Catalog News LV1 N 12/2008 17 EN - Siemens · Catalog News LV 1 N ... SENTRON air circuit...

40
3NP1 Fuse Switch Disconnectors up to 630 A Catalog News LV 1 N December 2008 SENTRON Answers for industry. © Siemens AG 2009

Transcript of Catalog News LV1 N 12/2008 17 EN - Siemens · Catalog News LV 1 N ... SENTRON air circuit...

3NP1 Fuse Switch Disconnectors up to 630 ACatalog News LV 1 N • December 2008

SENTRON

Answers for industry.

© Siemens AG 2009

Low-Voltage ControlsSIRIUS · SENTRON · SIVACONOrder No.:CatalogE86060-K1002-A101-A8incl. PDF CD-ROMTechnical InformationE86060-T1002-A101-A8

LV 1

LV 1 T

Systems · Switchgear: Contactors and contactor assemblies, solid-state switching devices · Protection equipment · motor, soft starter and load feeders · monitoring and control devices · detecting devices · commanding and signaling devices · transformers · power supplies · planning and configuration with SIRIUS · Power Management System · SIVACON Power Distri-bution Boards, Busway and Cubicle Systems · SENTRON Switching and Protection Devices for Power Distribution: Air cir-cuit breakers, molded case circuit breakers, switch disconnec-tors, busbar systems· Software for power distribution · BETA low-voltage circuit-protection devices

Low-voltage controls and distributionSwitchgear and components forapplications according to ULOrder No.:E86060-K1816-A101-A2

LV 16 SIRIUS Circuit Breaker 3RV17 and 3RV18 according to UL 489/CSA C22.2 No.5-02· SIVACON components for feeder circuits · SENTRON air circuit breaker/non-automatic air circuit breaker 3WL5 according to UL 489/IEC 60947-2· SENTRON 3VL molded case circuit breakers according to UL 489/IEC 60947-2 · ALPHA devices according to UL standard · BETA devices

SIMATIC NETIndustrial communicationOrder No.:E86060-K6710-A101-B6 IK PI

PROFINET/Industrial Ethernet · Industrial Wireless Communicaton · PROFIBUS · SIMATIC ET 200 distributed peripherals · AS-Interface · Telecontrol · Routers · ECOFAST system

SIVACONCubicle systems andcubicle air-conditioningOrder No.:E86060-K1920-A101-A4

LV 50 System Cubicles · Cubicle Modifications · Cubicle Expansion Components · Accessories · Special Cubicles · Cubicle solu-tions in operation · Cubicle Air-Conditioning · Special colors

SIDACReactors and filtersOrder No.:E86060-K2803-A101-A4

LV 60 Commutating reactors for converters · Mains reactors for frequency converters · iron output reactors · ferrite output reactors · iron smoothing reactors · iron smoothing reactors · filter reactors · application-specific reactors · radio interference suppression filters

SIVACON 8PSBusbar trunking systems CD-L, BD01, BD2 to 1250 AOrder No.:E86060-K1870-A101-A4

LV 70 Busbar Trunking Systems, Overview · CD-L system (25 A to 40 A) · BD01 system (40 A to 160 A) · BD2 system (160 A to 1250 A)

The Offline MallOrder No.:E86060-D4001-A500-C7 (DVD)

CA 01 All products of automation, operating mechanism and installation technology, incl. the products from the catalogs mentioned above.

The Online MallInternet:http://www.siemens.com/automation/mall

All products of automation, operating mechanism and installation technology, incl. the products from the catalogs mentioned above.

Catalog PDFInternet:http://www.automation.siemens.com/cd

All catalogs for low-voltage controls can be downloaded as PDF files.

Trademarks Technical Assistance

All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners.More information on low-voltage controls is available on the Internet at:http://www.siemens.com/lowvoltage

Competent expert advice for low-voltage controls and electrical wiring.Tel.: +49 (9 11) 8 95-59 00Fax: +49 (9 11) 8 95-59 07E-mail: [email protected]

Related catalogs Contents

LV1N_3NP1_12_2008_eng.book Seite 1 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

SENTRON3NP1 Fuse Switch Disconnectors

Catalog News LV 1 N · 12/2008

Contact your local Siemens sales officefor further information

© Siemens AG 2008

The products and sys-tems listed in this cata-log are distributed/manufactured using a certified quality management system which complies with EN ISO 9001 (for the Certificate Register No. see the Appendix to LV 1 · 2009). The certificate is recog-nized in all IQNet countries.

LV1N_3NP1_12_2008_eng.book Seite 1 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

LV1N_3NP1_12_2008_eng.book Seite 2 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

1 IntroductionAnswers for Industry.

Low-voltage controls and distribution.The basis for advanced solutions.

PG

104

, 400

, 401

11 Power Supplies4AV Non-Stabilized Power Supplies6EP Stabilized Power Supplies- SITOP- LOGO!Power

S I R

I U

S

I n d

u s

t r i

a l

C o

n t

r o l

s P

G 0

41, 1

01, 1

21, 2

30, 2

50, 5

40 ..

.

2 SystemsAS-Interface IO-Link ECOFAST SystemSIRIUS Safety Integrated PROFIBUSSIRIUS Modular System P

G 12

1, 1

31, 2

00

12 Engineering SoftwarePlanning and Configuration with SIRIUSMotor Starter ES ECOFAST ESSIMOCODE ES Modular Safety System ESSoft Starter ES

PG 0

41, 1

01, 1

21

3 Controls – Contactors and Contactor Assemblies3RT, 3TB, 3TF Contactors for Switching Motors3RA13, 3RA14, 3TD, 3TE Contactor Assemblies3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications3RH, 3TH Contactor Relays · 3RT Coupling Relays3TX7, 3RS18 Coupling Relays · Coupling Relays with LZS, LZX Plug-In Relays · 3TG10 Power Relays/Miniature Contactors

L o

w -

V o

l t a

g e

P

o w

e r

D i

s t r

i b

u t i

o n

PG 1

33

13 Power Management SystemSystem OverviewSENTRON PAC3200 Multifunction Measuring Instruments

PG 0

41, 1

01

4 Controls – Solid-State Switching DevicesFor switching resistive loads:3RF20, 3RF21, 3RF22 Solid-State Relays3RF23, 3RF24 Solid-State Contactors · 3RF29 Function Modules

For switching motors:3RF24 Solid-State Contactors and Solid-State Reversing Contactors

PG 0

16, 1

03

14 SIVACON Power Distribution Boards, Busway Systems and Cubicle SystemsS8, 8PV and 8PT Power Distribution Boards and Motor Control Centers 8PS Busbar Trunking Systems · 8MC, 8MF Cubicle Systems8MR, 8ME Cubicle Air-ConditioningALPHA Distribution BoardsALPHA FIX Terminal Blocks

PG

041,

044

, 101

, 102

, 143 5 Protection Equipment

3RV Motor Starter Protectors/Circuit Protectors up to 100 A3RV Molded Case Motor Starter Protectors up to 800 A3RU1 Thermal Overload Relays3RB2 Solid-State Overload Relays

PG 1

03, 1

33

15 SENTRON Switching and Protection Devicesfor Power Distribution3WL Air Circuit Breakers

PG

041,

101

, 102

, 103

, 121

, 131

...

