CHAPTER 07 · 2020. 8. 25. · CHAPTER 07 Tab ตัวอย่างการติดตั้ง: ติดตั้งแบบมีตัวรับพื้นโต๊ะและฉากรับ
Chapter 07
-
Upload
satish-reddy -
Category
Documents
-
view
271 -
download
12
Transcript of Chapter 07
CHAPTER -1 INTRODUCTION
CHAPTER-1
INTRODUCTION
1.1 Introduction
ELECTRIC utilities and end users of electric power are becoming increasingly
concerned about meeting the growing energy demand. Seventy five percent of total global
energy demand is supplied by the burning of fossil fuels. But increasing air pollution, global
warming concerns, diminishing fossil fuels and their increasing cost have made it necessary
to look towards renewable sources as a future energy solution. Since the past decade, there
has been an enormous interest in many countries on renewable energy for power generation.
The market liberalization and government’s incentives have further accelerated the
renewable energy sector growth.
Renewable energy source (RES) integrated at distribution level is termed as
distributed generation (DG). The utility is concerned due to the high penetration level of
intermittent RES in distribution systems as it may pose a threat to network in terms of
stability, voltage regulation and power-quality (PQ) issues. Therefore, the DG systems are
required to comply with strict technical and regulatory frameworks to ensure safe, reliable
and efficient operation of overall network.
With the advancement in power electronics and digital control technology, the DG
systems can now be actively controlled to enhance the system operation with improved PQ at
PCC. However, the extensive use of power electronics based equipment and non-linear loads
at PCC generate harmonic currents, which may deteriorate the quality of power.
Generally, current controlled voltage source inverters are used to interface the
intermittent RES in distributed system. Recently, a few control strategies for grid connected
inverters incorporating PQ solution have been proposed. In an inverter operates as active
inductor at a certain frequency to absorb the harmonic current. But the exact calculation of
network inductance in real-time is difficult and may deteriorate the control performance. A
similar approach in which a shunt active filter acts as active conductance to damp out the
harmonics in distribution network is proposed. A control strategy for renewable interfacing
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 1
CHAPTER -1 INTRODUCTION
inverter based on – theory is proposed. In this strategy both load and inverter current sensing
is required to compensate the load current harmonics.
The non-linear load current harmonics may result in voltage harmonics and can
create a serious PQ problem in the power system network. Active power filters (APF) are
extensively used to compensate the load current harmonics and load unbalance at distribution
level. This results in an additional hardware cost. However, in this paper authors have
incorporated the features of APF in the, conventional inverter interfacing renewable with the
grid, without any additional hardware cost. Here, the main idea is the maximum utilization of
inverter rating which is most of the time underutilized due to intermittent nature of RES. It is
shown in this paper that the grid-interfacing inverter can effectively be utilized to perform
following important functions: 1) transfer of active power harvested from the renewable
resources (wind, solar, etc.); 2) load reactive power demand support; 3) current harmonics
compensation at PCC; and 4) current unbalance and neutral current compensation in case of
3-phase 4-wire system. Moreover, with adequate control of grid-interfacing inverter, all the
four objectives can be accomplished either individually or simultaneously. The PQ
constraints at the PCC can therefore be strictly maintained within the utility standards
without additional hardware cost.
CHAPTER 2DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 2
CHAPTER -1 INTRODUCTION
LITERATURE SURVEY
The last decade has seen a marked increase on the deployment of end user equipment that
is highly sensitive to poor quality control electricity supply. Several large industrial users are
reported to have experienced large financial losses as a result of even minor lapses in the
quality of electricity supply. [21]
A great many efforts have been made to remedy the situation, where the solutions based
on the use of latest power electronic technology figure prominently. Indeed custom power
technology, the low voltage counterpart of the more widely known flexible as transmission
system (FACTS) technology, aimed at high voltage power transmission applications, has
emerged as a credible solution to solve many of the problems relating to continuity of supply
at the end user level. The various power quality Problems at the Distribution level are voltage
sag and swells, fluctuations, harmonics, flickering etc. [18]
Recently, various power electronic technology devices have been proposed especially to
be applied to medium voltage networks, generally named custom power. Custom power
concept introduced by N.G.Hingorani has been proposed to ensure high quality of power
supply in distribution networks using power electronics devices. Additionally, various
custom power devices are based on the voltage source converter technology introduced by
N.G.Hingorani and L.Gyugyi. [6]
At present, wide ranges of very flexible controllers, which capitalize on newly available
power electronics components, are emerging for custom power applications. Among these
the Distribution static Compensator (DSTATCOM) and dynamic voltage restorer (DVR),
both of them based on the VSC principle. [19]
The modeling and analysis of these custom power devices has applied for the study of
power quality by Olimpo Anaya-Lara and E Acha [7] presenting comprehensive results to
assess the performance of each device as a potential custom power application. The different
control techniques of DSTATCOM are discussed in papers [8]-[13].
Mahesh K. Mishra, Arindam Ghosh, and Avinash Joshi have demonstrated Operation of a
DSTATCOM in Voltage Control Mode. [9]
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 3
CHAPTER -1 INTRODUCTION
N.H. Woodley, L. Morgan, A. Sundaram introduces the prototype DVR installation and
presents early results from the demonstration project. [15]
Arindam Ghosh, and Avinash Joshi, Amit Kumar Jindal discusses the operating principles
and control characteristics of a dynamic voltage restorer (DVR) that protects sensitive but
unbalanced and/or distorted loads. They successfully given conclusion that DVR regulate the
voltage at the load terminal irrespective of sag/swell, distortion, or unbalance in the supply
voltage. [16]
Hideaki Fujita, Hirofumi Akagi demonstrates the unified power quality conditioner
(UPQC’s), which aim at the integration of series-active and shunt-active filters and results
reveal that UPQC compensate the voltage flicker/imbalance, reactive power, and harmonics.
[21]
Shairul Wizmar Wahab and Alias Mohd Yusof highlights voltage sag as one of a power
quality issue and Dynamic Voltage Restorer (DVR) is using for mitigation of voltage sag.
[17]
Zainal Salam , Tan Perng Cheng and Awang Jusoh intended to review the development of
active power filter (APF) technologies that are commonly used to mitigate harmonics in
utility power lines. The operation of common APF topologies, namely the shunt, series and
hybrid APFs are described in detail. [2]
K. Ça_atay BAYINDIR given detailed analysis on Modeling of custom power devices. [5]
Cai Rong had given Analysis of STATCOM for Voltage Dip Mitigation. [12]
S.V Ravi Kumar and S. Siva Nagaraju describes the techniques of correcting the supply
voltage sag, swell and interruption in a distributed system. Comprehensive results are
presented to assess the performance of DVR and DSTATCOM as a potential custom power
solution. [19]
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 4
CHAPTER -1 INTRODUCTION
CHAPTER 3
ELECTRIC POWER QUALITY MITIGATION
TECHNIQUES TO IMPROVE POWER QULITY
3.1 Introduction
Modem power systems are complex networks where hundreds of generating stations and
thousands of load centers are interconnected through long power transmission and
distribution networks. The main concern of consumers is the quality and reliability of power
supplies at various load centers where they are located at. Even though the power generation
in most well-developed countries is fairly reliable, the quality of the supply is not so reliable.
Power distribution systems, ideally, should provide their customers with an uninterrupted
flow of energy at smooth sinusoidal voltage at the contracted magnitude level and frequency.
However, in practice, power systems, especially the distribution systems, have numerous
nonlinear loads, which significantly affect the quality of power supplies.
As a result of the nonlinear loads, the purity of the waveform of supplies is lost. This ends
up producing many power quality problems. Apart from nonlinear loads, some system
events, both usual (e.g. capacitor switching, motor starting) and unusual (e.g. faults) could
also inflict power quality problems. The consequence of power quality problems could range
from a simple nuisance flicker in the electrical lamps to loss of money due to production
shutdown. [14]
3.2 Power Quality improvement methods
Here the following methods can improve power quality in the power system.
3.2.1 Motor-generator sets
Motor-generator sets are composed of the motor supplied the power system, a synchronous
generator connected with sensitive load and flywheel. The motor and generator are connected
together on a common axis, shown in Fig.3.1. The rotational energy, stored in the flywheel, can
be used to regulate the steady-state voltage and to support voltage during disturbances. The
advantages of this system are: high efficiency, low initial cost and the capability of long
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 5
CHAPTER -1 INTRODUCTION
duration ride through (several seconds). However, it can only be used in industrial environments
because of the limitation of its size, noise and maintenance. [12]
Fig.3.1 Motor-generator sets.
3.2.2 Transformer-based solutions
Electronic tap changer, shown in Fig.3.2, can be installed on a dedicated transformer for the
sensitive load. The load voltage can be maintained by change the turns ratio of the transformer while
the input voltage varies. The secondary winding, connected with the load, is separated in a number of
sections. Each section is connected or disconnected through a fast static switch. Therefore, the
secondary voltage can be regulated in steps. In general, thyristor-based switches that can only be
turned on once per cycle are used. Thus, this solution introduces a time delay, at least one half cycle,
into the dip compensation. [12]
Fig 3.2 Electronic tap changer.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 6
CHAPTER -1 INTRODUCTION
3.2.3 The Static Transfer Switch (STS)
The Static Transfer Switch (STS) is used to transfer the load from the primary source to
alternative source when a voltage dip is detected in the primary source. The load is transferred
between the two sources by a static switch, which is composed of two anti- parallel thyristors per
phase. The STS includes two three-phase static switches, as shown in Fig 3.3. The transfer time of the
STS ranges from 1/4 to 1/2 cycle of the fundamental frequency. Thus, the loads only suffer the
voltage dip for this transfer time, which most of the loads can tolerate. The main disadvantage of the
STS is that the continuous conducting of the thyristors causes a considerable conducting loss,
especially in high power applications, and the healthy source experiences a 1/4 or 1/2 cycle voltage
notch. [12]
Fig.3.3 Static transfer switch.
