Bulletin 100 Line - Rockwell Automation · Circuit Breaker Type Page 264 • Bulletin 105 Reversing...
Transcript of Bulletin 100 Line - Rockwell Automation · Circuit Breaker Type Page 264 • Bulletin 105 Reversing...
™
3
Bulletin 100 LineIEC Contactors, Starters, and Overload Relays
Section Overview
Motor Protection Circuit Breakers• Bulletin 140M Motor Protection Circuit Breakers Page 7
• Bulletin 140M Motor Circuit Protectors Page 9
• Bulletin 140M Accessories Page 14
Molded Case Circuit Breakers• Bulletin 140U Molded Case Circuit Breakers Page 38
IEC Contactors• Bulletin 100/104-M Miniature Contactors Page 65
• Bulletin 100/104-C Contactors Page 66
• Bulletin 100/104-D Contactors Page 69
• Bulletin 100-G Contactors Page 73
• Bulletin 100Q Capacitor Switching Contactors Page 74
• Bulletin 100L Lighting Contactors Page 75
• Bulletin 100S/104S Safety Contactors Page 76
• Bulletin 170 Wye-Delta Kits Page 88
• Bulletin 100 DeviceNet™ Starter Accessory Page 81
• Bulletin 100 Line Accessories Page 84
IEC Overload Relays• Bulletin 193-E (E1 and E2) Solid-State Overload Relays Page 138
• Bulletin 193 E3 and E3 Plus Solid-StateOverload Relays Page 143
• Bulletin 193-EF Solid-State Overload Relays Page 158
• Bulletin 193-T Bimetallic Overload Relays Page 162
• Bulletin 193-M Bimetallic Overload Relays Page 167
Overload Relay Code Selection forIEC Starters
Page 274
Bulletin 100 LineIEC Contactors, Starters, and Overload Relays
4
Section Overview, Continued
Eco and Compact Starters• Bulletin 190E Direct-On-Line Eco Starters Page 170
• Bulletin 191E Reversing Eco Starters Page 173
• Bulletin 190S Direct-On-Line Compact Starters Page 172
• Bulletin 191S Reversing Compact Starters Page 175
• Bulletin 190-CPS Coordinated Starters Page 183
Mounting System and Starters• Bulletin 141A Mounting System Page 200
• Bulletin 103S/107S Compact Combination Starter Assemblies Page 222
IEC Enclosed StartersBulletin 100 Line• Bulletin 103H/107H/140M Combination Starters Page 251
• Bulletin 109 Non-Reversing Starter Page 262
• Bulletin 112 Combination Starter Disconnect Type Page 263
• Bulletin 113 Combination Starter Circuit Breaker Type Page 264
• Bulletin 105 Reversing Starter Page 265
• Bulletin 106 Reversing Combination Starter Fusible Disconnect Type Page 266
• Bulletin 120E Multi-Speed Starter Two-Speed Separate Winding Page 267
• Bulletin 132 Pump Control Panels Disconnect Type Page 268
• Bulletin 133 Pump Control Panels Circuit Breaker Type Page 268
• Bulletin 198 IEC Enclosures Page 273
• Bulletin 198 Accessories Page 270
IEC Renewal PartsPage 282
5
Bulletin 140MMotor Protection Circuit Breakers
Overview
Your order must include: cat. no. of the Motor Protection Circuit Breaker selected and, if required, cat. no. of any accessories.
Product Line Overview
➊ Consult your local Allen-Bradley distributor.
Bulletin 140M Motor Protection Circuit Breakers• Current Range 0.1…315 A• UL Listed for Motor Loads
• Short Circuit Protection• Overload Protection
• Visible Trip Indication• High Current Limiting• High Switching Capacity
The Bulletin 140M Motor Protection Circuit Breakers provide short circuit and overload protection for individual motor loads. Factory-installed internal accessories make installation and wiring easy.
Table of ContentsProduct Selection . . . . . . . . .7Approximate Dimensions . .34
Conformity to StandardsIEC 947-1/2/4/5IEC 204-1CSA, C22.2 No.14UL 508UL 489
ApprovalsCECSA CertifiedUL Listed
C-Frame D-Frame F-Frame CMN-Frame I-Frame K-FrameMax. Current Ie 25 A 25 A 45 A 90 A 205 A 315 ACurrent Rating 0.1…25 A 1.6…25 A 6.3…45 A 16…90 A 40…205 A 160…315 AShort Circuit Protection
Standard Magnetic Trip
High Magnetic Trip — —Overload Protection
Trip Class 10 10 10 10 5, 10, 15, 20 5, 10, 15, 20Magnetic only Trip (MCP) — — —Standards Compliance:
CSA 22.2, No. 14
CSA 22.2, No. 5 — — — —
UL 508 (Group Install.) — —UL 508 (Type E) — — —UL 508 (Overload Protection)
UL489 — — — —
IEC 60947-2 ➊ ➊
IEC 60947-4 ➊ ➊
CE ➊ ➊
AccessoriesExt. Rotary Operator
Flex Cable Operator — — — —
Auxiliary Contacts
Trip Indication Contacts
Bulletin 140MMotor Protection Circuit Breakers
6
Product Overview
General InformationThe Bulletin 140M Motor Protection Circuit Breakers (MPCBs) provide overload protection as well as current limiting short-circuit protection for individual motor loads.
The C-, D-, and F-Frame MPCBs are approved for use as circuit breakers per IEC 947-2 for applications outside of North America. In the United States and Canada, they are UL/CSA listed as Manual Starters with the optional approvals for Motor Disconnecting and Group Motor applications. More importantly, these devices are UL/CSA listed as Manual Self-Protected (Type E) Combination Starters. Self-Protected Combination Motor Controllers eliminate the requirement for additional short-circuit protection in motor circuit applications per NEC Article 430-52(c)(6).
The I- and K-Frame Bulletin 140 MPCBs are UL/CSA Listed as circuit breakers per UL 489 and CSA22.2, No. 5. They are also listed for motor overload protection per UL 508 and CSA 22.2, No. 14.
The Bulletin 140M MPCBs reduce both panel space and cost in installations, and provide for truly global panel design. they also simplify engineering of multi-motor panels since the NEC/CEC rules that pertained to Manual Starters used in Group Motor applications no longer apply.
The following information is provided to aid in proper system design utilizing the capabilities of the new Bulletin 140M Motor Protection Circuit Breakers in North American applications. Please be sure to follow all local and national codes for your particular installation.
140M-C2E
-C10
100-C09
14 AWG
7.6AFan #25 HP
Motor Protector as
IEC Circuit Breaker
Contactor
Motor
400V, 50 Hz, 3-Phase Power Supply
Single Motor Installation
140M-C2E
-C10
100-C09
14 AWG
7.6AFan #15 HP
140M-C2E
-C10
100-C09
14 AWG
7.6AFan #25 HP
140M-C2E
-C10
100-C16
14 AWG
7.6AFan #35 HP
140M-C2E
-C10
100-C16
14 AWG
7.6AFan #45 HP
140M-C2E
-C16
100-C16
12 AWG
14.0APump #1
10 HP
6 AWG
194R-NN100P3 100A 80HP
480Y/277V, 60 Hz, 3-Phase Power Supply
Non-FusibleDisconnect
Commoning Links
Motor Protectors
Contactors
Motors
Milti-Motor Installation
7
Bulletin 140MMotor Protection Circuit Breakers
Product Selection
Motor Protection Circuit Breakers• Short Circuit Protection — Standard Magnetic Trip (Fixed at 13 x le)• Overload Protection — Trip Class 10 (Adjustable Current Range)
➊ Horsepower ratings shown in the table above are maximum values for each device. The final selection of the manual starter depends on the actual motor full load current and service factor.
Rated Operational
Current [A] (Ie)
Motor Current Adjustment Range
[A]
Magnetic Trip Current
[A]
1-phase Hp Ratings [Hp] ➊ 3-phase Hp Ratings [Hp] ➊
Cat. No. 115V 230V 200V 230V 460V 575V
C-Frame0.16 0.10…0.16 2.1 — — — — — — 140M-C2E-A160.25 0.16…0.25 3.3 — — — — — — 140M-C2E-A250.40 0.25…0.40 5.2 — — — — — — 140M-C2E-A400.63 0.40…0.63 8.2 — — — — — — 140M-C2E-A631.0 0.63…1.0 13 — — — — 1/2 3/4 140M-C2E-B101.6 1.0…1.6 21 — 1/10 — — 1 1 140M-C2E-B162.5 1.6…2.5 33 1/10 1/6 1/2 3/4 1-1/2 2 140M-C2E-B254 2.5…4 52 1/8 1/3 1 1 3 3 140M-C2E-B40
6.3 4…6.3 82 1/4 3/4 1-1/2 2 5 5 140M-C2E-B6310 6.3…10 130 1/2 1-1/2 3 3 7-1/2 10 140M-C2E-C1016 10…16 208 1 3 3 5 10 15 140M-C2E-C1620 14.5…20 260 1-1/2 3 5 7-1/2 15 20 140M-C2E-C2025 18…25 325 2 3 7-1/2 7-1/2 15 20 140M-C2E-C25
D-Frame2.5 1.6…2.5 33 1/10 1/6 1/2 3/4 1-1/2 2 140M-D8E-B254.0 2.5…4 52 1/8 1/3 1 1 3 3 140M-D8E-B406.3 4…6.3 82 1/4 3/4 1-1/2 2 5 5 140M-D8E-B6310 6.3…10 130 1/2 1-1/2 3 3 7-1/2 10 140M-D8E-C1016 10…16 208 1 3 3 5 10 15 140M-D8E-C1620 14.5…20 260 1-1/2 3 5 7-1/2 15 20 140M-D8E-C2025 18…25 325 2 3 7-1/2 7-1/2 15 20 140M-D8E-C25
F-Frame10 6.3…10 130 1/2 1-1/2 3 3 7-1/2 10 140M-F8E-C1016 10…16 208 1 3 3 5 10 15 140M-F8E-C1620 14.5…20 260 1-1/2 3 5 7-1/2 15 20 140M-F8E-C2025 18…25 325 2 3 7-1/2 10 20 25 140M-F8E-C2532 23…32 416 2 5 10 10 25 30 140M-F8E-C3245 32…45 585 3 7-1/2 15 15 30 40 140M-F8E-C45
CMN-Frame25 16…25 350 2 5 7-1/2 10 20 25 140-CMN-250040 25…40 560 3 7-1/2 10 15 30 40 140-CMN-400063 40…63 882 5 10 20 20 50 60 140-CMN-630090 63…90 1260 7-1/2 20 30 30 60 75 140-CMN-9000
I-Frame80 40…80 1200 7-1/2 10 25 30 60 75 140M-I8E-C80100 80…100 1500 10 — 30 40 75 100 140M-I8E-D10160 100…160 2400 — — 50 60 125 150 140M-I8E-D16205 160…205 2665 — — 60 75 150 200 140M-I8E-D20
K-Frame315 160…315 4725 — — 100 125 250 300 140M-K8E-D31
Cat. No. 140M-FCat. No. 140M-DCat. No. 140M-C
Bulletin 140MMotor Protection Circuit Breakers
8
Product Selection, Continued
Motor Protection Circuit Breakers• Short Circuit Protection — High Magnetic Trip (Fixed at 16…20 x le)• Overload Protection — Trip Class 10
➊ Horsepower ratings shown in the table above are maximum values for each device. The final selection of the manual starter depends on the actual motor full load current and service factor.
