11/17/2015 Calculate Industrial Battery Hydrogen Gas Emission GB Industrial Battery http://giantbatteryco.com/GLOSSARY/Calculate.Industrial.Battery.Hydrogen.Gas.Emission.html#ForcedVentilation 1/5 GB Home Email Tech Support Calculate Hydrogen Gas Emissions – Industrial Batteries When designing a battery room, ventilation requirements need to be taken into consideration. Lead acid motive power batteries give off hydrogen gas and other fumes when recharging and for a period after the charge is complete. Proper ventilation in the battery charging area is extremely important. A hydrogeninair mixture of 4% or greater substantially increases the risk of an explosion. The concentration of hydrogen should be kept below 1% to provide a safety factor. Hydrogen gas is colorless and odorless. It is also lighter than air and will disperse to the top of a building. Calculating Hydrogen Concentration Calculating Room Volume Determining Ventilation Requirement Determining Fan Requirement Do You Need Forced Ventilation Hydrogen Gas Detector (HGD1) The information below is provided for reference only. State and local codes may apply that supersede these guidelines. The following is for general understanding only, and GB Industrial Battery takes no responsibility for these guidelines. Step 1: Calculating Hydrogen Concentration A typical lead acid motive power battery will develop approximately .01474 cubic feet of hydrogen per cell at standard temperature and pressure. H = (C x O x G x A) ÷ R 100 (H) = Volume of hydrogen produced during recharge. (C) = Number of cells in battery. (O) = Percentage of overcharge assumed during a recharge, use 20%. (G) = Volume of hydrogen produced by one ampere hour of charge. Use .01474 to get cubic feet. (A) = 6hour rated capacity of the battery in ampere hours. (R) = Assume gas is released during the last (4) hours of an 8hour charge. Example: Number cells per battery = 24 Ampere size of battery = 450 A.H. (H) = (24 x 20 x .01474 x 450) ÷ 4

description

Calculate Industrial Battery Hydrogen Gas Emission

Transcript of Calculate Industrial Battery Hydrogen Gas Emission - GB Industrial Battery

Page 1: Calculate Industrial Battery Hydrogen Gas Emission - GB Industrial Battery

11/17/2015 Calculate Industrial Battery Hydrogen Gas Emission ­ GB Industrial Battery

http://giantbatteryco.com/GLOSSARY/Calculate.Industrial.Battery.Hydrogen.Gas.Emission.html#ForcedVentilation 1/5

GB Home Email Tech Support Calculate Hydrogen Gas Emissions – Industrial Batteries When designing a battery room, ventilationrequirements need to be taken intoconsideration. Lead acid motive power batteriesgive off hydrogen gas and other fumes whenrecharging and for a period after the charge iscomplete.

Proper ventilation in the battery charging area isextremely important.

A hydrogen­in­air mixture of 4% or greatersubstantially increases the risk of an explosion.The concentration of hydrogen should be keptbelow 1% to provide a safety factor.

Hydrogen gas is colorless and odorless. It isalso lighter than air and will disperse to the topof a building.

• Calculating HydrogenConcentration

• Calculating Room Volume

• Determining VentilationRequirement

• Determining FanRequirement

• Do You Need ForcedVentilation

• Hydrogen Gas Detector(HGD­1)

The information below is provided for reference only. State and local codes may apply that supersede theseguidelines. The following is for general understanding only, and GB Industrial Battery takes no responsibility forthese guidelines.

Step 1: Calculating Hydrogen Concentration

A typical lead acid motive power battery will develop approximately .01474 cubic feet of hydrogen per cell atstandard temperature and pressure.

H = (C x O x G x A) ÷ R

100

(H) = Volume of hydrogen produced during recharge.

(C) = Number of cells in battery.

(O) = Percentage of overcharge assumed during a recharge, use 20%.

(G) = Volume of hydrogen produced by one ampere hour of charge. Use .01474 to get cubic feet.

(A) = 6­hour rated capacity of the battery in ampere hours.

(R) = Assume gas is released during the last (4) hours of an 8­hour charge.

Example: Number cells per battery = 24Ampere size of battery = 450 A.H.(H) = (24 x 20 x .01474 x 450) ÷ 4

Page 2: Calculate Industrial Battery Hydrogen Gas Emission - GB Industrial Battery

11/17/2015 Calculate Industrial Battery Hydrogen Gas Emission ­ GB Industrial Battery

http://giantbatteryco.com/GLOSSARY/Calculate.Industrial.Battery.Hydrogen.Gas.Emission.html#ForcedVentilation 2/5

100

H = 7.9596 cubic feet per battery per hour

top

Step 2: Calculating Room Volume

For a room with a flat roof volume is calculated W x L x H less the volume of chargers and other fixed objects inthe battery room.

