Catalogue Wetown Busway Series

46

Transcript of Catalogue Wetown Busway Series

Page 1: Catalogue Wetown Busway Series
Page 2: Catalogue Wetown Busway Series

Contents

LZ series compact busway 18

Wind power busway 27

Copper bar 42

LM series compact busway 1

GM cast resin busway 21

Medium voltage busway 32

Page 3: Catalogue Wetown Busway Series

LM series compact busway

The compact "sandwich" design saves space with minimum voltage drop.

Specially designed to fit into the tight angle and height requirements of today's

architectural space, between floors and along walls.

The conductor is fully enclosed with the aluminium enclosure, which provides

excellent heat dissipation, thus improving the power transmission efficiency and

reducing voltage drop.

The operating handle of plug can be installed on the top or side with accurate

opening or closing indication.

The padlock mechanism is set for protecting the plug from mal-operation

and any unauthorized access.

Plug outlet covers prevent unintentional contact of the busbar.

Plug in units are automatically grounded on installation.

Polarized engagement of the plug to the busway provides the installer with

positive plug/phase alignment.

Bus plugs are provided with internal interlocking mechanisms to prevent their

doors from being opened whilst energized, ensuring operation safety.

LM series compact busway system is a flexible and reliable electrical distribution system with a sandwich

construction and superior performance. It is a safe and robust system with high electrical efficiency, low

temperature rise, efficient heat dissipation, low voltage drop, high mechanical strength and ease of installation.

It is suitable for alternating current three-phase three-wire, three-phase four-wire and three-phase

five-wire power supply and distribution system, with the frequency 50~60Hz, rated working voltage up to

690V, rated insulation voltage up to 1000V, and rated working current 100-5000A.

System introduction

Product featuresCompact design means flexibility

·

·

Safety Feature of the Bus Plug

·

·

·

·

·

·

01

Page 4: Catalogue Wetown Busway Series

Robust enclosure with light-weight feature

Busway system utilizes high performance tin-plated copper or silver-

plated aluminium conductor, and provides high quality protection from

corrosion and high conductivity at the contact surface.

The conductive busbar is wholly wrapped in Class B (130) insulating

material, providing significant insulation level and resistance to impact.

The insulating material meets the requirements of ROHS, and safety

requirements of GE.

The joint assembly's cone-shaped insul ation plate design increases

mechanical strength while its molded joint ground side plate ensures

even pressure applied across the joint.

Large sized Belleville washers assure even pressure on contact .

No special torque wrench is required. Just a common 16mm socket

wrench is used to fasten the xed captive torque bolt with red

indication disc. (When the indicating discfalls off, the joint is properly

tightened automatically).

4mm per joint field adjustable isolation allows for job site flexibility

during installation.

Precision sawing machine to assure the formation of

cross-section of copper bar and reduce the contact resistance

of busbar joints to a great extent.

With light-weight, aluminum alloy enclosure, the unique design can

fit your specific application with high exibility, safety and reliability.

The powder coated aluminum alloy enclosure has been tested to

withstand the salt spray test.

The aluminum alloy enclosure is corrosion resistant , provides high

heat dissipation and an extremely low impedance ground path , with

50% grounding capacity.

·

·

·

Reliable insulation

·

·

·

Ease of installation

·

·

·

Precision equipment

·

·

02

Page 5: Catalogue Wetown Busway Series

Technology parameters

Grouding resistance of LM busway system (50% grounding temperature=20℃)

Copper bar

Items

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

Rated current(A)

250

400

630

800

1000

1250

1350

1600

2000

2300

2500

3150

3200

3800

4000

4500

5000

Resistance(10-6 Ω/m)

308.8

208.1

179.1

141.1

108.1

94.2

81.0

64.3

55.8

45.8

37.6

28.9

28.9

24.8

23.3

18.8

17.4

Items

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

Rated current(A)

100

160

200

250

400

500

630

800

1000

1250

1350

1600

2000

2300

2500

3150

3800

4000

Resistance(10-6 Ω/m)

342.7

342.7

342.7

342.7

259.8

210.7

178.1

138.0

119.4

95.2

86.1

76.9

63.3

56.4

52.7

35.0

28.6

25.2

Table1-1

Aluminum bar

Short-circuit current ratings

LM busway provides predictable, consistent strength and high short-circuit ratings.

LM busway is third party certified by KEMA to be in compliance with IEC60439-1 and-2 short circuit

withstand test for 1 second.

Rated current

(A)

250~800

1000~1600

2000~3150

3200~5000

Rated short-time

withstand current(KA)

30

50

65

100

Rated peakwithstand current

(KA)

63

105

143

220

Rated current

(A)

100~250

400~800

1000~2500

3150~4000

Rated short-time

withstand current(KA)

10

30

50

80

Rated peakwithstand current

(KA)

17

63

105

176

Copper conductor Aluminum conductor

Table1-2

Table1-3 Table1-4

03

Page 6: Catalogue Wetown Busway Series

Ambient temperature's influence on application

Within the ambient temperature of 40, LM busway system can continuously operate at rated current

while the maximum enclosure temperature rise won't exceed 55 K.

If the busway continuously operated at higher ambient temperature, it should be derated first, i.e. the

busway current-carrying capacity = rated current x de-rating factor. (As shown in tables)

Ambient temperature (A)

40

45

50

55

60

65

70

Factor

1.00

0.95

0.90

0.85

0.80

0.74

0.67

Table1-5

Ambient temperature,24h average temperature(℃)

Table1-6

Rated

curren

tle

[%]

04

Page 7: Catalogue Wetown Busway Series

Resistance, reactance, impedance and voltage drop

LM busway has low voltage-drop values. Minimum reactance is due to very close bar spacings (sandwiched

construction) and a non-magnetic enclosure. Values shown are identical for plug-in and feeder.

