— BUYLOG SEC TION 10A

Low voltage dry type transformers600V class large power

Page 2: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-2 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

Page 3: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-3LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

— Table of contents

Overview10A-4 Large power transformers

General purpose DOE 2016 efficiency10A-6 Applicable standards10A-7 Single-phase, and NRCan efficiency10A-8 Single-phase, aluminum coil10A-9 Single-phase, copper coil10A-10 Three-phase catalog number nomenclature10A-12 Three-phase, aluminum coil10A-14 Three-phase, copper coil

K-factor DOE 2016 efficiency, shielded10A-15 Three-phase, aluminum coil10A-18 Three-phase, copper coil

K-factor low noise DOE 2016 efficiency, shielded10A-21 Three-phase, aluminum coil10A-23 Three-phase, copper coil

Low noise, DOE 2016 efficiency10A-25 Three-phase, aluminum coil10A-26 Three-phase, copper coil

Noise isolation-Guard I™ DOE 2016 efficiency shielded10A-27 Three-phase, aluminum coil10A-28 Three-phase, copper coil

Noise isolation-Guard II™ DOE 2016 efficiency, shielded10A-29 Three-phase, aluminum coil10A-30 Three-phase, copper coil

Harmonic mitigating-Guard III™ DOE 2016 efficiency shielded10A-31 Three-phase, copper coil

10A-32 Servicenter™ mini-unit substations – Integral transformer and distribution center

10A-33 Single-phase and three-phase DOE 2016 efficiency10A-34 Outlines, dimensions, wiring diagrams

Totally enclosed, nonventilated – TENV10A-35 Aluminum and copper NEMA TP-1 efficiency

Midtapped10A-37 Aluminum DOE 2016 efficiency10A-39 Copper DOE 2016 efficiency

Drive isolation10A-40 Three-phase

10A-42 Accessories and lugs10A-44 Enclosure parts10A-45 Wiring diagrams10A-47 Dimensions

edgardomendoza
Section updated 08/21
Page 4: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-4 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

IntroductionABB’s comprehensive family of low voltage dry type transformers (LVDTT) provide long life, quiet, and reliable operation.

Type QL are ABB’s large power transformers ranging from 15 kVA to 1000 kVA. The QL transformers come in standard NEMA 2 enclosures with rain shield kits available for NEMA 3R installations. Stainless steel enclosures are available as options as well. QL transformers are available in single or Three-phase configurations with either aluminum or copper windings. Type QL’s are DOE 2016 compliant with models available for Canadian NRCan efficiency standards.

All of the LVDTTs through 1,000 kVA are UL listed under the requirements of Standard 5085 and/or 1561. In addition, each transformer meets the requirements of NEMA T-20-2014.

General purpose transformers are rated 600 Volts and below for supplying appliances, lighting, and power loads from electrical distribution systems. Standard distribution voltages are 600, 480, and 240 Volts; standard load voltages are 480, 277, 240, 208, and 120 Volts. The transformer is used to obtain the load voltage from the distribution voltage while providing galvanic isolation. Since no vaults are required for installation, these transformers can be located right at the load to provide the correct voltage for the application. This eliminates the need for long, costly, low voltage feeders.

Construction – Type QLLarge power transformersQL units come standard enclosed in a NEMA 2 drip-proof painted metal enclosure with natural draft ventilation. The core-and-coil assembly is mounted on rubber isolation pads to reduce noise generated by transformer vibration. Rain shield kits are available for conversion to a NEMA 3R enclosure suitable for outdoor service. Type QL transformers are UL Listed: XQNX:E79145; XQNX7:E79145; XQNX2:E79145 or XQNX8:E79145.

Coil construction, 3 phase general purpose, all 100% production testedCoil material

kVA range

Coil temperature

Terminal connections

Windings1

AL

15 to 150 150 Bolted

Continuous

225 to 500 150 Welded15 to 112.5 115 Bolted150 to 500 115 Welded15 to 112.5 80 Bolted150 to 300 80 Welded

CU

15 to 150 150 Bolted

Continuous

225 to 500 150 Welded15 to 150 115 Bolted225 to 500 115 Welded15 to 112.5 80 Bolted150 to 300 80 Welded

1Rarely a coil may have a welded internal connection. All transformers are 100% tested, assuring internal resistance and losses are within established standards, UL and NEMA requirements.

NEMA enclosure ratingsType QL transformers are standard as NEMA 2 painted steel enclosures. NEMA 3R or NEMA 3R stainless steel (316) enclosures are available up to 150 kVA. NEMA 3R includes the rain shield kit (also 316 SS).

NEMA enclosure rating Standard or optional

Installation location

Optional rain shield

NEMA 2 (ANSI 61 Painted) Standard Indoor Not requiredNEMA 2 (316 Stainless Steel)2 Optional Indoor Not required

NEMA 3R (ANSI 61 painted) OptionalIndoor or Outdoor

Required & painted

NEMA 3R (316 Stainless Steel)2 OptionalIndoor or Outdoor

Required & 316 SS

NEMA 4X (316 Stainless Steel)3 OptionalIndoor or Outdoor

Required & 316 SS

2 Up to 150 kVA3 Special order only, must be quoted and not available for all transformers

To specify a stainless-steel enclosure for an aluminum wound transformer, substitute the letter “S” in the fifth character of the ABB product number. For example, 9T10A1004 changes to 9T10S1004. For copper wound transformers substitute the letter “Z” in the fifth character of the ABB product number. For example, 9T10C1004 changes to 9T10Z1004. All QL model product numbers begin with 9T1, 9T6, 9T7 and 9T8.

Transformer tapsTransformer taps compensate for high or low line (supply) voltages. FCAN (full capacity above nominal) and FCBN (full capacity below nominal) are standard on Type QL transformers rated 15 kVA through 300 kVA and with a primary voltage of 240 V or higher. These have a total of six available voltage taps – four 2.5% taps (FCBN) below the nominal tap and two 2.5% taps above (FCAN) the nominal tap. This arrangement provides a 15% range of tap voltage adjustment. Transformers rated 500 kVA and higher have four available voltage taps – two 2.5% taps above (FCAN) the nominal tap and two 2.5% taps below (FCBN) the nominal tap.

Sound levelsAll general purpose transformers are as quiet, or quieter than required by NEMA ST-20. Average sound levels are warranted not to exceed the values listed for each load rating shown in the below table. Sound characteristics vary between transformers of identical voltage and kVA rating. The range of variation may be 4 to 8 decibels.

These values apply only to specified test conditions because the characteristic of the installation can cause them to be higher under operating conditions. Where acoustical noise is deemed to be of concern, proper steps should be taken during installation to minimize audible noise transmission. Please refer to the installation manual for installation and operation recommended practices to minimize the audible sound of the transformer.

If lower sound levels are needed or desired, -3 dB and -5 dB options are available for most models.

Average Sound Level, DecibelsSelf cooled ventilated

Equivalent Winding kVA Range

A BK-factor = 1 K-factor = 4

K-factor = 13 K-factor = 20

9.01 to 15.00 45 4515.01 to 30.00 45 4530.01 to 50.00 45 4850.01 to 75.00 50 5375.01 to 112.50 50 53112.51 to 150.00 50 53150.01 to 225.00 55 58225.01 to 300.00 55 58300.01 to 500.00 60 63500.01 to 700.00 62 65700.01 to 1000.00 64 67

—General and technical informationLarge power transformers600 volts and below

Page 5: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-5LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—General and technical informationLarge power transformers600 volts and below

Insulation systemsIndustry standards classify insulation systems in accordance with the rating system shown below.

Transformer insulation systems

Insulation Rating

Insulation Letter Class (NEMA/UL)

Ambient+ Avg Coil Temp Rise

+ Hot Spot Temp Rise

= Max. Coil Temp

Class 105 A 40 °C 45 °C 20 °C 105 °CClass 155 F 40 °C 95 °C 20 °C 155 °CClass 180 H 40 °C 115 °C 25 °C 180 °CClass 220 R 40 °C 150 °C 30 °C 220 °C

All ABB Type QL (80 °C, 115 °C and 150 °C) DOE and NRCan compliant transformers use 220 °C insulation systems and meet all applicable NEMA, ANSI, UL, and IEEE dry type transformer standards.

The design life of transformers that have different insulation systems is the same, since the allowable temperature rise of an insulation material system is predicated on a specified life for all insulation. The lower temperature systems are designed for the same life as higher temperature systems.

Key to the chart• All assume 40 °C ambient temperature.• Coil temperature rating (Temp Rise) is a typical

specification when choosing a transformer• The Hot Spot is the buffer added for internal hot spots• For large power transformers, an 80 °C temp rise will

cost more than a 150 °C, and will likely last longer• Designing for other ambient temperatures like

50 °C for use in desert regions will increase the cost• Lower coil temp rise = higher price• Higher ambient temp requirement = higher price

Type QL insulation system• Insulation Class: 220 °C, UL recognized insulation system

with a maximum of 150, 115 or 80 °C rise above 40 °C ambient temperature

• Temperature rise ratings are in accordance with UL 1561• All ABB Type QL dry type transformers use a 220 °C

insulation rating class

Catalog number selection instructions1. Establish phase and frequency2. Determine the primary voltage—the voltage presently

available3. Determine the secondary voltage—the voltage needed at

the load4. Determine the kVA load, allowing room for expansion5. Using the facts determined in the four steps, locate the

transformer model in the listings on the following pages.

Large Power: Type QL, 15 kVA-250 kVA, Single-Phase, DOE 2016 Efficiency, 15 kVA-500 kVA, Three-Phase, DOE 2016 Efficiency

Single-Phase Servicenter™Three-Phase Servicenter™Three-Phase Servicenter™Guard III™ Transformer

Page 6: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-6 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—General purposeApplicable standards

ABB dry type transformers conform to the standards asshown above and are in compliance with thesestandards below:

• ANSI/NFPA 70: National Electrical Code• ANSI/IEEE C57.96, Distribution Transformers, Guide for

Loading Dry Type appendix to ANSI C57.12 standards• IEEE C57.12.01: General Requirements for Dry Type

Distribution Transformers• IEEE C57.12.91, Test Code for Dry Type Distribution

Transformers• NEMA ST-20: Dry Type Transformers for General

Applications• UL 1561, Dry Type General Purpose Power Transformer G.

Efficiency level DOE 2016 by 10 CFR PART 431• UL Energy Verification – for US and Canada

(ZXPC: EV519886) (ZZED: EV23760)

ABB’s dry type transformers are manufactured in an ISO 9001 certified plant.

Page 7: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-7LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—General purposeSingle-phase DOE 2016 and NRCan efficiencyCommon transformers

GE by ABB's general purpose single-phase dry type transformers are step-down transformers designed for installations that require a 3-wire secondary voltage for 120/240 V systems. These units can also be used in 2-wire, 120x240 V applications. Their primary voltages are 240x480.

Optional wall mount brackets are available for most models. lug kit and copper ground bar are included.

Aluminum windings 150 °C Rise NEMA 2

Primary Voltage

Secondary Voltage

kVATaps (FCBN,FCAN; %)

Wiring Diagram1

Product Net Weight (lbs.)

FrameSize

CatalogNumber

240 x 480 Volts 120 / 240 Volts

15 (-4,+2: 2.5%) 6 320 YX171 9T33A267025 (-4,+2: 2.5%) 6 320 YX171 9T33A267137.5 (-4,+2: 2.5%) 6 460 YX172 9T33A267250 (-4,+2: 2.5%) 6 490 XV173 9T33A267375 (-4,+2: 2.5%) 25 600 YX174 9T33A2674100 (-4,+2: 2.5%) 26 950 YX175 9T33A2675

Copper windings 150 °C Rise NEMA 2

Primary Voltage

Secondary Voltage

kVATaps (FCBN,FCAN; %)

Wiring Diagram1

Product Net Weight (lbs.)

FrameSize

CatalogNumber

240 x 480 Volts 120 / 240 Volts

15 (-4,+2: 2.5%) 6 350 YX171 9T33C267025 (-4,+2: 2.5%) 6 350 YX171 9T33C267137.5 (-4,+2: 2.5%) 6 510 YX172 9T33C267250 (-4,+2: 2.5%) 6 500 XV173 9T33C267375 (-4,+2: 2.5%) 25 750 YX174 9T33C2674

¹ See page 10A-45 and 10A-46 for wiring diagrams.

Technical characteristics • Connection: 3-wire or 2-wire secondaries• Voltages: (P) 240x480 (S) 120/240• Temperature rise: 150 °C; 220 °C insulation class;

IEC 60085 Class R• Frequency: 60 Hz• Ambient temperature: 40 °C• Standard single-phase tap arrangement• Painted, ANSI #61 gray NEMA 2 enclosure• Type QL• Audible sound level: NEMA ST-20 Standard• Seismic qualifications – CBC 2019 and IBC 2018;

ASCE 7.05-2016• UL 1561• UL & cUL listed (XQNX, XQNX7:E323777)• Energy efficiency: DOE 2016 (10 CFR Part 431)• Energy efficiency: NRCan (CSA 802.2)• UL energy verification – for US and Canada

(ZXPC:EV519886) (ZZED:EV23760)

Type QL Transformer

Page 8: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-8 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

240 x 480 Volts 120 x 240 Volts

15 (+2, -4: 2.5%) 23 320 YF171 9T83B2670²25 (+2, -4: 2.5%) 23 320 YF171 9T83B2671²37.5 (+2, -4: 2.5%) 23 320 YF171 9T83B2672²50 (+2, -4: 2.5%) 23 400 YF172 9T83B2673²75 (+2, -4: 2.5%) 23 510 YF174 9T83B2674²100 (+2, -4: 2.5%) 23 900 YF175 9T83B2675²167 (+2, -4: 2.5%) 23 1360 YF176 9T83B2676²250 (+2, -4: 2.5%) 23 1700 YF177 9T83B2677²

115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

240 x 480 Volts 120 x 240 Volts

15 (+2, -4: 2.5%) 23 320 YF171 9T83B2670G1525 (+2, -4: 2.5%) 23 320 YF171 9T83B2671G1537.5 (+2, -4: 2.5%) 23 400 YF172 9T83B2672G1550 (+2, -4: 2.5%) 23 500 XV173 9T83B2673G1575 (+2, -4: 2.5%) 23 510 YF174 9T83B2674G15100 (+2, -4: 2.5%) 23 900 YF175 9T83B2675G15

80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

240 x 480 Volts 120 x 240 Volts

15 (+2, -4: 2.5%) 23 320 YF171 9T83B2670G8025 (+2, -4: 2.5%) 23 320 YF171 9T83B2671G8050 (+2, -4: 2.5%) 23 510 YF174 9T83B2673G80100 (+2, -4: 2.5%) 23 1360 YF176 9T83B2675G80

¹ See page 10A-45 and 10A-46 for wiring diagrams.² Life Cycle Management stage: Classic

—General purposeAluminum coilSingle-phase DOE 2016 efficiency

Page 9: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-9LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

240 x 480 Volts 120 x 240 Volts

15 (+2, -4: 2.5%) 23 350 YF171 9T83C2570²25 (+2, -4: 2.5%) 23 350 YF171 9T83C2571²37.5 (+2, -4: 2.5%) 23 500 YF172 9T83C2572²50 (+2, -4: 2.5%) 23 520 YF173 9T83C2573²75 (+2, -4: 2.5%) 23 635 YF174 9T83C2574²100 (+2, -4: 2.5%) 23 1050 YF175 9T83C2575²167 (+2, -4: 2.5%) 23 1675 YF176 9T83C2576²

115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

240 x 480 Volts 120 x 240 Volts

15 (+2, -4: 2.5%) 23 350 YF171 9T83C2570G1525 (+2, -4: 2.5%) 23 350 YF171 9T83C2571G1537.5 (+2, -4: 2.5%) 23 500 YF172 9T83C2572G1550 (+2, -4: 2.5%) 23 520 YF173 9T83C2573G1575 (+2, -4: 2.5%) 23 635 YF174 9T83C2574G15100 (+2, -4: 2.5%) 23 1050 YF175 9T83C2575G15167 (+2, -4: 2.5%) 23 1675 YF176 9T83C2576G15

