CERTAINTEED CORPORATION INSULATION GROUP

42
SPECIMEN NO. 1 ( OPAQUE WALL DRAWINGS ) 3" ( TYP ) 3" ( TYP ) 1 CERTASPRAY ( THICKNESS 1" ) 2 CONCRETE MASONRY UNITS 3 STEEL STRUCTURE 4 SELF-ADHERING AIR BARRIER MEMBRANE W/ PRIMER 3 3 6" 8'-0" 3 3 4 2 3 4 1 4 3 3 3 4 2 2 4 CERTAINTEED CORPORATION INSULATION GROUP

Transcript of CERTAINTEED CORPORATION INSULATION GROUP

Page 1: CERTAINTEED CORPORATION INSULATION GROUP

SPECIMEN NO. 1 ( OPAQUE WALL DRAWINGS )

3" ( TYP )

3" ( TYP )

1 CERTASPRAY ( THICKNESS 1" ) 2 CONCRETE MASONRY UNITS 3 STEEL STRUCTURE 4 SELF-ADHERING AIR BARRIER MEMBRANE W/ PRIMER

3

36" 8'-0"

3

3 4 2 3 4 1 4 3

3 3

4

2 2

4

CERTAINTEED CORPORATION INSULATION GROUP

Page 2: CERTAINTEED CORPORATION INSULATION GROUP

SPECIMEN NO. 1 ( OPAQUE WALL DRAWINGS )

COMPOSITION 1 CERTASPRAY ( THICKNESS 1" ) 2 CONCRETE MASONRY UNITS 3 STEEL STRUCTURE 4 SELF-ADHESIVE AIR BARRIER MEMBRANE W/ PRIMER 5 STRUCTURAL TIE 24" 0.C. ( TYPICAL )

4 2 1 4

3 5

3 4 2 1

1 2 4 3

WALL UPPER SECTION

WALL LOWER SECTION

PLAN VIEW OF WALL

CERTAINTEED CORPORATION INSULATION GROUP

Page 3: CERTAINTEED CORPORATION INSULATION GROUP

SPECIMEN NO. 2 ( WALL WITH PENETRATIONS )

1 BLOK-LOK BL-407 SURFACE MOUNTED BRICK VENEER ANCHOR ( OR EQUAL ) 2 DUR-O-WALL DUR-O-EYE HORIZONTAL JOINT REINFORCIING WITH INTEGRAL WIRE TIES ( OR EQUAL ) NOTE: NO TRANSITION MEMBRANE AT THE PERIMETER OF PROJECTED TIES OF WALL SAMPLE

6" 8'-0"

2'-0

"2'

-0"

4'-0

"

2'-0" 8"

1

2

CERTAINTEED CORPORATION INSULATION GROUP

Page 4: CERTAINTEED CORPORATION INSULATION GROUP

SPECIMEN NO. 2 ( WALL WITH PENETRATIONS )

COMPOSITION 1 CERTASPRAY ( THICKNESS 1" ) 2 CONCRETE MASONRY UNITS 3 STEEL STRUCTURE 4 SELF-ADHESIVE MEMBRANE W/ PRIMER 5 SIMULATED WINDOW ASSEMBLY 6 POLYMER BASED CAULKING STRIP

3 4 2 1

1 2 4 6 7

7 CONCRETE FOOTING 8" X 10" 8 FOAM SEAL GASKET 9 CAULKING 10 URETHANE FOAM SEALANT 11 MASONRY VENEER ANCHOR

WALL UPPER SECTION

WALL LOWER SECTION

WALL SECTION

1 2 11

OPENING LOWER SECTION

5 10 4 2 1

8 9

CERTAINTEED CORPORATION INSULATION GROUP

Page 5: CERTAINTEED CORPORATION INSULATION GROUP

SPECIMEN NO. 3 ( WALL WITH PENETRATIONS )

1 CERTASPRAY ( THICKNESS 1" ) 2 CONCRETE MASONRY UNITS 3 STEEL STRUCTURE 4 SELF-ADHESIVE MEMBRANE W/ PRIMER 5 SIMULATED WINDOW ASSEMBLY

