Chaires Fire Station Addition - Leon County Chaires Fire...Max. Dead End Corridor: N/A (FBC Table...

10
Copyright Barnett Fronczak Barlowe, Architects. All rights Reserved 225 South Adams St, Tallahassee, FL 32301 Phone 850 224-6301 Fax 850 561-6978 Tallahassee Florida Revisions Date Project Code Drawn By: Checked By: CS-1 Leon County - Chaires Fire Station Addition Cover Sheet Construction Documents 14 April 2011 11000 JH2 RRB Chaires Fire Station Addition Leon County Chaires, FL for CONSTRUCTION DOCUMENTS

Transcript of Chaires Fire Station Addition - Leon County Chaires Fire...Max. Dead End Corridor: N/A (FBC Table...

Page 1: Chaires Fire Station Addition - Leon County Chaires Fire...Max. Dead End Corridor: N/A (FBC Table 1016) 20' (NFPA 7.3 Table A-7.6.1) N/A Min. Corridor/Aisle Width: N/A (FBC Table 1016)

Copyright Barnett Fronczak Barlowe, Architects. All rights Reserved

225 South Adams St, Tallahassee, FL 32301

Phone 850 224-6301 Fax 850 561-6978

Tallahassee Florida

Revisions

Date

Project Code

Drawn By:

Checked By:

CS-1

Leon County - ChairesFire Station Addition

Cover Sheet

ConstructionDocuments

14 April 2011

11000 JH2RRB

Chaires Fire Station AdditionLeon County

Chaires, FL

for

CONSTRUCTION DOCUMENTS

Page 2: Chaires Fire Station Addition - Leon County Chaires Fire...Max. Dead End Corridor: N/A (FBC Table 1016) 20' (NFPA 7.3 Table A-7.6.1) N/A Min. Corridor/Aisle Width: N/A (FBC Table 1016)

Copyright Barnett Fronczak Barlowe, Architects. All rights Reserved

225 South Adams St, Tallahassee, FL 32301

Phone 850 224-6301 Fax 850 561-6978

Tallahassee Florida

Revisions

Date

Project Code

Drawn By:

Checked By:

CS-2

Leon County - ChairesFire Station Addition

Index

ConstructionDocuments

14 April 2011

11000 JH2RRB

ARCHITECTURAL DRAWINGS

ELECTRICAL DRAWINGS

GENERAL

CIVIL DRAWINGS

GENERAL LEGEND INDEX OF DRAWINGSABBREVIATIONS

SITE LOCATION MAP

RIGID INSULATION

SAND/CEMENT MIX

BLOCK

PROPERTY LINEDOOR MARKREFER TO ROOM

REFER TO SHEET

PARTITION TYPEREFER TO SHEET

ELEVATION HEIGHT

SPOT ELEVATION

MORTAR/PLASTER

INFILL CONSTRUCTION

EARTH/COMPACTED

STUCCO

CONCRETE

NORTH ARROW

ROOM NAMEAND NUMBER

WINDOW TYPE

NUMBER

WOOD-CONTINUOUS

BATT INSULATION

CMU INFILL

GRAVEL

P.I.P. CONC.

FINISH WOOD

INFILL CONSTRUCTION

NON-CONTINUOUS

MATCH LINE

BREAK LINE

HIDDEN LINE(BEYOND)

OVERHANG ORSOFFIT LINE (ABOVE)

SHEET NUMBER

WALL OR SECTION

BUILDING SECTION

SECTION NUMBER

DETAIL NUMBERPLAN/SECTION/

SHEET NUMBER

SHEET NUMBERNUMBER

SHEET NUMBER

OR NUMBER

SHEET NUMBERNUMBER

COLUMN LETTER

INTERIOR ELEVATION

PLAN OR SECTIONNUMBER

30

EL.000.00'

OFFICE100

100

1A2.1

1A2.1

1A2.1

1A2.1

1A2.1

A1.1A1.2

A4.1

DEMOLITION & NEW CONSTRUCTION PLANSROOF & FRAMING PLANS, BUILDING ELEVATIONS/SECTIONSBUILDING ELEVATIONSWALL SECTIONS & DETAILS

INDEX & GENERAL NOTESSITE PLANGRADING PLAN

COVERC1.0C2.0

CS-1CS-2CS-3

COVER SHEETINDEX OF DRAWINGSCODE REVIEW

E1.1 ELECTRICAL PLAN, NOTES @ DETAILS

GYP. BD.

COND.

DIA., D.

AMP.,A

APPROX.

BLDG.

ARCH.

INV. EL.

INCAND.

DWG.(S)

EQUIP.

B.T.U.M.

COMP.

J.B.JCT.JT.

IN.

INSUL.INT.

HDWEHYD.

H.&V.

I.D.

EXIST. STEEL/MISC. METAL

NEW STEEL/MISC. METAL

G.P.M.

H.C.HT.H.M.

HTG.HR.H.P.

GR.GWB

H.B.

GALV.G.F.E.

GAL.

GL.GND.

FTG.

FPFT.

GA.

FVC

EXT.

F.D.

FL.FIN.F.H.C.F.E.C.F.E.

EXIST.

F.C.F.B.C.F.A.

EXP.E.J.

E.W.C.EXH.

EA.

EL

EQELEV

E.F.E.C.

BM.

FILL

A

P-1

DN.

E

D.S.DR.

DIFF.

D.J.DIST.

DIM.DISC.

CT

DET

CUC.T.B.

CONN.

CJCONT.

CONC.

CL

C.M.U.

CPTC.O.

CLG.

COL.

C.F.M.

C.I.CIRC.

CKT.

CER.

CAB.CAP.C/BC.D.

C

LC

BAL.BRG.

BBD.

BLK.

AN

ALUM.ALT.

A.C.ACP

A.F.F.A.H.U.

A.C.T.

AJ

JUNCTION BOX

JOINT JUNCTION

INVERT ELEVATION

INCANDESCENTINSULATION

INCHES

INTERIOR

HARDWAREHYDRANT

INSIDE DIAMETER

HEATING & VENTILATING WASTE CLEAN OUT

WIDE FLANGEWINDOW DIMENSION

WATER CLOSET

WELDED WIRE FABRIC

WEATHERPROOFWATER GAGEW.G.

W.W.F.WTR.WP.

WATER

W.C.O.WD.W.D.WF

W.C.

WOOD

GALLONS PER MINUTE

HANDICAP

HOLLOW METALHIGH POINT

HEIGHT

HEATINGHOUR

GYPSUM BOARDGYPSUM WALLBOARD

HOSE BIBB

GRILLE

GOVERNMENT FURNISHED EQUIPMENTGALVANIZEDGALLON

GLASSGROUND

FIRE PROOFINGFOOT-FEET

FIRE VALVE CABINETFOOTING

GAUGE

VENTILATION

VITROUS CLAYVINYL COMPOSITION TILE

VERTICAL EXPANSION JOINT

VERTICALVERIFY IN FIELDVENT THRU ROOFV.T.R.

