r- ~. 'l1ffif WGfiR qovemment of India ~~~ = ~cfJ{;t~W:~ Western Regional Power Committee ~-3, ~~~~(,!,<),~-400093 F-3, MIDC Area, Andheri (East), Mumbai - 400 093 ~ Phone:022-28250004,28221681;28200194;28200195;~ Fax: 022- 28370193 Website: www.wrpc.gov.in E-mail: [email protected] ~ .~ ~'3TI g 9001-2008 ISO: 9001-2008 ~ :~ ICllfOlfV:<:ICb -I/~ I~ Cblc:ltr~"112018/ No. : WRPC/Comml.-I/CCM/Supp. Agenda/2018 I Wrr1f ITa ~ : 17.07.2018 Date: 17.07.2018 As per List (~cfi ~) ~/Sir, Sub : Supplementary Agenda notes for 78 th Commercial Committee Meeting (Item No 18). ~ q;r cfi m~~ 19 107 12018 c€r 11800 ~, ~ ~, "Cf 1~1 fcr 1 ~, ~~ ~, ~mr~,~ 1f m cmrIT, CllfOlfV:<:ICb ~ tt 78clT ~ tt~ Cblc:ltrrj)~ ~ ~ \3lTCl"~?:[q) ~ ~ ~ ~ 1 ~ ~ If m<rW1~ ~ aqUu fcf;<:rr \;fRfT ~ I ~~~~~ ~ajfll$OC: www.wrpc.nic.in1R~U~. ~'5I\3'1~il'5 ~I Please find enclosed herewith Supplementary Agenda Notes for the 78 th Commercial Committee Meeting of WRPC to be held on 19.07.2018 at 11:00 Hrs at WRPC Secretariat, Mumbai . This is for your information and necessary action. The Agenda notes for the meeting is www.wrpc.nic.in, same may please be downloaded. available on website ~ / Yours' faithfully. ~ 111011 \g (K. B. Jaqtap) ~~ ~ (CllfOlfV:<:ICfi) / Superintending Engineer (Comml.)

Transcript of ~cfJ{;t~W:~wrpc.nic.in/ccm/78ccm-suppl_agenda.pdf · Mailing list for 78th CCM 1. Executive...

r-

~.

'l1ffif WGfiRqovemment of India~~~=~cfJ{;t~W:~

Western Regional Power Committee~-3, ~~~~(,!,<),~-400093

F-3, MIDC Area, Andheri (East), Mumbai - 400 093~ Phone: 022- 28250004, 28221681;28200194;28200195;~ Fax: 022 - 28370193

Website: www.wrpc.gov.in E-mail: [email protected]

~

.~ ~'3TI g 9001-2008ISO: 9001-2008

~ : ~ ICllfOlfV:<:ICb-I/~ I~ Cblc:ltr~"112018/No. : WRPC/Comml.-I/CCM/Supp. Agenda/2018 I

Wrr1f ITa

~ : 17.07.2018Date: 17.07.2018

As per List (~cfi ~)

~/Sir,

Sub : Supplementary Agenda notes for 78th Commercial Committee Meeting(Item No 18).

