    Technical Specications 

    ApplicationEarly detection of transformer faults using continuous monitoring of dissolved hydrogen in insulating uids.

    Monitoring dissolved carbon monoxide as a key indicator of cellulose degradation (Calisto 2 only).

    Continuous moisture monitoring.

    Performance

    Dissolved gases (H2 and CO) in oil

    Measurement technology Proprietary Morgan Schaffer cell

    Gas extraction technology Oil-immersed PTFE tubing

    Detection range H2: 2 - 50,000 ppmCO: 25 - 100,000 ppm

    Accuracy (ref: Morgan Schaffer ISO/IEC 17025

    accredited laboratory and True North oil standards)

    H2: Greater of ±5 ppm or ±5%

    CO: Greater of ±25 ppm or ±15%

    Repeatability H2: Greater of ±3 ppm or ±3%

    CO: Greater of ±25 ppm or ±10%

    Resolution H2: 1 ppm

    CO: 5 ppm

    Step response (typical conditions) H2: 50% in 60 minutes

    CO: 90% in 6 hours

    Interference H2: < 0.3% of other gases

    CO: < 5% from C2H2, C2H4; < 3% from H2, CH4, C2H6

    Moisture (H2O) in oil

    Measurement technology Oil-immersed RS sensor 

    Detection range 2 ppm - saturation, 2 - 100% RS

    Accuracy (ref: Morgan Schaffer ISO/IEC 17025

    accredited laboratory and Atlantis oil standards)

    ±3 ppm or ±3% RS

    Repeatability ±2 ppm or ±2% RS

    Resolution 1 ppm, 1% RS

    Step response (typical conditions) 95% in 20 minutes

    Reliability

    Power interruption protection 250 ms advanced power loss

    Expected operating life (EOL) > 15 years

  • 8/17/2019 CALISTO Brochure & Specs (1)

    8/14

    Operation

    Operating temperature range -40 to 55 °C standard

    -50 to 55 °C with Insulation Kit.

    Cold Start -50 °C

    Storage temperature range -40 to 75 °C

    Operating oil temperature range -40 to 120 °C

    Oil pressure operation range Full vacuum to 40 psi

    Operating humidity range 0 - 100% RH

    Storage humidity range 5 - 95% RH, non-condensing

    Elevation range Up to 4,000 m. Atmospheric pressure compensation.

    Construction

    Width x height x depth 381 x 483 x 325 mm (15 x 19 x 12.8 in.)

    Weight 22.7 kg / 50 lbs

    Enclosure Stainless steel 304 gauge 16, lockable

    Oil circulation  Anti-cavitation reciprocating pump, 10 - 60 ml/min.

    Oil ow monitoring Proprietary Morgan Schaffer system

    Oil lines (standard) ⅜ in. OD copper with brass compression ttings

    Air bubble elimination Proprietary Morgan Schaffer system: Intelligent Bubble Trap

    Enclosure temperature conditioning Thermoelectric feedback

    Oil temperature conditioning Passive heat exchanger / thermoelectric feedback

    Cooling Forced air convection

    Safety protection Thermal cut-off fuse, rated at 77 °C over-current protection fuse

    Oil sampling External quick-connect port with sampling accessories

    Installation

    Calibration No calibration required

    Maintenance  Annual visual inspection

    Electrical entry holes (standard) 4 x 22.2 mm / 0.875 in. diameter 

    Commissioning time 2 hours

    Mounting Shock mounts. MS Calisto Mounting Stand recommended

    Power requirements 100 - 240 VAC +10% 1), 50 - 60Hz, 1Ø

    100 - 220 VDC +10% 1)

    320W, Client disconnect breaker 10A minimum

    Power conductor size Max. 2.05 mm /AWG 12

    Oil supply line length 1.5 - 10.5 m /5 - 35 ft

    Oil return line length 1.5 - 10.5 m /5 - 35 ft

     1) As per IEC/EN 61010

  • 8/17/2019 CALISTO Brochure & Specs (1)

