONMENTAL CONTROL SYSTEMLavatory and Galley Ventilation System

MASTERFlight Crew Operating ManualCSP A--013

Galley Heating SystemFigure 08---50---1

GALLEY

GASPER

GALLEY

CEILING

EXHAUST

INLE

T

GALLEY

WARM

AIR

OUTLE

TSERVICE

DOOR

GALLEYEXHAUSTFA

N

GALLEY

HEATER

No.1

GALLEY

HEATING

FANFWDCABIN

AIR

OUTLE

T(AISLE

)

RIGHTGASPER

DUCT

RH

WINDSCREEN

HEATER

No.2

GALLEYAIR

OUTLE

T

CABIN

FLO

OR

LINE

RH

FWD

CABIN

EXHAUST

DUCT

IN SIDEWALL

FLIGHT

COMPT

BULK

HEAD

Page 31: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--50--3Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEMLavatory and Galley Ventilation System

Flight Crew Operating ManualCSP A--013

MASTER

Galley Heating System --- Control SwitchesFigure 08---50---2

Forward Attendant’s Panel

HTR 1 (green)INOP (amber)Activates the underfloorheater and fan.

FAN (green)FAIL (amber)Activates the fan only.

HTR 2 (green)INOP (amber)Activates the binheater.(RH PACK on)

TESTTests HTR 1 andHTR 2 systems.

Page 32: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--50--4ENVIRONMENTAL CONTROL SYSTEMLavatory and Galley Ventilation System

MASTERFlight Crew Operating ManualCSP A--013

A. System Circuit Breakers

SYSTEM SUB--SYSTEM CB NAME BUS BAR CBPANEL

CBLOCATION

NOTES

GalleyHeater #1,

GalleyHeating Heater #2 and GALLEY HTRS AC BUS 2 2 B11Heating

Fan

Page 33: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--60--1Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Pressurization System

Flight Crew Operating ManualCSP A--013

MASTER

1. PRESSURIZATION SYSTEM

The aircraft is pressurized by bleed air supplied by the air-conditioning system. Cabinpressure is normally controlled by regulating cabin air overboard through two outflow valveslocated on the rear pressure bulkhead. The outflow valves are automatically controlled byeither of two independent cabin pressure controllers. The pressurization is almost totallyautomatic, the crew only has to set the landing field elevation, on the CABIN PRESS controlpanel, to program the system for flight. If the normal automatic mode fails, the outflowvalves can be controlled manually by controls on the CABIN PRESS control panel. Bothvalves also operate as safety valves to provide overpressure and negative pressure relief. Ifcabin altitude exceeds 14,000 feet, a signal is sent to the passenger oxygen system todeploy the oxygen masks. A cabin pressure acquisition module (CPAM) is used in thesystem to supply signals to the EICAS.

Page 34: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--60--2ENVIRONMENTAL CONTROL SYSTEM

Pressurization System

MASTERFlight Crew Operating ManualCSP A--013

Pressurization Control System --- SchematicFigure 08---60---1

Page 35: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--60--3Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Pressurization System

Flight Crew Operating ManualCSP A--013

MASTER

Pressurization Control PanelFigure 08---60---2

Manual CabinAltitude RegulatorsUsed to controlpressurization systemin manual (pneumatic)mode.MAN ALT selector isused to change cabinaltitude manually:UP -- causes outflowvalves to open andincreases cabinaltitude. When selectedcabin altitude isacquired, selectmiddle/centre position.DOWN -- causesoutflow valves to closeand decreases cabinaltitude. When selectedcabin altitude isacquired, selectmiddle/centre position.Middle/Centreposition--Disables allprevious manualselections.

Cabin Pressurization

Overhead PanelSelector Panel

Pressurization Control Switch/LightSelects either manual or automatic control of pressurization system.When pressed in, manual mode selected. Removes electrical supplyfrom both outflow valves, locks them in their existing position andpermits their manual (pneumatic) operation. MAN (white) light comeson and EICAS displays pressurization system data on EICAS primarydisplay.When pressed out, automatic mode is selected and MAN light goes

secondary display.When pressed twice, the redundant controller gains control.FAULT (amber) light comes on when system detects failure of bothcabin pressure controllers. EICAS displays AUTO PRESS cautionmessage.

out. Automatic mode pressurization data is displayed on EICAS

RATE Control (NeedleValve) (Manual Mode)Pneumatically adjustsoutflow valve rateduring manual mode.Ascent from 50 fpm

Descent from 50

fpm.Ascent and descentrates indicated on ECSpage of EICAS.