~ q;r cfim~~ 19 107 12018 c€r 11800 ~, ~ ~, "Cf 1 ~ 1 fcr 1 ~, ~~

~, ~mr~, ~ 1fm cmrIT, CllfOlfV:<:ICb~ tt 78clT ~ tt ~ Cblc:ltrrj)~

~ ~ \3lTCl"~?:[q) ~ ~ ~ ~ 1 ~ ~ If m<rW1~ ~ aqUu fcf;<:rr \;fRfT ~ I

~~~~~ ~ajfll$OC: www.wrpc.nic.in1R~U~. ~'5I\3'1~il'5 ~I

Please find enclosed herewith Supplementary Agenda Notes for the 78th

Commercial Committee Meeting of WRPC to be held on 19.07.2018 at 11 :00 Hrs at

WRPC Secretariat, Mumbai . This is for your information and necessary action.

The Agenda notes for the meeting is

www.wrpc.nic.in, same may please be downloaded.

available on website

~ / Yours' faithfully.~

111011 \g(K. B. Jaqtap)

~~ ~ (CllfOlfV:<:ICfi)/ Superintending Engineer (Comml.)

Mailing list for 78th CCM

1. Executive Director (Finance), Gujarat Urja Vikas Nigam Ltd., Vadodara-390 0072. Chief Engineer (LD), Gujarat Energy Transmission Corpn. Ltd., Vadodara- 390 0213. Chief General Manager (Comml), MP Power Management Co.Ltd., Jabalpur-482 0084. Chief Engineer (LD), M P Power Transmission Company Ltd.,SLDC, Jabalpur 482 008.5. Chief Engineer (Comml), Chhattisgarh State Power Distribution Co. Ltd., Raipur – 492 0136. Chief Engineer (LD), Chhattisgarh State Power Transmission Co. Ltd., Bhilai-490 024.7. Chief Engineer (PP), Maharashtra State Electricity Distribution Co. Ltd., Mumbai-400 0518. Chief Engineer (LD), State Load Despatch Centre, MSETCL, New Mumbai - 400 7089. Chief Electrical Engineer, Panjim, Goa-403 00110. Executive Engineer, Electricity Department, Daman-396 21011. Executive Engineer (Elect),Electricity Department, Silvassa-396 23012. Addl. General Manager (Comml), Nuclear Power Corpn. of India Ltd., Mumbai-400 09413. General Manager (Comml), NTPC Ltd., New Delhi-110 00314. Regional Executive Director (West), NTPC Ltd., Mumbai-400 09315. General Manager (Com. & CP), NTPC SAIL Power Co. Pvt. Ltd., New Delhi -110 06616. Executive Director (Comml), PGCIL, Gurgaon, Haryana-122 00117. General Manager, WRTS-I, PGCIL, Nagpur-440 02618. Addl. General Manager (Comml), WRTS-I, PGCIL, Nagpur-440 02619. Executive Director, POSOCO,WRLDC, Mumbai-400 09320. Dy. General Manager (Comml), Ratnagiri Gas & Power Pvt. Ltd., Mumbai-400 09321. Vice President, Adani Power Limited, Ahmedabad – 38001522. Addl. Chief Engineer (R & C), Gujarat Energy Trans. Corpn. Ltd., Vadodara-390 00723. Chief Engineer (Trans. O&M), MSETCL, Mumbai-400 05124. General Manager (Comml), LANCO Amarkantak Power Private Ltd., Gurgaon – 122 01625. Member(Power), Narmada Control Authority, Indore.-452 01026. Vice President, Jindal Power Ltd., Tamnar, Raigarh, Chhattisgarh – 496 00127. Executive Director (Comml), Torrent Power Ltd., Ahmedabad- 380 00928. AVP(Power Trading),GMR Energy Trading Ltd., Bangalore-560 029.29. DGM Finance, CGPL, UMPP Mundra, Kutch-370 435.30. AGM(O&M/O&E) Ratnagiri Gas and Power Pvt Limited PO: Anjanvel, Taluka: Guhaghar

Disstt: Ratnagiri ( Maharastra) - Pin 41570331. Vice President (Powe CG) ACB India Ltd., 2*135 MW Kasaipali Power Project, Kasaipali, P.O.-

Jawali, Tehsil-Katghora, Korba –chhatisgarh-49544532. GM (O&M)Bharat Aluminium co. Ltd (BALCO), P.O. Balco Nagar, Distt. Korba -495684

Chhattisgarh33. AGM(F&A), DCPP JSPL, Dongamahua captive power plant(4*135 MW), Dhaurabhata(PO)

Raigarh-496107 (CG).34. Director, Jaypee Bina Thermal Power Plant, village sirchopi, Agasod P.O. Bina-470113 Distt.

Sagar(MP)35. Sr. Vice President (EPMPL), Essar Power MP Limited, Thana road, Near Chunkumari stadium,

Waidhan, Dist. Singrauli (MP)-486886.36. Vice-President, ACB India ltd. 7th floor , Corporate house, Ambience tower, National highway

Gurgaon-122001 Haryana.37. Sasan Power limited, Dhirubahi ambani knowledge city, 1 block, 2nd floor, north wing, Thane

belapur road, Navi Mumbai-400710.38. KSK Mahanadi Power CO. LTD, 8-2-293/82/A/431/A, Road no 22, Jubilee hills, Hyderabad-

50003339. Plant Head,GMR EMCO Energy ltd. B1, MIDC, Growth centre, Warora-post Chandrapur-

dist,Mahrashtra-44290740. Vice president(Comml.), Vandana Vidhut ltd., Vandana Bhavan, M.G. Road, Raipur-492001-CG41. Korba west power co. Limited, village chhotte bhandar, P.O. Babe Bhandar,Tehsil Pussore Dist.

Raigarh, chhattisgarh-49610

42. Ms. D B Power Ltd., 3rd floor, Naman corporate link, C-31, G-block, BKC Bandra eastMumbai-400051

43. Vice President-Power Infrastructure Plant- B MRSS, Essar Steel Ltd 27th km, Surat HaziraRoad,Surat-394270 Gujarat

44. Jaypee Nigrie Super Thermal Power Project( A Unit of Jaiprakash Power Ventures Limited )Vill-Nigrie, Tehsil- SaraiDistt.- Singrauli, MP-486669

45. GM-Coordination, Dhariwal Infrastruture LtdCESC ltd,CESC House, ChowringheeSquare,Kolkata-700001

46. Chief General Manager, RKM Powergen pvt ltd, Village Uchpinda, PO Dhurkot, Via chandrapur,Tehsil- Dabra, Janjgir-Champa dist, Chhattisgarh-495692.

47. GM (Operations)MB Power (Madhya Pradesh) LimitedHotel Govindam, Kotma Road,Anuppur,Madhya Pradesh – 484224

48. Head Project, Jhabua power ltd, Vill. Berela, post Attariya, Tehsil Ghansore, Dist-Seoni-480997(MP).

49. Sr. Vice-President (Power)TRN Energy Pvt ltd.18, Vasant EnclaveRao tula ram margNew Delhi-110057

50. Member Secretary, Northern Regional Power Committee, New Delhi 110 01651. Member Secretary, Southern Regional Power Committee, Bangalore 560 00952. Member Secretary, Eastern Regional Power Committee, Kolkata-700 03353. Member Secretary, North Eastern Regional Power Committee, Shillong 793 30354. Chief Engineer (GM), Central Electricity Authority, New Delhi –110 066.

