Central Cables Berhad

GUIDE TO THE USE OF PVC- INSULATED CABLES

CABLE TYPE AND USE

Single core, non-sheathed generalpurpose.

Installation in surface mounted orembedded conduits or similar closed

systems.

Single core, non-sheathed, for internal wiring.

Fixed protected installation. Insideappliances and in or on lighting ttings.

Light PVC- sheathed.

Fixed installation in dry or damp premises.

Single core, at twin and at -core,PVC-sheathed, with and without

protective conductor.

Fixed installation in dry or damp premises.

The cables are suitable for use where the combination ambient temperature and temperature rise

due to load results in a conductor temperature not exceeding 70°C and case of a short-circuit

(maximum allowance time is 5 seconds) the maximum conductor temperature does not exceed

0°C, up to and including 00 s . mm. and 0°C for si es above 00 s . mm.

COMMENTS

Suitable for use in channels with cover.Suitable for xed protected installation in or lighting ttings and inside appliances, up to 1000V ac or up to 750 V to earth,

dc.

Suitable for installation in surface mountedor embedded conduits, only for signalling

or control circuits.

Unsuitable for outdoor use or embedding in concrete.

Suitable for installation in walls, on boards and in channels, or embedded in

plaster.

1

Page 4: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC ARMOURED

2

PVC INSULATED PVC SHEATHED ARMOURED CABLE

CONSTRUCTION

Conductor : Plain annealed copper

Insulation : General purpose PVC compound TI 1 70°C

Colour of cores : Single core - red or black (or other colours are upon request)

2 cores - red and black

cores - red, yellow and blue

4 cores - red, yellow, blue and black

Formation : (i) Single core

(ii) 2, or 4 cores

- Stranded together and the interstices may be lled with the sheathing compound or non-hygroscopic llers a binder tape may be applied over the laid-up cores.

Bedding : Black general purpose PVC compound TI 1 70°C

Armour : Single core - Aluminium wires

2, or 4 cores - Galvanised steel wires

Sheath : Black general purpose PVC compound TM1 70°C

Page 5: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC ARMOURED

PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE)(BS 6346, 600/1000V)

5

1070

1400

1750

2100

2570

250

0

5100

5210

7750

1 .4

21.4

2 .7

26.6

28.6

1.1

4.4

7.2

42.2

45.7

4 .

0.8

0.8

0.8

1.0

1.0

1.0

1.0

1.0

1.2

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

2.8

2.8

1 1.78

1 2.14

1 2.52

7 2.0

7 2.25

7 2.52

61 2.25

61 2.52

61 2.85

61 .20

61 .65

1.5

1.6

1.6

1.7

1.7

1.8

1.

1.

2.1

2.1

2.2

1.25

1.25

1.25

1.6

1.6

1.6

1.6

1.6

2.0

2.0

2.0

50

70

5

120

150

185

240

00

400

500

6 0

Nominalcross-

sectionalarea of

conductor

mm2

NumberWire

diameter

No. mm

Thicknessof

insulation

mm

Thicknessof

bedding

mm

Approx.overall

diameter

mm

Approx.net

weight

kg km

Diameterof

armourwire

mm

Thicknessof sheath

mm

3

Page 6: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC ARMOURED

PVC INSULATED, PVC SHEATHED ARMOURED CABLE (2-CORE)(BS 6346, 600/1000V)

Nominalcross-

sectionalarea of

conductor

mm2

NumberWire

diameter

No. mm

Thicknessof

insulation

mm

Thicknessof

bedding

mm

Approx.overall

diameter

mm

Approx.net

weight

kg km

Diameterof

armourwire

mm

Thicknessof sheath

mm

4

11.

12.5

1 .

1 .7

15.2

16.5

20.1

22.2

26.2

25.

28.

0.

6.0

8.6

41.8

47.1

51.

57.0

62.

00

0

70

400

460

540

860

1080

15 0

1700

2110

2610

650

4 10

5050

6570

8100

7 0

11 10

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

1.0

1.0

1.0

1.0

1.2

1.2

1.2

1.4

1.4

1.6

1.6

0.6

0.6

0.7

0.7

0.8

0.8

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

1 1. 8

7 0.5

1 1.78

7 0.67

7 0.85

7 1.04

7 1. 5

7 1.70

7 2.14

1 1.5

1 1.78

1 2.14

1 2.52

7 2.0

7 2.25

7 2.52

61 2.25

61 2.52

61 2.85

1.5

1.5

2.5

2.5

4

6

10

16

25

5

50

70

5

120

150

185

240

00

400

0.

0.

0.

0.

0.

0.

1.25

1.25

1.6

1.6

1.6

1.6

2.0

2.0

2.0

2.5

2.5

2.5

2.5

1.

1.4

1.4

1.4

1.4

1.5

1.6

1.6

1.7

1.8

1.

1.

2.1

2.2

2.

2.4

2.5

2.7

2.

Page 7: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC ARMOURED

PVC INSULATED, PVC SHEATHED ARMOURED CABLE (3-CORE)(BS 6346, 600/1000V)

Nominalcross-

sectionalarea of

conductor

mm2

NumberWire

diameter

No. mm

Thicknessof

insulation

mm

Thicknessof

bedding

mm

Approx.overall

diameter

mm

Approx.net

weight

kg km

Diameterof

armourwire

mm

Thicknessof sheath

mm

12.

12.

1 .5

14.

15.

18.0

21.1

2 .

27.5

28.2

1.7

6.

40.7

4 .7

4 .1

5 .7

5 .8

65.4

71.8

0

50

70

420

520

750

1010

1 10

1 20

2200

2810

8 0

4 70

5 00

7510

050

11 0

1 750

16840

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.6

0.6

0.6

0.7

0.7

0.8

0.8

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

1 1. 8

7 0.5

1 1.78

7 0.67

7 0.85

7 1.04

7 1. 5

7 1.70

7 2.14

1 1.5

1 1.78

1 2.14

1 2.52

7 2.0

7 2.25

7 2.52

61 2.25

61 2.52

61 2.85

1.5

1.5

2.5

2.5

4

6

10

16

25

5

50

70

5

120

150

185

240

00

400

0.

0.

0.

0.

0.

1.25

1.25

1.25

1.6

1.6

1.6

2.0

2.0

2.0

2.5

2.5

2.5

2.5

2.5

1.4

1.4

1.4

1.4

1.4

1.5

1.6

1.6

1.7

1.8

1.

2.0

2.1

2.2

2.4

2.5

2.6

2.8

.0

5

Page 8: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC ARMOURED

PVC INSULATED, PVC SHEATHED ARMOURED CABLE (4-CORE)(BS 6346, 600/1000V)

Nominalcross-

sectionalarea of

conductor

mm2

NumberWire

diameter

No. mm

Thicknessof

insulation

mm

Thicknessof

bedding

mm

Approx.overall

diameter

mm

Approx.net

weight

kg km

Diameterof

armourwire

mm

Thicknessof sheath

mm

1 .0

1 .7

14.6

15.2

17.

1 .2

22.6

26.5

2 .

1.2

6.4

40.

45.

50.

54.6

60.