Rated Operational
Current [A] (le)
Motor Current Adjustment Range
[A]
Magnetic Trip Current [A]
1-phase Hp Ratings [Hp] ➊ 3-phase Hp Ratings [Hp] ➊
Cat. No. 115V 230V 200V 230V 460V 575V
C-Frame0.16 0.10…0.16 3.2 — — — — — — 140M-C2T-A160.25 0.16…0.25 5.2 — — — — — — 140M-C2T-A250.40 0.25…0.40 8.2 — — — — — — 140M-C2T-A400.63 0.40…0.63 13 — — — — — — 140M-C2T-A631.0 0.63…1.0 21 — — — — 1/2 3/4 140M-C2T-B101.6 1.0…1.6 32 — 1/10 — — 1 1 140M-C2T-B162.5 1.6…2.5 52 1/10 1/6 1/2 3/4 1-1/2 2 140M-C2T-B254.0 2.5…4 82 1/8 1/3 1 1 3 3 140M-C2T-B406.3 4…6.3 130 1/4 3/4 1-1/2 2 5 5 140M-C2T-B6310 6.3…10 208 1/2 1-1/2 3 3 7-1/2 10 140M-C2T-C1016 10…16 260 1 3 3 5 10 15 140M-C2T-C16
D-Frame16 10…16 260 1 3 3 5 10 15 140M-D8T-C1620 14.5…20 325 1-1/2 3 5 7-1/2 15 20 140M-D8T-C20
F-Frame25 18…25 416 2 3 7-1/2 10 20 25 140M-F8T-C2532 23…32 585 2 5 10 10 25 30 140M-F8T-C32
CMT-Frame40 25…40 560 3 7-1/2 10 15 30 40 140-CMT-400063 40…63 882 5 10 20 20 50 60 140-CMT-6300
Cat. No. 140M-FCat. No. 140M-DCat. No. 140M-C
9
Bulletin 140MMotor Circuit Protectors
Product Selection, Continued
Motor Circuit Protectors• Short Circuit Protection — Standard Magnetic Trip (Fixed at 13 x le)• Overload Protection — None (Magnetic Trip Only)
➊ Horsepower ratings shown in the table above are maximum values for each device. The final selection of the manual starter depends on the actual motor full load current and service factor.
Rated Operational
Current [A] (Ie)
Motor Current Adjustment Range
[A]
Magnetic Trip Current [A]
1-Phase Hp Ratings [Hp] ➊ 3-Phase Hp Ratings [Hp] ➊
Cat. No. 115V 230V 200V 230V 460V 575V
C-Frame0.16 — 2.1 — — — — — — 140M-C2N-A160.25 — 3.3 — — — — — — 140M-C2N-A250.40 — 5.2 — — — — — — 140M-C2N-A400.63 — 8.2 — — — — — — 140M-C2N-A631.0 — 13 — — — — 1/2 3/4 140M-C2N-B101.6 — 21 — 1/10 — — 1 1 140M-C2N-B162.5 — 33 1/10 1/6 1/2 3/4 1-1/2 2 140M-C2N-B25
D-Frame2.5 — 33 1/10 1/6 1/2 3/4 1-1/2 2 140M-D8N-B254.0 — 52 1/8 1/3 1 1 3 3 140M-D8N-B406.3 — 82 1/4 3/4 1-1/2 2 5 5 140M-D8N-B6310 — 130 1/2 1-1/2 3 3 7-1/2 10 140M-D8N-C1016 — 208 1 3 3 5 10 15 140M-D8N-C1625 — 325 2 3 7-1/2 7-1/2 15 20 140M-D8N-C25
F-Frame25 — 325 2 3 7-1/2 10 20 25 140M-F8N-C2532 — 416 2 5 10 10 25 30 140M-F8N-C3245 — 585 3 7-1/2 15 15 30 40 140M-F8N-C45
Cat. No. 140M-FCat. No. 140M-DCat. No. 140M-C
Bulletin 140MMotor Protection Circuit Breakers
10
Product Selection, Continued
UL Listed Application Ratings
Cat. No.
UL 508 — Manual Motor Controller UL 508 Manual Self-Protected
(Type E) Combination Motor Controller
UL 489 Inverse Time Circuit Breaker with
UL 508 Motor ProtectionGroup Installation Motor Disconnect
Max. Short Circuit Current [kA]
Max. Fuse or C.B. per
NEC
For Use With Contactors Below
(or larger)
Max. Short Circuit Current [kA]
Max. Short Circuit Current [kA]
Max. Short Circuit Current [kA]
480V 600V 480V 600V 480Y/277V 600Y/347V 480V 600V
C-Frame
140M-C2E-A16 65 47 450 100-M05,100-C09 65 47 65 47 — —
140M-C2E-A25 65 47 450 100-M05,100-C09 65 47 65 47 — —
140M-C2E-A40 65 47 450 100-M05,100-C09 65 47 65 47 — —
140M-C2E-A63 65 47 450 100-M05,100-C09 65 47 65 47 — —
140M-C2E-B10 65 47 450 100-M05,100-C09 65 47 65 47 — —
140M-C2E-B16 65 47 450 100-M05,100-C09 65 47 65 47 — —
140M-C2E-B25 65 30 450 100-M05,100-C09 65 30 65 30 — —
140M-C2E-B40 65 30 450 100-M05,100-C09 65 25 65 25 — —
140M-C2E-B63 65 30 450 100-M05,100-C09 65 30 65 — — —
140M-C2E-C10 65 30 450 100-M09,100-C09 65 30 65 — — —
140M-C2E-C16 30 30 450 100-C12 30 30 30 — — —
140M-C2E-C20 30 30 450 100-C16 10 10 10 — — —
140M-C2E-C25 25 10 450 100-C23 10 — — — — —
D-Frame
140M-D8E-B25 65 30 450 100-M05,100-C09 65 30 65 30 — —
140M-D8E-B40 65 30 450 100-M05,100-C09 65 30 65 30 — —
140M-D8E-B63 65 30 450 100-M05,100-C09 65 30 65 30 — —
140M-D8E-C10 65 30 450 100-M09,100-C09 65 30 65 30 — —
140M-D8E-C16 65 30 450 100-C12 65 30 65 30 — —
140M-D8E-C20 65 30 450 100-C16 65 30 65 — — —
140M-D8E-C25 65 30 450 100-C23 35 30 35 — — —
F-Frame
140M-F8E-C10 65 30 600 100-C09 65 30 65 30 — —
140M-F8E-C16 65 30 600 100-C12 65 30 65 30 — —
140M-F8E-C20 65 30 600 100-C16 65 30 65 30 — —
140M-F8E-C25 65 30 600 100-C23 65 30 65 30 — —
140M-F8E-C32 65 30 600 100-C30 65 30 65 30 — —
140M-F8E-C45 65 30 600 100-C37 65 30 65 — — —
CMN-Frame
140-CMN-2500 65 42 1000 100-C16 65 42 — — — —
140-CMN-4000 65 42 1000 100-C30 65 42 — — — —
140-CMN-6300 42 18 1000 100-C43 42 18 — — — —
140-CMN-9000 35 10 1000 100-C72 35 10 — — — —
I-Frame
140M-I8E-C80 — — — — — — — — 65 30
140M-I8E-D10 — — — — — — — — 65 30
140M-I8E-D16 — — — — — — — — 65 30
140M-I8E-D20 — — — — — — — — 65 30
K-Frame
140M-K8E-D31 — — — — — — — — 65 30
11
Bulletin 140MMotor Protection Circuit Breakers
Product Selection, Continued
UL Listed Application Ratings, Continued
Cat. No.
Manual Motor Controller Manual Self-Protected (Type E) Combination Motor
ControllerGroup Installation Motor Disconnect
Max. Short Circuit Current [kA] Max. Fuse or
C.B. per NECFor Use With Contactors
Below (or larger)
Max. Short Circuit Current [kA]
Max. Short Circuit Current [kA]
480V 600V 480V 600V 480Y/277V 600Y/347V
C-Frame
140M-C2T-A16 65 47 450 100-M05,100-C09 65 47 65 47
140M-C2T-A25 65 47 450 100-M05,100-C09 65 47 65 47
140M-C2T-A40 65 47 450 100-M05,100-C09 65 47 65 47
140M-C2T-A63 65 47 450 100-M05,100-C09 65 47 65 47
140M-C2T-B10 65 47 450 100-M05,100-C09 65 47 65 47
140M-C2T-B16 65 47 450 100-M05,100-C09 65 47 65 30
140M-C2T-B25 65 25 450 100-M05,100-C09 65 25 65 25
140M-C2T-B40 65 30 450 100-M05,100-C09 65 30 65 —
140M-C2T-B63 65 30 450 100-M05,100-C09 65 30 65 —
140M-C2T-C10 30 30 450 100-M09,100-C09 30 30 30 —
140M-C2T-C16 30 30 450 100-C12 10 10 10 —
D-Frame
140M-D8T-C16 65 30 450 100-C12 65 30 65 30
140M-D8T-C20 65 30 450 100-C16 35 30 35 —
F-Frame
140M-F8T-C25 65 30 600 100-C23 65 30 65 30
140M-F8T-C32 65 30 600 100-C30 65 30 65 30
CMN-Frame
140-CMT-4000 65 42 1000 100-C30 65 42 — —
140-CMT-6300 42 18 1000 100-C43 42 18 — —
Cat. No.
Manual Motor Controller
Group Installation Motor Disconnect
Max. Short Circuit Current [kA] Max. Fuse or
C.B. per NEC
For Use With Contactors below
(or larger)
Max. Short Circuit Current [kA]
480V 600V 480V 600V
C-Frame
140M-C2N-A16 65 47 450 100-M05,100-C09 65 47
140M-C2N-A25 65 47 450 100-M05,100-C09 65 47
140M-C2N-A40 65 47 450 100-M05,100-C09 65 47
140M-C2N-A63 65 47 450 100-M05,100-C09 65 47
140M-C2N-B10 65 47 450 100-M05,100-C09 65 47
140M-C2N-B16 65 47 450 100-M05,100-C09 65 47
140M-C2N-B25 65 30 450 100-M05,100-C09 65 30
D-Frame
140M-D8N-B25 65 30 450 100-M05,100-C09 65 30
140M-D8N-B40 65 30 450 100-M05,100-C09 65 30
140M-D8N-B63 65 30 450 100-M05,100-C09 65 30
140M-D8N-C10 65 30 450 100-M09,100-C09 65 30
140M-D8N-C16 65 30 450 100-C12 65 30
140M-D8N-C25 65 30 450 100-C23 35 30
F-Frame
140M-F8N-C25 65 30 600 100-C23 65 30
140M-F8N-C32 65 30 600 100-C30 65 30
140M-F8N-C45 65 30 600 100-C37 65 30
Bulletin 140MMotor Protection Circuit Breakers
12
Product Selection, Continued
Type 2 Coordination per UL508E
Definition of Type 2 Short Circuit Coordination:• The contactor or starter must not endanger persons or plant in the event of a short circuit.• No damage to the overload relay or other parts may occur with the exception of welding of the contactor or starter contacts if these can be easily separated without
appreciable deformation (such as with a screwdriver).
In the event of short circuit, fast-opening, strong current-limiting Bulletin 140M Motor Protection Circuit Breakers make it possible to build economical,fully short-circuit coordinated starter combinations to Type 2 coordination.