Item no.18: Any other Item – Following additional items are received for

discussion/noting in the 78th CCM -

18.a. Correction of Time drift in energy meters

WRLDC vide email dated 17.07.18 (copy enclosed at Annex 18) informed that time drift

in Energy meters may result in computational errors in energy accounts. As per the

technical specifications of SEM, the DCD could be used to carry out corrections in SEM

clock by accelerating /retarding the SEM clock by 1min / week. The list of meters where

time drift has been reported / observed is enclosed as Annex-18.a

Concerned utilities to check the meter clock every week and

retard/advance the clock if required. The procedure for time drift correction

through DCD in L&T, Secure and Elster Meters is enclosed.

POWERGRID is carrying out testing of SEMs which are more than 5 years

old. Time drift correction in the SEM could be done along with the testing

of meters.

Committee may like to discuss

18.b. Submission of Test Reports of Special Energy Meters in Western

Region

WRLDC vide email dated 17.07.18 (copy enclosed at Annex 18) informed that WRTS-II

vide its letter ref. no. WRTS-II/VDR/AM/SK/260/1002 informed that testing of SEMs

more than 10 years old has already taken up. It was understood that the testing has

already completed at various locations in WR-2. POWERGRID to share the Meter Test

Report with the concerned beneficiaries as well as with WRPC and WRLDC.

Committee may like to discuss

18.c. Relocation of Check meters for ISGS evacuated through dedicated

lines

WRLDC vide email dated 17.07.18 (copy enclosed at Annex 18) informed that the

redundancy of interface energy metering of ISGS evacuating through dedicated lines

was reviewed. It was observed that even after removal of interim LILO of ISTS lines /

commissioning of dedicated lines, the check meters are yet to be shifted from the

Generating station to the interface points (at POWERGRID substation). Vide letter ref.

no. WRLDC/SO/Metering/774-90 dtd. 03.07.2018, WRLDC has advised relocation of

meters for twelve generating stations (IPPs). The list is enclosed as Annex-18.c. This

relocation is essential for ensuring redundancy of measurement and for better validation

of main meter data (at the interface point) used in energy accounting.

Concerned Utilities to update the progress.

Committee may like to discuss

18.d. Revision in metering points at Solapur (PG) for computation of

MSEDCL drawal

WRLDC vide email dated 17.07.18 (copy enclosed at Annex 18) informed that the

present metering philosophy at Solapur (PG) is as below:

At present, active energy drawal of Maharashtra from Solapur (PG) is computed through the

summation of ISTS elements (10 in nos.) at the 400 kV bus (i.e.

M1+M2+M3+M4+M5+M6+M7+M8+M9+M10) (total 10 meters)

It is proposed that Maharashtra active energy drawal at Solapur (PG) may be computed from

the summation of drawal through ICT-1, ICT-2, ICT-3, 400 kV Solapur-Solapur (Lamboti) line

and Statcom auxiliary drawal (i.e. = S17+S11+S12+S13+S18) (Total – 5 meters). As total no. of

meters will be half as that in present scenario, the meter error will be minimized. Commercial

Committee to endorse

1. Installation of one standby SEM on 400 kV Solapur-Lamboti line at Lamboti end

2. Revision in the formula for computing MSEDCL drawal (Active & Reactive) from

Solapur (PG)

Committee may like to discuss

18.e. Inclusion of SEMs on tertiary winding for computation of reactive

Energy drawal

WRLDC vide email dated 17.07.18 (copy enclosed at Annex 18) informed that back up

station supply at several POWERGRID substations is through the tertiary winding of

765/400 kV. The discom of the host State has also installed their energy meters for billing.

The SEMs installed on the tertiary side of the ICT are already added in the active energy

reports of the respective state. Committee may deliberate on the inclusion of SEMs

installed on tertiary side in computation of Reactive Energy Drawal.

Sr. No. Meter ID Description Reactive Report

1 NP-9212-A

33KV Tertiary side of 400/220/33KV ICT-1 at Durg(Raipur-PS)

CS

2 NP-9213-A

33KV Tertiary side of 400/220/33KV ICT-2 at Dharamjaygarh(PG)

CS

3 NP-5548-A

38.5 KV side of STATCOM Auxiliary transformer at SATNA

MP

4 NP-9897-A

38.5 KV side of STATCOM Auxiliary transformer at Aurangabad

MH

5 NP-8976-A

33 kV side of 765/400 kV ICT-2 at Warora (PG)

MH

6 NP-2319-A 11kV supply-1 from MSEB at Bhadravathi MH

7 NP-4216-A 11kV supply-2 from MSEB at Bhadravathi MH

Committee may like to discuss

18.f. Re-installation of SEM meter at tertiary side of 765/400/33 kV ICT-2 at

Warora (PG)

WRLDC vide email dated 17.07.18 (copy enclosed at Annex 18) informed that SEM

(NP-8976-A) installed at the 33 kV side of the 765/400/33 kV ICT-2 (used in

Maharashtra drawal) was removed by MSEDCL/Warora(PG) on 19.06.18 without taking

permission from WRLDC metering department. After removal of SEM, the energy drawn

from tertiary at Warora could not be added to Maharashtra drawal due to non-availability

of data.

It is required that SEM shall be reinstalled so that energy drawn by Warora (PG) for

meeting local substation demand may be added to Maharashtra drawal. MSEDCL has

already installed their own meter to bill Warora (PG) for this drawal.

MSEDCL / POWERGRID to take corrective action.

Committee may like to discuss

18.g. Installation of standby energy meters at Seoni, Kanhan and Mansar

WRLDC vide email dated 17.07.18 (copy enclosed at Annex 18) informed that WRLDC