Copper busbar(50Hz, temperature=20℃)

Rated

current(A)

2504006308001000125013501600200023002500315032003800400045005000

Resistance

10-6Ω/m154.4104.089.670.558.947.140.535.327.922.918.814.414.412.411.79.48.7

Reactance

44.835.332.127.424.120.718.316.614.212.310.79.59.56.56.35.45.0

Impedance

160.8109.895.175.763.751.444.43931.326.021.617.317.314.013.310.810.0

Voltage drop (V/m)Power factor cosφ

0.60.0560.0630.0870.0890.0950.0970.0910.0960.0970.0940.0860.0890.0900.0830.0830.0780.080

0.70.0610.0680.0930.0950.1010.1030.0970.1010.1030.0990.0900.0920.0930.0870.0880.0810.084

0.80.0650.0720.0990.1010.1070.1080.1010.1060.1070.1020.0930.0940.0950.0910.0910.0840.086

0.90.0690.0760.1030.1050.1100.1120.1040.1080.1090.1040.0940.0940.0950.0920.0920.0840.087

1.00.0670.0720.0980.0980.1020.1020.0950.0980.0970.0910.0810.0790.0800.0820.0810.0730.075

Aluminum busbar(50Hz, temperature=20℃ )

Rated

current(A)

100

160

200

250

400

500

630

800

1000

1250

1350

1600

2000

2300

2500

3150

3800

4000

Resistance

10-6Ω/m

171.3

171.3

171.3

171.3

129.9

105.3

89.0

69.0

59.7

47.6

43.0

38.5

31.7

28.2

26.3

17.5

14.3

12.6

Reactance

35.3

35.3

35.3

35.3

29.5

25.6

22.8

19.1

17.1

14.5

13.6

12.5

10.9

10.0

9.5

5.8

5.0

4.8

Impedance

174.9

174.9

174.9

174.9

133.2

108.4

91.9

71.6

62.1

49.8

45.1

40.4

33.5

29.9

28.0

18.5

15.2

13.5

Voltage drop (V/m)

Power factor cosφ

0.6

0.023

0.036

0.045

0.057

0.070

0.072

0.078

0.079

0.086

0.087

0.086

0.092

0.096

0.099

0.101

0.083

0.083

0.079

0.7

0.025

0.040

0.050

0.063

0.078

0.080

0.086

0.086

0.093

0.094

0.093

0.099

0.104

0.107

0.109

0.089

0.089

0.085

0.8

0.027

0.044

0.055

0.069

0.084

0.086

0.093

0.092

0.100

0.101

0.100

0.106

0.110

0.114

0.116

0.095

0.095

0.090

0.9

0.029

0.047

0.059

0.073

0.090

0.092

0.098

0.098

0.106

0.107

0.105

0.111

0.115

0.119

0.121

0.100

0.099

0.093

1.0

0.030

0.047

0.059

0.074

0.090

0.091

0.097

0.096

0.103

0.103

0.101

0.107

0.110

0.112

0.114

0.096

0.094

0.087

Table1-7

Table1-8

05

Page 8: Catalogue Wetown Busway Series

Physical data

Feeder straight length

Feeder straight lengths may be installed

either vertically or horizontally.

Copper busbar

Rated

current

(A)

250

400

630

800

1000

1250

1350

1600

2000

2300

2500

3150

3200

3800

4000

4500

5000

Weight of busbar (kg/m)

Four-wire100%N

9.2

11.6

12.8

15.2

17.6

21.1

24.7

28.6

35.4

43.8

53.3

64.7

64.7

76.7

81.5

103.0

112.6

Five-wire 100%N, 50%PE

9.8

12.4

13.8

16.4

19.2

23.1

27.1

31.4

39.1

48.4

59.1

71.8

71.8

85.1

90.5

114.5

125.2

Fig

1-2

1-3

Rated

current

(A)

100-250

400

500

630

800

1000

1250

1350

1600

2000

2300

2500

3150

3800

4000

Weight of busbar (kg/m)

Four-wire100%N

6.9

7.7

8.6

9.4

11.1

12.3

14.8

16.1

17.7

21.1

23.6

25.2

37.3

45.1

48.6

Five-wire 100%N, 50%PE

7.2

8.1

9.0

9.9

11.8

13.1

15.9

17.3

19.1

22.8

25.6

27.4

40.5

49.1

52.9

Fig

1-2

1-3

Aluminum busbar

Notes: The figures are only for reference, our company reserves the right to amend the above datas without notice.

Dimensions and weight

Standard length is 3000mm, and the

minimum length is 400mm.

Table1-9 Table1-10

Fig1-1 Fig1-2 Fig1-3

06

Page 9: Catalogue Wetown Busway Series

Plug-in busway has a flexible design with optional

plug outlets on both sides. The minimum space

between plugs is 610mm and up to 4 plug outlets

may be fixed on each side of the 3-meter standard

length. The customer may reserve plug outlets for

extension in the future when changes occurs in terms

of the equipment load or busway run. The plug-in

busway may be installed either vertically or

horizontally.

Both base plate and socket cover are set for each

plug outlet. The former helps to prevent fingers from

contacting live conductors (IP2X) by accident, on

which the phase sequences of conductors are identied. And the latter prevents the conductive contacting

surface from ingress of dust or contaminant . A pad may be used to keep off dust or moisture.

Standard length is 3000mm, and the minimum length is 1000mm. The standard length of L1 (distance

from the center of plug outlet to standard end) is 600mm, and the standard length of L2 (distance between

the centers of two adjacent plug outlets) is 600mm.

Below is a drawing and form to show the minimum dimension of the busway length.

LM busway system adopts the double-headed torque

limiting joint bolt. When the bolt is properly tightened,

the top bolt head will break off so as to ensure the

correctness of installation.

The joint has 4mm adjustments for both side busway.

The connection cover plate avoids excessive adjustment

of the joint. The joint may be safely removed without

obstructing the adjacent length.

Plug-in straight length

Joint

Fig1-4

Fig1-5

07

Page 10: Catalogue Wetown Busway Series

This bolt is the standard joint bolt offered for all LM

Series Busway.

When the bolt is properly tightened, the outer head

will break off with the bright red label removed. This

will help eliminate any errors occur during installation

by a quick visual inspection.

No torque wrench is required for initial installation.

The bolt is reusable after the top head is broken off

by using a standard torque wrench on the second

bolt head.

The standard torque is 685N.m.

