C11 Brosura GB Lunga
-
Upload
florintermure -
Category
Documents
-
view
46 -
download
0
description
Transcript of C11 Brosura GB Lunga
-
Technical brochure- Polyphase meters- Class 1, 2, or 3 accuracy
Electricity meters114/116 Series
-
C114/116 meter family
SchlumbergerResourceManagementServices
2
Schlumberger Resource ManagementServices (RMS) is the leading utilitysupplier that spans all energy andresource industries - water, gas,electricity and heat. Services andsolutions for the resource industryinclude:
n Project design and implementation n Meter management services n Data management systems
and services n Metering products and consulting
services.
Schlumberger RMS builds andoperates integrated metering-basedsolutions for residential, commercial,industrial, transmission and distributionapplications and specializes inworking with clients of all sizes,from small local utilities in developingregions to the most advancedmulti-resource, multi-country utilityin regulated or deregulated markets.
-
1 General presentation ............................................................................................................................................................... 4
1.1 Construction ...................................................................................................................................................................................... 5
1.2 Mechanical tariff units ............................................................................................................................................................ 7
1.3 Adjustment facilities .................................................................................................................................................................. 8
1.4 114 Series meters ...................................................................................................................................................................... 10
1.5 116 Series meters ...................................................................................................................................................................... 11
2 Technical specifications
2.1 Four-wire meters .......................................................................................................................................................................... 12
2.2 Three-wire meters ...................................................................................................................................................................... 13
3 Average error curves
3.1 C114U ...................................................................................................................................................................................................... 14
3.2 C114W-1/6 ........................................................................................................................................................................................... 15
3.3 B114W-1/6 .......................................................................................................................................................................................... 16
3.4 C116W-1/6 Class 1.0 ................................................................................................................................................................... 17
3.5 B116W-1/6 Class 1.0 .................................................................................................................................................................. 18
4 Circuit diagrams
4.1 DIN version ................................................................................................................................................................................ 19-21
4.2 UTE version ............................................................................................................................................................................... 22-23
5 Dimensional drawings
5.1 DIN version ................................................................................................................................................................................ 24-26
5.2 UTE version ................................................................................................................................................................................ 27-28
5.3 Order sheet ........................................................................................................................................................................................ 30
6 Available Types ........................................................................................................................................................................... 31
Contents
3
-
HousingThe 114 meter family can besupplied in two different housings:
DIN version for asymmetricalconnections
UTE version for symmetricalconnections
DIN version - Housing dimensionsn For meters with direct connection
up to 80A maximum currentaccording to DIN 43857
n Up to 120A maximum current withreinforced terminals
n Up to 160A maximum current with reinforced terminals
n For transformer-operated meters according to DIN 43859
UTE version - Housing dimensionsn For meters with direct connection
up to 100A maximum current n Up to 120A (on special request up
to 160A) maximum current withreinforced terminals.
n For transformer-operated meters
The meter familyDirect connection
n Active energy meters -Class 2 accuracyFour-wire meters C114 up to 1000% load capacityThree-wire meters B114 up to 600% load capacity
n Reactive energy meters -Class 3 accuracyFour-wire meters BVC114 up to1000% load capacityThree-wire meters BVB114 up to600% load capacity
Transformer connectionn Active energy meters -
Class 2 accuracyFour-wire meters C114W Three-wire meters B114W 600% load capacity
n Active energy meters -Class 1 accuracyFour-wire meters C116W Three-wire meters B116W 600% load capacity
n Reactive energy meters -Class 3 accuracyFour-wire meters BVC114W Three-wire meters BVB114W 600% load capacity
Standardsn Metrology and general design
In addition to the aforementionedstandards, the 114/116 meter familyis designed to meet the requirementsof major international and nationalstandards.
n ApprovalThe 114/116 meter family isapproved by key national legalauthorities.The meters are CE marked, andseveral models have theEuropean Approval (EEC -Approval).
n Insulating classIP 54 according to IEC 60529.
1- General
4
PropertiesBoth the 114 family (as activeclass 2 meter according to IEC60521, and as reactive class 3meters according to IEC60145), and the 116 family(as active class 1.0 metersaccording to IEC 60521) ofpolyphase electromechanicalmeters are designed tomeet the most stringentrequirements for metering inresidential, commercial andindustrial applications.They are available for directand transformer connectionas three- and four-wire meters.
