    ASustainableRefrigeratingSystem

    forthePRWIndustry

    2012Heartland

    Chapter

    Meeting

    Chicago,IL.October34,2012

    CascadeCO2

    /NH3

    Refrigeration

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    2/34

    RefrigerationThen

    1924 Ball Horizontal Dual Acting Compressor

    2

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    3/34

    RefrigerationThen

    Rotary Blade Booster

    Compressors

    Reciprocating High Stage

    Compressors

    3

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    4/34

    RefrigerationNow

    Screw Compressor and Reciprocating Compressor

    4

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    5/34

    ModernRefrigerationEngine

    Room

    Cascade CO2/NH3 System

    5

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    6/34

    ShouldIChoseCO2

    (R744)formyRefrigerating

    System? Whattemperaturesdoyouneedtomaintain?

    Arethereproductfreezingrequirements?

    IsmaintainingareducedAmmoniasystem

    chargecritical?

    Isno

    contaminating

    refrigerants

    in

    the

    food

    storage,processingandemployeeworkareas

    desirableor

    needed?

    And,isprovidingaGreen

    refrigeration

    system

    important?

    6

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    7/34

    RefrigerationSystem FirstCost

    SingleStageEconomizedSystem(Lowest)

    CascadeCO2

    /NH3

    System(Mid

    Range)

    TwoStageAmmoniaSystem(Highest)

    7

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    8/34

    Independent3rd

    PartyStudySystem Efficiency Results

    Cascade CO2 vs. Two Stage NH3

    8

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    9/34

    Independent3rd

    PartyStudy

    2StageNH3

    Reference

    System[kW/TR]

    CO2/NH3

    CascadeSystem

    [kW/TR]

    %Improvement

    InEfficiency

    20FSuctionGroup 0.8 0.7 12.3

    58FSuctionGroup 1.6 1.0 37.3

    Combined

    20Fand

    58F

    Suction

    Groups 1.2 0.9 28.7

    HighTempSuctionGroup 0.7 0.8 8.5

    TotalSystemkW/TR(Compressors) 1.7 1.6 8.1

    Total

    System

    kW/TR

    (Compressors

    and

    Condenser) 1.9 1.8 6.8

    TotalSystemkW/TR(Compressors,

    CondenserandAirUnits) 2.4 2.3 5.8

    System Efficiency Results

    Cascade CO2 vs. Two Stage NH3

    9

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    10/34

    FieldTestMeasurement/Instrumentation

    Flow Meters

    10

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    11/34

    CO2

    SystemAdvantagesOperating

    0.80

    1.00

    1.20

    1.40

    1.60

    1.80

    2.00

    2.20

    -70 -65 -60 -55 -50 -45 -40 -35 -30 -25 -20

    COP

    Evaporating temp [deg F]

    COP comparison of CO2/Ammonia withconventionel Ammonia Systems at full load

    CO2/AmmoniaDT cascade = 9F

    Single stage withopen economizer

    Two stage withopen inter-midiate cooler

    11

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    12/34

    CO2

    SystemAdvantagesOperating

    COP comparison of CO2/Ammonia with

    conventionel Ammonia Systems at 50% load

    0.40

    0.60

    0.80

    1.00

    1.20

    1.40

    1.60

    1.80

    2.00

    2.20

    2.40

    -65 -60 -55 -50 -45 -40 -35 -30 -25 -20

    Evaporating temp [deg F]

    COP

    CO2/Ammonia

    DT cascade = 6F

    Single stage with

    open economizer

    Two stage with

    open inter-

    midiate cooler

    12

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    13/34

    CO2

    SystemAdvantagesOperating

    13

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    14/34

    CO2

    SystemAdvantagesOperating

    14

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    15/34

    CO2

    SystemAdvantagesOperating

    15

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    16/34

    RefrigerationSystem

    Ammoniacompressor

    CO2

    compressor

    Ammoniacondenser

    CO2

    /NH3

    heatexchanger(cascade

    cooler)