    9/14

    Communication and Data

    Front panel interface 112 x 16 pixel display, vacuum uorescent, day/night,

    3 weather-proof UV-resistant buttons

    Local USB 2.0 port (cable provided)

    Permanent connection RS-485 port (1,500 V isolation)

    RS-232 port (1,500 V isolation)

    2 Ethernet ports (1,500 V isolation)

    3 independent H2, CO and H

    20 analog outputs,

    4-20 mA (1,500 V isolation)

    Oil temperature analog input, 4-20 mA (1,500 V isolation)

    Communication SCADA: Modbus, DNP3 Level 2, Optional IEC 61850 kit integrator: MSSP

    (Morgan Schaffer System Protocol)

    Measurement alarms Programmable dual-level and trend alarms for H2, CO and H

    2O

    Alarm relays 5 NO/NC contacts, congurable for set-up, self-test and measurement alarm

    conditions (250VAC, 5A; 48VDC, 1.5A)

    Data update 8 readings/day, validated H2 and CO

    1 reading/minute, continous H2

    1 reading/5 seconds, continuous H2O

    Data storage 3,000 (1 year)

    Interface Software

    Calisto Manager TM English, French, Simplied and Traditional Chinese

    Local and remote Calisto conguration, maintenance,

    data downloads and diagnostic downloads

    Tracking network of Calisto, Calisto 2, Calisto 5, and/or Calisto 9 monitors

    Database of Calistos, transformers and measurements.

    Platforms Windows XP / Vista / Windows 7 / Windows 8 / Windows 10

    DGA data management and diagnostics Inside View software integrates DGA data from monitors and

    portable analyzers with laboratory oil quality data.

    Diagnostic tools for eetwide transformer health management(sold separately).

    Regulatory

    CE marking Low Voltage Directive 2006/95/EC

    EMC Directive 2004/108/EC

    WEEE Directive 2002/96/EC, amended 2003/108/EC

    RoHS Directive 2002/95/EU

    EMC (Electromagnetic Compatibility) IEC/EN 61326

    IEC/EN 61000-6-5

    FCC part 15 (US)

    IEC/EN 61850-3

    Class A, ICES-003 (Canada)

    Electrical safety IEC/EN 61010IEC/EN 60255-27

    Ingress protection IEC/EN 60529, IP56

    Mechanical IEC 60255-21-1, Class 1 (Vibration)

    IEC 60068-2-27 (Shock)

    IEC 60255-21-3 (Seismic)

    Shipping

    Gross weight 30.8 kg / 67.8 lbs

    Packaging (H x W x D) 508 x 584 x 470 mm (20 x 23 x 18.5 in.)

  • 8/17/2019 CALISTO Brochure & Specs (1)

    10/14C-C2_Spec_EN201

    Head Ofce

    8300 Saint-Patrick Street, Suite 150LaSalle, Quebec, Canada H8N 2H1

    Tel: 1.514.739.1967 Toll-Free: 1.855.861.1967 Fax: +1 514.739.0434

    E-mail:  [email protected]

    Morgan Schaffer USA 

    101 Henderson Drive Sharon Hill, Pennsylvania, USA 19079

    Tel: 1.215.279.5915 Toll-Free: 1.855.861.1967

    E-mail: [email protected]

    ©2015 Morgan Schaffer Inc. All rights reserved. The MS Morgan Schaffer logo is a trademark of Morgan Schaffer Inc.

    www.morganschaffer.com

    Accreditation

    Morgan Schaffer is ISO/IEC 17025:2005 accredited by the Standards Council of Canada for the testslisted on the scope of accreditation. Morgan Schaffer USA accreditation is forthcoming.Morgan Schaffer is certied ISO 9001:2008

    Standard Package

    Brass shipping kit

    1 x Calisto Manager interface software CD

    1 x Calisto Manager User Guide

    1 x Calisto/Calisto 2 Installation and Operation Manual

    1 x Quick-Connect Oil Sampling Tube

    4 x Stainless Steel Shock Mount Assembly (85 Shore A)