80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

240 x 480 Volts 120 x 240 Volts

15 (+2, -4: 2.5%) 23 350 YF171 9T83C2570G8025 (+2, -4: 2.5%) 23 350 YF171 9T83C2571G8037.5 (+2, -4: 2.5%) 23 500 YF172 9T83C2572G8050 (+2, -4: 2.5%) 23 635 YF174 9T83C2573G80

¹ See page 10A-45 and 10A-46 for wiring diagrams..² Life Cycle Management stage: Classic

—General purposeCopper coilSingle-phase DOE 2016 efficiencyCommon transformers

Page 10: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-10 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

3-Phase Common Voltages

Series Primary Voltage Secondary Voltage100 480 208Y/120101 480 220102 480 220Y/127103 480 208104 480 230Y/133105 480 240Y/139106 480 380107 480 380Y/219108 480 400Y/231109 480 415Y/240110 480 480111 480 575112 480 600113 480 440Y/254114 480 600Y/346115 480 440116 480 230/115117 480 480Y/277118 480 240/120119 480 240121 480 220/110123 480 400124 480 460125 480 420126 480 230127 480 575Y/332129 480 460Y/266131 208 240132 208 240/120133 208 480134 208 480Y/277135 208 380Y/219136 208 230137 208 575138 208 460139 208 400Y/231140 208 208141 208 230Y/133142 208 380143 208 220/110144 208 220Y/127145 208 208Y/120146 208 400147 208 315148 208 600149 208 460Y/266150 208 220151 208 230/115152 208 415Y/240153 240 480Y/277154 240 480155 240 400Y/231

3-Phase Common Voltages

Series Primary Voltage Secondary Voltage157 240 575158 240 460Y/266159 240 240Y/139160 240 600161 240 208Y/120162 240 380163 240 440164 240 240/120165 240 380Y/219166 220 380Y/219167 220 400Y/231168 220 240Y/139169 220 220170 220 208Y/120171 220 480Y/277172 220 440Y/254173 220 480/240174 220 480175 220 415Y/240176 380 220Y/127177 380 480178 380 220179 380 208Y/120180 380 415Y/240181 380 240/120184 380 480Y/277185 380 380Y/219186 380 230Y/133187 380 240188 440 220Y/127189 440 480190 440 208Y/120191 440 380192 440 380Y/219193 440 400Y/231194 440 575Y/332195 440 240/120196 440 480Y/277197 440 240198 230 460199 230 400Y/231200 230 400201 230 480Y/277202 230 208Y/120203 230 480204 400 230Y/133205 400 380Y/219206 400 480207 400 220Y/127209 400 400Y/231210 400 208Y/120211 400 208Y/120

3-Phase Common Voltages

Series Primary Voltage Secondary Voltage212 400 480Y/277213 415 208Y/120214 415 460215 415 220Y/127216 416 208Y/120217 416 480Y/277218 460 208Y/120219 460 220221 460 400Y/231222 460 220Y/127223 460 230224 460 575Y/332225 460 230Y/133226 460 460Y/266227 550 208Y/120228 550 480Y/277229 575 208Y/120230 575 480Y/277231 575 240Y/139232 575 460233 575 480234 575 230Y/133235 575 230236 600 240/120237 600 480238 600 480Y/277239 600 240240 600 208Y/120241 600 230Y/133242 600 240Y/139243 600 208244 600 600Y/346245 690 400Y/231246 690 208Y/120247 277 415Y/240248 315 208Y/120249 320 480Y/277250 420 480Y/277251 490 480Y/277252 500 480Y/277

—General purposeThree-phaseDOE 2016 catalog number nomenclature

ABB Standard

1 = QL DOE 2016 Design

Transformer Type0 = Standard, K11 = K132 = K204 = K47 = Guard II/Servicenter8 = Spare Parts

OptionsA = Aluminum CoilB1 = Aluminum C&C (no enclosure)C = Copper CoilS = AL Stainless Steel EnclosureV1 = Copper C&C (no enclosure)Z = CU Stainless Steel EnclosureY = Accessories

kVA Rating1 = 15 kVA2 = 30 kVA3 = 45 kVA4 = 75 kVA5 = 112.5 kVA6 = 150 kVA7 = 225 kVA8 = 300 kVA9 = 500 kVA

Catalog No. Suffix CodesCore & Coil Temp Rise150 °C 115 °C 80 °C

Co

re &

Co

il C

hara

cter

isti

cs

Temp Rise Rating Only G01 or blank G31 G61

-3 dB noise reduction G02 G32 G62

Electrostatic Shield* G03 G33 G63

-3 dB noise reduction + Electrostatic Shield G04 G34 G64

-5 dB noise reduction G05 G35 G65

-5 dB noise reduction + Electrostatic Shield G06 G36 G66

* An Electrostatic Shield (a Guard I transformer) is bonded to the ground terminal and is a copper barrier between the primary and secondary windings to reduce electrical noise. All K-factor transformers come standard with an Electrostatic Shield (K4, K13, K20).

Voltage SeriesSee Voltage Chart below

9T 1 0 A 1 G31100

1These options are UL recognized components.

Please Note: This catalog number nomenclature is for illustrative purposes only. Not all catalog number combinations are available for production. Please reference the ordering tables beginning on page 10A-12 for Three-phase DOE 2016 Efficiency transformers currently available for ordering. For additional assistance, please contact Customer Service at 1-800-431-7867.

Page 11: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-11LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

Advantages - Quiet performance - No-weld design - IEEE and NEMA factory testing assures quality - Accessible mounting foot design speeds installation - Lug kit and ground bar kit included up through 150 kVA - ABB’s exclusive wood crate packaging (up to 150 kVA)

helps reduce shipping damage

Key features

- Unique core and coil design makes QL transformers among the quietest available

- Core and coil assemblies are mounted on rubber isola-tion pads to reduce audible noise

- Single-piece front/back is easily removable for service - Accessible mounting flanges with front/back slotted

mounting holes make installation easier - 100% factory tested for shorts and coil integrity, cur-

rent and loss, voltage, impedance and noise. - NEMA 2 drip-proof enclosure is standard. Paint color is

ANSI #61 gray. Rain shield kits are available to convert standard NEMA 2 transformers to NEMA 3R for outdoor installations.

- NEMA 3R stainless steel enclosure is available up to 150 kVA. To specify a stainless steel enclosure, substi-tute the fifth character in the ABB catalog number per the following examples:

- For Aluminum coil: 9T10A1004 changes to 9T10S1004 - For Copper coil: 9T10C1004 changes to 9T10Z1004

- Seismic qualified to the requirements of ASCE 7-16, IEEE-693-2005 and IBC-2018/CBC-2019

- Copper or aluminum windings - Copper ground strap - Optional Individualized Test Reports available for IEEE

performance and/or NEMA ST-20 Audible Sound Levels

Applications

- Commercial - Industrial - Motors - Incandescent lighting - Resistance heating - Motor generators (without solid state drives) - Galvanic isolation - Power supply network conversion

Stan

dar

d

Gua

rd I™

El

ectr

ost

atic

Shi

eld

Gua

rd II

™ (f

ilter

ing

& s

urg

e p

rote

ctio

n)

Gua

rd II

I™ H

arm

oni

c M

itig

atin

g (H

MT

)

K -f

acto

r (K

=4)

K -f

acto

r (K

=13)

K -f

acto

r (K

=20)

Dri

ve Is

ola

tio

n

Serv

icen

ter™

TEN

V

Motors • • •Incandescent Lighting • • •Resistance Heating • • •Motor Generators (without solid state drives) • • •HID Lighting •Induction Heaters •Welders •UPS with optional input filtering •PLC & Solid state controls •Multiple receptacle circuits in heath care facilities •UPS without optional input filtering •Production or assembly line equipment •Schools & Classroom facilities •Surge Supression •Office Buildings • • • •SCR Variable Speed Drives •Circuits with exclusive data processing equipment • • •Critical Care facilities • • •Hospital Operating Rooms • • •X-ray equipment • • •Computer Installations • • •Programmable Controllers • • •Instrumentation • • •AC or DC Variable Speed Drives •Rectifier outputs •Temporary Power •Airborne contamins or dust-laden environments (indoor and outdoor) •

QL Transformer Selection Guide

—General purposeThree-phase DOE 2016 efficiency

Page 12: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-12 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—General purposeAluminum coilThree-phase DOE 2016 efficiency

K = 1 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T10A100130 (+2, -4: 2.5%) 12 330 UX72A 9T10A100245 (+2, -4: 2.5%) 12 444 UX73A 9T10A100375 (+2, -4: 2.5%) 12 561 UY74A 9T10A1004112.5 (+2, -4: 2.5%) 12 680 DY75A 9T10A1005150 (+2, -4: 2.5%) 12 1030 DY76A 9T10A1006225 (+2, -4: 2.5%) 12 1450 DY77A 9T10A1007300 (+2, -4: 2.5%) 12 1670 DY78A 9T10A1008500 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1009

K = 1 115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T10A1001G3130 (+2, -4: 2.5%) 12 330 UX72A 9T10A1002G3145 (+2, -4: 2.5%) 12 444 UX73A 9T10A1003G3175 (+2, -4: 2.5%) 12 603 UX74A 9T10A1004G31112.5 (+2, -4: 2.5%) 12 830 DX75A 9T10A1005G31150 (+2, -4: 2.5%) 12 1250 DX76A 9T10A1006G31225 (+2, -4: 2.5%) 12 1670 DX77A 9T10A1007G31300 (+2, -4: 2.5%) 12 1985 DX78A 9T10A1008G31500 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1009G31

K = 1 80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 330 UX72A 9T10A1001G6130 (+2, -4: 2.5%) 12 444 UX73A 9T10A1002G6145 (+2, -4: 2.5%) 12 561 UY74A 9T10A1003G6175 (+2, -4: 2.5%) 12 680 DY75A 9T10A1004G61112.5 (+2, -4: 2.5%) 12 1030 DY76A 9T10A1005G61150 (+2, -4: 2.5%) 12 1450 DY77A 9T10A1006G61225 (+2, -4: 2.5%) 12 1985 DX78A 9T10A1007G61300 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1008G61500 (+2, -2: 2.5%) 12 - DX67A 9T10A1009G61

K = 1 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

208 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T10A145130 (+2, -4: 2.5%) 12 330 UX72A 9T10A145245 (+2, -4: 2.5%) 12 561 UY74A 9T10A145375 (+2, -4: 2.5%) 12 680 DY75A 9T10A1454112.5 (+2, -4: 2.5%) 12 1030 DY76A 9T10A1455150 (+2, -4: 2.5%) 12 1250 DX76A 9T10A1456225 (+2, -4: 2.5%) 12 1670 DY78A 9T10A1457300 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1458

¹ See page 10A-45 and 10A-46 for wiring diagrams.

Type QL Transformer

Page 13: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-13LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—General purposeAluminum coilThree-phase DOE 2016 efficiency

K = 1 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

208 Volts Delta 480Y/277 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T10A134130 (+2, -4: 2.5%) 12 330 UX72A 9T10A134245 (+2, -4: 2.5%) 12 561 UY74A 9T10A134375 (+2, -4: 2.5%) 12 680 UY74A 9T10A1344112.5 (+2, -4: 2.5%) 12 1030 DY76A 9T10A1345150 (+2, -4: 2.5%) 12 1250 DX76A 9T10A1346225 (+2, -4: 2.5%) 12 1670 DY78A 9T10A1347300 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1348

K = 1 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

240 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T10A161130 (+2, -4: 2.5%) 12 330 UX72A 9T10A161245 (+2, -4: 2.5%) 12 444 UX73A 9T10A161375 (+2, -4: 2.5%) 12 561 UY74A 9T10A1614112.5 (+2, -4: 2.5%) 12 680 DY75A 9T10A1615150 (+2, -4: 2.5%) 12 1030 DY76A 9T10A1616225 (+2, -4: 2.5%) 12 1450 DY77A 9T10A1617300 (+2, -4: 2.5%) 12 1670 DY78A 9T10A1618500 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1619

K = 1 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

240 Volts Delta 480Y/277 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T10A153130 (+2, -4: 2.5%) 12 330 UX72A 9T10A153245 (+2, -4: 2.5%) 12 444 UX73A 9T10A153375 (+2, -4: 2.5%) 12 561 UY74A 9T10A1534112.5 (+2, -4: 2.5%) 12 680 DY75A 9T10A1535150 (+2, -4: 2.5%) 12 1030 DY76A 9T10A1536225 (+2, -4: 2.5%) 12 1450 DY77A 9T10A1537300 (+2, -4: 2.5%) 12 1670 DY78A 9T10A1538500 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1539

K = 1 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 240/120 Volts

15 (+2, -4: 2.5%) 19 231 UX71A 9T10A118130 (+2, -4: 2.5%) 19 330 UX72A 9T10A118245 (+2, -4: 2.5%) 19 444 UX73A 9T10A118375 (+2, -4: 2.5%) 19 561 UY74A 9T10A1184112.5 (+2, -4: 2.5%) 19 830 DX75A 9T10A1185150 (+2, -4: 2.5%) 19 1030 DY76A 9T10A1186225 (+2, -4: 2.5%) 19 1450 DY77A 9T10A1187300 (+2, -4: 2.5%) 19 1670 DY78A 9T10A1188500 (+2, -2: 2.5%) 19 2900 DX79A 9T10A1189

K = 1 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 480Y/277 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T10A117130 (+2, -4: 2.5%) 12 330 UX72A 9T10A117245 (+2, -4: 2.5%) 12 444 UX73A 9T10A117375 (+2, -4: 2.5%) 12 561 UY74A 9T10A1174112.5 (+2, -4: 2.5%) 12 680 DY75A 9T10A1175150 (+2, -4: 2.5%) 12 1030 DY76A 9T10A1176225 (+2, -4: 2.5%) 12 1450 DY77A 9T10A1177300 (+2, -4: 2.5%) 12 1670 DY78A 9T10A1178500 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1179

¹ See page 10A-45 and 10A-46 for wiring diagrams.

Page 14: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-14 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—General purposeCopper coilThree-phase DOE 2016 efficiency

K = 1 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 240 Volts

15 (+2, -4: 2.5%) 13 230 UX71C 9T10C119130 (+2, -4: 2.5%) 13 353 UX72C 9T10C119245 (+2, -4: 2.5%) 13 480 UX73C 9T10C119375 (+2, -4: 2.5%) 13 661 UY74C 9T10C1194112.5 (+2, -4: 2.5%) 13 790 DY75C 9T10C1195150 (+2, -4: 2.5%) 13 1085 DY76C 9T10C1196225 (+2, -4: 2.5%) 13 1610 DY77C 9T10C1197300 (+2, -4: 2.5%) 13 1970 DY78C 9T10C1198

K = 1 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

600 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 230 UX71C 9T10C240130 (+2, -4: 2.5%) 12 353 UX72C 9T10C240245 (+2, -4: 2.5%) 12 480 UX73C 9T10C240375 (+2, -4: 2.5%) 12 661 UY74C 9T10C2404112.5 (+2, -4: 2.5%) 12 790 DY75C 9T10C2405150 (+2, -4: 2.5%) 12 1085 DY76C 9T10C2406

K = 1 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 230 UX71C 9T10C100130 (+2, -4: 2.5%) 12 353 UX72C 9T10C100245 (+2, -4: 2.5%) 12 480 UX73C 9T10C100375 (+2, -4: 2.5%) 12 661 UY74C 9T10C1004112.5 (+2, -4: 2.5%) 12 790 DY75C 9T10C1005150 (+2, -4: 2.5%) 12 1085 DY76C 9T10C1006225 (+2, -4: 2.5%) 12 1610 DY77C 9T10C1007300 (+2, -4: 2.5%) 12 1970 DY78C 9T10C1008500 (+2, -2: 2.5%) 12 3720 DX79C 9T10C1009

K = 1 115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 230 UX71C 9T10C1001G3130 (+2, -4: 2.5%) 12 353 UX72C 9T10C1002G3145 (+2, -4: 2.5%) 12 480 UX73C 9T10C1003G3175 (+2, -4: 2.5%) 12 748 UX74C 9T10C1004G31112.5 (+2, -4: 2.5%) 12 900 DX75C 9T10C1005G31150 (+2, -4: 2.5%) 12 1240 DX76C 9T10C1006G31225 (+2, -4: 2.5%) 12 1847 DX77C 9T10C1007G31300 (+2, -4: 2.5%) 12 2150 DX78C 9T10C1008G31

K = 1 80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 353 UX72C 9T10C1001G6130 (+2, -4: 2.5%) 12 480 UX73C 9T10C1002G6145 (+2, -4: 2.5%) 12 661 UY74C 9T10C1003G6175 (+2, -4: 2.5%) 12 790 DY75C 9T10C1004G61112.5 (+2, -4: 2.5%) 12 1085 DY76C 9T10C1005G61150 (+2, -4: 2.5%) 12 1610 DY77C 9T10C1006G61225 (+2, -4: 2.5%) 12 2150 DX78C 9T10C1007G61300 (+2, -2: 2.5%) 12 3720 DX79C 9T10C1008G61

¹ See page 10A-45 and 10A-46 for wiring diagrams.