    CO2

    receiver(pump

    separator)

    CO2

    evaporator

    CO2

    liquidpump

    16

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    17/34

    CO2

    Application ColdStorage

    NH3 Surge

    Drum

    NH3 Screw

    11 / 95F

    Evap. Condenser

    CP-Receiver

    (Economizer)NH3/CO2 Cascade

    Heat Exchangers

    CO2

    VPR

    -55F

    CO2

    VPR

    -30F

    Blast FreezerFreezer

    NH3 Screw

    11 / 95F

    CO2 HPR

    20FCO2 Recip

    -55/ 20F

    CO2 Recip-55/ 20F

    CO2 Recip

    -30/ 20F

    CO2 Recip-30/ 20F

    Drier

    CoolerDock

    OilRectifier

    OilRectifie

    r

    17

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    18/34

    CO2

    SystemsBackgroundDrivers

    Refrigerantsituation

    Ammoniacharge

    restrictions

    Ammoniasdamagingeffects

    Electricity

    costs Lowerfirstcost

    Refrigerant

    cost Lowertemperaturesatreasonablecosts

    Lessspacerequired

    18

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    19/34

    CO2

    SystemsFactsonCO2

    (R744)

    CO2

    isalreadyintheatmosphere

    CO2

    isnon

    toxic

    and

    non

    flammable

    CO2

    isusedtoputoutfires

    A

    major

    leak

    will

    not

    damage

    products OnlyCO2

    snow(DryIce)willfalldownon

    products

    Dryicesublimatetovaporandwillnotleavea

    wetsurface

    19

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    20/34

    CO2

    SystemsFactsOnEmissions

    CO2CascadeSystemsreduceCO2emission

    lb.less

    CO2emission

    for

    each

    kWh

    saved

    1mileinanaveragecarproducesonepound

    ofCO2

    emission

    Cryogenicfreezingtypicallyuses2lbs.ofCO2

    foreachpoundofproductfrozen

    InaCO2cascadesystemstheCO2

    iskept

    insidetheclosedloop

    20

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    21/34

    CO2

    SystemAdvantagesLowerFirstCost

    LowerCosts

    Compressors(LTside)

    Suctionanddischargepiping,valvesinsulation,etc.

    Liquidseparatorvessels(plusinsulation)

    Refrigerant HigherCosts

    Cascadeheatexchangerinsteadofintermediatecooler

    vessel Liquidpiping,valvesinsulation,etc.

    Higherpressureratingforsomecomponents

    21

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    22/34

    CO2

    SystemAdvantagesLowerFirstCost

    0.3

    3.0

    30

    300

    -67 -58 -49 -40 -31

    Evaporating temperature (o

    F)

    Capacity(TR)

    CO2

    NH3

    HighPressureCompressor

    HPO28

    StandardCompressor

    CMO28

    Condensing temperature at 14oF

    22

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    23/34

    CO2

    SystemAdvantagesLowerFirstCost

    Liquid, 300ft pipeLiquid, 300ft pipe

    Pipe sizePipe size TemperatureTemperaturedropdrop

    PressurePressuredropdrop

    VelocityVelocity

    InchInch FF PSIPSI ft / secft / sec

    AmmoniaAmmonia 22"" 1.41.4 1.41.4 3.63.6

    CO2CO2 4"4" 0.30.3 1.051.05 3.53.5

    Discharge, 100ft pipeDischarge, 100ft pipe

    Pipe sizePipe size TemperatureTemperaturedropdrop

    PressurePressuredropdrop

    VelocityVelocity

    InchInch FF PSIPSI ft / secft / sec

    AmmoniaAmmonia 6"6" 0.210.21 0.20.2 7979

    CO2CO2 4"4" 0.140.14 0.90.9 2929

    Wet suction, 300ft pipe, two 90 bends, one stop valveWet suction, 300ft pipe, two 90 bends, one stop valve