3.2.4 Uninterruptible Power Supply
An Uninterruptible Power Supply (UPS) consists of a diode rectifier, an inverter and an energy
storage, which is usually a battery, connected to the dc link. The scheme is shown in Fig.3.4. Under
normal conditions, the power is transferred from the power system to the load while the ac voltage is
rectified and then inverted. The battery works in standby mode and keeps the dc voltage constant.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 7
CHAPTER -1 INTRODUCTION
However, the battery releases the energy to maintain the dc voltage when a voltage dip or interruption
occurs in the power system. Depending on the capacity of the battery, the load can be supplied for
several minutes or hours.
The UPS is one of the most common solutions for low power loads like computer due to its low
cost, simple operation and control. This solution is not suitable for the high power loads because of
the high costs associated with the losses of additional energy conversions and maintenance of the
battery. [12]
Fig.3.4 Uninterruptible power supply.
3.2.5 Static VAR compensator
SVC is one of the most commonly used solution to voltage control and reactive power control in
past years as well as capacitor banks. It can also perform some other tasks such as improvement in ac
system stability, damping power oscillations, voltage flicker mitigation, over voltage limitation at
load rejection, etc. SVC topology may consist of TCR (Thyrisor controlled reactor) and TCR
(Thyristor controlled capacitor).A SVC contains both these elements and in addition harmonic filters.
Fig 3.5 shows simple topology of SVC. [29]
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 8
CHAPTER -1 INTRODUCTION
Fig 3.5 simple one line diagram of SVC
3.2.6 Solution of Harmonic mitigation using power filters
Power filters are classified into two types namely passive filters and Active Filters
3.2.6.1 Passive filters
Harmonic distortion in power distribution systems can be suppressed using two approaches
namely, passive and active powering. The passive filtering is the simplest conventional solution to
mitigate the harmonic distortion. Although simple, the use of passive elements does not always
respond correctly to the dynamics of the power distribution systems. Over the years, these passive
filters have developed to high level of sophistication. Some even tuned to bypass specific harmonic
frequencies.
Conventional passive filters consist of inductance, capacitance, and resistance elements configured
and tuned to control harmonics. Figure 3.6 shows common types of passive filters and their
configurations
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 9
CHAPTER -1 INTRODUCTION
Single – tuned 1st-orderHigh-pass 2nd-orderHigh-pass 3rd-orderHigh-pass Figure 3.6 Common types of passive filters and their configurations
The notch filter is connected in shunt with the power distribution system and is series-
tuned to present low impedance to a particular harmonic current. Thus, harmonic currents are
diverted from their normal flow path through the filter. Another popular type of passive filter
is the high-pass filter (HPF). A HPF will allow a large percentage of all harmonics above its
corner frequency to pass through. The first-order, which is characterized by large power
losses at fundamental frequency, is rarely used. The second-order HPF is the simplest to
apply while providing good filtering action and reduced fundamental frequency losses. The
filtering performance of the third-order HPF is superior to that of the second-order HPF.
However, it is found that the third-order HPF is not commonly used for low-voltage or
medium-voltage applications since the economic, complexity, and reliability factors do not
justify them.
Although simple and least expensive, the passive filter inherits several shortcomings.
The filter components are very bulky because the harmonics that need to be
suppressed are usually of the low order.
Furthermore the compensation characteristics of these filters are influenced by the
source impedance. As such, the filter design is heavily dependent on the power
system in which it is connected to.
Passive filters are known to cause resonance, thus affecting the stability of the power
distribution systems.
Frequency variation of the power distribution system and tolerances in components
values affect the filtering characteristics. The size of the components become
impractical if the frequency variation is large.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 10
CHAPTER -1 INTRODUCTION
As the regulatory requirements become more stringent, the passive filters might not be
able to meet future revisions of a particular Standard. This may required a retrofit of new
filters. [2]
3.2.6.2 Active Power Filters
Remarkable progress in power electronics had spurred interest in APF for harmonic
distortion mitigation. The basic principle of APF is to utilize power electronics technologies
to produce specific currents components that cancel the harmonic currents components
caused by the nonlinear load.
APFs have a number of advantages over the passive filters. First of all, they can suppress
not only the supply current harmonics, but also the reactive currents.
Moreover, unlike passive filters, they do not cause harmful resonances with the power
distribution systems. Consequently, the APFs performances are independent on the power
distribution system properties. On the other hand, APFs have some drawbacks. Active
filtering is a relatively new technology, practically less than four decades old. There is still a
need for further research and development to make this technology well established.
An unfavorable but inseparable feature of APF is the necessity of fast switching of high
currents in the power circuit of the APF. This results in a high frequency noise that may
cause an electromagnetic interference (EMI) in the power distribution systems. In general,
APFs are divided into three main categories, namely shunt APF, series APF and hybrid APF.
[2]
3.2.6.2.1 Shunt Active Power Filter
This is most important configuration and widely used in active filtering applications. A
shunt APF consists of a controllable voltage or current source. The voltage source inverter
(VSI) based shunt APF is by far the most common type used today, due to its well known
topology and straight forward installation procedure. Figure 3.7 shows the principle
configuration of a VSI based shunt APF. It consists of a DC-bus capacitor (Cf), power
electronic switches and interfacing inductors (Lf).
Shunt APF acts as a current source, compensating the harmonic currents due to nonlinear
loads. The operation of shunt APF is based on injection of compensation current which is
equals to the distorted current, thus eliminating the original distorted current. This is
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 11
CHAPTER -1 INTRODUCTION
achieved by “shaping” the compensation current waveform (if), using the VSI switches. The
shape of compensation current is obtained by measuring the load current (iL) and subtracting
it from a sinusoidal reference. The aim of shunt APF is to obtain a sinusoidal source current
(is): is= iL- if
Fig 3.7 Principle configuration of a VSI based shunt APF
Suppose the nonlinear load current can be written as the sum of the fundamental current
Component (iL,f) and the current harmonics (iL,h) according to
iL = iL,f + iL,h (3.1)
then the injected compensation current by the shunt APF should be
if = iL,h (3.2)
the resulting source current is
is= iL - if =iL,f (3.3)
which only contains the fundamental component of the nonlinear load current and thus free from
harmonics. Figure 3.8 shows the ideal source current when the shunt APF performs harmonic filtering
of a diode rectifier. The injected shunt APF current completely cancels the current harmonics from
the nonlinear load, resulting in a harmonic free source current.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 12
CHAPTER -1 INTRODUCTION
Fig 3.8 Shunt APF harmonic filtering operation principle
From the nonlinear load current point of view, the shunt APF can be regarded as a varying shunt
impedance. The impedance is zero, or at least small, for the harmonic frequencies and infinite in
terms of the fundamental frequency. As a result, reduction in the voltage distortion occurs because the
harmonic currents flowing through the source impedance are reduced. Shunt APFs have the
advantage of carrying only the compensation current plus a small amount of active fundamental
current supplied to compensate for system losses. It can also contribute to reactive power
compensation. Moreover, it is also possible to connect several shunt APFs in parallel to cater for
higher currents, which makes this type of circuit suitable for a wide range of power ratings. [2]
3.2.6.2.2 Series Active Power Filter
The series APF is shown in Figure 3.9. It is connected in series with the distribution line through a
matching transformer. VSI is used as the controlled source, thus the principle configuration of series
APF is similar to shunt APF, except that the interfacing inductor of shunt APF is replaced with the
interfacing transformer.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 13
CHAPTER -1 INTRODUCTION
Fig 3.9 Principle configuration of a VSI based series APF
The operation principle of series APF is based on isolation of the harmonics in between the
nonlinear load and the source. This is obtained by the injection of harmonic voltages (Vf) across the
interfacing transformer. The injected harmonic voltages are added/subtracted, to/from the source
voltage to maintain a pure sinusoidal voltage waveform across the nonlinear load. It is controlled in
such a way that it presents zero impedance for the fundamental component, but appears as a resistor
with high impedance for harmonic frequencies components. That is, no current harmonics can flow
from nonlinear load to source, and vice versa.
Series APFs are less common than their rival, i.e. the shunt APF. This is because they have to
handle high load currents. The resulting high capacity of load currents will increase their current
rating considerably compared with shunt APF, especially in the secondary side of the interfacing
transformer. This will increase the I2R losses. However, the main advantage of series APFs is that
they are ideal for voltage harmonics elimination. It provides the load with a pure sinusoidal
waveform, which is important for voltage sensitive devices (such as power system protection
devices). With this feature, series APF is suitable for improving the quality of the distribution source
voltage. [2]
3.2.6.2.3 Hybrid Active Power filter
In this scheme, a low cost passive high-pass filter (HPF) is used in addition to the conventional
APF. The harmonics filtering task is divided between the two filters. The APF cancels the lower order
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 14
CHAPTER -1 INTRODUCTION
harmonics, while the HPF filters the higher order harmonics. The main objective of hybrid APF,
therefore is to improve the filtering performance of high-order harmonics while providing a cost-
effective low order harmonics mitigation.
There are various hybrid APFs but the two most prominent ones are shown in Figure 4.10. Figure
3.10 (a) is the system configuration of the hybrid shunt APF. Both the shunt APF and passive filter
are connected in parallel with the nonlinear load. The function of the hybrid APF can thus be divided
into two parts: the low-order harmonics are cancelled by the shunt APF, while the higher frequency
harmonics are filtered by passive HPF. This topology lends itself to retrofit applications with the
existing shunt APF.
Figure 3.10 (b) shows the system configuration of hybrid series APF, in which the series APF is
coupled to the distribution line by an interfacing transformer. The shunt passive filter consists of one
or more single-tuned LC filters and/or a HPF. The hybrid series APF is controlled to act as a
harmonic isolator between the source and nonlinear load by injection of a controlled harmonic voltage
source. It is controlled to offer zero impedance (short circuit) at the fundamental frequency and high
impedance (ideally open circuit) at all undesired harmonic frequencies. This constrains all the
nonlinear load current harmonics to flow into the passive filter, decoupling the source and nonlinear
load at all frequencies, except at the fundamental [2].