Page 15: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-15LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

Product descriptionK-factor is a standardized way to indicate the ability of a transformer to withstand harmonics. These units shall not exceed rated winding temperature rise at full load and rated K-factor. Neutrals and lugs are capable of handling 200% of rated secondary phase current.

Full-width copper electrostatic shielding is standard on all ABB K-factor rated transformers. Effective coupling ca-pacitance is 30 pf. Common mode noise attenuation averag-es 120 dB, and transverse mode noise attenuation averages 30 dB.

ApplicationsFor commercial applications with significant nonlinear electronic loading, use K=4 for systems with 50% connected nonlinear electronic loads; K=13 for systems with 100% connected nonlinear electronic loads.

Higher K-factor rated units are available for unique applications.

—K-factorAluminum coilThree-phase DOE 2016 efficiencyElectrostatic shield

Type QL, UL K-factor Transformer

K=4 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T14A1001G0330 (+2, -4: 2.5%) 12 444 UX73A 9T14A1002G0345 (+2, -4: 2.5%) 12 444 UX73A 9T14A1003G0375 (+2, -4: 2.5%) 12 680 DY75A 9T14A1004G03112.5 (+2, -4: 2.5%) 12 1030 DY76A 9T14A1005G03150 (+2, -4: 2.5%) 12 1250 DX76A 9T14A1006G03225 (+2, -4: 2.5%) 12 1670 DY78A 9T14A1007G03300 (+2, -2: 2.5%) 12 2900 DX79A 9T14A1008G03

K=4 115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T14A1001G3330 (+2, -4: 2.5%) 12 444 UX73A 9T14A1002G3345 (+2, -4: 2.5%) 12 561 UY74A 9T14A1003G3375 (+2, -4: 2.5%) 12 680 DY75A 9T14A1004G33112.5 (+2, -4: 2.5%) 12 1030 DY76A 9T14A1005G33150 (+2, -4: 2.5%) 12 1250 DX76A 9T14A1006G33225 (+2, -4: 2.5%) 12 1670 DY78A 9T14A1007G33300 (+2, -2: 2.5%) 12 2900 DX79A 9T14A1008G33

K=4 80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

30 (+2, -4: 2.5%) 12 444 UX73A 9T14A1002G6345 (+2, -4: 2.5%) 12 561 UY74A 9T14A1003G6375 (+2, -4: 2.5%) 12 830 DX75A 9T14A1004G63112.5 (+2, -4: 2.5%) 12 1250 DX76A 9T14A1005G63

¹ See page 10A-45 and 10A-46 for wiring diagrams.

Page 16: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-16 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—K-factorAluminum coilThree-phase DOE 2016 efficiencyElectrostatic shield

K=13 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

45 (+2, -4: 2.5%) 12 444 UX73A 9T11A1003G0375 (+2, -4: 2.5%) 12 603 UX74A 9T11A1004G03112.5 (+2, -4: 2.5%) 12 1030 DY76A 9T11A1005G03150 (+2, -4: 2.5%) 12 1250 DX76A 9T11A1006G03225 (+2, -4: 2.5%) 12 1670 DY78A 9T11A1007G03300 (+2, -2: 2.5%) 12 2900 DX79A 9T11A1008G03

K=13 115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

30 (+2, -4: 2.5%) 12 444 UX73A 9T11A1002G3375 (+2, -4: 2.5%) 12 680 DY75A 9T11A1004G33112.5 (+2, -4: 2.5%) 12 1250 DX76A 9T11A1005G33150 (+2, -4: 2.5%) 12 1450 DY77A 9T11A1006G33225 (+2, -4: 2.5%) 12 1670 DY78A 9T11A1007G33300 (+2, -2: 2.5%) 12 2900 DX79A 9T11A1008G33

K=13 80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

30 (+2, -4: 2.5%) 12 561 UY74A 9T11A1002G6345 (+2, -4: 2.5%) 12 561 UY74A 9T11A1003G6375 (+2, -4: 2.5%) 12 830 DX75A 9T11A1004G63112.5 (+2, -4: 2.5%) 12 1670 DX77A 9T11A1005G63150 (+2, -4: 2.5%) 12 1670 DY78A 9T11A1006G63225 (+2, -2: 2.5%) 12 2900 DX79A 9T11A1007G63

¹ See page 10A-45 and 10A-46 for wiring diagrams.

Page 17: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-17LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—K-factorAluminum coilThree-phase DOE 2016 efficiencyElectrostatic shield

K=20 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

45 (+2, -4: 2.5%) 12 561 UY74A 9T12A1003G0375 (+2, -4: 2.5%) 12 ² ² 9T12A1004G03112.5 (+2, -4: 2.5%) 12 1250 DX76A 9T12A1005G03150 (+2, -4: 2.5%) 12 1450 DY77A 9T12A1006G03225 (+2, -4: 2.5%) 12 1670 DY78A 9T12A1007G03

K=20 115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

30 (+2, -4: 2.5%) 12 561 UY74A 9T12A1003G3375 (+2, -4: 2.5%) 12 680 DY75A 9T12A1004G33112.5 (+2, -4: 2.5%) 12 ² ² 9T12A1005G33150 (+2, -4: 2.5%) 12 ² ² 9T12A1006G33225 (+2, -4: 2.5%) 12 ² ² 9T12A1007G33300 (+2, -4: 2.5%) 12 ² ² 9T12A1008G33

K=20 80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

30 (+2, -4: 2.5%) 12 ² ² 9T12A1002G63 45 (+2, -4: 2.5%) 12 ² ² 9T12A1003G63 75 (+2, -4: 2.5%) 12 830 DX75A 9T12A1004G63 112.5 (+2, -4: 2.5%) 12 ² ² 9T12A1005G63 150 (+2, -4: 2.5%) 12 1670 DX77A 9T12A1006G63 225 (+2, -4: 2.5%) 12 ² ² 9T12A1007G63 300 (+2, -4: 2.5%) 12 ² ² 9T12A1008G63

¹ See page 10A-45 and 10A-46 for wiring diagrams.² Contact Customer Service for more information on these transformers.

Page 18: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-18 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—K-factorCopper coilThree-phase DOE 2016 efficiencyElectrostatic shield

K=4 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 230 UX71C 9T14C1001G0330 (+2, -4: 2.5%) 12 353 UX72C 9T14C1002G0345 (+2, -4: 2.5%) 12 480 UX73C 9T14C1003G0375 (+2, -4: 2.5%) 12 661 UY74C 9T14C1004G03112.5 (+2, -4: 2.5%) 12 790 DY75C 9T14C1005G03150 (+2, -4: 2.5%) 12 1610 DY77C 9T14C1006G03225 (+2, -4: 2.5%) 12 1847 DX77C 9T14C1007G03300 (+2, -2: 2.5%) 12 3720 DX79C 9T14C1008G03

K=4 115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 353 UX72C 9T14C1001G3330 (+2, -4: 2.5%) 12 480 UX73C 9T14C1002G3345 (+2, -4: 2.5%) 12 661 UY74C 9T14C1003G3375 (+2, -4: 2.5%) 12 748 UX74C 9T14C1004G33112.5 (+2, -4: 2.5%) 12 900 DX75C 9T14C1005G33150 (+2, -4: 2.5%) 12 1610 DY77C 9T14C1006G33225 (+2, -4: 2.5%) 12 2150 DX78C 9T14C1007G33300 (+2, -2: 2.5%) 12 3720 DX79C 9T14C1008G33500 (+2, -2: 2.5%) 12 ² ² 9T14C1009G33

K=4 80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 353 UX72C 9T14C1001G6330 (+2, -4: 2.5%) 12 480 UX73C 9T14C1002G6345 (+2, -4: 2.5%) 12 661 UY74C 9T14C1003G6375 (+2, -4: 2.5%) 12 790 DY75C 9T14C1004G63112.5 (+2, -4: 2.5%) 12 1085 DY76C 9T14C1005G63150 (+2, -4: 2.5%) 12 1610 DY77C 9T14C1006G63225 (+2, -4: 2.5%) 12 2150 DX78C 9T14C1007G63300 (+2, -2: 2.5%) 12 3720 DX79C 9T14C1008G63

¹ See page 10A-45 and 10A-46 for wiring diagrams.² Contact Customer Service for more information on these transformers.

Page 19: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-19LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—K-factorCopper coilThree-phase DOE 2016 efficiencyElectrostatic shield

K=13 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 230 UX71C 9T11C1001G0330 (+2, -4: 2.5%) 12 353 UX72C 9T11C1002G0345 (+2, -4: 2.5%) 12 480 UX73C 9T11C1003G0375 (+2, -4: 2.5%) 12 790 DY75C 9T11C1004G03112.5 (+2, -4: 2.5%) 12 790 DY75C 9T11C1005G03150 (+2, -4: 2.5%) 12 1610 DY77C 9T11C1006G03225 (+2, -4: 2.5%) 12 2150 DX78C 9T11C1007G03300 (+2, -2: 2.5%) 12 3720 DX79C 9T11C1008G03

K=13 115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 353 UX72C 9T11C1001G3330 (+2, -4: 2.5%) 12 480 UX73C 9T11C1002G3345 (+2, -4: 2.5%) 12 661 UY74C 9T11C1003G3375 (+2, -4: 2.5%) 12 790 DY75C 9T11C1004G33112.5 (+2, -4: 2.5%) 12 1085 DY76C 9T11C1005G33150 (+2, -4: 2.5%) 12 1610 DY77C 9T11C1006G33225 (+2, -4: 2.5%) 12 3720 DX79C 9T11C1007G33300 (+2, -2: 2.5%) 12 3720 DX79C 9T11C1008G33500 (+2, -2: 2.5%) 12 ² ² 9T11C1009G33

K=13 80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 353 UX72C 9T11C1001G6330 (+2, -4: 2.5%) 12 480 UX73C 9T11C1002G6345 (+2, -4: 2.5%) 12 661 UY74C 9T11C1003G6375 (+2, -4: 2.5%) 12 790 DY75C 9T11C1004G63112.5 (+2, -4: 2.5%) 12 1085 DY76C 9T11C1005G63150 (+2, -4: 2.5%) 12 1610 DY77C 9T11C1006G63225 (+2, -2: 2.5%) 12 3720 DX79C 9T11C1007G63300 (+2, -4: 2.5%) 12 ² ² 9T11C1008G63

¹ See page 10A-45 and 10A-46 for wiring diagrams.² Contact Customer Service for more information on these transformers.

Page 20: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-20 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—K-factorCopper coilThree-phase DOE 2016 efficiencyElectrostatic shield

K=20 150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 230 UX71C 9T12C1001G0330 (+2, -4: 2.5%) 12 480 UX73C 9T12C1002G0345 (+2, -4: 2.5%) 12 661 UY74C 9T12C1003G0375 (+2, -4: 2.5%) 12 790 DY75C 9T12C1004G03112.5 (+2, -4: 2.5%) 12 1085 DY76C 9T12C1005G03150 (+2, -4: 2.5%) 12 ² ² 9T12C1006G03225 (+2, -4: 2.5%) 12 ² ² 9T12C1007G03300 (+2, -4: 2.5%) 12 ² ² 9T12C1008G03

K=20 115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 353 UX72C 9T12C1001G3330 (+2, -4: 2.5%) 12 ² ² 9T12C1002G3345 (+2, -4: 2.5%) 12 661 UY74C 9T12C1003G3375 (+2, -4: 2.5%) 12 790 DY75C 9T12C1004G33112.5 (+2, -4: 2.5%) 12 ² ² 9T12C1005G33150 (+2, -4: 2.5%) 12 ² ² 9T12C1006G33225 (+2, -4: 2.5%) 12 2150 DX78C 9T12C1007G33300 (+2, -4: 2.5%) 12 ² ² 9T12C1008G33

K=20 80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 ² ² 9T12C1001G6330 (+2, -4: 2.5%) 12 480 UX73C 9T12C1002G6345 (+2, -4: 2.5%) 12 ² ² 9T12C1003G6375 (+2, -4: 2.5%) 12 ² ² 9T12C1004G63112.5 (+2, -4: 2.5%) 12 ² ² 9T12C1005G63150 (+2, -4: 2.5%) 12 ² ² 9T12C1006G63

¹ See page 10A-45 and 10A-46 for wiring diagrams.² Contact Customer Service for more information on these transformers.

Page 21: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-21LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—K-factor low noise (-3 dB below NEMA ST-20 standard)Aluminum coilThree-phase DOE 2016 efficiencyElectrostatic shield

K=4 150°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T14A1001G0430 (+2, -4: 2.5%) 12 444 UX73A 9T14A1002G0445 (+2, -4: 2.5%) 12 444 UX73A 9T14A1003G0475 (+2, -4: 2.5%) 12 603 UX74A 9T14A1004G04112.5 (+2, -4: 2.5%) 12 1030 DY76A 9T14A1005G04150 (+2, -4: 2.5%) 12 1250 DX76A 9T14A1006G04225 (+2, -4: 2.5%) 12 1670 DY78A 9T14A1007G04300 (+2, -2: 2.5%) 12 2900 DX79A 9T14A1008G04

K=4 115°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T14A1001G3430 (+2, -4: 2.5%) 12 444 UX73A 9T14A1002G3445 (+2, -4: 2.5%) 12 561 UY74A 9T14A1003G3475 (+2, -4: 2.5%) 12 680 DY75A 9T14A1004G34112.5 (+2, -4: 2.5%) 12 1030 DY76A 9T14A1005G34150 (+2, -4: 2.5%) 12 1250 DX76A 9T14A1006G34225 (+2, -4: 2.5%) 12 1670 DY78A 9T14A1007G34300 (+2, -2: 2.5%) 12 2900 DX79A 9T14A1008G34

K=4 80°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts112.5 (+2, -4: 2.5%) 12 1250 DX76A 9T14A1005G64150 (+2, -4: 2.5%) 12 1670 DX77A 9T14A1006G64

K=13 150°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T11A1001G0430 (+2, -4: 2.5%) 12 444 UX73A 9T11A1002G0445 (+2, -4: 2.5%) 12 444 UX73A 9T11A1003G0475 (+2, -4: 2.5%) 12 603 UX74A 9T11A1004G04112.5 (+2, -4: 2.5%) 12 1030 DY76A 9T11A1005G04150 (+2, -4: 2.5%) 12 1250 DX76A 9T11A1006G04225 (+2, -4: 2.5%) 12 1670 DY78A 9T11A1007G04300 (+2, -2: 2.5%) 12 2900 DX79A 9T11A1008G04

K=13 115°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T11A1001G3430 (+2, -4: 2.5%) 12 444 UX73A 9T11A1002G3445 (+2, -4: 2.5%) 12 561 UY74A 9T11A1003G3475 (+2, -4: 2.5%) 12 680 DY75A 9T11A1004G34112.5 (+2, -4: 2.5%) 12 1250 DX76A 9T11A1005G34150 (+2, -4: 2.5%) 12 1450 DY77A 9T11A1006G34225 (+2, -4: 2.5%) 12 1670 DY78A 9T11A1007G34300 (+2, -2: 2.5%) 12 2900 DX79A 9T11A1008G34

K=13 80°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

30 (+2, -4: 2.5%) 12 561 UY74A 9T11A1002G6445 (+2, -4: 2.5%) 12 561 UY74A 9T11A1003G6475 (+2, -4: 2.5%) 12 680 DY75A 9T11A1004G64112.5 (+2, -4: 2.5%) 12 1670 DX77A 9T11A1005G64

¹ See page 10A-45 and 10A-46 for wiring diagrams.