Cat. No. Max. Short Circuit Current [kA] For Use With Contactors Below (or larger)Standard Trip High Trip Mag Only Trip 480V
C-Frame
140M-C2E-A16 140M-C2T-A16 140M-C2N-A16 65 100-M05, 100-C09
140M-C2E-A25 140M-C2T-A25 140M-C2N-A25 65 100-M05, 100-C09
140M-C2E-A40 140M-C2T-A40 140M-C2N-A40 65 100-M05, 100-C09
140M-C2E-A63 140M-C2T-A63 140M-C2N-A63 65 100-M05, 100-C09
140M-C2E-B10 140M-C2T-B10 140M-C2N-B10 65 100-M05, 100-C09
140M-C2E-B16 140M-C2T-B16 140M-C2N-B16 65 100-M05, 100-C09
140M-C2E-B25 140M-C2T-B25 140M-C2N-B25 50 100-C09
140M-C2E-B40 140M-C2T-B40 — 50 100-C30
140M-C2E-B63 140M-C2T-B63 — 50 100-C30
140M-C2E-C10 140M-C2T-C10 — 50 100-C30
140M-C2E-C16 140M-C2T-C16 — 10 100-C30
140M-C2E-C20 — — 10 100-C30
140M-C2E-C25 — — 10 100-C30
D-Frame
140M-D8E-B25 — 140M-D8N-B25 65 100-C09
140M-D8E-B40 — 140M-D8N-B40 65 100-C09
140M-D8E-B63 — 140M-D8N-B63 65 100-C09
140M-D8E-C10 — 140M-D8N-C10 65 100-C09
140M-D8E-C16 140M-D8T-C16 140M-D8N-C16 65 100-C12
140M-D8E-C20 140M-D8T-C20 — 65 100-C23
140M-D8E-C25 — 140M-D8N-C25 65 100-C23
F-Frame
140M-F8E-C10 — — 65 100-C09
140M-F8E-C16 — — 65 100-C12
140M-F8E-C20 — — 65 100-C16
140M-F8E-C25 140M-F8T-C25 140M-F8N-C25 65 100-C23
140M-F8E-C32 140M-F8T-C32 140M-F8N-C32 65 100-C30
140M-F8E-C45 — 140M-F8N-C45 65 100-C37
CMN-Frame
140-CMN-2500 — — 65 100-C16
140-CMN-4000 140-CMT-4000 — 65 100-C30
140-CMN-6300 140-CMT-6300 — 42 100-C43
140-CMN-9000 — — 35 100-C72
13
Bulletin 140MMotor Protection Circuit Breakers
Product Selection, Continued
Type 2 Coordination per UL508E, Continued
Definition of Type 2 Short Circuit Coordination:• The contactor or starter must not endanger persons or plant in the event of a short circuit.• No damage to the overload relay or other parts may occur with the exception of welding of the contactor or starter contacts if these can be easily separated without
appreciable deformation (such as with a screwdriver).
In the event of short circuit, fast-opening, strong current-limiting Bulletin 140M Motor Protection Circuit Breakers make it possible to build economical,fully short-circuit coordinated starter combinations to Type 2 coordination.
Cat. No. Max. Short Circuit Current [kA] For Use With Contactors Below (or larger)Standard Trip High Trip Mag Only Trip 600V
C-Frame
140M-C2E-A16 140M-C2T-A16 140M-C2N-A16 47 100-C09
140M-C2E-A25 140M-C2T-A25 140M-C2N-A25 47 100-C09
140M-C2E-A40 140M-C2T-A40 140M-C2N-A40 47 100-C09
140M-C2E-A63 140M-C2T-A63 140M-C2N-A63 47 100-C09
140M-C2E-B10 140M-C2T-B10 140M-C2N-B10 47 100-C09
140M-C2E-B16 140M-C2T-B16 140M-C2N-B16 47 100-C09
140M-C2E-B25 140M-C2T-B25 140M-C2N-B25 10 100-C16
140M-C2E-B40 140M-C2T-B40 — 10 100-C16
140M-C2E-B63 140M-C2T-B63 — 5 100-C23
140M-C2E-C10 140M-C2T-C10 — 5 100-C30
140M-C2E-C16 140M-C2T-C16 — 5 100-C30
140M-C2E-C20 — — 5 100-C30
140M-C2E-C25 — — 5 100-C30
D-Frame
140M-D8E-B25 — 140M-D8N-B25 30 100-C09
140M-D8E-B40 — 140M-D8N-B40 30 100-C16
140M-D8E-B63 — 140M-D8N-B63 30 100-C23
140M-D8E-C10 — 140M-D8N-C10 30 100-C30
140M-D8E-C16 140M-D8T-C16 140M-D8N-C16 30 100-C30
140M-D8E-C20 140M-D8T-C20 — 5 100-C30
140M-D8E-C25 — 140M-D8N-C25 5 100-C30
F-Frame
140M-F8E-C10 — — 30 100-C30
140M-F8E-C16 — — 30 100-C30
140M-F8E-C20 — — 30 100-C30
140M-F8E-C25 140M-F8T-C25 140M-F8N-C25 30 100-C30
140M-F8E-C32 140M-F8T-C32 140M-F8N-C32 30 100-C30
140M-F8E-C45 — 140M-F8N-C45 10 100-C37
CMN-Frame
140-CMN-2500 — — 42 100-C16
140-CMN-4000 140-CMT-4000 — 42 100-C30
140-CMN-6300 140-CMT-6300 — 18 100-C43
140-CMN-9000 — — 10 100-C72
Bulletin 140MMotor Protection Circuit Breakers
14
Accessories
➊ X = Contact ClosedO = Contact Open
➋
Description
Connection Diagram ➋For Use
With Cat. No.
Operator Position ➊
Term. No. Description
OFF ON Tripped
Front-Mounted Auxiliary Contact• 1-pole or 2-pole• No additional space
required
O X O 13-14 N.O. Aux 140M 140M-C-AFA10
X O X 11-12 N.C. Aux 140M 140M-C-AFA01
O X O 13-14 N.O. Aux
140M 140M-C-AFA11
X O X 21-22 N.C. Aux
O X O 13-14 N.O. Aux
140M 140M-C-AFA20
O X O 23-24 N.O. Aux
X O X 11-12 N.C. Aux
140M 140M-C-AFA02
X O X 21-22 N.C. Aux
Right Side-Mounted Auxiliary Contact• 2-pole• Adds 9 mm to the
width of the device
O X O 33-34 N.O. Aux
140M 140M-C-ASA20
O X O 43-44 N.O. Aux
X O X 31-32 N.C. Aux
140M 140M-C-ASA02
X O X 41-42 N.C. Aux
O X O 33-34 N.O. Aux
140M 140M-C-ASA11
X O X 41-42 N.C. Aux
I >>
13
14
I >>
11
12
13
14
21
22
I >>
I >>
13
14
23
24
I >>
11
12
21
22
I >>
33
34
43
44
I >>
31
32
41
42
33
34
41
42
I >>
I >>
140 M Operator
Overload (thermal) TripShort-Circuit (magnetic) Trip
15
Bulletin 140MMotor Protection Circuit Breakers
Accessories, Continued
➊ X = Contact ClosedO = Contact Open
➋
Description
Connection Diagram ➋For Use
With Cat. No.
Operator Position ➊
Term. No. Description
OFF ON Tripped
Front-MountedTrip Contact• 2-pole• Indicates tripping of
device• No additional space
required
O X O 13-14 N.O. Aux
140M 140M-C-AFAR10A10
O O X 27-28N.O. Trip
(Short-Circuit & Overload)
X O X 11-12 N.C. Aux
140M 140M-C-AFAR10A01
O O X 27-28N.O. Trip
(Short-Circuit & Overload)
Right Side-Mounted Trip Contact• 2-pole• Indicates tripping of
Motor Protection Circuit Breaker
• Adds 9 mm to the width of the circuit breaker
O O X 57-58N.O. Trip
(Short-Circuit & Overload)
140M 140M-C-ASAR10M10
O O X 67-68 N.O. Trip(Short-Circuit)
O O X 57-58N.O. Trip
(Short-Circuit & Overload)
140M 140M-C-ASAR10M01
X X O 65-66 N.C. Trip(Short-Circuit)
X X O 55-56N.C. Trip
(Short-Circuit & Overload)
140M 140M-C-ASAR01M10
O O X 67-68 N.O. Trip(Short-Circuit)
X X O 55-56N.C. Trip
(Short-Circuit & Overload)
140M 140M-C-ASAR01M01
X X O 65-66 N.C. Trip(Short-Circuit)
O O X 77-78 N.O. Trip(Short-Circuit)
140M 140M-C-ASAM11
X X O 65-66 N.C. Trip (Short-Circuit)
13 27
14I >>
28
11
12I >>
27
28
57
58
67
68
I >>
I >>
57
58
65
66
I >>
55
56
67
68
I >>
65
66
55
56
I >>
77
78
65
66
I >>
140 M Operator
Overload (thermal) TripShort-Circuit (magnetic) Trip
Bulletin 140MMotor Protection Circuit Breakers
16
Accessories, Continued
➊ X = Contact ClosedO = Contact Open
➋
Description
Connection Diagram ➋For Use
With Cat. No.
Operator Position ➊
Term. No. Description
OFF ON Tripped
Front-Mounted Auxiliary Contacts• Internal• 2-Pole
O X O 13-14 N.O. Aux
140-CMN 140-CA20
O X O 23-24 N.O. Aux
X O X 11-12 N.C. Aux
140-CMN 140-CA02
X O X 21-22 N.C. Aux
O X O 13-14 N.O. Aux
140-CMN 140-CA11
X O X 21-22 N.C. Aux
Front-MountedTrip Indicating Auxiliary Contacts• Internal• 2-Pole
O O X 37-38 N.O. Trip(Overload)
140-CMN 140-CT10-10
O O X 43-44 N.O. Trip(Short-Circuit)
X X O 35-36 N.C. Trip(Overload)
140-CMN 140-CT01-01
X X O 41-42 N.C. Trip(Short-Circuit)
X X O 35-36 N.C. Trip(Overload)
140-CMN 140-CT01-10
O O X 43-44 N.O. Trip(Short-Circuit)
O O X 37-38 N.O. Trip(Overload)
140-CMN 140-CT10-01
X X O 41-42 N.C. Trip(Short-Circuit)
13
14
23
24
I >>
140-CMN
140-CA20
I >>
21
22
11
12
140-CMN
140-CA02
I >>
13
14
21
22
140-CMN
140-CA11
37
38
43
44
I >>
140-CMN
140-CT10-10
a
b
a) Overload Tripb) Short-Circuit Trip
I >>
41
42
35
36
140-CMN
140-CT01-01
a
b
a) Overload Tripb) Short-Circuit Trip
I >>
35
36
43
44
140-CMN
140-CT01-10
a
b
a) Overload Tripb) Short-Circuit Trip
I >>
37
38
41
42
140-CMN
140-CT10-01
a
b
a) Overload Tripb) Short-Circuit Trip
I >>
140 M Operator
Overload (thermal) TripShort-Circuit (magnetic) Trip
17
Bulletin 140MMotor Protection Circuit Breakers
Accessories, Continued
➊
Description Connection Diagram ➊For Use
With Cat. No.