6" 8'-0"

2'-0

"2'

-0"

4'-0

"

2'-0" 8"

6 STRUCTURAL TIE 24" O.C. ( TYP ) 7 CONCRETE FOOTING 8" X 10" 8 GALVANIZED STEEL DUCT 4" X 4" 9 PVC PIPE 2" DIAM 10 ELECTRICAL STEEL CONDUIT 1-1/2" DIAM

3 4 2

7

2

4

3

4

8 9

4

3" TYP

10

4

5CERTAINTEED CORPORATION INSULATION GROUP

Page 6: CERTAINTEED CORPORATION INSULATION GROUP

SPECIMEN NO. 3 ( WALL WITH PENETRATIONS )

COMPOSITION 1 CERTASPRAY ( THICKNESS 1" ) 2 CONCRETE MASONRY UNITS 3 STEEL STRUCTURE 4 SELF-ADHESIVE MEMBRANE W/ PRIMER 5 SIMULATED WINDOW ASSEMBLY 6 POLYMER BASED CAULKING STRIP

3 4 2 1

1 2 4 6 7

7 CONCRETE FOOTING 8" X 10" 8 GALVANIZED STEEL DUCT 4" X 4" 9 STEEL PIPE 1-1/2" DIAM 10 FOAM SEAL GASKET 11 CAULKING 12 URETHANE FOAM SEALANT

WALL UPPER SECTION

WALL LOWER SECTION

WALL SECTION

1 2 4 8,9

OPENING LOWER SECTION

5 10 4 2 1

8 9

CERTAINTEED CORPORATION INSULATION GROUP

Page 7: CERTAINTEED CORPORATION INSULATION GROUP

SPECIMEN NO. 1 ( OPAQUE WALL DRAWINGS )

3" ( TYP )

3" ( TYP )

1 CERTASPRAY ( THICKNESS 1" ) 2 EXTERIOR GYPSUM BOARD 3 STEEL STRUCTURE 4 SELF-ADHESIVE AIR BARRIER MEMBRANE W/ PRIMER 5 20 GA. STEEL STUD

5 3

36" 8'-0"

3

3 4 5 2 3 4 1 4 3

3 3

4

2 2

4

CERTAINTEED CORPORATION INSULATION GROUP

Page 8: CERTAINTEED CORPORATION INSULATION GROUP

SPECIMEN NO. 1 ( OPAQUE WALL DRAWINGS )

COMPOSITION 1 CERTASPRAY ( THICKNESS 1" ) 2 EXTERIOR GYPSUM BOARD 3 STEEL STRUCTURE 4 SELF-ADHESIVE AIR BARRIER MEMBRANE W/ PRIMER 5 20 GA STEEL STUD

4 2 1 4

3 5

1 2 4 3

53 4 2 1

5

WALL UPPER SECTION

WALL LOWER SECTION

PLAN VIEW OF WALL

CERTAINTEED CORPORATION INSULATION GROUP

Page 9: CERTAINTEED CORPORATION INSULATION GROUP

SPECIMEN NO. 2 ( WALL WITH PENETRATIONS )

1 CERTASPRAY ( THICKNESS 1" ) 2 EXTERIOR GYPSUM BOARD 3 STEEL STRUCTURE 4 SELF-ADHESIVE MEMBRANE W/ PRIMER 5 SIMULATED WINDOW ASSEMBLY

6 7

36" 8'-0"

3 4 6 2 4 1 4 3

3

3

4 2'-0

"2'

-0"

4'-0

"

2'-0" 8"

4

4

4

10

4

8 9

4

11

7

3" TYP

3" TYP

6 20 GA. STEEL STUD 7 CONCRETE FOOTING 8" X 10" 8 GALVANIZED STEEL DUCT 4" X 4" 9 PVC PIPE 1-1/2" DIAM. 10 ELECTRICAL CONDUIT 1-1/2" DIAM. 11 GYPSUM BOARD PANEL JOINT

CERTAINTEED CORPORATION INSULATION GROUP

Page 10: CERTAINTEED CORPORATION INSULATION GROUP

SPECIMEN NO. 2 ( WALL WITH PENETRATIONS )