VERT.

W.

V.I.F.

W/WATTWITH

VENT.V.E.J.V.C.VTV. VOLT

TELEPHONETEMPERATURE

THRESHOLD (THRESH)

TYPICAL

UNLESS NOTED OTHERWISE

TOP OF WALL (BEAM)T.O.W.(B)

TYP.TOIL.

UNOUR. URINAL

TOILET

THD.

TEMP.TEL.

THK.

T

THICK

TOP

EXTERIOR

FIRE EXTINGUISHER & CABINETFIRE EXTINGUISHER & BRACKET

FIRE HOSE CABINET W/ EXTINGUISHER

FLORIDA BUILDING CODE

FLOOR DRAIN

FLOORFINISH

FIRE ALARM

FLEXIBLE CONNECTION

EXISTING

ELECTRIC WATER COOLEREQUIPMENT

EXPANSIONEXPANSION JOINT (EJ)

EXHAUST

ELEVATION

EXHAUST FANEMPTY CONDUIT

FLOOR ELEVATION

EACH

EQUAL

SHEETSHT.STAND PIPESPECIFICATIONS

STORAGE

STAINLESS STEEL

SQUARE FEETSTRAIGHT RESILIENT BASE

SUSPENDEDSTRUCTURAL

STOR.

SUSP.STRUC.

STL

SW.

STEEL

SWITCH

SPEC.SQ. FT.

SP

SSSRB

REVOLUTION/MINUTEROUGH OPENING

SECTION

SUPPLY AIR

SCHEDULE

RAIN WATER LEADER

SERVICESUPPLY GRILLE

SUSPENDED ACOUSTICAL TILE

SECT.SCH.S.A.T.

SERV.S.G.

R.P.M.R.O.RM.

S.A.

RWL

ROOM

NOT IN CONTRACTN.I.C.BEAM

COMPRESSER

DOWN

DRAWING (S)DOWNSPOUT

EAST

DRAIN

DIFFUSER

DUMMY JOINTDISTRIBUTIONDISCONNECTDIMENSION

CERAMIC TILE

DIAMETER

CONDENSING UNITCERAMIC TILE BASE

DETAIL

CONNECTIONCONTINUOUS

CONDENSATE

CONTROL JOINT

CONCRETE

RETURN AIR GRILLER.A.G.

ROOF DRAIN

RETURN AIR REGISTER

REGISTERREINFORCING

RECEPTACLERECIRCULATING

RETURN GRILLE

REQUIRED

RECP.REG.REINF.REQ.

R.G.RET. RETURN

R.A.R.

RDY.RECIRC.

RD.R.D.

ROUND

READY

QUARTERQUANTITY

QUARRY TILE

RETURN AIR

PAINTED

PRESSURE TREATED

QUAN.

RAD.

RR.A.

RADIUS

RADIUS

QTR.

PTD.

QT

PTP.T.

PAINT

CONCRETE MASONRY UNIT

CLEAR

CLEAN OUTCARPET

CEILING

COLUMN

CAST IRONCIRCULATINGCUBIC FEET/MINUTE

CIRCUIT

CERAMIC

CAPACITY

CENTER LINE

CIRCUIT BREAKERCEILING DIFFUSER

CABINETCONDUIT

BALANCE

UNIT/HOURBRITISH THERMALBEARING

PLUMBINGPLYWOOD

PERIMETER

PRESS. PRESSURE

PRECAST CONCRETE

PSF POUNDS/SQUARE FOOTPOUNDS/SQUARE INCHPOUNDS/SQUARE INCH GAGE

PANELPNL.

PSTG.PSI

PER.

PLBG.PLYW'D

PL.

PC

PLATE

NUMBERNOT TO SCALE

ON CENTER

OPENINGOPPOSITE

PLASTIC LAMINATE

OVERHEADOUTSIDE DIAMETER

PARTITION

OPP.

P. LAM

OPNG.

PART.

O.H.

NO.NTS

O.D.

O.C.

ARCHITECTURAL

BOTTOM

BUILDINGBOARD

BLOCK

AMPERESANODIZED

ALUMINUMALTERNATE

APPROXIMATELY

AIR CONDITIONED

ACOUSTICAL TILEACOUSTICAL PANEL

ABOVE FINISH FLOOR

ACOUSTICAL JOINTAIR HANDLING UNIT

MODIFIED BITUMENMOISTURE RESISTANT

MASONRY OPENINGMISCELLANEOUS

MOUNTINGMOUNTEDMETAL THRESHOLD

NOT APPLICABLE

MTD.MTG.

NN.A.

NORTH

MISC.

MOD.BIT.MRM.T.

MO

MIN. MINIMUM

MAINTENANCEMAXIMUM

MECHANICALMAIN DISTRIBUTION PANEL

MOTORM.

M.D.P.MECH.

MAX.MAINT.

MTL. METAL

E.W. EACH WAY

ON CENTER EACH WAYO.C.E.W.

4701 Chaires Cross Rd

4701 Chaires Cross Rd

Page 3: Chaires Fire Station Addition - Leon County Chaires Fire...Max. Dead End Corridor: N/A (FBC Table 1016) 20' (NFPA 7.3 Table A-7.6.1) N/A Min. Corridor/Aisle Width: N/A (FBC Table 1016)

4 53

4

4 53

1

2

2

1

1

Copyright Barnett Fronczak Barlowe, Architects. All rights Reserved

225 South Adams St, Tallahassee, FL 32301

Phone 850 224-6301 Fax 850 561-6978

Tallahassee Florida

Revisions

Date

Project Code

Drawn By:

Checked By:

CS-3

Leon County - ChairesFire Station Addition

DATA & CODE

ConstructionDocuments

14 April 2011

11000 JH2RRB

PROJECT DATA AND CODE INVESTIGATION SUMMARYProject Name: Chaires Fire Station Addition

Project Location:City: Tallahassee/Chaires CommunityCounty: LeonState: FloridaProject Address: 4701 Chaires Cross Road

Project Number: 11000 Date: 12 April 2011

1. GENERAL PROJECT INFORMATION

Zoning: Rural Community Site Size: N/A

Required: Provided:Building Setbacks: Front: 25' Sides: 20' Rear: 25' Front: 25' Sides: 76' Rear: 70'Parking Setbacks: Front: 40' Sides: 20' Rear: 20' Front: ?? Sides: 73' Rear: 37'Height Limit Per Zoning: 45' N/AMax. % Impervious Surface 60% N/ATotal Parking Spaces: N/A N/AOther: ________________________________________________

2. ZONING AND RESTRICTIONS

3. APPLICABLE CODES

Occupancy GroupClassification: FBC: Group R w/ accessory S FBC Ch. 4, Section 508.3

NFPA: NFPA 101, Ch. 6, Section 6.1.3Gross Floor Area: Existing: 3,240 sq. ft.

Addition: 420 sq. ft.TOTAL: 3,660 sq. ft.