Undervoltage Trip• Left-side mounted• Adds 18 mm to the width of the
circuit breaker• Trips motor protector when
voltage is removed
24V, 60 Hz24V, 50 Hz
120V, 60 Hz110V, 50 Hz
220…230V, 50 Hz240…260V, 60 Hz
277V, 60 Hz380…400V, 50 Hz
480V, 60 Hz/415V, 50 Hz600V, 60 Hz
575V, 60 Hz/500V, 50 Hz
140M
140M-C-UXJ140M-C-UXK140M-C-UXD140M-C-UXC140M-C-UXF140M-C-UXA140M-C-UXT140M-C-UXN140M-C-UXB
140M-C-UXUB140M-C-UXM
Shunt Trip• Left-side mounted• Adds 18 mm to the width of the
circuit breaker• Trips motor protector when
voltage is applied
24V, 60 Hz24V, 50 Hz
120V, 60 Hz110V, 50 Hz
220…230V, 50 Hz240…260V, 60 Hz
277V, 60 Hz380…400V, 50 Hz
480V, 60 Hz/415V, 50 Hz600V, 60 Hz
575V, 60 Hz/500V, 50 Hz
140M
140M-C-SNJ140M-C-SNK140M-C-SND140M-C-SNC140M-C-SNF140M-C-SNA140M-C-SNT140M-C-SNN140M-C-SNB
140M-C-SNUB140M-C-SNM
Undervoltage Trip Unit• Internal, front mounted• Integrated short circuit trip
indication• Trips Motor Protection Circuit
Breaker when voltage is removed
24V 50/60 Hz110V 50 Hz/120V 60 Hz220V 50 Hz/240V 60 Hz
140-CMN140-CUV-KJ140-CUV-D140-CUV-A
Shunt Trip Unit• Internal, front mounted• Integrated short circuit trip
indication• Trips Motor Protection Circuit
Breaker when voltage is applied
24V 50/60 Hz110V 50 Hz/120V 60 Hz220V 50 Hz/240V 60 Hz
140-CMN140-CRT-KJ140-CRT-D140-CRT-A
D1
D2I >>
U <
C1
C2I >>
I >>
140-CMN
b) Short-Circuit Trip
b
D1
D2
U <
43
44
140-CUV...
I >>
140-CMN
b) Short-Circuit Trip
b
C1
C2
43
44
140-CRT...
I >>
140 M Operator
Overload (thermal) TripShort-Circuit (magnetic) Trip
Bulletin 140MMotor Protection Circuit Breakers
18
Accessories, Continued
Description For Use With Cat. No.
Anti-Tamper Shield• Provides protection against inadvertent adjustment of the
current setting10 pcs/pkg 140M 140M-C-CA
Lockable Twist Knob• For 1 padlock 4…8 mm (5/16") dia. shackle• Can be locked in OFF position
black 140M 140M-C-KN
red/yellow 140M-C/-D 140M-C-KRY
red/yellow 140M-F 140M-F-KRY
Padlockable Operating Knob• Accepts 8 mm (5/16") padlock — up to three padlocks• Permits padlocking in the off position
black
140-CMN
140-KN
red/yellow 140-KRY
Door Coupling Handle• For 3 padlocks 4…8 mm (5/16") in diameter• IP66 Protection/Type 1, 12• Interlock override capability• Can be modified for locking in ON position• Ships with coupling — order extension shaft and legend plate
separately• Mounting depth (adapter-door):
140-C: 105.5 mm ± 5 mm (4.15" ± 3/16")140-D: 114.5 mm ± 5 mm (4.5" ± 3/16")140-F: 137.1 mm ± 5 mm (5.4" ± 3/16")
black
140M 140M-C-DN66
140-CMN 140-CDN66
red/yellow
140M 140M-C-DRY66
140-CMN 140-CDRY66
Extension Shaft• Cut to required length for mounting depth (adapter-door):
140-C: 117…338 mm (4.6"…13.3")140-D: 126…347 mm (5.0"…13.7")140-F: 149…369 mm (5.4"…14.5")
140M-C-DN66140M-C-DRY66
140-CDN66140-CDRY66
140M-C-DS
Legend Plate• Marking: "Haupschalter" and "Main Switch"• Marking: "Not-Aus" and "Emergency Off"
140M-C-DN66 140M-C-DFCN
140M-C-DRY66 140M-C-DFCRY
Locking Tag• Padlock attachment to the lockable handles• Up to three padlocks 4…8 mm (5/16") shackle
140M-C-KN140M-C-KRY140M-F-KRY
140M-C-M3
IP65 Non-Metallic Enclosure• Knockouts for PG16 and PG21 fittings• Suitable for flexible cable with internal ground wire or conduit
when externally grounded around the outside of the enclosure
black handle 140M-C 198E-AYTG2
red/yellow handle 140M-C 198E-AYTJ2
Terminal Cover• For covering of unused Commoning Link terminals• IP2X finger protection
140M-C140M-D 140M-C-WS
140M-F 140M-F-WS
Screw Adapter• For screw arrangement of a Motor Protection Circuit Breaker 10 pcs/pkg 140M 140M-C-N45
19
Bulletin 140MMotor Protection Circuit Breakers
Accessories, Continued
Description For Use With Cat. No.
ECO Connecting Modules — 25 A• Eco-starters mount on SINGLE DIN Rail (140M on DIN Rail)• ELECTRICAL AND MECHANICAL interconnection of 140M MPCB and 100-M
(with AC or DC coils) or 100-C (with AC coils) contactors
140M-C to100-M 140M-C-PEM12
140M-C to100-C09…C23 140M-C-PEC23
140M-D to100-C09…C23 140M-D-PEC23
Connecting Modules — 25 A and 45 A• Contactor and MPCB MUST BE mounted separately on (2) DIN Rails• ELECTRICAL interconnection between 140M MPCB and 100-C contactors
(with AC coils)
140M-C to100-C09…C23 140M-C-PNC23
140M-D to100-C09…C23 140M-D-PNC23
140M-D to100-C30…C37 140M-D-PNC37
140M-F to100-C30…C37 140M-F-PNC37
140M-F to100-C43 140M-F-PNC43
Spacing Adapter• Required for Self-Protected combination motor controller (Type E) applications
of 140M-C, -D, and -F MPCBs
140M-C, -D 140M-C-TE
140M-F 140M-F-TE
Commoning Link Feeder Terminal• For supply of commoning links• Top feed — overlaps commoning link
140M-C140M-D 140M-C-WTE
140M-F 140M-F-WTE
Three-Phase Commoning Link for 25 A Motor Protection Circuit Breakers — 63 A Max. Continuous Current
• 45 mm spacing• For use with front-mounted auxiliary contact
2 connections
140M-C140M-D
140M-C-W4523 connections 140M-C-W4534 connections 140M-C-W4545 connections 140M-C-W455
• 54 mm spacing• For use with side-mounted auxiliary contact
2 connections
140M-C140M-D
140M-C-W5423 connections 140M-C-W5434 connections 140M-C-W5445 connections 140M-C-W545
• 63 mm spacing• For use with side-mounted undervoltage trip and shunt trip
2 connections
140M-C140M-D
140M-C-W6323 connections 140M-C-W6334 connections 140M-C-W6345 connections 140M-C-W635
Jumper for 140M-D to 140M-C• Accommodates difference in depth from 140M-D to
140M-C• Can be used with all other commoning links• 54 mm spacing
2 connections140M-D
to140M-C
140M-C-WD542
Three-Phase Commoning Link for 45 A Motor Protection Circuit Breakers — 115 A Max Continuous Current
• 54 mm spacing• For use with front-mounted auxiliary contact
2 connections140M-F
140M-F-W5423 connections 140M-F-W5434 connections 140M-F-W544
• 63 mm spacing• For use with side-mounted auxiliary contact
2 connections
140M-F
140M-F-W6323 connections 140M-F-W633
4 connections 140M-F-W634
DIN (#3) Symmetrical Rail• 35 mm x 7.5 mm x 1 m long• Zinc-plated, yellow chromated • EN 50022
10 pcs/kg 140M-D140M-F 199-DR1
DIN (#3) Symmetrical Rail• 35 mm x 15 mm x 1 m long 5 pcs/pkg
140M-C140M-D140M-F
140-CMN
1492-DR9
140M-D 140M-C
Bulletin 140MMotor Protection Circuit Breakers
20
Accessories, Continued
140M-C/D/F Factory Modifications (Open)Note: For modifications add (option code ➍ ) for desired features to cat. no.➍ Add desired option codes. Example: 140M-C2E-A16-KY
External Accessories — I-Frame
Modifications Price Adder US $
KN Lockable Twist Knob (140M) - Black 15.00KY Lockable Twist Knob (140M) - Red/Yellow 18.00TE Spacing Adapter for UL508 Type E 13.00
Description Cat. No.Terminal End Cover — 0.25 in. Qty: 1 140U-I-TC2Terminal End Cover — 0.41 in. Qty: 1 140U-I-TC4
Terminal Shields (Plastic) IP20 Ingress Protection Qty: 1 140U-I-TS1
Flex-Cable Operating Mechanism NEMA Type 1/3/12/4/4X Flange-Mount Handle
3 ft. Cable Mechanism 140U-I-FCX03
4 ft. Cable Mechanism 140U-I-FCX04
6 ft. Cable Mechanism 140U-I-FCX06
10 ft. Cable Mechanism 140U-I-FCX10
Rotary Close Couple Handle International Gray 140U-I-RCB
Rotary Close Couple Handle International Red/Yellow 140U-I-RCR
Padlockable Handle Lock Hasp — Off only Padlocking HaspLock-OFF only — 140U-I-PL
End Cap KitProvides 3-phase connections for terminal or bolt-on connections
Metric HardwareQty: 1 140U-I-ECM
Phase Barriers Provides additional phase clearance when special connections are required Qty: 2 140U-I-PB
Cu/Al #4-4/0 Aluminum TerminalAluminum Terminal
Copper/Aluminum wire#4-4/0 AWG
Qty: 3 140U-I-TLA1
Cu/Al #14-1/0 Steel TerminalSteel Terminal
Copper/Aluminum wire#4-4/0 AWG
Qty: 3 140U-I-TLS1
Cu/Al #4-4/0 Stainless Steel TerminalStainless Steel TerminalCopper/Aluminum wire
#4-4/0 AWGQty: 3 140U-I-TLS2
21
Bulletin 140MMotor Protection Circuit Breakers
Accessories, Continued
External Accessories — K-Frame
Description Cat. No.
Terminal Shields IP20 Ingress Protection Qty: 1 140U-K-TS
Flex Cable Operating Mechanism NEMA Type 1/3/12/4/4X Flange-Mount Handle
3 ft. Cable Mechanism 140U-K-FCX03
4 ft. Cable Mechanism 140U-K-FCX04
6 ft. Cable Mechanism 140U-K-FCX06
10 ft. Cable Mechanism 140U-K-FCX10
Rotary, Variable-Depth Operating Mechanism
Type 1/12 Rotary Handle12 in. operating rod
Black Handle 140U-K-RM12B
Red/Yellow Handle 140U-K-RM12R
Rotary, Direct Couple Operating Mechanism Type 1 Rotary HandleBreaker Mounted
Black Handle 140U-K-RCB
Red/Yellow Handle 140U-K-RCR
Operating Handle Extension Provides handle extension for ease of operation Qty: 1 140U-K-OHE
Phase BarriersProvides additional phase
clearance when special connections are required
Qty: 2 140U-K-PB
Padlock Kit Padlocking HaspLock-OFF only — 140U-K-PL
Terminal Lugs
Copper wire only(1) 250…500 MCM Qty: 1 140U-K-TLC1
Copper wire only(1) 3/0…250 MCM Qty: 3 140U-K-TLC2
Aluminum or copper wire(1) 250…500 MCM Qty: 1 140U-K-TLA1
End Cap KitProvides 3-phase connections for terminal or bolt-on connections
Metric HardwareQty: 1 140U-K-ECM
Bulletin 140MMotor Protection Circuit Breakers
22
Specifications
0 00IEC Performance Data
➊ No back-up fuse required.
