Central OnLite System Zumtobel

64
Emergency lighting systems with central power supply. ONLITE central

Transcript of Central OnLite System Zumtobel

Page 1: Central OnLite System Zumtobel

Emergency lighting

systems with central

power supply.

ONLITE central

Page 2: Central OnLite System Zumtobel

ONLITE central LPSSelf-contained group battery system for maximum failure safety

ONLITE central CPSProject-specifi c customised, networked central battery system

No additional data cable required

Mixed operation (maintained mode and non-maintained mode) within one circuit

Simple commissioning

No external components required

Type-tested installations

Standard DALI monitoring

Adaptable circuit design – up to 300 circuits

Up to 6.000 emergency and escape sign luminaires are possible

Web browser-based visualisation

Page 3: Central OnLite System Zumtobel

3

Page 4: Central OnLite System Zumtobel

* LPS = Low Power Supply system (acc. to

EN 50171 Central power supply systems)

■ Limited output power

■ Comprises battery charger and charging

regulator, circuit outputs including battery

■ Type-tested installations

ONLITE central LPS *Self-contained group battery system for maximum failure safety

High level of safety

■ Entire system is split up into several

self-contained units■ Shorter cable lengths reduce fire loads

by up to 45 %■ Individual failure or error notification

Page 5: Central OnLite System Zumtobel

5

Less effort on installationImpressive cost effectiveness

■ Communication based on Powerline

(mains cable)■ No fire-resistant cables required within

a fire compartment (not UK)■ 25 % less installation effort thanks to

subdivision of entire system

■ Flexibly programmable emergency lighting

levels allow lower battery capacities■ DALI compatibility ensures straightforward,

affordable integration into general lighting

system ■ Built-in staircase lighting function

ON

LIT

E c

en

tra

l LP

S

Page 6: Central OnLite System Zumtobel

The ONLITE group battery system excels by combining maximum func-

tionality with seamless integration into the general lighting system. Sev-

eral self-contained systems ensure straightforward installation and quick

commissioning. ONLITE central LPS makes it possible to control and

monitor every luminaire individually. Emergency lighting is integrated into

the general lighting system and connection to the lighting management

system is obtained via DALI. The group batteries can be networked using

Ethernet in order to be able to control and monitor essential functions via

a graphical user interface.

Modular design for the most effective possible solution

Powder-coated

sheet-steel cabinet,

colour: RAL 7053

Ventilation slits for battery

ventilation and cooling

Inspection window

Terminal strip

EPS 360 Controller with

touch-sensitive panel

Battery compartment

partitioned off

from electronic system

Screwed cable glands

Page 7: Central OnLite System Zumtobel

7

Page 8: Central OnLite System Zumtobel

ONLITE central LPS system summary

LPS 360 LPS 720

* Limit values for group battery systems (LPS) according to

EN 50171:

Standby operating time 1 h: 1500 W

Standby operating time 3 h: 500 W

Four basic units delivering rated outputs from 360 W to 1440 W meet the

full range of group battery system requirements perfectly.

Circuits (each for up to 20 luminaires) 3 6

AC output power of each circuit (mains operation) 552 VA 552 VA

Mains connection 1 x 230 V

L/N/PE

2 x 400 V

L1/L2/N/PE

DC output power (emergency mode) 360 W* 720 W*

DC output power of each circuit (emergency mode) 120 W 120 W

Standby operating time 1 h 2 x 12 V 33 Ah 4 x 12 V 33 Ah

Standby operating time 3 h 2 x 12 V 75 Ah 4 x 12 V 75 Ah

Page 9: Central OnLite System Zumtobel

9

LPS 1080 LPS 1440

9 12

552 VA 552 VA

3 x 400 V

L1/L2/L3/N/PE

3 x 400 V

L1/L2/L3/N/PE

1080 W* 1440 W*

120 W 120 W

6 x 12 V 33 Ah 8 x 12 V 33 Ah

6 x 12 V 75 Ah 8 x 12 V 75 Ah

Page 10: Central OnLite System Zumtobel

NSI control gear with

built-in interface

ONLITE central LPS and

LED systems

www.zumtobel.com/onlite

Together, ONLITE central LPS and innovative LED emer-

gency and escape sign luminaires make a great team. Using

efficient LED luminaires which provide light distribution that

is perfectly matched to emergency lighting needs keeps the

installed load to a bare minimum. This means that required

battery capacities can be smaller and supply systems can

be significantly more compact. Communication between the

ONLITE central LPS system and the LED luminaires is based

on Powerline, which allows individual control and monitor-

ing of every luminaire. Emergency lighting can be operated

completely independently of the general lighting system.

Optimal solution for LED emergency lighting systems

3

Page 11: Central OnLite System Zumtobel

11

ONLITE central LPS and

integrated LED emergency

lighting systems

www.zumtobel.com/ml

General lighting luminaires can be integrated into the emer-

gency lighting system in order to achieve a uniform ceil-

ing look. The ONLITE central LPS system ensures visual

matching and optimal functional integration into the gen-

eral lighting system. Every luminaire can be integrated into

a Zumtobel lighting management system via the ONLITE

central LPS system’s built-in DALI interface. Special LED

solutions can be integrated into the general lighting system

in order to improve the efficiency of emergency lighting and

reduce the required battery capacities. This combines the

advantages of separate emergency lighting luminaires and

the enhanced appearance of a consistent ceiling look. The

light sources for the general lighting system are powered

through the conventional wiring system, and the LEDs for

the emergency lighting system are powered by the ONLITE

central LPS system.

PCA

control gear

NSI emergency

lighting module

Mains cable

3

Page 12: Central OnLite System Zumtobel

Monitoring, controlling and testing every group from a central location

Features of EPS 360■ Mains monitoring■ Control of power circuits and lumi-

naires■ Charging unit for batteries includ-

ing battery charging regulator■ Switchover device to change

from mains-powered operation to

emergency operation■ Transformer for emergency supply

from batteries■ Touch-sensitive screen for con-

trolling and configuring

Touch-sensitive screen

LED function display

Download the test log

book via infrared or RS

232 interface

3 output circuits

Up to 20 luminaires can be

connected to each of the

three output circuits of the

EPS 360 Controller. The

maximum permissible in-

stalled load per circuit is:

552 VA (mains operation)

and 120 W (emergency

operation).

The EPS 360 Controller is the core of every ONLITE central

LPS system. Depending on the size of the system, several

of these self-contained units are installed in order to ensure

maximum possible redundancy and hence optimum safety.

All settings and test logs are stored in non-volatile memory.

No data loss even in event of complete shutdown (mains

and battery power).

Page 13: Central OnLite System Zumtobel

13

Programmable test cycles

The date and time of day of all function and service

life/annual system tests can be user programmed.

This prevents tests being performed at inoppor-

tune times, e. g. while a film is being shown in a

cinema.

Electronic test log book

All function and service life/annual system tests

are logged and stored in the electronic test log

book of the EPS 360 Controller for at least three

years. The test log book can be read out at any

time via an infrared or RS 232 interface.

Methods of connection

A wide variety of methods of connection guar-

antees maximum flexibility. Luminaires can be

switched individually or as a complete circuit. With

the individual method of connection, it is possible

to specify, for every individual luminaire, whether

it is to be set up in maintained mode, non-main-

tained mode or switched via any of the switching

inputs. In addition, every EPS 360 Controller has

a built-in automatic staircase lighting function.

Page 14: Central OnLite System Zumtobel

Emergency lighting level at the push of a button The

emergency lighting level is set on the touch-sensitive display

of the EPS 360 Controller. These values, based on photo-

metric calculations, can be entered one circuit at a time or

for each individual luminaire. Zumtobel luminaires with DALI

dimmable ballasts (luminaire names starting with LDE) allow

individual definition of the dimming level in emergency op-

erating mode. The emergency luminous flux of emergency

luminaires can be reduced gradually down to 5 % of the

normal lighting.

Flexible illuminance levels Cut costs and reduce environmental impact

In the case of conventional emergency lighting solutions

with non-programmable emergency lighting levels, output in

emergency mode is identical to that in normal (mains opera-

tion) mode. This requires relatively high battery capacities

and results in higher energy consumption.

In most cases, 10 % of the lumen package of the mains

lighting is sufficient to guarantee minimum illuminance when

operating in emergency mode. The programmable emer-

gency lighting level minimises system costs because sets of

batteries and central installations can be designed consider-

ably smaller; this also helps reduce environmental impact.

Conventional solution

with non-programmable emergency lighting level

ONLITE central LPS solution

with programmable emergency lighting level

Lu

min

air

e 1

100 % 100 % 100 % 30 % 10 % 20 %

Lu

min

air

e 1

Lu

min

air

e 2

Lu

min

air

e 2

Lu

min

air

e 3

Lu

min

air

e 3

Circuit 1 120 W 13 x 11.5 W = 149.5 W (DC) = < 160 W

Circuit 2 120 W 10 x 11.5 W = 115.0 W (DC) = < 160 W

Circuit 3 120 W 11 x 8.0 W = 88.0 W (DC) = < 160 W

Total 360 W = 352.5 W (DC) = < 360 W

Output per controller:■ 360 W total emergency lighting output for

1 or 3 hours depending on battery set■ 3 output circuits, each for up to 20 luminaires■ Each output circuit rated 120 W in DC operation

and 552 VA in mains operation

The number of lighting points can be increased by

reducing the output of the luminaires

Page 15: Central OnLite System Zumtobel

15

Light

source

Wattage AC power

[100 %]

230 V/50 Hz

[VA]

DC [W] DC [W] DC [W] DC [W] DC [W] DC [W] DC [W] DC [W] DC [W] DC [W] Control gear / luminaire

Emergency

lighting level 5 % 10 % 15 % 20 % 30 % 40 % 50 % 60 % 70 % 100 %

LED 5.2 - - - - - - - - - 4.7 EM Power 1 LED NSI / ARTSIGN EW

LED 6.8 - - - - - - - - - 6.2 EM Power 1 LED NSI / ARTSIGN ED

LED 8.4 - - - - - - - - - 7.8 EM Power 2 LED NSI / PURESIGN AW

LED 11.8 - - - - - - - - - 11.2 EM Power 2 LED NSI / PURESIGN AD

LED 8.3 - - - - - - - - - 7.7 EM Power 1 LED NSI / COMSIGN II LED

LED 9.1 - 2.2 - - - - - - 6.5 8.5 EM Power 1 LED NSI / PROOFSIGN

LED 11.8 - - - - - - - - - 11.2 EM Power 2 LED NSI / SQUARESIGN 300

LED 11.8 - - - - - - - - - 11.2 EM Power 2 LED NSI / FREESIGN 300

LED 5.7 - - - - - - - - - 5.1 EM Power 1 LED NSI / RESCLITE

T16 14 W 17.3 7.3 8.0 8.6 8.9 10.1 11.7 12.4 14.0 14.5 14.7 PCA 1x14/24 T5 EXCEL one4all lp xitec

T16 2/14 W 32.7 11.4 12.7 14.6 15.3 17.9 21.3 23 26.4 27.7 28.0 PCA 2x14/24 T5 EXCEL one4all lp xitec

T16 21 W 24.8 7.1 8.3 9.7 10.3 12.2 14.8 16.2 18.8 20.0 20.3 PCA 1x21/39 T5 EXCEL one4all lp xitec

T16 2/21 W 47.0 12.3 14.3 16.9 18.2 22.2 27.1 29.9 35.2 37.8 38.3 PCA 2x21/39 T5 EXCEL one4all lp xitec

T16 28 W 31.9 7.7 9.2 11.0 12.0 14.7 18.1 20.2 23.7 25.4 25.8 PCA 1x28/54 T5 EXCEL one4all lp xitec

T16 2/28 W 63.1 13.7 16.3 19.7 21.5 26.7 33.2 37.1 43.9 47.3 48.0 PCA 2x28/54 T5 EXCEL one4all lp xitec