Net Floor Area: Existing: 3,240 sq. ft.Addition: 420 sq. ft.TOTAL: 3,660 sq. ft.

Total Occupancy: Existing: 3,240 sq. ft.Addition: 420 sq. ft.TOTAL: 3,660 sq. ft.

Occupancy Seperation: N/A - Mixed Occupancy FBC 708, NFPA Ch. 6, Sec. 6.1.14.1Tenant Seperation: N/A - Single Tenant FBC, Section 708

NOTE: Existing 2-hour separation between the residential occupancy and the apparatus bays will remainunchanged by this project

4. OCCUPANCY

Type of Construciton: FBC V FBC Ch. 5 & 6NPFA 101, Sec. 8.2.1, Table 8.1

Protected or Unprotected: UnprotectedNote: Protected or unprotected refers to the structure, NOT whether or not it is sprinkled.

Sprinkled or Non-Sprinkled: NonsprinkledAllowed: Provided:

Max. Building Height: 40' (FBC Tbl. 503) & Sec. 504 21'Max. No. of Stories: 1 (FBC Tbl. 503) & Sec. 504 1Max. Floor Area/Floor: 9,500 (FBC Table 505) 24,693 <(31,825 x 3)

SEE AREA MODIFICATION

Area Modificaiton Increase: Aa=[ ] + [ ] If=100 [ -.25] ( )

Total Allowable Area/Floor N / AMax. Building Area N / A

5. CONSTRUCTION

At x If 100

At x If 100

FP

W30

(FBC Table 601/NFPA Tbl. a.8.2.1)Fire Protection Requirements Required Provided

Exterior Bearing Walls, supporting more than 1 floor: 0/0 0Interior Bearing Partitions: 0/0 0Columns, supporting more than 1 floor: 0/0 0Beams, girders and trusses, supporting more than 1 floor: 0/0 0Floor & floor/ceiling 0/0 0Roof & roof/ceiling 0/0 0

(FBC Table 602)Exterior bearing wall(s) rating / % permitted openings Required Provided

North, Horizontal seperation distance: Over 30' 0/0 0South, Horizontal seperation distance: Over 30' 0/0 0East, Horizontal seperation distance: Over 30' 0/0 0West, Horizontal seperation distance Over 30' 0/0 0

Exterior non-bearing wall(s) rating / % permitted openings Required ProvidedNorth, Horizontal seperation distance: Over 30' 0/0 0South, Horizontal seperation distance: Over 30' 0/0 0East, Horizontal seperation distance: Over 30' 0/0 0West, Horizontal seperation distance Over 30' 0/0 0

Minimum Fire Resistance Walls & Partitions Protective Opening Limit of Fire Protective(FBC Tbl. 715.4) (FBC Tbl. 715.4) Rated Glazing(NFPA 7.1.3) (NFPA 8.2.3.2.3) (FBC Tbl. 715.4)

Fire Walls and Barriers (1hr Rated) N/A N/A N/AFire Walls and Barriers (>1hr Rated) 2hr / 2hr .75hr / .75hr 100 sq. in.Fire Partitions

Corridor Walls N/A N/A N/AOther Fire Partitions N/A N/A N/A

Exterior Walls N/A N/A N/ASmoke Barriers N/A N/A N/A(FBC Chapter 7)(NFPA 7.1.3.1)

Note: Janitor, Mechanical Rooms (w/ gas-fired equipment) and General Storage Areas in non-sprinkled buildingsrequire 1 hour rating and 3/4 hour opening protection.

Minimum Interior Finish ClassFBC Exits B Floor Exits access B FBC Table 803.5MFPA Exits B Floor Exits Access B or CNFPA 101, Chapter 10.2.2

Manual Fire Alarm Required YES FBC Chapter 9,NFPA 101, Chapter 12

6. FIRE PROTECTION

Required: Provided:Minimum Number of Exits: 2 (FBC Ch. 10, 1018, NFPA 7-4.1.2) 2

Max. Travel Distance: 100' (FBC Table 1015) 250' (NFPA 7.6, Table A-7.6.1) 85'

Max. Dead End Corridor: N/A (FBC Table 1016) 20' (NFPA 7.3 Table A-7.6.1) N/A

Min. Corridor/Aisle Width: N/A (FBC Table 1016) 44" (NFPA Ch. 48.2.3.2 N/A

Min. Egress Capacity Width 2.6" (FBC Table 1005) 2.6" (NFPA 7.3, Table 7.3.3.1) 72"(13 x .2 = 2.6)

Seperate or emergency source of light required? YES (FBC 1006, Table 1016) (NFPA, Ch 42.8.2.9) YES

7. EXITS

Required: Provided:Minimum Clear Door Width 32" (FBC 1008) (NFPA 7-2.1.2.3) N / AMinimum Egress Capacity Door With 32" (FBC 1008) (NFPA 7.2.1.2) N / AMaximum Door Width 48" (FBC 1008) N / AMinimum Door Height 6'-8" (FBC 1008) (NFPA7-1.5) N / ADoor Swing: Door must swing in the direction of egress if it serves 50 or more persons.

Doors shall not reduce the corridor or landing width to less than 1/2 the requried width during the openingprocess nor project more than 7" into the required width of the corridor or landing when fully open.

Minmum space between 2 hinged or pivoting doors = 48" plus the width of any door swinging into thespace. (FBC 1008)(NFPA 5-2.1.4)

Special egress panic hardware required? NO (FBC 1008)(NFPA 7.2.1.7)

8. DOORS

9. STAIRS N/A

10. RAMPS N/A

11. ELEVATORS N/A

12. HANDRAILS N/A

13. GUARDRAILS N/A

LIVE LOADS - FLOORS: (FBC Ch. 16, Table 1607.1) LIVE LOADS - ROOFS: (FBC 1607)

Condition: Load:Public Areas - Live Load 100 p.s.f.Public Areas - Dead Load 5 p.s.f.Storage - Live Load 125 p.s.f.Stair - Live Load 100 p.s.f.Stair - Dead Load 5 p.s.f.Mechanical / Electrical Rms. - LIve Load 125 p.s.f.Roof - Live Load 20 p.s.f.Roof - Dead Load 16 p.s.f.Guardrails / Handrails Point Load 200 lb. (FBC 1607)Wind Load 110 m.p.h.(FBC fig. 1609)Importance Factor 1.15 (FBC Tbl. 1604.5)

14. STRUCTURAL DESIGN LOADS

15. HANDICAPPED ACCESSIBILITY (ADA) REQUIREMENTS N/A

Code requirements FBC Ch. 13 - Energy Efficiency (Florida Energy Efficiency Code for Building Construction)Subchapter 4.

Recommended GuidlinesFloor Assemblies Wall Assemblies Roof AssembliesSlab on Grade R-0 Masonry R-7 Insulation Only R-19Raised Wood R-19 Wood Frame R-11 Assembly Total R-30Raised Concrete R-7 Metal Frame R-13

Note: Walls limited to exterior, adjacent & common walls.

