Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

download Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

of 12

Transcript of Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

  • 8/13/2019 Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

    1/12

    SUBSTATION DESIGN MANUAL

    CHAPTER 17

    Substation Layouts and Facilities - Outdoor

    Power & Water Corporation

    Power Networks

  • 8/13/2019 Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

    2/12

    Revision: 2

    Page 2 of 12

    Substation Design Manual

    Chapter 17 Substation Layouts and Facilities Outdoor

    Document Number

    D2010/287838

    Document Control

    Revision History

    Changes made to this manual since the last revision are highlighted in yellow.

    Disclaimer

    The information contained in this document has been carefully compiled but Power & Water

    Corporation takes no responsibility for any loss or liability of any kind suffered by any party, not

    being the intended recipient of this document, in reliance upon its contents whether arising

    from any error or inaccuracy in the information or any default, negligence or lack of care in

    relation to the preparation of the information in this document.

    Title Substation Design Manual

    Section Substation Layouts and Facilities Outdoor

    Document ID D2010/287838

    Prepared Hydro Tasmania Consulting 09/10/2009

    Reviewed Hydro Tasmania Consulting 09/10/2009

    Revision RevisionDate

    Details Authorised

    Name / Position Signature

    Draft 09/10/2009 For client review and input

    Final Draft 4/12/2009Revised following client comments Brendon Gannon

    Specialist Engineer

    Rev 1 2/11/2010

    Doc No & Doc Id InsertedSLD Initial & Ultimate DrawingNos insertedReference Docs [38] to [41] DocNos added17.2 second last paragraph

    switchyard added, last paragraphof the 11kV Switchboard added17.7 changed to aggregate shallbe installed17.8 last paragraph added

    Greg BrandManager Contracts& Projects

    Rev 2 17/01/2012Revised to suit client comments Luke Whitehouse/

    Entura

  • 8/13/2019 Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

    3/12

    Revision: 2

    Page 3 of 12

    Substation Design Manual

    Chapter 17 Substation Layouts and Facilities Outdoor

    Document Number

    D2010/287838

    Reference documents

    Documents listed below are relevant to this chapter of the Power & Water Corporation (PWC)

    Substation Design Manual. Each reference shall be followed by its list number E.g.: [1]. Anylisted reference which has a later edition will take precedence unless indicated otherwise.

    [1] AS 2067 Substations and high voltage installations exceeding 1 kV a.c.

    [2] ESAA National Guidelines for Prevention of Unauthorised Access toElectricity Networks

    [3] ENA EG1 Substation Earthing Guide

    [4] ESAA Substation Earthing Guide

    [5] AS 1940 The storage and handling of flammable and combustible liquids

    [6] ESAA (series) Guidelines for Oil Containment in the Electrical Supply Industry

    [7] IEEE 980 IEEE Guide for Containment and Control of Oil Spills in Substations

    [8] AS 1379 Specification and supply of concrete

    [9] AS 1478.1 Chemical admixture for concrete, mortar and grout - Admixturesfor concrete

    [10] AS 3600 Concrete structures

    [11] AS 3610 Formwork for concrete

    [12] AS 3799 Liquid membrane - forming curing compounds for concrete

    [13] AS 3972 Portland and blended cements

    [14] AS/NZS 4671 Steel reinforcing materials

    [15] AS 1726 Geotechnical site investigations

    [16]AS/NZS 3725 Design for installation of buried concrete pipes

    [17] AS 1597.2 Precast reinforced concrete box culverts - Large culverts (from1500 mm span and up to and including 4200 mm span and4200 mm height)

    [18] AS 4198 Precast concrete access chambers for sewerage applications

    [19] AS 2758 Aggregates and rock for engineering purposes (Series)

    [20] AS 1939 Degrees of protection provided by enclosures for electricalequipment (IP Code)

    [21] AS 4282 Control of the obtrusive effects of outdoor lighting

  • 8/13/2019 Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

    4/12

    Revision: 2

    Page 4 of 12

    Substation Design Manual

    Chapter 17 Substation Layouts and Facilities Outdoor

    Document Number

    D2010/287838

    [22] AS/NZS 3000 Electrical Installations - Wiring Rules

    [23] IEC 61936-1 Power Installations exceeding 1 kV a.c. Part 1: Common rules

    [24] AS/NZS 2312 Guide to the protection of structural steel against atmosphericcorrosion by the use of protective coatings

    [25] AS/NZS 2373 Electric cables - Twisted pair for control and protection circuits

    [26] AS 2650 Common specifications for high-voltage switchgear andcontrolgear standards (IEC 60694)

    [27] AS 2870 Residential slabs and footings

    [28] AS/NZS 3008.1.1 Electrical Installations - Selection of cables - Cables for alternating

    voltages up to and including 0.6/1 kV - Typical Australianinstallation conditions