COMPOSITION 1 CERTASPRAY ( THICKNESS 1" ) 2 CONCRETE MASONRY UNITS 3 STEEL STRUCTURE 4 SELF-ADHESIVE MEMBRANE W/ PRIMER 5 SIMULATED WINDOW ASSEMBLY 6 POLYMER BASED CAULKING STRIP

3 4 2 1

1 2 4 6 7

7 CONCRETE FOOTING 8" X 10" 8 FOAM SEAL GASKET 9 CAULKING 10 URETHANE FOAM SEALANT 11 MASONRY VENEER ANCHOR

WALL UPPER SECTION

WALL LOWER SECTION

WALL SECTION

1 2 11

OPENING LOWER SECTION

5 10 4 2 1

8 9

CERTAINTEED CORPORATION INSULATION GROUP

Page 11: CERTAINTEED CORPORATION INSULATION GROUP

SPECIMEN NO. 3 ( WALL WITH PENETRATIONS )

1 BLOK-LOK BL-407 SURFACE MOUNTED BRICK VENEER ANCHOR ( OR EQUAL ) 2 BLOK-LOK BL-607 SIDE MOUNTED BRICK VENEER ANCHOR ( OR EQUAL ) 3 GYPSUM BOARD PANEL JOINT NOTE: NO TRANSITION MEMBRANE AT THE PERIMETER OF THE PROJECTED BRICK VENEER ANCHORS OF WALL SAMPLE.

2'-0

"2'

-0"

4'-0

"

2'-0" 8"

3

1

2

CERTAINTEED CORPORATION INSULATION GROUP

Page 12: CERTAINTEED CORPORATION INSULATION GROUP

SPECIMEN NO. 3 ( WALL WITH PENETRATIONS )

COMPOSITION 1 CERTASPRAY ( THICKNESS 1" ) 2 EXTERIOR GYPSUM BOARD 3 STEEL STRUCTURE 4 SELF-ADHESIVE MEMBRANE W/ PRIMER 5 SIMULATED WINDOW OPENING 6 POLYMER BASED CAULKING STRIP

3 4 2 1

12

1 2 4 6 7

12

7 CONCRETE FOOTING 8" X 10" 8 FOAM SEAL GASKET 9 CAULKING 10 URETHANE FOAM SEALANT 11 BRICK VENEER ANCHOR 12 20 GA. STEEL STUD

WALL UPPER SECTION WALL LOWER

SECTION

WALL SECTION

1

OPENING LOWER SECTION

5 10 4 2 1

8 9

WALL SECTION

1

11

11

CERTAINTEED CORPORATION INSULATION GROUP

Page 13: CERTAINTEED CORPORATION INSULATION GROUP

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ WALL BASE 1 CMU BU

SK-01

4/22/09

CONCRETE FOUNDATION

WEEP BAFFLE

THRU WALL FLASHING

MASONRY VENEER

MASONRY VENEER ANCHOR

CMU BU

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

WEEP

METAL DRIP EDGE FLASHING ( IF REQUIRED )

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 14: CERTAINTEED CORPORATION INSULATION GROUP

CONCRETE FOUNDATION

WEEP BAFFLE

THRU WALL FLASHING

MASONRY VENEER

MASONRY VENEER ANCHOR

CMU BU

CAVITY

GROUT FILL

MEMBRANE W/P

DRAINAGE BOARD

CERTASPRAY™ CLOSED CELL FOAM

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ WALL BASE 2 CMU BU

SK-02

4/22/09

RIGID INSULATION

WEEP

METAL DRIP EDGE FLASHING ( IF REQUIRED )

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 15: CERTAINTEED CORPORATION INSULATION GROUP

CONCRETE FOUNDATION

WEEP BAFFLE

THRU WALL FLASHING

MASONRY VENEER

MASONRY VENEER ANCHOR

EXTERIOR GYPSUM SHEATHING

CAVITY

LGMF

INTERIOR GWB

CERTASPRAY™ CLOSED CELL FOAM

SKETCH: SKETCH NO:

DATE:

CERTASPRAY WALL BASE 1 LGMF BU

SK-03

4/22/09

WEEP

METAL DRIP EDGE FLASHING ( IF REQUIRED )

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 16: CERTAINTEED CORPORATION INSULATION GROUP

CONCRETE FOUNDATION

WEEP BAFFLE

THRU WALL FLASHING

MASONRY VENEER

MASONRY VENEER ANCHOR

CAVITY

LGMF

INTERIOR GWB

GROUT FILL

MEMBRANE W/P

DRAINAGE BOARD

CERTASPRAY™ CLOSED CELL FOAM

EXTERIOR GYPSUM SHEATHING

BOARD STOCK INSULATION

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ WALL BASE 2 LGMF BU

SK-04

4/22/09

WEEP

METAL DRIP EDGE FLASHING ( IF REQUIRED )

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 17: CERTAINTEED CORPORATION INSULATION GROUP

MASONRY VENEER ANCHOR

MASONRY VENEER

CMU BU

AIR BARRIER TRANSITION MEMBRANE

SILL PAN

ALUMINUM WINDOW UNIT

BACKER ROD & SEALANT ( AIR BARRIER TRANSITION TO WINDOW FRAME )

WINDOW SILL

CERTASPRAY™ CLOSED CELL FOAM

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ SILL 1 CMU BU

SK-05

4/22/09

APPROVED SPRAY POLYURETHANE FOAM SEALANT

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 18: CERTAINTEED CORPORATION INSULATION GROUP

MASONRY VENEER ANCHOR

MASONRY VENEER

EXTERIOR GYPSUM SHEATHING

SILL PAN

ALUMINUM WINDOW UNIT

BACKER ROD & SEALANT ( AIR BARRIER TRANSITION TO WINDOW FRAME )

WINDOW SILL

CERTASPRAY™ CLOSED CELL FOAM

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ SILL 2 LGMF BU

SK-06

4/22/09

INTERIOR GWB

LGMF

APPROVED SPRAY POLYURETHANE FOAM SEALANT

AIR BARRIER TRANSITION MEMBRANE

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 19: CERTAINTEED CORPORATION INSULATION GROUP

MASONRY VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

CMU BU

BACKER ROD & SEALANT

METAL OR PLASTIC ANGLE ADHERED OR FASTENED TO CMU

APPROVED SPRAY POLYURETHANE FOAM SEALANT

ALUMINUM WINDOW

BACKER ROD & SEALANT

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ JAMB 1 CMU BU

SK-07

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 20: CERTAINTEED CORPORATION INSULATION GROUP

MASONRY VENEER

CAVITY

CERTSPRAY™ CLOSED CELL FOAM

LGMF & GWB BU WALL

BACKER ROD & SEALANT

METAL OR PLASTIC ANGLE FASTENED TO LGMF

ALUMINUM WINDOW

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ JAMB 2 LGMF BU

SK-08

4/22/09

BACKER ROD & SEALANT APPROVED SPRAY POLYURETHANE FOAM SEALANT

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 21: CERTAINTEED CORPORATION INSULATION GROUP

ALUMINUM WINDOW UNIT

MASONRY VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

CMU BU

WEEP

THRU WALL FLASHING

LOOSE STEEL LINTELMETAL OR PLASTIC ANGLE ADHERED OR FASTENED TO CMU

WEEP BAFFLE

MASONRY VENEER ANCHOR

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ HEAD DETAIL1 CMU BU

SK-09

4/22/09

RIGID INSULATION

BACKER ROD & SEALANT APPROVED SPRAY POLYURETHANE FOAM SEALANT

METAL DRIP EDGE FLASHING ( IF REQUIRED )

DETAIL MEMBRANE

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 22: CERTAINTEED CORPORATION INSULATION GROUP

ALUMINUM WINDOW UNIT

MASONRY VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

CMU BU

WEEP

THRU WALL FLASHING

WEEP BAFFLE

MASONRY VENEER ANCHOR

FILL SHIMMED SPACE BETWEEN CMU AND LINTEL WITH SPF SEALANT ( IF REQUIRED )