T16 35 W 39.8 8.5 11.1 13.3 14.4 17.6 21.8 24.3 28.6 30.7 31.2 PCA 1x35/49/80 T5 EXCEL one4all lp xitec

T16 2/35 W 77.4 14.5 18.0 22.2 24.6 31.3 39.4 44.5 52.7 56.9 57.7 PCA 2x35/49 T5 EXCEL one4all lp xitec

T16 24 W 26.8 8.5 9.6 11.1 11.7 13.8 16.8 18.6 21.3 22.4 22.6 PCA 1x14/24 T5 EXCEL one4all lp xitec

T16 2/24 W 53.1 13.9 16.2 19.2 20.7 25.6 31.5 35.0 41.1 44.0 44.7 PCA 2x14/24 T5 EXCEL one4all lp xitec

T16 39 W 43.3 9.3 11.3 13.8 15.2 19.3 23.9 26.7 31.8 34.5 35.0 PCA 1x21/39 T5 EXCEL one4all lp xitec

T16 2/39 W 85.1 16.4 20.3 25.2 28.1 35.9 45.8 52.1 61.8 66.7 67.8 PCA 2x21/39 T5 EXCEL one4all lp xitec

T16 49 W 54.7 10.7 13.1 16.1 17.9 22.7 28.5 32.2 38.3 41.4 42.0 PCA 1x35/49/80 T5 EXCEL one4all lp xitec

T16 2/49 W 106.6 17.2 22.2 28.1 31.8 41.7 53.4 60.9 73.3 80.1 81.5 PCA 2x35/49 T5 EXCEL one4all lp xitec

T16 54 W 61.0 11.8 14.6 18.1 20.3 25.8 32.6 36.9 44.0 47.7 48.5 PCA 1x28/54 T5 EXCEL one4all lp xitec

T16 2/54 W 119.4 21.1 26.9 33.9 38.3 49.6 63.1 71.8 85.4 92.5 94.0 PCA 2x28/54 T5 EXCEL one4all lp xitec

T16 80 W 87.9 14.7 18.8 23.8 27.0 35.3 45.2 51.6 61.7 67.0 68.0 PCA 1x35/49/80 T5 EXCEL one4all lp xitec

T26 1/18 W 26.0 8.5 9.5 10.5 12.0 13.0 13.5 16.5 PCA excel one4all

T26 2/18 W 43.0 16.0 17.5 19.0 23.0 25.0 26.5 28.0 PCA excel one4all

T26 1/30 W 34.0 9.5 11.5 13.0 15.5 18.5 20.5 25.0 PCA excel one4all

T26 2/30 W 61.0 16.0 19.0 22.0 28.0 32.5 37.5 45.5 PCA excel one4all

T26 1/36 W 42.0 12.5 15.0 16.5 20.0 22.0 24.5 28.5 PCA excel one4all

T26 2/36 W 74.0 22.5 26.5 30.5 36.0 40.0 43.5 53.5 PCA excel one4all

T26 1/58 W 61.0 17.5 21.0 24.5 29.0 33.5 37.5 45.5 PCA excel one4all

T26 2/58 W 110.0 31.5 37.5 44.5 53.5 60.5 67.5 83.5 PCA excel one4all

TC-L/F 1/18 W 24.0 6.0 6.5 7.5 8.5 9.5 10.5 12.5 PCA excel one4all

TC-L/F 2/18 W 41.0 9.0 10.5 12.0 14.0 16.5 18.5 23.5 PCA excel one4all

TC-L/F 1/24 W 31.0 9.0 11.0 12.5 15.0 17.0 19.0 22.5 PCA excel one4all

TC-L/F 2/24 W 53.0 14.5 17.5 20.5 25.5 30.5 34.5 42.5 PCA excel one4all

TC-L/F 1/36 W 39.0 12.0 14.5 16.5 20.5 24.0 26.5 32.5 PCA excel one4all

TC-L/F 2/36 W 73.0 18.5 22.5 27.0 33.5 40.0 46.0 59.5 PCA excel one4all

TC-L/F 1/40 W 50.0 14.5 17.5 20.5 23.5 26.5 29.5 36.5 PCA excel one4all

TC-L/F 2/40 W 90.0 26.5 31.0 35.5 44.5 51.5 57.5 72.5 PCA excel one4all

TC-L/F 1/55 W 63.0 16.5 23.0 29.5 28.5 34.5 39.5 52.5 PCA excel one4all

TC-L/F 2/55 W 121.0 30.5 38.5 46.5 58.0 67.5 76.5 101.5 PCA excel one4all

TC-S/E 1/11 W 19.0 6.5 7.5 8.0 9.5 10.5 11.5 13.0 PCA excel one4all

TC-S/E 2/11 W 33.0 9.5 11.5 13.0 12.5 13.5 14.5 24.0 PCA excel one4all

TC-D/E 1/13 W 20.0 6.5 8.0 8.5 10.0 11.0 12.0 14.0 PCA excel one4all

TC-D/E 2/13 W 33.0 10.0 12.0 13.5 16.0 19.0 21.5 26.0 PCA excel one4all

TC-D/T 1/18 W 24.0 7.0 8.5 9.5 11.5 13.5 15.0 18.0 PCA excel one4all

TC-D/T 2/18 W 43.0 13.0 15.5 17.5 21.5 24.5 27.5 34.0 PCA excel one4all

TC-D/T 1/26 W 33.0 10.0 12.0 13.5 16.5 18.5 20.5 24.5 PCA excel one4all

TC-D/T 2/26 W 57.0 16.5 20.5 23.5 29.5 34.0 38.5 46.5 PCA excel one4all

TC-T/E 1/32 W 36.0 10.5 13.5 15.5 19.5 22.5 25.5 30.5 PCA excel one4all

TC-T/E 2/32 W 66.0 17.5 22.5 27.0 34.5 41.5 48.0 59.5 PCA excel one4all

TC-T/E 1/42 W 47.0 12.0 15.0 17.5 22.5 27.5 31.0 39.5 PCA excel one4all

TC-T/E 2/42 W 88.0 23.5 29.0 34.5 43.5 52.0 59.5 77.5 PCA excel one4all

TC-DD 1/55 W 60.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 PCA excel one4all

NV DSI 70 W 70.0 58.0 58.0 58.0 58.0 58.0 58.0 58.0 TEL 70 VA

NV DSI 105 W 105.0 85.0 85.0 85.0 85.0 85.0 85.0 85.0 TEL 105 VA

NV DSI 150 W 150.0 90.0 90.0 90.0 90.0 90.0 90.0 90.0 TEL 150 VA

NV DSI 210 W 210.0 137.0 137.0 137.0 137.0 137.0 137.0 137.0 TEL 210 VA

NV DALI 105 W 105.0 85.5 85.5 85.5 85.5 85.5 85.5 85.5 TEL one4all 105 VA

NV DALI 150 W 150.0 90.5 90.5 90.5 90.5 90.5 90.5 90.5 TEL one4all 150 VA

Page 16: Central OnLite System Zumtobel

ONLITE central LPSSystem topology

LUXMATE bus

3 (L, N, PE)

L' switching conductor

L1, L2, N, PE

Emergency luminaire

switched (L’)

Mains-powered

luminaire

Mains-powered

luminaire

Escape sign luminaire

switched (L’)

Emergency luminaire

switched (L’)

Emergency luminaire

switched (L’)

Emergency luminaire

switched (L’)

3 (L, N, PE)

3 (L, N, PE)

FI

HVA UVA

ONLITE central EPDOrder no. 22 156 808

optional

DALI 2 x 1.5 mm2

DALI input is optional (if it is used, local and central switching is no longer possible)

ONLITE IR printerOrder no. 22 154 522

Infrared

LM-DALIS

LM-DALIS

N L3 L2 L1

1 4

Page 17: Central OnLite System Zumtobel

17

EL1

EN

1P

EE

L2

EN

2P

EE

L3

EN

3P

ES

1S

3

El1

En1

PE

El2

En2

PE

El3

En3

PE

S1

S3

LS

LS

N N PE

K1

1K

12

K1

4K

21

K2

2K

24

K3

1K

32

K3

4

ONLITE central LPS 720 1h10Order no. 22 156 821

Battery cable Battery cable

ONLITE central EPDOrder no. 22 156 808

ONLITE central EPDOrder no. 22 156 808

UV2 UV3

ONLITE central Remote interface LPS/CPS

Order no. 22 154 740

Switching inputs, optional(only possible if there is no DALI input)

S2_

1

S3_

1

S2_

2

S3_

2

N S

4_

1

S5_

1

S5_

2

S4_

2

Indi

catio

n +

Indi

catio

n –

Emer

genc

y off

+

Emer

genc

y off

L'1

L'2

PH

W1 +

PH

W1 –

PH

W2 +

PH

W2 –

Syn

c +

Syn

c –

K1

Circuit 1

Circuit 2

Circuit 3

S1a S1b S1c

Ready for operation

Operation from battery

K2 K3 U+ U- S1 S2

L1L2L3N

PE

N L3 L2 L1

1 4

L1L2L3N

PE

N L3 L2 L1

1 4

Off

EPS 360 EPS 360

Notes:

■ Only ONLITE Powerline de vices and

the control gear to be controlled

may be connected to the EPS 360.

“External” consumers or interference

sources must not be connected to

the Powerline network.

■ Band-stop filters or filters are not

permitted in the Powerline domain.

■ Where the length of parallel cable

runs cannot be restricted to 10 m,

cables which are parallel must be

spaced at least 5 cm apart.

■ The maximum cable length is 300 m

(1.5 to 4 mm²).

Page 18: Central OnLite System Zumtobel

Design tips

Individual monitoring of luminaires

Monitoring of circuits

With individual monitoring of luminaires, there is an intelligent

monitoring module inside every emergency luminaire which

communicates with the central emergency lighting power

source via Powerline. Every emergency luminaire is assigned

a unique luminaire address at the time of commissioning.

This makes it possible to display the status of each individual

emergency luminaire on the ONLITE central LPS.

An EPS 360 Controller which measures the power output

into its output circuit in order to ascertain whether all the

luminaires in the circuit are operating correctly is a distinc-

tive feature of this circuit monitoring. In the case of circuit

monitoring, only circuit-wide switching is possible.

Benefi ts

■ When an emergency luminaire fails, the location of

the faulty luminaire is pinpointed.

■ Emergency luminaires in one output circuit can be

individually configured to various modes of opera-

tion.

■ Emergency luminaires can be integrated into DALI

lighting control.

■ Emergency lighting levels can be programmed via

central emergency lighting power source.

Benefi ts

■ Luminaires do not have to be equipped with

add-on modules.

■ Any load suitable for AC/DC may be connected.

Disadvantage

■ It is not possible to pinpoint every individual lumi-

naire failure (depends on wattage mix of output

circuit and output of the luminaires).

Circuit 1

Circuit 2

Circuit 3Emergency power supply

Emergency power supply

Emergency power supply

Powerline

communication

ONLITE central LPS

Circuit 1

Circuit 2

Circuit 3Emergency power supply

Emergency power supply

Emergency power supply

ONLITE central LPS

Pcircuit

Page 19: Central OnLite System Zumtobel

19

Integration into a lighting

management system

Central monitoring using

GO-ON package

The DALI interface ensures that emergency lighting can be

integrated seamlessly into general lighting. DALI commands

are converted to Powerline signals and are sent to the emer-

gency and escape sign luminaires. This way, every luminaire

can be individually controlled and included in automation

processes. LUXMATE lighting control systems make it pos-

sible to fully exploit a whole raft of advantages offered by

ONLITE central LPS.

Note: If DALI lighting control is enabled, the “central switch-

ing using switching inputs” and “local L' switching” functions

will no longer be available.

Note: ONLITE Central LPS version with Ethernet (Nport x)

must be used.