    [29] AS/NZS 3947.3 Low voltage switchgear and controlgear - Switches, disconnectors,switch-disconnectors and fuse-combination units

    [30] AS 4100 Steel Structures

    [31] AS/NZS 61000 Electromagnetic compatibility (Series)

    [32] AS 62271.200 High-voltage switchgear and controlgear - A.C. metal-enclosedswitchgear and controlgear for rated voltages above 1 kV and up

    to and including 52 kV (IEC 62271-200, Ed. 1 (2003) MOD)

    [33] AS 62271.201 High-voltage switchgear and controlgear - AC insulation-enclosedswitchgear and controlgear for rated voltages above 1 kV and upto and including 52 kV

    [34] AS 62271.301 High voltage switchgear and controlgear - Dimensionalstandardization of terminals

    [35] AS 2791 HV switchgear and controlgear - use and handling of SF6in HVswitchgear and controlgear

    [36] AS/NZS 1768 Lightning protection

    [37] D2010/287823 Chapter 1 - 11 or 22 kV Metal Clad Switchgear

    [38] D2010/287831 Chapter 6 - HV Cables and Conductors

    [39] D2010/287859 Chapter 15 - Earthing

    [40] D2010/287840 Chapter 19 - AC Supply

    [41] D2010/287847 Chapter 25 - Substation Signage

    [42] D2010/287851 Chapter 28 - Security

    [43] XXX Chapter 30 - 66 kV Gas Insulated Metal Enclosed Switchgear

  • 8/13/2019 Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

    5/12

    Revision: 2

    Page 5 of 12

    Substation Design Manual

    Chapter 17 Substation Layouts and Facilities Outdoor

    Document Number

    D2010/287838

    Table of Contents

    17.1 Single Line Diagram - Initial Development ................................................................. 617.2 Single Line Diagram - Ultimate Development ............................................................. 717.3 Fencing and Gates ................................................................................................... 717.4 Switchyard Lighting ................................................................................................. 817.5 Switchyard Civil Works ............................................................................................. 817.6 Ducts and Trenches ................................................................................................. 917.7 Transformer Bunding ............................................................................................. 1017.8 Oil Containment .................................................................................................... 1017.9 Fire Walls ............................................................................................................. 1117.10 Transformer Spacing ............................................................................................. 1117.11 Switchyard AC Supply ............................................................................................ 1217.12 Fire Protection ...................................................................................................... 12

  • 8/13/2019 Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

    6/12

    Revision: 2

    Page 6 of 12

    Substation Design Manual

    Chapter 17 Substation Layouts and Facilities Outdoor

    Document Number

    D2010/287838

    17.1 Single Line Diagram - Initial Development

    The typical initial development single line diagram of the substation is shown in the drawing

    B10-12014.

    The 66 kV plant shall be an outdoor air insulated switchyard arrangement. The initial

    development shall comprise:

    Two (2) 66 kV line circuits

    A single 66 kV busbar with two (2) 66 kV bus section circuit breakers and

    disconnectors to form three (3) bus sections, Bus A, Bus B and Bus C

    Two (2) 66/11 or 66/22 kV power transformers, with provision for a third transformer

    For further details on 66 kV indoor Gas Insulated Metal Enclosed Switchgear refer to[43].

    The 11 or 22 kV plant shall be an indoor metal clad switchboard arrangement. For further

    details refer to[37].Initial development shall consist of a single busbar with two (2) sections.

    Each 11 or 22 kV bus section shall have:

    o One (1) incoming circuit breaker

    o Five (5) outgoing feeder circuit breakers

    o One (1) capacitor banks circuit breaker

    o One (1) auxiliary transformer/outgoing feeder circuit breaker

    One (1) bus section circuit breaker on the right hand side of each bus when viewed

    from the front

    A cable connection chamber shall be installed at the left hand end of Bus 1, when viewed from

    the front, to facilitate future connection of ring bus cables.

    As w e l l as the above req u i reme nts the re may a l so be a need to supp ly f ac il i t ie s toc onne c t a Nom ad s ubs t a t io n i n t h e e ven t o f a t r an s fo rme r and equ i pmen t f a i l u reRe fe r to the s cope o f w o rks f o r f u r the r de ta i l sThe designer shall consider all aspects of civil and primary construction and installation of the

    future equipment in the design as described in section17.2.The initial substation design shall

    not impede on the ease of the installation of the future equipment.

  • 8/13/2019 Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

    7/12

    Revision: 2

    Page 7 of 12

    Substation Design Manual

    Chapter 17 Substation Layouts and Facilities Outdoor

    Document Number

    D2010/287838

    17.2 Single Line Diagram - Ultimate Development

    The typical single line diagram of the ultimate substation is shown in drawings B10-12015 and

    B10-12016.

