CHAPTER 1
-
Upload
bennie-bailey -
Category
Documents
-
view
77 -
download
2
Transcript of CHAPTER 1
![Page 1: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/1.jpg)
Power Systems Gate Material Vignan University
CHAPTER-1
PERFORMANCE OF TRANSMISSION LINES
1. TRANSMISSION LINE PARAMETERS
Basic Structure of a Power System
The basic structure of a power system is shown in Fig. 1.1.
Fig. 1.1 A typical power system.
It contains a generating plant, a transmission system, a subtransmission system and a
distribution system. These subsystems are interconnected through transformers T1 , T2 and T3 . Let us
consider some typical voltage levels to understand the functioning of the power system. The electric
power is generated at a thermal plant with a typical voltage of 22 kV (voltage levels are usually
specified line-to-line). This voltage is stepped up to 400 kV through transformer T1 for power
transmission. Transformer T2 steps this voltage down to 66 kV to supply power through the sub
transmission line to industrial loads that require bulk power at a higher voltage. Most of the major
industrial customers have their own transformers to step down the 66 kV supply to their desired
levels. The purpose of these change in voltage is to minimize the transmission ine cost for a given
power level. Distribution systems are designed to operate for much lower power levels and are
supplied with medium level voltages.
The power distribution network starts with transformer T3, which steps down the voltage from
66 kV to 11 kV. The distribution system contains loads that are either commercial type (like office
buildings, huge apartment complexes, hotels etc) or residential (domestic) type. Usually the
commercial customers are supplied power at a voltage level of 11 kV whereas the domestic
Dept. of Electrical Engineering Page 1
![Page 2: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/2.jpg)
Power Systems Gate Material Vignan University
consumers get power supply at 400-440 V. Note that the above figures are given for line-to-line
voltages. Since domestic customers get single-phase supplies, they usually receive 230-250 V at their
inlet points. While a domestic customer with a low power consumption gets a single-phase supply,
both industrial and commercial consumers get three-phase supplies not only because their
consumption is high but also because many of them use three-phase motors. For example, the use of
induction motor is very common amongst industrial customers who run pumps, compressors, rolling
mills etc.
The main components of a power system are generators, transformers and transmission lines.
Necessity of Transmission Lines:- Bulk amount of powers generation could able to produce on
economical basis by employing synchronous generators at remote locations. The bulk amount of
power from the remote generating station could able to be carried out to the load centre by using
suitable network and the network is called transmission network (or) transmission lines.
Necessity of Extra High Voltages for transmission system:
1. The size of the conductor is reduced so that the cost of the conductor is reduced. Ex:- For the
same power, same length and same material the size of the conductor will become 1/n th of
original size as the operating voltage increased by n times.
2. The transmission line loss will be reduced Ex:- For the same power, same length, same
material the copper loss becomes 1/nth to that of original loss as the voltage increased by n
times.
Special Case: As the level of voltage is increasing beyond certain limit, for the same amount of
power to be transmitted, the extra cost required for insulation is more than the saving in conductor
cost, so the selection of operating voltage to transmit the power is the compromise between
in saving of conductor cost and extra cost required for insulation.
Selection of the size of conductor in transmission lines:- In transmission lines there are no
taping (or) consumers in the middle. So the current throughout the transmission line is same from
the generating station to the load centre. Hence the conductor is designed based on current
carrying capacity (or) constant current density. This is up to 220kv transmission line only.
In case of the voltages beyond 220kv, the concept of corona is predominant than that of current
carrying capacity. So the transmission lines are designed based on concept or corona
Dept. of Electrical Engineering Page 2
![Page 3: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/3.jpg)
Power Systems Gate Material Vignan University
Types of Conductors:-
Mainly we are having four types of conductors.
1. Solid conductors. 2. Homogeneous Stranded conductors.
3. Composite Stranded conductors. 4. Bundled conductors
Solid Conductors:-
Fig 1.2 Solid conductor
Solid conductors is single piece of conductor
These conductors may be of copper (or) Aluminum
It is having high mechanical strength and tensile strength
Circular solid conductor will be preferred to make electrical field same
throughout the surface of the conductor.
There is no application of solid conductors as transmission lines
Flat (or) solid conductors are used for power transformer winding.
Homogeneous Stranded Conductors:- A number of strands are taken and are twisted
together to increase the current carrying capacity by maintaining the same operating voltage.
Fig 1.3 Stranded conductor
All strands are of same material
Compared to stranded conductor it is having high mechanical strength and
low tensile strength.
Stringing is easy in stranded conductor so transportation is easy
Composite Stranded Conductor:- Strands of different material are twisted together to form
the stranded conductor. Its purpose is to improve the tensile strength
Ex:- ACSR(Aluminium conductor steel reinforced)
Dept. of Electrical Engineering Page 3
![Page 4: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/4.jpg)
Power Systems Gate Material Vignan University
As the layer size in increased the number of strands will be increases in the
following manner.
1+6+12+18+24+30
d- is the diameter of each conductor and ‘n’ is the number of layers then
diameter of stranded conductor is
D=(2n-1)d
Generally ACSR conductor is represented by x/y
x← number of Al strands (or) steel strands
y← number of Al strands (or) steel strands
In Power conductors the number of Aluminum ¿ number of steel strands
Bundled Conductors:-
When voltage is above 230KV, corona loss and interference with the communication
lines is more. Corona occurs when the surface potential gradient of a conductor exceeds the
dielectric strength of the surrounding air. This causes ionization of the area near the
conductor. The high voltage surface gradient is reduced by using two or more conductors per
phase in close proximity. This is called conductor bundling. The conductors are bundled in
groups of two, three or four as shown in below Fig. The conductors of a bundle are separated
at regular intervals with spacer dampers that prevent clashing of the conductors and prevent
them from swaying in the wind.
GMR=selfGMD=Ds ,2b=
4√ (D s×d )2=√D s×d
Fig: Two conductors per phase
D s, 3 b=
9√( Ds×d×d )3=3√D s×d×d
Fig: Three conductors per phase
Dept. of Electrical Engineering Page 4
![Page 5: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/5.jpg)
Power Systems Gate Material Vignan University
D s, 4 b=
16√ (D s×d×√2d×d )4=1. 094√ Ds×d×d×d
Fig: Four conductors per phase
Parameters of Transmission lines:-
Parameters are:-
Resistance:- It is due to the property of conductor that it opposes the flow of current
Inductance:- Due to magnetic field around the conductor
Capacitance:- Due to electrostatic field around the conductor
Resistance:-
D.C resistance of a wire is given by Rdc=
ρlA
Ω
Where ρ is the resistivity of the wire in Ω - m, l is the length in meter and A is the
cross sectional area in m2. However the resistance of an overhead conductor is not the same
as that given by the above expression. When alternating current flows through a conductor,
the current density is not uniform over the entire cross section but is somewhat higher at the
surface. This is called the skin effect and this makes the ac resistance more than the dc
resistance. Moreover in a stranded conductor, the length of each strand is more that the length
of the composite conductor. Temperature also affects the resistivity of conductors.
R2
R1
=T+t2
T+t1
Where R1 and R2 are resistances at temperatures t1 and t2 respectively and T is a
constant that depends on the conductor material and its conductivity.
Inductance:- Current carrying conductor produces a magnetic field around it the magnetic
flux lines are concentric with their direction specified by Maxwells right hand thumb rule
L= λI
Dept. of Electrical Engineering Page 5
![Page 6: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/6.jpg)
Power Systems Gate Material Vignan University
where L is the inductance in Henry, λ is the flux linkage in Weber-turns and I is the phasor
current in Ampere
Internal inductance per unit length is
Lint=12×10−7
Fig:- Cross section of a round conductor
Inductance between any two points outside the conductor
Lext=2×10−7 lnD2
D1 H/mt
Inductance of single phase line
L1=( 12+2×ln
Dr1
)×10−7
H/mt
L1=2×10−7 ln
D
r1'
H/mt r1' =0 .7788 r 1
Loop Inductance
r1=r2=rLloop=L1+L2=4×10−7 ln
D
r 'H/mt
Inductance of 3-phase line with Asymmetrical spacing (Transposed)
L1=2×10−7 ln3√ Dab Dbc Dca
r ' H/mt
GMD=3√Dab Dbc D caFig:- Portion of a transposed line
If lines are of equilateral spacing
Then Dab=Dbc=Dca=D
Dept. of Electrical Engineering Page 6
![Page 7: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/7.jpg)
Power Systems Gate Material Vignan University
La=2×10−7 lnD
r 'H/mt
Capacitance:-
Capacitance is due to Electrostatic field around the conductor
C=qv
Where C is the capacitance in Farad, q is charge in coulombs, ν is potential difference
volts.
Capacitance of a single phase circuit:-
C12=πε
ln ( dr )
F/mt
Capacitance to neutral:-
C1n=2 πε
ln ( dr )
F/mt
Capacitance of 3-phase line with Asymmetrical spacing(Transposed):-
Can=2 πε
ln (GMDr )
F/mt
With equal spacing Then Dab=Dbc=Dca=D
GMD=3√Dab Dbc D ca=D
Dept. of Electrical Engineering Page 7
GMD=3√Dab Dbc D ca
![Page 8: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/8.jpg)
Power Systems Gate Material Vignan University
Can=2 πε
ln (Dr )
F/mt
Effect of earth on transmission line capacitance:-
Earth surface is considered as a equipotential surface To considered the effect
of earth we are considering image conductors below the ground at a depth equal
to the height of the overhead conductor above the ground with opposite
charge(Method of images)
Cxy=πε
lnDr−ln
H xy
H xx F/mt
Cn=2 πε
lnDr
− lnH xy
H xx F/mt
If conductors are very much above the ground then Hxy=Hxx
With the effect of earth capacitance increases.
For Bundled conductors:-
L1=2×10−7 lnGMDGMR H/mt
Can=2 πε
ln (GMDGMR )
F/mt
S.No Line Description R L XL C Xc
1 Length increases Increases Increases Increases Increases Decreases
2Distance of
separation increasesNo relation Increases Increases Decreases Increases
3Radius of conductor
increasesDecreases Decreases Decreases Increases Decreases
4 Symmetrical spacing No relation decreases Decreases Increases Decreases
5Unsymmetrical
spacingNo relation Increases Increases Decreases Increases
Dept. of Electrical Engineering Page 8
![Page 9: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/9.jpg)
Power Systems Gate Material Vignan University
6Effect of earth taken
into accountNo relation No change No change Increases Decreases
7Height of the
conductor increasesNo relation No change No change Decreases Increases
2. PERFORMANCE OF TRANSMISSION LINES:-
Synopsis:-
The important considerations in the operation of Transmission line are voltage drop,
Power loss, Efficiency
The performance of transmission lines depends on the R,L,C and conductor - G
Effect R - Voltage drop- IR and power loss -I2R
Effect L - Voltage drop-2π fl ( quadrature with the current)
Effect C - Charging current=
VXC
=V 2 π fc
Effect G - It is due to leakage current it is predominant only during bad
Whether conditions (so we are neglecting G)
In Overhead lines reactance effects are more
In Underground cables reactance effects are small and capacitance effects are more.
