1 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Certified CablingCertified CablingTest TechnicianTest Technician
DTX SeriesDTX Series
CableAnalyzer CableAnalyzer
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 2/141
2 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Presented by
David W. GibbsTraining Programs Manager
Fluke Networks
Office: 425.446.5912
E-mail: [email protected]
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 3/141
3
3 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Certified Cabling Test Technician Agenda
Understanding the Standards ± Copper
Certification
ISO, EN, and TIA Cabling Standards
Field Test Methods ± Channel vs. Permanent Link
Copper Testing with the DTX-1800
Configuration options with the DTX
Hands-on certification and troubleshooting
Passing a certification test ± reviewing and saving testresults
Troubleshooting failing links ± Fault Info and
HDTDX/HDTDR
Summary / Certification Exam
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 4/141
4 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Introduction to Certification
Defining Certification
The Industry Standards
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 5/141
5
5 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Levels of Field Testing
Verification
The installed link meets basic continuity
requirements
Does not imply any bandwidth or transmissionquality measure
Qualification
The installed cabling link successfully transmits datausing a specific network technology
(i.e. 100BASE-TX)
Does not imply compliance with other technologies
than the one used in the test
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 6/141
6
6 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Levels of Field Testing (Cont¶d)
Certification
The installed cabling link meets the transmission
performance criteria as defined by the applicable
industry standard; the test results are documentedand reported in compliance with the standard
The definition of performance and the level
(³category´) of performance is defined by industry
standards TIA-568-B defines Cat 5e, Cat 6
ISO 11801 and ISO/IEC 61935 define Class C, D , E and F
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 7/141
7
7 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
³Certification´
Compare the performance of an installed cabling
system to a standard
The cabling system includes: cables ³in the wall´, outletconnectors, interconnects, patch panels and patch cords
Performance depends on component quality and
installation workmanship
cer·ti·fy v. cer·ti·fied, cer·ti·fy·ing, cer·ti·fies. ± tr
1. a. To confirm formally as true, accurate, or genuine.
b. To guarantee as meeting a standard.
(Ex: butter that was certified Grade A.)[Source: American Heritage Dictionary]
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 8/141
8
8 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Installation Certification ± Why?
Components (Spools of cable, Patch panels, Outlets,
connectors, patch cords, etc.) are delivered to the
³construction site´
The cable is pulled and terminated (connectorized)on-site
The ³final product´ delivered to the customer is the
installed cabling system ± not the components
(spools, racks, panels, outlets, etc.)
This final product should be tested to verify that it
meets the desired performance specifications
Manufacturers¶ warranty is based on passing
certification results
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 9/141
9
9 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Performance Specification for Cabling
Defined by Industry Standards
In the US: TIA (Telecommunication Industry
Association)
Standard ANSI/TIA/EIA 568-BSpecific to field test requirements: TIA-568-B.1;
Section 11 Cabling Transmission Performance and
Test Requirements
International: ISO/IEC (International Organizationfor Standardization / International Electrotechnical
Commission)
ISO Standard 11801:2002
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 10/141
10
10 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Cabling Standards Around the World
ISO/IEC 11801:2002IT Generic Cabling for
Customer Premises
ANSI/TIA/EIA 568-BCommercial Building
Telecommunications
Wiring Standard
EN50173:2002Performance
Requirements Of
Generic Cabling
Systems
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 11/141
11
11 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Purpose of Industry Standards
(TIA, ISO & EN)
Define an application independent, openopen system
Provide guidance for building professionals to
allow for a cabling infrastructure before specificbefore specificrequirementsrequirements are known
Define a flexible cabling scheme such that
modificationsmodifications are both easy and economicaleasy and economical
Define a cabling system that supports current
applications and that is a basis for futurefuture
developmentdevelopment of network products
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 12/141
12
12 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Types of Standards
Component Specifications
Define performance and grades of cables, connectors
and hardware
Example: ANSI/TIA/EIA 568-B.2, ISO/IEC 61156-5/-6
Installed Link Specifications
Permanent Link and Channel Field Certification Tests
Example: ANSI/TIA/EIA 568-B.1, ISO std 11801
Network Technology Standards (Applications)
Define performance requirements for all elements
of the network
Example: IEEE 802, ATM-PHY
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 13/141
13
13 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Field Certification Confidence
Testing the right ³thing´
The correct connections
The proper test criteria (test standard)
The proper measurement technique
Testing it correctly
Use the proper equipment
Carefully follow all the rules defined by the proper technique (test standard)
A ³PASS ́ assures that the cabling will not cause
transmission problems
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 14/141
14
14 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Principle of ISO, EN, & TIA
Performance MeasurementsBased on a Signal-to-Noise Ratio
Insertion Loss (Attenuation)
Measure of signal strength at the end of thetransmission medium
Noise/Disturbance
All unwanted/undesirable signal noise inserted
between transmitter and receiver Characterized by test parameters that measure
crosstalk (NEXT, FEXT) and return loss
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 15/141
15 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
The ISO and EN Standards
International and European Standards
Overview: Class D to Class F
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 16/141
16
16 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
International Standards
Channel and Link requirements are grouped in Classes (A ± F)
Component requirements
Links and Channels are composed of components (connectors, cables
and patch cords)
Components conform to a category Cat.1 to 7
Example: Class E channel requires Cat.6 components or better
ISO/IEC 11801:2002
Defines Channel and Link limits up to and including Class-F
ISO/IEC IEC 60603-7-2 to ...-7 Requirements for connecting hardware (plug and jacks)
ISO/IEC 61935-1:2004
Defines performance requirements for field testers
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 17/141
17
17 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
European Standards
Channel and Link requirements are grouped in Classes (A ± F)
Component requirements
Links and Channels are composed of components (connectors, cables and
patch cords
Components conform to a category Cat.1 to 7
Example a Class E requires Cat.6 components or better
EN 50173:2002
Defines Channel and Link limits
Defines Cabling Systems up to Class F
ISO/IEC 60603-7-2 to ...-7
Requirements for connecting hardware (plug and jacks)
EN 50346 : Defines details about the test setup
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 18/141
18
18 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
ISO & EN Cabling Standards History
Version: 1995
Original Cabling Standard
Class A to D:
Version: 2000 Class A to D:
Supports 1000Base-T
Requirements for Class D enhanced
Version: 2002 Supports New Proposed Class E and F Cabling
A brief review of each in more detail «
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 19/141
19
19 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Transmit
Receive
WorkstationWorkstation
Transmit
Receive
LANLAN
EquipmentEquipment
Signal
Signal
The Class D:1995 ³System´
A two wire-pair system
The traditional or ³legacy´ transmission system
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 20/141
20
20 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Transmit
Receive
WorkstationWorkstation
Transmit
Receive
LANLAN
EquipmentEquipment
Signal
Signal
The Class D:1995 Test Parameters
Signal strength: measured by ³Attenuation´
Noise: Near-End Cross Talk (NEXT)
Attenuated Signal
NEXT
Signal-to-noise ratio: Attenuation to Crosstalk Ratio (ACR)
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 21/141
21
21 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Class D:2000
An update of Class D:1995
Improved performance limits to support
1000BASE-T
Add FEXT measurement and ELFEXT test
parameter
Add Power Sum parameters
Is not the same as the TIA Category 5e
NEXT (pair-to-pair) test limits are slightly lower
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 22/141
22
22 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
C lass D: Performance EvolutionC lass D: Performance Evolution
Class D:1995 Class D:2000
TIA Equivalent TSB67 C at 5 TSB95 C at 5
Frequency range 1 ± 100 MHz 1±100 MHz
Propagation Delay X No Change
Delay Skew NewAttenuation X 9.6% better
NEXT X 43% better
PSNEXT New
ELFEXT New
PS ELFEXT New
Return Loss Updated f (freq.)
