Catalogo Prodotti FIP Insulators
-
Upload
roberto-mira-dercole -
Category
Documents
-
view
343 -
download
10
description
Transcript of Catalogo Prodotti FIP Insulators
CATALOGO - CATALOGUE
INDICE - INDEX
PRESENTAZIONE - PRESENTATION ……………………………………………………………………………….….. 5 -12
PRESENTAZIONE DELL’AZIENDA ....................................................................................................... 5
PRESENTATION OF THE COMPANY ....................................................................................................... 5
CONTATTI ........................................................................................................................................................ 6
CONTACTS ........................................................................................................................................................ 6
CERTIFICAZIONI ............................................................................................................................................. 7
CERTIFICATIONS ............................................................................................................................................. 7
FOTOGRAFIE DELL’AZIENDA .................................................................................................................... 8
PICTURES OF THE COMPANY ………………………………………………………………………………………………………. 8
PRODUZIONE ……………………………………………….………………………………………………………………………………. 9
PRODUCTION ……………………………………………………………………………………………………………………………….. 9
NORME DI RIFERIMENTO – MAIN STANDARDS ....................................................................... 13 - 21
CATALOGO ISOLATORI – INSULATORS CATALOGUE .......................................................... 23 -121
MEDIA TENSIONE - ISOLATORI PORTANTI PER INTERNO CON ARMATURE INTERNE ........... 23 - 27
MEDIUM VOLTAGE - INDOOR POST INSULATORS WITH INTERNAL FITTINGS …………….………. 23 - 27
MEDIA TENSIONE - ISOLATORI PORTANTI PER ESTERNO CON ARMATURE INTERNE ............. 29 - 32
MEDIUM VOLTAGE - OUTDOOR POST INSULATORS WITH INTERNAL FITTINGS ……..…………. 29 - 32
MEDIA TENSIONE - ISOLATORI PORTANTI PER ESTERNO A NUCLEO PIENO ............................ 33 - 64
MEDIUM VOLTAGE - OUTDOOR POST INSULATORS IEC TYPE SOLID CORE ………………………… 33 - 64
- BIL 75 kV - 400/1250 daN ............................................................................................................................................... 33 - 35
- BIL 95 kV - 400/1250 daN ................................................................................................................................................ 37 - 39
- BIL 125 kV - 400/1250 daN ............................................................................................................................................... 41 - 43
- BIL 150 kV - 400/1250 daN ............................................................................................................................................... 45 - 47
- BIL 170 kV - 400/1250 daN ............................................................................................................................................... 49 - 52
- BIL 200 kV - 400/1250 daN ............................................................................................................................................... 53 - 56
- BIL 250 kV - 400/1250 daN ............................................................................................................................................... 57 - 60
- BIL 325 kV - 400/1600 daN ............................................................................................................................................... 61 - 64
ALTA TENSIONE - ISOLATORI PORTANTI PER ESTERNO A NUCLEO PIENO ................................ 65 -104
HIGH VOLTAGE - OUTDOOR POST INSULATORS IEC TYPE SOLID CORE ……………………………. 65 -104
- BIL 450 kV - 400/2000 daN ............................................................................................................................................. 65 - 69
- BIL 550 kV - 400/2000 daN ............................................................................................................................................. 71 - 75
- BIL 650 kV - 400/2000 daN ............................................................................................................................................. 77 - 81
- BIL 750 kV - 400/2000 daN ............................................................................................................................................. 83 - 87
- BIL 950 kV - 400/1250 daN ............................................................................................................................................. 89 - 92
- BIL 1050 kV - 400/1250 daN ............................................................................................................................................. 93 - 96
- BIL 1550 kV - 400/1600 daN ............................................................................................................................................. 97 -100
ALTA TENSIONE - COLONNINI DI MANOVRA ...................................................................................... 101 -104
HIGH VOLTAGE - OPERATING INSULATORS .…………………….....……………….………………………………… 101-104
MEDIA TENSIONE - ISOLATORI PASSANTI ……………………....…………………………………………………………..105-113
MEDIUM VOLTAGE - BUSHING INSULATORS …………………………….………………………………………………105-113
MEDIA TENSIONE - ISOLATORI PASSANTI PER CONDENSATORI …………………..……………………......115-120
MEDIUM VOLTAGE - HERMETIC BUSHINGS FOR CAPACITORS …………….……………………………….115-120
5TRADIZIONE E INNOVAZIONE
TRADITION AND INNOVATION
PR
ESE
NT
AZ
ION
E -
PR
ESE
NT
AT
ION
Grazie all’esperienza acquisita fin dal 1919, data della sua
fondazione, la F.I.P. s.p.a. - Fabbrica Isolatori Porcellana
può vantare una posizione di prestigio nel settore
elettroceramico italiano ed estero.
Le crescenti esigenze della clientela unite all’evoluzione
tecnologica hanno sempre incentivato la società a
sviluppare impianti e controlli di qualità in linea con le
nuove esigenze del settore.
I continui e frequenti investimenti uniti ad una esperienza
pluridecennale hanno reso la F.I.P. una fabbrica moderna,
dinamica e in costante sviluppo che tende a confermare e
migliorare le qualità del proprio prodotto.
Questa è l’immagine della nostra azienda: tradizione,
continuità, conoscenza tecnica ed evoluzione che viene
messa quotidianamente a disposizione dei propri clienti.
F.I.P. s.p.a. - Fabbrica Isolatori Porcellana, founded in
1919, boast a prestige position and four generations of
experience in the electroceramic field.
Customers’ growing needs added to technological
evolution have long encouraged the company to develop
machinery and quality control that are in line with the
new demands in the field.
Continual and frequent investments together with
decades of experience and reliability have made for an up
to date, dynamic factory that is always engaged in steady
development to both confirm and improve the quality of
its products.
This is the F.I.P. image: tradition, continuity, technical
know-how and evolution, placed daily at both regular
and prospective customers’ disposal.
6CONTATTI
CONTACTS
PR
ESE
NT
AZ
ION
E -
PR
ESE
NT
AT
ION
F.I.P. s.p.a.
Fabbrica Isolatori Porcellana
Via Novara 171
28078 Romagnano Sesia (No), ITALY
Tel.: +39 0163 824811
Fax: +39 0163 824831
Email: [email protected]
Web: http://www.fipinsulators.it
7CERTIFICAZIONI
CERTIFICATION
PR
ESE
NT
AZ
ION
E -
PR
ESE
NT
AT
ION
La qualità dei propri prodotti
dei processi di fabbricazione e
l’attenzione ai clienti sono
sempre stati un punto fermo
delle politiche aziendali di
F.I.P. s.p.a che ha ottenuto la
certificazione ISO 9001 dal
1996.
F.I.P. quality system has been
certified according to
standards ISO 9001 since
1996.
8
Filtropressatura - Filterpressing Reparto Trafile – Extruding Department
Gruppo Estrusori 750 mm – 750 mm Extruders Tornitura – Turning
Tornio Verticale – Turning Machine Tornio per Involucri – Lathe for Hollow Insulators
L’AZIENDA
THE FACTORY
PR
ESE
NT
AZ
ION
E -
PR
ESE
NT
AT
ION
9L’AZIENDA
THE FACTORY
PR
ESE
NT
AZ
ION
E -
PR
ESE
NT
AT
ION
Smaltatura – Glazing Machine
Forni – Shuttle Kilns
Sala Prove Meccaniche - Mechanical Lab
Tornio Automatico– Automatic Turning Machine
Smaltatura – Glazing Machine
Assemblaggio – Assembling Machine
10PRODUZIONE
PRODUCTION
INF
OR
MA
ZIO
NI T
EC
NIC
HE
-T
EC
HN
ICA
L IN
FO
RM
AT
ION
ISOLATORI PORTANTI• isolatori per interno
• isolatori per esterno con armature
interne
• isolatori a fusto pieno M.T. e A.T.
• colonnini di manovra per sezionatori
POST INSULATORS• indoor post insulators
• outdoor post insulators with internal
fittings
• M.V. and H.V. solid core station post
insulators
• operating insulators
LINE INSULATORS• railway insulators
• line post insulators
• long rod insulators
• spool and shackle insulators
• strain insulators
• insulators for spark gaps
• pin type insulators
ISOLATORI PASSANTI• isolatori per terminali di cavo
M.T. e A.T.
• isolatori passamuro
• passanti per condensatori
• isolatori per scaricatori
• isolatori per interruttori
• isolatori per trasformatori
• involucri isolanti A.T.
BUSHING INSULATORS• M.V. and H.V. cable terminal
insulators
• wall and roof insulators
• hermetic bushings for capacitors
• insulators for lightning arresters
• insulators for switchgears
• insulators for transformers
• H.V. hollow insulators
La nostra produzione standard comprende:
Our standard production includes:
ISOLATORI PER LINEA• isolatori per ferrovia
• isolatori portanti a fusto pieno
• isolatori long rod
• isolatori per ammarraggio
• isolatori per tiranti
• isolatori per spinterometri
• isolatori a perno
Una delle principali caratteristiche di F.I.P è
quella di lavorare su disegno del cliente.
Il nostro ufficio tecnico è sempre a
disposizione per studiare nuove soluzioni
sia che si tratti di modifiche ai prodotti
standard rappresentati in questo catalogo
sia che si tratti dello sviluppo e della
progettazione di nuovi modelli per
soddisfare il più possibile ogni esigenza dei
nostri clienti.
Per qualsiasi richiesta quindi non esitate a
contattarci.
One of our main features is working
according to customers’ drawing.
Our technical department is at your
disposal to develop new solutions and
meet your requirements for both
changes to the standard products of this
catalogue and development of a totally
new project.
Contact us for any request.
11
SMALTI - GLAZES
Le porcellane possono essere fornite con i seguenti colori:
Insulators can be supplied with the following glaze colours:
PROFILI – SHED PROFILES
In accordo con la norma i profili possibili sono:
According to the standard the possible shed profiles are:
aletta piatta
plain shed
aletta piatta alternata
alternating plain shed
aletta normale
standard shed
aletta nervata
under rib shed
aletta normale alternata
alternating standard shed
Marrone
Brown
Grigio
Grey
Bianco
White
ASSEMBLAGGIO - ASSEMBLING
I cementi comunemente utilizzati per l’assemblaggio delle parti metalliche sono:
Cements used for the assembling of metal fittings are:
Cemento Portland – Portland Cement
Cemento a base di Zolfo – Sulphur Cement (per applicazioni al di sotto dei 90 °C – for applications below 90 °C )Cemento Alluminoso – Aluminous Cement (per applicazioni speciali – for special applications )Lega Stagno/Piombo – Tin/Lead Alloy (per applicazioni speciali – for special applications )
Abbiamo di recente messo a punto un nuovo sistema di assemblaggio meccanico, senza alcun tipo di cemento , per piccoli pezzi
per applicazioni speciali
We recently developped a new mechanical assembling system, without any cement, for small pieces for special applications.
PRODUZIONE
PRODUCTION
INF
OR
MA
ZIO
NI T
EC
NIC
HE
-T
EC
HN
ICA
L IN
FO
RM
AT
ION
NORMATIVE - STANDARDS
A seconda delle esigenze dei nostri clienti possiamo lavorare secondo norme IEC, ANSI, DIN, BS, ecc…
According to the customers’ needs we can work by different standards such as IEC, ANSI, DIN, BS, etc…
12
- SCIOGLITURA
- DISSOLVING
- PESATURA
- WEIGHTING- STOCCAGGIO MATERIE PRIME
- STORAGE OF RAW MATERIALS
- CONSEGNA MATERIE PRIME
- DELIVERY OF RAW MATERIALS
- SEPARAZIONE MAGNETICA
- MAGNETIC SEPARATION
- MACINAZIONE
- GRINDING
- CONTROLLI LABORATORIO
- LABORATORY CHECKS
- MISCELAZIONE
- MIXING
- FILTROPRESSATURA
- FILTER PRESSING
- TRAFILATURA
- EXTRUSION
- ESAME A VISTA
- VISUAL CHECK
- COTTURA
- FIRING
- PROVA AD ULTRASUONI
- ULTRASONIC TEST
- CONTROLLO DIMENSIONALE
- CHECK OF DIMENSIONS
- ASSEMBLAGGIO- ASSEMBLING
- PROVE ELETTRICHE
- ELECTRICAL TESTS
- SPEDIZIONE
- DELIVERY
- IMBALLAGGIO
- PACKING
- CONTROLLO DENSITA'
- DENSITY CONTROL
- PRE-ESSICCAZIONE
- DRYING
- TORNITURA
- TURNING
- SMALTATURA A SPRUZZO
- SPRAY GLAZING
- ESSICCAZIONE
- FINAL DRYING
- SMALTATURA AD IMMERSIONE
- DIP GLAZING
- ESAME A VISTA
- VISUAL CHECK
- TAGLIO E RETTIFICA
- CUTTING AND GRINDING
- TEST DI POROSITA'
- POROSITY TEST
- SEPARAZIONE MAGNETICA
- MAGNETIC SEPARATION
- CONTROLLI LABORATORIO
- LABORATORY CHECKS
- CONTROLLO DIMENSIONALE- CHECK OF DIMENSIONS
- PROVE TERMICHE- TEMPERATURE CYCLE TEST
- PROVE MECCANICHE
- MECHANICAL TESTS
- CONTROLLO DIMENSIONALE
- CHECK OF DIMENSIONS
- Argille
- Caolino
- Ossido di Alluminio
- Feldspato
- Clay
- Kaolin
- Aluminium oxide
- Feldspar
Materie prime – Raw materials
- ASSEMBLAGGIO
- ASSEMBLING
- CONTROLLO DIMENSIONALE
- CHECK OF DIMENSIONS
- PROVE TERMICHE
- TEMPERATURE CYCLE TEST
FASI DI LAVORAZIONE
WORKING PROCESS
CONTROLLI
CHECKS
MATERIE PRIME
RAW MATERIALS
STATO LIQUIDO
LIQUID STATE
STATO PLASTICO
PLASTIC STATE
STATO SOLIDO
SOLID STATE
PORCELLANA COTTA
FIRED PORCELAIN
SMALTO
GLAZE
CONTROLLI
CHECKS
PROCESSO DI LAVORAZIONE
PRODUCTION PROCESS
INF
OR
MA
ZIO
NI T
EC
NIC
HE
-T
EC
HN
ICA
L IN
FO
RM
AT
ION
NORME DI RIFERIMENTO
MAIN STANDARDS
14NORME DI RIFERIMENTO
MAIN STANDARDS
INF
OR
MA
ZIO
NI T
EC
NIC
HE
-T
EC
HN
ICA
L IN
FO
RM
AT
ION DESCRIZIONE
DESCRIPTIONCEI EN-IEC
Prove su isolatori passanti per tensione alternata superiore a 1000 V
Tests on bushings for alternating voltages above 1000 V36-2 60137
Prove su isolatori portanti per interno/esterno
Tests on indoor and outdoor post insulators36-6 60168
Prove su involucri isolanti
Tests on hollow insulators36-8 60233
Dimensioni degli isolatori portanti
Dimensions of post insulators- 60273
Caratteristiche degli elementi di catene di isolatori del tipo cappa e perno
Characteristics of strings insulator unit of the cap and pin type- 60305
Prove sugli isolatori di linea
Tests on overhead line insulators36-5 60383
Caratteristiche degli elementi di catene di isolatori del tipo a fusto lungo
Characteristics of string insulators units of the long rod type- 60433
Prove di radio-interferenza su isolatori A.T.:
Radio interference test on H.V. insulatorsS/483 60437
Prove e dimensioni di isolatori A.T. a corrente continua
Tests and dimensions of H.V. d.c. insulatorsS/473 60438
Prove di sovratensione a impulso di manovra per isolatori A.T.