6 Motor Starters, Soft Starters and Load Feeders3RW Soft Starters 3RA1 Fuseless Load Feeders3RA6 Compact Feeders ET 200S Motor StartersET 200S Safety Motor Starter Solutions Local/PROFIsafeET 200pro Motor Starters · AS-Interface Compact Starters, 400 V ECOFAST Motor Starters and Soft Starters · 3RE Encapsulated Starters · Motor Starters, 24 V DC PG

101

, 102

, 103

, 113

, 131

, 250 16 SENTRON Switching and Protection Devices

for Power Distribution3VL, 3VF2 Molded Case Circuit Breakers

PG

101

, 102

, 121

, 131

, 192

, 200

...

7 Monitoring and Control DevicesSIMOCODE 3UF Motor Management and Control Devices LOGO! Logic Modules · 3RP, 3RT19 Timing Relays3UG Monitoring Relays for Electrical and Additional Measurements 3RS10, 3RS11 Temperature Monitoring Relays3RN1 Thermistor Motor Protection3TK28 Safety Relays 3RK3 Modular Safety System 3RS17 Interface Converters PG

013

, 046

, 101

, 102

, 103

, 113

, 143 17 SENTRON Switching and Protection Devices

for Power Distribution3KA, 3KE, 3LD Switch Disconnectors3KL, 3KM, 3NJ6 Switch Disconnectors with Fuses 3NP, 3NJ4, 3NJ5 Fuse Switch Disconnectors SENTRON 8US Busbar Systems

PG 1

02, 1

21, 5

74

8 Detecting Devices3SE2, 3SE3, 3SE5, 3SF1 Position Switches3SE2, 3SE5, 3SF1 Hinge Switches3SE6 Magnetically Operated Switches

PG 1

33

18 Software for Power DistributionDimensioning with SIMARIS designConfiguring, Visualizing and Controlling with SIMATIC Configuring, Visualizing and Controlling with SENTRON

PG 1

01, 1

02, 1

21

9 Commanding and Signaling Devices3SB2, 3SB3, 3SF5 Pushbutton Units and Indicator Lights3SE7, 3SF2 Cable-Operated Switches3SE2, 3SE3 Foot Switches8WD4 Signaling Columns8WD5 Integrated Signal Lamps

PG 0

01, 0

02, 0

03, 0

04, 0

05, 0

07 ..

.

19 BETA Low-Voltage Circuit ProtectionMiniature Circuit BreakersResidual Current Protective Devices Low-Voltage Fuse SystemsSITOR Semiconductor FusesSR 60 Busbar SystemsOvervoltage Protection DevicesSocket OutletsMeasuring Devices

PG

104

, 114

10 TransformersSingle-Phase TransformersThree-Phase Transformers

20 AppendixGlossary · Training · Order information · Further documenta-tion · Standards and approvals · Quality management Siemens contacts · External partners · Online servicesCustomer supportSoftware licenses · Subject index · Order number index includ-ing metal surcharges and export markings · Terms and condi-tions of sale and delivery, export regulations

New

LV1N_3NP1_12_2008_eng.book Seite 3 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

4 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008

Explanations

■ General information

Delivery time class (DT)

} Preferred type

A 2 working days

B 1 week

C 3 weeks

D 6 weeks

X On request

Preferred types are available immediately from stock, i.e.are dispatched within 24 hours.

Normal quantities of the products are usually deliv-ered within the specified time following receipt of your order at our branch.

In exceptional cases, the actual delivery time may differ from that specified.

The delivery times apply up to the ramp at Siemens AG (products ready for dispatch). The transport times depend on the destination and type of shipping. The standard transport time for Germany is 1 day.

The delivery times specified here represent the state of 10/2008. They are permanently optimized. Up-to-date information can be found athttp://www.siemens.com/automation/mall.

Price units (PU)

The price unit defines the number of units, sets or meters to which the specified price and weight apply.

Packaging sizes (PS)

The packaging size defines the number, e.g. of units, sets or meters, for outer packaging.

Only the quantity defined by the packaging size or a multiple thereof can be ordered!

For multi-unit packing and reusable packaging see Appendix.

Price groups (PG)

Each product is assigned to a price group.

Weight

The defined weight in kg refers to the price unit (PU).

Dimensions

All dimensions in mm.

LV1N_3NP1_12_2008_eng.book Seite 4 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

5Siemens LV 1 N Fuse Switch Disconnectors · 12/2008

Explanations

LV1N_3NP1_12_2008_eng.book Seite 5 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

6 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008

Explanations

■ ATEX explosion protection

In many industries the production, processing, transport and storage of combustible substances are accompanied by escap-ing gases, vapor or spray which find their way into the environ-ment. Other processes result in combustible dust. Together with the oxygen in the air, the result can be an explosive atmosphere which will explode if ignited.

Serious injury to persons and damage to property can result par-ticularly in the chemical and petrochemical industry, mineral oil and natural gas production, mining, mills (e.g. grain, solid mate-rials) and many other sectors.

To guarantee the maximum possible safety in these areas, the legislators of most countries have drawn up requirements in the form of laws, regulations and standards. In the course of global-ization, great progress has been made with regard to uniform di-rectives for explosion protection.

With Directive 94/9/EC, the European Union laid the foundations for complete harmonization by requiring that all new devices as from 1st July 2003 have to be approved in accordance with this directive.

In this catalog, special attention is drawn to devices which com-ply with the ATEX Directive. However, it does not replace inten-sive study of the relevant fundamentals and directives when planning and installing electrical systems.

■ UL-certified devices

UL standards are applied in North America and a number of other countries. This is important in particular for European ex-ports of electrical switchgear and machine-integrated equip-ment, above all to the USA. Acceptance and delivery are possi-ble only if the relevant UL standards are satisfied.

UL 508A "Standard for Industrial Control Panels" describes the design of control cabinets and implementation of integral com-ponents with reference to other pertinent UL standards where applicable. As such, this standard represents the basis for all electrical systems used in North America.

Our consideration of both IEC directives as well as UL standards as early as in our products' development phase results in a broad portfolio of UL-certified products for low-voltage switching and protection technology.

Whether SENTRON circuit breakers, SIRIUS switching devices – including motor-protective circuit breakers, starters, contactors and overload relays –, SENTRON switch disconnectors, SIRIUS detecting and command devices, busbar systems, terminals, miniature circuit breakers, fuses or SIRIUS transformers and fil-ters – our portfolio of low-voltage controls and distribution

products ensures your being on the safe side in terms of UL and facilitates the easy and fast assembly of control cabinets ac-cording to UL.

Our UL-certified portfolio can be found partly in this catalog and in greater concentration in Catalog LV 16, "Controls and Compo-nents for Applications According to UL".