Doors: Doors in exterior, adjacent and common walls should be limited to insulated glass, solid core wood,wood panel or insulated hollow metal types.

16. THERMAL RESISTANCE OF ASSEMBLIES

Approved Automatic Fire Sprinkler SystemsFlorida Statutes 553.895- Buildings 3 stories or more, except 1 & 2 family dwellings and open,

noncombustable parking garages > 20' from adjacent structures requirean approved automatic fire sprinkler system.

2004 FBC Chaper 9- Requirements as classified by occupancy and use. FBC Chapter 92003 NFPA 101 Sec. 9.7 Requirements as classified by occupancy and use. NFPA Chapter 12

Approved Automatic fire Sprinkler System Required? NO

Standpipe2004 FBC Section 905 Requirements as classified by listed condiditon. FBC Section 9052003 NFPA 101 Sec. 9.7.4.2 Requirements as classified by occupancy and use. NFPA Sec. 42.8.3.5

Standpipe Required? NO

Standpipe Class and Type2004 FBC Section 905 Requirements as Classified by listed condition. FBC Section 9052003 NFPA 14 Standard for the Installation of Standpipes.

Standpipe Class & Type Class 1 Semi-Automatic

Fire ExtinguishersCode Requirements: NFPA 10 Standards for Portable Fire Extinguishers 2002 EditionFire Hazard Classifications Class A, B & C NFPA 10, Ch 3.3.4Occupancy Hazard Class. Light (Low) NFPA 10, Ch 1.4.1Extinguisher Classification 10 lb. > 4A:60B:C

to be provided

Extinguisher Size & Distribution NFPA 10, Ch 5 &Annex E

Class "A" Hazards (Table 5.2.1)Min. Rating of Single Extinguisher 2-AMax. Floor (Coverage) Area / Unit "A" 3,000 sq. ft.Allowable Floor Area / Extinguisher 11,250 sq. ft.Max. Floor Area / Extinguisher 11,250 sq. ft.Max. Travel Distance to Extinguisher 75'

Class "B" Hazards (Table 5.3.1)Min. Rating of Single Extinguisher 10-BMax. Travel Distance to Extinguisher 30'

Class "C" Hazards To be distributed on the basis of anticipated Class "A" or Class "B" Hazards. Ch. 5-5Unit size as per other hazards.

Class "D" Hazards To be distributed in the immediate vicinity of hazard with max. travel distance Ch. 5-6of 75'. Unit size per mfgr.

Class "K" Hazards 30' max. travel distance. Ch 5-7

Total Extinguisher counts Required Provided*3,660 sq. ft. Floor area served 2 2 (Existing)11,250 sq. ft. Allowable Floor Area / ExtinguisherNote: Total provided must also meet max. travel distance.

17. FIRE EXTINGUISHING EQUIPMENT

Crawl Space (FBC 1203)

Crawl spaces under buildings shall be ventilated by mechanical means or foundation openings.

Mechanical Means See Mechanical Plans & Specifications

Foundation Openings Required Provided

Wood Floor Systems 1 sf net open area / 150 sf crawlspace N/A

Floor Systems other 1.5 sf net open area / 15 l.f. of exterior wall N/Athan Wood

Attic Space - Pitched Roof (FBC 2309.7)Required Provided

A ratio of total net free ventilating area to ceiling area of 1:150, orreduction to 1:300 providing a vapor retarder on warm side of ceilingor 50% or required vent area by means of mechanical ventilators andbalance by eave or cornice vents.

18. VENTILATION REQUIREMENTS

1/16" = 1'-0"CS-31 Wind Load

ZONE

1

2

3

4

5

ROOF INTERIOR FIELD

ROOF EDGES, HIPS & PEAKS

ROOF CORNERS & RIDGEAT EDGE

ROOF EDGES & HIPS,OVERHANG

ROOF CORNERS & RIDGE,OVERHANG

EDGE ZONE WIDTH = 3'-0"MEAN ROOF HEIGHT = 16'-0"IMPORTANCE FACTOR 1 = 1.15WIND SPEED = 110 MPHEXPOSURE CATEGORY = B

+-

+-

+-

+-

+-

1220

1234

1250

1243

1269

+-

+-

+-

+-

+-

1119

1131

1146

1143

1163

+-

+-

+-

+-

+-

1018

1028

1042

1043

1054

+-

+-

+-

+-

+-

918

925

939

943

948

+-

+-

+-

+-

+-

918

925

939

943

948

+-

+-

+-

+-

+-

918

925

939

943

948

10 20 50 100 200 500

EFFECTIVE TRIBUTARY AREA (SQ. FT.)

WIND PRESSURES FOR ROOF & WALLS (PSF)

(COMPONENTS & CLADDING)

Building Florida Building Code (FBC) 2007 Edition, w/ 2009 rev.Mechanical Florida Mechanical Code (FMC) 2007 Edition, w/ 2009 rev.Gas Florida Gas Code (FGC0 2007 Edition, w/ 2009 rev.Plumbing Florida Plumbing Code (FPC) 2007 Edition, w/ 2009 rev.Fire Florida Fire Prevention Code (FFPC) 2007 Edition,Life Safety NFPA 101, Life Safety Code (LSC) 2007 Edition,Electrical National Electrical Code (NEC 70) 2007 EditionEnergy Florida Mechanical Code (FMC, Chapter 13) 2007 Edition, w/ 2009 rev.ADA Florida Building Code (FBC, Chapter 11) 2007 Edition, w/ 2009rev.

Footing Bearing Capacity 2,500 p.s.f.(per Alpha Geotechnical Report #11-2205 dated 13 Feb. 2011)

Page 4: Chaires Fire Station Addition - Leon County Chaires Fire...Max. Dead End Corridor: N/A (FBC Table 1016) 20' (NFPA 7.3 Table A-7.6.1) N/A Min. Corridor/Aisle Width: N/A (FBC Table 1016)
Page 5: Chaires Fire Station Addition - Leon County Chaires Fire...Max. Dead End Corridor: N/A (FBC Table 1016) 20' (NFPA 7.3 Table A-7.6.1) N/A Min. Corridor/Aisle Width: N/A (FBC Table 1016)
Page 6: Chaires Fire Station Addition - Leon County Chaires Fire...Max. Dead End Corridor: N/A (FBC Table 1016) 20' (NFPA 7.3 Table A-7.6.1) N/A Min. Corridor/Aisle Width: N/A (FBC Table 1016)
Page 7: Chaires Fire Station Addition - Leon County Chaires Fire...Max. Dead End Corridor: N/A (FBC Table 1016) 20' (NFPA 7.3 Table A-7.6.1) N/A Min. Corridor/Aisle Width: N/A (FBC Table 1016)

5A1.2

6A1.2

4A4.1

378 SF

NEW TRUCK BAY101

NEW CONC. PORCH -SLOPE 1/8" / ft. FORDRAINAGE

ADDITION

15' - 0"

1' - 4" 1' - 4"

ADD

ITIO

N

28' -

0"

POR

CH

8' -

8"

MATCH SLOPE & FINISHOF EXIST. TRUCK BAY

3' - 0"

3' -

0"1'

- 4"

1' -

4"

4"

8" CONC. SLAB w/2 LAYERS OF WWF

6x6-W4.0xW4.0

4" CONC. SLAB W/8" TURN DOWN EDGE -

1 LAYER OF WWF6x6-W2.9xW2.9

8"

8"

3' -

0"23

' - 0

"

REMOVE EXISTING WINDOW (TO BEREOLOCATED) ANDEXTERIOR WALL BELOW TOFORM A WALK THROUGH OPENING.WAIT UNTIL ADDITION IS DRIED INTO PRESERVE BUILDING SECURITY

REMOVE EXISTING EXTERIOR WALL(UP TO 8'-8") TO FORM A WALKTHROUGH OPENING. WAIT UNTILADDITION IS DRIED IN TO PRESERVEBUILDING SECURITY.

