Page 1: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

— BUYLOG SEC TION 5

Surge Protection Devices

Page 2: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-2 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

Page 3: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-3SURGE PROTECTION DEVICES, BUYLOG SECTION 5

— Table of contents

Surge protection devices5-4 Introduction

ABB integrated surge protection devices5-5 To connect with ReliaGear® panelboards5-7 For ReliaGear distribution equipment5-11 9X box extensions for ReliaGear distribution equipment5-13 24X box extensions for ReliaGear distribution

equipment5-15 9X and 24X dimensions5-16 ME series wallmount SPD5-18 HE series wallmount SPD5-20 ME series wallmount SPD with enhanced thermal

protection5-22 HE series wallmount SPD with enhanced thermal

protection5-24 ME and HE series dimensions5-25 LE series wallmount SPD5-27 ME series wallmount SPD

OVRH series5-29 Product range overview5-30 OVRHSP (4,000A and below, 60 to 100kA)5-31 OVRHSP (4,000A and below, 120 to 160kA)5-32 OVRHSP (4,000A and below, 200 to 400kA)5-33 OVRHSR (wall recessed – 4,000A and below, 120 to

160kA)5-34 OVRHTE (1,000A and below, 25 to 100kA)5-35 OVRHT3B (400A and below, 50kA)5-36 OVRHT3C (400A and below, 50kA)5-37 OVRHS3U (400A and below, 40kA)5-38 OVRHLD (100A and below, 20 to 30KA)5-39 Dimensions

DIN-rail SPDs for distribution panels - UL 1449 4th edition

5-43 Overview5-44 Terminology of SPD electrical characteristics5-45 Standards5-47 Single-phase5-48 Split-phase5-49 3-phase wye5-50 3-phase delta system5-51 3-phase wye + N-G5-52 HLD system

5-53 Protection block assembly

Page 4: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-4 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—Surge protection devicesIntroduction

Surge Protection Devices (SPDs) are designed to protect against transient surge conditions.

Transient surges can reach values of hundreds of thousands of volts or instantaneous current flow of tens of thousands of amperes, but typically last less than one hundred microseconds in duration.

Transient surges generated within a facility typically account for 80% of the surge activity.

These internally generated transients can be caused by switching power supplies (computers), electronic ballasts (building lighting) and variable frequency drives (air handlers, elevators, etc).

The most destructive transient voltage surges can be attributed to lightning and utility load switching; however, experts predict that these two events account for 20% of all transient surge activity.

Reliable data sources suggest that lightning strikes have current magnitudes in excess of 200,000 amps. Moreover,

lightning strikes are not single strike events. Strikes typically consist of four to six “hits” and sometimes can be as high as 40kA.

Therefore, SPDs must be appropriately sized to provide adequate protection during multiple surge events.

Large transient surge conditions can damage printed circuit board traces and puncture semiconductors causing immediate or intermittent equipment failures. Continued exposure to surges can degrade printed circuit board traces or semiconductors resulting in seemingly random delayed equipment failures. Therefore, equipment failures cannot always be contributed to a single power quality event. Surge remnants on data lines can alter digital data and logic levels causing equipment failures and lockups.

Professionally installed ABB products provide superior protection against transient surges preventing unnecessary downtime and costly repairs.

Cost reduction on repairs

Installed ABBSPD

Increased protection

Reduction on downtime

Page 5: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-5SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB integrated surge protection deviceDesigned to connect within ReliaGear® panelboards

Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPME120Sxx*

208Y/120 3-phase, 4-wire + ground TPME120Yxx*

240 Delta 3-phase, 3-wire + ground TPME240Dxx*

240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPME240Hxx*

415Y/240 3-phase, 4-wire + ground TPME240Yxx*

480Y/277 3-phase, 4-wire + ground TPME277Yxx*

380Y/220 3-phase, 4-wire + ground TPME220Yxx*

600Y/347 3-phase, 4-wire + ground TPME347Yxx*

480 Delta 3-phase, 3-wire + ground TPME480Dxx*

Desired kA xx Code65 06

80 08

100 10

Options (*) Suffix (*)With UL 1283 noise filter and surge counter1 AS

Without UL 1283 noise filtering only (Available in 100 kA per mode only) ASNF

Without UL 1283 noise filter and surge counter (Available in 100kA per mode only) ASNC

1Standard option

Nominal Voltage (Volts RMS)

System Voltage Configuration

Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision

MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L

120S 120/240 1 Ph, 3 W + G 700 - 600 - 600 1200 125%

120Y 120Y/208 3 Ph, 4 W + G 700 - 600 - 600 1200 125%

240D 240 Delta 3 Ph, 3 W - - 900 - - 1800 115%

240H120/240 Delta HL

3 Ph, 4 W + G 700 1200 600 1000 600 1200 115%

240Y 240Y/415 3 Ph, 4 W + G 1200 - 1000 - 1000 2000 130%

277Y 277Y/480 3 Ph, 4 W + G 1200 - 1000 - 1000 2000 115%

220Y 220Y/380 3 Ph, 4 W + G 1200 - 1000 - 1000 2000 145%

347Y 347Y/600 3 Ph, 4 W + G 1500 - 1500 - 1500 3000 115%

480D 480 Delta 3 Ph, 3 W - - 1500 - - 3000 170%

Also available in 600D configurations. For details, please contact ABB Power Quality Customer Service at 800 637 1738.

T P M EProduct #

Maximum Surge Current CapacityPer Mode Per Phase

06 65kA 130kA

08 80kA 160kA

10 100kA 200kA

Phase Rating = (L-N + L-G)

Product # ExampleTPME277Y10AS277Y/480 V, 3 Ph, 4 W + G

100kA per mode

Full featured, with UL 1283 noise filtering and surge counter

Page 6: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-6 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB integrated surge protection deviceDesigned to connect within ReliaGear® panelboards

1.331 [33.81]

5.331 [135.41]

0.312 [7.91] TYP

0.236 [ 5.99] HOLE(4 PLACES)

5.064 [128.62]

9.494 [241.15]

8.321 [211.36]6.000 [152.40]

9.400 [238.76]

2.869 [72.87]

FeaturesUL Listed 1449 4th Edition, Type 1, Type 2

cUL, CSA C22.2

This model connects directly to the ReliaGear Panelboard bus bars

Factory installed in ABB ReliaGear Panels

Standard features include a surge counter, audible alarm, indicating lights, dry contacts and NEMA 4 painted steel enclosure

10 year limited warranty

Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode

Nominal discharge current rating (l-n) 20 kA

Operating frequency 50-60Hz

Surge life (IEEE C62.41 - C3 10kA) ≥5000 impulses

Connection method 6 to 2/0 Conductors, Parallel Connected

Modes of protection All Modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR) 200 kAIC

Standard monitoring

Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter

EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ

Mechanical characteristicsWeight 13 lbs. ( kg)

Enclosure type Painted steel, NEMA 12

Installation locationService Entrance Equipment, Primary Distribution Equipment, Secondary Distribution Equipment, Lighting Panels - Rated for UL and NEC 2008 Type 1 and Type 2

Mounting method Bolt-on to electrical panel interior frame

Operating temperature -40° F to 149° F (-40° C to +65° C)

Altitude 0 - 12,000 ft (3.66 km)

Product design Individually fused Thermally Protected MOV Technology

Regulations and certificationsUL 1449 4th edition VZCA2:E320456 Type 1/Type 2

cUL, CSA C22.2 VZCA8:E320456 Type 1/Type 2

UL 1283 FOKY2:E320456 Type 2

UL 96A Yes

IEEE C62.62, C62.72, C62.41 Yes

Listed By UL

Page 7: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-7SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB integrated surge protection deviceDesigned for ReliaGear distribution equipment

T P M EProduct #

Nominal Voltage (Volts RMS)

System Voltage Configuration

Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision

MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L

120S 120/240 1 Ph, 3 W + G 900 - 800 - 700 1200 125%

120Y 120Y/208 3 Ph, 4 W + G 900 - 800 - 700 1200 125%

220Y 220Y/380 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 145%

240D 240 Delta 3 Ph, 3 W + G - - 1200 - - 1800 196%

240H120/240 Delta HL

3 Ph, 4 W + G 1000 1200 800 1200 700 2000 115%

240Y 240Y/415 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 130%

277Y 277Y/480 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 115%

347Y 347Y/600 3 Ph, 4 W + G 1500 - 1500 - 1500 2500 115%

480D 480 Delta 3 Ph, 3 W + G - - 1800 - - 3000 198%

Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.

Maximum Surge Current CapacityExposure Level

Per Mode Per Phase

06 TPME 65kA 130kA

08 TPME 80kA 160kA

10 TPME 100kA 200kA

NOTE: For SPD field installation kit, add the prefix "A" and replace "PP" suffix with "K" suffix

Product # ExampleTPME277Y15PP (factory installed)

ATME277Y15K (field installation)

Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPME120Sxx*

208Y/120 3-phase, 4-wire + ground TPME120Yxx*

380Y/220 3-phase, 4-wire + ground TPME220Yxx*

240 Delta 3-phase, 3-wire + ground TPME240Dxx*

240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPME240Hxx*

415Y/240 3-phase, 4-wire + ground TPME240Yxx*

480Y/277 3-phase, 4-wire + ground TPME277Yxx*

600Y/347 3-phase, 4-wire + ground TPME347Yxx*

480 Delta 3-phase, 3-wire + ground TPME480Dxx*

Desired kA xx Code65 06

80 08

100 10

Options Mounting UL Type Suffix (*)ABB Spectra Power Panel Integral Type 2 PP

ABB Motor Control Centers Integral Type 2 ME

ABB Switchgear Integral Type 2 SG

ABB Spectra Power Panel Integral Type 1 PPT1

ABB Motor Control Centers Integral Type 1 MET1

ABB Switchgear Integral Type 1 SGT1

* PP suffix available for all kA ratings (integral to Spectra™ panel or switchboard SG suffix for all THE devices (100kA - 300kA) integral to switchgear ME suffix available for all kA ratings (integral to MCC)

Page 8: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-8 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB integrated surge protection deviceDesigned for ReliaGear distribution equipment

FeaturesUL Listed 1449 4th Edition, Type 1, Type 2

cUL, CSA C22.2

These SPD models connect to the panelboard or switchboard bus bars

Thermally protected MOV design eliminates the need for additional upstream over current protection

Standard features include a surge counter, audible alarm, indicating lights, dry contacts and NEMA 4 painted steel enclosure

10 year limited warranty

Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode

Nominal discharge current rating (l-n) 20 kA

Operating frequency 50-60Hz

Surge life (IEEE C62.41 - C3 10kA) ≥5000 impulses

Connection method 6 to 2/0 Conductors, Parallel Connected

Modes of protection All Modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR) 200 kAIC

Standard monitoring

Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter

EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ

Mechanical characteristicsWeight 24 lbs. (10.89 kg)

Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2008 Type 1 and Type 2

Mounting method Bolt-on to electrical panel interior frame

Operating temperature -40° F to 149° F (-40° C to +65° C)

Altitude 0 - 12,000 ft (3.66 km)

Product design Individually fused Thermally Protected MOV Technology

Regulations and certificationsUL 1449 4th edition VZCA2:E320456 Type 1/Type 2

cUL, CSA C22.2 VZCA8:E320456 Type 1/Type 2

UL 1283 FOKY2:E320456 Type 2

UL 96A Yes

IEEE C62.62, C62.72, C62.41 Yes

Listed By UL

0.340 [8.636]

17.382 [441.494]

2.638 [67.004] TYP

6.762 [171.751] TYP

0.280 [ 7.112] HOLE

(4 PLACES)

7.2

02

[182.9

22]

17.722 [450.130]

9.400 [238.755]

6.964 [176.877]

Page 9: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-9SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB integrated surge protection deviceDesigned for ReliaGear distribution equipment

T P H EProduct #

Nominal Voltage (Volts RMS)

System Voltage Configuration

Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision

MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L

120S 120/240 1 Ph, 3 W + G 900 - 800 - 700 1200 125%

120Y 120Y/208 3 Ph, 4 W + G 900 - 800 - 700 1200 125%

220Y 220Y/380 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 145%

240D 240 Delta 3 Ph, 3 W + G - - 1200 - - 1800 196%

240H120/240 Delta HL

3 Ph, 4 W + G 1000 1200 800 1200 700 2000 115%

240Y 240Y/415 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 130%

277Y 277Y/480 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 115%

347Y 347Y/600 3 Ph, 4 W + G 1500 - 1500 - 1500 2500 115%

480D 480 Delta 3 Ph, 3 W + G - - 1800 - - 3000 198%

Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.