    Pipe sizePipe size TemperatureTemperaturedropdrop

    PressurePressuredropdrop

    VelocityVelocity

    InchInch FF PSIPSI ft / secft / sec

    AmmoniaAmmonia 12"12" 1.011.01 0.310.31 5454

    CO2CO2 6"6" 0.960.96 2.852.85 2323

    Dry suction, 100ft pipe, two 90 bends, one stop valveDry suction, 100ft pipe, two 90 bends, one stop valve

    Pipe sizePipe size TemperatureTemperaturedropdrop

    PressurePressuredropdrop

    VelocityVelocity

    InchInch FF PSIPSI ft / secft / sec

    AmmoniaAmmonia 12"12" 0.290.29 0.0890.089 6868

    CO2CO2 6"6" 0.330.33 11 3939

    Piping example 300TR at -40F

    23

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    24/34

    CO2

    SystemAdvantagesCharge/Leaks

    Lowammoniacharge

    Ammonialimitedtoengineroom

    CO2

    doesnotdamageproducts

    CO2

    isnontoxicandnonflammable

    However!!

    Longtermexposurelimitis1%concentrationofCO2

    Shorttermexposurelimitis3%concentrationofCO2

    10 20%concentrationofCO2

    ishealthandlife

    threatening

    CO2

    detectors

    are

    required24

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    25/34

    CO2

    SystemAdvantages

    Service/Maint. Norecoveryunitorwaterbasinsrequiredforopening

    systemcomponent

    Nosmell

    NooildrainageonCO2

    side

    Alwayspositiveoperatingpressure

    However!!

    Becarefulwithtrappedliquid.Ifthetemperatureisincreasedby

    7F,thepressureincreasestotheyieldlimitofsteelpipes!

    Becareful

    with

    trapped

    liquid/gas.

    Saturated

    liquid/gas

    at

    room

    temperature e.g.68F=812 PSIG

    Componentevacuationforair/moisturerequiredafterservice

    25

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    26/34

    CO2

    SystemAdvantagesValveGroups

    Penthouses,

    piping and valvegroups on roof

    26

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    27/34

    CO2

    SystemAdvantagesPiping

    Condenserand

    mainpiping

    on

    roof

    27

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    28/34

    CO2

    RefrigerationSystems

    CO2

    Compressors

    8cyl.206TR

    4cyl.103TR

    28

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    29/34

    CO2

    RefrigerationSystems

    Ammonia

    Compressors

    Screw222TR

    Screw

    307

    TR

    Applications Typ. Cold Storage - Example

    29

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    30/34

    CO2

    RefrigerationSystems

    NH3

    Surge

    Acc.CascadeCO2Condenser

    HPR&

    LPR

    Applications Typ. Cold Storage - Example

    30

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    31/34

    CO2

    RefrigerationSystems

    Economizer(CPR)

    Glycolfloorwarming

    heatedbyoilcoolers

    CO2

    HPR

    (Highpressure

    receiver)

    Applications Typ. Cold Storage - Example

    31

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    32/34

    CO2

    RefrigerationSystems

    Oil Rectifier

    Oil reservoir

    Oil heater and

    Temp. sensor

    Oil return

    Oil float switch

    Applications Typ. Cold Storage - Example

    32

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    33/34

    CO2

    RefrigerationSystems

    Large PRWs utilizing Cascade

    CO2

    Refrigerating Systems

    33

  • 7/25/2019 Cascade Co2_nh3 Refrigeration

    34/34

    CCCCCCCCCCCCCCCCCCCCRRRRCCC

    CCCCCCCCCCCCCCCCCCCLLLLCCCCCCCCCCCCCCCCCCCCCCCCCCCLLLLLL

    LUCK

    ThankYou

    ChuckToogood

    M&MRefrigeration,

    Inc.

    [email protected]

    (410)7548005

    34