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ HEAD DETAIL 2 CMU BU

SK-10

4/22/09

WARNING: THIS LINTEL LOCATION AND ATTACHMENT DETAIL CAN RESULT IN HEAT LOSS AND CONDENSATION IN COLD CLIMATES. SEE AB-11 FOR COLD CLIMATE DETAIL

HUNG LINTEL SYSTEM FILL JTS IN HUNG LINTEL SYSTEM W/ SPF SEALANT

BACKER ROD & SEALANT APPROVED SPRAY POLYURETHANE FOAM SEALANT

METAL DRIP EDGE FLASHING ( IF REQUIRED )

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 23: CERTAINTEED CORPORATION INSULATION GROUP

ALUMINUM WINDOW UNIT

MASONRY VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

CMU BU

WEEP

THRU WALL FLASHING

OFFSET HUNG LINTELMETAL OR PLASTIC ANGLE ADHERED OR FASTENED TO CMU

WEEP BAFFLE

MASONRY VENEER ANCHOR

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ HEAD DETAIL 3 CMU BU

SK-11

4/22/09

APPROVED SPRAY POLYURETHANE FOAM SEALANT

BACKER ROD & SEALANT ZERODRAFT SPRAY POLYURETHANE FOAM SEALANT

METAL DRIP EDGE FLASHING ( IF REQUIRED )

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 24: CERTAINTEED CORPORATION INSULATION GROUP

ALUMINUM WINDOW UNIT

MASONRY VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

EXT GYPSUM SHEATHING & LGMF

WEEP

THRU WALL FLASHING

LOOSE STEEL LINTELMETAL OR PLASTIC ANGLE FASTENED TO LGMF

WEEP BAFFLE

MASONRY VENEER ANCHOR

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ HEAD DETAIL 1 LGMF BU

SK-12

4/22/09

BACKER ROD & SEALANT APPROVED SPRAY POLYURETHANE FOAM SEALANT

RIGID INSULATION

METAL DRIP EDGE FLASHING ( IF REQUIRED )

DETAIL MEMBRANE

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 25: CERTAINTEED CORPORATION INSULATION GROUP

ALUMINUM WINDOW UNIT

MASONRY VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

EXT GYPSUM SHEATHIING & LGMF

WEEP

THRU WALL FLASHING

WEEP BAFFLE

MASONRY VENEER ANCHOR

BACKER ROD & SEALANT APPROVED SPRAY POLYURETHANE FOAM SEALANT

HUNG LINTEL SYSTEM FILL JTS IN HUNG LINTEL SYSTEM W/ SPF SEALANT

METAL DRIP EDGE FLASHING ( IF REQUIRED )

WARNING: THIS LINTEL LOCATION AND ATTACHMENT DETAIL CAN RESULT IN HEAT LOSS AND CONDENSATION IN COLD CLIMATES. SEE AB-13 FOR COLD CLIMATE DETAIL

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ HEAD DETAIL 2 LGMF BU

SK-13

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 26: CERTAINTEED CORPORATION INSULATION GROUP

ALUMINUM WINDOW UNIT

MASONRY VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

WEEP

THRU WALL FLASHING

OFFSET HUNG LINTELMETAL OR PLASTIC ANGLE FASTENED TO LGMF

WEEP BAFFLE

MASONRY VENEER ANCHOR

SKETCH: SKETCH NO:

DATE:

CERTASPRAY HEAD DETAIL 3 LGMF BU

SK-14

4/22/09

BACKER ROD & SEALANT APPROVED SPRAY POLYURETHANE FOAM SEALANT

APPROVED SPRAY POLYURETHANE FOAM SEALANT

METAL DRIP EDGE FLASHING ( IF REQUIRED )