67.0

7 .5

82.7

60

80

450

470

7 0

870

1200

1770

2 40

2810

880

4 60

6400

8110

6 0

11700

14750

17860

2 110

0.8

0.8

0.8

0.8

0.8

0.8

0.8

1.0

1.0

1.0

1.2

1.2

1.2

1.4

1.4

1.6

1.6

1.6

1.6

0.6

0.6

0.7

0.7

0.8

0.8

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

1 1. 8

7 0.5

1 1.78

7 0.67

7 0.85

7 1.04

7 1. 5

7 1.70

7 2.14

1 1.5

1 1.78

1 2.14

1 2.52

7 2.0

7 2.25

7 2.52

61 2.25

61 2.52

61 2.85

1.5

1.5

2.5

2.5

4

6

10

16

25

5

50

70

5

120

150

185

240

00

400

0.

0.

0.

0.

1.25

1.25

1.25

1.60

1.6

1.6

2.0

2.0

2.0

2.5

2.5

2.5

2.5

2.5

.15

1.4

1.4

1.4

1.4

1.5

1.5

1.6

1.6

1.8

1.

2.0

2.1

2.2

2.4

2.5

2.6

2.8

.0

.

6

Page 9: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC ARMOURED

PVC INSULATED PVC SHEATHED ARMOURED AUXILIARY CABLE

PVC INSULATED, PVC SHEATHED ARMOURED AUXILIARY CABLE (1.5mm2)(BS 6346, 600/1000V)

Numberof core

7

0.8

0.8

0.8

0.8

0.8

1.0

1.0

1.0

0.

0.

1.25

1.25

1.25

1.6

1.6

1.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

7 0.5

7 0.5

7 0.5

7 0.5

7 0.5

7 0.5

7 0.5

7 0.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

5

7

10

12

1

27

7

48

1.4

1.4

1.5

1.5

1.6

1.7

1.8

1.

14.5

15.4

1 .2

18.6

22.

26.

2 .5

.1

4 0

500

780

8 0

10 0

1600

1 40

2 60

CONSTRUCTION

Conductor : Plain annealed copperInsulation : General purpose PVC compound TI 1 70°CColour of cores : White with black numberingFormation : Stranded together and the interstices may be filled with filler or the sheathing compound. Binder tape may be applied over the laid-up cores.Bedding : Black general purpose PVC compound TM1 70°CArmour : Galvanised steel wireSheath : Black general purpose PVC compound TM1 70°C

Nominalcross-

sectionalarea of

conductor

mm2

ConstructionNo. Wirediameter

No. mm

Thicknessof

insulation

mm

Thicknessof

bedding

mm

Approx.overall

diameter

mm

Approx.net

weight

kg km

Diameterof

armourwire

mm

Thicknessof sheath

mm

Page 10: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC ARMOURED

PVC INSULATED, PVC SHEATHED ARMOURED AUXILIARY CABLE (4mm2)(BS 6346, 600/1000V)

PVC INSULATED, PVC SHEATHED ARMOUREDAUXILIARY CABLE (2.5mm2)(BS 6346, 600/1000V)

Numberof core

Numberof core

5

7

10

12

1

27

7

48

5

7

10

12

1

27

7

48

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

4

4

4

4

4

4

4

4

7 0.67

7 0.67

7 0.67

7 0.67

7 0.67

7 0.67

7 0.67

7 0.67

7 0.85

7 0.85

7 0.85

7 0.85

7 0.85

7 0.85

7 0.85

7 0.85

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

1.0

1.0

1.0

1.2

0.8

0.8

1.0

1.0

1.0

1.2

1.2

1.2

0.

1.25

1.25

1.25

1.6

1.6

1.6

2.0

1.25

1.25

1.6

1.6

1.6

2.0

2.0

2.0

1.5

1.5

1.6

1.6

1.7

1.8

1.

2.1

1.5

1.6

1.7

1.7

1.8

2.0

2.1

2.2

16.4

18.1

21.8

22.4

26.7

0.

4.1

.8

1 .1

20.6

26.1

26.8

0.6

7.2

41.0

46.1

550

750

1000

1080

1640

2110

2600

520

820

70

1500

16 0

2170

170

10

47 0

Nominalcross-

sectionalarea of

conductor

mm2

Nominalcross-

sectionalarea of

conductor

mm2

ConstructionNo. Wirediameter

No. mm

ConstructionNo. Wirediameter

No. mm

Thicknessof

insulation

mm

Thicknessof

insulation

mm

Thicknessof

bedding

mm

Thicknessof

bedding

mm

Approx.overall

diameter

mm

Approx.overall

diameter

mm

Approx.net

weight

kg km

Approx.net

weight

kg km

Diameterof

armourwire

mm

Diameterof

armourwire

mm

Thicknessof sheath

mm

Thicknessof sheath

mm

8

Page 11: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC ARMOURED

PVC INSULATED PVC SHEATHED ARMOUREDWITH REDUCED NEUTRAL CABLE

PVC INSULATED, PVC SHEATHED ARMOURED WITH REDUCED NEUTRAL CABLE (4-CORE)(BS 6346 & MS 274, 600/1000V)

9

CONSTRUCTION

Conductor : Plain annealed copperInsulation : General purpose PVC compound TI 1 70°CColour of cores : Red, yellow, blue and black (neutral)Formation : Stranded together and the interstices may be filled with the sheathing compound. A non-hygroscopic filler with a binder tape may be applied over the laid-up cores.Bedding : Black general purpose PVC compoundArmour : Galvanised steel wiresSheath : Black general purpose PVC compound TM1 70°C

Nominalcross-

sectionalarea of

conductor

mm2

Phase Conductor Neutral Conductor

Nominalcross-

sectionalarea

mm2

ConstructionNumber

Wirediameter

No mm

ConstructionNumber

Wirediameter

No mm

Thicknessof

insulation

mm

Thicknessof

insulation

mm

Thicknessof

bedding

mm

Approx.overall

diameter

mm

Approx.net

weight

kg km

Diameterof armour

Wire

mm

Thicknessof

sheath

mm

25

5

50

70

5

120

150

185

240

00

00

400

7 2.14

1 1.5

1 1.78

1 2.14

1 2.52

7 2.0

7 2.25

7 2.52

61 2.25

61 2.52

61 2.52

61 2.85

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.4

2.6

16

16

25

5

50

70

70

5

120

150

185

185

7 1.70

7 1.70

7 2.14

1 1.5

1 1.78

1 2.14

1 2.14

1 2.52

7 2.0

7 2.25

7 2.52

7 2.52

1.0

1.0

1.2

1.2

1.4

1.4

1.4

1.6

1.6

1.8

2.0

2.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.4

1.6

1.6

1.6

1.8

1.6

1.6

1.6

2.0

2.0

2.5

2.5

2.5

2.5

2.5

2.5

.15

1.8

1.8

1.

2.0

2.2

2.

2.4

2.5

2.7

2.

2.

.1

2 .

1.0

5.0

40.1

45.

50.1

54.4

5 .7

66.8

7 .2

7 .2

82.