    50 x Copper Tubing - ⅜ in. OD x 25 ft (7.6 m)

    2 x Brass Elbow One-Lok® Tube Fitting, ⅜ in. x ½ in.NPT (Male)

    4 x Ferrules One-Lok® Brass, ⅜ in. tube

    1 x Thermal Fuse: 77 °C

    1 x USB Cable A-B Full Rated 6 ft (1.8 m) long

    Options

    IEC 61850 Ethernet Communication Kit

    Insulation Kit (for -50 to 55 °C operation)

    Ethernet Outdoor Connectivity Kit

    Fiber Optic Ethernet

    Accessories

    Stainless Steel ttings and hoses

    Morgan Schaffer Calisto Mounting StandInterchangeability Kit (to facilitate future exchange with Calisto 5 or Calisto 9)

    Calisto precision oil temperature probe (4-20 mA)

    Stainless steel braided ex lines

    Quick-connect dust plug

    900 MHz radio modem (RS-485)

    2.4 GHz radio modem (RS-485)

    Warranty

    Morgan Schaffer’s Calisto and Calisto 2 monitors are backed by a 30-month standard warranty.

    Service and Support

    On-site commissioning service and on-site maintenance program available upon request.

    Note

    Continuous research and improvements may result in specication or appearance changes at any time.

  • 8/17/2019 CALISTO Brochure & Specs (1)

    11/14

    Technical Specications 

    Application

    Online monitoring of fault gases, air components and moisture in transformer insulating uids.

    Technology

    Gas measurements Proprietary chromatographic method

    Gas extraction Oil-immersed Teon® tubing

    Moisture measurements Oil-immersed relative saturation (RS) sensor 

    Communications Electrical isolation rated for substation environments

    Performance

    H2

    CO CH4

    C2H

    2C

    2H

    4C

    2H

    6CO

    2O

    2N

    2SF

    63) H

    2O

    Lower detection

    limit (LDL)

    ppm1) 2 ppm, or

    2% RS0.5 10 0.2 0.2 0.2 0.2 15 500 2,000 2

    Top of range1) ppm Saturation,or 100% RS

    20,000 30,000 100,000 100,000 200,000 200,000 100,000 100,000 150,000 2,500

    Accuracy2) (LDL plus X% of reading) ppm 3 ppm, or3% RS

    X=5 X=5 X=5 X=5 X=5 X=6 X=5 X=15 X=15 X=15

    Repeatability (LDL plus Y% of reading) ppm 2 ppm, or2% RS

    Y=3 Y=3 Y=3 Y=3 Y=3 Y=4 Y=3 Y=10 Y=10 Y=10

    Resolutionat LDL

    ppm 1 ppm, or

    1% RS0.5 2 0.2 0.2 0.2 0.2 5 200 1,000 2

    Measurementinterval

    User congurable: 3-hour, 2-hour, 1-hour. Conditional cycle on alarm. 6 seconds

    Step response(typical)

    In 1 hour: 95% H2; 90% CO, CH

    4, CO

    2, O

    2, N

    2; 80% C

    2H

    2, C

    2H

    4, C

    2H

    6; 50% SF

    6. 95% in

    20 minutes

    Shaded area applies to Calisto 9 only; 1) All ppm in mineral oil; 2) Reference: Morgan Schaffer ISO 17025 accredited laboratory and True North/

    Atlantis oil standards; 3) Model C900S.