REMOVE EXISTING PORCH SLAB, ROOFAND COLUMNS.

EXISTING TRUCK BAY

BEDROOMBEDROOM

TOILET

TOILET

OFFICE

LIVING QUARTERS

RELOCATE EXISTING EXTERIORHORN TO SOUTHWEST CORNEROF NEW ADDITION

REMOVE EXISTING ROLL-UPDOORS AND PREPARE FORNEW 10x10 ROLL-UP DOORS(COORDINATE DEMOLITIONW/ INSTALLATION OF DOORIN ADDITION AND OWNER)

EXIST WINDOWTO REMAIN

DEMO FORRELOCATEDWINDOW

A1.24

2' - 4"

A1.2

3

5A1.2

14' - 6"

ADD

ITIO

N

28' -

0"

2' - 3" 10' - 0"

378 SF

NEW TRUCK BAY101

29' -

2"

3' -

4"

3' -

0"4'

- 1"

61' -

8"

79' - 4"

6A1.2

ADDITION

15' - 0"

EXIS

TIN

G B

UIL

DIN

G

EXIS

TIN

G B

UIL

DIN

G

New ConcretePorch

8' -

8"6"

8' -

2"

15' - 0"

6"

EXISTING TRUCK BAY

BEDROOMBEDROOM

TOILET

TOILET

OFFICE

LIVING QUARTERS

EXISTING DOOR- TO REMAIN

NEW 10' x 10'ROLL-UP DOOR

REMOVE EXIST.WINDOW & EXTENDOPENING TO FLOOR

EXISTING BUILDING

EXISTING BUILDING(Shaded Area)

HEASDER BEAM BYTRUSS MFGR.

-

4A4.1

NEWCASEDOPENING

NEW CASEDOPENING - SEETYPICAL DETAILS

5" BRICK

5" B

RIC

K27

' - 2

"5"

BR

ICK

REPLACE EXIST ROLL UPDOORS - MATCH TO NEW

EXIST. EXTERIORFINISHES TOREMAIN

6A4.1

CONTRACTOR SHALLVERIFY ALL EXISTING

CONDITIONS & DIMENSIONPRIOR TO BID

A1.15

3' -

0"

A1.16

A1.17

THIS FACILITY IS CONSTRUCTEDWITH LIGHT-GAUGE TRUSSES.PROVIDE & INSTALL SIGNAGECOMPLYING WITH FLA. ADMIN.CODE 69A-60.081 - RED REFLECTIVECOLOR- WITH THE LETTER "R"-MOUNTED TO WITHIN 24" OF THEDOOR & AT 5' AFF.

8" X 8"

LOCATION OFRELOCATED WINDOW- REPAIR SURROUNDINGG.W.B AND PROVIDEWOOD SILL - PAINT ALLTO MATCH EXISTING

12' -

0"

5A1.2

6A1.2

101GYP. 12'-0"

VINYL SOFFITMATERIAL (ATTACHTO BOTTOM CHORDOF TRUSSES - FURREDAS NEEDED)

SUSPENDED HEATER(COORDINATE W/ OWNER& ELEC. DWGS)

WRAP BEAM WITHVINYLTO MATCHSOFFIT COLOR

24" x 48" ATTICACCESS

VENTED VINYLSOFFIT (MATCHEXISTING)

5/8" GYPSUM BOARDCEILING ON 1-1/2"METAL HAT CHANNELS@ 16" O.C.

EXIST. 6" WD STUD W/BRICKVENEER CONSTRUCTION

BRICK VENEER TO MATCH EXIST.

5/8" GWB - LEVEL 4 FINISH -PAINTED (TYP.)

BATT INSULATION

1" AIR SPACE

EXTERIOR SHEATHING

NEW CASED OPENING - 1X TRIM- PAINTED

7"

3/4"

3"

CONSTRUCT 2X6 STUD FRAMINGAT WALL INTERSECTION ANDWALL OPENING

CAULK

EXIST. VINYL SIDING

CAP CUT EDGES WITHVINYL WITH VINYL DOOR OR"J" MOLDING

EXISTING BRICK VENEERWAINSCOT (BELOW) - TOREMAIN

NEW CASED OPENING -1X TRIM - PAINTED

NEW DBL. STUD AT OPENING

CAULK - TYP.

8 3/

4"

5 1/2"

VINYL JAMB CASING

SECTIONAL INSULATEDGARAGE DOOR

BRICK WAINSCOT- BELOW

VINYL SIDING WITH DOOR CASINGTRIM OR "J" MOLDING TRIM - MATCHADJACENT

EXTERIOR SHEATHING WITHVAPOR BARRIER

BATT INSULATION

5/8" G.W.B.

2X6 VERTICAL JAMBOR AS REQUIRED BYSECTIONAL DOOR FLA. PRODUCTAPPROVAL INSTALLATIONGUIDELINES

SECTIONAL GARAGE DOORWALL BRACKET MOUNTINGASSEMBLY - FASTEN PERFLA. PRODUCT APPROVAL

CAULK

PEEL & STICK WEATHERRESISTANT BARRIER - WRAPMIN. AROUND FACE OF OPENINGAND ENTIRE INTERIOR OF JAMB

8"

5 1/

2"

Copyright Barnett Fronczak Barlowe, Architects. All rights Reserved

225 South Adams St, Tallahassee, FL 32301

Phone 850 224-6301 Fax 850 561-6978

Tallahassee Florida

Revisions

Date

Project Code

Drawn By:

Checked By:

A1.1

Leon County - ChairesFire Station Addition

Demolition Plan, NewFoundation Plan, NewFloor Plan and NewReflected Ceiling Plan

ConstructionDocuments

14 April 2011

11000 JH2RRB

1/8" = 1'-0"A1.12 New Foundation Plan

1 06/20/2011 Code Comments

DEMOLITION NOTES1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

DEMOLITION CONTRACTOR SHALLVERIFY ALL BUILT CONDITIONS PRIORTO BIDDING. THE WINNINGCONTRACTOR TO RE-VERIFY ALLCONDITIONS PRIOR TO CONTRACTAND COMMENCEMENT OF WORK.

