Campbell Boston Market... · waste & vent piping plan fs tie into nearest vent v ... pipe below...
Transcript of Campbell Boston Market... · waste & vent piping plan fs tie into nearest vent v ... pipe below...
SCALE: 1/4" = 1'-0"
WASTE & VENT PIPING PLAN
FS
TIE INTO
NEAREST VENT
V
1-1/2"
TIE INTO
NEAREST VENT
V
1-1/2"
TIE INTO
NEAREST VENT
V
1-1/2"
FD
TD
FS
FS
FS
1
KEY NOTES
INDICATED BY SYMBOLS , , ETC.
1. REUSE EXISTING DRAIN AND VENT LINES
SERVING EXISTING HAND SINK FOR NEW
HAND SINK.
2. EXISTING FLOOR DRAIN/FLOOR SINK TO
REMAIN.
3. EXISTING FLOOR DRAIN/FLOOR SINK TO BE
REMOVED. CAP WASTE LINE BELOW SLAB
AND REPAIR SLAB PER ARCHITECT'S
DIRECTION.
4. EXISTING FLOOR CLEANOUT TO REMAIN.
5. EXISTING FLOOR CLEANOUT TO BE
REMOVED. EXTEND WASTE LINE TO NEW
CLEANOUT LOCATION. REPAIR SLAB PER
ARCHITECT'S DIRECTION.
6. EXISTING 4" GREASE WASTE LINE.
7. EXISTING 4" SANITARY WASTE LINE.
GENERAL NOTES
1. ALL PLUMBING WORK SHALL COMPLY WITH
THE 2009 EDITION OF THE INTERNATIONAL
PLUMBING CODE.
2. DRAWING IS DIAGRAMMATIC AND IS NOT TO
BE SCALED. REFER TO ARCHITECTURAL
PLANS AND FIELD CONDITIONS FOR
DIMENSIONS.
3. SEE SPECIFICATIONS FOR PIPING, VALVE
AND INSULATION REQUIREMENTS.
4. PLUMBING FIXTURES ARE TO BE
FURNISHED COMPLETE WITH ALL
NECESSARY STOPS, TRAPS, TAILPIECES,
TRIM, ETC.
5. PROVIDE WATER HAMMER ARRESTERS ON
THE SUPPLY PIPING (CW & HW) WHERE
INDICATED ON THE PLAN. ARRESTERS
SHALL BE SIOUX CHIEF MODEL 652-A OR
EQUAL. INSTALL ARRESTERS PER THE
MANUFACTURER'S RECOMMENDATIONS.
THE ARRESTERS SHALL BE RATED FOR
INSTALLATION IN CONCEALED LOCATIONS.
CAPPED AIR CHAMBERS ARE NOT
ALLOWED.
6. ALL HOT AND COLD WATER SUPPLY PIPING
CONNECTION TO FIXTURES ARE TO BE 1/2",
UNLESS NOTED OTHERWISE.
7. THE CONTRACTOR SHALL COORDINATE
WITH ALL OTHER CONTRACTORS AND
SUBCONTRACTORS IN LAYING OUT AND
INSTALLING HIS WORK. COORDINATION
DOES NOT MEAN "I WAS HERE FIRST".
8. THE CONTRACTOR IS RESPONSIBLE FOR
INSTALLING A COMPLETE AND OPERABLE
SYSTEM IN ACCORDANCE WITH THE INTENT
OF THE PLANS, WHETHER OR NOT EVERY
ELEMENT THEREOF IS SPECIFICALLY
CALLED OUT.
9. ALL FLOOR DRAINS, FLOOR SINKS AND
INTERIOR CLEANOUTS SHALL BE INSTALLED
FLUSH WITH FINISHED FLOOR COVERING.
FLOOR SHALL NOT BE SLOPED TO DRAIN
UNLESS SPECIFICALLY INDICATED ON THE
PLANS.
2
P08
P09
P10
P11
P11
P11
P14
P15
P16
1
S
KW
3
2
2
3
3
3
3
3
3
2
4
2
4
2
2
2
CO KW
6
6
7
S
KW
S
KW
S
KW
KW
KW
S
SS
KW
KW
S
KW
5
7
6
KW
TD
KW
V
1-1/2"
1
PROJECT:
Design. Spaces. People.
