C165 QUICK START GUIDE GETTING STARTED Press ”Power” in fresh air and allow to count- down for Fresh Air purge. Rotate selector dial to Flue 1. In fresh air, O 2 reading should be 20.9% ±0.3%. Rotate selector dial to Flue 2. In fresh air, CO reading should be zero (0). Connect the flue probe thermocouple connector to T1. Connect flue probe to water trap. Connect optional probe to T2. T2 T1 P1 P2 Menu Room CO Status Aux Flue1 Flue 2 Com Test Exch Test TIME 60 Prs/Temp Menu Room CO Status Aux Flue1 Flue 2 Com Test Exch Test Tf 42.4% Ta 0.03m Prs/Temp BASIC CO/COMBUSTION ANALYSIS Insert Flue probe into stack. Adjust cone so end of the probe is approximately at the center of the stack. NOTE: You will have to drill a hole at least 3/8”. Use appropriate sealing method after testing. Rotate selector dial to Flue 1 for: CO 2 , O 2 , Gross efficiency, Flue temperature, Inlet temperature. Fuel type can be changed via MENU or STATUS setting Rotate selector dial to Flue 2 for: CO (ppm), Losses calculated, Excess air %, pressure reading Fuel type can be changed via MENU or STATUS setting. Make any adjustments as needed for proper combustion and wait for ana- lyzer to display change in readings. (Repeat as necessary). Once complete, remove probe from stack, allow analyzer to purge in fresh air until CO sensor readings return to ZERO (0) and O 2 readings reading return to 0% to 21%. Continue to the next test or power analyzer off by pressing On/Off, if finished. NOTE: Print and store functions may be used at any time during testing. Status Aux Flue1 Flue 2 Com Test Exch Test FRESH AIR PURGE TURN OFF TIME 5 Prs/Temp Menu Room CO Status Aux Flue1 Flue 2 C165 Com Test Exch Test XAIR O2++% PRS 0.00i Prs/Temp Menu Room CO Status Aux Flue1 Flue 2 C165 Com Test Exch Test EfG O2++% Tf 42.4% Ta 0.03m Prs/Temp DIFFERENTIAL TEMPERATURE TEST Rotate the selector dial to Pressure/Temperature. Press ”Pump” to ZERO (0) pressure sensor. Connect probe to T1. Connect probe to T2. Compatible with any K-Type thermocouple probe or clamp. Connect thermocouples in test location to start testing Observe T1, T2 and differential (Delta T). Press “Print” to print results. Press and Hold to log results. T2 T1 P1 P2 Aux Flue1 Flue 2 Com Test PRS 0.04i i= inH20 T1 167,1F T2 104.3F T 62.8F Prs/Temp Menu Room CO Status Aux Flue1 Flue 2 Com Test Exch Test PRESS TO ZERO Prs/Temp Menu Room CO Status Aux Flue1 Flue 2 Com Test Exch Test Prs/Temp T1 167,1F T2 104.3F T 62.8F Menu Room CO Status Aux Flue1 Flue 2 Com Test Exch Test Prs/Temp PRESS TO ZERO

Transcript of C165 QuiCk Start Guide · C165 QuiCk Start Guide GETTING STARTED Press ”Power” in fresh air and...

Page 1: C165 QuiCk Start Guide · C165 QuiCk Start Guide GETTING STARTED Press ”Power” in fresh air and allow to count-down for Fresh Air purge. Rotate selector dial to Flue 1.In fresh

C165 QuiCk Start Guide

GETTING STARTED

Press ”Power” in fresh air and allow to count-down for Fresh Air purge.

Rotate selector dial to Flue 1. In fresh air, O2 reading should be 20.9% ±0.3%.Rotate selector dial to Flue 2. In fresh air, CO reading should be zero (0).

Connect the flue probe thermocouple connector to T1.Connect flue probe to water trap. Connect optional probe to T2.