Page 36: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--60--4ENVIRONMENTAL CONTROL SYSTEM

Pressurization System

MASTERFlight Crew Operating ManualCSP A--013

Pressurization --- EICAS Messages <MST>Figure 08---60---3 Sheet 1

EMER DEPRESS caution (amber)Comes on when EMER DEPR switch/light has beenselected on.

CABIN ALT caution (amber)Comes on when cabin altitude is greater than8,500 feet but not greater than 10,000 feet.

AUTO PRESS caution (amber)Comes on at a failure of both automatic pressurizationcontrollers.

Pressurization Readouts (manual mode)Comes on when PRESS CONTROL switch/lightoperated to MAN:C ALT -- Indicates current cabin altitude.RATE -- Indicates rate of change in feet per minute(increments of 100 fpm) and direction via arrowsymbol.P -- Indicates cabin and cockpit to ambient

differential pressure.Landing Elevation readout is not displayed.

Readouts removed from primarypage when automatic mode selected.

NOTE

There may be an EICAS timedelay/ instrument lag betweenthe display of a red P readoutand a subsequent DIFF PRESSwarning message and CABINPRESSURE aural coming on.

NOTE

500C ALT RATE P

500 4.0

CABIN ALT warning (red)Comes on when cabin altitudeis greater than 10,000 feet.Accompanied by aural warning:

DIFF PRESS warning (red)Comes on when differentialpressure is greater than 8.6 psi.Accompanied by aural warning:

Primary Page

<0006><0039>

CABINPRESSURE

CABINPRESSURE

Page 37: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--60--5Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Pressurization System

Flight Crew Operating ManualCSP A--013

MASTER

Pressurization --- EICAS Messages <MST>Figure 08---60---3 Sheet 2

Status Page

<0039>

<0039>

Pressurization Readouts (automatic mode)Comes on when pressurization system is operatedin automatic mode; PRESS CONTROL switch/lightpressed out.

LANDING FIELD ELEVATION readoutDisplays elevation (20 foot increments) as set at LDGELEV selector.-- Amber dashes are displayed if input value is invalid orgreater than 14,000 ft or less than --1,000 ft.

-- Elevation readout not displayed on status page whenmanual mode selected.

CABIN PRESS MAN status (white)Comes on to indicate that PRESS CONTROLswitch/light is operated to MAN.

CPAM FAIL status (white)Comes on to indicate failure of cabin pressureacquisition module (CPAM).-- Oxygen system will not auto--deploy at 14,000 feet.-- Seatbelt / No smoking signs will not automaticallycome on when cabin altitude exceeds 10,000 feet.

C ALT -- Indicates current cabin altitude. Readoutwill turn to amber, if cabin altitude is greater than8,500 feet but less than 10,000 feet. Readout willturn to red when cabin altitude is 10,000 feet orabove.RATE -- Indicates rate of change in feet per minute(increments of 100 fpm) and direction via arrowsymbol.

AUTO PRESS 1, 2 FAIL status (white)Comes on to indicate failure of respectiveautomatic pressurization controller module.

P -- Indicates cabin to ambient differentialpressure. Readout will turn red whendifferential pressure exceeds 8.65 psid.

Page 38: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--60--6ENVIRONMENTAL CONTROL SYSTEM

Pressurization System

MASTERFlight Crew Operating ManualCSP A--013

Pressurization Synoptic Page IndicationsFigure 08---60---4

CPAM FAIL status(white)Comes on to indicatefailure of cabin pressureacquisition module (CPAM).Corresponds to CPAM FAILmessage on status page.

EMER DEPRESScaution (amber)Comes on when EMERDEPRESS switch/light operated.

MONITORED DATA (LH) ACTIVE DATA (RH)

ITEM GREEN AMBER RED WHITE AMBER(------)

C ALT

RATE

LDG ELEV

AMBER(------)

Invalid Data

Invalid Data

Invalid Data

Invalid Data

Invalid Data

Invalid Data

Invalid Data

Monitored DataDisplayed on EICASPrimary page (MAN)Status page (AUTO)

Environmental Control System Page

AUTO PRESS 1, 2FAIL status (white)Comes on to indicatefailure of respectivecontroller.Corresponds to AUTOPRESS 1, 2 messageon status page.