Maximum Surge Current CapacityExposure Level

Per Mode Per Phase

12 TPHE 125kA 250kA

15 TPHE 150kA 300kA

20 TPHE 200kA 400kA

25 TPHE 250kA 500kA

30 TPHE 200kA 400kA

NOTE: For SPD field installation kit, add the prefix "A" and replace "PP" suffix with "K" suffix

Product # ExampleTPHE277Y15PP (factory installed)

ATHE277Y15K (field installation)

Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPHE120Sxx*

208Y/120 3-phase, 4-wire + ground TPHE120Yxx*

380Y/220 3-phase, 4-wire + ground TPHE220Yxx*

240 Delta 3-phase, 3-wire + ground TPHE240Dxx*

240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPHE240Hxx*

415Y/240 3-phase, 4-wire + ground TPHE240Yxx*

480Y/277 3-phase, 4-wire + ground TPHE277Yxx*

600Y/347 3-phase, 4-wire + ground TPHE347Yxx*

480 Delta 3-phase, 3-wire + ground TPHE480Dxx*

Desired kA xx Code125 12

150 15

200 20

250 25

300 30

Options Mounting UL Type Suffix (*)ABB Spectra Power Panel Integral Type 2 PP

ABB Motor Control Centers Integral Type 2 ME

ABB Switchgear Integral Type 2 SG

ABB Spectra Power Panel Integral Type 1 PPT1

ABB Motor Control Centers Integral Type 1 MET1

ABB Switchgear Integral Type 1 SGT1

* PP suffix available for all kA ratings (integral to Spectra™ panel or switchboard SG suffix for all THE devices (100kA - 300kA) integral to switchgear ME suffix available for all kA ratings (integral to MCC)

*

Page 10: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-10 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB integrated surge protection deviceDesigned for ReliaGear distribution equipment

FeaturesUL Listed 1449 4th Edition, Type 2

cUL, CSA C22.2

These SPD models connect to the panelboard or switchboard bus bars

Thermally protected MOV design eliminates the need for additional upstream over current protection

Standard features include a surge counter, audible alarm, indicating lights, dry contacts and integral surge rated disconnect

10 year limited warranty

Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode

Nominal discharge current rating (l-n) 20 kA

Operating frequency 50-60Hz

Surge life (IEEE C62.41 - C3 10kA) ≥20000 impulses

Connection method 6 to 2/0 Conductors, Parallel Connected

Modes of protection All Modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR) 200 kAIC

Standard monitoring

Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter

EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ

Mechanical characteristicsWeight 24 lbs. (10.89 kg)

Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2020 Type 1 and Type 2

Mounting method Bolt-on to electrical panel interior frame

Operating temperature -40° F to 149° F (-40° C to +65° C)

Altitude 0 - 12,000 ft (3.66 km)

Product design Individually fused Thermally Protected MOV Technology

Regulations and certificationsUL 1449 4th edition VZCA2:E320456 Type 1/Type 2

UL 1283 VZCA8:E320456 Type 1/Type 2

cUL, CSA C22.2 FOKY2:E320456 Type 2

UL 96A Yes

IEEE C62.62, C62.72, C62.41 Yes

Listed By UL

Page 11: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-11SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB 9X box extensionsDesigned for ReliaGear distribution equipment

Voltage Protection Rating (VPR) UL 1449 4th Edition - September 2014 RevisionB x 9 B x 24L-N HL-N L-G HL-G N-G L-L L-N HL-N L-G HL-G N-G L-L

120S 1500 - 1500 - 900 1800 1500 - 1500 - 1000 1800

120Y 1500 - 1500 - 900 1800 1500 - 1500 - 1000 1800

220Y 1800 - 2000 - 1500 2500 1800 - 1800 - 1500 2500

240D - - 1800 - - 2500 - - 1800 - - 2500

240H 1500 1800 1500 2000 900 1800 1500 1800 1500 1800 1000 1800

240Y 1800 - 2000 - 1500 2500 1800 - 1800 - 1500 2500

277Y 1800 - 2000 - 1500 2500 1800 - 1800 - 1500 2500

347Y 2000 - 2000 - 1800 3000 3000 - 2500 - 1800 3000

480D - - 2500 - - 4000 - - 2500 - - 4000

T P M EProduct # B X *

Nominal Voltage (Volts RMS)

System Voltage Configuration

MCOV% Max. Continuous Operating Voltage

120S 120/240 1 Ph, 3 W + G 125%

120Y 120Y/208 3 Ph, 4 W + G 125%

220Y 220Y/380 3 Ph, 4 W + G 145%

240D 240 Delta 3 Ph, 3 W + G 115%

240H120/240 Delta HL

3 Ph, 4 W + G 115%

240Y 240Y/415 3 Ph, 4 W + G 130%

277Y 277Y/480 3 Ph, 4 W + G 115%

347Y 347Y/600 3 Ph, 4 W + G 115%

480D 480 Delta 3 Ph, 3 W + G 170%

Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.

Maximum Surge Current CapacityExposure Level

Per Mode Per Phase

06 ME 65kA 130kA

08 ME 80kA 160kA

10 ME 100kA 200kA

12 HE 125kA 250kA

15 HE 150kA 300kA

20 HE 200kA 400kA

25 HE 250kA 500kA

30 HE 300kA 600kA

Phase Rating = (L-N + L-G)

Product # ExampleTPME277Y15BX24WF277Y/480 V, 3 Ph, 4 W + G

150kA per mode

Flush mounted, display access

Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPME120SxxBX*

208Y/120 3-phase, 4-wire + ground TPME120YxxBX*

380Y/220 3-phase, 4-wire + ground TPME220YxxBX*

240 Delta 3-phase, 3-wire + ground TPME240DxxBX*

240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPME240HxxBX*

415Y/240 3-phase, 4-wire + ground TPME240YxxBX*

480Y/277 3-phase, 4-wire + ground TPME277YxxBX*

600Y/347 3-phase, 4-wire + ground TPME347YxxBX*

480 Delta 3-phase, 3-wire + ground TPME480DxxBX*

Desired kA xx Code65 06

80 08

100 10

Options Suffix (*)Surface mounted, no display 9S

Surface mounted, display access 9WS

Flush mounted, no display 9F

Flush mounted, display access 9WF

Page 12: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-12 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

FeaturesUL Listed 1449 4th Edition, Type 2

cUL, CSA C22.2

The ReliaGear Box Extension SPD is field installed and attaches neatly to a standard panel at the top or bottom

The true maximum surge current rating, unlimited by fusing, has been proven successful in 3rd party tests

Standard features include a surge counter, audible alarm, indicating lights, dry contacts

10 year limited warranty

Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode

Nominal discharge current rating (l-n) 20 kA

Operating frequency 50-60Hz

Connection method6 to 2/0 Conductors, Parallel Connected *ABB recommends the use of a dedicated circuit breaker, rated 60A or above, to provide a local disconnecting means for the SPD.

Modes of protection All Modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR) 65 kAIC

Standard monitoring

Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter

EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ

Mechanical characteristicsWeight 31 lbs. (14.1 kg)

Enclosure type

Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2020 Type 1 and Type 2

Mounting method

Operating temperature -40° F to 149° F (-40° C to +65° C)

Altitude 0 - 12,000 ft (3.66 km)

Product design Individually fused Thermally Protected MOV Technology

Regulations and certificationsUL 1449 4th edition XUPD.E248748 Type 2

UL 1283 Yes

UL 96A Yes

cUL, CSA C22.2 VZCA7:E320456 Type 2

IEEE C62.62, C62.72 Yes

Listed By UL

—ABB 9X box extensionsDesigned for ReliaGear distribution equipment

Page 13: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-13SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB 24X box extensionsDesigned for ReliaGear distribution equipment

Voltage Protection Rating (VPR) UL 1449 4th Edition - September 2014 RevisionB x 9 B x 24L-N HL-N L-G HL-G N-G L-L L-N HL-N L-G HL-G N-G L-L

120S 1500 - 1500 - 900 1800 1500 - 1500 - 1000 1800

120Y 1500 - 1500 - 900 1800 1500 - 1500 - 1000 1800

220Y 1800 - 2000 - 1500 2500 1800 - 1800 - 1500 2500

240D - - 1800 - - 2500 - - 1800 - - 2500

240H 1500 1800 1500 2000 900 1800 1500 1800 1500 1800 1000 1800

240Y 1800 - 2000 - 1500 2500 1800 - 1800 - 1500 2500

277Y 1800 - 2000 - 1500 2500 1800 - 1800 - 1500 2500

347Y 2000 - 2000 - 1800 3000 3000 - 2500 - 1800 3000

480D - - 2500 - - 4000 - - 2500 - - 4000

T P H E B XProduct # *

Nominal Voltage (Volts RMS)

System Voltage Configuration

MCOV% Max. Continuous Operating Voltage

120S 120/240 1 Ph, 3 W + G 125%

120Y 120Y/208 3 Ph, 4 W + G 125%

220Y 220Y/380 3 Ph, 4 W + G 145%

240D 240 Delta 3 Ph, 3 W + G 115%

240H120/240 Delta HL

3 Ph, 4 W + G 115%

240Y 240Y/415 3 Ph, 4 W + G 130%

277Y 277Y/480 3 Ph, 4 W + G 115%

347Y 347Y/600 3 Ph, 4 W + G 115%

480D 480 Delta 3 Ph, 3 W + G 170%

Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.

Maximum Surge Current CapacityExposure Level

Per Mode Per Phase

06 ME 65kA 130kA

08 ME 80kA 160kA

10 ME 100kA 200kA

12 HE 125kA 250kA

15 HE 150kA 300kA

20 HE 200kA 400kA

25 HE 250kA 500kA

30 HE 300kA 600kA

Phase Rating = (L-N + L-G)

Product # ExampleTPHE277Y15BX24WF277Y/480 V, 3 Ph, 4 W + G

150kA per mode

Flush mounted, display access

Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPHE120SxxBX*

208Y/120 3-phase, 4-wire + ground TPHE120YxxBX*

380Y/220 3-phase, 4-wire + ground TPHE220YxxBX*

240 Delta 3-phase, 3-wire + ground TPHE240DxxBX*

240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPHE240HxxBX*

415Y/240 3-phase, 4-wire + ground TPHE240YxxBX*

480Y/277 3-phase, 4-wire + ground TPHE277YxxBX*

600Y/347 3-phase, 4-wire + ground TPHE347YxxBX

480 Delta 3-phase, 3-wire + ground TPHE480DxxBX

Desired kA xx Code125 12

150 15

200 20

250 25

300 30

Options Suffix (*)Surface mounted, display access 24WS

Flush mounted, display access 24WF

Page 14: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-14 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

FeaturesUL Listed 1449 4th Edition for Type 2 applications

cUL, CSA C22.2

This model is installed in an extended box and connects to the "A-Series™" Panelboard

The true maximum surge current rating, unlimited by fusing, has been proven successful in 3rd party tests

Standard features include a surge counter, audible alarm, indicating lights, dry contacts

10 year limited warranty

Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode

Nominal discharge current rating (l-n) 20 kA

Operating frequency 50-60Hz

Connection method6 to 2/0 Conductors, Parallel Connected *ABB recommends the use of a dedicated circuit breaker, rated 60A or above, to provide a local disconnecting means for the SPD.