Efficiency:-
η= outputoutput+ losses
%η=Pr
Pr+3 I 2 R×100
(3-phase)
By knowing the efficiency of the system we can understand how much amount of
power loss in the form of heat.
Losses in the network depend on the resistance.
In case of transmission lines R is less (area of cross section of conductor is more) so
power loss in transmission lines is very less (about 2-5%).
In distribution network size of conductor is less so resistance is more losses will be
more, so losses in the distribution system will be more(about 8-10%)
Dept. of Electrical Engineering Page 9
![Page 10: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/10.jpg)
Power Systems Gate Material Vignan University
Voltage Regulation:- It is the change of voltage at receiving end from No load to full load
while keeping the sending end voltage constant and also supply frequency made as constant
|V ro|= No load receiving end voltage
|V r|= Full load receiving end voltage
∈=|V ro|−|V r|
As the load at the load end increases from no load to full load the mechanical
input will also increases. So that the the mechanical input is equal to the electrical
output which will result as the synchronous machine is working at synchronous
speed.
However the excitation will remain same so that the sending end voltage is
Constant
Percentage regulation 2.1
The performance of Transmission will be analyzed in % regulation of line
rather than actual regulation
By knowing the regulation of line we can understand the change of voltage
from no load to full load.
Voltage drop =|V s|−|V r|
In transmission lines due to shunt capacitance the regulation of line is not same as
voltage drop. Because |V Ro|∉|V s|
The performance of transmission line will be studied in terms of regulation rather
than the efficiency because of shunt capacitance effect of the line.
Wavelength of transmission line:-
For f =50Hz (where f is the frequency of supply)
fλ=υ
Dept. of Electrical Engineering Page 10
%∈=|V ro|−|V r|
|V r|×100
![Page 11: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/11.jpg)
Power Systems Gate Material Vignan University
λ = wavelength i.e the length of the line
υ =velocity of the wave=3×108m/sec
∴ λ= υ
f=3×108
50=6000
km 2.2
Classification of Transmission lines:-
Transmission lines are classified based on the physical length of the line at specified
frequency (50Hz/60Hz)
1. Short Transmission lines length<80KM Capacitance effect is ignored
(R and L are lumped)
2. Medium Transmission lines length (80-250)KM Capacitance effect is considered
(R,L and C are lumped)
Long Transmission lines length>250KM Capacitance effect is
considered
(R,L and C are lumped for steady state)
(R,L and C are lumped for Transient behaviour)
ABCD PARAMETSRS:-
Consider the power system shown in Fig. 2.1. In this the sending and receiving end
voltages are denoted by VS and VR respectively. Also the currents IS and IR are entering and
leaving the network respectively. The sending end voltage and current are then defined in
terms of the ABCD parameters as
2.2
I S=CV R+DI R 2.3
Dept. of Electrical Engineering Page 11
V S=AV R+BI R
![Page 12: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/12.jpg)
Power Systems Gate Material Vignan University
Fig. 2.1 Two port representation of a transmission network.
VS ,IS and VR,IR are per phase quantities.
If A=D the network is symmetric
If AD-BC=1 the network is Reciprocal (or) bilateral
A network is said to be Reciprocal the ratio of response to excitation will be
same even though their positions are interchanged.
Open circuit at receiving end:-
From (2.2) we see that
A=V s
V R
|I R=0 2.4
This implies that A is the ratio of sending end voltage to the open circuit receiving end
voltage. This quantity is dimension less.
C=I s
V R
|I R=0 =Open circuit admittance in mhos
C=Y=Wc
2.5
Dept. of Electrical Engineering Page 12
[V S
I S]=[A B
C D ] [V R
I R]
[V R
I R]=[A B
C D ]−1 [V S
I S]
V S
I S
= AC
![Page 13: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/13.jpg)
Power Systems Gate Material Vignan University
%∈=|V Ro|−|V R|
|V R|×100
%∈=|V S
A|−|V R|
|V R|×100
Short Circuit at receiving end:-
B=V s
I R
|V R=0Ω
2.6
i.e., B, given in Ohm, is the ratio of sending end voltage and short circuit receiving end
current. In a similar way we can also define
D=I s
I R
|V R=0 (unit less) 2.7
Short circuit impedance in ohms
V S
I S
= BD 2.8
Open circuit and short circuit conditions are ideal cases during load conditions, the
transmission line will have the effect of series impedance and shunt admittance.
The combined effect of the line will be represented as characteristic impedance ZC
Characteristic impedance ZC=2.5×2.8
V S
I S
×V S
I S
= AC
× BD
V S
I S
=√ AC
× BD
ZC=V S
I S
=√ BC
ZC=√ Z sc
Y oc
=√Zsc×Zoc
Dept. of Electrical Engineering Page 13
B=Z=R+ jX
![Page 14: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/14.jpg)
Power Systems Gate Material Vignan University
2.2 SHORT LINE
The shunt capacitance for a short line is almost negligible. The series impedance is
assumed to be lumped as shown in Fig. 2.2. If the impedance per km for an l km long line is
z0 = r + jx, then the total impedance of the line is Z = R + jX = lr + jlx. The sending end
voltage and current for this approximation are given by
Fig. 2.2 Short transmission line representation
Z=R+jXL
V S=V R+ZI R 2.9
I S=I R 2.10
The A,B,C,D parameters are given by
A=D=1 , B=Z Ω and C=1 2.11
A=D & AD-BC=1 so short transmission line is symmetric and reciprocal
For short transmission line VRO=VS so voltage regulation is equal to the voltage
drop of line.
Regulation:-
%∈=|V Ro|−|V R|
|V R|×100
At No load condition IR=0 so VRo=VS
%∈=|V S|−|V R|
|V R|×100
%∈=V R+ IZ−V R
V R
×100
%∈= IZV R
×100
Dept. of Electrical Engineering Page 14
![Page 15: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/15.jpg)
Power Systems Gate Material Vignan University
From phasor diagram of Short transmission line the approximate value of Sending voltage
will be
V S=V R+ I R R cos φr±I R X sin φr
Where φr is the load power factor + for lagging power factor
_ for leading power factor
%∈=|V S|−|V R|
|V R|×100
%∈=IR R cos φr±IR X sin φr
V R
×100
%∈=%V Rcos φr±%V X sin φr
%V R=I R X
V R
×100
%V X=IR X
V R
×100
Maximum regulation will occur only for lagging power factor load
Condition for maximum regulation:-
Zero regulation will occur only for leading power factor load
Condition for zero regulation:- φr=tan−1 (R / X )
2.2 MEDIUM TRANSMISSION LINES
Medium transmission lines are modelled with lumped shunt admittance. There are two
different representations − nominal-π and nominal-T depending on the nature of the network.
These two are discussed below.
2.2.1 Nominal-π Representation
In this representation the lumped series impedance is placed in the middle while the shunt
admittance is divided into two equal parts and placed at the two ends. The nominal-π
representation is shown in Fig. 2.3. This representation is used for load flow studies, as we shall
Dept. of Electrical Engineering Page 15
φr=tan−1 ( X / R )
![Page 16: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/16.jpg)
Power Systems Gate Material Vignan University
see later. Also a long transmission line can be modeled as an equivalent π-network for load flow
studies.
Fig. 2.3 Nominal-π representation
Let us define three currents I1, I2 and I3 as indicated in Fig. 2.3. Applying KCL at nodes
M and N we get
Is I1 I2 I1 I3 IR
I S=Y2
V S+Y2
V R+ I R 2.12
V S=ZI 2+V R=Z [V RY2
+ IR ]+V R
= (YZ
2+1)V R+ZI R
2.13
Substituting (2.13) in (2.12) we get
I S=Y2 [(YZ
2+1)V R+ZI R]+Y
2V R+ I R
=Y (YZ
4+1)V R+(YZ
2+1) I R
2.14
Therefore from (2.13) and (2.14) we get the following ABCD parameters of the nominal-
π representation
A=D=(YZ2
+1)2.15
B=Z Ω 2.16
C=Y (YZ4
+1)mho 2.17
2.2.1 Nominal-T Representation
Dept. of Electrical Engineering Page 16
![Page 17: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/17.jpg)
Power Systems Gate Material Vignan University
In this representation the shunt admittance is placed in the middle and the series
impedance is divided into two equal parts and these parts are placed on either side of the shunt
admittance. The nominal-T representation is shown in Fig. 2.4. Let us denote the midpoint
voltage as VM. Then the application of KCL at the midpoint results in
Fig. 2.4 Nominal-T representation.
I S=V M Y+ I R
V S−V M
Z2
=YV M+V M−V R
Z2
Rearranging the above equation can be written as
V M= 2
YZ+4 (V S+V R ) 2.18
Now the receiving end current is given by
I R=V M−V R
Z2 2.19
Substituting the value of VM from (2.16) in (2.17) and rearranging we get
V S=(YZ
2+1)V R+Z(YZ
4+1) I R
2.20
Furthermore the sending end current is
I S=YV M+ I R 2.21
Then substituting the value of VM from (2.18) in (2.21) and solving
I R=YV R+(YZ
2+1) I R
2.22
Then the ABCD parameters of the T-network are
Dept. of Electrical Engineering Page 17
![Page 18: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/18.jpg)
Power Systems Gate Material Vignan University
A=D=(YZ2
+1) 2.23
B=Z (YZ4
+1)Ω 2.24
C=Y mho 2.25
A=D & AD-BC=1 so Medium transmission lines are symmetric and reciprocal
For Medium transmission line VRO≠VS so voltage regulation is not equal to the
voltage drop of line.
