CDVR Troubleshooting

download CDVR Troubleshooting

of 37

Transcript of CDVR Troubleshooting

  • 7/28/2019 CDVR Troubleshooting

    1/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    CDVR Troubleshooting

    October 30, 2007

  • 7/28/2019 CDVR Troubleshooting

    2/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Outline

    Troubleshooting

    If operation is not as expected

    Excitation loss (reverse kvar)

    Generator over voltage

    Generator under voltage

    No generator voltage

    Exciter diode monitor fault

  • 7/28/2019 CDVR Troubleshooting

    3/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Outline (continued)

    Troubleshooting

    Over excitation fault

    Loss of sensing

    Field over current

    Internal Memory Failure

    Internal Watchdog Failure

    Unstable Voltage

    Poor Transient Response

  • 7/28/2019 CDVR Troubleshooting

    4/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    CAUTION

  • 7/28/2019 CDVR Troubleshooting

    5/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    If Operations is not as Expected:

    Check for Alarms or Shutdown Faults

    If Fault LED is lit Continuously Alarm Output Drive Active

    If Fault LED is Flashing Shutdown Output Drive Active

    Open Communications with CDVR to determine what Alarm /Shutdown is active

    Alarm Signal Indicator Visible on all Screens

    Go to Metering Screen, look at Alarms area

    Check Programmable Settings

  • 7/28/2019 CDVR Troubleshooting

    6/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    CAT PC Metering Screen

  • 7/28/2019 CDVR Troubleshooting

    7/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    CAT PC Protection Screen

  • 7/28/2019 CDVR Troubleshooting

    8/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    If Excitation Loss(Reverse kvar) has Occurred:

    Verify programmable settings are consistent with application

    Check wiring of generator voltage (P12 10 to 12) and Current

    Sensing (P12 1 & 2) Check phase rotation, if not consistent with wiring diagram,

    modify connections

    Check other paralleled generators or voltage sources for over

    voltage (this can cause reverse var flow into generator) Replace regulator

  • 7/28/2019 CDVR Troubleshooting

    9/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    If Generator Over Voltage has Occurred:

    Check wiring of generator voltage sensing (P12 10 to 12)

    Verify that the generator over voltage fault settings are correct

    Verify that voltage adjustment is not set too high

    Verify that sensing PT (if used) has correct turns ratio

    Verify that sensing PT fuses (if used) have not opened

    High voltage may occur if operating in droop mode withcapacitive load or if CT connection is backwards or wrong phaserotation

    High voltage may occur if operating in line drop compensationmode with a large generator load

    Verify auxiliary input voltage is not too high

    Replace regulator

  • 7/28/2019 CDVR Troubleshooting

    10/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    If Generator Under Voltage has Occurred:

    Check wiring of generator voltage sensing (P12 10 to 12)

    Verify that the generator under voltage fault settings are correct

    Verify that voltage adjustment is not set too low

    Verify that the generator is running at rated speed

    Verify that the under frequency setpoint (knee frequency) is notgreater than generator frequency

    Verify that sensing PT (if used) has correct turns ratio

    Check for correct input power

    Low voltage may occur if operating in droop mode with highinductive load

    Verify auxiliary input voltage is not too low

    Replace regulator

  • 7/28/2019 CDVR Troubleshooting

    11/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    If No Generator Voltage is Present:

    Check wiring

    Verify that the generator is running at rated speed

    Verify that residual voltage applied to the power input is at least6Vac or greater

    Verify that the fuse is not open

    Verify that CDVR is connected to 24Vdc control power

    Verify that common alarm / shutdown LED is not flashing

  • 7/28/2019 CDVR Troubleshooting

    12/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    If No Generator Voltage is Present and an Exciter Diode MonitorFault has Occurred:

    Stop machine

    Insure power input to CDVR has been removed, unplug P6 Refer to generator manual for instructions on checking the

    rotating exciter diodes

    If no fault is found with rotating exciter diodes, the EDM trip value

    may be too low Increase EDM trip value to a level greater than the ripple current

    under normal operation

    If rotating exciter diodes are at fault, repair, reinstall P6 then

    reset the CDVR using the Fault Reset contact input or cycle the24Vdc control power

  • 7/28/2019 CDVR Troubleshooting

    13/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    If No Generator Voltage is Present and an Over Excitation Fault hasOccurred:

    Stop machine

    Check generator and load conditions for a fault that could causeexcessive exciter field current

    If no fault is found, reset the CDVR using the Fault Reset contact input

    or cycle the 24Vdc control power

    Verify the over excitation settings are properly adjusted for the

    generator, set slightly above the requirement of the application but notso high as to render the protection ineffective

    If an exciter diode fault has occurred, the instantaneous trip value of

    28A may have been reached. The EDM fault will not indicate this, due toa 5 sec time delay

    SR4 &SR4B generator require up to 12Adc for full load. A 10 second

    setting is required to insure 300% short circuit requirements

  • 7/28/2019 CDVR Troubleshooting

    14/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    If No Generator Voltage is Present and a Loss of Sensing Fault hasOccurred:

    Stop machine

    Check wiring Check generator and load conditions for a fault that could cause

    sensed voltage to be low

    If sensing potential transformers are used, verify that they are

    functional and have not blown a fuse Once fault is repaired, reset the CDVR using the Fault Reset

    contact input or cycle the 24Vdc control power

  • 7/28/2019 CDVR Troubleshooting

    15/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    If No Generator Voltage is Present and a Field Over Current Faulthas Occurred:

    Stop machine

    Check wiring Check generator and load conditions for a fault that could cause

    a field over current

    A field over current fault occurs when output current exceeds

    28A (approximately) Once fault is repaired, reset the CDVR using the Fault Reset

    contact input or cycle the 24Vdc control power

  • 7/28/2019 CDVR Troubleshooting

    16/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    If No Generator Voltage is Present and an Internal Memory FailureFault has Occurred:

    Try resetting the CDVR using the Fault Reset contact input or

    cycle the 24Vdc control power If after resetting the CDVR, if another Internal Memory Failure

    fault occurs, replace regulator

  • 7/28/2019 CDVR Troubleshooting

    17/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    If No Generator Voltage is Present and an Internal Watchdog FailureFault has Occurred:

    Try resetting the CDVR using the Fault Reset contact input or

    cycle the 24Vdc control power If after resetting the CDVR, if another Internal Watchdog Failure

    fault occurs, replace regulator

  • 7/28/2019 CDVR Troubleshooting

    18/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    Unstable Voltage:

    Verify that the governor for the engine is operating properly

    Verify that the sensing and power leads are connected securely

    Verify that the CDVR stability range is set to the proper range Verify that the stability level (Kg) is properly set

  • 7/28/2019 CDVR Troubleshooting

    19/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    Poor Voltage Response to a Transient Load:

    Verify that the governor for the engine is operating properly

    Verify that the CDVR stability range is set to the proper range

    Verify that the stability level is properly set Tune the CDVR for the application

  • 7/28/2019 CDVR Troubleshooting

    20/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    CDVR PID Tuning:

    Perform a step of reference test with 1 or 2% steps

    Look at terminal voltage response with chart recorder

    Determine if voltage response is acceptable Rise time

    Over shoot

    Settling time

    Damping

    If not acceptable, tune the CDVR for the application

    Once step of reference test is suitable, verify load application /rejection performance

  • 7/28/2019 CDVR Troubleshooting

    21/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Step of Reference Test

    Rise Time

  • 7/28/2019 CDVR Troubleshooting

    22/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Step of Reference Test

    Over Shoot

  • 7/28/2019 CDVR Troubleshooting

    23/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Step of Reference Test

    Settling Time

    +/- 2%

  • 7/28/2019 CDVR Troubleshooting

    24/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Step of Reference Test

    Damping

  • 7/28/2019 CDVR Troubleshooting

    25/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Troubleshooting

    CDVR PID Tuning:

    Examples of step of reference test results

    Tests performed on 300kW, 240V, 60Hz AREP generator

    Factory defaults PID calculator

    Magic PID values = 80, 20 and 10

  • 7/28/2019 CDVR Troubleshooting

    26/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Default PID = 200, 600, 30 with Kg = 50

  • 7/28/2019 CDVR Troubleshooting

    27/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Default PID = 200, 600, 30 with Kg = 25

  • 7/28/2019 CDVR Troubleshooting

    28/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Default PID = 200, 600, 30 with Kg = 10

  • 7/28/2019 CDVR Troubleshooting

    29/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Default PID = 200, 600, 30 with Kg = 1

  • 7/28/2019 CDVR Troubleshooting

    30/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    PID Calculator, Tdo = 2s, Te = 0.1s

    PID &Kg = 25, 43, 2.7 & 50

  • 7/28/2019 CDVR Troubleshooting

    31/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    PID Calculator, Tdo = 2s, Te = 0.1s

    PID &Kg = 25, 43, 2.7 & 200

  • 7/28/2019 CDVR Troubleshooting

    32/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    PID Calculator, Tdo = 1.5s, Te = 0.1s

    PID &Kg = 25, 51, 2.6 & 200

  • 7/28/2019 CDVR Troubleshooting

    33/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    PID Calculator, Tdo = 1.0s, Te = 0.1s

    PID &Kg = 42, 100, 4.5 & 200

  • 7/28/2019 CDVR Troubleshooting

    34/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Magic PID Values = 80, 20, 10

    Kg = 50

  • 7/28/2019 CDVR Troubleshooting

    35/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    PID Tuning Conclusion

    Must adjust Kg to achieve best results

    Factory Default Values result in OK performance

    PID Calculator gives very good results but must know Tdo and Te

    Magic PID values also very good and it is simple Once step of reference test is suitable, verify load application /

    rejection performance

  • 7/28/2019 CDVR Troubleshooting

    36/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    Information Needed If Replacement of CDVR is Selected

    When sending back a CDVR, please provide the following:

    Detailed statement of problem including

    Symptoms of the failed CDVR

    Genset configuration and ratings Operating Conditions (kW, voltage, current etc)

    Run time

    Anything unique about the installation

    Did anything of significance occur just before the failureoccurred? (i.e. sparks, re-wiring, etc.)

    Is there any mechanical damage to the CDVR or mounting?

  • 7/28/2019 CDVR Troubleshooting

    37/37

    EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

    QUESTIONS?