LV1N_3NP1_12_2008_eng.book Seite 6 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

7Siemens LV 1 N Fuse Switch Disconnectors · 12/2008

Explanations

■ Order number index and export markings

Order No. Export markings

Page

ECCN AL

3NP13NP11 23-1BB N N 17/7

3NP11 23-1BC N N 17/9

3NP11 23-1C N N 17/5

3NP11 23-1J N N 17/8, 17/10

3NP11 33-1BB N N 17/7

3NP11 33-1BC N N 17/9

3NP11 33-1C N N 17/5

3NP11 33-1J N N 17/8, 17/10

3NP11 43-1B N N 17/9

3NP11 43-1D N N 17/6

3NP11 43-1J N N 17/10

3NP11 53-1B N N 17/9

3NP11 53-1D N N 17/6

3NP11 53-1J N N 17/10

3NP11 63-1B N N 17/9

3NP11 63-1D N N 17/6

3NP11 63-1J N N 17/10

3NP19 0 N N 17/13, 17/17, 17/21, 17/24, 17/27

3NP19 20 N N 17/13

3NP19 23-1BD N N 17/11

3NP19 23-1BE EAR99 N 17/11, 17/14

3NP19 23-1BF1 EAR99 N 17/11

3NP19 23-1BF2 EAR99 N 17/11

3NP19 23-1BF3 EAR99 N 17/11

3NP19 23-1BF4 EAR99 N 17/11

3NP19 23-1BF5 N N 17/11

3NP19 23-1BG N N 17/11

3NP19 23-1C N N 17/12

3NP19 23-1D N N 17/12

3NP19 23-1E N N 17/12

3NP19 23-1G N N 17/13

3NP19 30 N N 17/16

3NP19 33-1BA N N 17/14

3NP19 33-1BB N N 17/14

3NP19 33-1BC N N 17/14

3NP19 33-1BE EAR99 N 17/14

3NP19 33-1BG N N 17/14

3NP19 33-1C N N 17/15

3NP19 33-1D N N 17/16

3NP19 33-1E N N 17/16

3NP19 33-1G N N 17/17

3NP19 40 N N 17/20, 17/24, 17/27

3NP19 43-1BA N N 17/18

3NP19 43-1BB EAR99 N 17/18

3NP19 43-1BG N N 17/18, 17/22, 17/25

3NP19 43-1CA N N 17/19

3NP19 43-1CB N N 17/19

3NP19 43-1CD N N 17/19

3NP19 43-1CF N N 17/19, 17/23, 17/26

3NP19 43-1D N N 17/20

3NP19 43-1E N N 17/20

3NP19 43-1G N N 17/21

3NP19 53-1BA N N 17/22

3NP19 53-1BB EAR99 N 17/22

3NP19 53-1BG N N 17/22, 17/25

3NP19 53-1C N N 17/23

3NP19 53-1D N N 17/23

3NP19 53-1G N N 17/24

3NP19 63-1BA N N 17/25

3NP19 63-1BB EAR99 N 17/25

3NP19 63-1C N N 17/26

3NP19 63-1D N N 17/26

3NP19 63-1G N N 17/27

Order No. Export markings

Page

ECCN AL

LV1N_3NP1_12_2008_eng.book Seite 7 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

8 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008

Explanations

LV1N_3NP1_12_2008_eng.book Seite 8 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

17

Siemens LV 1 N Fuse Switch Disconnectors · 12/2008

3NP Fuse Switch Disconnectorsup to 630 A3NP1 for Industrial Applications and Power DistributionIntroduction

17/2 - Overview17/4 - Benefits17/4 - Application

Floor mounting17/5 - Selection and ordering data

40 mm busbar systems17/7 - Selection and ordering data

60 mm busbar systems17/9 - Selection and ordering data

Accessories17/11 - Selection and ordering data

You will find technical information atwww.siemens.com/lowvoltage/supportunder:- Technical specifications- Manuals/operating instructions- Characteristic curves- Certificates

and configurators underwww.siemens.com/lowvoltage/configurators

SENTRON Switching and Protection DevicesSwitch Disconnectors

Catalog

Technical Information

LV1N_3NP1_12_2008_eng.book Seite 1 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Introduction

17/2 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008

17

■ Overview

✓ Available

-- Not available

Type 3NP 1 forfloor mounting

3NP1 for40 mm busbar system

3NP1 for60 mm busbar system

SENTRON switch disconnectorsRated uninterrupted current Iu

At 35 °C ambient temperature A 160 up to 630 160 up to 630 160 up to 630

Rated operational voltage

Ue V 690 690 690

AC-21

At 400 V ✓ ✓ ✓

At 500 V ✓ ✓ ✓

At 690 V ✓ ✓ ✓

AC-22

At 400 V ✓ ✓ ✓

At 500 V ✓ ✓ ✓

At 690 V ✓ ✓ ✓

AC-23

At 400 V ✓ ✓ ✓

At 500 V ✓ ✓ ✓

At 690 V ✓ ✓ ✓

Switch versions

Front mounting -- -- --

Floor mounting ✓ -- --

Busbars

• 40 mm -- ✓ --

• 60 mm -- -- ✓

• 185 mm -- -- --

Molded-plastic enclosures ✓ -- --

Switch accessories

Auxiliary contact elements

• 1 NO + 1 NC -- -- --

• 1 CO ✓ ✓ ✓

Fuse monitoring

• With circuit breakers ✓ ✓ ✓

• With electronics ✓ ✓ ✓

Current transformers -- -- --

LV1N_3NP1_12_2008_eng.book Seite 2 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Introduction

17/3Siemens LV 1 N Fuse Switch Disconnectors · 12/2008

17

3NP1 fuse switch disconnector

All key product features at a glance• Box terminals available for all sizes• Connection of circular conductors and laminated conductors• Fuse monitoring possible throughout• Busbar supports can be built over• Conversion of 5 /10 mm thick busbars without parts which can

be lost or broken off• Convertibility of cable feeder at top/bottom without interven-

tion in the internal conducting paths• Optimum integration in various system environments through

cover levels and on busbar systems with/without base• Touch protection also with rear incoming unit• Fuses are removed using a release shaft without the fuses be-

ing touched• All units can be sealed and locked

Overview of components and accessory parts

SENTRON 3NP1 fuse switch disconnector

Cover support

Reach-around protection for Siemens busbar system

Reach-around protection for Rittal busbar system

Locking device

Auxiliary switch with actuator

Molded-plastic masking frame

Fuse carrier with MFM electromechanical fuse monitoring

Fuse carrier with EFM 20/25 electronic fuse monitoring

Fuse carrier with EFM 10 electronic fuse monitoring

Box terminal

Auxiliary conductor connection for box terminal

Flat connector

Auxiliary conductor connection for flat connector

Deep-drawn connection module

Prism terminal

Auxiliary conductor connection for prism terminal

Saddle terminal

Cable connection cover with rear reach-around protection

Cable connection cover

LV1N_3NP1_12_2008_eng.book Seite 3 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Introduction

17/4 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008

17

■ Benefits

Advantages during planning and configuration• Low level of equipment variance through easy convertibility of

cable feeder at top/bottom (delivered from factory with cable feeder at bottom).

• Only one device variant for applications in industry and infra-structure thanks to touch and reach-around protection as a standard feature.

• Uniform grid sizes for easy configuration.

Advantages during operation and service• The optional rear covers for the cable connections guarantee

optimum touch protection even for distribution boards with ac-cess from the rear.

• Innovative design enables the highest safety for equipment and personnel.

• Fuses can be released and removed using a release shaft.• Lockable and sealable design enables safe working and

prevents unauthorized access.

Advantages during installation• Only one device variant is required for cable feeders at

top/bottom and there is no need to intervene in the internal conducting paths.

• One device variant with very high short-circuit values dis-penses with having to order and install arc splitters to increase the electrical values.

• On all sizes it is possible to install two CO contacts for indicat-ing the switch position.

