BUS BAR Presantation

download BUS BAR Presantation

of 35

Transcript of BUS BAR Presantation

  • 7/27/2019 BUS BAR Presantation

    1/35

    BUS BAR

    PROTECTION

  • 7/27/2019 BUS BAR Presantation

    2/35

  • 7/27/2019 BUS BAR Presantation

    3/35

    Requirement of bus bar protection

    scheme Complete reliability

    Must be completely stable under all through fault conditions.

    Must be capable of complete discrimination between sections

    of bus bars.

    Must operate with high speed to minimize damage andmaintain system stabillity.

  • 7/27/2019 BUS BAR Presantation

    4/35

  • 7/27/2019 BUS BAR Presantation

    5/35

  • 7/27/2019 BUS BAR Presantation

    6/35

    Types of protection system

    A number of protection systems have

    been devised popular among them are

    Frame earth protection

    High impedance differential protection

    Low impedance differential protection

  • 7/27/2019 BUS BAR Presantation

    7/35

    Frame earth protection

    Only earth fault system

    Involves measuring fault current from switchgear

    frame to earth

    Switchgear insulated by standing on concrete plinth Only one earth point allowed switchgear

    C.T mounted on single earth conductor use to

    energize instantaneous relays

    All cable glands must be insulated

  • 7/27/2019 BUS BAR Presantation

    8/35

    Differential protection

    Uses Merz-price circulating current

    principle . All current entering and leaving

    bus bar are compared. One set of CT,s for

    each circuit associated with a particularzone are all connected to a relay

    A single element relay gives earth fault

    protection only. A three element relaygives phase and earth fault protection.

  • 7/27/2019 BUS BAR Presantation

    9/35

  • 7/27/2019 BUS BAR Presantation

    10/35

  • 7/27/2019 BUS BAR Presantation

    11/35

    High impedance differential

    protection This is a versatile and reliable protection system

    applied to many different Busbar configurations.if CT requirements are met , schemeperformance may be predicated by calculation

    without heavy current conjunctive tests. Uses equal ratio CT,s .Scheme assumes that

    with heaviest through fault , one CT saturates ,the other not.To ensure stability , voltage settingof relay circuit made higher than voltagedeveloped accros relay circuit. To achieve thisan extra relay circuit resistance is required this isnon as stabilizing resistance.

  • 7/27/2019 BUS BAR Presantation

    12/35

  • 7/27/2019 BUS BAR Presantation

    13/35

  • 7/27/2019 BUS BAR Presantation

    14/35

    aEffective settings

    Since in each zone of protection there are sevaeral CT,sin the paralell with the relay and each other, thecombined CT magnitising currents will increase theprimary operating current.

    POC=CT ratio (Ir+INLR+NIm) Where

    Ir = relay setting current

    IM =CT magnetising current

    N = number of paralleled CT,s INLR = non linear resistor current at relay setting

    voltage.

  • 7/27/2019 BUS BAR Presantation

    15/35

    Primary operating current

    The value of primary operating current

    should be arround 30%of minimum fault

    current avalible . This ensures sufficient

    relay current during internal faultconditions for high speed operation.

  • 7/27/2019 BUS BAR Presantation

    16/35

    Through fault stability

    Busbar protection stability limit is based on

    maximum through faulrt current.

    Generally this value is derived from the

    rating of the associtiated switchgear

    irrespective of existing faul level,since it

    can be expected that system will develop

    up to limit of rating.

  • 7/27/2019 BUS BAR Presantation

    17/35

    Check feature

    Usually provided by duplication of primary

    protection using second set of CTs on all

    circuits other than bus section and coupler

    units.Check system forms one zoneonly,covering whole of the busbar system

    and not discriminating between faults on

    various sections

  • 7/27/2019 BUS BAR Presantation

    18/35

    Use of non linear resistor

    Under in zone faults conditions it is possible for voltagesabove the relay withstand of 3kv peak to beproduced.metrosil non linear resistor may be necessaryto limit the peak voltage below this level.

    Approximately peak volts=2 Metrosil characteristics :- v=cib

    where:-v and I are peak values

    c=constant depending on metrosil

    construction b=constant in range of .2-.25

    The values of c and b are chosen to limit metrosil voltageto less than 3kv peak at maximum fault current.

  • 7/27/2019 BUS BAR Presantation

    19/35

    Metrosil limitation of ray voltage

    To ensure primary operating current not

    adversly affected metrosil constant c

    must be sufficently high to restrict metrosil

    current at relay setting voltage VS.

    Typical currents :-

    30 ma for use with one

    ampere CTs100 ma for use with 5ampere CTs

  • 7/27/2019 BUS BAR Presantation

    20/35

    Differential relays

    Relays used for high impedence protection

    are high stabililty unbiased and tuned to

    nominal frequency.

    Two modular types are MFAC14/34

  • 7/27/2019 BUS BAR Presantation

    21/35

    CT wiring supervision

    Open circuit connections between CTs and relay

    circuits result in unbalanced currents whioch

    may operate the protection.

    Supervision is applied by voltage relay acrossdifferential relay circuit.supervision relays is time

    delayed gives alarm and also short out bus

    wires to protect differential relay circuit.typiucal

    effective setting is 25 primary amperes or 10%of lowest circuit rating which ever is greater.

  • 7/27/2019 BUS BAR Presantation

    22/35

  • 7/27/2019 BUS BAR Presantation

    23/35

  • 7/27/2019 BUS BAR Presantation

    24/35

    Current transformers and wiring

    CT must be low reactance tyoe(class x)and haveidentical terms ratio. They should be of similardesign or if not of rreasonabely matchedmagnetic characteristic.it is common character

    to use CTs having one ampere secendories Load burdens between various sets of CTs must

    be kept low . Usually bus wires are run in closedring between breaker control panels.

    Typical routes:-CTs to marshelling kiosk, MK toisolator yo auxallaries, loop between MK

  • 7/27/2019 BUS BAR Presantation

    25/35

  • 7/27/2019 BUS BAR Presantation

    26/35

  • 7/27/2019 BUS BAR Presantation

    27/35

  • 7/27/2019 BUS BAR Presantation

    28/35

    Isolator auxillary switches

    On double bus installations , the two bars

    are treated as separate zones. The bus

    isolator switches must carry auxillary

    contacts to transfer CTs and also trippingsircuits between zones.

    Auxillary switches should be early make

    Late break

  • 7/27/2019 BUS BAR Presantation

    29/35

  • 7/27/2019 BUS BAR Presantation

    30/35

    Tripping circuits

    One trip[ping rel;ay device is required for

    each feeder breaker and two far each bus

    section or bus coupler breakers.both

    ma8in and check relays must beenergized before triiping relays trip all

    breakers assocaited with zones

  • 7/27/2019 BUS BAR Presantation

    31/35

  • 7/27/2019 BUS BAR Presantation

    32/35

    Busbar protection and breaker fail

    Where breaker fail protection is applied to

    a system, back tripping of associated

    breaker is required in the event of breaker

    failure. Often,breaker fail protection isarranged in conjunctio with busbar

    protection tripping circuits to initiate triiping

    of breakers opn busbar zone associatedwith field breaker

  • 7/27/2019 BUS BAR Presantation

    33/35

  • 7/27/2019 BUS BAR Presantation

    34/35

    Low inmpedence busbar protection

    Low impedence protection has been used

    for many years.in paricular on installations

    where CT output not suuficient for high

    impedence application.

    Low impedence protection also operates

    on circulating cuurrents. Through fault

    stability often assured by low valuestabilizing resistance plus throug load bias

  • 7/27/2019 BUS BAR Presantation

    35/35