Modes of protection All Modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR) 200 kAIC

Standard monitoring

Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter

EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ

Mechanical characteristicsWeight 57 lbs. (25.9 kg)

Enclosure type

Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2020 Type 1 and Type 2

Mounting method

Operating temperature -40° F to 149° F (-40° C to +65° C)

Altitude 0 - 12,000 ft (3.66 km)

Product design Individually fused Thermally Protected MOV Technology

Regulations and certificationsUL 1449 4th edition XUPD.E248748 Type 2

UL 1283 Yes

UL 96A Yes

cUL, CSA C22.2 VZCA7:E320456 Type 2

IEEE C62.62, C62.72 Yes

Listed By UL

—ABB 24X box extensionsDesigned for ReliaGear distribution equipment

Page 15: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-15SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB 9X and 24X box extensionsDesigned for ReliaGear distribution equipment

21.500 [546.10]

10.440 [265.18]

9.000 [228.60]

7.375 [187.34]

10.000 [254.00]

12.625 [320.69]

15.400 [391.16]

1.719 [43.67]

0.344 [8.74]

6.023 [152.98]

0.588 [14.94]

9.000 [228.6]

9.810 [249.174]

20.250 [514.35]

7.375 [187.338]

10.000 [254]

12.6255 [320.69]

15.400 [391.16]

1.719 [43.675]

0.344 [8.738]

6.023 [152.984]

0.042 [1.067]

10.440 [265.176]

9.000 [228.600]

21.500 [546.100]

1.617 [41.072]

6.412 [162.865]

7.239 [183.871]

14.254 [362.052]

7.375 [187.338]

10.000 [254.000]

12.625 [320.688]

15.400 [391.160]

6.023 [152.984]

0.588 [14.935]

2.389 [60.693]

0.344 [8.738]

20.250 [514.350]

9.810 [249.174]

9.000 [228.600]

2.247 [57.074]

7.042 [178.867]

6.609 [167.869]

13.624 [346.050]

6.023 [152.984]

2.389 [60.693]

7.375 [187.338]

10.000 [254.000]

12.625 [320.688]

15.400 [391.160]

[8.738] 0.344

6.333 [160.86]

20.280 [515.11]

21.500 [546.10]

24.743 [628.47]

25.440 [646.18]

24.000 [609.60]

12.560 [319.02]

5.390 [136.91]

6.899 [175.23]

7.624 [193.65]

6.810 [172.97]

7.085 [179.95]

3.176 [80.67]

0.711 [18.06]

6.074 [154.28]

8.030 [203.96] 8.635

[219.33]

1.400 [35.56]

7.246 [184.048]

24.743 [628.472]

7.246 [184.044]

20.280 [515.112]

6.333 [160.858]

24.000 [609.600]

11.940 [303.276]

5.390 [136.906]

6.274 [159.360]

7.624 [193.650]

6.810 [172.969]

7.085 [179.954]

8.635 [219.329]

11.635 [295.529]

8.030 [203.962]

1.400 [35.560]

3.176 [80.672]

0.711 [18.059]

6.074 [154.280]

BX9F Dimensions

BX9WF Dimensions

BX24WF Dimensions

BX9S Dimensions

BX9WS Dimensions

BX24WS Dimensions

Page 16: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-16 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB ME seriesWallmount SPD

Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TME120SxxxWMN

208Y/120 3-phase, 4-wire + ground TME120YxxxWMN

380Y/220 3-phase, 4-wire + ground TME220YxxxWMN

240 Delta 3-phase, 3-wire + ground TME240DxxxWMN

240/120 Hi-Leg Delta 3-phase, 4-wire + ground TME240HxxxWMN

415Y/240 3-phase, 4-wire + ground TME240YxxxWMN

480Y/277 3-phase, 4-wire + ground TME277YxxxWMN

600Y/347 3-phase, 4-wire + ground TME347YxxxWMN

480 Delta 3-phase, 3-wire + ground TME480DxxxWMN

Desired kA xxx Code65 065

80 080

100 100

T M E W M NProduct #

Nominal Voltage (Volts RMS)

System Voltage Configuration

Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision

MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L

120S 120/240 1 Ph, 3 W + G 1000 - 1000 - 700 1200 - 125%

120Y 120Y/208 3 Ph, 4 W + G 1000 - 1000 - 700 1200 - 125%

220Y 220Y/380 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 145%

240D 240 Delta 3 Ph, 4 W - - 1500 - - 1800 - 196%

240H120/240 Delta HL

3 Ph, 4 W + G 1000 1500 1000 1500 700 1200 2500 115%

240Y 240Y/415 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 130%

277Y 277Y/480 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 115%

347Y 347Y/600 3 Ph, 4 W + G 1800 - 1500 - 1500 2500 - 115%

480D 480 Delta 3 Ph, 4 W - - 2000 - - 4000 - 198%

Maximum Surge Current CapacityExposure Level

Per Mode Per Phase

065 ME 65kA 130kA

080 ME 80kA 160kA

100 ME 100kA 200kA

Product # ExampleTME277Y150WMN4S

Suffix DescriptionNEMA Enclosure

Mounting Disconnect

4S Painted Steel 4 Surface No

4X Stainless Steel 4X Surface No

Page 17: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-17SURGE PROTECTION DEVICES, BUYLOG SECTION 5

FeaturesUL Listed 1449 4th Edition, Type 2

cUL Listed, CSA C22.2

UL 96A, for use in lightning protection systems

UL Recognized 200kAIC Surge Rated Fuses in combination with patented thermal fuse technology

Standard features include a surge counter, audible alarm, indicating lights, dry contacts and NEMA 4 painted steel enclosure

10 year limited warranty

Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode

Nominal discharge current rating (l-n) 20 kA

Operating frequency 50-60Hz

Surge life (IEEE C62.41 - C3 10kA) ≥5000 impulses

Connection method 6 to 2/0 Conductors, Parallel Connected

Modes of protection All Modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR) 65 kA (30A breaker required)

Standard monitoring

Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter

EMI/RFI filter attenuationMaximum attenuation frequency -44dB @ (50-100kHZ)

Mechanical characteristicsWeight 32 lbs. (14.51 kg)

Enclosure type Painted steel, NEMA 4

Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2020 Type 2 Installation Locations

Mounting method Dual Mounting Flanges / 3/4" NPT Offset Nipple

Operating temperature -40° F to 149° F (-40° C to +65° C)

Altitude 0 - 12,000 ft (3.66 km)

Product design Thermal fuse technology

Regulations and certificationsUL 1449 4th edition VZCA:E320456 Type 2

cUL, CSA C22.2 VZCA7:E320456 Type 2

UL 1283 FOKY:E320456 Type 2

UL 96A Yes

IEEE C62.62, C62.72 Yes

Listed By UL

—ABB ME seriesWallmount SPD

1.852 [47.04]

13.478 [342.34]

14.759 [374.88]

16.000 [406.40]

8.978 [228.04]

15.330 [389.38]

19.330 [490.98]

8.978 [228.04]

15.330 [389.38]6.440

[163.58]

1.471 [37.36]

0.571 [14.50]

15.478 [393.14]

18.759 [476.48]

0.571 [14.50]

0.282 [ 7.16] HOLES

(8 PLACES)

3.852 [97.84]

12.000[304.80]

WMN12F Dimensions

Page 18: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-18 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB HE seriesWallmount SPD

Voltage Configuration Product Number240/120 1-phase, 3-wire + ground THE120SxxxWMN

208Y/120 3-phase, 4-wire + ground THE120YxxxWMN

380Y/220 3-phase, 4-wire + ground THE220YxxxWMN

240 Delta 3-phase, 3-wire + ground THE240DxxxWMN

240/120 Hi-Leg Delta 3-phase, 4-wire + ground THE240HxxxWMN

415Y/240 3-phase, 4-wire + ground THE240YxxxWMN

480Y/277 3-phase, 4-wire + ground THE277YxxxWMN

600Y/347 3-phase, 4-wire + ground THE347YxxxWMN

480 Delta 3-phase, 3-wire + ground THE480DxxxWMN

600 Delta 3-phase, 3-wire + ground THE600DxxxWMN

Desired kA xxx Code125 125

150 150

200 200

300 300

T H E W M NProduct #

Nominal Voltage (Volts RMS)

System Voltage Configuration

Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision

MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L

120S 120/240 1 Ph, 3 W + G 1000 - 1000 - 700 1200 - 125%

120Y 120Y/208 3 Ph, 4 W + G 1000 - 1000 - 700 1200 - 125%

220Y 220Y/380 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 145%

240D 240 Delta 3 Ph, 4 W - - 1500 - - 1800 - 196%

240H120/240 Delta HL

3 Ph, 4 W + G 1000 1500 1000 1500 700 1200 2500 115%

240Y 240Y/415 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 130%

277Y 277Y/480 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 115%

347Y 347Y/600 3 Ph, 4 W + G 1800 - 1500 - 1500 2500 - 115%

480D 480 Delta 3 Ph, 4 W - - 2000 - - 4000 - 198%

Maximum Surge Current CapacityExposure Level

Per Mode Per Phase

125 HE 125kA 250kA

150 HE 150kA 300kA

200 HE 200kA 400kA

250 HE 250kA 500kA

300 HE 300kA 600kA

Product # ExampleTHE277Y150WMN4S

Suffix DescriptionNEMA Enclosure

Mounting Disconnect

4S Painted Steel 4 Surface No

4X Stainless Steel 4X Surface No

Page 19: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-19SURGE PROTECTION DEVICES, BUYLOG SECTION 5

FeaturesUL Listed 1449 4th Edition, Type 2

cUL Listed, CSA C22.2

UL 96A, for use in lightning protection systems

UL Recognized 200kAIC Surge Rated Fuses in combination with patented thermal fuse technology

Standard features include a surge counter, audible alarm, indicating lights, dry contacts and NEMA 4 painted steel enclosure

10 year limited warranty

Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode

Nominal discharge current rating (l-n) 20 kA

Operating frequency 50-60Hz

Surge life (IEEE C62.41 - C3 10kA) ≥20000 impulses

Connection method 6 to 2/0 Conductors, Parallel Connected

Modes of protection All Modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR) 200 kAIC (60A breaker required as a local disconnect means)

Standard monitoring

Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter

EMI/RFI filter attenuationMaximum attenuation frequency -44dB @ (50-100kHZ)

Mechanical characteristicsWeight 50 lbs. (22.68 kg)

Enclosure type Painted steel, NEMA 4

Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2020 Type 2 Installation Locations

Mounting method Dual Mounting Flanges / 3/4" NPT Offset Nipple

Operating temperature -40° F to 149° F (-40° C to +65° C)

Altitude 0 - 12,000 ft (3.66 km)

Product design Thermal fuse technology

Regulations and certificationsUL 1449 4th edition VZCA:E320456 Type 2

cUL, CSA C22.2 VZCA7:E320456 Type 2

UL 1283 Yes

UL 96A Yes

IEEE C62.62, C62.72 Yes

Listed By UL

—ABB HE seriesWallmount SPD

12.000 [304.80]

10.750 [273.05]

12.015 [305.18]

12.000 [304.80]

26.500 [673.10]

9.276 [235.61]

1.250 [31.75]

24.000 [609.60]

0.625 [15.87]

0.440 [ 11.18]

(2 PLACES)

0.625 [15.87]

0.440 [ 11.18] HOLE

(2 PLACES)

WMN1 Dimensions

Page 20: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-20 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB ME seriesWallmount SPD with enhanced thermal protection

Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPME120SxxxWMN

208Y/120 3-phase, 4-wire + ground TPME120YxxxWMN

380Y/220 3-phase, 4-wire + ground TPME220YxxxWMN

240 Delta 3-phase, 3-wire + ground TPME240DxxxWMN

240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPME240HxxxWMN

415Y/240 3-phase, 4-wire + ground TPME240YxxxWMN

480Y/277 3-phase, 4-wire + ground TPME277YxxxWMN

600Y/347 3-phase, 4-wire + ground TPME347YxxxWMN

480 Delta 3-phase, 3-wire + ground TPME480DxxxWMN

Desired kA xxx Code65 065

80 080

100 100

Product # ExampleTPME277Y15WMN4S277Y/480 V, 3 Ph, 4 W + G

150kA per mode

Surface mount enclosure without disconnect

Painted steel

T P M E W M NProduct #

Nominal Voltage (Volts RMS)

System Voltage Configuration

Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision

MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L

120S 120/240 1 Ph, 3 W + G 900 - 800 - 700 1200 - 125%

120Y 120Y/208 3 Ph, 4 W + G 900 - 800 - 700 1200 - 125%

220Y 220Y/380 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 145%

240D 240 Delta 3 Ph, 4 W - - 1200 - - 1800 - 196%

240H120/240 Delta HL

3 Ph, 4 W + G 1000 1200 800 1200 700 2000 2200 115%

240Y 240Y/415 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 130%

277Y 277Y/480 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 115%

347Y 347Y/600 3 Ph, 4 W + G 1500 - 1500 - 1500 2500 - 115%

480D 480 Delta 3 Ph, 4 W - - 1800 - - 3000 - 198%

Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.