Due to their solid design andexceptionally high torque, theyexhibit excellent metrologicalcharacteristics. Throughcareful selection of key designparameters, meters designedfor various network types,reference voltages and loadcurrents exhibit essentially thesame typical error curves andbehavior.
-
Meter housingThe meter housing consists of abaseplate, cover and terminal cover.
DIN version
n BaseplateThe baseplate (black duroplast)and the terminal block form acommon moulding. The upper suspension lug can berotated by 180, enabling the meterto be installed in covered oruncovered locations.The diameter of the current terminalsmeets the requirements for thedifferent maximum currents:up to 80A 7.2mmup to 120A 9.5mmup to 160A 11.2mmTransformer connected 5mm.The terminals are suitable forcopper and aluminium cables.The terminal block has slopedcable inputs to facilitate cableinstallation.The terminal block iscovered by an insulating piece onwhich the lower suspension lugsare also located. Into this insulatingpiece can be laid up to 12 auxiliaryterminals for transformer connectedand up to 9 for direct connectedmeters to support incoming andoutgoing functions for tariff devices.The bore diameter of the auxiliaryterminals is 3.2mm.
n CoverTwo different designs of covers areavailable:transparent cover standarddesign - and black cover with glasswindow.The cover is fixed to the baseplateby two sealable captive screws onthe sides.
n Terminal coverIn order to meet the cablerequirements of different maximumcurrents the following terminalcovers are available:- without free space (black
duroplast) up to 160A, - 40mm of free space (black duroplast)
for transformer connection,- 60mm of free space (black duroplast)
up to 80A,
- free space 60mm (blackpolycarbonate) up to 80A,
- free space 80mm (black duroplast) up to 160A.
The terminal cover is fixed to the terminal block by two sealablecaptive screws.
UTE version
n BaseplateThe baseplate (black duroplast)and the terminal block are separateparts that are fastened together.The upper suspension lug has6 different positions, enabling themeter to be installed in coveredor uncovered locations.The diameter of the current termi-nals meets the requirements of thedifferent maximum currents:up to 100A 8.2mmup to 120A 9.5mm(up to 160A 9.5mm)Transformer connected 4.5mm.The terminal block for direct con-nected meters has 8 phase and neu-tral terminals, and 3 auxiliaryterminals . The bore diameter ofthe auxiliary terminals is 3mm.The terminal block of transformerconnected meters has 14 terminalsfor incoming and outgoing functionsof phases, neutrals and tariff andpulse devices.The lower suspension lugs arelocated on the terminal blocks.
n CoverTwo different desings of covers areavailable:Transparent cover - standarddesign - and black cover with glasswindow.The cover is fixed to the baseplateby three sealable captive screws,arranged at the sides and the top.
n Terminal cover Without free space up to 160A,free space 38mm up to 60A,free space 62mm for transformerconnection,free space 65mm up to 120A (forspecial request up to 160A).The terminal cover is fixed to theterminal block by two sealablecaptive screws.
Measuring system support frameThe measuring system support frameconsists of an aluminium alloydie-casting. In order to guaranteehigh mechanical stability it is abox-shaped construction with strongreinforcing ribs. This ensures accuratepositioning of all parts fixed to it.The measuring system supportframe is fixed without distortionby two screws in the baseplatewhich is reinforced at thecontact surfaces.
The driving elementsThe voltage and current systems aremounted on the measuring system support frame. The voltage coils aretotally encapsulated in thermoplasticmaterial. Current and voltage coresstand tangentially to the rotor disc.The two limbs of the current corecarry the varnished copper currentcoil which generates the currentdriving flux. They are insulated fromthe current core by a plastic coil former having a high electrical and thermal resistance.The 3 driving elements of the four-wiremeter are arranged such that the twodiametrically arranged S and T ele-ments act on the lower rotor disc.The R element and the brake magnetact on the upper rotor disc. Three-wire meters with 2 driving elementshave the same construction, only thathere the S element is omitted.
Brake magnetThe double-flux brake magnetconsists of two plate-shaped Alnicopermanent magnets. These magnetsare glued in a steel bracket whichserves as a return leg. The temperature compensation is integrated in the magnet material.For fine adjustment, a swiveling steeltongue is fixed on the brake element.The brake element is fixed directly tothe measuring system support frame.