Cat. No. 140M-C2E-
A16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16 C20 C25
Rated Operational Current, Ie [A] 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 10 16 20 25
Magnetic Release Current [A] 2.1 3.3 5.2 8.2 13 21 33 52 82 130 208 260 325
Switching of StandardThree-Phase Motors
AC-2, AC-3
230/240V [kW] — — — 0.06/0.09 0.12 0.18/0.25 0.37 0.55/0.75 1.1/1.5 2.2 3.0/4.0 4.0/5.5 —
400/415V [kW] 0.02 0.06 0.09 0.12/0.18 0.25 0.37/0.55 0.75 1.1/1.5 2.2 3.0/4.0 5.5/7.5 7.5/10 11
500V [kW] — — — 0.18 0.25/0.37 0.55/0.75 1.1 1.5/2.2 2.5/3.0 4.0/6.3 7.5/10 11 15
690V [kW] — — — 0.25 0.37/0.55 0.75/1.1 1.8 2.2/3.0 4.0 5.5/7.5 11/13 15/17 18.5/22
Back-Up FusesgG, gL, only if Icc > Icu
230/240V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 100 100
400/415V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 80 100 100
440/460V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 63 63 80 80
500V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 80 80 80 80
690V [A] ➊ ➊ ➊ ➊ ➊ 16 20 35 50 50 63 63 63
Ultimate Short Circuit Breaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 50 50
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 50 15 15
440/460V [kA] 100 100 100 100 100 100 100 100 100 50 10 10 10
500V [kA] 100 100 100 100 100 100 100 100 100 50 10 6 6
690V [kA] 100 100 100 100 100 10 8 8 4 4 3 3 3
Rated Service Short CircuitBreaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 50 50
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 50 15 15
440/460V [kA] 100 100 100 100 100 100 100 100 100 50 6 6 6
500V [kA] 100 100 100 100 100 100 100 100 100 50 6 6 6
690V [kA] 100 100 100 100 100 8 8 8 4 4 3 3 3
23
Bulletin 140MMotor Protection Circuit Breakers
Specifications, Continued
IEC Performance Data, Continued
➊ No back-up fuse required.➋ Power ratings: Preferred values according to IEC 60072-1
Cat. No. 140M-D8E- Cat. No. 140M-F8E-
B25 B40 B63 C10 C16 C20 C25 C10 C16 C20 C25 C32 C45
Rated Operational Current, Ie [A] 2.5 4.0 6.3 10 16 20 25 10 16 20 25 32 45
Magnetic Release Current [A] 33 52 82 130 208 260 325 130 208 260 325 416 585
Switching of StandardThree-Phase Motors
AC-2, AC-3
230/240V [kW] 0.37 0.55/0.75 1.1/1.5 2.2 3.0/4.0 4.0/5.5 — 2.2 3.0/4.0 4.0/5.5 5.5/6.3 7.5 11/13
400/415V [kW] 0.75 1.1/1.5 2.2 3.0/4.0 5.5/7.5 7.5/10 11 3.0/4.0 5.5/7.5 7.5/10 11 15 18.5/22
500V [kW] 1.1 1.5/2.2 2.5/3.0 4.0/6.3 7.5/10 11 15 4.0/6.3 7.5/10 11 15 15/20 22/30
690V [kW] 1.8 2.2/3.0 4.0 5.5/7.5 11/13 15/17 18.5/22 5.5/7.5 11/13 15/17 18.5/22 22/25 30/40
Back-Up FusesgG, gL, only if Icc > Icu
230/240V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
400/415V [A] ➊ ➊ ➊ ➊ ➊ 100 100 80 100 100 100 125 125
440/460V [A] ➊ ➊ ➊ ➊ 80 100 100 80 100 100 100 125 125
500V [A] ➊ ➊ ➊ ➊ 80 80 80 80 100 100 125 125 125
690V [A] 20 35 50 50 63 63 63 63 80 80 80 100 100
Ultimate Short CircuitBreaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 50 65 65 65 65 65 65 65
440/460V [kA] 100 100 100 100 65 65 65 65 65 65 65 65 50
500V [kA] 100 100 100 100 50 50 50 50 50 50 50 50 50
690V [kA] 10 10 10 6 6 6 6 10 10 10 10 10 10
Rated Service Short CircuitBreaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 50 25 25 50 50 50 50 50 50
440/460V [kA] 100 100 100 100 50 25 25 50 50 50 50 50 50
500V [kA] 100 100 100 100 50 25 25 50 50 50 50 50 50
690V [kA] 10 10 10 6 4 4 4 10 10 10 10 6 6
Cat. No.140-CMN-…
-2500 -4000 -6300 -9000Rated Operational Current, Ie [A] 25 40 63 90
Switching of Standard Three-Phase MotorsAC-2, AC-3
230/240 V ➋ [kW] 5.5/7.5 10/11 13/20 22/25400/415 V ➋ [kW] 7.5/13 15/22 25/32 37/45500 V ➋ [kW] 11/15 18.5/25 30/40 45/55690 V ➋ [kW] 15/22 25/30 37/55 63/75
Back-up fusesgG, gL,, only if Icc > Icu
230/240 V [A] ➊ ➊ ➊ ➊
400/415 V [A] 160 160 160 160500 V [A] 160 160 160 160690 V [A] 160 160 160 160
Ultimate short-circuit breaking capacity Icu
230/240 V [kA] 100 100 100 100400/415 V [kA] 65 65 65 50500 V [kA] 50 30 30 25690 V [kA] 15 8 8 6
Rated service short-circuit breaking capacity Ics
230/240 V [kA] 100 100 100 100400/415 V [kA] 65 50 50 25500 V [kA] 50 25 25 13690 V [kA] 15 6 6 6
Bulletin 140MMotor Protection Circuit Breakers
24
Specifications, Continued
0 00IEC Performance Data, Continued
➊ No back-up fuse required.
Cat. No. 140M-C2N-
A16 A25 A40 A63 B10 B16 B25
Rated Operational Current,Ie [A] 0.16 0.25 0.4 0.63 1 1.6 2.5
Magnetic Release Current [A] 2.1 3.3 5.2 8.2 13 21 32
Switching of StandardThree-Phase Motors
AC-2, AC-3
230/240V [kW] — — — 0.06/0.09 0.12 0.18/0.25 0.37
400/415V [kW] 0.02 0.06 0.09 0.12/0.18 0.25 0.37/0.55 0.75
500V [kW] — — — 0.18 0.25/0.37 0.55/0.75 1.1
690V [kW] — — — 0.25 0.37/0.55 0.75/1.1 1.8
Back-Up FusesgG, gL, only if Icc > Icu ➊
230/240V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊
400/415V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊
440/460V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊
500V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊
690V [A] ➊ ➊ ➊ ➊ ➊ 16 20
Ultimate Short CircuitBreaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100
440/460V [kA] 100 100 100 100 100 100 100
500V [kA] 100 100 100 100 100 100 100
690V [kA] 100 100 100 100 100 100 8
Rated Service Short CircuitBreaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100
440/460V [kA] 100 100 100 100 100 100 100
500V [kA] 100 100 100 100 100 100 100
690V [kA] 100 100 100 100 100 8 8
25
Bulletin 140MMotor Protection Circuit Breakers
Specifications, Continued
IEC Performance Data, Continued
➊ No back-up fuse required.➋ Consult your local Allen-Bradley distributor.
Cat. No. 140M-D8N- Cat. No. 140M-F8N-
B25 B40 B63 C10 C16 C25 C25 C32 C45
Rated Operational Current,Ie [A] 2.5 4.0 6.3 10 16 25 25 32 45
Magnetic Release Current [A] 32 52 82 130 208 325 325 416 585
Switching of StandardThree-Phase Motors
AC-2, AC-3
230/240V [kW] 0.37 0.55/0.75 1.1/1.5 2.2 3.0/4.0 — 5.5/6.3 7.5 11/13
400/415V [kW] 0.75 1.1/1.5 2.2 3.0/4.0 5.5/7.5 11 11 15 18.5/22
500V [kW] 1.1 1.5/2.2 2.5/3.0 4.0/6.3 7.5/10 15 15 15/20 22/30
690V [kW] 1.8 2.2/3.0 4.0 5.5/7.5 11/13 18.5/22 18.5/22 22/25 30/40
Back-Up FusesgG, gL, only if Icc > Icu
230/240V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
400/415V [A] ➊ ➊ ➊ ➊ ➊ 100 100 125 125
440/460V [A] ➊ ➊ ➊ ➊ 80 100 100 125 125
500V [A] ➊ ➊ ➊ ➊ 80 80 125 125 125
690V [A] 20 35 50 50 63 63 80 100 100
Ultimate Short CircuitBreaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 50 65 65 65
440/460V [kA] 100 100 100 100 65 50 65 65 50
500V [kA] 100 100 100 100 50 50 50 50 50
690V [kA] 10 10 10 6 6 6 10 10 10
Rated Service Short CircuitBreaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 25 50 50 50
440/460V [kA] 100 100 100 100 50 25 50 50 50
500V [kA] 100 100 100 100 50 25 50 50 50
690V [kA] 10 10 10 6 4 4 10 6 6
Bulletin 140MMotor Protection Circuit Breakers
26
Specifications, Continued
IEC Performance Data, Continued
➊ No back-up fuse required.
Cat. No. 140M-C2T-
A16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16
Rated Operational Current,Ie [A] 0.16 0.25 0.40 0.63 1.0 1.6 2.5 4.0 6.3 10 16
Magnetic Release Current [A] 3.2 5.2 8.2 13 21 32 52 82 130 208 260
Switching of StandardThree-Phase Motors
AC-2, AC-3
230/240V [kW] — — — 0.06/0.09 0.12 0.18/0.25 0.37 0.55/0.75 1.1/1.5 2.2 3.0/4.0
400/415V [kW] 0.02 0.06 0.09 0.12/0.18 0.25 0.37/0.55 0.75 1.1/1.5 2.2 3.0/4.0 5.5/7.5
500V [kW] — — — 0.18 0.25/0.37 0.55/0.75 1.1 1.5/2.2 2.5/3.0 4.0/6.3 7.5/10
690V [kW] — — — 0.25 0.37/0.55 0.75/1.1 1.8 2.2/3.0 4.0 5.5/7.5 11/13
Back-Up FusesgG, gL, only if Icc > Icu
230/240V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
400/415V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 80
440/460V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 63 63
500V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 80 80
690V [A] ➊ ➊ ➊ ➊ ➊ 16 20 35 50 50 63
Ultimate Short CircuitBreaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 50
440/460V [kA] 100 100 100 100 100 100 100 100 100 65 10
500V [kA] 100 100 100 100 100 100 100 100 100 50 10
690V [kA] 100 100 100 100 100 8 8 8 4 4 3
Rated Service Short CircuitBreaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 15
440/460V [kA] 100 100 100 100 100 100 100 100 100 50 6
500V [kA] 100 100 100 100 100 100 100 100 100 50 6
690V [kA] 100 100 100 100 100 8 8 8 4 4 3
27
Bulletin 140MMotor Protection Circuit Breakers
Specifications, Continued
IEC Performance Data, Continued
➊ No back-up fuse required.➋ Consult your local Allen-Bradley distributor.