Likely OK for 1000BASE-T
A more complete specification
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 23/141
23
23 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Horizontal CablingWorkstation Switch
Four wire pairs ± Full duplex on each pair
Effective for Cat5e / Class D:2002 cabling and higher
Applications: 1000BASE-T and 10GBASE-T
The ³New´ Transmission Model
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 24/141
24
24 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Multiple Pair Transmission
Workstation LAN HubTransmit
(Output)
Transmit(Output)
Receive
Input
Receive
(Input)
Signal 2
Signal 1
Example: 1000BASE-T: (4 pairs are used.)
Attenuation (signal loss) and FEXT (internal noise)
are the key measurement parameters
FEXT
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 25/141
25
25 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Attenuatio
n
Affects of all 3 disturbing pairs = Power Sum
Signal
Power Sum ELFEXT
FEXTPSELFEXT
ELFEXT
(signaldifference
in dB)
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 26/141
26
26 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Signal A to B
Signal B to A
Return Loss measures the signal echo within each pair
Desired signal = attenuated signal from other end.
Noise = reflected signal on same wire pair.
Full Duplex Transmission
System B
Receive
Transmit
System A
Transmit
Receive
Directional
Coupler
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 27/141
27
27 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
C ombined affects of all 3 disturbing pairs = Power Sum
Combined 7 Noise Sources - Disturbances
Combined NEXT disturbance from 3 wire-pairs: PSNEXT
Return Loss within the same wire-pair
Combined FEXT disturbance from 3 wire-pairs: PSELFEXT
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 28/141
28
28 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Class D:2002
An update of Class D:2000
Improved performance limits for NEXT Loss
Requirements harmonized with TIA Category 5elink specifications
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 29/141
29
29 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Class E:2002
4-pair 100 ; Cabling System with guaranteed
useable bandwidth to 200 MHz
Performance is specified and must be tested to
250MHz Same test parameters and testing rules as for
Class D:2002
May be executed as a shielded or unshielded
system
Shielded system is expected to meet transmission
requirements of the 100 m channel for the 10GBASE-T
network technology currently under development by IEEE,
TIA and ISO/IEC
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 30/141
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 31/141
31
31 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Performance C omparisonPerformance C omparison
Allowable NEXT (Near-End Crosstalk)
Class D:1995 Class D:2000 Class D:2002 Class E:2002
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 32/141
32
32 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Class F
Class F links and Category 7 components are
specified in ISO/IEC standards documents
Refers to individually-shielded pair construction with
a shield surrounding all four wire-pairs Known as SSTP or PiMF (Pairs in Metal Foil) cabling systems
Ensures much higher performance on crosstalk performance
Standard specifies performance from 1 through 600
MHz Class F will meet the requirements of the 100 m
channel for the 10GBASE-T network technology
currently under development by IEEE, TIA and
ISO/IEC
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 33/141
33
33 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
NEXT Limits for Permanent Link
¡
¢
¡
£
¡
3
¡
¤
¡
5
¡
6
¡
7
¡
5
¢
¢ 5
£ £
5
3
35 ¤ ¤
5
5
55
6
Fre uen y
N E X T
d
Class C
Class DClass E
Class F
Each 20 dB increase inmeasurement level requires
a 10x increase in voltage
measurement accuracy
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 34/141
34
34 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Evolution (Harmonization) of Standards
Year ISO/IEC TIA/EIA
1995 Class D / Cat 5
ISO/IEC 11801:1995 NEXT 24 dB
ANSI/TIA/EIA-568-ANEXT 27.1 dB
2000Class D / Cat 5e
ISO/IEC 11801:2000NEXT 27.1 dB
ANSI/TIA/EIA-568-BNEXT 30.1 dB
2002Class D / Cat 5e
ISO/IEC 11801:2002NEXT 30.1 dB
ANSI/TIA/EIA-568-BNEXT 30.1 dB
2002Class E / Cat 6 Class ENEXT 39.9 dB Addendum B.2-1NEXT 39.9 dB
Note: All NEXT values are pair-to-pair NEXT limit values for the
C hannel at 100 MHz ± PL values are approximately 2 dB higher
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 35/141
35
35 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Test Parameters
Parameter IS TIAInsertion Loss ( ttenuation) 3
Return Loss 3
ropagation Delay 3
kew 3
N T 3 N T C 3
CRCR C
LF T 3
LF T C 3 DC Loop ResistanceLength v 3
Wire ap 3
Legend: : andatory; C: Calculated; v: Infor ation only
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 36/141
36
36 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Classes of Copper Cabling Review
Class A is specified up to 100 kHz
Class B is specified up to 1 MHz
Class C is specified up to 16 MHz
Class D is specified up to 100 MHz
Class E is specified up to 250 MHz
Class EA is specified up to 500 MHz (in draft)
Class F is specified up to 600 MHz
Note -- This list is greatly simplified
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 37/141
37 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
The TIA Standards
Telecommunications Industry Association
Overview: Categories 5e, 6, and 6A
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 38/141
38
38 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
ANSI/TIA/EIA Standards
568-B Commercial Building Telecommunications
Cabling Standard
569-B Commercial Building Standards for
Telecommunications Pathways and Spaces
570-B Residential and Light Commercial
Telecommunications Wiring Standard
606-A The Administration Standard for the
Telecommunications Infrastructure of
Commercial Buildings
607 Commercial Building Grounding and Bonding
Requirements for telecommunications
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 39/141
39
39 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
568 Standard - Revision B
TIA goal to revise standards every 6 years