Fort Worth, Texas 76104
www.qarch.comfx. (817) 738-9524ph. (817) 738-8095
707 W. Vickery Blvd. #101
SOLICITATION ISSUE
04/15/16 95% SUBMITTAL
CDI
ARMY AND AIR FORCE EXCHANGE SERVICE
CONVERT :
TO BOSTON MARKET /
QDOBA
FT. CAMPBELL, KY
SCALE:
AFFES NO:
DATE:
2146-15-000007
AS NOTED
SHEET:
DRAWING TITLE:
DRAWING PROJ. NO.
16014
23 JULY 2016
05/23/16
SOLICITATION
ISSUE
CDI
06-23/16ADDENDUM #1
CDI
P-101
WASTE & VENT
PIPING PLAN
SCALE: 1/4" = 1'-0"
SUPPLY PIPING PLAN
RE-USE EXISTING
FW CONNECTION
1
KEY NOTES
INDICATED BY SYMBOLS , , ETC.
1. CONNECT TO EXISTING FILTERED WATER
LINE OF 1/2" OR LARGER AT EXISTING
WATER FILTER.
2. EXISTING 1" GAS LINE DOWN THROUGH
ROOF AT 7" W.C. CONNECT NEW 1" GAS LINE
BELOW ROOF PENETRATION.
3. CONNECT TO NEAREST GAS LINE ON ROOF
AT 5 PSI, 1" OR LARGER.
4. GAS PRESSURE REGULATOR ON ROOF. 5
PSI INLET PRESSURE TO 7" W.C. OUTLET
PRESSURE.
5. 1-1/4" GAS LINE DOWN THROUGH ROOF.
PROVIDE PITCH PAN AND PROPERLY SEAL
ROOF PENETRATION.
6. REUSE EXISTING 1/2" CW AND HW LINES
SERVING EXISTING HAND SINK FOR NEW
HAND SINK.
7. EXISTING 2" CW AND EXISTING 1" HW (140)
LINES.
8. THERMOSTATIC MIXING VALVE, LEONARD
MODEL 270-LF OR EQUIVALENT.
9. THIS SINK IS PROVIDED WITH TEMPERED
HW AND DOES NOT REQUIRE AN INDIVIDUAL
MIXING VALVE PER THE CONNECTION
SCHEDULE.
PLUMBING LEGEND
2
P04 P03
P01
P02
P05
P05
P05
P06
G01 G03 G02
P12
P13
G04
G06
G05
2
1"
3/4" 3/4"
G
G G
CW
FD
CO
R
COLD WATER
HOT WATER
BUILDING WASTE/SEWER
KITCHEN WASTE
VENT
GAS
EXISTING PIPE
PIPE BELOW GRADE
PIPING CONTINUATION
ELBOW UP
ELBOW DOWN
TEE
TEE UP
TEE DOWN
BALL VALVE
FLOOR DRAIN
CLEANOUT
GAS PRESSURE REGULATOR
HW
S
KW
V
G
WATER HAMMER ARRESTOR
FLOOR SINK
WALL CLEANOUT
WCO
ELBOW
FILTERED WATERFW
DENOTES "CONNECT TO
EXISTING"
R
CW
HW (140)
3
4
5
1"1-1/4" 1"
6
CW
HW (140)
CW
HW (140)
CW
HW
CW
HW
7
FW FW FW
FW
FW
FW
HW
CW
7
TEMPERING VALVE
1/2"
8
3/4"
3/4" 1"
3/4"
1"
1
9
3
R
3/4"
MAU-1
4
1
PROJECT:
Design. Spaces. People.
Fort Worth, Texas 76104
www.qarch.comfx. (817) 738-9524ph. (817) 738-8095
707 W. Vickery Blvd. #101
SOLICITATION ISSUE
04/15/16 95% SUBMITTAL
CDI
ARMY AND AIR FORCE EXCHANGE SERVICE
CONVERT :
TO BOSTON MARKET /
QDOBA
FT. CAMPBELL, KY
SCALE:
AFFES NO:
DATE:
2146-15-000007
AS NOTED
SHEET:
DRAWING TITLE:
DRAWING PROJ. NO.
