    Chapter 18

    Appliance Fuel Connector - assembly of listed semi-rigid or exible tubing and

    ttings to carry fuel bet. a fuel-piping outlet and a fuel burning appliance

    Fuel Gas- atural! manufactured! li"ueed petroleum or a mixture of these

    Gas #iping- any installation of pipe! $al$es! or ttings that is used to con$ey fuel

    gas! installed on any premises or in any but shall not include%

    &any portion of the ser$ice piping

    &any appro$ed piping connection six feet '1!8()mm* or less in length

    bet+een an existing gas

    outlet and a gas appliance in the same room +ith the outlet

    Gas #iping ,ystem- any arrangement of gas piping supplied by one meter and each

    arrangement of gas piping ser$ing a building! structure! or premises! +hether

    indi$idually metered or not

    ,er$ice #iping- he piping and e"uipment bet+een the street gas main and the gas

    piping system inlet that is installed by and is under the control and maintenance of

    the ser$ing gas supplier

     ransition Gas iser- any listed or appro$ed section or sections of pipe and ttings

    used to con$ey fuel gas and installed in a gas piping system for the purpose of

    pro$iding a transition from belo+ the ground to abo$e the ground

    /arth"ua0e actuated Gas ,huto 2al$e- a $al$e to be installed in a gas piping

    system designed to automoatically shut o the gas +hen a seismic disturbance is

    detected

    Copper and brass pipe shall not be used if the gas contains more than an a$erage of 

    3.4 grains of hydrogen sulde per 133scf of gas '3.5mg61337*

     hreaded copper! brass or aluminum alloy pipe shall not be used +ith gases

    corrosi$e to such material

    Copper and brass tubing shall not be used if the gas! contains more than an

    a$erage of 3.4g of hydrogen sulde per 133scf of gas '3.5mg61337*

    Copper tubing shall comply +ith standard type or 7 of A,9 : 88

    :ra;ing alloys shall not contain more than 3.3< percent phosphorus

    Gas meters shall be located at least 4 feet '3.)m* from sources of ignition

    7ongest 7ength 9ethod- the pipe si;e of each section of gas piping shall be

    determined using the longest length of piping from the point of deli$ery to the most

    remote outlet and the load of the section