CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL 1901.1 Scope. The provisions of this chapter shall govern the materials, quality control, design and construction of concrete used in structures. 1901.2 Plain and reinforced concrete. Structural concrete shall be designed and constructed in accordance with the requirements of this chapter and ACI 318 as amended in Sec- tion 1908 of this code. Except for the provisions of Sections 1904 and 1911, the design and construction of slabs on grade shall not be governed by this chapter unless they transmit verti- cal loads or lateral forces from other parts of the structure to the soil. 1901.3 Source and applicability. Sections 1902 through 1907 of this chapter are derived from the provisions for structural concrete in ACI 318. Where sections within Chapters 2 through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions of Sections 1902 through 1907 of this code shall apply. 1901.4 Construction documents. The construction docu- ments for structural concrete construction shall include: 1. Specified compressive strength of concrete at the stated ages or stages of construction for which each concrete element is designed. 2. Specified strength or grade of reinforcement. 3. Size and location of structural elements, reinforcement, and anchors. 4. Provision for dimensional changes resulting from creep, shrinkage and temperature. 5. Magnitude and location of prestressing forces. 6. Anchorage length of reinforcement and location and length of lap splices. 7. Type and location of mechanical and welded splices of reinforcement. 8. Details and location of contraction or isolation joints specified for plain concrete. 9. Minimum concrete compressive strength at time of posttensioning. 10. Stressing sequence for posttensioning tendons. 11. For structures assigned to Seismic Design Category D, a statement if slab on grade is designed as a structural diaphragm (see Section 21.10.3.4 of ACI 318). 12. Freezing and thawing and deicing chemical exposure classifications (see Section 1904.2). 13. Sulfate exposure classification (see Section 1904.3). 14. Maximum water soluble chloride ion (CI) concentra- tions (see Section 1904.4). 1901.5 Special inspection. The special inspection of concrete elements of buildings and structures and concreting operations shall be in accordance with Chapter 17. SECTION BC 1902 DEFINITIONS 1902.1 General. The following words and terms shall have the meanings shown herein. ADMIXTURE. Material other than water, aggregate or hydraulic cement, used as an ingredient of concrete and added to concrete before or during its mixing to modify its properties. AGGREGATE. Granular material, such as sand, gravel, crushed stone and iron blast-furnace slag, used with a cement- ing medium to form a hydraulic cement concrete or mortar. AGGREGATE, LIGHTWEIGHT. Aggregate with a dry, loose weight of 70 pounds per cubic foot (pcf) (1120 kg/m 3 ) or less. CEMENTITIOUS MATERIALS. Materials as specified in Section 1903 that have cementing value when used in concrete either by themselves, such as portland cement, blended hydraulic cements and expansive cement, or such materials in combination with fly ash, other raw or calcined natural pozzolans, silica fume, and/or ground granulated blast-furnace slag. COLUMN. A member with a ratio of height-to-least-lateral dimension exceeding three, used primarily to support axial compressive load. CONCRETE. A mixture of portland cement or any other hydraulic cement, fine aggregate, coarse aggregate and water, with or without admixtures. CONCRETE, SPECIFIED COMPRESSIVE STRENGTH OF, (f' c ). The compressive strength of concrete used in design and evaluated in accordance with the provisions of Section 1905, expressed in pounds per square inch (psi) (MPa). Whenever the quantity f' c is under a radical sign, the square root of the numerical value only is intended, and the result has units of psi (MPa). CONTRACTION JOINT. Formed, sawed or tooled groove in a concrete structure to create a weakened plane and regulate the location of cracking resulting from the dimensional change of different parts of the structure. DEFORMED REINFORCEMENT. Deformed reinforcing bars, bar mats, deformed wire, welded plain wire fabric and welded deformed wire fabric conforming to ACI 318, Section 3.5.3. DUCT. A conduit (plain or corrugated) to accommodate prestressing steel for postensioned installation. 2008 NEW YORK CITY BUILDING CODE 403

Transcript of CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through...

Page 1: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

CHAPTER 19

CONCRETE

SECTION BC 1901GENERAL

1901.1 Scope. The provisions of this chapter shall govern thematerials, quality control, design and construction of concreteused in structures.

1901.2 Plain and reinforced concrete. Structural concreteshall be designed and constructed in accordance with therequirements of this chapter and ACI 318 as amended in Sec-tion 1908 of this code. Except for the provisions of Sections1904 and 1911, the design and construction of slabs on gradeshall not be governed by this chapter unless they transmit verti-cal loads or lateral forces from other parts of the structure to thesoil.

1901.3 Source and applicability. Sections 1902 through 1907of this chapter are derived from the provisions for structuralconcrete in ACI 318. Where sections within Chapters 2through 7 of ACI 318 are referenced in other chapters andappendices of ACI 318, the provisions of Sections 1902through 1907 of this code shall apply.

1901.4 Construction documents. The construction docu-ments for structural concrete construction shall include:

1. Specified compressive strength of concrete at the statedages or stages of construction for which each concreteelement is designed.

2. Specified strength or grade of reinforcement.

3. Size and location of structural elements, reinforcement,and anchors.

4. Provision for dimensional changes resulting fromcreep, shrinkage and temperature.

5. Magnitude and location of prestressing forces.

6. Anchorage length of reinforcement and location andlength of lap splices.

7. Type and location of mechanical and welded splices ofreinforcement.

8. Details and location of contraction or isolation jointsspecified for plain concrete.

9. Minimum concrete compressive strength at time ofposttensioning.

10. Stressing sequence for posttensioning tendons.

11. For structures assigned to Seismic Design Category D,a statement if slab on grade is designed as a structuraldiaphragm (see Section 21.10.3.4 of ACI 318).

12. Freezing and thawing and deicing chemical exposureclassifications (see Section 1904.2).

13. Sulfate exposure classification (see Section 1904.3).

14. Maximum water soluble chloride ion (CI) concentra-tions (see Section 1904.4).

1901.5 Special inspection. The special inspection of concreteelements of buildings and structures and concreting operationsshall be in accordance with Chapter 17.

SECTION BC 1902DEFINITIONS

1902.1 General. The following words and terms shall have themeanings shown herein.

ADMIXTURE. Material other than water, aggregate orhydraulic cement, used as an ingredient of concrete and addedto concrete before or during its mixing to modify its properties.

AGGREGATE. Granular material, such as sand, gravel,crushed stone and iron blast-furnace slag, used with a cement-ing medium to form a hydraulic cement concrete or mortar.

AGGREGATE, LIGHTWEIGHT. Aggregate with a dry,loose weight of 70 pounds per cubic foot (pcf) (1120 kg/m3) orless.

CEMENTITIOUS MATERIALS. Materials as specified inSection 1903 that have cementing value when used in concreteeither by themselves, such as portland cement, blendedhydraulic cements and expansive cement, or such materials incombination with fly ash, other raw or calcined naturalpozzolans, silica fume, and/or ground granulated blast-furnaceslag.

COLUMN. A member with a ratio of height-to-least-lateraldimension exceeding three, used primarily to support axialcompressive load.

CONCRETE. A mixture of portland cement or any otherhydraulic cement, fine aggregate, coarse aggregate and water,with or without admixtures.

CONCRETE, SPECIFIED COMPRESSIVESTRENGTH OF, (f 'c). The compressive strength of concreteused in design and evaluated in accordance with the provisionsof Section 1905, expressed in pounds per square inch (psi)(MPa). Whenever the quantity f 'c is under a radical sign, thesquare root of the numerical value only is intended, and theresult has units of psi (MPa).

CONTRACTION JOINT. Formed, sawed or tooled groove ina concrete structure to create a weakened plane and regulate thelocation of cracking resulting from the dimensional change ofdifferent parts of the structure.

DEFORMED REINFORCEMENT. Deformed reinforcingbars, bar mats, deformed wire, welded plain wire fabric andwelded deformed wire fabric conforming to ACI 318, Section3.5.3.

DUCT. A conduit (plain or corrugated) to accommodateprestressing steel for postensioned installation.

2008 NEW YORK CITY BUILDING CODE 403

119_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:10:57 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 2: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

EFFECTIVE DEPTH OF SECTION (d). The distance mea-sured from extreme compression fiber to the centroid of ten-sion reinforcement.

ISOLATION JOINT. A separation between adjoining parts ofa concrete structure, usually a vertical plane, at a designed loca-tion such as to interfere least with performance of the structure,yet to allow relative movement in three directions and avoidformation of cracks elsewhere in the concrete and throughwhich all or part of the bonded reinforcement is interrupted.

PEDESTAL. An upright compression member with a ratio ofunsupported height-to-average-least-lateral dimension of threeor less.

PLAIN CONCRETE. Structural concrete with no reinforce-ment or with less reinforcement than the minimum amountspecified for reinforced concrete.

PLAIN REINFORCEMENT. Reinforcement that does notconform to the definition of "Deformed reinforcement" (seeACI 318, Section 3.5.4).

POSTTENSIONING. Method of prestressing in whichprestressing steel is tensioned after concrete has hardened.

PRECAST CONCRETE. A structural concrete element castelsewhere than its final position in the structure.

PRESTRESSED CONCRETE. Structural concrete in whichinternal stresses have been introduced to reduce potential ten-sile stresses in concrete resulting from loads.

PRESTRESSING STEEL. High-strength steel element suchas wire, bar or strand, or a bundle of such elements, used toimpart prestress forces to concrete.

PRETENSIONING. Method of prestressing in whichprestressing steel is tensioned before concrete is placed.

REINFORCED CONCRETE. Structural concrete rein-forced with no less than the minimum amounts of prestressingsteel or nonprestressed reinforcement specified in ACI 318,Chapters 1 through 21 and ACI 318 Appendices A through C.

REINFORCEMENT. Material that conforms to Section1903.5, excluding prestressing steel unless specificallyincluded.

RESHORES. Shores placed snugly under a concrete slab orother structural member after the original forms and shoreshave been removed from a larger area, thus requiring the newslab or structural member to deflect and support its own weightand existing construction loads applied prior to the installationof the reshores.

SHORES. Vertical or inclined support members designed tocarry the weight of the formwork, concrete and constructionloads above.

SPIRAL REINFORCEMENT. Continuously wound rein-forcement in the form of a cylindrical helix.

STRIPPING OPERATIONS. Removal on the floor of anyparts of the concrete formwork, including shoring, bracing andother supports.

STIRRUP. Reinforcement used to resist shear and torsionstresses in a structural member; typically bars, wires or weldedwire fabric (plain or deformed) either single leg or bent into L,

U or rectangular shapes and located perpendicular, or at anangle to, longitudinal reinforcement. (The term "stirrups" isusually applied to lateral reinforcement in flexural membersand the term "ties" to those in compression members.)

STRUCTURAL CONCRETE. Concrete used for structuralpurposes, including plain and reinforced concrete.

TENDON. In pretensioning applications, the tendon is theprestressing steel. In posttensioned applications, the tendon is acomplete assembly consisting of anchorages, prestressing steeland sheathing with coating for unbonded applications or ductswith grout for bonded applications.

SECTION BC 1903SPECIFICATIONS FOR TESTS AND MATERIALS

1903.1 General. Materials used to produce concrete and test-ing thereof shall comply with the applicable standards listed inACI 318 and this section. Tests of concrete and the materialsused in concrete shall be in accordance with ACI 318, Section3.8. Where required, special inspections and tests shall be inaccordance with Chapter 17.

1903.2 Cement. Cement used to produce concrete shall com-ply with ACI 318, Section 3.2.

1903.3 Aggregates. Aggregates used in concrete shall complywith ACI 318, Section 3.3.

1903.4 Water. Water used in mixing concrete shall be cleanand free from injurious amounts of oils, acids, alkalis, salts,organic materials or other substances that are deleterious toconcrete or steel reinforcement and shall comply with ACI 318,Section 3.4.

1903.5 Steel reinforcement. Reinforcement and welding ofreinforcement to be placed in concrete construction shall con-form to the requirements of this section.

1903.5.1 Reinforcement type. Reinforcement shall bedeformed reinforcement, except plain reinforcement ispermitted for spirals or prestressing steel, and reinforce-ment consisting of structural steel, steel pipe or steel tub-ing is permitted where specified in ACI 318.Reinforcement shall comply with ACI 318, Section 3.5.

1903.5.2 Welding. Welding of reinforcing bars shallconform to AWS D1.4. Type and location of weldedsplices and other required welding of reinforcing barsshall be indicated on the construction documents or inthe project specifications. The ASTM reinforcing barspecifications, except for ASTM A 706, shall be supple-mented to require a report of material properties neces-sary to conform to the requirements in AWS D1.4. Awritten welding procedure shall be provided to the regis-tered design professional of record for approval prior toany welding. All welding shall be subject to specialinspection by an approved agency.

1903.6 Admixtures. Admixtures to be used in concrete shallbe subject to prior approval by the registered design profes-sional of record and shall comply with ACI 318, Section 3.6.