Cat. No. 140M-D8T- Cat. No. 140M-F8T-
C16 C20 C25 C32
Rated Operational Current,Ie [A] 16 20 25 32
Magnetic Release Current [A] 260 325 416 585
Switching of Standard Three-Phase MotorsAC-2, AC-3
230/240V [kW] 3.0/4.0 4.0/5.5 5.5/6.3 7.5
400/415V [kW] 5.5/7.5 7.5/10 11 15
500V [kW] 7.5/10 11 15 15/20
690V [kW] 11/13 15/17 18.5/22 22/25
Back-Up FusesgG, gL, only if Icc > Icu
230/240V [A] ➊ ➊ ➊ ➊
400/415V [A] 80 100 100 125
440/460V [A] 80 100 100 125
500V [A] 80 80 100 125
690V [A] 63 63 80 100
Ultimate Short Circuit Breaking CapacityIcu
230/240V [kA] 100 100 100 100
400/415V [kA] 65 65 65 65
440/460V [kA] 65 65 65 65
500V [kA] 50 50 50 50
690V [kA] 6 6 10 10
Rated Service Short Circuit Breaking CapacityIcs
230/240V [kA] 100 100 100 100
400/415V [kA] 25 25 50 50
440/460V [kA] 25 25 50 50
500V [kA] 25 25 50 50
690V [kA] 4 4 10 6
Bulletin 140MMotor Protection Circuit Breakers
28
Specifications, Continued
General Data
Cat. No. 140M-C 140M-D 140M-F 140-CMNRated Insulation Voltage UiIEC, SEV, VDE 0660 [V]
690 690
UL, CSA [V] 600 690Rated Impulse Withstand Voltage UimpPollution degreeMain circuitsAuxiliary circuits
6 kV/36 kV/3 6 kV/3
6 kV/3Rated Frequency [Hz] 50/60 40…60Utilization Category IEC 947-2 (Circuit breaker) IEC 947-4-1 (Motor starter)
AAC-3
Life SpanMechanical [operations] 100 000 30 000 30 000
Electrical (Ie max.) [operations] 100 000 30 000 10 000 (up to 63 A)5 000 (up to 90 A)
Switching Frequency [operations/h] max. 25 (motor starts) max. 20Ambient TemperatureStorage [°C] - 40…+ 80 - 25…+ 80
Operation [°C] - 25…+ 60 - 25…+ 60Resistance to Climatic Change IEC 68-2 C IV (acc. to IEC 68)
Moisture/heat resistance 40 °C, 92 %, 56 days
Moisture/change resistance 23 °C, 8 %/40 ×C, 93 %, 56 cycles
Site Altitude [m] to 2000 N.N.Protection Class IP20, when wired IP20Resistance to Shock [g] 30, 11 ms in preparation 30, 11 msResistance to VibrationFrequency range [Hz]in all directions [g]
IEC 68-210…150
under testingRated Thermal Current IthIEC, SEV, VDE 0660up to 40°C ambient temperature [A]up to 60°C ambient temperature [A]
0.1…250.1…25
1.6…251.6…25
6.3…456.3…45
16…9016…90
Rated Supply Current Ie [A]Number of setting ranges
0.1…2513
1.6…257
6.3…456
16…904
Dependence on Temperature40 °C [A]50 °C [A]60 °C [A]
no reduction no reduction
70 °C [A] 15 % current reduction of the upper rated current Ie15 % current reduction of the upper
rated current Ie
Overload ProtectionCharacteristics
IEC 60947-4-1 Motor protection (except 140M-C2N, 140M-D8N, 140M-F8N)
IEC 60947-4-1Motor protection
Ambient Temperature Compensation [°C] - 20…+ 60 - 20…+ 60Phase-loss Protection Differential release Differential release
Trip class 10 (except 140M-C2N, 140M-D8N, 140M-F8N) 10
Magnetic ReleaseRelease current
fixed setting13 x Iemax. (for 140M-C2E, 140M-D8E, 140M-F8E, 140M-
C2N, 140M-D8N, 140M-F8N)16…20 x Ie max. (for 140M-C2T, 140M-D8T, 140M-F8T)
Ie max. = maximum values of setting ranges
fixed setting14 x Ie max.
Total Power loss PvCircuit Breaker at rated load operating temperature [W]
6…8 6…8 9…16 33
Main Circuit Breaker Application Usable as main circuit breaker according to IEC 204 with corresponding accessories
29
Bulletin 140MMotor Protection Circuit Breakers
Specifications, Continued
General Data
Accessories for Bulletin 140M Motor Protection Circuit Breakers
Cat. No. 140M-C… 140M-D… 140M-F… 140-CMN
Conformity to StandardsIEC 947;
EN 60947;UL 508; CSA 22.2
IEC 60947;EN 60947;
UL 508; CSA 22.2
Approvals CE, UL, CSA
CE, UL Listed, CSA, (Germanischer Lloyd, Bureau Veritas,
Lloyd’s Register of Shipping,Maritime Register of Shipping, RINA,
in preparation)
Terminal PartsType of terminals
Screwdriver Pozidriv No. 2/Blade No. 3 Pozidriv No. 2/Blade No. 3
1. conductor [mm2]/[AWG]2. conductor [mm2]/[AWG]
1…4/No. 16…121…4/No. 16…12
2.5…16/No.14…62.5…10/No. 14…8
2.5…35
1. conductor [mm2]/[AWG]2. conductor [mm2]/[AWG]
1…6/No. 16…81…6/No. 16…8
2.5…25/No. 14…42.5…16/No. 14…6 4…50 / No. 12…2
1. conductor [mm2]/[AWG]2. conductor [mm2]/[AWG]
1.5…6/No. 16…81.5…6/No. 16…8
2.5…25/No. 14…42.5…16/No. 14…6
Tightening torque [Nm]/[lb-in] 1…2.5/8.9…22 1.5…3.5/13…31 6…10/53…120
Auxiliary Contact Blocks for Front Mounting
Cat. No. 140M-C-AFA…, 140M-C-AFAR…
Auxiliary Contact Blocks for Right-Side Mounting
Cat. No. 140M-C-ASA…, 140M-C-ASAR…
Rated Thermal Current Ithat 40°C ambient temperature [A]at 60°C ambient temperature [A]
54
106
Contact Class CoordinationAccording to NEMA(UL/CSA Standards) AC
DCB 300Q 300
B 600Q 600
Back-Up Fuses gG, gL [A] 10 10
Rated Supply Current [V]AC-15 [A]
244
1203
2401.5
246
1205
2403
4152
6900.7
DC-13 [V][A]
242
1200.5
2400.25
242
1200.5
2400.25
4150.15
Terminal PartsType of terminals
Screwdriver Pozidriv No. 2/Blade No. 3
1. conductor [mm2]/[AWG]2. conductor [mm2]/[AWG]
0.5…2.5/No. 18…140.5…2.5/No. 18…14
1. conductor [mm2]/[AWG]2. conductor [mm2]/[AWG]
0.75…2.5/No. 18…140.75…2.5/No. 18…14
1. conductor [mm2]/[AWG]2. conductor [mm2]/[AWG]
0.75…2.5/No. 18…140.75…2.5/No. 18…14
Tightening torque [Nm]/[lb-in.] 1.5/13.3
Bulletin 140MMotor Protection Circuit Breakers
30
Specifications, Continued
Accessories for Bulletin 140M Motor Protection Circuit Breakers, Continued
Weights
Undervoltage Tripfor Left-Side MountingCat. No. 140M-C-UX…
Undervoltage Tripwith 2 Auxiliary Contacts
for Left-Side MountingCat. No. 140M-C-UC…
Shunt Trip for Left-Side MountingCat. No. 140M-C-SN…
Actuating VoltagePull-inDrop-out
0.85…1.1 x Us0.7…0.35 x Us
0.85…1.1 x Us0.7…0.35 x Us
0.7…1.1 x Us
Rated Control Voltage min.max.
21V 50 Hz, 24V 60 Hz600V 50 Hz
21V 50 Hz, 24V 60 Hz600V 50 Hz
21V 50 Hz, 24V 60 Hz600V 50 Hz
On-Time 100% 100% 100%
Coil Rating Pull-inHold
8.5 VA, 6 W3 VA, 1.2 W
8.5 VA, 6 W3 VA, 1.2 W
8.5 VA, 6 W3 VA, 1.2 W
Terminal PartsType of terminals
Screwdriver Pozidriv No. 2/Blade No. 3
1. conductor [mm2]/[AWG]2. conductor [mm2]/[AWG]
0.5…2.5/No. 18…140.5…2.5/No. 18…14
1. conductor [mm2]/[AWG]2. conductor [mm2]/[AWG]
0.75…2.5/No. 18…140.75…2.5/No. 18…14
1. conductor [mm2]/[AWG]2. conductor [mm2]/[AWG]
0.75…2.5/No. 18…140.75…2.5/No. 18…14
Tightening torque [Nm]/[lb-in] 1.5/13.3
Commoning Link Feeder Terminal 140M-C-WTE Commoning Link 140M-C-W
Rated Thermal Current Ithat 60°C ambient temperature [A] 63 63
1. conductor [mm2]/[AWG]2. conductor [mm2]/[AWG]
4…164…10 —
1. conductor [mm2]/[AWG]2. conductor [mm2]/[AWG]
6…25/No. 14…46…16/No. 14…6 —
1. conductor [mm2]/[AWG]2. conductor [mm2]/[AWG]
6…25/No. 14…46…16/No. 14…6 —
Tightening torque [Nm]/[lb-in] 3/27 —
Description Cat. No. Weight
Motor Protection Circuit Breakers
140M-C2E-…140M-D8E-…140M-F8E-…
317 g373 g782 g
140M-C2N-…140M-D8N-…140M-F8N-…
315 g365 g782 g
140M-C2T-…140M-D8T-…140M-F8T-…
315 g365 g782 g
140-CMN-… 1845 g
Auxiliary Contacts
140M-C-AFA10140M-C-AFA01
10 g140M-C-AFA11140M-C-AFA20
140M-C-ASA…
140M-C-AFAR10A…15 g140M-C-ASAR…M…
140M-C-ASAM11
140-A… 31 g
Undervoltage Trip
140M-C-UX… 108 g
140M-C-SN… 110 g
140M-C-UC… 116 g
140-CUV… 94 g
Trip Contact Blocks 140-CT… 31 g
Shunt Trip 140-CRT… 94 g
Description Cat. No. Weight
Anti-Tamper Cover 140M-C-CA 2 g
Lockable Twist Knob 140M-C-KN140M-C-KRY 5 g
Locking Tag 140M-C-M3 30 g
Door Coupling Handle 140M-C-DN66140M-C-NRY66 123 g
Extension Shaft 140M-C-DS 46 g
Legend Plate 140M-C-DFC… 4 g
Feeder Terminal 140M-C-WT140M-F-WT 172 g
Commoning Links
140M-C-W452140M-C-W453140M-C-W454140M-C-W455
47 g80 g104 g132 g
140M-C-W542140M-C-W543140M-C-W544140M-C-W545
52 g86 g118 g154 g
140M-C-W632140M-C-W633140M-C-W634140M-C-W635
56 g92 g134 g170 g
31
Bulletin 140MMotor Protection Circuit Breakers
Specifications, Continued
Accessories for Bulletin 140-CMN Circuit BreakersCat. No. 140-CT
Trip Contact Block for Flush Mounting on Cat. No. 140-CMN Circuit Breakers
Cat. No. 140-CRT, 140-CUV Undervoltage Trip and Shunt Trip for Flush Mounting on Cat.
