Page 1: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

GB

GUIDE MANUAL

Page 2: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

3

GB

INDEX1- Introduction................................................................................................................5

.............................................................................................5

...............................................................................................6

4- The Control Pane .................................................................................................... 7l 4.1- The Control Panel 1 and 2 Loops ......................................................................... 7 4.2- The Control Panel 4 and 8 Loops...................................................................................9

5- Installation Guide................................................................................................... 10 5.1- Pre-Installation Checks ..................................................................................... 10

.................................................................................................. 11 5.3- Installation Steps 1 and 2 Loops ........................................................................ 12 5.4- Installation Steps 4 and 8 Loops..................................................................................18

............................................................................................ 24 1 and 2 Loops ................................................................. 24 4 and 8 Loops ..........................................................................43

.......................................................................................... 85 7.1- System Check ................................................................................................... 85

.................................................................................................. 85 7.3- System Test ...................................................................................................... 86

8- Maintenance .......................................................................................................... 92 8.1- User maintenance ............................................................................................. 92 8.2- Maintainer maintenance .................................................................................... 92

9- Features ............................................................................................................... 93

Page 3: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

5

GB

This manual contains instructions for installation, commissioning and maintenance of the range of analogue panels, and technical data.

The range of analogue panel consists of 2 models:

1 loop.2 loop.

detection system, such as businesses, schools, small and medium enterprises, etc.

detection and alarm systems listed in the standards EN54 Part 2 and 4.

guidelines of EN54 Part 14.

2- Pre-Installment Checks

One panel.

5x20 2A fuse for 1 and 2 loops.5x20 5A fuse for 4 and 8 loops.5X20 0.5A fuse.5X20 4A fuse.

Installation manual.User manual.Language labels according the control panel.

Page 4: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

6

GB

input / output modules. Devices can also be connected on one or more spurs off the closed loop.

Each loop of the system can be connected to up to 250 randomly routed sensor points, manual call points and input and / or output modules. The maximum loop length should

2

The system autosearches all of the points connected to the panel.

Record up to 4.000 events in the Event Log.

modules.

An auxiliary 24V DC output on the motherboard.

Page 5: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

7

GB

4- The Control Panel

4.1 The Control Panel 1 and 2 Loops A description of all equipment components and a description of indicators and control

1 LCD Display 132 Navigation controls 14 Output disablement LED3 Alarm zone LEDs 154 Fault-disablement-test-zone LEDs 16 Alarm LED5 17 Disablement LED6 18 Fault LED7 19 Test LED8 Reset control 20 Out of service LED9 2110 2211 Earth fault LED12 Delay ON LED

Page 6: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

8

GB

1. Loop One connector.2. 3. Fault and Alarm Connectors.4. 5. 6. Display contrast.7. 8. Auxiliary 24V output fuse.9. 10. 11. 12. Mains connector13. Mains fuse14.

Page 7: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

9

GB

4.2 The Control Panel 4 and 8 Loops

1 Display 11 Test LED2 12 Out of service LED3 134 145 15 Earth fault LED6 Reset Control 16 Delay ON LED7 Alarm LED 178 Alarm LED 18 Output disablement LED9 Disablement LED 1910 Fault LED 20

Page 8: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

10

GB

the instructions in this manual can cause damage to equipment.

connections.

Page 9: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

11

GB

Cable cutters or strippers.Voltmeter.

Programmer.

Page 10: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

12

GB

5.3.1 Removing the front cover

cover.

5.3.2 Panel location on the wall

are easily seen, and the cover can be easily removed. The panel must be located at a height of 1.5 m.

5.3.3 Fixing the panel to the wall

irreparable damage to the equipment.

Page 11: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

13

GB

5.3.5- Electrical wiring

devices such as sensors, manual call points etc. The panel must be connected via an 2 cable section. The voltage should be 230VAC.

communication bus lines. If the system can be affected by an electrical disturbance,

insert the cable glands.

It is advisable to use a shielded cable. Connect the cable shield to the corresponding

has an approved mains Earth.

and C.

Page 12: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

14

GB

5.3.6.1- Mains connection

coming loose in the case of sudden removal.

Page 13: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

15

GB

5.3.6.2- Battery connection

for the proper functioning of the panel.