T2 T1

P1 P2

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

FRESH

AIR

PURGE

TIME 60

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

NAT GAS

C02 8.3%

O2 20.9%

EfG O2++%

Tf 42.4%

Ta 0.03m

Prs/Temp

BASIC CO/COMBUSTION ANALYSIS

Insert Flue probe into stack.Adjust cone so end of the probe is approximately at the center of the stack.NOTE: You will have to drill a hole at least 3/8”. Use appropriate sealing method after testing.

Rotate selector dial to Flue 1 for: CO2, O2, Gross efficiency, Flue temperature, Inlet temperature.Fuel type can be changed via MENU or STATUS setting

Rotate selector dial to Flue 2 for: CO (ppm), Losses calculated, Excess air %, pressure readingFuel type can be changed via MENU or STATUS setting.Make any adjustments as needed for proper combustion and wait for ana-lyzer to display change in readings. (Repeat as necessary).

Once complete, remove probe from stack, allow analyzer to purge in fresh air until CO sensor readings return to ZERO (0) and O2 readings reading return to 0% to 21%.Continue to the next test or power analyzer off by pressing On/Off, if finished.NOTE: Print and store functions may be used at any time during testing.

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

FRESH AIR

PURGE

TURN

OFF

TIME 5

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

NAT GAS

CO 80P

COa 80P

LOSS O2++%

XAIR O2++%

PRS 0.00i

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

NAT GAS

C02 8.3%

O2 20.9%

EfG O2++%

Tf 42.4%

Ta 0.03m

Prs/Temp

DIFFERENTIAL TEMPERATURE TEST

Rotate the selector dial to Pressure/Temperature.

Press ”Pump” to ZERO (0) pressure sensor.

Connect probe to T1.Connect probe to T2.Compatible with any K-Type thermocouple probe or clamp.

Connect thermocouples in test location to start testingObserve T1, T2 and differential (Delta T).

Press “Print” to print results.

Press and Hold to log results.

T2 T1

P1 P2

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

PRS 0.04i

i= inH20

T1 167,1F

T2 104.3F

T 62.8F

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

PRS/TEMP

PRESS

TO

ZERO

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

Prs/Temp

PRS 0.04i

i= inH20

T1 167,1F

T2 104.3F

T 62.8F

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

Prs/Temp

PRS/TEMP

PRESS

TO

ZERO

Page 2: C165 QuiCk Start Guide · C165 QuiCk Start Guide GETTING STARTED Press ”Power” in fresh air and allow to count-down for Fresh Air purge. Rotate selector dial to Flue 1.In fresh

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

BLOWER ON

NAT GAS

CO 0p

O2 20.0%

XAIR 02++%

TIME 60

Prs/Temp

DRAFT & STATIC PRESSURE TEST

T2 T1

P1 P2

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

Prs/Temp

PRS 0.04i

i= inH20

T1 167,1F

T2 104.3F

T 62.8F

Rotate the selector dial to Pressure/Temperature.

Press ”Pump” to ZERO (0) pressure sensor.

Connect true draft hose to PI.Connect to P2 for differential.Place probe tip in stack to measure draft.Connect static pressure hose for measure differential pressure.

Place true draft probe tip in the flue to measure draft.You can also use the combustion probe for measuring pressure.

Press “Print” to print results.

Press and Hold to log results.

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

PRS/TEMP

PRESS

TO

ZERO

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

Prs/Temp

PRS/TEMP

PRESS

TO

ZERO

HEAT EXCHANGER TEST

Rotate selector dial to EXCH Test, press the “Print”.

Confirm the Fuel Type. Scroll or to switch a different fuel type.

Press to select fuel type.

NOTE: The analyzer will perform a fresh air purge if it did not perform one on start up. Otherwise it will skip past the zeroing step to the Blower Off screen. See manual for details.

Press to continue.

Ensure the analyzer is in fresh air during the countdown. The screen will automatically advance when complete.

