— BUYLOG SEC TION 5
Surge Protection Devices
5-2 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
5-3SURGE PROTECTION DEVICES, BUYLOG SECTION 5
— Table of contents
Surge protection devices5-4 Introduction
ABB integrated surge protection devices5-5 To connect with ReliaGear® panelboards5-7 For ReliaGear distribution equipment5-11 9X box extensions for ReliaGear distribution equipment5-13 24X box extensions for ReliaGear distribution
equipment5-15 9X and 24X dimensions5-16 ME series wallmount SPD5-18 HE series wallmount SPD5-20 ME series wallmount SPD with enhanced thermal
protection5-22 HE series wallmount SPD with enhanced thermal
protection5-24 ME and HE series dimensions5-25 LE series wallmount SPD5-27 ME series wallmount SPD
OVRH series5-29 Product range overview5-30 OVRHSP (4,000A and below, 60 to 100kA)5-31 OVRHSP (4,000A and below, 120 to 160kA)5-32 OVRHSP (4,000A and below, 200 to 400kA)5-33 OVRHSR (wall recessed – 4,000A and below, 120 to
160kA)5-34 OVRHTE (1,000A and below, 25 to 100kA)5-35 OVRHT3B (400A and below, 50kA)5-36 OVRHT3C (400A and below, 50kA)5-37 OVRHS3U (400A and below, 40kA)5-38 OVRHLD (100A and below, 20 to 30KA)5-39 Dimensions
DIN-rail SPDs for distribution panels - UL 1449 4th edition
5-43 Overview5-44 Terminology of SPD electrical characteristics5-45 Standards5-47 Single-phase5-48 Split-phase5-49 3-phase wye5-50 3-phase delta system5-51 3-phase wye + N-G5-52 HLD system
5-53 Protection block assembly
5-4 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—Surge protection devicesIntroduction
Surge Protection Devices (SPDs) are designed to protect against transient surge conditions.
Transient surges can reach values of hundreds of thousands of volts or instantaneous current flow of tens of thousands of amperes, but typically last less than one hundred microseconds in duration.
Transient surges generated within a facility typically account for 80% of the surge activity.
These internally generated transients can be caused by switching power supplies (computers), electronic ballasts (building lighting) and variable frequency drives (air handlers, elevators, etc).
The most destructive transient voltage surges can be attributed to lightning and utility load switching; however, experts predict that these two events account for 20% of all transient surge activity.
Reliable data sources suggest that lightning strikes have current magnitudes in excess of 200,000 amps. Moreover,
lightning strikes are not single strike events. Strikes typically consist of four to six “hits” and sometimes can be as high as 40kA.
Therefore, SPDs must be appropriately sized to provide adequate protection during multiple surge events.
Large transient surge conditions can damage printed circuit board traces and puncture semiconductors causing immediate or intermittent equipment failures. Continued exposure to surges can degrade printed circuit board traces or semiconductors resulting in seemingly random delayed equipment failures. Therefore, equipment failures cannot always be contributed to a single power quality event. Surge remnants on data lines can alter digital data and logic levels causing equipment failures and lockups.
Professionally installed ABB products provide superior protection against transient surges preventing unnecessary downtime and costly repairs.
Cost reduction on repairs
Installed ABBSPD
Increased protection
Reduction on downtime
5-5SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB integrated surge protection deviceDesigned to connect within ReliaGear® panelboards
Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPME120Sxx*
208Y/120 3-phase, 4-wire + ground TPME120Yxx*
240 Delta 3-phase, 3-wire + ground TPME240Dxx*
240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPME240Hxx*
415Y/240 3-phase, 4-wire + ground TPME240Yxx*
480Y/277 3-phase, 4-wire + ground TPME277Yxx*
380Y/220 3-phase, 4-wire + ground TPME220Yxx*
600Y/347 3-phase, 4-wire + ground TPME347Yxx*
480 Delta 3-phase, 3-wire + ground TPME480Dxx*
Desired kA xx Code65 06
80 08
100 10
Options (*) Suffix (*)With UL 1283 noise filter and surge counter1 AS
Without UL 1283 noise filtering only (Available in 100 kA per mode only) ASNF
Without UL 1283 noise filter and surge counter (Available in 100kA per mode only) ASNC
1Standard option
Nominal Voltage (Volts RMS)
System Voltage Configuration
Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision
MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L
120S 120/240 1 Ph, 3 W + G 700 - 600 - 600 1200 125%
120Y 120Y/208 3 Ph, 4 W + G 700 - 600 - 600 1200 125%
240D 240 Delta 3 Ph, 3 W - - 900 - - 1800 115%
240H120/240 Delta HL
3 Ph, 4 W + G 700 1200 600 1000 600 1200 115%
240Y 240Y/415 3 Ph, 4 W + G 1200 - 1000 - 1000 2000 130%
277Y 277Y/480 3 Ph, 4 W + G 1200 - 1000 - 1000 2000 115%
220Y 220Y/380 3 Ph, 4 W + G 1200 - 1000 - 1000 2000 145%
347Y 347Y/600 3 Ph, 4 W + G 1500 - 1500 - 1500 3000 115%
480D 480 Delta 3 Ph, 3 W - - 1500 - - 3000 170%
Also available in 600D configurations. For details, please contact ABB Power Quality Customer Service at 800 637 1738.
T P M EProduct #
Maximum Surge Current CapacityPer Mode Per Phase
06 65kA 130kA
08 80kA 160kA
10 100kA 200kA
Phase Rating = (L-N + L-G)
Product # ExampleTPME277Y10AS277Y/480 V, 3 Ph, 4 W + G
100kA per mode
Full featured, with UL 1283 noise filtering and surge counter
5-6 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB integrated surge protection deviceDesigned to connect within ReliaGear® panelboards
1.331 [33.81]
5.331 [135.41]
0.312 [7.91] TYP
0.236 [ 5.99] HOLE(4 PLACES)
5.064 [128.62]
9.494 [241.15]
8.321 [211.36]6.000 [152.40]
9.400 [238.76]
2.869 [72.87]
FeaturesUL Listed 1449 4th Edition, Type 1, Type 2
cUL, CSA C22.2
This model connects directly to the ReliaGear Panelboard bus bars
Factory installed in ABB ReliaGear Panels
Standard features include a surge counter, audible alarm, indicating lights, dry contacts and NEMA 4 painted steel enclosure
10 year limited warranty
Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode
Nominal discharge current rating (l-n) 20 kA
Operating frequency 50-60Hz
Surge life (IEEE C62.41 - C3 10kA) ≥5000 impulses
Connection method 6 to 2/0 Conductors, Parallel Connected
Modes of protection All Modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR) 200 kAIC
Standard monitoring
Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter
EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ
Mechanical characteristicsWeight 13 lbs. ( kg)
Enclosure type Painted steel, NEMA 12
Installation locationService Entrance Equipment, Primary Distribution Equipment, Secondary Distribution Equipment, Lighting Panels - Rated for UL and NEC 2008 Type 1 and Type 2
Mounting method Bolt-on to electrical panel interior frame
Operating temperature -40° F to 149° F (-40° C to +65° C)
Altitude 0 - 12,000 ft (3.66 km)
Product design Individually fused Thermally Protected MOV Technology
Regulations and certificationsUL 1449 4th edition VZCA2:E320456 Type 1/Type 2
cUL, CSA C22.2 VZCA8:E320456 Type 1/Type 2
UL 1283 FOKY2:E320456 Type 2
UL 96A Yes
IEEE C62.62, C62.72, C62.41 Yes
Listed By UL
5-7SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB integrated surge protection deviceDesigned for ReliaGear distribution equipment
T P M EProduct #
Nominal Voltage (Volts RMS)
System Voltage Configuration
Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision
MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L
120S 120/240 1 Ph, 3 W + G 900 - 800 - 700 1200 125%
120Y 120Y/208 3 Ph, 4 W + G 900 - 800 - 700 1200 125%
220Y 220Y/380 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 145%
240D 240 Delta 3 Ph, 3 W + G - - 1200 - - 1800 196%
240H120/240 Delta HL
3 Ph, 4 W + G 1000 1200 800 1200 700 2000 115%
240Y 240Y/415 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 130%
277Y 277Y/480 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 115%
347Y 347Y/600 3 Ph, 4 W + G 1500 - 1500 - 1500 2500 115%
480D 480 Delta 3 Ph, 3 W + G - - 1800 - - 3000 198%
Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.
Maximum Surge Current CapacityExposure Level
Per Mode Per Phase
06 TPME 65kA 130kA
08 TPME 80kA 160kA
10 TPME 100kA 200kA
NOTE: For SPD field installation kit, add the prefix "A" and replace "PP" suffix with "K" suffix
Product # ExampleTPME277Y15PP (factory installed)
ATME277Y15K (field installation)
Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPME120Sxx*
208Y/120 3-phase, 4-wire + ground TPME120Yxx*
380Y/220 3-phase, 4-wire + ground TPME220Yxx*
240 Delta 3-phase, 3-wire + ground TPME240Dxx*
240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPME240Hxx*
415Y/240 3-phase, 4-wire + ground TPME240Yxx*
480Y/277 3-phase, 4-wire + ground TPME277Yxx*
600Y/347 3-phase, 4-wire + ground TPME347Yxx*
480 Delta 3-phase, 3-wire + ground TPME480Dxx*
Desired kA xx Code65 06
80 08
100 10
Options Mounting UL Type Suffix (*)ABB Spectra Power Panel Integral Type 2 PP
ABB Motor Control Centers Integral Type 2 ME
ABB Switchgear Integral Type 2 SG
ABB Spectra Power Panel Integral Type 1 PPT1
ABB Motor Control Centers Integral Type 1 MET1
ABB Switchgear Integral Type 1 SGT1
* PP suffix available for all kA ratings (integral to Spectra™ panel or switchboard SG suffix for all THE devices (100kA - 300kA) integral to switchgear ME suffix available for all kA ratings (integral to MCC)
5-8 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB integrated surge protection deviceDesigned for ReliaGear distribution equipment
FeaturesUL Listed 1449 4th Edition, Type 1, Type 2
cUL, CSA C22.2
These SPD models connect to the panelboard or switchboard bus bars
Thermally protected MOV design eliminates the need for additional upstream over current protection
Standard features include a surge counter, audible alarm, indicating lights, dry contacts and NEMA 4 painted steel enclosure
10 year limited warranty
Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode
Nominal discharge current rating (l-n) 20 kA
Operating frequency 50-60Hz
Surge life (IEEE C62.41 - C3 10kA) ≥5000 impulses
Connection method 6 to 2/0 Conductors, Parallel Connected
Modes of protection All Modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR) 200 kAIC
Standard monitoring
Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter
EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ
Mechanical characteristicsWeight 24 lbs. (10.89 kg)
Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2008 Type 1 and Type 2
Mounting method Bolt-on to electrical panel interior frame
Operating temperature -40° F to 149° F (-40° C to +65° C)
Altitude 0 - 12,000 ft (3.66 km)
Product design Individually fused Thermally Protected MOV Technology
Regulations and certificationsUL 1449 4th edition VZCA2:E320456 Type 1/Type 2
cUL, CSA C22.2 VZCA8:E320456 Type 1/Type 2
UL 1283 FOKY2:E320456 Type 2
UL 96A Yes
IEEE C62.62, C62.72, C62.41 Yes
Listed By UL
0.340 [8.636]
17.382 [441.494]
2.638 [67.004] TYP
6.762 [171.751] TYP
0.280 [ 7.112] HOLE
(4 PLACES)
7.2
02
[182.9
22]
17.722 [450.130]
9.400 [238.755]
6.964 [176.877]
5-9SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB integrated surge protection deviceDesigned for ReliaGear distribution equipment
T P H EProduct #
Nominal Voltage (Volts RMS)
System Voltage Configuration
Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision
MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L
120S 120/240 1 Ph, 3 W + G 900 - 800 - 700 1200 125%
120Y 120Y/208 3 Ph, 4 W + G 900 - 800 - 700 1200 125%
220Y 220Y/380 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 145%
240D 240 Delta 3 Ph, 3 W + G - - 1200 - - 1800 196%
240H120/240 Delta HL
3 Ph, 4 W + G 1000 1200 800 1200 700 2000 115%
240Y 240Y/415 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 130%
277Y 277Y/480 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 115%
347Y 347Y/600 3 Ph, 4 W + G 1500 - 1500 - 1500 2500 115%
480D 480 Delta 3 Ph, 3 W + G - - 1800 - - 3000 198%
Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.
