Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric...
Transcript of Changes to the 2017 National Electrical Code PE 2017 Presentation... · The 2017 National Electric...
Changes to the 2017 National Electrical Code
1
The 2017 National Electric Code:
“IntroducesmorechangestoArticle690,‘SolarPhotovoltaic(PV)Systems’,thananyrevisioncyclesince1984,whentheNECfirstadoptedArticle690”
BillBrooks
2017 NEC
2
Main Changes to Article 690New articles added to NEC:• 691: Large Scale Photovoltaic (PV) Electric Power Production
Facility• Article 706: Energy Storage Systems• Article 710: Stand Alone Systems• Article 712: Direct Current Micro Grids (This will not be covered
today)
Articles removed from the NEC:• 690.35: Ungrounded PV Power Systems
2017 NEC
3
Defined the limits of the PV system.
The 2017 version of the NEC redefined the PV System disconnect. It is now system dependent:
• 690.13 Photovoltaic System Disconnecting Means. Means shall be provided to disconnect the PV system from all wiring systems including power systems, energy storage systems, and utilization equipment and its associated premises wiring.
2017 NEC
4
2017 NEC
Drawingcourtesy:SolarProfessionalMagazine,May/June20165
2017 NEC
Drawingcourtesy:SolarProfessionalMagazine,May/June20166
2017 NEC
Drawingcourtesy:SolarProfessionalMagazine,May/June20167
Adds new definition for Grounding in Article 690:
Functional Grounded PV System: A PV system that has an electrical reference to ground that is not solidly grounded.
• Acknowledges that most PV systems installed in the last 20 years were functionally grounded PV Systems.
• This uses a definition used and accepted in Europe.
2017 NEC
8
What the new functional grounding definition means:
• A single overcurrent device shall be permitted to protect the PV modules and conductors of each source circuit. (690.9(C))
• Disconnect switches shall isolate all PV equipment from all conductors that are not solidly grounded. (690.15)
• It is easier to replace grounded inverters with transformerless or non-isolated inverters.
• All PV systems are subject to the same installation requirements under NEC 2017, regardless of inverter topology.
2017 NEC
9
690.7 Maximum Voltage.
- The highest voltage between any two circuit conductors or any conductor and ground.
• One and two family dwellings still limited to 600Vdc.• PV Systems DC circuits on other types of buildings shall be permitted to
have a maximum voltage of 1000 volts or less.• Where not located on buildings, listed PV equipment, rated at a maximum
voltage of 1500Vdc or less.
2017 NEC
10
Maximum Voltage and Current:
For a PV system with a generating capacity of 100kW or greater:• Maximum system voltage calculated by an industry standard method shall be
permitted. (References Sandia publication SAND 2004-3535)• Maximum PV Source and output current can be calculated using industry
standard methods. The calculated maximum current shall be based on the highest 3 hour current average resulting from the simulated local irradiance. The current calculated using this method shall not be less than 70% of the value calculated using the method described in 690.8(A)(1)(1).
2017 NEC
11
2017 NEC
12
690.12RapidShutdown690.12(B)- Controllimits:• Arrayboundaryisloweredto30cm(1ft)inalldirections.All
conductorsoutsidethisboundaryshallbelimitedtonomorethan30Vwithin30secondsofinitiatingRapidShutdown.
2017 NEC
690.12RapidShutdown690.12(B)(2)InsidetheArrayBoundary:1. ThePVarrayshallbelistedorfieldlabeledasarapidshutdownPV
array.2. ConductorslocatedinsidethePVarrayboundaryornotmorethan
one1meter(3ft)fromthepointofpenetrationofthesurfaceofthebuildingshallbelimitedtonotmorethan80voltswithin30secondsofrapidshutdowninitiation.
3. PVArrayswithnoexposedwiringmethods,noexposedconductiveparts,andinstalledmorethan2.5m(8ft)fromexposedgroundedconductivepartsorgroundshallnotberequiredtocomplywith690.12(B)(2)
Thissection(690.(B)(2)doesnotbecomeeffectiveuntil1January2019.