vide its letter dated 03.01.18 had advised for installation of check meter at Pench HPS

and Standby meter at remote end. The check meters had been installed at Pench statin

by POWERGRID and main meters have been replaced with new meters as per the

following details.

Sr.No. Element name Main Meter Check Meter Standby meter 1 132kV Seoni line-1 at Pench Replaced (NR-3955-A) Installed (NR-3956- - 2 132kV Seoni line-2 at Pench Replaced (NR-4321-A) Installed (NR-3954- - 3 132kV Kanhan line at Pench Replaced (NR-3918-A) Installed (NR-3965- - 4 132kV Mansar line at Pench Replaced (NR-3957-A) Installed (NR-3962- - 5 132 kV Pench line-1 at Seoni - - To be installed 6 132 kV Pench line-2 at Seoni - - To be installed 7 132 kV Pench line at Kanhan - - To be installed 8 132 kV Pench line at Mansar - - To be installed

POWERGRID to apprise the CCM regarding the plan for installation of standby

energy meters at Seoni, Kanhan and Mansar end.

Committee may like to discuss

18.h. Interface Energy Meter Data Discrepancies

WRLDC vide email dated 17.07.18 (copy enclosed at Annex 18) informed that the

discrepancy report of SEMs is being forwarded to WRPC secretariat every week along with

the processed energy meter readings. These details are also posted on the WRLDC

website. The summary of these discrepancies is provided below:

a. 400kV side of ICT-2 at Aurangabad(PG)

The energy meter (NP-8716-A) data of 400kV side of ICT-2 at Aurangabad(PG) was corrupt

for the period 02.04.18 to 30.05.18. Therefore, 400 kV side data was replaced with the 220

kV side standby meter data.

b. 400kV Kansari Line-1 at Veloda

The energy meter (GJ-2971-A) data of 400kV Kansari Line-1 at Veloda was under recording

for the period 26.03.18 to 21.04.18. Therefore, Veloda end data was replaced with the

standby meter data at Kansari end.

c. 400kV Shujalpur line-1 at Nagda

The energy meter (NP-4229-A) of 400kV Shujalpur line-1 at Nagda, was under-recording for

the period 09.04.18 to 07.06.18. Therefore, Nagda end data was replaced with the standby

meter data at Shujalpur end.

d. 400kV GMR Warora line-1 at Bhadrawati

The energy meter (NP-2648-A) of 400kV GMR Warora line-1 at Bhadrawati was under-

recording for the period 26.04.18 to 25.05.18. Therefore, Bhadrawati end data was replaced

with the standby meter data at GMR Warora.

e. 400kV side of 400/220kV ICT-2 at ITARSI(PG)

The energy meter (NP-6222-A) data of 400kV side 400/220kV ICT-2 at ITARSI(PG) was

under-recording for the period 30.04.18 to 06.05.18. Therefore, 400kV side data was

replaced with the standby meter data at 220kV side of Itarsi ICT-2.

f. 400kV side of ICT-4 at Boisar(PG)

The date in the energy meter (NP-5511-A) of 400kV side 400/220kV ICT-4 at Boisar(PG)

was wrong for the period 04.05.18 to 21.05.18. Therefore, 400kV side data was replaced

with the standby meter data at 220kV side of Boisar ICT-4.

g. 400kV Bhadravati line-1 at Chandrapur

The energy meter (NP-2412-A) of 400kV Bhadravati line-1 at Chandrapur was under-

recording for the period 21.05.18 to 27.05.18. Therefore, Chandrapur end data was replaced

with the standby meter data at Bhadrawati end.

h. 220kV Korba line-3 at Budhipadar

The energy meter (NP-5944-A) of 400kV Korba line-3 at Budhipadar was under-recording

for the period 28.05.18 to 05.06.18. Therefore, Budhipadar end data was replaced with the

standby meter data at Korba end.

i. Other Stations with discrepancy of less than one week

The other Stations where meter related discrepancies were observed for a week/ less than 1

week are tabulated below for kind information of members:

S.No SEM ID Date Location Feeder/ICT Remarks

1 NP-5592-A 26.03.18 to

01.04.18 VSTPS-IV

400kV side of Vidhyachal (PS) ckt-III

Zero recording by both main & check meter.

2 GJ-2971-A 26.03.18 to

01.04.18 Veloda 400kV Zerda(kansari) line-1

Under recording (Action : Veloda)

3

NP-8918-A

02.04.18 Tamnar(PS)

400kV Trn Energy Line 2

Under recording (Action : Tamnar(PG)

S.No SEM ID Date Location Feeder/ICT Remarks

4 NP-5439-A

02.04.18

Nicole-2(Torrent)

400kV Dehgam Line

Wrong CT Polarity was Corrected

5 NP-5432-A 02.04.18

Nicole-2(Torrent)

400kV Pirana Line

Wrong CT Polarity was Corrected

6 NP-2115-A

04.04.18

Vindhyachal(PS)

400kV Line-1 to HVDC

Under recording (Action :Vindhyachal)

7 NP-5748-A 04.04.18 Gwalior

400kV Side Of ICT-1

Under recording (Action:Gwalior)

8 NP-5748-A 05.04.18 Gwalior

400kV Side Of ICT-1

Under recording at HV Side.Due to incorrect data of LV Side of ICT(due to mater testing), data replaced with ICT-2 data)

9 NP-6366-A 06.04.18 Gwalior 765KV Agra Line-2 Meter Testing At Gwalior.

10 NP-5755-A 10.04.18 Gwalior

765KV Jaipur(Phagi_NR) line 1

Under recording due to meter testing at Gwalior.

11 NP-5750-A

10.04.18

Gwalior

765KV Jaipur(Phagi_NR) Line-2

Under recording due to meter tesing.

12 NP-8918-A 09.04.18 to

10.04.18 Tamnar(PS) 400kV TRN Energy line-2

Faulty meter at Tamnar PS(PG) relaced on 10.04.18

13 NP-6420-A 19.04.18 Pirana(PG) 400kV Side of ICT-1

Meter testing at Pirana end. 220KV Side of ICT-1 under recording for past couple of months. Therefore, SEM data of 400kV side of ICT-2 used.

S.No SEM ID Date Location Feeder/ICT Remarks

14 NP-2631-A 27.04.18 Bilaspur 400kV ACBIL Line-1 Under-recording Action: Bilaspur (PG)

15 NP-6419-A 28.04.18 Pirana(PG) 400kV Side of ICT-2 Meter Testing at Pirana

16 NP-6312-A 28.04.18 Bhatapara(PG) 400kV Side Of ICT-1 Under recording Action: Bhatapara(PG)