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 27: CERTAINTEED CORPORATION INSULATION GROUP

MASONRY VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

CMU BU

WEEP

THRU WALL FLASHING

MASONRY VENEER ANCHOR

WEEP BAFFLE

BACKER ROD & SEALANT

HUNG LINTEL SYSTEM FILL JTS IN HUNG LINTEL SYSTEM W/ SPF SEALANT TO TRANSITION AVB

TRANSITION MEMBRANE W/ BACKER ROD TO CREATE A BELLOW FOR DEFLECTION

COMPRESSIBLE FILLER

COMPRESSIBLE FILLER

APPROVED SPFS AT SHIM SPACE BEHIND HUNG LINTEL TO SUPPORT FLASHIING ( IF REQ'D )

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ RELIEVING ANGLE 1 CMU BU

SK-15

4/22/09

METAL DRIP EDGE FLASHING ( IF REQUIRED )

WARNING: THIS LINTEL LOCATION AND ATTACHMENT DETAIL CAN RESULT IN HEAT LOSS AND CONDENSATION IN COLD CLIMATES. SEE AB-16 FOR COLD CLIMATE DETAIL

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 28: CERTAINTEED CORPORATION INSULATION GROUP

MASONRY VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

CMU BU

WEEP

THRU WALL FLASHING

MASONRY VENEER ANCHOR

WEEP BAFFLE

BACKER ROD & SEALANT

OFFSET HUNG LINTEL SYSTEM

TRANSITION MEMBRANE W/ BACKER ROD TO CREATE BELLOW FOR DEFLECTION

COMPRESSIBLE FILLER

COMPRESSIBLE FILLER

APPROVED SPRAY POLYURETHANE FOAM SEALANT INFILL BEHIND HUNG LINTEL

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ RELIEVING ANGLE 2 CMU BU

SK-16

4/22/09

METAL DRIP EDGE FLASHING ( IF REQUIRED )

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 29: CERTAINTEED CORPORATION INSULATION GROUP

MASONRY VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

EXT GYPSUM SHEATHING & LGMF

WEEP

THRU WALL FLASHING

MASONRY VENEER ANCHOR

WEEP BAFFLE

BACKER ROD & SEALANT

HUNG LINTEL SYSTEM FILL JTS IN HUNG LINTEL SYSTEM W/ SPF SEALANT TO TRANSITION AVB

TRANSITION MEMBRANE W/ BACKER ROD TO CREATE BELLOW FOR DEFLECTION HEAD

COMPRESSIBLE FILLER

APPROVED SPFS FILL AT SHIM SPACE BEHIND ANGLE ( IF NEEDED )

SKETCH: SKETCH NO:

DATE:

CERTSPRAY™ RELIEVING ANGLE 1 LGMF BU

SK-17

4/22/09

METAL DRIP EDGE FLASHING ( IF REQUIRED )

WARNING: THIS LINTEL LOCATION AND ATTACHMENT DETAIL CAN RESULT IN HEAT LOSS AND CONDENSATION IN COLD CLIMATES. SEE AB-18 FOR COLD CLIMATE DETAIL

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 30: CERTAINTEED CORPORATION INSULATION GROUP

MASONRY VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

EXT GYPSUM SHEATHING & LGMF

WEEP

THRU WALL FLASHING

MASONRY VENEER ANCHOR

WEEP BAFFLE

BACKER ROD & SEALANT

OFFSET HUNG LINTEL SYSTEM

TRANSITION MEMBRANE W/ BACKER ROD TO CREATE BELLOW FOR DEFLECTION

COMPRESSIBLE FILLER

APPROVED SPRAY POLYURETHANE FOAM SEALANT INFILL BEHIND HUNG LINTEL

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ RELIEVING ANGLE 2 LGMF BU

SK-18

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 31: CERTAINTEED CORPORATION INSULATION GROUP

MASONRY VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

CMU BU

DETAIL MEMBRANE

BACKER ROD ( TO SUPPORT DETAIL MEMBRANE )

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ CONTROL JOINT CMU BU

SK-19

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 32: CERTAINTEED CORPORATION INSULATION GROUP

BRICK VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

LGMF BU

DETAIL MEMBRANE

BACKER ROD ( TO SUPPORT DETAIL MEMBRANE )