Cabin/CockpitAltitude ReadoutDisplays current cabin/cockpit altitude (in automaticor manual mode).

Cabin/Cockpit Rate ofChange ReadoutDisplays rate of change infeet per minute and directionvia arrow symbol.

Delta Pressure ReadoutDisplays cabin and cockpit toambient differential pressure.Excursions above 8.65 psiindicated on EICAS as DIFFPRESS warning and CABINPRESSURE warning is heard.

Landing Field Elevation ReadoutDisplays elevation (in feet) as setat LDG ELEV selector. Scale set in20--foot increments.

Less than8,500 feet

Positive/negative ratesat 100 fpm

Less than8.65 psi

More than8,500 but lessthan 10,000 feet

More than8.65 psi

More than10,000 feet

Incrementsof 100 feet

Positive/negative ratesat 100 fpm

Incrementsof 0.1 psi

Incrementsof 20 feet(cyan)Data measured by the activecontroller (PRESS CONT 1,PRESS CONT 2)

Data measured by the monitoring source(CPAM, PRESS CONT 1, PRESS CONT 2)

P

SOURCE INDICATOR --Monitoring / ReferenceComes on (white) toindicate monitoring source:CPAM, orPRESS CONT 1, orPRESS CONT 2

If all sources failed, comeson as dashes (amber).

SOURCE INDICATOR --ACTIVE CONTROLLERComes on (white) toindicate pressurizationcontroller:PRESS CONT 1, orPRESS CONT 2, orPRESS MAN

Active Controller’s DataDisplayed on ECSpage only.

Page 39: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--60--7Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Pressurization System

Flight Crew Operating ManualCSP A--013

MASTER

2. OUTFLOW VALVES

The dual, redundant, electro--pneumatic outflow valves are installed on the rear pressurebulkhead, below floor level, and are designated as the primary and secondary valves. Bothvalves are slaved together through a pneumatic line and are electrically controlled. Thevalves will respond to either electrical signals in automatic mode, or to pneumatic inputsignals from the manual regulators on the CABIN PRESS control panel.

3. CABIN PRESSURE CONTROLLERS

The aircraft is equipped with dual, redundant pressure controllers, which operate only inautomatic mode. All controller outputs are sent to the outflow valves. While one controller isin use, the other updates automatically. The active cabin pressure controller commands theoutflow valve to a nominal differential pressure of 8.33 psid. Inputs to the pressurecontrollers are received from air data computer (ADC 1) normally. ADC 2 is the backup toADC 1. If a controller fails, the system will automatically switch over to the other controller.If automatic switch--over fails, select the PRESS CONTROL switch twice. This will enablethe redundant controller. If both pressure controllers fail, both outflow valves will go to anisobaric hold mode.When the airplane is on the ground for 3 minutes, automatic pressurecontroller switch--over will occur.

The pressurization system automatically maintains cabin pressure through all phases offlight. Typical values used in the cabin/flight altitude schedule during manual mode are asfollows:

CABIN PRESSURE ALTITUDE (feet) AC FLIGHT ALTITUDE(feet)

DECENT CLIMB--600 --600 0--600 0 5,000--350 575 10,000740 1,240 15,0001,260 1,630 17,5001,770 2,020 20,0004,270 4,330 30,0005,990 5,990 35,0006,880 6,880 37,5007,990 7,990 41,000

A. Automatic Pressurization Modes

S Ground mode,Both outflow valves are driven full open.

S Pre-Pressure mode,When thrust levers are advanced to take-off, the cabin is pressurized to --150 feet atapproximately 300 ft/min.

Page 40: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--60--8ENVIRONMENTAL CONTROL SYSTEM

Pressurization System

MASTERFlight Crew Operating ManualCSP A--013

S Take-Off abort mode,When the thrust levers are retarded to idle, the cabin ascends at approximately 500ft/min for 20 seconds, then the outflow valves are driven full open.

S Climb mode,Cabin climb is in accordance with a fixed schedule, cabin altitude vs aircraft altitudeat a rate of approximately 500 ft/min. The controller compares selected landingelevation to the climb schedule, then selects the highest pressure schedule.

S Flight abort mode,When the aircraft has maintained 6,000 feet altitude or lower altitude for 10 minutes,and then has initiated a descent of 1,000 ft/min, the system will then assume theelevation for the departing airport, regardless of the pre-selected landing elevation.