Switching impulse tests on H.V. insulators36-7 60506
Prove in condizioni di inquinamento artificiale per isolatori A.T. a corrente alternata
Artificial pollution tests on H.V. insulators to be used on a.c. systemsS/487 60507
Prove di resistenza termomeccanica e meccanica su elementi di catene
Thermal-mechanical and mechanical performance tests on string insulator unitsS/563 60575
Regole di prelievo di campioni e d’accettazione quando si applica il metodo statistico
Sampling rules and acceptance criteria when applying statistical control methodsS/522 60591
Caratteristiche degli isolatori portanti di linea a nucleo pieno
Characteristics of line post insulators- 60720
Guida per la scelta di isolatori in condizioni di inquinamento ambientale
Guide for the selection of insulators in respect of polluted conditions- 60815
Coordinazione dell’isolamento
Insulation co-ordination- 6071
Specifica per materiali isolanti a base ceramica o vetro
Specification for ceramic and glass insulating materials- 60672
Norme di riferimento: EN – IEC 6071
Standards: EN-IEC 6071
15
Norme di riferimento: EN-IEC 60672 – 1/2/3 Standards: EN-IEC 60672 – 1/2/3
Gruppo
GroupC-100
Sottogruppo
Sub-group110 120 130
Po
rce
lla
ne
sil
ice
e
Sil
icio
us
po
rce
lain
s
Po
rce
lla
ne
all
um
ino
se
Re
sis
ten
za s
tan
da
rd
Alu
min
ou
sp
orc
ela
ins
Sta
nd
ard
str
en
gth
Po
rce
lla
ne
all
um
ino
se
Ele
va
ta r
esis
ten
za
Alu
min
ou
sp
orc
ela
ins
Hig
hstr
en
gth
Proprietà
Properties
Simboli
Symbols
Unità
Units
Al2O3
<30%
Al2O3
30÷50%
Al2O3
> 50%
Porosità apparente (aperta)
Apparent porosity (open)max Pa Volume % 0.0 0.0 0.0
Densità apparente
Bulk densitymin. δa g/cm3 2,2 2,3 2,5
Resistenza a flessione
Flexural strengthmin.
non smaltato
unglazedRf N/mm2 50 90 140
smaltato
glazedRf N/mm2 60 110 160
Modulo di elasticità minima
Modulus of elasticitymin. E GPa 60 70 100
Coefficiente medio di dilatazione lineare
Mean coefficient of linear expansion
α 20-100°C 10-6K-1 3-6 3-6 4-7
α 20-300°C 10-6K-1 3-6 3-6 5-7
α 20-600°C 10-6K-1 4-7 5-7 5-7
Capacità termica
Specific heat capacity20°-100°C cp J/kgK 750÷900 750÷900 800÷900
Conduttività termica
Thermal conductivity20°-100°C λ W/mK 1÷2,5 1,2÷2,6 1,5÷4,0
Resistenza alle variazioni di temperatura
Resistance to thermal shockmin. Δt K 150 150 150
Rigidità dielettrica
Electric strengthmin. Ed kV/mm 20 20 20
Tensione di tenuta
Withstand voltagemin. U kV 30 30 30
Permittività relativa
Relative permittivity48÷62 Hz εr 6÷7 6÷7 6÷7,5
Fattore di dissipazione a 20°C
Dissipation at 20°Cmax
48÷62 Hz tanδ 10-3 25 25 30
1 kHz tanδ 10-3
1 MHz tanδ 10-3 12 12 15
Resistività di volume in funzione della temperatura
Volume resistivity in terms of temperaturemin.
20°C ρv Ωcm 1013 1013 1013
200°C ρv Ωcm 108 108 108
600°C ρv Ωcm 104 104 104
Temperatura relativa ad una resisitività di volume
Temperature corresponding to a volume resistivitymin.
100 MΩcm tK100 °C 200 200 200
1 MΩcm tK1 °C 350 350 350
MATERIALI CERAMICI ISOLANTI USATI PER LA COSTRUZIONE DI
ISOLATORI
CERAMIC INSULATING MATERIALS USED FOR INSULATORS
PRODUCTION
INF
OR
MA
ZIO
NI T
EC
NIC
HE
-T
EC
HN
ICA
L IN
FO
RM
AT
ION
16LIVELLI DI ISOLAMENTO NORMALIZZATI
STANDARD INSULATION LEVELS
Norme di riferimento: EN – IEC 6071
Standards: EN-IEC 6071
MASSIMA TENSIONE DI ESERCIZIO
HIGHEST SYSTEM VOLTAGE (r.m.s.)
TENUTA DI TENSIONE SOTTO PIOGGIA
WET WITHSTAND VOLTAGE
TENSIONE DI TENUTA AD IMPULSO
LIGHTNING IMPULSE WITHSTAND VOLTAGE
kV (ef.) kV (ef.) kV (cresta)
3,6 10 40
7,2 20 60
12 28 75
17,5 38 95
24 50 125
36 70 170
52 95 250
72,5 140 325
123 185 450
145 230 550
170 275 650
245 325 750
360 850
395 950
460 1050
TENSIONE DI TENUTA AD IMPULSO DI MANOVRA 250/2500 uS (CRESTA)
SWITCHING IMPULSE WITHSTAND VOLTAGE 250/2500 uS (PEAK)
kV (ef.) kV (ef.)
300
750
850
850
950
1050
362
850
950
950
1050
1175
420
950
1050
1050
1175
1300
1425
525
1050
1175
1175
1300
1425
1550
765
1300
1425
1550
1425
1550
1800
1950
2100
2400
INF
OR
MA
ZIO
NI T
EC
NIC
HE
-T
EC
HN
ICA
L IN
FO
RM
AT
ION
17LIVELLI DI INQUINAMENTO
POLLUTION LEVELS
Livello di
inquinamento
Pollution level
Esempi di ambienti tipici
Examples of typical environments
Minima linea di fuga
specifica mm/kV
Minimum specific
creepage distance
mm/kV
I Basso
I Light
Aree senza industrie e con bassa densità di abitazioni dotate di impianti di riscaldamento
Aree con bassa densità di industrie o abitazioni ma soggette a frequenti venti e/o temporali
Zone agricole
Zone montuose
Tutte queste aree devono essere situate ad almeno 10/20 km dal mare e non devono essere esposte a venti
provenienti direttamente dal mare
Areas without industries and with low density of houses equipped with heating plants
Areas with low density of industries or houses but subjected to frequent winds and/or rainfall
Agricultural areas
Mountainous areas
All these areas shall be situated at least 10 to 20 km from the sea and shall not be exposed to winds directly
from the sea
16
II Medio
II Medium
Aree con industrie che non producono particolari scarichi inquinanti e/o con densità media di abitazioni
dotate di impianti di riscaldamento
Aree con alta densità di abitazione e/o industrie ma soggette a frequenti venti e/o temporali
Aree esposte a vento proveniente direttamente dal mare ma non così vicine alla costa
(distanti almeno parecchi chilometri)
Areas with industries not producing particularly polluting smoke and/or with average density of houses
equipped with heating plants
Areas with high density of houses and/or industries but subjected to frequent winds and/or rainfall
Areas exposed to winds from the sea but not too close to the coast (at least several kilometers distant)
20
III Alto
III Heavy
Aree con alta densità di industrie e sobborghi di grandi città con alta densità di impianti di riscaldamento
che producono inquinamento
Aree vicine al mare od in qualsiasi caso esposte a venti relativamente forti provenienti dal mare
Areas with high density of industries and suburbs of large cities with high density of heating plants
producing pollution
Areas close to the sea or in any case exposed to relatively strong winds from the sea
25
IV Molto alto
IV Very heavy
Aree generalmente di moderate estensioni, soggette a polvere conduttiva ed agli scarichi industriali che
producono inquinamento
Aree generalmente di moderate estensioni molto vicine alla costa ed esposte agli spruzzi del mare o a
venti molto forti ed inquinanti provenienti dal mare
Aree desertiche, caratterizzate dall’assenza di piogge per lunghi periodi, esposte a forti venti che portano
sale e sabbia e soggette a regolare condensazione
Areas generally of moderate extent, subjected to conductive dusts and to industrial smoke producing
particularly thick conductive deposits
Areas generally of moderate extent, very close to the coast and exposed to sea-spray or to very strong and
polluting winds from the sea
Desert areas, characterized by no rain for long periods, exposed to strong winds carrying sand and salt,
and subjected to regular condensation
31
I valori così ottenuti devono poi essere maggiorati di un fattore kD dipendente dal diametro medio Dm
The values of the creepage distance obtained must be increased by a factor kD which depends to the average diameter Dm
1)Alette normali
Regular sheds Dm =De + Di
2
2)Alette alternate
alternating shedsDm =
De1 + De2 + 2Di
4
Dm < 300 mm : kD = 1
300 ≤ Dm ≤ 500 mm : kD = 1,1
Dm > 500 mm : kD = 1,2
Norme di riferimento: EN-IEC 60815 – 6071-2 Standards: EN-IEC 60815 – 6071-2
INF
OR
MA
ZIO
NI T
EC
NIC
HE
-T
EC
HN
ICA
L IN
FO
RM
AT
ION
18TOLLERANZE DIMENSIONALI
DIMENSIONAL TOLERANCES
Parallelismo su isolatori assemblati
Parallelism on assembled insulators
Per H ≤ 1m : 0,5 mm
Per H > 1m : 0,5 x H mm (H in m)
A2
Sulla ceramica non lavorata
On unground porcelain
d ≤ 300: ± (0,04 d + 1,5) mm
d ≥ 300: ± (0,025 d + 6) mm
1
Eccentricità su isolatori assemblati
Eccentricity on assembled insulators
e ≤ 2 x (1 + H) mm (H in m)
B3
Freccia in assenza di carico
Static camber
F = (1,5 + 0,008H) mm (H in mm)C4
Deviazione angolare
Angular deviation
α ≤ ± 1°
5
Le tolleranze sul parallelismo sono riferite ad un diametro di 250 mm
Tolerances on the parallelism are related to a diameter of 250 mm
α
Linea di fuga - Creepage distance
Quando la linea di fuga è specificata come valore nominale, includendo un valore minimo nominale come
indicato nella IEC 60273
When the creepage distance is specified as a nominal value, including a minimum nominal value as given in
IEC 60273
± (0,04D+1,5)mm
Quando la linea di fuga è specificata come valore minimo non devono esserci tolleranze negative e la
tolleranza positiva deve essere:
When the creepage distance is specified as a minimal value, there shall be no negative tolerance and the
positive one shall be:
2x(0,04d+1,5)mm
6
Norme di riferimento: EN-IEC 60168 – 60273 / CEI 36-6Standards: EN-IEC 60168 – 60273 / CEI 36-6
INF
OR
MA
ZIO
NI T
EC
NIC
HE
-T
EC
HN
ICA
L IN
FO
RM
AT
ION
19INVOLUCRI ISOLANTI
HOLLOW INSULATORS
Tolleranza freccia: ≤1,5 mm + 0,8% dell’altezza quando il rapporto:
Tolerance of camber: : ≤1,5 mm + 0,8% of the height when the ratio:
Altezza (Height) Altezza (Height)< 6 ; ≥ 6 su accordo
Diametro massimo interno Diametro massimo interno to be agreed(Maximum inner diameter) (Maximum inner diameter)
Deviazione dalla circolarità dei diametri interno o esterno
Deviation from circularity of inner or outer diameter
Ovalizzazione massima ammissibile
Maximum deviation from roundness
Limite di tolleranza inferiore / Lower limit
Diametro nominale / Nominal diameter
Limite di tolleranza superiore / Upper limit
La tolleranza di ovalizzazione è compresa
nella tolleranza del diametro
The deviation from roundness is included
in the tolerance of the diameter
Tolleranze di spessore di parete
Tolerances of wall thickness
Spessore di pareteDimensione nominale “t”
Nominal wall thickness “t”
Tolleranze dispessore di pareteTolerances of wall
thickness
Differenza dispessore di parete
Difference of wall thickness
t < 70t max – t min
±2
x + y
2
x e y sono rispettivamente le tolleranze dei diametri d1 e d2x and y are resp. the tolerances of the diameters d1 and d2
tmax tmind1 ± x
d2 ± y
“t”
Norme di riferimento: EN-IEC 60233 Standards: EN-IEC 60233
INF
OR
MA
ZIO
NI T
EC
NIC
HE
-T
EC
HN
ICA
L IN
FO
RM
AT
ION
20CALCOLO DELLA RESISTENZA MECCANICA DELLA PORCELLANA
CALCULATION OF MECHANICAL STRENGTH OF PORCELAIN
FxHσ =
WFxH2
σ = W
FxHσ =
Wσ = LxP
π W= xD3
32
π W= xD3
32
π D4 - d4
W=32 D
D2 + d2
L=D2 - d2
Momento flettente in testa – Bending moment at the top metal fitting
Tutti gli isolatori portanti cilindrici devono poter resistere ai seguenti momenti minimi flettenti M applicati sulla parte
metallica superiore:
All cylindrical post insulators must be able to withstand to the following minimum bending moments M at the top
metal fitting:
per isolatori portanti da C4-60 fino al C20-650M = 0.5 P0H
for post insulators from C4-60 up to C20-650
per isolatori portanti da C2-750 fino al C10-2550M = 0.2 P0H
for post insulators from C2-750 up to C10-2550
Dove
P0 = carico minimo di rottura specificato
H = altezza totale
Where
P0 = minimum failing load
H = total height
Norme di riferimento: EN-IEC 60273 Standards: EN-IEC 60273
INF
OR
MA
ZIO
NI T
EC
NIC
HE
-T
EC
HN
ICA
L IN
FO
RM
AT
ION
21
COLORE – COLOUR- Approssimativamente quello prescritto dal disegno. Leggere variazioni non possono essere oggetto di rifiuto
(smalto più sottile o leggero)
- Approximately the colour specified on the drawing. Small variations shall not justify rejection
(thinner or lighter glaze)
DIFETTI DI SMALTO – GLAZE DEFECTS- Punti senza smalto, scheggiature, inclusioni nello smalto , puntinature.