Double-headed torque limiting joint bolt

·

·

·

Fig1-6

·

08

Page 11: Catalogue Wetown Busway Series

Fittings

LM busway system has a complete family of fittings to meet virtually all layout requirements using the

compact minimum sizes shown. Special turns such as at angles greater than 90and crosses are also available.

Each piece of busway is labeled to maintain proper

phasing. All enclosure width and depth dimensions are

identical to straight lengths.

Note: Offsets and combination elbows are typically used

only when standard elbows will not fit.

Edgewise elbow Flatwise elbow

Edgewise offset Flatwise offset

Fig1-7

Fig1-8

Fig1-9

Fig1-10

09

Page 12: Catalogue Wetown Busway Series

Edgewise tee Flatwise tee

Flanged end

Flanged end and end tap box can be used in connection with switchgear and transformer of any type, and

users can determine, the spacing between the stubs of the bus bar based on the specic applications.

Flatwise cross Edgewise cross

Fig1-11Fig1-12

Fig1-13Fig1-14

Fig1-15

10

Page 13: Catalogue Wetown Busway Series

Note:1. AS a standard anged end, when the bus bar current is less than or equal to 1600A, K =100mm; when

the bus bar current is more than 1600A, K =120mm.2. The dimension of flanged end cover Aand B can be decided by switch cabinet and transformer end or

according to customer’s requirements.3.“a”and“b”is the distance between the centres of holes, which dimension is decided by the hole of

switch cabinet and transformer end.4. All the dimensions provided are for standard products. Please contact our engineers for customized

products' dimensions.

Flanged end details

Fig1-16

Fig1-17

11

Page 14: Catalogue Wetown Busway Series

Rated Current (A)

250

400

630

800

1000

1250

1350

1600

2000

2300

2500

3150

3200

3800

4000

4500

5000

A

20

20

20

20

25

25

20

25

30

30

30

30

30

25

25

30

30

B

40

40

40

40

50

50

40

50

60

60

60

60

60

50

50

60

60

C

40

40

60

60

60

60

60

60

50

50

60

60

K

100

100

100

100

100

100

100

100

120

120

120

120

120

120

120

120

120

2-M

2-φ11

2-φ11

2-φ11

2-φ11

2-φ14

4-φ14

4-φ14

4-φ18

6-φ18

6-φ18

6-φ18

4-φ18

4-φ18

6-φ18

6-φ18

6-φ18

6-φ18

Type

A

A

A

A

A

B

B

B

C

C

C

B

B

C

C

C

C

Rated current (A)

100

160

200

250

400

500

630

800

1000

1250

1350

1600

2000

2300

2500

3150

3800

4000

A

20

20

20

20

20

25

25

20

20

30

30

25

30

30

30

25

30

30

B

40

40

40

40

40

50

50

40

40

60

60

50

60

60

60

50

60

60

C

40

40

60

60

50

60

60

60

50

60

60

K

100

100

100

100

100

100

100

100

100

100

100

100

120

120

120

120

120

120

2-M

2-φ11

2-φ11

2-φ11

2-φ11

2-φ11

2-φ14

2-φ14

4-φ14

4-φ14

4-φ18

4-φ18

6-φ18

6-φ18

6-φ18

6-φ18

6-φ18

6-φ18

6-φ18

Type

A

A

A

A

A

A

A

B

B

B

B

C

C

C

C

C

C

C

Aluminium busbar

Copper busbar

Table1-11

Table1-12

12

Page 15: Catalogue Wetown Busway Series

End tap box

LM busway system tap boxes are used where a run of busway is

fed by cable. We offer standard size end tap box (1m1m1m) while

we also supply with nonstandard box according to the on-site

measurement.

All the dimension provided are for standard products. Please

contact our engineers for customized products' dimensions.

Terminnal cover

Terminal cover is installed to terminate the busway, preventing outsider environment from contacting with

the live parts, thus enclosing the whole bus system.

Connection between flanged end and end tap box

The flange can be produced according to the dimension of end

tap and connected to end tap directly.

13

Page 16: Catalogue Wetown Busway Series

Flanged end cutout and hole pattern

Note:1. "A" indicates the length of end tap box while "B" indicates the width, they are based on the site

situation.2. "L1" and "L2" are based on the location of flanged end. For standard product, they' are the same.3. "M1" is based on the location of flanged end. For standard product, M1=M/24. As shown in the figure, the hole in the corner shall be 75mm away from one edge of end tap box and

20mm away from the other, the rest distance wherein is given uniformly for mid holes according to situation.5. "a" and " b" indicate the distance between the centers of two adjacent holes, and the value shall be

limited with the extension from 100mm to 250mm.

Rated Current

(A)

250

400

630

800

1000

1250

1350

1600

2000

2300

2500

3150

3200

3800

4000

4500

5000

M

4 Wire

330

330

330

330

330

330

330

330

390

390

390

390

390

390

390

390

390

5 Wire

430

430

430

430

430

430

430

430

510

510

510

510

510

510

510

510

510

N

50

60

65

75

85

100

115

130

160

195

235

312

312

362

382

472

512

Rated Current

(A)

100

160

200

250

400

500

630

800

1000

1250

1350

1600

2000

2300

2500

3150

3800

4000

M

4 Wire

330

330

330

330

330

330

330

330

330

330

330

330

390

390

390

390

390

390

5 Wire

430

430

430

430

430

430

430

430

430

430

430

430

510

510

510

510

510

510

N

60

60

60

60

70

80

90

110

125

155

170

190

230

260

280

432

522

562

Copper busbar Aluminium busbar

Table1-13 Table1-14

Fig1-18

14

Page 17: Catalogue Wetown Busway Series

Wall flange

Note:

1. W indicates the width of busway while H

indicates the height;

2. A indicates the width of cutout while B

indicates the height;

3. W1 indicates the external width of ange

while H1 indicates the height;

4. W2 indicates the internal width of ange

while H2 indicates the height;

5. The ange is dimidiate;

6. Flange is necessary in both sides of the

cutout;

7. Flange is fixed against the wall with internal

expansion bolt.