Page 22: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-22 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—K-factor low noise (-3 dB below NEMA ST-20 standard)Aluminum coilThree-phase DOE 2016 efficiencyElectrostatic shield

K=20 150°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 ² ² 9T12A1001G0430 (+2, -4: 2.5%) 12 ² ² 9T12A1002G0445 (+2, -4: 2.5%) 12 ² ² 9T12A1003G0475 (+2, -4: 2.5%) 12 ² ² 9T12A1004G04112.5 (+2, -4: 2.5%) 12 ² ² 9T12A1005G04150 (+2, -4: 2.5%) 12 ² ² 9T12A1006G04225 (+2, -4: 2.5%) 12 ² ² 9T12A1007G04

K=20 115°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 ² ² 9T12A1001G3430 (+2, -4: 2.5%) 12 ² ² 9T12A1002G3445 (+2, -4: 2.5%) 12 ² ² 9T12A1003G3475 (+2, -4: 2.5%) 12 ² ² 9T12A1004G34112.5 (+2, -4: 2.5%) 12 ² ² 9T12A1005G34

K=20 80°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 ² ² 9T12A1001G6430 (+2, -4: 2.5%) 12 ² ² 9T12A1002G6445 (+2, -4: 2.5%) 12 ² ² 9T12A1003G6475 (+2, -4: 2.5%) 12 ² ² 9T12A1004G64112.5 (+2, -4: 2.5%) 12 ² ² 9T12A1005G64

¹ See page 10A-45 and 10A-46 for wiring diagrams.² Contact Customer Service for more information on these transformers.

Page 23: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-23LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—K-factor low noise (-3 dB below NEMA ST-20 standard)Copper coilThree-phase DOE 2016 efficiencyElectrostatic shield

K=4 150°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 230 UX71C 9T14C1001G0430 (+2, -4: 2.5%) 12 353 UX72C 9T14C1002G0445 (+2, -4: 2.5%) 12 480 UX73C 9T14C1003G0475 (+2, -4: 2.5%) 12 661 UY74C 9T14C1004G04112.5 (+2, -4: 2.5%) 12 790 DY75C 9T14C1005G04150 (+2, -4: 2.5%) 12 1610 DY77C 9T14C1006G04225 (+2, -4: 2.5%) 12 1970 DY78C 9T14C1007G04300 (+2, -2: 2.5%) 12 3720 DX79C 9T14C1008G04

K=4 115°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 353 UX72C 9T14C1001G3430 (+2, -4: 2.5%) 12 353 UX72C 9T14C1002G3445 (+2, -4: 2.5%) 12 661 UY74C 9T14C1003G3475 (+2, -4: 2.5%) 12 790 DY75C 9T14C1004G34112.5 (+2, -4: 2.5%) 12 900 DX75C 9T14C1005G34150 (+2, -4: 2.5%) 12 1610 DY77C 9T14C1006G34225 (+2, -4: 2.5%) 12 2150 DX78C 9T14C1007G34300 (+2, -2: 2.5%) 12 3720 DX79C 9T14C1008G34

K=4 80°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 353 UX72C 9T14C1001G6430 (+2, -4: 2.5%) 12 480 UX73C 9T14C1002G6445 (+2, -4: 2.5%) 12 661 UY74C 9T14C1003G6475 (+2, -4: 2.5%) 12 790 DY75C 9T14C1004G64112.5 (+2, -4: 2.5%) 12 1240 DX76C 9T14C1005G64

K=13 150°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 230 UX71C 9T11C1001G0430 (+2, -4: 2.5%) 12 353 UX72C 9T11C1002G0445 (+2, -4: 2.5%) 12 480 UX73C 9T11C1003G0475 (+2, -4: 2.5%) 12 790 DY75C 9T11C1004G04112.5 (+2, -4: 2.5%) 12 790 DY75C 9T11C1005G04150 (+2, -4: 2.5%) 12 1610 DY77C 9T11C1006G04225 (+2, -4: 2.5%) 12 1970 DY78C 9T11C1007G04300 (+2, -2: 2.5%) 12 3720 DX79C 9T11C1008G04

K=13 115°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 353 UX72C 9T11C1001G3430 (+2, -4: 2.5%) 12 480 UX73C 9T11C1002G3445 (+2, -4: 2.5%) 12 661 UY74C 9T11C1003G3475 (+2, -4: 2.5%) 12 790 DY75C 9T11C1004G34112.5 (+2, -4: 2.5%) 12 1085 DY76C 9T11C1005G34150 (+2, -4: 2.5%) 12 1610 DY77C 9T11C1006G34225 (+2, -2: 2.5%) 12 3720 DX79C 9T11C1007G34300 (+2, -2: 2.5%) 12 3720 DX79C 9T11C1008G34

K=13 80°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 353 UX72C 9T11C1001G6430 (+2, -4: 2.5%) 12 661 UY74C 9T11C1002G6445 (+2, -4: 2.5%) 12 661 UY74C 9T11C1003G6475 (+2, -4: 2.5%) 12 790 DY75C 9T11C1004G64112.5 (+2, -4: 2.5%) 12 1240 DX76C 9T11C1005G64150 (+2, -4: 2.5%) 12 1610 DY77C 9T11C1006G64225 (+2, -2: 2.5%) 12 3720 DX79C 9T11C1007G64

¹ See page 10A-45 and 10A-46 for wiring diagrams.

Page 24: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-24 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—K-factor low noise (-3 dB below NEMA ST-20 standard)Copper coilThree-phase DOE 2016 efficiencyElectrostatic shield

K=20 150°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 ² ² 9T12C1001G0430 (+2, -4: 2.5%) 12 ² ² 9T12C1002G0445 (+2, -4: 2.5%) 12 ² ² 9T12C1003G0475 (+2, -4: 2.5%) 12 ² ² 9T12C1004G04112.5 (+2, -4: 2.5%) 12 ² ² 9T12C1005G04150 (+2, -4: 2.5%) 12 ² ² 9T12C1006G04

K=20 115°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 ² ² 9T12C1001G3430 (+2, -4: 2.5%) 12 ² ² 9T12C1002G3445 (+2, -4: 2.5%) 12 ² ² 9T12C1003G3475 (+2, -4: 2.5%) 12 ² ² 9T12C1004G34112.5 (+2, -4: 2.5%) 12 ² ² 9T12C1005G34150 (+2, -4: 2.5%) 12 ² ² 9T12C1006G34

K=20 80°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 ² ² 9T12C1001G6430 (+2, -4: 2.5%) 12 ² ² 9T12C1002G6445 (+2, -4: 2.5%) 12 ² ² 9T12C1003G6475 (+2, -4: 2.5%) 12 ² ² 9T12C1004G64112.5 (+2, -4: 2.5%) 12 ² ² 9T12C1005G64

¹ See page 10A-45 and 10A-46 for wiring diagrams.² Contact Customer Service for more information on these transformers.

Page 25: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-25LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

Product descriptionThese low noise transformers are designed to operate at re-duced noise levels. The vibrations within the magnetic steel core have been greatly reduced, thus lowering the humming of the transformer 3 dB less than NEMA/ANSI standards. Available in Aluminum or Copper windings, with either a 150°C, 115°C or 80°C rise.

ApplicationsType QL low noise transformers are ideal when quiet opera-tion is required such as near offices, in school buildings, or hospitals. Although they are inherently quieter, installation can greatly influence their noise level and therefore care should be taken in following acoustical principles as well as proper installation procedures. Closets and corners should be avoided as they act as megaphones by seemingly increas-ing noise levels.

—Low noise (-3 dB below NEMA ST-20 standard)Aluminum coilThree-phase DOE 2016 efficiency

Type QL Low Noise Transformer (front panel removed)

150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T10A1001G0230 (+2, -4: 2.5%) 12 330 UX72A 9T10A1002G0245 (+2, -4: 2.5%) 12 444 UX73A 9T10A1003G0275 (+2, -4: 2.5%) 12 561 UY74A 9T10A1004G02112.5 (+2, -4: 2.5%) 12 680 DY75A 9T10A1005G02150 (+2, -4: 2.5%) 12 1030 DY76A 9T10A1006G02225 (+2, -4: 2.5%) 12 1450 DY77A 9T10A1007G02300 (+2, -4: 2.5%) 12 1670 DY78A 9T10A1008G02500 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1009G02

115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T10A1001G3230 (+2, -4: 2.5%) 12 330 UX72A 9T10A1002G3245 (+2, -4: 2.5%) 12 444 UX73A 9T10A1003G3275 (+2, -4: 2.5%) 12 603 UX74A 9T10A1004G32112.5 (+2, -4: 2.5%) 12 830 DX75A 9T10A1005G32150 (+2, -4: 2.5%) 12 1250 DX76A 9T10A1006G32225 (+2, -4: 2.5%) 12 1670 DX77A 9T10A1007G32300 (+2, -4: 2.5%) 12 1985 DX78A 9T10A1008G32500 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1009G32

80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 330 UX72A 9T10A1001G6230 (+2, -4: 2.5%) 12 444 UX73A 9T10A1002G6245 (+2, -4: 2.5%) 12 561 UY74A 9T10A1003G6275 (+2, -4: 2.5%) 12 680 DY75A 9T10A1004G62112.5 (+2, -4: 2.5%) 12 1030 DY76A 9T10A1005G62150 (+2, -4: 2.5%) 12 1450 DY77A 9T10A1006G62225 (+2, -4: 2.5%) 12 1985 DX78A 9T10A1007G62300 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1008G62

¹ See page 10A-45 and 10A-46 for wiring diagrams.

Page 26: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-26 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Low noise (-3 dB below NEMA ST-20 standard)Copper coilThree-phase DOE 2016 efficiency

150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 230 UX71C 9T10C1001G0230 (+2, -4: 2.5%) 12 353 UX72C 9T10C1002G0245 (+2, -4: 2.5%) 12 480 UX73C 9T10C1003G0275 (+2, -4: 2.5%) 12 661 UY74C 9T10C1004G02112.5 (+2, -4: 2.5%) 12 790 DY75C 9T10C1005G02150 (+2, -4: 2.5%) 12 1085 DY76C 9T10C1006G02225 (+2, -4: 2.5%) 12 1610 DY77C 9T10C1007G02300 (+2, -4: 2.5%) 12 1970 DY78C 9T10C1008G02500 (+2, -2: 2.5%) 12 3720 DX79C 9T10C1009G02

115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 230 UX71C 9T10C1001G3230 (+2, -4: 2.5%) 12 353 UX72C 9T10C1002G3245 (+2, -4: 2.5%) 12 480 UX73C 9T10C1003G3275 (+2, -4: 2.5%) 12 748 UX74C 9T10C1004G32112.5 (+2, -4: 2.5%) 12 900 DX75C 9T10C1005G32150 (+2, -4: 2.5%) 12 1240 DX76C 9T10C1006G32225 (+2, -4: 2.5%) 12 1847 DX77C 9T10C1007G32300 (+2, -4: 2.5%) 12 2150 DX78C 9T10C1008G32500 (+2, -2: 2.5%) 12 3720 DX79C 9T10C1009G32

80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 353 UX72C 9T10C1001G6230 (+2, -4: 2.5%) 12 480 UX73C 9T10C1002G6245 (+2, -4: 2.5%) 12 661 UY74C 9T10C1003G6275 (+2, -4: 2.5%) 12 790 DY75C 9T10C1004G62112.5 (+2, -4: 2.5%) 12 1085 DY76C 9T10C1005G62150 (+2, -4: 2.5%) 12 1610 DY77C 9T10C1006G62225 (+2, -4: 2.5%) 12 2150 DX78C 9T10C1007G62300 (+2, -2: 2.5%) 12 3720 DX79C 9T10C1008G62

¹ See page 10A-45 and 10A-46 for wiring diagrams.

Page 27: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-27LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Noise isolation — Guard I™

Aluminum coilThree-phase DOE 2016 efficiencyElectrostatic shield

Guard I™ Noise Isolation Transformers provide common mode noise signal between neutral and ground and transverse mode noise protection. Common mode noise is caused by electromagnetic interference, radio interference and ground loops.

Key features - 120 db common mode noise protection - 30 db transverse mode noise protection - NEMA 1 and/or 2 drip-proof enclosure - Rain shield available for field conversion to NEMA 3R - NEMA 3R stainless steel (Type 316) available through 150 kVA

150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T10A1001G0330 (+2, -4: 2.5%) 12 330 UX72A 9T10A1002G0345 (+2, -4: 2.5%) 12 444 UX73A 9T10A1003G0375 (+2, -4: 2.5%) 12 561 UY74A 9T10A1004G03112.5 (+2, -4: 2.5%) 12 680 DY75A 9T10A1005G03150 (+2, -4: 2.5%) 12 1030 DY76A 9T10A1006G03225 (+2, -4: 2.5%) 12 1450 DY77A 9T10A1007G03300 (+2, -4: 2.5%) 12 1670 DY78A 9T10A1008G03500 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1009G03750 (+2, -2: 2.5%) 12 ² DX67A 9T10A1302G03

115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 231 UX71A 9T10A1001G3330 (+2, -4: 2.5%) 12 330 UX72A 9T10A1002G3345 (+2, -4: 2.5%) 12 444 UX73A 9T10A1003G3375 (+2, -4: 2.5%) 12 603 UX74A 9T10A1004G33112.5 (+2, -4: 2.5%) 12 830 DX75A 9T10A1005G33150 (+2, -4: 2.5%) 12 1250 DX76A 9T10A1006G33225 (+2, -4: 2.5%) 12 1670 DX77A 9T10A1007G33300 (+2, -4: 2.5%) 12 1985 DX78A 9T10A1008G33500 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1009G33750 (+2, -2: 2.5%) 12 ² DX67A 9T10A1302G33

80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 330 UX72A 9T10A1001G6330 (+2, -4: 2.5%) 12 444 UX73A 9T10A1002G6345 (+2, -4: 2.5%) 12 561 UY74A 9T10A1003G6375 (+2, -4: 2.5%) 12 680 DY75A 9T10A1004G63112.5 (+2, -4: 2.5%) 12 1030 DY76A 9T10A1005G63150 (+2, -4: 2.5%) 12 1450 DY77A 9T10A1006G63225 (+2, -4: 2.5%) 12 1985 DX78A 9T10A1007G63300 (+2, -2: 2.5%) 12 2900 DX79A 9T10A1008G63

¹ See page 10A-45 and 10A-46 for wiring diagrams.² Contact Customer Service for more information on these transformers.