Fig 3.10 Hybrid APFs: (a) combination of shunt APF and shunt passive filter and
(b) Combination of series APF and shunt passive filter
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 15
CHAPTER -1 INTRODUCTION
CHAPTER 4
FACTS AND CUSTOM POWER DEVICES
4.1 Introduction
Flexible AC Transmission Systems, called FACTS, got in the recent years a well known
term for higher controllability in power systems by means of power electronic devices.
Several FACTS-devices have been introduced for various applications worldwide. A number
of new types of devices are in the stage of being introduced in practice. In most of the
applications the controllability is used to avoid cost intensive or landscape requiring
extensions of power systems, for instance like upgrades or additions of substations and power
lines. FACTS-devices provide a better adaptation to varying operational conditions and
improve the usage of existing installations
The usage of lines for active power transmission should be ideally up to the thermal
limits. Voltage and stability limits shall be shifted with the means of the several different
FACTS devices. It can be seen that with growing line length, the opportunity for FACTS
devices gets more and more important. The influence of FACTS-devices is achieved through
switched or controlled shunt compensation, series compensation or phase shift control. The
devices work electrically as fast current, voltage or impedance controllers. The power
electronic allows very short reaction times down to far below one second.
The development of FACTS-devices has started with the growing capabilities of power
electronic components. Devices for high power levels have been made available in
converters for high and even highest voltage levels. The overall starting points are network
elements influencing the reactive power or the impedance of a part of the power system.
4.2 Basic types of FACTS Controllers
In general, facts controllers can be divided into four categories:
1. Series controllers
2. Shunt controllers
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 16
CHAPTER -1 INTRODUCTION
3. Combined series-series controllers
4. Combined series-shunt controllers
4.2.1 Series Controllers
The series controller could be a variable impedance, such as capacitor, reactor etc.
Power electronics based variable source of main frequency, sub synchronous and harmonic
frequencies to serve the desired need. In principle, all series controllers inject voltage in
series with the line. Even variable impedance multiplied by a current flow through it,
represents an injected series voltage in the line. As long as the voltage is in phase quadrature
with the line current, the series controller only supplies or consumes variable reactive power.
The main applications are:
1. reduction of series voltage decline in magnitude and angle over a power line,
2. reduction of voltage fluctuations within defined limits during changing power transmissions,
3. Improvement of system damping response. damping of oscillations,
4. limitation of short circuit currents in networks or substations,
5. Power flow adjustments.[6]
4.2.2 Shunt Controllers
As in the case of series controllers, the shunt controllers may be variable impedance,
variable source or a combination of these. In principle, all shunt controllers inject current into
the system at the point of connection. Even variable shunt impedance connected to line
voltage causes a variable current flow and hence represents injection of current into the line.
As long as the injected current is in phase quadrature with the line voltage the shunt
controllers only supplies or consumes variable reactive power. These shunt devices are
operating as reactive power compensators. The main applications in transmission,
distribution and industrial networks are:
1. Reduction of unwanted reactive power flows and therefore
reduced network losses.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 17
CHAPTER -1 INTRODUCTION
2. Keeping of contractual power exchanges with balanced reactive power.
3. Compensation of consumers and improvement of power quality especially with huge
demand fluctuations like industrial machines, metal melting plants, railway or
underground train systems. [6]
4.2.3 Combined Series-Series Controllers
This could be a combination of separate series controllers, which are controlled in a
coordinated manner, in a multi line transmission system or it could be a unified controller in
which series controllers provide independent series reactive compensation for each line but
also transfer real power among the lines via the power link. The real power transfer
capability of the unified series-series controller, referred to as interline power flow controller,
makes it possible to balance both the real and reactive power flow in the lines.[6]
4.2.4 Combined Series-Shunt Controllers
This could be a combination of separate shunt and series controllers which are controlled
in a coordinated manner, or a unified power flow controller with series and shunt elements.
In principle, combined shunt and series controllers inject current into the system with the
shunt part of the controller and voltage in series in the line with a series part of the controller.
However, when the shunt and series controllers are unified, there can be a real power
exchange between the series and shunt controllers via the power link. [6]
4.3 Advantages of FACTS devices
The benefits of utilizing FACTS devices in electrical systems can be summarized as
follows
1. Control of power flow as ordered.
2. Increase the loading capability of the lines to their thermal capabilities.
3. Increase the system security through raising the transient stability limit, limiting
short circuit currents and overloads and damping the electromechanical
oscillations of power systems and machines.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 18
CHAPTER -1 INTRODUCTION
4. Reduce reactive power flows, there by improving active power flows. [6]
4.4 What is Custom Power?
Custom power is the employment of power electronic or static controllers in medium and
low voltage distribution systems for the purpose of supplying a level of reliability and/or
power quality that is needed by electric power customers sensitive to power quality
variations. In other words custom power is intended to protect the customers from
interruptions and voltage reductions originating in the utility system as well as those
transferred to customers from other customers via the utility system and even internal
disturbances.
Custom power devices, or controllers, include static switches, active filters, DVRs,
injection transformers, energy storage modules that have the ability to perform current
interruption and voltage regulation functions in a distribution system to improve reliability
and/or power quality.
In a Custom Power system customer receives specified power quality from a utility or a
service provider which includes an acceptable combination of the following features:
No (or rare) power interruptions
Magnitude and duration of voltage reductions within specified limits.
Magnitude and duration of over voltages within specified limits.
Low harmonic voltage.
Low phase unbalance
The need for the Custom Power concept arises from the fact that:
1. Most of the interruptions and voltage reductions occur in the utility system on account of
lightning faults on transmission and distribution lines, trees touching the wires, equipment
failure, switching, etc. Voltage sags may also be a consequence of large load changes
affecting customers own equipment or affecting other equipment via the utility system.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 19
CHAPTER -1 INTRODUCTION
2. Impulses, switching surges and over voltages affecting the insulation, would most likely
result from lightning strikes and switching events in the transmission and distribution system.
3. Temporary over voltages lasting from several cycles to several seconds would largely
result from large load changes, capacitor switching, transformer switching, excessive
leading-VARs during light loads, etc. in the utility system.
4. Voltage unbalances in a three-phase supply would occur mostly due to large unbalanced
loads on a utility's distribution lines and long lines with unbalanced phase impedances.
5. Harmonics would most likely be the consequence of high harmonics in the customer load,
or the saturation of a utility's transformers. These harmonics would then be amplified by the
natural resonances in the utility system and/or the customer system. [5]
4.5 Custom Power Devices
Just as FACTS controllers improve the reliability and quality of power transmission
systems, the custom power enhances the quality and reliability of power delivered to
customer.Custom Power Devices are intended for improving the power quality of distribution
networks against disturbances such as
sags, swells,
Transients, harmonics.
The incorporation of the classical devices, such as D-STATCOM (Distribution Static
Synchronous Compensator), DVR (Dynamic Voltage Restorer), and UPQC (Unified Power
Quality Conditioner), means a continuous control, with a very fast response time, and they
allow and assure an improvement in the wave quality of the power supply.
A DSTATCOM can compensate for distortion and unbalance in a load such that a
balanced sinusoidal current flows in the feeder. A DVR can compensate for voltage sag/swell
and distortion in the supply side voltage such that the voltage across a sensitive/critical load
terminal is perfectly regulated. A UPQC can perform the functions of both DSTATCOM and
DVR.The following terminologies useful for a better study of UPQC. [1]
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 20
CHAPTER -1 INTRODUCTION
4.5.1 Dynamic Voltage Restorer (DVR)
The DVR is a powerful controller that is commonly used for voltage sags mitigation at
the point of connection. The DVR employs VSC, coupling Transformer and DC energy
storage capacitor and the coupling transformer connected in series with the ac system, as
illustrated in Fig 4.1. The VSC generates a three-phase ac output voltage, which is
controllable in phase and magnitude These voltages are injected into the ac distribution
system in order to maintain the load voltage at the desired voltage reference.
Fig 4.1 Schematic representation of the DVR
The DVR is a solid state dc to ac switching power converter that injects a set of three
single phase ac output voltages in series with the distribution feeder and in synchronism with
the voltages of the distribution system. By injecting voltages of controllable amplitude, phase
angle and frequency (harmonic) into the distribution feeder in instantaneous real time via a
series injection transformer, the DVR can restore the quality of voltage at its load side
terminals when the quality of the source side terminal voltage is significantly out of
specification for sensitive load equipment.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 21
CHAPTER -1 INTRODUCTION
4.5.1.1 Principle of operation of Series-connected VSC (DVR)
The basic idea involved in principle of operation is to inject a voltage ec(t) of desired
amplitude, frequency and phase between the PCC and the load in series with the grid voltage.
A typical configuration of the DVR is shown in Fig.4.2. Figure 4.3 shows a simplified single-
line diagram of the system with DVR.The DVR can be represented as a voltage source with
controllable amplitude, phase and frequency. The DVR is mainly used for voltage dip
mitigation. The device maintains the load voltage el(t) to the pre-fault condition by injecting
a fundamental voltage of appropriate amplitude and phase. Figure 4.4 shows the phasor
diagram of the series injection principle during voltage dip mitigation, where Ec is the phasor
of the voltage injected by the compensator, Il is the phasor of the load current and where Ψ is
the angle displacement between load voltage and current. In order to be able to restore both
magnitude and phase of the load voltage to the pre-fault conditions, the DVR has to inject
both active and reactive power. The voltage dip mitigation capability of this device depends
on the rating of the energy storage and on the voltage ratings of the VSC and the injection
transformer.
