CHAPTER 2 Bridge Loads

download CHAPTER 2 Bridge Loads

of 23

Transcript of CHAPTER 2 Bridge Loads

  • 8/17/2019 CHAPTER 2 Bridge Loads

    1/23

  • 8/17/2019 CHAPTER 2 Bridge Loads

    2/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 2

    The m-factors specified below shall not be applied in conjunction with approximate load

    distribution factors  specified in Chapter 13: Approximate Methods of Analysis of ERA

    design manual,  except where the lever rule is used or where special requirements for

    exterior beams in beam-slab bridges is applied.

     Number of Loaded Lanes 1 2 3 >3

    Multiple Presence Factors “m”  1.20 1.0 0.85 0.65

    Table 2.2 Multiple Presence Factors "m"

    The multiple presence factors have been included in the approximate equations for

    distribution factors in Chapter 13: Approximate Methods of Analysis of ERA Bridgedesign manual,  both for single and multiple loaded lanes. The equations are based on

    evaluation of several combinations of loaded lanes with their appropriate multiple

     presence factors and are intended to account for the worst case scenario. Where use of the

    lever rule is specified the Designer must determine the number and location of vehiclesand lanes, and, therefore, must include the multiple presence. Stated another way, if a

    sketch is required to determine load distribution, the Designer is responsible for includingmultiple presence factors and selecting the worst design case. The factor 1.20 from Table

    2-2 has already been included in the approximate equations and should be removed forthe purpose of fatigue investigations.

    If a component supported a sidewalk and one lane, it would be investigated for thevehicular live load alone with m = 1.20, and for the pedestrian loads combined with the

    vehicular live load with m = 1.0. If a component supported a sidewalk and two lanes of

    vehicular live load, it would be investigated for:

      One lane of vehicular live load, m = 1.20;

      The greater of the more significant lane of vehicular live load and the pedestrian loads

    or two lanes of vehicular live load, m = 1.0 applied to the governing case; and  Two lanes of vehicular live load and the pedestrian loads, m = 0.85.

    The multiple presence factor of 1.20 for a single lane does not apply to the pedestrian

    loads. Therefore, the case of the pedestrian loads without the vehicular live load is a

    subset of the second bulleted item.

    The multiple presence factors in Table 2.2 were developed based on an ADTT (Average

    Daily Truck Traffic) of 5000 trucks in one direction. The force effect resulting from the

    appropriate number of lanes shall be reduced for sites with lower ADTT as follows:

     

    If 100  ADTT  1000; 95 % of the specified force effect shall be used; and  If ADTT < 100; 90 % of the specified force effect shall be used.

    This adjustment is based on the reduced probability of attaining the design event during a75-year design life with reduced truck volume.

    Design Truck

  • 8/17/2019 CHAPTER 2 Bridge Loads

    3/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 3

    The weights and spacing of axles and wheels for the design truck shall be as specified in

    Figure 2-1. A dynamic load allowance shall be considered as specified in the following

    subchapter on Vehicular Dynamic Load Allowance.

     F  IGURE 2-1 C  HARACTERISTICS OF THE D ESIGN T  RUCK  

    Except as specified in following subchapters on the application of Design Vehicular Live

    Loads and Fatigue Loads, the spacing between the two 145 kN axles shall be varied

     between 4.3 and 9.0 m to produce extreme force effects.

    Design Tandem

    The design tandem used for Strategic Bridges shall consist of a pair of 110 kN  axlesspaced 1.2 m apart. The transverse spacing of wheels shall be taken as 1.8 m. A dynamic

    load allowance shall be considered as specified in a following subchapter. The spacing

    and loading is illustrated in Figure 3-2

    Figure 2-2 Design Tandem Load

    Design Lane Load

    4.3 m

    4.3 –9.0 m

    1.8 m

    Plan of Design Truck Loadshowing tire contact areas

     110 kN

    110 kN

    1.2 m

    1.8 m

  • 8/17/2019 CHAPTER 2 Bridge Loads

    4/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 4

    The design lane load shall consist of a load of 9.3 kN/m, uniformly distributed in the

    longitudinal direction. Transversely, the design lane load shall be assumed to be

    uniformly distributed over a 3.0-m width. The force effects from the design lane load

    shall not be subject to a dynamic load allowance.

    2.3  PEDESTRIAN LOADS A pedestrian load of 4.0 kPa (kN/m

    2) shall be applied to all sidewalks wider than 0.6 m

    and considered simultaneously with the vehicular design live load.See the provisions of above subchapter  Multiple Presence of Live Load  for applying the

     pedestrian loads in combination with the vehicular live load. Usually the 4 kN/m2  load

    will allow for small cars to pass. To avoid accidents for bridges wider than 2.4 m, provision shall be made for an additional axle load.

    Where sidewalks, pedestrian, and/or bicycle bridges are intended to be used by

    maintenance and/or other incidental vehicles, these loads shall be considered in the

    design. If unknown, at least one movable axle load of 70 kN acting together with the pedestrian load shall be applied. The dynamic load allowance need not be considered for

    these vehicles.

    In half-through-trusses of steel, the compressed top chord of a simple span truss shall be

    designed to resist a lateral force of not less than 4.0 kN/m length, considered as a permanent load for the Strength I Load Combination and factored accordingly.

    2.4  DYNAMIC LOAD ALLOWANCE (IM  =  VEHICULAR DYNAMIC LOAD

    ALLOWANCE)Unless otherwise permitted in subchapters  Buried Components  and Wood Components 

     below, the static effects of the design truck or tandem, other than centrifugal and braking

    forces, shall be increased by the percentage specified in Table 2.3 for dynamic load

    allowance.