Page 28: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-28 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Noise isolation — Guard I™

Copper coilThree-phase DOE 2016 efficiencyElectrostatic shield

150°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 230 UX71C 9T10C1001G0330 (+2, -4: 2.5%) 12 353 UX72C 9T10C1002G0345 (+2, -4: 2.5%) 12 480 UX73C 9T10C1003G0375 (+2, -4: 2.5%) 12 661 UY74C 9T10C1004G03112.5 (+2, -4: 2.5%) 12 790 DY75C 9T10C1005G03150 (+2, -4: 2.5%) 12 1085 DY76C 9T10C1006G03225 (+2, -4: 2.5%) 12 1610 DY77C 9T10C1007G03300 (+2, -4: 2.5%) 12 1970 DY78C 9T10C1008G03500 (+2, -2: 2.5%) 12 3720 DX79C 9T10C1009G03

115°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 230 UX71C 9T10C1001G3330 (+2, -4: 2.5%) 12 353 UX72C 9T10C1002G3345 (+2, -4: 2.5%) 12 480 UX73C 9T10C1003G3375 (+2, -4: 2.5%) 12 748 UX74C 9T10C1004G33112.5 (+2, -4: 2.5%) 12 900 DX75C 9T10C1005G33150 (+2, -4: 2.5%) 12 1240 DX76C 9T10C1006G33225 (+2, -4: 2.5%) 12 1847 DX77C 9T10C1007G33300 (+2, -4: 2.5%) 12 2150 DX78C 9T10C1008G33500 (+2, -2: 2.5%) 12 3720 DX79C 9T10C1009G33

80°C Rise NEMA 2

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 353 UX72C 9T10C1001G6330 (+2, -4: 2.5%) 12 480 UX73C 9T10C1002G6345 (+2, -4: 2.5%) 12 661 UY74C 9T10C1003G6375 (+2, -4: 2.5%) 12 790 DY75C 9T10C1004G63112.5 (+2, -4: 2.5%) 12 1085 DY76C 9T10C1005G63150 (+2, -4: 2.5%) 12 1610 DY77C 9T10C1006G63225 (+2, -4: 2.5%) 12 2150 DX78C 9T10C1007G63300 (+2, -2: 2.5%) 12 3720 DX79C 9T10C1008G63

1 See page 10A-45 and 10A-46 for wiring diagrams.

Page 29: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-29LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Noise isolation — Guard II™

Aluminum coilThree-phase DOE 2016 efficiencyElectrostatic shield

150°C Rise

InputVoltage

OutputVoltage kVA Taps Wiring

Diagram No.¹Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 260 XV371 9T17A1001G0330 (+2, -4: 2.5%) 12 370 XV372 9T17A1002G0345 (+2, -4: 2.5%) 12 460 XV373 9T17A1003G0375 (+2, -4: 2.5%) 12 680 XV374 9T17A1004G03112.5 (+2, -4: 2.5%) 12 830 XV375 9T17A1005G03

115°C Rise

InputVoltage

OutputVoltage kVA Taps Wiring

Diagram No.¹Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts15 (+2, -4: 2.5%) 12 260 XV371 9T17A1001G3330 (+2, -4: 2.5%) 12 370 XV372 9T17A1002G3345 (+2, -4: 2.5%) 12 460 XV373 9T17A1003G33

80°C Rise

InputVoltage

OutputVoltage kVA Taps Wiring

Diagram No.¹Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts45 (+2, -4: 2.5%) 12 680 XV374 9T17A1003G6375 (+2, -4: 2.5%) 12 830 XV375 9T17A1004G63

150°C Rise

InputVoltage

OutputVoltage kVA Taps Wiring

Diagram No.¹Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

208 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 260 XV371 9T17A1451G0330 (+2, -4: 2.5%) 12 370 XV372 9T17A1452G0345 (+2, -4: 2.5%) 12 460 XV373 9T17A1453G0375 (+2, -4: 2.5%) 12 680 XV374 9T17A1454G03112.5 (+2, -4: 2.5%) 12 830 XV375 9T17A1455G03

115°C Rise

InputVoltage

OutputVoltage kVA Taps Wiring

Diagram No.¹Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

208 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 260 XV371 9T17A1451G3330 (+2, -4: 2.5%) 12 370 XV372 9T17A1452G3345 (+2, -4: 2.5%) 12 460 XV373 9T17A1453G3375 (+2, -4: 2.5%) 12 680 XV374 9T17A1454G33

80°C Rise

InputVoltage

OutputVoltage kVA Taps Wiring

Diagram No.¹Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

208 Volts Delta 208Y/120 Volts 75 (+2, -4: 2.5%) 12 830 XV375 9T17A1454G631 See page 10A-45 and 10A-46 for wiring diagrams.

Guard II™ noise isolation transformers provide common mode noise attenuation plus an enhanced level of transverse mode noise attenuation for increased protection of sensitive electronic equipment.

Key features - Grounded copper electrostatic shield between

primary and secondary windings - Noise suppressors and spike/surge suppressors - 120dB common mode noise rejection - 60dB transverse mode noise rejection - Compliance with ANSI and NEMA standards - Sound levels below NEMA ST-20 limits - UL Listed - NEMA 2 enclosure

Guard II™ Transformer Guard II™ Transformer, (front panel removed)

Page 30: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-30 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Noise isolation — Guard II™

Copper coilThree-phase DOE 2016 efficiencyElectrostatic shield

150°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 270 XV371 9T17C1001G0330 (+2, -4: 2.5%) 12 420 XV372 9T17C1002G0345 (+2, -4: 2.5%) 12 540 XV373 9T17C1003G0375 (+2, -4: 2.5%) 12 770 XV374 9T17C1004G03112.5 (+2, -4: 2.5%) 12 1010 XV375 9T17C1005G03

115°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 270 XV371 9T17C1001G3330 (+2, -4: 2.5%) 12 420 XV372 9T17C1002G3345 (+2, -4: 2.5%) 12 540 XV373 9T17C1003G3375 (+2, -4: 2.5%) 12 770 XV374 9T17C1004G33112.5 (+2, -4: 2.5%) 12 1010 XV375 9T17C1005G33

80°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 420 XV372 9T17C1001G6330 (+2, -4: 2.5%) 12 540 XV373 9T17C1002G6345 (+2, -4: 2.5%) 12 770 XV374 9T17C1003G6375 (+2, -4: 2.5%) 12 1010 XV375 9T17C1004G63

150°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

208 Volts Delta 208Y/120 Volts15 (+2, -4: 2.5%) 12 270 XV371 9T17C1451G0330 (+2, -4: 2.5%) 12 420 XV372 9T17C1452G0345 (+2, -4: 2.5%) 12 540 XV373 9T17C1453G03

115°C Rise

InputVoltage

OutputVoltage

kVA TapsWiringDiagram No.¹

Approx. NetWeight (Lbs)

FrameSize

CatalogNumber

208 Volts Delta 208Y/120 Volts

15 (+2, -4: 2.5%) 12 270 XV371 9T17C1451G3330 (+2, -4: 2.5%) 12 420 XV372 9T17C1452G3345 (+2, -4: 2.5%) 12 540 XV373 9T17C1453G3375 (+2, -4: 2.5%) 12 770 XV374 9T17C1454G33

1 See page 10A-45 and 10A-46 for wiring diagrams.

Page 31: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-31LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Harmonic mitigating — Guard III™

Copper coilThree-phase DOE 2016 efficiencyElectrostatic shield

150°C Rise NEMA 2, 0° Phase Shift

InputVoltage

OutputVoltage

kVAApprox. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 318 H371C 9T76H9871G0330 552 H372C 9T76H9872G0345 643 H373C 9T76H9873G0375 1053 H374C 9T76H9874G03112.5 1980 H375C 9T76H9875G03150 2125 H376C 9T76H9876G03300 3170 YF378 9T76H9878G03

150°C Rise NEMA 2, -30° Phase Shift

InputVoltage

OutputVoltage

kVAApprox. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts

15 318 H371C 9T77H9871G0330 552 H372C 9T77H9872G0345 643 H373C 9T77H9873G0375 1053 H374C 9T77H9874G03112.5 1980 H375C 9T77H9875G03150 2125 H376C 9T77H9876G03300 3170 YF378 9T77H9878G03

150° C Rise NEMA 2, +15° Phase Shift

InputVoltage

OutputVoltage

kVAApprox. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts 112.5 1980 H375C 9T79H9875G03

150° C Rise NEMA 2, -15° Phase Shift

InputVoltage

OutputVoltage

kVAApprox. NetWeight (Lbs)

FrameSize

CatalogNumber

480 Volts Delta 208Y/120 Volts 112.5 1980 H375C 9T78H9875G03

Guard III™ Harmonic Mitigating Transformers help eliminate harmonics, improve power quality, and help save energy by reducing the energy (heating) losses. They maintain DOE 2016 energy efficiency even when harmonics are present. Power supplies that convert AC to DC current – for plant floor equipment, computers, copiers, electronic ballasts, and others – generate harmonics that create an irregular current waveform. These harmonics, in turn, create power quality problems such as overheated transformers, motors and neutral wires; nuisance breaker trips; and electronic equipment malfunction and failure.

Key features - 0° Phase shift; +15° Phase Shift; -15° Phase Shift or -30° Phase Shift - Copper windings - K-factor load profile of 20 - Crest factor load profile of 5 - NEMA 1 and/or 2 drip-proof enclosure - Rain shield available for field conversion to NEMA 3R - NEMA 3R stainless steel (Type 316) up through 150 kVA

Page 32: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-32 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

Product descriptionThis easily installed and serviceable unit incorporates a Type QMS transformer (single-phase) or a Type QL transformer (three-phase), a primary main circuit breaker, a secondary main circuit breaker, and a load-center-design breaker panel. Since these components don’t have to be installed and interconnected separately, the contractor or user can reduce installation time and costs. Because of the single-unit concept, only one, handy Servicenter™ needs to be mounted.

Available in single-phase, 5 through 25 kVA, and in three-phase, 15 through 30 kVA, 600 Volt class ratings, the ABB Servicenter™ is a convenient, economical way to meet your industrial and temporary power requirements.

The transformer—The Servicenter™ utilizes ABB transformer design which has twenty years of field-proven experience behind it and a long track record for assuring consistent, reliable performance. Type QMS transformers employ a 180°C UL Recognized insulation system with a 115°C rise. Type QL transformers employ a 220°C UL Recognized insulation system with a 150°C rise.

The panel—The panel assembly includes the rugged ABBPowerMark Plus™ circuit breaker load center interior, E-frame primary breakers, and E-frame or Q Line secondary breakers. The load center will accept one-, two-, or three-pole (three-phase) common trip circuit breakers and ground fault breakers. All Servicenters™ come equipped with the properly sized primary main and secondary main circuit breakers installed and prewired. Branch breakers are not included.

Advantages

- Transformer, distribution panel and breakers are all designed, built and assembled by ABB

- Saves time and money - pre-assembled, pre-wired unit saves time on the job

- High reliability – assembled and tested in our UL approved factory to assure consistency and quality

- Available ABB ground-fault breakers ensure electrical safety around construction sites or wherever water may be present

-Key features

- Keyhole mounting flange facilitates easy mounting- Indoor and outdoor use- Front-accessible, hinged or removable panel door is safe

and convenient- Heat barrier under core and coil provides electrical and

thermal isolation for wiring compartment- High-efficiency core construction results in quiet trans-

former operation and low no-load losses- Factory installed and wired ABB main and secondary

main circuit breakers

—Servicenter™ mini-unit substationsIntegral transformer and distribution center

Single-Phase Servicenter™, Hinged Door Removed

Three-Phase Servicenter™, Closed View

ApplicationThe single-phase Servicenter™ can be used wherever 480 Voltpower is available and 120 or 240 Volt branch circuits are required. The three-phase Servicenter™ can be used wherever 240 Volt, 480 Volt or 600 Volt primary is available and 208Y/120 Volt secondary circuits are required. The unit can be used in such applications as vending machine areas, construction laboratory test areas, general construction sites where temporary or quickly obtained power is required, or where future expansion of branch circuits is planned.

- Vending or concession areas- Office buildings- Assembly lines- Mining applications- Parking lots- Light industrial areas- Warehouses- Construction sites-

NEC requirementsThe Servicenter™ conforms with Article 450-3 of the National Electric Code regarding overcurrent protection requirements for transformers and are UL listed to UL 1062, YEFR:E75204.

Three-Phase Servicenter™, Closed View

Page 33: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-33LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Servicenter™ mini-unit substationsIntegral transformer and distribution centerSingle-phase and three-phase DOE 2016 efficiency

Single-Phase Indoor/Outdoor 60 Hz 115°C Winding Temperature

InputVoltage

OutputVoltage

kVA

Max. BranchSpaces 1 THQL,1-pole

Max. BranchSpaces 1 THQL,2-pole

Total1-pole Spaces

Breaker Rating-Primary Main

Breaker Rating-Secondary Main

CatalogNumber

480 Volts Delta 120/240 Volts

5 8 4 12 25A 30A 9T21S10507.5 8 4 12 35A 40A 9T21S107010 12 6 16 50A 50A 9T21S110015 12 6 24 60A 70A 9T21S115025 20 10 24 100A 150A 9T21S1250

Three-Phase2 Indoor/Outdoor 60 Hz¹ 150°C DOE 2016 Efficiency Aluminum Transformer Windings

InputVoltage

OutputVoltage

kVAMax. BranchSpaces, 1-pole

Max. BranchSpaces 3-pole

Total1-pole Spaces

Breaker Rating-Primary Main

Breaker Rating-Secondary Main

CatalogNumber

240 Volts Delta 208Y/120 Volts15 12 4 12 100A 50A 9T17A000130 24 8 24 100A 100A 9T17A0003

480 Volts Delta 208Y/120 Volts15 12 4 12 40A 50A 9T17A001122.5 18 6 18 70A 70A 9T17A001230 24 8 24 90A 100A 9T17A0013

600 Volts Delta 208Y/120 Volts15 12 4 12 40A 50A 9T17A002130 24 8 24 40A 100A 9T17A0023

Three-Phase2 Indoor/Outdoor 60 Hz¹ 150°C DOE 2016 Efficiency Copper Transformer Windings

InputVoltage

OutputVoltage

kVAMax. BranchSpaces, 1-pole

Max. BranchSpaces 3-pole

Total1-pole Spaces

Breaker Rating-Primary Main

Breaker Rating-Secondary Main

CatalogNumber

240 Volts Delta 208Y/120 Volts 15 12 4 12 100A 50A 9T17C0004

480 Volts Delta 208Y/120 Volts15 12 4 12 40A 50A 9T17C001422.5 18 6 18 70A 70A 9T17C001530 24 8 24 90A 100A 9T17C0016

1 (3) 5% taps 1 above and 2 below rated primary volts.2 Stainless steel (Type 316) enclosures are available as an engineered made to order item.

Single-Phase Servicenter™Three-Phase Servicenter™Three-Phase Servicenter™

Page 34: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-34 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

NP

***

**

Concentric knockouts on sides and bottom

Provisional holes for padlocking cover

C B

AHinged cover

A Max

B Max

2.62 support opening height

15 KVA unit shown

Line1

Line3

Primary main3-pole type TED , 90A, 480V

Line2

7 6 5 4 3 2 1 7 6 5 4 3 2 1 7 6 5 4 3 2 1H1 H3H2

X1 X3 XOX2

Secondary main

breaker

Primary main breaker

Secondary main3-pole type TEB, 100A, 480V

Neutral N

eutr

al

Neutral is bonded to enclosure by use of bonding screw

Ground when required

1(3)57

(9)1113

(15)1719

(21)23

2(4)68

(10)1214

(16)1820

(22)24

Line 1Line 2

H1 H2 H3 H4

X1X2 X3X4

135791113151719

2468101214161820

I4-4 CUI2-4 AL

Secondary main2-pole type THQL or TEB

Branch Breakers70A max using CU wire55A max using AL wire

* Short ciruit current rating 10,000 RMS symmetrical amperes, 240V maximum

** Provisions for branch circuit breakers Type THHQL, THHQAL, THQP, THQL,

THQL-AC, THQAL-AC, THQL-GRC I, THHQL-GFCI or circuit breakers

NeutralBonded to enclosure

Grouding electrode conductor terminal

Primary groundNo.6 - No.4 CU

Suitable for use as service equipment

PRI connected for max voltage at factory

Primary main - 2-pole type TED 600V max, U.L. Listed, RMS. SYM. Amps 14 K

Neutral and equipment ground wire size Solid Stranded

Large holes 14-8 AWG-CU 10-4 AWG-CU 6-4 AWG-ALSmall holes 14-8 AWG-CU 12-8 AWG-CU 12-8 AWG-AL 12-8 AWG-AL

—Servicenter™ mini-unit substationsIntegral transformer and distribution centerOutlines, dimensions and wiring diagrams

Dimensions Single-Phase

Dimensions Three-Phase

Typical Wiring Diagram Single-Phase Typical Wiring Diagram Three-Phase1

¹ For 22.5 and 15 kVA three-phase Servicenters™, secondary main breaker is a backfed plug-in type with positive retainers.

Single-Phase

kVACatalogNumber

Approx. NetWeight (Lbs.)

"A"Height (in.)

"B"Width (in.)

"C"Depth (in.)

FrameSize

5 9T21S1050 103 32.5 10.75 11.12 163507.5 9T21S1070 147 32.5 10.75 11.12 1660010 9T21S1100 198 35 12.62 12.62 1940015 9T21S1150 220 35 12.62 12.62 1950025 9T21S1250 388 44.75 16.75 16 50500

Three-Phase DOE 2016 Efficiency Aluminum

kVACatalogNumber

Approx. NetWeight (Lbs.)