17 NP-5720-A 28.04.18 Bhatapara(PG) 400kV Side Of ICT-2 Under recording Action: Bhatapara(PG)

18 NP-5748-A 01.05.18 Gwalior(PG) 400kV Side Of ICT-1 Under recording Action: Gwalior(PG)

19 NP-6432-A 01.05.18 Pirana(PG) 400kV Pirana(TPL) Line-2

Meter Calibration was done

20 NP-6431-A 02.05.18 Pirana(PG) 400kV Pirana(TPL) Line-1

Meter Calibration was done

21 NP-6383-A 07.05.18 Vadavi(GETCO) 400kV Veloda Line Under recording Action:GETCO

22 NP-6346-A 08.05.18 Vadavi(GETCO) 400kV Zerda(Kansari) Line-2 Under recording Action:GETCO

23 NP-6424-A 09.05.18 Vadavi(GETCO) 400kV Bhachau Line-1 Under recording Action:GETCO

24 NP-6425-A 10.05.18 Vadavi(GETCO) 400kV Bhachau Line-2 Under recording Action:GETCO

25 NP-6381-A 11.05.18 Kansari(Getco) 400kV Kankroli line-1 Under recording Action:GETCO

26 NP-6382-A 12.05.18 Kansari(Getco) 400kV Kankroli line-1 Under recording Action:GETCO

27 NP-6226-A 14.05.18 Zerda(Kansari) 400kV Vadavi Line-1 Under recording Action:GETCO

28 NP-6348-A 15.05.18 Zerda(Kansari) 400kV Vadavi Line-2 Under recording

S.No SEM ID Date Location Feeder/ICT Remarks

Action:GETCO

29 NP-5526-A 26.05.18 Kawas 22KV Ichapur Line-1 Meter Testing At Kawas

30 NP-2147-A 23.05.18 Vindhyachal STPS

400kV Side of ICT-3 Under recording

31 NP-5620-A 23.05.18 Betul GIS 400kV Side of ICT-1 Zero recording Action: Betul (PG)

32 NP-5539-A 23.05.18 Betul GIS 400kV Side of ICT-2 Zero recording Action: Betul (PG)

33 NP-2732-A 23.05.18 Vav 220KV Kawas Line-1 Meter Testing at Vav end

34 NP-6791-A 22.05.18 Auraiya 220KV Mehgaon Line Under Recording

35 NP-2604-A 22.05.18 Ichapur 220KV Kawas Line-2 Meter testing at Ichapur end

36 NP-2156-A 21.05.18 Balaghat 132KV Dongargarh Line Under Recording Action: Balaghat(MPPTCL)

37 NP-5511-A 21.05.18 Boisar 400kV Side Of ICT-4 Wrong date in meter rectified on 21.05.18

38 NP-4190-A

31.05.18

Magarwada

220KV Vapi(PG) Line-1

Under recording Action:DDED

39 GJ-1514-A

07.06.18 To 08.06.18

Kosamba(Getco) 400kV Gandhar Line

Under recording Action:GETCO

40 NP-2156-A

08.06.18 To 09.06.18

Balaghat/Bhanegaon

132KV Dongargarh Line

Under recording Action:MPPTCL

41 NP-6427-A 16.06.18 Dehgam 400kV Nicole Line-2 Meter Testing at Dehgam

42 NP-8626-A 12.06.18 Magarwada 400kV Side of ICT-1 Mater Testing at Magarwada

43 NP-8604-A 12.06.18 Magarwada 400kV Side of ICT-2 Mater Testing at

S.No SEM ID Date Location Feeder/ICT Remarks

Magarwada

44 NP-5765-A 15.06.18 Dehgam 400kV Nagda Line-2 Meter Testing at Dehgam

45 NP-5764-A 15.06.18 Dehgam 400kV Nagda Line-1 Meter Testing at Dehgam

46 NP-6380-A 17.06.18 Dehgam 400kV Sami Line-1 Meter Testing at Dehgam

47 NP-6379-A 17.06.18 Dehgam 400kV Sami Line-2 Meter Testing at Dehgam

48 NP-6426-A 16.06.18 Dehgam 400kV Pirana (PG) Line-1 Meter Testing at Dehgam

49 NP-6432-A

15.06.18 Pirana(PG) 400kV Pirana(TPL) Line-2

Under – Recording Action: Pirana

50 NP-6221-A 23.06.18 Varsana(Getco) 400kV Bhachau Line-2 Meter Testing At Varsana

51 NP-2462-A 23.06.18 Taps 220KV Borivali Line Meter Testing At TAPS

52 NP-6220-A 22.06.18 Varsana(Getco) 400kV Bhachau Line-1 Meter Testing At Varsana

53 NP-2540-A 22.06.18 Taps 220KV Boisar Line Meter Testing At TAPS

54 NP-2777-A 21.06.18 Mansar 400kV Chornia Line Meter Testing At Mansar

55 NP-2609-A 21.06.18 Mansar 400kV Bhachau Line Meter Testing At Mansar

56 NP-2416-A 20.06.18 Boisar 400kV side of ICT-1 Meter Testing At Boisar(PG)

57 NP-2414-A 20.06.18 Boisar 400kV Side of ICT-3 Meter Testing At Boisar(PG)

58 NP-2785-A 20.06.18 Jetpur 400kV CGPL LINE-1 Meter Testing At Jetpur

59 NP-2202-A 19.06.18 Boisar 400kV Side of ICT-2

Due to Meter Testing(Both HV&LV Side)at Boisar, Wrong meter data, since, ICT was out of service, therefore wrong reading replaced with zero

60 NP-2784-A 19.06.18 Jetpur 400kV CGPL Line-2 Meter Testing At Jetpur

S.No SEM ID Date Location Feeder/ICT Remarks

61 NP-2747-A 19.06.18 Kasor 400kV Rajgarh(PG) Line-2 Meter Testing At Kasor

62 NP-6428-A 18.06.18 Limbdi 400kV Mansar Line Meter Testing At Limbdi(Chornia)

63 NP-2430-A 18.06.18 Kasor 400kV Rajgarh(PG) Line-1 Meter Testing At Kasor

64 NP-6435-A 18.06.18 Limbdi 400kV Bhachau Line-1 Meter Testing At Limbdi(Chornia)

65 NP-2558-A 30.06.18 Taps 220KV Bhilad Line Meter Tesing at Taps

66 NP-6444-A 30.06.18 Vapi 220KV Vapi(GEB) Line Meter Tesing at Vapi(PG)

67 NP-6433-A 28.06.18 Bhachau 400kV Side Of ICT-1 Meter Tesing at Bhachau

68 NP-6442-A 27.06.18 Bhachau 400kV Side Of ICT-2 Meter Tesing at Bhachau

69 NP-6439-A 27.06.18 Vapi(PG) 220KV Bhilad Line-1 Meter Tesing at Vapi(PG)

69 NP-6443-A 27.06.18 Vapi(PG) 220KV Bhilad Line-3 Meter Tesing at Vapi(PG)

70 NP-2438-A 26.06.18 Taps 220KV Vapi Line Meter Tesing at Taps

Committee may like to note

18.i. SEM Data discrepancy at Bhadrawti station

GMR Warora vide their email dated 17.07.18 informed that there was discrepancy in SEM

data (SEM Sr no-2648A) at PGCIL Bhadrawati end which has resulted into variations in

their weekly DSM settlement. Further they informed that from 46th time block of 26thApr’18,

there was sudden variation in the readings which continued till 46th block of 25thMay’18.

Total Line Loss has increased from 0.3% to 1.6% from 26th Apr’18 leading to loss in

injection quantum in DSM calculations.

GMR Warora have intimated to WRLDC vide mail dated 25th May’18. Followed by letter

dated 1st June’18 & reply letter on 29th June’18 (copy enclosed at Annex 18.i).

GMR Warora informed that they have dedicated 400KV D/C line of 33Kms length

connected to bhadrawati & considering generally adopted practice is penalizing us when