    The factor to be applied to the static load shall be taken as: (1 + IM/100).

    The dynamic load allowance shall not be applied to pedestrian loads or to the design laneload.

    Component IM

    Deck Joints –  All Limit States 75%

    All Other Components

      Fatigue and Fracture Limit State

      All Other Limit States

    15%

    33%

    Table 2.3 Dynamic Load Allowance, IM

    Dynamic load allowance need not be applied to:

      Retaining walls not subject to vertical reactions from the superstructure, and

      Foundation components that are entirely below ground level.

    The dynamic load allowance shall be reduced for components, other than joints, if

     justified by sufficient evidence, but in no case shall the dynamic load allowance used in

    design be less than 50% of IM in the table above.

  • 8/17/2019 CHAPTER 2 Bridge Loads

    5/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 5

    The dynamic load allowance (IM) in Table 3.3 is an increment to be applied to the static

    wheel load to account for wheel load impact from moving vehicles.

    Dynamic effects due to moving vehicles shall be attributed to two sources:

      Hammering effect is the dynamic response of the wheel assembly to riding surface

    discontinuities, such as deck joints, cracks, potholes, and delamination’s, and  Dynamic response of the bridge as a whole to passing vehicles, which shall be due to

    long undulations in the roadway pavement, such as those caused by settlement of fill,

    or to resonant excitation as a result of similar frequencies of vibration between bridge

    and vehicle. The frequency of vibration of any bridge should not exceed 3 Hz.

    B URIED C OMPONENTS  

    The dynamic load allowance for culverts and other buried structures, in %, shall be taken

    as:

    IM = 33 (1.0 - 4.l*10-4

     DE) > 0%

    Where:DE  = the minimum depth of earth cover above the structure (mm)

    W OOD C OMPONENTS  

    Wood structures are known to experience reduced dynamic wheel load effects due to

    internal friction between the components and the damping characteristics of wood.

    For wood bridges and wood components of bridges, the dynamic load allowance values

    specified in table of dynamic load allowance shall be reduced to 70   of the valuesspecified therein for IM.

    2.5 TIRE CONTACT AREA 

    The tire contact area of a wheel consisting of one or two tires shall be assumed to be a

    single rectangle, whose width is 500 mm and whose length () in mm shall be taken as:

    l   = 2.28 x 10-3

      (1 + IM/100) P (2.1)

    where:  = load factor for the limit state under consideration.IM = dynamic load allowance percent

    P = 72.5 kN for the design truck and 55 kN for the design tandem

    The tire pressure shall be assumed to be uniformly distributed over the contact area. The

    tire pressure shall be assumed to be distributed as follows:

     

    On continuous surfaces, uniformly over the specified contact area, and  On interrupted surfaces, uniformly over the actual contact area within the footprintwith the pressure increased in the ratio of the specified to actual contact areas.

    However, for all concrete decks including composite decks the length 200 mm shall be

    used in Equation 2.1.

    2.6 APPLICATION OF DESIGN VEHICULAR LIVE LOADS 

  • 8/17/2019 CHAPTER 2 Bridge Loads

    6/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 6

    The effects of an axle sequence and the lane load are superimposed in order to obtain

    extreme values.

    Unless otherwise specified, the extreme force effect shall be taken as the larger of thefollowing:

      The effect of the design tandem combined with the effect of the design lane load, or

     

    The effect of one design truck with the variable axle spacing specified in thesubchapter  Multiple Presence of Live Load   above, combined with the effect of thedesign lane load, and

      For both negative and positive moment between points of contraflexure under auniform load on all spans, and reaction at interior piers only, 90% of the effect of two

    design trucks spaced a minimum of 15.0 m between the lead axle of one truck and therear axle of the other truck, combined with 90% of the effect of the design lane load.

    The distance between the 145 kN axles of each truck shall be taken as 4.3 m.

    The design truck or tandem shall be positioned transversely such that the center of anywheel load is not closer than:

      For the design of the deck overhang - 300 mm from the face of the curb or railing,

    and

      For the design of all other components - 600 mm from the edge of the design lane.

    Unless otherwise specified, the lengths of design lanes, or parts thereof, that contribute to

    the extreme force effect under consideration, shall be loaded with the design lane load.

    The lane load is not interrupted to provide space for the axle sequences of the design

    tandem or the design truck.

    2.7 CENTRIFUGAL FORCES (CE= VEHICULAR CENTRIFUGAL FORCE)Centrifugal forces shall be taken as the product of the axle weights of the design truck or

    tandem and the factor C, taken as:

    C = 4 v2

    3 g*R

    where: v = highway design speed (m/s)

    g = gravitational acceleration: 9.81 (m/s2)

    R = radius of curvature of traffic lane (m)

    Highway design speed shall not be taken to be less than the value specified in theGeometric Design Manual-2001, Chapter 5: Design Controls & Criteria, Section 5.8:

     Design Speed . The multiple presence factors specified above in subchapter  Multiple Presence of Live Load   shall apply. Centrifugal forces shall be applied horizontally at a

    distance 1.8 m above the roadway surface.

  • 8/17/2019 CHAPTER 2 Bridge Loads

    7/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 7

    Lane load is neglected in computing the centrifugal force, as the spacing of vehicles at

    high speed is assumed to be large, resulting in a low density of vehicles following and/or

     preceding the design truck.

    2.8 BRAKING FORCE (BR= VEHICULAR BRAKING FORCE)Based on energy principles, and assuming uniform deceleration (retardation), the braking

    force determined as a fraction "b" of vehicle weight is:

     b = v2 

    2gawhere a = the length of uniform deceleration.