• All devices feature all-round touch protection.• Box terminals are available for all sizes and shorten the as-

sembly time appreciably.• Snapping on the sizes NH000 and NH00 shortens the mount-

ing time greatly compared to fixing with screws.• The screw-fixing method on sizes NH1, NH2 and NH3 pro-

vides for easy positioning and at the same time secure con-tacting of the larger and heavier device variants.

• Small space requirement through compact devices and bus-bar supports which can be built over.

• Device variants for busbar mounting can be converted to 5 mm or 10 mm thick busbars without parts which can be lost or broken off.

■ Application

Possible uses

3NP1 fuse switch disconnectors can be used for protecting and switching the most diverse electrical loads:• Motor starter combinations• In conjunction with SITOR fuses for the protection of frequency

converters and soft starters• Fusing of compensation modules• Cable feeders• Group fusing of small loads

The devices are optimized for use in all kinds of systemenvironments:• Low-voltage switchboards for power distribution and MCCs

(e.g. main and sub-distribution boards)• Distribution systems with cover levels of 32 and 70 mm or

45 and 70 mm• Mechanical engineering• Railway applications

Fuse monitors are used to detect, indicate and report faults:• MFM – electromechanical fuse monitoring for AC/DC networks• EFM 20 – electronic fuse monitoring with

network monitoring for AC networks• EFM 25 – electronic fuse monitoring with network monitoring

for DC networks

Standards and specifications

The 3NP1 fuse switch disconnectors are compliant with:• IEC 60947-1, EN 60947-1• IEC 60947-3, EN 60947-3

Mounting

Floor mounting

3NP1 fuse switch disconnector for floor mounting

Busbar mounting

3NP1 fuse switch disconnector for busbar mounting

System cover(alternatively)

Mounting plate

NSG0_00236

7045

NH 000, 00 NH 1, 2, 3

Mounting plateBusbar supportBusbar support

Base

Mounting on Siemens 8US busbar systems with 32/70 mm cover level

Mounting on Rittal Riline 60 busbar systems with base

70 32

NSG0_00237

LV1N_3NP1_12_2008_eng.book Seite 4 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Floor mounting

17/5Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

■ Selection and ordering data

Rated uninterrupted current Iu

LV HRC fuse links acc. to DIN 43620

DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

A Size kg

For 45 mm cover levelBasic units

3NP133-1CA20

Flat connectors

160 00 / 000 A 3NP1 133-1CA10 1 1 unit 143 0.730

Box terminals

160 000 A 3NP1 123-1CA20 1 1 unit 143 0.470

160 00 / 000 A 3NP1 133-1CA20 1 1 unit 143 0.730

With MFM electromechanical fuse monitoring

3NP1 133-1CA21

Flat connectors

160 00 / 000 A 3NP1 133-1CA11 1 1 unit 143 1.170

Box terminals

160 00 / 000 A 3NP1 133-1CA21 1 1 unit 143 1.170

With electronic EFM 20 fuse monitoring and network monitoring

3NP1 133-1CA23

Flat connectors

160 00 / 000 A 3NP1 133-1CA13 1 1 unit 143 0.870

Box terminals

160 000 A 3NP1 123-1CA23 1 1 unit 143 0.590

160 00 / 000 A 3NP1 133-1CA23 1 1 unit 143 0.870

LV1N_3NP1_12_2008_eng.book Seite 5 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Floor mounting

17/6 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Rated uninterrupted current Iu

LV HRC fuse links acc. to DIN 43620

DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

A Size kg

For 70 mm cover levelBasic units

3NP1 143-1DA20

Flat connectors

250 1 and 0 A 3NP1 143-1DA10 1 1 unit 143 2.190

400 2 and 1 A 3NP1 153-1DA10 1 1 unit 143 4.210

630 3 and 2 A 3NP1 163-1DA10 1 1 unit 143 6.310

Box terminals

250 1 and 0 A 3NP1 143-1DA20 1 1 unit 143 2.190

400 2 and 1 A 3NP1 153-1DA20 1 1 unit 143 4.660

630 3 and 2 A 3NP1 163-1DA20 1 1 unit 143 6.730

With MFM electromechanical fuse monitoring

3NP1 143-1DA21

Flat connectors

250 1 and 0 A 3NP1 143-1DA11 1 1 unit 143 2.630

400 2 and 1 A 3NP1 153-1DA11 1 1 unit 143 4.650

630 3 and 2 A 3NP1 163-1DA11 1 1 unit 143 6.750

Box terminals

250 1 and 0 A 3NP1 143-1DA21 1 1 unit 143 2.630

400 2 and 1 A 3NP1 153-1DA21 1 1 unit 143 5.100

630 3 and 2 A 3NP1 163-1DA21 1 1 unit 143 7.170

With electronic EFM 20 fuse monitoring and network monitoring

3NP1 143-1DA23

Flat connectors

250 1 and 0 A 3NP1 143-1DA13 1 1 unit 143 2.330

400 2 and 1 A 3NP1 153-1DA13 1 1 unit 143 4.350

630 3 and 2 A 3NP1 163-1DA13 1 1 unit 143 6.450

Box terminals

250 1 and 0 A 3NP1 143-1DA23 1 1 unit 143 2.330

400 2 and 1 A 3NP1 153-1DA23 1 1 unit 143 4.800

630 3 and 2 A 3NP1 163-1DA23 1 1 unit 143 6.870

LV1N_3NP1_12_2008_eng.book Seite 6 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

40 mm busbar systems

17/7Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

■ Selection and ordering data

Note:

Delivered from factory with cable feeder at bottom and convert-ible by the customer

Rated uninterrupted current Iu

LV HRC fuse links acc. to DIN 43620

DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

A Size kgFor cover level 32/70 mm, with reach-around protection for busbars and Rittal system without base

Basic units

3NP1 133-1BB20

Flat connectors

160 00 / 000 A 3NP1 133-1BB10 1 1 unit 143 0.980

Box terminals

160 000 A 3NP1 123-1BB20 1 1 unit 143 0.820

160 00 / 000 A 3NP1 133-1BB20 1 1 unit 143 0.980

With MFM electromechanical fuse monitoring

3NP1 133-1BB21

Flat connectors

160 00 / 000 A 3NP1 133-1BB11 1 1 unit 143 1.420

Box terminals

160 00/000 A 3NP1 133-1BB21 1 1 unit 143 1.420

With electronic EFM 20 fuse monitoring and network monitoring

3NP1 133-1BB23

Flat connectors

160 00 / 000 C 3NP1 133-1BB13 1 1 unit 143 1.120

Box terminals

160 000 C 3NP1 123-1BB23 1 1 unit 143 0.940

160 00 / 000 C 3NP1 133-1BB23 1 1 unit 143 1.120

LV1N_3NP1_12_2008_eng.book Seite 7 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

40 mm busbar systems

17/8 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Note:

Delivered from factory with cable feeder at bottom and convert-ible by the customer

