BD-FP Central Data Bank List of Building Materials A. General Department: Buildings Type of building material: Fire protection materials for structural use Applications: For protection of structural elements to resist the action of fire for the specified periods B. Acceptance criteria Testing standards: Fire test/assessment should be carried out in accordance with BS 476: Parts 20 to 24: 1987. Conditions of Acceptance: To satisfy section 6.5 of the Code of Practice for Fire Resisting Construction 1996, valid and full fire test/assessment report shall be submitted to demonstrate that the concerned product or material has been tested in accordance with or assessed against BS 476: Parts 20 to 24: 1987 by a laboratory accredited under HOKLAS or recognized under mutual recognition agreements/arrangements with HOKLAS, or one of the assessing organizations listed in PNAP 251. Details of application such as surface preparation, application of primer, top coating etc, shall be strictly in accordance with the manufacturer’s specifications/recommendations and are compatible with those adopted in the fire tests.

Transcript of Central Data Bank List of Building Materials · BS 476: Parts 20 to 24: 1987 by a laboratory...

BD-FP

Central Data Bank List of Building Materials

A. General

Department: Buildings

Type of building material: Fire protection materials for structural use

Applications: For protection of structural elements to resist the action of fire for the specified periods

B. Acceptance criteria

Testing standards: Fire test/assessment should be carried out in accordance with BS 476: Parts 20 to 24: 1987.

Conditions of Acceptance: • To satisfy section 6.5 of the Code of Practice for Fire Resisting

Construction 1996, valid and full fire test/assessment report shall be submitted to demonstrate that the concerned product or material has been tested in accordance with or assessed against BS 476: Parts 20 to 24: 1987 by a laboratory accredited under HOKLAS or recognized under mutual recognitionagreements/arrangements with HOKLAS, or one of the assessing organizations listed in PNAP 251.

• Details of application such as surface preparation, application ofprimer, top coating etc, shall be strictly in accordance with themanufacturer’s specifications/recommendations and arecompatible with those adopted in the fire tests.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

001

Bollom

Fireshield

J.W. Bollom &

Company Limited

(See remarks)

Intumescent Coating Protection of

steel I-beams up

to 11/2 hrs. FRP;

steel I-columns,

CHS & RHS

columns up to 1

hr. FRP.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC81169 May 1991 May 1993 18/01/2005 No-objection letter

issued in 1991.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire protection coating

should be in

accordance with

appendix 2 of the

report no. CC81169.

BD-FP

002 Cafco 280,

800 & Cafco

Blaze-Shield

Isolatek

International

(See remarks)

Cementitious

mineral fibre

Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

376.3 December

1993

January 1997 18/01/2005 No-objection letter

issued in 1994.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Thickness of fire

protection material

should be in

accordance with data

sheets attached to BD’s

letter Ref. (37) in BD

GR/BM/2(23).

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

003

Cafco 280 Cafco Europe Sarl

Foetz,

Luxembourg

Cementitious

mineral fibre

Upgrade

structural

concrete slab up

to 4 hrs. FRP.

BS 476: Parts 20

& 21: 1987

BS 8110: Part 2:

1985

N/A Warrington

Fire Research

Centre

WFRC No.

C81024

January 1994 March 1998 18/01/2005 No-objection letter

issued in 1996.

Required thickness of

fire protection material

should be in

accordance with Tables

1, 2 & 3 in the

assessment report

WFRC No. C81024.

Both structural stability

and insulation

requirements should be

considered and the

higher of the thickness

applied.

BD-FP

004 Cape Supalux

Board

Cape Building

Products Limited

(See remarks)

Fibre reinforced

calcium silicate

board

2 hrs. fire

protection to

timber floor in

terms of load

bearing capacity,

integrity and

insulation.

As the system

does not form an

integral part of

the structure, the

actual

application and

acceptability of

the system

should be

considered on a

job-by-job basis.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

TE6640 January 1989 N/A 18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

The fire protection

system shall be as

described in the report

no. TE6640.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

005

Cape Supalux

Board

Cape Building

Products Limited

(See remarks)

Fibre reinforced

calcium silicate

board.

Protection of

steel beams and

columns up to 2

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC82875 February 1993 February

1996

18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire protection material

should be in

accordance with Tables

9 to 18 in the report no.

CC82875.

BD-FP

006 Cape

Vermiculux

Board

Cape Building

Products Limited

(See remarks)

Vermiculux board Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Building

Research

Establishment

The Loss

Prevention

Council

FRS.3/06/15

FCA/MEF

CC82017D

RHE/MB

March 1981

December

1991

December

1994

18/01/2005 No-objection letter

issued in 1992.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting board

shall be in accordance

with BRE’s assessment

letter ref.

FRS.3/06/15FCA/MEF

.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

007

Cape

Vermiculux

Board

Cape Building

Products Limited

(See remarks)

Vermiculux board

fixed by expansion

bolts with or without

steel hat-sections.

Protection of

R.C. slabs up to

4 hrs. FRP.

As the system

does not form an

integral part of

the structure, the

actual

application and

acceptability of

the system

should be

considered on a

job-by-job basis.

BS 476: Parts 20

& 21: 1987

BS 8110: Part 1:

1985

N/A The Loss

Prevention

Council

CC10626/R

HE

November

1990

November

1992

18/01/2005 No-objection letter

issued in 1992.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

The fire protection

system shall be as

described in the report

no. CC10626/RHE.

BD-FP

008

Conlit 100 Rockwool Limited

(See remarks)

Resin bonded rock

fibre insulation

board

Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC10806/R

HE,

CC81338A/

RHE

August 1989

May 1991 May 1993

18/01/2005 No-objection letter

issued in 1991.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting board

shall be in accordance

with the data indicated

in “Fire Protection for

Structural Steel in

Buildings (2nd

Edition)” published by

the Association of

Structural Fire

Protection Contractors

and Manufacturers Ltd.

(ASFPCM).

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

009

Conlit 150 &

150P

Rockwool Limited

(See remarks)

Mineral fibre

fire-resisting board

Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC81338 May 1991 N/A 18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with

Figures 1 & 2 in the

report no. CC81338.

BD-FP

010

Cryosil Cryotherm

Insulation Limited

(See remarks)

Silicate bonded

vermiculite board

Protection of

steel beams and

columns up to 2

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC81951 December

1991

December

1994

18/01/2005 No-objection letter

issued in 1992.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Figure

1 in the report no.

CC81951.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

011

Durasteel Floor

(System)

Cape Durasteel

Limited

(See remarks)

Durasteel 3DF2

panels (9.5mm

thick) enclosing a

core of Rocksil

LR/AT 140 (overall

thickness 120mm).

Fire resisting

floor for up to 4

hrs. FRP in terms

of loadbearing

capacity,

integrity and

insulation.

Clear spans of

the two way

floor slab limited

to 4.17m x 3.5m.

Imposed load

limited to 5kPa

maximum.

Strength design

of the steelwork

is to be carried

out and

considered

separately by the

RSE.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

TE82867 December

1992

N/A 18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

The construction

details should be in

accordance with that

shown in the technical

evaluation TE82867.

BD-FP

012

Fendolite MII Mandoval

Coatings Limited

(See remarks)

Premix based on

vermiculite and

Portland cement.

Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC82278A July 1992 July 1995 18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Table

5 in the report no.

CC82278A.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

013

Firetex

M70/M71

W & J Leigh &

Co.

(See remarks)

Intumescent Coating Protection of

steel I-beams up

to 11/2 hrs. FRP;

Protection of

SHS and CHS

steel columns up

to 1 hr. FRP;

Protection of

steel I-columns

and RHS steel

beams up to 2

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Warrington

Fire Research

Consultants

WFRC No.

C81691

WFRC No.

C80529

WFRC No.

C47373

March 1995

December

1992

June 1989

April 1997 18/01/2005 No-objection letter

issued in 1995.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Tables

1 to 7 in the report

WFRC No. C47373.

Thickness quoted

refers to total dry film

thickness including the

primer and any top

sealer, where the

thickness of the primer

and any top sealer

together do not exceed

0.125mm.

BD-FP

014

Firetex M70

Intubuild

W & J Leigh &

Co.

(See remarks)

Intumescent Coating Protection of

steel columns up

to 1 hr. FRP.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

TE5944 November

1986

N/A 18/01/2005 No-objection letter

issued in 1990.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with the

test report no. TE5944.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

015 Glulite Fire

Protection

Board

Cryotherm

Insulation Limited

(See remarks)

Resin-bonded

mineral fibre board.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC80705B/

RHE

October 1990 October

1992

18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with

Figures 1 & 2 in the

report no.

CC80705B/RHE.

Protection of

steel beams and

columns up to 4

hrs. FRP.

Panels are glued

with Rockbond

WR adhesive,

fastened to the

noggins with

Rockbond WR

adhesive and

wire nails.

BD-FP

016 Impact Fire

Board

Pilkington

Insulation Limited

(See remarks)

Fibre reinforced

cement board.

Protection of

steel beams and

columns up to 2

hrs. FRP.

Special

consideration is

required when

the web depth

exceeds 686mm

or flange width

exceeds 325mm.

BS 476: Parts 20

& 21: 1987

N/A Warrington

Fire Research

Consultants

WFRC No.