    Calculations using a braking length of 122 m and a speed of 90 km/h (25 m/s) yield b =

    0.26 for a horizontal force that will act for a period of about 10 seconds. The factor "b"

    applies to all lanes in one direction because all vehicles may have reacted within this time

    frame. Only the design truck or tandem is to be considered.

    Braking forces shall be taken as 25 % of the axle weights of the design truck or tandem

     per lane placed in all design lanes which are considered to be loaded in accordance withabove subchapter Number of Design Lanes, and which are carrying traffic headed in the

    same direction. These forces shall be assumed to act horizontally at the level of theroadway surface in either longitudinal direction to cause extreme force effects. All

    design lanes shall be simultaneously loaded for bridges likely to become one-directional

    in the future.

    2.9 WIND LOAD (WL= WIND ON LIVE LOAD; WS= WIND LOAD ON STRUCTURE)

    H ORIZONTALW IND P RESSURE  

    General

    Pressures specified herein shall be assumed to be caused by a base design wind velocity,

    VB, of 160 km/h (= 45 m/s).

    Wind load shall be assumed to be uniformly distributed on the area exposed to the wind.The exposed area shall be the sum of areas of all components, including floor system and

    railing, as seen in elevation taken perpendicular to the assumed wind direction. This

    direction shall be varied to determine the extreme force effect in the structure or in its

    components. Areas that do not contribute to the extreme force effect under considerationshall be neglected in the analysis.

    For bridges or parts of bridges more than 10 m above low ground or water level, the

    design wind velocity, VDZ (km/h), at design elevation, z, should be adjusted according to:

    where: V10 = wind velocity at 10 m above low ground or above design water level (km/h)

    o B

    o DZ 

     Z 

     Z  In

    V V V 

    10

    *5.2  

  • 8/17/2019 CHAPTER 2 Bridge Loads

    8/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 8

    VB = base wind velocity of 160 km/h (45 m/s) at 10 m height, yielding design

     pressures specified in following subchapters Wind Pressure on Structures 

    and Vertical Wind Pressure 

    Z = height of structure at which wind loads are being calculated as measured fromlow ground, or from water level, > 10 m (m)

    Vo = friction velocity, a meteorological wind characteristic taken, as specified in

    Table 3-4, for various upwind surface characteristics (km/h)

    Zo = friction length of upstream fetch, a meteorological wind characteristic takenas specified in Table 3-4 below (m)

    V10 shall be established from:

      Basic Wind Speed charts available from National Meteorological Services Agencyfor various recurrence intervals,

      Site-specific wind surveys, or

      In the absence of better criterion, the assumption that V10 = VB =145 km/h (= 40 m/s)shall be used for small and medium sized bridges.

    The following descriptions are for the terms "open country" and "suburban" in Table 3-4:

      Open Country: Open terrain with scattered obstructions having heights generally less

    than 10 m. This category includes flat open country and grasslands.

      Urban and Suburban: Urban and suburban areas, wooded areas, or other terrainwith numerous closely spaced obstructions having the size of single-family or larger

    dwellings. Use of this category shall be limited to those areas for whichrepresentative terrain prevails in the upwind direction at least 500 m.

    CONDITION OPEN COUNTRY URBAN AND SUBURBAN

    Vo (km/h) 13.2 17.6

    Zo (m) 70 1000Table 2-4 Values of Vo and Zo for Various Upstream Surface Conditions

    Base design wind velocity varies significantly due to local conditions. For small and/or

    low structures, wind usually does not govern. For large and/or tall bridges, however, thelocal conditions should be investigated.

    Pressures on windward and leeward sides are to be taken simultaneously in the assumed

    direction of wind.Typically, a bridge structure should be examined separately under wind pressures from

    two or more different directions in order to ascertain those windward, leeward, and side

     pressures producing the most critical loads on the structure.

    The suggested wind speed V10 = 40 m/s should be compared with the Ethiopian BuildingCode Standard, where V10 = 150 km/h (42 m/s) is used for the highest mountaintops. The

     National Atlas of Ethiopia shows that the western parts of the country (Bahar Dar,

     Nekemte, Gore, Jima, Awasa and Goba) have a wind speed (V10) that never exceeds 15knots (equal to 30 m/s or 105 km/h). However, since the National Meteorological

    Services Agency has collected wind data only every 4 hours it is not certain that the

    maximum  wind speeds are given at the meteorological stations. Therefore, it is

    recommended to make separate observations for large or wind-sensitive bridges.

  • 8/17/2019 CHAPTER 2 Bridge Loads

    9/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 9

    Equation 3.2 below is based on boundary layer theory combined with empirical

    observations and represents the most recent approach to defining wind speeds for various

    conditions as used in meteorology. In the past, an exponential equation was sometimesused to relate wind speed to heights above 10 m. This formulation was based solely on

    empirical observations and had no theoretical basis.

    10

    Z*CVV

    10DZ   (2.2)

    The purpose of the term C and exponent "" was to adjust the equation for variousupstream surface conditions, similar to the use of Table 3-4 (further information can befound in Refs.)

    Wind Pressure on Structures: WS

    For small and medium sized concrete bridges below 50m length the wind load on

    structures shall be neglected.