The ONLITE GO-ON package visualisation module provides

users with a convenient facility for monitoring their entire

ONLITE emergency lighting system from one central loca-

tion. Perfectly planned monitoring systems link up the group

or separate battery systems in one or more buildings into an

intelligent information network, which delivers information on

the status of the emergency lighting system round the clock.

230 V AC

230 V AC/DC

Emergency power supply

ONLITE central LPS

DALI

DALI

TCP/IP network

GO-ON

package

ONLITE central LPS

Page 20: Central OnLite System Zumtobel

* CPS = Central Power Supply system

(acc. to EN 50171).

Can be used with no output limits

ONLITE central CPSProject-specific customised, networked central battery system

Less effort on design

■ Manageable, clearly structured product

range■ Integration into lighting management with

resulting significant technical and economic

benefits■ Project-specific solutions thanks to modular

system■ Full functionality as standard, renders ad-

ditional software and modules superfluous

Page 21: Central OnLite System Zumtobel

21

Convenience at every levelPerfect design freedom

■ Simple, easily understandable operation

using removable Touch PC■ System information can be downloaded

via the Internet by using Web browser-

based software■ Function and annual system tests are run

and documented completely automati-

cally

■ Individual switching mode for each lumi-

naire, even within a single circuit■ Combination of monitoring of circuits and

individual luminaires in one system■ Simple project planning thanks to compe-

tent design support and extensive design

tools

ON

LIT

E c

en

tra

l C

PS

Page 22: Central OnLite System Zumtobel

Every central battery system is designed project-specifically on the basis

of a modular system. This produces solutions which are optimised in

terms of the cost and functionality of the system. The modular design of

ONLITE central CPS guarantees a tailor-made solution for any project

and a significantly optimised cost/functionality ratio.

Tailor-made emergency lighting systemModular system for best possible price/performance ratio

Powder-coated sheet-steel cabinet,

colour: RAL 7053

Maximum energy efficiency thanks to■ Low-loss components■ Optimal battery capacity

Built-in Touch PC

Left-hand or right-hand door hinge

Detachable grating for safe transport using

lifting truck

Integral base with ventilation slits for battery

ventilation and cooling

Large wiring space for

convenient wiring

Disconnect terminals for all

connections

Modular cabinet design for

project-specific solutions

Generous battery compartment

with strong shelf supports for

simple connection and mainte-

nance of batteries

Integral collecting trough

eliminates need for electrolyte-

resistant floor surface

Page 23: Central OnLite System Zumtobel

23

Page 24: Central OnLite System Zumtobel

System designExamples of compact station and main station applications

CPS K

Compact station

Besides the internal controller and circuit modules, a battery with a

capacity of up to 75 Ah is accommodated in the main distribution unit of

the emergency lighting power supply. In addition, outgoing fuse protec-

tion for external sub-distribution boards of the emergency lighting system

can be catered for. It is preferable to use compact or combined stations

in medium-sized buildings.

UVS 2 UVS 7 UVS 8 UVS 3

UVS 1 UVS 1 UVS 2

E E

ES S

S S

7 Ah

12 Ah

17 Ah

24 Ah

28 Ah

33 Ah

45 Ah

55 Ah

75 Ah

7 Ah

12 Ah

17 Ah

24 Ah

28 Ah

33 Ah

45 Ah

55 Ah

75 Ah

Each internal or external substation (UVS)

can be selected to monitor circuits (S) or

individual luminaires (E).

Page 25: Central OnLite System Zumtobel

25

CPS H

Main station

The main station contains the internal controller and, optionally, internal

circuit modules and outgoing circuits to the substations of the emergency

lighting system. Compared with the CPS K, batteries are accommodated

in external battery cabinets (output per cabinet up to 150 Ah; no more

than 2 cabinets) or on a battery rack. Main stations like these with a set

of external batteries are used in large buildings. Several self-contained

systems can be used where higher outputs are required (> 25–30 kW).

UVS 4 UVS 14 UVS 15

E

E

UVS 2

UVS 3

S

S S

UVS 1

S

Each internal or external substation (UVS)

can be selected to monitor circuits (S) or

individual luminaires (E).

Page 26: Central OnLite System Zumtobel

ONLITE central CPS system overview

CPS K

Compact station

CPS H

Main station

Every ONLITE central CPS offers full functionality in order to comprehen-

sively meet the requirements placed on a central battery system using

as few components as possible. No additional software or modules are

needed. There is no need to fit any separate components in the luminaire

because every DALI luminaire can be used as an emergency luminaire

which can be individually monitored and controlled. This also reduces

effort on commissioning, inspecting and maintaining the system. A large

removable Touch PC is the core of the system. It enables, for example,

straightforward commissioning by one person or neatly laid out, easily-

manageable visualisation of the system’s status.

Features ■ Power in emergency mode from

1 to 30 kW■ Up to 300 circuits, each for

20 emergency luminaires■ Up to 12 external substations per

main station (CPS H)■ Mixed operation within one circuit is

possible■ Between 120 and 240 (optional)

freely assignable switching inputs■ Web browser-based user interface

Circuits (up to 20 luminaires) 1) Up to 40 internal + 20 external

2) Up to 20 internal + 140 external

Up to 60 internal + 240 external

Maximum number of luminaires 1) 1,200 pcs.

2) 3,200 pcs.

6,000 pcs.

Mains connection 5-pole 3 x 400 V 5-pole 3 x 400 V

Mains operation Total AC output power 7–30 kVA 30 kVA

Max. AC output power per circuit 1,300 VA 1,300 VA

AC output power per 20 circuits (per UVS) 4,700 VA 4,700 VA

Mains operation Total DC output power 7.6 kW [1 h]* 3.3 kW [3 h]* 22.7 kW [1 h]* 10 kW [3 h]*

Max. DC output power per circuit 1,300 W 1,300 W

DC output power per 20 circuits (per UVS) 4,700 W 4,700 W

Standby operating time 1 h–8 h 18 x 12 V / 7–75 Ah

accommodated in combined cabinet

18 x 12 V bis 200 Ah

accommodated in sep. battery cabinet or battery rack

* Including 25 % reserve capacity (battery ageing)

Page 27: Central OnLite System Zumtobel

27

CPS U E30

Fire-resistant substation

CPS U E00

Substation

20 20

4,700 VA 4,700 VA

1,300 VA 1,300 VA

4,700 VA 4,700 VA

Page 28: Central OnLite System Zumtobel

Control gear with built-in

DALI interface

ONLITE central CPS and

LED systems

www.zumtobel.com/onlite

Combining ONLITE central CPS with innovative LED emer-

gency and escape sign luminaires offers distinct advan-

tages. Using efficient LED luminaires that provide light

distribution which is perfectly matched to emergency light-

ing needs keeps the installed load to a bare minimum. This

means that required battery capacities can be smaller and

supply systems can be significantly more compact. Com-

munication between the CPS system and LED luminaires

is based on DALI and therefore supports individual control

and monitoring of every luminaire. Emergency lighting can

be operated completely independently of the general light-

ing system.

Every DALI standard luminaire is also an emergency luminaire

5

Page 29: Central OnLite System Zumtobel

29

www.zumtobel.com/ecoos

PCA DALI

control gear

ONLITE central CPS and

general lighting system

Every DALI standard luminaire can be used as an emergency

luminaire which can be individually controlled and moni-

tored. No additional modules need to be fitted to achieve

this, and functionality of the general lighting system is com-

pletely preserved. This simplifies project planning, reduces

both costs and effort and makes choosing luminaires easy.

Delivery times for emergency luminaires are short because

they are luminaires in the standard product range.5

Page 30: Central OnLite System Zumtobel

A system control centre for operating, displaying and networking

ONLITE central CPS sets new standards when it comes to monitoring

and display of emergency lighting systems. A 7" LED-backlit WVGA

widescreen (16:9) colour Touch PC displays the entire installation. Touch

and control: It takes no more than three touches to access individual

luminaire data and status displays. All events are recorded for at least

three years on a built-in SD card as a test log book.

Ethernet / WLAN / Internet

Networkability comes as standard

Every ONLITE central CPS module can be visu-

alised via Ethernet using a web-based browser

without the need for any additional software.

The system can therefore be managed remotely

from any PC.

Page 31: Central OnLite System Zumtobel

31

Info

248.50 V

0.10 A

20.00 °C

24.11.201014:03:31

ONLITE CPS 7000Zumtobel

Ready for operation TestMains operation Unit malfunction Maintained lightMains failure UVA Luminaire failure System bus

Battery voltage

Charging current

Battery temperature

Info

24.11.201014:06:03

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

248.40 V

0.10 A

22.10 °C

UV summary Show all faulty lamps

Ready for operation TestMains operation Unit malfunction Maintained lightSystem bus

Info

24.11.201014:21:23

UV: UVS 15Line monitor:

Circuit 1: [Kal.: 0 W, Ist: 0 W]

Select

UV:

Circuits:

UVS 15

1 – 5U< U< U< U< U< U< U< U<

Circuit 2: [Kal.: 0 W, Ist: 29 W]

Circuit 3: [Kal.: 0 W, Ist: 0 W]

Circuit 4: [Kal.: 0 W, Ist: 0 W]

Circuit 5: [Kal.: 0 W, Ist: 0 W]

Luminaire status Faulty luminaires only

System status

Neatly laid out status display, includes system

voltage and battery temperature among other

parameters. Faults are displayed in plain lan-

guage and indicated visually.

Details of substations

Each of up to 7 substations can be displayed

on the central Touch PC. This simplifies the

job of the person tasked with maintenance

and helps them keep an overview of the entire

installation.

Details of luminaire status

Each individual luminaire is displayed at the

control centre. As well as visual error display,

further additional information is made avail-

able. The Touch PC provides details of the

location, light source type, wattage, method

of connection and address of every individual

luminaire.

Page 32: Central OnLite System Zumtobel

Plug-in and networkPortable Touch PC for commissioning

Besides performing major system documentation and display tasks,

the removable unit with LED backlighting also offers substan-

tial benefits when commissioning the ONLITE central CPS system.

This operating and control unit plugs not only into the control centre

but also into every substation – for local commissioning, for example.

Every cabinet is equipped with a four-pole plug connector for this pur-

pose. Two conductors carry the 24 V power supply and two carry data.

The large number of ports is indicative

of the high quality of the unit’s internal

components: the Touch PC has no ro-

tating parts and is therefore extremely

rugged; the Windows CE Pro operating

system is pre-installed and it also has

an SD memory card with a storage

capacity of 512 MB.

A single cable is used for the 24 V sup-

ply voltage and the control bus.

Page 33: Central OnLite System Zumtobel

33

All system information is available

anywhere on the network through Web

services. As well as querying the sys-

tem status, emergency luminaires can

also be visually addressed quickly and

easily. A combination of Powerline and

WLAN link provides the best possible

freedom of action. Using repeaters

eliminates the possibility of any gaps

in radio coverage. This “one-man”

commissioning saves both time and

money.

Luminaire addressing using

wireless network

Touch PCRouter (optional)

Line topology

900 m JY (St) Y 2 x 2 x 0.8 mm

Touch PC

Free topology

500 m JY (St) Y 2 x 2 x 0.8 mm

Touch PC

Total system control (bus line) cable

lengths of 500 m can be realised using

the standard “free topology” version.

Up to 320 m between any nodes.

The length of the system control cable

can be increased to as much as 900 m

by locating terminating resistors ( )

correctly.

Page 34: Central OnLite System Zumtobel

Monitoring of circuits

Types of monitoring

Individual monitoring of luminaires

Monitoring of circuits

using LUXMATE LITENET

Circuit monitoring is used primarily in extensive buildings

which have consistent lighting concepts. Industrial factory

buildings and parking garages are typical examples of such

buildings. Even a circuit error of 10 % can be localised in final

circuits which incorporate luminaires of similar wattages.