Maximum Surge Current CapacityExposure Level
Per Mode Per Phase
12 TPHE 125kA 250kA
15 TPHE 150kA 300kA
20 TPHE 200kA 400kA
25 TPHE 250kA 500kA
30 TPHE 200kA 400kA
NOTE: For SPD field installation kit, add the prefix "A" and replace "PP" suffix with "K" suffix
Product # ExampleTPHE277Y15PP (factory installed)
ATHE277Y15K (field installation)
Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPHE120Sxx*
208Y/120 3-phase, 4-wire + ground TPHE120Yxx*
380Y/220 3-phase, 4-wire + ground TPHE220Yxx*
240 Delta 3-phase, 3-wire + ground TPHE240Dxx*
240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPHE240Hxx*
415Y/240 3-phase, 4-wire + ground TPHE240Yxx*
480Y/277 3-phase, 4-wire + ground TPHE277Yxx*
600Y/347 3-phase, 4-wire + ground TPHE347Yxx*
480 Delta 3-phase, 3-wire + ground TPHE480Dxx*
Desired kA xx Code125 12
150 15
200 20
250 25
300 30
Options Mounting UL Type Suffix (*)ABB Spectra Power Panel Integral Type 2 PP
ABB Motor Control Centers Integral Type 2 ME
ABB Switchgear Integral Type 2 SG
ABB Spectra Power Panel Integral Type 1 PPT1
ABB Motor Control Centers Integral Type 1 MET1
ABB Switchgear Integral Type 1 SGT1
* PP suffix available for all kA ratings (integral to Spectra™ panel or switchboard SG suffix for all THE devices (100kA - 300kA) integral to switchgear ME suffix available for all kA ratings (integral to MCC)
*
5-10 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB integrated surge protection deviceDesigned for ReliaGear distribution equipment
FeaturesUL Listed 1449 4th Edition, Type 2
cUL, CSA C22.2
These SPD models connect to the panelboard or switchboard bus bars
Thermally protected MOV design eliminates the need for additional upstream over current protection
Standard features include a surge counter, audible alarm, indicating lights, dry contacts and integral surge rated disconnect
10 year limited warranty
Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode
Nominal discharge current rating (l-n) 20 kA
Operating frequency 50-60Hz
Surge life (IEEE C62.41 - C3 10kA) ≥20000 impulses
Connection method 6 to 2/0 Conductors, Parallel Connected
Modes of protection All Modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR) 200 kAIC
Standard monitoring
Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter
EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ
Mechanical characteristicsWeight 24 lbs. (10.89 kg)
Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2020 Type 1 and Type 2
Mounting method Bolt-on to electrical panel interior frame
Operating temperature -40° F to 149° F (-40° C to +65° C)
Altitude 0 - 12,000 ft (3.66 km)
Product design Individually fused Thermally Protected MOV Technology
Regulations and certificationsUL 1449 4th edition VZCA2:E320456 Type 1/Type 2
UL 1283 VZCA8:E320456 Type 1/Type 2
cUL, CSA C22.2 FOKY2:E320456 Type 2
UL 96A Yes
IEEE C62.62, C62.72, C62.41 Yes
Listed By UL
5-11SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB 9X box extensionsDesigned for ReliaGear distribution equipment
Voltage Protection Rating (VPR) UL 1449 4th Edition - September 2014 RevisionB x 9 B x 24L-N HL-N L-G HL-G N-G L-L L-N HL-N L-G HL-G N-G L-L
120S 1500 - 1500 - 900 1800 1500 - 1500 - 1000 1800
120Y 1500 - 1500 - 900 1800 1500 - 1500 - 1000 1800
220Y 1800 - 2000 - 1500 2500 1800 - 1800 - 1500 2500
240D - - 1800 - - 2500 - - 1800 - - 2500
240H 1500 1800 1500 2000 900 1800 1500 1800 1500 1800 1000 1800
240Y 1800 - 2000 - 1500 2500 1800 - 1800 - 1500 2500
277Y 1800 - 2000 - 1500 2500 1800 - 1800 - 1500 2500
347Y 2000 - 2000 - 1800 3000 3000 - 2500 - 1800 3000
480D - - 2500 - - 4000 - - 2500 - - 4000
T P M EProduct # B X *
Nominal Voltage (Volts RMS)
System Voltage Configuration
MCOV% Max. Continuous Operating Voltage
120S 120/240 1 Ph, 3 W + G 125%
120Y 120Y/208 3 Ph, 4 W + G 125%
220Y 220Y/380 3 Ph, 4 W + G 145%
240D 240 Delta 3 Ph, 3 W + G 115%
240H120/240 Delta HL
3 Ph, 4 W + G 115%
240Y 240Y/415 3 Ph, 4 W + G 130%
277Y 277Y/480 3 Ph, 4 W + G 115%
347Y 347Y/600 3 Ph, 4 W + G 115%
480D 480 Delta 3 Ph, 3 W + G 170%
Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.
Maximum Surge Current CapacityExposure Level
Per Mode Per Phase
06 ME 65kA 130kA
08 ME 80kA 160kA
10 ME 100kA 200kA
12 HE 125kA 250kA
15 HE 150kA 300kA
20 HE 200kA 400kA
25 HE 250kA 500kA
30 HE 300kA 600kA
Phase Rating = (L-N + L-G)
Product # ExampleTPME277Y15BX24WF277Y/480 V, 3 Ph, 4 W + G
150kA per mode
Flush mounted, display access
Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPME120SxxBX*
208Y/120 3-phase, 4-wire + ground TPME120YxxBX*
380Y/220 3-phase, 4-wire + ground TPME220YxxBX*
240 Delta 3-phase, 3-wire + ground TPME240DxxBX*
240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPME240HxxBX*
415Y/240 3-phase, 4-wire + ground TPME240YxxBX*
480Y/277 3-phase, 4-wire + ground TPME277YxxBX*
600Y/347 3-phase, 4-wire + ground TPME347YxxBX*
480 Delta 3-phase, 3-wire + ground TPME480DxxBX*
Desired kA xx Code65 06
80 08
100 10
Options Suffix (*)Surface mounted, no display 9S
Surface mounted, display access 9WS
Flush mounted, no display 9F
Flush mounted, display access 9WF
5-12 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
FeaturesUL Listed 1449 4th Edition, Type 2
cUL, CSA C22.2
The ReliaGear Box Extension SPD is field installed and attaches neatly to a standard panel at the top or bottom
The true maximum surge current rating, unlimited by fusing, has been proven successful in 3rd party tests
Standard features include a surge counter, audible alarm, indicating lights, dry contacts
10 year limited warranty
Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode
Nominal discharge current rating (l-n) 20 kA
Operating frequency 50-60Hz
Connection method6 to 2/0 Conductors, Parallel Connected *ABB recommends the use of a dedicated circuit breaker, rated 60A or above, to provide a local disconnecting means for the SPD.
Modes of protection All Modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR) 65 kAIC
Standard monitoring
Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter
EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ
Mechanical characteristicsWeight 31 lbs. (14.1 kg)
Enclosure type
Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2020 Type 1 and Type 2
Mounting method
Operating temperature -40° F to 149° F (-40° C to +65° C)
Altitude 0 - 12,000 ft (3.66 km)
Product design Individually fused Thermally Protected MOV Technology
Regulations and certificationsUL 1449 4th edition XUPD.E248748 Type 2
UL 1283 Yes
UL 96A Yes
cUL, CSA C22.2 VZCA7:E320456 Type 2
IEEE C62.62, C62.72 Yes
Listed By UL
—ABB 9X box extensionsDesigned for ReliaGear distribution equipment
5-13SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB 24X box extensionsDesigned for ReliaGear distribution equipment
Voltage Protection Rating (VPR) UL 1449 4th Edition - September 2014 RevisionB x 9 B x 24L-N HL-N L-G HL-G N-G L-L L-N HL-N L-G HL-G N-G L-L
120S 1500 - 1500 - 900 1800 1500 - 1500 - 1000 1800
120Y 1500 - 1500 - 900 1800 1500 - 1500 - 1000 1800
220Y 1800 - 2000 - 1500 2500 1800 - 1800 - 1500 2500
240D - - 1800 - - 2500 - - 1800 - - 2500
240H 1500 1800 1500 2000 900 1800 1500 1800 1500 1800 1000 1800
240Y 1800 - 2000 - 1500 2500 1800 - 1800 - 1500 2500
277Y 1800 - 2000 - 1500 2500 1800 - 1800 - 1500 2500
347Y 2000 - 2000 - 1800 3000 3000 - 2500 - 1800 3000
480D - - 2500 - - 4000 - - 2500 - - 4000
T P H E B XProduct # *
Nominal Voltage (Volts RMS)
System Voltage Configuration
MCOV% Max. Continuous Operating Voltage
120S 120/240 1 Ph, 3 W + G 125%
120Y 120Y/208 3 Ph, 4 W + G 125%
220Y 220Y/380 3 Ph, 4 W + G 145%
240D 240 Delta 3 Ph, 3 W + G 115%
240H120/240 Delta HL
3 Ph, 4 W + G 115%
240Y 240Y/415 3 Ph, 4 W + G 130%
277Y 277Y/480 3 Ph, 4 W + G 115%
347Y 347Y/600 3 Ph, 4 W + G 115%
480D 480 Delta 3 Ph, 3 W + G 170%
Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.
Maximum Surge Current CapacityExposure Level
Per Mode Per Phase
06 ME 65kA 130kA
08 ME 80kA 160kA
10 ME 100kA 200kA
12 HE 125kA 250kA
15 HE 150kA 300kA
20 HE 200kA 400kA
25 HE 250kA 500kA
30 HE 300kA 600kA
Phase Rating = (L-N + L-G)
Product # ExampleTPHE277Y15BX24WF277Y/480 V, 3 Ph, 4 W + G
150kA per mode
Flush mounted, display access
Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPHE120SxxBX*
208Y/120 3-phase, 4-wire + ground TPHE120YxxBX*
380Y/220 3-phase, 4-wire + ground TPHE220YxxBX*
240 Delta 3-phase, 3-wire + ground TPHE240DxxBX*
240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPHE240HxxBX*
415Y/240 3-phase, 4-wire + ground TPHE240YxxBX*
480Y/277 3-phase, 4-wire + ground TPHE277YxxBX*
600Y/347 3-phase, 4-wire + ground TPHE347YxxBX
480 Delta 3-phase, 3-wire + ground TPHE480DxxBX
Desired kA xx Code125 12
150 15
200 20
250 25
300 30
Options Suffix (*)Surface mounted, display access 24WS
Flush mounted, display access 24WF
5-14 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
FeaturesUL Listed 1449 4th Edition for Type 2 applications
cUL, CSA C22.2
This model is installed in an extended box and connects to the "A-Series™" Panelboard
The true maximum surge current rating, unlimited by fusing, has been proven successful in 3rd party tests
Standard features include a surge counter, audible alarm, indicating lights, dry contacts
10 year limited warranty
Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode
Nominal discharge current rating (l-n) 20 kA
Operating frequency 50-60Hz
Connection method6 to 2/0 Conductors, Parallel Connected *ABB recommends the use of a dedicated circuit breaker, rated 60A or above, to provide a local disconnecting means for the SPD.