2220

26 0

70

4650

5 80

76 0

7 0

10840

1 640

16440

16710

21260

Page 12: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC ARMOURED

TECHNICAL DATA CURRENT RATING

Current ratings are based on the following conditions:

1. Ambient air temperature 0°C

2. Ground temperature 15°C

. Soil thermal resistivity 1.2°C m W

4. Depth of laying: (a) For 600 1000V cables 0.5m

(b) For 1 00 00V cables 0.8m

5. Maximum conductor operating temperature 70°C

Rating factors of other temperature:

Cable in air

Temperature 25°C 0°C 5°C 40°C 45°C

Factor 1.06 1.00 0. 4 0.87 0.7

Cables in ground

Temperature 15°C 20°C 25°C 0°C 5°C

Factor 1.00 0. 5 0. 0 0.8 0.80

600/1000V COPPER CONDUCTOR PVC ARMOURED CABLES (SINGLE-CORE)

Currentrating

A

Laid directin ground

(15°C trefoil)

2 cables, single-phase

ac flat & touching

or 4 cables, -phase

ac flat & touching

2 cables, dc Horizontal

space

Laid in free airLaid on cable tray

cables, phase space

ac trefoil

Nominalcross-

sectionalarea of

conductor

mm2

Currentrating

A

Currentrating

A

Currentrating

A

Currentrating

A

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

50705

12015018524000

4005006 0

20525160

4146550624728058 1

0. 50.680.520.40. 70. 20.270.240.220.210.1 5

182 8285277

4224 254761867728

0.840.620.500.40. 80. 40. 00.280.260.250.24

222 457

41547548648748885

10 51218

0.0.60.460. 6 0.20.20.18

0.1450.1050.0850.068

1812 1280247

4255015676577 180

0.820.580.450. 70. 20.270.20.21

0.1 50.180.17

22827

481

4274825586271681012

10

Page 13: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC ARMOURED

600/1000V COPPER CONDUCTOR PVC ARMOURED CABLES (MULTI-CORE)

Currentrating

A

Laid directin ground

(15°C trefoil)

2 core & 4 core 2 core

Laid in free airLaid on cable tray

& 4 core

Nominalcross-

sectionalarea of

conductor

mm2

Currentrating

A

Currentrating

A

Currentrating

A

Currentrating

A

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

1.5

2.5

4

6

10

16

25

5

50

70

5

120

150

185

240

00

400

21

28

8

4

67

8

118

145

175

222

26

10

55

405

476

547

621

2

18

11

7.

4.4

2.8

1.75

1.25

0. 4

0.65

0.50

0.41

0. 4

0.2

0.24

0.21

0.185

18

25

42

58

77

102

125

151

1 2

2 1

267

06

48

40

46

540

25

15

.5

6.4

.8

2.4

1.5

1.1

0.81

0.57

0.4

0. 5

0.2

0.25

0.21

0.185

0.16

22

1

41

5

72

7

128

157

1 0

241

2 1

6

86

4

516

5 2

68

2

18

11

7.

4.4

2.8

1.75

1.25

0. 4

0.65

0.5

0.41

0. 4

0.2

0.24

0.21

0.185

1

26

5

45

62

8

110

1 5

16

207

251

2 0

2

78

445

510

5 0

25

15

.5

6.4

.8

2.4

1.5

1.1

0.81

0.57

0.4

0. 5

0.2

0.25

0.21

0.185

0.16

22

2

8

48

64

8

110

1 1

157

1 1

22

26

2

1

87

4

485

11

Page 14: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC ARMOURED

12

600/1000V ALUMINIUM CONDUCTOR PVC ARMOURED CABLES (MULTI-CORE)

* The Voltage drop between consumer’s terminals and any other point in the installation must not exceed 4% of the nominal voltage.

Defineded ConditionsClipped Direct to a surface of on a Cable Tray, and Unenclosed

Conductor Nominalcross-

sectionalarea of

conductor

mm2

Currentrating

A

Currentrating

A

Currentrating

A

Currentrating

A

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

One Twin cable single-phase

ac or dc

One or 4-core Cable

Three-Phase

One Twin cable single-phase

ac or dc

One or 4-core Cable

Three-Phase

1.5

2.5

4

6

10

16

25

5

50

70

5

120

150

185

240

00

400

-

-

-

8

52

68

1

112

180

220

270

10

55

410

485

550

620

14

20

26

2

45

58

76

150

180

225

260

2 0

40

400

460

520

28

17

11

7.0

4.1

2.6

1.7

1.2

a.c. d.c

0. 2 0. 2

0.65 0.64

0.48 0.46

0.40 0. 6

0. 2 0.25

0.2 0.2

0.25 0.18

0.2 0.14

0.22 0.11

-

-

-

7.0

4.1

2.6

1.7

1.2

a.c. d.c

0. 2 0. 2

0.65 0.64

0.48 0.46

0.40 0. 6

0. 2 0.25

0.2 0.2

0.25 0.18

0.2 0.14

0.22 0.11

1

17

22

28

8

50

66

80

125

155

1 0

220

250

2 0

50

400

460

-

-

-

2

44

58

77

4

155

1 0

2 0

270

10

50

420

475

550

24

15

.1

6.0

.6

2.2

1.5

1.0

0.81

0.57

0.42

0. 4

0.2

0.24

0.20

0.18

0.17

-

-

-

6.0

.6

2.2

1.5

1.0

0.81

0.57

0.42

4

0.2

0.24

0.20

0.18

0.17

Page 15: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC UNARMOURED

PVC INSULATED CABLE (BS 6004, 450/750V)

Nominal Cross-Sectional area

of conductor

mm2

Number Wire diameter of

wires

No. mm

Thickness ofinsulation

mm

Approx. overalldiameter

mm

Approx. netweight

kg km

1.5

1.5

2.5

2.5

4

6

10

16

25

5

50

70

5

120

150

185

240

00

400

500

6 0

1 1. 8

7 0.58

1 1.78

7 0.67

7 0.85

7 1.04

7 1. 5

7 1.70

7 2.14

1 1.5

1 1.78

1 2.14

1 2.52

7 2.0

7 2.25

7 2.52

61 2.25

61 2.52

61 2.85

61 .20

61 .65

0.7

0.7

0.8

0.8

0.8

0.8

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

2.8

2.8

2.

.1

.5

.7

4.

4.8

6.2

7.2

8.

10.2

11.

1 .7

16.0

17.6

1 .6

21.

25.0

27.8

1.2

4.7

8.7

22

24

5

8

50

70

125

178

2 0

00

500

725

1225

1510

1 10

24 0

110

70

4 0

6 70

13

CONSTRUCTION

Conductor : Plain annealed copper

Insulation : General purpose PVC compound TI 1 70°C

Colour of cores : Red, Black or other colours

PVC INSULATED CABLE

Page 16: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC UNARMOURED

PVC INSULATED PVC SHEATHEDUNARMOURED CABLE

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE(1-CORE)(BS 6004, 300/500V)

1.5

2.5

4

6

10

16

25

5

0.7

0.8

0.8

0.8

1.0

1.0

1.2

1.2

0.8

0.8

0.

0.

0.

1.0

1.1

1.1

4.7

5.

6.

6.8

8.2

.4

11.

12.6

7

51

76

150

220

40

440

1 1. 8

1 1.78

7 0.85

7 1.04

7 1. 5

7 1.70

7 2.14

1 1.5

14

CONSTRUCTION

Conductor : Plain annealed copperInsulation : General purpose PVC compound TI 1 70°CColour of cores : Single core - red and black ( Other colours are upon request) 2 cores - red and black cores - red, yellow and blue 4 cores - red, yellow, blue and blackFormation : (i) Single core (ii) 2, or 4 cores - stranded together and the interstices may be filled with the sheathing compound. A non-hygroscopic fillers or a binder tape may be applied over the laid-up cores.