Direct calculation of ABCD parameters:-
For Series impedance:-
For shunt admittance:-
[V s
I s]=[ 1 0
Y 1 ] [V r
I r]
For medium transmission lines (Nominal Π):-
[V S
I S]=[ 1+ZY /2 ZY (1+ZY /4 ) 1+ZY /2 ] [V r
Ir]
A=1+ZY /2 B=Z
C=Y (1+ZY /4 ) D=1+ZY /2
A=D and AD−BC=1 , So the model is symmetric and reciprocal
For medium transmission lines (Nominal T):-
Dept. of Electrical Engineering Page 18
[V s
I s]=[1 Z
0 1 ] [V r
I r]
[V S
I S]=[ 1 0
Y /2 1 ][1 Z0 1 ] [ 1 0
Y /2 1 ] [V r
I r]
![Page 19: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/19.jpg)
Power Systems Gate Material Vignan University
A=1+ZY /2 B=Z (1+ZY /4 )
C=Y D=1+ZY /2
A=D and AD−BC=1 , So the model is symmetric and reciprocal
Source end capacitance:-
A=1. 0 , B=Z , C=Y and D=1+ZY
Load end capacitance:-
A=1+ZY B=Z , C=Y and D=1 .0
Sending end capacitance method is a uncompensation method.Load end capacitance
method is a overcompensated method and the both the method are not symmetric. So the
medium transmission lines are represented in either nominal T (or) nominal II
Transmission lines in Series (or) cascade:-
Dept. of Electrical Engineering Page 19
[V S
I S]=[1 Z /2
0 1 ][1 0Y 1 ][1 Z /2
0 1 ][V r
Ir]
[V S
I S]=[ 1 0
Y 1 ] [1 Z0 1 ] [V r
I r]
[V S
I S]=[1 Z
0 1 ][ 1 0Y 1 ] [V r
I r]
![Page 20: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/20.jpg)
Power Systems Gate Material Vignan University
Where
Two transmission lines are in parallel:-
In parallel transmission lines
V s1=V s 2=V s
V r 1=V r 2=V r
I S=I s 1+ I s 2 and I r=I r1+ I r2
Dept. of Electrical Engineering Page 20
[V s
I s]=[ A B
C D ] [V r
I r]
[A BC D ]=[A1 B1
C1 D1] [A2 B2
C2 D2]
[V S
I S]=[A B
C D ] [V r
I r]
![Page 21: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/21.jpg)
Power Systems Gate Material Vignan University
Where
[A BC D ]=[
A1B2+ A2 B1
B1+B2
B1 B2
B1+B2
C1+C2+( A1−A2) (D2−D1 )
(B1+B2 )D1 B2+D2 B1
B1+B2
]2.3 LONG LINE MODEL
For accurate modeling of the transmission line we must not assume that the parameters are
lumped but are distributed throughout line. The single-line diagram of a long transmission line is
shown in Fig. 2.5. The length of the line is l. Let us consider a small strip ∆x that is at a distance x
from the receiving end. The voltage and current at the end of the strip are V and I respectively and
the beginning of the strip are V + ∆V and I + ∆I respectively. The voltage drop across the strip is
then ∆V. Since the length of the strip is ∆x, the series impedance and shunt admittance are z ∆x
and y ∆x. It is to be noted here that the total impedance and admittance of the line are
Z=z×l and Y= y×l 2.26
Fig. 2.5 Long transmission line representation
From the circuit of Fig. 2.5 we see that
ΔV =Iz Δx ⇒ ΔVΔx
=Iz 2.27
Again asΔx →0 , from (2.27) we get
dVdx
=Iz 2.28
Now for the current through the strip, applying KCL we get
ΔI=(V + ΔV ) yΔx=Vy Δx+ ΔVy Δx 2.29
Dept. of Electrical Engineering Page 21
![Page 22: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/22.jpg)
Power Systems Gate Material Vignan University
The second term of the above equation is the product of two small quantities and therefore
can be neglected. For ∆x → 0 we then have
dIdx
=Vy2.30
Taking derivative with respect to x of both sides of (2.28) we get
ddx ( dV
dx )=zdIdx
Substitution of (2.30) in the above equation results
d2Vdx2
− yzV =02.31
The roots of the above equation are located at √(yz). Hence the solution of (2.31) is of the
form
V=A1 ex √ yz+A2 e− x√ yz2.32
Taking derivative of (2.32) with respect to x we get
dVdx
=A1√ yz ex √yz−A2 √ yz e−x √ yz
2.33
Combining (2.28) with (2.33) we have
I= 1Z ( dV
dx )= A1
√ zy
ex √ yz−A2
√ zy
ex√ yz
2.34
Let us define the following two quantities
ZC=√ zy Ω which is called the characteristic impedance 2.35
γ=√ yz which is called the propagation constant 2.36
Then (2.32) and (2.34) can be written in terms of the characteristic impedance and propagation
constant as
V=A1 eγx+ A2 e−γx 2.37
I=A1
ZC
eγx−A2
ZC
e−γx
2.38
Let us assume that x = 0. Then V = VR and I = IR. From (2.37) and (2.38) we then get
Dept. of Electrical Engineering Page 22
![Page 23: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/23.jpg)
Power Systems Gate Material Vignan University
V R=A1+ A2 2.39
I R=1
ZC( A1−A2 )
2.40
Solving (2.39) and (2.40) we get the following values for A1 and A2.
A1=V R+ZC I R
2 and A2=
V R−ZC I R
2
Also note that for l = x we have V = VS and I = IS. Therefore replacing x by l and substituting the
values of A1 and A2 in (2.37) and (2.38) we get
V S=V R+ZC IR
2eγl+
V R−ZC I R
2e−γl
2.41
I S=
V R
ZC
+ I R
2eγl+
V R
ZC
−IR
2e−γl
2.42
Noting that
eγl−e−γl
2=sinh γl
and
eγl−e−γl
2=cosh γl
We can rewrite (2.41) and (2.42) as
V S=V R cosh γl+ZC I R sinh γl 2.43
I S=V Rsinh γl
Zc
+ I Rcosh γl 2.44
The ABCD parameters of the long transmission line can then be written as
A=D=cosh γl 2.43
B=ZC sinh γlΩ 2.44
Dept. of Electrical Engineering Page 23
![Page 24: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/24.jpg)
Power Systems Gate Material Vignan University
c=sinh γlZC mho 2.45
A=D & AD-BC=1 so Long transmission lines are symmetric and reciprocal
For long transmission line VRO≠VS so voltage regulation is not equal to the
voltage drop of line.
Propagation constant:-
γ=√ yz
γ=√(R+ jwL )(G+ jwC )
γ=α+ jβ
α =real part = attenuation constant
β = imaginary part= quadrature constant (or) phase constant
Attenuation means fall in the magnitude of voltage and current while it is
travelling in the transmission line from sending end to the receiving end
The inductance and capacitance of transmission line will able to provide the
phase displacement so that the supply voltage and current will be travelled
from the sending end towards the receiving end and it can be understand in
terms β
For lossless transmission line (R=0, G=0)
γ=√( jwL)( jwC )= jw√ LC= jβ
Characteristic Impedance:- When the switch is closed the Transmission line is in a transient
condition and it is dealing with surge waveform so that corresponding impedance is called as
surge impedance (or) characteristic impedance.
ZC=√ zy=√ R+ jwL
G+ jwC
For loss less line Zc=√ jwL
jwC=√ L
C
Surge impedance is the characteristic impedance of a loss free line
Zc(or) Zs=400Ω for Overhead transmission lines , Zs=40Ω for Underground
Dept. of Electrical Engineering Page 24
![Page 25: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/25.jpg)
Power Systems Gate Material Vignan University
cables.
During transient condition of the line the transmission line will be neither
inductive nature nor capacitive. So that the nature of the characteristic
impedance is to be treated as resistive.
Characteristic Impedance loading(or) Surge impedance loading:-
It is the loading of the line where the load impedance is equal to characteristic
impedance of the line (or) whenever the transmission line is terminated by a load with an
impedance equal to characteristic impedance of the line. The loading of the line is called
characteristic impedance loading.
When transmission line dealing with surge impedance loading, such a line is
called flat line.
Flat line is the one in which the magnitude of the voltage throughout the line
will be same
Surge impedance loading=
V sV r
Zc
[V s=V r=V ]
SIL
Surge Impedance Loading is the ideal loading capacity.
The most economical loading on transmission line is loading more than the
SIL.
For Underground cables most economical loading is less than the SIL.
Ferranti Effect:-When the transmission line is operating at no-load (or) light load condition.
The receiving end voltage is more than the sending end voltage. This phenomenon is called
Ferranti effect.