Call for heat.Observe and wait for O2 readings to stabilize.After the blower turns on, press the Button to start the Post-Blower test.

There are many methods to test heat exchanger integrity. One of these is to observe Excess Air, O2 AND CO readings both before and after the blower turns on. If the heat exchanger is sealed your O2 and CO readings should remain fairly stable. A breach in the heat exchanger may allow fresh air to be forced into the flue after the blower turns on due to a pressure increase in the plenum. The result may be a rise in the measured O2 in the stack gas and an increase in the Excess Air. In some sealed systems the fresh air drawn in the breach may reduce the combustion available leading to an increase in the CO reading. If either of these situations are present it is probable that there is a problem with the Heat Exchanger which may require additional testing and inspection.NOTE: Many cracks are invisible to borescopes or the naked eye and only open or separate from pressure or temperature during operation.

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

EXCHANGE

TEST

TO

START

PRESS

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

SETUP

FUEL TYPE

NAT GAS

PRESS

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

EXCHANGE

WITH PROBE

IN FRESH

AIR

PRESS

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

BLOWER OFF

NAT GAS

CO 0p

O2 20.0%

XAIR 02++%

PRESS

Prs/Temp

The analyzer will wait 60 seconds and then record the Post-Blower values for CO, 02 and Excess Air.

Test results will automati-cally be stored to exchange reports. Report includes both Pre and post Blower test segments.

Press to start printing.See REPORTS section in this guide.

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

EXCHANGE

ZEROING

TIME 60

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

LOG No. 10

12:00:00

CO 0p

O2 20.0%

XAIR 02++%

PRINT

Prs/Temp

Page 3: C165 QuiCk Start Guide · C165 QuiCk Start Guide GETTING STARTED Press ”Power” in fresh air and allow to count-down for Fresh Air purge. Rotate selector dial to Flue 1.In fresh

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

Prs/Temp

O2 20.9%

CO 0P

C02 8.3%

XAIR 42.4%

PRS -0.02i

Ta 80.3F

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

MENU

SETUP

UNITS

SCREEN

REPORT

SERVICE

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

ROOM CO

TEST 1/15

INT. 120s

CO 5p

LIMIT 10p

ALARM 30p

Prs/Temp

REPORTS: PRINTING & VIEWING

HIGH CO ALERT

Press ”Print” to start printouts of results from any test screen.

Press during printing to cancel.

Press and hold to log current readings.Align printer above Analyzer.

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

NAT GAS

Ra 0.0010

CO 80P

C02 8.3%

XAIR 42.4%

PRS 0.03m

Prs/Temp

To view test results, rotate dial to Menu.Scroll or to Report Press to select.

Scroll or to type of test wanted.

Press to select. [Exchange shown]Press to select View.

Press to select report log number. When indicator lights blink, use or to scroll through logged reports.

Press to view a selected report log.

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

NAT GAS

Ra 0.0010

CO 80P

C02 8.3%

XAIR 42.4%

PRS 0.03m

Prs/Temp

At 1000 ppm CO the screen will display HIGH CO and an indicator light will flash and analyzer will beep several times. Above 2000 ppm the purge pump starts.

Print and Log easily from the following test screens: Aux, Flue 1, Flue 2, Commission Test, Pressure/Temperature, Exchange Test and Room CO

CO ROOM TEST

No probes or hose connections required for this test.Rotate selector dial to ROOM CO.

Press ”Print” to start the GENERAL test.

Press start the test. CO readings will be logged every 2 minutes for a 30 minute time span.Readings will be stored once the 30 minute test is completed.

Press to print results. Test results will automatically be stored in ROOM CO reports.See REPORTS section in this guide.