Fig. 4.2 Single line diagram of series connected VSC
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 22
CHAPTER -1 INTRODUCTION
Fig.4.3 Simplified line diagram of series connected VSC
Fig. 4.4 Phasor diagram of voltage mitigation using series VSC
The reactive power exchanged between the DVR and distribution system is internally
generated by the DVR without any ac passive reactive components, i.e. reactors and
capacitors. For large variations in the source voltage, the DVR supplies partial power to the
load from a rechargeable energy source attached to the DVR dc terminal. The DVR, with its
three single phase independent control and inverter design is able to restore line voltage to
critical loads during sags caused by unsymmetrical L-G, LL, L-L-G, as well as symmetrical
three phase faults on adjacent feeders or disturbances that may originate many miles away on
the higher voltage interconnected transmission system. Connection to the distribution
network is via three single-phase series transformers there by allowing the DVR to be applied
to all classes of distribution voltages. At the point of connection the DVR will, within the
limits of its inverter, provide a highly regulated clean output voltage.
4.5.2 Distribution STATCOM (DSTATCOM)
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 23
CHAPTER -1 INTRODUCTION
The DSTATCOM is basically one of the custom power devices. It is nothing but a
STATCOM but used at the Distribution level. The key component of the DSTATCOM is a
power VSC that is based on high power electronics technologies.
The Distribution STATCOM (shown in Fig 4.5) is a versatile device for providing
reactive compensation in ac networks. The control of reactive power is achieved via the
regulation of a controlled voltage source behind the leakage impedance of a transformer, in
much the same way as a conventional synchronous compensator. However, unlike the
conventional synchronous compensator, which is essentially a synchronous generator where
the field current is used to adjust the regulated voltage, the DSTATCOM uses an electronic
voltage sourced converter (VSC), to achieve the same regulation task. The fast control of the
VSC permits the STATCOM to have a rapid rate of response.
The DSTATCOM is the solid – state based power converter version of the SVC.
Operating as a shunt – connected SVC, its capacitive or inductive output currents can be
controlled independently from its connected AC bus voltage. Because of the fast switching
characteristic of power converters, the DSTATCOM provides much faster response as
compare to SVC. DSTATCOM is a shunt connected, reactive compensation equipment,
which is capable of generating and or absorbing reactive power whose output can be varied
so as to maintain control of specific parameters of the electric power system. DSTATCOM
provides operating characteristics similar to a rotating synchronous compensator without
mechanical inertia, due to the DSTATCOM employ solid state power switching devices it
provides rapid controllability of the three phase voltages, both in magnitude and phase angle.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 24
CHAPTER -1 INTRODUCTION
Fig 4.5 Schematic representation of the DSTATCOM
In addition, in the event of a rapid change in system voltage, the capacitor voltage does
not change instantaneously; therefore the DSTATCOM reacts for the desired responses. For
example, if the system voltage drops for any reason, there is a tendency for the DSTATCOM
inject capacitive power to support the dipped voltages.
4.5.2.1 Principle of operation of Shunt-Connected VSC
The basic idea of the shunt-connected VSC is to dynamically inject a current i r(t) of
desired amplitude, frequency and phase into the grid. The typical configuration of a shunt-
connected VSC is shown in Fig.4.6. The device consists of a VSC, an injection transformer,
an ac filter and a dc-link capacitor. Energy storage can also be mounted on the dc link to
allow active power injection into the ac grid.
The line impedance has a resistance Rg and inductance Lg. The grid voltage and current
are denoted by es(t) and ig(t), respectively. The voltage at the point of common coupling
(PCC), which is also equal to the load voltage, is denoted by eg(t) and the load current by il(t).
The inductance and resistance of the ac-filter reactor are denoted by Lr and Rr respectively.
Figure 4.7 shows a simplified single-line diagram, where the VSC is represented as a current
source. Amplitude, frequency and phase of the current ir(t) can be controlled. By injecting a
controllable current, the shunt-connected VSC can limit voltage fluctuation leading to flicker
and cancel harmonic currents absorbed by the load, thus operating as an active filter. In both
cases, the principle is to inject a current with same amplitude and opposite phase as the
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 25
CHAPTER -1 INTRODUCTION
undesired frequency components in the load current, so that they are cancelled in the grid
current.
These mitigation actions can be accomplished by only injecting reactive power. A shunt-
connected VSC can also be used for voltage dip mitigation. In this case, the device has to
inject a fundamental current in the grid, resulting in an increased voltage amplitude at the
PCC, as shown in the phasor diagram in Fig.4.8. The voltage phasor at PCC is denoted by
Eg, Zg is the line impedance, Es,dip is the grid voltage phasor during the dip and Ψ is the
phase-angle jump of the dip. From the diagram it is possible to understand that when the
shunt-connected VSC is used to mitigate voltage dips, it is necessary to provide an energy
storage for injection of active power in order to avoid phase-angle jumps of the load voltage.
If only reactive power is injected, it is possible to maintain the load voltage amplitude Eg to
the pre-fault conditions but not its phase. Therefore, the voltage dip mitigation capability of a
shunt-connected VSC depends on the rating of the energy storage and on the rating in
current.
Fig. 4.6 Single line diagram of shunt connected VSC
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 26
CHAPTER -1 INTRODUCTION
Fig.4.7 Simplified line diagram of shunt connected VSC
Fig 4.8 Phasor diagram of voltage dip mitigation using shunt VSC
4.5.3 Unified Power Quality Conditioner (UPQC)
Poor power quality in a system could be due to different factors such as voltage sag,
voltage swell, voltage outage and over correction of power factor and unacceptable levels of
harmonics in the current and voltage. Modern solution for poor power quality is to take
advantage of advanced power electronics technology.
Recent research efforts have been made towards utilizing a device called unified power
quality conditioner (UPQC) to solve almost all power quality problems. The main purpose of
a UPQC is to compensate for supply voltage flicker/imbalance, reactive power, and
harmonics. In other words, the UPQC has the capability of improving power quality at the
point of installation on power distribution systems or industrial power systems. The UPQC,
therefore, is expected as one of the most powerful solutions to large capacity loads sensitive
to voltage flicker/imbalance.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 27
CHAPTER -1 INTRODUCTION
Unified Power Quality Conditioner (UPQC) for non-linear and voltage sensitive loads has
following facilities.
It eliminates the harmonics in the supply current, thus improves utility current
quality for nonlinear loads.
UPQC provides the VAR requirement of the load, so that the supply voltage
and current are always in phase, therefore, no additional power factor
correction equipment is necessary.
UPQC maintains load end voltage at the rated value even in the presence of supply
voltage sag.
The voltage injected by UPQC to maintain the load end voltage at the desired value
is taken from the same dc link, thus no additional dc link voltage support is required
for the series compensator.
The UPQC consists of two three phase inverters (VSI) connected in cascade in such a
manner that one inverter is connected in parallel with the load. Second Inverter is connected
in series with the supply voltage through a transformer (Figure 4.9). [5]
The main purpose of the shunt compensator is to compensate for the reactive power
demanded by the load, to eliminate the harmonic components of
nonlinear loads in such a way that the source current is sinusoidal and
balanced. This equipment is a good solution for the case when the voltage
source presents distortion and a harmonic sensitive load is close to a
nonlinear load.
The series compensator is operated in PWM voltage controlled mode. It
injects voltage in quadrature advance to the supply voltage (current) such
that the load end voltage is always maintained at the desired value. The
two inverters operate in a coordinated manner.
.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 28
CHAPTER -1 INTRODUCTION
Fig 4.9 Basic Block Diagram of UPQC
If UPQC is connected between two feeders then the new conditioner developed which is
called Interline Unity Power Quality conditioner (IUPQC).This IUPQC comes under series-
shunt facts device.
CHAPTER 5
INTERLINE UNIFIED POWER QUALITY CONDITIONER (IUPQC)
5.1 Introduction
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 29
CHAPTER -1 INTRODUCTION
Voltage-source converter based custom power devices are increasingly being used in
custom power applications for improving the power quality (PQ) of power distribution
systems. Devices such as distribution static Compensator (DSTATCOM) and dynamic
voltage restorer (DVR) have already been discussed extensively. A DSTATCOM can
compensate for distortion and unbalance in a load such that a balanced sinusoidal current
flows through the feeder. It can also regulate the voltage of a distribution bus. A DVR can
compensate for voltage sag/swell and distortion in the supply side voltage such that the
voltage across a sensitive/critical load terminal is perfectly regulated. A unified power-
quality conditioner (UPQC) can perform the functions of both DSTATCOM and DVR .The
UPQC consists of two voltage-source converters (VSCs) that are connected to a common dc
capacitor. One of the VSCs is connected in series with a distribution feeder, while the other
one is connected in shunt with the same feeder. It is also possible to connect two VSCs to
two different Feeders in a distribution system. [1]
5.2 IUPQC to Control power Quality
The series and shunt connected forms the basic principle for the operation of UPQC as it
is the back to back connection of the series and shunt connection of the VSCs. If the UPQC
device is connected between two feeders fed from different substations then it is called as
interline Unified Power Quality Conditioner(IUPQC).IUPQC cam improve the power
quality by injecting voltage in to any feeder from the DC link Capacitor. This whole
operation is controlled by controlling the two voltage souse converters (VSC) connected
between the two feeders in the Electrical distribution system. [1]
5.3 Structure and Control
The IUPQC shown in Fig. 5.1 consists of two VSCs (VSC-1 and VSC-2) that are
connected back to back through a common energy storage dc capacitor. Let us assume that
the VSC-1is connected in shunt to Feeder-1 while the VSC-2 is connected in series with
Feeder-2. Each of the two VSCs is realized by three H-bridge inverters. Inverters are
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 30
CHAPTER -1 INTRODUCTION
supplied from a common single dc capacitor and each inverter has a transformer connected at
its output.