S The cabin descent schedule occurs when the aircraft altitude is maintained at0±200 feet for 10 minutes. The system pre--sets a decent rate of approximately300 ft/min.

S The cabin full descent schedule occurs when the aircraft is in descent. Cabinaltitude decreases at approximately 300 ft/min, to either landing elevation, ormaximum differential, whichever is highest. When the landing elevation exceeds8,000 feet, cabin altitude will be maintained at maximum differential, until the aircraftdescends, then the cabin altitude will rate up to the pre-selected landing elevation.

S Landing mode,The cabin altitude is driven below field elevation or the aircraft is unpressurized.When the cabin is below field elevation, then the cabin is rated up at approximately500 ft/min for 60 seconds, then the outflow valve is driven full open.

S Touch and Go mode,On aircraft touchdown, the system will assume landing mode; as the thrust leversare advanced, the system will schedule pre-pressure mode.

B. Manual Pressurization Modes

S UP selection,Cabin ascends at selected rate of 50 fpm to 3,000 ±1000 fpm. When the desiredcabin altitude is reached, select MAN ALT to mid position.

S DN selection,Cabin descends at selected rate of 50 fpm to 3,000 ±1000 fpm. When the desiredcabin altitude is reached, select MAN ALT to mid position.

S Mid selection,Disables all previous MAN ALT selections.

Automatic mode schedules the pressurization controllers to automatically regulate therate of change of cabin altitude:

S Ascent from 500 ±75 fpm.

Page 41: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

08--60--9Vol. 1

REV 56, Jan 31/03ENVIRONMENTAL CONTROL SYSTEM

Pressurization System

Flight Crew Operating ManualCSP A--013

MASTER

S Decent from 300 ±75 fpm.

Manual mode rate controls are provided to manually regulate the rate of change tocabin altitude:

S Ascent from 150 ±150 fpm to 3,000 ±500 fpm and

S Decent from 100 ±100 fpm to 2,500 ±500 fpm..

C. Differential Pressure Control

Each outflow valve has positive and negative pressure relief. The pressure controllersnormally control the cabin--to--outside pressure to 8.33 psid. The valves are preset toopen at a maximum positive differential pressure of 8.6 ±0.1 psid and at a negativedifferential pressure of −0.5 psid.

D. Cabin Altitude Limitation

Altitude limit controllers within each outflow valve, operate to prevent the cabin altitudefrom increasing above 14,250 ±750 feet.

E. Emergency Depressurization

Electrical signals from the EMER DEPRESS switch commands both outflow valves toopen. If the aircraft is at a cruise altitude (above 15,000 feet), the altitude limitersoperate to prevent cabin altitude from exceeding 14,250 ±750 feet.

F. Cabin Pressure Monitoring

The system uses measurements from the two cabin pressure controllers and the cabinpressure acquisition module (CPAM) to control and monitor the system. The CPAMsupplies signals to the EICAS to display the following information:

S Cabin altitude (z)

S Cabin altitude rate of change (dz/dt)

S Cabin to ambient differential pressure (delta P)

S CPAM failure -- If a CPAM fails, the redundant controller will assume the function ofthe failed CPAM (indications only)

S If the PASS SIGNS switches are selected to AUTO, the CPAM will cause the NOSMKG and SEAT BLTS signs to come on when the cabin altitude reaches 10,000feet

S The CPAM will automatically trigger the passenger oxygen auto deploy systemwhen the cabin altitude reaches 14,000 feet.

Page 42: CHAPTER 8 --- ENVIRONMENTAL CONTROL SYSTEM

REV 56, Jan 31/03

Vol. 1 08--60--10ENVIRONMENTAL CONTROL SYSTEM

Pressurization System

MASTERFlight Crew Operating ManualCSP A--013

A “CABIN PRESSURE” voice alert is also provided during the following EICASwarnings:

S DIFF PRESS warning message

S CABIN ALT warning message (cabin altitude above 10,000 feet).

G. System Circuit Breakers

SYSTEM SUB--SYSTEM CB NAME BUS BAR CBPANEL

CBLOCATION

NOTES

FlightCompartment CONT PNL A10CompartmentControl Panel

CONT PNLDC ESS 4

A10

Cabin ControllerCONT 1

DC ESS 4A8

CabinPressurization

ControllerCONT 2 A9Pressurization

Control CabinPressureAcquisitionModule(CPAM)

CABIN PRESSMOD DC BAT 2 P6