16014
23 JULY 2016
05/23/16
SOLICITATION
ISSUE
CDI
06-23/16ADDENDUM #1
CDI
P-102
SUPPLY PIPING
PLAN
3309
KITCHEN PLUMBING REQUIREMENT SCHEDULE
MARK ITEM SIZE LOCATION SERVICE TOA.F.F. REMARKS
P01
P02
P03
1. PIPE DRAIN INDIRECT TO FLOOR SINK/DRAIN. SEE KITCHEN EQUIPMENT PLANS FOR EQUIPMENT
LOCATIONS AND INDIRECT DRAIN SIZES.
2. REFERENCE DETAIL 1/P201.
3. TEE AT VALVE AND MAKE FINAL CONNECTION TO (2) DISPENSER.
4. INSTALL MANUAL VALVE AND AUTOMATIC VALVE (FIRE SUPPRESSION SYSTEM ACTUATED)BELOW CEILING.
INSTALL A GAS COCK FOR EACH APPLIANCE.
5. PROVIDE SHUT-OFF VALVE AND PROVIDE FINAL CONNECTION.
6. REFERENCE DETAIL 4/P201.
7. TEE AT WALL PENETRATION AT ROUGH IN TO TWO 3/4" CONNECTIONS.
8. PROVIDE POINT OF USE THERMOSTATIC MIXING VALVE LEONARD MODEL 170-LF OR EQUIVALENT.
9. PROVIDE POINT OF USE THERMOSTATIC MIXING VALVE LEONARD MODEL 270-LF OR EQUIVALENT.
REMARKS
P04
P05
P06
P07
P08
P09
P10
P11
G01
GENERAL NOTES
1. ALL EQUIPMENT IS AAFES FURNISHED/CONTRACTOR INSTALLED.
1/4"
WALL
HOT WATER DISPENSER
50"
-
4,7
-
G02
G03
5
5,8
5
5
3FILTERED WATER
11403/4"
WALL
ROTISSERIE OVEN, DOUBLE
18"
GAS
30403/4"
WALL
CONVECTION OVEN, DOUBLE
18"
GAS
38001/4"
WALL
RETHERMALIZER
24"
HW
45161/2"
WALL 1-COMP. SINK12"
CW/HW
45051/4"
WALL
VEGGIE WASH SYSTEM
48"
45501/2"
WALL
HAND SINK
18"
1/2"
WALL 12"
-
-
-
-
38003/4"
WALL
RETHERMALIZER
18"
GAS
CW
CW/HW
CW/HW
NOT USED
3"
FLOORFLOOR SINK --
4516
1-COMP. SINK1
1,6
1
2"
WALLDIRECT DRAIN 18"
3"
FLOORFLOOR SINK --
4623 POWERSOAK SINK
3800RETHERMALIZER
2"
WALLDIRECT DRAIN 16"
4550 HAND SINK
5,9
-
4,7
4
606
P12
1/4"
WALL
ICE MAKER
50"3
FILTERED WATER
P13
5
3171/2"
WALL PREP SINK FAUCET16"
CW/HW
P14
1
3"
FLOORFLOOR SINK --
113HOT FOOD TABLE
P15 3"
FLOORFLOOR SINK --
315
PREP SINK1
P16 3"
FLOORFLOOR SINK --
608
ICE BIN1
G04
4
G05
G06
1003/4"
WALL
FRYER
12"
GAS
1193/4"
WALL
OVEN / BROILER
12"
GAS
1213/4"
WALL
RANGE
12"
GAS
4
4
2x PIPE DIAMETER
CUT END OF WASTE LINE AT 45°
TO REDUCE SPLASHING.
CONCRETE SLAB
FLOOR COVERING
SET FLOOR SINK FLUSH
WITH FINISHED FLOOR
DOME STRAINER
NO HUB JOINT CLAMP
FLOOR SINK
P-TRAP
SET CLEANOUT FLUSH
WITH FINISHED FLOOR
FLOOR COVERING
CONCRETE SLAB
SAME SIZE AS WASTE
LINE
1/8 BEND ELBOWS
NO HUB JOINT CLAMP
P-TRAP
SET FLOOR DRAIN FLUSH
WITH FINISHED FLOOR
FLOOR COVERING
CONCRETE SLAB
NO HUB JOINT CLAMP
NOTE: DO NOT SLOPE FLOOR TO DRAIN
UNLESS OTHERWISE NOTED.