Individual monitoring is preferred in buildings such as shop-

ping malls, hospitals or museums where there are a variety

of lighting systems. Addressable, switchable and dimmable

standard luminaires with DALI ballasts are used. Here too, it

is possible to set the desired emergency power level without

any additional components. Besides conventional DC emer-

gency operation, the built-in security function also trips in AC

emergency mode. This guarantees consistent functionality,

even if the control cable is interrupted or short-circuited.

Using LUXMATE LITNET, the leading lighting system which

is used in large office buildings in particular, allows the user

to dispense with a large proportion of ONLITE central CPS

hardware and software for luminaire monitoring. A system

with circuit monitoring is sufficient; individual monitoring

of luminaires is taken care of by LITENET. This way, every

emergency luminaire need only be addressed once at the

time of commissioning.

■ Straightforward design and commissioning ■ Use of standard luminaires with electronic ballasts ■ Lower investment costs but restricted functionality

■ Maximum safety ■ Lower operating costs ■ Maximum functionality

■ Maximum convenience and flexibility■ Many ONLITE central CPS functions are already incor-

porated in the LUXMATE LITENET lighting management

system■ Easy commissioning

Page 35: Central OnLite System Zumtobel

35

Page 36: Central OnLite System Zumtobel

Variable monitoring Anything is possible: circuit, individual luminaires or a combination of both systems

Monitoring of circuits or monitoring of indi-

vidual luminaires may be useful, depending

on the particular application. ONLITE central

CPS caters for specific circumstances, every

station can be designed with both methods of

connection. The modular system design even

makes it possible to mix modules with circuit

monitoring and modules with individual moni-

toring of luminaires within one installation. One

to three bays are available for monitoring mod-

ules depending on the design of the relevant

distribution cabinet. These bays can either be

fitted with modules for circuit-wide monitoring

or individual monitoring of luminaires. Every

module can handle 1 to 20 circuits.

CPS U E00

The sub-distribution board can be

equipped either for circuit moni-

toring or individual monitoring of

luminaires.

S E

Module for Module for

circuit individual

monitoring monitoring of

luminaires

Circuits 0–20 0–20

Number of luminaires 0–400 0–400

Max. power (W) 4700 4700

Max. power per circuit (W) 1300 1300

Fuse per circuit (A) 10 10

Outgoing terminals (mm²) 4 4

Digital potential-free inputs 8–16 8–16

CPS U E30

The sub-distribution board can be

equipped either for circuit moni-

toring or individual monitoring of

luminaires.

CPS H

600 mm

Each of the two bays sections can

be fitted with a sub-distribution

board for circuit monitoring or in-

dividual monitoring of luminaires.

CPS K

Each of the two bays can be fitted

with a module for circuit monitor-

ing or individual monitoring of

luminaires.

CPS H

850 mm

Each of the three bays can be fit-

ted with a sub-distribution board

for circuit monitoring or individual

monitoring of luminaires.

Page 37: Central OnLite System Zumtobel

37

Example

Circuit monitored

S

Example

Individual luminaires monitored

E

Example

Circuit monitored

Example

Combination

SS ES

Example

Individual luminaires monitored

Example

Combination

E E ES

Example

Circuit monitored

Example

Combination

S S

S

S E

E

Page 38: Central OnLite System Zumtobel

High-performance batteriesLarge choice of powerful block batteries

According to EN 50 272 specifi cations, reliable OGiV block

batteries are required for stationary applications. Sealed,

rechargeable batteries with a high discharge rate, these bat-

teries are built to the very latest standards. With a design life

of over 10 years at 20 °C, they meet EUROBAT requirements

for batteries classified as “high performance”. The accessories

required for battery installation are supplied.

12

Service life

(years)

Ambient temperature

(°C)

10

8

6

4

2

5020 25 30 35 40 45

EUROBAT “high per-

formance” class with

design life of more than

10 years at 20 °C

Page 39: Central OnLite System Zumtobel

39

■ Grid-type plates with high discharge rate (lead-calcium)■ Absorptive glass mat technology■ Capacity from 7 to 200 Ah in 12 V blocks■ Housing and lid made of ABS■ Recessed battery terminals with brass core, internally

screwable■ Conforms to DIN EN 60896-21:2004■ Extremely low gassing■ Low self discharge■ 100 % recyclable■ Not classed as dangerous goods for transport by road,

rail, air or inland waterway■ Maintenance free

Battery temperature must be maintained

between +5 °C min. and +30 °C max. in

order to obtain full battery performance. A

nominal temperature of 20 °C is ideal. The

temperature difference between cells or

blocks in a battery bank must not exceed

5 °C.

An electrolyte-resistant floor surface in

the room where batteries are installed and

acid-resistant troughs in cabinets can be

dispensed with because leakproof batter-

ies according to DIN EN 50272-2:2001 are

used.

Notes on battery planning and installation

Battery selection table

Technical data

Trickle-charge voltage: 2.3 V/cell

Temperature compensation: ± 20 mV / 1 °C

Battery type Battery

block-voltage

[V]

Capacity (Ah)

25 °C, 1.8 V / Zelle

8 h 3 h 1 h

Dimensions

L x B x H [mm]

Weight

[kg]

Terminal

connection

12-7.2 12 6.7 5.3 4.8 151 x 65 x 94 2.5 Faston

12-12 12 11.5 9.0 8.2 151 x 65 x 95 3.9 Faston

12-17 12 16.4 15.6 13.8 181 x 77 x 167 5.9 M5

12-24 12 23.2 21.7 17.4 166 x 175 x 125 9.0 M5

12-28 12 27.3 24.9 20.9 165 x 125 x 175 9.7 M5

12-33 12 32.0 27.7 22.9 195 x 130 x 168 11.7 M6

12-45 12 42.9 36.3 29.0 197 x 165 x 170 14.8 M6

12-55 12 54.1 47.0 38.7 229 x 138 x 208 18.0 M6

12-75 12 70.3 57.9 46.2 258 x 166 x 215 24.0 M6

12-80 12 76.9 65.1 53.9 350 x 167 x 179 26.2 M6

12-90 12 86.7 72.6 60.5 306 x 169 x 214 30.0 M6

12-100 12 98.2 86.1 70.0 330 x 171 x 222 33.0 M6

12-120 12 118.1 104.5 81.5 410 x 176 x 277 37.7 M8

12-134 12 138.0 123.6 100.9 341 x 173 x 283 44.8 M8

12-150 12 146.1 124.9 130.0 485 x 172 x 240 46.4 M8

12-190 12 175.0 124.0 130.0 522 x 238 x 223 64.8 M8

12-200 12 198.1 175.3 143.7 522 x 238 x 223 67.0 M8

Page 40: Central OnLite System Zumtobel

info

?

<

>

ONLITE central

Touch PC

SC U+ U-K1 K2 K3 GND 24V A BS1

24V

0V

2 x

5

L1

L2

L3 N PE

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

–2x4S

3S

2

S4

S5

S6

S7

A1 +

A1 –

PE

A2 + +

-

A2 –

Ax +

Ax –

3 3

+

32

–2x1

=~

JY

(S

t) Y

2 x

2 x

0.8

ONLITE central CPS System topology

HVA

HVS

LE loading unit

Emergency-off

By pressing the emergency-off

button, the complete ONLITE

central CPS system (including

all substations) is disconnected

from power supply. This ensures

that emergency forces can safely

do their job. The internal +24 V

supply is carried via an NC switch

(emergency-off) and connected

to the S5 terminal (2 x 1 terminal

strip at the main station), while

the configuration is adjusted to

the emergency-off function using

the Touch PC.

ONLITE central

Remote Interface LPS/CPS

Order no. 22 154 740

Te

mp

era

ture

se

nso

r

Fa

n f

au

lt in

dic

ati

on

to U

VS

1

to U

VS

2

Ma

ins f

rom

HV

A

Battery

216 V

Po

we

r su

pp

ly b

us 2

4 V

Bloc

king

the

sys

tem

Read

ines

s fo

r se

rvic

e

Ope

ratio

n fr

om b

atte

ry

Cent

ralis

ed f

ault

Page 41: Central OnLite System Zumtobel

41

NW1

L1

L2

L3

N

PE

N L3 L2 L1

1 4FINW2

L1

L2

L3

N

PE

N L3 L2 L1

1 4FI+

-

+

-

AD

12

PE

1 2 3 4 5 6 7 8 910

11

12

13

14

15

16

17

18

19

20

AD

12

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

AD

12

AD

12

AD

12

AD

12

AD

12

AD

12

AD

12

AD

12

BD

12

12

BD

12

12

BD

12

12

BD

12

12

BD

12

12

CD

12

12

CD

12

12

CD

12

12

CD

12

12

CD

12

12

DD

12

12

DD

12

12

DD

12

12

DD

12

12

DD

12

12

5x1

3 32

B1+

B1–

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

S1

S2

S8

[...]

5x1

B1+

B1–

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

PE

S1

S2

S8

[...]

E30

JY

(S

t) Y

2 x

2 x

0.8

JY

(S

t) Y

2 x

2 x

0.8

4x2

4x3

5x2

5x3

UVA 1 UVA 2

UVS

circuit monitoring

UVS

individual

monitoring

To next UV

Syste

m b

us

Syste

m b

us

Page 42: Central OnLite System Zumtobel

Emergency lighting as an isolated solutionDesign tips

Regardless of circuit monitoring or individual monitoring of luminaires,

individual emergency and escape sign luminaires are switched by po-

tential-free inputs or permanently used as maintained or non-maintained

luminaires. Built-in functions such as staircase lighting or switching by

variable timers are available.

digital in

DALI

fire-p

roof cab

ling

Data

CPS-U

E30

Individually monitored

E

ES

DALI

Individually monitored

Mains-

emergency

Circuit monitored

8 –16 digital in

Phase detector loop

CPS-K

7 Ah

to

75 Ah

Page 43: Central OnLite System Zumtobel

43

Potential-free inputs Every ONLITE central CPS main station and sub-

station provides eight digital potential-free inputs as standard. The first

input (S1) is designed as a critical circuit and, as a rule, is used for the

phase detector loop. Several phase detector loops or other potential-free

switching inputs can be parameterised. Each of the switching inputs is

connected to the internal 24 V reference potential. Eight other potential-

free inputs are optionally available for each ONLITE central CPS station.

UV1

+ 24 V

1

2

8

9 – 16 potential-free digital inputs

Phase detector loop

Optionally: 8 additional expansion inputs

Mains L´ for external switching inputs

L1L2L3N

PE

N L3 L2 L1

1 4

UVA 1

FI

Mains L´ for external switching inputs

Page 44: Central OnLite System Zumtobel

Emergency lighting with LUXMATE LITENETDesign tips

This system topology is based on an ONLITE central CPS with circuit-

monitored modules (S). All luminaires (general and emergency luminaires)

are metallically separated from one or more common DALI chains and

networked to the LAN hardware (Ethernet, TCP/IP) via the LITENET

netlink. All status in formation is available via the LUXMATE LITENET

network. The ONLITE central CPS operates completely independently,

and autonomously forwards messages concerning battery and charger

to LUXMATE LITENET via the Ethernet network.

www.zumtobel.com/litenet

S

S

S

CPS-BS

33 Ah45 Ah55 Ah75 Ah80 Ah90 Ah

100 Ah120 Ah134 Ah150 Ah

LAN

TC

P/IP

Data

8 –16 digital in

Phase detector loop

Temperature sensor

CPS-H

CPS-U E30

Individually monitored (DALI) combined

with LUXMATE LITENET

to UVA (L/N)

to UVA (L/N)

DALILITENET netlink

DALILITENET netlink

fire-

proo

f ca

blin

g

fire-proof cabling

Page 45: Central OnLite System Zumtobel

45

LITENET netlink

Ethernet TCP/IP

DALI

UV1

L1L2L3N

PE

N L3 L2 L1

1 3

UVA 1

FI

Phase detector also monitors A standard built-in phase detector

monitors the general power supply system. If this power supply fails,

the DALI circuit in question is short-circuited. All DALI emergency and

escape sign luminaires change to system-failure level and immedi-

ately switch to the configured value. This security function is exe-

cuted without communicating with the emergency luminaires.