568-B approved (all sections) March, 2001
Standard is split into 3 parts
B.1- Part 1, General Requirements(Added Permanent Link test method to harmonizewith ISO/EN; Obsoleted Basic Link Test Method)
B.2 - Part 2, 100 ohm Balanced Twisted-Pair Cabling Standard (Obsoleted TSB-67 and TSB-95)
B.3 - Part 3, Optical Fiber Cabling ComponentsStandard
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 40/141
40
40 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Transmit
Receive
WorkstationWorkstation
Transmit
Receive
LANLAN
EquipmentEquipment
Signal
Signal
The Two Wire-Pair System ± Test Parameters
Signal Strength: Measured by ³Insertion Loss´
Noise: Near-End Cross Talk (NEXT)
Attenuated Signal
NEXT
SNR: Attenuation to Crosstalk Ratio (ACR or ACR-N)
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 41/141
41
41 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Horizontal CablingWorkstation Switch
Four wire pairs ± Full duplex on each pair
Effective for Cat5e / Class D:2002 cabling and higher
Applications: 1000BASE-T and 10GBASE-T
The ³New´ Transmission Model
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 42/141
42
42 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Cabling Standards Evolution for
High-Bandwidth Networking Category 5e Rated UTP Cabling Tests ±
Published 2/2000
Category 6 Rated UTP Cabling Tests ±Published 6/2002
TSB-155 ± Recertifying Cat6 for 10Gigabit Ethernet
Published 3/2007
Category 6A Rated UTP Cabling Tests ±
Still being created (in draft)
A brief review of each in more detail «
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 43/141
43
43 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Category 5e
Originally released as Addendum #5 to the 568-A
Standard in February 2000. Currently listed in 568-B.
Specified for new installations to fully support
1000Base-T with additional margin.
NEXT has a more stringent test limit than the original
TSB-67 (Cat 5) test specs.
Adds Return Loss, ELFEXT (Equal Level Far End
Crosstalk), power sum calculations of PSNEXT and
PSELFEXT to qualify multi-pair transmission.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 44/141
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 45/141
45
45 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Multiple Pair Transmission
Workstation LAN HubTransmit
(Output)
Transmit(Output)
ReceiveInput
Receive
(Input)
Signal 2
Signal 1
Example: 1000BASE-T: (4 pairs are used.)
Attenuation (signal loss) and FEXT (internal noise)
are the key measurement parameters
FEXT
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 46/141
46
46 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Attenuatio
n
Affects of all 3 disturbing pairs = Power Sum
Signal
Power Sum ELFEXT
FEXTPSELFEXT
ELFEXT
(signaldifference
in dB)
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 47/141
47
47 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Signal A to B
Signal B to A
Return Loss measures the signal echo within each pair
Desired signal = attenuated signal from other end.
Noise = reflected signal on same wire pair.
Full Duplex Transmission
System B
Receive
Transmit
System A
Transmit
Receive Directional
Coupler
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 48/141
48
48 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
C ombined affects of all 3 disturbing pairs = Power Sum
Combined 7 Noise Sources - Disturbances
Combined NEXT disturbance from 3 wire-pairs: PSNEXT
Return Loss within the same wire-pair
Combined FEXT disturbance from 3 wire-pairs: PSELFEXT
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 49/141
49
49 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Test Parameters
easuredTest Parameter
Cal ulatedTest Parameter
N XT pair-to-pair
eturn oss
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 50/141
50 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Caution!
There is no such thing as Category ³5E´,
there is only one Category 5e
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 51/141
51
51 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Category 6 was approved on June 4th, 2002.
Released as addendum #1 to 568-B.2
Pre-Standardization: In order to meet performance
requirements, vendors developed proprietary
connectors (jacks) and matching plugs.
Early designs violated TIA interoperability requirements
for connecting hardware !
Post-Standardization (2002): Full interoperability
among various manufacturers with standardized
plugs and jacks.
Category 6
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 52/141
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 53/141
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 54/141
54
54 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Alien Crosstalk
Crosstalk between wire-pairsin adjacent cables
General rules:
This crosstalk is worst betweenwire-pairs with the same twist rate
The effect is greater if cablesstay in parallel at the link ends
Impact increases with the
distance over which the cablesrun in parallel
Impact increases with thefrequency of the transmittedsignals
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 55/141
55
55 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
10 Gigabit Ethernet Development
Activities in the Cabling Industry:
Support for 10GBASE-T over Cat 6 / Class E cabling
TIA: TSB-155 (Telecommunications Systems Bulletin)
ISO/IEC: TR24750 (Technical Report)
Support for 10GBASE-T over the full 100 m
(horizontal) channel ± including alien crosstalk testing
TIA: Addendum #10 to TIA/EIA-568-B.2
TIA/EIA-568-B.2-10 ± Augmented Cat 6 (Cat 6 A)
ISO/IEC: 2nd Amendment of ISO/IEC 11801
Augmented Class E (Class E A)
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 56/141
56
56 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Channel Length Limitation for Cat 6
TIA: TSB-155 (Telecommunications Systems Bulletin)
Support for 10GBASE-T over limited channel length
should operate for channel length 37 m
should operate for channel length of 37 to 55 m, depending
on AXTalk test results
may operate over channels > 55 m after ³mitigation´
ISO/IEC: TR24750 (Technical Report)
Similar limitations for Class E as outlined in TSB-155
for Category 6 systems. For Assured Performance ± To test is to know!
