Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric...

56
Changes to the 2017 National Electrical Code 1

Transcript of Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric...

Page 1: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

Changes to the 2017 National Electrical Code

1

Page 2: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

The 2017 National Electric Code:

“IntroducesmorechangestoArticle690,‘SolarPhotovoltaic(PV)Systems’,thananyrevisioncyclesince1984,whentheNECfirstadoptedArticle690”

BillBrooks

2017 NEC

2

Page 3: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

Main Changes to Article 690New articles added to NEC:• 691: Large Scale Photovoltaic (PV) Electric Power Production

Facility• Article 706: Energy Storage Systems• Article 710: Stand Alone Systems• Article 712: Direct Current Micro Grids (This will not be covered

today)

Articles removed from the NEC:• 690.35: Ungrounded PV Power Systems

2017 NEC

3

Page 4: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

Defined the limits of the PV system.

The 2017 version of the NEC redefined the PV System disconnect. It is now system dependent:

• 690.13 Photovoltaic System Disconnecting Means. Means shall be provided to disconnect the PV system from all wiring systems including power systems, energy storage systems, and utilization equipment and its associated premises wiring.

2017 NEC

4

Page 5: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

Drawingcourtesy:SolarProfessionalMagazine,May/June20165

Page 6: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

Drawingcourtesy:SolarProfessionalMagazine,May/June20166

Page 7: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

Drawingcourtesy:SolarProfessionalMagazine,May/June20167

Page 8: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

Adds new definition for Grounding in Article 690:

Functional Grounded PV System: A PV system that has an electrical reference to ground that is not solidly grounded.

• Acknowledges that most PV systems installed in the last 20 years were functionally grounded PV Systems.

• This uses a definition used and accepted in Europe.

2017 NEC

8

Page 9: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

What the new functional grounding definition means:

• A single overcurrent device shall be permitted to protect the PV modules and conductors of each source circuit. (690.9(C))

• Disconnect switches shall isolate all PV equipment from all conductors that are not solidly grounded. (690.15)

• It is easier to replace grounded inverters with transformerless or non-isolated inverters.

• All PV systems are subject to the same installation requirements under NEC 2017, regardless of inverter topology.

2017 NEC

9

Page 10: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

690.7 Maximum Voltage.

- The highest voltage between any two circuit conductors or any conductor and ground.

• One and two family dwellings still limited to 600Vdc.• PV Systems DC circuits on other types of buildings shall be permitted to

have a maximum voltage of 1000 volts or less.• Where not located on buildings, listed PV equipment, rated at a maximum

voltage of 1500Vdc or less.

2017 NEC

10

Page 11: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

Maximum Voltage and Current:

For a PV system with a generating capacity of 100kW or greater:• Maximum system voltage calculated by an industry standard method shall be

permitted. (References Sandia publication SAND 2004-3535)• Maximum PV Source and output current can be calculated using industry

standard methods. The calculated maximum current shall be based on the highest 3 hour current average resulting from the simulated local irradiance. The current calculated using this method shall not be less than 70% of the value calculated using the method described in 690.8(A)(1)(1).

2017 NEC

11

Page 12: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

12

690.12RapidShutdown690.12(B)- Controllimits:• Arrayboundaryisloweredto30cm(1ft)inalldirections.All

conductorsoutsidethisboundaryshallbelimitedtonomorethan30Vwithin30secondsofinitiatingRapidShutdown.

Page 13: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

690.12RapidShutdown690.12(B)(2)InsidetheArrayBoundary:1. ThePVarrayshallbelistedorfieldlabeledasarapidshutdownPV

array.2. ConductorslocatedinsidethePVarrayboundaryornotmorethan

one1meter(3ft)fromthepointofpenetrationofthesurfaceofthebuildingshallbelimitedtonotmorethan80voltswithin30secondsofrapidshutdowninitiation.

3. PVArrayswithnoexposedwiringmethods,noexposedconductiveparts,andinstalledmorethan2.5m(8ft)fromexposedgroundedconductivepartsorgroundshallnotberequiredtocomplywith690.12(B)(2)

Thissection(690.(B)(2)doesnotbecomeeffectiveuntil1January2019.