RatedCurrent

(A)

100

160

200

250

400

500

630

800

1000

1250

1350

1600

2000

2300

2500

3150

3200

3800

4000

4500

5000

External dimension ofbuswayW×H

Cu

128×78

128×88

128×93

128×103

128×113

128×128

128×143

128×158

128×188

128×223

128×263

128×340

128×340

128×390

128×410

128×500

128×540

Al

128×88

128×88

128×88

128×88

128×98

128×108

128×118

128×138

128×153

128×183

128×198

128×218

128×258

128×288

128×308

128×460

128×550

128×590

Dimension of cutoutA×B(≥)

Cu

230×180

230×190

230×195

230×205

230×215

230×230

230×245

230×260

230×290

230×325

230×365

230×442

230×442

230×492

230×512

230×602

230×642

Al

230×190

230×190

230×190

230×190

230×200

230×210

230×220

230×240

230×255

230×285

230×300

230×320

230×360

230×390

230×410

230×562

230×652

230×692

External dimension of wallange

W1×H1(≥)

Cu

215×380

215×390

215×395

215×405

215×415

215×430

215×445

215×460

215×490

215×525

215×565

215×642

215×642

215×692

215×712

215×802

215×842

Al

215×390

215×390

215×390

215×390

215×400

215×410

215×420

215×440

215×455

215×485

215×500

215×520

215×560

215×590

215×610

215×762

215×852

215×892

Internal dimension of wallange

W2×H2(≥)

Cu

140×90

140×100

140×105

140×115

140×125

140×140

140×155

140×170

140×200

140×235

140×275

140×352

140×352

140×402

140×422

140×512

140×552

Al

140×100

140×100

140×100

140×100

140×110

140×120

140×130

140×150

140×165

140×195

140×210

140×230

140×270

140×300

140×320

140×472

140×562

140×602

Table1-15

Fig1-19

15

Page 18: Catalogue Wetown Busway Series

Expansion length is the transition section

compensating for thermal expansion, it is normally

set each 60m in linear distance.

This transition section is used for reducing

busbar size to the final load, it provides users

with more economic power transmission and

distribution method.

Transposition section is the transition parts used for changing phase sequence of the busbar; its min-

imum size is 1500mm. The phase sequence of both sides has to be provided by the customer.

Expansion length Reducer

Transposition section

Note:

All the dimensions provided are for standard products. Please contact our engineers for customized

products' dimensions.

Note: H2=H+70mm (H is busbar height)

Fig1-20 Fig1-21

Fig1-22

16

Page 19: Catalogue Wetown Busway Series

Bus plugLM bus plugs are used to apply electrical power directly to the load from the busway system. The

protection component in abus plug can be either a circuit breaker or fuse.

Circuit breaker bus plugs- Circuit breaker protection is available for a current between 16A~1000A.

- GE circuit breakers are provided as standard offering.

- 3-Pole or 4-Pole circuit breakers may be installed in the plug for load protection, including accessories

of circuit breakers such as rotary handles, shunt release, thermal magnetic release and leakage-current

protection module.

Fused bus plugsFused bus plugs are made specically per customer's project specications.

Please contact with our local sales ofce for ordering information.

- Unique fail-safe base pins: the plug is equipped with a positioning device that prevents incorrect

installations.

- Base lugs: all the lugs are silver-plated to improve their electrical conductivity.

Physical data of plug (LWH) mm

Note: The added 70mm is for the rotary handle installation space.

*For any nonstandard dimension ,please contact with us.

Operation mode

Manual operating mechanism

Rotary operating mechanism

Rated current (A)

100

160-250

400

630

800-1000

100

160-250

400

630

800-1000

Dimension of plug (L×W×H) mm

450×240×260

550×260×280

650×300×300

750×340×320

900×400×460

450×240×(300+70)

550×260×(320+70)

650×300×(340+70)

750×340×(360+70)

900×400×(500+70)

Table1-16

Fig1-23

17

Page 20: Catalogue Wetown Busway Series

LZ series compact busway

System introductionBased on the technology of LM and fully absorb-

ing the latest technology in today’s world, Wetown

devotes to R&D LZ series compact busway with 20

years of manufacturing experiences. LZ series com-

pact busway is of features such as novel structure,

beautiful shape, reliable performance, easy installation,

and economical cost. LZ busway with technology ad-

vanced in the world are widely applied in high buildings, intelligent buildings, industrial plants, hospitals and

other important projects.

Product features

Sandwich structure

·Conductors with smaller space with better heat dissipation and more time of running at lower temperature

·Compact structure with less chimney effect

·Width of 125mm with a smaller space occupation

·better capacity of current loading due to the special structure ,more convenient for installation

"Two-piece" enclosure structure

Traditional busbar enclosure is normally composed of four

parts, while "Two-piece" enclosure of LZ with overall structure has

the following advantages:

· Sandwich structure and "Two-piece" enclosure makes the overall

heat transmission with better heat dissipation and more current

carrying capacity.

· "Two-piece " enclosure with less duct entry to busway, isolated

protection rating up to IP66.

High-quality conductor

·Higher -purity copper conductor material, imported from Chile in South America.

·Silver-plated copper bar surface .more helpful to current loading capacity with less corrosion or resis-

tance.

Reliable insulation

DuPont polyester film as the insulating material

for LZ series busway, works well at B-130 ℃ .

Fire-resistant surface can meet the requirements of

UL 94 standards .

18

Page 21: Catalogue Wetown Busway Series

Light aluminum alloy enclosure

·The enclosure of LZ busway, with aluminum alloy profile, is of high mechnical strength and can be applied

in different environments.

·Aluminum alloy enclosure has passed 1000-hour salt spray test .

·The heat dissipation of aluminum alloy enclosure is much better than the normal steel enclosure.

·Aluminum alloy is of excellent conductivity performance with 50% grounding capacity.

· Aluminum alloy is made of weak magnetic material to decrease the effect of eddy current and hysteresis

loss.

Environment

·To obtain KEMA certification

·To adopt LSZH material in accordance with ROHS

·Recycling rate for all parts up to 95% to 98%

Automatic assembly

A new line of automatically self-piercing riveting production, BOLLHOFF, made in Germany, greatly

improving the efficiency and quality of assembly.

