ASME CSD-1Rules for boilers above400,000 btu input up to
12,500,000 btu input
9.5hp to 300hp Boilers
2
Open Book Test:ASME CSD-1 Is allowed tobe used.
ASME CSD-1-2009 Five Sections
General CG
TestingMaintenance
CMCombustion
CF
“CG” “CM” “CE” “CW” “CF”
TestingMaintenance
CM
Electrical CESteam
WatersideCW
CombustionCF
Burners 400,000 Btu input and under are exempt(10 Boiler hp, 3 gph oil, 115 kw electric)
All boilers must comply with CSD-1 sections CW & CE
Control compliance and operation based upon:400,000 to 2,500,000 Btu input
60 Boiler hp max.2,500,000 to 5,000,000 Btu input
120 Boiler hp max.5,000,000 to 12,500,000 Btu input
300 Boiler hp max.
ASME CSD-1 2009 “CF” Three DivisionsControls need to be provided and operate based upon the burner input rating
4
Burners 400,000 Btu input and under are exempt(10 Boiler hp, 3 gph oil, 115 kw electric)
All boilers must comply with CSD-1 sections CW & CE
Control compliance and operation based upon:400,000 to 2,500,000 Btu input
60 Boiler hp max.2,500,000 to 5,000,000 Btu input
120 Boiler hp max.5,000,000 to 12,500,000 Btu input
300 Boiler hp max.
Control DynamicsAction determined by burner size
• Purging• Safety Control Timing• Action On Flame Failure• Loss Of Combustion Air• Combustion Air Proving• Fuel Supervision
• Purging• Safety Control Timing• Action On Flame Failure• Loss Of Combustion Air• Combustion Air Proving• Fuel Supervision