The batteries are placed in the bottom of the box, vertically in the space provided.

5.3.7- Loop connection

The cable used must be at least 1.5 mm2, braided shield should be used to avoid

loop must be less than 44 Ohms, and the maximum capacity of the line should be less than 500 nF.

and R-, and the screen returns to terminal indicated as . It is essential to have a continuous screen on each loop.

Page 14: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

16

GB

5.3.8 Detectors connection

Heat ROR detector.Optical-Heat detector.Detector High ROR detector.

algorithmic analysis of signals received by the detectors. Each loop on the system can have up to 250 sensors connected. Analogue detectors should be routed prior

station Z-200, remember that there must be continuity of the cable screen on each loop connected.

A single monitored output module.A dual monitored output module.A conventional zone module.A dual conventional zone module.An analogue MCP.An analogue sounder.

230 Vac Relay Module.Isolator module.

Page 15: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

17

GB

source, located as close as possible to the module.

For more information see the installation manual of each module.

mA.

It is imperative that the sounders are polarized, or else it is necessary to insert a diode

resistor is required.

diode to prevent reverse current effect.

5.3.11 Relay connection

The panel has a fault relay and an alarm relay for outputs that act as an alarm or malfunction. The maximum relay contact current is 2A.

Page 16: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

18

GB

5.3.12 USB Connection

5.3.1 Removing the front cover

5.3.2 Panel location on the wall

are easily seen, and the cover can be easily removed. The panel must be located at a height of 1.5 m.

5.3.3 Fixing the panel to the wall

irreparable damage to the equipment.

Page 17: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

19

GB

5.3.5- Electrical wiring

devices such as sensors, manual call points etc. The panel must be connected via an 2 cable section. The voltage should be 230Vac.

communication bus lines. If the system can be affected by an electrical disturbance,

insert the cable glands.

It is advisable to use a shielded cable. Connect the cable shield to the corresponding

has an approved mains Earth.

and C.

Page 18: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

20

GB

5.3.6.1- Mains connection

coming loose in the case of sudden removal.

5.3.6.2- Battery connection

for the proper functioning of the panel.

The batteries are placed in the bottom of the box, vertically in the space provided.

Page 19: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

21

GB

5.3.7- Loop connection

The cable used must be at least 1.5 mm2, braided shield should be used to avoid

must be less than 44 ohms, and the maximum capacity of the line should be less than 500nF.

and R-, and the screen returns to terminal indicated as Earth. It is essential to have a continuous screen on each loop.

5.3.8 Detectors connection

Heat ROR detector.Optical-Heat detector.Detector High ROR detector.

algorithmic analysis of signals received by the detectors. Each loop on the system can have up to 250 sensors connected. Analogue detectors should be routed prior to

-tion Z-200, remember that there must be continuity of the cable screen on each loop connected.

Page 20: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

22

GBA single monitored output module.A dual monitored output module.A conventional zone module.A dual conventional zone module.An analogue MCP.An analogue sounder.

230 Vac Relay Module.Isolator module.

source, located as close as possible to the module.

For more information see the installation manual of each module.

mA.

It is imperative that the sounders are polarized, or else it is necessary to insert a diode

resistor is required.

Page 21: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

23

GB

diode to prevent reverse current effect.

5.3.11 Relay connection

The panel has a fault relay and an alarm relay for outputs that act as an alarm or malfunction. The maximum relay contact current is 2A.

5.3.12 USB Connection

Page 22: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

24

GB

After entering the access level 2 code, the installation engineer can access the

Page 23: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

25

GB

indicating all points that are connected to the loop. This report should be compared to the actual points installed to ensure that the devices are correctly detected and there are no connection errors.

and modules.

Page 24: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

26

GB

Pressing the Acceptthe points detected in the loop.

Pressing the Cancel

Pressing the Reportsfor the implementation of the system.

reports all addresses that have been found in the loop, indicating the type of point found at the address.

If there is no abbreviation under an address, it means that this address is free, and if you see XXX, it means there is more than one point that responds to that address.

Page 25: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

27

GB

end of the loop

found, and from the return connector on the loop 27 points have been found. This tells th point from the output connector and

To access the previous menu, press the Exit button.

options are available in the zone menu:

Page 26: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

28

GB

of the building covered by the zone.

given loop.