    Provision for installation of a third incoming transmission line and a third 66 kV transformer

    shall be made as indicated on the SLD. This will enable PWC to increase the capacity of its

    substation with minimal disruptions to the operation of the existing equipment.

    The designer shall consider the construction of transformer foundations, bund walls and all the

    other components of the transformer circuit.

    The space allowed on site for the future equipment shall be sufficient to install equipment of

    the same type as the equipment being installed.

    Foundat i ons f o r f u tu re sw i t chyard equ ipment f o rm ing par t o f the u l t imatedeve lopment sha l l no t be i n s ta l l ed un le s s ca l l ed fo r i n the s cope o f wo rks f o r thespec i f i c pro jec tUltimate development of the 11 or 22 kV Switchboard will include the installation of a third bus

    section (No. 3) and connection of cable from this section to No. 1 section to form a ring bus.

    17.3 Fencing and Gates

    Due to the high voltages within the PWC substations, any access by unauthorised personnel

    can result in loss of life or serious injury and damage to plant items. To prevent unauthorised

    access PWC substations shall have adequate fencing and locked gates. Refer to AS2067 [1]

    Section 5.2. An emergency door/gate shall be provided adjacent to the main gate for the use in

    emergency evacuation. This door shall have a quick release button that can only be activated

    from the inside and shall not allow personal to enter into the site.

    All security fences and gates shall be designed in accordance with[1] and[2].

    To reduce the risk associated with step and touch potentials during a fault, fences and gates

    shall be earthed to the main earth grid in accordance with[1], [3],and[4].

    The type of fence shall be TG/CE anti climb, 4 barbed cyclone fence.

    Othe r se cu r i t y m easu re s sha l l be se l e c ted i n ac co rdance w i th the c r i t e r i a s e t ou t i nthe s cope o f wo rks f o r the par t i cu l a r s i t e , also refer to [42] for further details onsubstation security.

  • 8/13/2019 Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

    8/12

    Revision: 2

    Page 8 of 12

    Substation Design Manual

    Chapter 17 Substation Layouts and Facilities Outdoor

    Document Number

    D2010/287838

    17.4 Switchyard Lighting

    Switchyards and substations shall have sufficient lighting to allow personnel to move around

    the switchyard and operate equipment safely at night.

    The designer shall perform lux level calculations to ensure that 20 lux is maintained throughout

    the switchyard at ground level.

    Additional lighting shall be provided at places where particular hazard existed such as stairs or

    step changes in ground level.

    The outdoor lights shall be of industrial type, and illumination shall cover the entire switchyard

    area and the property boundary fence.

    The lighting shall be designed such that the light spill does not disturb neighbouring areas.

    Substation yard lights shall have High Pressure Sodium bulbs and a minimum of IP56 rating

    and comply with[20] and[21].

    If hinged mast lights are used, the designer shall ensure that the light does not impinge on the

    clearances around any of the equipment while in motion.

    The outdoor lighting shall not be on a single circuit. Lighting shall also be on a separate circuit

    to the outdoor GPOs.

    Switchyard lighting shall not be mounted on lightning protection masts.

    17.5 Switchyard Civil Works

    Fo r fu l l de s c r i p t i on o f s i t e c i v i l r equ i rements re fe r to p ro je c t spec i f i c t e chn i ca ldo cumen ta t i o n and s c ope o f wo r kThe civil works that shall be undertaken for construction of new substations or switchyards shall

    cover, but not be limited to:

    Full geotechnical investigation shall be performed at all new sites in accordance with[15]

    Permanent datum points shall be installed on the site based on geotechnical

    investigations

    The site shall be cleared of any vegetation and other materials

    Earth works

    Slopes, crowns and ditches shall be excavated and filled to ensure satisfactory storm

    water drainage of the site. The installation and design of pipes, culverts and pits shall

    be in accordance with[16], [17] and [18].PWC has a preference for a near level site

    where possible. Where a gradient is required for drainage a fall of 1:50 shall be used.

  • 8/13/2019 Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

    9/12

    Revision: 2

    Page 9 of 12

    Substation Design Manual

    Chapter 17 Substation Layouts and Facilities Outdoor

    Document Number

    D2010/287838

    The site shall be compacted to achieve appropriate soil strength. Consideration shall be

    given to operation and maintenance equipment that shall be driven onto the site when

    designing the switchyard civil works.

    Substation base layer and finishing - installation of loose crushed granite or other form

    of rock to a nominal depth of 100 mm, using a maximum of 20 mm aggregate size on

    the switchyard surface to provide acceptable step and touch voltages. The layer shall be

    designed in accordance with[19].Refer to[39] for earthing design details.