13
2017 NEC
14
690.12RapidShutdown690.12(C)- Initiationdevice:• Thedevice“off”positionshallindicatethatRapidShutdownhasbeen
initiated• Foroneandtwofamilydwellings,theinitiationdeviceshallbelocated
atareadilyaccessiblelocationoutsidethebuilding.• TheRapidShutdowninitiationdeviceshallconsistofatleastoneofthe
following:o PVsystemdisconnecto ServiceDisconnecto Readilyaccessibleswitch
• Amaximumofsixdevicestoinitiaterapidshutdownofmultiplesystems.
2017 NEC
15
690.12RapidShutdown(D)- Equipment:EquipmentthatperformstheRapidShutdownfunctions,otherthaninitiationdevicessuchaslisteddisconnectswitches,circuitbreakers,orcontrolswitches,shallbelisted,labeledandidentifiedforprovidingRapidShutdownprotection.
2017 NEC
16
RapidShutdown690.56IdentificationofPowerSources.• ThetypeofRapidShutdownequipmentshallbeidentified.• BuildingswithmorethanonetypeofRapidShutdownequipment
mustshowareasaroundPVsystemthatareenergizedaftertheRapidShutdownswitchisoperated.
• TheRapidShutdownswitchshallbelabeled.
2017 NEC
690.11Arc-FaultCircuitProtection(DirectCurrent)
• AnexemptiontotheArc-FaultrequirementforPVsystemsthatare notinstalledonbuildingshasbeenaddedto2017.
• LargesystemsonbuildingsarestillrequiredtohaveArc-Faultprotectionequipment.
17
2017 NEC
PVSystemLabeling
• MaximumpowerpointvoltageandcurrenthavebeenremovedfromDCswitchlabelrequirements.
• PVsystemoutputcircuitsshallbemarkedtoshowpolaritywhereconnectedtoanenergystoragedevice.
• Rapidshutdownlabelingrequirementshavebeenexpandedtoinclude:- Rapidshutdowntype- Identifyrapidshutdownswitch- Identifywhichsystemshaverapidshutdownforbuildingswithmore
thanonerapidshutdowntype• ReferencesArticle705.10forsystemswithbothutilityandPVsystems
18
2017 NEC
19
Article691:LargeScalePhotovoltaic(PV)ElectricPowerProductionFacility
Scope:CoverstheinstallationoflargescalePVelectricpowerproductionfacilitieswithageneratingcapacityofnolessthan5,000kW,andnotunderexclusiveutilitycontrol.
InformationalnotesreferencetheNationalElectricalSafetyCodeandindicatethatfacilitiescoveredby691“havespecificdesignandsafetyfeaturesuniquetolargescalePVsystemsoperatedforthesolepurposeofprovidingelectricsupplytoasystemoperator”
2017 NEC
20
691.4SpecialRequirementsforLargeScalePVElectricSupplyStations
• Accessibletoonlyauthorizedpersonnel• Operatedandmaintainedonlybyqualifiedpersonnel• AccesstoPVsystemtoberestrictedbyfencingorotheradequatemeans• TheconnectionbetweenthePVsystemandthegridshallbethrough
mediumorhighvoltageswitchgear• Electricalloadswithinthefacilityshallonlypowerequipmentforthe
generationofPVpower• LargescalePVelectricsupplystationsshallnotbeinstalledonbuildings.
2017 NEC
21
691:LargescalePVpowersystems
• Tryingtoenforcestandard690requirementsdidnotmakesense.• Equipmentmaynotbelistedand/orlabeled.Article691allowsfor
approvalby“engineeringreviewvalidatingthattheelectricalequipmentistestedtorelevantstandards”
• Documentationof,andindependentengineeringreportsoftheelectricalportionoftheengineeringdesignshallbestampedbyaprofessionalelectricalengineerandshalldetailconformanceofthedesigntoArticle690oralternativemethodstoArticle690orotherarticlesofthiscode.
2017 NEC
22
Article705:InterconnectedElectricPowerProductionSources
705.12(B)(2)(d):Aconnectionateitherendbutnotbothendsofacentertappedpanelboardisallowedaslongasthesum125%ofthepowersource(s)outputcircuitcurrentandtheratingoftheovercurrentdeviceprotectingthebusbardoesnotexceed120%ofthecurrentratingofthebusbar.