Sheath : Black general purpose PVC compound TM1 70°C

Nominal Cross-Sectional area

of conductor

mm2

NumberWire

diameter

No. mm

Thickness of

insulation

mm

Thickness of

sheath

mm

Approx. overalldiameter

mm

Approx. netweight

kg km

Page 17: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC UNARMOURED

15

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (2-CORE)(BS 6004, 300/500V)

1.5

1.5

2.5

2.5

4

6

10

0.7

0.7

0.8

0.8

0.8

0.8

1.0

1.2

1.2

1.2

1.2

1.2

1.2

1.4

8.5

8.

.7

10.1

11.2

12.

15.

100

110

140

150

200

260

415

1 1. 8

7 0.5

1 1.78

7 0.67

7 0.85

7 1.04

7 1. 5

Nominal Cross-Sectional area

of conductor

mm2

NumberWire

diameter

No. mm

Thickness of

insulation

mm

Thickness of

sheath

mm

Approx. overalldiameter

mm

Approx. netweight

kg km

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (3-CORE)(BS 6004, 300/500V)

1.5

1.5

2.5

2.5

4

6

10

0.7

0.7

0.8

0.8

0.8

0.8

1.0

1.2

1.2

1.2

1.2

1.2

1.4

1.4

8.

.4

10.2

10.7

11.

1 .5

16.

120

1 0

170

180

240

20

52

1 1. 8

7 0.5

1 1.78

7 0.67

7 0.85

7 1.04

7 1. 5

Nominal Cross-Sectional area

of conductor

mm2

NumberWire

diameter

No. mm

Thickness of

insulation

mm

Thickness of

sheath

mm

Approx. overalldiameter

mm

Approx. netweight

kg km

Page 18: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC UNARMOURED

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (4-CORE)(BS 6004, 300/500V)

1.5

1.5

2.5

2.5

4

6

10

0.7

0.7

0.8

0.8

0.8

0.8

1.0

1.2

1.2

1.2

1.2

1.4

1.4

1.4

.7

10.2

11.2

11.7

1 .4

14.7

17.

150

160

210

220

10

410

660

1 1. 8

7 0.5

1 1.78

7 0.67

7 0.85

7 1.04

7 1. 5

16

Nominal Cross-Sectional area

of conductor

mm2

NumberWire

diameter

No. mm

Thickness of

insulation

mm

Thickness of

sheath

mm

Approx. overalldiameter

mm

Approx. netweight

kg km

Page 19: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC UNARMOURED

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE(MULTI CORE) AUXILIARY(BS 6004, 300/500V)

17

PVC INSULATED PVC SHEATHED CABLES

CONSTRUCTION

Conductor : Plain annealed copper

Insulation : General purpose PVC compound TI 1 70°C

Sheath : Black general purpose PVC compound TM1 70°C

Colour of cores : White with numbering

77101012121127277777101012121127277771012

1.51.51.51.51.51.51.51.51.51.51.51.52.52.52.52.52.52.52.52.52.52.52.52.5444

1 1. 87 0.51 1. 87 0.51 1. 87 0.51 1. 87 0.51 1. 87 0.51 1. 87 0.51 1.787 0.671 1.787 0.671 1.787 0.671 1.787 0.671 1.787 0.671 1.787 0.677 0.857 0.857 0.85

0.70.70.70.70.70.70.70.70.70.70.70.70.80.80.80.80.80.80.80.80.80.80.80.80.80.80.8

1.21.21.1.1.1.1.1.41.41.51.51.61.1.1.41.41.41.41.51.51.61.61.71.71.41.5

1.5

11.612.215.115.815.216.118.01 .021.622.24.025.81 .21 .717.017.817.018.020.621.525.526.027.528.816.020.2

20.8

22024020506080

54056074076080

1010200

4 04504 0520770810

108011 014 014 0520670

780

Numberof core

Nominalcross-

sectionalarea of

conductor

mm2

NumberNominaldiameterof wires

mm

Thicknessof

insulation

mm

Approx.Overall

diameter

mm

Approx.net

weight

kg km

Thicknessof sheath

mm

Page 20: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC UNARMOURED

PVC INSULATED PVC SHEATHED SHEATHEDUNARMOURED CABLE

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE(1-CORE)(BS 6364 & MS 274, 600/1000V)

50

70

5

120

150

185

240

00

400

500

6 0

800

1000

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

2.8

2.8

2.8

.0

1.4

1.4

1.5

1.5

1.6

1.7

1.8

1.

2.0

2.1

2.2

2.

2.5

14.

16.

1 .2

20.8

2 .0

25.5

28.8

1.8

5.4

.1

4 .

47.8

5 .1

600

820

1110

1150

1680

2080

2710

400

4 00

5 50

6800

8560

10770

1 1.78

1 2.14

1 2.52

7 2.0

7 2.25

7 2.52

61 2.25

61 2.52

61 2.85

61 .20

61 .65

127 2.85

127 .20

18

CONSTRUCTION

Conductor : Plain annealed copper or aluminiumInsulation : General purpose PVC compound TI 1 70°CColour of cores : Single core - red and black 2 cores - red and black cores - red, yellow and blue 4 cores - red, yellow, blue and blackFormation : (i) Single core (ii) 2, or 4 cores - stranded together and the interstices may be filled with the sheathing compound. A non-hygroscopic filler or binder tape may be applied over the laid-up cores.Sheath : Black general purpose PVC compound TM1 70°C

Nominal Cross-Sectional area

of conductor

mm2

NumberWire

diameter

No. mm

Thickness of

insulation

mm

Thickness of

sheath

mm

Approx. overalldiameter

mm

Approx. netweight

kg km

Page 21: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC UNARMOURED

19

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (2-CORE)(BS 6346, 600/1000V)

1016255

50705

12015018524000

400

7 1. 57 1.707 2.14

1 1.51 1.781 2.141 2.527 2.07 2.257 2.52

61 2.2561 2.5261 2.85

1.01.01.21.21.41.41.61.61.82.02.22.42.6

16.218.21.01 .22.725.52 .21.85.0.1

4 . 48.65 .

1.81.81.81.81.81.2.02.12.22.42.52.72.

46061088050

1200166022502780410

426055506 208780

Nominal Cross-Sectional area

of conductor

mm2

NumberWire

diameter

No. mm

Thickness of

insulation

mm

Thickness of

sheath

mm

Approx. overalldiameter

mm

Approx. netweight

kg km

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (3-CORE)(BS 6346, 600/1000V)

Nominal Cross-Sectional area

of conductor

mm2

NumberWire

diameter

No. mm

Thickness of

insulation

mm

Thickness of

sheath

mm

Approx. overalldiameter

mm

Approx. netweight

kg km

1016255

50705

12015018524000

400

7 1. 57 1.707 2.14

1 1.51 1.781 2.141 2.527 2.07 2.257 2.52

61 2.2561 2.5261 2.85

1.01.01.21.21.41.41.61.61.82.02.22.42.6

1.81.81.81.81.81.2.12.22.2.52.62.8.1

17.21 .422.22.826.12 .54.17.1

40.45.751.457.06 .6

510740

10 01 50180024 0

04160510064008 50104001 200

Page 22: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC UNARMOURED

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (4-CORE)(BS 6346, 600/1000V)

10

16

25

5

50

70

5

120

150

185

240

00

400

7 1. 5

7 1.70

7 2.14

1 1.5

1 1.78

1 2.14

1 2.52

7 2.0

7 2.25

7 2.52

61 2.25

61 2.52

61 2.85

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

1.8

1.8

1.8

1.8

1.