    Road works to ensure that access roads and substation roads are suitable for transport

    of power transformers and crane as the largest onsite equipment and suit the turning

    radius of low loader for road used to transport transformers

    Power transformer foundations and bunds - The power transformer foundations and

    bund walls shall be connected to the oil containment system. Refer to17.7 and17.9

    Control building and its foundations

    Cable ducts/trenches - The main cable duct shall be installed from the substation control

    building to the outdoor yard equipment. Refer to17.6.Below ground basement cable

    ducts shall use, as a minimum, water tight rubber membranes to maintain a seal from

    external water ingress. Additional concrete admixtures to increase the concrete

    waterproofing may also be applied if the designer considers the benefits advantageous

    and economical, however, this does not preclude the use of the rubber membrane.

    Modular buildings may be used as long as they are designed to a similar standard.

    17.6 Ducts and Trenches

    A main cable duct shall be installed from the outside of the control room to the switchyard

    outdoor equipment. Subsidiary cable ducts shall be installed along each bay of equipment. The

    ducts shall be constructed from inverted precast concrete box culverts with appropriate checker

    plate covers and be adequate to support all types of cables including control. LV cables shall be

    supported on the walls of the duct by means of a cable tray assembly. Buried PVC conduit shall

    connect the concrete duct to individual items of equipment.

    Ducting shall be designed to allow stormwater to be drained away from the switchroom via

    gravity. In situations where gravity draining is not possible, such as a basement, a sump and

    sump pump may be provided. The duct shall have a sufficient width to allow for a person to

    stand inside the duct as well as room for mounting two sets of cable trays. Refer to drawings

    XXX for an example of a typical installation. Also refer to[38] for cabling segregation details.

    Transformer 11 or 22 kV cabling shall also be installed in concrete ducts or conduits, using

    separate ducts or conduits for each transformer.

    The duct covers shall have sufficient strength to withstand the load of heavy vehicles when the

    trench crosses a substation road or accessway.

  • 8/13/2019 Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

    10/12

  • 8/13/2019 Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

    11/12

    Revision: 2

    Page 11 of 12

    Substation Design Manual

    Chapter 17 Substation Layouts and Facilities Outdoor

    Document Number

    D2010/287838

    Bund drainage system

    Oil/water separator

    An environmental risk/impact assessment shall be undertaken for every new oil/water separatorat a zone substation site to assess the risk of off-site impacts arising from discharge of water

    from the oil/water separator and must be designed to trap oil on site. PWC has a preference for

    passive oil/water separators. The units shall:

    be suitable for a 1 in 50 year storm

    allow a maximum of 30 ppm suspended solids at its outlet

    allow a maximum of 10 mg/L of oil at its outlet

    17.9 Fire Walls

    [1] suggests that designers use ENA 18-2008 as a guideline for fire protection of HV

    substations. This standard establishes that the Building code of Australia (BCA) class 8

    requirements can be used as a guide for buildings used for HV installations. Table 6.1 of[1]

    provides a guide for outdoor transformer segregation.

    Where a fire hazard exists, HV substation enclosures within or adjacent to buildings must be

    designed with a minimum FRL 120/120/120 fire rating. Fire barriers providing FRL 120/120/120

    are to be used where this minimum cannot be met. Where a transformer fire is part of the riskassessment, then a fire rating greater than 120 minutes needs to be considered.

    Sufficient space shall be provided around the transformer to the walls of the enclosure or fire

    wall for the purpose of operation and maintenance access.

    The structural adequacy, integrity of barrier material and insulative materials must be

    maintained in the event of a fire for the FRL period.

    The FRL applies in the same way for the enclosure and any penetrations or opening in the

    enclosure.

    Flame traps shall be provided inside the bund of the transformer through the use of a non-

    flammable pipe within a pit in the bund.

    17.10Transformer Spacing

    There shall be sufficient spacing between the power transformer bunds to provide safety

    clearances and service access to equipment in the HV busbar areas, the lines circuits and

    transformer circuits.

    Transformers access shall be free from line crossings to allow the transporting and lifting of

    transformers and buildings without the restrictions presented by overhead lines.

  • 8/13/2019 Chapter 17 - NT PWC SDM Substation Layouts and Facilities - Outdoor Section Rev 2 - 17-1-2012

    12/12

    Revision: 2

    Page 12 of 12

    Substation Design Manual

    Chapter 17 Substation Layouts and Facilities Outdoor

    Document Number

    D2010/287838

    17.11Switchyard AC Supply

    A 3 phase 300 A weatherproof junction box shall be installed adjacent to transformers for

    supplying power to transformer oil filtering equipment.

    15 A outlets shall be strategically positioned throughout the yard to provide power for operation

    and maintenance. Refer to[40] for further details for AC Supply.

    17.12Fire Protection

    Fire hydrants shall be strategically located around the switchyard and transformer bays.

    Thermal detectors shall be installed in the transformer area and connected to the substation

    fire incident panel (FIP).