actual line losses are coming in the range of 0.16 to 0.30%. Since check meter are not

installed at PGCIL end, as per adopted procedure injection readings were computed based on

the notional loss of 2% by WRLDC.

GMR Warora have request CCM to kindly consider this as special case and evaluate the

readings as per actual line losses and accordingly modify the DSM bills of the said period.

Committee may like to discuss

Annex-18.a

LIST OF SEMS WHERE TIME DRIFT NEEDS TO BE CHECKED/CORRECTED

Sr.No. Meter Id Description Time drift

correction to be

done by

1 NP-5447-A 400kV Side Of ICT-2 At Vadodara(PG) POWERGRID

2 NP-5449-A 220KV Side Of ICT-2 At Vadodara(PG) POWERGRID

3 NP-2726-A 765KV ICT-2 At BHOPAL(BDTCL) BDTCL

4 NP-2719-A 400kV Bhopal(MP) Line-2 At BHOPAL(BDTCL) BDTCL

5 NP-2742-A 400kV ICT-1 At BHOPAL(BDTCL) BDTCL

6 NP-2741-A 400kV Bhopal(MP) Line-1 At BHOPAL(BDTCL) BDTCL

7 NP-2727-A 765KV Indore(PGCILl) Line-1 At BHOPAL(BDTCL) BDTCL

8 NP-2720-A 400kV ICT-2 At BHOPAL(BDTCL) BDTCL

9 NP-2713-A 765KV Jabalpur(PS)(PGcil) Line At BHOPAL(BDTCL) BDTCL

10 NP-8809-A 765KV Vadodara(PG) Line At Dhule(BDTCL) BDTCL

11 NP-8791-A 400kV DHULE (MSETCL) Line-2 At DHULE(BDTCL) BDTCL

12 NP-8798-A 400kV Side Of ICT-2 At Dhule (BDTCL) BDTCL

13 NP-8790-A 765kV Side Of ICT-2 At Dhule (BDTCL) BDTCL

14 NP-8800-A 765kV Aurangabad Line At Dhule (BDTCL) BDTCL

15 NP-8818-A 765kV Side Of ICT-1 At Dhule (BDTCL) BDTCL

16 NP-8817-A 400kV DHULE (MSETCL) Line-1 At DHULE(BDTCL) BDTCL

17 NP-8799-A 400kV Side Of ICT-1 At Dhule (BDTCL) BDTCL

18 NP-8754-A 400kV Kotra(PG) Line-1 At SKS SKS

19 NP-8755-A 400kV Kotra(PG) Line-1 At SKS SKS

20 NP-8756-A 400kV Kotra(PG) Line-2 At SKS SKS

21 NP-8757-A 400kV Kotra(PG) Line-2 At SKS SKS

22 NP-8726-A 400kV Side GT-1 At SKS POWER SKS

23 NP-8733-A 400kV Side GT-2 At SKS POWER SKS

24 NP-8759-A 400kV SKS Line-2 At Kotra(PG) POWERGRID

25 NP-5719-A 400kV Korba Line At Bhatapara(PG) POWERGRID

26 NP-5718-A 400kV Bhilai Line At Bhatapara(PG) POWERGRID

27 NP-6306-A 220kV Side Of ICT-2 At Bhatapara(PG) POWERGRID

28 NP-6312-A 400kV Side Of ICT-1 At Bhatapara(PG) POWERGRID

29 NP-5720-A 400kV Side Of ICT-2 At Bhatapara(PG) POWERGRID

30 NP-5763-A 400kV Nicol Line At Pirana(PG) POWERGRID

31 NP-6231-A 765KV Wardha(PG) Line-2 At Seoni(PG) POWERGRID

32 NP-6233-A 765kV Side Of 765/400kV ICT-3 At Seoni(PG) POWERGRID

33 NP-6232-A 765kV Wardha Line-1 At Seoni(PG) POWERGRID

34 NP-5742-A 400kV Khandwa Line-1 At Seoni(PG) POWERGRID

35 NP-6234-A 765kV Side Of 765/400 kV ICT-2 At Seoni(PG) POWERGRID

36 NP-5739-A 400kV Side Of 765/400 kV ICT-1 At Seoni(PG) POWERGRID

37 NP-5738-A 220kV Side Of 400/220 kV ICT-2 At Seoni(PG) POWERGRID

38 NP-5740-A 400kV Khandwa Line-2 At Seoni(PG) POWERGRID

39 NP-6230-A 765kV Bina(PG) Line At Seoni(PG) POWERGRID

40 NP-5745-A 400kV Satpura Line At Seoni(PG) POWERGRID

41 NP-5741-A 400kV Side Of 400/220 kV ICT-1 At Seoni(PG) POWERGRID

42 NP-5737-A 765kV Side Of 765/400kV ICT-1 At Seoni(PG) POWERGRID

43 NP-5743-A 400kV Side Of 400/220kV ICT-2 At Seoni(PG) POWERGRID

44 NP-5736-A 220kV Side Of 400/220kV ICT-1 At Seoni(PG) POWERGRID

45 NP-6229-A 400kV Side Of 765/400kV ICT-3 At Seoni(PG) POWERGRID

46 NP-5744-A 400kV Side Of 765/400kV ICT-2 At Seoni(PG) POWERGRID

47 NP-5746-A 400kV Bhiali Line At Seoni(PG) POWERGRID

48 NP-2878-A 765kV Side Of ICT-2 At Kotra(PS) POWERGRID

49 NP-2871-A 765kV Side Of ICT-4 At Kotra(PS) POWERGRID

50 NP-9189-A 400kV KWPCL Line-I At Kotra(PS) POWERGRID

51 NP-2879-A 765KV Tamnar(PS) Line-1 At Kotra(PS) POWERGRID

52 NP-2869-A 400kV Side Of ICT-3 At Kotra(PS) POWERGRID

53 NP-2852-A 400kV Raigarh(PG) Line-1 At Kotra(PS) POWERGRID

54 NP-9190-A 400kV KWPCL Line-II At Kotra(PS) POWERGRID

55 NP-2870-A 765KV Durg(Raipur-PS) Line-2 At Kotra(PS) POWERGRID

56 NP-2851-A 400kV Raigarh(PG) Line-2 At Kotra(PS) POWERGRID

57 NP-2895-A 765kV Side Of ICT-3 At Kotra(PS) POWERGRID

58 NP-8906-A 400kV Rkm Power Line-1 At Kotra POWERGRID

59 NP-2877-A 400kV Side Of ICT-2 At Kotra(PS) POWERGRID

60 NP-8758-A 400kV SKS Line-1 At Kotra(PG) POWERGRID

61 NP-8908-A 400kV Rkm Power Line-2 At Kotra POWERGRID

62 NP-2855-A 400kV Side Of ICT-1 At Kotra(PS) POWERGRID

63 NP-2893-A 400kV Korba-1 Line At Bhilai CSPTCL

64 NP-2133-A 220kV Budhipadar Line-III At Korba(E) CSPTCL

65 NP-2122-A 20kV Budhipadar Line-II At Korba(E) CSPTCL

66 NP-4220-A 400kV Bina(PG) Line-1 At Bina(MP) MPPTCL

67 NP-2715-A 400kV BINA(PG) Line-3 At Bina(MP) MPPTCL

68 NP-2714-A 400kV BINA(PG) Line-4 At Bina(MP) MPPTCL

69 NP-2345-A 220kV Navsari Line-1 At Nasik MSETCL

70 NP-2199-A 220kV Navsari Line-2 At Nasik MSETCL

71 NP-8808-A 400kV Side Of ST-01 At RKM POWER RKM

72 NP-8805-A 400kV Side Of GT-01 At RKM Power RKM

73 NP-8806-A 400kV Kotra Line-1 At RKM Power RKM

74 NP-8807-A 400kV Kotra Line-2 At RKM Power RKM

75 NP-8794-A 400kV Kotra Line-1 At RKM Power RKM

76 NP-2695-A 765KV Satna Line-2 at Sasan SASAN

77 NP-2687-A 400kV Side Of St-1 At Sasan SASAN

78 NP-2662-A 765KV Side of GT-5 at Sasan SASAN

79 NP-2667-A 765KV Satna Line-1 at Sasan SASAN

80 NP-2663-A 765kV Side Of ICT-1 At Sasan SASAN

81 NP-2665-A 400kV Side of ICT-2 AT Sasan SASAN

82 NP-2668-A 765KV Satna Line-1 at Sasan SASAN

83 NP-2614-A 400kV Side of GT-2 at Mahan(Essar) ESSAR MAHAN

84 NP-2611-A 400kV Side of GT-1 at Mahan(Essar) ESSAR MAHAN

85 NP-2612-A 400kV Vindhyachal line-1 at Mahan(Essar) ESSAR MAHAN

86 NP-2350-A 66kV Dhokadwa at Diu D&D

87 NP-2399-A 66kV Una line at Diu D&D