404 2008 NEW YORK CITY BUILDING CODE

CONCRETE

219_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:10:58 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 3: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

1903.7 Storage of materials. The storage of materials for usein concrete shall comply with the provisions of Sections1903.7.1 and 1903.7.2.

1903.7.1 Manner of storage. Cementitious materials andaggregates shall be stored in such a manner as to preventdeterioration or intrusion of foreign matter.

1903.7.2 Unacceptable material. Any material that hasdeteriorated or has been contaminated shall not be used forconcrete.

1903.8 Glass fiber reinforced concrete. Glass fiber rein-forced concrete (GFRC) and the materials used in such con-crete shall be in accordance with the PCI MNL 128 standard.

SECTION BC 1904DURABILITY REQUIREMENTS

1904.1 Water-cementitious materials ratio. Thewater-cementitious materials ratios specified in Tables1904.2.2 and 1904.3 shall be calculated using the weight ofcement meeting ASTM C 150, ASTM C 595, ASTM C 845 orASTM C 1157, plus the weight of fly ash and other pozzolansmeeting ASTM C 618, slag meeting ASTM C 989 and silicafume meeting ASTM C 1240, if any, except that where con-crete is exposed to deicing chemicals, Section 1904.2.3 furtherlimits the amount of fly ash, pozzolans, silica fume, slag or thecombination of these materials.

1904.2 Freezing and thawing exposures. Concrete that willbe exposed to freezing and thawing or deicing chemicals shallcomply with Sections 1904.2.1 through 1904.2.3.

1904.2.1 Air entrainment. Normal-weight and lightweightconcrete exposed to freezing and thawing or deicing chemi-cals shall be air entrained in accordance with Table1904.2.1. Tolerance of air content as delivered shall be ± 1.5percent. For specified compressive strength (f ' c) greaterthan 5,000 psi (34.47 MPa), reduction of air content indi-cated in Table 1904.2.1 by 1.0 percent is permitted.

1904.2.2 Concrete properties. Concrete that will be sub-ject to the exposures given in Table 1904.2.2(1) shall con-form to the corresponding maximum water-cementitiousmaterials ratios and minimum specified concrete compres-sive strength requirements of that table. In addition, con-crete that will be exposed to deicing chemicals shallconform to Section 1904.2.3.

Exception: For Group R and accessory occupancies thatare in buildings less than four stories in height, nor-mal-weight aggregate concrete that is subject to freezingand thawing or deicer chemicals shall comply with therequirements of Table 1904.2.2(2).

1904.2.3 Deicing chemicals. For concrete exposed todeicing chemicals, the maximum weight of fly ash, otherpozzolans, silica fume or slag that is included in the concreteshall not exceed the percentages of the total weight ofcementitious materials given in Table 1904.2.3.

1904.3 Sulfate exposures. Where concrete will be exposed tosulfate-containing solutions, it shall comply with the provi-sions of Sections 1904.3.1 and 1904.3.2.

1904.3.1 Concrete quality. Concrete to be exposed to sul-fate-containing solutions or soils shall conform to therequirements of Table 1904.3 or shall be concrete made witha cement that provides sulfate resistance and that has a max-imum water-cementitious materials ratio and minimumcompressive strength as set forth in Table 1904.3.

1904.3.2 Calcium chloride. Calcium chloride as an admix-ture shall not be used in concrete to be exposed to thosesevere or very severe sulfate-containing solutions defined inTable 1904.3.

1904.4 Corrosion protection of reinforcement. Reinforce-ment in concrete shall be protected from corrosion and expo-sure to chlorides as provided by Sections 1904.4.1 and1904.4.2.

1904.4.1 General. For corrosion protection of reinforce-ment in concrete, the maximum water-soluble chloride ionconcentrations in hardened concrete at ages from 28 to 42days contributed from the ingredients including water,aggregates, cementitious materials and admixtures shall notexceed the limits of Table 1904.4.1. When testing is per-formed to determine water-soluble chloride ion content, testprocedures shall conform to ASTM C 1218.

2008 NEW YORK CITY BUILDING CODE 405

CONCRETE

TABLE 1904.2.1TOTAL AIR CONTENT FOR FROST-RESISTANT CONCRETE

NOMINAL MAXIMUMAGGREGATE SIZEa

(inches)

AIR CONTENT (percent)

Severe exposureb Moderate exposureb

3/8 71/2 6

1/2 7 51/2

3/4 6 5

1 6 41/2

11/2 51/2 41/2

2c 5 4

3c 41/2 31/2

For SI: 1 inch = 25.4 mm.a. See ASTM C 33 for tolerance on oversize for various nominal maximum

size designations.b. The severe and moderate exposures referenced in this table are not based on

the weathering regions shown in Figure 1904.2.2. For the purposes of thissection, severe and moderate exposures shall be defined as follows:

1. Severe exposure occurs where concrete will be in almost continuouscontact with moisture prior to freezing, or where deicing salts areused. Examples are pavements, bridge decks, sidewalks, parkinggarages and water tanks.

2. Moderate exposure occurs where concrete will be only occasionallyexposed to moisture prior to freezing, and where deicing salts are notused. Examples are certain exterior walls, beams, girders and slabsnot in direct contact with soil.

c. These air contents apply to total mix, as for the preceding aggregate sizes.When testing these concretes, however, aggregate larger than 11/2 inches isremoved by hand picking or sieving and air content is determined on theminus 11/2-inch fraction of the mix (tolerance on air content as deliveredapplies to this value). Air content of total mix is computed from value deter-mined on the minus 11/2-inch fraction.

319_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:10:58 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 4: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

406 2008 NEW YORK CITY BUILDING CODE

CONCRETE

TABLE 1904.2.2(2)MINIMUM SPECIFIED COMPRESSIVE STRENGTH (f c)

TYPE OR LOCATION OF CONCRETE CONSTRUCTION MINIMUM SPECIFIED COMPRESSIVE STRENGTH (f c at 28 days, psi)

Basement wallsc and foundations not exposed to the weather 2,500a

Basement slabs and interior slabs on grade, except garage floorslabs 2,500a

Basement wallsc, foundation walls, exterior walls and othervertical concrete surfaces exposed to the weather 3,000b

Driveways, curbs, walks, patios, porches, carport slabs, steps andother flatwork exposed to the weather, and garage floor slabs 3,500b

For SI: 1 pound per square inch = 0.00689 MPa.a. Concrete in these locations that can be subjected to freezing and thawing during construction shall be of air-entrained concrete in accordance with Table 1904.2.1.b. Concrete shall be air entrained in accordance with Table 1904.2.1.c. Structural plain concrete basement walls are exempt from the requirements for special exposure conditions of Section 1904.2.2 (see Section 1909.1.1).

TABLE 1904.2.3REQUIREMENTS FOR CONCRETE EXPOSED TO DEICING CHEMICALS

CEMENTITIOUS MATERIALSMAXIMUM PERCENT OF TOTAL CEMENTITIOUS

MATERIALS BY WEIGHTa, b

Fly ash or other pozzolans conforming to ASTM C 618 25

Slag conforming to ASTM C 989 50

Silica fume conforming to ASTM C 1240 10

Total of fly ash or other pozzolans, slag and silica fume 50c

Total of fly ash or other pozzolans and silica fume 35c

a. The total cementitious material also includes ASTM C 150, ASTM C 595, ASTM C 845 and ASTM C 1157 cement.b. The maximum percentages shall include:

1. Fly ash or other pozzolans present in Type IP or I (PM) blended cement, ASTM C 595, or ASTM C 1157.2. Slag used in the manufacture of an IS or I (SM) blended cement, ASTM C 595, or ASTM C 1157.3. Silica fume, ASTM C 1240, present in a blended cement.

c. Fly ash or other pozzolans and silica fume shall constitute no more than 25 and 10 percent, respectively, of the total weight of the cementitious materials.

TABLE 1904.2.2(1)REQUIREMENTS FOR SPECIAL EXPOSURE CONDITIONS

EXPOSURE CONDITION

MAXIMUM WATER-CEMENTITIOUS MATERIALSRATIO, BY WEIGHT, NORMAL-WEIGHT

AGGREGATE CONCRETEMINIMUM f c, NORMAL-WEIGHT AND

LIGHTWEIGHT AGGREGATE CONCRETE (psi)

Concrete intended to have low permeabilitywhen exposed to water 0.50 4,000

Concrete exposed to freezing and thawing ina moist condition or to deicing chemicals 0.45 4,500

For corrosion protection of reinforcement inconcrete exposed to chlorides from deicingchemicals, salt, saltwater, brackish water,seawater or spray from these sources

0.40 5,000

For SI: 1 pound per square inch = 0.00689 MPa.

419_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:10:58 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 5: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

1904.4.2 Exposure to chlorides. Where concrete with rein-forcement will be exposed to chlorides from deicing chemi-cals, salt, saltwater, brackish water, seawater or spray fromthese sources, the requirements of Table 1904.2.2(1) forwater-cementitious materials ratio and concrete strength,and the minimum concrete cover requirements of Section1907.7, shall be satisfied. For corrosion protection ofunbonded tendons compliance with ACI 318, Section 18.16shall be required. The limits on acid-soluble and water-solu-ble chlorides in fresh concrete that contains reinforcing steelor other metals shall conform to the requirements of ACI222, Section 3.2.

SECTION BC 1905CONCRETE QUALITY, MIXING AND PLACING

1905.1 General. The required strength and durability of con-crete shall be governed by compliance with the proportioning,testing, mixing and placing provisions of Sections 1905.1.1through 1905.13.

1905.1.1 Strength. Concrete shall be proportioned to pro-vide an average compressive strength in accordance withSection 1905.3, and shall satisfy the durability criteria ofSection 1904. Concrete shall be produced to minimize thefrequency of strengths below f ' c in compliance with Section1905.6.3.3. For concrete designed and constructed in accor-dance with this chapter, f ' c shall not be less than 2,500 psi(17.22 MPa). No maximum specified compressive strengthshall apply unless restricted by a specific provision of thiscode or ACI 318.

1905.1.2 Cylinder tests. Requirements for f ' c shall bebased on tests of cylinders made and tested in accordancewith Section 1905.6.3.

1905.1.3 Basis of f ' c . Unless otherwise specified, f ' c shallbe based on 28-day tests. If other than 28 days, test age for f'cshall be as indicated in construction documents. If at anytime during the concrete operations, the concrete is not inconformance with ASTM C 94 or is otherwise compro-mised, it shall be rejected. If it is placed, the location of theload shall be recorded and a pair of cylinders shall be

2008 NEW YORK CITY BUILDING CODE 407

CONCRETE

TABLE 1904.4.1MAXIMUM CHLORIDE ION CONTENT FOR CORROSION PROTECTION OF REINFORCEMENT

TYPE OF MEMBERMAXIMUM WATER SOLUBLE CHLORIDE ION (CI)

IN CONCRETE, PERCENT BY WEIGHT OF CEMENT

Prestressed concrete 0.06

Reinforced concrete exposed to chloride in service 0.15

Reinforced concrete that will be dry or protected from moisture in service 1.00

Other reinforced concrete construction 0.30

TABLE 1904.3REQUIREMENTS FOR CONCRETE EXPOSED TO SULFATE-CONTAINING SOLUTIONS

SULFATEEXPOSURE

WATER SOLUBLESULFATE (SO4) INSOIL, PERCENT

BY WEIGHT

SULFATE (SO4)IN WATER

(ppm)

CEMENT TYPE

MAXIMUMWATER-CEMENTITIOUS

MATERIALS RATIO,BY WEIGHT,

NORMAL-WEIGHTAGGREGATECONCRETEa

MINIMUM f cNORMAL-WEIGHT

AND LIGHTWEIGHTAGGREGATE

CONCRETE (psi)a

ASTMC 150

ASTMC 595

ASTMC 1157

Negligible 0.00 - 0.10 0 - 150 ⎯ ⎯ ⎯ ⎯ ⎯

Moderateb 0.10 - 0.20 150 - 1,500 II

II, IP (MS),IS (MS), P (MS),

I (PM)(MS),I (SM)(MS)

MS 0.50 4,000

Severe 0.20 - 2.00 1,500 - 10,000 V ⎯ HS 0.45 4,500

Very severe Over 2.00 Over 10,000 V pluspozzolanc ⎯ HS plus

pozzoland 0.45 4,500

For SI: 1 pound per square inch = 0.00689 MPa.a. A lower water-cementitious materials ratio or higher strength may be required for low permeability or for protection against corrosion of embedded items or freez-

ing and thawing (see Table 1904.2.2).b. Seawater.c. Pozzolan that has been determined by test or service record to improve sulfate resistance when used in concrete containing Type V cement.d. Pozzolan that has been determined by test or service record to improve sulfate resistance when used in concrete containing Type HS blended cement.

519_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:10:58 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 6: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

molded from the load per ASTM C 31 and included in theaverage f' c.