13

Page 14: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

14

690.12RapidShutdown690.12(C)- Initiationdevice:• Thedevice“off”positionshallindicatethatRapidShutdownhasbeen

initiated• Foroneandtwofamilydwellings,theinitiationdeviceshallbelocated

atareadilyaccessiblelocationoutsidethebuilding.• TheRapidShutdowninitiationdeviceshallconsistofatleastoneofthe

following:o PVsystemdisconnecto ServiceDisconnecto Readilyaccessibleswitch

• Amaximumofsixdevicestoinitiaterapidshutdownofmultiplesystems.

Page 15: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

15

690.12RapidShutdown(D)- Equipment:EquipmentthatperformstheRapidShutdownfunctions,otherthaninitiationdevicessuchaslisteddisconnectswitches,circuitbreakers,orcontrolswitches,shallbelisted,labeledandidentifiedforprovidingRapidShutdownprotection.

Page 16: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

16

RapidShutdown690.56IdentificationofPowerSources.• ThetypeofRapidShutdownequipmentshallbeidentified.• BuildingswithmorethanonetypeofRapidShutdownequipment

mustshowareasaroundPVsystemthatareenergizedaftertheRapidShutdownswitchisoperated.

• TheRapidShutdownswitchshallbelabeled.

Page 17: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

690.11Arc-FaultCircuitProtection(DirectCurrent)

• AnexemptiontotheArc-FaultrequirementforPVsystemsthatare notinstalledonbuildingshasbeenaddedto2017.

• LargesystemsonbuildingsarestillrequiredtohaveArc-Faultprotectionequipment.

17

Page 18: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

PVSystemLabeling

• MaximumpowerpointvoltageandcurrenthavebeenremovedfromDCswitchlabelrequirements.

• PVsystemoutputcircuitsshallbemarkedtoshowpolaritywhereconnectedtoanenergystoragedevice.

• Rapidshutdownlabelingrequirementshavebeenexpandedtoinclude:- Rapidshutdowntype- Identifyrapidshutdownswitch- Identifywhichsystemshaverapidshutdownforbuildingswithmore

thanonerapidshutdowntype• ReferencesArticle705.10forsystemswithbothutilityandPVsystems

18

Page 19: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

19

Article691:LargeScalePhotovoltaic(PV)ElectricPowerProductionFacility

Scope:CoverstheinstallationoflargescalePVelectricpowerproductionfacilitieswithageneratingcapacityofnolessthan5,000kW,andnotunderexclusiveutilitycontrol.

InformationalnotesreferencetheNationalElectricalSafetyCodeandindicatethatfacilitiescoveredby691“havespecificdesignandsafetyfeaturesuniquetolargescalePVsystemsoperatedforthesolepurposeofprovidingelectricsupplytoasystemoperator”

Page 20: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

20

691.4SpecialRequirementsforLargeScalePVElectricSupplyStations

• Accessibletoonlyauthorizedpersonnel• Operatedandmaintainedonlybyqualifiedpersonnel• AccesstoPVsystemtoberestrictedbyfencingorotheradequatemeans• TheconnectionbetweenthePVsystemandthegridshallbethrough

mediumorhighvoltageswitchgear• Electricalloadswithinthefacilityshallonlypowerequipmentforthe

generationofPVpower• LargescalePVelectricsupplystationsshallnotbeinstalledonbuildings.

Page 21: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

21

691:LargescalePVpowersystems

• Tryingtoenforcestandard690requirementsdidnotmakesense.• Equipmentmaynotbelistedand/orlabeled.Article691allowsfor

approvalby“engineeringreviewvalidatingthattheelectricalequipmentistestedtorelevantstandards”

• Documentationof,andindependentengineeringreportsoftheelectricalportionoftheengineeringdesignshallbestampedbyaprofessionalelectricalengineerandshalldetailconformanceofthedesigntoArticle690oralternativemethodstoArticle690orotherarticlesofthiscode.

Page 22: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

22

Article705:InterconnectedElectricPowerProductionSources

705.12(B)(2)(d):Aconnectionateitherendbutnotbothendsofacentertappedpanelboardisallowedaslongasthesum125%ofthepowersource(s)outputcircuitcurrentandtheratingoftheovercurrentdeviceprotectingthebusbardoesnotexceed120%ofthecurrentratingofthebusbar.