    For large and/or light bridges the following shall apply. If justified by local conditions, adifferent base design wind velocity shall be selected for load combinations not involving

    wind on live load. The direction of the design wind shall be assumed horizontal, unless

    otherwise specified in the following subchapter Aero elastic Instability. In the absence of

    more precise data, design wind pressure, PD in kPa, shall be determined as:

    25600

    VP

    V

    VPP

      DZ

    2

    B

    2

    B

    DZ

    BD  

     

    Where PB = base wind pressure specified in Table 3-5 (kPa):

    STRUCTURAL COMPONENT WINDWARD LOAD, kPa LEEWARD LOAD, kPaTrusses, Columns, and Arches 2.4 1.2

    Beams 2.4 Not applicable

    Large Flat Surfaces 1.9 Not applicable

    Table 2-5 Base Pressures, PB Corresponding to VB = 160 km/h (45 m/s)

    The wind loading shall not be taken less than 4.4 kN/m2 in the plane of a windward chord

    and 2.2 kN/m2 in the plane of a leeward chord on truss and arch components, and not

    less than 4.4 kN/m2 on beam or girder components.

    Wind tunnel tests shall be used to provide more precise estimates of wind pressures. Suchtesting should be considered where wind is a major design load.

    Where the wind is not taken as normal to the structure, the base wind pressures, PB, forvarious angles of wind direction shall be taken as specified in Table 2-6 and shall be

    applied to a single place of exposed area. The skew angle shall be taken as measuredfrom a perpendicular to the longitudinal axis. The wind direction for design shall be that

    which produces the extreme force effect on the component under investigation. The

    transverse and longitudinal pressures shall be applied simultaneously.

  • 8/17/2019 CHAPTER 2 Bridge Loads

    10/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 10

    Columns and Arches Girders

    Skew Angle of Wind,

    Degrees

    Lateral

    Load (kPa)

    Longitudinal

    Load(kPa)

    Lateral Load

    (kPa)

    Longitudinal

    Load (kPa)

    0 3.6 0 2.4 0

    15 3.4 0.6 2.1 0.3

    30 3.1 1.3 2.0 0.6

    45 2.3 2.0 1.6 0.860 1.1 2.4 0.8 0.9

    Table 2-6 Base Wind Pressures, PB (kPa) for Various Angles of Attack VB=160 km/h.

    For trusses, columns, and arches, the base wind pressures specified in Table 2-6 are thesum of the pressures applied to both the windward and leeward areas.

    The transverse and longitudinal forces to be applied directly to the substructure shall be

    calculated from an assumed base wind pressure of 1.9 kPa. For wind directions takenskewed to the substructure, this force shall be resolved into components perpendicular to

    the end and front elevations of the substructure. The component perpendicular to the end

    elevation shall act on the exposed substructure area as seen in end elevation, and thecomponent perpendicular to the front elevation shall act on the exposed areas and shall be

    applied simultaneously with the wind loads from the superstructure.

    Wind Pressure on Vehicles: WL

    When vehicles are present, the design wind pressure shall be applied to both structure and

    vehicles. Wind pressure on vehicles shall be represented by an interruptible, movingforce of 1.5 kN/m acting normal to, and 1.8 m above, the roadway and shall be

    transmitted to the structure.

    When wind on vehicles is not taken as normal to the structure, the components of normal

    and parallel force applied to the live load shall be taken as specified in Table 3-7 with theskew angle taken as referenced normal to the surface.

    Skew Angle (Degrees) Normal Component (kN/m) Parallel Component (kN/m)

    0 1.46 0

    15 1.28 0.18

    30 1.20 0.35

    45 0.96 0.47

    60 0.50 0.55

    Table 2-7 Wind Components on Live Load

    Based on practical experience, maximum live loads are not expected to be present on the bridge when the wind velocity exceeds 90 km/h. The load factor corresponding to the

    treatment of wind on structure only in Load Combination Strength III would be

    (90/145)2*1.4 = 0.54, which has been rounded to 0.5 in the Strength IV Load

    Combination. This load factor corresponds to 0.3 in Service 1.

  • 8/17/2019 CHAPTER 2 Bridge Loads

    11/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 11

    V ERTICAL W IND P RESSURE  

    Unless otherwise determined in following subchapter  Aero elastic Instability, a vertical

    upward wind force of 1.0 kPa (kN/m2) times the width of the deck, including parapets

    and sidewalks, shall be considered a longitudinal line load. This force shall be applied

    only for large and/or other than concrete bridges. It shall be applied only for limit states

    that do not involve wind on live load, and only when the direction of wind is taken to be

     perpendicular to the longitudinal axis of the bridge. This lineal force shall be applied atthe windward quarter-point of the deck width in conjunction with the horizontal wind

    loads specified in the previous subchapter Horizontal Wind Pressure.

    The intent of this subchapter is to account for the effect resulting from interruption of the

    horizontal flow of air by the superstructure. This load is to be applied even todiscontinuous bridge decks, such as grid decks. This load may govern where overturning 

    of the bridge is investigated.

    AERO ELASTIC I NSTABILITY  

    Aero elastic force effects shall be taken into account in the design of bridges and

    structural components that are wind-sensitive. All bridges and structural components

    thereof with a span length to width or depth ratio exceeding 30.0 shall be deemed wind-sensitive.

    Many bridges, decks, or individual structural components have been shown to be aero

    elastically insensitive if their length-to-width or length-to-depth ratios are about 30.0, asomewhat arbitrary value helpful only in identifying likely wind-sensitive cases.

    2.10 WATER LOADS (WA= WATER LOAD AND STREAM PRESSURE)

    S TATIC P  RESSURE  

    Static pressure of water shall be assumed to act perpendicular to the surface that is

    retaining the water. Pressure shall be calculated as the product of height of water above

    the point of consideration, the density of water, and "g" (the acceleration of gravity =9.81 m/s

    2).

     p =  * g * z * 10-9

    where p = static pressure (Mpa)

     = density of water (kg/m3)

    z = height of water above the point of consideration (mm)

    g = Gravitational acceleration (m/s2)

    S TREAM P  RESSURE  

    Longitudinal

    For the purpose of this chapter, the longitudinal direction refers to the major axis of asubstructure unit.