Rated uninterrupted current Iu

LV HRC fuse links acc. to DIN 43620

DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

A Size kg

For Rittal system with baseBasic units

3NP1 133-1JB20

Flat connectors

160 00 / 000 A 3NP1 133-1JB10 1 1 unit 143 0.980

Box terminals

160 000 A 3NP1 123-1JB20 1 1 unit 143 0.820

160 00 / 000 A 3NP1 133-1JB20 1 1 unit 143 0.980

With MFM electromechanical fuse monitoring

3NP1 133-1JB21

Flat connectors

160 00 / 000 C 3NP1 133-1JB11 1 1 unit 143 1.420

Box terminals

160 00 / 000 C 3NP1 133-1JB21 1 1 unit 143 1.420

With electronic EFM 20 fuse monitoring and network monitoring

3NP1 133-1JB23

Flat connectors

160 00 / 000 C 3NP1 133-1JB13 1 1 unit 143 1.120

Box terminals

160 000 C 3NP1 123-1JB23 1 1 unit 143 0.940

160 00 / 000 C 3NP1 133-1JB23 1 1 unit 143 1.120

LV1N_3NP1_12_2008_eng.book Seite 8 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

60 mm busbar systems

17/9Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

■ Selection and ordering data

Note:

Delivered from factory with cable feeder at bottom and convert-ible by the customer

Rated uninterrupted current Iu

LV HRC fuse links acc. to DIN 43620

DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

A Size kgFor cover level 32/70 mm, with reach-around protection for busbars and Rittal Riline60 system without base

Basic units

3NP133-1BC20

Flat connectors

160 00 / 000 A 3NP1 133-1BC10 1 1 unit 143 0.980

250 1 and 0 A 3NP1 143-1BC10 1 1 unit 143 2.850

400 2 and 1 A 3NP1 153-1BC10 1 1 unit 143 4.760

630 3 and 2 A 3NP1 163-1BC10 1 1 unit 143 6.840

Box terminals

160 000 A 3NP1 123-1BC20 1 1 unit 143 0.820

160 00 / 000 A 3NP1 133-1BC20 1 1 unit 143 0.980

250 1 and 0 A 3NP1 143-1BC20 1 1 unit 143 2.850

400 2 and 1 A 3NP1 153-1BC20 1 1 unit 143 4.990

630 3 and 2 A 3NP1 163-1BC20 1 1 unit 143 7.040

With MFM electromechanical fuse monitoring

3NP133-1BC21

Flat connectors

160 00 / 000 A 3NP1 133-1BC11 1 1 unit 143 1.420

250 1 and 0 A 3NP1 143-1BC11 1 1 unit 143 3.290

400 2 and 1 A 3NP1 153-1BC11 1 1 unit 143 5.200

630 3 and 2 A 3NP1 163-1BC11 1 1 unit 143 7.280

Box terminals

160 00 / 000 A 3NP1 133-1BC21 1 1 unit 143 1.420

250 1 and 0 A 3NP1 143-1BC21 1 1 unit 143 3.290

400 2 and 1 A 3NP1 153-1BC21 1 1 unit 143 5.430

630 3 and 2 A 3NP1 163-1BC21 1 1 unit 143 7.480

With electronic EFM 20 fuse monitoring and network monitoring

3NP133-1BC23

Flat connectors

160 00 / 000 C 3NP1 133-1BC13 1 1 unit 143 1.120

250 1 and 0 C 3NP1 143-1BC13 1 1 unit 143 2.990

400 2 and 1 C 3NP1 153-1BC13 1 1 unit 143 4.900

630 3 and 2 C 3NP1 163-1BC13 1 1 unit 143 6.980

Box terminals

160 000 C 3NP1 123-1BC23 1 1 unit 143 0.940

160 00 / 000 C 3NP1 133-1BC23 1 1 unit 143 1.120

250 1 and 0 C 3NP1 143-1BC23 1 1 unit 143 2.990

400 2 and 1 C 3NP1 153-1BC23 1 1 unit 143 5.130

630 3 and 2 C 3NP1 163-1BC23 1 1 unit 143 7.180

LV1N_3NP1_12_2008_eng.book Seite 9 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

60 mm busbar systems

17/10 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Note:

Delivered from factory with cable feeder at bottom and convert-ible by the customer

Rated uninterrupted current Iu

LV HRC fuse links acc. to DIN 43620

DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

A Size kg

For Rittal Riline60 system with baseBasic units

3NP1 133-1JC20

Flat connectors

160 00 / 000 A 3NP1 133-1JC10 1 1 unit 143 0.980

250 1 and 0 A 3NP1 143-1JC10 1 1 unit 143 2.850

400 2 and 1 A 3NP1 153-1JC10 1 1 unit 143 4.760

630 3 and 2 A 3NP1 163-1JC10 1 1 unit 143 6.840

Box terminals

160 000 A 3NP1 123-1JC20 1 1 unit 143 0.820

160 00 / 000 A 3NP1 133-1JC20 1 1 unit 143 0.980

250 1 and 0 A 3NP1 143-1JC20 1 1 unit 143 2.850

400 2 and 1 A 3NP1 153-1JC20 1 1 unit 143 4.990

630 3 and 2 A 3NP1 163-1JC20 1 1 unit 143 7.040

With MFM electromechanical fuse monitoring

3NP1 133-1JC21

Flat connectors

160 00 / 000 C 3NP1 133-1JC11 1 1 unit 143 1.420

250 1 and 0 C 3NP1 143-1JC11 1 1 unit 143 3.290

400 2 and 1 C 3NP1 153-1JC11 1 1 unit 143 5.200

630 3 and 2 C 3NP1 163-1JC11 1 1 unit 143 7.280

Box terminals

160 00 / 000 C 3NP1 133-1JC21 1 1 unit 143 1.420

250 1 and 0 C 3NP1 143-1JC21 1 1 unit 143 3.290

400 2 and 1 C 3NP1 153-1JC21 1 1 unit 143 5.430

630 3 and 2 C 3NP1 163-1JC21 1 1 unit 143 7.480

With electronic EFM 20 fuse monitoring and network monitoring

3NP1 133-1JC23

Flat connectors

160 00 / 000 C 3NP1 133-1JC13 1 1 unit 143 1.120

250 1 and 0 C 3NP1 143-1JC13 1 1 unit 143 2.990

400 2 and 1 C 3NP1 153-1JC13 1 1 unit 143 4.900

630 3 and 2 C 3NP1 163-1JC13 1 1 unit 143 6.980

Box terminals

160 000 C 3NP1 123-1JC23 1 1 unit 143 0.940

160 00 / 000 C 3NP1 133-1JC23 1 1 unit 143 1.120

250 1 and 0 C 3NP1 143-1JC23 1 1 unit 143 2.990

400 2 and 1 C 3NP1 153-1JC23 1 1 unit 143 5.130

630 3 and 2 C 3NP1 163-1JC23 1 1 unit 143 7.180

LV1N_3NP1_12_2008_eng.book Seite 10 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/11Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

■ Selection and ordering data

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Size NH000 compact Connection method

3NP1 923-1BD00

Feeder terminals 16 ... 95 mm2 (1 set = 3 units) A 3NP1 923-1BD00 1 1 unit 143 0.097

3NP1 923-1BE20

Three-tier terminals for box terminal 3 x 2.5 ... 16 mm2 (1 set = 3 units)

A 3NP1 923-1BE20 1 1 unit 143 0.134

3NP1 923-1BF10

Covering caps for 1 blank space on a 3-phase busbar(1 set = 20 units)

A 3NP1 923-1BF10 1 1 unit 143 0.012

3NP1 933-1BF20

3-phase busbars for 2x NH000 (1 set = 5 units)