Page 23: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

23

705.12(D)(6)WireHarnessandExposedCableArc-FaultProtection

Duetoissuescomplyingwiththissectionformicroinverter,ithasbeenremovedfromthe2017NEC.InadditionTIA14-11wasissuedthatremoves705.12(D)(6)fromthe2014versionofthecode.

Page 24: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

24

PartIV.MicrogridSystems

MicrogridshavebeenaddedtoArticle705.

Definedin705.2as“Apremiseswiringsystemthathasgeneration,energystorageandload(s),oranycombinationthereof,thatincludestheabilitytodisconnectfromandparallelwiththeprimarysource”.

InformationalNote:Theapplicationofarticle705tomicrogridsystemsislimitedbytheexclusionsin90.2(B)(5)relatedtoelectricutilities(exclusivecontrol).

Page 25: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

25

Article706EnergyStorageSystems

Scope:Thisarticleappliestoallpermanentlyinstalledenergystoragesystems(ESS)operatingatover50voltsacor60voltsdcthatmaybestandaloneorinteractivewithotherelectricpowerproductionsources.

Page 26: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

26

Notcoveredintoday’sdiscussion.Theadditionof:

Article710Stand-AloneSystems

Article712DirectCurrentMicrogrids

Page 27: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

27

OtherChangestotheSection690:• 690.2NewdefinitionsforDC-to-DCconvertercircuits,PVSystemdccircuit,

Generatingcapacity,functionalgroundedPVsystem• 690.4(D)clarifiesthatmultiplePVsystems,notjustmultipleinvertersare

permittedonasinglebuilding• 690.4(E)clarifiesthatPVsystemequipmentanddisconnectingmeansshall

notbeinstalledinbathrooms.• 690.13(F)Typeofdisconnectdefinessimultaneousdisconnectionofall

conductors,prohibitsuseofdevicesmarked“line”and“load”frombeingbackfedandallowstheuseofvarioustypesofDCratedswitches.

• 690.15definesanisolatingdevice,ratingrequirementsforequipmentdisconnectingmeansandrequirementsforequipmentdisconnectingmeans.

Page 28: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

2017 NEC

28

MoreChangestotheSection690:• 690.31(B)(1)DisallowstheuseofwhitewireonthedcsideofaPVsystem

foranythingexceptsolidlygroundedPVsystems.• 690.72Selfregulatedchargecontrollers.• Table690.31(E)forminimumPVwirestrandsforflexiblecordsandcables

(table690.31(E)Correctionfactorsfromthe2014NEChasbeenrelabeledtotable690.31(A))

• 690.47(B)AdditionalAuxiliaryElectrodesforArrayGrounding• 690.59ConnectionstoOtherSourcesreferencesPartsIandIIofArticle

705.• PartVIIIrenamedtoEnergystoragesystemsandreferencesarticle706.• PartIX.Systemsover1000VoltsandPartX.ElectricVehicleCharging,both

removedfromArticle690astheyarecoveredelsewhere.

Page 29: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

NYS Uniform Code Amendments and Supplements for Roof

Mounted Solar Electric Arrays

Page 30: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

Fire Code and Structural Code Issues in Siting Residential and Commercial Systems

30

Safety concerns expressed by the fire fighting community, regarding exposure to high dc voltage roof top, or concealed conductors has fostered many changes in the 2014 NEC.

Access to ground mounted, and access and ventilation of roofs with solar arrays on them are also of concern. This has resulted in restrictions in the area that can be covered by modules.

NY State has updated its building codes with respect to the location of solar modules for roof and ground mounted arrays during the development of this course.

The following is not an all –inclusive summary of these updates

Page 31: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

Fire Codes Issues in Siting PV Systems

• The 2015 International Fire Code (IFC), Section 605.11 addresses requirements for solar photovoltaic power systems.– Requires minimum setbacks for roof-mounted PV arrays to allow

firefighters safe access, pathways and areas for smoke ventilation.

• The 2016 New York State Uniform Fire Prevention and Building Code (the “Uniform Code”) has adopted by reference the 2015 edition of the International Fire Code (2015 IFC) with amendments.– Portions of the 2015 IFC have been adopted in the 2015 edition of

the International Residential Code (2015 IRC) with amendments in SECTION R324: SOLAR ENERGY SYSTEMS.