Modes of protection All Modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR) 200 kAIC
Standard monitoring
Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter
EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ
Mechanical characteristicsWeight 57 lbs. (25.9 kg)
Enclosure type
Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2020 Type 1 and Type 2
Mounting method
Operating temperature -40° F to 149° F (-40° C to +65° C)
Altitude 0 - 12,000 ft (3.66 km)
Product design Individually fused Thermally Protected MOV Technology
Regulations and certificationsUL 1449 4th edition XUPD.E248748 Type 2
UL 1283 Yes
UL 96A Yes
cUL, CSA C22.2 VZCA7:E320456 Type 2
IEEE C62.62, C62.72 Yes
Listed By UL
—ABB 24X box extensionsDesigned for ReliaGear distribution equipment
5-15SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB 9X and 24X box extensionsDesigned for ReliaGear distribution equipment
21.500 [546.10]
10.440 [265.18]
9.000 [228.60]
7.375 [187.34]
10.000 [254.00]
12.625 [320.69]
15.400 [391.16]
1.719 [43.67]
0.344 [8.74]
6.023 [152.98]
0.588 [14.94]
9.000 [228.6]
9.810 [249.174]
20.250 [514.35]
7.375 [187.338]
10.000 [254]
12.6255 [320.69]
15.400 [391.16]
1.719 [43.675]
0.344 [8.738]
6.023 [152.984]
0.042 [1.067]
10.440 [265.176]
9.000 [228.600]
21.500 [546.100]
1.617 [41.072]
6.412 [162.865]
7.239 [183.871]
14.254 [362.052]
7.375 [187.338]
10.000 [254.000]
12.625 [320.688]
15.400 [391.160]
6.023 [152.984]
0.588 [14.935]
2.389 [60.693]
0.344 [8.738]
20.250 [514.350]
9.810 [249.174]
9.000 [228.600]
2.247 [57.074]
7.042 [178.867]
6.609 [167.869]
13.624 [346.050]
6.023 [152.984]
2.389 [60.693]
7.375 [187.338]
10.000 [254.000]
12.625 [320.688]
15.400 [391.160]
[8.738] 0.344
6.333 [160.86]
20.280 [515.11]
21.500 [546.10]
24.743 [628.47]
25.440 [646.18]
24.000 [609.60]
12.560 [319.02]
5.390 [136.91]
6.899 [175.23]
7.624 [193.65]
6.810 [172.97]
7.085 [179.95]
3.176 [80.67]
0.711 [18.06]
6.074 [154.28]
8.030 [203.96] 8.635
[219.33]
1.400 [35.56]
7.246 [184.048]
24.743 [628.472]
7.246 [184.044]
20.280 [515.112]
6.333 [160.858]
24.000 [609.600]
11.940 [303.276]
5.390 [136.906]
6.274 [159.360]
7.624 [193.650]
6.810 [172.969]
7.085 [179.954]
8.635 [219.329]
11.635 [295.529]
8.030 [203.962]
1.400 [35.560]
3.176 [80.672]
0.711 [18.059]
6.074 [154.280]
BX9F Dimensions
BX9WF Dimensions
BX24WF Dimensions
BX9S Dimensions
BX9WS Dimensions
BX24WS Dimensions
5-16 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB ME seriesWallmount SPD
Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TME120SxxxWMN
208Y/120 3-phase, 4-wire + ground TME120YxxxWMN
380Y/220 3-phase, 4-wire + ground TME220YxxxWMN
240 Delta 3-phase, 3-wire + ground TME240DxxxWMN
240/120 Hi-Leg Delta 3-phase, 4-wire + ground TME240HxxxWMN
415Y/240 3-phase, 4-wire + ground TME240YxxxWMN
480Y/277 3-phase, 4-wire + ground TME277YxxxWMN
600Y/347 3-phase, 4-wire + ground TME347YxxxWMN
480 Delta 3-phase, 3-wire + ground TME480DxxxWMN
Desired kA xxx Code65 065
80 080
100 100
T M E W M NProduct #
Nominal Voltage (Volts RMS)
System Voltage Configuration
Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision
MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L
120S 120/240 1 Ph, 3 W + G 1000 - 1000 - 700 1200 - 125%
120Y 120Y/208 3 Ph, 4 W + G 1000 - 1000 - 700 1200 - 125%
220Y 220Y/380 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 145%
240D 240 Delta 3 Ph, 4 W - - 1500 - - 1800 - 196%
240H120/240 Delta HL
3 Ph, 4 W + G 1000 1500 1000 1500 700 1200 2500 115%
240Y 240Y/415 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 130%
277Y 277Y/480 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 115%
347Y 347Y/600 3 Ph, 4 W + G 1800 - 1500 - 1500 2500 - 115%
480D 480 Delta 3 Ph, 4 W - - 2000 - - 4000 - 198%
Maximum Surge Current CapacityExposure Level
Per Mode Per Phase
065 ME 65kA 130kA
080 ME 80kA 160kA
100 ME 100kA 200kA
Product # ExampleTME277Y150WMN4S
Suffix DescriptionNEMA Enclosure
Mounting Disconnect
4S Painted Steel 4 Surface No
4X Stainless Steel 4X Surface No
5-17SURGE PROTECTION DEVICES, BUYLOG SECTION 5
FeaturesUL Listed 1449 4th Edition, Type 2
cUL Listed, CSA C22.2
UL 96A, for use in lightning protection systems
UL Recognized 200kAIC Surge Rated Fuses in combination with patented thermal fuse technology
Standard features include a surge counter, audible alarm, indicating lights, dry contacts and NEMA 4 painted steel enclosure
10 year limited warranty
Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode
Nominal discharge current rating (l-n) 20 kA
Operating frequency 50-60Hz
Surge life (IEEE C62.41 - C3 10kA) ≥5000 impulses
Connection method 6 to 2/0 Conductors, Parallel Connected
Modes of protection All Modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR) 65 kA (30A breaker required)
Standard monitoring
Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter
EMI/RFI filter attenuationMaximum attenuation frequency -44dB @ (50-100kHZ)
Mechanical characteristicsWeight 32 lbs. (14.51 kg)
Enclosure type Painted steel, NEMA 4
Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2020 Type 2 Installation Locations
Mounting method Dual Mounting Flanges / 3/4" NPT Offset Nipple
Operating temperature -40° F to 149° F (-40° C to +65° C)
Altitude 0 - 12,000 ft (3.66 km)
Product design Thermal fuse technology
Regulations and certificationsUL 1449 4th edition VZCA:E320456 Type 2
cUL, CSA C22.2 VZCA7:E320456 Type 2
UL 1283 FOKY:E320456 Type 2
UL 96A Yes
IEEE C62.62, C62.72 Yes
Listed By UL
—ABB ME seriesWallmount SPD
1.852 [47.04]
13.478 [342.34]
14.759 [374.88]
16.000 [406.40]
8.978 [228.04]
15.330 [389.38]
19.330 [490.98]
8.978 [228.04]
15.330 [389.38]6.440
[163.58]
1.471 [37.36]
0.571 [14.50]
15.478 [393.14]
18.759 [476.48]
0.571 [14.50]
0.282 [ 7.16] HOLES
(8 PLACES)
3.852 [97.84]
12.000[304.80]
WMN12F Dimensions
5-18 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB HE seriesWallmount SPD
Voltage Configuration Product Number240/120 1-phase, 3-wire + ground THE120SxxxWMN
208Y/120 3-phase, 4-wire + ground THE120YxxxWMN
380Y/220 3-phase, 4-wire + ground THE220YxxxWMN
240 Delta 3-phase, 3-wire + ground THE240DxxxWMN
240/120 Hi-Leg Delta 3-phase, 4-wire + ground THE240HxxxWMN
415Y/240 3-phase, 4-wire + ground THE240YxxxWMN
480Y/277 3-phase, 4-wire + ground THE277YxxxWMN
600Y/347 3-phase, 4-wire + ground THE347YxxxWMN
480 Delta 3-phase, 3-wire + ground THE480DxxxWMN
600 Delta 3-phase, 3-wire + ground THE600DxxxWMN
Desired kA xxx Code125 125
150 150
200 200
300 300
T H E W M NProduct #
Nominal Voltage (Volts RMS)
System Voltage Configuration
Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision
MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L
120S 120/240 1 Ph, 3 W + G 1000 - 1000 - 700 1200 - 125%
120Y 120Y/208 3 Ph, 4 W + G 1000 - 1000 - 700 1200 - 125%
220Y 220Y/380 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 145%
240D 240 Delta 3 Ph, 4 W - - 1500 - - 1800 - 196%
240H120/240 Delta HL
3 Ph, 4 W + G 1000 1500 1000 1500 700 1200 2500 115%
240Y 240Y/415 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 130%
277Y 277Y/480 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 115%
347Y 347Y/600 3 Ph, 4 W + G 1800 - 1500 - 1500 2500 - 115%
480D 480 Delta 3 Ph, 4 W - - 2000 - - 4000 - 198%
Maximum Surge Current CapacityExposure Level
Per Mode Per Phase
125 HE 125kA 250kA
150 HE 150kA 300kA
200 HE 200kA 400kA
250 HE 250kA 500kA
300 HE 300kA 600kA
Product # ExampleTHE277Y150WMN4S
Suffix DescriptionNEMA Enclosure
Mounting Disconnect
4S Painted Steel 4 Surface No
4X Stainless Steel 4X Surface No
5-19SURGE PROTECTION DEVICES, BUYLOG SECTION 5
FeaturesUL Listed 1449 4th Edition, Type 2
cUL Listed, CSA C22.2
UL 96A, for use in lightning protection systems
UL Recognized 200kAIC Surge Rated Fuses in combination with patented thermal fuse technology
Standard features include a surge counter, audible alarm, indicating lights, dry contacts and NEMA 4 painted steel enclosure
10 year limited warranty
Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode
Nominal discharge current rating (l-n) 20 kA
Operating frequency 50-60Hz
Surge life (IEEE C62.41 - C3 10kA) ≥20000 impulses
Connection method 6 to 2/0 Conductors, Parallel Connected
Modes of protection All Modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR) 200 kAIC (60A breaker required as a local disconnect means)
Standard monitoring
Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter
EMI/RFI filter attenuationMaximum attenuation frequency -44dB @ (50-100kHZ)
Mechanical characteristicsWeight 50 lbs. (22.68 kg)
Enclosure type Painted steel, NEMA 4
Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2020 Type 2 Installation Locations
Mounting method Dual Mounting Flanges / 3/4" NPT Offset Nipple
Operating temperature -40° F to 149° F (-40° C to +65° C)
Altitude 0 - 12,000 ft (3.66 km)
Product design Thermal fuse technology
Regulations and certificationsUL 1449 4th edition VZCA:E320456 Type 2
cUL, CSA C22.2 VZCA7:E320456 Type 2
UL 1283 Yes
UL 96A Yes
IEEE C62.62, C62.72 Yes
Listed By UL
—ABB HE seriesWallmount SPD
12.000 [304.80]
10.750 [273.05]
12.015 [305.18]
12.000 [304.80]
26.500 [673.10]
9.276 [235.61]
1.250 [31.75]
24.000 [609.60]
0.625 [15.87]
0.440 [ 11.18]
(2 PLACES)
0.625 [15.87]
0.440 [ 11.18] HOLE
(2 PLACES)
WMN1 Dimensions
5-20 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB ME seriesWallmount SPD with enhanced thermal protection
Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPME120SxxxWMN
208Y/120 3-phase, 4-wire + ground TPME120YxxxWMN
380Y/220 3-phase, 4-wire + ground TPME220YxxxWMN
240 Delta 3-phase, 3-wire + ground TPME240DxxxWMN
240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPME240HxxxWMN
415Y/240 3-phase, 4-wire + ground TPME240YxxxWMN
480Y/277 3-phase, 4-wire + ground TPME277YxxxWMN
600Y/347 3-phase, 4-wire + ground TPME347YxxxWMN
480 Delta 3-phase, 3-wire + ground TPME480DxxxWMN
Desired kA xxx Code65 065
80 080
100 100
Product # ExampleTPME277Y15WMN4S277Y/480 V, 3 Ph, 4 W + G
150kA per mode
Surface mount enclosure without disconnect
Painted steel
T P M E W M NProduct #
Nominal Voltage (Volts RMS)
System Voltage Configuration
Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision
MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L
120S 120/240 1 Ph, 3 W + G 900 - 800 - 700 1200 - 125%
120Y 120Y/208 3 Ph, 4 W + G 900 - 800 - 700 1200 - 125%
220Y 220Y/380 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 145%
240D 240 Delta 3 Ph, 4 W - - 1200 - - 1800 - 196%
240H120/240 Delta HL
3 Ph, 4 W + G 1000 1200 800 1200 700 2000 2200 115%
240Y 240Y/415 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 130%
277Y 277Y/480 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 115%
347Y 347Y/600 3 Ph, 4 W + G 1500 - 1500 - 1500 2500 - 115%
480D 480 Delta 3 Ph, 4 W - - 1800 - - 3000 - 198%
Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.