    The pressure of flowing water acting in the longitudinal direction of substructures shall be taken as:

     p = 5.14*10-4

     CDV2  (2.3)

    where: p = pressure of flowing water (MPa)

  • 8/17/2019 CHAPTER 2 Bridge Loads

    12/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 12

    CD = drag coefficient for piers as specified in Table 2-8

    V = design velocity in m/s of water for the design flood in strength and service

    limit states and for the check flood in the extreme event limit state (see ERA

     Drainage Design Manual-2001, Chapter 5: Hydrology).

    Type CD 

    Semicircular-nosed pier 0.7Square-ended pier 1.4

    Debris lodged against the pier 1.4

    Wedged-nosed pier with nose angle 90o or less 0.8

    Table 2-8 Drag Coefficient

    The longitudinal drag force shall be taken as the product of longitudinal stream pressure

    and the projected surface exposed thereto.

    Floating logs, roots, and other debris may accumulate at piers and, by blocking parts of

    the waterway, increase stream pressure load on the pier. Such accumulation is a functionof the availability of such debris and level of maintenance efforts by which it is removed.

    It shall be accounted for by the judicious increase in both the exposed surface and thevelocity of water.

    The following provision (Ref. 2) shall be used as guidance in the absence of site-specificcriteria:

      Where a significant amount of driftwood is carried, water pressure shall also beallowed for on a driftwood raft lodged against the pier. The size of the raft is a matter

    of judgment, but as a guide, Dimension A in Figure 3-3 should be half the waterdepth, but not greater than 3m. Dimension B should be half the sum of adjacent span

    lengths, but no greater than 14 m. Pressure shall be calculated using Equation 3.3,

    with CD = 0.5.

    Figure 2-3 Debris Raft for Pier Design

    Lateral 

    The lateral, uniformly distributed pressure on substructure due to water flowing at an

    angle, , to the longitudinal axis of the pier (see Figure 2-4) shall be taken as:

    PL  = 5.14 x 10-4

    CLV2

    where: PL = lateral pressure (MPa)

  • 8/17/2019 CHAPTER 2 Bridge Loads

    13/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 13

    CL = lateral drag coefficient specified in Table 3-9 below.

    Figure 2-4 Plan View of Pier Showing Stream Flow Pressure

    Angle, , between direction of flow and

    longitudinal axis of the pier

    CL 

    0o  0.0

    1o  0.5

    10o  0.7

    20o  0.9

    30o  1.0

    (Ref 15)

    Table 2-9 Lateral Drag Coefficient

    The lateral drag force shall be taken as the product of the lateral stream pressure and the

    surface exposed thereto.

    2.11  EARTHQUAKE EFFECTS (EQ= EARTHQUAKE)

    G ENERAL 

    Earthquake loads shall be taken to be horizontal force effects determined on the basis of

    the elastic response coefficient, Csm  and the equivalent weight of the superstructure,

    adjusted by the response modification factor, R.

     ACCELERATION C OEFFICIENT  

    The coefficient, "A", to be used in the application of these provisions shall be determined

    from the contour map of Ethiopia in Figure 3-5. Linear interpolation shall be used for

    sites located between contour lines or between a contour line and a local maximum or

    minimum.

     I  MPORTANCE C  ATEGORIES  

    The bridges within Zone 4 (mainly Rift Valley) shall be classified into one of three

    importance categories as follows:

      Critical bridges,

      Essential bridges, or

      Other bridges.

  • 8/17/2019 CHAPTER 2 Bridge Loads

    14/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 14

    The basis of classification shall include social/survival and security/defense requirements.

    In classifying a bridge, consideration should be given to possible future changes in

    conditions and requirements.

    Figure 2.5. Earthquake zones

    Essential bridges are generally those that should, as a minimum, be open to emergencyvehicles and for security/defense purposes immediately after the design earthquake, i.e., a

    475-year return period event. However, some bridges must remain open to all traffic after

    the design earthquake and be usable by emergency vehicles and for security/defense

     purposes immediately after a large earthquake, e.g., a 2500 year return period event.

    These bridges should be regarded as critical structures.

  • 8/17/2019 CHAPTER 2 Bridge Loads

    15/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 15

     ACCELERATION C OEFFICIENTS  

    Each bridge shall be assigned to one of the seismic zones in accordance with Table 2-10

     below:

    EBCS zone from Figure 3-9 Acceleration Coefficient

    1 A  0.03

    2 0.03 < A  0.05

    3 0.05 < A  0.07

    4 0.07 < A  0.10

    Table 2-10 Seismic Zones

    S  ITE E  FFECTS : S OIL P  ROFILES  

    Site effects shall be included in the determination of seismic loads for bridges. Siteeffects on structural response are due to the soil conditions. Four soil profiles are used in

    these Specifications to define a site coefficient used to modify the acceleration

    coefficient.

    The site coefficient, S, is used to include the effect of site conditions on the elastic

    seismic response coefficient as specified in the following subchapter.

    The site coefficient, S, specified in Table 2-11 (below), shall be based upon soil profile

    types defined below.

    Site

    Coefficient

    Soil Profile Type

    I II III IV

    S 1.0 1.2 1.5 2.0

    Table 2-11 Site Coefficients

    In locations where the soil properties are not known in sufficient detail to determine the

    soil profile type, or where the profile does not fit any of the four types, the site coefficient

    for Soil Profile Type II shall be used.