- Spots without glaze, chips, inclusions in the glaze and pinholes
TOLLERANZE SUI DIFETTI – TOLERANCES ON DEFECTS-Si applicano a ciascun elemento di colonna, isolatore cavo e di linea.
-Are applied on each post insulator unit, bushing and line insulator.
AREA COMPLESSIVA DEI DIFETTI – TOTAL AREA OF GLAZE DEFECTS
D x FIEC 60168 CEI 36-6 100 + mm2
2000
D x LIEC 60233 CEI 36-8 100 + mm2
1000
D x FIEC 60383 CEI 36-5 100 + mm2
2000
AREA MASSIMA DI OGNI SINGOLO DIFETTO – MAXIMUM AREA OF ANY SINGLE GLAZE DEFECT
D x FIEC 60168 CEI 36-6 50 + mm2
20000
D x LIEC 60233 CEI 36-8 50 + mm2
10000
D x FIEC 60383 CEI 36-5 50 + mm2
20000
SUL FUSTO DELL’ ISOLATORE – ON THE INSULATOR CORE
- Mancanza di smalto ammissibile ≤ 25 mm2
- Spots without glaze shall not exceed 25 mm2
INCLUSIONI NELLO SMALTO – INCLUSION IN THE GLAZE
- Area complessiva ≤ 25 mm2
-Total area ≤ 25 mm2
SPORGENZA INCLUSIONI – INCLUSION PROTRUDE
- Massimo 2 mm
-2 mm maximum
PUNTINATURE – PINHOLES
-Su una superficie di 50x10 mm : numero massimo dei fori ≤ 15
-In an area of 50x10 mm : maximum number of pinholes ≤ 15
-Numero totale delle puntinature sull’ elemento di colonna: D x F- 50 x- Total number of pinholes on the post insulator unit: 1500
Diametro massimoMaximum diameter
Linea di fugaCreepage distance
AltezzaHeight
D =
F =
L =
TOLLERANZE SUI DIFETTI DI SMALTO
TOLERANCES ON GLAZE DEFECTS
Norme di riferimento: EN-IEC 60168 - 60233 - 60383 Standards: EN-IEC 60168 - 60233 - 60383
INF
OR
MA
ZIO
NI T
EC
NIC
HE
-T
EC
HN
ICA
L IN
FO
RM
AT
ION
MEDIA TENSIONE - MEDIUM VOLTAGE
BIL 60 325 kV - 200/1600 daN
ISOLATORI PORTANTI PER INTERNOCON ARMATURE INTERNE
INDOOR POST INSULATORSWITH INTERNAL FITTINGS
24
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER INTERNOINDOOR POST INSULATORSserie IEC - armature interne - IEC 60273IEC type - internal fittings
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
IEC CN55 CN56 CN57
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 45 55 70height
diametro porcellanaD mm 60 60 75
porcelain diameter
filettatura armatured1 mm
M8
M8
M10 M12
M10 M12
M12
M12metal fittings thread
profondità forih1 mm 15 20 26
holes deep
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 1 3 6operating voltage
tensione di provakV 15 20 30
test voltage
tensione di arco a seccokV 20 30 40
power frequency dry flashover voltage
tensione di perforazione in oliokV 70 90 110
puncture voltage in oil
Colore smalto Glaze colour
25
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER INTERNOINDOOR POST INSULATORS
serie IEC - armature interne - IEC 60273IEC type - internal fittings
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 60 75 kV - 200/1600 daN
IEC J2-60 J4-60 J8-60
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 95±1 95±1 95±1height
diametro porcellanaD mm 60 75 85
porcelain diameter
diametro armatura di testa / filettaturad mm
35 50 50
top metal fitting diameter / thread M12 M12 M16
diametro armatura di base / filettaturad1 mm
35 60 60
bottom metal fitting diameter / thread M12 M12 M16
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 6/7,2 6/7,2 6/7,2operating voltage
tensione di tenuta a seccokV 28 28 28
dry withstand voltage
tensione di tenuta ad impulso a seccokV 60 60 60
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
P0 daN 200 400 800cantilever failing load
carico di rottura a flessioneP50 daN 130 260 520
cantilever failing load
IEC J2-75 J4-75 J8-75 J16-75
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 130±1 130±1 130±1 130±1height
diametro porcellanaD mm 60 75 100 125
porcelain diameter
diametro armatura di testa / filettaturad mm
35 50 60 90
top metal fitting diameter / thread M12 M12 M16 M16
diametro armatura di base / filettaturad1 mm
45 60 80 115
bottom metal fitting diameter / thread M12 M16 M16 M16
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 10/12 10/12 10/12 10/12operating voltage
tensione di tenuta a seccokV 38 38 38 38
dry withstand voltage
tensione di tenuta ad impulso a seccokV 75 75 75 75
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
P0 daN 200 400 800 1600cantilever failing load
carico di rottura a flessioneP50 daN 145 290 580 1160
cantilever failing load
Colore smalto Glaze colour
26
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
BIL 95 125 kV - 200/1600 daN
ISOLATORI PORTANTI PER INTERNOINDOOR POST INSULATORSserie IEC - armature interne - IEC 60273IEC type - internal fittings
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
IEC J2-95 J4-95 J8-95 J16-95
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 175±1 175±1 175±1 175±1height
diametro porcellanaD mm 60 75 100 130
porcelain diameter
diametro armatura di testa / filettaturad mm
35 50 60 90
top metal fitting diameter / thread M12 M12 M16 M16
diametro armatura di base / filettaturad1 mm
45 60 80 115
bottom metal fitting diameter / thread M12 M16 M20 M20
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 15/17,5 15/17,5 15/17,5 15/17,5operating voltage
tensione di tenuta a seccokV 50 50 50 50
dry withstand voltage
tensione di tenuta ad impulso a seccokV 95 95 95 95
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
P0 daN 200 400 800 1600cantilever failing load
carico di rottura a flessioneP50 daN 155 310 620 1250
cantilever failing load
IEC J2-125 J4-125 J8-125 J16-125
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 210±1 210±1 210±1 210±1height
diametro porcellanaD mm 75 85 125 140
porcelain diameter
diametro armatura di testa / filettaturad mm
35 55 70 95
top metal fitting diameter / thread M12 M12 M16 M16
diametro armatura di base / filettaturad1 mm
45 70 95 115
bottom metal fitting diameter / thread M12 M16 M20 M20
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 20/24 20/24 20/24 20/24operating voltage
tensione di tenuta a seccokV 50 50 50 50
dry withstand voltage
tensione di tenuta ad impulso a seccokV 125 125 125 125
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
P0 daN 200 400 800 1600cantilever failing load
carico di rottura a flessioneP50 daN 160 320 645 1300
cantilever failing load
Colore smalto Glaze colour
27
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
BIL 170 325 kV - 200/1600 daN
ISOLATORI PORTANTI PER INTERNOINDOOR POST INSULATORS
serie IEC - armature interne - IEC 60273IEC type - internal fittings
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
Colore smalto Glaze colour
IEC J2-170 J4-170 J8-170 J16-170
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 300±1 300±1 300±1 300±1height
diametro porcellanaD mm 75 100 125 160
porcelain diameter
diametro armatura di testa / filettaturad mm
35 55 70 100
top metal fitting diameter / thread M12 M12 M16 M16
diametro armatura di base / filettaturad1 mm
45 80 115 115
bottom metal fitting diameter / thread M12 M16 M24 M24
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 30/36 30/36 30/36 30/36operating voltage
tensione di tenuta a seccokV 70 70 70 70
dry withstand voltage
tensione di tenuta ad impulso a seccokV 170 170 170 170
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
P0 daN 200 400 800 1600cantilever failing load
carico di rottura a flessioneP50 daN 170 340 685 1370
cantilever failing load
IEC J4-250 J8-250 J4-325 J8-325
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 500±1 500±1 620±1 620±1height
diametro porcellanaD mm 125 140 125 160
porcelain diameter
diametro armatura di testa / filettaturad mm
70 80 70 80
top metal fitting diameter / thread M12 M16 M12 M16
diametro armatura di base / filettaturad1 mm
115 115 115 115
bottom metal fitting diameter / thread M16 M24 M20 M24
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 45/52 45/52 66/72,5 66/72,5operating voltage
tensione di tenuta a seccokV 95 95 140 140
dry withstand voltage
tensione di tenuta ad impulso a seccokV 250 250 325 325
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
P0 daN 400 800 400 800cantilever failing load
carico di rottura a flessioneP50 daN 360 725 370 740
cantilever failing load
MEDIA TENSIONE - MEDIUM VOLTAGE
BIL 60 170 kV - 400/1600 daN
ISOLATORI PORTANTI PER ESTERNOCON ARMATURE INTERNE
OUTDOOR POST INSULATORSWITH INTERNAL FITTINGS
30
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
BIL 60 75 kV - 400/1600 daN
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - armature interne - IEC 60273IEC type - internal fittings
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
IEC H4-60 H8-60 H16-60
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 95±1 95±1 95±1height
linea di fuga minimamm 230 230 230
minimum creepage distance
diametro massimo porcellanaD mm 125 152 185
porcelain max diameter
filettatura armatura superioreM16 M16 M20
top metal fitting thread
filettatura armatura inferioreM16 M16 M20
bottom metal fitting thread
diametro armatura di based mm 60 60 115
bottom metal fitting diameter
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 7,2 7,2 7,2operating voltage
tensione di tenuta sotto pioggiakV 20 20 20
wet withstand voltage
tensione di tenuta ad impulso a seccokV 60 60 60
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 800 1600cantilever failing load
IEC H4-75 H8-75 H16-75
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 130±1 130±1 130±1height
linea di fuga minimamm 290 240 240
minimum creepage distance
diametro massimo porcellanaD mm 125 152 177
porcelain max diameter
filettatura armatura superioreM16 M20 M20
top metal fitting thread
filettatura armatura inferioreM16 M20 M20
bottom metal fitting thread
diametro armatura di based mm 60 80 115
bottom metal fitting diameter
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 12 12 12operating voltage
tensione di tenuta sotto pioggiakV 28 28 28
wet withstand voltage
tensione di tenuta ad impulso a seccokV 75 75 75
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 800 1600cantilever failing load
Colore smalto Glaze colour
31
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - armature interne - IEC 60273
IEC type - internal fittings
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 95 125 kV – 400/1600 daN
Colore smalto Glaze colour
IEC H4-95 H8-95 H16-95
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 175±1 175±1 175±1height
linea di fuga minimamm 380 380 380
minimum creepage distance
diametro massimo porcellanaD mm 127 152 182
porcelain max diameter
filettatura armatura superioreM16 M20 M20
top metal fitting thread
filettatura armatura inferioreM16 M20 M20
bottom metal fitting thread
diametro armatura di based mm 60 80 115
bottom metal fitting diameter
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 17,5 17,5 17,5operating voltage
tensione di tenuta sotto pioggiakV 38 38 38
wet withstand voltage
tensione di tenuta ad impulso a seccokV 95 95 95
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 800 1600cantilever failing load
IEC H4-125 H8-125 H16-125
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 210±1 210±1 210±1height
linea di fuga minimamm 460 440 440
minimum creepage distance
diametro massimo porcellanaD mm 127 162 192
porcelain max diameter
filettatura armatura superioreM16 M20 M24
top metal fitting thread
filettatura armatura inferioreM16 M20 M24
bottom metal fitting thread
diametro armatura di based mm 60 95 115
bottom metal fitting diameter
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 24 24 24operating voltage
tensione di tenuta sotto pioggiakV 50 50 50
wet withstand voltage
tensione di tenuta ad impulso a seccokV 125 125 125
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 800 1600cantilever failing load
32
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
BIL 170 kV - 400/1600 daN
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - armature interne - IEC 60273IEC type - internal fittings
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
Colore smalto Glaze colour
IEC H4-170 H8-170 H16-170
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 300±1 300±1 300±1height
linea di fuga minimamm 680 640 640
minimum creepage distance
diametro massimo porcellanaD mm 150 177 200
porcelain max diameter
filettatura armatura superioreM16 M24 M24
top metal fitting thread
filettatura armatura inferioreM16 M24 M24
bottom metal fitting thread
diametro armatura di based mm 80 115 130
bottom metal fitting diameter
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 36 36 36operating voltage
tensione di tenuta sotto pioggiakV 70 70 70
wet withstand voltage
tensione di tenuta ad impulso a seccokV 170 170 170
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 800 1600cantilever failing load
MEDIA TENSIONE - MEDIUM VOLTAGE
BIL 75 kV - 400/1250 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
34
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
BIL 75 kV - 400/800 daN
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
IEC C4-75 C4-75 C4-75
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 215±1 215±1 215±1height
linea di fuga minimamm 192 240 300
minimum creepage distance
diametro massimo porcellanaD mm 140 136 150
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 12 12 12operating voltage
tensione di tenuta sotto pioggiakV 28 28 28
wet withstand voltage
tensione di tenuta ad impulso a seccokV 75 75 75
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400cantilever failing load
carico di rottura a torsionedaNm 100 100 100
torsion failing load
IEC C8-75 C8-75 C8-75
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 215±1 215±1 215±1height
linea di fuga minimamm 192 240 300
minimum creepage distance
diametro massimo porcellanaD mm 140 140 185
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 12 12 12operating voltage
tensione di tenuta sotto pioggiakV 28 28 28
wet withstand voltage
tensione di tenuta ad impulso a seccokV 75 75 75
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800cantilever failing load
carico di rottura a torsionedaNm 100 100 100
torsion failing load
Colore smalto Glaze colour
AlettaturaShed profile
35
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
BIL 75 kV – 1250 daN
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
IEC C12,5-75 C12,5-75 C12,5-75
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 215±1 215±1 215±1height
linea di fuga minimamm 192 240 300
minimum creepage distance
diametro massimo porcellanaD mm 144 160 175
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 12 12 12operating voltage
tensione di tenuta sotto pioggiakV 28 28 28
wet withstand voltage
tensione di tenuta ad impulso a seccokV 75 75 75
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 150 150 150
torsion failing load
Colore smalto Glaze colour
AlettaturaShed profile
MEDIA TENSIONE - MEDIUM VOLTAGE
BIL 95 kV - 400/1250 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
38
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 95 kV - 400/800 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C4-95 C4-95 C4-95
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 255±1 255±1 255±1height
linea di fuga minimamm 280 350 437,5
minimum creepage distance
diametro massimo porcellanaD mm 140 140 185
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 17,5 17,5 17,5operating voltage
tensione di tenuta sotto pioggiakV 38 38 38
wet withstand voltage
tensione di tenuta ad impulso a seccokV 95 95 95
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400cantilever failing load
carico di rottura a torsionedaNm 100 100 100
torsion failing load
IEC C8-95 C8-95 C8-95
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 255±1 255±1 255±1height
linea di fuga minimamm 280 350 437,5
minimum creepage distance
diametro massimo porcellanaD mm 150 160 167
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 17,5 17,5 17,5operating voltage
tensione di tenuta sotto pioggiakV 38 38 38
wet withstand voltage
tensione di tenuta ad impulso a seccokV 95 95 95
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800cantilever failing load
carico di rottura a torsionedaNm 200 200 200
torsion failing load
39
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
Colore smalto Glaze colour
AlettaturaShed profile
BIL 95 kV – 1250 daN
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
IEC C12,5-95 C12,5-95 C12,5-95
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 255±1 255±1 255±1height
linea di fuga minimamm 280 350 437,5
minimum creepage distance
diametro massimo porcellanaD mm 150 165 180