1905.1.4 Lightweight aggregate concrete. Where designcriteria in ACI 318, Sections 9.5.2.3, 11.2 and 12.2.4, pro-vide for use of a splitting tensile strength value of concrete (fct), laboratory tests shall be made in accordance with ASTMC 330 to establish the value of f ct corresponding to the spec-ified value of f ' c.

1905.1.5 Field acceptance. Splitting tensile strength testsshall not be used as a basis for field acceptance of concrete.

1905.2 Selection of concrete proportions. Concrete propor-tions shall be determined in accordance with the provisions ofSections 1905.2.1 through 1905.2.3.

1905.2.1 General. Proportions of materials for concreteshall be established to provide:

1. Workability and consistency to permit concrete to beworked readily into forms and around reinforcementunder the conditions of placement to be employed,without segregation or excessive bleeding.

2. Resistance to special exposures as required by Sec-tion 1904.

3. Conformance with the strength test requirements ofSection 1905.6.

1905.2.2 Different materials. Where different materialsare to be used for different portions of proposed work, eachcombination shall be evaluated.

1905.2.3 Basis of proportions. Concrete proportions shallbe established in accordance with Section 1905.3 or Section1905.4, and shall comply with the applicable requirementsof Section 1904.

1905.3 Proportioning on the basis of field experienceand/or trial mixtures. Concrete proportioning determined onthe basis of field experience or trial mixtures shall be done inaccordance with ACI 318, Section 5.3. If the required f' c isobtained for trial batch mixes prior to the date specified, thetrial mix design may be approved. All mixes shall be approvedby the registered design professional of record. prior to con-struction.

1905.4 Proportioning without field experience or trial mix-tures. Concrete proportioning determined without field expe-rience or trial mixtures shall be done in accordance with ACI318, Section 5.4. This method of proportioning shall not bepermitted for load-carrying structural concrete or concrete mixproportions that are required to conform with Section 1904.

1905.5 Average strength reduction. As data become avail-able during construction, it is permissible to reduce the amountby which the average compressive strength (f ' c) is required toexceed the specified value of f ' c in accordance with ACI 318,Section 5.5.

1905.6 Evaluation and acceptance of concrete. The criteriafor evaluation and acceptance of concrete shall be as specifiedin Sections 1905.6.2 through 1905.6.5.5.

1905.6.1 Qualified technicians. Concrete shall be tested inaccordance with the requirements in Sections 1905.6.2through 1905.6.5. An approved agency shall perform tests

on fresh concrete at the job site, prepare specimens requiredfor curing under field conditions, prepare specimensrequired for testing in the laboratory and record the temper-ature of the fresh concrete when preparing specimens forstrength tests. All field sampling and testing, including thetesting of aggregates, concrete mixes, and strength testingof specimens, shall be subject to special inspection by anapproved agency. All testing laboratories shall be approvedtesting agencies and shall employ qualified special inspec-tors to perform all required laboratory tests. Test resultsshall be promptly distributed by the testing laboratory to theregistered design professional of record, concrete producer,owner and contractor.

1905.6.2 Frequency of testing. The frequency of conduct-ing strength tests of concrete shall be as specified in Sec-tions 1905.6.2.1 through 1905.6.2.4.

1905.6.2.1 Minimum frequency. Samples for strengthtests of each class of concrete placed each day shall betaken not less than once a day, nor less than once for each50 cubic yards (38 m3) of concrete nor less than once foreach 5,000 square feet (465 m2) of surface area for slabsor walls. For concrete mixes proportioned for durabilityrequirements specified in Section 1904, the registereddesign professional of record shall specify additionalfield testing of the concrete for unit weight, air and watercontent. At the discretion of the registered design profes-sional of record, the frequency of testing may bereduced, but not less than once for each 150 cubic yards(115 m3).

1905.6.2.2 Minimum number. On a given project, if thetotal volume of concrete is such that the frequency oftesting required by Section 1905.6.2.1 would provideless than five strength tests for a given class of concrete,tests shall be made from at least five randomly selectedbatches or from each batch if fewer than five batches areused.

1905.6.2.3 Small volume. When the total volume of agiven class of concrete is less than 50 cubic yards (38m3), and the concrete is nonstructural and is not subject tothe durability requirements of Section 1904, testing maybe waived by the registered design professional ofrecord.

1905.6.2.4 Strength test. A strength test shall be theaverage of the strengths of two cylinders made from thesame sample of concrete and tested at 28 days or at thetest age designated for the determination of f ' c. Consid-eration shall be given specifying an f ' c at 56 days or laterfor concrete utilizing pozzolans in the mix proportions.At the discretion of the registered design professional ofrecord or the approved agency performing the testing,additional pairs of test cylinders may be taken at the timeof sampling for testing at a later date. The additional cyl-inders may be tested at a later date should the strength atthe specified date not meet the required f ' c.

1905.6.3 Laboratory-cured specimens. Laboratory-curedspecimens shall comply with the provisions of Sections1905.6.3.1 through 1905.6.3.4.

408 2008 NEW YORK CITY BUILDING CODE

CONCRETE

619_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:10:59 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 7: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

1905.6.3.1 Sampling. Samples for strength tests shall betaken in accordance with ASTM C 172.

1905.6.3.2 Cylinders. Cylinders for strength tests shallbe molded and laboratory-cured in accordance withASTM C 31. The contractor shall be responsible for pro-viding the specified field storage curing facility and formonitoring the temperature as defined in ASTM C 31.The cylinders shall be tested in accordance with ASTMC 39.

1905.6.3.3 Acceptance of results. The strength level ofan individual class of concrete shall be considered satis-factory if both of the following requirements are met:

1. Every arithmetic average of any three consecutivestrength tests equals or exceeds f ' c.

2. No individual strength test (average of two cylin-ders) falls below f ' c by more than 500 psi (3.45MPa) when f ' c is 5,000 psi (34.50 MPa) or less, orby more than 0.10 f ' c when f ' c is more than 5,000psi (34.50 MPa).

1905.6.3.4 Correction. If either of the requirements ofSection 1905.6.3.3 is not met, steps shall be taken toincrease the average of subsequent strength test results.The requirements of Section 1905.6.5 shall govern if therequirement of Section 1905.6.3.3, Item 2‡, is not met.

1905.6.4 Field-cured specimens. Field-cured specimensshall comply with the provisions of Sections 1905.6.4.1through 1905.6.4.4.

1905.6.4.1 When required. Where required by the com-missioner, the results of strength tests of cylinders curedunder field conditions shall be provided to the depart-ment.

1905.6.4.2 Curing. Field-cured cylinders shall be curedunder field conditions in accordance with ASTM C 31.

1905.6.4.3 Sampling. Field-cured test cylinders shall bemolded at the same time and from the same samples aslaboratory-cured test cylinders.

1905.6.4.4 Correction. Procedures for protecting andcuring concrete shall be improved when the strength offield-cured cylinders at the test age designated for deter-mination of f ' c is less than 85 percent of that of compan-ion laboratory-cured cylinders. The 85-percentlimitation shall not apply if the field-cured strengthexceeds f ' c by more than 500 psi (3.45 MPa).

1905.6.5 Low-strength test results. The investigation oflow-strength test results shall be in accordance with the pro-visions of Sections 1905.6.5.1 through 1905.6.5.5.

1905.6.5.1 Precaution. If any strength test of labora-tory-cured cylinders performed in accordance with Sec-tion 1905.6.2.4 falls below the specified value of f' c bymore than the values given in Section 1905.6.3.3, Item2‡, or if tests of field-cured cylinders performed inaccordance with Section 1905.6.4.4 indicate deficien-cies in protection and curing, steps shall be taken toassure that the load-carrying capacity of the structure isnot jeopardized.

1905.6.5.2 Core tests. Where calculations indicate thatload-carrying capacity is significantly reduced, tests ofcores drilled from the area in question in accordance withASTM C 42 shall be permitted. In such cases, three coresshall be taken for each strength test that falls below thevalues given in Section 1905.6.3.3, Item 2‡.

1905.6.5.3 Condition of cores. Cores shall be preparedfor transport and storage by wiping drilling water fromtheir surfaces and placing the cores in water-tight bags orcontainers immediately after drilling. Cores shall betested not earlier than 48 hours nor later than seven daysafter coring unless approved by the registered designprofessional of record.

1905.6.5.4 Test results. Concrete in an area representedby core tests shall be considered structurally adequate ifthe average of three cores is equal to at least 85 percent off ' c and if no single core is less than 75 percent of f ' c.Additional testing of cores extracted from locations rep-resented by erratic core strength results is permitted.

1905.6.5.5 Strength evaluation. If the criteria of Sec-tion 1905.6.5.4 are not met and the structural adequacyremains in doubt, the commissioner may order a strengthevaluation in accordance with ACI 318, Chapter 20, forthe questionable portion of the structure, or take otherappropriate action. The registered design professional ofrecord shall present to the commissioner a completeanalysis showing the final safe load-carrying capacity ofthe questionable portion of the structure including anyproposed remedial actions necessary for review andapproval.

1905.7 Preparation of equipment and place of deposit.Preparation before concrete placement shall include the fol-lowing:

1. Equipment for mixing and transporting concrete shall beclean.

2. Debris and ice shall be removed from spaces to be occu-pied by concrete.

3. Forms shall be properly coated.

4. Masonry filler units that will be in contact with concreteshall be well drenched.

5. Reinforcement shall be thoroughly clean of ice or otherdeleterious coatings.

6. Water shall be removed from the place of deposit beforeconcrete is placed unless a tremie is to be used or unlessotherwise permitted by the commissioner.

7. Laitance and other unsound material shall be removedbefore additional concrete is placed against hardenedconcrete.

1905.8 Mixing. Mixing of concrete shall be performed inaccordance with Sections 1905.8.1 through 1905.8.3.

1905.8.1 General. Concrete shall be mixed until there is auniform distribution of materials and shall be dischargedcompletely before the mixer is recharged.

2008 NEW YORK CITY BUILDING CODE 409

CONCRETE

719_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:10:59 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 8: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

1905.8.2 Ready-mixed concrete. Ready-mixed concreteshall be mixed and delivered in accordance with the require-ments of ASTM C 94 or ASTM C 685. Concrete plants shallbe certified by the National Ready Mixed Concrete Associa-tion (NRMCA) and shall comply with the rules of thedepartment. Concrete producers shall have their plantsinspected quarterly and have their scales and trucks certi-fied. In fulfilling this certification requirement, the concreteproducer may present certification by either a New YorkCity government agency, or by the New York State Depart-ment of Transportation subject to the approval of the com-missioner. Concrete ready-mix truck drivers shall becertified by the NRMCA and shall comply with the rules ofthe department.

If required by the registered design professional ofrecord, batch tickets shall accompany every load of concretedelivered to a site. The batch ticket shall contain the infor-mation given below:

1. Plant name and location;

2. Contract number and project;

3. Mix designation as to type and strength;

4. Each material in the load along with quantities of eachby weight; and

5. The total amount of mix proportion water approved,quantity of water added at the plant and in transit, andthe remaining water that can be added on site.

1905.8.3 Job-mixed concrete. Job-mixed concrete shallcomply with ACI 318, Section 5.8.3.

1905.9 Conveying. The method and equipment for conveyingconcrete to the place of deposit shall comply with Sections1905.9.1 and 1905.9.2.

1905.9.1 Method of conveyance. Concrete shall be con-veyed from the mixer to the place of final deposit by meth-ods that will prevent separation or loss of materials that mayalter the properties of the concrete delivered. Cylinders shallbe made at the truck to determine the quality of concretedelivered to the site. Cylinders shall be made at the point ofplacement to determine the quality of concrete in-place.

1905.9.2 Conveying equipment. The conveying equip-ment shall be capable of providing a supply of concrete atthe site of placement without separation of ingredients andwithout interruptions sufficient to permit the loss of plastic-ity between successive increments.

1905.10 Depositing. The depositing of concrete shall complywith the provisions of Sections 1905.10.1 through 1905.10.8.

1905.10.1 Segregation. Concrete shall be deposited asnearly as practicable to its final position to avoid segregationdue to rehandling or flowing.

1905.10.2 Placement timing. Concreting operations shallbe carried on at such a rate that the concrete is at all timesplastic and flows readily into spaces between reinforce-ment.

1905.10.3 Unacceptable concrete. Concrete that has par-tially hardened or been contaminated by foreign materialsshall not be deposited in the structure.

1905.10.4 Retempering. Retempered concrete or concretethat has been remixed after initial set shall not be used unlessapproved by the registered design professional.

1905.10.5 Continuous operation. After concreting hasstarted, it shall be carried on as a continuous operation untilplacing of a panel or section, as defined by its boundaries orpredetermined joints, is completed, except as permitted orprohibited by Section 1906.8.

1905.10.6 Placement in vertical lifts. The top surfaces ofvertically formed lifts shall be generally level.

1905.10.7 Construction joints. When construction jointsare required, they shall be made in accordance with Section1906.8.