Page 46: Central OnLite System Zumtobel

System project planningStep-by-step guide to the perfect lighting solution

Do photometric calculations for escape routes

Defi ne percentage Ballast Lumen Factor (BLF) as basis

for output of each emergency luminaire

Plan the locations of escape sign luminaires

Defi ne the circuits in each fi re compartment

Add up power output (PAC and PDC) of all emergency

and escape sign luminaires for each output circuit

Determine battery capacity depending on duration

of battery-powered operation

The entire design process is broken down into individual

design steps in order to ensure a target-oriented approach

when designing emergency lighting. This is a tried-and-

tested strategy for arriving at the optimum solution.

Page 47: Central OnLite System Zumtobel

47

A Light

source

Wattage AC power

[100 %]

230 V/50 Hz

[VA]

DC [W] DC [W] DC [W] DC [W] DC [W] DC [W] DC [W] DC [W] DC [W] DC [W] Control gear / luminaire

Emergency

lighting level 5 % 10 % 15 % 20 % 30 % 40 % 50 % 60 % 70 % 100 %

LED 5.2 - 1.7 - - - - - - 3.5 4.8 EM Power 1 LED DALI / ARTSIGN EW

LED 6.6 - 3.2 - - - - - - 5.0 6.3 EM Power 1 LED DALI / ARTSIGN ED

LED 8.1 - 2.4 - - - - - - 5.0 7.7 EM Power 2 LED DALI / PURESIGN AW

LED 11.1 - 2.8 - - - - - - 8.1 10.8 EM Power 2 LED DALI / PURESIGN AD

LED 8.1 - - - - - - - - - 7.7 EM Power 1 LED DALI / COMSIGN II LED

LED 8.8 - - - - - - - - - 8.5 EM Power 1 LED DALI / PROOFSIGN

LED 11.1 - 2.8 - - - - - - 8.1 10.8 EM Power 2 LED DALI / SQUARESIGN

LED 11.1 - 2.8 - - - - - - 8.1 10.8 EM Power 2 LED DALI / FREESIGN

LED 5.4 - - - - - - - - - 5.0 EM Power 1 LED DALI / RESCLITE

T16 14 W 16.3 6.8 7.5 8.1 8.4 9.6 11.0 11.9 13.2 14.0 14.2 PCA 1x14/24 T5 EXCEL one4all lp xitec

T16 2/14 W 31.7 10.9 12.2 13.8 14.8 17.4 20.3 22.5 25.3 27.2 27.5 PCA 2x14/24 T5 EXCEL one4all lp xitec

T16 21 W 23.8 6.6 7.8 9.0 9.8 11.7 14.0 15.7 18.0 19.5 19.8 PCA 1x21/39 T5 EXCEL one4all lp xitec

T16 2/21W 46.0 11.8 13.8 16.1 17.7 21.7 26.1 29.4 34.0 37.3 37.8 PCA 2x21/39 T5 EXCEL one4all lp xitec

T16 28 W 30.9 7.2 8.7 10.3 11.5 14.2 17.3 19.7 22.7 24.9 25.3 PCA 1x28/54 T5 EXCEL one4all lp xitec

T16 2/28 W 62.1 13.2 15.8 18.8 21.0 26.2 32.0 36.6 42.5 46.8 47.5 PCA 2x28/54 T5 EXCEL one4all lp xitec

T16 35 W 38.8 8.0 10.6 12.5 13.9 17.1 20.9 23.8 27.5 30.2 30.7 PCA 1x35/49/80 T5 EXCEL one4all lp xitec

T16 2/35 W 76.4 14.0 17.5 21.2 24.1 30.8 38.1 44.0 51.2 56.4 57.2 PCA 2x35/49 T5 EXCEL one4all lp xitec

T16 24 W 25.8 8.0 9.1 10.4 11.2 13.3 16.0 18.1 20.4 21.9 22.1 PCA 1x14/24 T5 EXCEL one4all lp xitec

T16 2/24 W 52.1 13.4 15.7 18.3 20.2 25.1 30.4 34.5 39.8 43.5 44.2 PCA 2x14/24 T5 EXCEL one4all lp xitec

T16 39 W 42.3 8.8 10.8 13.0 14.7 18.8 23.0 26.2 30.7 34.0 34.5 PCA 1x21/39 T5 EXCEL one4all lp xitec

T16 2/39 W 84.1 15.9 19.8 24.2 27.6 35.4 44.4 51.6 60.1 66.2 67.3 PCA 2x21/39 T5 EXCEL one4all lp xitec

T16 49 W 53.7 10.2 12.6 15.3 17.4 22.2 27.5 31.7 37.0 40.9 41.5 PCA 1x35/49/80 T5 EXCEL one4all lp xitec

T16 2/49 W 105.6 16.7 21.7 27.0 31.3 41.2 51.8 60.4 71.4 79.6 81.0 PCA 2x35/49 T5 EXCEL one4all lp xitec

T16 54 W 60.0 11.3 14.1 17.3 19.8 25.3 31.5 36.4 42.6 47.2 48.0 PCA 1x28/54 T5 EXCEL one4all lp xitec

T16 2/54 W 118.4 20.6 26.4 32.7 37.8 49.1 61.4 71.3 83.3 92.0 93.5 PCA 2x28/54 T5 EXCEL one4all lp xitec

T16 80 W 86.9 14.2 18.3 22.8 26.5 34.8 43.8 51.1 60.0 66.5 67.5 PCA 1x35/49/80 T5 EXCEL one4all lp xitec

T26 1/18 W 26.0 8.5 9.5 10.5 12.0 13.0 13.5 16.5 PCA excel one4all

T26 2/18 W 43.0 16.0 17.5 19.0 23.0 25.0 26.5 28.0 PCA excel one4all

T26 1/30 W 34.0 9.5 11.5 13.0 15.5 18.5 20.5 25.0 PCA excel one4all

T26 2/30 W 61.0 16.0 19.0 22.0 28.0 32.5 37.5 45.5 PCA excel one4all

T26 1/36 W 42.0 12.5 15.0 16.5 20.0 22.0 24.5 28.5 PCA excel one4all

T26 2/36 W 74.0 22.5 26.5 30.5 36.0 40.0 43.5 53.5 PCA excel one4all

T26 1/58 W 61.0 17.5 21.0 24.5 29.0 33.5 37.5 45.5 PCA excel one4all

T26 2/58 W 110.0 31.5 37.5 44.5 53.5 60.5 67.5 83.5 PCA excel one4all

TC-L/F 1/18 W 24.0 6.0 6.5 7.5 8.5 9.5 10.5 12.5 PCA excel one4all

TC-L/F 2/18 W 41.0 9.0 10.5 12.0 14.0 16.5 18.5 23.5 PCA excel one4all

TC-L/F 1/24 W 31.0 9.0 11.0 12.5 15.0 17.0 19.0 22.5 PCA excel one4all

TC-L/F 2/24 W 53.0 14.5 17.5 20.5 25.5 30.5 34.5 42.5 PCA excel one4all

TC-L/F 1/36 W 39.0 12.0 14.5 16.5 20.5 24.0 26.5 32.5 PCA excel one4all

TC-L/F 2/36 W 73.0 18.5 22.5 27.0 33.5 40.0 46.0 59.5 PCA excel one4all

TC-L/F 1/40 W 50.0 14.5 17.5 20.5 23.5 26.5 29.5 36.5 PCA excel one4all

TC-L/F 2/40 W 90.0 26.5 31.0 35.5 44.5 51.5 57.5 72.5 PCA excel one4all

TC-L/F 1/55 W 63.0 16.5 23.0 29.5 28.5 34.5 39.5 52.5 PCA excel one4all

TC-L/F 2/55 W 121.0 30.5 38.5 46.5 58.0 67.5 76.5 101.5 PCA excel one4all

TC-S/E 1/11 W 19.0 6.5 7.5 8.0 9.5 10.5 11.5 13.0 PCA excel one4all

TC-S/E 2/11 W 33.0 9.5 11.5 13.0 12.5 13.5 14.5 24.0 PCA excel one4all

TC-D/E 1/13 W 20.0 6.5 8.0 8.5 10.0 11.0 12.0 14.0 PCA excel one4all

TC-D/E 2/13 W 33.0 10.0 12.0 13.5 16.0 19.0 21.5 26.0 PCA excel one4all

TC-D/T 1/18 W 24.0 7.0 8.5 9.5 11.5 13.5 15.0 18.0 PCA excel one4all

TC-D/T 2/18 W 43.0 13.0 15.5 17.5 21.5 24.5 27.5 34.0 PCA excel one4all

TC-D/T 1/26 W 33.0 10.0 12.0 13.5 16.5 18.5 20.5 24.5 PCA excel one4all

TC-D/T 2/26 W 57.0 16.5 20.5 23.5 29.5 34.0 38.5 46.5 PCA excel one4all

TC-T/E 1/32 W 36.0 10.5 13.5 15.5 19.5 22.5 25.5 30.5 PCA excel one4all

TC-T/E 2/32 W 66.0 17.5 22.5 27.0 34.5 41.5 48.0 59.5 PCA excel one4all

TC-T/E 1/42 W 47.0 12.0 15.0 17.5 22.5 27.5 31.0 39.5 PCA excel one4all

TC-T/E 2/42 W 88.0 23.5 29.0 34.5 43.5 52.0 59.5 77.5 PCA excel one4all

TC-DD 1/55 W 60.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 PCA excel one4all

NV DSI 70 W 70.0 58.0 58.0 58.0 58.0 58.0 58.0 58.0 TEL 70 VA

NV DSI 105 W 105.0 85.0 85.0 85.0 85.0 85.0 85.0 85.0 TEL 105 VA

NV DSI 150 W 150.0 90.0 90.0 90.0 90.0 90.0 90.0 90.0 TEL 150 VA

NV DSI 210 W 210.0 137.0 137.0 137.0 137.0 137.0 137.0 137.0 TEL 210 VA

NV DALI 105 W 105.0 85.5 85.5 85.5 85.5 85.5 85.5 85.5 TEL one4all 105 VA

NV DALI 150 W 150.0 90.5 90.5 90.5 90.5 90.5 90.5 90.5 TEL one4all 150 VA

Ballast/lumen factor table

Page 48: Central OnLite System Zumtobel

Specify battery size (OGiV block batteries) For optimum battery dimensioning, add 25 % reserve capacity to these values

(EN 50171 - 6.12.4).B

Battery set

DC output in W

Battery power

25 °C, 1.8 V per cell

7 Ah 12 Ah 17 Ah 24 Ah 28 Ah 33 Ah 45 Ah 55 Ah 75 Ah 80 Ah 90 Ah 100 Ah 120 Ah 150 Ah 190 Ah 200 Ah

216 V system 1 h 864 1.685 2.786 3.618 4.417 4.752 5.886 7.765 9.558 10.778 12.312 14.256 17.064 21.384 24.840 28.404

216 V system 3 h 454 662 1.075 1.415 1.782 2.030 2.549 3.262 4.180 4.644 5.119 6.145 7.171 8.888 10.638 12.528

216 V system 8 h 170 292 430 606 761 875 1.166 1.469 2.009 2.171 2.387 2.754 3.316 4.158 4.730 5.573

Survey ventilation conditions Data for ventilation of battery rooms according to EN 50272-2.