NOT TO SCALE
FLOOR SINK DETAIL 1
P201
NOT TO SCALE
INTERIOR CLEANOUT DETAIL 3
P201
NOT TO SCALE
FLOOR DRAIN DETAIL 2
P201
ATTACH RODS TO STRUCTURE
ABOVE USING BEAM CLAMPS OR
SIMILAR MEANS OF CONNECTION.
3/8" THREADED
ROD, TYPICAL
"UNISTRUT" P1000 1-5/8"
CHANNEL, LENGTH AS
REQUIRED.
1-PIECE PIPE CLAMP, TYPICAL PROVIDE
SHEET METAL SHIELD BELOW CLAMP
FOR INSULATED PIPE.
PIPE, TYPICAL
NOTE:
1. CLAMPS SHALL NOT INTERRUPT
INSULATION.
2. PROVIDE COPPER PLATED SUPPORTS
FOR UNINSULATED COPPER PIPING.
INSULATION, TYPICAL
PIPE SUPPORT SPACING
1/2" PIPING: 4'-0" CENTERS
3/4"-1" PIPING: 6'-0" CENTERS
1-1/4" AND LARGER PIPING: 10'-0" CENTERS
NOT TO SCALE
TRAPEZE PIPE HANGER DETAIL 5
P201
EQ
UA
L
L
C
EQ
UA
L
PIPE (TYPICAL GAS OR WATER LINE)
THREADED ROD
Z-PURLIN AT ROOF
PIPE HANGER SHALL BE ATTACHED TO
Z-PURLIN WITH BOLT, NUT AND WASHER
LOCATED AT CENTERLINE OF Z-PURLIN WEB
ONLY
B-LINE FIG. B3060 SIDE
BEAM ANGLE CLAMP
B-LINE FIG B3170 ADJUSTABLE
SWIVEL RING PIPE HANGER
PIPE SUPPORT SPACING
1/2" PIPING: 4'-0" CENTERS
3/4"-1" PIPING: 6'-0" CENTERS
1-1/4" AND LARGER PIPING: 10'-0" CENTERS
NOT TO SCALE
PIPE HANGER ATTACHMENT DETAIL 6
P201
CLEANOUT PLUG
IN TEE
2" DRAIN
TYPICAL
CLEANOUT
FLOOR SINK
2"
FINISHED
FLOOR
NOT TO SCALE
THREE COMPARTMENT SINK DETAIL 4
P201
CO CLEANOUT (INTERIOR) SEE PLANZN1400 ---- SAME SIZE AS LINE
PLUMBING FIXTURE SCHEDULE
PIPING REQUIREMENTS
VENT
MARK MODEL NO.DESCRIPTION MANUFACTURER ACCESSORIES
WASTE
REMARKS
SUPPLY
APPROVED MANUFACTURERS
FD ZURN 2" 1-1/2"FLOOR DRAIN ZN415BJAY R SMITH, WADE, MIFAB, JOSAM
-- --
5" NICKLE BRONZE LIGHT DUTY STRAINER
AND "PROSET" SYSTEMS TRAP GUARD
FS ZURN Z17513"
--1-1/2
DOME STRAINER, 8" SUMP DEPTH,
SEDIMENT BUCKET AND 1/2 GRATE
16 GA. 304 SS CONST, OUTLET
SIZE SAME AS LINE
1. COORDINATE THE ROUGH-IN OF ALL PLUMBING FIXTURES WITH THE ARCHITECTURAL PLANS.
2. PROVIDE SERVICE VALVES ON ALL SUPPLY FIXTURES.
NOTES:
FLOOR SINK
(12x12)
JAY R SMITH, WADE, MIFAB, JOSAM
ZURNJAY R SMITH, WADE, MIFAB, JOSAM
DURA-COATED CAST IRON BODY
W/POLISHED NICKEL BRONZE LIGHT
DUTY TOP
4623POWERSOAK SINK
TD TRENCH DRAIN Z-886-FSZURN
1
1
2" 1-1/2" --
HDPE TRENCH DRAIN WITH
SLOTTED STAINLESS STEEL
GRATE
--JAY R SMITH, MIFAB
1
PROJECT:
Design. Spaces. People.