Maximum Surge Current CapacityExposure Level

Per Mode Per Phase

06 ME 65kA 130kA

08 ME 80kA 160kA

10 ME 100kA 200kA

Phase Rating = (L-N + L-G)

Suffix DescriptionNEMA Enclosure

Mounting Disconnect

1 Painted Steel 1 Surface Yes

1T11 Painted Steel 1 Surface Yes

4 Fiberglass 4X Surface Yes

4T11 Fiberglass 4X Surface Yes

4S Painted Steel 4 Surface No

4ST11 Painted Steel 4 Surface No

4X Stainless Steel 4X Surface No

4XT11 Stainless Steel 4X Surface No1UL Type 1 device

Page 21: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-21SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB ME seriesWallmount SPD with enhanced thermal protection

FeaturesUL Listed 1449 4th Edition, Type 1, Type 2

cUL Listed, CSA C22.2

UL 96A, for use in lightning protection systems

Patented thermal fuse technology

Standard features include a surge counter, audible alarm, indicating lights, dry contacts and NEMA 4 painted steel enclosure

10 year limited warranty

Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode

Nominal discharge current rating (l-n) 20 kA

Operating frequency 50-60Hz

Surge life (IEEE C62.41 - C3 10kA) ≥5000 impulses

Connection method 6 to 2/0 Conductors, Parallel Connected

Modes of protection All Modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR) 200 kAIC

Standard monitoring

Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter

EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ

Mechanical characteristics

WeightVaries and depends on enclosure typePlease see Available Options

Enclosure type Painted steel, NEMA 4

Installation location Service Entrance Equipment, Primary Distribution

Mounting method Surface Mount, 4-point mounting brackets

Operating temperature -40° F to 149° F (-40° C to +65° C)

Altitude 0 - 12,000 ft (3.66 km)

Product design Individually fused thermally protected MOV technology

Regulations and certificationsUL 1449 4th edition VZCA:E320456 Type 1/Type 2

cUL, CSA C22.2 VZCA7:E320456 Type 2/Type 2

UL 1283 FOKY:E320456 Type 2

UL 96A Yes

IEEE C62.62, C62.72, C62.41 Yes

Listed By UL

Page 22: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-22 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB HE seriesWallmount SPD with enhanced thermal protection

Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TPHE120SxxxWMN

208Y/120 3-phase, 4-wire + ground TPHE120YxxxWMN

380Y/220 3-phase, 4-wire + ground TPHE220YxxxWMN

240 Delta 3-phase, 3-wire + ground TPHE240DxxxWMN

240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPHE240HxxxWMN

415Y/240 3-phase, 4-wire + ground TPHE240YxxxWMN

480Y/277 3-phase, 4-wire + ground TPHE277YxxxWMN

600Y/347 3-phase, 4-wire + ground TPHE347YxxxWMN

480 Delta 3-phase, 3-wire + ground TPHE480DxxxWMN

600 Delta 3-phase, 3-wire + ground TPHE600DxxxWMN

Desired kA xxx Code150 150

200 200

250 250

300 300

T P H E W M NProduct #

Nominal Voltage (Volts RMS)

System Voltage Configuration

Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision

MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L

120S 120/240 1 Ph, 3 W + G 900 - 800 - 700 1200 - 125%

120Y 120Y/208 3 Ph, 4 W + G 900 - 800 - 700 1200 - 125%

220Y 220Y/380 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 145%

240D 240 Delta 3 Ph, 4 W - - 1200 - - 1800 - 196%

240H120/240 Delta HL

3 Ph, 4 W + G 1000 1200 800 1200 700 2000 2200 115%

240Y 240Y/415 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 130%

277Y 277Y/480 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 115%

347Y 347Y/600 3 Ph, 4 W + G 1500 - 1500 - 1500 2500 - 115%

480D 480 Delta 3 Ph, 4 W - - 1800 - - 3000 - 198%

Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.

Maximum Surge Current CapacityExposure Level

Per Mode Per Phase

12 HE 125kA 250kA

15 HE 150kA 300kA

20 HE 200kA 400kA

25 HE 250kA 500kA

30 HE 300kA 600kA

Phase Rating = (L-N + L-G)

Product # ExampleTPHE277Y15WMN4S277Y/480 V, 3 Ph, 4 W + G

150kA per mode

Surface mount enclosure without disconnect

Painted steel

Suffix DescriptionNEMA Enclosure

Mounting Disconnect

1 Painted Steel 1 Surface Yes

1T11 Painted Steel 1 Surface Yes

4 Fiberglass 4X Surface Yes

4T11 Fiberglass 4X Surface Yes

4S Painted Steel 4 Surface No

4ST11 Painted Steel 4 Surface No

4X Stainless Steel 4X Surface No

4XT11 Stainless Steel 4X Surface No1UL Type 1 device

Page 23: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-23SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB HE seriesWallmount SPD with enhanced thermal protection

FeaturesUL Listed 1449 4th Edition, Type 1, Type 2

cUL Listed, CSA C22.2

UL 96A, for use in lightning protection systems

Thermally protected MOV design eliminates the need for additional upstream over current protection

Standard features include a surge counter, audible alarm, indicating lights, dry contacts and NEMA 4 painted steel enclosure

10 year limited warranty

Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode

Nominal discharge current rating (l-n) 20 kA

Operating frequency 50-60Hz

Surge life (IEEE C62.41 - C3 10kA) ≥20000 impulses

Connection method 6 to 2/0 Conductors, Parallel Connected

Modes of protection All Modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR) 200 kAIC

Standard monitoring

Status indicator lights (one per phase) and red service lightAudible alarm with silencer & test switchContacts for remote monitoring (2 amp, 125VAC)-(1 amp, 30VDC)6 Digit LCD re-settable surge event counter

EMI/RFI filter attenuationMaximum attenuation frequency -50dB @ 100kHZ

Mechanical characteristics

WeightVaries and depends on enclosure typePlease see Available Options

Enclosure type Painted steel, NEMA 4

Installation location Service Entrance Equipment, Primary Distribution

Mounting method Surface Mount, 4-point mounting brackets

Operating temperature -40° F to 149° F (-40° C to +65° C)

Altitude 0 - 12,000 ft (3.66 km)

Product design Individually fused thermally protected MOV technology

Regulations and certificationsUL 1449 4th edition VZCA:E320456 Type 1/Type 2

cUL, CSA C22.2 VZCA7:E320456 Type 2/Type 2

UL 1283 FOKY:E320456 Type 2

UL 96A Yes

IEEE C62.62, C62.72, C62.41 Yes

Listed By UL

Page 24: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-24 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB ME and HE seriesWallmount, with enhanced thermal protection

12.000 [304.80]

10.750 [273.05]

12.015 [305.18]

12.000 [304.80]

26.500 [673.10]

9.276 [235.61]

1.250 [31.75]

24.000 [609.60]

0.625 [15.87]

0.440 [ 11.18]

(2 PLACES)

0.625 [15.87]

0.440 [ 11.18] HOLE

(2 PLACES)

24.000 [609.60]

25.500 [647.70]

20.000 [508.00]

12.651 [321.34]

21.500 [546.10]

9.912 [251.76]

1.852 [47.04]

13.478 [342.34]

14.759 [374.88]

16.000 [406.40]

8.978 [228.04]

15.330 [389.38]

19.330 [490.98]

8.978 [228.04]

15.330 [389.38]6.440

[163.58]

1.471 [37.36]

0.571 [14.50]

15.478 [393.14]

18.759 [476.48]

0.571 [14.50]

0.282 [ 7.16] HOLES

(8 PLACES)

3.852 [97.84]

12.000[304.80]

19.118 [485.61]

9.226 [234.33]

10.399 [264.14]

17.659 [448.53]

9.226 [234.33]

11.999 [304.77]6.439

[163.56]

1.475 [37.46]

0.380 [ 9.65] HOLE

(4 PLACES)

WMN1 Dimensions WMN4 Dimensions

WMN12F Dimensions WMN12S, WMN4S, WMN4X Dimensions

Page 25: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-25SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB LE seriesWallmount SPD

Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TLE120SxxxWM

208Y/120 3-phase, 4-wire + ground TLE120YxxxWM

380Y/220 3-phase, 4-wire + ground TLE220YxxxWM

240 Delta 3-phase, 3-wire + ground TLE240DxxxWM

240/120 Hi-Leg Delta 3-phase, 4-wire + ground TLE240HxxxWM

415Y/240 3-phase, 4-wire + ground TLE240YxxxWM

480Y/277 3-phase, 4-wire + ground TLE277YxxxWM

480 Delta 3-phase, 3-wire + ground TLE480DxxxWM

Desired kA xxx Code25 025

50 050

T L E W MProduct #

Nominal Voltage (Volts RMS)

System Voltage Configuration

Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision

MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L

120S 120/240 1 Ph, 3 W + G 600 - 600 - 600 1000 - 125%

120Y 120Y/208 3 Ph, 4 W + G 600 - 600 - 600 1000 - 125%

220Y 220Y/380 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 145%

240D 240 Delta 3 Ph, 4 W - - 900 - - 1800 - 196%

240H120/240 Delta HL

3 Ph, 4 W + G 600 1200 600 1000 600 1000 1800 115%

240Y 240Y/415 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 130%

277Y 277Y/480 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 115%

480D 480 Delta 3 Ph, 4 W - - 1800 - - 4000 - 198%

025 25 kA per mode 50 kA per phase (TLE)

050 50 kA per mode 100 kA per phase (TLE)

Page 26: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-26 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB LE seriesWallmount SPD

FeaturesUL Listed 1449 4th Edition, Type 2

cUL Listed, CSA C22.2

Compact and economical design for use at medium exposure, distribution or branch panels

Patented thermal fuse technology

Standard features include status indicating LEDs, form C dry contacts for remote monitoring and NEMA 12 painted steel enclosure

10 year limited warranty

Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode

Nominal discharge current rating (l-n) 10 kA

Operating frequency 50-60Hz

Surge life (IEEE C62.41 - C3 10kA) ≥3500 impulses

Connection method 10 AWG Conductors, Parallel Connected

Modes of protection All Modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR) 65 kA (30A breaker required)

Standard monitoringStatus indicator lights (one per phase)Standard dry (Form "C") relay contacts

Mechanical characteristicsWeight 17 lbs. (7.7 kg)

Enclosure type Painted steel, NEMA 12

Installation locationSecondary Distribution Equipment, Branch Panels - Rated for UL and NEC 2020 Type 2 Installation Locations

Mounting method Dual Mounting Flanges / 3/4" NPT Offset Nipple

Operating temperature -40° F to 149° F (-40° C to +65° C)

Altitude 0 - 12,000 ft (3.66 km)

Product design Thermal fuse technology

Regulations and certificationsUL 1449 4th edition VZCA:E320456 Type 2

cUL, CSA C22.2 VZCA7:E320456 Type 2

IEEE C62.62, C62.72 Yes

Listed By UL

TME TLE4.00

7.50

6.75

6.25

6.25

3/4" N.P.T.