1905.10.8 Consolidation. Concrete shall be thoroughlyconsolidated by suitable means during placement and shallbe thoroughly worked around reinforcement and embeddedfixtures and into corners of the forms.

1905.11 Curing. The curing of concrete shall be in accordancewith Sections 1905.11.1 through 1905.11.3.

1905.11.1 Regular. Concrete (other than high earlystrength) shall be maintained above 50°F (10°C) and in amoist condition for at least the first seven days after place-ment, except when cured in accordance with Section1905.11.3.

1905.11.2 High-early-strength. High-early-strength con-crete shall be maintained above 50°F (10°C) and in a moistcondition for at least the first three days, except when curedin accordance with Section 1905.11.3.

1905.11.3 Accelerated curing. Accelerated curing of con-crete shall comply with ACI 318, Section 5.11.3.

1905.12 Cold weather requirements. Concrete that is to beplaced during freezing or near-freezing weather shall complywith the following:

1. Adequate equipment shall be provided for heating con-crete materials and protecting concrete during freezingor near-freezing weather.

2. Concrete materials and reinforcement, forms, fillers andground with which concrete is to in contact shall be freefrom frost.

3. Frozen materials or materials containing ice shall not beused.

1905.13 Hot weather requirements. During hot weather,proper attention shall be given to ingredients, production meth-ods, handling, placing, protection and curing to prevent exces-sive concrete temperatures or water evaporation that couldimpair the required strength or serviceability of the member orstructure.

SECTION BC 1906FORMWORK, EMBEDDED PIPES AND

CONSTRUCTION JOINTS1906.1 General requirements. The design, fabrication anderection of forms shall comply with the requirements of section1906.1.1 through 1906.1.6.

410 2008 NEW YORK CITY BUILDING CODE

CONCRETE

819_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:10:59 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 9: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

1906.1.1 Safe support of loads. Formwork, including allrelated braces, shoring, framing, and auxiliary construction,shall be proportioned, erected, supported, braced, and main-tained so that it will safely support all vertical and lateralloads that might be applied until such loads can be sup-ported by the permanent construction.

1906.1.2 Vertical and lateral loads. Vertical and lateralloads shall be carried to the ground by the formwork system,by the new construction after it has attained adequatestrength for that purpose, or by existing structures. Formsand their supports shall be designed so as not to damage pre-viously placed structures.

1906.1.3 Bracing. Forms shall be properly braced or tiedtogether so as to maintain position and shape, and shall con-form to the sizes and shapes of members as shown on thedesign drawings.

1906.1.4 Ramps, runways and platforms. Ramps, run-ways, and platforms shall meet the requirements of Section3315.

1906.1.5 Design. Design of formwork shall comply withACI 318, Section 6.1.5.

1906.1.6 Forms for prestressed and post-tensioned con-crete. Forms for prestressed and post-tensioned concretemembers shall be designed and constructed to permit move-ment of the member without damage during application ofthe pre-stressing force.

1906.2 Inspection. Formwork, including shores, reshores,braces and other supports, shall be inspected prior to placementof reinforcing steel to verify that the sizes of the concrete mem-bers that are being formed conform to the construction docu-ments and form design drawings. Such inspections shall beperformed by a qualified person designated by the contractor.Subsequently, inspections shall be performed by such personperiodically during the placement of concrete. During and after

concreting, the elevations, camber, and vertical alignment offormwork systems shall be inspected using tell-tale devices. Arecord of all such inspections shall be kept at the site availableto the commissioner. The names of the persons responsible forsuch inspections and the foreman in charge of the formworkshall be posted in the field office.

1906.3 Design of concrete formwork. Wherever the shoreheight exceeds 14 feet (4267 mm) or the total load on the formsexceeds 150 pounds per square foot (732 kg/m2), or whereverpower buggies or two-stage shores are used, the forms, includ-ing shoring foundation, shall be designed by a registereddesign professional and shall be constructed in conformancewith such design. A copy of the design drawings and any con-struction drawings and specifications shall be kept on the jobsite available to the commissioner.

1906.3.1 Vertical loads. Vertical loads shall include thetotal dead and live loads. Dead load shall include the weightof the formwork plus the weight of the reinforcement andfresh concrete. Live load shall allow for the weight of theworkers and equipment, with allowance for impact, but inno case shall be less than 20 pounds per square foot (98kg/m2).

1906.3.2 Lateral concrete pressure. Design of forms, tiesand bracing shall satisfy the minimum lateral pressures offresh concrete specified in Table 1906.3.2.

1906.3.3 External lateral loads. Braces and shores shall bedesigned to resist all external lateral loads, including, butnot limited to, wind, cable tensions, inclined supports,dumping of concrete, and starting and stopping of equip-ment. In no case shall the assumed value of lateral load dueto wind, dumping of concrete, and equipment acting in anydirection at each floorline be less than 100 plf edge or 2 per-cent of total dead load of the floor, whichever is greater.Except for foundation walls that are poured against a rigid

2008 NEW YORK CITY BUILDING CODE 411

CONCRETE

TABLE 1906.3.2MINIMUM LATERAL PRESSURES TO BE ASSUMED FOR FRESH CONCRETE WEIGHING 150 POUNDS PER CUBIC FOOT

TYPE OF WORKMINIMUM LATER PRESSURE ASSUMED

(psf) LIMITATIONS

Columns: Ordinary work with normal internalvibration

pR

T= +150

9000Maximum 3,000 psf or 150h, whichever is less

Walls: Rate of placement at 7 ft. per hr. or less pR

T= +150

9000Maximum 2,000 psf or 150h, whichever is less

Walls: Rate of placement at greater than 7 ft. per hr. pT

RT

= + +15043 400 2800,

Maximum 2,000 psf or 150h, whichever is less

Slabs p h=150 None

For SI: 1 inch = 25.4 mm, 1 foot per second = 0.305 m/s, 1 pound per cubic foot = 16.02 kg/m3, 1 pound per square foot = 4.882 kg/m2, °C = (°F-32)/1.8.a. Allowances for change in lateral pressure shall be made for concrete weighing other than 150 pcf; for concrete containing pozzolanic additions or cements other

than Type I, for concrete having slumps greater than 6 inches, or for concrete consolidated by revibration or external vibration of forms.b. Where retarding admixtures are employed under hot weather conditions an effective value of temperature less than that of the concrete in the forms shall be used in

the above formula.c. If retarding admixtures are used in cold weather, the lateral pressure may be assumed as that exerted by a fluid weighing 150 pcf.

where:

R = rate of placement, feet per hour.

T = temperature of concrete in the forms, °F.

h = height of fresh concrete above point considered, feet.

919_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:00 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 10: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

backing, wall forms shall be designed for a minimum lateralload of 10 pounds per square foot (49 kg/m2), and bracingfor wall forms shall be designed for a lateral load of at least100 plf of wall, applied at the top. The lateral load acting onwalls greater than 14 feet (4267 mm) high shall be deter-mined by analysis of conditions applicable to the site andbuilding.

1906.3.4 Special loads. The formwork shall be designed forany special conditions of construction likely to occur, suchas unsymmetrical placement of concrete, impact ofmachine-delivered concrete, uplift and concentrated loads.

1906.3.5 Shoring and bracing. Shoring and bracing shallcomply with Sections 1906.3.5.1 through 1906.3.5.4.

1906.3.5.1 Approval. When patented or commercialdevices that are not susceptible to design are used forshoring, bracing, or splicing, they shall be approved bythe commissioner.

1906.3.5.2 Splices. Splices shall develop the fullstrength of the spliced members.

1906.3.5.3 Bracing. Where shore height exceeds 10 feet(3048 mm), or when necessary to provide structural sta-bility, diagonal bracing shall be provided. Struts,anchored into masonry or to panel joints of adjacentbraced bays may be used to prevent buckling of individ-ual members not supported by the diagonal bracing, butbracing an entire tier of shores with struts without diago-nal bracing shall be prohibited unless the system can bedemonstrated to be braced by other rigid construction.

1906.3.5.4 Unbraced length of shores. The unbracedlength of shores shall not exceed the maximum lengthdetermined in accordance with the requirements of thiscode for the structural material used.

1906.3.6 Foundations. Foundations for shores more than10 feet (3048 mm) high and supported on the ground shallbe designed by a registered design professional.

1906.3.7 Settlement. Formwork shall be so constructedthat vertical adjustments can be made to compensate fortake-up and settlements. Wedges, jacks or other positivemeans shall be provided for this purpose.

1906.3.8 Structural ramps, runways and platforms.Structural runways, ramps and platforms shall comply withSection 3315 in addition to the requirements of Section1906.3.

1906.4 Construction. Construction of concrete formworkshall comply with the requirements of Sections 1906.4.1through 1906.4.4.

1906.4.1 Field-constructed lap splices. Field-constructedlap splices, other than approved devices, shall not be usedmore often than for every other shore under slabs or forevery third shore under beams and shall develop the fullstrength of the members. Such spliced shores shall be uni-formly distributed throughout the work. Splices shall not belocated near the midheight of the shores unless lateral sup-port is provided, nor midway between points of lateral sup-port.

1906.4.2 Vertical shores. Vertical shores for multifloorforms shall be set plumb and in alignment with lower tiers sothat loads from upper tiers are transferred directly to thelower tiers, or adequate transfer members shall be provided.Provision shall be made to transfer the lateral loads to theground or to completed construction of adequate strength.Vertical shores shall be so erected that they cannot tilt, andshall have firm bearing. Inclined shores and the bearingends of all shores shall be braced against slipping or sliding.The bearing surfaces shall be cut square and have a tight fitat splices.

1906.4.3 Runways. Runways for moving equipment shallbe provided with struts or legs as required and shall be sup-ported directly on the formwork or structural member andnot on the reinforcement.

1906.4.4 Unsafe conditions. Any unsafe condition or nec-essary adjustment revealed by inspection shall be remediedimmediately. If, during construction, any weakness devel-ops and the formwork shows any undue settlement or distor-tion, the work shall be stopped, the affected constructionremoved if permanently damaged, and the formworkstrengthened.

1906.5 Removal of forms and shoring. The removal of formsand shoring shall comply with the requirements of Sections1906.5.1 through 1906.5.6.

1906.5.1 Removal schedule. Before starting construction,the contractor shall develop a procedure and schedule forremoval of shores and installation of reshores and for calcu-lating the loads transferred to the structure during the pro-cess.

1906.5.1.1 Data and analysis. The structural analysisand concrete strength data used in planning and imple-menting form removal and reshoring shall be furnishedby the registered design professional responsible for theremoval schedule to the commissioner when sorequested.

1906.5.1.2 Support and removal. No constructionloads shall be supported on, nor any shoring removedfrom, any part of the structure under construction exceptwhen that portion of the structure in combination withthe remaining forming and shoring system has sufficientstrength to support safely its weight and the loads placedthereon.

1906.5.1.3 Concrete strength. Sufficient strength shallbe demonstrated by structural analysis of the proposedloads, the strength of the forming and shoring system,and concrete strength data. Concrete strength data shallbe based on tests of field-cured cylinders or, whenapproved by the commissioner, on other procedures forevaluating concrete strength.

1906.5.2 Construction loads. No construction loadsexceeding the combination of superimposed dead load plusspecified live load shall be supported on any unshored por-tion of the structure under construction, unless analysisindicates adequate strength to support such additional loads.

1906.5.3 Prestressed members. Form supports for pre-stressed concrete members shall not be removed until suffi-

412 2008 NEW YORK CITY BUILDING CODE

CONCRETE

1019_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:00 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 11: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

cient prestressing has been applied to prestressed membersto carry their dead load and anticipated construction loads.

1906.5.4 Manner of removal. Forms shall be removed insuch a manner as to assure the complete safety of the struc-ture and workers.

1906.5.5 Shores support. Where the structure as a whole issupported on shores, beam and girder sides, columns andsimilar vertical forms may be removed after the concrete issufficiently hard to withstand damage from the removal. Inno case shall the supporting forms or shoring be removeduntil the members have acquired sufficient strength to sup-port safely their weight and the load thereon.

1906.5.6 Control tests and alternate methods. The resultsof control tests, including concrete cylinder specimens pre-pared in accordance with ANSI/ASTM C 31, 2003a,cast-in-place cores, or other device that will produce testspecimens representative of the condition of the concrete inplace, of suitable size and proportions, and approved by theregistered design professional of record shall be evidencethat the concrete has attained sufficient strength or thestrength as may be specified on the drawings. The contrac-tor may submit alternate methods of stripping, reshoring,and strength control for approval by the registered designprofessional of record, subject to review by the commis-sioner.

1906.6 Reshoring. Reshoring shall be provided to support theconstruction where forms and shores are stripped before theconcrete has attained sufficient strength to support the super-imposed loads due to construction above. Reshoring shall com-ply with Sections 1906.6.1 through 1906.6.7.