A 3NP1 923-1BF20 1 1 unit 143 0.268

3NP1 933-1BF30

3-phase busbars for 3x NH000(1 set = 5 units)

A 3NP1 923-1BF30 1 1 unit 143 0.436

3NP1 933-1BF40

3-phase busbars for 4x NH000(1 set = 5 units)

A 3NP1 923-1BF40 1 1 unit 143 0.650

3NP1 933-1BF50

Link rails for 3-phase busbar(1 set = 3 units)

A 3NP1 923-1BF50 1 1 unit 143 0.263

3NP1 933-1BG40

Auxiliary conductor connectionon box terminal 0.25 ... 1 mm2

(1 set = 3 units)

A 3NP1 923-1BG40 1 1 unit 143 0.004

LV1N_3NP1_12_2008_eng.book Seite 11 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/12 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Device covers

3NP1 923-1CA10

Reach-around protection for busbars, system Siemens 8US(1x at top, 1x at bottom)

A 3NP1 923-1CA10 1 1 unit 143 0.048

3NP1 923-1CA20

Reach-around protection for busbars, system Rittal (1x at top, 1x at bottom)

A 3NP1 923-1CA20 1 1 unit 143 0.053

3NP1 923-1CB00

Cable connection covers (only for busbar systems 40 mm/ 60 mm, top and bottom)

A 3NP1 923-1CB00 1 1 unit 143 0.039

3NP1 923-1CF00

Cover supports (1 set = 2 units) A 3NP1 923-1CF00 1 1 unit 143 0.012

System covers

3NP1 923-1DA00

Dimensions (HxW) 215 x 130 mm A 3NP1 923-1DA00 1 1 unit 143 0.049

Fixing kits

3NP1 923-1EA00

For 1 standard mounting rail A 3NP1 923-1EA00 1 1 unit 143 0.009

LV1N_3NP1_12_2008_eng.book Seite 12 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/13Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Auxiliary switches

3NP1 920-1FA00

1 CO contact A 3NP1 920-1FA00 1 1 unit 143 0.012

3NP1 920-1FB00

1 CO contact, solid-state compatible A 3NP1 920-1FB00 1 1 unit 143 0.012

Fuse carriers

3NP1 923-1GA00

Standard A 3NP1 923-1GA00 1 1 unit 143 0.124

3NP1 923-1GB30

With electronic EFM 20 fuse monitoring and network monitoring

A 3NP1 923-1GB30 1 1 unit 143 0.573

3NP1 923-1GB50

With electronic EFM 25 fuse monitoring A 3NP1 923-1GB50 1 1 unit 143 0.573

Locking devices

3NP1 900-1HA00

(1 set = 10 units) A 3NP1 900-1HA00 1 1 unit 143 0.006

LV1N_3NP1_12_2008_eng.book Seite 13 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/14 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Size NH00 Connection method

3NP1 933-1BA00

Saddle terminals, 1.5 ... 70 mm2 A 3NP1 933-1BA00 1 1 unit 143 0.081

3NP1 933-1BB10

Prism terminals single, 16 ... 95 mm2 A 3NP1 933-1BB10 1 1 unit 143 0.121

3NP1 933-1BC00

Connection modules for 32 mm cover level with box terminal 6 ... 70 mm2

A 3NP1 933-1BC00 1 1 unit 143 0.145

3NP1 933-1BE10

Three-tier terminals for flat connector 3 x 2.5 ... 16 mm2 (1 set = 3 units)

A 3NP1 933-1BE10 1 1 unit 143 0.087

3NP1 923-1BE20

Three-tier terminals for box terminal 3 x 2.5 ... 16 mm2 (1 set = 3 units)

A 3NP1 923-1BE20 1 1 unit 143 0.134

3NP1 933-1BG10

Auxiliary conductor connection on flat connector 0.25 ... 1 mm2

(1 set = 3 units)

A 3NP1 933-1BG10 1 1 unit 143 0.006

3NP1 933-1BG30

Auxiliary conductor connection on prism terminal 0.25 ... 1 mm2

(1 set = 3 units)

A 3NP1 933-1BG30 1 1 unit 143 0.004

3NP1 933-1BG40

Auxiliary conductor connection on box terminal 0.25 ... 1 mm2

(1 set = 3 units)

A 3NP1 933-1BG40 1 1 unit 143 0.006

LV1N_3NP1_12_2008_eng.book Seite 14 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/15Siemens LV 1 N Fuse Switch Disconnectors · 12/2008

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Device covers

3NP1 933-1CA10

Reach-around protection for busbars, system Siemens(1x at top, 1x at bottom)

A 3NP1 933-1CA10 1 1 unit 143 0.058

3NP1 933-1CA20

Reach-around protection for busbars, system Rittal (1x at top, 1x at bottom)

A 3NP1 933-1CA20 1 1 unit 143 0.044

3NP1 933-1CB00

Cable connection covers (at top and bottom) A 3NP1 933-1CB00 1 1 unit 143 0.045

3NP1 933-1CC00

Cable connection covers with rear reach-around protection in case of floor mounting (at top and bottom)

A 3NP1 933-1CC00 1 1 unit 143 0.093

3NP1 933-1CD00

Cable connection covers with rear reach-around protection in case of busbar mounting (at top and bottom)

A 3NP1 933-1CD00 1 1 unit 143 0.079

3NP1 933-1CF00

Cover supports (1 set = 2 units) A 3NP1 933-1CF00 1 1 unit 143 0.012

* You can order this quantity or a multiple thereof.

LV1N_3NP1_12_2008_eng.book Seite 15 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/16 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

System covers

3NP1 933-1DA00

Dimensions (HxW) 215 x130 mm A 3NP1 933-1DA00 1 1 unit 143 0.024

Fixing kits

3NP1 933-1EB00

For 2 standard mounting rails 125/150 mm A 3NP1 933-1EB00 1 1 unit 143 0.009

Auxiliary switches

3NP1 930-1FA00

1 CO contact A 3NP1 930-1FA00 1 1 unit 143 0.012

3NP1 930-1FB00

1 CO contact, solid-state compatible A 3NP1 930-1FB00 1 1 unit 143 0.012

LV1N_3NP1_12_2008_eng.book Seite 16 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/17Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Fuse carriers

3NP1 933-1GA00

Standard A 3NP1 933-1GA00 1 1 unit 143 0.165

3NP1 933-1GB10

With MFM electromechanical fuse monitoring A 3NP1 933-1GB10 1 1 unit 143 1.293

3NP1 933-1GB30

With electronic EFM 20 fuse monitoring and network monitoring

A 3NP1 933-1GB30 1 1 unit 143 0.611

3NP1 933-1GB50

With electronic EFM 25 fuse monitoring A 3NP1 933-1GB50 1 1 unit 143 0.611

Locking devices

3NP1 900-1HA00

(1 set = 10 units) A 3NP1 900-1HA00 1 1 unit 143 0.006

LV1N_3NP1_12_2008_eng.book Seite 17 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/18 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price € per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Size NH1 Connection method

3NP1 943-1BA00

Saddle terminals, 70 ... 150 mm2 (1 set = 3 units)

A 3NP1 943-1BA00 1 1 unit 143 0.144

3NP1 943-1BB10

Prism terminals single, 70 ... 150 mm2 (1 set = 3 units)