2.0

2.2

2.

2.5

2.6

2.8

.1

.

18.7

21.

24.5

25.6

2 .6

.5

8.7

42.1

46.6

51.

58.6

65.

72.6

710

40

1400

1810

2440

20

4560

5600

6 00

8610

11280

14100

17840

20

Nominal Cross-Sectional area

of conductor

mm2

NumberWire

diameter

No. mm

Thickness of

insulation

mm

Thickness of

sheath

mm

Approx. overalldiameter

mm

Approx. netweight

kg km

Page 23: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

PVC UNARMOURED

PVC INSULATED PVC SHEATHED UNARMOURED WITH REDUCED NEUTRAL CABLE

PVC INSULATED, PVC SHEATHED UNARMOURED WITH REDUCED NEUTRAL CABLE (4-CORE)(BS 6346 & MS 274, 600/1000V)

21

CONSTRUCTION

Conductor : Plain annealed copperInsulation : General purpose PVC compound TI 1 70°CColour of cores : Red, yellow, blue and black (neutral)Formation : Stranded together and the interstices may be filled with the sheathing compound. A non-hygroscopic filter or binder tape may be applied over the laid-up cores.Sheath : Black general purpose PVC compound TM1 70°C

Phase Conductor Neutral Conductor

Nominal

cross-

sectional

area of

conductor

mm2

Nominal

cross-

sectional

area of

conductor

mm2

ConstructionNo Wirediameter

No mm

ConstructionNo Wirediameter

No mm

Thicknessof

insulation

mm

Thicknessof

insulation

mm

Approx.overall

diameter

mm

Approx.net

weight

kg km

Thicknessof

sheath

mm

25

5

50

70

5

120

150

185

240

00

00

400

7 2.14

1 1.5

1 1.78

1 2.14

1 2.52

7 2.0

7 2.25

7 2.52

61 2.25

61 2.52

61 2.52

61 2.85

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.4

2.6

16

16

25

5

50

70

70

5

120

150

185

185

7 1.70

7 1.70

7 2.14

1 1.5

1 1.78

1 2.14

1 2.14

1 2.52

7 2.0

7 2.25

7 2.52

7 2.52

1.0

1.0

1.2

1.2

1.4

1.4

1.4

1.6

1.6

1.8

2.0

2.0

1.8

1.8

1.

2.0

2.1

2.2

2.4

2.5

2.7

2.

2.

.2

24.5

25.6

2 .6

.5

8.5

41.

46.4

51.7

58.4

64.8

64.8

72.4

12 0

1650

2250

060

4150

5160

62 0

7850

101 0

12670

12 40

16050

Page 24: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA & CURRENT RATING

Current ratings are based on the following conditions:

1. Ambient air temperature 0°C

2. Ground temperature 15°C

. Soil thermal resistivity 1.2°C m w

4. Depth of laying: (a) For 600 1000V cables 0.5m

(b) For 1 00 00V cables 0.8m

5. Maximum conductor operating temperature 70°C

Rating factors of other temperature:

Cable in air :

Temperature 25°C 0°C 5°C 40°C 45°C

Factor 1.06 1.00 0. 4 0.87 0.7

Cables in ground :

Temperature 15°C 20°C 25°C 0°C 5°C

Factor 1.00 0. 5 0. 0 0.85 0.80

600/1000V COPPER CONDUCTOR PVC UNARMOURED CABLES (SINGLE-CORE)

cables,-phase,

ac trefoil2 cables, single-phase ac or dc

or 4-cables -phase, ac

Laid in free air

2 cables, single-phase, cables,

-phase ac, Horizontal flat spaced

Clipped DirectNominalcross-

sectionalarea of

conductor

mm2

Currentrating

A

Currentrating

A

Currentrating

A

Currentrating

A

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

50

70

5

120

150

185

240

00

400

500

6 0

800

1000

0. 5

0.66

0.50

0.41

0. 4

0.2

0.25

0.22

0.20

0.185

0.175

0.165

0.160

167

214

261

0

4

400

472

545

6 4

72

826

4

1058

0.82

0.57

0.4

0. 6

0. 0

0.26

0.22

0.1

0.175

0.16

0.15

0.145

0.14

21

281

41

6

456

521

615

70

852

82

11 8

1265

1420

0. 7

0.6

0.54

0.45

0.

0. 5

0. 1

0.2

0.27

0.26

0.25

0.25

0.24

167

216

264

08

56

40

485

561

656

74

855

71

107

0.82

0.57

0.4

0. 6

0. 0

0.26

0.22

0.1

0.18

0.16

0.15

0.15

0.14

182

2 4

284

0

81

4 6

515

5 4

6 4

7 2

04

10 0

1154

22

Page 25: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA & CURRENT RATING

Current ratings are based on the following conditions:1. Ambient air temperature 0°C2. Ground temperature 15°C. Soil thermal resistivity 1.2°C m w

4. Depth of laying: (a) For 600 1000V cables 0.5m (b) For 1 00 00V cables 0.8m

5. Maximum conductor operating temperature 70°C

Rating factors of other temperature:

Cable in air :

Temperature 25°C 0°C 5°C 40°C 45°C

Factor 1.06 1.00 0. 4 0.87 0.7

Cables in ground :

Temperature 15°C 20°C 25°C 0°C 5°C

Factor 1.00 0. 5 0. 0 0.85 0.80

600/1000V COPPER CONDUCTOR PVC UNARMOURED CABLES (MULTI-CORE)

&4core -phase,

ac

2 core, single-phase, ac or dc

&4-core-phase, ac

Laid on cable tray

2 core, single-phase, ac or dc

Clipped DirectNominalcross-

sectionalarea of

conductor

mm2

Currentrating

A

Currentrating

A

Currentrating

A

Currentrating

A

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

1.52.5461016255

50705

12015018524000

400

20276

46685

1121 8

168212582442

4615 06 4

18242

4157766

11

1441842225241

40464557

2515.5

6.4.8

2.41.51.1

0.810.570.40. 50.20.250.21

0.1850.160

220

4051704

11148

1802 2282287

4 45145715

1254

46080101126

151 62 8276164

4 04 75 7

2515.5

6.4.8

2.41.51.1

0.810.570.40. 50.20.250.21

0.1850.160

218117.4.42.8

1.751.25

ac dc0. 4 0.0.65 0.60.50 0.460.41 0. 60. 4 0.20.2 0.20.24 0.18

0.210 0.145 0.185 0.105

218117.4.42.81.751.25

ac dc0. 4 0.0.65 0.60.50 0.460.41 0. 60. 4 0.20.2 0.20.24 0.18

0.210 0.145 0.185 0.105

23

Page 26: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA & CURRENT RATING

Current ratings are based on the following conditions:

1. Ambient air temperature 0°C

2. Ground temperature 15°C

. Soil thermal resistivity 1.2°C m w

4. Depth of laying: (a) For 600 1000V cables 0.5m

(b) For 1 00 00V cables 0.8m

5. Maximum conductor operating temperature 70°C

Rating factors of other temperature:

Cable in air :

Temperature 25°C 0°C 5°C 40°C 45°C

Factor 1.06 1.00 0. 4 0.87 0.7

Cables in ground :

Temperature 15°C 20°C 25°C 0°C 5°C

Factor 1.00 0. 5 0. 0 0.85 0.80

600/1000V ALUMINIUM CONDUCTOR PVC UNARMOURED CABLES (SINGLE-CORE)

2 cables, single-phase ac or dc

2 cables, single-phase ac or dc

or 4 cables -phase, ac

or 4 cables -phase, ac

Clipped Direct to a Surface or on Cable Tray,Bunched and Unenclosed

Bunched and Enclosed in Conduit or TurkingNominalcross-

sectionalarea of

conductor

mm2

Currentrating

A

Currentrating

A

Currentrating

A

Currentrating

A

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

16255

50705

12015018524000

4005006 0

60786

1201501752052 5

------

52678100125150175200

------

.2.51.81.41.0

0.800.700.64

-----

-

724

1151401752102402752080

4405 0620

720

6585

105125155185215245285400

475550

640

.2.51.81.0.0.60.560.480.400. 40. 00.270.25

0.24

ac dc4.5 4.52. 2.82.1 2.01.6 1.51.2 1.00. 0.80.80 0.60.7 0.5

- -- -- -- -- -- -

ac dc4.5 4.52.8 2.82.1 2.01.5 1.51.1 1.0

0.77 0.750.62 0.600.51 0.40.42 0.0. 4 0.20.2 0.20.25 0.180.22 0.15

0.20 0.11

24

* The Voltage drop between consumer’s terminals and any other point in the installation must not exceed 2.5% of the nominal voltage.

Page 27: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA & CURRENT RATING

Current ratings are based on the following conditions:

1. Ambient air temperature 0°C

2. Ground temperature 15°C

. Soil thermal resistivity 1.2°C m w

4. Depth of laying: (a) For 600 1000V cables 0.5m

(b) For 1 00 00V cables 0.8m

5. Maximum conductor operating temperature 70°C

Rating factors of other temperature:

Cable in air :

Temperature 25°C 0°C 5°C 40°C 45°C

Factor 1.06 1.00 0. 4 0.87 0.7

Cables in ground :

Temperature 15°C 20°C 25°C 0°C 5°C

Factor 1.00 0. 5 0. 0 0.85 0.80

600/1000V ALUMINIUM CONDUCTOR PVC UNARMOURED CABLES (MULTI-CORE)

One twin cables, single-phase ac or dc

One twin cables, single-phase ac or dc

One or 4-corecable -phase, ac

or 4-corecable -phase, ac

Clipped Direct to a Surface or on Cable Tray,Unenclosed

Enclosed in Conduit or Trunking Nominalcross-

sectionalarea of

conductor

mm2

Currentrating

A

Currentrating

A

Currentrating

A

Currentrating

A

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

Voltdrop

mV A m

16255

50705

12015018524000

4647

-------

4577087-------

4.02.61.1.4-------

58762

1151401651 52202500040

526782

1001201501701 522026000

42.51.81.0.0.60.540.450. 70. 00.25

ac dc4.6 4.62. 2.2.2 2.11.7 1.5

- -- -- -- -- -- -- -

ac dc4.6 4.62. 2.2.1 2.11.6 1.51.1 1.1

0.7 0.77 0.6 0.610.52 0.500.4 0.400. 4 0. 10.2 0.25

25

Page 28: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA & CURRENT RATING

CURRENT RATING FACTOR

26

25° 0° 5° 40° 45° 50° 55° 60° 65°

1.0 1.00 0. 7 0. 4 0. 1 0.87 0.84 0.6 0.48

Current rating are based on the following condition:1) Ambient air temperature 0°C2) Max. conductor operating temperature 70°C

* ‘Space’ means a clearance between adjacent surfaces of at least one cable diameter (D) where the horizontal clearances between adjacent cables exceeds 2D, no correction factor need to be applied.

Notes: 1. The factors in the table are applicable to groups of cables all of one sizes. The value of current derived from application of the appropriate factors is the maximum continuous current to be carried by any of the cables in the group.

2. If, due to known operating conditions, a cable is expected to carry not more than 0% of its grouped rating, it may be ignored for the purpose of obtaining the rating factor for the rest of the group.

Rating Factors

For Groups

For Ambient Temperature

Correction factor (c)

Enclosed bunched and clipped

direct to a non- metallic surface

Single layer multicore touching on

ladder supports

Single layer clippedto a non-metallicsurface

Single layer

multicore on a

perforated metal

cable tray, vertical

or horizontal

Single layer single

core on a

perforated metal

cable tray, touching

Touching

Spaced*

Touching

Spaced*

Horizontal

Vertical

Reference method of installation Number of circuits or multicore cables

2 4 5 6 7 8 10 12 14 16 18 20

0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.4 0.41 0. 0. 8

0.86 0.81 0.77 0.75 0.74 0.7 0.7 0.72 0.71 0.70 - - - -

0. 1 0.8 0.88 0.87 0.87 - - - - - - - - -

0. 0 0.85 - - - - - - - - - - - -

0.85 - - - - - - - - - - - - -

0.86 0.82 0.80 0.7 0.78 0.78 0.78 0.77

0. 4 0. 0 0. 0 0. 0 0. 0 0. 0 0. 0 0. 0 0. 0 0. 0 0. 0 0. 0 0. 0 0. 0

0.85 0.7 0.75 0.7 0.72 0.72 0.71 0.70 - - - - - -

Factor (General purpose PVC Insulation)

Page 29: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA & CURRENT RATING

27

PVC NON-ARMOURED MULTI-CORE (1.0mm2 TO 400mm2) - Copper

The ratings tabulated apply where the cable is provided with close excess-current production.

2 coreConductor Laid on cable tray Clipped direct to a non-metallic surface

2 core or 4 core or 4 core-phase, ac -phase, acsingle-phase, ac or dc single-phase, ac or dc

Nominalcross-

sectionalarea

1mm2

Currentrating

A

Currentrating

7A

Currentrating

A

Currentrating

5A

Volt drop perampere per metre

4mV A m

Volt drop perampere per metre

8mV A m

Volt dropper ampere per metre

6mV A m

Volt dropper ampere per metre

10mV A m

No. anddia. (mm)of wires

2

1.0

1.5

2.5

4

6

10

16

25

5

50

70

5

120

150

185

240

00

400

17

22

0

40

51

70

76

11

148

180

2 2

282

28

7

4 4

514

5

715

15

1

25

4

4

60

68

101

126

15

1 6

2 8

276

1

64

4 0

4 7

5 7

8

25

15

.5

6.4

.8

2.4

1.5

1.1

0.81

0.57

0.4

0. 5

0.2

0.25

0.21

0.185

0.160

15

1 .5

27

6

46

6

87

112

1 8

168

21

258

2

44

2

461

5 0

6 4

14

18

24

2

41

57

7

1.5

11

144

22

22

25

2

41

40

464

557

8

25

15

.5

6.4

.8

2.4

1.5

1.1

0.81

0.57

0.4

0. 5

0.2

0.25

0.21

0.185

0.160

44

2

18

11

7.