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ CONTROL JOINT LGMF BU

SK-20

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 33: CERTAINTEED CORPORATION INSULATION GROUP

BRICK VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

CMU BU

BOND BREAKER TAPE & SEALANT

APPROVED SPF SEALANT

METAL OR PLASTIC ANGLE

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ EXPANSION JOINT CMU BU

SK-21

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 34: CERTAINTEED CORPORATION INSULATION GROUP

BRICK VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

CMU BU

APPROVED SPF SEALANT

METAL OR PLASTIC ANGLE

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ EXPANSION JOINT LGMF BU

SK-22

4/22/09

BOND BREAKER TAPE & SEALANT

1400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 35: CERTAINTEED CORPORATION INSULATION GROUP

BRICK VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

CMU BU

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ EXTERNAL CORNER CMU BU

SK-23

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 36: CERTAINTEED CORPORATION INSULATION GROUP

BRICK VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

LGMF BU

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ EXTERNAL CORNER LGMF BU

SK-24

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 37: CERTAINTEED CORPORATION INSULATION GROUP

BRICK VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

CMU BU

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ INTERNAL CORNER CMU BU

SK-25

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 38: CERTAINTEED CORPORATION INSULATION GROUP

BRICK VENEER

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

LGMF BU

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ INTERNAL CORNER LGMF BU

SK-26

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 39: CERTAINTEED CORPORATION INSULATION GROUP

MASONRY VENEER

MASONRY VENEER ANCHOR

CMU BU

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

BOND BEAM CMU

MASONRY CRAMP ANCHOR

ROOF COUNTER FLASHING

ROOF FLASHING

ROOF MEMBRANE

COMPRESSIBLE FILLER

WOOD BLOCKING

BACKER ROD TO CREATE BELLOW FOR DEFLECTION

BENT PLATE

DETAIL MEMBRANE

ROOF UNDERLAYMENT

STEEL BEAM

ROOF VAPOR BARRIER

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ ROOF DETAIL 1 CMU BU

SK-27

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 40: CERTAINTEED CORPORATION INSULATION GROUP

MASONRY VENEER

CMU BU

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

BOND BEAM CMU

ROOF CAP FLASHING

ROOF MEMBRANE

COMPRESSIBLE FILLER

WOOD BLOCKING

BACKER ROD TO CREATE BELLOW FOR DEFLECTION

BENT PLATE POUR STOP

ROOF VAPOR BARRIER

STEEL BEAM

MASONRY VENEER ANCHOR

SLAB ON METAL DECK

DETAIL MEMBRANE

DETAIL MEMBRANE

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ ROOF DETAIL 2 CMU BU

SK-28

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 41: CERTAINTEED CORPORATION INSULATION GROUP

MASONRY VENEER

MASONRY VENEER ANCHOR

LGMF BU

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

ROOF COUNTER FLASHING

ROOF FLASHING

ROOF MEMBRANE

COMPRESSIBLE FILLER

WOOD BLOCKING

BACKER ROD TO CREATE BELLOW FOR DEFLECTION

BENT PLATE

DETAIL MEMBRANE

ROOF UNDERLAYMENT

STEEL BEAM

ROOF VAPOR BARRIER

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ ROOF DETAIL 1 LGMF BU

SK-29

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com

Page 42: CERTAINTEED CORPORATION INSULATION GROUP

MASONRY VENEER

EXT GYPSUM SHEATHING & LGMF

CAVITY

CERTASPRAY™ CLOSED CELL FOAM

ROOF CAP FLASHING

ROOF MEMBRANE

DEFLECTION HEAD

WOOD BLOCKING

BACKER ROD TO CREATE BELLOW FOR DEFLECTION

BENT PLATE POUR STOP

ROOF VAPOR BARRIER

STEEL BEAM

MASONRY VENEER ANCHOR

SLAB ON METAL DECK

EXT GYPSUM SHEATHING & LGMF

DETAIL MEMBRANE

DETAIL MEMBRANE

SKETCH: SKETCH NO:

DATE:

CERTASPRAY™ ROOF DETAIL 2 LGMF BU

SK-30

4/22/091400 Union Meeting Road Blue Bell, PA 19422 T 610-341-6712 F 610-341-6773 www.certainteed.com