    A soil profile shall be taken as Type I  if composed of rock of any description, eithershale-like or crystalline in nature, or stiff soils where the soil depth is less than 60 m, and

    the soil types overlying the rock are stable deposits of sands, gravels, or stiff clays.These materials shall be characterized by a shear wave velocity greater than 765 m/s.

    A profile with stiff cohesive or deep cohesionless soils where the soil depth exceeds 60 mand the soil types overlying the rock are stable deposits of sands, gravels, or stiff clays

    shall be taken as Type II.

  • 8/17/2019 CHAPTER 2 Bridge Loads

    16/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 16

    A profile with soft to medium-stiff clays and sands, characterized by 9 m or more of soft

    to medium-stiff clays with or without intervening layers of sand or other cohesionless

    soils shall be taken as Type III.

    A profile with soft clays or silts greater than 12 m in depth shall be taken as Type IV.

    These materials shall be characterized by a shear wave velocity of less than 152 m/s andmight include loose natural deposits or manmade, nonengineered fill.

     E  LASTIC S  EISMIC R ESPONSE C OEFFICIENT  

    Unless specified otherwise as exceptions in this subchapter, the elastic seismic response

    coefficient, Csm, for the mth

     mode of vibration shall be taken as:  

     AT 

     AS C 

    m

     sm   5.22.1

    3/2  

    where:Tm = period of vibration of the m

    th

     mode (s)A = acceleration coefficient specified in Table 2-10

    S = site coefficient specified in Table 2-11  

    The determination of the period of vibration, Tm, should be based on the nominal,unfactored mass of the component or structure.

    The elastic seismic response coefficient shall be normalized using the input ground

    acceleration "A” and the result plotted against the period of vibration. Such a plot is

    given in Figure 2-6 for different soil profiles, based on 5 % damping.

    Figure 2-6 Seismic Response Coefficients, Csm  for Various Soil Profiles,

    Normalized with Respect to Acceleration Coefficient "A" (Csm  on the left

    axis)

    Exceptions to the application of Equation for Csm are as follows:

  • 8/17/2019 CHAPTER 2 Bridge Loads

    17/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 17

      For bridges on soil profiles III or IV, Csm need not exceed 2.0*A.

      For soil profiles III and IV, and for modes other than the fundamental mode, that have periods less than 0.3 s, Csm shall be taken as:

    Csm = A (0.8 + 4.0*Tm)

      If the period of vibration for any mode exceeds 4.0 s, the value of Csm for that modeshall be taken as:

    Csm  = 3ASTm

    4/3 

     R ESPONSE M ODIFICATION F  ACTORS  

    Except as noted herein, seismic design force effects for substructures and the connections between parts of structures shall be determined by dividing the force effects resulting

    from elastic analysis by the appropriate response modification factor, R, as specified inTables 2-12 and 2-13, respectively.

    Substructure Importance Category

    Critical Essential Other

    Wall-type piers –  larger dimension 1.5 1.5 2.0

    Reinforced concrete pile bents

      Vertical piles only

      With battered piles

    1.51.5

    2.01.5

    3.02.0

    Single columns 1.5 2.0 3.0

    Steel or composite steel and concrete pile bents

      Vertical pile only

      With battered piles 1.51.5

    3.52.0

    5.03.0

    Multiple column bents 1.5 3.5 5.0

    Table 2-12 Response Modification R-Factors for Substructures

    Connection All Importance Categories

    Superstructure to abutment 0.8

    Expansion joints within a span of the superstructure 0.8

    Columns, piers, or pile bents to cap beam or superstructure 1.0

    Columns or piers to foundations 1.0

    Table 2-13 Response Modification R-Factors for Connections 

  • 8/17/2019 CHAPTER 2 Bridge Loads

    18/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 18

     A NALYSIS FOR E  ARTHQUAKE LOADS  

    General

    Bridges in Seismic Zone 1-3 need not be analyzed for seismic loads, regardless of their

    importance and geometry.

    Single-Span Bridges

    Seismic analysis is not required for single-span bridges, regardless of seismic zone.

    Multispan Bridges

    For multispan structures, the minimum analysis requirements shall be as specified below:

    SeismicZone

    Single-SpanBridges

    Multispan Bridges

    Other Bridges Essential Bridges Critical Bridges

    Regular Irregular Regular Irregular Regular Irregular

    1-3

    4

     No Seismic Analysis

    Seismic Analysis

    *

    SM/UL

    *

    SM

    *

    SM/UL

    *

    MM

    *

    MM

    *

    MM

    Table 2-14 Minimum Analysis Requirements for Seismic Effectsin which:

    * = no seismic analysis required (Zone 1-3)

    UL = uniform load elastic method

    SM = single-mode elastic methodMM = multimode elastic method

    2.12 LOAD FACTORS AND COMBINATIONS 

    G ENERAL 

    The total factored force effect: Q = ii Qi  ----------- Equation 2.4

    where:

    i= load modifier (a factor relating to ductility, redundancy and operationalimportance)

    Qi = force effects from loads specified herein

    i = load factors

    Ductility, redundancy, and operational importance are significant aspects affecting themargin of safety of bridges. Whereas the first two directly relate to physical strength, the

    last concerns the consequences of the bridge being out of service.

    D UCTILITY  

    The response of structural components or connections beyond the elastic limit can be

    characterized by either brittle or ductile behavior. Under repeated seismic loading, large

  • 8/17/2019 CHAPTER 2 Bridge Loads

    19/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 19

    reversed cycles of inelastic deformation dissipate energy and have a beneficial effect on

    structural survival.