Battery capacity

C10 at 1.8 V per cell

7 Ah 12 Ah 17 Ah 24 Ah 28 Ah 33 Ah 45 Ah 55 Ah 75 Ah 80 Ah 90 Ah 100 Ah 120 Ah 134 Ah 150 Ah 190 Ah 200 Ah

Required air volume fl ow

rate in case of artifi cial

ventilation [m³/h]

0.04 0.07 0.73 1.04 1.21 1.43 1.94 2.38 3.24 3.64 3.89 4.32 5.18 5.79 6.48 8.21 8.64

Cross-sectional area of

ventilation openings with

natural ventilation [cm²]

1.06 1.81 20.44 29.12 33.88 40.04 54.32 66.64 90.72 96.88 108.92 120.96 145.04 162.12 181.44 229.88 241.92

C

This table shows the maximum power requirements of a

system. To provide for the permissible voltage drop of cable

dimensioning and to protect the system, the total installed

load actually calculated must be used.

Power requirements of CPS system

Total connected load [VA]

7,000 14,000 21,000 30,000

Fuse protection

Switch-disconnector-fuse [A]

80

Single phase

80

Two phase

80

Three phase

100

Three phase

D

Where possible, choose a standard Cu cross-section of

1.5 mm² in order to obtain optimum expansion.

* Free topology is recommended, system bus need not be

adapted for this (see page 33).

DALI cable lengths

System bus cable lengths

DALI control circuit cable length [m]

300 200 150 100

Recommended Cu cross-section

with standard wiring [mm²] 1.5 1.0 0.8 0.5

DATA bus cable length [m]

500 (standard equipment) 900

Line topology JY (St) Y 2 x 2 x 0.8 mm

Free topology * JY (St) Y 2 x 2 x 0.8 mm

Dimension cable appropriately depending on distance and

connecting cable to ensure permissible voltage drop.

* Depending on cable length

Indication = minimum cross-section

Power requirements of ONLITE central substation (E00/E30)

Total installed load [VA]

1,000 2,000 3,000 3,500 4,000 4,300

Fuse protection,

Neozed fuse [A] 16 16 20 20 25 25

Calculation for 50 m

cable length * [mm²] 4 10 10 16 16 16

Calculation for 100 m

cable length * [mm²] 6 16 25 25 35 35

E

Circuits are protected by 6.3 A fuses suitable for DC on

both poles. 3 A, 15 A or 10 A fuses can be used for specific

projects.

ONLITE central CPS outgoing circuits

Output power [W]

435 870 (standard equipment) 1380

Fuse protection

Outgoing circuit [A] 3.15 6.30 10.00

Max. current carrying capacity [A] 1.90 3.80 6.00

F

G

H

Page 49: Central OnLite System Zumtobel

DALI

Data

Data

CPS-U

E30

CPS-K

DALI

E

CPS-U

E30

DALI

E

E GDALI cable lengths

Power and fuse protection

Individual monitoring

Individual monitoring

Individual monitoring

EConnected loads

ABallast lumen factor

AC/DC power

See page 36/37 for

module versions

Battery selection

B

D Power and fuse protection

COutlet air and

volume of air

F

CInlet air and volume of air

System bus cable lengths

H

fire

-pro

of

ca

blin

g

fire-proof cabling

Page 50: Central OnLite System Zumtobel

www.zumtobel.com/onlite

ONLITE central LPS

Self-contained group

battery system for excellent

failure safety.

The ONLITE group battery sys-tem excels by combining maxi-mum functionality with seamless integration into the general light-ing system. Several self-con-tained systems ensure straight-forward installation and quick commissioning.

Characteristics– Four basic sizes: power in

emergency mode 360, 720, 1080 or 1440 W

– 3 to 12 circuits, each for 20 luminaires

– Monitoring of individual lumi-naires and circuit monitoring

– Mixed operation within one cir-cuit is possible

– Individually adjustable emer-gency power level for every luminaire

Benefits– Straightforward ordering from

catalogue thanks to standard-ised basic sizes

– Extremely simple installation without E30 fire-resistant cables within fire compartment (not UK)

– Highly flexible in the event of changes and extensions

– Optimised battery capacities reduce both costs and envi-ronmental pollution

– Easy connection to lighting management system

ONLITE central LPS

Page 51: Central OnLite System Zumtobel

ON

LIT

E P

rod

uc

t C

ata

log

ue

51

System application ONLITE CENTRAL

PLC-Relais

PLC-Interface

Circuit 1

TECTON

PLC-Interface TECTON

Energy-saving lamp

Escape sign luminaire

Momentary-action switch L’

L1 Circuit 2

Circuit 3

Connection to lighting management systemSwitch inputs S1/S2/S3 and L‘- function are not available in case of connection to lighting management system!

Staircase lighting func-tion

Sub-distribution board

EPS 360

EPD

Switch inputs are only available if connection to lighting management system is not activated!

Momentary-action switch L’

Limit values for group battery systems according to EN50171:Output power:Standby operating time 1 h: 1,500 WStandby operating time 3 h: 500 W

Supplied with OGiV block batteries required for stationary applications according to EN50272. The sealed, rechargeable bat-teries with a high discharge rate are built to the very latest standards. With a design life of 10 years at 20 °C they meet EUROBAT requirements for batteries classified as “high performance”.

ONLITE CENTRAL LPS 360

■ Central supply and monitoring of emergency and escape sign lumi-naires/version central

■ Individual monitoring of luminaires ■ Backlit touch panel for control/pro-

gramming and visualisation ■ Test log book function > 3 years ■ 3 output circuits each for a max. of

20 luminaires ■ Power line communication to lumi-

naires ■ Housing sheet-steel cabinet incl. bat-

tery compartment ■ All cable outputs have been prewired

on a terminal strip ■ Charging unit for lead-gel batteries

incl. temperature display ■ Set of batteries included in the supply ■ Incl. interface box ■ Voltage: 230 V  ±10 %, frequency:

50/60 Hz Output voltage: 230 V AC (mains operation), 230 V DC (emer-gency operation)

■ ONLITE Central LPS 360: Max. installed load: 1.7 kVA (at full load), output power of circuits: circuit 1–3: 550 VA AC (4AT) each, max. 120 W DC

kg Order no.

ONLITE central LPS 360 360 W 1 h 10 JB 32 Ah 2 x 12 V Housing model: 02 48.0 22 156 815

360 W 3 h 10 JB 61 Ah 2 x 12 V Housing model: 03 89.0 22 156 817

ONLITE central LPS 360 Nport2 Ethernet version 360 W 1 h 10 JB 32 Ah 2 x 12 V Housing model: 02 48.0 22 154 543

360 W 3 h 10 JB 61 Ah 2 x 12 V Housing model: 03 89.0 22 154 544

500

800

420

720

125°

Typ 2

Ø 9 mm202

600

1000

520

920

125°

Typ 3

Ø 9 mm202

Page 52: Central OnLite System Zumtobel

ONLITE central LPS

ONLITE CENTRAL LPS 720 / 1080 / 1440

■ Central supply and monitoring of emergency and escape sign lumi-naires/version central

■ Individual monitoring of luminaires ■ Backlit touch panel for control/pro-

gramming and visualisation ■ Test log book function > 3 years ■ 3 output circuits each for a max. of

20 luminaires ■ Power line communication to lumi-

naires ■ Housing sheet-steel cabinet incl. bat-

tery compartment ■ All cable outputs have been prewired

on a terminal strip ■ Charging unit for lead-gel batteries

incl. temperature display ■ Set of batteries included in the supply ■ Incl. interface box ■ Voltage: 230 V  ±10 %, frequency:

50/60 Hz Output voltage: 230 V AC (mains operation), 230 V DC (emer-gency operation)

■ ONLITE Central LPS 720: Max. installed load: 3.4 kVA (at full load), output power of circuits: circuit 1–6: 550 VA AC (4AT) each, max. 120 W DC

■ ONLITE Central LPS 1080: Max. installed load: 5.0 kVA (at full load), output power of circuits: circuit 1–9: 550 VA AC (4AT) each, max. 120 W DC

■ ONLITE Central LPS 1440: Max. installed load: 6.7 kVA (at full load), output power of circuits: circuit 1–12: 550 VA AC (4AT) each, max. 120 W DC

Order no.

CENTRAL LPS 720 720 W 1 h 10 JB 32 Ah 4 x 12 V Housing model: 03 22 156 821

720 W 3 h 10 JB 61 Ah 4 x 12 V Housing model: 03 22 156 822

CENTRAL LPS 720 Nport2 Ethernet version 720 W 1 h 10 JB 32 Ah 4 x 12 V Housing model: 03 22 154 548

720 W 3 h 10 JB 61 Ah 4 x 12 V Housing model: 03 22 154 549

CENTRAL LPS 1080 1080 W 1 h 10 JB 32 Ah 6 x 12 V Housing model: 04 22 156 824

1080 W 3 h 10 JB 61 Ah 6 x 12 V Housing model: 04 22 156 825

CENTRAL LPS 1080 Nport4 Ethernet version 1080 W 1 h 10 JB 32 Ah 6 x 12 V Housing model: 04 22 154 551

1080 W 3 h 10 JB 61 Ah 6 x 12 V Housing model: 04 22 154 552

CENTRAL LPS 1440 1440 W 1 h 10 JB 32 Ah 8 x 12 V Housing model: 04 22 156 827

1440 W 3 h 10 JB 61 Ah 8 x 12 V Housing model: 04 22 156 828

CENTRAL LPS 1440 Nport4 Ethernet version 1440 W 1 h 10 JB 32 Ah 8 x 12 V Housing model: 04 22 154 554

1440 W 3 h 10 JB 61 Ah 8 x 12 V Housing model: 04 22 154 555

600

1000

520

920

125°

Typ 3

Ø 9 mm202

900

1590

720

1480

125°

Typ 4

Ø 9 mm 30 mm

40

202

Page 53: Central OnLite System Zumtobel

53

ONLITE CENTRAL PHASE DETECTOR

■ Three-phase monitoring module installed in switch cabinet, DIN-rail mounting

■ Checks three-phase systems for undervoltage and phase failure; also detects if neutral conductor goes open-circuit

■ 3 LEDs for status display (mains volt-age applied)

■ 2 change-over contacts ■ Voltage range: 230 V AC, max. volt-

age of outer conductor: 450 V AC Wattage: 15 W Switching contact: 125 V AC/DC, 2 A (60 W) Monitoring window: Unetz 0.6–0.85 Unenn

Order no.

ONLITE central EPD 22 156 808

Suitable for use in EN 50172 compliant installations (DIN VDE0108-100).

90 35

35 59

ONLITE CENTRAL POWER SUPPLY

■ Power supply module for Section central GSM

■ Power: voltage 24 V AC, current 350 mA

■ Switch-cabinet module

L/W/H DB Modules Order no.

ONLITE Power Supply 35/90/59 2 22 156 809

90 35

35 59

Page 54: Central OnLite System Zumtobel

ONLITE central LPS

ONLITE CENTRAL PRINTER

■ For printing out test logs ■ Insensitive to interferences and short

interruptions of infrared connection ■ Sturdy, fixed thermo-print line ■ Battery pack and mains unit included

in scope of supply ■ Incl. 4 reels of thermopaper

Order no.

ONLITE IR-Printer 22 154 522

90

467

6

160

ONLITE CENTRAL REMOTE INTERFACE

■ Remote indication of system status via LEDs

■ Emergency lighting installation blocked using lockswitch

■ Max. 24 V AC/DC, max. 2 A ■ Connection to the floating signalling

contact of the central section

Order no.

ONLITE central Remote Interface LPS/CPS 22 154 740

80

32

95

ONLITE CENTRAL INTERFACE FOR LUMINAIRES

■ PLC-DALI module converts the Powerline signal into a DALI signal

■ Lamp faults are reported back to the emergency power supply (section central)

■ 20 physically adjustable addresses ■ SET DC function via PLC to electronic

ballast (emergency lighting level can be adjusted in electronic ballast)

■ Switching and dimming without addi-tional control line

■ With integrated L´ switching input ■ The cable from the emergency power

supply to the PLC may have a max. length of 300 m

■ Input voltage: 230 V AC / 230 V DC Wattage: AC mode < 2 W (without load), DC mode < 0.5 W (without load)

■ Luminaire installation module (max. distance between module and luminaire is 10 m)

Order no.