Meter rotorThe meter rotor consists of two1mm thick aluminium discs of100mmdiameter, which are permanentlyjoined to the rotor shaft by
1.1 - Construction
5
-
12
3
8
9
45
67
diecasting. The upper rotor dischas 400 divisions and a red markon its periphery.
Double jewel bearing system
n Upper needle bearing The upper needle bearing is fixedwith a screw to the measuringsystem support frame. The upperend of the rotor shaft (3), coveredby the upper bearing sleeve (2),projects into the bearing hole of theupper bearing housing (1) and iscentred by a highly polished needlewith a diameter of 0.4mm. Theupper bearing sleeve is designed toalso act as a worm gear, andtransfers the rotor rotations tothe register.
n Double jewel bottom bearing The double jewel bottom bearing isdesigned as a closed unit to guardagainst dust ingress, and is fixedby a screw to the measuringsystem support frame. The bottombearing housing (9) contains thebearing chamber (4) with the twojewel nipples (5, 7) and the bearingball (6). The bearing chamber (4) is held in the bottom bearing housing(9) via a compression spring (8)by means of a stop bush ball plug
Magnetic bearing system
n Upper needle bearing The upper needle bearing is fixedwith a screw to the measuringsystem support frame. The upperend of the rotor shaft (4), coveredby the upper bearing sleeve (3),projects into the bearing hole ofthe top bearing housing (1) and iscentred by a highly polished 0.4mmdiameter needle (2). The upperbearing sleeve is designed to alsoact as a worm gear, and transfersthe rotor rotations to the register.
n Magnetic bottom bearing A bottom bearing sleeve (5) with acentral bore is fitted at the lower endof the rotor shaft (4). The bottombearing sleeve (5) is centred by a highpolished needle (8) and carries apermanent magnet disc (6) intowhich two concentric pole rings aremagnetized. The outer pole ring is a magnetic north pole, and the inner isa magnetic south pole.The bottom bearing housing (9) bearsa similar magnetic disc (7). Both(9 and 7) are fixed by a screw to themeasuring system support frameThe weight of the rotor is constantly balanced by the forces actingbetween the two magnets.
Figure 1. Double jewel bearing system
Bearing systemsTwo different bearingsystems for the meter rotor areavailable:
Double jewel bearing system(figure 1) andMagnetic bearing system (figure 2)
Double jewelbearing system1 Upper bearing housing
2 Upper bearing sleevewith worm
3 Rotor shaft
4 Bearing chamber
5 Top jewel nipple
6 Bearing ball
7 Bottom jewel nipple
8 Compressing spring
9 Bottom bearing housing
6
7
1
2
3
89
4
56
Figure 2. Magnetic bearing system
-
Figure 3. Single-tariff register Figure 4. Double-tariff register
Single-tariff registerRegistration with single-tariff registersis accomplished by means of acyclometer register, fitted with a7-digit display as standard (seefigure 3). The plastic cipher rolls,stepping drives and gear wheelsrun without lubrication on highlypolished shafts which at one endare pressed into a stamped andfolded part. A slidable plasticpart arranged on the left endenables accurate adjustment ofthe end play of cipher rolls and gearwheels. When being fitted,the register is pushed up against aboundary surface on the uppermeasuring system support andthen fixed with a screw.The nameplate is fixed onto thealuminium stamped stand, via ahook-in nose on the left of the registerand a screw on the right of thecipher cutout.
Two-tariff registerRegistration with two-tariff registersoccurs by means of a twinroll registerwith a 7-digit display as standard (seefigure 4). It works according to theswinging shaft principle. The registerbracket consists of a stamped andfolded part of 1.5mm thick aluminiumsheet. The two shafts each for cipherrolls and drives are at one end pressedinto the aluminium stand and at theother end held by a plastic part, whichholds the register bracket, the shaftsand clamps, the cutout blade relaywith its shielding, and the PCB.The nameplate is fixed onto thestamped aluminium stand via twohook-in noses on the right side of theregister and a screw at the lever of thecipher cutout on the left.The switch-over will be done by thesame voltage, to which the meter isconnected but on special request thisswitch-over voltage can be different.
Further options
n Reverse running stop R1 with 1 stopping pointR with 20 stopping points
n Pulse emitters Various designs, - with S0 interface acc. to DIN 43864:L3 with direction of rotation logic.X6 without direction of rotationlogic.X7 without EEC-approval.
