CA10 A004/GBA002 *FT2 Product DataSlip ring motor starting, reversing and plugging, star-delta...

3
Ltd. Page 1 of 3 CA10_A004/GBA002 *FT2_06/12A CA10 A004/GBA002 *FT2 Product Data f OFF YB BR RY 13 57 24 68 0 L1-L2 X X L2-L3 XX L3-L1 XX A004 17 5 2 4 L1 L2 L3 V 45° Switch type = CA10, ratings as per page 3. 3 phase, 3 wire with „OFF‰ voltmeter switch. Switch function = A004, switch chart and connection diagram as shown left. Mounting type = FT2, single hole, 22.5 Dia. • Black handle.

Transcript of CA10 A004/GBA002 *FT2 Product DataSlip ring motor starting, reversing and plugging, star-delta...

Page 1: CA10 A004/GBA002 *FT2 Product DataSlip ring motor starting, reversing and plugging, star-delta starting, 3 phase, 3pole. 220V - 240V 4kW 380V - 440V 7.5kW 500V 10kW 660V - 690V 10kW

Ltd.

Page 1 of 3 CA10_A004/GBA002 *FT2_06/12A

CA10 A004/GBA002 *FT2

Product Data

f

OFF

YBBRRY

1 3 5 7

2 4 6 80L1-L2 X XL2-L3 X XL3-L1 X X

A004

1 7 5

2 4L1L2L3

V

45°

• Switch type = CA10, ratings as per page 3.

• 3 phase, 3 wire with „OFF‰ voltmeter switch.

• Switch function = A004, switch chart and connection diagram as shown left.

• Mounting type = FT2, single hole, 22.5 Dia.

• Black handle.

Page 2: CA10 A004/GBA002 *FT2 Product DataSlip ring motor starting, reversing and plugging, star-delta starting, 3 phase, 3pole. 220V - 240V 4kW 380V - 440V 7.5kW 500V 10kW 660V - 690V 10kW

Page 2 of 3

Ltd.

CA10_A004/GBA002 *FT2_06/12A

Dimensional Data

3,2 0.20

+

0.40

+

22,3

0.4

0+

24,1

Page 3: CA10 A004/GBA002 *FT2 Product DataSlip ring motor starting, reversing and plugging, star-delta starting, 3 phase, 3pole. 220V - 240V 4kW 380V - 440V 7.5kW 500V 10kW 660V - 690V 10kW

Page 3 of 3 CA10_A004/GBA002 *FT2_06/12A

Ltd.

CA10 - Electrical Rating Data

Main Contacts, AC Values to IEC 60947, BS EN 60947

Rated Insulation Voltage, Ui 1) 690V

Rated Thermal Current, lth 20A

Rated Operational Current, Ie

AC-20A No-Load operation 20A

AC-21A Switching of resistive loads, including moderate overloads 20A

AC-22A Switching of combined resistive or low inductive loads, including moderate overloads 20A

AC-15 Switching of control devices, contactors, valves etc.220V - 240V 5A

380V - 440V 4A

Rated Utilization Category

AC-2 Slip ring motor starting, reversing and plugging, star-delta starting, 3 phase, 3pole.

220V - 240V 4kW

380V - 440V 7.5kW

500V 10kW

660V - 690V 10kW

AC-3 Direct-on-Line starting, star-delta starting,3 phase, 3pole.

220V - 240V 3kW

380V - 440V 5.5kW

500V 5.5kW

660V - 690V 5.5kW

AC-4 Direct-on-Line starting, reversing, plugging and inching 3 phase, 3pole.

220V - 240V 0.55kW

380V - 440V 1.5kW

500V 1.5kW

660V - 690V 1.5kW

AC-23A Frequent switching of motors or other high inductive loads 3 phase, 3pole.

220V - 240V 3.7kW

380V - 440V 7.5kW

500V 7.5kW

660V - 690V 7.5kW

Short Circuit Protection

Max. fuse size (gL/gG-characteristic) 25A

Rated short-time withstand current (1second) 140A

Max. Permissible Wire Gage - copper wires only

Single-core or stranded wire 2 x 2.5mm²

Flexible wire 2 x 2.5mm²

1) Valid for lines with grounded common neutral termination, overvoltage category lll.