A 3NP1 943-1BB10 1 1 unit 143 0.270

3NP1 943-1BB20

Prism terminals double, 2 x 35 ... 70 mm2 (1 set = 3 units)

A 3NP1 943-1BB20 1 1 unit 143 0.311

3NP1 943-1BG10

Auxiliary conductor connection on flat connector 0.25 ... 1 mm2 (1 set = 3 units)

A 3NP1 943-1BG10 1 1 unit 143 0.009

3NP1 943-1BG30

Auxiliary conductor connection on saddle or prism terminal 0.25 ... 1 mm2 (1 set = 3 units)

A 3NP1 943-1BG30 1 1 unit 143 0.004

3NP1 943-1BG40

Auxiliary conductor connection on box terminal 0.25 ... 1 mm2 (1 set = 3 units)

A 3NP1 943-1BG40 1 1 unit 143 0.014

LV1N_3NP1_12_2008_eng.book Seite 18 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/19Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Device covers

3NP1 943-1CA10

Reach-around protection for busbar mounting, system Siemens 8US (1x at top, 1x at bottom)

A 3NP1 943-1CA10 1 1 unit 143 0.024

3NP1 943-1CA20

Reach-around protection for busbar mounting, system Rittal (1x at top, 1x at bottom)

A 3NP1 943-1CA20 1 1 unit 143 0.034

3NP1 943-1CB00

Cable connection covers (at top and bottom) A 3NP1 943-1CB00 1 1 unit 143 0.172

3NP1 943-1CD00

Cable connection covers with rear reach-around protection (at top and bottom)

A 3NP1 943-1CD00 1 1 unit 143 0.277

3NP1 943-1CF00

Cover supports (1 set = 2 units) A 3NP1 943-1CF00 1 1 unit 143 0.026

LV1N_3NP1_12_2008_eng.book Seite 19 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/20 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

System covers

3NP1 943-1DA00

Dimensions (HxW) 375 x220 mm A 3NP1 943-1DA00 1 1 unit 143 0.092

Fixing kits

3NP1 943-1EB00

For 2 standard mounting rails 125/150 mm A 3NP1 943-1EB00 1 1 unit 143 0.017

Auxiliary switches

3NP1 940-1FA00

1 CO contact A 3NP1 940-1FA00 1 1 unit 143 0.018

3NP1 940-1FB00

1 CO contact, solid-state compatible A 3NP1 940-1FB00 1 1 unit 143 0.018

LV1N_3NP1_12_2008_eng.book Seite 20 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/21Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Fuse carriers

3NP1 943-1GA00

Standard A 3NP1 943-1GA00 1 1 unit 143 0.602

3NP1 943-1GB10

With MFM electromechanical fuse monitoring A 3NP1 943-1GB10 1 1 unit 143 1.726

3NP1 943-1GB30

With electronic EFM 20 fuse monitoring and network monitoring

A 3NP1 943-1GB30 1 1 unit 143 1.044

3NP1 943-1GB520

With electronic EFM 25 fuse monitoring A 3NP1 943-1GB50 1 1 unit 143 1.044

Locking devices

3NP1 900-HA00

(1 set = 10 units) A 3NP1 900-1HA00 1 1 unit 143 0.006

LV1N_3NP1_12_2008_eng.book Seite 21 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/22 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Size NH2 Connection method

3NP1 953-1BA00

Saddle terminals, 120 ... 240 m2 (1 set = 3 units)

A 3NP1 953-1BA00 1 1 unit 143 0.187

3NP1 953-1BB10

Prism terminals single, 120 ... 240 m2 (1 set = 3 units)

A 3NP1 953-1BB10 1 1 unit 143 0.420

3NP1 953-1BB20

Prism terminals double, 2 x 70 ... 120 mm2 (1 set = 3 units)

A 3NP1 953-1BB20 1 1 unit 143 0.473

3NP1 943-1BG10

Auxiliary conductor connection on flat connector 0.25 ... 1 mm2 (1 set = 3 units)

A 3NP1 943-1BG10 1 1 unit 143 0.009

3NP1 953-1BG30

Auxiliary conductor connectionon saddle or prism terminal 0.25 ... 1 mm2 (1 set = 3 units)

A 3NP1 953-1BG30 1 1 unit 143 0.006

3NP1 953-1BG40

Auxiliary conductor connectionon box terminal 0.25 ... 1 mm2 (1 set = 3 units)

A 3NP1 953-1BG40 1 1 unit 143 0.029

LV1N_3NP1_12_2008_eng.book Seite 22 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/23Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Device covers

3NP1 953-1CA10

Reach-around protection for busbar mounting, system Siemens 8US (1x at top, 1x at bottom)

A 3NP1 953-1CA10 1 1 unit 143 0.028

3NP1 953-1CA20

Reach-around protection for busbar mounting, system Rittal (1x at top, 1x at bottom)

A 3NP1 953-1CA20 1 1 unit 143 0.038

3NP1 953-1CB00

Cable connection covers (at top and bottom) A 3NP1 953-1CB00 1 1 unit 143 0.242

3NP1 953-1CD00

Cable connection covers with rear reach-around protection (at top and bottom)

A 3NP1 953-1CD00 1 1 unit 143 0.362

3NP1 943-1CF00

Cover supports (1 set = 2 units) A 3NP1 943-1CF00 1 1 unit 143 0.026

System covers

3NP1 953-1DA00

Dimensions (HxW) 375 x 245 mm A 3NP1 953-1DA00 1 1 unit 143 0.097

LV1N_3NP1_12_2008_eng.book Seite 23 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/24 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Auxiliary switches

3NP1 940-1FA00

1 CO contact A 3NP1 940-1FA00 1 1 unit 143 0.018

3NP1 940-1FB000

1 CO contact, solid-state compatible A 3NP1 940-1FB00 1 1 unit 143 0.018

Fuse carriers

3NP1 953-1GA00

Standard A 3NP1 953-1GA00 1 1 unit 143 0.754

3NP1 953-1GB10

With MFM electromechanical fuse monitoring A 3NP1 953-1GB10 1 1 unit 143 1.797

3NP1 953-1GB30

With electronic EFM 20 fuse monitoring and network monitoring

A 3NP1 953-1GB30 1 1 unit 143 1.115

3NP1 953-1GB50

With electronic EFM 25 fuse monitoring A 3NP1 953-1GB50 1 1 unit 143 1.115

Locking devices

3NP1 900-1HA00

(1 set = 10 units) A 3NP1 900-1HA00 1 1 unit 143 0.006

LV1N_3NP1_12_2008_eng.book Seite 24 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/25Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Size NH3 Connection method

3NP1 963-1BA00

Saddle terminals, 150 ... 300 m2 (1 set = 3 units)

A 3NP1 963-1BA00 1 1 unit 143 0.210

3NP1 963-1BB10

Prism terminals single, 150 ... 300 m2 (1 set = 3 units)

A 3NP1 963-1BB10 1 1 unit 143 0.643

3NP1 963-1BB20

Prism terminals double, 2 x 150 ... 185 mm2 (1 set = 3 units)

A 3NP1 963-1BB20 1 1 unit 143 0.681

3NP1 943-1BG10

Auxiliary conductor connection on flat connector 0.25 ... 1 mm2 (1 set = 3 units)

A 3NP1 943-1BG10 1 1 unit 143 0.009

3NP1 953-1BG30

Auxiliary conductor connectionon saddle or prism terminal 0.25 ... 1 mm2 (1 set = 3 units)