Fort Worth, Texas 76104
www.qarch.comfx. (817) 738-9524ph. (817) 738-8095
707 W. Vickery Blvd. #101
SOLICITATION ISSUE
04/15/16 95% SUBMITTAL
CDI
ARMY AND AIR FORCE EXCHANGE SERVICE
CONVERT :
TO BOSTON MARKET /
QDOBA
FT. CAMPBELL, KY
SCALE:
AFFES NO:
DATE:
2146-15-000007
AS NOTED
SHEET:
DRAWING TITLE:
DRAWING PROJ. NO.
16014
23 JULY 2016
05/23/16
SOLICITATION
ISSUE
CDI
06-23/16ADDENDUM #1
CDI
P-201
PLUMBING SCHEDULES
& DETAILS
SCALE: 1/4" = 1'-0"
POWER PLAN
BOSTON MARKET
QDOBA
1
KEY NOTES
INDICATED BY SYMBOLS , , ETC.
1. RECEPTACLE AT SOFFIT FOR DIGITAL MENU
BOARD/PANEL. FIELD COORDINATE EXACT
ROUGH-IN LOCATION. COORDINATE
CONTROL WITH OWNER.
2. RECEPTACLE AT SOFFIT FOR DIGITAL
CONTROLLER. FIELD COORDINATE EXACT
ROUGH-IN LOCATION. COORDINATE
CONTROL WITH OWNER.
3. PROVIDE DATA OUTLET(S) AS REQUIRED
FOR DIGITAL MENU BOARD/PANEL(S) AND
DIGITAL CONTROLLER(S). COORDINATE
WITH EQUIPMENT PURVEYOR.
4. EXISTING KITCHEN HOOD RELOCATED,
REFER TO HVAC PLAN, SHEET M101.
EXTEND/RE-ROUTE EXISTING CIRCUITRY
AND CONTROL WIRING AS REQUIRED.
5. KITCHEN HOOD (KH-1) UTILITY CABINET.
REFER TO HVAC PLANS.
CIRCUITS: LBL-30/HOOD CONTROL AND
LIGHTS; LBL-32,34,36/EXHAUST FAN (EF-1);
LBL-38,40,42-MAKE-UP AIR (MAU-1).
6. #12'S TO KITCHEN HOOD UTILITY CABINET.
7. PROVIDE DUPLEX RECEPTACLE FOR
RELOCATED BAG-IN-BOX EQUIPMENT.
COORDINATE EXACT LOCATION AND
MOUNTING HEIGHT WITH EQUIPMENT.
EXTEND/RE-ROUTE EXISTING CIRCUITRY.
GENERAL NOTES
1. ALL ELECTRICAL WORK SHALL COMPLY
WITH THE 2011 EDITION OF THE N.E.C.
2. DRAWINGS ARE DIAGRAMMATIC AND ARE
NOT TO BE SCALED. REFER TO THE
ARCHITECTURAL PLANS AND FIELD
CONDITIONS FOR DIMENSIONS.
3. ALL CONDUCTORS SHALL BE COPPER.
4. ALL WIRING SHALL BE IN CONDUIT. CONDUIT
SHALL BE AS CALLED FOR ON PLANS OR
WHERE PLANS DO NOT INDICATE, CONDUIT
SHALL BE AS CALLED FOR IN
SPECIFICATIONS.
5. ALL WIRING IN FINISHED SPACES SHALL BE
CONCEALED, UNLESS NOTED OTHERWISE.