Page 27: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

29

GB

6.1.3.1 Edit Point

In the Edit Point menu, the name of points can be provided, and a zone can be assigned. The mode of the point is also displayed, i.e. enabled or disabled.

analogue value of the point being displayed.

Page 28: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

30

GB

6.1.3.2 Address programming

6.1.3.3 Toggling LED

light until either another address is chosen or the Exit option is selected.

Cause and effect actions are created from this menu.

Page 29: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

31

GB

6.1.4.1 New Actions (Action Creation)

An action is the cause and effect generated by an event in the building protected by

points connected to the panel.

“Point” as the Input in Action number 0001.

Page 30: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

32

GB

General alarm.MCP Alarm.Detector Alarm.Multi Point Alarm.

Pressing the More button changes the type of alarm that is generated by the panel.

General Alarm.Multi Point Alarm.

Page 31: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

33

GB

The actions on the points may be of ON or OFF, i.e. activate the output point such as

Pressing the More button changes the type of output that can be activated or de-

Outputs ONOutputs OFF.

Relays ON.Relays OFF.

Page 32: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

34

GB

Pressing the More button changes the type of loop output that is activated or de-

Outputs ON.Outputs OFF.

Relays ON.Relays OFF.

Pressing the More button changes the type of output that is activated on the entire

Outputs ON.Outputs OFF.

Relays ON.

Page 33: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

35

GB

Relays OFF.

is displayed in the top right of the LCD. All actions are started simultaneously so be

6.1.4.2 Modify Actions

of programmed actions is 3.Press the Input button to modify the Input.Press the Output button to modify the Output.Press the Erase button to cancel the displayed action.

leave the sub-menu.

6.1.5 Event Log

Alternatively you can list all events.

Page 34: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

36

GB

As a last option in this menu, the Erase option. This deletes all events from Event Log. This process is recommended to be used after commissioning the installation, so that

6.1.6.1 Installation name

In this submenu the installation engineer can enter the name of the facility, the company responsible for maintaining the facility and a help line.

facility.

and its phone number.

In the General menu you can enter the installation name, choose the menu language,

Page 35: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

37

GB

The system can operate in different languages to suit local requirements. The available

installation engineer.

menu.

Page 36: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

38

GB

Press Exit to exit the application.

search.

Page 37: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

39

GBcontroller node.

controller node.

Page 38: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

40

GB 6.1.7.2 Network Filter

DIRECCION:

Page 39: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

41

GB

- Possible number of nodes from 01 to 32.

Page 40: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

42

GB

6.1.8.2 Print LOG

FROM: - Day. Range from 01 to 31. - Month. Range from 01 to 31.

6.1.9 Day and time

Use this submenu to change the date and time displayed on the panel.

Page 41: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

43

GB

After entering the access level 2 code, the installation engineer can access the

Page 42: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

44

GB

Page 43: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

45

GB

indicating all points that are connected to the loop. This report should be compared to the actual points installed to ensure that the devices are correctly detected and there are no connection errors.

Page 44: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

46

GB

and modules.

elementos encontrados en el lazo.

reports all addresses that have been found in the loop, indicating the type of point found at the address and the status.

Again the and

If there is no abbreviation under an address, it means that this address is free, and if you see XXX, it means there is more than one point that responds to that address.

points detected in the loop.

Page 45: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

47

GB

Page 46: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

48

GB

found, and from the return connector on the loop 27 points have been found. This tells

To access the previous menu, press the Exit button.

options are available in the zone menu:

Page 47: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

49

GB

the area of the building covered by the zone.

Page 48: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

50

GB

sounders in this mode.

given loop.

loop.

Page 49: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

51

GB

Page 50: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

52

GB

given loop.

enable mode, disable mode or test mode.

Page 51: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

53

GB

in this mode.

After 20 minutes under the test mode selection, if the system detects that there has

test mode.

Page 52: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

54

GB

In the Edit Point menu, the name of points can be provided, and a zone can be as-signed. The mode of the point is also displayed, i.e. enabled or disabled. Also turn on the led.