31

Page 32: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

• The 2015 International Building Code (2015 IBC) Section 101.4.5 on fire prevention requires compliance with the 2015 International Fire Code (2015 IFC) for commercial buildings and other structures permitted under the 2015 IBC.

• The NY State Uniform Code Supplement has amended Section 605.11 of the 2015 IFC by the replacement of sections 605.11.1 through 605.11.1.2.5 in their entirety, and the addition of a new section 605.11.1.2.6.

– TheseNYamendmentschangethe2015IFCsetbackrequirementsforrooftopmountedPVarraysbasedonnewdefinitionsforACCESSROOF,GROUNDACCESSAREA,andROOFACCESSPOINT.

• NY State has amended the 2015 International Residential Code (2015 IRC) in the 2016 Uniform Code Supplement to include certain fire code requirements for residential construction in Section R324.

32

2015 International Fire CodeResidential vs. Commercial

Page 33: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

• The residential building code as amended for New York State allows the designers of photovoltaic systems several options and alternatives. These illustrations are offered as possible examples. It is not possible to show every possible scenario. It is however up to the judgement of the local code official to determine final compliance with the code.

• Contractors, design professionals, and AHJ’s must consider many ventilation scenarios and consider that:

– 1.Afirecanbreakoutanywhereinabuilding.– 2.Emergencyrespondersdonothavex-rayvision.Alternateventilationmethodsshouldconsiderfiresoccurringinlessthanideallocations.

– 3.ContractorsandAHJmustrememberthatthedirectionandmagnitudeofaprevailingwindcanaffectthelocationoftheventilationopening

33

NYSERDA’s Assessment of These Changes

Page 34: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

• R324.7.4 Single ridge roofs. Panels, modules, or arrays installed on roofs with a single ridge shall be located in a manner that provides two, 36 inches wide (914 mm) access pathways extending from the roof access point to the ridge. Access pathways on opposing roof slopes shall not be located along the same plane as the truss, rafter, or other such framing system that supports the pathway.

• Exceptions:# 1.Roofswithslopesof2unitsverticalin12unitshorizontal(16.6percent)andless.

# 2.Structureswhereanaccessrooffrontsastreet,driveway,orotherareareadilyaccessibletoemergencyresponders.

# 3.Oneaccesspathwayshallberequiredwhenaroofslopecontainingpanels,modulesorarraysislocatednotmorethan24inches(610mm)verticallyfromanadjoiningroofwhichcontainsanaccessroof.

34

2015 IRC Section R324.7.4Access and Pathways: Single Ridge Roofs

Page 35: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

35

Single ridge roof showing a smaller array without any exceptions

Source:NYSERDASystemshownwithoutanyexceptionswhereverticalventilationtechniqueswillbeemployedresultinasmallerarray.

Page 36: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

36

Single ridge roof — single pathway with exception #2 single ridge roof indicating ground access

Source:NYSERDA

Exceptionemployed.Groundaccesspointsmustalignwithroofaccesspoints.Notethatthetwoaccesspointsand36”pathwaysallowtwodirectionsofaccessandegressanddonotshareacommontrussorrafter.Thereisalsoadequateunobstructedgroundaccess.Noteincreasedsizeofarraypossible.

Page 37: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

37

Single ridge roof — single pathway with exception #3 adjoining roof within 24 Inches

Source:NYSERDA

Withanadjoiningroofwithin24inchesofthearrayroof,applyingexception#3youwouldonlyneedasingleaccesspointandpathwayonthemainroof,asthereissecondaryaccessviaanadjoiningroofwithin24inches.Thisstillallowstwodirectionsofegress,anddoesnotshareacommontrussofrafter.

Page 38: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

38

Single ridge roof –with Alternate Ventilation Location

Source:NYSERDA

Roof Access

sitew/proposedalternateventilation

Ifventilationisrequireditmaybepossibletoproposeanalternateventilationlocationonroofslopeoppositethearrayorthesidewallofanatticspace.AlternatelocationsshouldbecoordinatedandapprovedbytheAHJ.