6.00

1.55

4.37

2.85

TLE

Page 27: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-27SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB ME seriesWallmount SPD

Voltage Configuration Product Number240/120 1-phase, 3-wire + ground TME120SxxxWM

208Y/120 3-phase, 4-wire + ground TME120YxxxWM

380Y/220 3-phase, 4-wire + ground TME220YxxxWM

240 Delta 3-phase, 3-wire + ground TME240DxxxWM

240/120 Hi-Leg Delta 3-phase, 4-wire + ground TME240HxxxWM

415Y/240 3-phase, 4-wire + ground TME240YxxxWM

480Y/277 3-phase, 4-wire + ground TME277YxxxWM

480 Delta 3-phase, 3-wire + ground TME480DxxxWM

Desired kA xxx Code65 065

80 080

100 100

T M E W MProduct #

Nominal Voltage (Volts RMS)

System Voltage Configuration

Voltage Protection Rating (VPR) UL 1449 4th Edition September 2014 Revision

MCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L

120S 120/240 1 Ph, 3 W + G 600 - 600 - 600 1000 - 125%

120Y 120Y/208 3 Ph, 4 W + G 600 - 600 - 600 1000 - 125%

220Y 220Y/380 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 145%

240D 240 Delta 3 Ph, 4 W - - 900 - - 1800 - 196%

240H120/240 Delta HL

3 Ph, 4 W + G 600 1200 600 1000 600 1000 1800 115%

240Y 240Y/415 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 130%

277Y 277Y/480 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 115%

480D 480 Delta 3 Ph, 4 W - - 1800 - - 4000 - 198%

065 65 kA per mode 130 kA per phase (TME)

080 80 kA per mode 160 kA per phase (TME)

100 100 kA per mode 200 kA per phase (TME)

Page 28: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-28 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—ABB ME seriesWallmount SPD

FeaturesUL Listed 1449 4th Edition, Type 2

cUL Listed, CSA C22.2

UL 96A, for use in lightning protection systems

Compact and economical design for use at medium exposure, distribution or branch panels

Standard features include status indicating LEDs, form C dry contacts for remote monitoring and NEMA 12 painted steel enclosure

10 year limited warranty

Electrical characteristicsMaximum surge current rating xxx per phase/half xxx per mode

Nominal discharge current rating (l-n) 20 kA

Operating frequency 50-60Hz

Surge life (IEEE C62.41 - C3 10kA) ≥5000 impulses

Connection method 10 AWG Conductors, Parallel Connected

Modes of protection All Modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR) 65 kA (30A breaker required)

Standard monitoringStatus indicator lights (one per phase)Standard dry (Form "C") relay contacts

EMI/RFI filter attenuationMaximum attenuation frequency -44dB @ (50kHz - 100MHz)

Mechanical characteristicsWeight 17 lbs. (7.7 kg)

Enclosure type Painted steel, NEMA 12

Installation locationService Entrance Equipment, Primary Distribution Equipment - Rated for UL and NEC 2020 Type 2 Installation Locations

Mounting method Dual Mounting Flanges / 3/4" NPT Offset Nipple

Operating temperature -40° F to 149° F (-40° C to +65° C)

Altitude 0 - 12,000 ft (3.66 km)

Product design Thermal fuse technology

Regulations and certificationsUL 1449 4th edition VZCA:E320456 Type 2

cUL, CSA C22.2 VZCA7:E320456 Type 2

UL 1283 FOKY:E320456 Type 2

UL 96A Yes

IEEE C62.62, C62.72 Yes

Listed By UL

TME TLE4.00

7.50

6.75

6.25

6.25

3/4" N.P.T.

6.00

1.55

4.37

2.85

TME

Page 29: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-29SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—OVRH seriesProduct range overview

NameOVRHSP (200, 240, 300, 400)

OVRHSP (120, 160)

OVRHSP (60, 80, 100)

OVRHSR (120, 160)

OVRHTE OVRHT3B OVRHT3C OVRHS3U OVRHLD

Connection Ampacity

1,000A and higher

1,000A and below

400A and below

1,000A and below

100–80kA1,000A and below50kA400A and below25kA100A and below

400A and below

400A and below

400A and below

100A and below

SPD Type Type 1 Type 1 Type 1 Type 1 Type 2 Type 1 Type 1 Type 1 and Type 2

Type 1

Certifications UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449

Surge Ratings 200, 240, 300, 400kA per phase

120, 160kA per phase

60, 80, 100kA per phase

120, 160kA per phase

25, 50, 80 and 100 per mode

50kA per phase

50kA per phase

40kA per phase

20, 25, 30kA per phase

LEDs Yes Yes Yes Yes Yes Yes Yes Yes Yes

Dry Relay Contacts

Standard Standard Optional Standard Optional Not available

Not available

Optional Not available

EMI Filter Optional Optional Optional Optional Optional Not available

Not available

Not available

Not available

Surge Counter Optional Optional Not available

Not available

Not available

Not available

Not available

Not available

Not available

Warranty 10 years 10 years 10 years 10 years 5 years 3 year 3 year 1 year 1 year

Page 30: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-30 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

Voltage Network type Part number

120 Vac1PH, 2W + GND

OVRHSPxx1201P

240 Vac OVRHSPxx2401P

240/120 Vac 2PH, 3W + GND OVRHSPxx1202S

208/120 Vac

3PH, 4W + GND (Wye)

OVRHSPxx1203Y

380/220 Vac OVRHSPxx2203Y

415/240 Vac OVRHSPxx2403Y

480/277 Vac OVRHSPxx2773Y

240/120 Vac 3PH, 4W + GND (High-leg) OVRHSPxx1203H

240 Vac 3PH, 3W + GND (Delta) OVRHSPxx2403D

xx indicates 60kA, 80kA or 100kA

Available Options (Add applicable suffix to the end of the part number)

Suffix

Advanced monitoring1 1

Transient filter (meets UL1283)2 3

Stainless steel enclosure (SS) 4

Advanced monitoring + SS enclosure A

Transient filter + SS enclosure C

1Includes dry relay contacts, audible alarm, alarm silence button and fault light2Not recommended when using telecom rectifiers

Electrical characteristics

Maximum surge current rating xx per phase/half xx per mode

Nominal discharge current rating (I-n) 10kA

Operating frequency 47-63Hz

Connection methodParallel to electrical distribution system

Modes of protection All modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR)200kAIC - No upstream over-current protection device required (breaker or fuse)

Response time Less than 1 nanosecond

Standard monitoringLED status indicator lights (1 per phase)

EMI/RFI filter attenuation

Maximum attenuation frequency 41dB @ 106kHz

Mechanical characteristics

Weight 10 lbs. (4.5 kg)

Enclosure typePowder coated, impact-resistance steel, weather-proof NEMA 4

Installation location Indoor/outdoor

Mounting method Dual mounting flanges

Operating temperature -40° to +185° F (-40° to +70° C)

Altitude Up to 13,000 ft. (4000 m)

Product designParallel design with individually fused MOVs

Regulations & certifications

UL 1449 4th edition Type 1

UL 1283 Yes

IEEE C62.41.1, .2, C62.45 Yes

Listed by ETL

Product features• Listed by ETL to UL 1449 4th Edition for Type 1 and Type 2

SPD applications• Fail-safe design with individually fused Metal Oxide

Varistors (MOV) eliminating single point failure, protecting against both overcurrent and overvoltage events

• 200kAIC short circuit rating permits direct bus connection to most electrical services

• Low let through voltage ensured by the lowest possible impedance path to ground and equal current sharing during surge events

• All weather sealed, powder-coated NEMA 4/IP65 housing is designed for any orientation and indoor/outdoor applications

• 10-year standard warranty

—OVRH seriesOVRHSP (4,000A and below, 60 to 100kA)

Page 31: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-31SURGE PROTECTION DEVICES, BUYLOG SECTION 5

Voltage Network type Part number

120 Vac1PH, 2W + GND

OVRHSPxx1201P

240 Vac OVRHSPxx2401P

240/120 Vac 2PH, 3W + GND OVRHSPxx1202S

208/120 Vac

3PH, 4W + GND (Wye)

OVRHSPxx1203Y

380/220 Vac OVRHSPxx2203Y

415/240 Vac OVRHSPxx2403Y

480/277 Vac OVRHSPxx2773Y

600/347 Vac OVRHSPxx3473Y

240/120 Vac 3PH, 4W + GND (High-leg) OVRHSPxx1203H

240 Vac

3PH, 3W + GND (Delta)

OVRHSPxx2403D

380 Vac OVRHSPxx3803D

480 Vac OVRHSPxx4803D

600 Vac OVRHSPxx6003D

xx indicates 120kA or 160kA

Available Options (Add applicable suffix to the end of the part number)

Suffix

Surge counter 2

Transient filter (meets UL1283)1 3

Stainless steel enclosure (SS) 4

Transient filter + Surge counter B

Transient filter + SS enclosure C

Surge counter + SS enclosure D

Filter + counter + SS enclosure T

1Not recommended when using telecom rectifiers

Product features• Listed by UL 1449 4th Edition for Type 1 and Type 2 SPD

applications• Fail-safe design with individually fused Metal Oxide

Varistors (MOV) eliminating single point failure, protecting against both overcurrent and overvoltage events

• 200kAIC short circuit rating permits direct bus connection to most electrical services

• Low let through voltage ensured by the lowest possible impedance path to ground and equal current sharing during surge events

• All weather sealed, powder-coated NEMA 4/IP65 housing is designed for any orientation and indoor/outdoor applications

• 10-year standard warranty

—OVRH seriesOVRHSP (4,000A and below, 120 to 160kA)

Electrical characteristics

Maximum surge current rating xx per phase/half xx per mode

Nominal discharge current rating (I-n) 20kA

Operating frequency 47-63Hz

Connection methodParallel to electrical distribution

Modes of protection All modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR)200kAIC - No upstream over-current protection device required (breaker or fuse)

Response time Less than 1 nanosecond

Standard monitoringLED status indicator lights (1 per phase), dry contacts, alarm

EMI/RFI filter attenuation

Maximum attenuation frequency 41dB @ 106kHz

Mechanical characteristics

Weight 20 lbs. (9 kg)

Enclosure typePowder coated, impact-resistance steel, weather-proof NEMA 4

Installation location Indoor/outdoor

Mounting method Dual mounting flanges

Operating temperature -40° to +185° F (-40° to +70° C)

Altitude Up to 13,000 ft. (4000 m)

Product designParallel design with individually fused MOVs

Regulations & certifications

UL 1449 4th edition Type 1

UL 1283 Yes

IEEE C62.41.1, .2, C62.45 Yes

Listed by UL

Page 32: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-32 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

Product features• Listed by UL 1449 4th Edition for Type 1 and Type 2 SPD

applications• Fail-safe design with individually fused Metal Oxide

Varistors (MOV) eliminating single point failure, protecting against both overcurrent and overvoltage events

• 200kAIC short circuit rating permits direct bus connection to most electrical services

• Low let through voltage ensured by the lowest possible impedance path to ground and equal current sharing during surge events

• All weather sealed, powder-coated NEMA 4/IP65 housing is designed for any orientation and indoor/outdoor applications

• 10-year standard warranty

—OVRH seriesOVRHSP (4,000A and below, 200 to 400kA)

Voltage Network type Part number

120 Vac1PH, 2W + GND

OVRHSPxx1201P

240 Vac OVRHSPxx2401P

240/120 Vac 2PH, 3W + GND OVRHSPxx1202S

208/120 Vac

3PH, 4W + GND (Wye)

OVRHSPxx1203Y

380/220 Vac OVRHSPxx2203Y

415/240 Vac OVRHSPxx2403Y

480/277 Vac OVRHSPxx2773Y

600/347 Vac OVRHSPxx3473Y

240/120 Vac 3PH, 4W + GND (High-leg) OVRHSPxx1203H

240 Vac

3PH, 3W + GND (Delta)

OVRHSPxx2403D

380 Vac OVRHSPxx3803D

480 Vac OVRHSPxx4803D

600 Vac OVRHSPxx6003D

xx indicates 200kA, 240kA, 300kA or 400kA

Available Options (Add applicable suffix to the end of the part number)

Suffix

Surge counter 2

Transient filter (meets UL1283)1 3

Stainless steel enclosure (SS) 4

Transient filter + Surge counter B

Transient filter + SS enclosure C

Surge counter + SS enclosure D

Filter + counter + SS enclosure T

1Not recommended when using telecom rectifiers

Electrical characteristics

Maximum surge current rating xx per phase/half xx per mode

Nominal discharge current rating (I-n) 20kA

Operating frequency 47-63Hz

Connection methodParallel to electrical distribution

Modes of protection All modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR)200kAIC - No upstream protection required (breaker/fuse)

Response time Less than 1 nanosecond

Standard monitoringLED status indicator lights (1 per phase), dry contacts, alarm

EMI/RFI filter attenuation

Maximum attenuation frequency 41dB @ 106kHz

Mechanical characteristics

Weight 40 lbs. (18 kg)

Enclosure typePowder coated, impact-resistance steel, weather-proof NEMA 4

Installation location Indoor/outdoor

Mounting method Dual mounting flanges

Operating temperature -40° to +185° F (-40° to +70° C)

Altitude Up to 13,000 ft. (4000 m)

Product designParallel design with individually fused MOVs

Regulations & certifications

UL 1449 4th edition Type 1

UL 1283 Yes

IEEE C62.41.1, .2, C62.45 Yes

Listed by ETL

Page 33: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-33SURGE PROTECTION DEVICES, BUYLOG SECTION 5

Voltage Network type Part number

120 Vac1PH, 2W + GND

OVRHSRxx1201P

240 Vac OVRHSRxx2401P

240/120 Vac 2PH, 3W + GND OVRHSRxx1202S

208/120 Vac

3PH, 4W + GND (Wye)

OVRHSRxx1203Y

380/220 Vac OVRHSRxx2203Y

415/240 Vac OVRHSRxx2403Y

480/277 Vac OVRHSRxx2773Y

600/347 Vac OVRHSRxx3473Y

240/120 Vac 3PH, 4W + GND (High-leg) OVRHSRxx1203H

240 Vac

3PH, 3W + GND (Delta)