A,B,C and D values:-
A=|A|∠α ,
B=|B|∠ β ,
C=|C|∠γ D=|D|∠α
Dept. of Electrical Engineering Page 25
= V 2
Z C
![Page 26: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/26.jpg)
Power Systems Gate Material Vignan University
Short transmission lines:-
|A|=1 and α=0o |B|=variable value and β=600-700
|C|=0 and γ =90o |D|=1.0 and α=00
Medium transmission lines:-
|A|=1 and α=1-2o |B|=variable value and β=700-800 |C|=Variable and γ =90o
Long transmission lines:-
|A|=1 and α=2-5o |B|=variable value and β=800-870 |C|=Variable and γ =90o
Power Transfer Equations:- Receiving end
The receiving end power transfer Sr=V r I¿r
The purpose of conjugate is to assign polarity for inductive or capacitive load
reactive powers
Sr=V r(V S−AV r
B )¿
Sr=|V S||V r|
|B|∠( β−δ )−
|A||B|
|V r|2∠ ( β−α )
Pr=|V S||V r|
|B|cos( β−δ )−
|A||B|
|V r|2 cos ( β−α )
Qr=|V S||V r|
|B|sin( β−δ )−
|A||B|
|V r|2 sin ( β−α )
The locus of the above equations is circle. For fixed receiving end voltages they will
be concentric circles
For short transmission lines:-
Dept. of Electrical Engineering Page 26
![Page 27: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/27.jpg)
Power Systems Gate Material Vignan University
|A|=1 .0 ,
α=0o ,
|B|=Z ,
∠B=θ ,
Pr=Pr max=|V S||V r|
|Z|cos (θ−δ )−
|A||Z|
|V r|2 cos (θ )
Pr=Pr max=|V S||V r|
|Z|−
|V r|2
|Z|cos (θ )
[ δ=θ ]
Qr=−|V r|
2
|Z|sin θ
For loss less transmission line:-
|A|=1 .0 ,
α=0o ,
|Z|=|X|
θ=900
Pr=|V S||V r|
|Z|sin δ
Pr=Pmax=|V S||V r|
|Z|
[δ=900]Pr=Pmaxsin δ
Qr=|V S||V r|
|X|cos δ−
|V r|2
|X|
In case of short transmission lines δ is very small. So cosδ~1.0
Qr=V r
X [V S−V r ]=V r
XΔV
The real power transfer depends on the power angle and the reactive power depends on the
difference of voltage between the sending end and load end
1) The inductance of a power transmission line increases with (GATE-1992)
a) Decreases in line length
b) Increases in diameter of conductor
c) Increasing in spacing between the phase conductors
d) Increases in load current carried by the conductor
Dept. of Electrical Engineering Page 27
![Page 28: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/28.jpg)
Power Systems Gate Material Vignan University
2) A three phase overhead transmission line has its conductors horizontally spaced with spacing
between adjacent conductors equal to ‘d’. If now the conductors of the line are rearranged to
form an equilateral trainable of sides equal to ‘d’ then (GATE-1993)
a) Average capacitance and inductance will increase
b) Average capacitance will increase and inductance will decrease
c) Average capacitance will increase and inductance will increase
d) Surge impedance loading of the line increases
3) The insulation level of a 400KV, EHV over head transmission line is deeded on the basis of
a) Lightning over voltage (GATE-1995)
b) Switching over voltage
c) Corona inception voltage
d) Radio and TV interference
4) For a 500 Hz frequency excitation, a 50km short power line will be modeled as(GATE-1996)
a) Short line
b) Medium line
c) Long line
d) Data insufficient for decisions
5) Consider a long, two-wire line composed of solid round conductors. The radius of both
conductors is 0.25cm and the distance between their centres is 1m. if this distance is doubled,
then the inductance per unit length. (GATE-2002)
a) Doubles c) halves
b) increases but does not double d) decreases but does not halve
6) A long wire composed of a smooth round conductor runs above parallel to the ground
(Assumed to be a large conducting plane). A high voltage exists between the conductor and
the ground. The maximum electric stress occurs at (GATE-2002)
a) The upper surface of the conductor
b) The lower surface of the conductor
c) The ground surface
d) Midway between the conductor and the ground
7) Bundled conductors are mainly used in high voltage overhead transmission lines to
a) Reduce transmission line losses (GATE-2003)
b) Increases mechanical strength of the line
c) Reduce corona
Dept. of Electrical Engineering Page 28
![Page 29: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/29.jpg)
Power Systems Gate Material Vignan University
d) Reduce sag
8) The rated voltage of a 3-phase power system is given as (GATE-2004)
a) RMS phase voltage
b) PEAK phase voltage
c) RMS line to line voltage
d) PEAK line to line voltage
9) The phase sequene of the 3-phae system shown in figure is (GATE-2004)
a) RYB b) RBY c) BRY d) YBR
10) The concept of an electricity short, medium and long line is primarily based on the
(GATE-2006)
a) Nominal voltage of the line
b) Physical length of the line
c) Wavelength of the line
d) Power transmitted over the line
Two Marks Questions:
11) For equilateral spacing of conductors of an untransposed 3-phase line, we have (GATE-1996)
a) Balanced receiving end voltage and no communication interference
b) Unbalanced receiving end voltage and no communication interference
c) Balanced receiving end voltage and communication interference
d) Unbalanced receiving end voltage and communication interference
12) For a single phase overhead line having solid copper conductors of diameter 1 cm, spaced 60
cm between centers, the inductance in mH/km is (GATE-1999)
a) 0.05+0.2 In 60
b) 0.2 In 60
c) 0.05+0.2 In (60/0.5)
d) 0.2 In (60/0.5)
13) The conductors of a 10 km long, single phase, two wire likne are separated by a distance of
1.5m. the diameter of each conductor is 1 cm. if the conductors are of copper, the inductance
of the circuit is (GATE-2001)
a) 50.0 mH b) 45.3 mH c) 23.8 mH d) 19.6 mH
Dept. of Electrical Engineering Page 29
![Page 30: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/30.jpg)
Power Systems Gate Material Vignan University
14) A 800 kV transmission line is having per phase line inductance of 1.1 mH/km and per phase
line capacitance of 11.78 nF/km. Ignoring the length of the line, its ideal power transformer
capability in MW is (GATE-2004)
a) 1204 MW b) 1504 MW c) 2085 MW d) 2606 MW
15) 230V (phase) 50Hz, three-phase 4-wire, system has a sequence ABC. A unity power-factor
load of 4kW is connected between phase A and neutral N. it is desired to achieve zero neutral
current through the use of a pure capacitor in the other two phases. The value of inductor and
capacitor is (GATE-2007)
a) 72.95 mH in phase C & 139.02µF in Phase B
b) 72.95 mH in phase B & 139.02µF in Phase C
c) 42.12 mH in phase C & 240.79 µF in Phase B
d) 42.12 mH in phase B & 240.79 µF in Phase C
One mark questions
16) The surge impedance of a 400 km long overhead transmission line is 400Ω. For a 200km
length of the same line, the surge impedance will be (GATE-1995)
a) 200 Ω b) 800Ω c) 400Ω d) 100Ω
17) In a 400Kv network, 360 Kv is recorded at a 400kV bus. The reactive power absorbed by a
shunt rated for 50MV AR, 400kV connected at the bus is (GATE-1994)
a) 61.73 MVAR b) 55.56 MVAR c) 45 MVAR d) 40.5
MVAR
18) The reflection coefficient for the transmission line shown in figure at P is (GATE-1998)
a) +1 b) -1 c) 0 d) 0.5
19) Series capacitive compensation in EHV transmission lines is used to (GATE-1998)
a) Reduce the line loading
b) Improve the stability of the system
c) Reduce the voltage profile
d) Improve the protection of the line
20) An overhead line having a surge impedance of 400 Ω is connected in series with an
underground cable having a surge impedance of 100 Ω. If a surge of 50kV travels from the
Dept. of Electrical Engineering Page 30
![Page 31: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/31.jpg)
Power Systems Gate Material Vignan University
line towards the cable junctions, the value of the transmitted voltage wave at the junction is
(GATE-1999)
a) 30kV b) 20kV c) 80kV d) -30kV
21) The load carrying capability of long AC transmission line is (GATE-1999)
a) Always limited by the conductor size
b) Limited by stability considerations
c) Reduced at low ambient temperature
d) Decreased by the use of bundled conductors of single conductors
22) Corona losses are minimized when.
a) Conductor size is reduced
b) Smoothness of conductor is reduced
c) Sharp points are provided in the line hardware
d) Current density in conductors is reduced
23) A lossless radial transmission line with surge impedance loading (GATE-2001)
a) Takes negative VAR at sending end and zero VAR at receiving end
b) Takes positive VAR at sending end and zero VAR at receiving end
c) Has flat voltage profile and unity power factor at all points along it
d) Has sending end voltage higher than receiving end voltage and unity power factor at
sending end
24) A 3-phase 11-kV generator feeds power to a constant power unity power factor load of
100MW through a 3-phase transmission line. The line-to-line voltage at the terminals of the
machine is maintained constant at 11 kV. The per unit positive sequence impedance of theline
based on 100MA and 11kV is j0.2. the line to line voltage at the load terminals is measured
to be less than 11 kV. The total reactive power to be injected at the terminals of the load to
increase the line-to-line voltage at the load terminals to 11kV is (GATE-2003)
a) 100MVAR b) 10.1 MVAR c) -100MVAR d) 10.1 MVAR
25) Total instantaneous power supplied by a 3-phase ac supply to a balanced R-L load is
a) Zero (GATE-2004)
b) Constant
c) Pulsating with zero average
d) Pulsating wit non-zero average
26) A 400V, 50Hz, three phase balanced source supplies power to a star connected load whose
rating is 12√3 KVA, 0.8 pf(lag). The rating (in KVAR) of the delta connected (capacitive)
reactive power bank necessary to bring the pf to unity is (GATE-2006)
a) 28.78 b) 21.60 c) 16.60 d) 12.47
Dept. of Electrical Engineering Page 31
![Page 32: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/32.jpg)
Power Systems Gate Material Vignan University
27) An extra high voltage transmission line of length 300km can be approximate by a lossless line
having propagation constant β=0.00127 radians per km then the percentage ratio of line
length to wavelength will be given by (GATE-2008)
a) 24.24% b) 12.12% c) 19.05% d) 6.06%
28) For a fixed value of complex power flow in transmission line having a sending end voltage V,
the real power loss will be proportional to (GATE-2009)
a) V b) V2 c) 1
V 2 d) 1V
29) Consider a step voltage wave of magnitude 1 pu travelling along a lossless transmission line
that terminates in a reactor. The voltage magnitude across the reactor at the instant the
travelling at the instant the travelling eave reaches the reactor is (GATE-2010)
a) -1 pu b) 1pu c) 2 pu d) 3 pu
30) Consider two buses connected by an impedance of (0+j5) Ω. The bus 1 voltage is 100angle of
300 V, and bus 2 voltage is 100 angle of 00 V. the real and reactive power supplied by bus1,
respectively, are (GATE-2010)
a) 1000W, 268 V Ar
b) -1000W, -134 V Ar
c) 276.9 W, -56.7 Ar
d) -276.9W, 56.7 V Ar
31) A nuclear power station of 500MW capacity is located at 300km away from a load center.
Select the most suitable power evacuation transmission configuration among the following
options (GATE-2011)
32) For enhancing the power transmission in a long EHV transmission line, the most preferred is
to connect a (GATE-2011)
a) Series inductive compensator in the line
b) Shunt inductive compensator at the receiving end
Dept. of Electrical Engineering Page 32
![Page 33: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/33.jpg)
Power Systems Gate Material Vignan University
c) Series capacitive compensator in the line
d) Shunt capacitive compensator at the sending end
Two marks questions
33) A shunt reactor of 100MVAR is operated at 98% of its rated voltage and at 96% of its rated
frequency. The reactive power absorbed by the reactor is (GATE-1998)
a) 98 MVAR b) 104.02 MVAR c) 96.04 MVAR d) 100.04 MVAR
34) A 220 kV, 20 km long, 3 phase transmission line has the following A, B, C, D constants.