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 17,5 17,5 17,5operating voltage
tensione di tenuta sotto pioggiakV 38 38 38
wet withstand voltage
tensione di tenuta ad impulso a seccokV 95 95 95
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 200 200 200
torsion failing load
MEDIA TENSIONE - MEDIUM VOLTAGE
BIL 125 kV - 400/1250 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
42
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 125 kV - 400/800 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C4-125 C4-125 C4-125
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 305±1 305±1 305±1height
linea di fuga minimamm 384 480 600
minimum creepage distance
diametro massimo porcellanaD mm 148 150 190
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 24 24 24operating voltage
tensione di tenuta sotto pioggiakV 50 50 50
wet withstand voltage
tensione di tenuta ad impulso a seccokV 125 125 125
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400cantilever failing load
carico di rottura a torsionedaNm 100 100 100
torsion failing load
IEC C8-125 C8-125 C8-125
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 305±1 305±1 305±1height
linea di fuga minimamm 384 480 600
minimum creepage distance
diametro massimo porcellanaD mm 164 202 174
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 24 24 24operating voltage
tensione di tenuta sotto pioggiakV 50 50 50
wet withstand voltage
tensione di tenuta ad impulso a seccokV 125 125 125
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800cantilever failing load
carico di rottura a torsionedaNm 200 200 200
torsion failing load
43
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 125 kV – 1250 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C12,5-125 C12,5-125 C12,5-125
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 305±1 305±1 305±1height
linea di fuga minimamm 384 480 600
minimum creepage distance
diametro massimo porcellanaD mm 170 175 226
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 24 24 24operating voltage
tensione di tenuta sotto pioggiakV 50 50 50
wet withstand voltage
tensione di tenuta ad impulso a seccokV 125 125 125
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 200 200 200
torsion failing load
MEDIA TENSIONE - MEDIUM VOLTAGE
BIL 150 kV - 400/1250 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
46
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 150 kV - 400/800 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C4-150 C4-150 C4-150
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 355±1 355±1 355±1height
linea di fuga minimamm 384 480 600
minimum creepage distance
diametro massimo porcellanaD mm 157 155 140
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 24 24 24operating voltage
tensione di tenuta sotto pioggiakV 50 50 50
wet withstand voltage
tensione di tenuta ad impulso a seccokV 150 150 150
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400cantilever failing load
carico di rottura a torsionedaNm 100 100 100
torsion failing load
IEC C8-150 C8-150 C8-150
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 355±1 355±1 355±1height
linea di fuga minimamm 384 480 600
minimum creepage distance
diametro massimo porcellanaD mm 170 163 178
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 24 24 24operating voltage
tensione di tenuta sotto pioggiakV 50 50 50
wet withstand voltage
tensione di tenuta ad impulso a seccokV 150 150 150
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800cantilever failing load
carico di rottura a torsionedaNm 150 150 150
torsion failing load
47
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 150 kV – 1250 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C12,5-150 C12,5-150 C12,5-150
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 355±1 355±1 355±1height
linea di fuga minimamm 384 480 600
minimum creepage distance
diametro massimo porcellanaD mm 165 178 185
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 24 24 24operating voltage
tensione di tenuta sotto pioggiakV 50 50 50
wet withstand voltage
tensione di tenuta ad impulso a seccokV 150 150 150
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 250 250 250
torsion failing load
MEDIA TENSIONE - MEDIUM VOLTAGE
BIL 170 kV - 400/1250 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
50
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 170 kV - 400/600 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C4-170 C4-170 C4-170 C4-170
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 445±1 445±1 445±1 445±1height
linea di fuga minimamm 576 720 900 1116
minimum creepage distance
diametro massimo porcellanaD mm 144 190 184 200
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 36 36 36 36operating voltage
tensione di tenuta sotto pioggiakV 70 70 70 70
wet withstand voltage
tensione di tenuta ad impulso a seccokV 170 170 170 170
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400 400cantilever failing load
carico di rottura a torsionedaNm 120 120 120 120
torsion failing load
IEC C6-170 C6-170 C6-170 C6-170
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 445±1 445±1 445±1 445±1height
linea di fuga minimamm 576 720 900 1116
minimum creepage distance
diametro massimo porcellanaD mm 144 168 194 200
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 36 36 36 36operating voltage
tensione di tenuta sotto pioggiakV 70 70 70 70
wet withstand voltage
tensione di tenuta ad impulso a seccokV 170 170 170 170
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600 600 600cantilever failing load
carico di rottura a torsionedaNm 150 150 150 150
torsion failing load
51
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 170 kV – 800/1000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C8-170 C8-170 C8-170 C8-170
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 445±1 445±1 445±1 445±1height
linea di fuga minimamm 576 720 900 1116
minimum creepage distance
diametro massimo porcellanaD mm 153 173 202 213
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 36 36 36 36operating voltage
tensione di tenuta sotto pioggiakV 70 70 70 70
wet withstand voltage
tensione di tenuta ad impulso a seccokV 170 170 170 170
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800 800cantilever failing load
carico di rottura a torsionedaNm 200 200 200 200
torsion failing load
IEC C10-170 C10-170 C10-170
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 445±1 445±1 445±1height
linea di fuga minimamm 576 720 900
minimum creepage distance
diametro massimo porcellanaD mm 162 173 202
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 36 36 36operating voltage
tensione di tenuta sotto pioggiakV 70 70 70
wet withstand voltage
tensione di tenuta ad impulso a seccokV 170 170 170
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1000 1000 1000cantilever failing load
carico di rottura a torsionedaNm 250 250 250
torsion failing load
52
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 170 kV - 1250 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C12,5-170 C12,5-170 C12,5-170
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 445±1 445±1 445±1height
linea di fuga minimamm 576 720 900
minimum creepage distance
diametro massimo porcellanaD mm 174 220 220
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 36 36 36operating voltage
tensione di tenuta sotto pioggiakV 70 70 70
wet withstand voltage
tensione di tenuta ad impulso a seccokV 170 170 170
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 300 300 300
torsion failing load
MEDIA TENSIONE - MEDIUM VOLTAGE
BIL 200 kV - 400/1250 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
54
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 200 kV - 400/600 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C4-200 C4-200 C4-200 C4-200
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 475±1 475±1 475±1 475±1height
linea di fuga minimamm 576 720 900 1116
minimum creepage distance
diametro massimo porcellanaD mm 170 166 184 204
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 36 36 36 36operating voltage
tensione di tenuta sotto pioggiakV 70 70 70 70
wet withstand voltage
tensione di tenuta ad impulso a seccokV 200 200 200 200
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400 400cantilever failing load
carico di rottura a torsionedaNm 120 120 120 120
torsion failing load
IEC C6-200 C6-200 C6-200 C6-200
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 475±1 475±1 475±1 475±1height
linea di fuga minimamm 576 720 900 1116
minimum creepage distance
diametro massimo porcellanaD mm 150 170 195 195
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 36 36 36 36operating voltage
tensione di tenuta sotto pioggiakV 70 70 70 70
wet withstand voltage
tensione di tenuta ad impulso a seccokV 200 200 200 200
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600 600 600cantilever failing load
carico di rottura a torsionedaNm 180 180 180 180
torsion failing load
55
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 200 kV – 800/1000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C8-200 C8-200 C8-200 C8-200
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 475±1 475±1 475±1 475±1height
linea di fuga minimamm 576 720 900 1116
minimum creepage distance
diametro massimo porcellanaD mm 155 177 202 222
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 36 36 36 36operating voltage
tensione di tenuta sotto pioggiakV 70 70 70 70
wet withstand voltage
tensione di tenuta ad impulso a seccokV 200 200 200 200
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800 800cantilever failing load
carico di rottura a torsionedaNm 200 200 200 200
torsion failing load
IEC C10-200 C10-200 C10-200 C10-200
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 475±1 475±1 475±1 475±1height
linea di fuga minimamm 576 720 900 1116
minimum creepage distance
diametro massimo porcellanaD mm 165 177 208 228
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 36 36 36 36operating voltage
tensione di tenuta sotto pioggiakV 70 70 70 70
wet withstand voltage
tensione di tenuta ad impulso a seccokV 200 200 200 200
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1000 1000 1000 1000cantilever failing load
carico di rottura a torsionedaNm 250 250 250 250
torsion failing load
56
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 200 kV - 1250 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C12,5-200 C12,5-200 C12,5-200 C12,5-200
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 475±1 475±1 475±1 475±1height
linea di fuga minimamm 576 720 900 1116
minimum creepage distance
diametro massimo porcellanaD mm 172 205 215 235
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 36 36 36 36operating voltage
tensione di tenuta sotto pioggiakV 70 70 70 70
wet withstand voltage
tensione di tenuta ad impulso a seccokV 200 200 200 200
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 300 300 300 300
torsion failing load
MEDIA TENSIONE - MEDIUM VOLTAGE
BIL 250 kV - 400/1250 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
58
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 250 kV - 400/600 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C4-250 C4-250 C4-250 C4-250
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 560±1 560±1 560±1 560±1height
linea di fuga minimamm 832 1040 1300 1612
minimum creepage distance
diametro massimo porcellanaD mm 142 190 220 205
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 52 52 52 52operating voltage
tensione di tenuta sotto pioggiakV 95 95 95 95
wet withstand voltage
tensione di tenuta ad impulso a seccokV 250 250 250 250
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400 400cantilever failing load
carico di rottura a torsionedaNm 180 180 180 180
torsion failing load
IEC C6-250 C6-250 C6-250 C6-250
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 560±1 560±1 560±1 560±1height
linea di fuga minimamm 832 1040 1300 1612
minimum creepage distance
diametro massimo porcellanaD mm 152 165 187 215
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 76 76 76 76
top metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
parte metallica inferiore (p.c.d. / foratura)d2
mm 76 76 76 76
bottom metal fitting (p.c.d. / thread) n° 4xM12 4xM12 4xM12 4xM12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 52 52 52 52operating voltage
tensione di tenuta sotto pioggiakV 95 95 95 95
wet withstand voltage
tensione di tenuta ad impulso a seccokV 250 250 250 250
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600 600 600cantilever failing load
carico di rottura a torsionedaNm 200 200 200 200
torsion failing load
59
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 250 kV – 800/1000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C8-250 C8-250 C8-250 C8-250
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 560±1 560±1 560±1 560±1height
linea di fuga minimamm 850 1040 1300 1612
minimum creepage distance
diametro massimo porcellanaD mm 166 194 212 224
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 52 52 52 52operating voltage
tensione di tenuta sotto pioggiakV 95 95 95 95
wet withstand voltage
tensione di tenuta ad impulso a seccokV 250 250 250 250
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800 800cantilever failing load
carico di rottura a torsionedaNm 250 250 250 250
torsion failing load
IEC C10-250 C10-250 C10-250
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 560±1 560±1 560±1height
linea di fuga minimamm 850 1040 1300
minimum creepage distance
diametro massimo porcellanaD mm 174 199 221
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 52 52 52operating voltage
tensione di tenuta sotto pioggiakV 95 95 95
wet withstand voltage
tensione di tenuta ad impulso a seccokV 250 250 250
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1000 1000 1000cantilever failing load
carico di rottura a torsionedaNm 300 300 300
torsion failing load
60
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 250 kV - 1250 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C12,5-250 C12,5-250 C12,5-250
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 560±1 560±1 560±1height
linea di fuga minimamm 832 1040 1300
minimum creepage distance
diametro massimo porcellanaD mm 180 190 215
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 52 52 52operating voltage
tensione di tenuta sotto pioggiakV 95 95 95
wet withstand voltage
tensione di tenuta ad impulso a seccokV 250 250 250
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 400 400 400
torsion failing load
MEDIA TENSIONE - MEDIUM VOLTAGE
BIL 325 kV - 400/1600 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
62
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 325 kV - 400/600 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C4-325 C4-325 C4-325 C4-325
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 770±1 770±1 770±1 770±1height
linea di fuga minimamm 1160 1450 1812,5 2247,5
minimum creepage distance
diametro massimo porcellanaD mm 165 188 207 230
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 72,5 72,5 72,5 72,5operating voltage
tensione di tenuta sotto pioggiakV 140 140 140 140
wet withstand voltage
tensione di tenuta ad impulso a seccokV 325 325 325 325
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400 400cantilever failing load
carico di rottura a torsionedaNm 200 200 200 200
torsion failing load
IEC C6-325 C6-325 C6-325 C6-325
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 770±1 770±1 770±1 770±1height
linea di fuga minimamm 1160 1450 1812,5 2247,5
minimum creepage distance
diametro massimo porcellanaD mm 166 166 180 232
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 72,5 72,5 72,5 72,5operating voltage
tensione di tenuta sotto pioggiakV 140 140 140 140
wet withstand voltage
tensione di tenuta ad impulso a seccokV 325 325 325 325
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600 600 600cantilever failing load
carico di rottura a torsionedaNm 250 250 250 250
torsion failing load
63
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 325 kV – 800/1000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C8-325 C8-325 C8-325 C8-325
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 770±1 770±1 770±1 770±1height
linea di fuga minimamm 1160 1450 1812,5 2247,5