High compact and low reactance

It is the most compact and intensive busway which applies higher-quality busway with lower voltage

drop and less power loss.

Large capacity

Maximum current is up to 1600A .

Joint unit

·Single-bolt clamping mechanism promotes installation speed twice as fast as the more traditional connectors.

· To adopt double-headed bolt with torch control and indicator function. the indicator will fall off when the

torch value is up to the specified value by using 19mm normal torque when installation.

·To Fasten the joint with single bolts and bowl washers helps to disperse the pressure in the contact surface.

·Conductive contact surface with silver or tin plating treatment provides more effective reducing of the contact

resistance.

·To add the embossing grooves on the edge of Insulation board helps increase the creepage distance

·Temperature Indicator reminds of the timely inspection because of the high temperature.

Unique anti-phase installation

Unique anti-phase installation method

can avoid the wrong installation.

19

Page 22: Catalogue Wetown Busway Series

Technology parameters

Current

(A)

400

630

800

1000

1250

1600

2000

2500

3150

4000

5000

6300

Numbers of per

phase

1

1

1

1

1

1

1

1

2

2

2

3

AC resistance per

m (mΩ)

0.132

0.099

0.072

0.056

0.044

0.032

0.025

0.018

0.016

0.012

0.009

0.008

Inductance per

m (mΩ)

0.036

0.031

0.026

0.023

0.020

0.016

0.014

0.010

0.009

0.007

0.004

0.002

Indepance per

m (mΩ)

0.137

0.104

0.076

0.061

0.048

0.036

0.028

0.021

0.018

0.014

0.010

0.008

Voltage drop (V/

m)

0.09

0.11

0.11

0.11

0.10

0.10

0.10

0.09

0.10

0.10

0.08

0.08

Voltage

loss

2.5%

2.9%

2.8%

2.8%

2.7%

2.6%

2.6%

2.4%

2.6%

2.6%

2.2%

2.2%

Current (A)

400

630

800

1000

1250

1600

2000

2500

3150

4000

5000

6300

Short-time

withstand

current

(KA)

30

50

65

100

150

Peak withstand

current (KA)

63

105

143

220

330

IP

IP42/IP54

IP65/IP66

without

plugs

IP42/IP54

with plugs

Rated

insulation

voltage(V)

1000

Rated working

voltage (V)

690

Rated inpulse

withstand voltage

(V)

8000

Table2-1

Table2-2

20

Page 23: Catalogue Wetown Busway Series

GM cast resin buswaySystem introduction

·To be appied in key projects where continuous power supply is needed.

·To be appied in public facilities where life and property safety is crucial.

·To be appied in tall buildings where fire-fighting is difficult.

·To be appied in hostile surroundings easy to be explosive or corrosive.

·To be appied in humid environment such as in the trench, under the water and etc.

Product features

·Break voltage: up to 5000V

·Air tight and watertight wall bushings

·Fire resistance:950℃ for 1.5 hrs (no toxic gas releases)

·Nonmetallic external, free of casing electro-erosion

·High short circuit withstand current

·High overloading performance

·Low voltage drop and power consumption

·High mechanism strength

·Maintenance free

·Non-chimney effect

·Full-insulated with cast resin

·Small external dimension

·All-weather environment

21

Page 24: Catalogue Wetown Busway Series

Comparisons

Technology parameters

Withstand voltage (V)

IP

Heat dissipation

Chimney effect

Dimension

Short-circuit withstand

Over loading performance

Working environment

Air-insulated busway

2500

IP30-54

Bad

Exist

Big

Good

Good

Indoor and dry site

Compact busway

3750

IP40-65

Good

None

Small

Good

Good

Indoor and dry site

GM series cast rasin busway

5000

IP68

Good

None

Small

Excellent

Excellent

All-weather

System common criteria

Current (A)

Rated working voltage (V)

Rated insulated voltage (V)

Frequency (HZ)

Wire

IP

Conductor/ Purity

Enclosure material

Enclosure colour

Installation

IEC60439-1~2,IEC60331,IEC60332,GB7251.1~2005,GB7251.2~2006

GB/T12666.6-1990,CECS170-2004,JB/T9639-1999

250~6300

400V/690V

690V/1000V

50

3 phase 4 wire(100%N)/ 3 phase 5 wire (50%PE)

IP68

Copper /99.95%

Epoxy resin

Light gray/light yellow

Horizontal installation/Vertical installation

Table3-1

Table3-2

22

Page 25: Catalogue Wetown Busway Series

Rated current(A)

250

400

630

800

1000

1250

1350

1600

1700

2000

2500

3150

4000

5000

6100

6300

Resistance

(mΩ/m)

0.220

0.157

0.096

0.069

0.051

0.038

0.036

0.030

0.027

0.025

0.019

0.015

0.012

0.008

0.006

0.005

Reactance

0.097

0.093

0.085

0.025

0.019

0.014

0.013

0.011

0.010

0.009

0.007

0.006

0.005

0.004

0.003

0.002

Impedance

0.240

0.182

0.128

0.073

0.054

0.040

0.038

0.031

0.029

0.027

0.020

0.016

0.013

0.009

0.007

0.005

Voltage drop(V/m)

0.1

0.1

0.1

0.1

0.11

0.11

0.11

0.11

0.11

0.11

0.11

0.12

0.12

0.13

0.14

0.15

Resistance, reactance, impedance and voltage drop (50Hz)

Dimension and weight

Rated current

(A)

250

400

630

800

1000

1100

1250

1350

1600

1700

2000

2500

3150

4000

5000

6100

6300

3 phase 4 wire

Width (mm)

107

107

107

107

107

107

107

107

107

107

107

107

190

190

190

292

292

Height (mm)

64

74

84

99

114

124

134

144

164

174

194

254

189

229

284

214

229

Weight (Kg)

15.28

18.85

22.42

27.77

33.13

37.59

40.26

43.83

50.95

54.53

61.67

83.08

101.33

125.43

158.58

183.43

197.88

3 phase 5 wire

Width (mm)