Page 53: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

55

GB

In the Edit Point menu, the name of points can be provided, and a zone can be as-signed. The mode of the point is also displayed, i.e. enabled or disabled.

The device type is available in the display. AV is the analogue value of the point being displayed.

Page 54: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

56

GB the loop.

Page 55: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

57

GB

to use this function.

displayed.

Page 56: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

58

GB

type, the text of the point, the zone and the zone text for the selected device.

A summary of the number of devices enabled and disabled.

disable addresses of each loop.

in the loop.

Page 57: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

59

GB

Page 58: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

60

GB

-

mode.

light until either another address is chosen or the Exit option is selected.

Page 59: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

61

GB

-

Cause and effect actions are created from this menu.

Page 60: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

62

GB

Press the Erase button to cancel the displayed action.

6.2.4.1 New Actions (Action Creation)

An action is the cause and effect generated by an event in the building protected by

points connected to the panel.

Page 61: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

63

GB-mediate actions in case of false alarms.

action can be done by an input from a Panel, Loop, Zone or Point Input.

General Alarm.Multiple Point Alarm.Multiple Zone Alarm.

General Alarm.

General Alarm.MCP Alarm.Detector Alarm.Multiple Alarm.

types:

Alarm.

Page 62: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

64

GB

activate. The action can be done by an output from a Panel, Loop, Zone or Point Input.

Enable outputs.Disable outputs.Enable sounders.Disable sounders.Enable relays.Disable relays.

Enable outputs.Disable outputs.Enable sounders.Disable sounders.Enable relays.Disable relays.

Enable outputs.Disable outputs.Enable sounders.Disable sounders.Enable relays.Disable relays.

After selecting the loop and the address point

Enable.Disable.

Page 63: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

65

GB

Alternatively you can list all events.

As a last option in this menu, the Erase option. This deletes all events from Event Log. This process is recommended to be used after commissioning the installation, so that

Page 64: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

66

GB

In this submenu the installation engineer can enter the name of the facility, the com-pany responsible for maintaining the facility and a help line.

In the General menu you can enter the installation name, choose the menu language,

Page 65: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

67

GB

facility.

and its phone number.

The system can operate in different languages to suit local requirements. The available

Page 66: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

68

GB

The system can operate in different languages to suit local requirements. The available

Page 67: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

69

GB

installation engineer.

Page 68: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

70

GB

the loops.

Page 69: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

71

GB

Page 70: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

72

GB

Press Exit to exit the application.

Page 71: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

73

GB

the Loop.

the Loop.

Page 72: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

74

GB

version.

-

Page 73: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

75

GB

Page 74: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

76

GB

controller node.

panel.

Page 75: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

77

GB

- Possible number of nodes from 01 to 32.

Page 76: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

78

GB

installed in the panel.

Page 77: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

79

GB

Page 78: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

80

GB

Page 79: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

81

GB

6.2.8.2 Print LO

FROM: - Day. Range from 01 to 31. - Month. Range from 01 to 31.

Page 80: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

82

GB

Use this submenu to change the date and time displayed on the panel.

Page 81: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

83

GB

Page 82: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

84

GB

Here are the steps for a basic installation.

Date and Time Settings. To set the date and time on the panel see section 6.1.7

Name the installation. To enter the name of the installation, and the maintenance company & phone number see section 6.1.6.1 of this manual.

Set a loop.

to be structured according to installation requirements. To create and assign zones see section 6.1.2 of this manual.

and zone. The points can be disabled if necessary. To name and assign the points see section 6.1.3 of this manual.

Set actions.

delay in seconds, to avoid false alarms in case of immediate actions. To access the

protect the installation.

Page 83: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

85

GB Use the tester to verify continuity of the line. Verify that the circuits connected to zone

EOL resistors.

have a voltage greater than 24V.

is:

Connect the batteries.

also see the sounder delay LED on.

If you notice any indication other than those described above, the origin of the problem

Page 84: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

86

GB

relay operates and the fault is indicated on the LEDs and LCD.

7.4- How to solve common problems

it is important to solve the problem, since it can affect communications. If an Earth fault

Verify that the fault is not caused by the panel itself, by disconnecting all circuits connected to the panel.

Once the circuit that causes the Earth fault is ascertained, disconnect the return loop,

connected. Continue this process until the exact location of the Earth fault is found.