C44908

Re-Issue No.

1

October 1988 October

1990

18/01/2005 No-objection letter

issued in 1990.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Dry thickness of the

material should be in

accordance with Tables

4 & 4A in the report

WFRC No. C44908

(Re-Issue No. 1).

BD-FP

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

017

Interbond

FP-HFA 900

International Paint

Limited

(See remarks)

Intumescent Coating Protection of

hollow steel

sections up to 1

hr. FRP.

Protection of

steel I sections

up to 11/2 hrs.

FRP.

BS 476: Parts 20

& 21: 1987

N/A Warrington

Fire Research

Consultants

Warrington

Fire Research

Consultants

WFRC No.

C44900

WFRC No.

C49685

August 1988

July 1990

August 1990

July 1992

18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Table

2 in the reports WFRC

No. C44900 & WFRC

No. C49685.

BD-FP

018 Mandolite CP2 Mandoval

Coatings Limited

(See remarks)

Pre-mix based on

vermiculite and

Portland cement.

Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Warrington

Fire Research

Consultants

WFRC No.

C52252

November

1990

N/A 18/01/2005 No-objection letter

issued in 1991.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Tables

12 & 13 in the report

WFRC No. C52252.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

019

Mandolite CP2 Mandoval

Coatings Limited

(See remarks)

Pre-mix based on

vermiculite and

Portland cement.

Upgrade

reinforced

concrete slabs up

to 4 hrs. FRP.

BS 476: Parts 20

& 21: 1987

BS 8110: Part 2:

1985

N/A Warrington

Fire Research

Centre

WFRC No.

CP92117

March 1992 April 1994 18/01/2005 No-objection letter

issued in 1992.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Tables

1, 2 & 3 in the reports

WFRC No. CP92117.

Both structural stability

and insulation

requirements should be

considered and the

greater of the

thicknesses applied.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

020

Mandolite CP2 Mandoval

Coatings Limited

(See remarks)

Pre-mix based on

vermiculite and

Portland cement.

Upgrade

reinforced

concrete beams,

columns and

walls up to 4 hrs.

FRP.

BS 476: Parts 20

& 21: 1987

BS 8110: Part 2:

1985

N/A Warrington

Fire Research

Centre

WFRC No.

C80520

WFRC No.

CP92117

December

1992

March 1992

January 1995

April 1994

18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Table

2 in the report WFRC

No. CP92117.

The minimum sizes of

reinforced concrete

beams, columns and

walls should not be less

than those specified in

the Code of Practice

for Fire Resisting

Construction.

BD-FP

021

Monokote

MK5 & MK6

W.R. Grace & Co.

Construction

Products Division

(See remarks)

Sprayed-applied

cementitious

fire-proofing plaster.

Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Warrington

Fire Research

Centre

C80173-AH

B/mj

May 1992 N/A 18/01/2005 No-objection letter

issued in 1992.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with data

sheet referred to in the

letter Ref.

C80173-AHB/mj.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

022

Monokote

Zonolite Z-106

W.R. Grace & Co.

Construction

Products Division

(See remarks)

Sprayed-applied

cementitious fire

protection material.

Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Ian Smith

(Consultancy)

Limited

CIS/ER/329/

B

November

1988

N/A 18/01/2005 No-objection letter

issued in 1992.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Table

2 attached to Ian Smith

(Consultancy) Ltd’s

letter Ref.

CIS/ER/329/B.

BD-FP

023

New Promalit Eternit UK

Limited

(See remarks)

Lightweight

rockwool board.

Protection of

steel beams and

columns up to 3

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Building

Research

Establishment

FRO512/2

FT92/259/B

S

April 1993 N/A 18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with the

table in BRE’s letter

Ref. FRO512/2

FT92/259/BS.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

024 Nullifire S602

& S603

Nullifire Limited

(See remarks)

Intumescent Coating Protection of

steel I-beams and

I-columns, RHS

and CHS

columns up to 1

hr. FRP.

Protection of

RHS beams up

to 11/2 hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Certifire

Limited

CF103 May 1987 and

revised on

March 1990.

N/A 18/01/2005 No-objection letter

issued in 1990.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Tables

3, 4 & 5 in the

certificate no. CF103.

Thickness quoted refer

to total dry film

thickness including the

primer and any top

sealer, where the

thickness of the primer

and any top sealer

together do not exceed

0.1mm.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

025

Nullifire S605 Nullifire Limited

(See remarks)

Intumescent

Coating.

Protection of

steel I-beams and

I-columns up to

2 hrs. FRP.

Protection of

CHS columns up

to 1 hr. FRP.

BS 476: Parts 20

& 21: 1987

N/A Certifire

Limited

CF103 May 1987 and

revised on

March 1990.

N/A 18/01/2005 No-objection letter

issued in 1990.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Tables

6, 7, 8 & 9 in the

certificate no. CF103.

Thickness quoted refer

to total dry film

thickness including the

primer and any top

sealer, where the

thickness of the primer

and any top sealer

together do not exceed

0.1mm.

BD-FP

026

Nullifire S607 Nullifire Limited

(See remarks)

Intumescent Coating Protection of

steel I-beams up

to 11/2 hrs. FRP.

Protection of

steel I-columns,

RHS and CHS

columns up to 1

hr. FRP.

BS 476: Parts 20

& 21: 1987

N/A Certifire

Limited

CF103 May 1987 and

revised on

October 1992.

N/A 18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Tables

10, 11 & 12 in the

certificate no. CF103.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

027

Nullifire Firec

F333

Nullifire Limited

(See remarks)

Intumescent

Coating.

Protection of

steel I-beams and

I-columns and

CHS up to 2 hrs.

FRP.

Protection of

solid circular tie

bars up to 3 hrs.

FRP.

BS 476: Parts 20

& 21: 1987

N/A Certifire

Limited

CF103 May 1987 and

revised on

March 1990.

N/A 18/01/2005 No-objection letter

issued in 1990.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Tables

10 to 14 in the

certificate no. CF103.

Thickness quoted refer

to total dry film

thickness including the

primer and any top

sealer, where the

thickness of the primer

and any top sealer

together do not exceed

0.1mm.

BD-FP

028

Panelcrete

Impact Fire

Board

Panelcrete Limited

(See remarks)

Fibre reinforced

concrete board

Protection of

steel beams and

columns up to 2

hrs. FRP.

Application

limited to

I-section with

web depth not

exceeding

686mm and

flange width not

exceeding

325mm.

BS 476: Parts 20

& 21: 1987

N/A Warrington

Fire Research

Consultants

WFRC No.

C44908

Re-Issue No.

1

October 1988 October

1990

18/01/2005 No-objection letter

issued in 1994.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Tables

4 & 4A in the report

WFRC No. C44908

(Re-Issue No. 1).

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

029

Promatect H Eternit UK

Limited,

Blackburn, UK.

or

Eternit N.V.

Kapelle-op-den-bo

s Belgium.

Fibre-reinforced

calcium silicate

insulating board.

Protection of

steel beams and

columns up to 2

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC82518/R

HE

June 1992 June 1995 18/01/2005 No-objection letter

issued in 1992.

Required thickness of

fire-resisting material

should be in

accordance with Figure

1 in the report no.

CC82518/RHE.

BD-FP

030

Promatect L Eternit UK

Limited,

Blackburn, UK.

or

Eternit N.V.

Kapelle-op-den-bo

s Belgium.

Fibre reinforced

calcium silicate

insulating board

Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC82519/R

HE

June 1992 June 1995 18/01/2005 No-objection letter

issued in 1992.

Required thickness of

fire-resisting material

should be in

accordance with Figure

1 in the report no.

CC82519/RHE.

BD-FP

031

Pyrok CV25 Pyrok Building

Products Limited

(See remarks)

Cement-based fire

resisting plaster

aining

vermiculite.

cont

Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Building

Research

Establishment

FRO512/-FT

91/409/BS

February 1992 N/A 18/01/2005 No-objection letter

issued in 1992.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with the

BRE’s letter Ref.

FRO512/-FT91/409/B

S.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting

into CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

032

Pyrok CV27 Pyrok Building

Products Limited

(See remarks)

Cement-based fire

resisting plaster

containing

vermiculite.

Upgrade

reinforced

concrete slabs up

to 4 hrs. FRP.

BS 476: Parts 20

& 21: 1987

BS 8110: Part 2:

1985

N/A Warrington

Fire Research

Centre

WFRC No.

C80277

WFRC No.

41664

September

1992

June 1987

October

1994

18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Tables

1, 2 & 3 in the report

WFRC 41664.

Both structural stability

and insulation

requirements should be

considered and the

greater of the

thicknesses applied.

BD-FP

033

Quelfire

Steelcote 60

Quelfire Limited

(See remarks)

Intumescent Coating Protection of

steel I- beams up

to 11/2 hrs. FRP.

Protection of

steel I-columns

and RHS beams

up to 2 hrs. FRP.

Protection of

RHS and CHS

columns up to 1

hr. FRP.

Protection of

circular hollow

and cruciform

cast iron

columns up to 1

hr. FRP.

BS 476: Parts 20

& 21: 1987

N/A Warrington

Fire Research

Consultants

WFRC No.