1906.6.1 Reshores limitations. Reshores shall complywith the requirements of Sections 1906.6.1.1 through1906.6.1.7.

1906.6.1.1 Secureness of reshores. Reshores of woodor metal shall be screw adjusted or jacked and locked andwedged to make them secure. Reshores shall not bejacked or screwed so tight that they preload the floorbelow or remove the normal deflection of the slab above.

1906.6.1.2 Reshores in proximity to facades. Reshoreswithin 10 feet (3048 mm) of the facade of a building shallbe secured to prevent them from falling off the building.

1906.6.1.3 Wedges. Wedges shall not be used within 10feet (3048 mm) of the facade or at such other locations asdetermined by the commissioner.

1906.6.1.4 Stresses. In no case shall shores be so locatedas to alter the pattern of stresses determined in the origi-nal structural analysis or to induce tensile stresses wherereinforcing bars are not provided.

1906.6.1.5 Angle to surface. Reshores shall be perpen-dicular to the surface that they are supporting.

1906.6.1.6 Adjusting devices. Adjusting devices shallnot be used if heavily rusted, bent, dented, rewelded orhaving broken weldments or other defects.

1906.6.1.7 Metal shoring and accessory parts. Metalshoring and accessory parts shall be fully operative whenin use.

1906.6.2 Site safety provisions. Reshoring shall complywith all of the requirements of Chapter 33 regarding safe-guards during construction and the requirements of Sec-tions 1906.6.2.1 through 1906.6.2.3.

1906.6.2.1 Emergency. Extra shores or material andequipment that might be needed in an emergency shall befurnished.

1906.6.2.2 Stripping. Care shall be taken while strip-ping is underway to insure that material does not fall offthe building.

1906.6.2.3 Building materials. Building materials shallbe properly piled and tied or contained.

1906.6.3 Bracing. Lateral bracing shall be provided duringreshoring operations, and reshores shall be located as closeas practical to the same position on each floor to providecontinuous support from floor to floor.

1906.6.4 Reshoring beam and girder construction.Where reshoring of beam and girder construction isrequired, the forms shall not be removed from more thanone girder at a time, and the girder shall be reshored beforeany other supports are removed. After the supporting gird-ers are reshored, the form shall be removed from one beamwith its adjacent slabs and the beam shall be reshored beforeany other supports are removed. Slabs spanning 10 feet(3048 mm) or more shall be reshored along the centerline ofthe span.

1906.6.5 Reshoring flat slabs. Where reshoring of flat-slabconstruction is required, the formwork cannot be strippeduntil the concrete has acquired sufficient strength to safelysupport its weight and the load thereon, or temporarypreshores are provided supporting the slab at intervals of nomore than 8 feet (2438 mm) on center to be replaced byreshores prior to placing concrete on the floor above.Reshores must be installed and remain in place until theconcrete reaches full or sufficient strength to sustain thesuperimposed loads to which the concrete will be subjected.

1906.6.6 Stripping operation. Waste debris as a result ofstripping operations shall be immediately contained andremoved at reasonable intervals. Stripping operations onconcrete structures shall not be performed more than threestories below the story being formed.

1906.6.7 Prestressed construction. Solid safety shieldsshall be provided at end anchorages of prestressing beds, orwhere necessary, for protection against breakage ofprestressing strands, cables, or other assemblies duringprestressing or casting operations.

1906.7 Conduits and pipes embedded in concrete. Conduits,pipes and sleeves of any material not harmful to concrete andwithin the limitations of ACI 318, Section 6.3, are permitted tobe embedded in concrete with approval of the registered designprofessional of record.

1906.8 Construction joints. Construction joints shall complywith the provisions of Sections 1906.8.1 through 1906.8.6.

2008 NEW YORK CITY BUILDING CODE 413

CONCRETE

1119_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:00 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 12: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

1906.8.1 Surface cleaning. The surface of concrete con-struction joints shall be cleaned and laitance removed.

1906.8.2 Joint treatment. Immediately before new con-crete is placed, construction joints shall be wetted and stand-ing water removed.

1906.8.3 Location for force transfer. Construction jointsshall be so made and located as not to impair the strength ofthe structure. Provision shall be made for the transfer ofshear and other forces through construction joints in accor-dance with ACI 318, Section 11.7.9.

1906.8.4 Location in slabs, beams and girders. Construc-tion joints in floors shall be located within the middle thirdof spans of slabs, beams and girders. Joints in girders shallbe offset a minimum distance of two times the width ofintersecting beams.

1906.8.5 Vertical support. Beams, girders or slabs sup-ported by columns or walls shall not be cast or erected untilconcrete in the vertical support members is no longer plas-tic.

1906.8.6 Monolithic placement. Beams, girders, haunch-es, drop panels and capitals shall be placed monolithicallyas part of a slab system, unless otherwise shown in thedesign drawings or specifications.

SECTION BC 1907DETAILS OF REINFORCEMENT

1907.1 Hooks. Standard hooks on reinforcing bars used inconcrete construction shall comply with ACI 318, Section 7.1.

1907.2 Minimum bend diameters. Minimum reinforcementbend diameters utilized in concrete construction shall complywith ACI 318, Section 7.2.

1907.3 Bending. The bending of reinforcement shall complywith Sections 1907.3.1 and 1907.3.2.

1907.3.1 Cold bending. Reinforcement shall be bent cold,unless otherwise permitted by the registered design profes-sional of record.

1907.3.2 Embedded reinforcement. Reinforcement par-tially embedded in concrete shall not be field bent, except asshown on the construction documents or permitted by theregistered design professional of record.

1907.4 Surface conditions of reinforcement. The surfaceconditions of reinforcement shall comply with the provisionsof Sections 1907.4.1 through 1907.4.3.

1907.4.1 Coatings. At the time concrete is placed, rein-forcement shall be free from mud, oil or other nonmetalliccoatings that decrease bond. Epoxy coatings of steel rein-forcement in accordance with ACI 318, Sections 3.5.3.7 and3.5.3.8, are permitted.

1907.4.2 Rust or mill scale. Except for prestressing steel,steel reinforcement with rust, mill scale or a combination ofboth, shall be permitted, provided the minimum dimen-sions, including height of deformations and weight of ahand-wire-brushed test specimen, comply with applicableASTM specifications specified in Section 1903.5.

1907.4.3 Prestressing steel. Prestressing steel shall beclean and free of oil, dirt, scale, pitting and excessive rust. Alight coating of rust is permitted.

1907.5 Placing reinforcement. The placement of concretereinforcement shall comply with the provisions of Sections1907.5.1 through 1907.5.4.

1907.5.1 Support. Reinforcement, including tendons, andposttensioning ducts shall be accurately placed and ade-quately supported before concrete is placed, and shall besecured against displacement within tolerances permitted inSection 1907.5.2. Where approved by the registered designprofessional of record, embedded items (such as dowels orinserts) that either protrude from precast concrete membersor remain exposed for inspection are permitted to be embed-ded while the concrete is in a plastic state, provided the fol-lowing conditions are met:

1. Embedded items are maintained in the correct posi-tion while the concrete remains plastic.

2. The concrete is properly consolidated around theembedded item. Embedded items are not required tobe hooked or tied to reinforcement within the con-crete.

1907.5.2 Tolerances. Unless otherwise specified by theregistered design professional of record, reinforcement,including tendons, and posttensioning ducts shall be placedwithin the tolerances specified in Sections 1907.5.2.1 and1907.5.2.2.

1907.5.2.1 Depth and cover. Tolerance for depth, d, andminimum concrete cover in flexural members, walls andcompression members shall be as shown in Table1907.5.2.1, except that tolerance for the clear distance toformed soffits shall be minus 1/4 inch (6.4 mm) and toler-ance for cover shall not exceed minus one-third the mini-mum concrete cover required in the design drawings orspecifications.

TABLE 1907.5.2.1TOLERANCES

DEPTH (d) (inches)TOLERANCE ON d

(inch)

TOLERANCE ONMINIMUM CONCRETE

COVER

d 8 ± 3/8 − 3/8

d > 8 ± 1/2 – 1/2

For SI: 1 inch = 25.4 mm.

1907.5.2.2 Bends and ends. Tolerance for longitudinallocation of bends and ends of reinforcement shall be ± 2inches (± 51 mm) except the tolerance shall be ± 1/2 inch(± 12.7 mm) at the discontinuous ends of brackets andcorbels, and ± 1 inch (25 mm) at the discontinuous endsof other members. The tolerance for minimum concretecover of Section 1907.5.2.1 shall also apply at discontin-uous ends of members.

1907.5.3 Welded wire fabric. Welded wire fabric with wiresize not greater than W5 or D5 used in slabs not exceeding10 feet (3048 mm) in span is permitted to be curved from apoint near the top of the slab over the support to a point near

414 2008 NEW YORK CITY BUILDING CODE

CONCRETE

1219_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:01 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 13: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

the bottom of the slab at midspan, provided such reinforce-ment is either continuous over, or securely anchored at sup-port.

1907.5.4 Welding. Welding of crossing bars shall not bepermitted for assembly of reinforcement unless authorizedby the registered design professional of record.

1907.6 Spacing limits for reinforcement. The clear distancebetween reinforcing bars, bundled bars, tendons and ductsshall comply with ACI 318, Section 7.6.

1907.7 Concrete protection for reinforcement. The mini-mum concrete cover for reinforcement shall comply with Sec-tions 1907.7.1 through 1907.7.7.

1907.7.1 Cast-in-place concrete (nonprestressed). Mini-mum concrete cover shall be provided for reinforcement innonprestressed, cast-in-place concrete construction inaccordance with Table 1907.7.1, but shall not be less thanrequired by Sections 1907.7.5 and 1907.7.7.

TABLE 1907.7.1MINIMUM CONCRETE COVER

CONCRETE EXPOSURE

MINIMUMCOVER(inches)

1. Concrete cast against and permanentlyexposed to earth 3

2. Concrete exposed to earth or weatherNo. 6 through No. 18 barNo. 5 bar, W31 or D31 wire, and smaller

211/2

3. Concrete not exposed to weather or in contactwith ground

Slabs, walls, joists:No. 14 and No. 18 barsNo. 11 bar and smaller

Beams, columns:Primary reinforcement, ties, stirrups, spirals

Shells, folded plate members:No. 6 bar and largerNo. 5 bar, W31 or D31 wire, and smaller

11/23/4

11/2

3/41/2

For SI: 1 inch = 25.4 mm.

1907.7.2 Cast-in-place concrete (prestressed). The mini-mum concrete cover for prestressed and nonprestressedreinforcement, ducts and end fittings in cast-in-place pre-stressed concrete shall comply with ACI 318, Section 7.7.2.

1907.7.3 Precast concrete (manufactured under plantcontrol conditions). The minimum concrete cover for pre-stressed and nonprestressed reinforcement, ducts and endfittings in precast concrete manufactured under plant con-trol conditions shall comply with ACI 318, Section 7.7.3.

1907.7.4 Bundled bars. The minimum concrete cover forbundled bars shall comply with ACI 318, Section 7.7.4.

1907.7.5 Corrosive environments. In corrosive environ-ments or other severe exposure conditions, prestressed andnonprestressed reinforcement shall be provided with addi-tional protection in accordance with ACI 318, Section 7.7.5.

1907.7.6 Future extensions. Exposed reinforcement,inserts and plates intended for bonding with future exten-sions shall be protected from corrosion.

1907.7.7 Fire protection. When this code requires a thick-ness of cover for fire protection greater than the minimumconcrete cover specified in Section 1907.7, such greaterthickness shall be used.

1907.8 Special reinforcement details for columns. Offsetbent longitudinal bars in columns and load transfer in structuralsteel cores of composite compression members shall complywith the provisions of ACI 318, Section 7.8.

1907.9 Connections. Connections between concrete framingmembers shall comply with the provisions of ACI 318, Section7.9.

1907.10 Lateral reinforcement for compression members.Lateral reinforcement for compression members shall complywith the provisions of ACI 318, Section 7.10.

1907.11 Lateral reinforcement for flexural members. Lat-eral reinforcement for compression reinforcement in flexuralmembers shall comply with the provisions of ACI 318, Section7.11.

1907.12 Shrinkage and temperature reinforcement. Rein-forcement for shrinkage and temperature stresses in concretemembers shall comply with the provisions of ACI 318, Section7.12.

1907.13 Requirements for structural integrity. The detail-ing of reinforcement and connections between concrete mem-bers shall comply with the provisions of ACI 318, Section 7.13.

SECTION BC 1908MODIFICATIONS TO ACI 318

1908.1 General. The text of ACI 318 shall be modified as indi-cated in Sections 1908.1.1 through 1908.1.7.

1908.1.1 ACI 318, Section 21.1. Modify existing defini-tions and add the following definitions to ACI 318, Section21.1.

DESIGN DISPLACEMENT. Total lateral displacementexpected for the design-basis earthquake, as specified bySection 9.5.5.7 of ASCE 7 or 1617.5.4 of this code.

STORY DRIFT RATIO. The design displacement over astory divided by the story height.