6. THE ELECTRICAL SYSTEM DESIGN IS BASED
IN PART ON THE HVAC EQUIPMENT
SPECIFIED ON THE MECHANICAL
DRAWINGS. IT IS THE RESPONSIBILITY OF
THE CONTRACTOR TO COORDINATE THE
ELECTRICAL REQUIREMENTS OF THE HVAC
EQUIPMENT BEING FURNISHED AND TO
PROVIDE THE CORRECT CONDUCTORS AND
BREAKERS WITH NO ADDITIONAL COST TO
THE OWNER. SHOULD THE LOAD OF THE
EQUIPMENT BEING FURNISHED RESULT IN
THE NEED TO INCREASE THE AMPACITY OF
THE PANELS OR FEEDERS, THAT WORK
SHALL ALSO BE PROVIDED AT NO
ADDITIONAL COST TO THE OWNER.
7. THE CONTRACTOR IS RESPONSIBLE FOR
INSTALLING A COMPLETE AND OPERABLE
SYSTEM IN ACCORDANCE WITH THE INTENT
OF THE PLANS WHETHER OR NOT EVERY
ELEMENT THEREOF IS SPECIFICALLY
CALLED OUT.
8. COORDINATE ALL WORK WITH OTHER
TRADES TO AVOID CONFLICTS.
9. FIELD VERIFY THE EXISTING CONDITIONS
AND MAKE ALLOWANCES FOR THE SAME.
10. VERIFY ALL ELECTRICAL SERVICE
REQUIREMENTS WITH THE UTILITY CO. AND
INCLUDE ALL WORK IN THE BID.
ALL BRANCH CIRCUITS SHALL HAVE AN
EQUIPMENT GROUNDING CONDUCTOR ROUTED
WITH THE CIRCUIT CONDUCTORS. THIS MEANS
ALL CONDUITS MUST HAVE A "GREEN" WIRE
INSTALLED THAT IS SIZED IN ACCORDANCE
WITH N.E.C. ARTICLE 250.
1. REMOVE ALL EXISTING FIXTURES, DEVICES,
EQUIPMENT AND ASSOCIATED WIRING IN
CONFLICT WITH CONSTRUCTION.
2. FIELD VERIFY THE EXISTING CONDITIONS
AND MAKE ALLOWANCES FOR SAME.
3. EXISTING OUTLET BOXES AND CONDUIT
MAY BE USED AS LOCATION PERMITS.
4. PATCH AND REPAIR WHERE REQUIRED BY
REMOVAL OF EXISTING ELECTRICAL ITEMS.
2
'LBL''KBR'
'L
1A
'
E0
E1 E2 E3
E5
E6
E7
E8 E9 E10E11 E12 E13 E14
E15
E16
22
E17E18E18
1 1 1 1
2222
3
E4E4
E0
E3
E4
E6E8
E9
2
E11
ELEC. CHARACTERISTICS
EQUIPMENT
WIRING REQUIREMENTS CIRCUIT
BOSTON MARKET EQUIPMENT SCHEDULE
MARK
MARK
EQUIP.REF.
* CONTRACTOR TO VERIFY ALL UTILITY REQUIREMENTS OF EQUIPMENT PROVIDED PRIOR TO ROUGH-IN.
* ALL DISCONNECTS SERVING 'KITCHEN' EQUIPMENT SHALL BE EQUAL TO HUBBELL #HBLDS SERIES. AMPACITY AS REQUIRED.
E11
E10
E8
E9
E7
E6
E5
E4
E3
E1
E12
E13
E14
E15
E16
E17
E18
REACH-IN FREEZER, 1-DOOR 115V, 1Ø, 9.0A
REACH-IN REFRIGERATOR, 1-DOOR
115V, 1Ø, 6.0A
25 QT. MIXER 115V, 1Ø, 11.0A, 3/4HP
E2
P.O.S. TERMINAL & PRINTER 120V, 1Ø
LOW TEMPERATURE HOLDING CABINET, 750-S 208-240V, 1Ø, 3.9A, 810W NEMA 6-15 RECEPTACLE 24" A.F.F.
FOOD WARMER WITH INSERT 120V, 1Ø, 3.3A, 400W
HOLDING CABINET, DOUBLE STACK, 1000-UP 208V, 1Ø, 7.0A, 1400WNEMA 6-15 RECEPTACLE 24" A.F.F.