- with potential-free pulse outlet: L3F
n Voltage failure indicator D
n Dual voltage versionsFour-wire meters C114 for twonominal voltages, e.g.3 x 127/220V & 3 x 220/380V.
n Voltage linksFor direct connected meters, stan-dard version: under the terminalcover, special version: under themeter cover, only or additional.
1.2Mechanicaltariff units
Magnetic bearingsystem1 Upper bearing housing
2 Upper bearing needle
3 Upper bearing sleeveand worm
4 Rotor shaft
5 Bottom bearing sleeve
6 Permanent magnet disc
7 Permanent magnet disc
8 Bottom bearing needle
9 Bottom bearing housing
7
-
62
3
16 15
12
95
1314
10
8
99
77
66
44
33
11 22
55
88
1010 1111 1212
TT
11SS
R
7
1
4
1.3Adjustmentfacilities
1 Voltage core2 Voltage coil3 Current core4 Current coil5 Return arm6 Brake magnet7 Fine adjustment brake
magnet8 Phase adjustment9 Swivelling lever for
low-load setting10 Low-load screw for
low-load setting11 Torque screw12 Holding vane on driving
element13 No-load hook14 Rotating field lever15 Current shunt16 Spacer
Low-load settingThe low-load setting is adjusted withthe low-load screw (10). When it isoperated, a swiveling lever (9) fixed tothe voltage return of the R systemchanges its position relative to thecentre pole of the voltage core.In systems S and T adjustment tostandstill proceeds in the same waywith voltage connected.
Torque compensationFor torque balancing a screw (11) inthe return leg of the voltage system isprovided. By turning this adjustmentscrew the airgap of a magnetic shuntpath on the voltage system and hencethe voltage driving flux is altered.
Phase sequence compensationFor four-wire active energy meters arotating field lever (14) between therotor shaft and the T-system compen-sates the rotating field dependent errortorques on low load. Adjustmentproceeds at low-load connected inincorrect phase sequence.
Phase compensationTo set the 90 displacement betweenthe driving fluxes required on non-
inductive load, two copper vanes (8)are swung into the shunt gap of thevoltage core by turning the fixing shaft. Coarse adjustment of the phase angleis achived by opening the short-circuiting rings on the current core.
Braking forceThe braking force can be coarsely var-ied by swinging the braking systemabout its mounting point. Fineadjustment is achieved by means of asteel swivelling tongue (7) which actsas a magnetic shunt and, depending onits setting, weakens to a greater orlesser extent the magnetic flux actingon the rotor disc.
Starting/no-load settingThe starting on no-load setting isadjusted by means of the holdingvane (12) fixed to one driving element,which attracts the no-load hook (13)to be found on the rotor shaft. Theholding vane (12) is located in systemS only for four-wire active energymeters, for all other types it is locatedin element T. For accurate adjustmentthe distance between these two partscan be altered by bending theholding vane.
Figure 5. Adjusting facilities
8
-
Each figure must have a cap-tion. The caption cannot beexactly the same as the body
Figure 6. Three-phase meter model C114U - Main cover and register removed
3
9
6854
7
1
6
54
45
6
2
1 Driving element R (L1)2 Driving element S (L2)3 Driving element T (L3)4 Low-load screw5 Torque screw6 Phase adjustment7 Fine adjustment
on brake magnet8 Starting - no load9 Adjustment device
for phase sequence
9
-
Direct connected meters, 114 SeriesDirect connected meters are availablewith a load capacity of up to 1000%.They can be supplied with maximumcurrents up to 160A.Direct connected meters can beequipped with up to 9 (DIN version)resp. 3 (UTE version) auxiliaryterminals to support incoming andoutgoing functions of tariff devices.
Active energy, class 2.0 according to IEC 60521
n Four-wire design(can be used also in three-wire networks)C114G 400% load capacityC114N 500% load capacityC114U 600% load capacityC114K 800% load capacityC114T 1000% load capacity
n Three-wire designB114G 400% load capacityB114U 600% load capacity
Reactive energy, class 3.0 according to IEC 60145Three- and four-wire meters Model114 are also available as reactiveenergy meters, being recognizableby the model code prefix BV:The voltage coils are operated inan artificial circuit, to maintain thecorrect phase position of the drivingfluxes.Also in the three-wire meter,3 voltage systems are used, wherebyno series resistors are necessary.BV-meters are always equippedwith a reverse running stop.