    If, by means of confinement or other measures, a structural component or connection

    made of brittle materials can sustain inelastic deformations without significant loss ofload-carrying capacity, this component can be considered ductile. Such ductile

     performance shall be verified by testing.

    The structural system of a bridge shall be proportioned and detailed to ensure thedevelopment of significant and visible inelastic deformations at the strength and extreme

    event limit states prior to failure.

    For the strength limit state, the ductility factor

    D   1.05 for non-ductile components and connections

    D  = 1.00 for conventional designs and details complying with these

    Specifications

    D ≤ 0.95 for components and connections for which additional ductility-enhancing measures have been specified beyond those required by these

    SpecificationsFor all other limit states:

    D = 1.00

    R EDUNDANCY  

    Main elements and components whose failure is expected to cause the collapse of the

     bridge shall be designated as failure-critical and the associated structural system as non-

    redundant. Alternatively, failure-critical members in tension shall be designated fracture-critical.

    Those elements and components whose failure is not expected to cause collapse of the

     bridge shall be designated as non-failure-critical and the associated structural system asredundant.

    For the strength limit state:

    R     1.05 for non-redundant members= 1.00 for conventional levels of redundancy

      0.95 for exceptional levels of redundancyFor all other limit states:

    R   = 1.00For each load combination and limit state under consideration, member redundancyclassification (redundant or non-redundant) should be based upon the member

    contribution to the bridge safety.

    O PERATIONAL I MPORTANCE  

    This definition shall apply to the strength and extreme event limit states only. Some

     bridges or structural components and connections shall be declared to be of operational

    importance.Such classification should be based on social/survival and/or security/defense

    requirements.

    Three levels of importance are specified with respect to seismic design: "critical,"

    "essential," and "other." Bridges classified as "critical" or "essential" should beconsidered of "operational importance."

  • 8/17/2019 CHAPTER 2 Bridge Loads

    20/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 20

    For the strength limit state:

    l    1.05 for important bridges= 1.00 for typical bridges

      0.95 for relatively less important bridges

    For all other limit states:

    l  = 1.00

    2.12 LIMIT STATES

    S TRENGTH L IM IT S TATE  

    The strength limit state shall be taken to ensure that strength and stability, both local and

    global, are provided to resist the specified statistically significant load combinations that

    a bridge is expected to experience in its design life.Extensive distress and structural damage may occur under strength limit state, but overall

    structural integrity is expected to be maintained.

    E XTREME E VENT L IM IT S TATES  

    The extreme event limit state shall be taken to ensure the structural survival of a bridge

    during a major earthquake or flood, possibly under scoured conditions.

    Extreme event limit states are considered to be unique occurrences whose return periodshall be significantly greater than the design life of the bridge.

    S ERVICE L IM IT S TATE  

    The service limit state shall be taken as restrictions on stress, deformation, and crack

    width under regular service conditions. The service limit state provides certain experience

    related provisions that cannot always be derived solely from strength or statisticalconsiderations.

    F ATIGUE AND F RACTURE L IM IT S TATE  

    The fatigue limit state shall be taken as restrictions on stress range as a result of a single

    design truck occurring at the number of expected stress range cycles.

    The fatigue limit state is intended to limit crack growth under repetitive loads to prevent

    fracture during the design life of the bridge.

    The fracture limit state shall be taken as a set of material toughness requirements of the

    Technical Specifications.

    Limit States

    STRENGTH I Basic load combination relating to the normal vehicular use of the bridge without wind.

    STRENGTH II Load combination relating to the use of the bridge by ERA-specified special design or permit vehicles, without wind.

    STRENGTH III Load combination relating to the bridge exposed to wind velocity exceeding 90 km/h.

    STRENGTH IV Load combination relating to very high dead load to live load force effect ratios.

    STRENGTH V Load combination relating to normal vehicular use of the bridge with wind of 90 km/h(25 m/s) velocity

    EXTREME Load combination including earthquake

  • 8/17/2019 CHAPTER 2 Bridge Loads

    21/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 21

    EVENT

    SERVICE I Load combination relating to the normal operational use of the bridge with a 90 km/h(25 m/s) wind and all loads taken at their nominal values. Also related to deflection

    control in buried metal structures, tunnel liner plate, and thermoplastic pipe and to

    control crack width in reinforced concrete structures. This load combination should also

     be used for the investigation of slope stability.

    Compression in prestressed concrete components is investigated using this loadcombination. Service III is used to investigate tensile stresses in prestressed concrete

    components.

    SERVICE II Load combination intended to control yielding of steel structures and slip of slip-critical connections due to vehicular live load.

    This load combination corresponds to the overload provision for steel structures, and it

    is applicable only to steel structures. From the point of view of load level, this

    combination is approximately halfway between that used for Service I and Strength I

    Limit States.

    SERVICE III Load combination relating only to tension in prestressed concrete structures with theobjective of crack control.

    FATIGUE Fatigue and fracture load combination relating to repetitive gravitational vehicular liveload and dynamic responses under a single design truck having a constant axle spacingof 9.0 m between 145 kN axles.

    The load factor, applied to a single design truck, reflects a load level found to be

    representative of the truck population with respect to a large number of return cycles of

    stresses and to their cumulative effects in steel elements, components, and connections.

    The load factors for various loads comprising a design load combination shall be taken as

    specified in the following table. All relevant subsets of the load combinations shall be

    investigated. For each load combination, every load that is indicated to be taken into

    account and that is germane to the component being designed, including all significant

    effects due to distortion, shall be multiplied by the appropriate load factor and multiple presence factor, if applicable. The products shall be summed as specified in Equation 3.4

    and multiplied by the load modifiers.