No. 140-CMN Circuit Breakers
Rated Thermal Current Ith
up to 40 °C ambient temperature [A] 10 2
up to 60 °C ambient temperature [A] 6 2
NEMA contact class(UL/CSA-Approval) AC
DCB 600 Standard Pilot Duty
R 300 Light Pilot Duty
MakeBrake max. voltage432 VA72 VA480 V28 VA28 VA250 V
Back-Up Fuse gG, gL 16 A 16 A
Rated Current Ie[V]
AC-15: [A]2303
4002.5
5001.5
6900.75 AC-14: 24
1.51101.5
2301.0
4001.0
5000.75
[V]DC-13: [A]
242
480.6
1100.2
2300.1
4400.04 DC 13: 24
1.5480.5
600.4
1100.2
Terminals
Screwdriver
1.conductor [mm2]/[AWG]2.conductor [mm2]/[AWG]
0.75…2.5/No. 18…140.75…2.5/No. 18…14
0.75…2.5/No. 18…140.75…2.5/No. 18…14
1.conductor [mm2]/[AWG]2.conductor [mm2]/[AWG]
0.75…2.5/No. 18…140.75…2.5/No. 18…14
0.75…2.5/No. 18…140.75…2.5/No. 18…14
Tightening torque [Nm]/[lb-in] 1…1.5/8.8…10.3 1…1.5/8.8…10.3
Cat. No. 140-CUV…Undervoltage Trip Unit for Right-Side Mounting on
Cat. No. 140-CMN Circuit Breakers
Cat. No. 140-CRT…Shunt Trip for Flush Mounting on
Cat. No. 140-CMN Circuit Breakers
Operating Voltage
Pick-up 0.8…1.1 x Us 0.7…1.1 x Us
Drop-out 0.7…0.35 x Us —
Duty cycle 100 % ED 100 % ED
Control Voltagemin. 12 V 50 Hz/14 V 60 Hz 12 V 50 Hz/14 V 60 Hz
max. 600 V 50 Hz 600 V 50 Hz
Coil PerformancePick-up [VA/W] 11 / 8 12 / 7
Drop-out [VA/W] 4 / 1 6 / 2
TerminalsTerminal type
Fine-stranded [mm2] 2 x 0.75…2.5 2 x 0.75…2.5
Coarse-strande [mm2] 2 x 0.75…2.5 2 x 0.75…2.5
Tightening torque [Nm] 1…1.5 1…1.5
Coarse-stranded [AWG] No. 18…. 14 No. 18…. 12
Tightening torque [lb-in] 8.8…10.3 8.8…10.3
Bulletin 140MMotor Protection Circuit Breakers
32
Specifications, Continued
Cut-off current
Î s
Icc
Icc
I D asymmetrical
symmetrical
The Bulletin 140-M limits solid short-circuit current Icc (prospective short-circuit current). ID is the maximum cut-off current (highest instantaneous value of the limited short-circuit current). This value is indicated in the following diagrams as a function of the progressive system short-circuit current.
1
10
100
1 10 100
25A 16A20A
10A
6.3A
4.0A
1
10
100
1 10 100
25A
0.25
0.30
0.50
0.70
0.80
cos ϕ =
16A
20A10A
6.3A
4.0A
0.90
140M-C Circuit BreakerMaximum cut-off currentRated operating voltage 415V
max
. cut
-off
curr
ent I
D [k
A]
max
. for
war
d en
ergy
Maximum forward energyRated operating voltage 415V
Prospective short-circuit current Icc [kA] Prospective short-circuit current Icc [kA]
i2t
103
A2
s[
]d
∫
33
Bulletin 140MMotor Protection Circuit Breakers
Specifications, Continued
1
10
100
1 10 100
25A
0.25
0.30
0.50
0.70
0.80
0.90
cos ϕ =
16A20A
10A
6.3A
4.0A
1
10
100
1 10 100
25A
16A20A
6.3A
10A
4.0A
140M-D Circuit BreakerMaximum cut-off currentRated operating voltage 415V
Maximum cut-off currentRated operating voltage 415V
max
. cut
-off
curr
ent I
D [k
A]
max
. for
war
d en
ergy
Prospective short-circuit current Icc [kA] Prospective short-circuit current Icc [kA]
i2t
103
A2
s[
]d
∫
1
10
100
1000
1 10 100
45A32A25A20A
10A
16A
1
10
100
1 10 100
0.25
0.30
0.50
0.70
0.80
0.90
cos ϕ = 45A32A25A20A16A
10A
140M-F Circuit BreakerMaximum cut-off currentRated operating voltage 415V
Maximum cut-off currentRated operating voltage 415V
max
. cut
-off
curr
ent I
D [k
A]
max
. for
war
d en
ergy
Prospective short-circuit current Icc [kA] Prospective short-circuit current Icc [kA]
i2t
103
A2
s[
]d
∫
Bulletin 140MMotor Protection Circuit Breakers
34
Specifications, Continued/Approximate Dimensions
Time-Current Characteristic
Approximate DimensionsDimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 140M Motor Protector
1) Thermal Release Trip CurrentThe adjustable current-dependent delayed bimetal release protects motors against overload. The curve shows the mean operating current at an ambient temperature of 20°C starting from the cold state. Careful testing and setting ensures effective motor protection even in the case of single-phasing. The overload characteristic is also valid for transformer protection.
2) Magnetic Release Trip CurrentThe instantaneous magnetic trip has a fixed operating current setting. This corresponds to 13 times the maximum value of setting range. (Transformer protection up to 20 x Ie max.) At a lower setting it is correspondingly higher.
Current Setting IeF
The overload trip corresponds to a thermal overload relay in a motor starter conforming to IEC 947-4-1. If a different value is prescribed (e.g., reduced Ie for cooling medium having a temperature higher than 40°C or a place of installation higher than 2000 m above sea level), the setting current is equal to the reduced rated current Ie of the motor.
0.8
1 000
1h
10 000
100
10
1
0.1
0.01
0.001
1 2 4 6 20 40 60 10010
1
2
Multiple of set current IeF
Trip
ping
tim
e [s
]
9(23/64)
24.8 (31/32)
90 (
3-35
/64)
18(23/32)
4.5
(3/1
6)
45(1-25/32)
➌
➋ 54 (2-1/8)
72 (2-53/64) 7.5(19/64)
4.5(3/16)
➍
➊45
(1-
25/3
2)
45 (
1-25
/32)
44 (1-47/64)
62 (2-7/16)
4.5(3/16) 7.5
(19/64)
➍
➊
45 (
1-25
/32)
45 (
1-25
/32)
45 (
1-25
/32)
➋
➍
18(23/32)
4.5
(3/1
6)
➌
55 (
2-11
/64)
110
(4-2
1/64
)
29.4 (1-5/32)
54(2-1/8)
9(23/64)
91 (3-37/64)
➊
55 (
2-11
/64)
4.5(3/16) 102 (4-1/64) 7.5
(19/64)
45 (
1-25
/32) ➊ Mounting on 35 mm DIN Rail EN 50 022-35
➋ Auxiliary contact (side-mounted)➌ Undervoltage trip or Shunt trip➍ Auxiliary contact (front-mounted)
140M-C…, 140M-D… 140M-C…. 140M-D…
140M-F….
35
Bulletin 140MMotor Protection Circuit Breakers
Approximate Dimensions, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Cat. No. 140M-C, -D, -F
9(23/64)
90 (
3-35
/64)
18(23/32)
4.5
(3/1
6)
45(1-25/32)
➌ ➋
54(2-1/8)
72(2-53/64)
7.5(19/64)
4.5(3/16)
➍
➊
45 (
1-25
/32)
45 (
1-25
/32)
44(1-47/64)
62(2-7/16)
4.5(3/16)
7.5(19/64)
➍
➊
12 (
15/3
2)45 (
1-25
/32)
45 (
1-25
/32)
24.8(31/32)
45 (
1-25
/32)
12 (
15/3
2)
➋ ➍
18
(23/32)
4.5
(3/1
6)
➌
55 (
2-11
/64)
110
(4-
21/6
4)
29.4
(1-5/32)
54
(2-1/8)
9
(23/64)
91
(3-37/64)
➊
55 (
2-11
/64)
4.5
(3/16)
102
(4-1/64)7.5
(19/64)
45 (
1-25
/32)
12 (
15/3
2)
min. 100
53.5
53.5
a
1.5...5Ø 35...45
4.5
Ø 3.5
Ø 4...8
b
± 5 mm
2.4
4.5
c2c1
90˚ 90˚90˚ 90˚d
d
➊ Can be mounted on DIN Rail EN 50 022-35➋ Auxiliary contact block (Side mounting)➌ Undervoltage trip or shunt trip➍ Auxiliary contact (Front mounting)
Mounting position/safety clearance of Cat. No. 140M-C…, 140M-D…, 140M-F…
140M-C…, 140M-D… 140M-C… 140M-D…
140M-F….
140M-C-D…66
Cat. No. a b c1 c2 d140M-C 117…338 105.5 ±5 49.5 40.5 25140M-D 126…347 114.5 ±5 49.5 40.5 25140M-F 148.6…369.6 137.1 ±5 59.35 50.35 30
Bulletin 140MMotor Protection Circuit Breakers
36
Approximate Dimensions, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Cat. No. 198E…
130
(5-1
/8)
47(1-27/32)
101(3-31/32)
4 (5/32)
150
(5-2
9/32
)
22 (
55/6
4)
50
(1-31/32)
ø 2
0.5
(13/
16)
ø 2
5.5
(1)
30(1-3/16)
I
90
(3-35/64)
50
(1-31/32)
70 (
2-3/
4)
53.5
(2-7/64)
53.5
(2
-7/6
4)
130
(5-1
/8)
ø 4,6 (3/16)
198E-AYT..
37
Bulletin 140MMotor Protection Circuit Breakers
Approximate Dimensions, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Cat. No. 140-CMN…
90˚ 30˚7070
90˚ 90˚
25.5
(1)
25 (63/64)
45.4 (1-51/64)
ø 4.5(3/16)
160
(6-1
9/64
)
77.5
(3-
3/64
)
2 (5/64)
25
(63/64)
4 (5
/32)
12.5 (1/4) 12.5 (1/4)
168
(6-3
9/64
)
165
(6-1
/2) 45.4 (1-51/64)
EN 50022
24(15/16)
24(15/16)
2 (5
/64)
140
(5-3
3/64
)10
(25/
64)
5 (13/64)
15 (19/32)
68.3
(2-
11/1
6)35
.4
(1-2
5/64
)
64.3
(2-
17/3
2)
16 (5/8
)45
(1-2
5/32
)16 (5/8
)41
.5(1
-41/
64)
41.5
(1-4
1/64
)
6 (1/4)
63 (2-31/64)
97 (3-13/16)
114 (4-31/64)
140.6 (5-17/32)
56 (2-13/64)
79.5 (3-1/8) ø 7 (15/64)
10 (25/64)
120 (4-23/32)
T
TESTmin. 100
53.5
53.5180...402
1.5...5Ø 35...45
5
Ø 3.5
Ø 4...8
169±5
±5 mm
140-CMN
Mounting position/safety clearance of Cat. No. 140-CMN
140-CD…
Bulletin 140UMolded Case Circuit Breakers
38
Overview
Product Line Overview
Bulletin 140U Molded Case Circuit Breakers• 15…1200 A Molded Case Circuit Breakers
Thermal-Magnetic 15…800 AElectronic 70…1200 A
-LS — Long Time/Short Time-LSI — Long Time/Short Time/High Instantaneous-LSG — Long Time/Short Time/Ground Fault-LSIG — Long Time/Short Time/High Instantaneous/Ground Fault
Molded Case Switches 125…1200 A• Factory- or field-installed accessories• Flex cable operating mechanisms• Rotary variable-depth operating mechanisms• High interrupting ratings in compact dimensions• Globally rated and approved product line for worldwide application
Product Selection125 A H-Frame .............. 41250 A J-Frame ............... 45400 A K-Frame .............. 49600 A Q-Frame .............. 53800 A M-Frame.............. 571200 A N-Frame ............ 61
Conformity to StandardsUL 489CSA 22.2, No. 5IEC 60947-2
ApprovalsUL ListedCSA CertifiedCEKEMA-KEUR
Frame Reference H-Frame J-Frame K-Frame Q-Frame M-Frame N-FrameMax. Current In 125 A 250 A 400 A 600 A 800 A 1200 ACurrent Range 15…125 A 70…250 A 100…400 A 300…600 A 300…800 A 600…1200 AThermal Magnetic —Electronic: —
LS —
LSI —
LSG —
LSIG —
Interrupting Ratings:380…415V (Icu) 25 40 70 25 40 70 40 65 100 45 70 50 70 50 70 100480V 25 35 65 25 35 65 35 65 100 35 65 50 65 50 65 100600V 18 22 25 18 18 25 25 35 50 25 35 25 35 25 35 50690V (Icu) 3 4 6 6 6 7 10 13 18 20 25 20 25 20 25 30
Molded Case Switches
Flex Cable Operators
Rotary Operators
Internal Control Modules (Field installed)
Standards ComplianceUL 498
CSA 22.2, No. 5
IEC 60947-2 —
CE —
KEMA-KEUR
39
Bulletin 140UMolded Case Circuit Breakers
Catalog Number Explanation
Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a valid cat. no. Refer to the tables on the following pages for descriptions of options.