OVRHSRxx2403D

380 Vac OVRHSRxx3803D

480 Vac OVRHSRxx4803D

600 Vac OVRHSRxx6003D

xx indicates 120kA or 160kA

Available Options (Add applicable suffix to the end of the part number)

Suffix

Transient filter (meets UL1283)1 3

Stainless steel enclosure (SS) 4

Filter + counter + SS enclosure C

1Not recommended when using telecom rectifiers

Stand alone option Part number

Flush-mount plate kit OVRHSP-FMP

Product features• Listed by UL 1449 4th Edition for Type 1 and Type 2 SPD

applications• CE compliant• Compact design to allow the SPD to be recessed into the

wall• Fail-safe design with individually fused Metal Oxide

Varistors (MOV) eliminating single point failure, protecting against both overcurrent and overvoltage events

• 200kAIC short circuit rating permits direct bus connection to most electrical services

• Low let through voltage ensured by the lowest possible impedance path to ground and equal current sharing during surge events

• 10-year standard warranty

Electrical characteristics

Maximum surge current rating xx per phase/half xx per mode

Nominal discharge current rating (I-n) 20kA

Operating frequency 47-63Hz

Connection methodParallel to electrical distribution

Modes of protection All modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR)200kAIC - No upstream protection required (breaker/fuse)

Response time Less than 1 nanosecond

Standard monitoringLED status indicator lights (1 per phase), dry contacts, alarm

EMI/RFI filter attenuation

Maximum attenuation frequency 41dB @ 106kHz

Mechanical characteristics

Weight 30 lbs. (13.6 kg)

Enclosure typePowder coated, impact-resistance steel, weather-proof NEMA 4

Installation location Indoor/outdoor

Mounting method Dual mounting flanges

Operating temperature -40° to +185° F (-40° to +70° C)

Altitude Up to 13,000 ft. (4000 m)

Product designParallel design with individually fused MOVs

Regulations & certifications

UL 1449 4th edition Type 1

UL 1283 Yes

IEEE C62.41.1, .2, C62.45 Yes

Listed by UL

—OVRH seriesOVRHSR (Wall recessed - 4,000A and below, 120 to 160kA)

Page 34: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-34 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—OVRH seriesOVRHTE (1,000A and below, 25 to 100kA)

Product features• Listed by UL 1449 4th Edition for Type 2 SPD applications• Protects facilities and equipment against the harmful

effects of lightning strikes and internally generated electrical transients

• Includes pre-wired pigtail conductors to streamline installation

• Features internal copper bus conduction path to minimize system impedances, lowering clamping voltage and increasing protection

• Pre-wired with 24 in (609.6mm) cables #10AWG (5mm2)• 5-year standard warranty

Voltage Network type Part number

120 Vac1PH, 2W + GND

OVRHTExx1201P

240 Vac OVRHTExx2401P

240/120 Vac 2PH, 3W + GND OVRHTExx1202S

208/120 Vac

3PH, 4W + GND (Wye)

OVRHTExx1203Y

380/220 Vac OVRHTExx2203Y

415/240 Vac OVRHTExx2403Y

480/277 Vac OVRHTExx2773Y

600/347 Vac OVRHTExx3473Y

240/120 Vac 3PH, 4W + GND (High-leg) OVRHTExx2403H

240 Vac

3PH, 3W + GND (Delta)

OVRHTExx2403D

380 Vac OVRHTExx3803D

480 Vac OVRHTExx4803D

xx indicates 25kA, 50kA, 80kA or 100kA

Available Option (Add applicable suffix to the end of the part number. Example: OVRHTE251201P5)

Suffix

Dry Form "C" relay contacts 5

Electrical characteristics

Maximum surge current rating xx per phase/half xx per mode

Nominal discharge current rating (I-n) 20kA

Operating frequency 47-63Hz

Connection method Parallel to load (with breaker)

Modes of protection All modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR)65kAIC - upstream protection (breaker or fuse required)

Response time Less than 1 nanosecond

Standard monitoringLED status indicator lights (1 per phase)

EMI/RFI filter attenuation

Maximum attenuation frequency 50dB @ 100kHz

Mechanical characteristics

Weight 12.7 lbs. (5.8 kg)

Enclosure typeNEMA 4X fiberglass-reinforced polyester (FRP) surface-mount, non-removable cover

Installation location Indoor/outdoor

Mounting method Dual mounting flanges

Operating temperature -40° to +140° F (-40° to +60° C)

Altitude Up to 16,400 ft. (5000 m)

Product design No internal fusing

Regulations & certifications

UL 1449 4th edition Type 2

UL 1283 Yes

IEEE C62.41.1, .2, C62.45 Yes

Listed by UL

Page 35: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-35SURGE PROTECTION DEVICES, BUYLOG SECTION 5

Voltage Network type 1 SPD Part number

120 Vac

1PH, 2W + GND

OVRHT3B501201P

240 Vac OVRHT3B502401P

277 Vac OVRHT3B502771P

480 Vac OVRHT3B504801P

240/120 Vac2PH, 3W + GND

OVRHT3B501202S

480/240 Vac OVRHT3B502402S

240/120 Vac 3PH, 4W + GND (Hi-Leg) OVRHT3B502403H

208/120 Vac

3PH, 4W + GND (Wye)

OVRHT3B501203Y

380/220 Vac OVRHT3B502203Y

400/230 Vac OVRHT3B502303Y

415/240 Vac OVRHT3B502403Y

480/277 Vac OVRHT3B502773Y

600/347 Vac OVRHT3B503473Y

240 Vac

3PH, 3W + GND (Delta)

OVRHT3B502403D

380 Vac OVRHT3B503803D

400 Vac OVRHT3B504003D

480 Vac OVRHT3B504803D

600 Vac OVRHT3B506003D

Product features• Listed to UL 1449 4th Edition for Type 1 SPD applications• 50kA protection per phase• Individually thermally fused and protected MOVs• LED indication• Pre-wired conductors included• Multiple MOVs per phase eliminates single point failure• 3-year standard warranty

Electrical characteristics

Nominal discharge current rating (I-n) 10kA

Operating frequency 47-63Hz

Connection method Parallel to load (with breaker)

Modes of protection Model dependent

Fault rating (SCCR) 100kAIC

Response time Less than 1 nanosecond

Standard monitoring LED status indicator lights

Mechanical characteristics

Weight 0.5 lbs. (0.23 kg)

Enclosure type NEMA 4X non-metallic

Installation location Indoor/outdoor

Mounting method 1/2 in (12.7mm) - 14 NPT thread

Operating temperature -31° to +176° F (-35° to +80° C)

Altitude Up to 16,400 ft. (5000 m)

Product design Individual therm. fused MOVs

Regulations & certifications

UL 1449 4th edition Type 1

UL 96A Yes

IEEE C62.41.1, .2, C62.45 Yes

Listed by UL

—OVRH seriesOVRHT3B (400A and below, 50kA)

Page 36: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-36 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—OVRH seriesOVRHT3C (400A and below, 50kA)

Product features• Listed to UL 1449 4th Edition for Type 1 SPD applications• 50kA protection per phase• Individual thermally fused and protected MOVs• LED indication• Pre-wired conductors included• Multiple MOVs per phase eliminates single point failure• 3-year standard warranty

Voltage Network type 1 SPD Part number

120 Vac

1PH, 2W + GND

OVRHT3C501201P

240 Vac OVRHT3C502401P

277 Vac OVRHT3C502771P

480 Vac OVRHT3C504801P

240/120 Vac2PH, 3W + GND

OVRHT3C501202S

480/240 Vac OVRHT3C502402S

240/120 Vac 3PH, 4W + GND (Hi-Leg) OVRHT3C502403H

208/120 Vac

3PH, 4W + GND (Wye)

OVRHT3C501203Y

380/220 Vac OVRHT3C502203Y

400/230 Vac OVRHT3C502303Y

415/240 Vac OVRHT3C502403Y

480/277 Vac OVRHT3C502773Y

600/347 Vac OVRHT3C503473Y

240 Vac

3PH, 3W + GND (Delta)

OVRHT3C502403D

380 Vac OVRHT3C503803D

400 Vac OVRHT3C504003D

480 Vac OVRHT3C504803D

600 Vac OVRHT3C506003D

Electrical characteristics

Nominal discharge current rating (I-n) 10kA

Operating frequency 47-63Hz

Connection method Parallel to load (with breaker)

Modes of protection Model dependent

Fault rating (SCCR) 100kAIC

Response time Less than 1 nanosecond

Standard monitoring LED status indicator lights

Mechanical characteristics

Weight 0.5 lbs. (0.23 kg)

Enclosure type NEMA 4X non-metallic

Installation location Indoor/outdoor

Mounting method 1/2 in (12.7mm) - 14 NPT thread

Operating temperature -31° to +176° F (-35° to +80° C)

Altitude Up to 16,400 ft. (5000 m)

Product design Individual therm. fused MOVs

Regulations & certifications

UL 1449 4th edition Type 1

UL 96A Yes

IEEE C62.41.1, .2, C62.45 Yes

Listed by UL

Page 37: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-37SURGE PROTECTION DEVICES, BUYLOG SECTION 5

Product features• Listed to UL 1449 4th Edition for Type 1 or Type 2 SPD

applications• Individual fusing for each Metal Oxide Varistors (MOVs)• LED indicating proper functioning of L-N and N-G MOVs• Pre-wired with 18in (450mm) cables #14AWG (2mm2)• 1-year standard warranty

—OVRH seriesOVRHS3U (400A and below, 40kA)

Voltage Network Type 1 SPD Part number

120 Vac 1PH, 2W + GND OVRHS3U401201P

240/120 Vac 2PH, 3W + GND OVRHS3U401202S

240V 3PH, 4W + GND (Delta) OVRHS3U402403D

208/120 Vac 3PH, 4W + GND (Wye) OVRHS3U401203Y

Voltage Network Type 2 SPD Part number

240V 1PH, 2W + GND OVRHS3U402401P

240/120V 2PH, 3W + GND1 OVRHS3U801202SR

480V 3PH, 3W + GND (Delta) OVRHS3U404803D

240/120V 3PH, 4W + GND (Hi-Leg) OVRHS3U401203H

480/277V 3PH, 4W + GND (Wye) OVRHS3U402773Y

400/230V 3PH, 3W + GND (Wye) OVRHS3U402303Y

180kA unit including 1283 listed filter, dry contacts option not available

Available Options Suffix

Dry relay contacts 5

Dry relay contacts + mounting bracket P

Electrical characteristics

Nominal discharge current rating (I-n) 20kA

Operating frequency 47-63Hz

Connection method Parallel to load

Modes of protection All modes (L-N, L-G, N-G, L-L)

Fault rating (SCCR) 100kAIC

Response time Less than 1 nanosecond

Standard monitoring LED status indicator lights

Mechanical characteristics

Weight 2 lbs. (0.9 kg)

Enclosure type NEMA 1 non-metallic

Installation location Indoor

Mounting method 1/2in (12.7mm) - 14 NPT thread

Operating temperature -40° to +176° F (-40° to +80° C)

Altitude Up to 16,400 ft. (5000 m)

Product design Individually fused MOVs

Regulations & certifications

UL 1449 4th edition Type 1 and Type 2

UL 1283 Only for OVRHS3U802402SR

IEEE C62.41.1, .2, C62.45 Yes

Listed by UL

Page 38: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-38 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—OVRH seriesOVRHLD (100A and below, 20 to 30kA)

Product features• Listed by ETL to UL 1449 4th Edition for Type 1 SPD

applications• Multiple metal oxide varistors (MOVs), with individual

current fusing and thermal disconnects for each MOV• LED indicating proper functioning of L-N MOVs• Pre-wired with 18in (450mm) cables #14AWG (2mm2)• 1-year warranty

Description Part number

xxkA, yyyV, L-N / N-G (1 LED) OVRHLDxx-yyy-1

xxkA, yyyV, L1-N / L2-N (2 LEDs) OVRHLDxx-yyy-2

xxkA, yyyV, L1-G / L2-G (2 LEDs) OVRHLDxx-yyy-3

xxkA, yyyV, L1-G / N-G (1 LED) OVRHLDxx-yyy-4

xxkA, yyyV, L-N / L-G (2 LEDs) OVRHLDxx-yyy-5

xxkA, yyyV, L-N (1 LED) OVRHLDxx-yyy-6

xxkA, yyyV, L-G (1 LED) OVRHLDxx-yyy-7

xxkA, yyyV, N-G (0 LED) OVRHLDxx-yyy-8

xxkA, yyyV, L1-L2 (1 LED) OVRHLDxx-yyy-9

Available Option

(Add applicable suffix to the end of the part number)