The Alien Crosstalk performance should be
sample tested for all cabling links.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 57/141
57
57 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Categories of Cable
Category Frequency Data Rate Application
3
4
5
5e
6
6 A
7
16 MHz
20 MHz
100 MHz
100 MHz
250 MHz
500 MHz
600 MHz
10 Mbit/s
16 Mbit/s
100 Mbits/s
1,000 Mbits/s
** - **
10,000 Mbits/s
-
Ethernet 10BASE-T
Token Ring
100BASE-TX
1000BASE-T
** - **
10GBASE-T
-
** Category 6 will require re-certification to TSB-155 for 10GBase-T operation.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 58/141
58 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Field Test Procedures
Channel versus Permanent Link
Measuring with Accuracy
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 59/141
59
59 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Limits Are Established in a Sequential Process
Definition of requirements and limits for the CHANNEL: Length,
Crosstalk, Reflections, Attenuation
Definition of requirements and limits for the CHANNEL: Length,
Crosstalk, Reflections, Attenuation
Requirements for the Permanent LINKRequirements for the Permanent LINK
Requirements for components: Plugs & Jacks (CH ),
Cables
Requirements for components: Plugs & Jacks (CH ),
Cables
Definition of the component test procedureDefinition of the component test procedure
Range of
TEST Plugs
Range of
TEST PlugsCertification of compliant jacksCertification of compliant jacks
Definition for a PATCH CORD Test HeadDefinition for a PATCH CORD Test Head
T he way to IN T EROPABILTY !
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 60/141
60
60 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Test Configurations
Perform channel testing with user cords connected
IEEE performance specified for installation
TIA, ISO, EN Channel performance spec¶d for installation
Maintenance testing on ³end-to-end´ cabling in service
Perform permanent link testing of ³installed cabling´
TIA-568B, ISO, EN Permanent Link performance is spec¶d
Installation and arranty service
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 61/141
61
61 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
An Installed ³Cabling Link´
HUB or
SWITCH
EquipmentCord
Cross-
Connect
Panel
Telecom
Outlet
User¶s
Patch
Cord
WORKSTATION
TELECOMMUNICATIONTELECOMMUNICATION
ROOMROOM
FLOOR DISTRIBUTORFLOOR DISTRIBUTOR
WORK AREAWORK AREA
CP
CP: Consolidation Point
(optional)
NIC
HORIZONTAL CABLE
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 62/141
62
62 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
The Channel Measurement
EquipmentCord
Cross-
Connect
Panel
Telecom
Outlet
User¶s
Patch
Cord
TELECOMMUNICATIONTELECOMMUNICATION
ROOMROOM
FLOOR DISTRIBUTORFLOOR DISTRIBUTOR
WORK AREAWORK AREA
CP
CP: Consolidation Point
(optional)
HORIZONTAL CABLE
Two transitions allowed at each end
Must test with user¶s patch cords
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 63/141
63
63 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Test results must not include any contributionsmade by the tester patch cables
The Permanent Link Measurement
TelecommunicationTelecommunication
RoomRoom
Link End
Tester
Launch
Cable
TelecomOutlet
Tester
Launch
Cable
Work AreaWork Area
Patch
Panel
HORIZONTAL CABLE
Link End
CP
CP: Consolidation Point
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 64/141
64
64 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Why the ³Permanent Link´?
The true ³foundation´ ± cabling that is permanent
and part of the building infrastructure
Network equipment, patch cables and equipment
cables are changed many times during the life of the
the cabling infrastructure
Provide guarantee that the µChannel¶ (permanent
link plus patch cables) meets the network
application requirements
Compliant Perm. Link
+ Compliant Patch Cord
= Compliant Channel
Compliant Perm. Link
+ Compliant Patch Cord
= Compliant Channel
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 65/141
65
65 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Permanent Link Accuracy
With excellent baseline accuracy, the focus is on
the performance of the Permanent Link Adapter
The performance of the adapters can only make
things worse whether the baseline accuracy is good
or questionable With high-quality adapters the measurement accuracy
of the PL measurement is only degraded a very small
amount from the baseline accuracy
The principle rules:
The adapters should not contribute to the measurement results of any
test parameter (degradation to be minimized)
Mated NEXT of the test plug and jack at the end of the link-under-test
have a significant influence (this µvariability¶ is not included in the
standard accuracy model)
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 66/141
66
66 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Fundamental Characteristics of
NEXT and Return Loss
NEXT and Return Loss (RL) disturbance is more
significant when the source of the disturbance
(defect or problem) is closer to the
transmitter/receiver end (end of the link)
We will review the fundamentals of each of these
disturbances (test parameters) for Permanent Link
measurements
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 67/141
67
67 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
patch panel jack telecom outlet
End of
permanent
link
Beginning of
permanent
link
The very first element in the Permanent Link is the
mated NEXT of the patch cord plug and link jack
NEXT Measurement of the PL
The mated NEXT of the end-connections of the PL has a very
significant impact on NEXT results!
The test plug is the µreference¶ ³centered´ Cat 6 plug
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 68/141
68 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Cat 6 ³center definition´ for all wire pairs
Universal / shielded solution
Limits the variability between PMs
Increases repeatability (perceived accuracy)
Provides optimum result with compliant jack
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 69/141
69
69 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Standards Compliant Cat 6 Plug
Patented design yields the most accurate and
repeatable test results in the field.
Interoperable with all Category 6 compliant systems.
Features ³snag-free´ clip for a longer life.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 70/141
70 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Cat 6A ³center definition´ for all wire pairs
Universal / shielded solution
Limits the variability between test plugs
Increases repeatability (perceived accuracy)
Provides optimum result with compliant jack
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 71/141
71
71 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Standards Compliant Cat 6A Plug
Patented design yields the most accurate
and repeatable test results in the field.
Metal plug assembly with a replaceable
comb delivers a much longer life.
Locks in place without a clip «
no clip to break!
Interoperable with all compliant
Category 6A systems
Fully backwards
compatible with
lower categories.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 72/141
72
72 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Return Loss ± A Major Test Challenge
Return Loss in the tester¶s adapter cords ± closest to the
transmitter/receiver ± potentially adds a significant
measurement error that must be avoided
RL disturbance is more significant when the
disturbance is closer to a transmitter/receiver
(i.e., the end of the link)
Permanent Link
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 73/141
73
73 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
0
5
10
15
20
25
30
35
40
45
50
0 50 100 150 200 250 300 350 400
CAT6 ¥
L
¥
L +12d¥
Initial
50 cyc
100 cyc
200 cyc
Cable Li¦
21-7*L§ ̈
(f/20)
26-12*L§ ̈
(f/100)
Perm. Link
RL Test Limit
PL + 12 dB
Frequency (MHz)
Return Loss of Twisted-pair Adapter
Impact of handling ± ³aging´ of twisted-pair Class F patch cables.