Maximum Surge Current CapacityExposure Level
Per Mode Per Phase
06 ME 65kA 130kA
08 ME 80kA 160kA
10 ME 100kA 200kA
Phase Rating = (L-N + L-G)
Suffix DescriptionNEMA Enclosure
Mounting Disconnect
1 Painted Steel 1 Surface Yes
1T11 Painted Steel 1 Surface Yes
4 Fiberglass 4X Surface Yes
4T11 Fiberglass 4X Surface Yes
4S Painted Steel 4 Surface No
4ST11 Painted Steel 4 Surface No
4X Stainless Steel 4X Surface No
4XT11 Stainless Steel 4X Surface No1UL Type 1 device
5-21SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB ME seriesWallmount SPD with enhanced thermal protection
FeaturesUL Listed 1449 4th Edition, Type 1, Type 2
cUL Listed, CSA C22.2
UL 96A, for use in lightning protection systems
Patented thermal fuse technology
Standard features include a surge counter, audible alarm, indicating lights, dry contacts and NEMA 4 painted steel enclosure
10 year limited warranty
Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode
Nominal discharge current rating (l-n) 20 kA
Operating frequency 50-60Hz
Surge life (IEEE C62.41 - C3 10kA) ≥5000 impulses
Connection method 6 to 2/0 Conductors, Parallel Connected
Modes of protection All Modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR) 200 kAIC
Standard monitoring
Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter
EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ
Mechanical characteristics
WeightVaries and depends on enclosure typePlease see Available Options
Enclosure type Painted steel, NEMA 4
Installation location Service Entrance Equipment, Primary Distribution
Mounting method Surface Mount, 4-point mounting brackets
Operating temperature -40° F to 149° F (-40° C to +65° C)
Altitude 0 - 12,000 ft (3.66 km)
Product design Individually fused thermally protected MOV technology
Regulations and certificationsUL 1449 4th edition VZCA:E320456 Type 1/Type 2
cUL, CSA C22.2 VZCA7:E320456 Type 2/Type 2
UL 1283 FOKY:E320456 Type 2
UL 96A Yes
IEEE C62.62, C62.72, C62.41 Yes
Listed By UL
5-22 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB HE seriesWallmount SPD with enhanced thermal protection
Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPHE120SxxxWMN
208Y/120 3-phase, 4-wire + ground TPHE120YxxxWMN
380Y/220 3-phase, 4-wire + ground TPHE220YxxxWMN
240 Delta 3-phase, 3-wire + ground TPHE240DxxxWMN
240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPHE240HxxxWMN
415Y/240 3-phase, 4-wire + ground TPHE240YxxxWMN
480Y/277 3-phase, 4-wire + ground TPHE277YxxxWMN
600Y/347 3-phase, 4-wire + ground TPHE347YxxxWMN
480 Delta 3-phase, 3-wire + ground TPHE480DxxxWMN
600 Delta 3-phase, 3-wire + ground TPHE600DxxxWMN
Desired kA xxx Code150 150
200 200
250 250
300 300
T P H E W M NProduct #
Nominal Voltage (Volts RMS)
System Voltage Configuration
Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision
MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L
120S 120/240 1 Ph, 3 W + G 900 - 800 - 700 1200 - 125%
120Y 120Y/208 3 Ph, 4 W + G 900 - 800 - 700 1200 - 125%
220Y 220Y/380 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 145%
240D 240 Delta 3 Ph, 4 W - - 1200 - - 1800 - 196%
240H120/240 Delta HL
3 Ph, 4 W + G 1000 1200 800 1200 700 2000 2200 115%
240Y 240Y/415 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 130%
277Y 277Y/480 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 115%
347Y 347Y/600 3 Ph, 4 W + G 1500 - 1500 - 1500 2500 - 115%
480D 480 Delta 3 Ph, 4 W - - 1800 - - 3000 - 198%
Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.
Maximum Surge Current CapacityExposure Level
Per Mode Per Phase
12 HE 125kA 250kA
15 HE 150kA 300kA
20 HE 200kA 400kA
25 HE 250kA 500kA
30 HE 300kA 600kA
Phase Rating = (L-N + L-G)
Product # ExampleTPHE277Y15WMN4S277Y/480 V, 3 Ph, 4 W + G
150kA per mode
Surface mount enclosure without disconnect
Painted steel
Suffix DescriptionNEMA Enclosure
Mounting Disconnect
1 Painted Steel 1 Surface Yes
1T11 Painted Steel 1 Surface Yes
4 Fiberglass 4X Surface Yes
4T11 Fiberglass 4X Surface Yes
4S Painted Steel 4 Surface No
4ST11 Painted Steel 4 Surface No
4X Stainless Steel 4X Surface No
4XT11 Stainless Steel 4X Surface No1UL Type 1 device
5-23SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB HE seriesWallmount SPD with enhanced thermal protection
FeaturesUL Listed 1449 4th Edition, Type 1, Type 2
cUL Listed, CSA C22.2
UL 96A, for use in lightning protection systems
Thermally protected MOV design eliminates the need for additional upstream over current protection
Standard features include a surge counter, audible alarm, indicating lights, dry contacts and NEMA 4 painted steel enclosure
10 year limited warranty
Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode
Nominal discharge current rating (l-n) 20 kA
Operating frequency 50-60Hz
Surge life (IEEE C62.41 - C3 10kA) ≥20000 impulses
Connection method 6 to 2/0 Conductors, Parallel Connected
Modes of protection All Modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR) 200 kAIC
Standard monitoring
Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter
EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ
Mechanical characteristics
WeightVaries and depends on enclosure typePlease see Available Options
Enclosure type Painted steel, NEMA 4
Installation location Service Entrance Equipment, Primary Distribution
Mounting method Surface Mount, 4-point mounting brackets
Operating temperature -40° F to 149° F (-40° C to +65° C)
Altitude 0 - 12,000 ft (3.66 km)
Product design Individually fused thermally protected MOV technology
Regulations and certificationsUL 1449 4th edition VZCA:E320456 Type 1/Type 2
cUL, CSA C22.2 VZCA7:E320456 Type 2/Type 2
UL 1283 FOKY:E320456 Type 2
UL 96A Yes
IEEE C62.62, C62.72, C62.41 Yes
Listed By UL
5-24 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB ME and HE seriesWallmount, with enhanced thermal protection
12.000 [304.80]
10.750 [273.05]
12.015 [305.18]
12.000 [304.80]
26.500 [673.10]
9.276 [235.61]
1.250 [31.75]
24.000 [609.60]
0.625 [15.87]
0.440 [ 11.18]
(2 PLACES)
0.625 [15.87]
0.440 [ 11.18] HOLE
(2 PLACES)
24.000 [609.60]
25.500 [647.70]
20.000 [508.00]
12.651 [321.34]
21.500 [546.10]
9.912 [251.76]
1.852 [47.04]
13.478 [342.34]
14.759 [374.88]
16.000 [406.40]
8.978 [228.04]
15.330 [389.38]
19.330 [490.98]
8.978 [228.04]
15.330 [389.38]6.440
[163.58]
1.471 [37.36]
0.571 [14.50]
15.478 [393.14]
18.759 [476.48]
0.571 [14.50]
0.282 [ 7.16] HOLES
(8 PLACES)
3.852 [97.84]
12.000[304.80]
19.118 [485.61]
9.226 [234.33]
10.399 [264.14]
17.659 [448.53]
9.226 [234.33]
11.999 [304.77]6.439
[163.56]
1.475 [37.46]
0.380 [ 9.65] HOLE
(4 PLACES)
WMN1 Dimensions WMN4 Dimensions
WMN12F Dimensions WMN12S, WMN4S, WMN4X Dimensions
5-25SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB LE seriesWallmount SPD
Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TLE120SxxxWM
208Y/120 3-phase, 4-wire + ground TLE120YxxxWM
380Y/220 3-phase, 4-wire + ground TLE220YxxxWM
240 Delta 3-phase, 3-wire + ground TLE240DxxxWM
240/120 Hi-Leg Delta 3-phase, 4-wire + ground TLE240HxxxWM
415Y/240 3-phase, 4-wire + ground TLE240YxxxWM
480Y/277 3-phase, 4-wire + ground TLE277YxxxWM
480 Delta 3-phase, 3-wire + ground TLE480DxxxWM
Desired kA xxx Code25 025
50 050
T L E W MProduct #
Nominal Voltage (Volts RMS)
System Voltage Configuration
Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision
MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L
120S 120/240 1 Ph, 3 W + G 600 - 600 - 600 1000 - 125%
120Y 120Y/208 3 Ph, 4 W + G 600 - 600 - 600 1000 - 125%
220Y 220Y/380 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 145%
240D 240 Delta 3 Ph, 4 W - - 900 - - 1800 - 196%
240H120/240 Delta HL
3 Ph, 4 W + G 600 1200 600 1000 600 1000 1800 115%
240Y 240Y/415 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 130%
277Y 277Y/480 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 115%
480D 480 Delta 3 Ph, 4 W - - 1800 - - 4000 - 198%
025 25 kA per mode 50 kA per phase (TLE)
050 50 kA per mode 100 kA per phase (TLE)
5-26 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB LE seriesWallmount SPD
FeaturesUL Listed 1449 4th Edition, Type 2
cUL Listed, CSA C22.2
Compact and economical design for use at medium exposure, distribution or branch panels
Patented thermal fuse technology
Standard features include status indicating LEDs, form C dry contacts for remote monitoring and NEMA 12 painted steel enclosure
10 year limited warranty
Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode
Nominal discharge current rating (l-n) 10 kA
Operating frequency 50-60Hz
Surge life (IEEE C62.41 - C3 10kA) ≥3500 impulses
Connection method 10 AWG Conductors, Parallel Connected
Modes of protection All Modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR) 65 kA (30A breaker required)
Standard monitoringStatus indicator lights (one per phase)Standard dry (Form "C") relay contacts
Mechanical characteristicsWeight 17 lbs. (7.7 kg)
Enclosure type Painted steel, NEMA 12
Installation locationSecondary Distribution Equipment, Branch Panels - Rated for UL and NEC 2020 Type 2 Installation Locations
Mounting method Dual Mounting Flanges / 3/4" NPT Offset Nipple
Operating temperature -40° F to 149° F (-40° C to +65° C)
Altitude 0 - 12,000 ft (3.66 km)
Product design Thermal fuse technology
Regulations and certificationsUL 1449 4th edition VZCA:E320456 Type 2
cUL, CSA C22.2 VZCA7:E320456 Type 2
IEEE C62.62, C62.72 Yes
Listed By UL
TME TLE4.00
7.50
6.75
6.25
6.25
3/4" N.P.T.