A=D=0.96angleof 30, B=55angle of 650 Ω/phase C=0.5x10-4 angle of 900 S/phase. Its correct
charging current per phase is (GATE-1999)
a) 11/√3A b) 11A C) 220A d) 220//√3A
35) A 3-phase, 11kV, 50 Hz, 200kW load has a power factor of 0.8 lag. A delta connected 3-
phase capacitor is used to improve the power factor to unity. The capacitance per-phase of the
capacitor in micro-farads is (GATE-1999)
a) 3.948 b) 1.316 c) 0.439 d) 11.844
b)
36) A transmission line has equal voltages at the two ends, maintained constant by tow sources. A
third source is to be provided to maintain constant voltage (equal to end voltages) at either the
midpoint of the line of at 75% of the distances from the sending end. Then the maximum
power transfer capabilities of the line in the original case and the other two cases respectively
will be in the following ratios (GATE-2000)
a) 1:1:1 b) 1:2:1/0.75 c) 1:2:4 d) 1:4:6
37) The corona loss on a particular system at 50Hz is 1kW/Km per phase. The corona loss at 60hz
would be (GATE-2000)
a) 1kW/km per phase
b) 0.83kW/km per phase
c) 1.2kW/km per phase
d) 1.13kW/km per phase
38) Consider the model shown in figure of a transmission line with a series capacitor at its mid-
point. The maximum voltage on the line is at the location (GATE-2000)
Dept. of Electrical Engineering Page 33
![Page 34: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/34.jpg)
Power Systems Gate Material Vignan University
a) P1 b)P2 c) P3 d) P4
39)The ABCD parameters of a 3-phase over head transmission line are A=D=0.9, ∟900 Ω and
C=0.95 x10-3∟900S. At no-load condition a shunt inductive, reaction is connected at the receiving
end of the line to limit the receiving end voltage to be equal to the sending –end voltage. The
ohmic value of the reactor is (GATE-2003)
a) ∞Ω b) 2000 Ω c) 105.26Ω d) 1052.6 Ω
40) A surge of 20kV magnitude travels along a lossless cable towards its junction with two identical
lossless over head transmission lines. The inductance and the capacitance of the cable are 0.4mH
and 0.5µF per km. the inductance and capacitance of the overhead transmission lines are 1.5 mH
and 0.015 µF per km. the magnitude of the voltage at the junction due to surge is (GATE-2003)
a) 36.72kV b) 18.36 kV c) 6.07kV d) 33.93kV
41) A balanced delta connected load of (8+j6) Ω per phase is connected to a 400 V, 50Hz, 3-phase
supply lines. If the input power factor is to be improved to 0.9 by connecting a bank of star
connected capacitors the required KVAR of the bank is (GATE-2003)
a) 42.7 b) 10.2 c) 28.8 d) 39.4
42) A lightning stroke discharges impulse current of 10kA (peak) on a 400kV transmission line
having surge impedance of 250 Ω. The magnitude of transient over-voltage travelling waves in
either direction assuming equal distribution from the point of lightning strike will be
a) 1250kV b) 1650kV c) 2500kV d) 2900kV (GATE-2004)
43) The generalized circuit constants of a 3-phase, 220kV rated voltage, medium length transmission
line are (GATE-2004)
A=D=0.936+j0.016=0.936∟0.980
B=33.5+j138=142.0∟76.40 Ω
C=(-5.18+j914 x 10-6 Ω
If the load at the receiving end is 50MW at 220kV with a power factor of 0.9 lagging, then
magnitude of line to line sending end voltage should be
a) 133.23kV b) 220.00kV c) 230.78kV d) 246.30kV
44) At an industrial sub-station with a 4MW load, a capacitor of 2MVAR is installed to maintain the
load factor at 0.97 lagging. If the capacitor goes out of service, the load power factor becomes
a) 0.85 b) 1.00 c) 0.80 lag d) 0.90 lag (GATE-2005)
45) Two networks are connected in cascade as shown in the figure. With the usual notations the
equivalent A,B,C and D constants are obtained. Given that, C=0.025 ∟450, the value of Z2 is
Dept. of Electrical Engineering Page 34
![Page 35: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/35.jpg)
Power Systems Gate Material Vignan University
a) 10∟300 Ω b) 40∟-450 Ω c) 1 ohm d) 0 Ω (GATE-2005)
46) The A,B,C,D constant of a 220kV line are: A=D=0.94∟10, B=130∟730, C=0.001∟900. if the
sending end voltage of the line for a given load delivered at normal voltage is 240kV, the %
voltage regulation of the line is (GATE-2006)
a) 5 b) 9 c) 16 d) 21
47) The total reactance and total susceptance of a lossless overhead EHV line, operating at 50 Hz, are
given by 0.045 pu and 1.2 pu respectively. If the velocity of wave propagation is 3x105 km/s, then
the approximate length of line is (GATE-2007)
a) 122km b) 172 km c) 222km d) 272km
48) A lossless transmission line having Surge impedance Loading (SIL) of 2280MW. A series
capacitive compensation of 30% is emplaced. Then SIL of 2280MW. A series capacitive
compensation of 30% is emplaced. Then SIL of the compensated transmission line will be
(GATE-2008)
a) 1835MW b) 2280MW c) 2725MW d) 3257MW
49) Match the items List-I (To) with the items in List-II (use) and select the correct answer using the
codes given below the lists (GATE-2009)
List I List II
A. Improve power factor 1. Shunt reactor
B. Reduce the current ripples 2. Shunt capacitor
C. Increase the power flow in line 3. Series capacitor
D. Reduce the Ferranti effect 4. Series reactor
(a) a 2, b3, c4, d-1
(b) a 2, b4, c3, d-1
(c) a 4, b3, c1, d-2
(d) a 4, b1, c3, d-2
Dept. of Electrical Engineering Page 35
![Page 36: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/36.jpg)
Power Systems Gate Material Vignan University
Miscellaneous questions
50) A factory draws 100kW at 0l.7 p.f. lagging from a 3-phase, 11kV supply. It is desired to raise the
p.f. to 0.95 lagging using series capacitors. Calculate the rating of the capacitor required(GATE-
1997)
51) A 66 kV, 3-phase, 50Hz, 150kM long overhead transmission line is open circuited at the receiving
end. Each conductor has a resistance of 0.25 Ω/km, an inductive reactance of 0.5 Ω/km and a
capacitive admittance to neutral of 0.04x10-4 S/km (GATE-
1999)
a) Draw the nominal π-equivalent circuit and indicate the value of each parameter
b) Calculate the receiving end voltage if the sending end voltage is 66kV
52) A 275kV, 3-phase, 50Hz, 400km lossless line has following parameters: x=0.05 ohms/km, line
charging susceptance y=3.0 micro-Siemens/k (GATE-2000)
a) Calculate the receiving end voltage on open circuit using justifiable assumptions
b) What load at the receiving end will result in a flat voltage profile on the line?
c) If the flat voltage profile is to be achieved at 1.2 times the loading in (b), what will be nature
and quantum of uniformly distributed compensation required?
53) A long lossless transmission line has a unity power factor (UPF) load at the receiving end and an
ac voltage source at the sending end. The parameters of the transmission line are as follows:
characteristics impedance Zc=400 Ω, propagation constant β=1.2x10-3rad/km, and length
l=100km. The equation relating sending and receiving end question is
Vs=Vrcosh(βl)+jZcsinh(βl)IR. Complete the maximum power that can be transferred to the UPF
load at the receiving end if |Vs|=230kV. (GATE-2002)
Practice questions:-
IES 2001
1) The ABCD constants of a 3-phase transmission line are A=D=0.8∟10
A=D=0.8 ∟10
B=170∟850
C=0.002 ∟90.40 mho
The sending end voltages is 400kV. The receiving end voltage under no-load condition is
a) 400kV b) 500kV c) 320kV d) 417kV
2) In a short transmission line,voltage regulation is zero when the power factor angle of the load
at the receiving end side is equal to
a) Tan-1(X/R) b) Tan-1(R/X) c) Tan-1(X/Z) d) Tan-1(R/Z)
Dept. of Electrical Engineering Page 36
![Page 37: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/37.jpg)
Power Systems Gate Material Vignan University
3) Consider the following statements:
Surge impedance loading of a transmission line can be increased by
1. Increasing its voltage level
2. Addition of lumped inductance in parallel
3. Addition of lumped capacitance in series
4. Reducing the length of the line
Of these statements
a) 1 and 3 are correct
b) 1 and 4 are correct
c) 2 and 4 are correct
d) 3 and 4 are correct
4) The surge impedance of a 3-phase,400kV transmission line is 400Ω. The surge impedance
loading (SIL) is
a) 400 MW b) 100MW c) 1600MW d) 200MW
5) If a travelling-wave travelling along a loss-free overhead line does not result in any reflection
after it has reached the far end, then the far end of the line is
a) Open circulited
b) Short circuited
c) Terminated into a resistance equal to surge impedance of the line
d) Terminated into a capacitor
6) The active and the reactive power delivered at the receiving end of a short transmission lineof
impedance Z<ψare respectively given by
PR =V S V R
Zcos (φ−δ )−
V 2R
ZCosφand
QR=V S V R
Zsin (φ−δ )−
V 2R
Zsinφ, with
VS and VR being the magnitude of voltage at the sending and receiving ends, δ the power
angle. At the power-limit condition i.e. for maximum PR
a) leading VARs (QR) goes to the load for any values of VS and VR
b) leading VARs (QR) goes to the load ONLY for VS = VR
c) lagging VARs (QR) goes to the load for any values of VS and VR
d) lagging VARs (QR) goes to the load for any values of VS = VR
7) Bundled conductors are used for EHV transmission lines primarily for reducing the
a) Corona loss
b) Surge impedance of the line
c) Voltage drop across the line
d) I2R losses
Dept. of Electrical Engineering Page 37
![Page 38: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/38.jpg)
Power Systems Gate Material Vignan University
IES-2002
8) For transmission line which one of the following relations is true?
a) AD-BC=1 b) –AD-BC=1 c) AD-BC=-1 d) AD-BC=0
9) The reflection coefficient for the transmission line shown in figure below at point P is
a) +1 b) 0.5 c) 0 d) -1
10) A 3-phase transmission line has its conductors at the corners of an equilateral triangle with
side 3m. The diameter of each conductor is 1.63cm. the inductance of the line per phase per
km is
a) 1.232 mH b) 1.182 mH c) 1.093mH d) 1.043 mH
11) A cable has inductance of 0.22mH per km and capacitance of 0.202µF per km. The surge
impedance of the cable is
a) 28Ω b) 33Ω c) 42Ω d) 50 Ω
12) For some given transmission line the expression for voltage regulation is given by
¿V s∨−¿V R∨¿
¿V R∨¿¿¿x 100% Hence,
a) This must be a short line
b) This may either be a medium line or a short line
c) This expression is true for any line
d) This may either be a medium line or a long line
13) The capacitance of an overhead transmission line increases with
1) Increase in mutual geometrical mean distance
2) Increase in height of conductors above ground
Select the correct answer from the following
a) Both 1 and 2 are true c) Both 1 and 2 are false
b) Only 1 is true d) Only 2 is true
14) Consider the following statements
Addition of lumped capacitance in parallel to a loss-free transmission line increases
1. Characteristic impedance
2. Propagation constant
3. System stability
4. Charging current
Dept. of Electrical Engineering Page 38
![Page 39: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/39.jpg)
Power Systems Gate Material Vignan University
Which of these statements are correct ?
a) 1 and 3 b) 2 and 4 c) 2,3 and 4 d) 1,2 and 4
15) In a certain single-phase a.c. circuit the instantaneous voltage is given by v=Vsin(ωt+300)p.u.