Fig 5.1 Structure of IUPQC Controller
The complete structure of a three-phase IUPQC with two such VSCs is
shown in Fig.5.2. The secondary (distribution) sides of the shunt-
connected transformers are connected in star with the neutral point being
connected to the load neutral. The secondary winding of the series-
connected transformers are directly connected in series with the bus B-2
and load L-2. The ac filter capacitors Cf and Ck are also connected in each
phase to prevent the flow of the harmonic currents generated due to
switching. The six inverters of the IUPQC are controlled independently. [1]
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 31
CHAPTER -1 INTRODUCTION
Fig. 5.2 Complete structure of an IUPQC
5.4 Structure of a VSC in IUPQC
The schematic structure of a VSC in IUPQC is shown in Fig. 6.3. In this structure, each
switch represents a power semiconductor device (e.g.MOSFET,IGBT) and an anti-parallel
diode as shown in Fig.5.3.
Fig 5.3 Schematic structure of VSC
All the inverters are supplied from a common single dc capacitor Cdc and each inverter
has a transformer connected at its output. The six inverters of the IUPQC are controlled
independently. The switching action is obtained using output feedback control. [1]
5.4.1 Basics of Voltage Source Converter
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 32
CHAPTER -1 INTRODUCTION
Generally Pulse-Width Modulated Voltage Source Inverter (PWMVSI) is
used. The basic function of the VSI is to convert the DC voltage supplied
by the energy storage device into an AC voltage. In the DVR power circuit
step up voltage injection transformer is used. Thus a VSI with a low
voltage rating is sufficient. The common inverter connection method for
three phase DVRs are 3 phase Graetz bridge inverter as shown in Fig 5.4
This is referred to as two-level since the phase output voltage waveform
consists of two output levels; +Vd and 0 Volts. [18]
Fig. 5.4 Three phase voltage source converter
It is made of six valves each consisting of a gate turn off device (GTO) paralleled with a
reverse diode, and a DC capacitor. An AC voltage is generated from a DC voltage through
sequential switching of the GTOs. The DC voltage is unipolar and the DC current can flow in
either direction.
Controlling the angle of the converter output voltage with respect to the AC system
voltage controls the real power exchange between the converter and the AC system. The real
power flows from the DC side to AC side (inverter operation) if the converter output voltage
is controlled to lead the AC system voltage. If the converter output voltage is made to lag the
AC system voltage the real power will flow from the AC side to DC side (rectifier
operation). Inverter action is carried out by the GTOs while the rectifier action is carried out
by the diodes. Two switches on the same leg cannot be on at the same time.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 33
CHAPTER -1 INTRODUCTION
Controlling the magnitude of the converter output voltage controls the reactive power
exchange between the converter and the AC system. The converter generates reactive power
for the AC system if the magnitude of the converter output voltage is greater than the
magnitude of the AC system voltage. If the magnitude of the converter output voltage is less
than that of the AC system the converter will absorb reactive power.
5.4.1.1 H bridge inverter
In the H bridge inverter, four switches are used. When it used for
multilevel arrangement especially for high voltage application, it is
commonly called as chain circuits. For fundamental switching each switch
is on for a duty cycle of 50% and shown in Figure 5.5. 18]
Figure 5.5 H-bridge inverter configuration
The Inverter contains four switches S1-S4, each comprising a semi-conductor device and
an anti-parallel diode as indicated in fig 5.5. Power semiconductor device can be a power
MOSFET for low power applications.
The Inverter is supplied by a DC source with a voltage of Vdc.The switch of each leg
usually have complementary values, e.g: when S1 is ON, S4 is OFF and vice versa. Further
the switches are operated in pairs. When the switches S1 & S2 are ON, S3 & S4 are OFF.
Similarly when S3 & S4 are ON, S1& S2 are OFF. However a small time delay is provided
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 34
CHAPTER -1 INTRODUCTION
between the turn OFF a pair of switches and turning ON the other pair. This period is called
‘Blanking Period’, is provided to prevent the DC source from being short circuited.
Consider for example the transition when S3 and S4 are turned OFF and S1 & S2 are
turned ON.Durng this period if the switch S1 gets turned ON before the switch S4 turns OFF
completely, then it will connect the two leads of the DC source directly. It is therefore
mandatory that switch S4 turns OFF completely before the switch S1 is turned ON. To
ensure this, the blanking Period (dead time) is used. Continuity of the current during the
blanking period is maintained by the anti-parallel diode. [26]
5.4.2 PWM-control scheme
There are many forms of modulation used for communicating information. When
communication is by pulses was introduced, the amplitude, frequency and pulse width
become possible modulation options. In many power electronic converters pulse width
modulation (PWM) the most reliable way of reconstructing a desired out put voltage wave
form. For a reliable signal representation it is necessary that the frequency of switching be
significantly higher than that of the desired signal.
Modulation in power electronics is a process of a switched representation of a wave form.
The switched representation is more efficient form. Ideally the switched signal can handle
high power with efficiency 100%. [26]
5.4.2.1 Sinusoidal PWM for H-Bridge Inverter
The schematic diagram for generation of PWM control signal is shown in fig 5.6.
It contains a carrier signal and a modulating signal. The magnitudes of these two signals
are compared through an analog comparator. The PWM control signal is set HIGH when
modulating signal has a higher numerical value than the carrier signal and is set LOW when
the carrier signal has a higher numerical value.
This implies that in the H-Bride inverter, switches S1 & S2 (fig 6.5) are closed when
modulating signal is higher than the carrier and switches S3 & S4 are closed when carrier is
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 35
CHAPTER -1 INTRODUCTION
higher than the modulating signal. Since the out put voltage of the Inverter for such an
arrangement is +Vdc or –Vdc, this is called bipolar voltage switching.
Fig 5.6 Generation of PWM control signal
The most popular form of PWM synthesis is the Sinusoidal PWM (SPWM).In an SPWM
the modulating signal is sinusoidal and carrier signal is a triangular wave. The frequency of
the modulating signal is chosen to be the fundamental frequency of the output waveform to
be synthesized. [26]
The converter output voltage can be controlled using various control techniques. Pulse
Width Modulation (PWM) techniques can be designed for the lowest harmonic content.
When sinusoidal PWM technique is applied turn on and turn off signals for GTOs are
generated comparing a sinusoidal reference signal Vr of amplitude Ar with a triangle carrier
waveform Vc of amplitude Ac as shown in Fig 6.6 The frequency of the triangle waveform
establishes the frequency at which GTOs are switched.
Consider a phase-leg as shown in Fig. 5.7(a) In this case Vr>Vc results in a turn on signal
for the device one and gate turn off signal for the device four and Vr<Vc results in a turn off
signal for the device one and gate turn on signal for the device four.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 36
CHAPTER -1 INTRODUCTION
Fig. 5.7 PWM inverter (a) A phase leg, (b) PWM waveforms
The fundamental frequency of the converter output voltage is determined by the
frequency of the reference signal. Controlling the amplitude of the reference signal controls
the width of the pulses. The amplitude modulation index is defined as ratio of Ar to Ac
m = Ar/Ac (5.1)
For m≤1 the peak magnitude of the fundamental frequency component of the converter
output voltage can be expressed as
V=m Vdc/2 (5.2)
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 37
CHAPTER -1 INTRODUCTION
Fig 5.8 Voltage Control block Diagram
The aim of the control scheme is to maintain constant voltage magnitude at the point
where a sensitive load is connected, under system disturbances. The control system only
measures the rms voltage at the load point. The VSC switching strategy is based on a
sinusoidal PWM technique which offers simplicity and good response. Besides, high
switching frequencies can be used to improve on the efficiency of the converter, without
incurring significant switching losses. An error signal is obtained by comparing the reference
voltage with the rms voltage measured at the load point.
The PI controller process the error signal and generates the required delay angle to drive
the error to zero, i.e., the load rms voltage is brought back to the reference voltage. In the
PWM generators, the sinusoidal V control signal is phase modulated by means of the delay
angle. The modulated signal Vcontrol is compared against a triangular signal (carrier) in
order to generate the switching signals for theVSC valves. [27]
5.5 System Description
An IUPQC connected to a distribution system is shown in Fig 5.9. In this figure, the
feeder impedances are denoted by the Pairs (Rs1, Ls1) and (Rs2, Ls2). It can be seen that the
two feeders supply the loads L-1 and L-2. The load L-1 is assumed to have two separate
components—an unbalanced part (L-11) and a non-linear part (L-12). The currents drawn by
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 38
CHAPTER -1 INTRODUCTION
these two loads are denoted by il11and il12 respectively. We further assume that the load L-2 is
a sensitive load that requires uninterrupted and regulated voltage. The shunt VSC (VSC-1) is
connected to bus B-1 at the end of Feeder-1, while the series VSC (VSC-2) is connected at
bus B-2 at the end of Feeder-2. The voltages of buses B-1 and B 2 and across the sensitive
load terminal are denoted by Vt1, Vt2 and Vl2 respectively.
The aim of the IUPQC is two-fold:
1. To protect the sensitive load L-2 from the disturbances occurring in the system by
regulating the voltage Vt2.
2. To regulate the bus B-1 voltage Vt1 against sag/swell and or disturbances in the system.
Due to the presence of unbalanced and non-linear load L-1, the voltage is both unbalanced
and distorted. Also, the load L-11 causes an unbalance in the current. While load L-12 causes
distortion in the current.