C51739

October 1990 October

1992

18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Tables

1 to 6 in the report

WFRC No. C51739.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

034

Rockcem Cryotherm

Insulation Limited

(See remarks)

Premix based on

rock-fibre and

Portland cement.

Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Building

Research

Establishment

A22/3349

FCA/IC

June 1984 N/A 18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with the

BRE’s letter Ref.

A22/3349 FCA/IC.

BD-FP

035

Spiralite Fire

Protection

Board

Cryotherm

Insulation Limited

(See remarks)

Resin-bonded

mineral fibre board.

Protection of

steel beams and

columns up to 2

hrs. FRP.

Panels are

fastened to the

noggins with

Spiralite coil

screws.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC10786/81

887A

RHE/MB

July 1989 and

reviewed in

November

1991

November

1993

18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Table

1 in the report no.

CC10786/81887A

RHE/MB.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

036

Spraydon F. G. Thermoduric

Limited

(See remarks)

Spray applied

mineral wool.

Protection of

structural

steelwork up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Warrington

Fire Research

Centre

Warrington

Fire Research

Consultants

WFRC No.

C80980

WFRC No.

C43587

November

1993

March 1988

November

1995

18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with

Summary Table 1 in

the report WFRC No.

C43587.

BD-FP

037

Sprayed

Limpet

Mineral Wool

Pilkington

Insulation Limited

(See remarks)

Sprayed mineral

wool

Protection of

structural

steelwork up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A N/A N/A*

* Test or

assessment

report could

not be

retrieved.

N/A N/A 18/01/2005 No-objection letter

issued in 1994.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with the

data indicated on page

73 of “Fire Protection

for Structural Steel in

Buildings (2nd

Edition)” published by

the Association of

Structural Fire

Protection Contractors

and Manufacturers Ltd.

(ASFPCM).

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

038

Sprayed

Limpet

Vermiculite

Pilkington

Insulation Limited

(See remarks)

Sprayed vermiculite

cement

Protection of

structural

steelwork up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A N/A N/A*

* Test or

assessment

report could

not be

retrieved.

N/A N/A 18/01/2005 No-objection letter

issued in 1994.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with the

data indicated on pages

75 & 77 of “Fire

Protection for

Structural Steel in

Buildings (2nd

Edition)” published by

the Association of

Structural Fire

Protection Contractors

and Manufacturers Ltd.

(ASFPCM).

BD-FP

039

Steelguard FM Mebon Limited

(See remarks)

Intumescent Coating Protection of

steel I- beams,

I-columns and

RHS beams up

to 11/2 hrs. FRP.

Protection of

RHS columns up

to 1 hr. FRP.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC80320

CC81382

December

1990

December

1992

18/01/2005 No-objection letter

issued in 1992.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Tables

5 & 6 in the report no.

CC80320, Table 2 in

the report no.

CC81382.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

040

Steelmaster Mebon Limited

(See remarks)

Intumescent Coating Protection of

steel I-beams,

I-columns and

RHS beams up

to 11/2 hrs. FRP.

Protection of

RHS and CHS

columns up to 1

hr. FRP.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC81987

CC81987A

December

1991

December

1993

18/01/2005 No-objection letter

issued in 1992.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Tables

5 & 6 in the report no.

CC81987, Table 2 in

the report no.

CC81987A.

BD-FP

041

TD Board Thermoduric

Limited

(See remarks)

Mineral Wool Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC83128 December

1992

18/01/2005 No-objection letter

issued in 1993.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with

Figures 1 & 2 in the

report no. CC83128.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

042

Unitherm

38091

Herberts GmbH.

(See remarks)

Intumescent Coating Protection of

steel I-beams and

I-columns up to

2 hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Warrington

Fire Research

Centre

WFRC No.

C81065

March 1994 April 1996 18/01/2005 No-objection letter

issued in 1994.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Table

1 in the report WFRC

No. C81065.

BD-FP

043

Unitherm A60 Herberts GmbH.

(See remarks)

Intumescent Coating Protection of

steel I-beams and

I-columns up to

1 hr. FRP.

BS 476: Parts 20

& 21: 1987

N/A Warrington

Fire Research

Consultants

WFRC No.

C44347

May 1988 18/01/2005 No-objection letter

issued in 1991.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Figure

3 in the report no.

CC44347.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

044

Unitherm Fire

Protection

Coating

Dispersal,

Water Soluble

Herberts GmbH.

(See remarks)

Intumescent Coating Protection of

internal steel

I-beams up to

11/2 hrs. FRP.

Protection of

internal steel

I-columns up to

1 hr. FRP.

BS 476: Parts 20

& 21: 1987

N/A Warrington

Fire Research

Centre

WFRC No.

C80058

March 1992 April 1994 18/01/2005 No-objection letter

issued in 1992.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Table

1 in the report WFRC

No. C80058.

BD-FP

045

Vicuclad Eternit UK

Limited,

Blackburn, UK.

or

Eternit N.V.

Kapelle-op-den-bo

s Belgium

Insulation boards

produced from

mixing vermiculite

with inorganic

binders.

Protection of

steel beams and

columns up to 2

hrs. FRP in

screw-fix

Vicuclad system.

Protection of

steel beams and

columns up to 4

hrs. FRP in

bonded Vicuclad

system.

BS 476: Parts 20

& 21: 1987

N/A The Loss

Prevention

Council

CC82520/R

HE

June 1992 June 1995 18/01/2005 No-objection letter

issued in 1992.

Required thickness of

fire-resisting material

should be in

accordance with Figure

1 in the report no.

CC82520/RHE.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

046

Zonolite W.R. Grace & Co.

(See remarks)

Cementitious

fibre-reinforced

material.

Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Ian Smith

(Consultancy)

Limited.

CIS/ER/329/

B

November

1988

N/A 18/01/2005 No-objection letter

issued in 1989.

Updated information

on place of

manufacture to be

provided by the

manufacturer.

Required thickness of

fire-resisting material

should be in

accordance with Table

2 in Ian Smith

(Consultancy) Ltd’s

letter ref.

CIS/ER/329/B.

BD-FP

047

Firecut

FM-900

Yung Chi Paint &

Varnish Mfg Co

Ltd.

Koahsiung,

Taiwan

Single pack solvent

based intumescent

coating

Protection of

steel I-beams and

I-columns up to

1 hr. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC No.

C123992

WFRC No.

C110854

8 April 2002

1 November

1999

valid until 1

April 2007

lapse on 1

December

2001

28/04/2005

BD-FP

048

Firecut

FM-900

Yung Chi Paint &

Varnish Mfg Co

Ltd.

Koahsiung,

Taiwan

Single pack solvent

based intumescent

coating

Protection of

steel I-beams and

I-columns up to

2 hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC No.

C125252

19 June 2002 valid until 1

July 2007

28/04/2005

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

049

Firecut

FM-900

Yung Chi Paint &

Varnish Mfg Co

Ltd.

Koahsiung,

Taiwan

Single pack solvent

based intumescent

coating

Protection of

4-side exposed

RHS and CHS

up to 2 hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC No.

C125331

19 June 2002 valid until 1

July 2007

28/04/2005

BD-FP

050

Firecut

FM-900

Yung Chi Paint &

Varnish Mfg Co

Ltd.

Koahsiung,

Taiwan

Single pack solvent

based intumescent

coating

Protection of

3-side exposed

RHS up to 2 hrs.

FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC No.

C126749

WFRC No.

C115007

27 August

2002

31 July 2000

valid until 1

September

2007

valid until 1

August 2002

28/04/2005

BD-FP

051

Vermitex AF L&A Fazzini

Manufacturing Pty

Ltd.

Greenacre NSW,

Australia

Gypsum-vermiculite

coating

Protection of

steel I-sections

up to 2 hrs. FRP.

AS 1530.4 and

BS 476: Part 21

NATA CSIRO FCO-1299

(Revision)

FCO-0812

(Revision)

22 October

2003

9 November

2001

lapse on 31

July 2007

lapse on 1

March 2005

28/04/2005 According to the

manufacturer’s

recommendation,

Vermitex AF is for

internal application.

CSIRO opinion no.

FCO-0812 (Revision)

assessed compatibility

of Vermitex spray

protection system with

certain types of primer.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

052

Vermitex DX L&A Fazzini

Manufacturing Pty

Ltd.

Greenacre NSW,

Australia

Cement-vermiculite

coating

Protection of

steel I-sections

up to 2 hrs. FRP.

AS 1530.4 and

BS 476: Part 21

NATA CSIRO FCO-1299

(Revision)

FCO-0812

(Revision)

22 October

2003

9 November

2001

lapse on 31

July 2007

lapse on 1

March 2005

28/04/2005 According to the

manufacturer’s

recommendation,

Vermitex DX is for

external application.

CSIRO opinion no.

FCO-0812 (Revision)

assessed compatibility

of Vermitex spray

protection system with

certain types of primer.

BD-FP

053

Cafco 300 Isolatek

International

New Jersey, USA

Single package

factory controlled

premix based on

vermiculite and

gypsum

Protection of

3-side exposed

UB and UC

sections up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

Recognized by

PNAP 251

Building

Research

Establishment

CC 206998 17 April 2002 next review

date: 4

March 2007

28/04/2005

BD-FP

054

Hilti HIT-HY

150

Hilti Corporation

Kaufering,

Gemany

Hybrid resin system Injection system

for making

nominal

anchorage

connections of

Grade 460 rebars

of diameters up

to 25mm in

reinforced

concrete

elements up to 4

hrs. FRP.