and the instantaneous current is given by i=Isin(ωt-300) p.u. Hence the per unit value of
reactive power is
a) ¼ b) ½ c) √3/4 d) √3/2
IES-2003
16) A 100 km long transmission line is loaded at 110kV. If the loss of line is 15MW and the load
is 150MVA, the resistance of the line is
a) 8.06 ohms per phase
b) 0.806 ohms per phase
c) 0.0806 ohms per phase
d) 80.6 ohms per phase
17) A rectangular voltage wave is impressed on a loss-free over head line, with the far end of the
line being short-circulated. On reaching the end of this line
a) The current wave is reflected back with positive sign, but the voltage wave with negative
sign
b) The current wave is reflected back with negative sign, but the voltage wave with positive
sign
c) Both the current and the voltage waves are reflected with positive sign
d) Both the current and the voltage waves are reflected with negative sign
18) Which one of the following statements is NOT correct for the use of bundled conductors in
transmission lines?
a) Control of voltage gradient
b) Reduction in corona loss
c) Reduction in radio interference
d) Increase in interference with communication lines
19) Ds is the GMR of each sub condutor of a four subconductor bundle conductor and d is the
bundle spacing. What is the GMR of the equivalent single conductor?
a) 1.09√ Ds xd3 b) 1.09√ D3s xd3 c) 1.09
4√ D3s xd3 d) 1.09
4√ Ds xd3
20) Which one of the following statements is correct? Corona loss increases with
a) Decrease in conductor size and increase in supply frequency
b) Increase in both conductor size and supply frequency
c) Decrease in both conductor size and supply frequency
Dept. of Electrical Engineering Page 39
![Page 40: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/40.jpg)
Power Systems Gate Material Vignan University
d) Increase in conductor size & decrease in supply frequency
21) For a fixed receiving end and sending end voltage in a transmission system, what is the locus
of the constant power?
a) A straight line b) an ellipse c) a parabola d) a circle
IES - 2005
22) On what basis is the insulation level of a 400kV, EHV overhead transmission line decided?
a) Lightning overvoltage
b) Corona inception voltage
c) Switching overvoltage
d) Radio and TV interference
23) Equivalent π model is quite suitable for analyzing the performance of transmission line of
a) 50kM length b) 150kM Length c) 250 kM length d) all of the above
24) In a 7/30 ACSR conductor why is grease put between steel and aluminium conductors?
a) To reduce corrosion by electrolytic action between zinc (galvanizing agent on steel ) and
aluminum
b) To reduce friction between the stands
c) To reduce leakage of current from aluminium strands to steel stands
d) To eliminate air pockets
25) If X is the inductive reactance /phase and R is the resistance/phase of a short transmission
line, what is the power factor angle of the load for maximum voltage regulation?
a) Cos-1X/R b) tan-1X/R c) Cos-1R/X d) tan-1R/X
26) For a loss-free long transmission line, the conventional line equations become
Vs = (cosβl)VR+(jsinβl)IR and Is=( jsinβlZc
)VR+(cosβl)IR
Which one of the following statements is correct? If the line is terminated at the receiving end
by its natural load impedance Zc, then
a) The voltage is constant in magnitude at all points along the line and, Vs and VR always
remain in phase
b) The voltage is constant in magnitude at all points along the line but V s advances in phase
relative to VR by angle β radius per km
c) The magnitude of the voltage along the line changes in proportion to the line length, and,
Vs and VR always remain in phase
d) The magnitude of the voltage along the line changes in proportion to the line length, Vs
advances in phase relative to VR by β radians per km
Dept. of Electrical Engineering Page 40
![Page 41: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/41.jpg)
Power Systems Gate Material Vignan University
IES 2008
27) When is the Ferranti effect on long overhead lines experienced?
a) The line is lightly loaded
b) The line is heavily loaded
c) The line is fully loaded
d) The power factor is unity
28) What is the surge impedance loading of a loss less 400 kV, 3-phase, 50Hz overhead line of
average of surge impedance of 400 ohms?
a) 400 MW b) 400√3 MW c) 400/√3 MW d) 400MW
IES-2009
29) In a transmission line, the mid-point voltage is maintained to V by a compensating device as
shown in the circuit below. What is the real power flow through the line?
a)
V 2
Xsin
δ2 b)
2V 2
Xsin δ
c)
V 2
Xsin δ
d)
2V 2
Xsin
δ2
30) A short transmission line having zero resistance and total series reactance of 0.4 pu is
provided with reactive power compensation at the mid-point of the line such that the mid-
point voltage is held at 0.96pu when the voltage at both ends are 1.0pu. what is the steady
state power transmission limit of such a system?
a) 4.8 pu b) 0.0 pu c) 2.4 pu d) 9.6pu
Dept. of Electrical Engineering Page 41
![Page 42: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/42.jpg)
Power Systems Gate Material Vignan University
Solutions:-
1 . Ans:- (c)
Hint:- Inductance per phase of transmission line is Lph=0 .2 ln( d
r ' )mh/KM
Where ' d ' is the space between the two conductors , r'is the effective radius of the
conductor
∴Lph α ln(d )
2 Ans:- (c)
Hint:-
Case(i):- When conductors are horizontally spaced .
Inductance/phase= 0 .2 ln( GMD
Gmr)
Capacitance/phase=
2 πεo
ln (GMDr )
In case (ii)GMD=3√d×2d×d
GMD=3√2×d=1. 26 d
GMR=0 .7788 r
In case (ii):- When conductors are placed in equilateral triangle form
In this case GMD=d
GMR=0 .7788 r
SinceGMR∧r are constant in both the cases
Dept. of Electrical Engineering Page 42
![Page 43: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/43.jpg)
Power Systems Gate Material Vignan University
L/ ph α ln(GMD )
C / ph α
1ln(GMD )
∴ From cas(i) and case(ii) the inductance decreases and capacitance increases.
3. Ans:- (b)
Hint:- In any transmission line lightning over voltages are more severe compared to
switching over voltages. The lighting voltages are external voltages. Hence the
insulation is provided for switching voltage.
4. Ans:- (c)
For f =50Hz (where f is the frequency of supply)
fλ=υ
λ = wavelength i.e the length of the line
υ =velocity of the wave=3×108m/sec
∴ λ= υ
f=3×108
50=6000
km
For 6000 Km wave length, the line with more then 160KM length is treated as long
line
For 500Hz supply frequency. λ= υ
f=3×108
500=600
km
Hence with 500Hz supply, a line with more than 16KM length is treated as long line
where line parameters are distributed
∴ For 500Hz supply frequency 50KM line is long line.
5. Ans:- (c)
Hint:- Lph=0 .2 ln( d
r ' )mH/Km
Dept. of Electrical Engineering Page 43
![Page 44: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/44.jpg)
Power Systems Gate Material Vignan University
Lph=0 .2 ln( 1
0 .7788×0 .25×10−2)mh/Km
Lph =1.248 mH/Km
If the distance between the conductors is doubled then
Lph=0 .2 ln( 2
0 .7788×0 .25×10−2)mh/Km
Lph =1.38 mH/Km
Hence inductance per unit length increases but not doubles
6. Ans:- (b)
7. Ans:- (c)
Electric field intensity at surface of each conductor
E= V
( Self⋅GMD ) ln( GMDself .GMR )
For bundle conductors increase in self GMD will be predominant compared to
decrease in ln ( GMD
self . GMR )
Hence Electric field intensity at surface of each conductor will be reduced. Hence the
corona loss will be reduced, because chances for ionization of air are reduced.
8. Ans:- (c)
9. Ans:- (b)
Hint:- Phase sequence is verified in opposite direction to the vector rotation. Vectors
rotation is normally considered in anticlockwise direction hence phase sequence is verified
in clock wise direction.
10.Ans:- (c)
Dept. of Electrical Engineering Page 44
![Page 45: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/45.jpg)
Power Systems Gate Material Vignan University
Two marks questions:-
11.Ans:- (a)
Hint:- For the transmission line with equilateral spacing of conductors (Inductance/Phase)
is equal
(Current/Phase) is equal
(Flux/Phase) is equal
(Voltage/Phase) is equal
Hence no communication interference and also the receiving end voltages are balanced.
12. Ans:- (c)
Hint:-
Given r=0.5cm, d=60cm
Inductance per conductor La=La . int ernal+ La. external
=( 1
2×10−7+2×10−7 ln( d
r ))H/mt
=( 1
2×10−1+2×10−1 ln( d
r ))mH/Km
From given data La= ( 12×10−1+2×10−1 ln(60
0.5 ))mH/Km
La= (0 . 05+0 . 2 ln(600 .5 ))
mH/Km
13. Ans:- (c)
Sol:- Inductance of 1-Phase circuit with copper conductors
Lab=2 La=2×0 .2 ln( d
r ' )mh/KM
Dept. of Electrical Engineering Page 45
![Page 46: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/46.jpg)
Power Systems Gate Material Vignan University
Given, d=1.5m, r=0.5cm, r'=.7788×0 .5×10−2
m
∴Lab=0 . 4 ln( 1. 5
0 . 7788×0. 5×10−2)mH/Km
Lab =2.38 mH/Km
For 10Km length of the line
Lab = 2.38 ×10 mH
Lab =23.8 mH
14. Ans:- (c)
Sol:- Ideal Power transfer capability is nothing but the surge impedance loading of the line
∴surge impedance Zc=√ L /Km
C / Km
=√ 1. 1×10−3
11.68×10−9
= 306.88 Ω
∴Surge impedance loading =V 2
Zc
=
(800×103 )2
306 . 88
= 2085.47 MW
15. Ans:- (b)
Sol:- Load current phase A= 4×103
230∠0°=17 .39
Amp
VPhA= 230∠0 °
Dept. of Electrical Engineering Page 46
![Page 47: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/47.jpg)
Power Systems Gate Material Vignan University
VPhB= 230∠−120 °
VPhC= 230∠−240 °
From options
L=72 . 95 mH⇒ X L=22 .91 Ω⇒ I L=10∠−90°
C=72 .95 µF⇒ XC=22 . 9Ω⇒ I C=10∠90°
By assuming inductor in phase B and capacitor in phase C
IBph=10∠−90−120=10∠−210°
ICph=10∠90−240=10∠−150°
(Since VBph=230 ∠−120° and current lags voltage by 90°
in case of inductive load)
∴ For zero neutral current
IAph+ IBph + Icp = 0
17.39∠0°+10∠−210°
+10∠−150°¿0
Hence option (b) is the correct one
Performance of Transmission lines and Voltage Control
One Mark questios:
16. Ans:- (c)
Hin
t:- Surge impedance for a given transmission line is constant and is independent
of length of the transmission line and the frequency of surge. It depends only on
magnitude of inductance/Km and capacitance/Km [∴Zc=√ L/ Km
C / Km ]17. Ans:- (d)
Dept. of Electrical Engineering Page 47
![Page 48: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/48.jpg)
Power Systems Gate Material Vignan University
Hint:- 50MVAR,400Kv inductor means for an applied voltage of 400 KV, the
inductor absorbs 50 MVAR reactive power.