minimum creepage distance
diametro massimo porcellanaD mm 175 181 185 230
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 72,5 72,5 72,5 72,5operating voltage
tensione di tenuta sotto pioggiakV 140 140 140 140
wet withstand voltage
tensione di tenuta ad impulso a seccokV 325 325 325 325
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800 800cantilever failing load
carico di rottura a torsionedaNm 300 300 300 300
torsion failing load
IEC C10-325 C10-325 C10-325 C10-325
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 770±1 770±1 770±1 770±1height
linea di fuga minimamm 1160 1450 1812,5 2247,5
minimum creepage distance
diametro massimo porcellanaD mm 184 205 223 235
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 72,5 72,5 72,5 72,5operating voltage
tensione di tenuta sotto pioggiakV 140 140 140 140
wet withstand voltage
tensione di tenuta ad impulso a seccokV 325 325 325 325
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1000 1000 1000 1000cantilever failing load
carico di rottura a torsionedaNm 400 400 400 400
torsion failing load
64
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
BIL 325 kV - 1250/1600 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C12,5-325 C12,5-325 C12,5-325 C12,5-325
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 770±1 770±1 770±1 770±1height
linea di fuga minimamm 1160 1450 1812,5 2247,5
minimum creepage distance
diametro massimo porcellanaD mm 200 210 237 255
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 72,5 72,5 72,5 72,5operating voltage
tensione di tenuta sotto pioggiakV 140 140 140 140
wet withstand voltage
tensione di tenuta ad impulso a seccokV 325 325 325 325
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 400 400 400 400
torsion failing load
IEC C16-325 C16-325 C16-325 C16-325
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 770±1 770±1 770±1 770±1height
linea di fuga minimamm 1160 1450 1812,5 2247,5
minimum creepage distance
diametro massimo porcellanaD mm 205 230 245 268
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 225 225 225 225
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 72,5 72,5 72,5 72,5operating voltage
tensione di tenuta sotto pioggiakV 140 140 140 140
wet withstand voltage
tensione di tenuta ad impulso a seccokV 325 325 325 325
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1600 1600 1600 1600cantilever failing load
carico di rottura a torsionedaNm 500 500 500 500
torsion failing load
ALTA TENSIONE - HIGH VOLTAGE
BIL 450 kV - 400/2000 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
66
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
BIL 450 kV - 400/600 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C4-450 C4-450 C4-450 C4-450
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1020±1 1020±1 1020±1 1020±1height
linea di fuga minimamm 1600 2000 2500 3100
minimum creepage distance
diametro massimo porcellanaD mm 178 180 207 244
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 178 178 178 178
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 100 100 100 100operating voltage
tensione di tenuta sotto pioggiakV 185 185 185 185
wet withstand voltage
tensione di tenuta ad impulso a seccokV 450 450 450 450
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400 400cantilever failing load
carico di rottura a torsionedaNm 250 250 250 250
torsion failing load
IEC C6-450 C6-450 C6-450 C6-450
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1020±1 1020±1 1020±1 1020±1height
linea di fuga minimamm 1600 2000 2500 3100
minimum creepage distance
diametro massimo porcellanaD mm 190 206 208 242
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 178 178 178 178
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 100 100 100 100operating voltage
tensione di tenuta sotto pioggiakV 185 185 185 185
wet withstand voltage
tensione di tenuta ad impulso a seccokV 450 450 450 450
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600 600 600cantilever failing load
carico di rottura a torsionedaNm 350 350 350 350
torsion failing load
67
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 450 kV – 800/1000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C8-450 C8-450 C8-450 C8-450
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1020±1 1020±1 1020±1 1020±1height
linea di fuga minimamm 1600 2000 2500 3100
minimum creepage distance
diametro massimo porcellanaD mm 197 203 217 232
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 200 200 200 200
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 100 100 100 100operating voltage
tensione di tenuta sotto pioggiakV 185 185 185 185
wet withstand voltage
tensione di tenuta ad impulso a seccokV 450 450 450 450
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800 800cantilever failing load
carico di rottura a torsionedaNm 400 400 400 400
torsion failing load
IEC C10-450 C10-450 C10-450 C10-450
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1020±1 1020±1 1020±1 1020±1height
linea di fuga minimamm 1600 2000 2500 3100
minimum creepage distance
diametro massimo porcellanaD mm 196 225 233 260
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 225 225 225 225
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 100 100 100 100operating voltage
tensione di tenuta sotto pioggiakV 185 185 185 185
wet withstand voltage
tensione di tenuta ad impulso a seccokV 450 450 450 450
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1000 1000 1000 1000cantilever failing load
carico di rottura a torsionedaNm 400 400 400 400
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
68
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 450 kV - 1250/1600 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C12,5-450 C12,5-450 C12,5-450 C12,5-450
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1020±1 1020±1 1020±1 1020±1height
linea di fuga minimamm 1600 2000 2500 3100
minimum creepage distance
diametro massimo porcellanaD mm 205 226 250 270
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 225 225 225 225
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 100 100 100 100operating voltage
tensione di tenuta sotto pioggiakV 185 185 185 185
wet withstand voltage
tensione di tenuta ad impulso a seccokV 450 450 450 450
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
IEC C16-450 C16-450 C16-450 C16-450
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1020±1 1020±1 1020±1 1020±1height
linea di fuga minimamm 1600 2000 2500 3100
minimum creepage distance
diametro massimo porcellanaD mm 220 250 255 285
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 254 254 254 254
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 100 100 100 100operating voltage
tensione di tenuta sotto pioggiakV 185 185 185 185
wet withstand voltage
tensione di tenuta ad impulso a seccokV 450 450 450 450
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1600 1600 1600 1600cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
69
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 450 kV – 2000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C20-450 C20-450 C20-450 C20-450
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1020±1 1020±1 1020±1 1020±1height
linea di fuga minimamm 1600 2000 2500 3100
minimum creepage distance
diametro massimo porcellanaD mm 230 243 275 293
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 254 254 254 254
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 100 100 100 100operating voltage
tensione di tenuta sotto pioggiakV 185 185 185 185
wet withstand voltage
tensione di tenuta ad impulso a seccokV 450 450 450 450
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 2000 2000 2000 2000cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
ALTA TENSIONE - HIGH VOLTAGE
BIL 550 kV - 400/2000 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
72
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 550 kV - 400/600 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C4-550 C4-550 C4-550 C4-550
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1220±1 1220±1 1220±1 1220±1height
linea di fuga minimamm 1968 2460 3075 3813
minimum creepage distance
diametro massimo porcellanaD mm 185 208 217 250
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 178 178 178 178
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 123 123 123 123operating voltage
tensione di tenuta sotto pioggiakV 230 230 230 230
wet withstand voltage
tensione di tenuta ad impulso a seccokV 550 550 550 550
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400 400cantilever failing load
carico di rottura a torsionedaNm 300 300 300 300
torsion failing load
IEC C6-550 C6-550 C6-550 C6-550
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1220±1 1220±1 1220±1 1220±1height
linea di fuga minimamm 1968 2460 3075 3813
minimum creepage distance
diametro massimo porcellanaD mm 188 222 232 265
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 200 200 200 200
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 123 123 123 123operating voltage
tensione di tenuta sotto pioggiakV 230 230 230 230
wet withstand voltage
tensione di tenuta ad impulso a seccokV 550 550 550 550
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600 600 600cantilever failing load
carico di rottura a torsionedaNm 400 400 400 400
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
73
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 550 kV – 800/1000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C8-550 C8-550 C8-550 C8-550
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1220±1 1220±1 1220±1 1220±1height
linea di fuga minimamm 1968 2460 307 3813
minimum creepage distance
diametro massimo porcellanaD mm 196 243 245 249
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 200 200 200 200
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 123 123 123 123operating voltage
tensione di tenuta sotto pioggiakV 230 230 230 230
wet withstand voltage
tensione di tenuta ad impulso a seccokV 550 550 550 550
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800 800cantilever failing load
carico di rottura a torsionedaNm 400 400 400 400
torsion failing load
IEC C10-550 C10-550 C10-550 C10-550
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1220±1 1220±1 1220±1 1220±1height
linea di fuga minimamm 1968 2460 3075 3813
minimum creepage distance
diametro massimo porcellanaD mm 208 243 252 270
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 225 225 225 225
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 123 123 123 123operating voltage
tensione di tenuta sotto pioggiakV 230 230 230 230
wet withstand voltage
tensione di tenuta ad impulso a seccokV 550 550 550 550
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1000 1000 1000 1000cantilever failing load
carico di rottura a torsionedaNm 400 400 400 400
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
74
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 550 kV - 1250/1600 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C12,5-550 C12,5-550 C12,5-550 C12,5-550
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1220±1 1220±1 1220±1 1220±1height
linea di fuga minimamm 1968 2460 3075 3813
minimum creepage distance
diametro massimo porcellanaD mm 221 252 266 278
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 254 254 254 254
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 123 123 123 123operating voltage
tensione di tenuta sotto pioggiakV 230 230 230 230
wet withstand voltage
tensione di tenuta ad impulso a seccokV 550 550 550 550
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
IEC C16-550 C16-550 C16-550 C16-550
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1220±1 1220±1 1220±1 1220±1height
linea di fuga minimamm 1968 2460 3075 3813
minimum creepage distance
diametro massimo porcellanaD mm 246 276 290 295
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 254 254 254 254
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 123 123 123 123operating voltage
tensione di tenuta sotto pioggiakV 230 230 230 230
wet withstand voltage
tensione di tenuta ad impulso a seccokV 550 550 550 550
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1600 1600 1600 1600cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
75
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 550 kV – 2000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C20-550 C20-550 C20-550 C20-550
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1220±1 1220±1 1220±1 1220±1height
linea di fuga minimamm 1968 2460 3075 3813
minimum creepage distance
diametro massimo porcellanaD mm 247 272 291 309
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 275 275 275 275
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 123 123 123 123operating voltage
tensione di tenuta sotto pioggiakV 230 230 230 230
wet withstand voltage
tensione di tenuta ad impulso a seccokV 550 550 550 550
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 2000 2000 2000 2000cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
ALTA TENSIONE - HIGH VOLTAGE
BIL 650 kV - 400/2000 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
78
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 650 kV - 400/600 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C4-650 C4-650 C4-650 C4-650
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1500±2,5 1500±2,5 1500±2,5 1500±2,5height
linea di fuga minimamm 2320 2900 3625 4495
minimum creepage distance
diametro massimo porcellanaD mm 185 210 220 260
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 200 200 200 200
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 145 145 145 145operating voltage
tensione di tenuta sotto pioggiakV 275 275 275 275
wet withstand voltage
tensione di tenuta ad impulso a seccokV 650 650 650 650
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400 400cantilever failing load
carico di rottura a torsionedaNm 300 300 300 300
torsion failing load
IEC C6-650 C6-650 C6-650 C6-650
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1500±2,5 1500±2,5 1500±2,5 1500±2,5height
linea di fuga minimamm 2320 2900 3625 4495
minimum creepage distance
diametro massimo porcellanaD mm 188 188 240 253
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 200 200 200 200
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 145 145 145 145operating voltage
tensione di tenuta sotto pioggiakV 275 275 275 275
wet withstand voltage
tensione di tenuta ad impulso a seccokV 650 650 650 650
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600 600 600cantilever failing load
carico di rottura a torsionedaNm 300 300 300 300
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
79
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 650 kV – 800/1000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C8-650 C8-650 C8-650 C8-650
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1500±2,5 1500±2,5 1500±2,5 1500±2,5height
linea di fuga minimamm 2320 2900 3625 4495
minimum creepage distance
diametro massimo porcellanaD mm 210 238 252 252
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 225 225 225 225
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 145 145 145 145operating voltage
tensione di tenuta sotto pioggiakV 275 275 275 275
wet withstand voltage
tensione di tenuta ad impulso a seccokV 650 650 650 650
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800 800cantilever failing load
carico di rottura a torsionedaNm 400 400 400 400
torsion failing load
IEC C10-650 C10-650 C10-650 C10-650
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1500±2,5 1500±2,5 1500±2,5 1500±2,5height
linea di fuga minimamm 2320 2900 3625 4495
minimum creepage distance
diametro massimo porcellanaD mm 215 251 265 267
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 254 254 254 254
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 145 145 145 145operating voltage
tensione di tenuta sotto pioggiakV 275 275 275 275
wet withstand voltage
tensione di tenuta ad impulso a seccokV 650 650 650 650
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1000 1000 1000 1000cantilever failing load
carico di rottura a torsionedaNm 400 400 400 400
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
80
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 650 kV - 1250/1600 daN