Roof Access

Roof Access

Page 39: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

• R324.7.5 Hip roofs. Panels, modules, and arrays installed on dwellings with hip roofs shall be located in a manner that provides a clear access pathway not less than 36 inches wide (914 mm), extending from the roof access point to the ridge or peak, on each roof slope where panels, modules, or arrays are located.

• Exceptions: # 1.Roofswithslopesof2unitsverticalin12unitshorizontal(16.6percent)andless.

# 2.Structureswhereanaccessrooffrontsastreet,driveway,orotherareareadilyaccessibletoemergencyresponders.

39

2015 IRC Section R324.7.5:Access and Pathways: Hip Roofs

Page 40: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

40

Hip roof showing alternate venting with two roof pathways and ground access - no exception necessary

Source:NYSERDA

Atypicalhiproof,showingalternateventinglocationandclearaccesspathwaynotlessthan36incheswide(914mm)extendingfromtheroofaccesspointtotheridgeorpeak.

Page 41: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

• R324.7.6 Roofs with valleys. Panels and modules shall not be located less than 18 inches (457 mm) from a valley.

• Exception: # Roofswithslopesof2unitsverticalin12unitshorizontal(16.6percent)andless.

41

2015 IRC Section R324.7.5:Access and Pathways: Hip Roofs

Page 42: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

42

Valley Roof showing 18” clearance in yellow to the array-no exception necessary

Source:NYSERDA

Thisimageshowsthe18inchclearspacefromthevalleytothearray.Thereisanadditional18clearspaceontheothersideofthevalleyatB.

B

Page 43: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

43

Hip roof with exception #2 where access roof fronts a street or driveway

Source:NYSERDA

Page 44: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

• R324.7.7 Allowance for smoke ventilation operations. Panels and modules shall not be located less than 18 inches (457 mm) from a ridge or peak.

• Exceptions: # 1.Whereanalternativeventilationmethodhasbeenprovidedorwhereverticalventilationmethodswillnotbeemployedbetweentheuppermostportionofthesolarphotovoltaicsystemandtheroofridgeorpeak.

# 2.Detachedgaragesandaccessorystructures.

44

2015 IRC Section R324.7.7Allowance for Smoke Ventilation

Page 45: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

The following slides provide NY amendments to the 2015 IFC that apply to COMMERCIAL buildings constructed per the 2015 IBC.

Many of the requirements are the same as amended to the 2015 IRC Section 324.7 regarding new requirements for access, pathways and ventilation.

45

2015 IFC Section 605.11.1.3Requirements for Other Than Group R-3 Buildings

Page 46: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

• 605.11.1.3 Other than Group R-3 buildings. Access to systems for buildings, other than those containing Group R-3 occupancies, shall be provided in accordance with Sections 605.11.1.3.1 through 605.11.1.3.3.

• Exception: Where it is determined by the fire code official that the roof configuration is similar to that of a Group R-3 occupancy, the residential access and ventilation requirements in Sections 605.11.1.2.1 through 605.11.1.2.5 shall be permitted to be used.

46

2015 IFC Section 605.11.1.3Requirements for Other Than Group R-3 Buildings

Page 47: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

• 605.11.1.3.1 Access. There shall be a minimum 6-foot-wide clear perimeter around the edges of the roof.

– Exception:Whereeitheraxisofthebuildingis250feetorless,theclearperimeteraroundtheedgesoftheroofshallbepermittedtobereducedtoaminimum4footwide.

47

Requirements for Other Than Group R-3 Buildings2015 IFC Section 605.11.1.3.1: Access

Page 48: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

• 605.11.1.3.2 Pathways. The solar installation shall be designed to provide designated pathways. The pathways shall meet the following requirements:

– 1.Thepathwayshallbeoverareascapableofsupportingfirefightersaccessingtheroof.

– 2.Thecenterlineaxispathwaysshallbeprovidedinbothaxesoftheroof.Centerlineaxispathwaysshallrunwheretheroofstructureiscapableofsupportingfirefightersaccessingtheroof.

– 3.Pathwaysshallbeastraightlinenotlessthan4feetcleartoroofstandpipesorventilationhatches.

– 4.Pathwaysshallprovidenotlessthan4feetcleararoundroofaccesshatchwithnotlessthanonesingularpathwaynotlessthan4feetcleartoaparapetorroofedge.