"A"Height (in.)

"B"Width (in.)

"C"Depth (in.)

FrameSize

15 9T17A0001 280 27.3 27.4 16.9 UX71A30 9T17A0003 450 32.2 34.5 24 UX72A15 9T17A0011 280 27.3 27.4 16.9 UX71A22.5 9T17A0012 450 32.2 34.5 24 UX72A30 9T17A0013 450 32.2 34.5 24 UX72A15 9T17A0021 280 27.3 27.4 16.9 UX71A30 9T17A0023 450 32.2 34.5 24 UX72A

Three-Phase DOE 2016 Efficiency Copper

kVACatalogNumber

Approx. NetWeight (Lbs.)

"A"Height (in.)

"B"Width (in.)

"C"Depth (in.)

FrameSize

15 9T17C0004 290 27.3 27.4 16.9 UX71C15 9T17C0014 290 27.3 27.4 16.9 UX71C22.5 9T17C0015 460 32.2 34.5 24 UX72C30 9T17C0016 460 32.2 34.5 24 UX72C

NP

***

**

Concentric knockouts on sides and bottom

Provisional holes for padlocking cover

C B

AHinged cover

A Max

B Max

2.62 support opening height

15 KVA unit shown

Line1

Line3

Primary main3-pole type TED , 90A, 480V

Line2

7 6 5 4 3 2 1 7 6 5 4 3 2 1 7 6 5 4 3 2 1H1 H3H2

X1 X3 XOX2

Secondary main

breaker

Primary main breaker

Secondary main3-pole type TEB, 100A, 480V

Neutral N

eutr

al

Neutral is bonded to enclosure by use of bonding screw

Ground when required

1(3)57

(9)1113

(15)1719

(21)23

2(4)68

(10)1214

(16)1820

(22)24

Line 1Line 2

H1 H2 H3 H4

X1X2 X3X4

135791113151719

2468101214161820

I4-4 CUI2-4 AL

Secondary main2-pole type THQL or TEB

Branch Breakers70A max using CU wire55A max using AL wire

* Short ciruit current rating 10,000 RMS symmetrical amperes, 240V maximum

** Provisions for branch circuit breakers Type THHQL, THHQAL, THQP, THQL,

THQL-AC, THQAL-AC, THQL-GRC I, THHQL-GFCI or circuit breakers

NeutralBonded to enclosure

Grouding electrode conductor terminal

Primary groundNo.6 - No.4 CU

Suitable for use as service equipment

PRI connected for max voltage at factory

Primary main - 2-pole type TED 600V max, U.L. Listed, RMS. SYM. Amps 14 K

Neutral and equipment ground wire size Solid Stranded

Large holes 14-8 AWG-CU 10-4 AWG-CU 6-4 AWG-ALSmall holes 14-8 AWG-CU 12-8 AWG-CU 12-8 AWG-AL 12-8 AWG-AL

Page 35: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-35LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

Totally enclosed nonventilated (TENV) transformers are an excellent choice for applications where dry-type transformer benefits are desired but the standard enclosure openings are unacceptable because of adverse atmospheric conditions. TENV transformers are recommended where dust, dirt or lint may be present or where transformers are subject to sprays or controlled wash-down conditions. They are UL Listed through 75kVA for indoor or protected outdoor applications.

Advantages

- Dry-type transformer is housed in an enclosed NEMA 3R (IP32) non-ventilated compartment

- Convenient wiring compartment is located beneath the transformer and has removable front and rear covers

- Copper bus bars are located at the front of the wiring compartment and are clearly labeled

- All electrical connections between the transformer and bus bars are factory wired

- Quiet performance – meets NEMA ST-20 - No-weld coil termination design – an industry first - Comprehensive factory testing assures quality

Features

- Quiet design - unique core and coil design makes ABB TENV transformers among the quietest available

- Core and coil assembly mounted on rubber isolation pads to reduce noise

- Bolted coil terminations are more reliable than welded terminations, and they eliminate weld failures and problems associated with welding and weld splatter

- 100% factory tested for shorts and coil integrity, current and loss, voltage, impedance and noise

- Qualified to the seismic requirements of IEEE-693-2005 and IBC-2018/CBC-2019

- Copper ground strap - Copper or aluminum windings available - Available in 150°C, 115°C, and 80°C rise models - Indoor or outdoor use

Applications

- Textile - Automotive - Foundry - Paper mills - Wash-down areas

—Totally enclosed, nonventilatedTENV15-75kVA, three-phase, NEMA TP-1 efficiency

TENV Transformer

Page 36: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-36 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Totally enclosed, nonventilatedTENVThree-phase NEMA TP-1 efficiency

Aluminum 150°C Rise

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 208Y/120

15 (+2, -4: 2.5%) 370 XV372 9T85B387130 (+2, -4: 2.5%) 450 XV373 9T85B387245 (+2, -4: 2.5%) 670 XV374 9T85B387375 (+2, -4: 2.5%) 815 XV375 9T85B3874

Aluminum 115°C Rise

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 208Y/120

15 (+2, -4: 2.5%) 370 XV372 9T85B3871G1530 (+2, -4: 2.5%) 450 XV373 9T85B3872G1545 (+2, -4: 2.5%) 670 XV374 9T85B3873G1575 (+2, -4: 2.5%) 815 XV375 9T85B3874G15

Aluminum 80°C Rise

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 208Y/120 30 (+2, -4: 2.5%) 670 XV374 9T85B3872G80

Copper 150°C Rise

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 208Y/120

15 (+2, -4: 2.5%) 410 XV372 9T85C987130 (+2, -4: 2.5%) 525 XV373 9T85C987245 (+2, -4: 2.5%) 760 XV374 9T85C987375 (+2, -4: 2.5%) 1000 XV375 9T85C9874

Copper 115°C Rise

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 208Y/120

15 (+2, -4: 2.5%) 410 XV372 9T85C9871G1530 (+2, -4: 2.5%) 525 XV373 9T85C9872G1545 (+2, -4: 2.5%) 760 XV374 9T85C9873G1575 (+2, -4: 2.5%) 1000 XV375 9T85C9874G15

Copper 80°C Rise

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 208Y/12015 (+2, -4: 2.5%) 410 XV372 9T85C9871G8045 (+2, -4: 2.5%) 760 XV374 9T85C9873G80

Page 37: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-37LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

ABB Type QL midtapped transformer enables the user to transform three-phase power from 480 Volts primary to 240 Volts secondary and have 120 Volt, reduced capacity tap (RCT) single-phase capability as well. This is because a single-phase midtap is brought out of one coil of the unit’s three-phase secondary winding. These transformers are UL listed, File E-79145.

ApplicationThe Type QL midtapped design can be used wherever there is 480 Volt, three-phase supply available and the load is primarily 240 Volt three-phase with a nominal amount of 120 Volt, single-phase power required. Normally, in this instance, a small single-phase as well as a three-phase transformer would be required to provide the necessary transformation.

Caution: When utilizing the 120 Volt midtap for single-phase applications, the single-phase load should not exceed 5 percent of the three-phase kVA rating. The three-phase kVA load must be reduced by the same percentage as that added by the single-phase load. Additional loading beyond 5 percent may cause the transformer to overheat and fail. If the single-phase load is in excess of 5 percent, it is recommended that a separate single-phase unit be used to handle the load.

—MidtappedAluminumThree-phase DOE 2016 efficiency

Type QL Midtapped Transformer

150°C Rise 60Hz

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 240/120

15 (+2, -4: 2.5%) 231 UX71A 9T10A118130 (+2, -4: 2.5%) 330 UX72A 9T10A118245 (+2, -4: 2.5%) 444 UX73A 9T10A118375 (+2, -4: 2.5%) 561 UY74A 9T10A1184112.5 (+2, -4: 2.5%) 830 DX75A 9T10A1185150 (+2, -4: 2.5%) 1030 DY76A 9T10A1186225 (+2, -4: 2.5%) 1450 DY77A 9T10A1187300 (+2, -4: 2.5%) 1670 DY78A 9T10A1188500 (+2, -2: 2.5%) 2900 DX79A 9T10A1189

115°C Rise 60Hz

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 240/120

15 (+2, -4: 2.5%) 231 UX71A 9T10A1181G3130 (+2, -4: 2.5%) 330 UX72A 9T10A1182G3145 (+2, -4: 2.5%) 444 UX73A 9T10A1183G3175 (+2, -4: 2.5%) 603 UX74A 9T10A1184G31112.5 (+2, -4: 2.5%) 830 DX75A 9T10A1185G31150 (+2, -4: 2.5%) 1250 DX76A 9T10A1186G31225 (+2, -4: 2.5%) 1670 DX77A 9T10A1187G31300 (+2, -4: 2.5%) 1985 DX78A 9T10A1188G31500 (+2, -2: 2.5%) 2900 DX79A 9T10A1189G31

80°C Rise 60Hz

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 240/120

15 (+2, -4: 2.5%) 330 UX72A 9T10A1181G6130 (+2, -4: 2.5%) 444 UX73A 9T10A1182G6145 (+2, -4: 2.5%) 561 UY74A 9T10A1183G6175 (+2, -4: 2.5%) 680 DY75A 9T10A1184G61150 (+2, -4: 2.5%) 1450 DY77A 9T10A1186G61225 (+2, -4: 2.5%) 1985 DX78A 9T10A1187G61

Page 38: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-38 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—MidtappedAluminumThree-phase DOE 2016 efficiency

150°C Rise 60Hz Low Noise (-3dB)

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 240/120

15 (+2, -4: 2.5%) 231 UX71A 9T10A1181G0230 (+2, -4: 2.5%) 330 UX72A 9T10A1182G0245 (+2, -4: 2.5%) 444 UX73A 9T10A1183G0275 (+2, -4: 2.5%) 561 UY74A 9T10A1184G02112.5 (+2, -4: 2.5%) 680 DX75A 9T10A1185G02150 (+2, -4: 2.5%) 1030 DY76A 9T10A1186G02225 (+2, -4: 2.5%) 1450 DY77A 9T10A1187G02300 (+2, -4: 2.5%) 1670 DY78A 9T10A1188G02500 (+2, -2: 2.5%) 2900 DX79A 9T10A1189G02

115°C Rise 60Hz Low Noise (-3dB)

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 240/120

15 (+2, -4: 2.5%) 231 UX71A 9T10A1181G3230 (+2, -4: 2.5%) 330 UX72A 9T10A1182G3245 (+2, -4: 2.5%) 444 UX73A 9T10A1183G3275 (+2, -4: 2.5%) 603 UX74A 9T10A1184G32112.5 (+2, -4: 2.5%) 830 DX75A 9T10A1185G32150 (+2, -4: 2.5%) 1250 DX76A 9T10A1186G32225 (+2, -4: 2.5%) 1670 DX77A 9T10A1187G32300 (+2, -4: 2.5%) 1985 DX78A 9T10A1188G32500 (+2, -2: 2.5%) 2900 DX79A 9T10A1189G32

Page 39: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-39LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—MidtappedCopperThree-phase DOE 2016 efficiency

150°C Rise 60Hz

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 240/120

15 (+2, -4: 2.5%) 230 UX71C 9T10C118130 (+2, -4: 2.5%) 353 UX72C 9T10C118245 (+2, -4: 2.5%) 480 UX73C 9T10C118375 (+2, -4: 2.5%) 661 UY74C 9T10C1184112.5 (+2, -4: 2.5%) 790 DY75C 9T10C1185150 (+2, -4: 2.5%) 1085 DY76C 9T10C1186225 (+2, -4: 2.5%) 1610 DY77C 9T10C1187300 (+2, -4: 2.5%) 1970 DY78C 9T10C1188500 (+2, -2: 2.5%) 3720 DX79C 9T10C1189

115°C Rise 60Hz

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 240/120

15 (+2, -4: 2.5%) 230 UX71C 9T10C1181G3130 (+2, -4: 2.5%) 353 UX72C 9T10C1182G3145 (+2, -4: 2.5%) 480 UX73C 9T10C1183G3175 (+2, -4: 2.5%) 748 UX74C 9T10C1184G31112.5 (+2, -4: 2.5%) 900 DX75C 9T10C1185G31150 (+2, -4: 2.5%) 1240 DX76C 9T10C1186G31300 (+2, -4: 2.5%) 2150 DX78C 9T10C1188G31500 (+2, -2: 2.5%) 3720 DX79C 9T10C1189G31

80°C Rise 60Hz

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 240/120

15 (+2, -4: 2.5%) 353 UX72C 9T10C1181G6130 (+2, -4: 2.5%) 480 UX73C 9T10C1182G6145 (+2, -4: 2.5%) 661 UY74C 9T10C1183G6175 (+2, -4: 2.5%) 790 DY75C 9T10C1184G61225 (+2, -4: 2.5%) 2150 DX78C 9T10C1187G61

150°C Rise 60Hz Low Noise (-3dB)

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 240/120

15 (+2, -4: 2.5%) 230 UX71C 9T10C1181G0230 (+2, -4: 2.5%) 353 UX72C 9T10C1182G0245 (+2, -4: 2.5%) 480 UX73C 9T10C1183G0275 (+2, -4: 2.5%) 661 UY74C 9T10C1184G02112.5 (+2, -4: 2.5%) 790 DY75C 9T10C1185G02225 (+2, -4: 2.5%) 1610 DY77C 9T10C1187G02

115°C Rise 60Hz Low Noise (-3dB)

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 240/12075 (+2, -4: 2.5%) 748 UX74C 9T10C1184G32112.5 (+2, -4: 2.5%) 900 DX75C 9T10C1185G32

80°C Rise 60Hz Low Noise (-3dB)

InputVoltage

OutputVoltage

kVA TapsNetWeight (Lbs)

FrameSize

CatalogNumber

480 240/120

15 (+2, -4: 2.5%) 353 UX72C 9T10C1181G6230 (+2, -4: 2.5%) 480 UX73C 9T10C1182G6275 (+2, -4: 2.5%) 790 DY75C 9T10C1184G62150 (+2, -4: 2.5%) 1610 DY77C 9T10C1186G62

Page 40: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-40 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

15 - 220 kVA Indoor Type QL UL Listed

InputVoltage

OutputVoltage

kVA Frequency (Hz)WiringDiagram No.¹

Weight(Lbs)

FrameSize

CatalogNumber

230 Volts Delta 230Y/133 Volts

15 60Hz 16 240 XV371 9T83B4000G2920 60Hz 16 334 XV372 9T83B4001G2927 60Hz 16 334 XV372 9T83B4002G2934 60Hz 16 334 XV372 9T83B4003G2940 60Hz 16 415 XV373 9T83B4004G2951 60Hz 16 415 XV373 9T83B4005G2975 60Hz 16 620 XV374 9T83B4007G2993 60Hz 16 765 XV375 9T83B4008G29118 60Hz 16 1070 XV376 9T83B4009G29

230 Volts Delta 460Y/266 Volts

15 60Hz 16 240 XV371 9T83B4000G2820 60Hz 16 334 XV372 9T83B4001G2827 60Hz 16 334 XV372 9T83B4002G2834 60Hz 16 334 XV372 9T83B4003G2863 60Hz 16 620 XV374 9T83B4006G2893 60Hz 16 765 XV375 9T83B4008G28118 60Hz 16 1070 XV376 9T83B4009G28145 60Hz 16 1070 XV376 9T83B4010G28175 60Hz 16 1590 XV377 9T83B4011G28

1 See page 10A-45 and 10A-46 for wiring diagrams.

ApplicationThe use of SCR control circuitry with adjustable-speed drives has resulted in a need for a line of isolation transformers specifically designed to meet the demanding requirements of SCR drives. Symmetrically placed taps and added coil bracing minimize mechanical forces caused by the often severe SCR drive duty cycles. These features also help protect the transformer from the regenerative duty and more frequent short-circuits associated with SCR drives.

—Drive isolationAluminumThree-phase

Isolation transformers also reduce line-pollution feedback resulting from SCR firing circuits. The ABB delta-wye designs meet the NEC requirements for grounded secondary neutrals that isolate primary distribution systems. kVA ratings of the DIT line cover most dc motor requirements from 3 to 1000 hp.