PROTECT ALL NON-DEMOLITIONAREAS FROM DEMOLITION RELATEDDAMAGE (INCLUDING DUST).

PROTECT ALL NON-DEMOLITIONAREAS FROM THE ELEMENTS,INCLUDING MAINTAINING AWEATHERTIGHT ENVELOPE AT ALLTIMES IN THE EXISTING FACILITY.

CAP ALL UNUSED UTILITIES ORREROUTE ALL IN-SERVICE UTILITIESPER CIVIL AND/OR MEP ENGINEERS.REFERENCE SPECIFIC ENGINEERDRAWINGS FOR ADDITIONALINFORMATION.

REMOVE AND SALVAGE ALL ITEM ASREQUESTED BY THE COUNTY ORARCHITECT/ENGINEER ON THESEPLANS. ANY AND ALL SALVAGEDITEMS SHALL BESTOCKPILED/STORED IN REMOVEDOR RECONDITIONED STATE, ORDELIVERED TO OWNER AS SPECIFIED,UNTIL RE-USED ON SITE IFAPPLICABLE.

CONSULT STRUCTURAL ENGINEERFOR QUESTIONS REGARDING THESEQUENCE OF THE DEMOLITION OFSTRUCTURAL ITEMS.

KEEP THE SITE CLEAN AND ORDERLY.

CONTRACTOR IS TO LIMIT THELOCATION OF CONSTRUCTIONVEHICLES, DEBRIS, MATERIALSTORAGE, LAY-OUT AREAS, ETC. TOLOCATIONS SPECIFIED BY OWNER.

CONTRACTOR IS RESPONSIBLE FORFOLLOWING SPECIFICATIONSGOVERNING CONSTRUCTIONACTIVITIES FOUND IN SECTION011000-SUMMARY.

CONTRACTOR IS RESPONSIBLE FORALL DEMOLITION BARRICADES,FENCING, ETC. SEPARATING STAFFFROM ALL CONSTRUCTIONACTIVITIES INCLUDING DUST, ODORAND NOISE.

CONTRACTOR IS SOLELYRESPONSIBLE FOR MAINTAININGSAFE CONSTRUCTION ZONEENVIRONMENT FOR STAFF.

1/8" = 1'-0"A1.11 Demolition Floor Plan

1/8" = 1'-0"A1.13 New Floor Plan

1/8" = 1'-0"A1.14 Reflected Ceiling Plan

1 1/2" = 1'-0"A1.15 Cased Opening - Detail 1

1 1/2" = 1'-0"A1.16 Cased Opening - Detail 2

1 1/2" = 1'-0"A1.17 Section Garage Door - Typical Detail

1

NOTE: ALL EXTERIOR COMPONENTS SHALL PROVIDEFLORIDA PRODUCT APPROVAL CERTIFICATION.

1

Page 8: Chaires Fire Station Addition - Leon County Chaires Fire...Max. Dead End Corridor: N/A (FBC Table 1016) 20' (NFPA 7.3 Table A-7.6.1) N/A Min. Corridor/Aisle Width: N/A (FBC Table 1016)

( SUBMIT GIRDER TRUSSCONNECTION FOR REVIEW)

HIP RAFTER

JAC

K TR

USS

@ 2

'-0" O

.C.

@ 2'-0" O.C. (TYP.)

STEP DN TRUSS 6' - 0"

@ 2'-0" O.C. (TYP.)

PIGGY BACK TRUSS

6' -

0"6'

- 0"

HIP RAFTER

WOOD BEAM4 - 2x10 No. 2 S.P.

2' - 0" O.H.

O.H

.2'

- 0"

O.H

.2'

- 0"

2' - 4"ROLL UP DOOR

10' - 0"

EXISTING ROOF(SHADED AREA)

3A4.1

5A4.1

4A4.1

6A4.1

SLOPE

SLO

PESL

OPE

SLO

PE

SLOPESLOPE

SLO

PE

SLOPE

SLOPE

SLO

PESL

OPE

WO

OD

BEA

M4

- 2x1

0 N

o. 2

S.P

.

GIR

DER

TR

USS

EXISTING ROOFFRAMING (DASHEDLINES)

6A4.1

5A1.2

6A1.2

NEW ROOF OVERNEW ADDITIONMATCH EXISTINGSLOPE OF 6:12 V.I.F.(SHADED AREA)

EXISTING ROOF(NON-SHADED AREA)

SLOPE

SLO

PESL

OPE

SLO

PE

SLOPE

RIDGE VENT

SLOPE

SLO

PE

SLOPE

SLOPE

SLO

PESL

OPE

Floor Plan0"

B.O.Truss-Truck Bay11' - 9 1/4"

6A1.2

ARCH. ASPHALT SHINGLES (MATCH EXISTING),VAPOR BARRIER AND 3/4" CDX ON PRE-ENGINEERED WOOD TRUSSES @24" O.C. TYP. (MAX.)

MATCH NEW RIDGEW/ EXISTING RIDGE

126

VERIFY SLOPEIN FIELD 12

6

EXISTING BUILDING ADDITIONReplace ExistingSECTIONALINSULATEDOVERHEAD

DOORS

SECTIONALINSULATEDOVERHEAD

DOOR

VINYL SIDING (MATCH EXISTING)

BRICK VENEER (MATCH EXISTING)

VISIONPANELS

(TYPICAL)

5' -

8"

WRAP OPENING AND INSIDE OFJAMB W/PEEL & STICK VAPORRESISTANT BARRIER UNDER VINYLSIDING

Floor Plan0"

B.O.Truss-Truck Bay11' - 9 1/4"

126

VERIFY SLOPEIN FIELD 12

6

ADDITION EXISTING BUILDING

ARCHITECTURAL ASPHALT SHINGLES(MATCH EXISTING), VAPORBARRIER AND 3/4" CDX ON PRE-ENGINEERED WOOD TRUSSES @24" O.C. TYP. (MAX.)

VINYL SIDING(MATCH EXISTING)

BRICK VENEER(MATCH EXISTING)

EXISTING DOORTO REMAIN

RELOCATED WINDOW- MATCH EXIST TRIM DETAILS

REMOVE BRICK AND VINYL ASNEEDED TO FLASH UNDERRELOCATED WINDOW

WRAP WINDOW PERIMETER OPENING -INSIDE JAMBS AND 8" OUTSIDE WITHPEEL & STICK OVERLAPPING SECTIONFROM THE BOTTOM TO TOP. PER ASTME2112-STANDARD PRACTICE FOR THEINSTALLATION OF EXTERIOR WINDOWS

Floor Plan0"

B.O.Truss-Truck Bay11' - 9 1/4"

6A1.2

A4.11

TRUSS BEARING8' - 0"

ADDITIONEXISTING BUILDING

EXISTING BUILDING TO REMAIN PIGGYBACK & NEW TRUSSES

126

VERIFY SLOPEIN FIELD 12

6

ARCHITECTURAL ASPHALTSHINGLES (MATCH EXISTING),VAPOR BARRIER AND 3/4" CDXON PRE-ENGINEERED WOODTRUSSES @ 24" O.C. TYP.(MAX.)