Suffix

Mounting bracket 6

Electrical characteristics

Nominal discharge current rating (I-n) 10kA

Operating frequency 47-63Hz

Connection method Parallel to load

Modes of protection L-N, L-G, N-G

Fault rating (SCCR) 65kAIC

Response time Less than 1 nanosecond

Standard monitoringLED status indicator lights 1 per phase

Mechanical characteristics

Weight 1 lb. (0.5 kg)

Enclosure type NEMA 1 non-metallic

Installation location Indoor

Mounting method NPS thread or bracket

Operating temperature -40° to +176° F (-40° to +80° C)

Altitude Up to 16,400 ft. (5000 m)

Product designIndividually fused MOVs, Overcurrent fusing, thermal fusing

Regulations & certifications

UL 1449 4th edition Type 1

UL 1283 No

IEEE C62.41.1, .2, C62.45 Yes

Listed by ETL

Page 39: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-39SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—OVRH seriesDimensions

Dimensions OVRHSP (60 to 100kA)

Value Inches / Millimeters

H1 6.00 / 152.4

H2 6.75 / 171.5

H3 7.50 / 190.5

W1 6.00 / 152.4

W2 4.00 / 101.6

D1 4.16 / 105.7

D2 2.00 / 50.8

Dimensions OVRHSP (120 to 160kA)

Value Inches / Millimeters

H1 10.00 /254.0

H2 10.75 / 273.1

H3 11.50 / 292.1

W1 8.00 / 203.2

W2 6.00 / 152.4

D 6.20 / 157.5

Dimensions

Value Inches / Millimeters

H1 14.00 / 355.6

H2 14.75 / 374.7

H3 15.50 /393.7

W1 12.00 / 304.8

W2 10.00 / 254.0

D 6.20 / 157.5

(W1)

(W2)

(H1)

(H2)

(H3)

(D1) (D2)

19.05 (3/4) Myers Hub

ø7.87 (0.31)

(W1)

(W2)

(H1)(H2)

(H3)

ø7.87 (0.31)

(D)

34.5(1.36)

83.8(3.20)

Allowable area for conduit entry

(W1)

(W2)

(H1)(H2)

(H3)

ø0.31 (7.87)

(D)

Allowable area for conduit entry

34.5(1.36)

83.8(3.20)

Page 40: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-40 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—OVRH seriesDimensions

Dimensions OVRHSR (120 to 160kA)

Value Inches / Millimeters

H1 10.00 / 254.0

H2 10.75 / 273.1

H3 11.50 / 292.1

W1 8.00 / 203.2

W2 6.00 / 152.4

D1 4.20 / 106.9

D2 2.00 / 50.8

Stud

Drywall

Flush-mount plate

OVRHSR unit

Page 41: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-41SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—OVRH seriesDimensions

Dimensions OVRHTE

Value Inches / Millimeters

H1 6.17 / 156.7

H2 6.75 / 171.5

H3 7.50 / 190.4

W1 4.01 / 101.9

W2 6.12 / 155.4

D 5.01 / 127.5

Dimensions OVRHT3B

Value Inches / Millimeters

W 3.36 / 90.0

D 2.93 / 75.0

H 2.93 / 75.0

Dimensions OVRHT3C

Value Inches / Millimeters

W 3.18 / 80.8

D 3.10 / 78.7

H 3.56 / 90.4

(W2)

(W1)(D)

(H1) (H2) (H3)

90mm(3.56")

75mm(2.93")

75mm(2.93")

32mm(1.26")

35mm(1.37")

19mm (.75")

64mm(2.52")

3.31mm2 (#12 AWG) stranded wire600V PVC insulation914.4mm (36") long

Aluminum bracket

Ø 5.5mm (.21") 2 holes

12.7mm (1/2")-14 NPS thread

Bracket detail

W

H

D

Page 42: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-42 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—OVRH seriesDimensions

Dimensions OVRHS3U (with and without dry contacts option)

Value Inches / Millimeters

W 2.90 / 73.0

D 2.00 / 51.0

H 5.60 / 142.0

Dimensions mounting bracket OVRHS3U

Value Inches / Millimeters

W 1.94 / 49.0

H 8.25 / 210.0

(2.90")73mm

(5.6") 142mm

19mm (.75")

Remote monitoring terminals

LED

2mm2 (#14 AWG) stranded wire600V PVC insulation450mm (18") long

210mm (8.25")

195mm (7.690")

7mm (.28") Mounting

bracket

12mm (.47")

25mm(1.000")

49mm (1.94")

M4 threaded hole4 plcs.

(2.90")73mm

(2.00")51mm

(1.60") 41mm

(5.6") 142mm

(2.30") 58mm

19mm (.75")

.136 dia. blind holes, .40 deep for #8 self-tapping screws (2)

(0.25")6mm

LED

1/2–14 NPT thread

2mm2 (#14 AWG) stranded wire600V PVC insulation450mm (18") long

Page 43: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-43SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—DIN-rail SPDs for distribution panelsUL 1449 4th edition

Transient Voltage Surges in LV Power LinesTransient overvoltages are voltage surges that can reach tens of kilovolts with a duration in the order of microseconds.

Despite their short duration, the high energy content can cause serious problems to equipment connected to the line, from premature aging to destruction, causing disruptions to service and financial loss.

This type of surge can have various different causes, including atmospheric lightning directly striking the external protection (lightning rods) on a building or transmission line, or the associated induction of electromagnetic fields on metallic conductors. Outdoor and longer lines are the most exposed to these fields, which often receive high levels of induction.

It is also common for non-weather phenomena such as transformer center switching or the disconnection of motors or other inductive loads to cause voltage spikes in adjacent lines.

The protector will discharge excess energy to earth, thus limiting the peak voltage to a value acceptable for the electrical equipment connected.

Risk of Electrical SurgesLightning and surge protection electrical and electronic equipment is indispensable in the daily activities of today’s businesses and individuals.

Such devices are connected to the electricity grid, often exchanging data and signals through communication lines and are usually sensitive to disturbances.

These interconnecting networks provide a propagation path for overvoltages.

Protection against lightning and overvoltages not only ensures the safety of people, goods and equipment, but also ensures continuity of installation services and meets criteria of energy efficiency.

Overvoltage protection extends the life of the equipment by more than 20%, which significantly reduces the volume of electronic waste. It also reduces the power consumption of the installations, all of which translates into cost savings and environmental sustainability.

U(V)

2

4000

3500

3000

2000

1000

500

-500

-10001ms max.

04 6 8 10 12 14 16 18 20 t(ms)

When the peak voltage reaches a value higher than the equipment can withstand, it causes its destruction.

Page 44: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-44 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—DIN-rail SPDs for distribution panelsUL 1449 4th editionTerminology of SPD electrical characteristics

ImaxMaximum Discharge CapacityMaximum peak current, per phase, in 8/20 μs wave that the protection device is able to withstand.

VPRVoltage Protection RatingThis indicates the maximum residual voltage between the terminals of the protection device during application of an In peak current.

InNominal Discharge Current RatingPeak current in 8/20 μs wave that the protection device can withstand on 15 occasions without reaching the end of its service life.

MCOVMaximum Continuous Operating Voltage This indicates the maximum effective or direct current voltage that can be permanently applied to the terminals of the protection device.

TYPEType 1Permanently connected SPDs intended for installation betweenbthe secondary of the service transformer and the line side of the service equipment (main panel) overcurrent device, as well as the load side, including watt-hour meter socket enclosures and intended to be installed without an external overcurrent protective device.

Type 2Permanently connected SPDs intended for installation on the load side of the service equipment (main panel) overcurrent device; including SPDs located at the branch panel.

Type 3Point of utilization SPDs, installed at a minimum conductor length of 30 feet (10 meters) from the electrical service panel to the point of utilization. For example cord connected, direct plug-in, receptacle type and SPDs installed at the utilization equipment being protected. The distance 30 feet (10 meters) is exclusive of conductors provided with or used to attach SPDs that the protection device is able to withstand.

Operating principle of an SPD

Page 45: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-45SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—DIN-rail SPDs for distribution panelsUL 1449 4th editionStandards

The objective of UL 1449 has always been to increase safety in terms of surge protection.

Change in the standard's name: From TVSS to SPDsPrior to UL 1449 4th Edition taking effect, the devices this standard covers were known as Transient Voltage Surge Suppressors (TVSS), operating on power circuits not exceeding 600 V. With the inception of the 3rd and 4th Edition, these devices are now known as Surge Protective Devices (SPDs), and may operate on power circuits not exceeding 1500 V DC.

This new designation moves the UL standard closer to the international designation and to IEC standards.

The different type designations of surge protective devicesThe UL 1449 placed SPDs into five different Type categories based on installation location within an electrical system.While Type 1, Type 2 and Type 3 categories refer to different types of SPDs that can be installed at specific locations, Type 4 and Type 5 categories refer to components used in an SPDs configuration.

Type 1 - “Permanently connected SPDs intended for installation between the secondary of the service transformer and the line side of the service equipment overcurrent device.”Type 2 - “Permanently connected SPDs intended for installation on the load side of the service equipment overcurrent device.”Type 3 - “Point of utilization SPDs, installed at a minimum conductor length of 10 meters (30 feet) from the electrical service panel.”Type 4 - Component assemblies - “Component assembly consisting of one or more Type 5 components together with a disconnect (integral or external) or a means of complying with the limited current tests.”Type 1, 2, 3 - Component assemblies - “Consists of a Type 4 component assembly with internal or external short circuit protection.”Type 5 - “Discrete component surge suppressors, such as MOVs that may be mounted on a PWB, connected by its leads or provided within an enclosure with mounting means and wiring terminations.”

The closer an SPD is installed to the equipment, the better the protection is. This is a push in the direction of providing stepped protection including external and internal surge protection.

The measured voltage protection levelThe Measured Limiting Voltage (MLV) is the maximum magnitude of voltage measured at the application of a specific impulse wave shape.

When applying a certain surge current on the SPD the measured voltage at the device terminals is the so called “let-through voltage.”

In UL 1449 2nd Edition, the let-through voltage was referred to as Suppressed Voltage Rating (SVR) and was calculated with a 0.5 kA surge wave form at 6 kV. The new designation is Voltage Protection Rating (VPR) and is calculated with a 3 kA surge wave form at 6 kV.

All products you will find in this chapter have been certified according to the UL 1449 4th Edition.

The MLV will allow comparison of different types of SPDs with regards to the let-through voltage. However, it is important to note that the surge current used to measure the let-through voltage is six times higher in the 3rd and 4th Edition than in the 2nd Edition. This means that, comparing the obsolete SVR designation with the new VPR ratings will not be valid, as VPR ratings will of course be higher than SVR ratings.

The Underwriters Laboratories (UL) standard for surge protective devices (SPDs) has been the primary safety standard for surge protection since the first edition was published in 1985, the fourth edition became mandatory for AC SPDs in March 2016.

Page 46: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-46 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—DIN-rail SPDs for distribution panelsUL 1449 4th editionStandards

Wiring Diagrams According to ANSI C84.1The majority of modern installations in both the US and Canada feature the following kind of power distribution system.

Single Phase System Residential Buildings

i.e. Single phase 240 (Ph-Ph)/120V (to GRND) Grounded midpoint

For example:120V are used on the wall receptacle and 240V for ovens, ranges, air conditioning and laundry dryers

Three Phase/Three Wire System Industrial and Commercial Buildings

Three Phase/Four Wire System Industrial and Commercial Buildings

* Y describes the solidly grounded circuit.The value “Y” indicates the voltage between phases. The value behind the slash indicates the voltage between phase and the grounding or neutral conductor.