BS 476: Part 20:

1987

UKAS Warrington

Fire Research

Centre

WFRC No.

C121086

25 September

2002

valid until 1

October

2007

28/04/2005 Load carrying capacity

of the injection system

for rebar fixing under

the effects of fire

should be assessed

with an appropriate

factor of safety

compatible with the

structural design of the

parent structure.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

055

Hilti HIT-RE

500

Hilti Corporation

Kaufering,

Gemany

Epoxy resin system Injection system

for making

nominal

anchorage

connections of

Grade 460 rebars

of diameters up

to 40mm in

reinforced

concrete

elements up to 4

hrs. FRP.

BS 476: Part 20:

1987

UKAS Warrington

Fire Research

Centre

WFRC No.

C121086

25 September

2002

valid until 1

October

2007

28/04/2005 Load carrying capacity

of the injection system

for rebar fixing under

the effects of fire

should be assessed

with an appropriate

factor of safety

compatible with the

structural design of the

parent structure.

BD-FP

056

Durasteel

board

Intumex Asia

Pacific Pte. Ltd.

Blackburn, UK

9.5mm thick

Durasteel board

Fire resisting

steel platform

floors covered

with two layers

of Durasteel

(constructions

are given in the

assessment

reports) when

exposed to fire

for 1 hr. FRP in

terms of

loadbearing

capacity,

integrity and

insulation.

Maximum

imposed load to

be 7.5kPa..

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC

Assessment

Report No.

138676

19 May 2004 valid until 1

June 2009

03/08/2005 The construction

details should be

identical to those

covered in the

assessment reports.

All requirements given

in the assessment

reports should be

checked to ensure

compatibility with

proposed applications.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

057

Unitherm

38091

Dupont

Performance

Coatings GmbH &

Co.

Stuttgart, Gemany

Intumescent coating Protection of

RHS and CHS

beams and

columns up to 1

hr. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC

Assessment

Report No.

C126392

Issue 3

WFRC No.

C105708

WFRC No.

C125342

Issue 2

WFRC

Assessment

Report No.

140896

22 July 2004

8 February

1999

13 August

2002

14 July 2004

N/A

See WFRC

Assessment

Report No.

C126392

Issue 3

valid until 1

September

2007

valid until 1

August 2009

03/08/2005

BD-FP

058

Cafco 300 Isolatek

International

New Jersey, USA

Single package

factory controlled

premix based on

vermiculite and

gypsum

Protection of

steel I-columns,

RHS and CHS

beams and

columns up to 2

hrs. FRP.

BS 476: Parts 20

& 21: 1987

Recognized by

PNAP 251

Building

Research

Establishment

CC 206998 17 April 2002 next review

date: 4

March 2007

03/08/2005 Section 1.6.2 of Fire

Protection for

Structural Steel in

Buildings published by

the Association for

Specialist Fire

Protection contains

recommendations for

determination of spray

thickness for hollow

sections based on

technical data for steel

I-sections.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

059

Cafco

SprayFilm

WB3

Cafco International

UK

Guangzhou, China

Intumescent coating Protection of

steel I-beams,

I-columns, RHS

and CHS beams

and columns up

to 2 hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC

Assessment

Report No.

C139823

WFRC

Assessment

Report No.

139822

27 May 2004

16 June 2004

valid until 1

June 2009

valid until 1

July 2009

03/08/2005

BD-FP

060

Firetherm

Firesteel

Classic

Firetherm

Intumescent &

Insulation Supplies

Ltd.

Dartford, UK

Solvent based

intumescent coating

Protection of

steel I-beams and

I-columns up to

1 hr. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC No.

123080

WFRC No.

100784

28 January

2001

22 October

1997

valid until 1

February

2007

see WFRC

No. 123080

03/08/2005

BD-FP

061

Nullifire S606 Nullifire Limited

Coventry, UK

Intumescent coating Protection of

4-side exposed I

sections, RHS

and CHS

columns up to 2

hrs. FRP.

BS 476: Parts 20

& 21: 1987

Recognized by

PNAP 251

Building

Research

Establishment

CC 92856A

CC 92856B

10 April 2003

10 April 2003

next review

date: 10

April 2008

next review

date: 10

April 2008

03/08/2005

BD-FP

062

Nullifire S605 Nullifire Limited

Coventry, UK

Intumescent coating Protection of

4-side exposed

RHS up to 1 hr.

FRP.

BS 476: Parts 20

& 21: 1987

Recognized by

PNAP 251

Building

Research

Establishment

CC 93058B

Review 2

21 July 2003 next review

date: 21 July

2008

26/10/2005

BD-FP

063

Interchar 963 International Paint

Limited

Shanghai, China

Intumescent coating Protection of

3-side exposed

steel channels

and angles up to

1 hr. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC

Assessment

Report No.

136405

15 January

2004

valid until 1

February

2009

03/02/2006

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

064

Phoenix 167 Phoenix Fire

Protection (Asia)

Ltd.

Mannheim,

Germany

Intumescent coating Protection of

4-side exposed

hollow columns

up to 1 hr. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC

Assessment

Report No.

143912

20 December

2004

valid until 1

January 2010

03/02/2006

BD-FP

065

Phoenix 168 Phoenix Fire

Protection (Asia)

Ltd.

Mannheim,

Germany

Intumescent coating Protection of

3-side and 4-side

exposed I beam

sections up to 1

hr. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC No.

C126964

WFRC No.

C126965

30 September

2002

30 September

2002

valid until 1

October

2007

valid until 1

October

2007

03/02/2006

BD-FP

066

Cafco 280 Cafco International

Indiana, USA

Cementitious

mineral fibre

Protection of

steel beams and

columns up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

Recognized by

PNAP 251

Building

Research

Establishment

CC 376.3 17 March

2003

next review

date: 17

March 2008

21/04/2006

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

067

Durasteel Floor

Assemblies

Intumex Asia

Pacific Pte. Ltd.

Blackburn, UK

Single layer of

9.5mm thick

Durasteel board,

fastened above and

below a framework

of steel channels,

enclosing a cavity

containing 140kg/m3

density rock wool

with a minimum

overall thickness of

80mm.

Fire resisting

floor assemblies

(construction

details are given

in the assessment

reports) for up to

2 hrs. FRP in

terms of

loadbearing

capacity,

integrity and

insulation.

Maximum

imposed load to

be 10kPa.

Primary

members of the

steel framework

are located

parallel with and

on top of main

structural

supporting

beams at 1m,

1.2m or 2.4m

centers as given

in the assessment

reports. Cross

members are

spaced at

600mm max.

centers.

BS 476: Parts 20

& 21: 1987

Recognized by

PNAP 251

UKAS

Building

Research

Establishment

Warrington

Fire Research

Centre

CC 94333

WFRC

Assessment

report No.

136396

22 March

2002

22 March

2004

next review

date: 22

March 2007

valid until 1

April 2009

21/07/2006 The construction

details should be

identical to those

covered in the

assessment reports.

All requirements given

in the assessment

reports should be

checked to ensure

compatibility with

proposed applications.

The assembly shall be

supported by structural

steel beams that are

fitted with a

proprietary fire

protection system of

suitable thickness for

the relevant fire

resistance period and

for the section factor of

the beams.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

068

Durasteel Floor

Assembly

Intumex Asia

Pacific Pte. Ltd.

Blackburn, UK

Two layers of 9.5mm

thick Durasteel

board, fastened to

the top of a steel

framework.

Fire resisting

floor assembly

(construction

details are given

in the assessment

report) for up to

1 hr. FRP (fire

attack from

either above or

below) in terms

of loadbearing

capacity,

integrity and

insulation.

Maximum

imposed load to

be 10kPa.

The steel

framework

consists of

primary

supporting

members at

maximum

2400mm centers

welded to

secondary

supporting

members at

maximum

600mm centers.

BS 476: Parts 20

& 21: 1987

UKAS Warringtonfire WF

Assessment

Report No.

148104

12 September

2005

valid until 1

October

2010

21/07/2006 The construction

details should be

identical to those

covered in the

assessment report.

All requirements given

in the assessment

report should be

checked to ensure

compatibility with

proposed application.

The steel framework of

the floor shall be

designed to be able to

bear the specified

uniformly distributed

imposed load of up to a

maximum of 10kPa.

When it is required to

withstand fire attack

from below, the steel

framework shall be

cladded with a

proprietary fire

protection system of

suitable thickness for

the relevant fire

resistance period at the

designed critical steel

temperature and for the

section factors of the

members.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

069

Phoenix 270 Phoenix Fire

Protection (Asia)

Ltd.

Mannheim,

Germany

Intumescent coating Protection of

4-side exposed I-

sections up to 2

hrs. FRP.

BS 476: Parts 20

& 21: 1987

Recognized by

PNAP 251

International

Fire

Consultants

Ltd.