VINYL SIDING(MATCH EXISTING)

BRICK VENEER(MATCH EXISTING)

EXISTING WOOD FRAMING -ACTUAL DESIGN MAY VARY

SEALED CONCRETEFLOOR

5/8" GWB CEILING& WALLS - PAINTED

WOOD TRIM - PAINTED

Floor Plan0"

B.O.Truss-Truck Bay11' - 9 1/4"

5A1.2

8' -

8"

CONTRACTOR TO ENSURENEW FASCIA HEIGHT ANDSOFFIT DEPTH MATCHESEXISTING CONSTRUCTION

126

VERIFY SLOPEIN FIELD

BEAM BY TRUSS MFG.A4.1

3

A4.15

ARCHITECTURAL ASPHALT SHINGLES(MATCH EXISTING), VAPORBARRIER AND 3/4" CDX ON PRE-ENGINEERED WOOD TRUSSES @24" O.C. TYP. (MAX.)

BRICK VENEER(MATCH EXISTING)

EXISTING EXTERIORFINISHES TO REMAIN

SECTIONAL INSULATEDOVERHEAD DOORW/OPENER

VINYL SIDING(MATCH EXISTING)

VINYL WRAPPEDHEADER BEAM BYTRUSS MFG.

PROVIDE STUD PACKIN WALL (DASHED LINE)

ADDITION EXISTING BUILDING

6' -

8" 3' - 0"

3' - 0"

EXIST. DOORTO REMAINTURN CUT BRICK AT OPENING

SO THAT NATURAL EDGES FACESOPENING (TYP.)

Copyright Barnett Fronczak Barlowe, Architects. All rights Reserved

225 South Adams St, Tallahassee, FL 32301

Phone 850 224-6301 Fax 850 561-6978

Tallahassee Florida

Revisions

Date

Project Code

Drawn By:

Checked By:

A1.2

Leon County - ChairesFire Station Addition

Roof Plans, BuildingElevations andBuilding Sections

ConstructionDocuments

14 April 2011

11000 JH2RRB

1/8" = 1'-0"A1.22 Roof Framing Plan

1/8" = 1'-0"A1.21 Roof Plan

1 06/20/2011 Code Comments

1/8" = 1'-0"A1.23 West - New Building Elevation

1/8" = 1'-0"A1.24 South - New Building Elevation

1/8" = 1'-0"A1.25 New Building Section @ Truck Bay

1/8" = 1'-0"A1.26 New Building Section @ Addition

NOTE: ALL EXTERIOR COMPONENTS SHALL PROVIDEFLORIDA PRODUCT APPROVAL CERTIFICATION.

Page 9: Chaires Fire Station Addition - Leon County Chaires Fire...Max. Dead End Corridor: N/A (FBC Table 1016) 20' (NFPA 7.3 Table A-7.6.1) N/A Min. Corridor/Aisle Width: N/A (FBC Table 1016)

Floor Plan0"

B.O.Truss-Truck Bay11' - 9 1/4"

VINYL SIDING - MATCH EXISTING

CONT. VAPOR BARRIER ON5/8" CDX PLYWOOD SHEATHING

2x6 WOOD STUDS @ 16" O.C.& R-13 FIBERGLASS BATTINSULATION (MIN.)

BRICK ROWLOCK SET INMORTAR BED - SLOPE TOMATCH EXISTING

MAT

CH

EXI

STIN

G

12 B

RIC

K C

OU

RSE

S H

IGH1"

ASPHALT SHINGLES (MATCHEXISTING) ON 3/4" CDXPRE-ENGINEERED WOOD TRUSSES @24" O.C. W/ SIMPSON H10 HURRICANECLIP [8 - 8d x 1-1/2" TO PLATE & 8 - 8d x1-1/2" TO TRUSS (TYP.)

2x P.T. WD FASCIA W/ VINYLWRAP (MATCH EXISTING)(2) 2x6 TOP PLATE (TYP.)

5/8" GYP. BD. CEILINGON 1-1/2" MTL. HATCHANNELS @ 16" O.C.

R-30 FIBERGLASSBATT INSULATION -ALLOW FOR AIRFLOW AT ROOFDECK

5/8" GYP. BD.

WALL BASE(MATCHEXISTING)

8" CONC. SLAB W/2 LAYERS OF WWF6"x6"-W4.0xW4.0ON VAPORBARRIER ANDCOMPACTEDFILL - SEE SOILSREPORT

CONTRACTOR TO ENSURENEW FASCIA HEIGHT ANDSOFFIT DEPTH MATCHESEXISTING CONSTRUCTION

3 - #5 REBAR (CONT.)W/ #3 REBAR @ 16"(PERP.)

MIN

.

1' -

0"

1/2" DIA. ANCHOR BOLT@ 24" O.C.

TYP. EACH STUD:2 - SIMPSON SSP CONNECTOR(1 EACH SIDE OF STUD) W/4 - 10d NAILS TO STUD AND1 - 10d NAIL TO BOTTOM PLATE

TYP. EACH STUD:2 - SIMPSON SSP CONNECTOR(1 EACH SIDE OF STUD) W/4 - 10d NAILS TO STUD AND3 - 10d NAILS TO TOP PLATE

1' - 4"8"

VENTED VINYL SOFFIT

MIN4" SLOPE PER CIVIL DWGS.

A4.17

A4.18

MTL DRIP EDGE

CONT. NAILER

VINYL SIDING- INSTALLPER MANUFACTURERSTANDARD DETAILS

1 - SIMPSON VTCR CLIP @EA. INTERSECTION OF ANEW PIGGYBACK TRUSS &EXISTING TRUSS

PIGGYBACK TRUSS

EXISTING TRUSS & SHEATHING

3/4" CDX W/ VAPOR BARRIER

PLYWOOD & STUDWALL UP TO ROOFDECK

PRE-ENGINEEREDWOOD TRUSS

LAP SIDING - MATCH EXISTING

VAPOR BARRIER ON9/16" CDX PLYWOODSHEATHING

2x6 WOOD STUDS @ 16" O.C.& R-13 FIBERGLASS BATTINSULATION (MIN.)

(2) 2x6 TOP PLATE (TYP.)

5/8" GYP. BD. CEILINGON 1-1/2" MTL. HATCHANNELS @ 16" O.C.

5/8" GYP. BD.

2 - SIMPSON TBE6 CLIPS10 - 10dx1-1/2" TO TRUSS10 - 10dx1-1/2" TO PLATE

VENTED VINYL SOFFIT(MATCH EXISTING)

CONT. NAILER

PRE-ENGINEEREDWOOD JACKTRUSS

4 - 2x10 No. 2 S.P.(NAIL & GLUE TOMAKE BEAM)

SIMPSON H10 HURRICANE CLIP[8 - 8d x 1-1/2" TO BEAM &8 - 8d x 1-1/2" TO TRUSS (TYP.)