Single phase 120V, 240/277V

L1

NG

Grounded Wye 208Y/120V, 480Y/277V, 600Y/347V

L1L2

N

L3G

Split phase 240/120V, 480/240V

L1

L2

N

G

High-Leg Delta 240/120V HLD

L1L2

N

L3G

Single Phase 2 Wires120/240/277V

Grounded Wye208Y/120V, 480Y/277V, 600Y/347V

Delta 240/480/600V

Split Phase 3 Wires240/120V, 480/240V

High-Leg Delta240/120V HLD

Delta 240/480/600V

L1

L2

L3G

Page 47: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-47SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—DIN-rail SPDs for distribution panelsSingle-phase

Product features• UL recognized, Type 4 component for Type 2 device• Pluggable modules, fingersafe design - IP20 package• Remote indicator with 3 pin COM/NO/NC contacts• Built-in visual status indicator• Easy installation or retrofit device

Network typeNominal voltage

No. of wires

Max discharge current (Imax, 8/20 μs, kA)

Wiringconfig-uration

Nominal discharge current (In, kA)

MCOVL-L

MCOVL-G

MCOVL-N

VPR

Part number

L-N L-G N-G L-L

120V

2 Wire/1 Pole

25kA

Single phase

20

- -

180 600

- - -

TD120S1025RMP

50kA 20 180 600 TD120S1050RMP

240V25kA 20 275 900 TD240S1025RMP

50kA 20 275 900 TD240S1050RMP

277V25kA 20 320 1000 TD277S1025RMP

50kA 20 320 1000 TD277S1050RMP

347V25kA 10 420 1500 TD347S1025RMP

50kA 10 420 1500 TD347S1050RMP

Electrical characteristics

Modes of protection L-N

Fault rating (SCCR) 200kAIC

Standard monitoring Built-in visual status indicator and dry contacts

Mechanical characteristics

Installation location Type 2, indoor

Mounting method DIN rail

Operating temperature -13° F to 140° F (-25° C to +60° C)

Wire range (stranded/solid) #14 AWG to #6 AWG

Product design Thermally protected MOV technology

Regulations & certifications

UL 1449 4th edition VZCA2:E320456

ANSI/IEEE C62.41 Yes

RoHS compliant Yes

Listed by Type 4 UL recognized component (tested to SPD Type 2)

L

NG

Page 48: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-48 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—DIN-rail SPDs for distribution panelsSplit-phase

Product features• UL recognized, Type 4 component for Type 2 device• Pluggable modules, fingersafe design - IP20 package• Remote indicator with 3 pin COM/NO/NC contacts• Built-in visual status indicator• Easy installation or retrofit device

Network typeNominal voltage

No. of wires

Max discharge current (Imax, 8/20 μs, kA)

Wiringconfig-uration

Nominal discharge current (In, kA)

MCOVL-L

MCOVL-G

MCOVL-N

VPR

Part number

L-N L-G N-G L-L

208/120V, 240/120V

3 Wire/2 Pole

25kA

Split phase

20

360

-

180 600

- -

1200 TD120S2025RMP

50kA 360 180 600 1200 TD120S2050RMP

480/240V

25kA 550 275 900 1800 TD240S2025RMP

50kA 550 275 900 1800 TD240S2050RMP

Electrical characteristics

Modes of protection L-L and L-N

Fault rating (SCCR) 200kAIC

Standard monitoring Built-in visual status indicator and dry contacts

Mechanical characteristics

Installation location Type 2, indoor

Mounting method DIN rail

Operating temperature -13° F to 140° F (-25° C to +60° C)

Wire range (stranded/solid) #14 AWG to #6 AWG

Product design Thermally protected MOV technology

Regulations & certifications

UL 1449 4th edition VZCA2:E320456

ANSI/IEEE C62.41 Yes

RoHS compliant Yes

Listed by Type 4 UL recognized component (tested to SPD Type 2)

L1

L2

N

G

Page 49: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-49SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—DIN-rail SPDs for distribution panels3-phase wye

Product features• UL recognized, Type 4 component for Type 2 device• Pluggable modules, fingersafe design - IP20 package• Remote indicator with 3 pin COM/NO/NC contacts• Built-in visual status indicator• Easy installation or retrofit device

Network typeNominal voltage

No. of wires

Max discharge current (Imax, 8/20 μs, kA)

Wiringconfig-uration

Nominal discharge current (In, kA)

MCOVL-L

MCOVL-G

MCOVL-N

VPR

Part number

L-N L-G N-G L-L

208/120V

4 Wire/3 Pole

25kA

3-phase wye,common N/G

20 360

-

180 600

- -

1200 TD120Y3025RMP

50kA 20 360 180 600 1200 TD120Y3050RMP

480/277V

25kA 20 640 320 1000 1800 TD277Y3025RMP

50kA 20 640 320 1000 1800 TD277Y3050RMP

600/347V

25kA 10 840 420 1500 2500 TD347Y3025RMP

50kA 10 840 420 1500 2500 TD347Y3050RMP

Electrical characteristics

Modes of protection L-L and L-N

Fault rating (SCCR) 200kAIC

Standard monitoring Built-in visual status indicator and dry contacts

Mechanical characteristics

Installation location Type 2, indoor

Mounting method DIN rail

Operating temperature -13° F to 140° F (-25° C to +60° C)

Wire range (stranded/solid) #14 AWG to #6 AWG

Product design Thermally protected MOV technology

Regulations & certifications

UL 1449 4th edition VZCA2:E320456

ANSI/IEEE C62.41 Yes

RoHS compliant Yes

Listed by Type 4 UL recognized component (tested to SPD Type 2)

L1L2

N

L3G

Page 50: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-50 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—DIN-rail SPDs for distribution panels3-phase delta system

Product features• UL recognized, Type 4 component for Type 2 device• Pluggable modules, fingersafe design - IP20 package• Remote indicator with 3 pin COM/NO/NC contacts• Built-in visual status indicator• Easy installation or retrofit device

Network typeNominal voltage

No. of wires

Max discharge current (Imax, 8/20 μs, kA)

Wiringconfig-uration

Nominal discharge current (In, kA)

MCOVL-L

MCOVL-G

MCOVL-N

VPR

Part number

L-N L-G N-G L-L

240V

4 Wire/3 Pole

25kA

3-phase delta

20 550 275

- -

900

-

1800 TD240D3025RMP

50kA 20 550 275 900 1800 TD240D3050RMP

480V

25kA 10 1100 550 1800 3000 TD480D3025RMP

50kA 10 1100 550 1800 3000 TD480D3050RMP

Electrical characteristics

Modes of protection L-L and L-G

Fault rating (SCCR) 200kAIC

Standard monitoring Built-in visual status indicator and dry contacts

Mechanical characteristics

Installation location Type 2, indoor

Mounting method DIN rail

Operating temperature -13° F to 140° F (-25° C to +60° C)

Wire range (stranded/solid) #14 AWG to #6 AWG

Product design Thermally protected MOV technology

Regulations & certifications

UL 1449 4th edition VZCA2:E320456

ANSI/IEEE C62.41 Yes

RoHS compliant Yes

Listed by Type 4 UL recognized component (tested to SPD Type 2)

L3L2

L1

G

Page 51: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-51SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—DIN-rail SPDs for distribution panels3-phase wye + N-G

Product features• UL recognized, Type 4 component for Type 2 device• Pluggable modules, fingersafe design - IP20 package• Remote indicator with 3 pin COM/NO/NC contacts• Built-in visual status indicator• Easy installation or retrofit device

Network typeNominal voltage

No. of wires

Max discharge current (Imax, 8/20 μs, kA)

Wiringconfig-uration

Nominal discharge current (In, kA)

MCOVL-L

MCOVL-G

MCOVL-N

VPR

Part number

L-N L-G N-G L-L

208/120V

5 Wire/4 Pole

25kA

3-phase wye,plus N-G

20 360 360 180 600 1200 600 1200 TD120Y4025RMN

50kA 20 360 360 180 600 1200 600 1200 TD120Y4050RMN

480/277V

25kA 20 640 500 320 1000 1500 600 1800 TD277Y4025RMN

50kA 20 640 500 320 1000 1500 600 1800 TD277Y4050RMN

600/347V

25kA 10 840 695 420 1500 2000 900 2500 TD347Y4025RMN

50kA 10 840 695 420 1500 2000 900 2500 TD347Y4050RMN

Electrical characteristics

Modes of protection L-L, L-G, N-G and L-N

Fault rating (SCCR) 200kAIC

Standard monitoring Built-in visual status indicator and dry contacts

Mechanical characteristics

Installation location Type 2, indoor

Mounting method DIN rail

Operating temperature -13° F to 140° F (-25° C to +60° C)

Wire range (stranded/solid) #14 AWG to #6 AWG

Product design Thermally protected MOV technology

Regulations & certifications

UL 1449 4th edition VZCA2:E320456

ANSI/IEEE C62.41 Yes

RoHS compliant Yes

Listed by Type 4 UL recognized component (tested to SPD Type 2)

L1L2

N

L3G

Page 52: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-52 SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—DIN-rail SPDs for distribution panelsHLD system

Product features• UL recognized, Type 4 component for Type 2 device• Pluggable modules, fingersafe design - IP20 package• Remote indicator with 3 pin COM/NO/NC contacts• Built-in visual status indicator• Easy installation or retrofit device

Network type

Nominal voltage

No. of wires

Max discharge current (Imax, 8/20 μs, kA)

Wiringconfig-uration

Nominal discharge current (In, kA)

MCOV VPR

Part number

L-L L-G L-N L-N L-G N-G L-L H-L1 H-N H-G

240/120V

5 Wire/4 Pole

25kA

3-phase high-leg delta

20

***

600 1200 600 1200 1500 900 1500 TD240H4025RM

50kA 600 1200 600 1200 1500 900 1500 TD240H4050RM

480/240V

25kA

10

900 1500 600 1800 2500 1800 2000 TD480H4025RM

50kA 900 1500 600 1800 2500 1800 2000 TD480H4050RM

Electrical characteristics

Modes of protection L-L, L-N and L-G

Fault rating (SCCR) 200kAIC

Standard monitoring Built-in visual status indicator and dry contacts

Mechanical characteristics

Installation location Type 2, indoor

Mounting method DIN rail

Operating temperature -13° F to 140° F (-25° C to +60° C)

Wire range (stranded/solid) #14 AWG to #6 AWG

Product design Thermally protected MOV technology

Regulations & certifications

UL 1449 4th edition VZCA2:E320456

ANSI/IEEE C62.41 Yes

RoHS compliant Yes

Listed by Type 4 UL recognized component (tested to SPD Type 2)

L2L1

N

L3

Page 53: BUYLOG SECTION 5 Surge Protection Devices - ABB · 2020. 9. 11. · SURGE PROTECTION DEVICES, BULOG SECTION 5 5-5 ABB integrated surge protection device Designed to connect within

5-53SURGE PROTECTION DEVICES, BUYLOG SECTION 5

—Protection block assembly

IntroductionThe ABB 427 patented 5 Pin Protection Block Assembly is equipped with a multi-layered printed circuit board, providing a connectorized interface for cable assemblies. It accommodates 25, 50 or 100 pair cable. It is used in many applications, including: central offices, remote switching sites, customer premises and building entrances, to protect telephone and voice/data lines.

When wiring cabinets with conventional wire wrap blocks each block becomes a different part number and causes difficulty for OEMs who have to inventory parts.

The same ABB 427 Protection Block Assembly is used in every position of a cabinet or mainframe. The cables are now treated as less expensive parts and are stocked by length and mating connector type. Manual labor, in running cables and making wire wrap connections, is reduced significantly by employing ABB Connectorized Block Assemblies.

Performance Features - Gold pins and sockets ensure proper electrical

connections - Self-locking aluminum hood (optional) provides

protection to connectors and printed circuit board and serves as the cable strain relief tie point

- Multi-layered printed circuit board - Handle heavy transient current surges - U.S. Patent No. 5,457,593

Benefits - Provides maximum reliability by eliminating all wire wraps - Provides the high quality installation of a protection block - Provides additional flexibility for equipment installations - Easily serviceable in the field - Eliminates the need for wire wrapping - Allows connectorization into many different applications

and greatly reduces installation, labor and repair costs - All cables connected to this unit can be removed,

permitting specific cable change out or change out of the entire protection block assembly. This allows the protected equipment to quickly be put back into service.

- Covered by a two year limited product warranty

Protection Block Assembly

Protection Block Assembly - Surge Protection Device

Pair Block Type HoodProduct Number

50 Marconi Block YES 427-050-202

100 Avaya Block YES 427-100-102

100 Marconi Block YES 427-100-202

100 Corning Block YES 427-100-302

SpecificationsVoltage Class: 600V

BIL rating: 10kV

Primary Currents: 10 to 5000 amps