Field of

Application

Report

IFCA/05199

July 2005 valid until

July 2010

20/10/2006 A critical temperature

of 550℃ has been

assumed for 4-side

exposed steel sections.

BD-FP

070

Mandolite CP2 Cafco International

Alfreton,

Derbyshire, UK

Pre-mix based on

vermiculite and

Portland cement.

Upgrade

reinforced

concrete slabs,

beams, columns

and walls up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

BS 8110: Part 2:

1985

UKAS Warrington

Fire Research

Centre

WFRC No.

C132081C

WFRC No.

C80520

Issue No. 2

WFRC No.

C132081A

WFRC No.

CP92117

Rev.1

19 May 2003

19 January

1993

19 May 2003

5 March 1992

valid until 1

June 2008

valid until 1

February

1995

valid until 1

June 2008

valid until 1

April 1994

20/10/2006 For use on reinforced

concrete beams,

columns and walls, the

minimum size

requirements specified

in the Code of Practice

for Fire Resisting

Construction 1996 and

the criterion of stability

should be satisfied.

For use on reinforced

concrete slabs, the

criteria of stability and

insulation should be

satisfied.

BD-FP

071

Nullifire

System E

Carboline

USA

Intumescent coating Protection of

4-side exposed

CHS up to 1 hr.

FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC No.

C124329A

WFRC No.

C100578

19 April 2002

30 September

1997

valid until 1

May 2007

valid until 1

November

1999

20/10/2006 A critical temperature

of 550℃ has been

assumed for 4-side

exposed steel sections.

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

072

Phoenix 270 Phoenix Fire

Protection (Asia)

Ltd.

Mannheim,

Germany

Intumescent coating BS 476: Parts 20

& 21: 1987

Recognized by

PNAP 251

International

Fire

Consultants

Ltd.

Field of

Application

Report

IFCA/05196

July 2005 valid until

July 2010

22/01/2007 Protection of

4-side exposed

hollow sections

up to 2 hrs. FRP.

BD-FP

073

Unitherm

38091

Dupont

Performance

Coatings GmbH &

Co.

Stuttgart, Gemany

Intumescent coating Protection of

steel I-beams and

I-columns up to

2 hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

Assessment

Summary

WFRC No.

133394

WFRC No.

133000

WFRC No.

C125126

WFRC No.

C128560

WFRC No.

C105561

Issue 2

10 July 2003

20 June 2003

3 July 2002

27 November

2002

8 February

1999

N/A

valid until

1 July 2008

valid until

1 August

2007

valid until

1 December

2007

valid until

1 March

2001

22/01/2007

Reference List of Fire Protection Materials for Structural Use

BD-FP

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

074

Renitherm

PMA 1200

Audax-Keck

GmbH

Weiherstrasse,

Germany

Intumescent coating Protection of

3-side and 4-side

exposed

I sections up to 2

hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warringtonfire WF

Assessment

Report No.

156366

12 July 2006 valid until

1 August

2011

22/01/2007

BD-FP

075

Pyrok CV27 Axiom

Engineering Ltd.

Hong Kong

Cement-based fire

resisting plaster

containing

vermiculite.

Upgrade

reinforced

concrete slabs up

to 4 hrs. FRP.

BS 476: Parts 20

& 21: 1987

BS 8110: Part 2:

1985

UKAS Warrington

Fire Research

Centre

WFRC No.

C139153

WFRC No.

41664

21 April 2004

June 1987

valid until

1 May 2009

22/01/2007 Required thickness of

fire-resisting material

should be in

accordance with Tables

1, 2 & 3 in the report

WFRC 41664.

Both structural stability

and insulation

requirements should be

considered and the

greater of the

thicknesses applied.

BD-FP

076

Firetherm

Firesteel

Classic 120

Firetherm

Intumescent &

Insulation Supplies

Ltd.

Kent, UK

Solvent based

intumescent coating

Protection of

3-side exposed

steel channel

sections /

I-section up to 2

hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC No.

C130413

6 March 2003 valid until 1

April 2008

3/8/2007 Assessment applicable

to steel I-section up to

a maximum web size

of 686mm and flange

size of 305mm

BD-FP

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

077

Hilti HIT-RE

500

Hilti Corporation

Kaufering,

Gemany

Epoxy resin system Injection system

for making

nominal

anchorage

connections of

Grade 460 rebars

of diameters up

to 40mm in

reinforced

concrete

elements up to 2

hrs. FRP.

BS 476: Part 20:

1987

UKAS Bodycote

Warringtonfire

WF 166402 26 October

2007

valid until

1 November

2012

21.1.2008 Load carrying capacity

of the injection system

for rebar fixing under

the effects of fire

should be assessed

with an appropriate

factor of safety

compatible with the

structural design of the

parent structure.

BD-FP

078

Firetherm

Firesteel

Classic 120

Firetherm

Intumescent &

Insulation Supplies

Ltd.

Kent, UK

Solvent based

intumescent coating

Protection of

3-sides/ 4-sides

exposed steel

hollow beam

sections up to 2

hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC No.

C130414

6 March 2003 valid until

1 April 2008

21.1.2008

BD-FP

079

Nullifire S605 Nullifire Limited

Coventry, UK

Solvent based

intumescent coating

Protection of

Built up Box

Sections up to 2

hrs FRP and

SHS up to 1 hr.

FRP (4-side

exposed for both

sections)

BS 476: Parts 20

& 21: 1987

HOKLAS Research

Engineering

Development

Façade

Consultants

Limited

R07K15 24 October

2007

Valid until

21 July 2008

21/1/2008 The relationship

between protection

thickness, section

factor, and fire

resistance of structural

steel shall refer to BRE

assessment report

number CC 93058B.

The assessment of the

built up box section

under the fire test

report R07K15 was

based on fire test of a

rolled hollow section.

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

080

Nullifire S606 Nullifire Limited

Coventry, UK

Solvent based

intumescent coating

Protection of

SHS beam

sections with

3-side exposed

and maximum

span of 1.3m for

2 hrs FRP

BS 476: Parts 20

& 21: 1987

HOKLAS Research

Engineering

Development

Façade

Consultants

Limited

R07L03 9 November

2007

Valid until

8 November

2009

21/1/2008 The relationship

between protection

thickness, section

factor, and fire

resistance of structural

steel shall refer to BRE

assessment report

number CC92856B.

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

081

Durasteel Floor

Assemblies

Intumex Asia

Pacific Pte. Ltd.

Blackburn, UK

Single layer of

9.5mm thick

Durasteel board,

fastened above and

below a framework

of steel channels,

enclosing a cavity

containing 140kg/m3

density rock wool

with a minimum

overall thickness of

120mm.

Fire resisting floor

assemblies

(construction details

are given in the

assessment reports)

for up to 4 hrs. FRP

in terms of

load-bearing

capacity, integrity

and insulation.

Maximum imposed

load to be 5.0kPa.

Primary members of

the steel framework

are located parallel

with and on top of

main structural

supporting beams at

1m, 1.2m or 2.4m

centers as given in

the assessment

reports. Cross

members are spaced

at 600mm c/c.

Additional 2 nos. of

cover strips shall be

required for the top

and bottom flange of

the channel sections

for insulation use.

BS 476:

Parts 20 &

21: 1987

UKAS Warrington

Fire Research

Centre

WFRC

Assessment

report No.

136396

22 March

2004

valid until 1

April 2009

25/4/2008 The construction

details should be

identical to those

covered in the

assessment reports.

All requirements given

in the assessment

reports should be

checked to ensure

compatibility with

proposed applications.

The assembly shall be

supported by structural

steel beams that are

fitted with a

proprietary fire

protection system of

suitable thickness for

the relevant fire

resistance period and

for the section factor of

the beams.

Maximum load ratio of

structural steel

elements inside the

assembly shall be less

than or equal to 0.5

to BS5950: Part 1

Fire stop/ sealant shall

be provided for the

interface between the

perimeter of the

Durasteel floor and the

surrounding structures

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

082

Durasteel

Protected Steel

Stair

Intumex Asia

Pacific Pte. Ltd.

Blackburn, UK

Single layer of

9.5mm thick

Durasteel board,

fastened above and

below a framework

of steel angles and

cold formed steel

sheet, enclosing a

cavity containing

140kg/m3 density

rock wool with a

minimum overall

thickness of 120mm.

Protected stairs

(construction details

are given in the

assessment reports)

for up to 4 hrs. FRP

in terms of

loadbearing capacity,

integrity and

insulation.

Maximum imposed

load to be 5.0kPa.

Cold formed steel

sheet supported by

steel angles create

the treads and risers

of the stair assembly

as well as supporting

the Durasteel board

on top. Back-to-back

steel angle spaced at

1.2m c/c hanging the

Durasteel board at

the underside of the

stairs. The main

structural beam

(I-section or hollow

section) along the

staircase is enclosed

inside the assembly

BS 476:

Parts 20 &

21: 1987

UKAS Warrington

Fire Research

Centre

WFRC

Assessment

report No.

141176

31 August

2004

valid until 1

September

2009

25/4/2008 The construction

details should be

identical to those

covered in the

assessment reports.

All requirements given

in the assessment

reports should be

checked to ensure

compatibility with

proposed applications.