ONLITE central PLC DALI Interface II 22 162 080

160

149

4,5

21

30

0

2

67

134

5

89 + 0

+10

L'LN

101234567

89

Luminaire address Adresss switch 1 Adress switch 2

1 0 1

2 0 2

3 0 3

. . .

.. .. ..

10 0 10

11 10 1

12 10 2

. . .

.. .. ..

20 10 10

Mains/Netz

Failure/Stˆrung

ZUMTOBEL STAFFDAS LICHT

SEPS 360

Æ

Fuse / Sicherung

L NPE

O3O2 U3U2O1U1

S1 S2 D1 D2Rx GndTx +_

12 14T1

11T3 P1 P2

Relais 122 2421

Relais 232 3431

Relais 3T2

230 V/AC/DC power supply

PLC Powerline communcation

230 V AC/DC

230 V AC/DC

up to 20 luminaires per circuit

ONLITEPLC-Relay

ONLITEPLC-Relay

Adress switch 1

Adress switch 2

Powerline in

230 V~ 50Hz

Page 55: Central OnLite System Zumtobel

55

ONLITE CENTRAL RELAY FOR LUMINAIRES

■ PLC relay module switches AC/DC-compatible consumers via the Power-line signal

■ Lamp faults are reported back to the emergency power supply (section central)

■ 20 physically adjustable addresses ■ Switching without additional control

line ■ With integrated L´ switching input ■ Input voltage: 230 V AC / 230 V DC

Wattage: AC mode < 2 W (without load), DC mode < 0.5 W (without load)

■ Luminaire installation module ■ The cable from the emergency power

supply to the PLC may have a max. length of 300 m

Order no.

ONLITE central PLC DALI Relais 22 156 805

190

180

4,5

28

30

0

2

67

134

5

89 + 0

+10

L'LN

101234567

89

Luminaire address Adresss switch 1 Adress switch 2

1 0 1

2 0 2

3 0 3

. . .

.. .. ..

10 0 10

11 10 1

12 10 2

. . .

.. .. ..

20 10 10

Mains/Netz

Failure/Stˆrung

ZUMTOBEL STAFFDAS LICHT

SEPS 360

Æ

Fuse / Sicherung

L NPE

O3O2 U3U2O1U1

S1 S2 D1 D2Rx GndTx +_

12 14T1

11T3 P1 P2

Relais 122 2421

Relais 232 3431

Relais 3T2

230 V/AC/DC power supply

PLC Powerline communcation

230 V AC/DC

230 V AC/DC

up to 20 luminaires per circuit

ONLITEPLC-Relay

ONLITEPLC-Relay

Adress switch 1

Adress switch 2

Powerline in

230 V~ 50Hz

ONLITE CENTRAL ELECTRONIC BALLAST FOR LUMINAIRES

■ PLC electronic ballast module for operating one T5 8 W fluorescent lamp

■ Lamp faults are reported back to the emergency power supply (section central)

■ 20 physically adjustable addresses ■ Switching and dimming without addi-

tional control line ■ Input voltage: 230 V AC / 230 V DC

Power input: AC operation < 11 VA ■ Luminaire installation module ■ The cable from the emergency power

supply to the PLC may have a max. length of 300 m

Order no.

ONLITE central PLC EVG 8 W 22 156 799

230

219

4,5

28

30

Page 56: Central OnLite System Zumtobel

ONLITE GO-ON package

IP30

■ Visualisation package for graphic display and monitoring of up to 500 emergency or escape sign luminaires

■ Visualisation software with single user licence enabled

■ Commissioning/configuration of a Section Central or an SB 128 CTP Controller

■ Pre-defined GO plan files for Section Central 360, 720, 1080, 1440 and SB 128 Controller

■ Caption for up to 60 emergency or escape sign luminaires

■ Mouse, German keyboard and Y-plug ■ Rail-mounted PC with external

230 V / 24 V power pack

Order no.

GO-ON package ONLITE visualisation computer 22 154 418

12

1

187 69

63

GO-ON GO GO

RS-232 RS-232 RS-232 RS-232 RS-232 RS-232

RS-232 RS-232

HUB

TCP/IP TCP/IP

Nport4 Nport2

24V/GND DC-IN

VGA MS/KB COM2 COM1

LAN1 LAN2

RS-232 RS-232 RS-232 RS-232

EPS 360 EPS 360 EPS 360 EPS 360

SB 128 SB 128

Client PC

AN TCP IP

RJ 45 crossed network cable

Extension line RS-232 (uncrossed) max. 2 m

ONLITE central LPS

Page 57: Central OnLite System Zumtobel

www.zumtobel.com/onlite

ONLITE central CPS

Central Battery System –

safety ensured by modular

large-size unit.

The progress of ONLITE emer-gency lighting systems is based on the strategy - unique in the world – of using any DALI lumi-naire as an emergency luminaire, monitoring it and supplying it with emergency power in case of an emergency. Maintenance work is done fully automatically, faults are displayed clearly.

New, and especially suitable for projects involving more than 100 emergency luminaires: the CPS Central Power System with a mobile monitoring and programming unit, which comes as a touch-sensitive panel with colour display, Ethernet and Web browser link, USB port and multimedia card, relying on state-of-the-art technology as well as utmost convenience, easy operation and flexibility.

57

Page 58: Central OnLite System Zumtobel

ONLITE central CPS

ONLITE CENTRAL CPS K

■ Central battery system in compact cabinet

■ Fully automatic execution of tests and documentation in electronic test book

■ 2 x 0–20 circuits, with monitoring of individual luminaires or circuit, also mixed monitoring mode in units of 20

■ All cable outputs have been prewired on a terminal strip

■ 7" Touch PC for operating and visual-ising the installation

■ Ethernet connection for web-browser based system-networking and visuali-zation

■ USB/MMC or SD for test book archiv-ing

■ Sheet steel housing in powder-coated RAL 7035 finish

■ Power per circuit (AC/DC): 1300 W ■ Max. 20 luminaires per circuit ■ In single-luminaire monitoring mode,

each DALI luminaire can be control-led and monitored individually. Mixed operation possible within one circuit.

■ Available models: Left/right door hinge ■ Power can be increased up to 21 kVA ■ 0–7 outlets for sub-stations ■ OGI monobloc batteries 216 V,

7–75 Ah in combi-cabinet with tem-perature-controlled U/I charging

Order no.

ONLITE central CPS K 22 154 689

18

00

600850

CPS K

Battery Batteries CPS-K Total weight

ets 18 blocks CPS-K

(kg) (kg) (kg)

7 Ah 45 180 ~ 225

12 Ah 71 180 ~ 251

17 Ah 107 180 ~ 287

24 Ah 162 180 ~ 342

28 Ah 175 180 ~ 355

33 Ah 211 180 ~ 391

45 Ah 267 180 ~ 447

55 Ah 324 180 ~ 504

75 Ah 432 180 ~ 612

Dimensions (H x W x D) 1800 x 850 x 600 mm

max. 2 outputs for substations

otal power 7 – 30 kVA

Circuits internal 0 – 40

Outgoing units to external UVS max. 7

only possible if there are max. 20 circuits internal)

use protection UVS to 35 A

Outgoing terminals UVS 16 mm²

Battery voltage (18 blocks) 216 V

Battery capacity range 7–75 Ah

thernet port 1

Potential free outputs 5

Digital potential-free inputs 8–16 (per UVS)

ONLITE CENTRAL CPS U

■ Sub-distribution system for emer-gency lighting housed in sheet-steel cabinet in powder-coated RAL 7010 finish

■ 1–20 circuits, monitoring of individual luminaires or circuit

■ All cable outputs have been prewired on a terminal strip

■ Power per circuit (AC/DC): 1300 W ■ Max. 20 luminaires per circuit ■ In single-luminaire monitoring mode,

each DALI luminaire can be control-led and monitored individually. Mixed operation possible within one circuit.

■ Available models: Left/right door hinge ■ E30 model possible RAL 7035

includes cable cooling attachment

Order no.

ONLITE central CPS U E00 22 154 691

ONLITE central CPS U E30 22 154 692

CPS U E00

80

0

300 161

1.3

76

50

2

195374

334CPS U E30

Page 59: Central OnLite System Zumtobel

59

ONLITE CENTRAL CPS H

■ Central battery facility housed in sheet steel cabinet in powder-coated RAL 7035 finish

■ Fully automatic execution of tests and documentation in electronic test book

■ 3 x 0–20 circuits, with monitoring of individual luminaires or circuit, also mixed monitoring mode in units of 20

■ All cable outputs have been prewired on a terminal strip

■ Ethernet connection for web-browser based system-networking and visuali-zation

■ 7" Touch PC for operating and visual-ising the installation

■ USB/MMC or SD for test book archiv-ing

■ Power per circuit (AC/DC): 1300 W ■ Max. 20 luminaires per circuit ■ In single-luminaire monitoring mode,

each DALI luminaire can be control-led and monitored individually. Mixed operation possible within one circuit.

■ Please order batteries separately for fitting in external battery box or on battery rack

■ Available models: Left/right door hinge ■ Power increase up to 30 kVA ■ 0–12 outlets for substations

Order no.

ONLITE Central CPS H 22 154 690

18

00

600850

CPS H E00 Rmax. 40 circuits

CPS H E00 Rmax. 60 circuits

600

CPS-H main station technical data

Total power 7 – 30 kVA

Circuits internal 0 – 60

Fuse UVS up to 35 A

Battery outgoing terminals 35 mm²

Battery capacity range 7–200 Ah (ext. battery)

Ethernet port 1

Potential free outputs 5

Digital potential free inputs 8–16

Dimensions (H x W x D) 1800 x 600 x 600 mm

(max. 40 internal circuits; no outputs for substation)

Total weight CPS-H 114 kg

Outgoing units to external UVS max. 12 (240 circuits external)

Dimensions (H x W x D) 1800 x 850 x 600 mm

(max. 60 internal circuits; with outputs for substation)

Outgoing terminals UVS 16 mm²

Total weight CPS-H 180 kg

ONLITE CENTRAL CPS BS

■ Sheet-steel battery cabinet in powder-coated RAL 7035 finish with compartment trays for batteries

■ Electrolyte capture tray built into base of cabinet

■ Temperature sensor can be installed in battery cabinet

■ Connecting leads included with bat-teries

■ OGI monobloc batteries 216 V, 7–200 Ah

■ Available models: Left/right door hinge

Order no.

ONLITE central CPS BS 33–75 Ah 22 154 693

ONLITE central CPS BS 80–134 Ah 22 162 076

ONLITE central CPS BS 120 Ah 22 162 077

ONLITE central CPS BS 150 Ah 22 162 078

ONLITE central CPS BS 190+200 Ah 22 162 079

External battery cabinet (CPS-BS) Set of Batteries CPS-BS CPS-BS Total weight

batteries 18 blocks H x W x D CPS-BS

(kg) (mm) (kg) (kg)

7 Ah 45 1600 x 600 x 600 80 125

12 Ah 71 1600 x 600 x 600 80 151

17 Ah 107 1600 x 600 x 600 80 187

24 Ah 162 1600 x 600 x 600 80 242

28 Ah 175 1600 x 600 x 600 80 255

33 Ah 211 1600 x 600 x 600 80 291

45 Ah 267 1600 x 600 x 600 80 347

55 Ah 324 1600 x 600 x 600 80 404

75 Ah 432 1600 x 600 x 600 80 512

80 Ah 472 1800 x 850 x 600 100 572

90 Ah 540 1800 x 850 x 600 100 640

100 Ah 540 1800 x 850 x 600 100 640

120 Ah 679 1800 x 950 x 600 130 809

134 Ah 765 1800 x 950 x 600 130 895

150 Ah 836 1800 x 1100 x 600 150 986

190 Ah 1800 x 1800 x 600

1167 1800 x 600 x 600 260 1427

200 Ah 1800 x 1800 x 600

1206 1800 x 600 x 600 260 1466

Page 60: Central OnLite System Zumtobel

ONLITE central CPS

ONLITE CENTRAL CPS BG

■ PE sinter-coated, fully insulated, acid-resistant longitudinal and transverse supports

■ Height-adjustable feet made of insu-lating plastic

■ Quick, easy and clean to install ■ Withstand voltage to DIN VDE 0100

and DIN VDE 0510 TV ■ Simple grounding facility

L/W/H kg Order no.