IEC C12,5-650 C12,5-650 C12,5-650 C12,5-650
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1500±2,5 1500±2,5 1500±2,5 1500±2,5height
linea di fuga minimamm 2320 2900 3625 4495
minimum creepage distance
diametro massimo porcellanaD mm 230 251 270 275
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 254 254 254 254
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 145 145 145 145operating voltage
tensione di tenuta sotto pioggiakV 275 275 275 275
wet withstand voltage
tensione di tenuta ad impulso a seccokV 650 650 650 650
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
IEC C16-650 C16-650 C16-650 C16-650
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1500±2,5 1500±2,5 1500±2,5 1500±2,5height
linea di fuga minimamm 2320 2900 3625 4495
minimum creepage distance
diametro massimo porcellanaD mm 246 276 290 295
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 225 225 225 225
top metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
parte metallica inferiore (p.c.d. / foratura)d2
mm 275 275 275 275
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 145 145 145 145operating voltage
tensione di tenuta sotto pioggiakV 275 275 275 275
wet withstand voltage
tensione di tenuta ad impulso a seccokV 650 650 650 650
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1600 1600 1600 1600cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
Colore smalto Glaze colour
AlettaturaShed profile
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
81
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 650 kV – 2000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C20-650 C20-650 C20-650 C20-650
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1500±2,5 1500±2,5 1500±2,5 1500±2,5height
linea di fuga minimamm 2320 2900 3625 4495
minimum creepage distance
diametro massimo porcellanaD mm 256 286 300 305
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 225 225 225 225
top metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
parte metallica inferiore (p.c.d. / foratura)d2
mm 300 300 300 300
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 145 145 145 145operating voltage
tensione di tenuta sotto pioggiakV 275 275 275 275
wet withstand voltage
tensione di tenuta ad impulso a seccokV 650 650 650 650
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 2000 2000 2000 2000cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
ALTA TENSIONE - HIGH VOLTAGE
BIL 750 kV - 400/2000 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
84
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 750 kV - 400/600 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C4-750 C4-750 C4-750 C4-750
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1700±2,5 1700±2,5 1700±2,5 1700±2,5height
linea di fuga minimamm 2720 3400 4250 5270
minimum creepage distance
diametro massimo porcellanaD mm 190 216 242 256
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 200 200 200 200
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 170 170 170 170operating voltage
tensione di tenuta sotto pioggiakV 325 325 325 325
wet withstand voltage
tensione di tenuta ad impulso a seccokV 750 750 750 750
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400 400cantilever failing load
carico di rottura a torsionedaNm 300 300 300 300
torsion failing load
IEC C6-750 C6-750 C6-750 C6-750
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1700±2,5 1700±2,5 1700±2,5 1700±2,5height
linea di fuga minimamm 2720 3400 4250 5270
minimum creepage distance
diametro massimo porcellanaD mm 200 235 250 250
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 225 225 225 225
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 170 170 170 170operating voltage
tensione di tenuta sotto pioggiakV 325 325 325 325
wet withstand voltage
tensione di tenuta ad impulso a seccokV 750 750 750 750
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600 600 600cantilever failing load
carico di rottura a torsionedaNm 300 300 300 300
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
85
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 750 kV – 800/1000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C8-750 C8-750 C8-750 C8-750
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1700±2,5 1700±2,5 1700±2,5 1700±2,5height
linea di fuga minimamm 2720 3400 4250 5270
minimum creepage distance
diametro massimo porcellanaD mm 211 233 246 261
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 225 225 225 225
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 170 170 170 170operating voltage
tensione di tenuta sotto pioggiakV 325 325 325 325
wet withstand voltage
tensione di tenuta ad impulso a seccokV 750 750 750 750
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800 800cantilever failing load
carico di rottura a torsionedaNm 400 400 400 400
torsion failing load
IEC C10-750 C10-750 C10-750 C10-750
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1700±2,5 1700±2,5 1700±2,5 1700±2,5height
linea di fuga minimamm 2720 3400 4250 5270
minimum creepage distance
diametro massimo porcellanaD mm 223 253 257 281
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 254 254 254 254
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 170 170 170 170operating voltage
tensione di tenuta sotto pioggiakV 325 325 325 325
wet withstand voltage
tensione di tenuta ad impulso a seccokV 750 750 750 750
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1000 1000 1000 1000cantilever failing load
carico di rottura a torsionedaNm 400 400 400 400
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
86
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 750 kV - 1250/1600 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C12,5-750 C12,5-750 C12,5-750 C12,5-750
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1700±2,5 1700±2,5 1700±2,5 1700±2,5height
linea di fuga minimamm 2720 3400 4250 5270
minimum creepage distance
diametro massimo porcellanaD mm 250 253 293 299
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 254 254 254 254
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 170 170 170 170operating voltage
tensione di tenuta sotto pioggiakV 325 325 325 325
wet withstand voltage
tensione di tenuta ad impulso a seccokV 750 750 750 750
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
IEC C16-750 C16-750 C16-750 C16-750
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1700±2,5 1700±2,5 1700±2,5 1700±2,5height
linea di fuga minimamm 2720 3400 4250 5270
minimum creepage distance
diametro massimo porcellanaD mm 265 294 308 314
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 225 225 225 225
top metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
parte metallica inferiore (p.c.d. / foratura)d2
mm 275 275 275 275
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 170 170 170 170operating voltage
tensione di tenuta sotto pioggiakV 325 325 325 325
wet withstand voltage
tensione di tenuta ad impulso a seccokV 750 750 750 750
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1600 1600 1600 1600cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
87
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 750 kV – 2000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C20-750 C20-750 C20-750 C20-750
livello di inquinamento / pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1700±2,5 1700±2,5 1700±2,5 1700±2,5height
linea di fuga minimamm 2720 3400 4250 5270
minimum creepage distance
diametro massimo porcellanaD mm 265 295 308 315
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 225 225 225 225
top metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
parte metallica inferiore (p.c.d. / foratura)d2
mm 300 300 300 300
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 170 170 170 170operating voltage
tensione di tenuta sotto pioggiakV 325 325 325 325
wet withstand voltage
tensione di tenuta ad impulso a seccokV 750 750 750 750
dry lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 2000 2000 2000 2000cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
ALTA TENSIONE - HIGH VOLTAGE
BIL 950 kV – 400/1250 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
90
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 950 kV - 400/600 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C4-950 C4-950 C4-950
livello di inquinamento /pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 2100±3,5 2100±3,5 2100±3,5height
linea di fuga minimamm 3920 4900 6125
minimum creepage distance
diametro massimo porcellanaD mm 196 226 260
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 200 200 200
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 245 245 245operating voltage
tensione di tenuta sotto pioggiakV 395 395 395
wet withstand voltage
tensione di tenuta ad impulso a seccokV 950 950 950
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 750 750 750
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400cantilever failing load
carico di rottura a torsionedaNm 300 300 300
torsion failing load
IEC C6-950 C6-950 C6-950
livello di inquinamento /pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 2100±3,5 2100±3,5 2100±3,5height
linea di fuga minimamm 3920 4900 6125
minimum creepage distance
diametro massimo porcellanaD mm 211 225 275
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 225 225 225
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 245 245 245operating voltage
tensione di tenuta sotto pioggiakV 395 395 395
wet withstand voltage
tensione di tenuta ad impulso a seccokV 950 950 950
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 750 750 750
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600 600cantilever failing load
carico di rottura a torsionedaNm 300 300 300
torsion failing load
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
91
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
BIL 950 kV – 800/1000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C8-950 C8-950 C8-950
livello di inquinamento /pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 2100±3,5 2100±3,5 2100±3,5height
linea di fuga minimamm 3920 4900 6125
minimum creepage distance
diametro massimo porcellanaD mm 223 250 272
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 254 254 254
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 245 245 245operating voltage
tensione di tenuta sotto pioggiakV 395 395 395
wet withstand voltage
tensione di tenuta ad impulso a seccokV 950 950 950
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 750 750 750
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800cantilever failing load
carico di rottura a torsionedaNm 400 400 400
torsion failing load
IEC C10-950 C10-950 C10-950
livello di inquinamento /pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 2100±3,5 2100±3,5 2100±3,5height
linea di fuga minimamm 3920 4900 6125
minimum creepage distance
diametro massimo porcellanaD mm 231 261 295
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 254 254 254
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 245 245 245operating voltage
tensione di tenuta sotto pioggiakV 395 395 395
wet withstand voltage
tensione di tenuta ad impulso a seccokV 950 950 950
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 750 750 750
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1000 1000 1000cantilever failing load
carico di rottura a torsionedaNm 400 400 400
torsion failing load
92
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 950 kV - 1250 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C12,5-950 C12,5-950 C12,5-950
livello di inquinamento / pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 2100±3,5 2100±3,5 2100±3,5height
linea di fuga minimamm 3920 4900 6125
minimum creepage distance
diametro massimo porcellanaD mm 248 276 310
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 275 275 275
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 245 245 245operating voltage
tensione di tenuta sotto pioggiakV 395 395 395
wet withstand voltage
tensione di tenuta ad impulso a seccokV 950 950 950
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 750 750 750
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 600 600 600
torsion failing loadAL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
ALTA TENSIONE - HIGH VOLTAGE
BIL 1050 kV – 400/1600 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
94
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 1050 kV - 400/600 daN
Colore smalto Glaze colour
AlettaturaShed profile
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
IEC C4-1050 C4-1050 C4-1050 C4-1050
livello di inquinamento /pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 2300±3,5 2300±3,5 2300±3,5 2300±3,5height
linea di fuga minimamm 3920 4900 6125 7595
minimum creepage distance
diametro massimo porcellanaD mm 201 235 260 290
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 200 200 200 200
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 245 245 245 245operating voltage
tensione di tenuta sotto pioggiakV 460 460 460 460
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1050 1050 1050 1050
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 750 750 750 750
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400 400cantilever failing load
carico di rottura a torsionedaNm 300 300 300 300
torsion failing load
IEC C6-1050 C6-1050 C6-1050 C6-1050
livello di inquinamento /pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 2300±3,5 2300±3,5 2300±3,5 2300±3,5height
linea di fuga minimamm 3920 4900 6125 7595
minimum creepage distance
diametro massimo porcellanaD mm 216 280 260 285
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 225 225 225 225
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 245 245 245 245operating voltage
tensione di tenuta sotto pioggiakV 460 460 460 460
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1050 1050 1050 1050
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 750 750 750 750
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600 600 600cantilever failing load
carico di rottura a torsionedaNm 300 300 300 300
torsion failing load
95
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
BIL 1050 kV – 800/1000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C8-1050 C8-1050 C8-1050 C8-1050
livello di inquinamento /pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 2300±3,5 2300±3,5 2300±3,5 2300±3,5height
linea di fuga minimamm 3920 4900 6125 7595
minimum creepage distance
diametro massimo porcellanaD mm 226 247 272 295
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 254 254 254 254
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 245 245 245 245operating voltage
tensione di tenuta sotto pioggiakV 460 460 460 460
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1050 1050 1050 1050
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 750 750 750 750
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800 800cantilever failing load
carico di rottura a torsionedaNm 400 400 400 400
torsion failing load
IEC C10-1050 C10-1050 C10-1050 C10-1050
livello di inquinamento /pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 2300±3,5 2300±3,5 2300±3,5 2300±3,5height
linea di fuga minimamm 3920 4900 6125 7595
minimum creepage distance
diametro massimo porcellanaD mm 228 271 304 311
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 275 275 275 275
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 245 245 245 245operating voltage
tensione di tenuta sotto pioggiakV 460 460 460 460
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1050 1050 1050 1050
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 750 750 750 750
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1000 1000 1000 1000cantilever failing load
carico di rottura a torsionedaNm 400 400 400 400
torsion failing load
96
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 1050 kV – 1250/1600 daN
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
Colore smalto Glaze colour
AlettaturaShed profile
IEC C12,5-1050 C12,5-1050 C12,5-1050 C12,5-1050
livello di inquinamento /pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 2300±3,5 2300±3,5 2300±3,5 2300±3,5height
linea di fuga minimamm 3920 4900 6125 7595
minimum creepage distance
diametro massimo porcellanaD mm 250 283 311 318
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 275 275 275 275