48

Requirements for Other Than Group R-3 Buildings2015 IFC Section 605.11.1.3.2: Pathways

Page 49: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

• 605.11.1.3.3 Smoke ventilation. The solar installation shall be designed to meet the following requirements:

– 1.Arraysshallbenotgreaterthan150feetby150feetindistanceineitheraxisinordertocreateopportunitiesforfiredepartmentsmokeventilationoperations.

– 2.Smokeventilationoptionsbetweenarraysectionsshallbeoneofthefollowing:

– 2.1.Apathway8feetorgreaterinwidth.– 2.2.A4-footorgreaterinwidthpathwayandborderingroofskylightsorgravity-operateddropoutsmokeandheatventsonnotlessthanoneside.

– 2.3.A4-footorgreaterinwidthpathwayandborderingallsidesofnongravity-operateddropoutsmokeandheatvents.

– 2.4.A4-footorgreaterinwidthpathwayandbordering4-footby8-footventingcutoutsevery20feetonalternatingsidesofthepathway.

49

Requirements for Other Than Group R-3 Buildings2015 IFC Section 605.11.1.3.3: Smoke Ventilation

Page 50: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

Access, Pathways and Ventilation: Examples

Access pathways are provided around the perimeter and throughout building-mounted PV arrays to provide for firefighter access and ventilation.

Page 51: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

Access, Pathways and VentilationLarge Commercial Example

LargeCommercial(Axis>250’)8’Walkways

CALFIRE-OSFMAccess pathways51

Building Requirements: Large Commercial ExampleCodeCompliantforLargeCommercial

Page 52: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

Building Requirements: Large Commercial Example

52

CodeCompliantforLargeCommercial

Fire Code Issues in Siting Systems

Access and Ventilation Requirements are a function of Building Size

Access pathways

Page 53: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

CAL FIRE-OSFM

Building Requirements: Small Commercial Example

53

CodeCompliantforSmallCommercial

Fire Code Issues in Siting Systems

Access and Ventilation Requirements are a function of Building Size

Access pathways

Page 54: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

Access pathways CAL FIRE-OSFM

Building Requirements: Small Commercial Example

54

CodeCompliantforSmallCommercial

Fire Code Issues in Siting Systems

Access and Ventilation Requirements are a function of Building Size

Page 55: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

Photos courtesy of DOE/NREL

Ground Mounted Systems

55

Fire Code Issues in Siting Systems

• R324.6Ground-mountedphotovoltaicsystems.Ground-mountedphotovoltaicsystemsshallbedesignedandinstalledinaccordancewithSectionR301(DesignCriteria).⁻ R324.6.1Fireseparationdistances.Ground-mountedphotovoltaic

systemsshallbesubjecttothefireseparationdistance requirementsdeterminedbythelocaljurisdiction.

Page 56: Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric Code: “Introduces more changes to Article 690, ‘Solar Photovoltaic (PV) Systems’,

56

Question and Answer Assessment

NEC2017Q1)WhataretheboundarylimitationsforRapidShutdown?A1) Arrayboundaryis30cm(1ft)inalldirections.Allconductorsoutsidethisboundaryshallbelimitedtonomorethan30Vwithin30secondsofinitiatingRapidShutdown.Q2)Whatisthehighestvoltageallowedonbuildingsotherthanoneortwofamilydwellings?A2)PVSystemsDCcircuitsonothertypesofbuildingsshallbepermittedtohaveamaximumvoltageof1000voltsorless.Q3)Whatchangeshavebeenmadetofacilitatethereplacementofisolatedinverterswithnonisolatedinverters?A3)Disconnectswitchwiringandovercurrentprotectionhasbeenmademostlyuniformirrespectiveofwhethertheinverterisisolatedornonisolated.NYSUniformCodeAmendmentsandSupplementsforRoofMountedArraysQ4)WhatisoneofthepurposesofTheUniformCodeAmendmentsandSupplementforRoofMountedArrays?A4)Toallowalternativepathsforaccessandventilationofroofsinthecaseofafire.Q5)WhoultimatelyhasdecisionmakingauthorityforaccessandventilationplansA5)TheAuthorityHavingJurisdiction(AHJ).ConferwiththeAHJontheseplans.