BusBar Short Circuit Calculation
Click here to load reader
-
Upload
bhaskarinvu -
Category
Documents
-
view
2.236 -
download
18
Transcript of BusBar Short Circuit Calculation
01.03.2007 (Rev.)
CALCULATIONS IN SUPPORT OF FAULT LEVEL OF 65 kA FOR ONE SECOND
4000 A TP ALUMINIUM BUS DUCT
DRAWING NO.G 7643 R0
i) Rating 4000 Amps ii) Bus Bars Per Phase 3 x 200 mm x 12 mm iii) Fault Level 65 kA for 1 Second iv) Enclosure In a ventilated room v) Ambient Temperature 50OC vi) Working Temperature 85OC vii) Rating Chart INDAL Electrical Grade Aluminium
(1) THERMAL RATING
a) Rating as per Table 2 (INDAL) 5300 Amps For 3 x 200 mm x 12 mm Aluminium Bus Bars
b) Derating Factor
• Temperature Rise of 35OC 0.817 over an ambient of 50OC. • Magnetic Enclosure 0.850
• Proximity Factor 1.000
• Enclosure Factor 0.920 • Paint / Sleeving Factor 1.250 • Combined Derating Factor 0.817 x 0.850 x 1.000 x 0.920 x 1.250
0.799 Say 0.80
c) Actual Current Rating of above 0.80 x 5300 Bus Bars 4240 Amps
Conclusion Safe as the rating works out to be 4240 Amps as against 4000 Amps required.
….Contd..2
(2)
(2) SHORT TIME RATING
I Short Circuit Current = 65 kA T Short Circuit Time = 1 Second Q1 Initial Temperature = 85OC Q2 = Final Temperature = 200OC A = Cross Sectional Area in Sq. inch A = I x t
14 x 10 4 Q2 + 258
log 10 Q1 + 258
X) Cross sectional Area in case of initial temperature of 85OC and final temperature of 200OC. = 65 x 103 x 1
14 x 10 4
458 log 10
343 = 1.309 Sq. inch = 845 Sq.mm
Conclusion Area considered is 7200 Sq.mm – Hence SAFE
(3) MECHANICAL STRESS & INSULATOR SPAN FM Mechanical Force Developed at the time of Short Circuit.
I Short Circuit Current.
K Space Factor For Rectangular Bus Bar.
S Spacing between the Phases = 190 mm.
FM = 16 x I 2 x 10 - 4 x K N/M S
….Contd..3
(3)
The value of K as calculated from the graph given in J&P Hand Book page 212 by taking the ratio (S-a) / (a+b) on comparing it with a/b will be 0.50. Hence FM = 16 x 65 x 70 x 10 6 x 10 - 4 x 0.50
190
= 19158 N/M = 1954.88 Kg Per Meter
Force Developed at a span of 350 mm = 1954.88 x 0.350 = 684.20 Kg.
Since there are two supports – one at on top and one at bottom, force per support will be 342.10 Kg.
a) Powermat supports (SMC) type 312-K having capacity to withstand force of
2000 kg will be provided meaning thereby that there will be a safety factor of 5.85 times.
b) Distance : The support to support distance of max 350 mm will be
maintained.
c) Above calculations / recommendations are OK for a phase to phase gap of 130 mm.
(4) FINAL DESIGN OFFERED
Chamber Size 700 mm (minimum) Bus Bars 3 x 200 mm x 12 mm per phase Phase to Phase Gap 130 mm Support to Support Distance 350 mm