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 245 245 245 245operating voltage
tensione di tenuta sotto pioggiakV 460 460 460 460
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1050 1050 1050 1050
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 750 750 750 750
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
IEC C16-1050 C16-1050 C16-1050 C16-1050
livello di inquinamento /pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 2300±3,5 2300±3,5 2300±3,5 2300±3,5height
linea di fuga minimamm 3920 4900 6125 7595
minimum creepage distance
diametro massimo porcellanaD mm 267 297 313 336
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 225 225 225 225
top metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18 4xØ18
parte metallica inferiore (p.c.d. / foratura)d2
mm 300 300 300 300
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 245 245 245 245operating voltage
tensione di tenuta sotto pioggiakV 460 460 460 460
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1050 1050 1050 1050
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 750 750 750 750
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1600 1600 1600 1600cantilever failing load
carico di rottura a torsionedaNm 600 600 600 600
torsion failing load
ALTA TENSIONE - HIGH VOLTAGE
BIL 1550 kV – 400/1600 daN
ISOLATORI PORTANTI PER ESTERNOA NUCLEO PIENO
OUTDOOR POST INSULATORSIEC TYPE SOLID CORE
98
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 1550 kV - 400/600 daN
Colore smalto Glaze colour
AlettaturaShed profile
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
IEC C4-1550 C4-1550 C4-1550
livello di inquinamento /pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 3350±4,5 3350±4,5 3350±4,5height
linea di fuga minimamm 6720 8400 10500
minimum creepage distance
diametro massimo porcellanaD mm 216 246 280
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 225 225 225
bottom metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 420 420 420operating voltage
tensione di tenuta sotto pioggiakV 680 680 680
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1550 1550 1550
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 1050 1050 1050
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400cantilever failing load
carico di rottura a torsionedaNm 300 300 300
torsion failing load
IEC C6-1550 C6-1550 C6-1550
livello di inquinamento /pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 3350±4,5 3350±4,5 3350±4,5height
linea di fuga minimamm 6720 8400 10500
minimum creepage distance
diametro massimo porcellanaD mm 231 261 295
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 254 254 254
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 420 420 420operating voltage
tensione di tenuta sotto pioggiakV 680 680 680
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1550 1550 1550
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 1050 1050 150
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600 600cantilever failing load
carico di rottura a torsionedaNm 300 300 300
torsion failing load
99
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORS
serie IEC - a nucleo pieno - IEC 60273IEC type - solid core
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
BIL 1550 kV – 800/1000 daN
Colore smalto Glaze colour
AlettaturaShed profile
IEC C8-1550 C8-1550 C8-1550
livello di inquinamento /pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 3350±4,5 3350±4,5 3350±4,5height
linea di fuga minimamm 6720 8400 10500
minimum creepage distance
diametro massimo porcellanaD mm 250 320 368
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 275 275 275
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 420 420 420operating voltage
tensione di tenuta sotto pioggiakV 680 680 680
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1550 1550 1550
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 1050 1050 1050
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 800 800 800cantilever failing load
carico di rottura a torsionedaNm 400 400 400
torsion failing load
IEC C10-1550 C10-1550 C10-1550
livello di inquinamento /pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 3350±4,5 3350±4,5 3350±4,5height
linea di fuga minimamm 6720 8400 10500
minimum creepage distance
diametro massimo porcellanaD mm 266 296 330
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 300 300 300
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 420 420 420operating voltage
tensione di tenuta sotto pioggiakV 680 680 680
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1550 1550 1550
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 1050 1050 150
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1000 1000 1000cantilever failing load
carico di rottura a torsionedaNm 400 400 400
torsion failing load
100
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PORTANTI PER ESTERNOOUTDOOR POST INSULATORSserie IEC - a nucleo pieno - IEC 60273IEC type - solid core
BIL 1550 kV – 1250/1600 daN
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
Colore smalto Glaze colour
AlettaturaShed profile
IEC C12,5-1550 C12,5-1550 C12,5-1550
livello di inquinamento /pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 3350±4,5 3350±4,5 3350±4,5height
linea di fuga minimamm 6720 8400 10500
minimum creepage distance
diametro massimo porcellanaD mm 281 345 400
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM16 4xM16 4xM16
parte metallica inferiore (p.c.d. / foratura)d2
mm 325 325 325
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 420 420 420operating voltage
tensione di tenuta sotto pioggiakV 680 680 680
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1550 1550 1550
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 1050 1050 1050
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1250 1250 1250cantilever failing load
carico di rottura a torsionedaNm 600 600 600
torsion failing load
IEC C16-1550 C16-1550 C16-1550
livello di inquinamento /pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 3350±4,5 3350±4,5 3350±4,5height
linea di fuga minimamm 6720 8400 10500
minimum creepage distance
diametro massimo porcellanaD mm 291 321 360
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 225 225 225
top metal fitting (p.c.d. / thread) n° 4xØ18 4xØ18 4xØ18
parte metallica inferiore (p.c.d. / foratura)d2
mm 356 356 356
bottom metal fitting (p.c.d. / thread) n° 8xØ18 8xØ18 8xØ18
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 420 420 420operating voltage
tensione di tenuta sotto pioggiakV 680 680 680
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1550 1550 1550
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 1050 1050 150
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 1600 1600 1600cantilever failing load
carico di rottura a torsionedaNm 600 600 600
torsion failing load
ALTA TENSIONE - HIGH VOLTAGE
BIL 650 -1550 kV
COLONNINI DI MANOVRA
OPERATING INSULATORS
102
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
COLONNINI DI MANOVRA OPERATING INSULATORS
BIL 650 – 750 kV
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
Colore smalto Glaze colour
AlettaturaShed profile
BIL 650 650 650 650
livello di inquinamento /pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1500±2,5 1500±2,5 1500±2,5 1500±2,5height
linea di fuga minimamm 2320 2900 3625 4495
minimum creepage distance
diametro massimo porcellanaD mm 166 200 250 210
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM10 4xM10 4xM10 4xM10
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xM10 4xM10 4xM10 4xM10
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 145 145 145 145operating voltage
tensione di tenuta sotto pioggiakV 275 275 275 275
wet withstand voltage
tensione di tenuta ad impulso a seccokV 650 650 650 650
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV - - - -
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 200 200 200 200cantilever failing load
carico di rottura a torsionedaNm 250 250 250 250
torsion failing load
BIL 750 750 750 750
livello di inquinamento /pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 1700±2,5 1700±2,5 1700±2,5 1700±2,5height
linea di fuga minimamm 2720 3400 4250 5270
minimum creepage distance
diametro massimo porcellanaD mm 155 196 187 215
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xM10 4xM10 4xM10 4xM10
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xM10 4xM10 4xM10 4xM10
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 170 170 170 170operating voltage
tensione di tenuta sotto pioggiakV 325 325 325 325
wet withstand voltage
tensione di tenuta ad impulso a seccokV 750 750 750 750
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV - - - -
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 200 200 200 200cantilever failing load
carico di rottura a torsionedaNm 250 250 250 250
torsion failing load
103
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
COLONNINI DI MANOVRA OPERATING INSULATORS
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
BIL 950- 1050 kV
Colore smalto Glaze colour
AlettaturaShed profile
BIL 950 950 950
livello di inquinamento /pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 2100±3,5 2100±3,5 2100±3,5height
linea di fuga minimamm 3920 4900 6125
minimum creepage distance
diametro massimo porcellanaD mm 160 190 218
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xØ12 4xØ12 4xØ12
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xØ12 4xØ12 4xØ12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 245 245 245operating voltage
tensione di tenuta sotto pioggiakV 395 395 395
wet withstand voltage
tensione di tenuta ad impulso a seccokV 950 950 950
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV - - -
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 200 200 200cantilever failing load
carico di rottura a torsionedaNm 250 250 250
torsion failing load
BIL 1050 1050 1050 1050
livello di inquinamento /pollution level (IEC 60815) I II III IV
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 2300±3,5 2300±3,5 2300±3,5 2300±3,5height
linea di fuga minimamm 4000 5650 6224 7595
minimum creepage distance
diametro massimo porcellanaD mm 160 196 246 224
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127 127
top metal fitting (p.c.d. / thread) n° 4xØ12 4xØ12 4xØ12 4xØ12
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xØ12 4xØ12 4xØ12 4xØ12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 245 245 245 245operating voltage
tensione di tenuta sotto pioggiakV 460 460 460 460
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1050 1050 1050 1050
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 750 750 750 750
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 200 200 200cantilever failing load
carico di rottura a torsionedaNm 250 250 250
torsion failing load
104
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
COLONNINI DI MANOVRA OPERATING INSULATORS
BIL 1550 kV
AL
TA
TE
NSIO
NE
–H
IGH
VO
LT
AG
E
Colore smalto Glaze colour
AlettaturaShed profile
BIL 1550 1550 1550
livello di inquinamento /pollution level (IEC 60815) I II III
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 3350±4,5 3350±4,5 3350±4,5height
linea di fuga minimamm 6720 8400 10500
minimum creepage distance
diametro massimo porcellanaD mm 160 196 246
porcelain max diameter
parte metallica superiore (p.c.d. / filettatura)d1
mm 127 127 127
top metal fitting (p.c.d. / thread) n° 4xØ12 4xØ12 4xØ12
parte metallica inferiore (p.c.d. / foratura)d2
mm 127 127 127
bottom metal fitting (p.c.d. / thread) n° 4xØ12 4xØ12 4xØ12
DATI ELETTRICI / ELECTRICAL VALUEStensione di esercizio
kV 420 420 420operating voltage
tensione di tenuta sotto pioggiakV 680 680 680
wet withstand voltage
tensione di tenuta ad impulso a seccokV 1550 1550 1550
dry lightning impulse withstand voltage
tensione di tenuta ad impulso di manovra sotto pioggiakV 1050 1050 1050
wet switching impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 200 200 200cantilever failing load
carico di rottura a torsionedaNm 250 250 250
torsion failing load
MEDIA TENSIONE - MEDIUM VOLTAGE
BIL 95 -170 kV
ISOLATORI PASSANTI
BUSHING INSULATORS
106
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
BIL 95 kV
ISOLATORI PASSANTIBUSHING INSULATORSpassamuro esterno-interno - IEC 60137wall crossing outdoor-indoor type
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
modello / model E.1027/20 F.342/20 F.342/30
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 562 487 487height
altezza esternoh1 mm 280 193 193
outdoor height
altezza internoh2 mm 282 294 294
indoor height
diametro massimo porcellanaD mm 140 140 140
porcelain max diameter
flangia metallica (p.c.d. / foratura)d1
mm
n°
145 145 145
metal flange (p.c.d. / hole pattern) 4xØ11 6xØ11 6xØ11
sezione barra in ramed2 mm M12 M12 M16
copper bar section
lunghezza barra in rameL mm 675 600 600
copper bar lenght
linea di fuga (esterna/interna)mm 600/550 360/380 360/380
creepage distance (outdoor/indoor)
DATI ELETTRICI / ELECTRICAL VALUEScorrente nominale
A 250 250 400nominal current
tensione di eserciziokV 15/17,5 15/17,5 15/17,5
operating voltage
tensione di arco a seccokV
dry flashover voltage
tensione di arco sotto pioggiakV
wet flashover voltage
tensione di tenuta sotto pioggiakV 38 38 38
wet withstand voltage
tensione di tenuta ad impulso a seccokV 95 95 95
lightning impulse dry withstand voltage
COMPORTAMENTO IN NEBBIA SALINA / BEHAVIOUR IN SALTY FOGtensione di prova
kVtest voltage
salinità tenutag/l
salinity withstand
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daNcantilever failing load
Colore smalto Glaze colour
107
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PASSANTIBUSHING INSULATORS
passamuro esterno-interno - IEC 60137wall crossing outdoor-indoor type
BIL125 kV
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
Colore smalto Glaze colour
modello / model RS1851/20 RS1851/30 RS1852/20 RS1852/30 RS1755
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 590 590 634 634 495height
altezza esternoh1 mm 236 236 280 280 258
outdoor height
altezza internoh2 mm 354 354 354 354 262
indoor height
diametro massimo porcellanaD mm
140140 140 140 140
porcelain max diameter
flangia metallica (p.c.d. / foratura)d1
mm
n°
145 145 145 145 135
metal flange (p.c.d. / hole pattern) 6xØ11 6xØ11 6xØ11 6xØ11 4XØ12
sezione barra in ramed2 mm M12 M16 M12 M20 M12
copper bar section
lunghezza barra in rameL mm 700 700 740 754 600
copper bar lenght
linea di fuga (esterna/interna)mm 485/440 485/440 600/465 600/465 500/200
creepage distance (outdoor/indoor)
DATI ELETTRICI / ELECTRICAL VALUEScorrente nominale
A 250 400 250 630 250nominal current
tensione di eserciziokV 20/24 20/24 20/24 20/24 20/24
operating voltage
tensione di arco a seccokV 85 85 85 85 80
dry flashover voltage
tensione di arco sotto pioggiakV 70 70 70 70 75
wet flashover voltage
tensione di tenuta sotto pioggiakV 60 60 60 60 60
wet withstand voltage
tensione di tenuta ad impulso a seccokV 125 125 125 125
lightning impulse dry withstand voltage
COMPORTAMENTO IN NEBBIA SALINA / BEHAVIOUR IN SALTY FOGtensione di prova
kV 18 18test voltage
salinità tenutag/l 56 56
salinity withstand
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400 400 400 400cantilever failing load
108
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
BIL 125 kV
ISOLATORI PASSANTIBUSHING INSULATORSpassamuro esterno-interno - IEC 60137wall crossing outdoor-indoor type
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
Colore smalto Glaze colour
modello / model E.1273 F.188 F.238
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 630 590 590height
altezza esternoh1 mm 276 236 236
outdoor height
altezza internoh2 mm 354 354 354
indoor height
diametro massimo porcellanaD mm 140 165 175
porcelain max diameter
flangia metallica (p.c.d. / foratura)d1 mm
175 180 188
metal flange (p.c.d. / hole pattern) 4xØ12 6xØ11,5 6xØ12
sezione barra in ramed2 mm M12 M30 M36
copper bar section
lunghezza barra in rameL mm 740 770 810
copper bar lenght
linea di fuga (esterna/interna)mm 785/525 485/450 490/440
creepage distance (outdoor/indoor)
DATI ELETTRICI / ELECTRICAL VALUEScorrente nominale
A 250 800/1250 1600nominal current
tensione di eserciziokV 20/24 20/24 20/24
operating voltage