Loss of 10 dB
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 74/141
74
74 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Return Loss ± Adapter Requirements
What is required to accurately measure RL?
The permanent link interface cable itself must
have very good return loss characteristics
Impedance (differential): very close to 100 ;
Very good Return Loss performance
Stability: Very stable impedance characteristic over time
(after coiling and uncoiling the cable while packing, etc.)
Move the calibration reference plane
to the ³end of the permanent link.´
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 75/141
75
75 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
The U nique Permanent Link Solution
DTX round cable and DSP/OMNI flat cableoffer the same superior electrical
performance:
Tightly controlled impedance (100 1)
Very good NEXT and FEXT performance
Very good RL performance
Very stable RL performance
The electrical performance is much better
than typical commercial Class F (Cat 7) cords
Proprietary technology in:
Design, materials used, manufacturing
processes and tolerances applied
Benefits of the round DTX adapter cable:
Lighter, more flexible, and longer
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 76/141
76
76 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX Series ± Broad Manufacturer Support
Over 30 Cabling and Connectivity Manufacturers haveendorsed the DTX permanent link and channel for field testing
Letters are posted on the Fluke Networks website atwww.flukenetworks.com/dtxunder ³endorsements´
Below is a partial sample of the cabling vendors «
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 77/141
77
77 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Review of the Test Methods
Beginning of
permanent link
End of
permanent link
Tester cable is not included
Consolidation point is OK
OK
CPPermanent
Link
TOC2 (PP)
End of
channel
Beginning
of channel
Channel
C1 CP
(cross-connect)
TOC2 (PP)
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 78/141
78 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX Series
CableAnalyzer
Product Overview
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 79/141
79
79 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
The DTX Series CableAnalyzers
Provides fast test times(Cat 6 Autotest of 9 seconds)
Tests up to 900 MHz (DTX-1800 model)
Level IV accuracy for certifying 10Gigabit
Ethernet and beyond
Unique AC wiremap test for POE applications
Advanced time-saving diagnostics pinpoints
the location of failure
Familiar and easy-to-use operation
with a bright color screen
Long battery life (12 hours)
Test results management in LinkWare
Bi-directional / dual wavelength fiber
certification with optional Loss/Length
and OTDR test modules
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 80/141
80
80 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX-1800 Series Capabilities
Certifies UTP and STP cabling in permanent link and channelconfigurations to EIA/TIA, IEEE, ISO/IEC and ANSI standards.
Optional Loss/Length and OTDR Fiber Test Modules certify MM and
SM fiber cabling to TIA/EIA, IEEE and ISO/IEC standards.
Autotest runs all cabling tests automatically with the press of a button.
Upon failure, an intelligent ³Fault Info´ feature identifies key cablingproblems, provides probable causes, and suggests repair solutions.
Bright color screen is easy to read in both dark and bright rooms.
Lithium Ion batteries provide 12 hours of operation.
Provides displays and printed reports in 15 languages.
DTX-1800 can store 5,600 Cat6 graphical test reports on a 128MBremovable memory card plus up to 340 Cat6 graphical test reportsin nonvolatile internal memory.
Sends stored test reports to a host computer directly via USB, serial,
or Memory Card reader.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 81/141
81
81 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX-1800 Series Capabilities (cont¶d)
Includes all test standards plus a manufacturer¶s cable library for common copper and fiber cabling.
Allows for the configuration of custom test standards.
³Talk´ feature allows 2-way voice communication between the main and
remote units over twisted pair cable (and fiber using a Fiber Module).
Advanced High Definition Time Domain Crosstalk (HDTDX) and HighDefinition Time Domain Return Loss (HDTDR) analyzer locates theposition of problems on a cable with High Definition resolution.
Shows NEXT, RL, ELFEXT, PSNEXT, PSELFEXT, Attenuation, ACR,and PSACR results up to 900 MHz with Level IV testing accuracy. Givesremote results for NEXT, RL, PSNEXT, ACR.
Tone generator for cable locating using any inductive tone probe such asthe Fluke Networks IntelliTone Probe or Pro3000 analog probe.
Optional link interface adapters allows testing of other types of cable andIDC blocks such as 110, S210, Highband,Ultim8, GIGAbix, 610XC,GIGA-PUNCH, and Class F connections.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 82/141
82
82 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX-1800 Series Includes:
DTX-1800 CableAnalyzer with lithium-ion battery
DTX-1800 SmartRemote with lithium-ion battery
Two Cat 6/Class E permanent link
adapters with long life metal plug assembly
Two Cat 6/Class E channel adapters
Hardened carrying case with strap
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 83/141
83
83 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX-1800 Series Includes (cont¶d)
128 MB multimedia memory card (MMC)
Two headsets to use with talk feature
USB cable for PC communications
RS-232 serial cable for PC communications
Two conditioning ac power supplies
DTX Series CableAnalyzer Users Manual
DTX Product CD Link are Software CD
1 Yr Standard arranty
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 84/141
84
84 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Fiber Test Adapters
Basic Loss Test Modules (Tier 1)
Advanced OTDR Module (Tier 2)
10Gig Twisted-Pair Alien Crosstalk Kit
Class F (Cat 7) Permanent Link Adapter Class F (Cat 7) Channel Adapter
SFF Fiber Test Adapter Kits
Patch Cord Test Adapter
Network Service Module Coax Test Adapter
Tone Probes
³Gold´ Support
DTX-1800 Series Accessories:
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 85/141
85 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Copper Testing
and Certification
HandsHands--On Time!On Time!