2017 NEC
23
705.12(D)(6)WireHarnessandExposedCableArc-FaultProtection
Duetoissuescomplyingwiththissectionformicroinverter,ithasbeenremovedfromthe2017NEC.InadditionTIA14-11wasissuedthatremoves705.12(D)(6)fromthe2014versionofthecode.
2017 NEC
24
PartIV.MicrogridSystems
MicrogridshavebeenaddedtoArticle705.
Definedin705.2as“Apremiseswiringsystemthathasgeneration,energystorageandload(s),oranycombinationthereof,thatincludestheabilitytodisconnectfromandparallelwiththeprimarysource”.
InformationalNote:Theapplicationofarticle705tomicrogridsystemsislimitedbytheexclusionsin90.2(B)(5)relatedtoelectricutilities(exclusivecontrol).
2017 NEC
25
Article706EnergyStorageSystems
Scope:Thisarticleappliestoallpermanentlyinstalledenergystoragesystems(ESS)operatingatover50voltsacor60voltsdcthatmaybestandaloneorinteractivewithotherelectricpowerproductionsources.
2017 NEC
26
Notcoveredintoday’sdiscussion.Theadditionof:
Article710Stand-AloneSystems
Article712DirectCurrentMicrogrids
2017 NEC
27
OtherChangestotheSection690:• 690.2NewdefinitionsforDC-to-DCconvertercircuits,PVSystemdccircuit,
Generatingcapacity,functionalgroundedPVsystem• 690.4(D)clarifiesthatmultiplePVsystems,notjustmultipleinvertersare
permittedonasinglebuilding• 690.4(E)clarifiesthatPVsystemequipmentanddisconnectingmeansshall
notbeinstalledinbathrooms.• 690.13(F)Typeofdisconnectdefinessimultaneousdisconnectionofall
conductors,prohibitsuseofdevicesmarked“line”and“load”frombeingbackfedandallowstheuseofvarioustypesofDCratedswitches.
• 690.15definesanisolatingdevice,ratingrequirementsforequipmentdisconnectingmeansandrequirementsforequipmentdisconnectingmeans.
2017 NEC
28
MoreChangestotheSection690:• 690.31(B)(1)DisallowstheuseofwhitewireonthedcsideofaPVsystem
foranythingexceptsolidlygroundedPVsystems.• 690.72Selfregulatedchargecontrollers.• Table690.31(E)forminimumPVwirestrandsforflexiblecordsandcables
(table690.31(E)Correctionfactorsfromthe2014NEChasbeenrelabeledtotable690.31(A))
• 690.47(B)AdditionalAuxiliaryElectrodesforArrayGrounding• 690.59ConnectionstoOtherSourcesreferencesPartsIandIIofArticle
705.• PartVIIIrenamedtoEnergystoragesystemsandreferencesarticle706.• PartIX.Systemsover1000VoltsandPartX.ElectricVehicleCharging,both
removedfromArticle690astheyarecoveredelsewhere.
NYS Uniform Code Amendments and Supplements for Roof
Mounted Solar Electric Arrays
Fire Code and Structural Code Issues in Siting Residential and Commercial Systems
30
Safety concerns expressed by the fire fighting community, regarding exposure to high dc voltage roof top, or concealed conductors has fostered many changes in the 2014 NEC.
Access to ground mounted, and access and ventilation of roofs with solar arrays on them are also of concern. This has resulted in restrictions in the area that can be covered by modules.
NY State has updated its building codes with respect to the location of solar modules for roof and ground mounted arrays during the development of this course.
The following is not an all –inclusive summary of these updates
Fire Codes Issues in Siting PV Systems
• The 2015 International Fire Code (IFC), Section 605.11 addresses requirements for solar photovoltaic power systems.– Requires minimum setbacks for roof-mounted PV arrays to allow
firefighters safe access, pathways and areas for smoke ventilation.