123

123

123

123

123

123

123

123

123

123

123

123

209

209

209

335

335

Height (mm)

64

74

84

99

114

124

134

144

164

174

194

254

189

229

284

214

229

Weight (Kg)

17.83

21.93

26.04

32.22

38.38

42.49

46.59

50.71

58.94

63.04

71.27

95.93

112.73

139.58

176.50

201.41

217.30

Table3-3

Table3-4

23

Page 26: Catalogue Wetown Busway Series

Straight length

L=1000,2000,3000,4000

Flanged end

1. Straight length

2. ClampⅠ

3. Bolt

4. ClampⅡ

5. Insulated outside board

6. Ccopper bar

7. Iusulated inside board

Physical data

24

Page 27: Catalogue Wetown Busway Series

Flatwise elbow

L1≥300, L2≥300

Edgewise elbow

L1≥400, L2≥400

Flatwise elbow offset

L1≥300, L2≥350, L3≥300

Edgewise elbow offset

L1≥400, L2≥450, L3≥400

Edgewise and flatwise elbow

L1≥300, L2≥400, L3≥400 L1≥300, L2≥400, L3≥400

25

Page 28: Catalogue Wetown Busway Series

Commutation unit

L =590 B =350 H =W+185(W is the width of copper bar )' ' '

Edgewise elbow tee

L1≥400, L2≥400, L3≥400

Flatwise elbow tee

L1≥550, L2≥550, L3≥550

Vertical spring support device

26

Page 29: Catalogue Wetown Busway Series

Wind power buswaySystem introduction

WLK、WLH series wind power busway (hereafter

refers to busduct) is applied for wind power unit

with 750kw or above generation capability.

·Air-insulated type;

·The environmental protection index of original materials can meet the requirements of ROHS;

·IP ratings up to IP54;

·Product usage life is over 40 years;

·Tightening bolt with low temperature resistant alloy material;

·Rated voltage: 690V Insulation voltage: 1000V;

·Better performance price ratio than wind power;

WLH series wind power busway(≤1000A)

WLK series wind power busway(>1000A)

27

Page 30: Catalogue Wetown Busway Series

Product features

1) Air insulation for wind power busway,wrapping with

resistance insulation mylar and insulation support for the

conductor to increase the insulation rating.

2) Wind power busway adopts al-alloy rectangle

conductor;

Compound plating for the conductor surface to improve

anti-oxidation;

Silver-plated connection reducing contact resistance

and improving conductive capability.

3) Wholly a-alloy and steel-aluminum hybrid

construction for the enclosure to improve heat

dissipation, also eliminate bow wave and guarantee

loop distribution.

4) Wind power busway surface coating adopting

imported static powder with 1000 salt fog test and 40

years life.

5) Wind power busway installed in the drum adopting

support with elastic performance to keep average load

and eliminate the positition error.

Special designed elastic part eliminating the vibration

caused by drum.

28

Page 31: Catalogue Wetown Busway Series

6) Each wind power busway unit adopting

modularization design. With the dimension of

drum to install the subsections sequently;

Special quick joint is offered to guarantee fast

connection.

7) Cable transfer box is applied for the quick

connection between wind power device and

cable.

8) Double headed torque limiting construction to

ensure fast assembly; Special bowl washer and

nut are free of Maintenance; Alloy material for

the bolt.

9) Compared with the cable, wild power busway

can be equipped with drum before delivery,

which saves time and expense.

29

Page 32: Catalogue Wetown Busway Series

Wind Power Alternative Plan

Comparison between busduct and cable

1

2

3

4

5

6

7

8

Currentcarryingcapability

DissipationPerformance

Occupyingarea

Overloadcapability

FireRetardant

Performance

Conductivity

Installation

Economiccalculation

Wind Power Busway

Large one-way current carrying: 500A~4000A

Good heat dissipation by conduction with goodheat convection

Small area occupation with small size

Excellent overload capability, heat resistance upto class B (130℃)

Excellent fire retardant capability

Excellent and reliable qualityLow loop loss, large anti-harmonic capability,

metal enclosure with wholly grounding

Adopt by installating sections sequently

Resonable price withhigh performance price ratio

Wind Power Cable

Limited single-core current carrying capability(<400A),multiple cables for each phase

Poor cable heat dissipation as wrapping withisulating material

Large area occupation with multiple cablestogther

Poor overload capability, heat resistance up toclass A(105℃)

Poor fire retardant capability

General QualityLarge loop loss and high voltage drop

Adopt integral hoisting with whole multiplecables and long lines

Low performance price ratio with specific cables

Table4-1

30

Page 33: Catalogue Wetown Busway Series

Technical parameters

Wind Type

Busduct Type

Standard

Environmental Temperature

IP Ratings

Rated Insulation voltage (AC,V)

Rated working voltage (AC,V)

Rated Working Current (A)

Rated Peak Tolerance Current (KV)

Rated Short-term Tolerance Current (KV)

Rated Frequency (Hz)

Air clearance

Creepage

distance

The high-point of temperature rise on connections of

busway (K)

The high-point of temperature rise on tangible

enclosures and covers (K)

Material group

Overvoltage categories

Pollution degree

Protect Type

Wire

Dielectric Strength (V/min)

Insulation Resistance(MΩ)

Between energized conductors

Between energized conductor and

enclosure

Between energized conductors

Between energized conductor and

enclosure

1.5/2MW Double Feeder Wind Power Unit

WLK

IEC60439-1、2;GB7251.1、2

-40℃~+50℃

IP31、IP40、IP54 (Optional)

1000/1500

690/1000

1300、1400、1800、2000 (Optional)

105~176

50~80

50~60

≥20

≥18

≥25

≥22

70

30

Ⅰ □, Ⅱ □, Ⅲ □, Ⅳ ■

Ⅰ ■, Ⅱ □, Ⅲ □

L1+L2+L3+PEN

3750/AC, 1min

≥20 (Phase-to-phase or phase-to-ground,1000MΩ)

WLH

690/1000

500、630、800 (Optional)

63~85

30~40

≥20

≥18

≥25

≥22

70

30

Table4-2

31

Page 34: Catalogue Wetown Busway Series

Medium voltage buswayProduct installation diagram

Product type and definition

/

Features cade

Cooling method

Rated voltage(kV)