Removal of any point of the loop.

Page 85: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

87

GB

should be 32V.

return the same loop. Are there cross the system from both the output and input from only communicate to the nearest crossing insulators.

Disconnect half of the loop.

problems disappear, this means that the communication problem interference is in the other half of the installation. If problem persists this means that the

problem. Once you reach the area, the normal solution is to remove from the loop

Once solved the problem, reconnect the loop in all its entirety and carry out another

During the installation of the system, it can fail because of the same address at different points of the loop.

Page 86: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

88

GB

Press the Reports button to go to the next screen:

found in the loop indicating the type of the point at the address.

If there is not any abbreviation under an address, it means that this address is free, and if you see XXX, it means there is more than one point that responds to that address.

address of 6 has accidentally been given an address of 9.

During the installation of the system, it can fail because of the same address at different points of the loop.

Page 87: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

89

GB

Press the Reports button to go to the next screen:

Page 88: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

90

GB

found in the loop indicating the type of the point at the address.

If there is not any abbreviation under an address, it means that this address is free, and if you see XXX, it means there is more than one point that responds to that address.

address of 6 has accidentally been given an address of 9.

Page 89: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

91

GB

dealer.

7.4.6 Password incorrect

and installers, respectively. If you forget the code, contact your dealer.

Page 90: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

92

GB

8- Maintenance

recommendations found in this section.

8.1- User maintenance

or manual call point. A different area should be tested every month. Any anomaly

action as soon as possible.

8.2- Maintainer maintenance

The company in charge of maintenance of the facility shall test every six months as

»actions. » Examine the battery connections and load voltage. » » Visually inspect the equipment to detect any increase in moisture or any other deterioration. »alter the normal operation of the facility

» The company responsible for maintenance of the facility must demonstrate annually that:

» Put the panel on test mode, and verify that all sensors and call points operate

» Inspect all connections to the panel and its attachments to verify that there has been no deterioration. » Examine the state of the batteries and replace if necessary. »

Page 91: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

93

GB

439 mm x 268 mm x 112 mm

Material

4 and 8

460 mm x 360mm x 120 mm

460 mm x 450 mm x 120 mm

460 mm x 450 mm x 200

Material

Relative Humidity Maximum 95% dry

IP Rating IP30

Class type

Maximum points per loop 250 points

Loop voltage Min 25 Vdc Max 32 Vdc

Loop maximum output current 225 mA

Maximum loop length

Maximum loop capacitance 500 nF2

Maximum loop resistance 44 Ohms

Características salida de relé de alarma

Relé libre de tensión 1 relé con contactos C, NA, NC

Potencia máxima de conmutación 2A a 30 Vdc

Características salida del relé de avería

Relé libre de tensión 1 relé con contactos C, NA, NC

Potencia de máxima de conmutación 24 a 30 Vdc

Energizado

Page 92: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

94

GB

Number of monitored sounder outputs 2

Quiescent output voltage

Min 18 Vdc Max 29 Vdc

Maximum output current 400 mA per sounder output2

End of line resistor

Output voltage Min 18Vdc Max 29 Vdc

Maximum output current 400 mA2

Protecting fuses 24V aux

Mains voltage

Output voltage Max 29 Vdc

Protecting fuse

Maximum output current 2A

Output voltage 27,6 Vdc at 20ºC

Temperature compensation 3 mV/ºC x C

Maximum load current 350 mA

Rimax resistance 2.3 Ohms

Recommended battery NP7-12

Minimum battery voltage 21.0V

Maximum battery voltage 28,7V

Imax per panel 1,65A

Page 93: CAD-150 Installation Manual EN -  · PDF file5.3- ...Installation Steps 1 and 2 Loops ... Th vol ag hould b 230VAC. ... CAD-150_Installation_Manual_EN.pdf

95

GB

Output voltage 27,6 Vdc at 20ºC

Temperature compensation 3 mV/ºC x C

Maximum load current 1200 mA

Rimax resistance 2.3 Ohms

Recommended battery NP7-12 NP24-12 Plus version

Minimum battery voltage 21.0V

Maximum battery voltage 28,7V

Imax per panel 1,65A

User level code 1111

Installator level code 2222