WALL PIER. A wall segment with a horizontallength-to-thickness ratio of at least 2.5, but not exceedingsix, whose clear height is at least two times its horizontallength.

1908.1.2 ACI 318, Section 21.2.1. Modify Sections21.2.1.2, 21.2.1.3 and 21.2.1.4 to read as follows:

21.2.1.2 For structures assigned to Seismic Design Cate-gory B, provisions of Chapters 1 through 18 and 22 shallapply except as modified by the provisions of this chap-ter. Where the seismic design loads are computed usingprovisions for intermediate or special concrete systems,the requirements of Chapter 21 for intermediate or spe-cial systems, as applicable, shall be satisfied.

21.2.1.3 For structures assigned to Seismic Design Cate-gory C, intermediate or special moment frames, or ordi-nary or special reinforced concrete structural walls shall

2008 NEW YORK CITY BUILDING CODE 415

CONCRETE

1319_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:01 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 14: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

be used to resist seismic forces induced by earthquakemotions. Where the design seismic loads are computedusing provisions for special concrete systems, therequirements of Chapter 21 for special systems, as appli-cable, shall be satisfied.

21.2.1.4 For structures assigned to Seismic Design Cate-gory D, E or F, special moment frames, special rein-forced concrete structural walls, diaphragms and trussesand foundations complying with Sections 21.2 through21.10 shall be used to resist forces induced by earthquakemotions when special systems are required. Intermediatemoment frames and ordinary reinforced concrete walls,where allowed, shall comply with Chapter 21. Framemembers not proportioned to resist earthquake forcesshall comply with Section 21.11.

1908.1.3 ACI 318, Section 21.2.5. Modify ACI 318, Sec-tion 21.2.5, by renumbering as Section 21.2.5.1 and addingnew Sections 21.2.5.2, 21.2.5.3 and 21.2.5.4 to read as fol-lows:

21.2.5 Reinforcement in members resisting earth-quake-induced forces.

21.2.5.1 Except as permitted in Sections 21.2.5.2through 21.2.5.4, reinforcement resisting earth-quake-induced flexural and axial forces in frame mem-bers and in structural wall boundary elements shallcomply with ASTM A 706. ASTM 615, Grades 40 and60 reinforcement, shall be permitted in these members if(a) the actual yield strength based on mill tests does notexceed the specified yield strength by more than 18,000psi (retests shall not exceed this value by more than anadditional 3,000 psi), and (b) the ratio of the actual ulti-mate tensile strength to the actual tensile yield strength isnot less than 1.25.

21.2.5.2 Prestressing steel shall be permitted in flexuralmembers of frames, provided the average prestress, f pc,calculated for an area equal to the member’s shortestcross-sectional dimension multiplied by the perpendicu-lar dimension shall be the lesser of 700 psi (4.83MPa) orf ' c /6 at locations of nonlinear action where prestressingsteel is used in members of frames.

21.2.5.3 Unless the seismic-force-resisting frame isqualified for use through structural testing as required bythe ACI Provisional Standard ITG/T1.1, for members inwhich prestressing steel is used together with mild rein-forcement to resist earthquake-induced forces,prestressing steel shall not provide more than one-quar-ter of the strength for either positive or negative momentsat the nonlinear action location and shall be anchored atthe exterior face of the joint or beyond.

21.2.5.4 Anchorages for tendons must be demonstratedto perform satisfactorily for seismic loadings. Anchor-age assemblies shall withstand, without failure, a mini-mum of 50 cycles of loading ranging between 40 and 85percent of the minimum specified tensile strength of theprestressing steel.

1908.1.4 ACI 318, Section 21.7. Modify ACI 318, Section21.7, by adding a new Section 21.7.10 to read as follows:

21.7.10 Wall piers and wall segments.

21.7.10.1 Wall piers not designed as a part of a specialmoment frame shall have transverse reinforcementdesigned to satisfy the requirements in Section 21.7.10.2.

Exceptions:

1. Wall piers that satisfy Section 21.11.

2. Wall piers along a wall line within a story whereother shear wall segments provide lateral sup-port to the wall piers, and such segments have atotal stiffness of at least six times the sum of thestiffness of all the wall piers.

21.7.10.2 Transverse reinforcement shall be designed toresist the shear forces determined from Sections 21.3.4.2and 21.4.5.1. Where the axial compressive force, includ-ing earthquake effects, is less than Agf 'c /20, transversereinforcement in wall piers is permitted to have standardhooks at each end in lieu of hoops. Spacing of transversereinforcement shall not exceed 6 inches (152 mm).Transverse reinforcement shall be extended beyond thepier clear height for at least the development length ofthe largest longitudinal reinforcement in the wall pier.

21.7 .10.3 Wall segments with a horizontallength-to-thickness ratio less than 2.5 shall be designedas columns.

1908.1.5 ACI 318, Section 21.10.1.1. Modify ACI 318,Section 21.10.1.1, to read as follows:

21.10.1.1 Foundations resisting earthquake-inducedforces or transferring earthquake-induced forcesbetween a structure and the ground shall comply with therequirements of Section 21.10 and other applicable pro-visions of ACI 318 unless modified by Chapter 18 of thiscode.

1908.1.6 ACI 318, Section 21.11. Modify ACI Sections21.11.1 and 21.11.2.2 and add Sections 21.11.5 through21.11.7 as follows:

21.11.1 Frame members assumed not to contribute to lat-eral resistance shall be detailed according to Section21.11.2 or 21.11.3 depending on the magnitude ofmoments induced in those members when subjected tothe design displacement. If effects of design displace-ments are not explicitly checked, it shall be permitted toapply the requirements of Section 21.11.3. Slab-columnconnections shall comply with Sections 21.11.5 through21.11.7. Conformance to Section 21.11 satisfies thedeformation compatibility requirements of Section9.5.2.2.4.3 of ASCE 7.

21.11.2.2 Members with factored gravity axial forcesexceeding (Ag f ' c /10) shall satisfy Sections 21.4.3,21.4.4.1(c), 21.4.4.3 and 21.4.5. The maximum longitu-dinal spacing of ties shall be, So, for the full columnheight. The spacing, So, shall not be more than six diame-

416 2008 NEW YORK CITY BUILDING CODE

CONCRETE

1419_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:01 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 15: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

ters of the smallest longitudinal bar enclosed or 6 inches(152 mm), whichever is smaller. Lap splices of longitudi-nal reinforcement in such members need not satisfy Sec-tion 21.4.3.2 in structures where the seismicforce-resisting system does not include special momentframes.

21.11.5 Reinforcement to resist punching shear shall beprovided in accordance with Sections 21.11.5.1 and21.11.5.2 at slab column connections where story driftratio exceeds [0.035 – 0.05 (Vu/ Vc)] except that Sec-tions 21.11.5.1 and 21.11.5.2 need not be satisfied whereVu/ Vc is less than 0.2 or where the story drift ratio is lessthan 0.005. Vu equals the factored punching shear fromgravity load excluding shear stress from unbalancedmoment. Vu is calculated for the load combination 1.2D+1.0L + 0.2S. The load factor on L is permitted to bereduced to 0.5 in accordance with Section 9.2.1(a). In nocase shall shear reinforcement be less than that requiredin Section 11.12 for loads without consideration of seis-mic effects.

21.11.5.1 — The slab shear reinforcement shall provideVs not less than 3.5v f' c .

21.11.5.2 — Slab shear reinforcement shall extend notless than five times the slab thickness from the face of col-umn.

21.11.6 — Bottom bars or wires within the column stripshall conform to Section 13.3.8.5 except that splicesshall be Class B.

21.11.7—Within the effective slab width defined in Sec-tion 13.5.3.2, the ratio of nonprestressed bottom rein-forcement to gross concrete area shall not be less than0.004. Where bottom reinforcement is not required to becontinuous, such reinforcement shall extend a minimumof five times the slab thickness plus one developmentlength beyond the face of the column or terminated at theslab edge with a standard hook.

1908.1.7 ACI 318, Section 21.13.2. Modify ACI 318, Sec-tion 21.13.2, to read as follows:

21.13.2 In connections between wall panels, or betweenwall panels and the foundation, yielding shall berestricted to reinforcement.

1908.2 General. The text of ACI 318 shall be modified as indi-cated in Sections 1908.2.1 through 1908.2.4.

1908.2.1 ACI 318, Section 10.15. Modify ACI 318 by add-ing Section 10.15.4 to read as follows:

10.15.4 When the specified compressive strength of con-crete in a column is greater than 1.4 times that specifiedfor a floor system, the following additional requirementsshall be adhered to:

1. All of the design provisions of Section 10.15(unmodified) are adhered to.

2. The concrete construction is supervised andinspected continuously by a full-time professionalengineer responsible for the concrete placementspecial inspection. Such professional engineer

shall not delegate this responsibility to any subor-dinates.

1908.2.2 ACI 318, Section 16.3. Modify ACI 318 by add-ing Section 16.3.3 to read as follows:

16.3.3 - Lifting devices shall have a capacity sufficient tosupport four times the appropriate portion of the mem-ber's dead weight. The inclination of the lifting forceshall be considered.

1908.2.3 ACI 318, Section 21.12.3. Modify ACI 318, Sec-tion 21.12.3 to read as follows:

21.12.3 Design shear strength of beams and columnsresisting earthquake effect shall not be less than either 1or 2:

1. The sum of the shear associated with developmentof nominal moment strengths of the member ateach restrained end of the clear span and the shearcalculated for factored gravity loads;

2. The maximum shear obtained from design loadcombinations that include earthquake effect E,with E assumed to be twice that prescribed by thiscode for earthquake-resistant design.

1908.2.4 ACI 318, Section 21.12.6.8. Modify ACI 318,Section 21.12.6.8 to read as follows:

21.12.6.8 At the critical sections for columns defined in11.12.1.2, two-way shear caused by factored gravityloads shall not exceed 0.4φVc , where Vc shall be calcu-lated as defined in 11.12.2.1. for nonprestressed slabsand in 11.12.2.2. for prestressed slabs. For slabs withshear reinforcing, it shall be permitted to waive thisrequirement if the contribution of the earth-quake-induced factored two way shear stress transferredby eccentricity of shear in accordance with 11.12.6.1 and11.12.6.2 at the point of maximum stress does not exceedone-half of the stress φVn permitted by 11.12.6.2.

SECTION BC 1909STRUCTURAL PLAIN CONCRETE

1909.1 Scope. The design and construction of structural plainconcrete, both cast-in-place and precast, shall comply with theminimum requirements of Section 1909 and ACI 318, Chapter22.

1909.1.1 Special structures. For special structures, such asarches, underground utility structures, gravity walls andshielding walls, the provisions of Section 1909 shall governwhere applicable.

1909.2 Limitations. The use of structural plain concrete col-umns and structural plain concrete footings on piles is not per-mitted. In addition to the limitations set forth in Section 1910 ofthis chapter, the use of structural plain concrete shall otherwisebe limited to:

1. Members that are continuously supported by soil, suchas walls and footings, or by other structural memberscapable of providing continuous vertical support.

2008 NEW YORK CITY BUILDING CODE 417

CONCRETE

1519_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:02 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 16: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

2. Members for which arch action provides compressionunder all conditions of loading.

3. Walls and pedestals.

1909.3 Joints. Contraction or isolation joints shall be providedto divide structural plain concrete members into flexurally dis-continuous elements in accordance with ACI 318, Section22.3.

1909.4 Design. Structural plain concrete walls, footings andpedestals shall be designed for adequate strength in accordancewith ACI 318, Sections 22.4 through 22.8.

Exception: For Group R-3 occupancies and buildings ofother occupancies less than two stories in height oflight-frame construction, the required edge thickness ofACI 318 is permitted to be reduced to 6 inches (152 mm),provided that the footing does not extend more than 4 inches(102 mm) on either side of the supported wall.

1909.5 Precast members. The design, fabrication, transporta-tion and erection of precast, structural plain concrete elementsshall be in accordance with ACI 318, Section 22.9.

1909.6 Walls. In addition to the requirements of this section,structural plain concrete walls shall comply with the applicablerequirements of ACI 318, Chapter 22.

1909.6.1 Basement walls. The thickness of exterior base-ment walls and foundation walls shall be not less than 71/2

inches (191 mm). Structural plain concrete exterior base-ment walls shall be exempt from the requirements for spe-cial exposure conditions of Section 1904.2.2.

1909.6.2 Other walls. Except as provided in Section1909.6.1, the thickness of bearing walls shall be not lessthan 1/24 the unsupported height or length, whichever isshorter, but not less than 51/2 inches (140 mm).

1909.6.3 Openings in walls. Not less than two No. 5 barsshall be provided around window and door openings. Suchbars shall extend at least 24 inches (610 mm) beyond thecorners of openings.

SECTION BC 1910SEISMIC DESIGN PROVISIONS

1910.1 General. The design and construction of concrete com-ponents that resist seismic forces shall conform to the require-ments of this section and to ACI 318 as modified by Section1908.