6.00
1.55
4.37
2.85
TLE
5-27SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB ME seriesWallmount SPD
Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TME120SxxxWM
208Y/120 3-phase, 4-wire + ground TME120YxxxWM
380Y/220 3-phase, 4-wire + ground TME220YxxxWM
240 Delta 3-phase, 3-wire + ground TME240DxxxWM
240/120 Hi-Leg Delta 3-phase, 4-wire + ground TME240HxxxWM
415Y/240 3-phase, 4-wire + ground TME240YxxxWM
480Y/277 3-phase, 4-wire + ground TME277YxxxWM
480 Delta 3-phase, 3-wire + ground TME480DxxxWM
Desired kA xxx Code65 065
80 080
100 100
T M E W MProduct #
Nominal Voltage (Volts RMS)
System Voltage Configuration
Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision
MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L
120S 120/240 1 Ph, 3 W + G 600 - 600 - 600 1000 - 125%
120Y 120Y/208 3 Ph, 4 W + G 600 - 600 - 600 1000 - 125%
220Y 220Y/380 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 145%
240D 240 Delta 3 Ph, 4 W - - 900 - - 1800 - 196%
240H120/240 Delta HL
3 Ph, 4 W + G 600 1200 600 1000 600 1000 1800 115%
240Y 240Y/415 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 130%
277Y 277Y/480 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 115%
480D 480 Delta 3 Ph, 4 W - - 1800 - - 4000 - 198%
065 65 kA per mode 130 kA per phase (TME)
080 80 kA per mode 160 kA per phase (TME)
100 100 kA per mode 200 kA per phase (TME)
5-28 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—ABB ME seriesWallmount SPD
FeaturesUL Listed 1449 4th Edition, Type 2
cUL Listed, CSA C22.2
UL 96A, for use in lightning protection systems
Compact and economical design for use at medium exposure, distribution or branch panels
Standard features include status indicating LEDs, form C dry contacts for remote monitoring and NEMA 12 painted steel enclosure
10 year limited warranty
Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode
Nominal discharge current rating (l-n) 20 kA
Operating frequency 50-60Hz
Surge life (IEEE C62.41 - C3 10kA) ≥5000 impulses
Connection method 10 AWG Conductors, Parallel Connected
Modes of protection All Modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR) 65 kA (30A breaker required)
Standard monitoringStatus indicator lights (one per phase)Standard dry (Form "C") relay contacts
EMI/RFI filter attenuationMaximum attenuation frequency -44dB @ (50kHz - 100MHz)
Mechanical characteristicsWeight 17 lbs. (7.7 kg)
Enclosure type Painted steel, NEMA 12
Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2020 Type 2 Installation Locations
Mounting method Dual Mounting Flanges / 3/4" NPT Offset Nipple
Operating temperature -40° F to 149° F (-40° C to +65° C)
Altitude 0 - 12,000 ft (3.66 km)
Product design Thermal fuse technology
Regulations and certificationsUL 1449 4th edition VZCA:E320456 Type 2
cUL, CSA C22.2 VZCA7:E320456 Type 2
UL 1283 FOKY:E320456 Type 2
UL 96A Yes
IEEE C62.62, C62.72 Yes
Listed By UL
TME TLE4.00
7.50
6.75
6.25
6.25
3/4" N.P.T.
6.00
1.55
4.37
2.85
TME
5-29SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—OVRH seriesProduct range overview
NameOVRHSP (200, 240, 300, 400)
OVRHSP (120, 160)
OVRHSP (60, 80, 100)
OVRHSR (120, 160)
OVRHTE OVRHT3B OVRHT3C OVRHS3U OVRHLD
Connection Ampacity
1,000A and higher
1,000A and below
400A and below
1,000A and below
100–80kA1,000A and below50kA400A and below25kA100A and below
400A and below
400A and below
400A and below
100A and below
SPD Type Type 1 Type 1 Type 1 Type 1 Type 2 Type 1 Type 1 Type 1 and Type 2
Type 1
Certifications UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449
Surge Ratings 200, 240, 300, 400kA per phase
120, 160kA per phase
60, 80, 100kA per phase
120, 160kA per phase
25, 50, 80 and 100 per mode
50kA per phase
50kA per phase
40kA per phase
20, 25, 30kA per phase
LEDs Yes Yes Yes Yes Yes Yes Yes Yes Yes
Dry Relay Contacts
Standard Standard Optional Standard Optional Not available
Not available
Optional Not available
EMI Filter Optional Optional Optional Optional Optional Not available
Not available
Not available
Not available
Surge Counter Optional Optional Not available
Not available
Not available
Not available
Not available
Not available
Not available
Warranty 10 years 10 years 10 years 10 years 5 years 3 year 3 year 1 year 1 year
5-30 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
Voltage Network type Part number
120 Vac1PH, 2W + GND
OVRHSPxx1201P
240 Vac OVRHSPxx2401P
240/120 Vac 2PH, 3W + GND OVRHSPxx1202S
208/120 Vac
3PH, 4W + GND (Wye)
OVRHSPxx1203Y
380/220 Vac OVRHSPxx2203Y
415/240 Vac OVRHSPxx2403Y
480/277 Vac OVRHSPxx2773Y
240/120 Vac 3PH, 4W + GND (High-leg) OVRHSPxx1203H
240 Vac 3PH, 3W + GND (Delta) OVRHSPxx2403D
xx indicates 60kA, 80kA or 100kA
Available Options (Add applicable suffix to the end of the part number)
Suffix
Advanced monitoring1 1
Transient filter (meets UL1283)2 3
Stainless steel enclosure (SS) 4
Advanced monitoring + SS enclosure A
Transient filter + SS enclosure C
1Includes dry relay contacts, audible alarm, alarm silence button and fault light2Not recommended when using telecom rectifiers
Electrical characteristics
Maximum surge current rating xx per phase/half xx per mode
Nominal discharge current rating (I-n) 10kA
Operating frequency 47-63Hz
Connection methodParallel to electrical distribution system
Modes of protection All modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR)200kAIC - No upstream over-current protection device required (breaker or fuse)
Response time Less than 1 nanosecond
Standard monitoringLED status indicator lights (1 per phase)
EMI/RFI filter attenuation
Maximum attenuation frequency 41dB @ 106kHz
Mechanical characteristics
Weight 10 lbs. (4.5 kg)
Enclosure typePowder coated, impact-resistance steel, weather-proof NEMA 4
Installation location Indoor/outdoor
Mounting method Dual mounting flanges
Operating temperature -40° to +185° F (-40° to +70° C)
Altitude Up to 13,000 ft. (4000 m)
Product designParallel design with individually fused MOVs
Regulations & certifications
UL 1449 4th edition Type 1
UL 1283 Yes
IEEE C62.41.1, .2, C62.45 Yes
Listed by ETL
Product features• Listed by ETL to UL 1449 4th Edition for Type 1 and Type 2
SPD applications• Fail-safe design with individually fused Metal Oxide
Varistors (MOV) eliminating single point failure, protecting against both overcurrent and overvoltage events
• 200kAIC short circuit rating permits direct bus connection to most electrical services
• Low let through voltage ensured by the lowest possible impedance path to ground and equal current sharing during surge events
• All weather sealed, powder-coated NEMA 4/IP65 housing is designed for any orientation and indoor/outdoor applications
• 10-year standard warranty
—OVRH seriesOVRHSP (4,000A and below, 60 to 100kA)
5-31SURGE PROTECTION DEVICES, BUYLOG SECTION 5
Voltage Network type Part number
120 Vac1PH, 2W + GND
OVRHSPxx1201P
240 Vac OVRHSPxx2401P
240/120 Vac 2PH, 3W + GND OVRHSPxx1202S
208/120 Vac
3PH, 4W + GND (Wye)
OVRHSPxx1203Y
380/220 Vac OVRHSPxx2203Y
415/240 Vac OVRHSPxx2403Y
480/277 Vac OVRHSPxx2773Y
600/347 Vac OVRHSPxx3473Y
240/120 Vac 3PH, 4W + GND (High-leg) OVRHSPxx1203H
240 Vac
3PH, 3W + GND (Delta)
OVRHSPxx2403D
380 Vac OVRHSPxx3803D
480 Vac OVRHSPxx4803D
600 Vac OVRHSPxx6003D
xx indicates 120kA or 160kA
Available Options (Add applicable suffix to the end of the part number)
Suffix
Surge counter 2
Transient filter (meets UL1283)1 3
Stainless steel enclosure (SS) 4
Transient filter + Surge counter B
Transient filter + SS enclosure C
Surge counter + SS enclosure D
Filter + counter + SS enclosure T
1Not recommended when using telecom rectifiers
Product features• Listed by UL 1449 4th Edition for Type 1 and Type 2 SPD
applications• Fail-safe design with individually fused Metal Oxide
Varistors (MOV) eliminating single point failure, protecting against both overcurrent and overvoltage events
• 200kAIC short circuit rating permits direct bus connection to most electrical services
• Low let through voltage ensured by the lowest possible impedance path to ground and equal current sharing during surge events
• All weather sealed, powder-coated NEMA 4/IP65 housing is designed for any orientation and indoor/outdoor applications
• 10-year standard warranty
—OVRH seriesOVRHSP (4,000A and below, 120 to 160kA)
Electrical characteristics
Maximum surge current rating xx per phase/half xx per mode
Nominal discharge current rating (I-n) 20kA
Operating frequency 47-63Hz
Connection methodParallel to electrical distribution
Modes of protection All modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR)200kAIC - No upstream over-current protection device required (breaker or fuse)
Response time Less than 1 nanosecond
Standard monitoringLED status indicator lights (1 per phase), dry contacts, alarm
EMI/RFI filter attenuation
Maximum attenuation frequency 41dB @ 106kHz
Mechanical characteristics
Weight 20 lbs. (9 kg)
Enclosure typePowder coated, impact-resistance steel, weather-proof NEMA 4
Installation location Indoor/outdoor
Mounting method Dual mounting flanges
Operating temperature -40° to +185° F (-40° to +70° C)
Altitude Up to 13,000 ft. (4000 m)
Product designParallel design with individually fused MOVs
Regulations & certifications
UL 1449 4th edition Type 1
UL 1283 Yes
IEEE C62.41.1, .2, C62.45 Yes
Listed by UL
5-32 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
Product features• Listed by UL 1449 4th Edition for Type 1 and Type 2 SPD
applications• Fail-safe design with individually fused Metal Oxide
Varistors (MOV) eliminating single point failure, protecting against both overcurrent and overvoltage events
• 200kAIC short circuit rating permits direct bus connection to most electrical services
• Low let through voltage ensured by the lowest possible impedance path to ground and equal current sharing during surge events
• All weather sealed, powder-coated NEMA 4/IP65 housing is designed for any orientation and indoor/outdoor applications
• 10-year standard warranty
—OVRH seriesOVRHSP (4,000A and below, 200 to 400kA)
Voltage Network type Part number
120 Vac1PH, 2W + GND
OVRHSPxx1201P
240 Vac OVRHSPxx2401P
240/120 Vac 2PH, 3W + GND OVRHSPxx1202S
208/120 Vac
3PH, 4W + GND (Wye)
OVRHSPxx1203Y
380/220 Vac OVRHSPxx2203Y
415/240 Vac OVRHSPxx2403Y
480/277 Vac OVRHSPxx2773Y
600/347 Vac OVRHSPxx3473Y
240/120 Vac 3PH, 4W + GND (High-leg) OVRHSPxx1203H
240 Vac
3PH, 3W + GND (Delta)
OVRHSPxx2403D
380 Vac OVRHSPxx3803D
480 Vac OVRHSPxx4803D
600 Vac OVRHSPxx6003D
xx indicates 200kA, 240kA, 300kA or 400kA
Available Options (Add applicable suffix to the end of the part number)
Suffix
Surge counter 2
Transient filter (meets UL1283)1 3
Stainless steel enclosure (SS) 4
Transient filter + Surge counter B
Transient filter + SS enclosure C
Surge counter + SS enclosure D
Filter + counter + SS enclosure T
1Not recommended when using telecom rectifiers
Electrical characteristics
Maximum surge current rating xx per phase/half xx per mode
Nominal discharge current rating (I-n) 20kA
Operating frequency 47-63Hz
Connection methodParallel to electrical distribution
Modes of protection All modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR)200kAIC - No upstream protection required (breaker/fuse)
Response time Less than 1 nanosecond
Standard monitoringLED status indicator lights (1 per phase), dry contacts, alarm
EMI/RFI filter attenuation
Maximum attenuation frequency 41dB @ 106kHz
Mechanical characteristics