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 86/141
86
86 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Test Equipment - Ready for Use
Before going into the field
Charge & verify battery levels
Review performance
testing specs for install
Gather appropriate testadapters & accessories
Inspect test adapters
Setup unit with proper test
and report identification
Run Self Test (as needed)
Bring extra Memory Cards
for large jobs to keep the
tester working in the field
Ongoing maintenance
Load latest firmware upgrade(s)
Set Reference
Copper Testing ± 1x per month
Fiber Loss Testing ± 1x per day
Self Test (only as needed)
Factory calibration (1x per year)
Optional ± Calibrate Permanent
Link Adapters to Main Remote
for added accuracy (six months)
Visit www.flukenetworks.com
for latest revisions of DTX
firmware and Link are
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 87/141
87
87 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX Main Unit Characteristics
Soft Key Labels
Keypad and
Rotary Knob
High performanceconnector for copper
adapters
MMC Card SlotTalk Set Jack
Fiber-ready at all
times with resident
fiber modules (back)
USB and Serial
Interface Connectors
AC Power Connection
Color Display
Backlight / Contrast
Stand Power On Button
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 88/141
88
88 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX Remote Unit Characteristics
High performanceconnector for copper
adapters
Talk Set Jack
Fiber-ready at all
times with resident
fiber modules (back)
USB Interface
Connection
AC Power Connection
Colorful LEDs
Stand Power On Button
Test from Remote
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 89/141
89
89 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX Setup ± Startup
Press the Green Buttonto turn the DTX on.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 90/141
90
90 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
1. Turn rotary knob to SETUP
2. Select ³Instrument Settings´
3. Select ³Cable ID Source´ to set
labeling options. Options include: Auto Increment (rolls to next ID number)
List (pre-create download list from PC)
Auto Sequence (pre-create list in tester)
None (you have to type every label)
4. Select ³Store Plot Data´ to save thefrequency graphs. Options include: No (no graphs saved - not recommended)
Standard (saves graphs to the standards)
Extended (saves graphs to a higher freq.)
Setup ± Instrument Settings
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 91/141
91
91 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
5. Select ³Current Folder´ to setwhere test results will be saved.
You can create up to 20 folders.
Press F1 to ³Create Folder´
Create a new folder name andpress <SAVE> when completed
Select your new folder from the list
6. Select ³Result Storage Location´ to
set the data storage location. Internal Memory ± allows storage of
one to two days of test reports.
Memory Card (preferred) ± allows
storage of thousands of test reports.
Setup ± Instrument Settings
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 92/141
92
92 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
1. Press the right arrow key to accesspage 2 of ³Instrument Settings´.
2. Select ³Operator´. Press F1 to
create a new user name (20 max).
3. Select ³Site´ and enter a new name.
You can store up to 20 site names.
4. ³Company´ is your company name.
For this class, the setting should be³Fluke Networks Training´.
5. You can choose from 15 different
³Languages´ within the DTX.
Setup ± Instrument Settings
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 93/141
93
93 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
1. Press right arrow key to accesspage 3 of ³Instrument Settings´.
2. This page sets the date, time,
numeric format, and length.
3. Press right arrow key again to view
page 4 of ³Instrument Settings´.
4. Set the parameters as follows:
Power Down Time-Out: 30 minutes Backlight Time-Out: 10 minutes
Audible Tone: Yes
Power Line Frequency: 60 Hz or 50Hz
Setup ± Instrument Settings
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 94/141
94
94 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
1. Press right arrow key to accesspage 5 of ³Instrument Settings´.
2. This page sets the following:
Auto Save Results ± Saves test results
automatically to the next ID at the end
of the test without touching a button.
Plot Grid ± Adds a grid to the graphs
to help make visual measuring easier.
3. Press <EXIT> to return to themain ³Setup´ screen.
Setup ± Instrument Settings
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 95/141
95
95 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
1. Arrow up to ³Twisted Pair´ andpress <ENTER>.
2. Select ³Test Limit´ to choose which
test standard to run.
³Last Used´ lists the tests recently
utilized in this tester (up to 9).
3. Press F1 ³More´ to see a complete
list of all the global test standards.
4. Select ³TIA´ and review the choices.
Highlight ³TIA Cat 6 Perm. Link´
and press <ENTER>.
Setup ± Twisted Pair
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 96/141
96
96 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Setup ± Twisted Pair
1. Arrow down to ³Cable Type´and press <ENTER>.
2. ³Cable Type´ is simply the name of
the cable. This name prints on the
test report and helps set the NVP.You have the following choices:
Basic Names: UTP, FTP, or SSTP
Manufacturer: Lists major cable names
Custom: Add a new cable name
3. For this class, select ³UTP´, then
select ³Cat 6 UTP´ as a generic
cable name.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 97/141
97
97 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Setup ± Twisted Pair
1. Arrow down to ³NVP´and press <ENTER>.
2. NVP is an abbreviation for the
Nominal Velocity of Propagation.
Displayed as a % of the speed of light
Converts the propagation delay time
measurement into an equivalent length
Varies by a few percent based upon the
construction of the cable (largestfactor is plenum vs. non-plenum cable)
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 98/141
98
98 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Setup ± Twisted Pair
3. Several methods to set the NVP:
Generic Default ± Do nothing ± Distance
will be off up to 3 percent in error
Manufacture List within ³Cable Type´ ±
Selecting a specific brand will tune the
NVP for that particular cable
Manual Entry ± ithin the NVP menu,
use up or down arrow keys to change
Sampling ± ithin the NVP menu, field
test the cable to determine the NV
P
4. For this class, we will use the
default. A small error in the length
is typically OK. Press <EXIT>.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 99/141
99
99 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX Setup ± Twisted Pair
1. Arrow down to ³Outlet Configuration´and press <ENTER>.
2. Outlet Configuration creates an
accurate color wiremap picture in
the tester and test reports. TheDTX displays the valid terminations
per the test standard selected.
Press F1 ³Sample´ to see a picture
3. For this class, select T568B for theoutlet configuration.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 100/141
100
100 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX Setup ± Twisted Pair
1. Press right arrow key to accesspage 2 of ³Twisted Pair´ settings.
2. Select ³HDTDX / HDTDR´ and
press <ENTER>. This setting
determines when the DTX createstroubleshooting diagnostics.
Pass* / Fail Only (recommended) ±
Provides diagnostics upon a marginal
(*) pass or fail condition. All Autotests ± Provides diagnostics for
every test.
3. For this class, set the tester to
Pass*/Fail only.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 101/141
101
101 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX Setup ± Twisted Pair
1. Arrow down to ³AC ire Map´and press <ENTER>.
2. There are two testing options:
Disable (standard setting) ± Tests
wiremap with a DC signal. This is the
typical test method of all cable testers.