    The factors shall be selected to produce the total extreme factored force effect. For each

    load combination, both positive and negative extremes shall be investigated.

    In load combinations where one force effect decreases another effect, the minimum value

    shall be applied to the load reducing the force effect. For permanent force effects, the

    load factor that produces the more critical combination shall be selected from thefollowing table. Where the permanent load increases the stability or load-carryingcapacity of a component or bridge, the minimum value of the load factor for that

     permanent load shall also be investigated.

    The larger of the two values provided for load factors of Uniform Temperature (TU),

    Creep (CR), and Shrinkage (SH) shall be used for deformations and the smaller values

    for all other effects.

  • 8/17/2019 CHAPTER 2 Bridge Loads

    22/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

     Fundamentals of bridge design –  Chapter 2 22

    In the application of permanent loads, force effects for each of the specified six load

    types should be computed separately. It is unnecessary to assume that one type of load

    varies by span, length, or component within a bridge.

    LoadCombination

    Limit State

    DCDD

    DWEH

    EVES

    LLIM

    CEBR

    PLLSEL

    WA WS WL FR TUCR

    SH

    TG SE Use one ofthese at a

    time

    EQ CT

    STRENGTH 1

    (Unless noted) p  1.75 1.00 - - 1.00 0.50/1.20 TG  SE  - -

    STRENGTH II  p  1.35 1.00 - - 1.00 0.50/1.20 TG  SE  - -

    STRENGTH III  p  - 1.00 1.40 - 1.00 0.50/1.20 TG  SE  - -

    STRENGTH IV

    EH, EV, ES, DWDC ONLY

     p 1.5

    - 1.00 - - 1.00 0.50/1.20- -

    - -

    STRENGTH V  p  1.35 1.00 0.50 1.0 1.00 0.50/1.20 TG  SE  - -EXTREME

    EVENT p  EQ  1.00 - - 1.00 - - - 1.0

    0-

    SERVICE I 1.00 1.00 1.00 0.30 1.0 1.00 1.00/1.20 TG  SE  - -

    SERVICE II 1.00 1.30 1.00 - - 1.00 1.00/1.20 - - - -

    SERVICE III 1.00 0.80 1.00 - - 1.00 1.00/1.20 TG  SE  - -

    FATIGUE

    LL, IM and CEONLY

    - 0.75 - - - - - - - - -

    Where (see following text):

    BR = vehicular braking forceCE = vehicular centrifugal force

    CR = creepCT = vehicular collision forceDC = dead load of structural componentsDD = downdragDW = dead load of wearing surfaces and utilities

    EH = horizontal earth pressure loadEL = accumulated locked-in effects resulting

    from the construction processEQ = earthquake loadES = earth surcharge load

    EV = vertical pressure from dead load of earth fill

    FR = frictionIM = vehicular dynamic load allowance

    LL = vehicular live loadLS = live load surchargePL = pedestrian live loadSE = settlementSH = shrinkage

    TG = temperature gradientTU = uniform temperatureWA = water load and stream pressureWL = wind on live loadWS = wind load on structure

    Load Combinations and Load Factors

    Consider the investigation of uplift. Where a permanent load produces uplift, that loadwould be multiplied by the maximum load factor, regardless of the span in which it islocated. If another permanent load reduces the uplift, it would be multiplied by the

    minimum load factor, regardless of the span in which it is located. For example, at

  • 8/17/2019 CHAPTER 2 Bridge Loads

    23/23

     Dept. of Civil Eng., T. F., Hawassa University 

     _____________________________________________________________________________

    Fundamentals of bridge design – Chapter 223

    Strength I Limit State where the permanent load reaction is positive and live load can

    cause a negative reaction, the load combination would be:

    0.9DC + 0.65DW + 1.75(LL+IM)

    If both reactions were negative, the load combination would be:

    1.25DC + 1.50DW + 1.75(LL+IM).

    Type of Load Load Factor ( p)

    Maximum Minimum

    DC: Component and Attachments 1.25 0.90

    DD: Downdrag 1.80 0.45

    DW: Wearing Surfaces and Utilities 1.50 0.65

    EH: Horizontal Earth Pressure

      Active

      At-Rest

    1.50

    1.35

    0.90

    0.90

    EL: Locked-in Erection Stresses 1.0 1.0EV: Vertical Earth Pressure

      Overall Stability

      Retaining Structure

      Rigid Buried Structure

      Rigid Frames

      Flexible Buried Structures other thanMetal Box Culvert

      Flexible Metal Box Culverts

    1.35

    1.351.30

    1.35

    1.95

    1.50

     N/A

    1.000.90

    0.90

    0.90

    0.90

    ES: Earth Surcharge 1.50 0.75

    Load Factors for Permanent Loads, p 

    For each force effect, both extreme combinations may need to be investigated by

    applying either the high or the low load factor as appropriate. The algebraic sums of these

     products are the total force effects for which the bridge and its components should bedesigned.

    LOAD F ACTORS FOR C ONSTRUCTION LOADS  

    Load factors for the weight of the structure and appurtenances shall not be taken to be

    less than 1.25.

    Unless otherwise specified by ERA, the load factor for construction loads, for equipmentand for dynamic effects shall not be less than 1.5. The load factor for wind shall not be

    less than 1.25. All other load factors shall be taken as 1.0.The load factors presented here should not relieve the contractor of responsibility forsafety and damage control during construction.