88 NP-8628-A 33KV BARC LINE-4 at TAPS Zone-III NPCIL

89 NP-8629-A 33KV BARC LINE-6 at TAPS Zone-III NPCIL

90 NP-2436-A 220kV side of TT-2 at TAPS NPCIL

91 NP-2459-A 220kV side of GT-2 at TAPS NPCIL

92 NP-2449-A 220kV Boisar line at TAPS NPCIL

93 NP-2241-A 220kV TAPS 3&4 line at TAPS 1&2 NPCIL

94 NP-2440-A 220kV side of TT-1 at TAPS NPCIL

95 NP-2150-A 220kV side of GT-2 at TAPS NPCIL

96 NP-2423-A 220kV Borivali line at TAPS NPCIL

97 NP-2540-A 220kV Boisar line at TAPS NPCIL

98 NP-2558-A 220kV Bhilad line at TAPS NPCIL

99 NP-2889-A 33kV TAPS 3&4 line-2 at TAPS 1&2 NPCIL

100 NP-2467-A Zone 1 to Zone 3 at TAPS NPCIL

101 NP-2439-A 220kV side of GT-1 at TAPS NPCIL

102 NP-2239-A 33kV TAPS 3&4 line at TAPS 1&2 NPCIL

103 NP-2161-A 132kV side of ICT-2 VSTPS NTPC

104 NP-2387-A 220kV side of SUT-1 at TAPS NPCIL

105 NP-2115-A 400kV line-1 to HVDC at Vindhyachal STPS NTPC

106 NP-8929-A 400KV Rihand line-1 at Vindhyachal (PS) POWERGRID

107 NP-8948-A 400KV Rihand line-2 at Vindhyachal (PS) POWERGRID

108 NP-2684-A 400KV VINDHYACHAL(PS)LINE-2 at VSTPS-IV NTPC

109 LT-0033-A 400kV side of LANCO(Pathadi) line-2 at Bilaspur POWERGRID

110 NP-2225-A 500 220kV Boisar line at TAPS3&4 TAPS3&4

111 NP-2551-A 400kV Dhule line-2 at SSP(Main) SSP

112 NP-2549-A 400kV Rajgarh line-2 at SSP(Main) SSP

113 NP-2526-A 400kV Dhule line-1 at SSP(Main) SSP

114 NP-2155-A 220kV Amarkantak line-II at Kotmikala Maharashtra

115 NP-6774-A 220kV Budhipadar line-I at Raigarh(CSEB) Chhattisgarh

116 NP-6758-A 400kV Akola line-2 at WARDHA POWERGRID

117 NP-5590-A 220kV Kalmeshwar line at Pandurna Madhya Pradesh

118 NP-2117-A 220kV Amona line at Tillari Maharashtra

119 NP-5713-A 400kV Sundergarh(Jharsuguda) line at Raigarh(PG) POWERGRID

120 NP-6288-A 400kV Sundargarh(Jharsuguda) line at Raigarh(PG) POWERGRID

121 NP-5604-A 400KV BINA(MP) line-3 at Bina(PG) POWERGRID

122 NP-5759-A 400KV BINA(MP) line-4 at Bina(PG) POWERGRID

123 NP-2624-A 400KV INDORE(PG) LINE-1 AT INDORE(MP) Madhya Pradesh

124 NP-6304-A 400KV PUNE(GIS)(PG) LINE-1 AT PUNE(PG) POWERGRID

125 NP-2162-A 400KV JABALPUR(PS) LINE-I at JHABUA POWER Jhabua Power

126 NP-5755-A 765KV Jaipur(Phagi_NR) line 1 at Gwalior(PG) POWERGRID

127 NP-5750-A 765KV Jaipur(Phagi_NR) line 2 at Gwalior(PG) POWERGRID

128 NP-2451-A 400kV Kolhapur(GIS) Line-1 at Kolhapur(Telagade) POWERGRID

129 NP-2400-A 400kV Kolhapur(GIS) Line-2 at Kolhapur(Telagade) POWERGRID

130 NP-8824-A 400kV Aurangabad(PG) line-2 at Aurangabad(MSEB) Maharashtra

131 NP-8816-A 400KV DHULE (BDTCL) line-1 at DHULE(MSETCL) Maharashtra

132 NP-9656-A 400KV DHULE (BDTCL) line-2 at DHULE(MSETCL) Maharashtra

133 NP-4229-A 400kV Shujalpur line-1 at Nagda Madhya Pradesh

134 NP-2282-A 400kV Shujalpur line-2 at Nagda Madhya Pradesh

135 NP-2341-A 220kV Haldarwa line-1 at Gandhar NTPC

136 NP-2347-A 220kV Haldarwa line-1 at KAPS NPCIL

137 NP-5450-A 220kV Haldarwa line-1 at Kawas NTPC

138 NP-5765-A 400kV Nagda line-2 at Dehgam POWERGRID

139 NP-6382-A 400kV BHINMAL line at Zerda GETCO

140 GJ-0850-A 400KV PIRANA(PG) LINE-1 AT PIRANA(TPL) GETCO

141 GJ-0851-A 400KV PIRANA(PG) LINE-2 AT PIRANA(TPL) GETCO

142 NP-2778-A 400KV Vadodara(PG) line-2 at ASOJ GETCO

143 NP-2779-A 400KVVadodara(PG) line-1 at ASOJ GETCO

144 NP-2430-A 400KV Rajgarh(PG) line-1 at Kasor(Reliance line) GETCO

145 GJ-1298-A 400KV Navsari(PG) line at Ukai(GETCO) GETCO

146 NP-4221-A 400kV Bina(PG) line-2 at Bina(MP) Madhya Pradesh

147 NP-2213-A 400kV Rajgarh line-1 at Nagda Madhya Pradesh

148 NP-2211-A 400kV Rajgarh line-2 at Nagda Madhya Pradesh

149 NP-4227-A 400kV Itarsi line at Satpura Madhya Pradesh

150 NP-8782-A 400KV Balco line-2 at Dharamjaygarh(Dedicated line) POWERGRID

151 NP-8783-A 400KV Balco line-1 at Dharamjaygarh(Dedicated line) POWERGRID

152 NP-8853-A 400KV Solapur STPS(PG) line-2 at Solapur(NTPC) NTPC

153 NP-8871-A 400KV Solapur STPS(PG) line-3 at Solapur(NTPC) NTPC

154 NP-8867-A 400KV Solapur STPS(PG) line-4 at Solapur(NTPC) NTPC

155 NP-6226-A 400KV Ranchhodpura(Vadavi) Line-1 at Zerda

(Kansari) GETCO

156 NP-6226-A 400KV Ranchhodpura(Vadavi) Line-1 at Zerda

(Kansari) GETCO

157 NP-6383-A 400KV Zerda (Kansari) line-1 at Ranchhodpura(Vadavi) GETCO 158 NP-8936-A 400KV Vindhyachal(NTPC) line 2 at Vindhyachal(PS) POWERGRID

159 NP-6308-A 400kV side of Raipur line at Pathadi(LANCO) LANCO

160 NP-2218-A 220kV TAPS 3&4 line at Boisar(PG) POWERGRID

161 NP-2294-A 400kV SSP line-2 at Dhule Maharashtra

162 NP-6341-A 400kV SSP line-2 at Rajgarh(PG) POWERGRID

163 NP-2464-A 400kV SSP line-1 at Dhule Maharashtra

164 NP-4218-A 220kV Kotmikala line-II at Amarkantak Madhya Pradesh

165 NP-6268-A 400kV Wardha line-2 at Akola Maharashtra

166 NP-2313-A 220kV Pandurna line at Kalmeshwar Maharashtra

167 NP-2221-A 220kV Tillari line at Amona Goa

168 NP-2976-A 400KV INDORE(MP) LINE-1 AT INDORE(PG) POWERGRID

169 NP-8849-A 400KV Pune(PG) line-1 at Pune(GIS)(LILO of Pune- POWERGRID

Parli-1)

170 NP-2960-A 400KV JHABUA POWER LINE-I at JABALPUR(PS) POWERGRID

171 NP-8842-A 400KV Kolhapur(MSEB) line-2 at Kolhapur(GIS) POWERGRID

172 NP-8844-A 400KV Kolhapur(MSEB) line-1 at Kolhapur(GIS) POWERGRID

173 NP-8747-A 400KV Aurangabad(MSEB) line-2 at Aurangabad(PG) POWERGRID

174 NP-6369-A 400KV Nagda line-1 at Shujalpur(PG) POWERGRID

175 NP-6355-A 400KV Nagda line-2 at Shujalpur(PG) POWERGRID

176 NP-4167-A 220kV Gandhar line-1 at Haldarwa GETCO

177 NP-4160-A 220kV KAPS-1 at Haldarwa GETCO

178 NP-4163-A 220kV Kawas-1 at Haldarwa GETCO

179 NP-2238-A 400kV Dehgam line-2 at Nagda(MP) Madhya Pradesh