. Fig. 5.9 Typical IUPQC connected in distribution system
In order to attain these aims, the shunt VSC-1 is operated as a voltage controller while
the series VSC-2 regulates the voltage Vt2 across the sensitive load. Due to the presence of
unbalanced and non-linear load L-1, the voltage is both unbalanced and distorted. Also, the
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 39
CHAPTER -1 INTRODUCTION
load L-11 causes an unbalance in the current, while load L-12 causes distortion in the current
.These waveforms can be improved using the IUPQC. [1]
5.6 IUPQC Operation
The shunt VSC (VSC-1) holds the voltage of bus B-1 constant. This is accomplished by
making the VSC-1 to track a reference voltage across the filter capacitor Cf . The equivalent
circuit of the VSC-1 is shown in Fig. 5.8 (a) in which u1.Vdc denote the inverter output
voltage where Vdc is dc capacitor voltage and u1 is switching action equal to + n1 or –
n1where n1is turns ratio of the transformers of VSC-1. In Fig 6.8(a), the inverter losses and
leakage inductance of the transformers are denoted by Rf1 and Lf1 respectively. All system
parameters are referred to the line side of the transformers.
Defining the state vectors
(5.3)
The state space model of the voltage source converter -1 is written as
(5.4)
y= vt1 =Hx1 (5.5)
Where
(5.6)
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 40
CHAPTER -1 INTRODUCTION
(5.7) H= [1 0] (5.8)
(5.9)
Fig 5.8 (a) Single-phase equivalent circuit of VSC-1
u1c is the continuous time equivalent of u1. The system given here is descretized and is
written in input–output form as
A1(Z-1)y1(k)=B1(Z-1)u1c(k)+C1(Z-1)η1(k)
(5.10)
Where η1is a disturbance which is equal to ish.A pole shift controller is used to
determine the switching action u1 from u1c .and is used to track a reference signal y1ref(k).
The reference y1ref(k) is the desired voltage of the bus B-1.The peak of this
instantaneous voltage is pre-specified and its phase angle is adjusted to maintain the power
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 41
CHAPTER -1 INTRODUCTION
balance in the System. To set the phase angle, we note that the dc capacitor must be able to
supply VSC-1 while maintaining its dc bus voltage constant by drawing power from the ac
system .A proportional controller is used for controlling the dc capacitor voltage and is given
by δ1=K1 (Vdcref - Vdcav) (5.11) Where Vdcref is the average voltage across the dc capacitor over a cycle Vdcav is its set
reference value and K1 is the proportional gain. It is to be noted that the average voltage is
obtained using a moving average low pass filter to eliminate all switching components from
the signal. The equivalent circuit of the VSC-2 is shown in Fig. 5.8(b) and is similar to the
one shown in Fig. 5.8 (a) in every respect.
Fig 5.8 (b) Single-phase equivalent circuit of VSC-2
Defining a state and input vector, respectively, as
x2T= [Vk if2] (5.12)
z2T= [u2c is2] (5.13)
and the state space model for VSC-2 is given as
(5.14) y2 =Vt2=Hx2 (5.15)
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 42
CHAPTER -1 INTRODUCTION
where F2 and G2 are matrices that are similar to and F1 and G1 respectively. The
discrete-time input–output equivalent of is given as
A2(Z-1)y2(k)=B2(Z-1)u2c(k)+C2(Z-1) η2(k) (5.16)
Where η2 is a disturbance which is equal to is2.A pole shift controller
is used to determine the switching action u2 from u2c. A separate pole-shift
controller is used to determine the switching action so as to track the reference signal.
From Fig. 5.8(b), the purpose of the VSC-2 is to hold the voltage across the sensitive load
L-2 constant. Let us denote the reference load L-2 voltage as Vl2. Then the reference yref(k)
is computed by the application of Kirchoff’s voltage law as
yref (k) = v* l2 - vt2 (5.17)
Now demonstration of the operation of the IUPQC is through simulation using MATLAB.
[1]
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 43
CHAPTER -1 INTRODUCTION
CHAPTER 6
SIMULATION AND RESULTS
6.1 Introduction
In the analysis of IUPQC, the device is connected between two feeders; at the end of
feeder-1 non linear load and unbalanced loads are connected and at the end of feeder -2
sensitive load is connected. When the power system with these loads and without any
conditioner, develops poor power quality. This is in the form of voltage Sags (Swells). When
the conditioner like IUPQC is connected to the power system, it compensates the voltage
sags and maintains power quality. Now, the performance of IUPQC has been evaluated
considering various disturbance conditions. All the simulation work is done on the
MATLAB/SIMULINK
6.2 MATLAB/SIMULINK model of distribution system without IUPQC
This work presents a new connection for a UPQC called interline UPQC
(IUPQC). Two feeders called Feeder-1 and Feeder-2, which are connected
to two different substations, supply the system loads L-1 and L-2. The
purpose of the IUPQC is to hold the voltages and constant against voltage
sag/swell, temporary interruption in either of the two feeders. It has been
demonstrated that the IUPQC can absorb power from one feeder (say
Feeder-1) to hold constant in case of a sag in the voltage. This can be
accomplished as the two VSCs are supplied by a common dc capacitor.
The performance of the IUPQC has been evaluated through simulation
studies using MATLAB/SIMULINK.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 44
CHAPTER -1 INTRODUCTION
Fig 6.1 shows the distribution system without IUPQC is simulated in
MATLAB/SIMULINK. Here two blocks are considered one is source and second is load.
Three phase AC voltage source is used in MATLAB/SIMULINK. This source is connected
to three phase RL branch which gives the line resistance and reactance. Here the supply
is connected to the load L-1.and again the load L-1 is assumed to have
two separate components—an unbalanced part (L-11) and a non-linear
part (L-12).Here Bridge operation is considered. In bridge operation because of continuous
switching operation of the switches harmonics are developed in both supply side and load
side.
Fig 6.1 Simulink model of distribution system without IUPQC
Due to presence of the unbalanced and non-linear load the system response gives poor
power quality. This can be observed by seeing the response of the distribution system.
Fig.6.2 shows the three phase line voltage across unbalanced load without IUPQC is
considered, here because of the unbalanced condition, all the three phase voltages are
distorted and maintaining poor power quality. When no IUPQC is connected to the system,
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 45
CHAPTER -1 INTRODUCTION
there is no matter of introducing capacitive storage voltage in to the line, so the waveforms
are distorted.
Fig 6.3 shows three phase voltage across non-linear load without IUPQC .Due to
continuous switching operation of the thyristors, the voltage across the bridge circuit are
distorted.
Fig 6.4 shows three phase line current passing in to the load. These are also unbalanced.
So the main objective of IUPQC is to regulate these distorted unbalanced voltages and
currents.
Fig 6.2.Three phase line voltages across unbalanced load without IUPQC
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 46
CHAPTER -1 INTRODUCTION
Fig 6.3: Three phase line voltages across non-linear load without IUPQC
Fig 6.4: Three phase currents passing in to the load without IUPQC
6.3 MATLAB/SIMULINK model of distribution system with IUPQC
In this present work an IUPQC connected to a distribution system is
shown in Fig.6.5. Two feeders called Feeder-1 and Feeder-2, which are
connected to two different substations, supply the system loads L-1 and L-
2. Load L1 has two components one is unbalanced load (L11) and other is
non-linear load (L12).Load L2 is sensitive load. The IUPQC is connected
between two buses, and the IUPQC take care about maintaing constant
voltage at supply side of feeder1 and voltage across the sensitive load.
The IUPQC shown in Fig. 6.5 consists of two VSCs (VSC-1 and VSC-2) that are
connected back to back through a common energy storage dc capacitor.VSC-1 is connected
in shunt to Feeder-1 while the VSC-2 is connected in series with Feeder-2. Each of the two
VSCs is realized by three H-bridge inverters. In Voltage source converters, each switch is a
MOSFET with an anti-parallel diode. All the inverters are supplied from a common single dc
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 47
CHAPTER -1 INTRODUCTION
capacitor and each inverter has a transformer connected at its output. The secondary
(distribution) sides of+ the shunt-connected transformers are connected in star with the
neutral point being connected to the load neutral. The secondary winding of the series-
connected transformers are directly connected in series with the bus-2 and load L-2. The ac
filter capacitors Cf and Ck are also connected in each phase to prevent the
flow of the harmonic currents generated due to switching.
Fig 6.5 Simulink model of distribution system with IUPQC
The figure 6.6 represents the SIMULINK block of shunt connected VSC used in the
IUPQC device. It consists of three H-bridge inverters with twelve switching devices
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 48
CHAPTER -1 INTRODUCTION
(MOSFETS). The shunt VSC has three step-down identical transformers (1MVA, 11/3Kv).
The triggering pulses for the gate terminals are obtained from the PWM controller circuit
respectively.
The figure 6.7 represents the SIMULINK block of series connected VSC in the IUPQC
device. It consists of three H-bridge inverters with twelve switching devices (MOSFETS).
The series VSC has three step-up identical transformers (1MVA, 3/11Kv). The triggering
pulses for the gate terminals are obtained from the PWM controller circuit respectively.
Fig 6.6 Shunt connected VSC
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 49
CHAPTER -1 INTRODUCTION
Fig. 6.7 Series connected VSC
The aim of the IUPQC is two-fold:
1. To protect the sensitive load L-2 from the disturbances occurring in the system by
regulating the voltage
2. To regulate the bus voltage to which loads L-11 and L-12 are connected against
sag/swell and or disturbances in the system.
To analyze these, two conditions are considered, one is sag occurred in
feeder-1.Second is sag occurred in second feeder-2.
When the system with IUPQC as shown in the figure 7.5 is considered, all the voltages
and currents of the system are balanced without any distortions. This is because the capacitor
discharging the stored voltage in to the line by using controls circuit. It is assumed that
initially the capacitor is uncharged, and this capacitor acts as the conditioner for the distorted
and unbalanced voltages.
When the system without IUPQC is considered, because of the harmonics due to non
linear load it gives poor power quality. When the IUPQC is connected, it works as
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 50
CHAPTER -1 INTRODUCTION
conditioner to maintain constant voltage across sensitive load and voltage at supply side. The
conditioned voltages are shown in the following figures. Fig 6.8 shows three phase line
voltages across unbalanced load with IUPQC. Fig 6.9 shows three phase line voltages across
non-linear load with IUPQC. Fig 6.10 Three phase currents passing in to the load with
IUPQC. It is observed from all figs that all responses are maintaining values prior to
disturbance; hence IUPQC improves the power quality.
