Calculation of PFP Thickness

10
Calculation of PFP Thickness Friday, May 6, 2022

description

Thursday, 14 August 2014. Calculation of PFP Thickness. The thickness of fire protection required is determined by: Duration Critical Steel Temperature Steel section size and type Hp/A ratio Thickness stated in the local or international approval. SI Units: Hp/A = M/D = A/V = - PowerPoint PPT Presentation

Transcript of Calculation of PFP Thickness

Page 1: Calculation of PFP Thickness

Calculation of PFP ThicknessSaturday, April 22, 2023

Page 2: Calculation of PFP Thickness

The thickness of fire protection required is determined by:

1. Duration

2. Critical Steel Temperature

3. Steel section size and type

Hp/A ratio

4. Thickness stated in the local or international approval

Page 3: Calculation of PFP Thickness

SI Units:

Hp/A =

M/D =

A/V =

Imperial (US) Units:

W/D =

A/P =

Heated Perimeter

Cross Section Area=

metres

metres²= m-1 or /m

Heated Perimeter

Weight of section= inches

Pounds/foot= lb/ft/in

Heated Perimeter =Square inches =Cross Section Area

in2/ininches

All express the relationship between the amount of steel capable of absorbing heat to the area of steel surface exposed to the fire.

Heated Surface Area=

metres²

metres³= m-1 or /m

Volume of Steel

Mass of Section

Heated Perimeter=

Kilograms / metre

metres= kg/m²

Page 4: Calculation of PFP Thickness

How much PFP do I need?

Hp/A - Section Factors

Cross Sectional

Area (A = m²)

Heated Perimeter (Hp = m)

Low Hp/A = Thinner PFP305 x 305 x 240 kg/m

Hp/A = 1.905m / 0.0305m²Hp/A = 62 m-1

For H120 (400°C): Chartek 7 = 11 mm

High Hp/A = Thicker PFP305 x 305 x 97 kg/m

Hp/A = 1.789m / 0.0123m²Hp/A = 145 m-1

For H120 (400°C): Chartek 7 = 16 mm

Page 5: Calculation of PFP Thickness

How much PFP do I need?

How Hp/A changes with sides exposed to fire.(Example 305 x 305 x240 Kg/m UC)

Note: Cross Sectional Area Remains the same in all cases!

Wall, Floor or Deck Wall, Floor or Deck

4 Sides exposed

Hp/A=

Hp/A = 62 m-1

0.0305 m²

1.905 m

3 Sides exposed

Hp/A=

Hp/A = 52 m-1

0.0305 m²

1.587 m

Flange only exposed

Hp/A=

Hp/A = 13 m-1

0.0305 m²

0.393 m

Page 6: Calculation of PFP Thickness

How to calculate an Hp/A?

www.asfp.org.uk

TheYellowBook!

Page 7: Calculation of PFP Thickness

How to calculate an Hp/A?

Page 8: Calculation of PFP Thickness

What do I do with my Hp/A?

Example of Certificate of Fire Approval with table of Hp/A v required PFP thickness

Chartek 7 Certificate Interchar 963 loadings

Page 9: Calculation of PFP Thickness

What do I do with my Hp/A?

Interchar 963 loadings

Page 10: Calculation of PFP Thickness

What about other section shapes?

Wall, Floor or Deck Wall, Floor or Deck

Decreasing Hp/A = Lower PFP thickness required