tensione di arco a seccokV 85 85 85
dry flashover voltage
tensione di arco sotto pioggiakV 70 70 70
wet flashover voltage
tensione di tenuta sotto pioggiakV 60 60 60
wet withstand voltage
tensione di tenuta ad impulso a seccokV 125 125 125
lightning impulse dry withstand voltage
COMPORTAMENTO IN NEBBIA SALINA / BEHAVIOUR IN SALTY FOGtensione di prova
kVtest voltage
salinità tenutag/l
salinity withstand
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 400cantilever failing load
109
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PASSANTIBUSHING INSULATORS
passamuro esterno-interno - IEC 60137wall crossing outdoor-indoor type
BIL170 kV
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
Colore smalto Glaze colour
modello / model F.371/30 M12 F.371/30 M16 F.371/30 M20 F.371/45 M30
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 800 800 800 800height
altezza esternoh1 mm 350 350 350 350
outdoor height
altezza internoh2 mm 450 450 450 450
indoor height
diametro massimo porcellanaD mm
195195 195 205
porcelain max diameter
flangia metallica (p.c.d. / foratura)d1
mm
n°
265
4Ø11,5
265
4Ø11,5
265
4Ø11,5
265
4Ø11,5metal flange (p.c.d. / hole pattern)
sezione barra in ramed2 mm M12 M16 M20 M30
copper bar section
lunghezza barra in rameL mm 900 920 920 980
copper bar lenght
linea di fuga (esterna/interna)mm 810/670 810/670 810/670 810/670
creepage distance (outdoor/indoor)
DATI ELETTRICI / ELECTRICAL VALUEScorrente nominale
A 250 400 630 800/1250nominal current
tensione di eserciziokV 30/36 30/36 30/36 30/36
operating voltage
tensione di arco a seccokV 120 120 120 120
dry flashover voltage
tensione di arco sotto pioggiakV 100 100 100 100
wet flashover voltage
tensione di tenuta sotto pioggiakV 75 75 75 75
wet withstand voltage
tensione di tenuta ad impulso a seccokV 170 170 170 170
lightning impulse dry withstand voltage
COMPORTAMENTO IN NEBBIA SALINA / BEHAVIOUR IN SALTY FOGtensione di prova
kVtest voltage
salinità tenutag/l
salinity withstand
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600 600 600cantilever failing load
110
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
BIL 170 kV
ISOLATORI PASSANTIBUSHING INSULATORSpassamuro esterno-interno - IEC 60137wall crossing outdoor-indoor type
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
Colore smalto Glaze colour
modello / model F.374 M12 F.374 M16
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 800 800height
altezza esternoh1 mm 350 350
outdoor height
altezza internoh2 mm 450 450
indoor height
diametro massimo porcellanaD mm 215 215
porcelain max diameter
flangia metallica (p.c.d. / foratura)d1 mm
265 265
metal flange (p.c.d. / hole pattern) 4xØ11,5 4xØ11,5
sezione barra in ramed2 mm M12 M16
copper bar section
lunghezza barra in rameL mm 900 920
copper bar lenght
linea di fuga (esterna/interna)mm 1080/900 1080/900
creepage distance (outdoor/indoor)
DATI ELETTRICI / ELECTRICAL VALUEScorrente nominale
A 250 400nominal current
tensione di eserciziokV 30/36 30/36
operating voltage
tensione di arco a seccokV 120 120
dry flashover voltage
tensione di arco sotto pioggiakV 100 100
wet flashover voltage
tensione di tenuta sotto pioggiakV 75 75
wet withstand voltage
tensione di tenuta ad impulso a seccokV 170 170
lightning impulse dry withstand voltage
COMPORTAMENTO IN NEBBIA SALINA / BEHAVIOUR IN SALTY FOGtensione di prova
kVtest voltage
salinità tenutag/l
salinity withstand
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600cantilever failing load
111
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PASSANTIBUSHING INSULATORS
passamuro interno-interno - IEC 60137wall crossing outdoor-indoor type
BIL170 kV
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
Colore smalto Glaze colour
modello / model RS1803/35 RS1803/45
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza
H mm 800 800height
altezza esternoh1 mm 350 350
outdoor height
altezza internoh2 mm 450 450
indoor height
diametro massimo porcellanaD mm 170 180
porcelain max diameter
flangia metallica (p.c.d. / foratura)d1
mm
n°
265
4xØ11,5
265
4xØ11,5metal flange (p.c.d. / hole pattern)
sezione barra in ramed2 mm M20 M30
copper bar section
lunghezza barra in rameL mm 920 980
copper bar lenght
linea di fuga (esterna/interna)mm 590/670 590/670
creepage distance (outdoor/indoor)
DATI ELETTRICI / ELECTRICAL VALUEScorrente nominale
A 630 800/1250nominal current
tensione di eserciziokV 30/36 30/36
operating voltage
tensione di arco a seccokV 120 120
dry flashover voltage
tensione di arco sotto pioggiakV 100 100
wet flashover voltage
tensione di tenuta sotto pioggiakV 75 75
wet withstand voltage
tensione di tenuta ad impulso a seccokV 170 170
lightning impulse dry withstand voltage
COMPORTAMENTO IN NEBBIA SALINA / BEHAVIOUR IN SALTY FOGtensione di prova
kVtest voltage
salinità tenutag/l
salinity withstand
DATI MECCANICI / MECHANICAL VALUEScarico di rottura a flessione
daN 600 600cantilever failing load
112
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PASSANTIBUSHING INSULATORSper quadro interno-interno tipo ENELfor electrical indoor-indoor board - ENEL type
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
modello DJ1121 DJ1123
DATI DIMENSIONALI / DIMENSIONAL VALUES
altezzaH mm 860 810
height
lunghezza isolanteh1 mm 348,5 348,5
insulating lenght
lunghezza isolanteh2 mm 311,5 311,5
insulating lenght
diametro codolob mm 30 55
stud diameter
linea di fuga minimamm 420 420
minimum creepage distance
DATI ELETTRICI / ELECTRICAL VALUES
tensione di esercizio (indicativa)kV 24 24
operating voltage
corrente nominaleA 630 2500
nominal current
tensione di arco a seccokV 75 75
dry flashover voltage
tensione di arco 50% ad impulso di manovra 1,2/50μs, onda positivakV 140 140
lightning impulse flashover voltage 50%, 1,2/50μs, positive wave
tensione di tenuta a seccokV 50 50
dry withstand voltage
tensione di tenuta ad impulsi 1,2/50π skV 125 125
impulse withstand voltage 1,2/50π s
DATI MECCANICI / MECHANICAL VALUES
carico di rottura a flessionedaN 400 400
cantilever failing load
tipo ENEL / ENEL Type DJ1121/1 DJ1121/2 DJ1121/3 DJ1123/1 DJ1123/2 DJ1123/3
diametro codolo30 30 30 55 55 55
stud diameter
tipo codolo diritto
straight25° 60°
diritto
straight25° 60°
stud type
113
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PASSANTIBUSHING INSULATORS
per quadro interno-interno tipo ENELfor electrical indoor-indoor board - ENEL type
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
modello DJ1144
DATI DIMENSIONALI / DIMENSIONAL VALUES
altezzaH mm 560
height
linea di fuga minimamm 350
minimum creepage distance
diametro massimo porcellanaD mm 220
porcelain max diameter
diametro codolod1 mm 30
stud diameter
parte metallica (foratura)d2
mm 198x198
metal fitting (hole pattern) n° 4xØ14
DATI ELETTRICI / ELECTRICAL VALUES
tensione di eserciziokV 24
operating voltage
corrente termica nominaleA 630
nominal thermal current
corrente di breve durata nominalekA 12,5
nominal short lenght current
tensione di tenuta a frequenza industrialekV 50
power frequency withstand voltage
tensione di tenuta ad impulso atmosfericokV 125
lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUES
carico di rottura a flessionedaN 400
cantilever failing load
modello DJ1145
DATI DIMENSIONALI / DIMENSIONAL VALUES
altezzaH mm 560
height
linea di fuga minimamm 350
minimum creepage distance
diametro massimo porcellanaD mm 240
porcelain max diameter
diametro codolod1 mm 55
stud diameter
parte metallica (foratura)d2
mm 198x198
metal fitting (hole pattern) n° 4xØ14
DATI ELETTRICI / ELECTRICAL VALUES
tensione di eserciziokV 24
operating voltage
corrente termica nominaleA 2500
nominal thermal current
corrente di breve durata nominalekA 12,5
nominal short lenght current
tensione di tenuta a frequenza industrialekV 50
power frequency withstand voltage
tensione di tenuta ad impulso atmosfericokV 125
lightning impulse withstand voltage
DATI MECCANICI / MECHANICAL VALUES
carico di rottura a flessionedaN 400
cantilever failing load
MEDIA TENSIONE - MEDIUM VOLTAGE
ISOLATORI PASSANTI PER CONDENSATORI
HERMETIC BUSHING FOR CAPACITORS
116
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
SERIE KA/KB
ISOLATORI PASSANTI PER CONDENSATORIHERMETIC BUSHING FOR CAPACITORS
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
Colore smalto Glaze colour
modello / model KA35-C03F03 KA50-C03F03
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza totale
H mm 90 112±3,5total height
altezza assemblaggioh1 mm 76 98
assembly height
diametro massimo porcellanaD mm 34 34
porcelain max diameter
diametro forod1 mm 13 13
hole diameter
diametro/lunghezza codolod2 mm - -
stud diameter/lenght
diametro flangiad3 mm 44 44
flange diameter
linea di fugamm 34 75
creepage distance
linea d'arcomm 25 60
arching distance
DATI MECCANICI / MECHANICAL VALUEStensione di tenuta ad impulsi
kV 35 50lightning impulse withstand voltage
modello / model KB40-C41F15 KB40-C08F03 KB40-C40F15 KB60-C05F03
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza totale
H mm 97 90 102 116total height
altezza assemblaggioh1 mm 80 80 85 106
assembly height
diametro massimo porcellanaD mm 48 48 48 48
porcelain max diameter
diametro forod1 mm 13 13 13 13
hole diameter
diametro/lunghezza codolod2 mm M6x28 M12x22 M16x33 M12x27
stud diameter/lenght
diametro flangiad3 mm 60 44 60 44
flange diameter
linea di fugamm 84 84 84 100
creepage distance
linea d'arcomm 45 45 45 63
arching distance
DATI MECCANICI / MECHANICAL VALUEStensione di tenuta ad impulsi
kV 40 40 40 60lightning impulse withstand voltage
PROFILO KA
KA PROFILE
PROFILO KB
KB PROFILE
117
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PASSANTI PER CONDENSATORIHERMETIC BUSHING FOR CAPACITORS
SERIE KC/KD
Colore smalto Glaze colour
modello / model KC40-C16F10 KC45-C26F10 KC45-C16F10 KC75-C11F02 KC75-C01F02
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza totale
H mm 117 101±3 121±3 215 221total height
altezza assemblaggioh1 mm 98 87±2 107±2 181 187
assembly height
diametro massimo porcellanaD mm 50 74 74 95 95
porcelain max diameter
diametro forod1 mm 13 13 13 17,5 17,5
hole diameter
diametro/lunghezza codolod2 mm M12x30 M6x10 M12x30 M12x34 M14x39
stud diameter/lenght
diametro flangiad3 mm 54 54 54 75 75
flange diameter
linea di fugamm 53 82,5 82,5 210 210
creepage distance
linea d'arcomm 42 60 60 125 125
arching distance
DATI MECCANICI / MECHANICAL VALUEStensione di tenuta ad impulsi
kV 40 45 45 75 75lightning impulse withstand voltage
modello / model KD75-C13F09 KD95-C13F09 KD125-C13F09
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza totale
H mm 167 224 280total height
altezza assemblaggioh1 mm 154 211 254
assembly height
diametro massimo porcellanaD mm 90 100 100
porcelain max diameter
diametro forod1 mm 18 18 18
hole diameter
diametro/lunghezza codolod2 mm M14x30 M14x30 M14x30
stud diameter/lenght
diametro flangiad3 mm 82±1 82±1 82±1
flange diameter
linea di fugamm 165 300 380
creepage distance
linea d'arcomm 110 173 213
arching distance
DATI MECCANICI / MECHANICAL VALUEStensione di tenuta ad impulsi
kV 75 95 125lightning impulse withstand voltage
PROFILO KC
KA PROFILE
PROFILO KD
KB PROFILE
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
118
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
SERIE KE
ISOLATORI PASSANTI PER CONDENSATORIHERMETIC BUSHING FOR CAPACITORS
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
Colore smalto Glaze colour
modello / model KE95-C01F04 KE95-C14F04 KE125-C11F02 KE125-C01F04 KE125-C14F04
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza totale
H mm 233±12 233±12 274±12 278±12 278±12total height
altezza assemblaggioh1 mm 217 217 259 262 262
assembly height
diametro massimo porcellanaD mm 120 120 120 120 120
porcelain max diameter
diametro forod1 mm 17,5 17,5 17,5 20 17,5
hole diameter
diametro/lunghezza codolod2 mm M14x39 Ø14x40 M12x34 M14x39 Ø14x40
stud diameter/lenght
diametro flangiad3 mm 85 85 75±1 85 85
flange diameter
linea di fugamm 344 344 470 470 470
creepage distance
linea d'arcomm 148 148 224 224 224
arching distance
DATI MECCANICI / MECHANICAL VALUEStensione di tenuta ad impulsi
kV 95 95 125 125 125lightning impulse withstand voltage
modello / model KE170-C01F05 KE170-C14F05 KE250-C01F05 KE250-C19F05
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza totale
H mm 327,5±12 327,5±12 471±12 481±12total height
altezza assemblaggioh1 mm 310,5 310,5 445 455
assembly height
diametro massimo porcellanaD mm 120 120 120 120
porcelain max diameter
diametro forod1 mm 17,5 17,5 17,5 17,5
hole diameter
diametro/lunghezza codolod2 mm M14x39 Ø14x40 M14x39 M16x50
stud diameter/lenght
diametro flangiad3 mm 85 85 85 85
flange diameter
linea di fugamm 560 560 900 900
creepage distance
linea d'arcomm 270 270 400 400
arching distance
DATI MECCANICI / MECHANICAL VALUEStensione di tenuta ad impulsi
kV 170 170 250 250lightning impulse withstand voltage
119
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
ISOLATORI PASSANTI PER CONDENSATORIHERMETIC BUSHING FOR CAPACITORS
SERIE KF
Colore smalto Glaze colour
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
modello / model KF75-C21F01 KF75-C01F04 KF75-C19F01 KF75-C07F04 KF95-C20F08
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza totale
H mm 194 194 204 194 311total height
altezza assemblaggioh1 mm 178±5 181±5 188±5 181±5 250
assembly height
diametro massimo porcellanaD mm 86 86 86 84 95
porcelain max diameter
diametro forod1 mm 20 20 20 20 17
hole diameter
diametro/lunghezza codolod2 mm M14x39 M14x39 M16x49 M16x40 M12x40
stud diameter/lenght
diametro flangiad3 mm 70±0,5 85 70±0,5 85 115
flange diameter
linea di fugamm 245 255 255 235 470
creepage distance
linea d'arcomm 124 121 125 121 200
arching distance
DATI MECCANICI / MECHANICAL VALUEStensione di tenuta ad impulsi
kV 75 75 75 75 95lightning impulse withstand voltage
modello / model KF95-C01F04 KF95-C19F01 KF125-C01F04 KF125-C19F01 KF200-C19F01
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza totale
H mm 269 281 311,5 326 393total height
altezza assemblaggioh1 mm 255±5 265±5 298,5±5 310±5 377±5
assembly height
diametro massimo porcellanaD mm 86 84 82 84 84
porcelain max diameter
diametro forod1 mm 20 20 20 20 20
hole diameter
diametro/lunghezza codolod2 mm M14x39 M16x50 M14x39 M16x50 M16x50
stud diameter/lenght
diametro flangiad3 mm 85 70±0,5 85 70±0,5 70±0,5
flange diameter
linea di fugamm 375 390 505 505 670
creepage distance
linea d'arcomm 196 198 238 230 312
arching distance
DATI MECCANICI / MECHANICAL VALUEStensione di tenuta ad impulsi
kV 95 95 125 125 200lightning impulse withstand voltage
120
Tolleranze IEC / IEC Tolerances ≤300mm ±(4%+1,5mm) >300mm ± (2,5%+6mm)Dati tecnici indicativi soggetti a variazioni
Technical data provided as a guide subject to changes
SERIE KG
ISOLATORI PASSANTI PER CONDENSATORIHERMETIC BUSHING FOR CAPACITORS
ME
DIA
TE
NSIO
NE
–M
ED
IUM
VO
LT
AG
E
Colore smalto Glaze colour
modello / model KG95-C18F01 KG95-C17F01 KG125-C10F01 KG125-C18F01
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza totale
H mm 236±5 236±5 289±5 270±5total height
altezza assemblaggioh1 mm 230±5 230±5 275±5 264±5
assembly height
diametro massimo porcellanaD mm 83 83 93,5 93
porcelain max diameter
diametro forod1 mm 20 20 20 20
hole diameter
diametro/lunghezza codolod2 mm M12x40 M16x40 M12x40 M12x40
stud diameter/lenght
diametro flangiad3 mm 70±0,5 70±0,5 70±0,5 70±0,5
flange diameter
linea di fugamm 317 317 540 500
creepage distance
linea d'arcomm 163 163 225 200
arching distance
DATI MECCANICI / MECHANICAL VALUEStensione di tenuta ad impulsi
kV 95 95 125 125lightning impulse withstand voltage
modello / model KG125-C17F01 KG150-C32F01 KG150-C01F04 KG150-C16-F01
DATI DIMENSIONALI / DIMENSIONAL VALUESaltezza totale
H mm 270±5 313±5 311,5±5 322±5total height
altezza assemblaggioh1 mm 264±5 297±5 298,5±5 306±5
assembly height
diametro massimo porcellanaD mm 93 92 92 92
porcelain max diameter
diametro forod1 mm 20 20 20 20
hole diameter
diametro/lunghezza codolod2 mm M16x40 M10x40 M14x39 M16x49
stud diameter/lenght
diametro flangiad3 mm 70±0,5 70±0,5 85 70±5
flange diameter
linea di fugamm 500 600 600 600
creepage distance
linea d'arcomm 200 240 245 247,5
arching distance
DATI MECCANICI / MECHANICAL VALUEStensione di tenuta ad impulsi
kV 125 150 150 150lightning impulse withstand voltage