Rated current(A)

Busway typeQLFM Series IPBGFM Series NPBGGM Series Segregated Endosed Bus

7, neutral cabinet

8, PT-LA Cabinet

9, generator circuit breaker

4, excitation transformer

5, start (standby) Transformer

6, generator outlet box

1, generator

2, the main transformer

3, station transformer

Q Partial coolingJ Forced coolingZ Natural cooling

Ⅴ Busway drying deviceⅣ Heat tracing device

ⅢMicro-pressure coexisted withfost saturation reactor

ⅡFast saturation reactorⅠMiero-pressure

NPB

Excitation transformerenclosed bus Excitation cublicle

AC excitation bus

DC excitation busBranch IPB

Main cirucuit IPB

32

Page 35: Catalogue Wetown Busway Series

QLFM series isolated phase bus

Main circuit Site branch circuit Generator connection structure

Site transformerconnection structure

Main transformerconnection structure

Excitation transformerconnection structure

PT-LA Cabinet connection structure CT assembly structure

ApplicationQLFM series Isolated phase bus (IPB for short) Isolated phase enclosed bus is a widely used

in Power Plant of 50MW and above, with branch leads to loops, and plant high-current loop

transmission device.

33

Page 36: Catalogue Wetown Busway Series

Product features

1.Produce all the company's style from the phase enclosed bus shell and the conductor are used welded

aluminum rolling conductor support insulator was inverted "Y"-type arrangement is conducive to improving the

insulator by the force status, bus structure, good stability.

2.Bus conductor with its mechanical protection, which can effectively remove moisture, dust and foreign

objects due to earth fault; sub-phase closed structure to avoid the occurrence of inter-phase short circuit.

3.Bus conductors conductive shell when the value will be generated in the opposite direction with the

conductor current is aost equal to the induced current, the magnetic field generated by the current induced

magnetic fields cancel each other out with the conductor, making the remainder of the magnetic field outside

the shell greatly reduced, so that bus around the steel or reinforced concrete is aost non-existent heat loss or

temperature rise.

4.Bus and the device interface end with disc insulator (SMC suppressed) closed up to IP54 protection

grade is closed over the internal bus can be used to make micro-pressure run, we can dispel this moisture,

dust, etc., preventing insulator Gel .

5.All with type isolated phase enclosed bus inside the shell in the same phase (including the branch

circuit) along the length direction of all the connectivity, all in the bus terminal by short-circuit boards will be

connected into a complete shell of each phase of electrical pathways, so that bus Shell basically at the other

potentials, grounding greatly simplified.

6.When the bus line length of 20 - 30m, or set the case in the underlying settlement at bellows

expansion joint, enabling horizontal and vertical degrees of freedom adjustment in both directions, not only to

meet the bus due to thermal expansion and contraction caused by stretching requirements, you can also right

because the error caused by foundation settlement to compensate.

7.At the junction with the equipment, busbar installation of insulating rubber bellows shell in order to

achieve electrical isolation, to avoid the circulation of the equipment bus shell impacts; internal conductor

connections are using copper compiled soft-link to eliminate the vibration generated when equipment

operation the impact on the bus.

8.Bus interface and equipment at current transformer according to need to set up, easy to measure and

protection.

Through-wall sealing and expansion joint structure Removable expansion joint structure

34

Page 37: Catalogue Wetown Busway Series

Technology parameters

Rated voltagerange(kV)

≤24

≤24

≤24

≤24

≤24

≤24

≤24

≤24

≤24

≤35

Rated current range(A)

≤2000

≤2500

≤4500

5000~8000

8000~9000

9000~10000

10000~14000

20000~24000

24000~26000

27000~30000

Insulationratings(kV)

75/150

75/150

75/150

75/150

75/150

75/150

75/150

75/150

75/150

100/185

Dimesnsions(mm)

Enciosure

Φ650

Φ700

Φ750

Φ750

Φ850

Φ900

Φ1050

Φ1450

Φ1500

Φ1650

Conduct

Φ150

Φ150

Φ200

Φ300

Φ350

Φ400

Φ500

Φ900

Φ950

Φ1000

Distance between phases(S)

≥900

≥950

≥1000

≥1000

≥1100

≥1150

≥1300

≥1800

≥1900

≥2000

Height(H)

490

515

540

540

590

615

690

890

915

990

Weight(Kg/m)

213

222

252

283

316

367

480

845

890

980

Mounting diagram of bus

Table5-1

35

Page 38: Catalogue Wetown Busway Series

IPB applied in project

Scope of Supply

According to user needs, wetown can provide the following equipment and accessories:

1.Away from the phase enclosed bus: From the generator terminal qualifying start to the main transformer

low voltage side leads to the main circuit bus terminal; self-loop leads to the station transformer high-voltage

side of the excitation transformer and voltage transformer, lightning arrester cabinets, excitation change

cabinets, load switch cabinet and other branch circuits.

2.From the phase enclosed bus ancillary equipment cabinets: voltage transformer cabinet, arrester

cabinets, neutral grounding cabinets, counters excitation changes, load switch cabinet and so on.

3.Busbar current transformer.

4.Measuring hydrogen and hydrogen emission devices.

5.Intelligent micro-pressure devices, hot air maintenance device or air-drying devices, electrical heating

device, silica gel dehumidifying unit ventilator.

6.On-line or portable infrared temperature measurement devices, platinum resistance temperature device.

7.Install hot-dip zinc steel structure.

8.Welding machine, welding wire and so on.

9.Air-cooled unit.

36

Page 39: Catalogue Wetown Busway Series

GFM series non-segregated phase bus

GFM series non-segregated phase bus(NPB for shart) for AC 50 ~ 60Hz, voltage 3.6 ~ 40.5kV, rated

current of 1000 ~ 6800A in the high-voltage transmission system.