(2) CONVECTION OVEN115V, 1Ø, 5.0A, 1/3HP
GAS RETHERMALIZER120V, 1Ø, 3.0A
FOOD WARMER 120V, 1Ø, 15.0A, 1800W
ROTISSERIE OVEN, DOUBLE STACKED 115V, 1Ø, 2.2A, 250W
PROGRAMMABLE TIMER
115V, 1Ø, 20VA
(2) MICROWAVE 208-240V, 1Ø, 21.2A, 4400W
NEMA 6-30 RECEPTACLE 24" A.F.F.
(2) LOW TEMPERATURE HOLDING CABINET, 300-S 120V, 1Ø, 6.7A, 800W
HOT WATER DISPENSER NEMA 14-20 RECEPTACLE 60" A.F.F.208V, 1Ø, 19.5A, 4000W
DUAL TEMPERATURE REACH-IN 115V, 1Ø, 7.5ANEMA 5-15 RECEPTACLE 84" A.F.F.
MEGA TOP REFRIGERATOR 115V, 1Ø, 7.2A
3-WELL HOT FOOD TABLE 120V, 1Ø, 10.0A, 1200W
E0 REACH-IN REFRIGERATOR, ROLL-IN, 2-DOOR 115V, 1Ø, 9.5A NEMA 5-15 RECEPTACLE 84" A.F.F.
L3E-5
L3E-7
L3E-37,39
L32-9
L32-10
5270
5290
5279
3336
9005
3506
3890
3826
1140
3530
3800
3040
3303
3518
3981
3309
5389
5349
3825
NEMA 5-15 RECEPTACLE 84" A.F.F.
NEMA 5-15 RECEPTACLE 84" A.F.F.
NEMA 5-15 RECEPTACLE 48" A.F.F.
QUADRUPLEX RECEPTACLE 24" A.F.F.
NEMA 5-15 RECEPTACLE 48" A.F.F.
NEMA 5-15 RECEPTACLE 48" A.F.F.
NEMA 5-15 RECEPTACLE 24" A.F.F.
NEMA 5-15 RECEPTACLE 24" A.F.F.
NEMA 5-15 RECEPTACLE 24" A.F.F.
NEMA 5-15 RECEPTACLE 24" A.F.F.
NEMA 5-15 RECEPTACLE 24" A.F.F.
NEMA 5-15 RECEPTACLE 24" A.F.F.
NEMA 5-15 RECEPTCEL 24" A.F.F. L32-11
L3E-3
L3E-1
L3E-6
9000
L3E-17,19,21
L3E-9,11
L3E-13,15
L3E-14,16,18
L3E-20,22
L3E-24
L3E-30,32
ELEC. CHARACTERISTICS
EQUIPMENT
WIRING REQUIREMENTS REMARKSCIRCUIT
QDOBA EQUIPMENT SCHEDULE
MARK
MARK
EQUIP.REF.
* CONTRACTOR TO VERIFY ALL UTILITY REQUIREMENTS OF EQUIPMENT PROVIDED PRIOR TO ROUGH-IN.
* ALL DISCONNECTS SERVING 'KITCHEN' EQUIPMENT SHALL BE EQUAL TO HUBBELL #HBLDS SERIES. AMPACITY AS REQUIRED.
E7
E6
E5
E4
E3
E1 DOUBLE-SIDED GRIDDLE 120V, 1Ø, 15.0A
3-BAY HOT FOOD TABLE
208V, 1Ø, 12.48A
CONVECTION STEAMER 208V, 3Ø, 22.0A
E2
WARM/HOLDING CABINET 120V, 1Ø, 10.0A, 1500WNEMA 5-15 RECEPTACLE 18" A.F.F.
WARMING DRAWER 120V, 1Ø, 7.5A, 900W
REFRIGERATED SALAD TOP W/HEATER 120V, 1Ø, 9.0A
FOOD WARMER 120V, 1Ø, 10.0A, 1200W
E0 TIMER 115V, 1Ø, 0.5A, 1/2HP NEMA 5-15 RECEPTACLE-VERIFY HEIGHT LBL-10
LBL-14,16
LBL-2,4,6,8
LBL-26
LBL-10
LBL-24
LBL-18200
143
136
130
125
113
108
107
NEMA 5-15 RECEPTACLE 18" A.F.F.LBL-12
NEMA 6-20 RECEPTACLE 18" A.F.F.