Fig 6.8 Three phase line voltages across unbalanced load with IUPQC
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 51
CHAPTER -1 INTRODUCTION
Fig 6.9 Three phase line voltages across non-linear load with IUPQC
Fig 6.10 Three phase currents passing in to the load with IUPQC
6.4 System with Voltage Sag in Feeder-1
System with IUPQC and having sag in feeder-1 as shown in Fig. 6.11. Now to analyze
system performance against sag, sag is applied at feeder-1 by using timer and circuit
breakers. Here by changing the line impedance value which is less than existing value can
produce sag in the voltages. This logic is applied by using timer.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 52
CHAPTER -1 INTRODUCTION
Fig. 6.11 System with IUPQC and having sag in feeder-1
Two circuit breakers are connected to lines by different impedance values. When the
timer is 1, then only one circuit breaker will conducts. Like this, sag is applied in the feeder.
With the system operating in the steady state, voltage sag occurs in which peak of the
supply Voltage Vs1, reduces from their nominal value of 9 kV. The trends in the other two
phases are similar. The dc capacitor voltage Vdc, drops as soon as the sag occurs. If the bus
voltage remains constant, the load power also remains constant. However, since the source
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 53
CHAPTER -1 INTRODUCTION
voltage Vs1 has dropped, the power coming out of the source has reduced. In order to supply
the balance power requirement of the load, the Vdc drops.
To offset this, the angle δ1 retards such that the power supplied by the source increases.
As the sag is removed, both the voltage Vdc and phase angle δ1 returns to their steady state
values. In order to supply the same load power at a reduced source voltage, the feeder current
increases.
6.4.1 System response without IUPQC during sag in feeder-1
When the system without IUPQC is considered i.e. without connecting the IUPQC to the
distribution system of fig.6.11, there is no conditioning of the voltages and currents. Fig7.12
represents the source voltage and it is balanced because of that sag is applied after the source.
So it is a balanced three phase voltage. The following figures show the results of the system
without IUPQC.
Now sag is introduced in feeder 1. Fig 6.13 is voltage across the unbalanced load. Sag is
occurred from 0.1 sec to 0.2 sec. Also the voltage across the bridge circuit (non linear load)
also has the sag between 0.1 sec and 0.2 sec as shown in fig 6.14.Line current shown in fig
7.15 has the sag between 0.1sec and 0.2 sec.
This fig.6.12 represents the input voltage given to the feeder-1 at the first bus.
Fig. 6.12 Vabc_11, kV (voltage at first bus on feeder-1)
From the fig6.13, it is clear that there is a dip in the unbalanced voltage during the sag conditions and it is found at third bus of feeder-1.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 54
CHAPTER -1 INTRODUCTION
Fig. 6.13 Vabc_31, kV (voltage at third bus on feeder-1)
From the fig 6.14 it is clear that there is a dip in the non linear load voltage during the sag condition at the fourth bus of feeder-1
Fig. 6.14 Vabc_41, kV (voltage at fourth bus on feeder-1)
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 55
CHAPTER -1 INTRODUCTION
There is dip in the current waveform also at the second bus of feeder-1 shown in fig 7.15
Fig. 6.15 Iabc_21, A (current at second bus on feeder-1)
6.4.2 System response with IUPQC during sag in feeder-1
Here the system responses with IUPQC are discussed. Here the charged capacitor is
discharging depending on the control circuit. Depending on the sag value the controller is
injects the voltage in to the line. All the following figures show the results of the system with
IUPQC.
It is clear from the following waveform that the sag in the unbalanced voltage is
completely removed in the presence of the IUPQC.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 56
CHAPTER -1 INTRODUCTION
Fig. 6.16 Vabc_31, kV (voltage at third bus on feeder-1)
The sag in the nonlinear load voltage is also completely removed in the presence of IUPQC shown in fig 6.17.
Fig. 6.17 Vabc_41, kV (voltage at fourth bus on feeder-1)
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 57
CHAPTER -1 INTRODUCTION
Fig. 6.18 Iabc_21, A (current at second bus on feeder-1)
The current waveform at the second bus of feeder-1 is found to be sinusoidal.
6.5 System having Voltage Sag in Feeder-2
Now Sag is applied in feeder-2.Here also by changing the line reactance values sag is
applied in feeder-2 With the system operating in the steady state, Feeder-2 is subjected to
voltage sag in which the peak of all three phases of the supply voltage reduces from their
nominal value of 9.0 kV.The load L-2 voltage remains balanced and sinusoidal.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 58
CHAPTER -1 INTRODUCTION
Fig.6.19 System with IUPQC and having sag in feeder-2
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 59
CHAPTER -1 INTRODUCTION
6.5.1 System response without IUPQC during sag in feeder-2
When the system without IUPQC is considered i.e. without connecting the IUPQC to the
distribution system of fig.6.19 there is no conditioning of the voltages and currents.Fig7.20
represents voltage of the feeder-2, because of the sag in feeder 2 all the three phase voltages
are contains sag between 0.1 sec and 0.2 sec. Fig 7.21 is line current of feeder 2 having the
sag between 0.1sec and 0.2 sec.
Following fig 6.20 shows that there is a dip in voltage at second bus of feeder-2.
Fig. 6.20 Vabc_22, kV (voltage at second bus on feeder-2)
There exists a dip even in the current waveform at the second bus of feeder-2 shown in fig 6.21.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 60
CHAPTER -1 INTRODUCTION
Fig. 6.21 Iabc_21, A (current at second bus on feeder-1)
6.5.2 System response with IUPQC during sag in feeder-2
Here the system responses with IUPQC are discussed. Here the charged capacitor is
discharging depending on the control circuit. Depending on the sag value the controller is
injects the voltage in to the line. All the following figures show the results of the system with
IUPQC.
IUPQC remove the voltage sag and restore the original values across sensitive loads as shown in following fig.
Fig. 6.22 Vabc_32, kV (voltage at third bus on feeder-2)
The current waveform still found to be sinusoidal at the input side as shown in fig 6.23.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 61
CHAPTER -1 INTRODUCTION
Fig. 6.23 Vabc_12, kV (voltage at first bus on feeder-2)
6.6 System response during Faults
The performance of the IUPQC is tested when faults occurs in Feeder-2 at sensitive load
without and with IUPQC.
6.6.1 System response without IUPQC during Faults in feeder-2
In order to know the sytem performance without IUPQC L-G, L-L-G, 3-phase faults are created in sytem and simulated.
6.6.1.1 System response without IUPQC during L-G Fault in feeder-2
Simulink Diagram during L-G Fault is as shown in Fig 6.24.By setting Timer, fault is created during 0.05s to 0.1s in Phase-a.
Fig 6.24 simulink Diagram during L-G Fault without IUPQC
The system response is shown in Fig 6.25 when L-G fault occurs at
0.01 s such that the a-phase of B-32 bus voltage becomes zero. When the
fault occurs, the power fed to load
L-2(sensitive load) by Feeder-2 is reduced.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 62
CHAPTER -1 INTRODUCTION
Fig 6.25 Voltage across Sensitive Load (B-32 bus voltages) Vabc_b32 without IUPQC
6.6.1.2 System response without IUPQC during L-L-G Fault in feeder-2
Simulink Diagram during L-L-G Fault is as shown in Fig 6.25.By setting Timer, fault is created during 0.05s to 0.1s in Phase-a and phase-b
Fig 6.26 simulink Diagram during L-L-G Fault without IUPQC
The system response is shown in fig 6.27 when L-L-G fault occurs
during 0.01s to 0.5s such that both a and b-phases of bus voltage to
which sensitive load is connected become zero.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 63
CHAPTER -1 INTRODUCTION
Fig 6.27 Voltage across Sensitive Load Vabc_b32 without IUPQC
6.6.1.3 System response without IUPQC during 3-phase Fault in feeder-2
Simulink Diagram during 3-Phase Fault is as shown in Fig 6.28.By setting Timer; fault is created during 0.05s to 0.1s in 3-phases.
Fig 6.28 simulink Diagram during 3-phase fault without IUPQC
Now, the system performance has been tested when a three phase
fault occurs during 0.01s to 0.5s in Feeder-2 at sensitive load such that
the voltage becomes zero. The system response is shown in Figs.6.29.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 64
CHAPTER -1 INTRODUCTION
When the fault occurs, the power fed to sensitive load by Feeder-2
becomes zero.
Fig 6.29 Voltage across Sensitive Load Vabc_b32 without IUPQC
6.6.2 System response during Faults with IUPQC
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 65
CHAPTER -1 INTRODUCTION
Simulink diagram with IUPQC during faults is as shown in fig 6.30. IUPQC can restore
voltage values to prior to faults at sensitive load.
Fig 6.30 simulink Diagram with IUPQC during faults
6.6.2.1 System response with IUPQC during L-G Fault in feeder-2
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 66
CHAPTER -1 INTRODUCTION
Here the system response with IUPQC is shown in Fig6.31.It shows balanced sinusoidal
waveform. Here the charged capacitor is discharging depending on the control circuit.
Depending on the fault level value the controller is injects the voltage in to the line. To
meet the power requirement of the load L-2, the dc capacitor starts
supplying this power momentarily so that the L-2 load voltages remain
balanced throughout the fault period.
Fig 6.31 Voltage across Sensitive Load Vabc_b32 with IUPQC during L-G fault
6.6.2.2 System response with IUPQC during L-L-G Fault in feeder-2
Here the system responses with IUPQC are shown in Fig6.32.IUPQC improve voltage
quality. Here the charged capacitor is discharging depending on the control circuit.