A 3NP1 953-1BG30 1 1 unit 143 0.006

3NP1 953-1BG40

Auxiliary conductor connection on box terminal 0.25 ... 1 mm2 (1 set = 3 units)

A 3NP1 953-1BG40 1 1 unit 143 0.029

LV1N_3NP1_12_2008_eng.book Seite 25 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/26 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Device covers

3NP1 963-1CA10

Reach-around protection for busbar mounting, system Siemens 8US (1x at top, 1x at bottom)

A 3NP1 963-1CA10 1 1 unit 143 0.032

3NP1 963-1CA20

Reach-around protection for busbar mounting, system Rittal (1x at top, 1x at bottom)

A 3NP1 963-1CA20 1 1 unit 143 0.043

3NP1 963-1CB00

Cable connection covers (at top and bottom) A 3NP1 963-1CB00 1 1 unit 143 0.269

3NP1 963-1CD00

Cable connection covers with rear reach-around protection (at top and bottom)

A 3NP1 963-1CD00 1 1 unit 143 0.411

3NP1 943-1CF00

Cover supports (1 set = 2 units) A 3NP1 943-1CF00 1 1 unit 143 0.026

System covers

3NP1 963-1DA00

Dimensions (HxW) 375 x 290 mm A 3NP1 963-1DA00 1 1 unit 143 0.116

LV1N_3NP1_12_2008_eng.book Seite 26 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A3NP1 for Industrial Applications and Power Distribution

Accessories

17/27Siemens LV 1 N Fuse Switch Disconnectors · 12/2008* You can order this quantity or a multiple thereof.

17

Version DT Order No. Price per PU

PU (UNIT, SET, M)

PS* PG Weight per PU approx.

kg

Auxiliary switches

3NP1 940-1FA00

1 CO contact A 3NP1 940-1FA00 1 1 unit 143 0.018

3NP1 940-1FB00

1 CO contact, solid-state compatible A 3NP1 940-1FB00 1 1 unit 143 0.018

Fuse carriers

3NP1 963-1GA00

Standard A 3NP1 963-1GA00 1 1 unit 143 0.825

3NP1 963-1GB10

With MFM electromechanical fuse monitoring A 3NP1 963-1GB10 1 1 unit 143 1.966

3NP1 963-1GB30

With electronic EFM 20 fuse monitoring and network monitoring

A 3NP1 963-1GB30 1 1 unit 143 1.284

3NP1 963-1GB50

With electronic EFM 25 fuse monitoring A 3NP1 963-1GB50 1 1 unit 143 1.284

Locking devices

3NP1 900-1HA00

(1 set = 10 units) A 3NP1 900-1HA00 1 1 unit 143 0.006

LV1N_3NP1_12_2008_eng.book Seite 27 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

3NP Fuse Switch Disconnectors up to 630 A

Notes

17/28 Siemens LV 1 N Fuse Switch Disconnectors · 12/2008

17

LV1N_3NP1_12_2008_eng.book Seite 28 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

Appendix

Conditions of sale and deliveryExport regulations

17/29

■ Terms and Conditions of Sale and Delivery

By using this catalog you can acquire hardware and software products described therein from Siemens AG subject to the fol-lowing terms. Please note! The scope, the quality and the condi-tions for supplies and services, including software products, by any Siemens entity having a registered office outside of Ger-many, shall be subject exclusively to the General Terms and Conditions of the respective Siemens entity. The following terms apply exclusively for orders placed with Siemens AG.

For customers with a seat or registered office in GermanyThe “General Terms of Payment” as well as the “General Condi-tions for the Supply of Products and Services of the Electrical and Electronics Industry” shall apply.For software products, the “General License Conditions for Soft-ware Products for Automation and Drives for Customers with a Seat or registered Office in Germany” shall apply.

For customers with a seat or registered office outside of GermanyThe “General Terms of Payment” as well as the “General Condi-tions for Supplies of Siemens, Automation and Drives for Cus-tomers with a Seat or registered Office outside of Germany” shall apply.For software products, the “General License Conditions for Soft-ware Products for Automation and Drives for Customers with a Seat or registered Office outside of Germany” shall apply.

GeneralThe dimensions are in mm. In Germany, according to the Ger-man law on units in measuring technology, data in inches only apply to devices for export. Illustrations are not binding.Insofar as there are no remarks on the corresponding pages, - especially with regard to data, dimensions and weights given - these are subject to change without prior notice.The prices are in € (Euro) ex works, exclusive packaging.The sales tax (value added tax) is not included in the prices. It shall be debited separately at the respective rate according to the applicable legal regulations.Prices are subject to change without prior notice. We will debit the prices valid at the time of delivery.Surcharges will be added to the prices of products that contain silver, copper, aluminum, lead and/or gold if the respective basic official prices for these metals are exceeded. These surcharges will be determined based on the official price and the metal fac-tor of the respective product.The surcharge will be calculated on the basis of the official price on the day prior to receipt of the order or prior to the release order.The metal factor determines the official price as of which the metal surcharges are charged and the calculation method used. The metal factor, provided it is relevant, is included with the price information of the respective products.

An exact explanation of the metal factor and the text of the Comprehensive Terms and Conditions of Sale and Delivery are available free of charge from your local Siemens business office under the following Order Nos.:• 6ZB5310-0KR30-0BA1

(for customers based in Germany)• 6ZB5310-0KS53-0BA1

(for customers based outside Germany)or download them from the Internethttp://www.siemens.com/automation/mall (Germany: A&D Mall Online-Help System)

■ Export regulations

The products listed in this catalog / price list may be subject to European / German and/or US export regulations.Therefore, any export requiring a license is subject to approval by the competent authorities.According to current provisions, the following export regulations must be observed with respect to the products featured in this catalog / price list:

Even without a label or with an “AL: N” or “ECCN: N”, authoriza-tion may be required due to the final destination and purpose for which the goods are to be used. The deciding factors are the AL or ECCN export authorization indicated on order confirmations, delivery notes and invoices.Errors excepted and subject to change without prior notice.

A&D/VuL_ohne MZ/En 05.09.06

AL Number of the German Export ListProducts marked other than “N” require an export license. In the case of software products, the export des-ignations of the relevant data medium must also be generally adhered to.Goods labeled with an “AL“ not equal to “N” are subject to a European or German export authori-zation when being exported out of the EU.

ECCN Export Control Classification NumberProducts marked other than “N” are subject to a reexport license to specific countries.In the case of software products, the exportdesignations of the relevant data medium must also be generally adhered to.Goods labeled with an “ECCN“ not equal to “N” are subject to a US re-export authorization.

LV1N_3NP1_12_2008_eng.book Seite 29 Montag, 19. Januar 2009 2:08 14

© Siemens AG 2009

Get more information

Low-Voltage Controls and Distribution:www.siemens.com/lowvoltage

The information provided in this catalog contains descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. Availability and technical specifications are subject to change without notice.All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners.www.siemens.com/automation

Subject to change without prior noticePDF only: (E86060-K1002-A241-A1-7600)3P.8103.50.26KG 1208 38 En© Siemens AG 2009

Siemens AGIndustry SectorIndustrial Automation SystemsPostfach 48 4890026 NÜRNBERGGERMANY

© Siemens AG 2009