Maximum load ratio of

structural steel

elements inside the

assembly shall be less

than or equal to 0.5

to BS5950: Part 1

Either full thickness or

at least half the

required thickness of

rock wool shall be

fitted between the

Durasteel and the main

structural steel

members supporting

the stair.

Fire stop/ sealant shall

be provided for the

interface between the

perimeter of the

Durasteel floor and the

surrounding structures

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

083

Firecut

FM-900

Yung Chi Paint &

Varnish Mfg Co

Ltd.

Koahsiung,

Taiwan

Single pack solvent

based intumescent

coating

Protection of steel

I-beams and

I-columns up to 2

hrs. FRP.

BS 476:

Parts 20 &

21: 1987

UKAS Bodycote

Warringtonfire

WF No.

164158

20 August

2007

valid until1

June 2012

22/7/2008 This is resulted from

the expiry pf

BD-FP048

It should be read in

conjunction with fire

assessment report

WFRC No. 125252

BD-FP

084

Firecut

FM-900

Yung Chi Paint &

Varnish Mfg Co

Ltd.

Koahsiung,

Taiwan

Single pack solvent

based intumescent

coating

Protection of steel

angle, channel and

T-section to 2 hrs.

FRP.

BS 476:

Parts 20 &

21: 1987

UKAS Bodycote

Warringtonfire

WF No.

164158

20 August

2007

valid until1

June 2012

22/7/2008 It should be read in

conjunction with

Bodycote

Warringtonfire

assessment letter dated

22.10.2007regarding

sections with re-entrant

details.

BD-FP

085

Firecut

FM-900

Yung Chi Paint &

Varnish Mfg Co

Ltd.

Koahsiung,

Taiwan

Single pack solvent

based intumescent

coating

Protection of 4-side

exposed RHS and

CHS up to 2 hrs.

FRP.

BS 476:

Parts 20 &

21: 1987

UKAS Bodycote

Warringtonfire

WF No.

164159

20 August

2007

valid until 1

June 2012

22/7/2008 This is resulted from

the expiry of

BD-FP049

It should be read in

conjunction with fire

assessment report

WFRC No. 125331

BD-FP

086

Firecut

FM-900

Yung Chi Paint &

Varnish Mfg Co

Ltd.

Koahsiung,

Taiwan

Single pack solvent

based intumescent

coating

Protection of 3-side

exposed RHS up to

2 hrs. FRP.

BS 476:

Parts 20 &

21: 1987

UKAS Bodycote

Warringtonfire

WF No.

164160

20 August

2007

valid until 1

June 2012

22/7/2008 This is resulted from

the expiry of

BD-FP050

It should be read in

conjunction with fire

assessment report

WFRC No. 115007

BD-FP

087

Southwest A/D

Type 5GP

A/D Fire

Protection Systems

Toronto, Canada

Single component,

factory blended

cementitious spray

applied coating

Protection of beam

or column of

I-section and hollow

section up to 4 hrs

FRP.

BS 476:

Parts 20 &

21: 1987

UKAS Bodycote

Warringtonfire

WF No.

163280

WF No.

160007

WF No.

160008

20 June 2007

N/A

N/A

Valid until 1

July 2012

22/7/2008 A/D Type 5GP is not

intended for direct

exposure to weather or

excessive physical

abuse.

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

088

Durasteel Floor

Assemblies

Intumex Asia

Pacific Pte. Ltd.

Blackburn, UK

Single layer of

9.5mm thick

Durasteel board,

fastened above and

below a framework

of steel channels,

enclosing a cavity

containing 140kg/m3

density rock wool

with a minimum

overall thickness of

80mm.

Fire resisting floor

assemblies

(construction details

are given in the

assessment reports)

for up to2 hrs. FRP

in terms of

load-bearing

capacity, integrity

and insulation.

Maximum imposed

load to be 10kPa.

Any point load shall

be distributed over

an area of

300mmx300mm.

Primary members of

the steel framework

are located parallel

with and on top of

main structural

supporting beams at

1m centers as given

in the assessment

reports. Cross

members are spaced

at 600mm c/c.

BS 476:

Parts 20 &

21: 1987

Recognized by

PNAP 251

Building

Research

Establishment

CC 94333

Review 2

20 July 2007 valid until

20 July 2012

22/7/2008 The construction

details should be

identical to those

covered in the

assessment reports.

All requirements given

in the assessment

reports should be

checked to ensure

compatibility with

proposed applications.

The assembly shall be

supported by structural

steel beams that are

fitted with a

proprietary fire

protection system of

suitable thickness for

the relevant fire

resistance period and

for the section factor of

the beams.

Maximum load ratio of

supporting steel

elements shall not

exceed 0.53 to

BS5950: Part 1

Fire stop/ sealant shall

be provided for the

interface between the

perimeter of the

Durasteel floor and the

surrounding structures

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

089

Phoenix 168 Phoenix Fire

Protection (Asia)

Ltd.

Mannheim,

Germany

Intumescent coating

(water based)

Protection of 3-side

and 4-side exposed I

beam sections up to

1 hr. FRP.

BS 476:

Parts 20 &

21: 1987

UKAS Bodycote

Warringtonfire

WF No.

160031

WF No.

160032

1 December

2006

1 December

2006

valid until 1

December

2011

22/7/2008 This is resulted from

the expiry of BD-FP

065

It should be read in

conjunction with fire

assessment report

WFRC No. C126964

and C126965

BD-FP

090

Phoenix

270-120

Phoenix Fire

Protection (Asia)

Ltd.

Wigan , UK

Intumescent coating

( water based)

Protection of 4-side

exposed hollow

column sections up

to 2 hrs. FRP.

BS 476:

Parts 20 &

21: 1987

UKAS Bodycote

Warringtonfire

WF No.

174358

19 June 2008 valid until

1August

2010

22/7/2008 It should be read in

conjunction with fire

assessment report WF

No. 156367 (expired

on 1.8.2008)

BD-FP

091

Phoenix

270-120

Phoenix Fire

Protection (Asia)

Ltd.

Wigan , UK

Intumescent coating

( water based)

Protection of high

strength steel rod

(MacAlloy Bars) up

to 2 hrs. FRP.

BS 476:

Parts 20 &

21: 1987

UKAS Bodycote

Warringtonfire

WF No.

167802

16 October

2007

valid until

1November

2009

22/7/2008 It should be read in

conjunction with fire

assessment report WF

No. 156367 (expired

on 1.8.2008)

Limiting temperature

for tension rod shall be

evaluated based on the

tensile force of the

member under

consideration.

BD-FP

092

Phoenix

270-120

Phoenix Fire

Protection (Asia)

Ltd.

Wigan , UK

Intumescent coating

( water based)

Protection of 4-side

exposed I- beam

sections up to 2 hrs

FRP.

BS 476:

Parts 20 &

21: 1987

UKAS Bodycote

Warringtonfire

WF No.

174358

19 June 2008 valid until

1August

2010

22/10/2008 It should be read in

conjunction with fire

assessment report WF

No. 156367 (expired

on 1.8.2008)

BD-FP

093

Tanda AP25 Warwick Building

Material Ltd

Guangzhou, China

Single component,

factory blended

cementitious spray

or trowel applied

coating

Protection of 3-side

exposed hollow

beam section; 4-side

exposed hollow

column section and

steel angle section

up to 2 hrs FRP.

BS 476:

Parts 20 &

21: 1987

HOKLAS Rearch

Engineering

Development

Façade

Consultants

Limited

R08C06 9 April 2008 valid until

8 April 2013

22/10/2008

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

094

Nullifire S605 Nullifire Limited

Coventry, UK

Solvent-borne

intumescent coating

Protection of 3-side

exposed I-section

beams and 4-side

exposed I-section

columns & beams up

to 2 hrs FRP.

Protection of 4-side

exposed CHS

columns up to 1 hr.

FRP.

BS 476:

Parts 20 &

21: 1987

UKAS Bodycote

Warringtonfire

WF No

165959

22 January

2008

Valid until

1 February

2013

23/1/2009 This is resulted from

the expiry of BD-FP

025

The relationship

between protection

thickness, section

factor, and fire

resistance period of

structural steel shall

refer to Table 1 & 2 of

report WF No. 165959.

BD-FP

095

Nullifire

System E

Nullifire Limited

Coventry, UK

Intumescent coating Protection of 4-side

exposed CHS up to

1 hr. FRP.

BS 476:

Parts 20 &

21: 1987

UKAS Bodycote

Warringtonfire

WF No

164410A

25 May 2007 Valid until

1 June 2012

23/1/2009 This is resulted from

the expiry of BD-FP

071

It should be read in

conjunction with fire

assessment report

WFRC No. C100578

& WFRC No.

C124329A (expired on

1.11.1999 & 1.5.2007

respectively)

BD-FP

096

Cafco 300 Promat

International

Bankok, Thailand

Plaster/ vermiculite

based product for

internal use.

Protection of 3-side

exposed I-section

beams and 4-side

exposed I-section

columns up to 4 hrs

FRP

BS 476:

Parts 20 &

21: 1987

Recognized by

PNAP 251

Building

Research

Establishment

CC 206998

Review 1

30 April 2007 next review

30 April

2012

23/1/2009 This is resulted from

the expiry of BD-FP

058

It should be read in

conjunction with fire

assessment report CC

206998

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

097

Cafco

Mandolite CP2

Promat

International

Bangkok ,Thailand

Spray applied, single

package factory

controlled premix,

based on vermiculite

and Portland cement

for internal use.