Reactive power absorbed by inductor (Q)= 3Vph Iph Sinφ
For a pure inductor φ=90°
Q=3 V ph I phsin 90°=3V ph
V ph
XLph
Q=3 V ph
2
X Lph
At 400Kv, Q=50MVAR
50×106=3×(400
√3×103)
2
X Lph
X Lph=3200Ω
For 360 kV applied voltage the reactive power absorbed by inductor
=
3×(360√3
×103)2
3200
=40.5 MVAR.
18. Ans :- (c)
Hint:- Since load impedance is equal to surge impedance, the voltage & current wave
forms are not going to experience any reflection.
Hence reflection coefficient is zero.
19. Ans :- (b)
Hint:- electrical power supplied by alternator is= EV
Xsin δ
By using series capacitor the effective value of reactance can be reduced.
Dept. of Electrical Engineering Page 48
![Page 49: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/49.jpg)
Power Systems Gate Material Vignan University
Hence for a given power transfer, we can operate the alternator at lower values of δ
so that machine will not lose its synchronism during abnormal conditions of
operation.
20. Ans:- (b)
The transmitted (or) refracted voltage
V 2=2 V ( ZL
Z L+ZC)
Here ‘2’ indicates that the voltage V2 is calculating in transient condition
∴V 2=2×50×103×(100100+400 )
V2=20KV
21. Ans:- (b)
Hint:- For a long line with AC transmission , reactance is more and is having more
effect on stability of system.
22. Ans:- (d)
Hint:- current density=
currentunitarea
For a given current, if the current density is reduced means the cross sectional
area of conductor is increased.
But corona loss α (V-Vo)2
Where V= operating voltage
Vo=Critical disruptive voltage
Voα rln ( d
r ) (d= separation between conductors=constant)
Voα r (radius of conductor)
As radius of conductor increases, critical disruptive voltage(Vo) also increases and
hence corona loss decreases.
∴ increase in ‘r’ is more effective than decrease in ln ( d
r )
Note:- Because of bundling radius of the conductor increases so corona loss decreases
Dept. of Electrical Engineering Page 49
![Page 50: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/50.jpg)
Power Systems Gate Material Vignan University
23. Ans:- (c)
Hint:- When transmission line dealing with surge impedance loading, then such a line
is called flat line,in which the magnitude of the voltage throughout is purely resistive
in nature. Hence the power factor is unity throughout its length.
24. Ans :- (b)
Sol:-
Given the X1 P.u=j 0.2 p.u
but X1=j0.2¿
(KV b)2
MVAb
= j0 . 2×112
100
= j0.242Ω
To make sending end voltage and receving end voltage equal, the net reactive power
demand at load must be zero.
Let Qc be the reactive power injected at load side and Q r be the reactive power
received from supply.
∴Qr+Qc=Qd
Qr+Qc=0
Qc=-Qr
Qr=
|V s||V r||B|
sin ( β−δ )−|A||B|
|V r|2 sin( β−α )
In this case , β= Line impedance angle=900
|B|=0.242Ω, α=00, |A|=1 .0
Pr=
|V s||V r||B|
cos ( β−δ )−|A||B|
|V r|2 cos ( β−α )
100=
11×110 .242
cos (90−δ )− 1. 00 .242
112cos (90−0)
100=
112
0 .242sin δ
δ = 11.530
Qr=11×110 . 242
sin (90−11. 53 )− 1. 00 .242
112sin(90 )
Qr=-10.1MVAR
∴ The reactive power to be injected =10.1MVAR
Dept. of Electrical Engineering Page 50
![Page 51: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/51.jpg)
Power Systems Gate Material Vignan University
25. Ans:- (b)
Sol:- Let the phase voltage be Va=VmSinwt
Vb= VmSin(wt-1200), Vc= VmSin(wt-2400)
Let the phase of load be ‘Φ’, As it is a RL load ‘Φ’ is a lagging angle.
Phase current ia=imSin(wt- Φ),
ib=imSin(wt- 120-Φ), ic=imSin(wt- 240-Φ)
Instantaneous total 3 phase power=( VmSinwt)( imSin(wt- Φ))+
( VmSin(wt-1200))( imSin(wt- 120-Φ))+
(VmSin(wt-2400))( imSin(wt- 240-Φ))
=
=V m Im
2¿ [cos(wt−wt+φ )−cos(2wt−φ)+cos(wt−120−wt+120+φ)−¿ ] [cos(wt−120+wt−120−φ)+cos(wt−240−wt+240+φ )−¿ ]¿
¿¿
=
V m I m
23 cos φ [cos (2 wt−φ )+cos (2 wt−240−φ )+cos (2 wt−480−φ) ]
=
32
V m Imcos φ−[cos (2wt−φ )+cos (2wt−120−φ )+cos (2wt−240−φ )]
=3
V m
√2
I m
√2cos φ−0
= 3 V ph I ph cosφ
26. Ans:- (d)
Sol:- KVAR demand of load at 0.8 power factor =12√3×sin 36 . 86×103
=12.47KVAR
[∵φ=cos−1 0. 8=36 .860 ]
KVAR demand of load at unity power factor =12√3×sin 0=0
∴KVAR to be supplied by capacitor
Bank connected at load=12.47-0=12.47KVAR
Dept. of Electrical Engineering Page 51
![Page 52: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/52.jpg)
Power Systems Gate Material Vignan University
27. Ans;- (d)
Sol:- propagation constant for loss less line β=2 πf √LC
Velocity of light υ= 1
√LC
λ= υf= 1
f √LC=2 π
β
λ= 2 π
0. 00127=4947 . 4 Km
∴
Linelengthwavelength
=3004747 . 4
=0 .0606=6 .06%
28. Ans:- (c)
Hint:- P=I2R=( S
3V )2
R= S2 R3V 2
Pα
1
V 2
29. Ans:- (c)
The Reactor is initially open circuit
V2=V+V1=1.0+1.0=2.0 p.u
V1=reflected voltage
V2=Switched voltage
30. Ans:- (a)
Sol:- β=Line impedance angle, δ=30o,α=00, A=D=1.0
(∴ Given line is short line)
Psending
=|DB
||V S|2 cos( β−α )−
|V s||V r||B|
cos ( β+δ )
Qsending
=|DB
||V S|2 sin( β−α )−
|V s||V r||B|
sin ( β+δ )
Psending
=|1 . 05
||100|2cos (90−0)−100×100|5|
cos ( 90+30 )
=1000 W
Qsending
=|1 . 05
||100|2sin(90−0 )−100×100|5|
sin (90+30 )
Dept. of Electrical Engineering Page 52
![Page 53: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/53.jpg)
Power Systems Gate Material Vignan University
=268 VAR
31. Ans:- (d)
Sol: SIL=V 2
Zc
SIL==400×400
400=400 Mw
To carrey 500Mw a double circuit 400Kv line is used.
32. Ans:- (c)
Sol:- To enhance the power transmission in a long EHV transmission line, a series
capacitance compensator is used.
P=V 2
X series capacitor will reduce the reactance.
Two Marks Questions:-
33. Ans:- (d)
Sol:- Reactive Power absorbed by reactor=
V 2
X L
Q1=
V12
2 πf 1 L=1000 MVAR
If V2 =0.98V1&f2=0.96f1
Then reactive power absorbed =
V22
2 πf 2 L
Q2=
(0. 98 V 1 )2
2 π (0 . 96 f 1) L
Q2=1 .000416 ( V
12
2 πf 1 L )Q2=1.000416¿ 100MVAR
Q2=100.04MVAR
34. Ans:- (a)
Sol:- Admittance per phase(Y)=C=0.5¿ 10-4∠800S
Dept. of Electrical Engineering Page 53
![Page 54: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/54.jpg)
Power Systems Gate Material Vignan University
Charging current per phase = Vph¿ Y
=
220
√3×103×0 .5×10−4
=
11
√3 A
35. Ans:- (b)
Sol:- 3-Phase,11KV,50Hz,200Kw load , at power factor=0.8
KVAR demand of Load (Q1)=
220×103
0. 8×sin (cos−10 . 8 )
∴Q1=150KVAR
KVAR demand of load at UPF=0
So as to operate the load at UPF, we have to supply the 150KVAR by using
capacitor bank
∴ KVAR rating of Δ - connected capacitor bank=
3V ph2
XCph
=150 KVAR
3×(11000 )2
XCph
=150×103
XCph = 2420Ω
12 π fc
=2420Ω
C= 12 π×50×2420
=1 . 3153µF
C¿ 1.316 µF
36. Ans:- (b)
Hint:- Initially without compensator Pmax =
V 2
X
With a compensator at the middle of the line, power transfer capability,
Pmax1=
2V 2
X
If the compensator is kept at the 75% of the line from the sending end, then the
longer transmission line would clearly determine the overall transmission limit.
Dept. of Electrical Engineering Page 54
![Page 55: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/55.jpg)
Power Systems Gate Material Vignan University
Pmax2=
V 2
0 .75 X
Pmax: Pmax1 :Pmax1=1:2:
10 .75
37. Ans:- (d)
Sol:- Empirical formula for corona loss is given by
P=241×10−5×( f +25
δ )×√ rd×(V p−V d )2 Kw / ph/km
∴Corona loss, Pα( f +25 )
P2
P1
=(f 2+25 )( f 1+25 )
P2=1Kw×(60+25 )(50+25 )
=1 .13 KW
∴ Corona loss at 60Hz (P2)=1.13KW/Km/Ph
38. Ans:- (a)
The voltage profile for the given line is shown in fig.
39. Ans:- (b)
Sol:- Given A=D=0.9∠00,B=200∠900Ω/C, C=0.95×10-3∠900
Dept. of Electrical Engineering Page 55
![Page 56: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/56.jpg)
Power Systems Gate Material Vignan University
[A1 B1
C1 D1 ]=[A BC D ] [1 0
Y 1 ]Vs=A1 Vro
A1=1.0
A+BY=1.0
Y=
0. 1200∠90
; Z=2000Ω
40. Ans:- (d)
Sol:-
In this case Z2=Z3
The Refracted voltage V2=
2VZ2 Z3
Z1 Z2+Z2 Z3+Z3 Z1
=2VZ2
2
Z1 Z2+Z22+Z3 Z1
=
2VZ2
2 Z1+Z2
Z1=characteristic impedance of cable
Z2=Z3=characteristic impedance of overhead line
Z1=√ L/kmC / Km
=√ 0. 4×10−3
0 .5×10−6=28 .28Ω
Z2=√ L/kmC / Km
=√ 1.5×10−3
0.015×10−6=316 .22Ω
V2=2¿20×103×316 .22
(2×28 . 28)+(316 . 22 )
V2=39.93KV
41. Ans:- (b)
Per phase current of the load=400
8+ j6=40∠−36 .860
∴Power factor = cos36.86
=0.8(lagging)
Dept. of Electrical Engineering Page 56
![Page 57: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/57.jpg)
Power Systems Gate Material Vignan University
By connecting a bank of star connected capacitors, the reactive power component of
current is changed, where as the active power component of current is unchanged.