180 NP-6431-A 400KV PIRANA(TPL) LINE-1 AT PIRANA(PG) POWERGRID

181 NP-6432-A 400KV PIRANA(TPL) LINE-2 AT PIRANA(PG) POWERGRID

182 NP-2985-A 400KV Asoj line-2 at Vadodara(PG) POWERGRID

183 NP-2986-A 400KV Asoj line-1 at Vadodara(PG) POWERGRID

184 NP-6357-A 400KV Kasor line-1 at Rajgarh(PG)(Reliance line) POWERGRID

185 NP-6349-A 400KV Ukai line at Navsari(PG) GIS POWERGRID

186 NP-5757-A 400kV Bina(MPPTCL) line-2 at Bina(PG) POWERGRID

187 NP-6336-A 400kV Nagda line-1 at Rajgarh(PG) POWERGRID

188 NP-6344-A 400kV Nagda line-2 at Rajgarh(PG) POWERGRID

189 NP-2441-A 400kV Satpura at Itarsi POWERGRID

190 NP-2799-A 400kV Korba line-1 at BALCO BALCO

191 NP-2800-A 400kV Birshinghpur line at BALCO BALCO

192 NP-8796-A 400KV Solapur STPS(NTPC) line-2 at Solapur(PG) POWERGRID

193 NP-8868-A 400KV Solapur STPS(NTPC) line-3 at Solapur(PG) POWERGRID

194 NP-8870-A 400KV Solapur STPS(NTPC) line-4 at Solapur(PG) POWERGRID

195 GJ-2971-A 400KV ZERDA(KANSARI) Line-1 at Veloda Gujarat

196 GJ-2971-A 400KV ZERDA(KANSARI) Line-1 at Veloda Gujarat

197 GJ-2968-A 400KV Ranchhodpura(Vadavi) Line-1 at Veloda Gujarat

Annex-18.c

LIST OF ISGS EVACUATING THROUGH DEDICATED LINES WHERE CHECK

METERS NEED TO BE RELOCATED

S.No

Name of Generating

Station

Evacuation Path

Interface point Remote end Recommendation

Main Standby Check

1 LANCO 400kV Lanco-Bilaspur line-1

Bilaspur Lanco Lanco Check meter to be shifted from Lanco to Bilaspur

2 LANCO 400kV Lanco-Bilaspur line-1

Bilaspur Lanco Lanco Check meter to be shifted from Lanco to Bilaspur

3 ACBIL 400kV ACBIL-Bilaspur line

Bilaspur ACBIL ACBIL Check meter to be shifted from ACBIL to Bilaspur

4 MCCPL 400kV MCCPL-Bilaspur line

Bilaspur MCCPL MCCPL Check meter to be shifted from MCCPL to Bilaspur

5 BALCO 400kV BALCO-Dharamjaygarh line-1

Dharamjaygarh BALCO BALCO Check meter to be shifted from Balco to Dharamjaygarh

6 BALCO 400kV BALCO-Dharamjaygarh line-2

Dharamjaygarh BALCO BALCO Check meter to be shifted from Balco to Dharamjaygarh

7 Jhabua Power

400kV Jhabua-Jabalpur(PS) line-1

Jabalpur (PS) Jhabua Jhabua Check meter to be shifted from Jhabua to Jabalpur(PS)

8 Jhabua Power

400kV Jhabua-Jabalpur(PS) line-1

Jabalpur (PS) Jhabua Jhabua Check meter to be shifted from Jhabua to Jabalpur(PS)

S.No

Name of Generating

Evacuation Path

Interface point Remote end Recommendation

9 DB Power 400kV DB Power-Kotra(PS) line-1

Kotra (PS) DB Power DB Power Check meter to be shifted from DB Power to Kotra(PS)

10 DB Power 400kV DB Power-Kotra(PS) line-2

Kotra (PS) DB Power DB Power Check meter to be shifted from DB Power to Kotra(PS)

11 KWPCL 400kV KWPCL-Kotra(PS) line-1

Kotra (PS) KWPCL KWPCL Check meter to be shifted from KWPCL to Kotra (PS)

12 KWPCL 400kV KWPCL-Kotra(PS) line-2

Kotra (PS) KWPCL KWPCL Check meter to be shifted from KWPCL to Kotra (PS)

13 RKM 400kV RKM-Kotra(PS) line-1

Kotra(PS) RKM RKM Check meter to be shifted from RKM to Kotra(PS)

14 RKM 400kV RKM-Kotra(PS) line-2

Kotra(PS) RKM RKM Check meter to be shifted from RKM to Kotra(PS)

15 SKS 400kV SKS-Kotra(PS) line-1

Kotra(PS) SKS SKS Check meter to be shifted from SKS to Kotra(PS)

16 SKS 400kV SKS-Kotra(PS) line-2

Kotra(PS) SKS SKS Check meter to be shifted from SKS to Kotra(PS)

17 Jaypee Nigrie

400kV Jaypee Nigrie-Satna line-1

Satna Jaypee Nigrie

Jaypee Nigrie

Check meter to be shifted from Jaypee Nigrie to Satna

18 Jaypee Nigrie

400kV Jaypee Nigrie-Satna line-2

Satna Jaypee Nigrie

Jaypee Nigrie

Check meter to be shifted from Jaypee Nigrie to Satna

19 DGEN 400kV DGEN-Navsari line-1

Navsari DGEN DGEN Check meter to be shifted from Dgen to Navsari

20 DGEN 400kV DGEN-Navsari line-2

Navsari DGEN DGEN Check meter to be shifted from Dgen to Navsari

21 GMR Chhattisgarh

400kV GMR Chhattisgarh-Durg(PS) line-1

Durg(PS) GMR Chhattisgarh

GMR Chhattisgarh

Check meter to be shifted from GMR Chhattisgarh to Durg (PS)

S.No

Name of Generating

Evacuation Path

Interface point Remote end Recommendation

22 GMR Chhattisgarh

400kV GMR Chhattisgarh-Durg(PS) line-1

Durg(PS) GMR Chhattisgarh

GMR Chhattisgarh

Check meter to be shifted from GMR Chhattisgarh to Durg (PS)

Acer
Typewritten text
ANNEX 18.i

28/05/2018 Gmail - SEM data discrepancy in SEM S.No.2648A at Bhadrawati Station

https://mail.google.com/mail/u/0/?ui=2&ik=9a30166b8b&jsver=-dxVNc9Y02g.en.&cbl=gmail_fe_180516.06_p8&view=pt&msg=1639647247dd73d6&q=bhadrawa

WRLDC SEM <[email protected]>

SEM data discrepancy in SEM S.No.2648A at Bhadrawati Station

Ranjith Kumar Panigrahi {रंजीत कुमार पािण�ही} <[email protected]> Fri, May 25, 2018 at 1:15 PMTo: "[email protected]" <[email protected]>, "[email protected]" <[email protected]>Cc: Raj Kishor Dash {राज िकशोर दाश} <[email protected]>, Naval Kishor Meena {Naval Kishor Meena}<[email protected]>

Dear sir,It is to inform you that the SEM data discrepancy in energy Meter S.No.2648A (Bhadrawati-EMCO ckt # 1) isattended.While attending the above issue, it is observed that the CT currents R-Ph & Y-Ph are not reporting the SEM meterand the same is corrected in the TTB connections.At present the CT,PT values are reporting healthy to the SEM meter. Regards,Ranjith K panigrahi,Jr Engineer,8275039152

दावा�ाग : यह ईमेल पावरि�ड के दावा�ाग िनयम व शत� �ारा शािसत है िजसे http://apps.powergridindia.com/Disclaimer.htm पर देखा जा सकता है। Disclaimer: This e-mail is governed by the Disclaimer Terms & Conditions of POWERGRID which may be viewed at http://apps.powergridindia.com/Disclaimer.htm