CHAPTER 1 GENERAL - o.b5z.neto.b5z.net/i/u/10069179/f/ecm_nec_webinarpresentation.pdf ·...
Transcript of CHAPTER 1 GENERAL - o.b5z.neto.b5z.net/i/u/10069179/f/ecm_nec_webinarpresentation.pdf ·...
Slide 2©MikeHolt.com
Dedication
I would like to take this moment to thank God for giving me the opportunity and skill to help others.
210.8 GFCI Protection
Requirement addresses the
accessibility of the test and reset
functions of GFCI devices.
210.8(B)(6) GFCI Protection
Receptacles Indoor Wet Location
(6) Indoor wet locations. All 15A and
20A, 125V receptacles installed
indoors in wet locations must be
GFCI protected.
210.8(B)(7) GFCI Protection
Locker Room Receptacles
(7) Locker Rooms. All 15A and 20A,
125V receptacles installed in locker
rooms with associated showering
facilities must be GFCI protected.
210.12 Arc-Fault Circuit-
Interrupter Protection—Dwelling
Units Changes address fire alarm circuiting,
use of Type MC cable, concrete-
encased raceways, and branch circuit
extensions or modifications.
210.12(B) Branch-Circuit
Extensions or Modifications—
Dwelling Units. Where branch-circuit wiring is modified, replaced, or
extended in any of the areas specified in 210.12(A), the branch circuit must be protected by:
(1) A listed combination AFCI located at the origin of the branch circuit; or
(2) A listed outlet branch circuit AFCI located at the first receptacle outlet of the existing branch circuit.
225.27 Raceway Seal
Underground raceways (used or
unused) entering buildings or
structures must be sealed or plugged
to prevent moisture from contacting
energized live parts [300.5(G)].
250.52(A) Electrodes Permitted
for Grounding
Rule explaining when a structural metal
frame can serve as a grounding
electrode was changed…again, and
the requirements for concrete
encased electrodes, ground rods, and
ground plates clarified.
250.52(A)(3)(2) Concrete
Encased Electrode
Note: Concrete containing insulation,
vapor barriers, films or similar items
separating it from the earth isn’t
considered to be in “direct contact”
with the earth.
250.121 Use of Equipment
Grounding Conductors
An equipment grounding conductor
isn’t permitted to be used as a
grounding electrode conductor.
300.11(A)(2) Nonfire-Rated
Ceiling Assemblies
Rule requiring identification of electrical
ceiling support wires expanded.
404.2(C) Switches Controlling
Lighting
New rule requires a neutral conductor
at nearly every switch point.
404.2(C) Switches Controlling
Lighting
Switches controlling line-to-neutral
lighting loads must have a neutral
provided at the switch location.
406.4(D) Receptacle
Replacements
Requirement addresses the
replacement of receptacles in areas
requiring AFCI protection, tamper-
resistant receptacles, or weather-
resistant receptacles.
406.4(D) Receptacle
Replacements
(4) Arc-Fault Circuit Interrupters. Effective January 1, 2014, where a receptacle outlet is supplied by a branch circuit that requires arc-fault circuit-interrupter protection [210.12(A)], a replacement receptacle at this outlet must be one of the following.
406.4(D)(4) Receptacle
Replacements
(1) A listed (receptacle) outlet branch-circuit type arc-fault circuit-interrupter receptacle.
(2) A receptacle protected by a listed (receptacle) outlet branch-circuit type arc-fault circuit-interrupter type receptacle.
(3) A receptacle protected by a listed combination type arc-fault circuit interrupter type circuit breaker.
406.4(D) Receptacle
Replacements
(5) Tamper-Resistant Receptacles. Listed tamper-resistant receptacles must be provided where replacements are made at receptacle outlets that are required to be tamper resistant elsewhere in this Code.
406.4(D) Receptacle
Replacements
(6) Weather-Resistant Receptacles.
Weather-resistant receptacles must be
provided where replacements are made
at receptacle outlets that are required to
be so protected elsewhere in the Code.
406.12 Tamper-Resistant
Receptacles in Dwelling Units
The required locations for tamper-
resistant receptacles in dwellings
lessened, and a clarification made.
406.12 Tamper-Resistant
Receptacles in Dwelling Units
406.12 Tamper-Resistant Receptacles in
Dwelling Units. All nonlocking type 15A
and 20A, 125V receptacles in the
following areas of a dwelling unit [210.52]
must be listed as tamper resistant.
406.12 Tamper-Resistant
Receptacles in Dwelling Units
Ex: Not required to be tamper-resistant:
(1) Recept located more than 5½ ft above the floor.
(2) Recept that are part of a luminaire or appliance.
(3) Recept located within dedicated space for an appliance that in normal use isn’t easily moved.
(4) Nongrounding receptacles used for replacements as permitted in 406.4(D)(2)(a).
406.13 Tamper-Resistant
Receptacles in Guest Rooms and
Guest Suites
Requirement for tamper-resistant
receptacles added.
406.13 Tamper-Resistant
Receptacles in Guest Rooms and
Guest Suites
Nonlocking type 15A and 20A, 125V
receptacles in guest rooms and guest
suites must be listed as tamper
resistant.
406.14 Tamper-Resistant
Receptacles in Child Care Facilities
Requirement for tamper-resistant
receptacles added.
406.14 Tamper-Resistant
Receptacles in Child Care Facilities
Nonlocking type 15A and 20A, 125V
receptacles in child care facilities
must be listed as tamper resistant.
517.16 Receptacles with
Insulated Grounding Terminal
Receptacles with insulated grounding
terminals no longer permitted in a
patient care area.
690.47 Grounding Electrode
System
Requirements for PV grounding
electrode systems were greatly
revised.