NEMA L15-30 RECEPTACLE 48" A.F.F.SHUNT-TRIP C/B
NEMA 5-15 RECEPTACLE 18" A.F.F.
E8 UNDERCOUNTER FREEZER 120V, 1Ø, 5.5A LBL-24204
E9 ICE MACHINE 115V, 1Ø, 13.2ANEMA 5-20 RECEPTACLE 24" A.F.F.
LBL-28606
E10 SAFE 120V, 1Ø, 1.5A LBL-20650
E11 P.O.S. SYSTEM 120V, 1ØNEMA 5-15 QUAD. RECEPTACLE 24" A.F.F.
LBL-201278
NEMA 5-15 RECEPTACLE 18" A.F.F.
NEMA 5-15 RECEPTACLE 18" A.F.F.
NEMA 5-15 RECEPTACLE 18" A.F.F.
NEMA 5-20 RECEPTACLE 18" A.F.F.
PROVIDE POWER CORD AND
PLUG (6'-0" MIN. LENGTH)
EXISTING PANEL TO
REMAIN. TYPICAL UNLESS
NOTED OTHERWISE.
'L3L' 'L3C' 'L3R'
'H3'
'L3'
STORE
CONTROL
PANEL
'L32'
'L3E'
EF-2
EF-1
MAU-1
ON ROOF
ON ROOF
ON ROOF
4
KH-1
KH-2
5
6
6
77
NOTE:
ALL 15- AND 20-AMP RECEPTACLES
SERVING KITCHEN AND PREP
AREAS SHALL BE GFCI PROTECTED.
LBL-22
LBL-13
L3E-2
GAS VALVE
LBL-17
GAS VALVE
L3E-26
L3E-13,15
L3E-20,22
L3E-20,22
L3E-33,35
NOTE TO ELECTRICAL CONTRACTOR:
UTILIZE EXISTING PANEL 'L1A' FOR CIRCUIT(S) SERVING
BOSTON MARKET SPACE, WHERE MADE AVAILABLE BY
DEMOLITION OF MANCHU WOK EQUIPMENT, IN LIEU OF
SERVING EQUIPMENT FROM PANEL 'L3E' OR 'L32' AS
NOTED. REMOVE BRANCH CIRCUIT OF DEMOLISHED
EQUIPMENT BACK TO PANEL, AND RE-USE CIRCUIT
BREAKER FOR NEW BOSTON MARKET EQUIPMENT AS
CONDITIONS ALLOW. CONTRACTOR TO FIELD VERIFY
NO OTHER LOAD(S) ARE ON CIRCUIT(S) BEING
DEMOLISHED PRIOR TO REMOVAL.
A NEW PANELBOARD SCHEDULE SHALL BE PRODUCED
AND CIRCUITS CLEARLY LABELED FOR ALL PANELS
AFFECTED IN RENOVATION, ('L1A', 'L3E', AND 'L32').
E12 WORKTOP FREEZER 120V, 1Ø LBL-29221NEMA 5-20 RECEPTACLE 24" A.F.F.
E12
E10E7E2E1E5
E5
1
2 2 2 2
1 1 1
3
LBL-35
JJ
E19 POWERSOAK SINK 208V, 3Ø, 26.7A, 2HP, 7000W4623DIRECT-WIRE THROUGH CONTROL L32-12,14,16
1
E19
1
PROJECT:
Design. Spaces. People.
Fort Worth, Texas 76104
www.qarch.comfx. (817) 738-9524ph. (817) 738-8095
707 W. Vickery Blvd. #101
SOLICITATION ISSUE
04/15/16 95% SUBMITTAL
CDI
ARMY AND AIR FORCE EXCHANGE SERVICE
CONVERT :
TO BOSTON MARKET /
QDOBA
FT. CAMPBELL, KY
SCALE:
AFFES NO:
DATE:
2146-15-000007
AS NOTED
SHEET:
DRAWING TITLE:
DRAWING PROJ. NO.
16014
23 JULY 2016
05/23/16
SOLICITATION
ISSUE
CDI
06-23/16ADDENDUM #1
CDI
E-101
POWER PLAN