Enable ± Tests wiremap with an AC
signal. This is necessary to test
through POE injectors, which will
block DC power at the injector (resulting in an open wiremap).
3. For this class, set AC ire Map to
³Disable´ and press <ENTER>.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 102/141
102
102 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX Special Functions
Rotate the dial to ³Special Functions´
Set Reference
View/Delete Results
Move/Copy Internal Results Tone Generator
Memory Status
Battery Status
Self Test
Update Software
Version Information
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 103/141
103
103 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX Single Test Function
Rotate the dial to ³Single Test´
Runs only a single test parameter.
Used to pre-test (wiremap only) or
isolate cabling problems.
HDTDR and HDTDX can
be run without a remote connected.
Scanning feature runs tests
continuously to help find intermittent problems: e.g. ire Map - turn
scanning on - then wiggle cabling
by connectors to expose problems.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 104/141
104
104 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
AUTOTEST Project Screen
The AUTOTEST project screendisplays:
Battery Status, Time, and Date.
Twisted Pair Settings ± Test Limit,
Cable Type, and Outlet Configuration. Instrument Settings ± Operator, Site,
Folder, and Store Plot Data.
Selecting ³Change Media´ (F1)
allows you to switch from copper to fiber testing with a press of the
button (assuming fiber modules
are inserted into tester).
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 105/141
105
105 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Cable Setup ± Good Link
Grey
Cable Loop
Permanent Link
Test Adapter
Permanent Link
Test Adapter
DTX-1800 Remote
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 106/141
106
106 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Autotest Results ± Pass or Fail?
* Marginal result
Individual Test Results Overall Result
All tests Pass PASS
One or more tests Pass*All other tests Pass
PASS*
One or more tests Fail*
All other tests Pass(*)
FAIL*
One or more tests Fail FAIL
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 107/141
107
107 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
To start the AUTOTEST, press TEST
Fast Certifying with the DTX
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 108/141
108
108 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Saving Test Results with the DTX
Test results naming hasnever been simpler with the
DTX Series Cable Analyzers.
Test results names can be:
Pre-loaded list createdthrough Link are
Auto Incremented
Auto Sequenced
Manually entered
Results can be saved in:
Memory card
Internal memory
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 109/141
109
109 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
DTX Test Data Capacity
How many graphical tests will the DTX Series store?
Why can you store more Cat 5e tests than Cat 6 or 10GBase-T?
Cat 6 and 10GBase-T have more data points to test and report than Cat 5e
Cat 6 = 68,712 data points; 10GBase-T (TSB-155) = 100,212 data points
Category 5e:
Category 6:
10GBase-T:
520
340
250
520
340
250
DTX LT DTX-1200 and DTX-1800
Internal Internal External ³ ³
128MB card 256MB
7,400
5,600
4,200
11,300
8,600
6,400
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 110/141
110
110 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Utilizes standard MMCs and SD/MMCs
Standard card - 128 MB
Optional cards - 256 MB to 1 GB
Backup the data to a PC everyfew days and save the MMCs
as an inexpensive backup
Eliminate the need to
re-test in the field «
Store and transfer every data point with the DTX
Re-certify to a new
standard at a later
date with Link are
Test Results Management --
Removable Memory Card
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 111/141
111
111 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Test Results Management --
LinkWare PC Software
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 112/141
112
112 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Create ANSI/EIA/TIA
606-A compliant
projects
Import data fromFluke Networks
testers into a
common database
Easily sort through
test reports Append files with
test reports from
another project
Test Results Management --
LinkWare PC Software
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 113/141
113
113 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
With LinkWare you can:
Upgrade software
databases for
various FlukeNetworks cable
test equipment
Create customized
setups for common
equipment Create custom
Cable ID lists
Test Results Management --
Tester Administration
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 114/141
114
114 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Example: You have the ID ³FLR1 CAB1 BOX 1 23´ in the DTX.
Using the Import Wizard in LinkWare, the 606-A Tree will be
created within LinkWare and sort the test results automatically.
Test Results Management --
LinkWare helps with TIA 606-A Standards
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 115/141
115
115 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
LinkWare provides
professional custom
reports to the TIA, ISO,
and EN standards
Custom company logos
can be incorporated
onto test reports
Reporting preferences
such as language,measurement (ft or m),
etc. can be changed
within LinkWare
Test Results Management --
Flexible Reporting
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 116/141
116
116 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Test Results Management --
Printed and Electronic PDF ReportsLinkWare Software supports several
formats to provide test results
information to your customer:
Graphical color report with measured
test points over full frequency range
Text format with worst case
and worst value data
Summary report which provides a
list of the cabling links tested and
key information
Reports can be printed on paper
or sent to an electronic PDF file.
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 117/141
117
117 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
ALWAYS save test results to a PC every few
days while testing in the field
Make two copies of the data « don¶t live
through the pain of loosing test data!
Print test results to paper or PDF files.
Do not delete results on the memory cards
until you have double-checked the results onthe printed or PDF output.
Test Results Management --
Documentation Suggestions
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 118/141
118 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
What if ...
The link doesn¶t pass?
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 119/141
119
119 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Troubleshooting with the DTX
Performance requirements in the standards (such
as CAT 6 and 6A) for NEXT and RL are much more
stringent than previous categories of cabling.
There is a probability that installed links will be
MARGINAL or FAIL even though all components
meet component level specifications and
installation workmanship is of acceptable quality
Troubleshooting failed links efficiently and
effectively is critical to ensure minimal loss of
project time and associated additional project cost
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 120/141
120
120 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Troubleshooting with the DTX
The two primary ³Performance Failures´ in a high
performance cabling system are caused by:
Near End Cross Talk (NEXT)
Return Loss (RL)
f
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 121/141
121
121 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
NEXT and NEXT Defects
Near End Cross Talk (NEXT) Crosstalk between two twisted pairs measured at the same
end of the cable as the disturbing signal source
Causes of NEXT include:
Untwisting of wire-pairs at connection points Poorly matched plug/jack combinations
Poor quality patch cables
Bad connectors
Bad cable
Split pairs
Excessive compression caused by plastic cable ties
Excessive noise source adjacent to measured cabling link
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 122/141
122
122 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Advantages of NEXT Diagnostics
Identify and locate the problem
Dramatically reduce the amount of time to locatethe NEXT failures (connector, cable, TP/CP)
Knowing what and where to inspect in the link
reduces the time and cost of fixing the problem
Disadvantage of ³random troubleshooting´:
Increase project time in re-terminating connectors that arenot the cause of the fault
Increase project time and material cost in pulling cable,replacing, re-terminating and re-testing cable that wasnot the fault
T bl h i NEXT i h h DTX
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 123/141
123
123 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Troubleshooting NEXT with the DTX
Fault Info ± need to add info on fault info here.