• The 2016 New York State Uniform Fire Prevention and Building Code (the “Uniform Code”) has adopted by reference the 2015 edition of the International Fire Code (2015 IFC) with amendments.– Portions of the 2015 IFC have been adopted in the 2015 edition of
the International Residential Code (2015 IRC) with amendments in SECTION R324: SOLAR ENERGY SYSTEMS.
31
• The 2015 International Building Code (2015 IBC) Section 101.4.5 on fire prevention requires compliance with the 2015 International Fire Code (2015 IFC) for commercial buildings and other structures permitted under the 2015 IBC.
• The NY State Uniform Code Supplement has amended Section 605.11 of the 2015 IFC by the replacement of sections 605.11.1 through 605.11.1.2.5 in their entirety, and the addition of a new section 605.11.1.2.6.
– TheseNYamendmentschangethe2015IFCsetbackrequirementsforrooftopmountedPVarraysbasedonnewdefinitionsforACCESSROOF,GROUNDACCESSAREA,andROOFACCESSPOINT.
• NY State has amended the 2015 International Residential Code (2015 IRC) in the 2016 Uniform Code Supplement to include certain fire code requirements for residential construction in Section R324.
32
2015 International Fire CodeResidential vs. Commercial
• The residential building code as amended for New York State allows the designers of photovoltaic systems several options and alternatives. These illustrations are offered as possible examples. It is not possible to show every possible scenario. It is however up to the judgement of the local code official to determine final compliance with the code.
• Contractors, design professionals, and AHJ’s must consider many ventilation scenarios and consider that:
– 1.Afirecanbreakoutanywhereinabuilding.– 2.Emergencyrespondersdonothavex-rayvision.Alternateventilationmethodsshouldconsiderfiresoccurringinlessthanideallocations.
– 3.ContractorsandAHJmustrememberthatthedirectionandmagnitudeofaprevailingwindcanaffectthelocationoftheventilationopening
33
NYSERDA’s Assessment of These Changes
• R324.7.4 Single ridge roofs. Panels, modules, or arrays installed on roofs with a single ridge shall be located in a manner that provides two, 36 inches wide (914 mm) access pathways extending from the roof access point to the ridge. Access pathways on opposing roof slopes shall not be located along the same plane as the truss, rafter, or other such framing system that supports the pathway.
• Exceptions:# 1.Roofswithslopesof2unitsverticalin12unitshorizontal(16.6percent)andless.
# 2.Structureswhereanaccessrooffrontsastreet,driveway,orotherareareadilyaccessibletoemergencyresponders.
# 3.Oneaccesspathwayshallberequiredwhenaroofslopecontainingpanels,modulesorarraysislocatednotmorethan24inches(610mm)verticallyfromanadjoiningroofwhichcontainsanaccessroof.
34
2015 IRC Section R324.7.4Access and Pathways: Single Ridge Roofs
35
Single ridge roof showing a smaller array without any exceptions
Source:NYSERDASystemshownwithoutanyexceptionswhereverticalventilationtechniqueswillbeemployedresultinasmallerarray.
36
Single ridge roof — single pathway with exception #2 single ridge roof indicating ground access
Source:NYSERDA
Exceptionemployed.Groundaccesspointsmustalignwithroofaccesspoints.Notethatthetwoaccesspointsand36”pathwaysallowtwodirectionsofaccessandegressanddonotshareacommontrussorrafter.Thereisalsoadequateunobstructedgroundaccess.Noteincreasedsizeofarraypossible.
37
Single ridge roof — single pathway with exception #3 adjoining roof within 24 Inches
Source:NYSERDA
Withanadjoiningroofwithin24inchesofthearrayroof,applyingexception#3youwouldonlyneedasingleaccesspointandpathwayonthemainroof,asthereissecondaryaccessviaanadjoiningroofwithin24inches.Thisstillallowstwodirectionsofegress,anddoesnotshareacommontrussofrafter.
38
Single ridge roof –with Alternate Ventilation Location
Source:NYSERDA
Roof Access
sitew/proposedalternateventilation
Ifventilationisrequireditmaybepossibletoproposeanalternateventilationlocationonroofslopeoppositethearrayorthesidewallofanatticspace.AlternatelocationsshouldbecoordinatedandapprovedbytheAHJ.