Upgrade reinforced

concrete slabs and

beams up to 4 hrs.

FRP.

BS 476:

Parts 20 &

21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No.

173530/A

Issue 2

28 May 2008 valid until

1 June 2013

23/1/2009 This is resulted from

the expiry of BD-FP

070

It should be read in

conjunction with fire

assessment report

Revision 1

WFRC No CP92117

BD-FP

098

Durasteel Floor

Assemblies

Intumex Asia

Pacific Pte. Ltd.

Blackburn, UK

Single layer of

9.5mm thick

Durasteel board,

fastened below a

framework of steel

channels spaced at

1000 center,

enclosing a cavity

containing 140kg/m3

density rock wool

with a minimum

overall thickness of

120mm.

Insulated ceiling

membrane

construction to

achieve 4 hours FRP

for the underside of

a composite floor

slab formed by steel

profile sheeting.

The ceiling

membrane is hung at

the slab soffit by

M20 steel threaded

hanger rods spaced

at 1200mm.

The ceiling

membrane will not

be subjected to

imposed load except

self weight.

BS 476:

Parts 22:

1987

Recognized by

PNAP 251

Building

Research

Establishment

CC208842

Review 1

6 July 2007 valid until

6 July 2012

23/1/2009 The construction

details should be

identical to those

covered in the

assessment reports.

All requirements given

in the assessment

reports should be

checked to ensure

compatibility with

proposed applications.

Fire stop/ sealant shall

be provided for the

interface between the

perimeter of the

Durasteel floor and the

surrounding structures

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

099

Promatect H Eternit

Guangzhou Co.

Ltd

Guangzhou,

China

Fibre-reinforced

calcium silicate

insulating board.

Protection of steel

beams and columns

up to 2 hrs. FRP.

BS 476:

Parts 20 &

21: 1987

Recognized by

PNAP 251

Building

Research

Establishment

CC84975

Review 5

9 January 2007 9 January

2012

23/1/2009 This is resulted from

the expiry of BD-FP

029

The relationship

between protection

thickness, section

factor, and fire

resistance period of

structural steel shall

refer to Table 3 of

report CC84975

Review 5

BD-FP

100

Monokote

Type Z-146

Grace Korea Inc

Inchon, Korea

Sprayed-applied

cementitious fire

protection material.

Protection of 3-side

exposed or 4-sides

exposed I-section

beams and columns

for FRP up to 1 hr.

Protection of 4-side

exposed hollow

section beams and

column for FRP up

to 1 hr.

BS 476:

Parts 20 &

21: 1987

UKAS Warrington

Fire Research

Centre

WFRC

Report No.

145418

8 March 2005 1 April 2010 23/1/2009 It should be read in

conjunction with fire

assessment report

WFRC No C81831 for

I-section and C109505

for hollow section.

BD-FP

101

Vermitex AF L&A Fazzini

Manufacturing Pty

Ltd.

Greenacre NSW,

Australia

Gypsum-vermiculite

coating

Protection of steel

I-sections, hollow

section and angle

section up to 1 hr.

FRP.

AS 1530.4

and BS 476:

Part 21

NATA CSIRO FCO-1299 1 July 2007 31 July 2012 30/4/2009 According to the

manufacturer’s

recommendation,

Vermitex AF is for

internal application.

BD-FP

102

Tanda AP25 Warwick Building

Material Ltd

Guangzhou, China

Single component,

factory blended

cementitious spray

or trowel applied

coating

Protection of 3-side

and 4-side exposed

I-section up to 4 hrs

FRP.

BS 476:

Parts 20 &

21: 1987

HOKLAS Rearch

Engineering

Development

Façade

Consultants

Limited

R08C06 9 April 2008 8 April 2013 30/4/2009

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

103

Hilti HIT-HY

150

Hilti Corporation

Kaufering,

Gemany

Hybrid resin system Injection system

for making

nominal

anchorage

connections of

Grade 460 rebars

of diameters up

to 25mm in

reinforced

concrete

elements up to 4

hrs. FRP.

BS 476: Part 20:

1987

UKAS Bodycote

Warringtonfire

WF Report

No. 166402

26 October

2007

1 November

2012

30/04/2009 Load carrying capacity

of the injection system

for rebar fixing under

the effects of fire

should be assessed

with an appropriate

factor of safety

compatible with the

structural design of the

parent structure.

BD-FP

104

Interchar 963 International Paint

Limited

Shanghai, China

Intumescent coating Protection of

3-side and 4-side

exposed steel

angles up to 1 hr.

FRP.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WFRC

Assessment

Report No.

136405

WF Report

No. 179990

15 January

2004

26 January

2009

1 February

2014

NA

12/08/2009

BD-FP

105

Interchar 973 International Paint

Limited

Shanghai, China

Intumescent coating Protection of

4-side exposed

I-section beams

and column up

to 1 hr. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No. 159150

3 September

2007

1 September

2012

12/08/2009

BD-FP

106

Vermiculux

Board

Intumex Asia

Pacific

Glasgow, UK

Low density

lightweight

non-combustible

board made from a

blend of calcium

silicate, vermiculite

and reinforced with

selected inorganic

fibres and fillers

Protection of

4-side exposed

I-section beams

and columns up

to 4 hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Building

Research

Establishment

CC 83123

Review 3

14 July 2008 14 July 2013 12/08/2009 Required thickness of

fire-resisting board

shall be in accordance

with Table 14 of BRE’s

assessment report .CC

83123 Review 3

BD-FP

107

Cafco

SprayFilm

WB3

Cafco International

UK

Guangzhou, China

Intumescent coating Protection of

steel channel

section up to 1

hr. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No.

176738A

19 September

2008

1 October

2013

4/11/2009 It should be read in

conjunction with

Warringtonfire’s

supplementary letter

176738/RHE.

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

108

Durasteel Floor

Assemblies

Intumex Asia

Pacific Pte. Ltd.

Blackburn, UK

Single layer of

9.5mm thick

Durasteel board,

fastened above and

below a framework

of steel channels,

enclosing a cavity

containing 140kg/m3

density rock wool

with a minimum

overall thickness of

80mm.

Fire resisting

floor assemblies

(construction

details are given

in the assessment

reports) for up to

2 hrs. FRP in

terms of

load-bearing

capacity,

integrity and

insulation.

Maximum

imposed load to

be 7.5kPa.

Additional 2 nos.

of cover strips

shall be required

for the top and

bottom flange of

the channel

sections for

insulation use.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No.

C181794C

30 March

2009

1 April 2014 4/11/2009 It should be read in

conjunction with fire

assessment report No

WFRC 141038.

The construction

details should be

identical to those

covered in the

assessment reports.

All requirements given

in the assessment

reports should be

checked to ensure

compatibility with

proposed applications.

Maximum load ratio of

structural steel

elements inside the

assembly shall be less

than or equal to 0.5

to BS5950: Part 1

Fire stop/ sealant shall

be provided for the

interface between the

perimeter of the

Durasteel floor and the

surrounding structures

BD-FP

109

Firetherm

Firesteel

Classic 120

Firetherm

Intumescent &

Insulation Supplies

Ltd.

Kent, UK

Solvent based

intumescent coating

Protection of

3-sides/ 4-sides

exposed steel

hollow beam

sections and

3-side exposed

steel channel

sections /

I-section up to 2

hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No.

C155649/A

WF Report

No.

C155649/B

15 June 2006

15 June 2006

1 July 2011

1 July 2011

4/11/2009 It should be read in

conjunction with fire

assessment report

WFRC C130414 &

C130413

Assessment applicable

to steel I-section up to

a maximum web size

of 686mm and flange

size of 305mm

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

110

Unitherm

38091

Sika

Korrosionsshutz

GmbH.

Stuttgart, Gemany

Intumescent coating Protection of

steel I-beams and

I-columns up to

2 hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No. 162163,

C105561

Issue 2,

C125126,

133000 and

summary

report WF

No. 133394.

19 March

2007

1 April 2012 22/2/2010

BD-FP

111

Unitherm

38091

Sika

Korrosionsshutz

GmbH.

Stuttgart, Gemany

Intumescent coating Protection of

steel RHS up to

2 hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No. 162164,

C105708,

C125342

Issue 2,

140896 and

summary

report WF

No. 126392

Issue 3..

19 March

2007

1 April 2012 22/2/2010

BD-FP

112

Cafco

SprayFilm

WB3

Cafco International

UK

Guangzhou, China

Intumescent coating Protection of

steel RHS,

channel and

angle section up

to 2 hrs. FRP

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No.

176738B for

RHS,

176738A

for channel

and angle

sections

4 April 2009

19 September

2009

1 October

2013

22/2/2010 It should be read in

conjunction with

Warringtonfire’s

supplementary letter

176738/RHE.for

channel and angle

section.

BD-FP

113

Firecut F-1 Yung Chi Paint &

Varnish Mfg. Co.