n Four-wire design(can be used also in three wire networks)BVC114G 400% load capacityBVC114N 500% load capacityBVC114U 600% load capacityBVC114K 800% load capacityBVC114T 1000% load capacity
n Three-wire designBVB114G 400% load capacityBVB114U 600% load capacity
Transformer connected meters,114 SeriesActive and reactive energy three -andfour-wire meters are supplied for con-nection to instrument transformerswith a load capacity up to 600%. Theprogramme covers all applications for120 and 200% load capacity currenttransformers.Transformer-operated meters can beequipped with up to 12 (DIN version)resp. 4 (UTE version) auxiliaryterminals to support incoming andoutgoing functions of tariff devices.Active energy transformer-operatedmeters have the accuracy class 2.0.Reactive energy (BV) transformer-operated meters have the accuracyclass 3.0. BV-meters are alwaysequipped with a reverse running stop.
Active energy, class 2.0according to IEC 60521
n Four-wire design(can be used also in three-wirenetworks)C114W-0.2/1.2 for 1A transformerC114W-1/6 for 5A transformerC114W-1.66/10 for 5 (10)Atransformer
n Three-wire designB114W-0.2/1.2 for 1A transformerB114W-1/6 for 5A transformerB114W-1.66/10 for 5 (10)Atransformer
Reactive energy, class 3.0 according to IEC 60145
n Four-wire design(can be used also in three-wire networks)BVC114W-0.2/1.2 for 1AtransformerBVC114W-1/6 for 5A transformerBVC114W-1.66/10 for 5 (10)Atransformer
n Three-wire designBVB114W-0.2/1.2 for 1AtransformerBVB114W-1/6 for 5A transformerBVB114W-1.66/10 for 5 (10)Atransformer
1.4 114 Series meters
10
-
Transformer connected high precisionmeters Class 1.0 accuracy, according toIEC 60521
The load capacity of these meters is upto 600%.
They are suitable for invoicing largerquantities of energy in substations orfor heavy consumers, and as comparatoror standard meters for testing and adjusting meters in general service.
The programme covers all applicationsfor 120 and 200% load capacitycurrent transformers.
They can be equipped with up to 12(DIN version) or 4 (UTE version) auxiliary terminals for incoming andoutgoing signals.
To meet the requirements for Class 1.0with the various influence quantities:
- the rated speed is reduced bybraking the meter rotor.
- the drop of the error curve in the low-load range is minimized by the use of a current core material with low remagnetization losses.
- the error curve drop from the highest point on the curve to the load limit is reduced by use of acurrent shunt.
- the torque for meters for connection to 120% load capacity transformers is increased by 20% by means of reinforced voltage and current driving fluxes.
1.5116 Series meters
11
-
Direct connected meters at 3 x 230/400VTransformer-connected meters additionally at 3 x 58/100V
n All four-wire meters are for ratedvoltages between 3 x 58/100V and 3 x 290/500V.
n The burdens in the voltage circuit at 50Hz for meters of class 2 and class3 accuracy are uniformly on average1.05W and 4.40VA, and for meters ofclass 1 accuracy, they are 1.10W and4.80VA respectively.
n The burdens in the voltage circuit at60Hz for meters of class 2 and class3 accuracy are uniformly on average0.85W and 4.10VA, and for meters ofclass 1 accuracy, they are 0.90W and4.30VA respectively.
Other meter layouts on request.
2.1 - Technical DataFour-wire meters
Direct connected
Transformer-operated
Transformer-operatedAccuracy Class 1.0
Meter modelfour-wire metersfor active energy
Class 2.0
C114G
C114NC114U
C114K
C114T
C114W-0.2/1.2C114W-1/6C114W-1.66/10
BVC114W-0.2/1.2BVC114W-1/6BVC114-1.66/10
BVC114G
BVC114NBVC114U
BVC114K
BVC114T
(40)(80)
(100)(30)(60)
(120)(40)(80)
(160)(50)
(100)
1020205
10205
10205
10
400
500600
800
1000
120120200
155(10)
0.130.200.110.050.080.110.040.050.090.020.03
0.700.700.35
0.170.240.130.070.090.130.050.060.110.040.04
1.281.280.55
13.113.112.28.78.78.76.56.58.06.16.1
34.834.825.2
1500030001875
120606015075
37.512060
37.512060
3750750480
2.92.93.22.92.93.02.92.93.23.03.2
2.92.92.9
C116W-0.2/1.2C116W-1/6C116W-1.66/10
120120200
155(10)
0.870.870.35
1.601.600.55
41.941.925.1
1200024001500
3000600375
2.92.92.9
Four-wire metersfor reactive
energy Class 3.0
Loadcapacity
Rated(max.