Active power component of current = IcosΦ
∴I1cosΦ1= I2cosΦ2
40×0.8=I20.9
I2=35.55A
Φ2=Cos-1(0.9)=25.840
I2=I1+Ic
Ic=I2+I1
=35.55 ∠-25.840 -40 ∠-36.860
Ic=8.5∠900
KVAR of th star connected bank
KVAR demand of load at 0.8 lag power factor
=√3V L I L sin φ1
=√3×400×√3×40×0 .6
=28.800KVAR
KVAR demand of load at 0.9lag power factor
=√3V L I L sin φ2
=√3×400×√3×40×sin 25 .84
=18.593KVAR
∴KVAR to be supplied by star connected capacitor bank
=28.8-18.59
=10.206KVAR
42. Ans:- (a)
Sol:- As the current is distributed equally, current on each side=5000A
Surge impedance of transmission line=205Ω
∴ The magnitude of transient over voltage=250×5000
= 1250KV
43. Ans:- (c)
Dept. of Electrical Engineering Page 57
![Page 58: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/58.jpg)
Power Systems Gate Material Vignan University
Sol:-
Power received by load=50MW
Current at receiving end= √3V r I r cos φ
∴ I r=50×106
√3×220×103×0 .9
= 145.79A
Load power factor cosΦ=0.9, Φ=25.840
I r=145 .79∠25 .840
V S=133. 246∠7 . 770KV
Line to line sending voltage= √3×133 . 246∠7 .770KV
=230.78∠7.770 KV
Magnitude of line to line sending end voltage=230.78KV.
44. Ans:- (c)
Sol:- Let the initial power factor angle=Φ1
After connecting a capacitor the power factor angle = Φ2
Given Φ2 =cos-1 0.97
=14.070
KVAR supplied by capacitor= P(Tan Φ1 – Tan Φ2)
2¿106=4¿106
P(Tan Φ1 – Tan 14.07)
Φ1=36.890
cos Φ1=0.8lag
Hence if the capacitor goes out of service the load power factor will become 0.8
lagging
45. Ans:- (b)
Sol:- Tow networks are cascaded
Dept. of Electrical Engineering Page 58
V s=AV r+BIr
[V S
I S ]=[1 Z1
0 1 ] [ 1 0
( 1Z2
) 1 ][V r
Ir ]
![Page 59: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/59.jpg)
Power Systems Gate Material Vignan University
C=1/Z2
Given C=0.025∠450
∴ Z2=1/C
Z2=40∠-450Ω
46. Ans:- (c)
Sol:
Under no load condition IR=0
VR(N.L)=
V S
A=240×103
0 .94
VR(N.L)= 255.3KV
% Voltage regulation =
V R (N . L)−V R (F . L)
V R( F .L)×100
=255 . 3−220
220×100
=16%
47. Ans:- (c)
Sol:- Velocity of wave propagation
Velocity wave propagation (
υ )
= 1
√( LKm )( C
Km )
Let ‘l’ be the total length of line
Total reactance of the line=0.045p.u.=2π fL
Total Inductance of line= 0 .045
2π×50
Dept. of Electrical Engineering Page 59
![Page 60: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/60.jpg)
Power Systems Gate Material Vignan University
Total susceptance of line=1.2.p.u=2 π fc
Total capacitance of line= 0 .045
2π×50
Inductance/Km = 0 .045
2 π×50×l
Capacitance/Km= 1 .2
2π×50×l
ϑ= 1
√ 0.0452π×50×l
× 1.22 π×50×l
30×105= 1
7 . 4×10−4 l
∴ Length of the line (l)=222km
48. Ans:- (c)
Sol:-
Given SIL=
V 2
ZC =2280MW
Let characteristic impedance(Zc)=√ Zsc
Y oc
=√ 1 . 01 . 0
=1 .0 p .u
=√ impedance /kmadmit tan ce /km
30% Series capacitive compensation is provided
So Zsc=0.7 times original value
Zcnew=√ 0.7×Z sc
Y oc
=√ 0 . 71 . 0
=0 .836 p .u
SILnew=
V 2
ZCnew
= V 2
0. 836 ZC
=22800 . 836 =2727MW
Dept. of Electrical Engineering Page 60
![Page 61: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/61.jpg)
Power Systems Gate Material Vignan University
49. Ans:- (b)
Hint:-
(A). Shunt capacitor is used at load end to improve the voltage profile. At the same
time it also improves the power factor at the load side.
(B). Series reactor smoothens the wave shape.
(C). By using series capacitor the net reactance of the line decreases
Power flow in the line=
EVX
Sin δ
Pα1X (So power flow of the line increases)
(D) Ferranti effect occurs during light load and no load condition of a long
transmission
Line due to shunt capacitance. To overcome the shunt capacitance effect we have to
connect the inductor in shunt to prevent the failure of insulation due to over
voltage.
50. Ans:-
Load rating =100 KW at 0.7 power factor (Lagging)
3-phse supply voltage = 11kv
KVAR demand of load at 0.7 P.f is
Q1100×103
0 . 7× sin( cos−1 0 . 7 )=102. 020 KVAR
KVAR demand of load at 0.95 p.f is
Q2100×103
0.95× sin (cos−10 .95 )=32 .868 KVAR
Hence to operate the load at 0.95 power factor
KVAR to be supplied by using series capacitors = (102.020-32.868)KVAR =
69.152KVAR
312XC=69.152KVAR
Dept. of Electrical Engineering Page 61
![Page 62: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/62.jpg)
Power Systems Gate Material Vignan University
√3 V L IL cosφ=100×103
√3×11×103×IL×0 . 95=100×103
I L=5. 525 A
Since transmission line is a Y connected one
ILine=Iph
Xc / ph =
69 .152×103
3×(5. 252 )2=755 .125Ω
12 π fC
=755 .125
C/ph=
12 π×50×755 . 125
=4 . 215 μF
Since series capacitors are connected in phase manner
KVAR rating of each capacitor =
69 .1523
=23 .05 KAVR
Rating of capacitor is, 4.215 F, 23.05KAVR, 11KV [GATE – 1997]
51. Ans:
(a) Nominal - equivalent circuit of given transmission line is shown below.
Figure
Total resistance of each conductor, RL = 0.25 x 150 = 37.5 Ω / ph
Total inductive reactance of each conductor, XL = 0.5 x 150 = 75 Ω / ph
Total capacitive admittance to neutral, YC = 0.04 x 10-4 x 150 = 6 x 10-4 S/ph
Y C
2=3×10−4⇒π fC=3×10−4
C=3×10−4
π×50=1 . 9098 μF
Dept. of Electrical Engineering Page 62
![Page 63: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/63.jpg)
Power Systems Gate Material Vignan University
V receiving / ph=(66
√3 )×103×− j 3333 .33
(37 . 5+ j75− j 3333. 33 )
¿(66√3 )×103×− j 3333 .33
(37 . 5− j3333 . 33 )V receiving / ph=38 .97 KV
V Re cieving( L−L)=√3×38 . 97=67 . 498 KV
[GATE – 1999]
52. Sol :- (a) By neglecting transmission line resistance for a long line, the nominal -
V s=(275
√3 )XL=0.05 x 400 = 20Ω
Y = 3x400 x 10-6 = 1200 x 10-6 = 1.2 ms
Y2
=1. 2×10−3
2=0 .ms
2 XC=1(Y /2 )
=1666 .67Ω
Receiving end voltage
Dept. of Electrical Engineering Page 63
![Page 64: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/64.jpg)
Power Systems Gate Material Vignan University
V rph=V s (− j2 xc )jxL− j2 xC
V rph=275
√3×[− j 1666 .67
− j 1646 .67 ]×103
V rph=160. 7 KV
V r (L−L)=160 . 7 x √3=278 . 34 KV
Sol: (b)For a flat line magnitude of voltage throughout the line length is same. To
have
flat voltage profile the load impedance must be equal to characteristic
impedance of transmission line.
Characteristic impedance ZC= √ LC
=√ impedanceperkmadmit tan ceperkm
=√ 0. 053×10−6
=129Ω
Characteristic impedance loading =
v( L−L )
2
ZC
=
(275×103)2
129
=586.24 MW
(c)1.2 times of surge impedance loading =1.2x586.24 MW
= 703.5 MW
In this case the loading is greater than the surge impedance loading. To achieve
flat voltage profile the compensation must be of capacitive type.[GATE 2000]
53. Ans:-
Sol:- Figure
VS=VR cos h (1) + jZC sinh (1) IR
From standard form VS= AVR + BIR
A=cosh((1) , B= jZC sinh (1)
A= cosh (1.2x10-3x100) = 1.0
Dept. of Electrical Engineering Page 64
![Page 65: CHAPTER 1](https://reader036.fdocuments.in/reader036/viewer/2022081514/55725c26497959da6be8b843/html5/thumbnails/65.jpg)
Power Systems Gate Material Vignan University
B= j 400 sin h (1.2 x 10-3 x 100) = 48.11 ∠900
Since given transmission line is of 100km length, let us consider the line as
short line
VS VR= 230KV
Maximum power transferred Pmax is given as
Prmax =
|V S||V r||B|
−|AB||V r|
2 cos ( β−α )
Qrmax= -|A
B| |V R|
2 sin( β−α)
∴Pr max=230×230×106
48 .11−| 1
48 . 11|(230×103 )2cos (90−0)
Prmax=1102.083MW
∴Qr max=−|148. 11
||230|2 sin( 90−0 )×106
¿−1102.83 MVAR
Total power transferred = (1102.083-j 1102.83) MVA [GATE-2000]
Solutions for Practice questions
1-b 6-a 11-a 16-a 21-d 26-b
2-b 7-a 12-a 17-a 22-c 27-a
3-a 8-a 13-b 18-d 23-c 28-a
4-a 9-c 14-b 19-d 24-a 29-c
5-c 10-a 15-c 20-b 25-b 30-c
Dept. of Electrical Engineering Page 65