Ltd

Kaohsiung,

Taiwan

Cementitious

coating

Protection of

steel channel

section up to 1

hr. FRP

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No. 149330

Issue 2

18 November

2005

1 December

2010

25/8/2010

BD-FP

114

Isolatek WB3 Isolatek

International

Stanhope, USA

Water-based in

tumescent coating

Protection of

steel channel and

hollow section

up to 2 hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No.

169583B &

169583C

19 December

2007

1 January

2013

17/10/2011

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

115

Supalux Board Intumex Asia

Pacific

Guangzhou, China

Non-combustible

board

Protection of

steel hollow

section up to1 hr.

FRP.

BS 476: Parts 20

& 21: 1987

N/A Building

Research

Establishment

CC 82876

Review 2

Issue 2

27 March

2006

11 August

2010

17/10/2011 Required thickness of

fire-resisting board

shall be in accordance

with the provision

shown in BRE’s

assessment report

CC 82876 Review 2

Issue 2

BD-FP

116

Nullifire S606 Nullifire Limited

Coventry, UK

Intumescent

coating

Protection of

steel hollow

section, channel

section, I-section

up to 1 hrs. FRP.

BS 476: Parts 20

& 21: 1987

N/A Building

Research

Establishment

CC 92856A

Review 3

CC92856B

Review 3

19 March

2008

next review

date: 10

April 2013

17/10/2011 The relationship

between protection

thickness, section

factor, and fire

resistance of structural

steel shall refer to BRE

assessment report

number CC92856A,

Review 3. and

CC92856B Review 3

BD-FP

117

Monokote

MK6

W.R. Grace & Co.

Incheon City,

South Korea

Sprayed-applied

cementitious

fire-proofing

plaster.

Upgrading of

FRP of RC slab

and beam from 1

hr to 2 hrs.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No. 186522

3 September

2009

1 November

2014

17/10/2011 It should be read in

conjunction with fire

assessment report

WFRC No C107230

BD-FP

118

Firecut F-1 Yung Chi Paint &

Vanish Mfg. Co.

Ltd.

Kaohsiung,

Taiwan

Cementitious fire

rated coating

Protection of

steel channel

section up to

1 hr. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Warrington

Fire Research

Centre

WFRC

Report No.

149330

18 November

2005

1 December

2010

17/10/2011

BD-FP

119

Tanda AP25 Warwick Building

Material Ltd

Guangzhou, China

Single component,

factory blended

cementitious spray

or trowel applied

coating

Protection of

steel channel

section up to 4

hrs FRP.

BS 476: Parts 20

& 21: 1987

HOKLAS Rearch

Engineering

Development

Façade

Consultants

Limited

R08C06 9 April 2008 valid until

8 April 2013

17/10/2011

BD-FP

120

Hensotherm

3KS

Rudolf Hensel

GmbH

Bornsen, Germany

Solvent based

intumescent

coating

Protection of

steel I-section up

to 2 hrs FRP.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No. 170770

28 May 2009 1 June 2014 17/10/2011

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

121

Nullifire

S707-60

Nullifire Limited

Coventry, UK

Intumescent

coating

Protection of

steel I-section up

to 1 hr. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No. 205546

6 June 2011 next review

date: 1 June

2016

21/9/2012 It should be read in

conjunction with fire

assessment report WF

Report No 154065

BD-FP

122

Cafco

SprayFilm

WB3

Cafco International

UK

Guangzhou, China

Intumescent

coating

Protection of

steel I-section up

to 1 hr. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No.

176738A

19 September

2008

1 October

2013

21/9/2012 It should be read in

conjunction with fire

assessment report WF

Report No 152624

Issue 3.

BD-FP

123

Firecut F-1 Yung Chi Paint &

Vanish Mfg. Co.

Ltd.

Kaohsiung,

Taiwan

Cementitious fire

rated coating

Protection of

steel I-section,

steel channel

section and angle

section up to 4

hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WFRC

Report No.

179160

11 December

2008

1 January

2014

21/9/2012

BD-FP

124

Firetherm

Firesteel

120WB

Firetherm

Intumescent &

Insulation Supplies

Ltd.

Kent, UK

Water borne

intumescent

coating

Protection of

3-sides/ 4-sides

exposed steel

I-section and

4-side exposed

steel hollow

section up to 2

hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Report

No. 169988

28 January

2008

1 February

2013

3/7/2013

Reference List of Fire Protection Materials for Structural Use

Ref.

No.

Product

Name

Name of

Manufacturer

and Place of

Manufacture

(City and

Country)

Material

Category Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of

Posting on

CDB

Remarks /

Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP

125

Durasteel Floor

Assemblies

Intumex Asia

Pacific Pte. Ltd.

Blackburn, UK /

Zhejiang, PRC

Single layer of

9.5mm thick

Durasteel board,

fastened above and

below a framework

of steel channels,

enclosing a cavity

containing

140kg/m3 density

rock wool with a

minimum overall

thickness of

80mm.

Fire resisting

floor assemblies

(construction

details are given

in the assessment

report) for up to

1 hr. FRP in

terms of

load-bearing

capacity,

integrity and

insulation.

Maximum

imposed load to

be 10kPa.

Additional 1 no.

of 9.5mm thick

Durasteel cover

strip shall be

required for the

top and bottom

flange of the

channel sections

for insulation

use.

BS 476: Parts 20

& 21: 1987

Department of

Standards

Malaysia

UKAS

Fire Science

Research

Group

(Malaysia)

Exova

Warringtonfire

FSRG

2014/005

WF Report

No. 189172

27 February

2014

21 December

2009

NA

1 January

2015

9 June 2014 The construction

details should be

identical to those

covered in the

assessment report.

All requirements given

in the assessment

reports should be

checked to ensure

compatibility with

proposed applications.

The assembly shall be

supported by structural

members with fire

protection system for

the relevant fire

resistance period.

Fire stop/ sealant shall

be provided for the

interface between the

perimeter of the

Durasteel floor and the

surrounding structures

BD-FP

126

Firecut

FM-900

Yung Chi Paint &

Varnish Mfg Co

Ltd.

Koahsiung,

Taiwan

Single pack

solvent based

intumescent

coating

Protection of

steel I-sections

with 3-side or

4-side exposed

up to 2 hrs. FRP.

BS 476: Parts 20

& 21: 1987

UKAS Exova

Warringtonfire

WF Review

Report No.

316831

23 March

2012

1 April 2017 9 June 2014 It should be read in

conjunction with

Bodycote

Warringtonfire fire

assessment report WF

No. 167317.

BD-FP

127

Firecut

FM-900

Yung Chi Paint &

Varnish Mfg Co

Ltd.

Koahsiung,

Taiwan

Single pack

solvent based

intumescent

coating

Protection of

steel angle,

channel and

I-sections with

3-side or 4-side

exposed to 1 hr.

FRP.

BS 476: Parts 20

& 21: 1987

UKAS Bodycote

Warringtonfire

WF Review

Report No.

307644

16 May 2011 1 June 2016 9 June 2014 It should be read in

conjunction with

Bodycote

Warringtonfire

assessment report WF

No. 145918.

Reference List of Fire Protection Materials for Structural Use

Ref. No.

Product Name

Name of Manufacturer and Place of Manufacture

(City and Country)

Material Category

Application Compliance

Testing

Standard

Details of Test or Assessment Report Date of Posting on

CDB

Remarks / Comments

Name of

Laboratory

Accreditation

Body

Name of

Laboratory /

Assessing

Organization

Report No. Date of Test /

Assessment

Report

Validity

Date

BD-FP 128

Ramset EPCON G5 Injection Adhesive with Grade 460 high yield deformed bars of diameters 12mm to 40mm

ITW Red Head

Illinois, USA Epoxy injection system

Injection system for making anchorage connections of Grade 460 rebars of diameters 12mm to 40mm in reinforced concrete elements up to 4 hrs. FRP.

BS 476: Part 20: 1987

UKAS Exova Warringtonfire

EWFA Report No. 25276-00

30 September 2010

30 November

2015

01/09/2014 It should be read in conjunction with Warringtonfire assessment report no. 45838.4.

Load carrying capacity of the injection system for rebar fixing under the effects of fire should be assessed with an appropriate factor of safety compatible with the structural design of the parent structure.

BD-FP 129

Firetex FX-5090

Sherwin-Williams Protective & Marine Coating

Bolton, UK

Intumescent coating

(water based)

Protection of steel I-sections and hollow sections with 3-side or 4-side exposed up to 2 hrs. FRP.

BS 476: Parts 20 & 21: 1987

UKAS Exova Warringtonfire

WF Report No. 336628

WF Report No. 347568

28 January 2014

9 July 2015

1 February 2019

1 June 2020

31 August 2016

The construction details should be identical to those covered in the assessment reports. All requirements given in the assessment reports should be checked to ensure compatibility with proposed applications.

BD-FP 130

Sika Unitherm Platinum-120

Sika Korrosionsshutz GmbH. Stuttgart, Germany

Intumescent coating

Protection of steel Rectangular and Circular Hollow columns up to 120 mins. FRR.

BS 476: Parts 20 & 21: 1987

UKAS Warringtonfire Testing and Certification Limited

WF Report No. 352248 issue 3

17 July 2019 1 August 2024

30 December 2019

The construction details should be identical to those covered in the assessment reports.