Battery rack ONLITE central BG BTX LS 17 600/500/632 27.0 22 154 694

ONLITE central BG BTX LS 24-75 600/715/1074 43.0 22 161 977

ONLITE central BG BTX LS 80-134 1200/500/1074 39.0 22 161 978

ONLITE central BG BTX LS 150 1200/715/1074 50.0 22 161 979

ONLITE central BG BTX LS 190-200 1500/715/1074 67.0 22 161 980

L

H

B

ONLITE CENTRAL monobloc battery

■ OGiV high-rate pasted plates (lead/calcium)

■ DIN EN 60896-2:1997 compliant ■ Absorbent glass mat technology ■ ABS case and lid ■ Recessed threaded bras post termi-

nals ■ E xtremely low gas ■ Low self-discharge ■ 100 % recyclable ■ Units are maintenance free ■ 17–200 Ah capacity in 12 V mono-

blocs

L/W/H Order no.

10-year monobloc battery Accu Pb/10 12 V 7 Ah, connection: Faston 151/65/94 22 162 309

Accu Pb/10 12 V 12 Ah, connection: Faston 151/98/95 22 162 307

Accu Pb/10 12 V 17 Ah, connection: M5 181/77/167 22 154 695

Accu Pb/10 12 V 24 Ah, connection: M5 166/175/125 22 154 696

Accu Pb/10 12 V 28 Ah, connection: M5 165/125/182 22 154 697

Accu Pb/10 12 V 33 Ah, connection: M6 195/130/172 22 154 698

Accu Pb/10 12 V 45 Ah, connection: M6 197/165/170 22 154 699

Accu Pb/10 12 V 55 Ah, connection: M6 239/132/210 22 154 700

Accu Pb/10 12 V 75 Ah, connection: M6 258/166/215 22 154 702

Accu Pb/10 12 V 80 Ah, connection: M6 350/167/179 22 154 703

Accu Pb/10 12 V 90 Ah, connection: M6 306/169/214 22 154 704

Accu Pb/10 12 V 100 Ah, connection: M6 330/171/222 22 154 705

Accu Pb/10 12 V 120 Ah, connection: M8 410/176/277 22 154 706

Accu Pb/10 12 V 134 Ah, connection: M8 342/172/277 22 154 707

Accu Pb/10 12 V 150 Ah, connection: M8 485/172/240 22 154 708

Accu Pb/10 12 V 190 Ah, connection: M8 522/238/223 22 154 709

Accu Pb/10 12 V 200 Ah, connection: M8 522/238/223 22 154 710

Art. no.

battery

rack

for

battery

set

Weight

battery set

[kg]

Positioning

of

batteries

Tiers Rows Height (HB)

above battery

[mm]

22154694 17 Ah 107 horizontal 2 2 830

22161977 24 Ah 162 longitudinal 3 2 1300

28 Ah 175 horizontal 3 2 1300

33 Ah 211 horizontal 3 2 1300

45 Ah 267 horizontal 3 2 1300

55 Ah 324 horizontal 3 2 1300

75 Ah 432 horizontal 3 2 1300

22161978 80 Ah 472 horizontal 3 1 1350

90 Ah 540 horizontal 3 1 1350

100 Ah 540 horizontal 3 1 1350

120 Ah 679 horizontal 3 1 1350

134 Ah 765 horizontal 3 1 1350

22161979 150 Ah 836 horizontal 3 1 1350

22161980 190 Ah 1167 horizontal 3 1 1350

200 Ah 1206 horizontal 3 1 1350

Page 61: Central OnLite System Zumtobel

61

Page 62: Central OnLite System Zumtobel

www.zumtobel.com/office

www.zumtobel.com/healthcare

www.zumtobel.com/education

www.zumtobel.com/industry

www.zumtobel.com/shop

www.zumtobel.com/sport

www.zumtobel.com/hotel

www.zumtobel.com/parking

www.zumtobel.com/culture

www.zumtobel.com/safety

Art.-Nr. 04 900 033-UK 10/10

© Zumtobel Lighting GmbH

Technical data was correct at time of

going to press. We reserve the right to

make technical changes without notice.

Please contact your local sales office for

further information.

For the sake of the environment:

Luxo Light is chlorine-free paper from

sustainably managed forests and

certified sources.

■ Offices and Communication■ Education and Science■ Presentation and Retail■ Hotel and Wellness■ Art and Culture

■ Health and Care■ Industry and Engineering■ Sport and Leisure■ Transit Areas and Parking■ Orientation and Safety

Zumtobel is the internationally leading supplier of integral lighting solu-

tions for professional interior and exterior lighting applications.

We provide unique customer benefits by integrating technology, design,

emotion and energy efficiency. Under the Humanergy Balance concept,

we combine the best possible ergonomic lighting quality for an indivi-

dual’s wellbeing with the responsible use of energy resources.

The company’s own sales organisa tions in twenty countries, as well as

commercial agencies in fifty other countries, form an international net-

work of experts and design partners providing professional lighting

consulting, design assistance and comprehensive services.

Lighting and sustainability In line with our corporate philosopy “We

want to use light to create worlds of experience, make work easier and

improve communications and safety while remaining fully aware of our

responsibility to the environment”, Zumtobel offers energy-efficient high-

quality products, while at the same time making sure that our production

processes based on the considerate use of resources are environmen-

tally compatible. www.zumtobel.com/sustainability

LIGHT FOR HEALTH AND CARE

LIGHTING FORORIENTATIONAND SAFETY

LIGHT FORSPORTAND LEISURE

LIGHT FORINDUSTRYAND ENGINEERING

LIGHT FORTRANSIT AREAS AND PARKING

LIGHT FOR OFFICESAND COMMUNICATION

LIGHT FOR HOTELAND WELLNESS

LIGHT FOR PRESENTATIONAND RETAIL

LIGHT FOR ART ANDCULTURE

www.natureOffi ce.com / AT-171-731213 www.pefc.org

LIGHT FOR EDUCATION AND SCIENCE

YEAR GUARANTEE

Top quality – with a fi ve-year guarantee.

As a globally leading luminaire manufacturer,

Zumtobel provides a five-year guarantee

for its complete product range with effect from

1 April 2010.

www.zumtobel.com/guarantee

Page 63: Central OnLite System Zumtobel

TRACK AND SPOTS

MODULAR LIGHTING SYSTEMS

DOWN-/UPLIGHTS

RECESSED LUMINAIRES

SURFACE-MOUNTED AND PENDANT LUMINAIRES

LED, TASK, WALL AND UPLIGHTS

CONTINUOUS ROW AND BATTEN LUMINAIRES

HIGH-BAY LUMINAIRES

LUMINAIRES WITH EXTRA PROTECTION

LIGHTING MANAGEMENT

EMERGENCY LIGHTING

MEDICAL SUPPLY SYSTEMS

United Kingdom

Zumtobel Lighting Ltd.

Unit 4 - The Argent Centre, Pump Lane

Hayes/Middlesex UB3 3BL

T +44/(0)20 8589 1800

F +44/(0)20 8756 4800

M [email protected]

www.zumtobel.co.uk

USA and Canada

Zumtobel Lighting Inc.

Location Highland

3300 Route 9W

Highland, New York 1258-2630

T +1/(0)845/691 62 62

F +1/(0)845/691 62 89

www.zumtobel.us

www.zumtobel.ca

Australia and New Zealand

Zumtobel Lighting Pty Ltd

333 Pacific Highway

North Sydney, NSW 2060

T +61/(2)8913 5000

F +61/(2)8913 5001

M [email protected]

www.zumtobel.com.au

China

Zumtobel Lighting China

Beijing Office

T5-2-152 Tayuan

Diplomatic Compound

No. 1 Xin Dong Road,

Chaoyang District

100600 Beijing

T +86/(10) 8532 3886

F +86/(10) 8532 3889

M [email protected]

Hong Kong

Zumtobel Lighting Hong Kong

Unit 319, Level 43,

Tower 1, Metroplaza,

223 Hing Fong Road,

Kwai Chung, N.T.

T +852/(0)2503 0466

F +852/(0)2503 0177

M [email protected]

India

Zumtobel Lighting GmbH

Branch Office India

S-605, Manipal Centre

Dickenson Road

560042 Bangalore

M [email protected]

United Arab Emirates

Zumtobel Lighting GmbH (Branch)

Dubai Airport Free Zone,

Building 6W, B Block, 233

PO Box 54302

Dubai

T +971/(0)4 299 3530

F +971/(0)4 299 3531

M [email protected]

Hungary

Zumtobel Lighting Kft

Lomb u. 15.

1139 Budapest

T +36/(1) 35 00 828

F +36/(1) 35 00 829

M [email protected]

www.zumtobel.hu

Croatia, Serbia,

Bosnia and Herzegovina

Zumtobel Licht d.o.o.

Radnička cesta 80 – Zagrebtower

10000 Zagreb

T +385/(1) 64 04 080

F +385/(1) 64 04 090

M [email protected]

M [email protected]

www.zumtobel.hr

Czech Republic and Slovak Republic

Zumtobel Lighting s.r.o.

Jankovcova 2

Praha 7

170 00 Praha

T +420/(2) 66 782 200

F +420/(2) 66 782 201

M [email protected]

www.zumtobel.cz

Poland

Zumtobel Licht GmbH Sp.z.o.o.

Przedstawicielstwo w Polsce

ul. Narbutta 46/48

02-541 Warszawa

T +48/(22) 856 7431

F +48/(22) 856 7432

www.zumtobel.pl

Slovenia

Zumtobel Licht d.o.o.

Dunajska cesta 159

1000 Ljubljana

T +386/(1) 56 09 820

F +386/(1) 56 09 866

M [email protected]

www.zumtobel.si

Russia

Zumtobel Lighting GmbH

Official Representative Office

Skakovaya Str. 17

Bld. No 1, Office 1104

125040 Moscow

T +7/(495) 945 36 33

F +7/(495) 945 16 94

www.zumtobel.ru

Norway

Zumtobel Belysning

Pilestredet 75 C

0354 Oslo

Postbox 5829 Majorstuen

0308 Oslo

T +47 22 46 85 00

F +47 22 46 85 02

M [email protected]

www.zumtobel.no

Sweden

Zumtobel Belysning

Birger Jarlsgatan 57

113 56 Stockholm

T +46 8 26 26 50

F +46 8 26 56 05

M [email protected]

www.zumtobel.se

Denmark

Light Makers AS

Indiavej 1

2100 København/Copenhagen

T +45 35 43 70 00

F +45 35 43 54 54

M [email protected]

www.lightmakers.dk

Headquarters

Zumtobel Lighting GmbH

Schweizer Strasse 30

Postfach 72

6851 Dornbirn, AUSTRIA

T +43/(0)5572/390-0

F +43/(0)5572/22 826

Zumtobel Licht GmbH

Grevenmarschstrasse 74-78

32657 Lemgo, GERMANY

T +49/(0)5261 212-0

F +49/(0)5261 212-7777

www.zumtobel.de

www.zumtobel.com

Page 64: Central OnLite System Zumtobel

www.zumtobel.com/onlite

Emergency lighting

systems with central

power supply.

ONLITE central