4.4

2.8

1.75

1.25

ac dc

0. 4 0.

0.65 0.6

0.50 0.46

0.41 0. 6

0. 4 0.2

0.2 0.2

0.24 0.18

0.21 0.145

0.185 0.105

44

2

18

11

7.

4.4

2.8

1.75

1.25

ac dc

0. 4 0.

0.65 0.6

0.50 0.46

0.41 0. 6

0. 4 0.2

0.2 0.2

0.24 0.18

0.21 0.145

0.185 0.105

1 1.1

1 1. 8

7 0.5

1 1.78

7 0.67

7 0.85

7 1.04

7 1. 5

7 1.70

7 2.14

1 1.5

1 1.78

1 2.14

1 2.52

7 2.0

7 2.25

7 2.52

61 2.25

61 2.52

61 2.85

Page 30: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA & CURRENT RATING

PVC NON-ARMOURED SINGLE-CORE (1.0mm2 TO 630mm2) - Copper

The ratings tabulated apply where the cable is provided with close excess-current production.

Conductor Enclosed in Conduit or Trunking Cables Clipped direct to a non-metallic surface2 Cables

single-phase2 Cables

single-phase or 4 Cables

Three-phase or 4 Cables

Three-phaseNominalcross-

sectionalarea

1mm2

Currentrating

A

Currentrating

7A

Currentrating

A

Currentrating

5A

Volt drop perampere per metre

4mV A m

Volt drop perampere per metre

8mV A m

Volt dropper ampere per metre

6mV A m

Volt dropper ampere per metre

10mV A m

No. anddia. (mm)of wires

2

1.0

1.5

2.5

4

6

10

16

25

5

50

70

5

120

150

185

240

00

400

500

6 0

14

18

24

2

41

57

76

101

125

151

1 2

2 2

26

00

41

400

458

546

626

720

12

15.5

21

28

6

50

68

8

110

1 4

171

207

2

262

2 6

46

4

467

5

611

8

16

15

.5

6.4

.8

2.4

1.55

1.10

0.85

0.61

0.48

0.41

0. 6

0. 2

0.2

0.27

0.25

0.25

0.24

16

20

27

7

47

65

87

114

141

182

2 4

284

0

81

4 6

515

5 4

6 4

7 2

04

14

18

25

4

5

7

104

12

167

214

261

0

4

400

472

545

6 4

72

826

8

25

15

.5

6.4

.8

2.4

1.5

1.1

0.82

0.57

0.4

0. 6

0. 0

0.26

0.22

0.1

0.175

0.160

0.150

44

2

18

11

7.

4.4

2.8

ac dc

1.8 1.75

1. 1.25

1.10 0.

0.72 0.6

0.56 0.46

0.47 0. 6

0.41 0.2

0. 7 0.2

0. 0.18

0. 1 0.145

0.2 0.105

0.28 0.086

0.27 0.068

44

2

18

11

7.

4.4

2.8

1.75

1.25

ac dc

0. 5 0.

0.66 0.6

0.50 0.46

0.41 0. 6

0. 4 0.2

0.2 0.2

0.25 0.18

0.22 0.145

0.20 0.105

0.185 0.086

0.175 0.068

1 1.1

1 1. 8

7 0.5

7 0.78

7 0.67

7 0.85

7 1.04

7 1. 5

7 1.70

7 2.14

1 1.5

1 1.78

1 2.14

1 2.52

7 2.0

7 2.25

7 2.52

61 2.25

61 2.52

61 2.85

61 .20

61 .65

28

Page 31: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA & CURRENT RATING

29

ALLOWABLE SHORT CIRCUITCURRENT FOR PVC INSULATED CABLES

100.090.080.0

70.0

60.0

50.0

40.0

30.0

20.0

10.09.08.0

7.0

6.0

5.0

4.0

3.0

2.0

16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

1.0

SEC

2.0

SEC

3.0

SEC

4.0

SEC

5.0

SEC

0.5

SEC

Conductor : CopperInsulation : PVCCurves based on formula -

I = 0.1154

Where -

I = Short circuit current (KA)

A = Conductor area (mm2)

t = Time of short circuit (seconds)

CONDUCTOR SIZE (mm2)

1.0

A t

Page 32: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA & CURRENT RATING

TECHNICAL DATAMINIMUM INSULATION RESISTANCE VALUES OF 600/1000V CABLES

30

1.5

2.5

4

6

10

16

25

5

50

70

5

120

150

185

240

00

400

500

6 0

800

1000

10

8

7

7

6

5

5

5

5

5

5

5

5

5

5

5

5

5

5

5

INSULATION RESISTANCE AT

1km@20o

C

M

CONDUCTOR

SIZE

sq. mm.

Page 33: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA & CURRENT RATING

Maximum Resistance Of Conductor For Single Core And Multicore Cables.

Nominal cross-sectional area

Nominal cross-sectional area

Maximum DCResistance of

conductor at 20°C

Maximum DCResistance of

conductor at 20°CCopper

ConductorCopper

ConductorAluminiumConductor

AluminiumConductor

mm2 mm2No. mm No. mmohm km ohm km ohm km ohm km

1.5

2.5

461016255

50705

1 1. 87 0.51 1.787 0.677 0.857 1.047 1. 57 1.707 2.141 1.51 1.781 2.141 2.52

12.1

7.41

4.61.08

1.81.15

0.7270.5240. 870.2680.1

-

-

7.414.61.08

1. 11.20

0.8680.6410.440. 20

120

150

185240

004005006 0800

1000

7 2.0

7 2.25

7 2.527 2.88

61 2.2561 2.5261 2.8561 .20

127 2.52127 2.85127 .20

0.15

0.124

0.0 10.0754

0.06010.04700.0 660.0280.02210.0176

0.25

0.206

0.1640.125

0.1000.07780.06050.0460.0 670.02 1

Properties

DensityVolume Resistivity

Coefficient of ResistanceMelting Point

Coefficient of ExpansionUltimate Tensile Strength

Unit

g cmohm.mm km

Per°C°C

Per°C x 10°N mm2

Insulation

PVCPE

XLPEEPR

Impregnatedpaper

SpecificGravity

1.440. 20. 21.21.1

RelativePermitivity

5.0 - 8.02.2.5

.5 - 5.06

ThermalResistivity(°C m W)

5.0 - 6.02.2.5

.5 - 5.06

VolumeResistivity

20°C (ohm-cm)

1014

1016

1016

1015

1015

Max. Cond.Temp.(°C)

707000

65 - 80

Max.ShortCircuit Temp.

(°C)

1601 0250250

160 - 250

Properties of Conductors

Typical Properties of Various Insulation materials

Annealed copper

8.817.241

0.0010716.8 275

Aluminium

2.7028.264

0.0040660

25.5205

31

Page 34: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA & CURRENT RATING

FORMULA FOR ELECTRICAL CALCULATION

pf - Power factor of equipment or system under considerationeff - Efficiency of motor or machineryV - Line voltage

To calculate

Current ( A)

Current ( A)

Current ( A)

Power (kW)

Apparent Power

(kVA)

Given

kW

kVA

hp

VA

VA

D.C.