T bl h ti NEXT ith th DTX
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 124/141
124
124 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Troubleshooting NEXT with the DTX
DTX Series utilizes Fluke Networks patented HighDefinition Time Domain Crosstalk Analyzer (HDTDX)
HDTDX accurately pinpoints the location of NEXT faults
quickly ± the taller the spike, the bigger the problem!
Poor termination
at consolidation
point
Bad cable or
wrong category
with excessive
crosstalk on
entire cable
RL d RL D f t
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 125/141
125
125 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
RL and RL Defects
Return Loss measures the reflected signalenergy caused by an impedance anomalies
and mismatches in the cabling link
Causes of RL include:
Patch cord impedance is not 100;
Untwist or kinks in the cable ±
original twist should be maintained
Bad connectors
Cable impedance is not uniform
Cable is not 100; (use of 120 ; cable, etc.)
Ad t f RL Di ti
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 126/141
126
126 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Advantages of RL Diagnostics
Identify and locate the problem
Dramatically reduce the amount of time to locate
the failures/defects (connector, cable, TP/CP)
Knowing what and where to inspect in the linkreduces the time and cost of fixing the problem
Disadvantage of ³random troubleshooting´:
Increase project time in re-terminating connectors that
are not the cause of the fault
Increase project time and material cost in pulling cable,
replacing, re-terminating and re-testing cable that was
not the fault
T bl h ti RL ith th DTX
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 127/141
127
127 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Troubleshooting RL with the DTX
Fault Info ± need to add info on fault info here.
T bl h ti RL ith th DTX
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 128/141
128
128 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Troubleshooting RL with the DTX
DTX Series utilizes Fluke Networks patented HighDefinition Time Domain Reflectometer (HDTDR)
HDTDR will accurately pinpoint the location of RL
faults quickly
Bad section of
cable caused by
poor construction
C bl S t B d Li k Y ll C bl
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 129/141
129
129 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Cable Setup ± Bad Links ± Yellow Cable
DTX-1800 Remote
Yellow Cable
GreyCable Loop
GreyCable Loop
6¶Cable
Permanent Link
Test Adapters
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 130/141
130
130 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Test automatically interrupts toshow a wire map problem.
Cable Testing with the Yellow Patch Cord
Replace ³good´ patch cord with bright
yellow patch cord.
Press ³Test´.
Remove the yellow patch cord and
reconnect it to the opposite
receptacle ends. Press ³Test´.
hat do you see?
Cable Setup Bad Links Red Cable
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 131/141
131
131 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Cable Setup ± Bad Links ± Red Cable
DTX-1800 Remote
Red Cable
GreyCable Loop
GreyCable Loop
6¶Cable
Permanent Link
Test Adapters
Troubleshooting with DTX
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 132/141
132
132 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Troubleshooting with DTX
1. hen a cable fails, the first action
is to press ³Fault Info´ (F1 key)
2. Fault Info visually shows the
problem(s) and provides
recommended solutions
3. To further evaluate the effects of the
NEXT, press the EXIT key to return to
the Summary screen, then select the
³HDTDX Analyzer´
4. HDTDX shows you high-level NEXT
details for cabling and connections
Cable Setup Bad Links Blue Cable
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 133/141
133
133 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Take the blue cable and spread out the wiresso it looks similar to this:
Cable Setup ± Bad Links ± Blue Cable
Cable Setup Bad Links Blue Cable
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 134/141
134
134 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Cable Setup ± Bad Links ± Blue Cable
Blue Cable
DTX-1800 Remote
GreyCable Loop
GreyCable Loop
6¶Cable
Permanent Link
Test Adapters
Troubleshooting with DTX
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 135/141
135
135 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Troubleshooting with DTX
1. hen a cable fails, the first action
is to press ³Fault Info´ (F1 key)
2. Review the Fault Info and the
recommended solutions. Press the
up arrow key to see other faults.
3. To further evaluate the effects of
the RL, press the EXIT key to
return to the Summary screen,
then select the ³HDTDR Analyzer´
4. HDTDR shows you high-level RL
details of cabling and connectors
Cable Setup Bad Links Black Cable
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 136/141
136
136 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Cable Setup ± Bad Links ± Black Cable
DTX-1800 Remote
Black Cable
GreyCable Loop
GreyCable Loop
6¶Cable
Permanent Link
Test Adapters
Troubleshooting with DTX
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 137/141
137
137 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Troubleshooting with DTX
1. hen a cable fails, the first action
is to press ³Fault Info´ (F1 key)
2. Fault Info visually shows the
problem(s) and provides
recommended solutions
3. To further evaluate the effects of the
NEXT, press the EXIT key to return to
the Summary screen, then select the
³HDTDX Analyzer´
4. HDTDX shows you high-level NEXT
details for cabling and connections
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 138/141
138
138 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Any QuestionsAny Questions?
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 139/141
139 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Fluke Networks Online Reference Material
Knowledge Base:
kb.flukenetworks.com
Technical reference web site ± includingstatement of work for Category 6 testing :
www.flukenetworks.com/consultants
Fluke Networks¶ training programs:
www.flukenetworks.com/training
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 140/141
140 CCTT DTX Series Copper Testing v.3A Fluke Networks 2007 - All rights reserved
Fluke Networks Contact Information
Sales / Technical Support: (800) 283 ± 5853
Orders / RMAs (800) 283 - 5853 (425) 446 - 4839 FAX
Service Center: (888) 993 ± 5853
Parts Department: (888) 993 - 5853
8/8/2019 Cctt Dtx Copper Ver3a
http://slidepdf.com/reader/full/cctt-dtx-copper-ver3a 141/141
Break Time
Please be back in 15 minutes