Depending on the fault level value the controller is injects the voltage in to the line.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 67
CHAPTER -1 INTRODUCTION
Fig 6.32 Voltage across Sensitive Load Vabc_b32 with IUPQC during L-L-G fault
6.6.2.3 System response with IUPQC during 3-phase Fault in feeder-2
When the 3-fault occurs, the power fed to sensitive load by Feeder-2
becomes zero. To meet the power requirement of the load, the dc
capacitor starts supplying this power momentarily. This causes the dc
capacitor voltage to drop and to offset the voltage drop, the angle
retards. As a result, power is drawn from the source through Feeder-1 and
supplied to both the loads in Feeder-1 and Feeder-2.
Here the system responses with IUPQC are shown in Fig6.33. Depending on the fault
level value the controller is injects the voltage in to the line.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 68
CHAPTER -1 INTRODUCTION
Fig 6.33 Voltage across Sensitive Load Vabc_b32 with IUPQC during 3-phase fault
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 69
CHAPTER -1 INTRODUCTION
CONCLUSIONS
The present work illustrates the operation and control of an interline Unified Power
Quality Conditioner (IUPQC). The device is connected between two feeders coming from
different substations. An unbalanced and non-linear load L-1 is supplied by Feeder-1 while a
sensitive load L-2 is supplied through Feeder-2. The main aim of the IUPQC is to regulate
the voltage at the terminals of Feeder-1 and to protect the sensitive load from disturbances
occurring upstream. The performance of the IUPQC has been evaluated under various
disturbance conditions such as voltage sag in either feeder and fault in one of the feeders. In
case of voltage sag, the phase angle of the bus voltage in which the shunt VSC is connected
plays an important role as it gives the measure of the real power required by the load. The
IUPQC can mitigate voltage sag in Feeder-1 and in Feeder-2 for long duration. The IUPQC
discussed is capable of handling system in which the loads are unbalanced and distorted.
From above discussion, it has been observed that an IUPQC is able to protect the
distribution system from various disturbances occurring either in Feeder-1 or in Feeder-2. As
far as the common dc link voltage is at the reasonable level, the device works satisfactorily.
The angle controller ensures that the real power is drawn from Feeder-1 to hold the dc link
voltage constant. Therefore, even for voltage sag or a fault in Feeder-2, VSC-1 passes real
power through the dc capacitor onto VSC-2 to regulate the voltage Vl2. Finally when a fault
occurs in Feeder-2 or Feeder-2 is lost, the power required by the Load L-2 is supplied
through both the VSCs. This implies that the power semiconductor switches of the VSCs
must be rated such that the total power transfer through them must be possible. This may
increase the cost of this device. However, the benefit that may be obtained can offset the
expense.
In the IUPQC configuration, the sensitive load is fully protected against sag/swell and
interruption. The sensitive load is usually a part of a process industry where interruptions
result in severe economic loss. Therefore, the cost of the series part of IUPQC must be
balanced against cost of interruptions. It is expected that a part of IUPQC cost can be
recovered in 5–10 years by charging higher tariff for the protected line. Furthermore, the
regulated bus can supply several customers who are also protected against sag and swell. The
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 70
CHAPTER -1 INTRODUCTION
remaining part of the IUPQC cost can be recovered by charging higher tariff to this class of
customers. Such detailed analysis is required for each IUPQC installation. In conclusion, the
performance under some of the major concerns of both customer and utility e.g., harmonic
contents in loads, unbalanced loads, supply voltage distortion, system disturbances such as
voltage sag, and fault has been studied. The IUPQC has been shown to compensate for
several of these events successfully.
Future scope
Unified power quality conditioner can be extended for compensation of voltage/current in
multibus/multifeeder systems.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 71
CHAPTER -1 INTRODUCTION
REFERENCES
[1] Amit kumar jindal, Arindam Ghosh,Avinash joshi., “Interline Unified Power Quality
Conditioner,” IEEE Trans Power De., vol. 22, no. 1, pp. 293–297,Jan.2007.
[2] Zainal Salam, Tan Perng Cheng and Awang Jusoh “ Harmonics Mitigation Using Active
Power Filter: A Technological Review” Vol. 8, NO. 2, 2006, 17-26 ELEKTRIKA.
[3] Hirofumi Akagi, Fellow, IEEE” New trends in active Filters for power conditioning”
IEEE Transactions on Industry applications, Vol 32, NO 6, November/December 1996.
[4] Luis A. Moran(1) Juan W. Dixon(2) José R. Espinoza(1) Rogel R. Wallace(1)” Using Active
power filters to improve power quality”.
[5] K. Ça_atay BAYINDIR on “Modeling of Custom power devices” PhD THESIS,
ADANA, 2006.
[6] N.G.Hingorani and L.Gyugyi, “Understanding FACTS: Concepts and
Technology of
Flexible ac transmission systems”, IEEE Press, New York, 1999.
[7] Olimpo Anaya-Lara and E. Acha “Modeling and Analysis of Custom Power Systems by
PSCAD/EMTDC” IEEE Transactions on Power Delivery, Vol. 17, NO. 1, January 2002.
[8] G. Ledwich and A. Ghosh, “A flexible DSTATCOM operating in voltage and current
control mode,” Proc. Inst. Elect. Eng., Gen., Transm. Distrib., vol. 149, no. 2, pp. 215–224,
2002.
[9] M. K. Mishra, A. Ghosh, and A. Joshi, “Operation of a DSTATCOM in voltage control
mode,” IEEE Trans. Power Del., vol. 18, no. 1, pp. 258–264, Jan. 2003.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 72
CHAPTER -1 INTRODUCTION
[10] Soo-Young Jung, Student Member, IEEE, Tae-Hyun Kim, Member, IEEE, Seung-Il
Moon, Member IEEE, Byung-Moon Han, Senior Member, IEEE ”Analysis and Control of
DSTATCOM for a Line Voltage Regulation”.
[11] A. Arulampalam, J.B. Ekanayake and N. Jenkins, ”Application study of a STATCOM
with energy storage”.
[12] Cai Rong, ” Analysis of STATCOM for Voltage Dip Mitigation”. Thesis for the Degree
of Master of Science, December 2004.
[13] Soo-Young Jung, Student Member, IEEE, Tae-Hyun Kim, Member, IEEE, Seung-Il Moon,
Member IEEE, Byung-Moon Han, Senior Member, IEEE “Analysis and Control of DSTATCOM for
a Line Voltage Regulation”.
[14] Paisan Boonchiam and Nadarajah Mithulananthan”Understanding of Dynamic Voltage
Restorers Through MATLAB Simulation “ Thammasat Int. J. Sc.Tech., Vol. 11,N o. 3, July-
September 2006.
[15] N. H. Woodley, L. Morgan, and A. Sundaram, “Experience with an inverter-based
dynamic voltage restorer,” IEEE Trans. Power Del., vol. 14, no. 3, pp. 1181–1186, Jul. 1999.
[16] A. Ghosh, A. K. Jindal, and A. Joshi, “Design of a capacitor-supported Dynamic
Voltage Restorer (DVR) for unbalanced and distorted loads,” IEEE Trans. Power Del., vol.
19, no. 1, pp. 405–413, Jan. 2004.
[17] Shairul Wizmar Wahab and Alias Mohd Yusof ” Voltage Sag and Mitigation Using
Dynamic Voltage Restorer (DVR) System “VOL. 8, NO. 2, 2006, 32-37 ELEKTRIKA.
[18] M.V.Kasuni Perera” Control of a Dynamic Voltage Restorer to compensate single phase
voltage sags” Master of Science Thesis, Stockholm, Sweden 2007.
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 73
CHAPTER -1 INTRODUCTION
[19] S.V Ravi Kumar and S. Siva Nagaraju “Simulation OF D-STATCOM and DVR in
power systems” Vol. 2, No. 3, June 2007 ISSN 1819-6608 ARPN Journal of Engineering and
Applied Sciences.
[20] M.H. Haque” compensation of distribution sytesm voltage sag by DVR AND D-
STATCOM” Paper accepted for presentation at PPT 2001 2001 IEEE Porto Power Tech
Conference 10th -13th September, Porto, Portugal.
[21] H. Fujita and H. Akagi, “The Unified Power Quality Conditioner: the integration of
series- and shunt-active filters,” IEEE Trans. Power Electron., vol. 13, no. 2, pp. 315–322,
Mar. 1998.
[22] F. Kamran and T. G. Habetler, “Combined deadbeat control of a seriesparallel converter
combination used as a universal power filter”, IEEE Trans. Power Electron., vol. 13, no. 1, pp. 160–
168, Jan. 1998.
[23] R.Rezaeipour and A.Kazemi, “Review of Novel control strategies for UPQC”
Internal Journal of Electric and power Engineering 2(4) 241-247,2008.
[24] Peter W. Sauer” What is Reactive Power?” Power Systems Engineering Research Center
PSERC Background Paper .
[25] Ewald F.Fuchs and A.S.Masoum “Power Quality in Power systems and Electrical
Machines“(Book).
[26] Amit Kumar Jindal, Student Member, IEEE, Arindam Ghosh, Fellow, IEEE, and
Avinash Joshi “Power quality enhancement using custom power devices”(Book).
[27] Hojat Hatami,Farhad Shahnia,Afshin Pashaei,S.H.Hosseini,”Investigation on D-
STATCOM and DVR operation for voltage control in Distribution Networks with a New
control strategy”
[28]”power quality “paper from BC hydro power smart
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 74
CHAPTER -1 INTRODUCTION
[29] Jiyun sun ”study of power quality at 69/13.8 kv Distribution system” for the degree of doctor of
Philosophy,January 2003
[30] Prof. DVSS Siva Sharma “Overview of Power Quality Issues” National Institute of
Technology, Warangal (work shop material)
[31] www.scribd.com
[32] www.arpnjournals.com
[33] www.pserc.com
[34] www.google.com
DEPARTMENT OF ELECTRICAL & ELCTRONICS ENGINEERING, MIST Page 75