Switching
l Monitors current during breaking.
l Est imates primary contact wear( åò i²dt)
l Monitors arc duration.
Auxiliary and control circuits
l Monitors operating coil continuity.
l Monitors auxiliary supply
voltage.l Monitors heater integrity.
CBWatch-2 continuously monitors circuit breaker condition. It signals in real time any malfunction to maintenance services. Therefore, CBWatch-2 facilitates reduced maintenance cost and failure risk.
CBWatch-2Modular circuit breaker monitoring system
Optional functions
SF l Monitors gas pressure and
temperature and calculates the SF or gas mixture density using the Beattie-Bridgeman algorithm.
l Detects liquefaction and inhibits false alarms in the event of liquefaction.
l Calculates SF leakage rates in order to give advance warning of alarm and lockout threshold levels.
Mechanical operation
l Monitors close and open operating times.
l Allows the use of conventional auxiliary switches, static auxiliary switches or primary contact travel sensors.
l Monitors primary contacts separation speed, buffering and over travel.
l Detects deterioration in mechanical performance (friction, corrosion, breakage, spring fatigue and buffer defects).
l Monitors auxiliary switch timing.
Spring operating mechanism
l Monitors recharging motor operating time.
l Detects motor or motor limit switch defects.
Hydraulic operating mechanism
l Monitors pump motor operating time.
l Detects internal and external leackage.
l Detects nitrogen loss from accumulator.
l Detects threshold pressure on hydraulic system.
6
6
6
Spring mechanism :l Spring motor limit switch
contacts.
Hydraulic mechanism : l Pump start contacts.l Hydraulic pressure sensor.
Auxiliary and control circuits :l Temperature sensors. l Coil supervision relays.
Installation
l Dimensions 310mm x 280mm x 95mm12 x 11” x 3
l Installation in operating mechanism, local control cubicle or separate enclosure.
Available versions
l Version for circuit breakers with one operating mechanism for all three poles.
l Version for circuit breakers with one operating mechanism for each of the three poles.
Environment
l Ambiant temperature -40°C to +55°C(Option : -50°C with heater)
l Electromagnetic compatibility according to standards :
- IEC 255-5- IEC 1000-4-4- ANSI C37-90-1- IEC 1000-4-12- IEC 255-22-3
Power supply
l 48 - 125V DC ; 48 - 120V ACl 150 - 250V DC ; 150 - 240V ACl Tolerance : -30% to +15%l Power consumption : 30 VA
maximum.
Dependability
l High reliability and high availability due to continuous self monitoring of electronic module and sensors.
Local interface
l LCD display and keypad (option) l 1 self monitoring status relay. l 4 configurable output relays.l 1 self monitoring status LED.l 4 local indication LEDs.l RS232 local communication port.
Network interface
l Isolated RS485 communication port with MODBUS protocol.
SF :l Pressure and temperature
sensors.
Operations :l Coil signal sensors. l Auxiliary contacts.l Primary contact travel sensors.
Primary current : l Auxiliary current transformers.
Example installationCircuit breaker with one operating mechanism per pole
Sensors required for different options
¼‘’ ¾’’
Pole A sensorsPole B sensors
Pole C sensors
INTERFACE :Local RS232 port
RS485 MODBUS portOutput relay contacts
6
Ref
: 22 B
80
- C
onte
nts
subje
t to
modific
ations
without notice
.