Weight 40 lbs. (18 kg)
Enclosure typePowder coated, impact-resistance steel, weather-proof NEMA 4
Installation location Indoor/outdoor
Mounting method Dual mounting flanges
Operating temperature -40° to +185° F (-40° to +70° C)
Altitude Up to 13,000 ft. (4000 m)
Product designParallel design with individually fused MOVs
Regulations & certifications
UL 1449 4th edition Type 1
UL 1283 Yes
IEEE C62.41.1, .2, C62.45 Yes
Listed by ETL
5-33SURGE PROTECTION DEVICES, BUYLOG SECTION 5
Voltage Network type Part number
120 Vac1PH, 2W + GND
OVRHSRxx1201P
240 Vac OVRHSRxx2401P
240/120 Vac 2PH, 3W + GND OVRHSRxx1202S
208/120 Vac
3PH, 4W + GND (Wye)
OVRHSRxx1203Y
380/220 Vac OVRHSRxx2203Y
415/240 Vac OVRHSRxx2403Y
480/277 Vac OVRHSRxx2773Y
600/347 Vac OVRHSRxx3473Y
240/120 Vac 3PH, 4W + GND (High-leg) OVRHSRxx1203H
240 Vac
3PH, 3W + GND (Delta)
OVRHSRxx2403D
380 Vac OVRHSRxx3803D
480 Vac OVRHSRxx4803D
600 Vac OVRHSRxx6003D
xx indicates 120kA or 160kA
Available Options (Add applicable suffix to the end of the part number)
Suffix
Transient filter (meets UL1283)1 3
Stainless steel enclosure (SS) 4
Filter + counter + SS enclosure C
1Not recommended when using telecom rectifiers
Stand alone option Part number
Flush-mount plate kit OVRHSP-FMP
Product features• Listed by UL 1449 4th Edition for Type 1 and Type 2 SPD
applications• CE compliant• Compact design to allow the SPD to be recessed into the
wall• Fail-safe design with individually fused Metal Oxide
Varistors (MOV) eliminating single point failure, protecting against both overcurrent and overvoltage events
• 200kAIC short circuit rating permits direct bus connection to most electrical services
• Low let through voltage ensured by the lowest possible impedance path to ground and equal current sharing during surge events
• 10-year standard warranty
Electrical characteristics
Maximum surge current rating xx per phase/half xx per mode
Nominal discharge current rating (I-n) 20kA
Operating frequency 47-63Hz
Connection methodParallel to electrical distribution
Modes of protection All modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR)200kAIC - No upstream protection required (breaker/fuse)
Response time Less than 1 nanosecond
Standard monitoringLED status indicator lights (1 per phase), dry contacts, alarm
EMI/RFI filter attenuation
Maximum attenuation frequency 41dB @ 106kHz
Mechanical characteristics
Weight 30 lbs. (13.6 kg)
Enclosure typePowder coated, impact-resistance steel, weather-proof NEMA 4
Installation location Indoor/outdoor
Mounting method Dual mounting flanges
Operating temperature -40° to +185° F (-40° to +70° C)
Altitude Up to 13,000 ft. (4000 m)
Product designParallel design with individually fused MOVs
Regulations & certifications
UL 1449 4th edition Type 1
UL 1283 Yes
IEEE C62.41.1, .2, C62.45 Yes
Listed by UL
—OVRH seriesOVRHSR (Wall recessed - 4,000A and below, 120 to 160kA)
5-34 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—OVRH seriesOVRHTE (1,000A and below, 25 to 100kA)
Product features• Listed by UL 1449 4th Edition for Type 2 SPD applications• Protects facilities and equipment against the harmful
effects of lightning strikes and internally generated electrical transients
• Includes pre-wired pigtail conductors to streamline installation
• Features internal copper bus conduction path to minimize system impedances, lowering clamping voltage and increasing protection
• Pre-wired with 24 in (609.6mm) cables #10AWG (5mm2)• 5-year standard warranty
Voltage Network type Part number
120 Vac1PH, 2W + GND
OVRHTExx1201P
240 Vac OVRHTExx2401P
240/120 Vac 2PH, 3W + GND OVRHTExx1202S
208/120 Vac
3PH, 4W + GND (Wye)
OVRHTExx1203Y
380/220 Vac OVRHTExx2203Y
415/240 Vac OVRHTExx2403Y
480/277 Vac OVRHTExx2773Y
600/347 Vac OVRHTExx3473Y
240/120 Vac 3PH, 4W + GND (High-leg) OVRHTExx2403H
240 Vac
3PH, 3W + GND (Delta)
OVRHTExx2403D
380 Vac OVRHTExx3803D
480 Vac OVRHTExx4803D
xx indicates 25kA, 50kA, 80kA or 100kA
Available Option (Add applicable suffix to the end of the part number. Example: OVRHTE251201P5)
Suffix
Dry Form "C" relay contacts 5
Electrical characteristics
Maximum surge current rating xx per phase/half xx per mode
Nominal discharge current rating (I-n) 20kA
Operating frequency 47-63Hz
Connection method Parallel to load (with breaker)
Modes of protection All modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR)65kAIC - upstream protection (breaker or fuse required)
Response time Less than 1 nanosecond
Standard monitoringLED status indicator lights (1 per phase)
EMI/RFI filter attenuation
Maximum attenuation frequency 50dB @ 100kHz
Mechanical characteristics
Weight 12.7 lbs. (5.8 kg)
Enclosure typeNEMA 4X fiberglass-reinforced polyester (FRP) surface-mount, non-removable cover
Installation location Indoor/outdoor
Mounting method Dual mounting flanges
Operating temperature -40° to +140° F (-40° to +60° C)
Altitude Up to 16,400 ft. (5000 m)
Product design No internal fusing
Regulations & certifications
UL 1449 4th edition Type 2
UL 1283 Yes
IEEE C62.41.1, .2, C62.45 Yes
Listed by UL
5-35SURGE PROTECTION DEVICES, BUYLOG SECTION 5
Voltage Network type 1 SPD Part number
120 Vac
1PH, 2W + GND
OVRHT3B501201P
240 Vac OVRHT3B502401P
277 Vac OVRHT3B502771P
480 Vac OVRHT3B504801P
240/120 Vac2PH, 3W + GND
OVRHT3B501202S
480/240 Vac OVRHT3B502402S
240/120 Vac 3PH, 4W + GND (Hi-Leg) OVRHT3B502403H
208/120 Vac
3PH, 4W + GND (Wye)
OVRHT3B501203Y
380/220 Vac OVRHT3B502203Y
400/230 Vac OVRHT3B502303Y
415/240 Vac OVRHT3B502403Y
480/277 Vac OVRHT3B502773Y
600/347 Vac OVRHT3B503473Y
240 Vac
3PH, 3W + GND (Delta)
OVRHT3B502403D
380 Vac OVRHT3B503803D
400 Vac OVRHT3B504003D
480 Vac OVRHT3B504803D
600 Vac OVRHT3B506003D
Product features• Listed to UL 1449 4th Edition for Type 1 SPD applications• 50kA protection per phase• Individually thermally fused and protected MOVs• LED indication• Pre-wired conductors included• Multiple MOVs per phase eliminates single point failure• 3-year standard warranty
Electrical characteristics
Nominal discharge current rating (I-n) 10kA
Operating frequency 47-63Hz
Connection method Parallel to load (with breaker)
Modes of protection Model dependent
Fault rating (SCCR) 100kAIC
Response time Less than 1 nanosecond
Standard monitoring LED status indicator lights
Mechanical characteristics
Weight 0.5 lbs. (0.23 kg)
Enclosure type NEMA 4X non-metallic
Installation location Indoor/outdoor
Mounting method 1/2 in (12.7mm) - 14 NPT thread
Operating temperature -31° to +176° F (-35° to +80° C)
Altitude Up to 16,400 ft. (5000 m)
Product design Individual therm. fused MOVs
Regulations & certifications
UL 1449 4th edition Type 1
UL 96A Yes
IEEE C62.41.1, .2, C62.45 Yes
Listed by UL
—OVRH seriesOVRHT3B (400A and below, 50kA)
5-36 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—OVRH seriesOVRHT3C (400A and below, 50kA)
Product features• Listed to UL 1449 4th Edition for Type 1 SPD applications• 50kA protection per phase• Individual thermally fused and protected MOVs• LED indication• Pre-wired conductors included• Multiple MOVs per phase eliminates single point failure• 3-year standard warranty
Voltage Network type 1 SPD Part number
120 Vac
1PH, 2W + GND
OVRHT3C501201P
240 Vac OVRHT3C502401P
277 Vac OVRHT3C502771P
480 Vac OVRHT3C504801P
240/120 Vac2PH, 3W + GND
OVRHT3C501202S
480/240 Vac OVRHT3C502402S
240/120 Vac 3PH, 4W + GND (Hi-Leg) OVRHT3C502403H
208/120 Vac
3PH, 4W + GND (Wye)
OVRHT3C501203Y
380/220 Vac OVRHT3C502203Y
400/230 Vac OVRHT3C502303Y
415/240 Vac OVRHT3C502403Y
480/277 Vac OVRHT3C502773Y
600/347 Vac OVRHT3C503473Y
240 Vac
3PH, 3W + GND (Delta)
OVRHT3C502403D
380 Vac OVRHT3C503803D
400 Vac OVRHT3C504003D
480 Vac OVRHT3C504803D
600 Vac OVRHT3C506003D
Electrical characteristics
Nominal discharge current rating (I-n) 10kA
Operating frequency 47-63Hz
Connection method Parallel to load (with breaker)
Modes of protection Model dependent
Fault rating (SCCR) 100kAIC
Response time Less than 1 nanosecond
Standard monitoring LED status indicator lights
Mechanical characteristics
Weight 0.5 lbs. (0.23 kg)
Enclosure type NEMA 4X non-metallic
Installation location Indoor/outdoor
Mounting method 1/2 in (12.7mm) - 14 NPT thread
Operating temperature -31° to +176° F (-35° to +80° C)
Altitude Up to 16,400 ft. (5000 m)
Product design Individual therm. fused MOVs
Regulations & certifications
UL 1449 4th edition Type 1
UL 96A Yes
IEEE C62.41.1, .2, C62.45 Yes
Listed by UL
5-37SURGE PROTECTION DEVICES, BUYLOG SECTION 5
Product features• Listed to UL 1449 4th Edition for Type 1 or Type 2 SPD
applications• Individual fusing for each Metal Oxide Varistors (MOVs)• LED indicating proper functioning of L-N and N-G MOVs• Pre-wired with 18in (450mm) cables #14AWG (2mm2)• 1-year standard warranty
—OVRH seriesOVRHS3U (400A and below, 40kA)
Voltage Network Type 1 SPD Part number
120 Vac 1PH, 2W + GND OVRHS3U401201P
240/120 Vac 2PH, 3W + GND OVRHS3U401202S
240V 3PH, 4W + GND (Delta) OVRHS3U402403D
208/120 Vac 3PH, 4W + GND (Wye) OVRHS3U401203Y
Voltage Network Type 2 SPD Part number
240V 1PH, 2W + GND OVRHS3U402401P
240/120V 2PH, 3W + GND1 OVRHS3U801202SR
480V 3PH, 3W + GND (Delta) OVRHS3U404803D
240/120V 3PH, 4W + GND (Hi-Leg) OVRHS3U401203H
480/277V 3PH, 4W + GND (Wye) OVRHS3U402773Y
400/230V 3PH, 3W + GND (Wye) OVRHS3U402303Y
180kA unit including 1283 listed filter, dry contacts option not available
Available Options Suffix
Dry relay contacts 5
Dry relay contacts + mounting bracket P
Electrical characteristics
Nominal discharge current rating (I-n) 20kA
Operating frequency 47-63Hz
Connection method Parallel to load
Modes of protection All modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR) 100kAIC
Response time Less than 1 nanosecond
Standard monitoring LED status indicator lights
Mechanical characteristics
Weight 2 lbs. (0.9 kg)
Enclosure type NEMA 1 non-metallic
Installation location Indoor
Mounting method 1/2in (12.7mm) - 14 NPT thread
Operating temperature -40° to +176° F (-40° to +80° C)
Altitude Up to 16,400 ft. (5000 m)
Product design Individually fused MOVs
Regulations & certifications
UL 1449 4th edition Type 1 and Type 2
UL 1283 Only for OVRHS3U802402SR
IEEE C62.41.1, .2, C62.45 Yes
Listed by UL
5-38 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—OVRH seriesOVRHLD (100A and below, 20 to 30kA)
Product features• Listed by ETL to UL 1449 4th Edition for Type 1 SPD
applications• Multiple metal oxide varistors (MOVs), with individual
current fusing and thermal disconnects for each MOV• LED indicating proper functioning of L-N MOVs• Pre-wired with 18in (450mm) cables #14AWG (2mm2)• 1-year warranty
Description Part number
xxkA, yyyV, L-N / N-G (1 LED) OVRHLDxx-yyy-1
xxkA, yyyV, L1-N / L2-N (2 LEDs) OVRHLDxx-yyy-2
xxkA, yyyV, L1-G / L2-G (2 LEDs) OVRHLDxx-yyy-3
xxkA, yyyV, L1-G / N-G (1 LED) OVRHLDxx-yyy-4
xxkA, yyyV, L-N / L-G (2 LEDs) OVRHLDxx-yyy-5
xxkA, yyyV, L-N (1 LED) OVRHLDxx-yyy-6
xxkA, yyyV, L-G (1 LED) OVRHLDxx-yyy-7
xxkA, yyyV, N-G (0 LED) OVRHLDxx-yyy-8
xxkA, yyyV, L1-L2 (1 LED) OVRHLDxx-yyy-9
Available Option
(Add applicable suffix to the end of the part number)
Suffix
Mounting bracket 6
Electrical characteristics
Nominal discharge current rating (I-n) 10kA
Operating frequency 47-63Hz
Connection method Parallel to load
Modes of protection L-N, L-G, N-G
Fault rating (SCCR) 65kAIC
Response time Less than 1 nanosecond
Standard monitoringLED status indicator lights 1 per phase
Mechanical characteristics