    Reliability

    Gas management Continuous monitoring of carrier and calibration gas pressure to detect andreport gas leak errors and to predict cylinder replacement time

    Enclosure and oil temperature conditioning Improves measurement accuracy and extends the lifetime of internalcomponents

    Power interruption protection 250 ms advanced power loss system

    Expected operating life (EOL) > 15 years

    Operation

    Operating temperature range -50 to +55 ºC; cold start -50 ºC

    Storage temperature range -40 to +75 ºC

    Operating oil temperature range -40 to +120 ºC

    Operating oil pressure range Full vacuum to 40 psi

    Operating humidity range 0 - 100% RH

    Storage humidity range 5 - 95%, non-condensing, with caps installed on the carrier gas manifold (CGM) ports and carrier gas inlet and outlet of the monitor 

    Elevation range Up to 4,000 m

  • 8/17/2019 CALISTO Brochure & Specs (1)

    12/14

    Construction

    Width x height x depth Instrument: 502 x 489 x 337 mm (19.8 x 19 x 13.3 in.) Carrier gas manifold: 213 x 292 x 122 mm (8.4 x 11.5 x 4.8 in.), plus mounting anges

    Weight Instrument: 43 kg / 94.5 lbs

    Carrier gas manifold: 5 kg / 11 lbs

    Enclosures Instrument: 304 S.S., gauge 16, lockableCarrier gas manifold: 304 S.S., gauge 14, lockable option

    Oil circulation  Anti-cavitation reciprocating pump, 10 - 60 ml/min.

    Oil ow monitoring Proprietary Morgan Schaffer system with low ow error 

    Oil lines ⅜ in. OD stainless steel

    Air bubble elimination Proprietary Morgan Schaffer system: Intelligent Bubble Trap

    Enclosure temperature conditioning Thermoelectric feedback

    Oil temperature conditioning Passive heat exchanger plus thermoelectric feedback

    Cooling Forced air 

    Equipment protection Thermal cut-off fuse (77 oC), over-current mains fuse

    Oil sampling installation External quick-connect port plus sampling accessories

    Installation

    Calibration On-board NIST traceable calibration gas, automatic calibration

    Carrier gas requirements 99.9999% He, 3000 psi maximum

    Maintenance Visual inspection every 12 months

    Carrier gas replacement every 24 months / Calibration gas replacement every

    36 months

    Electrical entry holes (standard) 5 x 22.2 mm / 0.875 in. diameter 

    Commissioning time 5 hours installation, plus 4 - 12 hours before rst readings

    Mounting Shock mounts. MS Calisto Mounting Stand recommended

    Power requirements (no selection required) 100 - 240 VAC ±10% 4) , 50 - 60Hz, 1Ø, 350W100 - 220 VDC ±10% 4), 350W / 10 A minimum client disconnect breaker 

    Power conductor size Max. 2.05 mm / AWG 12

    Oil supply line length 1.5 - 10.5 m / 5 - 35 ft

    Oil return line length 1.5 - 10.5 m / 5 - 35 ft

    Communication and Data

    Front panel interface English and French

    256 x 64 pixel display, vacuum uorescent, day/night

    Three weatherproof, UV resistant buttons

    Menu functions for readings, alarms, databank, set-up and maintenance

    Communication SCADA: Modbus, DNP3 Level 2, Optional IEC 61850 kit

    Time Synchronization: SNTP

    HTTP: Calisto Web Server Integrator: MSSP (Morgan Schaffer System Protocol)

    Local communication port USB 2.0 (cable provided)

    Isolated communication ports(5 kV impulse, 2.6 kVAC)

    RS-485, RS-232, Ethernet

    Isolated analog ports (5 kV impulse, 2.6 kVAC) 10 assignable 4-20 mA outputs (5 for Calisto 5)

    3 assignable 4-20 mA inputs

    Measurement alarms Programmable dual-level and trend alarms for all readings

    Relay outputs 

    (250VAC, 5A; 48VDC, 1.5A)10 NO/NC contacts (5 for Calisto 5) assignable for set-up, self-test and

    measurement alarm conditions

    Data storage 6 years

    Self diagnostics 192 error codes with intuitive descriptions and recommended client actions

  • 8/17/2019 CALISTO Brochure & Specs (1)

    13/14

    Interface Software

    Calisto Manager TM English, French, Simplied and Traditional Chinese 

    Local and remote Calisto conguration, maintenance, data downloads and

    diagnostic downloads 

    Tracking network of Calisto, Calisto 2, Calisto 5, and/or Calisto 9 monitors 

    Database of Calistos, transformers and measurements.