Enclosed drive isolation transformers are UL listed.

Page 41: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-41LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

15 - 220 kVA Indoor Type QL UL Listed (continued)

InputVoltage

OutputVoltage

kVA Frequency (Hz)WiringDiagram No.¹

Weight(Lbs)

FrameSize

CatalogNumber

460 Volts Delta 230Y/133

15 60 Hz 16 240 XV371 9T83B4000G2320 60 Hz 16 334 XV372 9T83B4001G2327 60 Hz 16 334 XV372 9T83B4002G2334 60 Hz 16 334 XV372 9T83B4003G2340 60 Hz 16 415 XV373 9T83B4004G2351 60 Hz 16 415 XV373 9T83B4005G2363 60 Hz 16 620 XV374 9T83B4006G2375 60 Hz 16 620 XV374 9T83B4007G2393 60 Hz 16 765 XV375 9T83B4008G23118 60 Hz 16 1070 XV376 9T83B4009G23145 60 Hz 16 1070 XV376 9T83B4010G23220 60 Hz 16 1590 XV377 9T83B4012G23

460 Volts Delta 460Y/266

15 60 Hz 16 240 XV371 9T83B4000G2220 60 Hz 16 334 XV372 9T83B4001G2227 60 Hz 16 334 XV372 9T83B4002G2234 60 Hz 16 334 XV372 9T83B4003G2240 60 Hz 16 415 XV373 9T83B4004G2251 60 Hz 16 415 XV373 9T83B4005G2263 60 Hz 16 620 XV374 9T83B4006G2275 60 Hz 16 620 XV374 9T83B4007G2293 60 Hz 16 765 XV375 9T83B4008G22118 60 Hz 16 1070 XV376 9T83B4009G22145 60 Hz 16 1070 XV376 9T83B4010G22175 60 Hz 16 1590 XV377 9T83B4011G22220 60 Hz 16 1590 XV377 9T83B4012G22

575 Volts Delta 230Y/133

20 60 Hz 16 334 XV372 9T83B4001G2763 60 Hz 16 620 XV374 9T83B4006G2775 60 Hz 16 620 XV374 9T83B4007G27118 60 Hz 16 1070 XV376 9T83B4009G27

575 Volts Delta 460Y/266

15 60 Hz 16 240 XV371 9T83B4000G2627 60 Hz 16 334 XV372 9T83B4002G2634 60 Hz 16 334 XV372 9T83B4003G2651 60 Hz 16 415 XV373 9T83B4005G26145 60 Hz 16 1070 XV376 9T83B4010G26175 60 Hz 16 1590 XV377 9T83B4011G26220 60 Hz 16 1590 XV377 9T83B4012G26

1 See page 10A-45 and 10A-46 for wiring diagrams.

NOTE: Full capacity symmetrical taps (1) +5% and (1) –5%, in primary windings for 230 and 460 Y thru 550 kVA; (1) +6.2% and (1) –6.2% at 750 kVA; (1) +6.4% and (1) –6.4%) at 1000 kVA. With 575 V primary, symmetrical 5% taps apply thru 750 kVA; at 1000 kVA, (1) +5.1% and (1) –5.1%. For ratings less than 15 kV contact ABB Sales Office.

—Drive isolationAluminumThree-phase

Page 42: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-42 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

Wall mount bracket

Frame Size Catalog NumberUX71A 9T18Y1071G07UX71C 9T18Y1071G07UX72A 9T18Y1071G07UX72C 9T18Y1071G07UX73A 9T18Y1071G07UX73C 9T18Y1071G07UX74A 9T18Y1074G07UX74C 9T18Y1074G07UY04A 9T18Y1074G07UY74A 9T18Y1074G07UY74C 9T18Y1074G07DX75C 9T18Y1074G07DY75A 9T18Y1074G07DY75C 9T18Y1074G07YF171 9T18Y5042YF172 9T18Y5043YF174 9T18Y5043YF175 Not availableYF176 Not availableYF177 Not availableYX171 9T18Y1071G07YX172 9T18Y1074G07XV173 9T18Y1074G07YX174 9T18Y1074G07YX175 Not available

Bottom pan

Frame Size Catalog NumberDY08A 9T18Y1078G09DX76A 9T18Y1077G09DX77A 9T18Y1077G09DX77C 9T18Y1077G09DY77A 9T18Y1077G09DY77C 9T18Y1077G09DX78A 9T18Y1078G09DX78C 9T18Y1078G09DY78A 9T18Y1078G09DY78C 9T18Y1078G09DX79A 9T18Y1079G09DY79A 9T18Y1079G09DY79C 9T18Y1079G09DX79C 9T18Y1079G09YF175 9T18Y4504G77YF176 9T18Y4504G79YF177 9T18Y4504G79

316 stainless steel rain shield kit

Frame Size Catalog NumberUX71A 9T18Y1171G06UX71C 9T18Y1171G06UX72A 9T18Y1172G06UX73A 9T18Y1172G06UX72C 9T18Y1172G06UX73C 9T18Y1172G06UY74A 9T18Y1174G06UX74A 9T18Y1174G06UY74C 9T18Y1174G06UX74C 9T18Y1174G06DY75A 9T18Y1174G06DY75C 9T18Y1174G06DX75C 9T18Y1174G06DY76A 9T18Y1176G06DY76C 9T18Y1176G06DX75A 9T18Y1176G06DX76C 9T18Y1176G06

Ground bar kit

Frame Size Catalog NumberUY04A 9T18Y1074G11UX71A 9T18Y1071G11UX71C 9T18Y1071G11UX72A 9T18Y1071G11UX73A 9T18Y1071G11UX72C 9T18Y1071G11UX73C 9T18Y1071G11UY74A 9T18Y1074G11UX74A 9T18Y1074G11UY74C 9T18Y1074G11UX74C 9T18Y1074G11DY75A 9T18Y1074G11DY76A 9T18Y1074G11DY75C 9T18Y1074G11DY76C 9T18Y1074G11DX75A 9T18Y1074G11DX75C 9T18Y1074G11DX76C 9T18Y1074G11

Rain shield kit

Frame Size Catalog NumberUY04A 9T18Y1074G06UX71A 9T18Y1071G06UX71C 9T18Y1071G06UX72A 9T18Y1072G06UX72C 9T18Y1072G06UX73A 9T18Y1072G06UX73C 9T18Y1072G06UY74A 9T18Y1074G06UX74A 9T18Y1074G06UY74C 9T18Y1074G06UX74C 9T18Y1074G06DY08A 9T18Y1077G06DY75A 9T18Y1074G06DY75C 9T18Y1074G06DX75A 9T18Y1076G06DX75C 9T18Y1074G06DY76A 9T18Y1076G06DY76C 9T18Y1076G06DX76A 9T18Y1077G06DX76C 9T18Y1076G06DX77A 9T18Y1077G06DX77C 9T18Y1077G06DY77A 9T18Y1077G06DY77C 9T18Y1077G06DY78C 9T18Y1077G06DY78A 9T18Y1077G06DX78A 9T18Y1077G06DX78C 9T18Y1077G06DX79A 9T18Y1079G06DX79C 9T18Y1079G06DY79A 9T18Y1079G06DY79C 9T18Y1079G06YF171 9T18Y4317G05YF172 9T18Y4317G06YF173 9T18Y4317G06YF174 9T18Y1074G06YF175 9Y18Y4322G77YF176 9T18Y4322G88YF177 9T18Y4322G88YX171 9T18Y1072G06YX172 9T18Y1074G06XV173 9T18Y1074G06YX174 9T18Y1074G06 YX175 9T18Y1077G06

Lug kits for QL transformers

Frame Size Catalog NumberUY04A 9T18Y1074G10UX71A 9T18Y1071G10UX71C 9T18Y1071G10UX72A 9T18Y1072G10UX73A 9T18Y1072G10UX72C 9T18Y1072G10UX73C 9T18Y1072G10UY74A 9T18Y1074G10UX74A 9T18Y1074G10UY74C 9T18Y1074G10UX74C 9T18Y1074G10DY08A 9T18Y1078G10DY75A 9T18Y1075G10DY75C 9T18Y1075G10DX75C 9T18Y1075G10DY76A 9T18Y1076G10DY76C 9T18Y1076G10DX75A 9T18Y1076G10DX76C 9T18Y1076G10DY77A 9T18Y1077G10DY77C 9T18Y1077G10DX76A 9T18Y1077G10DX77A 9T18Y1077G10DX77C 9T18Y1077G10DY78A 9T18Y1078G10DY78C 9T18Y1078G10DX78A 9T18Y1078G10DX78C 9T18Y1078G10DX79A 9T18Y1079G10DX79C 9T18Y1079G10DY79A 9T18Y1079G10DY79C 9T18Y1079G10YF171 9T18Y7240G02YF172 9T18Y7241G03YF174 9T18Y7240G03YF175 9T18Y7242G07YF176 9T18Y7242G05YF177 9T18Y7242G05

—Accessories and lugsSingle-phase and three-phase

Page 43: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-43LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Accessories and lugsSingle-phase and three-phase

Single-phase lug kits

Coil MaterialTemp Rise kVA

Frame Size

Primary Bus Bar Holes (Qty/Size)

Secondary Bus Bar Holes (Qty/Size) Lug Kit Cable Size

Stud Diameter Lug Qty

Alumninum/ Copper

115 or 150

15/25 YF171 (2) .406 dia (2) .406 dia 9T18Y7240G02 250MCM-6 (1) 21/64 P250 837.5

50 YF172 (2) .406 dia (2) .406 dia 9T18Y7241G03 250MCM-6 (1) 21/64 P250 4350MCM-6 (1) 13/32 P350 4

75 YF174 (2) .406 dia (2) .406 dia 9T18Y7240G03 250MCM-6 (1) 21/64 P250 12100 YF175 (2) .406 dia (2) .406 dia 9T18Y7242G07 350MCM-6 (1) 13/32 P350 12

150 167 YF176 (2) .406 dia (2) .406 dia 9T18Y7242G05 350MCM-6 (1) 13/32 P350 8500MCM-4 (1) 13/32 P500 12

Three-phase lug kits

Coil MaterialTemp Rise kVA

Frame Size

Primary Bus Bar Holes (Qty/Size)

Secondary Bus Bar Holes (Qty/Size) Lug Kit Cable Size

Stud Diameter Lug Qty

Aluminum

115 or 150

15 UX71A (2) .406 dia (2) .406 dia 9T18Y1071G10 1/0-14 (1) 17/64 P125 730 UX72A (2) .406 dia (2) .406 dia 9T18Y1072G10 250MCM-6 (1) 21/64 P250 745 UX73A (2) .406 dia (2) .406 dia 9T18Y1072G10 250MCM-6 (1) 21/64 P250 7

500 DX79A (4) .563 dia (6) .563 dia 9T18Y1079G10 350MCM-6 (1) 13/32 P350 9500MCM-4 (1) 13/32 P500 24

150 75 UY74A (2) .406 dia (2) .406 dia 9T18Y1074G10 250MCM-6 (1) 21/64 P250 3UY04A 350MCM-6 (1) 13/32 P350 4

115 75 UX74A (2) .406 dia (2) .406 dia 9T18Y1074G10 250MCM-6 (1) 21/64 P250 3350MCM-6 (1) 13/32 P350 4

150

112.5 DY75A (1) .563 dia (2) .563 dia 9T18Y1075G10 350MCM-6 (1) 13/32 P350 7

150 DY76A (1) .563 dia (2) .563 dia 9T18Y1076G10 350MCM-6 (1) 13/32 P350 3500MCM-4 (1) 13/32 P500 4

225 DY77A (2) .563 dia (4) .563 dia 9T18Y1077G10 350MCM-6 (1) 13/32 P350 6500MCM-4 (1) 13/32 P500 8

300DY78A

(4) .563 dia (6) .563 dia 9T18Y1078G10350MCM-6 (1) 13/32 P350 6500MCM-4 (1) 13/32 P500 2

DY08A 600MCM-2 (1) 13/32 P600 6

500 DY79A (4) .563 dia (6) .563 dia 9T18Y1079G10 350MCM-6 (1) 13/32 P350 9500MCM-4 (1) 13/32 P500 24

115

112.5 DX75A (1) .563 dia (2) .563 dia 9T18Y1076G10 350MCM-6 (1) 13/32 P350 3500MCM-4 (1) 13/32 P500 4

150 DX76A (2) .563 dia (4) .563 dia 9T18Y1077G10 350MCM-6 (1) 13/32 P350 6500MCM-4 (1) 13/32 P500 8

225 DX77A (2) .563 dia (4) .563 dia 9T18Y1077G10 350MCM-6 (1) 13/32 P350 6500MCM-4 (1) 13/32 P500 8

300 DX78A (2) .563 dia (4) .563 dia 9T18Y1078G10350MCM-6 (1) 13/32 P350 6500MCM-4 (1) 13/32 P500 2600MCM-2 (1) 13/32 P600 6

Copper

150 or 115

15 UX71C (2) .406 dia (2) .406 dia 9T18Y1071G10 1/0-14 (1) 17/64 P125 730 UX72C (2) .406 dia (2) .406 dia 9T18Y1072G10 250MCM-6 (1) 21/64 P250 745 UX73C (2) .406 dia (2) .406 dia 9T18Y1072G10 250MCM-6 (1) 21/64 P250 7

150 75 UY74C (2) .406 dia (2) .406 dia 9T18Y1074G10 250MCM-6 (1) 21/64 P250 3350MCM-6 (1) 13/32 P350 4

115 75 UX74C (2) .406 dia (2) .406 dia 9T18Y1074G10 250MCM-6 (1) 21/64 P250 3350MCM-6 (1) 13/32 P350 4

150

112.5 DY75C (1) .563 dia (2) .563 dia 9T18Y1075G10 350MCM-6 (1) 13/32 P350 7

150 DY76C (1) .563 dia (2) .563 dia 9T18Y1076G10 350MCM-6 (1) 13/32 P350 3500MCM-4 (1) 13/32 P500 4

225 DY77C (2) .563 dia (4) .563 dia 9T18Y1077G10 350MCM-6 (1) 13/32 P350 6500MCM-4 (1) 13/32 P500 8

300 DY78C (4) .563 dia (6) .563 dia 9T18Y1078G10350MCM-6 (1) 13/32 P350 6500MCM-4 (1) 13/32 P500 2600MCM-2 (1) 13/32 P600 6

500 DY79C (4) .563 dia (6) .563 dia 9T18Y1079G10 350MCM-6 (1) 13/32 P350 9500MCM-4 (1) 13/32 P500 24

115

112.5 DX75C (1) .563 dia (2) .563 dia 9T18Y1075G10 350MCM-6 (1) 13/32 P350 7

150 DX76C (1) .563 dia (2) .563 dia 9T18Y1076G10 350MCM-6 (1) 13/32 P350 3500MCM-4 (1) 13/32 P500 4

225 DX77C (2) .563 dia (4) .563 dia 9T18Y1077G10 350MCM-6 (1) 13/32 P350 6500MCM-4 (1) 13/32 P500 8

300 DX78C (2) .563 dia (4) .563 dia 9T18Y1078G10350MCM-6 (1) 13/32 P350 6500MCM-4 (1) 13/32 P500 2600MCM-2 (1) 13/32 P600 6

Page 44: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-44 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

Enclosure kits

Frame Size Catalog NumberUY04A 9T18Y1074UX71A 9T18Y1071UX71C 9T18Y1071UX72A 9T18Y1072UX73A 9T18Y1072UX72C 9T18Y1072UX73C 9T18Y1072UY74A 9T18Y1074UX74A 9T18Y1074UY74C 9T18Y1074UX74C 9T18Y1074DY08A 9T18Y1078DY75A 9T18Y1075DY75C 9T18Y1075DX75C 9T18Y1075DY76A 9T18Y1076DY76C 9T18Y1076DX75A 9T18Y1076DX76C 9T18Y1076DY77A 9T18Y1077DY77C 9T18Y1077DX76A 9T18Y1077DX77A 9T18Y1077DX77C 9T18Y1077DY78A 9T18Y1078DY78C 9T18Y1078DX78A 9T18Y1078DX78C 9T18Y1078DX79A 9T18Y1079DY79A 9T18Y1079DY79C 9T18Y1079