1910.2 Classification of shear walls. Structural concreteshear walls that resist seismic forces shall be classified inaccordance with Sections 1910.2.1 through 1910.2.4.

1910.2.1 Ordinary plain concrete shear walls. Ordinaryplain concrete shear walls are walls conforming to therequirements of Chapter 22 of ACI 318.

1910.2.2 Detailed plain concrete shear walls. Detailedplain concrete shear walls are walls conforming to therequirements for ordinary plain concrete shear walls andshall have reinforcement as follows: Vertical reinforcementof at least 0.20 square inch (129 mm2) in cross-sectionalarea shall be provided continuously from support to support

at each corner, at each side of each opening and at the endsof walls. The continuous vertical bar required beside anopening is permitted to substitute for one of the two No. 5bars required by Section 22.6.6.5 of ACI 318. Horizontalreinforcement at least 0.20 square inch (129 mm2) incross-sectional area shall be provided:

1. Continuously at structurally connected roof and floorlevels and at the top of walls;

2. At the bottom of load-bearing walls or in the top offoundations where doweled to the wall; and

3. At a maximum spacing of 120 inches (3048 mm).

Reinforcement at the top and bottom of openings, whereused in determining the maximum spacing specified in Item 3above, shall be continuous in the wall.

1910.2.3 Ordinary reinforced concrete shear walls. Ordi-nary reinforced concrete shear walls are walls conformingto the requirements of ACI 318 for ordinary reinforced con-crete structural walls.

1910.2.4 Special reinforced concrete shear walls. Specialreinforced concrete shear walls are walls conforming to therequirements of ACI 318 for special reinforced concretestructural walls or special precast structural walls.

1910.3 Seismic Design Category B. Structures assigned toSeismic Design Category B, as determined in accordance withSection 1616, shall conform to the requirements for SeismicDesign Category A and to the additional requirements for Seis-mic Design Category B of this section.

1910.3.1 Ordinary moment frames. In flexural membersof ordinary moment frames forming part of the seis-mic-force-resisting system, at least two main flexural rein-forcing bars shall be provided continuously top and bottomthroughout the beams, through or developed within exteriorcolumns or boundary elements.

1910.3.1.1 Shear. Columns of ordinary moment frameshaving a clear height-to-maximum-plan-dimension ratioof five or less shall be designed for shear in accordancewith Section 21.12.3 of ACI 318.

1910.4 Seismic Design Category C. Structures assigned toSeismic Design Category C, as determined in accordance withSection 1616, shall conform to the requirements for SeismicDesign Category B and to the additional requirements for Seis-mic Design Category C of this section.

1910.4.1 Seismic-force-resisting systems. Moment framesused to resist seismic forces shall be intermediate momentframes or special moment frames. Shear walls used to resistseismic forces shall be ordinary reinforced concrete shearwalls or special reinforced concrete shear walls. Ordinaryreinforced concrete shear walls constructed of precast con-crete elements shall comply with the additional require-ments of Section 21.13 of ACI 318 for intermediate precastconcrete structural walls, as modified by Section 1908.1.7.

1910.4.2 Discontinuous members. Columns supportingreactions from discontinuous stiff members, such as walls,shall be designed for the special load combinations in Sec-tion 1605.4 and shall be provided with transverse reinforce-ment at the spacing, So, as defined in Section 21.12.5.2 of

418 2008 NEW YORK CITY BUILDING CODE

CONCRETE

1619_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:02 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 17: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

ACI 318 over their full height beneath the level at which thediscontinuity occurs. This transverse reinforcement shall beextended above and below the column as required in Section21.4.4.5 of ACI 318.

1910.4.3 Plain concrete. Structural plain concrete mem-bers in structures assigned to Seismic Design Category Cshall conform to ACI 318 and with Sections 1910.4.3.1through 1910.4.3.3.

1910.4.3.1 Walls. Structural plain concrete walls are notpermitted in structures assigned to Seismic Design Cate-gory C.

Exception: Structural plain concrete basement, foun-dation or other walls below the base are permitted indetached one- and two-family dwellings constructedwith stud-bearing walls. Such walls shall have rein-forcement in accordance with Section 22.6.6.5 of ACI318.

1910.4.3.2 Footings. Isolated footings of plain concretesupporting pedestals or columns are permitted providedthe projection of the footing beyond the face of the sup-ported member does not exceed the footing thickness.

Exception: In detached one- and two-family dwell-ings three stories or less in height, the projection ofthe footing beyond the face of the supported memberis permitted to exceed the footing thickness.

1910.4.3.2.1 Reinforcing bars. Plain concrete foot-ings supporting walls shall be provided with not lessthan two continuous longitudinal reinforcing bars.Bars shall not be smaller than No. 4 and shall have atotal area of not less than 0.002 times the grosscross-sectional area of the footing. For footings whichexceed 8 inches (203 mm) in thickness, a minimum ofone bar shall be provided at the top and bottom of thefooting. For foundation systems consisting of a plainconcrete footing and a plain concrete stem wall, aminimum of one bar shall be provided at the top of thestem wall and at the bottom of the footing. Continuityof reinforcement shall be provided at corners andintersections.

Exceptions:

1. In detached one- and two-family dwellingsthree stories or less in height and constructedwith stud-bearing walls, plain concrete foot-ings supporting walls are permitted withoutlongitudinal reinforcement.

2. Where a slab-on-ground is castmonolithically with the footing, one No. 5bar is permitted to be located at either the topor bottom of the footing.

1910.4.3.3 Pedestals. Plain concrete pedestals shall notbe used to resist lateral seismic forces.

1910.5 Seismic Design Category D. Structures assigned toSeismic Design Category D, as determined in accordance withSection 1616, shall conform to the requirements for Seismic

Design Category C and to the additional requirements of thissection.

1910.5.1 Seismic-force-resisting systems. Moment framesused to resist seismic forces shall be special moment frames.Shear walls used to resist seismic forces shall be specialreinforced concrete shear walls.

1910.5.2 Frame members not proportioned to resistforces induced by earthquake motions. Frame compo-nents assumed not to contribute to lateral force resistanceshall conform to ACI 318, Section 21.11, as modified bySection 1908.1.6 of this chapter.

SECTION BC 1911MINIMUM SLAB PROVISIONS

1911.1 General. The thickness of concrete floor slabs sup-ported directly on the ground shall not be less than 31/2 inches(89 mm). A 6-mil (0.006 inch; 0.152 mm) polyethylene vaporretarder with joints lapped not less than 6 inches (152 mm)shall be placed between the base course or subgrade and theconcrete floor slab, or other acceptable equivalent methods ormaterials shall be used to retard vapor transmission through thefloor slab.

Exception: A vapor retarder is not required:

1. For detached structures accessory to occupancies inGroup R-3, such as garages, utility buildings or otherunheated facilities.

2. For unheated storage rooms having an area of lessthan 70 square feet (6.5 m2) and carports attached tooccupancies in Group R-3.

3. For buildings of other occupancies where migrationof moisture through the slab from below will not bedetrimental to the intended occupancy of the building.

4. For drive ways, walks, patios and other flat work thatwill not be enclosed at a later date.

5. Where approved based on local site conditions.

SECTION BC 1912ANCHORAGE TO CONCRETE—ALLOWABLE

STRESS DESIGN

1912.1 Scope. The provisions of this section shall govern theallowable stress design of headed bolts and headed studanchors cast in normal-weight concrete for purposes of trans-mitting structural loads from one connected element to theother. These provisions do not apply to anchors installed inhardened concrete or where load combinations include earth-quake loads or effects. The bearing area of headed anchorsshall be not less than one and one-half times the shank area.Where strength design is used, or where load combinationsinclude earthquake loads or effects, the design strength ofanchors shall be determined in accordance with Section 1913.Bolts shall conform to ASTM A 307 or an acceptableequivalent.

2008 NEW YORK CITY BUILDING CODE 419

CONCRETE

1719_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:02 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 18: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

1912.2 Allowable service load. The allowable service load forheaded anchors in shear or tension shall be as indicated in Table1912.2. Where anchors are subject to combined shear and ten-sion, the following relationship shall be satisfied:

(Ps / Pt )5/3 + (Vs / Vt )5/3 ≤ 1 (Equation 19-1)

where:

Ps = Applied tension service load, pounds (newtons).

Pt = Allowable tension service load from Table 1912.2,pounds (newtons).

Vs = Applied shear service load, pounds (newtons).

Vt = Allowable shear service load from Table 1912.2,pounds (newtons).

1912.3 Required edge distance and spacing. The allowableservice loads in tension and shear specified in Table 1912.2 arefor the edge distance and spacing specified. The edge distanceand spacing are permitted to be reduced to 50 percent of the val-ues specified with an equal reduction in allowable service load.Where edge distance and spacing are reduced less than 50 per-cent, the allowable service load shall be determined by linearinterpolation.

1912.4 Reserved.

1912.5 Increase for special inspection. Where special inspec-tion is provided for the installation of anchors, a 100-percentincrease in the allowable tension values of Table 1912.2 is per-mitted. No increase in shear value is permitted.

SECTION BC 1913ANCHORAGE TO CONCRETE—STRENGTH

DESIGN

1913.1 Scope. The provisions of this section shall govern thestrength design of anchors installed in concrete for purposes of

transmitting structural loads from one connected element to theother. Headed bolts, headed studs and hooked (J- or L-) boltscast in concrete and expansion anchors and undercut anchorsinstalled in hardened concrete shall be designed in accordancewith Appendix D of ACI 318, provided they are within thescope of Appendix D.

Exception: Where the basic concrete breakout strength intension of a single anchor, Nb, is determined in accordancewith Equation (D-7), the concrete breakout strengthrequirements of Section D.4.2.2 shall be considered satis-fied by the design procedures of Sections D.5.2 and D.6.2for anchors exceeding 2 inches (51 mm) in diameter or 25inches (635 mm) tensile embedment depth.

1913.1.1 Anchors outside scope of Appendix D. Thestrength design of anchors that are not within the scope ofAppendix D of ACI 318, as modified by this code, shall bein accordance with a procedure subject to the approval of thecommissioner.

SECTION BC 1914SHOTCRETE

1914.1 General. Shotcrete is mortar or concrete that is pneu-matically projected at high velocity onto a surface. Except asspecified in this section, shotcrete shall conform to the require-ments of this chapter for plain or reinforced concrete.

1914.2 Proportions and materials. Shotcrete proportionsshall be selected that allow suitable placement proceduresusing the delivery equipment selected and shall result in fin-ished in-place hardened shotcrete meeting the strength require-ments of this code.

1914.3 Aggregate. Coarse aggregate, if used, shall not exceed3/4 inch (19.1 mm).

420 2008 NEW YORK CITY BUILDING CODE

CONCRETE

TABLE 1912.2ALLOWABLE SERVICE LOAD ON EMBEDDED BOLTS (pounds)

BOLTDIAMETER

(inches)

MINIMUMEMBEDMENT

(inches)

EDGEDISTANCE

(inches)SPACING(inches)

MINIMUM CONCRETE STRENGTH (psi)

f c = 2,500 f c = 3,000 f c = 4,000

Tension Shear Tension Shear Tension Shear

1/4 21/2 11/2 3 200 500 200 500 200 500

3/8 3 21/4 41/2 500 1,100 500 1,100 500 1,100

1/244

35

65

9501,450

1,2501,600

9501,500

1,2501,650

9501,550

1,2501,750

5/841/241/2

33/461/4

71/271/2

1,5002,125

2,7502,950

1,5002,200

2,7503,000

1,5002,400

2,7503,050

3/455

41/271/2

99

2,2502,825

3,2504,275

2,2502,950

3,5604,300

2,2503,200

3,5604,400

7/8 6 51/4 101/2 2,550 3,700 2,550 4,050 2,550 4,050

1 7 6 12 3,050 4,125 3,250 4,500 3,650 5,300

11/8 8 63/4 131/2 3,400 4,750 3,400 4,750 3,400 4,750

11/4 9 71/2 15 4,000 5,800 4,000 5,800 4,000 5,800

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689MPa, 1 pound = 4.45 N.

1819_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:03 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 19: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

1914.4 Reinforcement. Reinforcement used in shotcrete con-struction shall comply with the provisions of Sections 1914.4.1through 1914.4.4.

1914.4.1 Size. The maximum size of reinforcement shall beNo. 5 bars unless it is demonstrated by preconstruction teststhat adequate encasement of larger bars will be achieved.

1914.4.2 Clearance. When No. 5 or smaller bars are used,there shall be a minimum clearance between parallel rein-forcement bars of 21/2 inches (64 mm). When bars largerthan No. 5 are permitted, there shall be a minimum clear-ance between parallel bars equal to six diameters of the barsused. When two curtains of steel are provided, the curtainnearer the nozzle shall have a minimum spacing equal to 12bar diameters and the remaining curtain shall have a mini-mum spacing of six bar diameters.