W= WidthL = LengthH = Height

Example: Room size 80 feet long, 60 feet wide and 30 feet tall.

V = 60 x 80 x 30V = 144,000 cu.ft.

top

Step 3: Determining Ventilation Requirement

Assume 75 batteries stored.

7.9596 x 75 = 596.97 cubic feet per hour (7.9596 calculated in Step 1)

Battery room 144,000 cu. ft. from example in Step 2

V = R x P ÷ H x 60 minutes

(V) = Ventilation required(R) = Room cu. ft.(P) = Maximum percentage of hydrogen gas allowed(H) = Total hydrogen produced per hour

V = 144,000 x .01% ÷ 596.97 x 60V = 144.73 or the air should be exchanged every 144.73 minutes (2 hours 24 minutes)

top

Step 4: Determining Fan Requirement

Fan Size = R x 60 minutes ÷ V(R) = Room cu. ft.(V) = Ventilation required

144,000 x 60 ÷ 144.73 = 59’ 697.36 cu. ft. per hour or 995 CFM.

The ventilation system should be capable of extracting 59,697.36 cu.ft. per hour or 995 CFM.

top

Step 5: Do You Need Forced Ventilation

In theory the 596.97 cu. ft./hr. only represents .004% which is < 1%. Therefore forced ventilation would not berequired for this example.

However, the following should be considered before ruling out forced ventilation:Is the battery room closed in or open? If closed in no natural ventilationmay be possible.Since hydrogen gas rises are there areas in the ceiling where gas maycollect in greater concentrations.

Page 3: Calculate Industrial Battery Hydrogen Gas Emission - GB Industrial Battery

11/17/2015 Calculate Industrial Battery Hydrogen Gas Emission ­ GB Industrial Battery

http://giantbatteryco.com/GLOSSARY/Calculate.Industrial.Battery.Hydrogen.Gas.Emission.html#ForcedVentilation 3/5

The above calculation represents worse case scenario assuming allbatteries are gassing at the same time. This is highly improbable.

If natural ventilation is sufficient in an open area forced ventilation should not be required.

If your calculations determine a percentage <1% hydrogen concentration, we recommend a Hydrogen Gas Detectorfor safe measure, part number HGD­1.

top

Hydrogen Gas Detector (HGD­1)

OperationShould the concentration of hydrogen gas in the air surrounding the sensor reach 1% by volume, the "1% caution"yellow LED will light and the 1% internal relay will close. Should the hydrogen gas concentration reach 2% byvolume, the "2% warning" red LED will flash and an 80 db alarm will sound; the 1% relay will remain closed and, ifa Dual­Relay model, the 2% internal relay will close. Either relay can activate a remote exhaust fan and/or alarm.

LocationHydrogen, colorless and odorless, is the lightest of all gases and thus rises. The detector, therefore, should beinstalled at the highest, draft­free location in the battery compartment or room where hydrogen gas wouldaccumulate.

The size of the area one detector will protect depends upon battery compartment room. The detector measures thehydrogen gas in the air immediately surrounding the sensor. If hydrogen gas might accumulate in several,unconnected areas in the compartment or room, individual detectors should be placed at each location.

Optional Accessories: steel junction box mounting on wall or ceiling; modular jack (with duplicate LEDs; test button;and buzzer if needed) for remote placement; telephone­type cable for connecting the modular jack to the detector.

Added BenefitsIn addition to protecting your employees and your property, the detector also may reduce the followingcosts:Electricity – Heating – Air Conditioning. Instead of continuously running an exhaust fan to prevent hydrogengas accumulation, use the detector to activate the fan only if the concentration reaches 1%. Insurance. Installationof a detector in areas where batteries are charged may result in a premium reduction.

Back to top

Have questions? Contact TECH SUPPORT:

[email protected]

Corporate | About Us | Site Map | Services | Clients | Global Presence | Email: Parts & Service | Battery Care

Privacy | Terms of Use | Ethics | Legal

Powered by: Sun Microsystems © Copyright GB Industrial Battery ­ All rights reserved.Last Updated: Monday, December 03, 2007 ­ 5:57 AM Eastern Time.

Page 4: Calculate Industrial Battery Hydrogen Gas Emission - GB Industrial Battery

11/17/2015 Calculate Industrial Battery Hydrogen Gas Emission ­ GB Industrial Battery

http://giantbatteryco.com/GLOSSARY/Calculate.Industrial.Battery.Hydrogen.Gas.Emission.html#ForcedVentilation 4/5

Page 5: Calculate Industrial Battery Hydrogen Gas Emission - GB Industrial Battery

11/17/2015 Calculate Industrial Battery Hydrogen Gas Emission ­ GB Industrial Battery

http://giantbatteryco.com/GLOSSARY/Calculate.Industrial.Battery.Hydrogen.Gas.Emission.html#ForcedVentilation 5/5