Its main applications:

1. Generators and transformers between the electrical

connection;

2. Transformer and high voltage electrical connection

between the power distribution cabinet;

3. AC main exciter with the electrical connection

between the rectifier cabinet

4. Excitation switchgear and motor rotor slip rings for

electrical connection;

5. Other high-voltage equipment, electrical connection between the main circuit.

A total of box plants Bus Application Preparation of variable loop of the Kai box Bus

Features

1.The series busbar has an excellent resistance to short-circuit performance, due to a weak magnetic

aluminum or steel shell of protection, which can effectively reduced the loading of structure of swirl or

circulation caused by heat, lower bus shell temperature, reducing power consumption, increased carrying

capacity and reduce short-circuit power.

Applications

37

Page 40: Catalogue Wetown Busway Series

2.This series of advanced bus structures, installation and maintenance holes may be placed in the top or

bottom of busbar, for high-current indoor busbar in the shell on both sides and bottom may be equipped with

ventilation shutters, in order to enhance heat dissipation and lower temperature rise.

3.When the bus line lengths up to 20 ~ 30m, the Bus expansion joint to meet the set causes thermal

expansion and contraction due to temperature, Can also be caused by the foundation settlement to

compensate for the error.

4.Equipment operation in order to eliminate the vibration generated when the impact on the bus, bus

connections and equipment are prepared using copper soft connection, and the shell was inserted between

the rubber pad to absorb shock; for the bus body, can be installed in the system damping device, for

insulators and conductors to achieve flexible support, can avoid mechanical vibrations produced by the device

and the seismic waves caused by damage to the enclosed bus.

5.Bus depends mainly on thermal radiation heat, in order to enhance heat dissipation effect, in the bus

outside the light gray paint surface coating to reduce the absorption of visible light; in bus black inner surface

of spray paint to enhance the internal heat of the shell of radiation, while preventing the corona .

6.In order to avoid the winter indoor and outdoor temperature difference caused by condensing

phenomena, wearing a cut off wall is set at installation, so that outdoor and indoor bus completely isolated.

7.In order to improve bus permission to run temperature rise to prevent the electrochemical corrosion of

coastal open space, as well as serious air on the joints electrolytic corrosion and reduce contact resistance, all

the joints are used silver-plated treatment, to allow the temperature rise of up to 65k, much higher than the

work of when the actual temperature.

8.In order to avoid the bus self-vibration frequency of resonance frequency range (for a single bus of its

resonance frequency range of 35 ~ 135Hz), and to act on the bus on the electric power decreases, preferred

insulator models, specifications and strength grade, and reasonably set the span between the insulators.

9.In order to monitor the temperature of the removable connector, in transformers, generators and power

distribution equipment and busbar connections can be set sealed observation window, through the showing

warm patch or far-infrared temperature measurement device to directly measure the temperature, and the

supporting intelligent on-line monitoring busbar systems can be real-time monitoring operation of the system,

greatly facilitated the work of operating personnel of the inspection and maintenance to improve the safe

operation of the closed busbar level.

38

Page 41: Catalogue Wetown Busway Series

System common criteria

Rated voltage(kV)

Rated insulated voltage(kV)

Rated current(A)

1000

1600

2000

2500

3000

3500

4000

4500

IEC364-5-54,GB/T8349-2000、JB/T9639-1999

3.15

25/40

Dimension(W×H)(mm)

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

6.3

32/60

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

10.5

42/75

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Table6-1Note:Groove profile can be applied in NPB over 4000A.

Technology parameters

Ⅰ Ⅱ

39

Page 42: Catalogue Wetown Busway Series

Bus fixed-form sketch

AC and DC excitation NPB

Rated voltage(V)

Rated power frequencywithstand voltage(kV)

Rated current(A)

AC Excitation NPB

DC Excitation NPB

400~2250

2500~3250

3500~6300

5000~6300

400~2250

2500~3250

3500~6300

5000~6300

380

2.5

Dimension(W×H)(mm)

copper bar

550×400

650×400

700×500

450×400

500×400

600×500

aluminum bar

550×400

650×400

700×500

450×400

500×400

600×500

1000

4.2

copper bar

650×400

750×400

800×500

550×400

600×400

700×500

aluminum bar

650×400

750×400

800×500

550×400

600×400

700×500

1500

5.4

copper bar

700×400

800×400

900×500

500×400

650×400

800×500

aluminum bar

700×400

800×400

900×500

500×400

650×400

800×500

Table6-2

AC excitation NPB DC excitation NPB

Enbedded part

40

Page 43: Catalogue Wetown Busway Series

System common criteria

Rated voltage(kV)

Rated insulated voltage(kV)

Rated current(A)

1000

1600

2000

2500

3000

3500

4000

4500

IEC364-5-54,GB/T8349-2000、JB/T9639-1999

3.15

25/40

Dimension(W×H)(mm)

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

Ⅰ800×500Ⅱ1000×440

6.3

32/60

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

10.5

42/75

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Ⅰ1200×560Ⅱ1400×500

Table6-3

GGM series segregated enclosed bus

GGM series segregated enclosed bus is a current up to 4500A, voltage up to 10.5kV products, the three

phases are separated individually to form three separate space, resulting in a smaller external magnetic field,

but also to avoid the white short-circuit, other Electrical boxes were closed with the GFM-based bus.

Main technical parameters and dimensions

Ⅰ Ⅱ

41

Page 44: Catalogue Wetown Busway Series

牌号

Cu+Ag

T1

≥99.95

T2

≥99.90

TU1

≥99.97

TU2

≥99.95

a

b

3~20

15~110

Chemical composition of copper bar, shaped copper and

copper rod is in accordance with GB/T5231-2001 standard.

The main ingredient table(%)

1.Cross-section shown in Figures:

2. Dimension scope

Copper bar

Copper bar

42

Page 45: Catalogue Wetown Busway Series

1. Cross-section shown in figures:

2. Dimension scope:

3. Standard:

Products is in accordance with YS/T615-2006 standard or

customer's requirements.

1. Cross-section shown in figures:

2. Standard:

The dimension tolerances, chemical specialty and electrical

capability can be in accordance with customer's requirements.

Shaped copper

Copper rod

Round

Φ6~Φ70

Square, Rectang & Hexgon

Diagonal≤70

43

Page 46: Catalogue Wetown Busway Series