Bywater Reliability Update

12
Bywater Reliability Update Gary Huntley Entergy New Orleans, Inc. Regional Manager Entergy New Orleans, Inc. July 28, 2010

description

Entergy New Orleans, Inc. Bywater Reliability Update. July 28, 2010. Gary Huntley Entergy New Orleans, Inc. Regional Manager. Why we are here. Update on Bywater Reliability Plan ENO Reliability Program Overview What effect this has had 2008-2010 What to expect going forward Summary. - PowerPoint PPT Presentation

Transcript of Bywater Reliability Update

Page 1: Bywater Reliability Update

Bywater Reliability Update

Gary HuntleyEntergy New Orleans, Inc.

Regional Manager

Entergy New Orleans, Inc.

July 28, 2010

Page 2: Bywater Reliability Update

2

Why we are here

Update on Bywater Reliability Plan ENO Reliability Program Overview What effect this has had 2008-2010 What to expect going forward Summary

Page 3: Bywater Reliability Update

3

Bywater Area About 5,500 customers

Serviced from Almonaster substation by three feeders: 621 1,800 customers622 2,400 customers623 900 customers

Feeder

Page 4: Bywater Reliability Update

4

Bywater Reliability in 2008

Numerous reliability complaints Ongoing post-storm remediation Initiated focused efforts for reliability

improvements

Page 5: Bywater Reliability Update

5

Reliability Programs

R

Recloser InspectionsCapacitor Bank

Inspections

Backbone

Inspections

T

A

C

T

I

C

S

VegetationPole

Inspections

Infrared Inspections

Substation Breaker

Page 6: Bywater Reliability Update

6

How ENO Prioritizes Reliability Projects

Selection Process

Gather performance

data on all circuits

Circuit Review:•Operations•Customer Service•Engineering

Circuits ranked by performance &

customers affected

Circuits patrolled and work identified

Design jobs created Schedule projects by priority

Page 7: Bywater Reliability Update

7

Reliability Improvement Work Since 2008

Added two feeders Replaced cross arms Upgraded shield wires around the

substation Installed and replaced ground wires Installed fuses Installed fault indicators Replaced jumpers Inspected equipment (reclosers,

capacitors) Performed infrared inspections Trimmed trees

Page 8: Bywater Reliability Update

8

Bywater Feeder Performance

SAIFI TREND

0

5

10

15

20

25

30

35

40

SC

OR

E

621 36.3 8.8 4.5

622 1.1 4.1 2.1

623 1.5 2 0.045

ENOI 2.28 2.07 1.16

2008 2009 YTD 2010

SAIFI - Average number of interruptions that a customer would experience.

Page 9: Bywater Reliability Update

9

Recent 2010 Bywater Outages

Lightning/wind/weather Equipment failures Animal contacts Public damage

Vehicle Theft Foreign Objects

Page 10: Bywater Reliability Update

10

Week of July 19th: Detailed inspection of feeders began.

Week of July 26th: Determine corrective actions needed on feeders. Conduct pole inspections.

August 2010 – October 2010: Begin implementation of corrective actions. Conduct infrared inspections.

November 2010 – May 2011 Addition of feeder breakers to further sectionalize customers. Implementation of Automatic Load Transfer Scheme between

Almonaster and Tricou Substation to reduce customer impact. (Project approved and equipment on order)

What to Expect in Bywater Going Forward

Page 11: Bywater Reliability Update

11

What to Expect Going Forward (cont’d)ENO has and will continue to manage systemreliability:

Planned projects and activities should further improve reliability. Monitor reliability performance indicators (SAIFI, SAIDI). Routine inspections and repairs. Analysis of outages to identify repetitive problems. Continue to review technological advancements that reduce customer outages.

Communicate our progress Provide updates to Bywater Neighborhood Association. Provide update to Council in first quarter of 2011.

Page 12: Bywater Reliability Update

12

Summary

We understand inconvenience for customers.

We are working diligently to continue positive trend in reliability.

We will continue to provide updates.

We are committed to providing safe, reliable service.