Weight 1 lb. (0.5 kg)
Enclosure type NEMA 1 non-metallic
Installation location Indoor
Mounting method NPS thread or bracket
Operating temperature -40° to +176° F (-40° to +80° C)
Altitude Up to 16,400 ft. (5000 m)
Product designIndividually fused MOVs, Overcurrent fusing, thermal fusing
Regulations & certifications
UL 1449 4th edition Type 1
UL 1283 No
IEEE C62.41.1, .2, C62.45 Yes
Listed by ETL
5-39SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—OVRH seriesDimensions
Dimensions OVRHSP (60 to 100kA)
Value Inches / Millimeters
H1 6.00 / 152.4
H2 6.75 / 171.5
H3 7.50 / 190.5
W1 6.00 / 152.4
W2 4.00 / 101.6
D1 4.16 / 105.7
D2 2.00 / 50.8
Dimensions OVRHSP (120 to 160kA)
Value Inches / Millimeters
H1 10.00 /254.0
H2 10.75 / 273.1
H3 11.50 / 292.1
W1 8.00 / 203.2
W2 6.00 / 152.4
D 6.20 / 157.5
Dimensions
Value Inches / Millimeters
H1 14.00 / 355.6
H2 14.75 / 374.7
H3 15.50 /393.7
W1 12.00 / 304.8
W2 10.00 / 254.0
D 6.20 / 157.5
(W1)
(W2)
(H1)
(H2)
(H3)
(D1) (D2)
19.05 (3/4) Myers Hub
ø7.87 (0.31)
(W1)
(W2)
(H1)(H2)
(H3)
ø7.87 (0.31)
(D)
34.5(1.36)
83.8(3.20)
Allowable area for conduit entry
(W1)
(W2)
(H1)(H2)
(H3)
ø0.31 (7.87)
(D)
Allowable area for conduit entry
34.5(1.36)
83.8(3.20)
5-40 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—OVRH seriesDimensions
Dimensions OVRHSR (120 to 160kA)
Value Inches / Millimeters
H1 10.00 / 254.0
H2 10.75 / 273.1
H3 11.50 / 292.1
W1 8.00 / 203.2
W2 6.00 / 152.4
D1 4.20 / 106.9
D2 2.00 / 50.8
Stud
Drywall
Flush-mount plate
OVRHSR unit
5-41SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—OVRH seriesDimensions
Dimensions OVRHTE
Value Inches / Millimeters
H1 6.17 / 156.7
H2 6.75 / 171.5
H3 7.50 / 190.4
W1 4.01 / 101.9
W2 6.12 / 155.4
D 5.01 / 127.5
Dimensions OVRHT3B
Value Inches / Millimeters
W 3.36 / 90.0
D 2.93 / 75.0
H 2.93 / 75.0
Dimensions OVRHT3C
Value Inches / Millimeters
W 3.18 / 80.8
D 3.10 / 78.7
H 3.56 / 90.4
(W2)
(W1)(D)
(H1) (H2) (H3)
90mm(3.56")
75mm(2.93")
75mm(2.93")
32mm(1.26")
35mm(1.37")
19mm (.75")
64mm(2.52")
3.31mm2 (#12 AWG) stranded wire600V PVC insulation914.4mm (36") long
Aluminum bracket
Ø 5.5mm (.21") 2 holes
12.7mm (1/2")-14 NPS thread
Bracket detail
W
H
D
5-42 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—OVRH seriesDimensions
Dimensions OVRHS3U (with and without dry contacts option)
Value Inches / Millimeters
W 2.90 / 73.0
D 2.00 / 51.0
H 5.60 / 142.0
Dimensions mounting bracket OVRHS3U
Value Inches / Millimeters
W 1.94 / 49.0
H 8.25 / 210.0
(2.90")73mm
(5.6") 142mm
19mm (.75")
Remote monitoring terminals
LED
2mm2 (#14 AWG) stranded wire600V PVC insulation450mm (18") long
210mm (8.25")
195mm (7.690")
7mm (.28") Mounting
bracket
12mm (.47")
25mm(1.000")
49mm (1.94")
M4 threaded hole4 plcs.
(2.90")73mm
(2.00")51mm
(1.60") 41mm
(5.6") 142mm
(2.30") 58mm
19mm (.75")
.136 dia. blind holes, .40 deep for #8 self-tapping screws (2)
(0.25")6mm
LED
1/2–14 NPT thread
2mm2 (#14 AWG) stranded wire600V PVC insulation450mm (18") long
5-43SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—DIN-rail SPDs for distribution panelsUL 1449 4th edition
Transient Voltage Surges in LV Power LinesTransient overvoltages are voltage surges that can reach tens of kilovolts with a duration in the order of microseconds.
Despite their short duration, the high energy content can cause serious problems to equipment connected to the line, from premature aging to destruction, causing disruptions to service and financial loss.
This type of surge can have various different causes, including atmospheric lightning directly striking the external protection (lightning rods) on a building or transmission line, or the associated induction of electromagnetic fields on metallic conductors. Outdoor and longer lines are the most exposed to these fields, which often receive high levels of induction.
It is also common for non-weather phenomena such as transformer center switching or the disconnection of motors or other inductive loads to cause voltage spikes in adjacent lines.
The protector will discharge excess energy to earth, thus limiting the peak voltage to a value acceptable for the electrical equipment connected.
Risk of Electrical SurgesLightning and surge protection electrical and electronic equipment is indispensable in the daily activities of today’s businesses and individuals.
Such devices are connected to the electricity grid, often exchanging data and signals through communication lines and are usually sensitive to disturbances.
These interconnecting networks provide a propagation path for overvoltages.
Protection against lightning and overvoltages not only ensures the safety of people, goods and equipment, but also ensures continuity of installation services and meets criteria of energy efficiency.
Overvoltage protection extends the life of the equipment by more than 20%, which significantly reduces the volume of electronic waste. It also reduces the power consumption of the installations, all of which translates into cost savings and environmental sustainability.
U(V)
2
4000
3500
3000
2000
1000
500
-500
-10001ms max.
04 6 8 10 12 14 16 18 20 t(ms)
When the peak voltage reaches a value higher than the equipment can withstand, it causes its destruction.
5-44 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—DIN-rail SPDs for distribution panelsUL 1449 4th editionTerminology of SPD electrical characteristics
ImaxMaximum Discharge CapacityMaximum peak current, per phase, in 8/20 μs wave that the protection device is able to withstand.
VPRVoltage Protection RatingThis indicates the maximum residual voltage between the terminals of the protection device during application of an In peak current.
InNominal Discharge Current RatingPeak current in 8/20 μs wave that the protection device can withstand on 15 occasions without reaching the end of its service life.
MCOVMaximum Continuous Operating Voltage This indicates the maximum effective or direct current voltage that can be permanently applied to the terminals of the protection device.
TYPEType 1Permanently connected SPDs intended for installation betweenbthe secondary of the service transformer and the line side of the service equipment (main panel) overcurrent device, as well as the load side, including watt-hour meter socket enclosures and intended to be installed without an external overcurrent protective device.
Type 2Permanently connected SPDs intended for installation on the load side of the service equipment (main panel) overcurrent device; including SPDs located at the branch panel.
Type 3Point of utilization SPDs, installed at a minimum conductor length of 30 feet (10 meters) from the electrical service panel to the point of utilization. For example cord connected, direct plug-in, receptacle type and SPDs installed at the utilization equipment being protected. The distance 30 feet (10 meters) is exclusive of conductors provided with or used to attach SPDs that the protection device is able to withstand.
Operating principle of an SPD
5-45SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—DIN-rail SPDs for distribution panelsUL 1449 4th editionStandards
The objective of UL 1449 has always been to increase safety in terms of surge protection.
Change in the standard's name: From TVSS to SPDsPrior to UL 1449 4th Edition taking effect, the devices this standard covers were known as Transient Voltage Surge Suppressors (TVSS), operating on power circuits not exceeding 600 V. With the inception of the 3rd and 4th Edition, these devices are now known as Surge Protective Devices (SPDs), and may operate on power circuits not exceeding 1500 V DC.
This new designation moves the UL standard closer to the international designation and to IEC standards.
The different type designations of surge protective devicesThe UL 1449 placed SPDs into five different Type categories based on installation location within an electrical system.While Type 1, Type 2 and Type 3 categories refer to different types of SPDs that can be installed at specific locations, Type 4 and Type 5 categories refer to components used in an SPDs configuration.
Type 1 - “Permanently connected SPDs intended for installation between the secondary of the service transformer and the line side of the service equipment overcurrent device.”Type 2 - “Permanently connected SPDs intended for installation on the load side of the service equipment overcurrent device.”Type 3 - “Point of utilization SPDs, installed at a minimum conductor length of 10 meters (30 feet) from the electrical service panel.”Type 4 - Component assemblies - “Component assembly consisting of one or more Type 5 components together with a disconnect (integral or external) or a means of complying with the limited current tests.”Type 1, 2, 3 - Component assemblies - “Consists of a Type 4 component assembly with internal or external short circuit protection.”Type 5 - “Discrete component surge suppressors, such as MOVs that may be mounted on a PWB, connected by its leads or provided within an enclosure with mounting means and wiring terminations.”
The closer an SPD is installed to the equipment, the better the protection is. This is a push in the direction of providing stepped protection including external and internal surge protection.
The measured voltage protection levelThe Measured Limiting Voltage (MLV) is the maximum magnitude of voltage measured at the application of a specific impulse wave shape.
When applying a certain surge current on the SPD the measured voltage at the device terminals is the so called “let-through voltage.”
In UL 1449 2nd Edition, the let-through voltage was referred to as Suppressed Voltage Rating (SVR) and was calculated with a 0.5 kA surge wave form at 6 kV. The new designation is Voltage Protection Rating (VPR) and is calculated with a 3 kA surge wave form at 6 kV.
All products you will find in this chapter have been certified according to the UL 1449 4th Edition.
The MLV will allow comparison of different types of SPDs with regards to the let-through voltage. However, it is important to note that the surge current used to measure the let-through voltage is six times higher in the 3rd and 4th Edition than in the 2nd Edition. This means that, comparing the obsolete SVR designation with the new VPR ratings will not be valid, as VPR ratings will of course be higher than SVR ratings.
The Underwriters Laboratories (UL) standard for surge protective devices (SPDs) has been the primary safety standard for surge protection since the first edition was published in 1985, the fourth edition became mandatory for AC SPDs in March 2016.
5-46 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—DIN-rail SPDs for distribution panelsUL 1449 4th editionStandards
Wiring Diagrams According to ANSI C84.1The majority of modern installations in both the US and Canada feature the following kind of power distribution system.
Single Phase System Residential Buildings
i.e. Single phase 240 (Ph-Ph)/120V (to GRND) Grounded midpoint
For example:120V are used on the wall receptacle and 240V for ovens, ranges, air conditioning and laundry dryers
Three Phase/Three Wire System Industrial and Commercial Buildings
Three Phase/Four Wire System Industrial and Commercial Buildings
* Y describes the solidly grounded circuit.The value “Y” indicates the voltage between phases. The value behind the slash indicates the voltage between phase and the grounding or neutral conductor.