currents)
CT ratedcurrent
(secondary)
Burdenper driving element in
current circuitat rated current
Torque atrated load
Net weightof meterwithoutterminal
cover
Meter constant
3x230/400V3x58/100V
[%ln] [A] [A] [W] [VA] [kg][x10-4 Nm]
[r/kWhresp.
r/kVArh]
[r/kWhresp.
r/kVArh]
(BV-meters alwayswith reverse running
stop)
12
-
2.2 - Technical DataThree-wire meters
Direct connected
Transformer-operated
Transformer-operatedAccuracy Class 1.0
Meter modelthree-wire
metersfor active
energyClass 2.0
B114G
B114U
B114W-0.2/1.2B114W-1/6B114W-1.66/10
BVB114W-0.2/1.2BVB114W-1/6BVB 114-1.66/10
BVB114G
BVB114U
(40)(80)
(120)(30)(60)
(120)(150)
1020305
102025
400
600
120120200
155(10)
0.130.200.250.050.080.110.11
0.870.870.35
0.170.240.290.070.090.130.14
1.601.600.55
7.57.57.55.05.05.05.9
25.125.115.1
1200024001500
964830120603030
3000600375
2.42.42.62.42.42.62.6
2.42.42.4
B116W-02/1.2B116W-1/6B116W-1.66/10
120120200
155(10)
0.870.870.30
1.601.600.50
24.224.214.5
960018751200
2400480300
2.42.42.4
Three-wire metersfor reactive
energy Class 3.0
Loadcapacity
Rated(max.
currents)
CT ratedcurrent
(secondary)
Borderper driving element in
current circuitat rated current
Torque atrated load
Net weightof meterwithoutterminal
cover
Meter constant
3x400V3x100V
[%ln] [A] [A] [W] [VA] [kg][x10-4 Nm]
(BV-meters always withreverse running stop)
[r/kWhresp.
r/kVArh]
[r/kWhresp.
r/kVArh]
Direct connected meters at 3 x 400VTransformer-connected meters additionally at 3 x 100V
n All three-wire meters are for rated voltages between 3 x 100V and 3 x500V.
n The burdens in the voltage circuit at 50Hz for meters of class 2 and class3 accuracy are uniformly on average1.05W and 4.40VA, and for meters ofclass 1 accuracy, they are 1.10W and4.80VA respectively.
n The burdens in the voltage circuit at60Hz for meters of class 2 and class3 accuracy are uniformly on average0.85W and 4.10VA, and for meters ofclass 1 accuracy, they are 0.90W and4.30VA respectively.
Other meter layouts on request.
13
-
Balanced load
Four-wire active energy meters, direct connectedClass 2.0 accuracy
C114U 5 (30)AC114U 10 (60)AC114U 20 (120)A
Unbalanced load
Voltage dependence at 50Hz
Temperature dependence at 50Hz
Frequency dependence at 50Hz
3.1Characteristicaveragecurves
Load dependenceat rated voltage UN, 50Hz and 60Hz and 23C (IN = rated current)
14
-
Four-wire active energy meters, transformer connectedClass 2.0 accuracy
C114W-1/6 , .../ 5A
Balanced load
Unbalanced load
Voltage dependence at 50Hz
Temperature dependence at 50Hz
Frequency dependence at 50Hz
3.2Characteristicaveragecurves
Load dependenceat rated voltage UN, 50Hz and 60Hz and 23C (IN = rated current)
15
-
Three-wire active energy meters, transformer connectedClass 2.0 accuracy
B114W-1/6, .../5A
Load dependenceat rated voltage UN, 50Hz and 60Hz and 23C (IN = rated current)
3.3Characteristicaveragecurves
Balanced load
Unbalanced load
Voltage dependence at 50Hz
Temperature dependence at 50Hz
Frequency dependence at 50Hz
16
-
Four-wire active energy meters, transformer connectedClass 1.0 accuracy
C116W-1/6, .../5A
Load dependenceat rated voltage UN, 50Hz and 60Hz and 23C (IN = rated current)
3.4Characteristicaveragecurves
Balanced load
Unbalanced load
Voltage dependence at 50Hz
Temperature dependence at 50Hz
Frequency dependence at 50Hz
17
-
Three-wire active energy meters, transformer connectedClass 1.0 accuracy
B116W-1/6, .../5A
Load dependenceat rated voltage UN, 50Hz and 60Hz and 23C (IN = rated current)
Balanced load
Unbalanced load
Voltage dependence at 50Hz
Temperature dependence at 50Hz
Frequency dependence at 50Hz
3.5Characteristicaveragecurves
18
-
Active energy Reactive energy
Direct connection