SEE DWG. 5/A2.1 FOR SOFFITCONSTRUCTION (WRAPPEDBEAM SHOWN GREY FORGRAPHIC CLARITY - SEEDWG. 8/A1.2)

2x4 No. 2 S.P. BLOCKING W/ 8d RINGSHANK NAILS @ 4" O.C.

VINYL CEILING PANELS(MATCH SOFFIT)

SIMPSON HWU8 - 16d TO SUPPORT BEAM8 - 16d x 1-1/2 TO BEAM

SIMPSON ECC(BEYOND)

6 x 6 WOOD POSTNo. 2 S.P. - PAINTED

8x8 SLAB TURNDOWN ELSEWHERE @ PORCH

3' - 0"

SIMPSON ABU66 W/2 - 1/2" MB

5/8" DIA. EPOXY ANCHOR

6"

3' x 3' x 16" DEEP FOUNDATION ATCORNER.

4 - #4 REBAR EA. WAY

MIN

.

3"

MIN.

3"

4" CONC. SLAB W/WWF 6x6xW2.9xW2.9

4"

VENTED VINYL SOFFIT & 1x P.T.WOOD TRIM W/ VINYL WRAP (MATCHEXISTING)

1' -

4"

1/2" PLYWOOD UP TOROOF DECK (EVERYOTHER SPACE)

PRE-ENGINEEREDWOOD TRUSS

WRAP BEAM TO MATCH SOFFITCOLOR

VAPOR BARRIER ON1/2" EXTERIOR SHEATHING

2x6 BLOCKING @ 16" O.C.

4 - 2x10 No. 2 S.P.(NAIL & GLUE TOMAKE BEAM)

2x6 TO FORM BOTTOMEDGE OF SOFFIT

SIMPSON H10 HURRICANE CLIP8 - 8d x 1-1/2" TO BEAM &8 - 8d x 1-1/2" TO TRUSS (TYP.)

SEE DWG. 5/A2.1 FOR SOFFITCONSTRUCTION

VINYL CEILING PANELS(MATCH SOFFIT)

BOTT

OM

OF

BEAM

1' -

6"

2x4 No. 2 S.P. BLOCKING W/ 8d RINGSHANK NAILS @ 4" O.C.

VENTED VINYL SOFFIT

MTL. DRIP EDGE

VINYL WRAPPED FASCIA

ASPHALT SHINGLE ROOFING

CONT. NAILER

4 - 2x10 No. 2 S.P. (NAIL & GLUETO MAKE BEAM) WRAP BEAM TOMATCH SOFFIT COLOR

SIMPSON H10 HURRICANE CLIP8 - 8d x 1-1/2" TO BEAM &8 - 8d x 1-1/2" TO TRUSS (TYP.)

VINYL CEILING PANELS(MATCH SOFFIT)

EXISTING PRE-ENGINEERED WOODTRUSS

LAP SIDING - MATCH EXISTING

VAPOR BARRIER ON1/2" EXTERIOR SHEATHING

2x6 WOOD STUDS @ 16" O.C.& R-13 FIBERGLASS BATTINSULATION (MIN.)

(2) 2x6 TOPPLATE (TYP.)

5/8" GYP. BD. CEILINGON 1-1/2" MTL. HATCHANNELS @ 16" O.C.

5/8" GYP. BD.

1/2" PLYWOOD DECK UP TOROOF DECK (EVERY OTHER

SPACE)

BOTT

OM

OF

BEAM

1' -

6"

8d RIM SHANK NAILS @6" INTO TRUSS

8d RIM SHANK NAILS@ 4" INTO BLOCKING

2x4 No. 2 S.P.BLOCKING

SIMPSON HUCQ610-SDSW/ 12 - SDS 1/4 x 2-1/2 TOSTUDS & 6 - SDS 1/4 x 2-1/2TO BEAM

STUD PACK @ BEAMINTERSECTION

VINYL SIDING - MATCH EXISTING

CONT. VAPOR BARRIER ON5/8" CDX PLYWOOD SHEATHING- LAP OVER FLASHING- 4" min.

BRICK ROWLOCK SET INMORTAR BED - SLOPE TOMATCH EXISTING

THROUGH WALL FLASHING W/WEEPS @ 24" O.C.

BRICK VENEER (MATCH EXIST.)W/ TIES @ 16" (VERT) AND32" (HORIZ)

1"

VINYL SIDING STARTER STRIP

EXT. SHEATHING WITH CONT.VAPOR RETARDER

min

.

8"

METAL FLASHING - SET INBED OF SEALANT - TYPICAL

Floor Plan0"

8" CONC. SLAB W/2 LAYERS OF WWF6"x6"-W4.0xW4.0ON VAPORBARRIER ANDCOMPACTEDFILL - SEE SOILSREPORT

MIN

.

1' -

0"

1' - 4"8"

MIN4"

8"

5/8" DIA. x 10" ANCHOR BOLT@ 32" O.C.

WALL BASE - MATCHEXISTING

CLR.3"

CLR

.

3"

CLR.

3"

8"

1"2"

BRICK VENEER (MATCH EXIST.)W/ TIES @ 16" (VERT) AND32" (HORIZ)

THRU-WALL FLASHING W/WEEPS @ 24" O.C.

GROUT FILL BELOW FLOOR LEVEL

SEALED CONCRETE SLAB

LAP VAPOR RETARDER OVERFLASHING (TYP.)

Copyright Barnett Fronczak Barlowe, Architects. All rights Reserved

225 South Adams St, Tallahassee, FL 32301

Phone 850 224-6301 Fax 850 561-6978

Tallahassee Florida

Revisions

Date

Project Code

Drawn By:

Checked By:

A4.1

Leon County - ChairesFire Station Addition

Wall Sections andDetails

ConstructionDocuments

14 April 2011

11000 JH2RRB

3/4" = 1'-0"A4.11 Typical Wall Section @ Truck Bay

OPTION 2

1 1/2" = 1'-0"A4.12 New Piggy Back Truss to Existing Roof

1 1/2" = 1'-0"A4.13 Wall Section @ Porch

1 1/2" = 1'-0"A4.14 Beam Section & Connection @ Porch

1 1/2" = 1'-0"A4.15 Typical Beam & Soffit @ Porch

1 1/2" = 1'-0"A4.16 Beam Connection @ Wall

1 06/20/2011 Code Comments

3" = 1'-0"A4.17 Brick Sill Detail

3" = 1'-0"A4.18 Sill Detail

NOTE: ALL EXTERIOR COMPONENTS SHALL PROVIDEFLORIDA PRODUCT APPROVAL CERTIFICATION UPONREQUEST

1

Page 10: Chaires Fire Station Addition - Leon County Chaires Fire...Max. Dead End Corridor: N/A (FBC Table 1016) 20' (NFPA 7.3 Table A-7.6.1) N/A Min. Corridor/Aisle Width: N/A (FBC Table 1016)