Single phase 120V, 240/277V
L1
NG
Grounded Wye 208Y/120V, 480Y/277V, 600Y/347V
L1L2
N
L3G
Split phase 240/120V, 480/240V
L1
L2
N
G
High-Leg Delta 240/120V HLD
L1L2
N
L3G
Single Phase 2 Wires120/240/277V
Grounded Wye208Y/120V, 480Y/277V, 600Y/347V
Delta 240/480/600V
Split Phase 3 Wires240/120V, 480/240V
High-Leg Delta240/120V HLD
Delta 240/480/600V
L1
L2
L3G
5-47SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—DIN-rail SPDs for distribution panelsSingle-phase
Product features• UL recognized, Type 4 component for Type 2 device• Pluggable modules, fingersafe design - IP20 package• Remote indicator with 3 pin COM/NO/NC contacts• Built-in visual status indicator• Easy installation or retrofit device
Network typeNominal voltage
No. of wires
Max discharge current (Imax, 8/20 μs, kA)
Wiringconfig-uration
Nominal discharge current (In, kA)
MCOVL-L
MCOVL-G
MCOVL-N
VPR
Part number
L-N L-G N-G L-L
120V
2 Wire/1 Pole
25kA
Single phase
20
- -
180 600
- - -
TD120S1025RMP
50kA 20 180 600 TD120S1050RMP
240V25kA 20 275 900 TD240S1025RMP
50kA 20 275 900 TD240S1050RMP
277V25kA 20 320 1000 TD277S1025RMP
50kA 20 320 1000 TD277S1050RMP
347V25kA 10 420 1500 TD347S1025RMP
50kA 10 420 1500 TD347S1050RMP
Electrical characteristics
Modes of protection L-N
Fault rating (SCCR) 200kAIC
Standard monitoring Built-in visual status indicator and dry contacts
Mechanical characteristics
Installation location Type 2, indoor
Mounting method DIN rail
Operating temperature -13° F to 140° F (-25° C to +60° C)
Wire range (stranded/solid) #14 AWG to #6 AWG
Product design Thermally protected MOV technology
Regulations & certifications
UL 1449 4th edition VZCA2:E320456
ANSI/IEEE C62.41 Yes
RoHS compliant Yes
Listed by Type 4 UL recognized component (tested to SPD Type 2)
L
NG
5-48 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—DIN-rail SPDs for distribution panelsSplit-phase
Product features• UL recognized, Type 4 component for Type 2 device• Pluggable modules, fingersafe design - IP20 package• Remote indicator with 3 pin COM/NO/NC contacts• Built-in visual status indicator• Easy installation or retrofit device
Network typeNominal voltage
No. of wires
Max discharge current (Imax, 8/20 μs, kA)
Wiringconfig-uration
Nominal discharge current (In, kA)
MCOVL-L
MCOVL-G
MCOVL-N
VPR
Part number
L-N L-G N-G L-L
208/120V, 240/120V
3 Wire/2 Pole
25kA
Split phase
20
360
-
180 600
- -
1200 TD120S2025RMP
50kA 360 180 600 1200 TD120S2050RMP
480/240V
25kA 550 275 900 1800 TD240S2025RMP
50kA 550 275 900 1800 TD240S2050RMP
Electrical characteristics
Modes of protection L-L and L-N
Fault rating (SCCR) 200kAIC
Standard monitoring Built-in visual status indicator and dry contacts
Mechanical characteristics
Installation location Type 2, indoor
Mounting method DIN rail
Operating temperature -13° F to 140° F (-25° C to +60° C)
Wire range (stranded/solid) #14 AWG to #6 AWG
Product design Thermally protected MOV technology
Regulations & certifications
UL 1449 4th edition VZCA2:E320456
ANSI/IEEE C62.41 Yes
RoHS compliant Yes
Listed by Type 4 UL recognized component (tested to SPD Type 2)
L1
L2
N
G
5-49SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—DIN-rail SPDs for distribution panels3-phase wye
Product features• UL recognized, Type 4 component for Type 2 device• Pluggable modules, fingersafe design - IP20 package• Remote indicator with 3 pin COM/NO/NC contacts• Built-in visual status indicator• Easy installation or retrofit device
Network typeNominal voltage
No. of wires
Max discharge current (Imax, 8/20 μs, kA)
Wiringconfig-uration
Nominal discharge current (In, kA)
MCOVL-L
MCOVL-G
MCOVL-N
VPR
Part number
L-N L-G N-G L-L
208/120V
4 Wire/3 Pole
25kA
3-phase wye,common N/G
20 360
-
180 600
- -
1200 TD120Y3025RMP
50kA 20 360 180 600 1200 TD120Y3050RMP
480/277V
25kA 20 640 320 1000 1800 TD277Y3025RMP
50kA 20 640 320 1000 1800 TD277Y3050RMP
600/347V
25kA 10 840 420 1500 2500 TD347Y3025RMP
50kA 10 840 420 1500 2500 TD347Y3050RMP
Electrical characteristics
Modes of protection L-L and L-N
Fault rating (SCCR) 200kAIC
Standard monitoring Built-in visual status indicator and dry contacts
Mechanical characteristics
Installation location Type 2, indoor
Mounting method DIN rail
Operating temperature -13° F to 140° F (-25° C to +60° C)
Wire range (stranded/solid) #14 AWG to #6 AWG
Product design Thermally protected MOV technology
Regulations & certifications
UL 1449 4th edition VZCA2:E320456
ANSI/IEEE C62.41 Yes
RoHS compliant Yes
Listed by Type 4 UL recognized component (tested to SPD Type 2)
L1L2
N
L3G
5-50 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—DIN-rail SPDs for distribution panels3-phase delta system
Product features• UL recognized, Type 4 component for Type 2 device• Pluggable modules, fingersafe design - IP20 package• Remote indicator with 3 pin COM/NO/NC contacts• Built-in visual status indicator• Easy installation or retrofit device
Network typeNominal voltage
No. of wires
Max discharge current (Imax, 8/20 μs, kA)
Wiringconfig-uration
Nominal discharge current (In, kA)
MCOVL-L
MCOVL-G
MCOVL-N
VPR
Part number
L-N L-G N-G L-L
240V
4 Wire/3 Pole
25kA
3-phase delta
20 550 275
- -
900
-
1800 TD240D3025RMP
50kA 20 550 275 900 1800 TD240D3050RMP
480V
25kA 10 1100 550 1800 3000 TD480D3025RMP
50kA 10 1100 550 1800 3000 TD480D3050RMP
Electrical characteristics
Modes of protection L-L and L-G
Fault rating (SCCR) 200kAIC
Standard monitoring Built-in visual status indicator and dry contacts
Mechanical characteristics
Installation location Type 2, indoor
Mounting method DIN rail
Operating temperature -13° F to 140° F (-25° C to +60° C)
Wire range (stranded/solid) #14 AWG to #6 AWG
Product design Thermally protected MOV technology
Regulations & certifications
UL 1449 4th edition VZCA2:E320456
ANSI/IEEE C62.41 Yes
RoHS compliant Yes
Listed by Type 4 UL recognized component (tested to SPD Type 2)
L3L2
L1
G
5-51SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—DIN-rail SPDs for distribution panels3-phase wye + N-G
Product features• UL recognized, Type 4 component for Type 2 device• Pluggable modules, fingersafe design - IP20 package• Remote indicator with 3 pin COM/NO/NC contacts• Built-in visual status indicator• Easy installation or retrofit device
Network typeNominal voltage
No. of wires
Max discharge current (Imax, 8/20 μs, kA)
Wiringconfig-uration
Nominal discharge current (In, kA)
MCOVL-L
MCOVL-G
MCOVL-N
VPR
Part number
L-N L-G N-G L-L
208/120V
5 Wire/4 Pole
25kA
3-phase wye,plus N-G
20 360 360 180 600 1200 600 1200 TD120Y4025RMN
50kA 20 360 360 180 600 1200 600 1200 TD120Y4050RMN
480/277V
25kA 20 640 500 320 1000 1500 600 1800 TD277Y4025RMN
50kA 20 640 500 320 1000 1500 600 1800 TD277Y4050RMN
600/347V
25kA 10 840 695 420 1500 2000 900 2500 TD347Y4025RMN
50kA 10 840 695 420 1500 2000 900 2500 TD347Y4050RMN
Electrical characteristics
Modes of protection L-L, L-G, N-G and L-N
Fault rating (SCCR) 200kAIC
Standard monitoring Built-in visual status indicator and dry contacts
Mechanical characteristics
Installation location Type 2, indoor
Mounting method DIN rail
Operating temperature -13° F to 140° F (-25° C to +60° C)
Wire range (stranded/solid) #14 AWG to #6 AWG
Product design Thermally protected MOV technology
Regulations & certifications
UL 1449 4th edition VZCA2:E320456
ANSI/IEEE C62.41 Yes
RoHS compliant Yes
Listed by Type 4 UL recognized component (tested to SPD Type 2)
L1L2
N
L3G
5-52 SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—DIN-rail SPDs for distribution panelsHLD system
Product features• UL recognized, Type 4 component for Type 2 device• Pluggable modules, fingersafe design - IP20 package• Remote indicator with 3 pin COM/NO/NC contacts• Built-in visual status indicator• Easy installation or retrofit device
Network type
Nominal voltage
No. of wires
Max discharge current (Imax, 8/20 μs, kA)
Wiringconfig-uration
Nominal discharge current (In, kA)
MCOV VPR
Part number
L-L L-G L-N L-N L-G N-G L-L H-L1 H-N H-G
240/120V
5 Wire/4 Pole
25kA
3-phase high-leg delta
20
***
600 1200 600 1200 1500 900 1500 TD240H4025RM
50kA 600 1200 600 1200 1500 900 1500 TD240H4050RM
480/240V
25kA
10
900 1500 600 1800 2500 1800 2000 TD480H4025RM
50kA 900 1500 600 1800 2500 1800 2000 TD480H4050RM
Electrical characteristics
Modes of protection L-L, L-N and L-G
Fault rating (SCCR) 200kAIC
Standard monitoring Built-in visual status indicator and dry contacts
Mechanical characteristics
Installation location Type 2, indoor
Mounting method DIN rail
Operating temperature -13° F to 140° F (-25° C to +60° C)
Wire range (stranded/solid) #14 AWG to #6 AWG
Product design Thermally protected MOV technology
Regulations & certifications
UL 1449 4th edition VZCA2:E320456
ANSI/IEEE C62.41 Yes
RoHS compliant Yes
Listed by Type 4 UL recognized component (tested to SPD Type 2)
L2L1
N
L3
5-53SURGE PROTECTION DEVICES, BUYLOG SECTION 5
—Protection block assembly
IntroductionThe ABB 427 patented 5 Pin Protection Block Assembly is equipped with a multi-layered printed circuit board, providing a connectorized interface for cable assemblies. It accommodates 25, 50 or 100 pair cable. It is used in many applications, including: central offices, remote switching sites, customer premises and building entrances, to protect telephone and voice/data lines.
When wiring cabinets with conventional wire wrap blocks each block becomes a different part number and causes difficulty for OEMs who have to inventory parts.
The same ABB 427 Protection Block Assembly is used in every position of a cabinet or mainframe. The cables are now treated as less expensive parts and are stocked by length and mating connector type. Manual labor, in running cables and making wire wrap connections, is reduced significantly by employing ABB Connectorized Block Assemblies.
Performance Features - Gold pins and sockets ensure proper electrical
connections - Self-locking aluminum hood (optional) provides
protection to connectors and printed circuit board and serves as the cable strain relief tie point
- Multi-layered printed circuit board - Handle heavy transient current surges - U.S. Patent No. 5,457,593
Benefits - Provides maximum reliability by eliminating all wire wraps - Provides the high quality installation of a protection block - Provides additional flexibility for equipment installations - Easily serviceable in the field - Eliminates the need for wire wrapping - Allows connectorization into many different applications
and greatly reduces installation, labor and repair costs - All cables connected to this unit can be removed,
permitting specific cable change out or change out of the entire protection block assembly. This allows the protected equipment to quickly be put back into service.
- Covered by a two year limited product warranty
Protection Block Assembly
Protection Block Assembly - Surge Protection Device
Pair Block Type HoodProduct Number
50 Marconi Block YES 427-050-202
100 Avaya Block YES 427-100-102
100 Marconi Block YES 427-100-202
100 Corning Block YES 427-100-302
SpecificationsVoltage Class: 600V
BIL rating: 10kV
Primary Currents: 10 to 5000 amps