    Platforms Windows XP / Vista / Windows 7 / Windows 8 / Windows 10

    DGA data management and diagnostics Inside View software integrates DGA data from monitors and portableanalyzers with laboratory oil quality data.

    Diagnostic tools for eetwide transformer health management

    (sold separately).

    Regulatory

    CE marking Low Voltage Directive 2006 / 95 / EC

    EMC Directive 2004 / 108 / EC WEEE Directive 2002 / 96 / EC, amended 2003 / 108 / EC

    RoHS Directive 2002 / 95 / EU

    EMC (Electromagnetic Compatibility) IEC/EN 61326

    IEC/EN 61000-6-5 

    IEC/EN 61850-3 

    FCC part 15 (US) Class A, ICES-003 (Canada)

    Electrical safety IEC/EN 61010

    IEC/EN 60255-27

    Ingress protection IEC/EN 60529, IP 56

    Shipping

    Gross weight Instrument: 49 kg / 107 lbs

    Standard accessories: 10 kg / 22 lbs

    Packaging Instrument: 600 x 584 x 410 mm (24 x 23 x 16 in.)Standard accessories: 510 x 510 x 254 mm (20 x 20 x 10 in.)

    Options

    IEC 61850 Ethernet communication kit Dissolved SF

    6 monitoring and alarms (Model C900S)

    Ethernet outdoor connectivity kitFiber Optic Ethernet

    Accessories

    Morgan Schaffer Calisto Mounting Stand 

    Calisto precision oil temperature probe (4-20mA)900 MHz radio modem (RS-485) 

    2.4 GHz radio modem (RS-485)

    Warranty

    Morgan Schaffer’s Calisto 5 and Calisto 9 monitors are backed by a 30-month standard warranty.

    Service and Support

    On-site commissioning service and on-site maintenance program available upon request.

    Note

    Continuous research and product improvements may result in specication or appearance changes at any time.

  • 8/17/2019 CALISTO Brochure & Specs (1)

    14/14

    Comparison Table

    Head Ofce

    8300 Saint-Patrick Street, Suite 150 LaSalle, Quebec, Canada H8N 2H1

    Tel: 1.514.739.1967 Toll-Free: 1.855.861.1967 Fax: +1 514.739.0434

    E-mail:  [email protected]

    Morgan Schaffer USA 

    101 Henderson DriveSharon Hill, Pennsylvania, USA 19079

    Tel: 1.215.279.5915 Toll-Free: 1.855.861.1967

    E-mail: [email protected]

    www.morganschaffer.com

    Accreditation

    Morgan Schaffer is ISO/IEC 17025:2005 accredited by the Standards Council of Canada for the testslisted on the scope of accreditation. Morgan Schaffer USA accreditation is forthcoming.Morgan Schaffer is certied ISO 9001:2008

    Calisto Calisto 2 Calisto 5 Calisto 9

    Hydrogen (H2)  

    Carbon monoxide (CO)

    Methane (CH4)

     Acetylene (C2H

    2)

    Ethylene (C2H4)

    Ethane (C2H

    6)

    Carbon dioxide (CO2)

    Oxygen (O2)

    Nitrogen (N2)

    SF6 gas (Model C900S)

    Moisture

    Programmable alarming

    Oil ow monitoring

    Compatible mounting

    3-hour sampling

    1-hour sampling

    Real-time on hydrogen

     All Duval Triangle* gases

     All DGA Diagnostic* gases

    DNP3 & Modbus

    IEC 61850 protocol (optional)

    CE marked-FCC compliant

    IP 56 enclosure

    *Additional software required, such as Morgan Schaffer’s Inside View.