Exception: Subject to the approval of the commissioner,required clearances shall be reduced where it is demon-strated by preconstruction tests that adequate encase-ment of the bars used in the design will be achieved.

1914.4.3 Splices. Lap splices of reinforcing bars shall uti-lize the noncontact lap splice method with a minimum clear-ance of 2 inches (51 mm) between bars. The use of contactlap splices necessary for support of the reinforcing is per-mitted when approved by the commissioner, based on satis-factory preconstruction tests that show that adequateencasement of the bars will be achieved, and provided thatthe splice is oriented so that a plane through the center of thespliced bars is perpendicular to the surface of the shotcrete.

1914.4.4 Spirally tied columns. Shotcrete shall not beapplied to spirally tied columns.

1914.5 Preconstruction tests. When required by the commis-sioner, a test panel shall be shot, cured, cored or sawn, exam-ined and tested prior to commencement of the project. Thesample panel shall be representative of the project and simulatejob conditions as closely as possible. The panel thickness andreinforcing shall reproduce the thickest and most congestedarea specified in the structural design. It shall be shot at thesame angle, using the same nozzleman and with the same con-crete mix design that will be used on the project. The equip-ment used in preconstruction testing shall be the sameequipment used in the work requiring such testing, unless sub-stitute equipment is approved by the commissioner.

1914.6 Rebound. Any rebound or accumulated loose aggre-gate shall be removed from the surfaces to be covered prior toplacing the initial or any succeeding layers of shotcrete.Rebound shall not be used as aggregate.

1914.7 Joints. Except where permitted herein, unfinishedwork shall not be allowed to stand for more than 30 minutesunless edges are sloped to a thin edge. For structural elementsthat will be under compression and for construction jointsshown on the approved construction documents, square jointsare permitted. Before placing additional material adjacent topreviously applied work, sloping and square edges shall becleaned and wetted.

1914.8 Damage. In-place shotcrete that exhibits sags, sloughs,segregation, honeycombing, sand pockets or other obvious

defects shall be removed and replaced. Shotcrete above sagsand sloughs shall be removed and replaced while still plastic.

1914.9 Curing. During the curing periods specified herein,shotcrete shall be maintained above 40°F (4°C) and in moistcondition.

1914.9.1 Initial curing. Shotcrete shall be kept continu-ously moist for 24 hours after shotcreting is complete orshall be sealed with an approved curing compound.

1914.9.2 Final curing. Final curing shall continue for sevendays after shotcreting, or for three days ifhigh-early-strength cement is used, or until the specifiedstrength is obtained. Final curing shall consist of the initialcuring process or the shotcrete shall be covered with anapproved moisture-retaining cover.

1914.9.3 Natural curing. Natural curing shall not be usedin lieu of that specified in this section unless the relativehumidity remains at or above 85 percent, and is authorizedby the registered design professional of record andapproved by the commissioner.

1914.10 Strength tests. Strength tests for shotcrete shall bemade by an approved agency on specimens that are representa-tive of the work and that have been water soaked for at least 24hours prior to testing. When the maximum-size aggregate islarger than 3/8 inch (9.5 mm), specimens shall consist of not lessthan three 3-inch-diameter (76 mm) cores or 3-inch (76 mm)cubes. When the maximum-size aggregate is 3/8 inch (9.5 mm)or smaller, specimens shall consist of not less than2-inch-diameter (51 mm) cores or 2-inch (51 mm) cubes.

1914.10.1 Sampling. Specimens shall be taken from thein-place work or from test panels, and shall be taken at leastonce each shift, but not less than one for each 50 cubic yards(38.2 m3) of shotcrete.

1914.10.2 Panel criteria. When the maximum-size aggre-gate is larger than 3/8 inch (9.5 mm), the test panels shallhave minimum dimensions of 18 inches by 18 inches (457mm by 457 mm). When the maximum size aggregate is 3/8

inch (9.5 mm) or smaller, the test panels shall have mini-mum dimensions of 12 inches by 12 inches (305 mm by 305mm). Panels shall be shot in the same position as the work,during the course of the work and by the nozzlemen doingthe work. The conditions under which the panels are curedshall be the same as the work.

1914.10.3 Acceptance criteria. The average compressivestrength of three cores from the in-place work or a single testpanel shall equal or exceed 0.85 f ' c with no single core lessthan 0.75 f ' c. The average compressive strength of threecubes taken from the in-place work or a single test panelshall equal or exceed f ' c with no individual cube less than0.88 f ' c. To check accuracy, locations represented by erraticcore or cube strengths shall be retested.

SECTION BC 1915REINFORCED GYPSUM CONCRETE

1915.1 General. Reinforced gypsum concrete shall complywith the requirements of ASTM C 317 and ASTM C 956.

2008 NEW YORK CITY BUILDING CODE 421

CONCRETE

1919_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:03 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 20: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

1915.2 Minimum thickness. The minimum thickness of rein-forced gypsum concrete shall be 2 inches (51 mm) except theminimum required thickness shall be reduced to 11/2 inches (38mm), provided the following conditions are satisfied:

1. The overall thickness, including the formboard, is notless than 2 inches (51 mm).

2. The clear span of the gypsum concrete between supportsdoes not exceed 33 inches (838 mm).

3. Diaphragm action is not required.

4. The design live load does not exceed 40 pounds persquare foot (psf) (1915 Pa).

1915.3 Limitations of use. Reinforced gypsum concrete shallnot be used where exposed directly to the weather or wheresubject to frequent or continuous wetting. Precast units shall beprotected by coverings or coatings from the weather and fromcontact with moisture during shipment and during storage atthe work site.

SECTION BC 1916CONCRETE-FILLED PIPE COLUMNS

1916.1 General. Concrete-filled pipe columns shall be manu-factured from standard, extra-strong or double-extra-strongsteel pipe or tubing that is filled with concrete so placed andmanipulated as to secure maximum density and to ensure com-plete filling of the pipe without voids.

1916.2 Design. The safe supporting capacity of concrete-filledpipe columns shall be computed in accordance with ACI 318and AISC-LRFD or AISC 335 or as determined by a testapproved by the commissioner.

1916.3 Connections. Caps, base plates and connections shallbe in accordance with ACI 318 and AISC-LRFD or AISC 335and shall be positively attached to the shell and anchored to theconcrete core. Welding of brackets without mechanicalanchorage shall be prohibited. Where the pipe is slotted toaccommodate webs of brackets or other connections, the integ-rity of the shell shall be restored by welding to ensure hoopingaction of the composite section.

1916.4 Reinforcement. Steel reinforcement shall be in theform of rods, structural shapes or pipe embedded in the con-crete core in accordance with ACI 318 and AISC-LRFD orAISC 335 with sufficient clearance to ensure the compositeaction of the section, but not nearer than 1 inch (25 mm) to theexterior steel shell. Structural shapes used as reinforcementshall be milled to ensure bearing on cap and base plates.

1916.5 Fire-resistance-rating protection. Pipe columns shallbe of such size or so protected as to develop the requiredfire-resistance ratings specified in Table 601. Where an outersteel shell is used to enclose the fire-resistant covering, the shellshall not be included in the calculations for strength of the col-umn section. The minimum diameter of pipe columns shall be4 inches (102 mm) except that in structures of Type V construc-tion not exceeding three stories or 40 feet (12 192 mm) inheight, pipe columns used in the basement and as secondarysteel members shall have a minimum diameter of 3 inches (76mm).

1916.6 Approvals. Details of column connections and splicesshall be shop fabricated in accordance with ACI 318 andAISC-LRFD or AISC 335. Shop-fabricated concrete-filledpipe columns shall be inspected by an approved agency pursu-ant to Chapter 17 of this code.

SECTION BC 1917STRUCTURAL INTEGRITY REQUIREMENTS

1917.1 General. Reinforced concrete structures shall meet allthe requirements of Sections 1917.1 through 1917.3. Concreteslabs on metal deck shall be governed by the provisions ofChapter 22. Reinforcement provided for gravity, seismic andwind forces or for other purposes may be regarded as formingpart of, or the whole of, these requirements. Reinforcing pro-vided for one requirement may be counted towards the otherrequirements.

1917.2 Continuity and ties. The structural integrity require-ments of ACI 318, Section 7.13 shall apply. In addition, the fol-lowing requirements shall be met.

1917.2.1 Slab reinforcement. At all floor and roof levels,slabs shall have a mat of bottom reinforcement in two per-pendicular (or roughly perpendicular) directions. Rein-forcement in this bottom mat shall be made continuous withlap, mechanical or welded tension splices.

1917.2.1.1 Bottom mat reinforcement. In each direc-tion, the bottom mat reinforcement shall be not less than,the steel required for temperature reinforcement. Thebottom mat reinforcement shall be anchored at discon-tinuous edges within the column strip, reentrant corners,elevation changes and anywhere else the continuity ofthe reinforcing is interrupted.

Exception: Flat plate middle strip bottom mat rein-forcing perpendicular to discontinuous slab edges.

In addition, the main bottom mat reinforcement inone-way slabs shall be anchored at discontinuous edges.

1917.2.2 Peripheral ties. At each floor and roof level, rein-forcement forming a continuous peripheral tie shall be pro-vided. Peripheral ties shall be located within perimeterbeams or walls, where they occur, or within 4 feet (1219mm) of the edge of slab, where perimeter beams or walls donot occur. Continuous tie reinforcement shall be equal tohalf of the bottom reinforcement within the edge or edgestrip for two-way slabs but not less than two bars.

1917.2.3 Horizontal ties. At each column, beam reinforce-ment or slab bottom reinforcement shall be provided at eachlevel that can develop a tension force equal to the maximumof 1 or 2:

1. Three times the load entering the column at that level,using a load combination of 1.0 x DL (self weight ofstructure only).

2. One and a half times the load entering the column at thatlevel using the load combinations of (1.2 DL + 1.6 LL) or1.4 DL.

1917.2.3.1 Bottom reinforcing‡. This beam or slab bot-tom reinforcement shall be distributed around the col-

422 2008 NEW YORK CITY BUILDING CODE

CONCRETE

2019_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:03 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 21: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

umn perimeter and shall be extended on all sides of thecolumn into the adjacent slab for at least one-third of thespan length. Where reinforcing bars cannot be extendedbeyond the column (e.g., at slab edges and openings),they shall be hooked or otherwise developed within thecolumn.

1917.2.4 Vertical ties. Each column and each wall carryingvertical load shall be vertically tied continuously from itslowest to highest level. The vertical ties composed of verti-cal column reinforcement shall be capable of resisting a ten-sile force equal to the maximum design dead and live loadreceived by the column or wall from any one story withinfour floors below.

1917.3 Precast concrete general. Precast concrete structuralelements shall be reinforced to meet all of the requirements ofthis section. However, reinforcement provided for gravity, seis-mic and wind forces and for other purposes may be regarded asforming part of, or the whole of, these requirements. Reinforc-ing provided for one requirement may be counted towards theother requirements.

1917.3.1 Continuity and ties. The structural integrityrequirements of ACI 318, Section 16.5, shall apply. In pre-cast and composite structures, ties within precast structuralelements shall be continuous and shall be anchored to thesupporting structure. In addition to Sections 1917.2.2 and1917.2.4, the following requirements shall be met.

1917.3.1.1 End connections. End connections of allprecast slabs, beams and girders shall have an axial ten-sion capacity equal to the larger of the vertical shearcapacity of the connection at either end, or at least 2 per-cent of the maximum factored vertical dead and live loadin the precast compression element, whichever is larger,but not less than 20 kips or 2,500 pounds per linear footof slab (36.48 kN/m). Where more than one elementframes in one direction, none of the elements or connec-tions shall have an axial tension capacity of less than 1percent of the column load but not less than 20 kips.

1917.3.1.2 Side connections. Side connections of allprecast elements shall have an axial tension capacity notless than the steel required for temperature reinforce-ment of the larger element at either side.

1917.3.1.3 Connection forces. For design of the con-nections, the transverse shear force and the axial tensileforce need not be considered to act simultaneously.

1917.3.2 Joints. Joints in precast structures shall not rely onfriction due to gravity to transfer load.

1917.3.3 Bearing. The net bearing area shall not be lessthan 2 inches (51 mm) wide and 3 inches (76 mm) long inthe direction of the member.

2008 NEW YORK CITY BUILDING CODE 423

CONCRETE

2119_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:04 AM

Color profile: Generic CMYK printer profileComposite Default screen

Page 22: CHAPTER 19 CONCRETE - iccsafe.org 19... · CHAPTER 19 CONCRETE SECTION BC 1901 GENERAL ... through 7 of ACI 318 are referenced in other chapters and appendices of ACI 318, the provisions

424 2008 NEW YORK CITY BUILDING CODE

2219_NYC_2008_IBC.psM:\data\CODES\STATE CODES\New York City\2008\Building\Final VP\19_NYC_2008_IBC.vpThursday, August 14, 2008 9:11:04 AM

Color profile: Generic CMYK printer profileComposite Default screen