A= 1000 x kW V

-

A= 746 x hp V x eff

kW = A x V 1000

-

A.C. single phase

A = 1000 x kW V x pf

A = 1000 x kVA V

A = 746 x hp V x eff x pf

kW = A x V x pf 1000

kVA = A x V 1000

A.C. phase

A = 1000 x kW 1.7 x V x pf

A = 1000 x kVA 1.7 x V

A = 746 x hp 1.7 x V x eff x pf

kW = 1.7 x A x V x pf 1000

kVA = 1.7 x A x V 1000

32

Page 35: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA

Unarmoured cable (6.6 ~ 33 kV)Single coreSingle core with LSHFThree coreThree core with LSHFArmoured cable (6.6 ~ 33 kV)Single coreSingle core with LSHFThree coreThree core with LSHFUnarmoured cable (more than 33 kV)Single coreThree coreArmoured cable (more than 33 kV)Single coreThree core0.6/1kV CablePVC insulatedXLPE insulatedPVC PVCXLPE PVCFR-XLPE – Flame RetardantLSHF InsulatedFR-XLPE PVC – Flame RetardantFR-XLPE LSHF – Flame RetardantLSHF LSHFPVC PVC SWA PVCXLPE PVC SWA PVCPVC PVC SWB PVCXLPE PVC SWB PVCXLPE LSHF SWA LSHFXLPE LSHF SWB LSHF300/500V CablePVC PVC, PVC or XLPE PVC SWA or SWB PVCFR-XLPE PVC or LSHF, LSHF LSHFXLPE LSHF SWA or SWB LSHF

20201515

15151215

2018

2018

6668

15151515156868

1515

101515

OD<=25 mmOD>25 mmOD <= 25 mmOD > 25 mm, shape

OD <= 25 mmOD > 25 mm, shapeOD <= 25 mmOD > 25 mm, shape

Cable Type

Factor

.Installation bending radius OD X Factor

33

CABLE INSTALLATION BENDING RADIUS

Page 36: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA

TABLE 9ASCHEDULE METHODS FOR INSTALLATION OF CABLES (CP5: 1988)

Installation Method

ExamplesNumber Description

Open and clipped direct:1 2 4

In conduit :

In trunking :

1

5

8

10

Method 1

Method

Method

Method

Method

Method

AppropriateReferenceMethod fordeterminingcurrent-carryingcapacities

Sheathed cablesclipped direct to orlying on a non-metallicsurface

Single-core non-sheathedcables in metallic or non-metallic conduit ona wall or ceiling

Cables in trunking on awall or suspended in air

Cables in flush floortrunking

Single-core cables inskirting trunking

Multicore cables havingnon-metallic sheath, inmetallic or non-metallicconduit on a wall orceiling

34

Page 37: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA

TABLE 9ASCHEDULE METHODS FOR INSTALLATION OF CABLES (CP5: 1988)

Installation Method

ExamplesNumber Description

Open and clipped direct:

In free air

11

12

1

-

-

-

Method 11

Method 12

Method 1

AppropriateReferenceMethod fordeterminingcurrent-carryingcapacities

Sheathed cables on a perfo-rated cable tray,bunched andunenclosed. A perforated cable tray is considered as a tray in which the holesoccupy at least 0 % of the surface area.

Sheathed single-core cablesin free air (any supportingmetal work under the cablesoccupying less than 10% ofthe plan area):

Two or three cables vertically one above the other, distance between cables equal to the overall cable diameter (De);distance from the wall notless than 0.5 (De)

Two or three cableshorizontally, with spacing as above

Three cables in trefoll,distance between wall and surface of nearest cable 0.5 De or nearest cables 0.75 DeSheathed multicore cables in free air distance betweenwall and cable surface notless than 0. De(any supporting metalwork occupying less than 10% of the plan area)

1 2 4

35

Page 38: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Central Cables Berhad

TECHNICAL DATA

APPENDIX TECHNICAL DATACOMMON CONVERSION FACTOR

1 mil = 0.001 in = 0.0254 mm1 CM(Circular mil) = 0.7854 x 10 in2 = 0.5067 x 10 mm2

Installation Method Reciprocal

1 cwt

1 oz

1 Ib

1 Ib

1 ton ( long)

1 in

1 ft

1 yd

1 mile

1 in2

1 ft2

1 yd2

1 in

1 ft

1 ft

1 ft

1 yd

1 gal (USA)

1 Ibf

1 kgf

1 ton ( long) f

1 atm

1 atm

1 Ib in2 ( psi)

1 bar

1 HP.h

1 Btu

1 Btu

1 Btu

1 cat

50.802

28. 4

0.45 6

0.00454

1.016

25.4

0. 048

0. 144

1.60

645.16

0.0 2

0.8 61

16. 87

0.028

6.22

28. 28

0.7645

0.8 27

0.45 5

.8065

. 64

0.101

1.01

6.8 4

1.01 7

2544.5

0.0002

1.0551

107.5

4.187

kg

gm

kg

tonne (metric)

tonne ( metric)

mm

m

m

km

mm2

m2

m2

cm (ml or cc)

m

gal (Imp)

I

m

gal (Imp)

kgf

N

kN

Mpa

bar

kN mm2 (kPa)

kgf cm2

Btu

kW.h

kJ

kgf.m

J

0.01 7

0.0 52

2.2046

220.26

0.0 842

0.0 7

.2808

1.0 6

0.6214

0.00155

10.7642

1.1 6

0.061

5. 5

0.1605

0.0 5

1. 07

1.200

2.2046

0.101

0.100 6

.86

0. 86

0.145

0.0 806

0.000

41

0. 478

0.00 2

0.2

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

Mass

Length

Area

Volume

Force

Pressure and Stress

Energy ( Work and Heat)

36

Page 39: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

Customer details ( please type or print clearly )

Name Position in company..............................................................................................................................................................................

Company..............................................................................................................................................................................

Address..............................................................................................................................................................................

..............................................................................................................................................................................

..............................................................................................................................................................................

Post Zip Code Country..............................................................................................................................................................................

Telephone Facsimile..............................................................................................................................................................................

e-mail @..............................................................................................................................................................................

Signed Date..............................................................................................................................................................................

Product Interested

Bare Cu Al Conductor

XLPE INSULATED Cu Al Power Armoured Cables (LV)

XLPE PVC Cu Al Cables (LV)

XLPE or PE Al Aerial Bundle Cables (LV&MV)

PVC Insulated Flexible Cords

PVC Insulated Cables (Non-Armoured)

For electric power and lighting

PVC Insulated Cables (Armoured) for electricity supply

XLPE Insulated Power Cables (MV)

XLPE Insulated Armoured Cables (MV)

---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Page 40: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Central Cables Berhad (7169-A)7862. Batu Berendam, 75 50 Melaka, Malaysia.

P.O. Box 1 , 75760 Melaka, Malaysia.

Fold this flap for sealing

Fold this flap for sealing

Fold this flap for sealing

Affix stamp

---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Page 41: Central Cables Berhad · Central Cables Berhad PVC ARMOURED PVC INSULATED, PVC SHEATHED ARMOURED CABLE (1-CORE) (BS 6346, 600/1000V) 5 1070 1400 1750 2100 2570 250 0 5100 5210