Roof Access
Roof Access
• R324.7.5 Hip roofs. Panels, modules, and arrays installed on dwellings with hip roofs shall be located in a manner that provides a clear access pathway not less than 36 inches wide (914 mm), extending from the roof access point to the ridge or peak, on each roof slope where panels, modules, or arrays are located.
• Exceptions: # 1.Roofswithslopesof2unitsverticalin12unitshorizontal(16.6percent)andless.
# 2.Structureswhereanaccessrooffrontsastreet,driveway,orotherareareadilyaccessibletoemergencyresponders.
39
2015 IRC Section R324.7.5:Access and Pathways: Hip Roofs
40
Hip roof showing alternate venting with two roof pathways and ground access - no exception necessary
Source:NYSERDA
Atypicalhiproof,showingalternateventinglocationandclearaccesspathwaynotlessthan36incheswide(914mm)extendingfromtheroofaccesspointtotheridgeorpeak.
• R324.7.6 Roofs with valleys. Panels and modules shall not be located less than 18 inches (457 mm) from a valley.
• Exception: # Roofswithslopesof2unitsverticalin12unitshorizontal(16.6percent)andless.
41
2015 IRC Section R324.7.5:Access and Pathways: Hip Roofs
42
Valley Roof showing 18” clearance in yellow to the array-no exception necessary
Source:NYSERDA
Thisimageshowsthe18inchclearspacefromthevalleytothearray.Thereisanadditional18clearspaceontheothersideofthevalleyatB.
B
43
Hip roof with exception #2 where access roof fronts a street or driveway
Source:NYSERDA
• R324.7.7 Allowance for smoke ventilation operations. Panels and modules shall not be located less than 18 inches (457 mm) from a ridge or peak.
• Exceptions: # 1.Whereanalternativeventilationmethodhasbeenprovidedorwhereverticalventilationmethodswillnotbeemployedbetweentheuppermostportionofthesolarphotovoltaicsystemandtheroofridgeorpeak.
# 2.Detachedgaragesandaccessorystructures.
44
2015 IRC Section R324.7.7Allowance for Smoke Ventilation
The following slides provide NY amendments to the 2015 IFC that apply to COMMERCIAL buildings constructed per the 2015 IBC.
Many of the requirements are the same as amended to the 2015 IRC Section 324.7 regarding new requirements for access, pathways and ventilation.
45
2015 IFC Section 605.11.1.3Requirements for Other Than Group R-3 Buildings
• 605.11.1.3 Other than Group R-3 buildings. Access to systems for buildings, other than those containing Group R-3 occupancies, shall be provided in accordance with Sections 605.11.1.3.1 through 605.11.1.3.3.
• Exception: Where it is determined by the fire code official that the roof configuration is similar to that of a Group R-3 occupancy, the residential access and ventilation requirements in Sections 605.11.1.2.1 through 605.11.1.2.5 shall be permitted to be used.
46
2015 IFC Section 605.11.1.3Requirements for Other Than Group R-3 Buildings
• 605.11.1.3.1 Access. There shall be a minimum 6-foot-wide clear perimeter around the edges of the roof.
– Exception:Whereeitheraxisofthebuildingis250feetorless,theclearperimeteraroundtheedgesoftheroofshallbepermittedtobereducedtoaminimum4footwide.
47
Requirements for Other Than Group R-3 Buildings2015 IFC Section 605.11.1.3.1: Access
• 605.11.1.3.2 Pathways. The solar installation shall be designed to provide designated pathways. The pathways shall meet the following requirements:
– 1.Thepathwayshallbeoverareascapableofsupportingfirefightersaccessingtheroof.
– 2.Thecenterlineaxispathwaysshallbeprovidedinbothaxesoftheroof.Centerlineaxispathwaysshallrunwheretheroofstructureiscapableofsupportingfirefightersaccessingtheroof.
– 3.Pathwaysshallbeastraightlinenotlessthan4feetcleartoroofstandpipesorventilationhatches.