This style enclosure is used with the following frames:

Frame Size Frame SizeUX71A UY74CUX71C UX74CUX72A DY75AUX72C DY75CUX73A DX75AUX73C DX75CUY74A DY76AUX74A DY76C

This style enclosure is used with the following frames:

Frame Size Frame SizeDX76A DX79ADX76C DX79CDX77A YF171DX77C YF172DY77A YF173DY77C YF174DY78C YF175DY78A YF176DX78A YF177DX78C -

Front/back panel

Frame Size Catalog NumberUY04A 9T18Y1074G03UX71A 9T18Y1071G03UX71C 9T18Y1071G03UX72A 9T18Y1072G03UX73A 9T18Y1072G03UX72C 9T18Y1072G03UX73C 9T18Y1072G03UY74A 9T18Y1074G03UX74A 9T18Y1074G03UY74C 9T18Y1074G03UX74C 9T18Y1074G03DY08A 9T18Y1078G03DY75A 9T18Y1075G03DY75C 9T18Y1075G03DX75C 9T18Y1075G03DY76A 9T18Y1076G03DY76C 9T18Y1076G03DX75A 9T18Y1076G03DX76C 9T18Y1076G03DY77A 9T18Y1077G03DY77C 9T18Y1077G03DX76A 9T18Y1077G03DX77A 9T18Y1077G03DX77C 9T18Y1077G03DY78A 9T18Y1078G03DY78C 9T18Y1078G03DX78A 9T18Y1078G03DX78C 9T18Y1078G03DX79A 9T18Y1079G03DY79A 9T18Y1079G03DY79C 9T18Y1079G03

Side panel

Frame Size Catalog NumberUY04A 9T18Y1074G04UX71A 9T18Y1071G04UX71C 9T18Y1071G04UX72A 9T18Y1072G04UX73A 9T18Y1072G04UX72C 9T18Y1072G04UX73C 9T18Y1072G04UY74A 9T18Y1074G04UX74A 9T18Y1074G04UY74C 9T18Y1074G04UX74C 9T18Y1074G04DY08A 9T18Y1078G04DY75A 9T18Y1075G04DY75C 9T18Y1075G04DX75C 9T18Y1075G04DY76A 9T18Y1076G04DY76C 9T18Y1076G04DX75A 9T18Y1076G04DX76C 9T18Y1076G04DY77A 9T18Y1077G04DY77C 9T18Y1077G04DX76A 9T18Y1077G04DX77A 9T18Y1077G04DX77C 9T18Y1077G04DY78A 9T18Y1078G04DY78C 9T18Y1078G04DX78A 9T18Y1078G04DX78C 9T18Y1078G04DX79A 9T18Y1079G04DY79A 9T18Y1079G04DY79C 9T18Y1079G04

Cover (top) panel

Frame Size Catalog NumberUY04A 9T18Y1074G05UX71A 9T18Y1071G05UX71C 9T18Y1071G05UX72A 9T18Y1072G05UX73A 9T18Y1072G05UX72C 9T18Y1072G05UX73C 9T18Y1072G05UY74A 9T18Y1074G05UX74A 9T18Y1074G05UY74C 9T18Y1074G05UX74C 9T18Y1074G05DY08A 9T18Y1078G05DY75A 9T18Y1074G05DY75C 9T18Y1074G05DX75C 9T18Y1074G05DY76A 9T18Y1076G05DY76C 9T18Y1076G05DX75A 9T18Y1076G05DX76C 9T18Y1076G05DY77A 9T18Y1077G05DY77C 9T18Y1077G05DX76A 9T18Y1077G05DX77A 9T18Y1077G05DX77C 9T18Y1077G05DY78A 9T18Y1078G05DY78C 9T18Y1078G05DX78A 9T18Y1078G05DX78C 9T18Y1078G05DX79A 9T18Y1079G05DY79A 9T18Y1079G05DY79C 9T18Y1079G05

—Enclosure parts

FRONT/BACKPANEL

COVER (TOP)PANEL

SIDE PANEL

BASE

ENCLOSURE KIT: 1 COVER + 2 SIDES + 2 FRONTS

FRONT/BACKPANEL

COVER (TOP)PANEL

SIDE PANEL

GRILL

BOTTOM PAN(NOT SHOWN)

ENCLOSURE KIT: 1 COVER + 2 SIDES + 2 FRONTSENCLOSURE KIT: 1 COVER + 2 SIDES + 2 FRONTS ENCLOSURE KIT: 1 COVER + 2 SIDES + 2 FRONTS

Page 45: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-45LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Wiring diagrams

Diagram 9Diagram 8Diagram 7

Diagram 11Diagram 10 Diagram 12

Diagram 6Diagram 5Diagram 4

Diagram 1 Diagram 3Diagram 2

Page 46: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-46 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Wiring diagrams

Diagram 14 Diagram 15Diagram 13

Diagram 18Diagram 17Diagram 16

Diagram 22

Diagram 25 Diagram 26

Diagram 23 Diagram 24

Diagram 21Diagram 19 Diagram 20

Page 47: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-47LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Dimensions

Three-phase, vented QL transformersIncludes General Purpose, K-factor, K-factor Low Noise,Low Noise, Guard I™, Midtapped, Drive Isolation

Product Weights and Dimensions Enclosure DimensionsMounting Feet

Dimensions Weight

Frame Size Outline Drawing No. Width (in.) Depth (in.) Height (in.) Width (in.) Depth (in.) Painted (lbs.) 316 Stainless Steel (lbs.)UX71A 303B111GEUXP71A 18.7 16.9 29.3 21.2 15.1 231 251UX71C 303B111GEUXP71C 18.7 16.9 29.3 21.2 15.1 230 250UX72A 303B111GEUXP72A 23.8 18.4 34.7 26.2 16.6 330 350UX72C 303B111GEUXP72C 23.8 18.4 34.7 26.2 16.6 353 373UX73A 303B111GEUXP73A 23.8 18.4 34.7 26.2 16.6 444 464UY72A 303B111GEUYP72A 23.8 18.4 34.7 26.2 16.6 297 317UY73A 303B111GEUYP73A 23.8 18.4 34.7 26.2 16.6 363 383UX73C 303B111GEUXP73C 23.8 18.4 34.7 26.2 16.6 480 500UY74A 303B111GEUYP74A 31.8 24 35.7 34.3 22.3 561 581UY04C 303B111GEUYP04C 31.8 24 35.7 22.3 34.3 503 523UY74C 303B111GEUYP74C 31.8 24 35.7 34.3 22.3 661 681UX74A 303B111GEUXP74A 31.8 24 35.7 34.3 22.3 603 623UX74C 303B111GEUXP74C 31.8 24 35.7 34.3 22.3 748 768DY75A 303B111GEDYP75A 31.8 24 42.2 34.3 22.3 680 760DY75C 303B111GEDYP75C 31.8 24 42.2 34.3 22.3 790 870DX75A 303B111GEDXP75A 34.8 24 45.8 37.3 22.3 830 850DX75C 303B111GEDXP75C 31.8 24 42.2 34.3 22.3 900 980DY76A 303B111GEDYP76A 34.8 24 45.8 37.3 22.3 1030 1050DY76C 303B111GEDYP76C 34.8 24 45.8 37.3 22.3 1085 1105DX76A 303B112GEDXP76A 38.4 33 47.4 41.1 32 1250 NADX76C 303B111GEDXP76C 34.8 24 45.8 37.3 22.3 1240 1260DY77A 303B112GEDYP77A 38.4 33 47.4 41.4 32 1450 NADY77C 303B112GEDYP77C 38.4 33 47.4 41.4 32 1610 NADX77A 303B112GEDXP77A 38.4 33 47.4 41.4 32 1670 NADY78A 303B112GEDYP78A 38.4 33 57.1 41.4 32 1670 NADX77C 303B112GEDXP77C 38.4 33 47.4 41.4 32 1847 NADY78C 303B112GEDYP78C 38.4 33 57.1 41.4 32 1970 NADX78A 303B112GEDXP78A 38.4 33 57.1 41.4 32 1985 NADX78C 303B112GEDXP78C 38.4 33 57.1 41.4 32 2150 NADX79A 303B112GEDXP79A 46.5 37.8 65.7 50.1 37 2900 NADX79C 303B112GEDXP79C 46.5 37.8 65.7 50.1 37 3720 NADY79A 303B112GEDYP79A 46.8 38.0 65.7 50.1 37.0 2713 NA

QL Transformer(Front Panel Removed)

Single-phase vented QL transformers

Product Weights and Dimensions Weight (Lb) Enclosure Dimensions (In)

Mounting Feet Dimensions

Frame Size Outline Drawing No. AL CU

Height (In.)

Width (In.)

Depth (In.)

Minimum Installation Clearance (4 sides) (in.)

Minimum Installation Clearance (Top) (in.)

Width (in.)

Depth (in.)

YF171 303B406AAP071 320 350 32.1 23.8 18.4 6.0 12.0 – –YF172 303B406AAP072 400 500 35.7 31.8 24 6.0 12.0 – –XV173 303B406AAP073 500 520 35.7 31.8 24 6.0 12.0 – –YF174 303B406AAP074 510 625 39.9 31.8 24 6.0 12.0 – –YF175 303B932AAP075 900 1050 37.4 29.5 28.5 6.0 12.0 – –YF176 303B932AAP076 1360 1675 45.5 38.5 33 6.0 12.0 – –YF177 303B932AAP077 1700 1960 45.5 38.5 33 6.0 12.0 – –YX171 303B409CAP071 320 350 18.4 26.2 34.7 6.0 12.0 25.1 15.3YX172 303B409CAP072 460 510 24 34.3 35.7 6.0 12.0 33.1 21.0XV173 303B409CAP073 490 520 24 34.3 35.7 6.0 12.0 33.1 21.0YX174 303B409CAP074 600 750 24 34.3 42.2 6.0 12.0 33.1 21.0YX175 303B409CAP075 950 N/A 28.5 32.4 37.4 6.0 12.0 30.6 23.0

Page 48: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-48 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Dimensions

Three-phase vented QL transformers

Package Weights and Dimensions Weight (Lb) Dimensions (In)Frame Size Outline Drawing No. AL AL-SS CU CU-SS Height (in) Width (in.) Depth (in.)UX71A 303B111GEUXP71A 268 288 NA NA 35.00 25.50 30.50UX71C 303B111GEUXP71C NA NA 267 287 35.00 25.50 30.50UX72A 303B111GEUXP72A 377 397 NA NA 40.73 30.25 30.50UX72C 303B111GEUXP72C NA NA 400 420 40.73 30.25 30.50UX73A 303B111GEUXP73A 491 511 NA NA 40.73 30.25 30.50UY72A 303B111GEUYP72A 344 364 NA NA 40.73 30.25 30.50UY73A 303B111GEUYP73A 410 430 NA NA 40.73 30.25 30.5UX73C 303B111GEUXP73C NA NA 527 547 40.73 30.25 30.50UY74A 303B111GEUYP74A 598 618 NA NA 35.00 25.50 30.50UY04C 303B111GEUYP04C NA NA 554 574 41.63 30.25 38.25UY74C 303B111GEUYP74C NA NA 712 732 41.63 30.25 38.25UX74A 303B111GEUXP74A 654 674 NA NA 41.63 30.25 38.25UX74C 303B111GEUXP74C NA NA 799 819 41.63 30.25 38.25DY75A 303B111GEDYP75A 730 810 NA NA 48.38 30.25 38.25DY75C 303B111GEDYP75C NA NA 840 920 48.38 30.25 38.25DX75A 303B111GEDXP75A 888 NA NA 908 51.88 30.00 41.00DX75C 303B111GEDXP75C NA NA 950 1030 48.38 30.25 38.25DY76A 303B111GEDYP76A 1088 1108 NA NA 51.88 30.00 41.00DY76C 303B111GEDYP76C NA NA 1143 1163 51.88 30.00 41.00DX76A 303B112GEDXP76A 1305 NA NA NA 52.78 41.50 47.75DX76C 303B111GEDXP76C NA NA 1298 1318 51.88 30.00 41.00DX77A 303B112GEDXP77A 1725 NA NA NA 52.78 41.50 47.75DY77C 303B112GEDYP77C NA NA 1665 NA 52.78 41.50 47.75DX77A 303B112GEDXP77A 1655 NA NA NA 40.28 41.50 47.75DY78A 303B112GEDYP78A 1725 NA NA NA 62.48 41.50 47.75DX77C 303B112GEDXP77C NA NA 1902 NA 52.78 41.5 47.7DY78C 303B112GEDYP78C NA NA 2025 NA 62.48 41.50 47.75DX78A 303B112GEDXP78A 2040 NA NA NA 62.48 41.50 47.75DX78C 303B112GEDXP78C NA NA 2205 NA 62.48 41.50 47.75DX79A 303B112GEDXP79A 2964 NA NA NA 72.20 43.00 56.00DX79C 303B112GEDXP79C NA NA 3784 NA 72.20 43.00 56.00DY79A 303B112GEDYP79A 2777 NA NA NA 72.20 43.00 56.00

Single-phase vented QL transformers

Package Weights and Dimensions Weight (Lb) Dimensions (In)Frame Size Outline Drawing No. AL CU Height (in) Width (in.) Depth (in.)YF171 303B406AAP071 362 392 38.13 27 30.25YF172 303B406AAP072 448 548 41.63 30.25 34.75XV173 303B406AAP073 548 568 41.63 30.25 34.75YF174 303B406AAP074 741 673 46 30.25 34.75YF175 303B932AAP075 925 1075 43.78 30 32YF176 303B932AAP076 1415 1730 52.88 41.5 47.75YF177 303B932AAP077 1755 2015 52.88 41.5 47.75YX171 303B409CAP071 367 397 40.73 30.25 30.5YX172 303B409CAP072 511 561 41.63 30.25 38.25XV173 303B409CAP073 541 551 41.63 30.25 38.25YX174 303B409CAP074 650 800 48.38 30.25 38.25YX175 303B409CAP075 TBD NA TBD TBD TBD

Page 49: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-49LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Dimensions

Guard II™ transformers

Frame Size

Outline Drawing No.

Height (In.)

Width (In.)

Depth (In.)

XV371 303B403AAP071 34.5 18.7 16.9XV372 303B403AAP072 41.3 23.8 18.4XV373 303B403AAP073 41.3 23.8 18.4XV374 303B403AAP074 44.8 31.8 24XV375 303B403AAP075 49.1 31.8 24

Guard III™ harmonic mitigating transformers

Frame Size

Outline Drawing No.

Height (In.)

Width (In.)

Depth (In.)

H371C 303B431SLP071 32.3 23.8 18.4H372C 303B431SLP072 35.7 31.8 24H373C 303B431SLP073 35.7 31.8 24H374C 303B431SLP074 39.9 31.8 24H375C 303B931SLP075 45.5 38.6 33H376C 303B931SLP076 45.4 38.5 33YF378 303B931SLP078 57.0 38.5 33

TENV transformers

Frame Size

Outline Drawing No.

Height (In.)

Width (In.)

Depth (In.)

XV372 303B405AAP072 41.3 23.8 18.4XV373 303B405AAP073 41.3 23.8 18.4XV374 303B405AAP074 44.8 31.8 24XV375 303B405AAP075 49.1 31.8 24

Servicenter™ transformers

Frame Size

Outline Drawing No.

Height (In.)

Width (In.)

Depth (In.)

16350 303B915AAP005 32.5 10.75 11.1216600 303B915AAP007 32.5 10.75 11.1219400 303B915AAP010 35 12.62 12.6219500 303B915AAP015 35 12.62 12.6250500 303B915AAP025 44.75 16.75 16XV371 303B404AAP015 27.3 27.4 16.9XV372 303B404AAP022 32.2 34.5 24XV372 303B404AAP030 32.2 34.5 24Y371C 303B404AAP015 27.3 27.4 16.9Y372C 303B404AAP022 32.2 34.5 24Y372C 303B404AAP030 32.2 34.5 24

Page 50: BUYLOG SECTION 10A Low voltage dry type transformers 600V ...

10A-50 LOW VOLTAGE DRY TYPE TRANSFORMERS, BUYLOG SECTION 10A

—Notes