With current transformers
With current and voltage transformers
Direct connection
With current transformers
With current and voltage transformers
4.1DIN 43856Circuit diagrams Four-wiremetersfor four-wiresystems
19
-
Active energy Reactive energy
Direct connection
Artificial connectionwith 2 current transformers
Artificial connection with2 current and voltage transformers
Direct connection
Artificial connectionwith 2 current transformers
Artificial connection with2 current and voltage transformers
DIN 43856Circuit diagrams Four-wiremetersfor three-wiresystems
20
-
Active energy Reactive energy
Direct connection
With current transformers
With current and voltagetransformers
Direct connection
With current transformers
With current and voltagetransformers
DIN 43856Circuit diagrams three-wiremeters
21
-
Active energy Reactive energy
1 2 3 N N 3 2 1 1 2 3 N N 3 2 1
Direct connection
With current transformers
With current and voltage transformers
Direct connection
With current transformers
With current and voltagetransformers
4.2UTE versionCircuit diagrams Four-wiremetersfor four-wiresystems
22
-
Active energy Reactive energy
1 2 3 1
L1
L2
L3
1 13 22 3 1
1 2 3 12 13
Direct connection
With current transformers
With current and voltage transformers
Direct connection
With current transformers
With current and voltage transformers
UTE versionCircuit diagrams Three-wiremeters
23
-
90
140
15010
158,5 42,5
1347,2
207
231
100
27,5
11
L G
177
6
Meter version
up to 80Aup to 160A
transformer-operated meter
263.5267.5263.5
Dimension "L"
Overall length ofmeter withoutterminal cover
267.5267.5267.5
307307
307*)
40
327*)327327
60
350350*)350
(*) standard(all dimensions in mm)
80
with nofree space
Terminal cover free space in mm
Dimension "G"
5.1DIN versionDimensions
24
-
(BV) C114above 80A to 120Amaximum currentBore diameterof current terminals 9.5mm
(BV) C114above 120A to 160Amaximum currentBore diameterof current terminals 11.2mm
(BV) C114W and C116Wfor transformer-operationBore diameter of terminals 5.0mmBore diameter of auxiliaryterminals 3.2mm
(BV) C114up to 80A maximumBore diameterof current terminals 7.2mm
DIN versionDimensionsPolyphase meters for three- andfour-wire systems(The auxiliary terminals areomitted for meters withoutinput/ output functions).
25
-
DIN versionDimensionsPolyphase meters forthree-wire systems(The auxiliary terminals areomitted for meters without input/ output functions).
(BV) B114above 80A to 120Amaximum currentBore diameterof current terminals 9.5mm
(BV) B114above 120A to 160A maximum currentBore diameterof current terminals 11.2mm
B114W and B116Wfor transformer-operationBore diameter of terminals 5.0mmBore diameter of auxiliaryterminals 3.2mm
(BV) B114up to 80A maximum currentBore diameterof current terminals 7.2mm
26
-
UTE versionDimensions
Polyphase meters for three-and four-wire systemsType series 114 and 116 UTE version (symmetrical)
158,5
G
L 230 2
11
154 120
6.5
160 58
Meter version
up to 120A(up to 160A)transformer-
operated meter
272
265
Dimension "L"
Overall length ofmeter withoutterminal cover
313
38
330*)
62
340*)
(*) standard
65
Overall length of meter with terminal coverTerminal cover free space in mm
Dimension "G"
27
-
UTE versionDimensions
7x15.3 = 107.1
3
150
20.5
35.5
18
13x8.7 = 113.118.5
150
14.2
Model (BV) C114-UTEup to 120A maximum currentHole diameter of currentterminals: 8.2mm (up to 100A)
9.5mm (up to 120A,on special requestup to 160A)
Model (BV) C114W-UTE andC116W-UTEfor transformer-operationHole diameters of terminals 4.5mm
28
-
29
-
30
Order Sheet Ref. No. ELECTROMECHANICAL POLYPHASE METER Delivery date:
Quantity:
Final customer:
Address:
Phone: Fax: E.mail:
1 Meter type (please indicate): o direct conn. o transf. conn.
2 Wires: o 3 o 4
3 Accuracy class: o 1 (only transf. conn.) o 2 o 3 (only reactive)
4 Connection: o BS (symmetrical) o BS (asymmetrical) o DIN (asymmetrical) o UTE (symmetrical)
5 Direct connected, nominal current (A): o 5 o 10 o 20 o others (indicate):
6 Direct connected, maximum current (A):
7 Transformer connected, load capacity: o 120% o 200%
8 Transformer connected, secondary current (A): o 1 o 5
9 Transformer connected, primary current (A):
10 Nominal voltage (3w) (V): o 100 o 230 o 400 o others (indicate):
11 Nominal voltage (4w) (V): o 58/100 o 230/400 o 240/415 o others (indicate):
12 Transformer connected, primary voltage (V):
313 Nominal frequency (Hz): o 50 o 60
14 Bearing system: o double jewel o magnetic
15 Register: o single tariff, DIN o single tariff, BS o 7 digits
o double tariff, DIN o others (indicate)
16 Anti-reverse system: o yes o no
17 Pulse emitter (only with anti-reverse system):
o L3 o L3F o X6 o X7 (without CE mark)
18 Cover: o polycarbonate, transparent o bakelite with glass window
19 Terminal cover, bakelite: o short o medium o long o long
freespace: without 40mm 60mm 80mm
20 Terminal cover, polycarbonate black: o
21 Nameplate language: o English o French o Others (indicate):
22 Customer Logotype: o yes (please attach) o no
23 Customer serial number: o yes (please attach) o no
24 Bar code: o yes (please attach) o no
25 Other features (please attach)
SLB- RBU: Date: Signature:
-
31
6
Available types
Direct connected meters Four-wire meters
Accuracy Energy type Current rating in Amps Model10 (40) 20 (80) C114G
20 (100) C114NClass 2 Active 5 (30) 10 (60) 20 (120) C114U
5 (40) 10 (80) 20 (160) C114K5 (50) 10 (100) C114T
10 (40) 20 (80) BVC114G20 (100) BVC114N
Class 3 Reactive 5 (30) 10 (60) 20 (120) BVC114U5 (40) 10 (80) 20 (160) BVC114K5 (50) 10 (100) BVC114T
Three-wire meters
Accuracy Energy type Current rating in Amps Model
Class 2 Active10 (40) 20 (80) 30 (120) B114G
5 (30) 10 (60) 20 (120) 25 (150) B114U
Class 3 Reactive10 (40) 20 (80) 30 (120) BVB114G
5 (30) 10 (60) 20 (120) 25 (150) BVB114U
Transformer connected meters Four-wire meters
Accuracy Energy type Current rating in Amps (secondary)Model1 C114W-0.2/1.2
Class 2 Active 5 C114W-1/65 (10) C114W-1.66/10
1 BVC114W-0.2/1.2Class 3 Reactive 5 BVC114W-1/6
5 (10) BVC114W-1.66/101 C116W-0.2/1.2
Class 1 Active 5 C116W-1/65 (10) C116W-1.66/10
Three-wire meters
Accuracy Energy type Current rating in Amps (secondary) Model1 B114W-0.2/1.2
Class 2 Active 5 B114W-1/65 (10) B114W-1.66/10
1 BVB114W-0.2/1.2Class 3 Reactive 5 BVB114W-1/6
5 (10) BVB114W-1.66/101 B116W-0.2/1.2
Class 1 Active 5 B116W-1/65 (10) B116W-1.66/10
-
For more information, please contact your local agency.
www.slb.com/rmsEU-EL-0034.0-GB-01.01 Copyright 2000, Schlumberger S.A., All Rights Reserved.
Schl
umbe
rger
rese
rves
the
right
to c
hang
e th
ese
spec
ifica
tions
with
out p
rior n
otic
e.
SchlumbergerZhler & Systemtechnik GmbH Kuhbrckenstrae 2-4 D-31785 Hameln, GermanyTel.: +49 (0)5151 782 372Fax: +49 (0)5151 782 427