– 4.Pathwaysshallprovidenotlessthan4feetcleararoundroofaccesshatchwithnotlessthanonesingularpathwaynotlessthan4feetcleartoaparapetorroofedge.
48
Requirements for Other Than Group R-3 Buildings2015 IFC Section 605.11.1.3.2: Pathways
• 605.11.1.3.3 Smoke ventilation. The solar installation shall be designed to meet the following requirements:
– 1.Arraysshallbenotgreaterthan150feetby150feetindistanceineitheraxisinordertocreateopportunitiesforfiredepartmentsmokeventilationoperations.
– 2.Smokeventilationoptionsbetweenarraysectionsshallbeoneofthefollowing:
– 2.1.Apathway8feetorgreaterinwidth.– 2.2.A4-footorgreaterinwidthpathwayandborderingroofskylightsorgravity-operateddropoutsmokeandheatventsonnotlessthanoneside.
– 2.3.A4-footorgreaterinwidthpathwayandborderingallsidesofnongravity-operateddropoutsmokeandheatvents.
– 2.4.A4-footorgreaterinwidthpathwayandbordering4-footby8-footventingcutoutsevery20feetonalternatingsidesofthepathway.
49
Requirements for Other Than Group R-3 Buildings2015 IFC Section 605.11.1.3.3: Smoke Ventilation
Access, Pathways and Ventilation: Examples
Access pathways are provided around the perimeter and throughout building-mounted PV arrays to provide for firefighter access and ventilation.
Access, Pathways and VentilationLarge Commercial Example
LargeCommercial(Axis>250’)8’Walkways
CALFIRE-OSFMAccess pathways51
Building Requirements: Large Commercial ExampleCodeCompliantforLargeCommercial
Building Requirements: Large Commercial Example
52
CodeCompliantforLargeCommercial
Fire Code Issues in Siting Systems
Access and Ventilation Requirements are a function of Building Size
Access pathways
CAL FIRE-OSFM
Building Requirements: Small Commercial Example
53
CodeCompliantforSmallCommercial
Fire Code Issues in Siting Systems
Access and Ventilation Requirements are a function of Building Size
Access pathways
Access pathways CAL FIRE-OSFM
Building Requirements: Small Commercial Example
54
CodeCompliantforSmallCommercial
Fire Code Issues in Siting Systems
Access and Ventilation Requirements are a function of Building Size
Photos courtesy of DOE/NREL
Ground Mounted Systems
55
Fire Code Issues in Siting Systems
• R324.6Ground-mountedphotovoltaicsystems.Ground-mountedphotovoltaicsystemsshallbedesignedandinstalledinaccordancewithSectionR301(DesignCriteria).⁻ R324.6.1Fireseparationdistances.Ground-mountedphotovoltaic
systemsshallbesubjecttothefireseparationdistance requirementsdeterminedbythelocaljurisdiction.
56
Question and Answer Assessment
NEC2017Q1)WhataretheboundarylimitationsforRapidShutdown?A1) Arrayboundaryis30cm(1ft)inalldirections.Allconductorsoutsidethisboundaryshallbelimitedtonomorethan30Vwithin30secondsofinitiatingRapidShutdown.Q2)Whatisthehighestvoltageallowedonbuildingsotherthanoneortwofamilydwellings?A2)PVSystemsDCcircuitsonothertypesofbuildingsshallbepermittedtohaveamaximumvoltageof1000voltsorless.Q3)Whatchangeshavebeenmadetofacilitatethereplacementofisolatedinverterswithnonisolatedinverters?A3)Disconnectswitchwiringandovercurrentprotectionhasbeenmademostlyuniformirrespectiveofwhethertheinverterisisolatedornonisolated.NYSUniformCodeAmendmentsandSupplementsforRoofMountedArraysQ4)WhatisoneofthepurposesofTheUniformCodeAmendmentsandSupplementforRoofMountedArrays?A4)Toallowalternativepathsforaccessandventilationofroofsinthecaseofafire.Q5)WhoultimatelyhasdecisionmakingauthorityforaccessandventilationplansA5)TheAuthorityHavingJurisdiction(AHJ).ConferwiththeAHJontheseplans.