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

ROOM CO

LOG No. 1

TEST 1

CO 5p

GENEAL

PRINT

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

SELECT

ROOM CO

TEST TYPE

GENERAL

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

ROOM CO

PRESS

TO

START

Prs/Temp

Great for checking ambient CO and back drafting situations

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

MENU

SETUP

UNITS

SCREEN

REPORT

SERVICE

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

SCREEN

CONTRAST

BACKLIGHT

AUX

BACK

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

AUX

LINE 1

LINE 2

LINE 3

LINE 4

LINE 5

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

SCREEN

AUX

LINE 5

PRS 0.02i

Prs/Temp

AUX SETTING

Rotate selector dial to Menu.Scroll or to Screen.

Press ”Print” to select.

Scroll or to AUX.

Press to select.

Scroll or to customize any Line.

Press to select.[Line 5 shown]

Scroll or to select the parameter for this line.

Press to select.[Pressure shown]

Rotate selector dial to AUX to view.Custom selections will now display in AUX mode.

Programmable Auxiliary screen allows for Tech selectable test parameters to be chosen.

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

REPORT

AUX

COMBUSTION

COMBUSTION

PRS/TEMP

EXCHANGE

Prs/Temp

Menu Room CO

Status

Aux

Flue1 Flue 2

C165

Com Test

Exch Test

LOG No. 9

12:00:00

CO 0p

02 20.9%

XAIR O2++%

PRINT

Prs/Temp

Page 4: C165 QuiCk Start Guide · C165 QuiCk Start Guide GETTING STARTED Press ”Power” in fresh air and allow to count-down for Fresh Air purge. Rotate selector dial to Flue 1.In fresh

www.ueitest.com Email: [email protected] USA: 1-800-547-5740 • 503-643-6322

CANADA: 1-877-475-0648 • 604-278-4311

Copyright © 2019 Kane USA, Inc. All Rights Reserved L466 0119

MAIN MENU SUB MENU OPTIONS / COMMENTS

SETUP LANGUAGE English

SET TIME HH:MM:SS formate.g. 7 am = 07:00:00, 7 pm = 19:00:00

SET DATE MM/DD/YY format

PRINTER KM IRPKANE IRP-2WIRELESS (if installed)SERIAL

PASSKEY 1111 (wait 5 secs after entering last digit)

BACK

UNITS FUEL TYPE NAT GAS, TOWN GAS, COKE GAS, PROPANE, BUTANE, LPG, LIGHT OIL, BIO OIL, WOOD PELLETS, BIO GAS, USER 1 to 5

FUEL ORIGIN UK, FRANCE, SPAIN, N AMERICA, BELGIUM, NETHERLAND

EFFICIENCY GROSS, NET, GROSS COND, NET COND

PRESSURE FILTER: OFF = normal response. ON = slower (damped) response

RESOLUTION: LOW = e.g. 0.00i inH20 resolution. HIGH = displays to an extra decimal place

UNITS: mbar, Pa, PSI, mmHg, hPa, inH2O, mmH20, kPa, psi

TIME: Test units not available in North American market

BACK:

GAS ppm, ppm(n), mg/m3, mg/m3(n), mg/kWh, mg/kWh(n)

TEMP C, F

02 REF Up/down to set value (3% default)

NOx CALC Up/down to set value (5% default)

BACK

SCREEN CONTRAST Factory setting is 14

BACKLIGHT 0 to 300 secs

AUX Enables users to customize the parameters on the AUX display: LINE 1, LINE 2, LINE 3, LINE 4, LINE 5, LINE 6, BACK

BACK

REPORT AUX Stored AUX testsVIEW, DEL ALL, BACK

COMBUSTION Stored combustion tests: VIEW, DEL ALL, BACK

COMMISSION Stored commission tests: VIEW, DEL ALL, BACK

PRS/TEMP Stored pressure tests: VIEW, DEL ALL, BACK

EXCH Stored exchange tests: VIEW, DEL ALL, BACK

ROOM CO Stored room CO tests: VIEW, DEL ALL, BACK

HEADER LINE 1LINE 2BACK

BACK

SERVICE CODE Password protected for authorized service agents only. Leave set to 000000.