Complete Circuit Breaker Assemblies
Bulletin No.
Code Description
140U Molded Case Circuit Breaker
140U - H 6 C 3 – C50 – H ⊗
Frame/Rating
Code Description
H 125 A
J 250 A
K 400 A
Q 600 A
M 800 A
N 1200 A
Interrupting Rating/Breaking Capacity (based on Ic at 480V)
Code Description
2 20…29 kA
3 30…39 kA
5 50…59 kA
6 60…69 kA
8 80…89 kA
0 ≥100 kA
Protection Type
Code Description
C Fixed Thermal/Fixed Magnetic
D Fixed Thermal/Adjust Magnetic
E Adjust Thermal/Fixed Magnetic
F Adjust Thermal/Adjust Magnetic
G Electronic (LSG) — Long, short, ground fault
H Electronic (LSI) — Long, short, high instant
I Electronic (LSIG) — Long, short, high instant, ground fault
L Electronic (LS) — Long and Short time
S Molded Case Switch (Isolator)
Poles
Code Description
3 3 poles
Current Range
Code Description
C 10 rr. A
D 100 rr0 A
E 1000 rr00 A
Internal Control Modules
Code Description
A 1 Auxiliary contact
B 2 Auxiliary contacts
D 1 Alarm contact
F 1 Auxiliary + 1 Alarm contact
G Undervoltage release only
P Shunt trip only
Control Module Combinations
Code Description
H 1 Auxiliary contact + undervoltage release
J 2 Auxiliary contacts + undervoltage release
L 1 Auxiliary + 1 Alarm contact + undervoltage release
N 1 Alarm contact + undervoltage release
Q 1 Auxiliary contact + shunt trip
R 2 Auxiliary contacts + shunt trip
T 1 Auxiliary + 1 Alarm contact + shunt trip
V 1 Alarm contact + shunt trip
Voltage Code
See the following pages forvoltage code descriptions:
H-Frame Page 41
J-Frame Page 45
K-Frame Page 49
Q-Frame Page 53
M-Frame Page 57
N-Frame Page 61
Bulletin 140UMolded Case Circuit Breakers
40
Catalog Number Explanation
Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a valid cat. no. Refer to the tables on the following pages for descriptions of options.
Frames
Trip Units
Bulletin No.
Code Description
140U Molded Case Circuit Breaker
140U - J 3 X 3
Frame/Rating
Code Description
J 250 A
K 400 A
L 600 A
M 800 A
Interrupting Rating/Breaking Capacity (based on Ic at 480V)
Code Description
2 20…29 kA
3 30…39 kA
5 50…59 kA
6 60…69 kA
8 80…89 kA
0 ≥100 kA
Protection Type
Code Description
X Frame Only
Poles
Code Description
3 3 poles
Bulletin No.
Code Description
140U Molded Case Circuit Breaker
140U - J T F 3 – C50
Frame/Rating
Code Description
J 250 A
K 400 A
Q 600 A
M 800 A
Interrupting Rating/Breaking Capacity (based on Ic at 480V)
Code Description
T Trip Unit
Protection Type
Code Description
C Fixed Thermal/Fixed Magnetic
D Fixed Thermal/Adjust Magnetic
E Adjust Thermal/Fixed Magnetic
F Adjust Thermal/Adjust Magnetic
G Electronic (LSG) — Long, short, ground fault
H Electronic (LSI) — Long, short, high instant
I Electronic (LSIG) — Long, short, high instant, ground fault
L Electronic (LS) — Long and Short time
S Molded Case Switch (isolator)
Poles
Code Description
3 3 poles
Current Range
Code Description
C 10 rr. A
D 100 rr0 A
E 1000 rr00 A
41
Bulletin 140UMolded Case Circuit Breakers
Product Selection — 125 A, H-Frame
40/35 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic
70/65 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magneticl
Molded Case Switch — UL 1087
Rated Current
In [A]
Thermal Trip [A]
Ir = In (Fixed)
Magnetic Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)[kA] Cat. No.Icu /Ics [kA]
220…240V 380…415V 500V 690V 240V 480V 600/347V15 15 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C1520 20 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C2025 25 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C2530 30 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C3035 35 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C3540 40 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C4045 45 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C4550 50 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C5060 60 600 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C6070 70 700 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C7080 80 800 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C8090 90 900 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C90
100 100 1000 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-D10110 110 1100 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-D11125 125 1250 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-D12
Rated Current
In [A]
Thermal Trip [A]
Ir = In (Fixed)
Magnetic Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)[kA] Cat. No.Icu /Ics [kA]
220…240V 380…415V 500V 690V 240V 480V 600/347V15 15 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C1520 20 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C2025 25 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C2530 30 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C3035 35 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C3540 40 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C4045 45 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C4550 50 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C5060 60 600 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C6070 70 700 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C7080 80 800 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C8090 90 900 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C90100 100 1000 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-D10110 110 1100 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-D11125 125 1250 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-D12
Rated Current
In [A]
Thermal Trip [A]
Ir = In (Fixed)
Magnetic Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)[kA] Cat. No.Icu /Ics [kA]
220…240V 380…415V 500V 690V 240V 480V 600/347V15 15 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C1520 20 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C2025 25 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C2530 30 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C3035 35 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C3540 40 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C4045 45 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C4550 50 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C5060 60 600 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C6070 70 700 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C7080 80 800 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C8090 90 900 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C90
100 100 1000 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-D10110 110 1100 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-D11125 125 1250 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-D12
Rated Current
In [A]
Thermal Trip Ir = In [A]
Magnetic Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)[kA] Cat. No.Icu /Ics [kA]
220…240V 380…415V 500V 690V 240V 480V 600/347V125 None 1250 100 50 70 35 35 18 6 3 100 65 25 140U-H6S3-D12
• UL 489• CSA 22.2, No. 5• IEC 60947-2• CE• KEMA-KEUR
25/25 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic
• Terminal box lugs provided as standard
Bulletin 140UMolded Case Circuit Breakers
42
Accessories — 125 A, H-FrameInternal Control Modules — Field Installed
Internal Control Modules — Factory Installed
➊ For additional voltages, consult your local Allen-Bradley distributor.
Description Mounting Location Diagram Cat. No.
Auxiliary Contact (AX)• Electrically indicates “ON/
OFF” status of breakers
(1) 1a-1b 140U-H-EA1
(2) 1a-1b 140U-H-EA2
Alarm Contact (AL)• Electrically indicates when
the breaker is in the “TRIPPED” state
(1) 1M (make)- 1B (break) 140U-H-ER1
Auxiliary/Alarm Contact (AX/AL) Combination• Combination of auxiliary
contact and alarm contact
(1) 1a-1b(1) 1M (make)-
1B (break)140U-H-EA1R1
Shunt Trip (SNT)• Provides remote tripping of
the circuit breaker• Undervoltage trip not
available when shunt trip is used
12…60V, 50/60/DC 140U-H-SNJ
110…240V, 50/60/DC 140U-H-SND
380…600V, 50/60 140U-H-SNB
Undervoltage Release (UVT)• Automatically trips breaker
when voltage falls between preset value, 35…70%
• Shunt trip is not available when undervoltage release is used
24V50/60/DC 140U-H-UJ
110…127V, 50/60 140U-H-UD
208…240V, 50/60 140U-H-UA
380…500V, 50/60 140U-H-UB
525…600V, 50/60 140U-H-UC
Auxiliary andAlarm Contacts Suffix Shunt Trip
Combinations Suffix Undervoltage ReleaseCombinations Suffix
(1) AX - A (1) SNT only - P⊗ (1) UVT only - G⊗(2) AX - B (1) AX + (1) SNT - Q⊗ (1) AX + (1) UVT - H⊗(1) AL - D (2) AX + (1) SNT - R⊗ (2) AX + (1) UVT - J⊗
(1) AX + (1) AL - F (1) AX + (1) AL + (1) SNT - T⊗ (1) AX + (1) AL + (1) UVT - L⊗(1) AL + (1) SNT - V⊗ (1) AL + (1) UVT - N⊗
⊗ Standard Voltage Suffix Codes ➊ ⊗ Standard Voltage Suffix Codes ➊Voltage [V] 12…60 110…240 380…600 Voltage [V] 24 110…127 208…240 380…500 525…600
AC, 50/60 Hz J D B AC,
50/60 Hz J D A B C
DC J D — DC J — — — —
Right side only
1b
1c
1a
I >
AX
ON
1b
1c
1a
OFF
1b
1c
1a
TRIP
Right side only
I >
ON
B
1c
M
OFF TRIP
AL B
1c
M B
1c
M
Right side only
1b
1c
1a
I >
AX
ON
B
1c
M
OFF TRIP
AL
1b
1c
1a
B
1c
M
1b
1c
1a
B
1c
M
Left side only
S1
I >
SNT
S2
Left side only
U1
I >
UVT
U2
U >
(1) Shunt Trip (SNT)or
(1) Undervoltage Release (UVT)
(1) Auxiliary contact (AX)or
(2) Auxiliary contacts (AX)or
(1) Alarm contact (AL)or
(1) Alarm contact (AL) + Auxiliary contact (AX)
Mounting LocationLeft side only Right side only
43
Bulletin 140UMolded Case Circuit Breakers
Accessories — 125 A, H-Frame, Continued
External Accessories
Description Cat. No.
Terminal End Cover
0.25 in. (6.4 mm) Diameter Cable Entry
Qty: 1
140U-H-TC2
0.41 in. (10.4 mm) Diameter Cable Entry 140U-H-TC4
Terminal Shields IP20 Ingress Protection Qty: 1 140U-H-TS
Flex-Cable Operating Mechanism
Non-Metallic — Type 1/3/12/4/4X Flange-Mount Operating Handle
3 ft. (0.9 m) Cable 140U-H-FCX03
4 ft. (1.3 m) Cable 140U-H-FCX04
6 ft. (1.8 m) Cable 140U-H-FCX06
10 ft. (3.0 m) Cable 140U-H-FCX10
Stainless Steel — Type 4/4X Flange-Mount Operating Handle
3 ft. (0.9 m) Cable 140U-H-FCS03
4 ft. (1.3 m) Cable 140U-H-FCS04
6 ft. (1.8 m) Cable 140U-H-FCS06
10 ft. (3.0 m) Cable 140U-H-FCS10
Rotary, Variable-Depth Operating Mechanism
Rotary Handle — Type 1/1212 in. (305 mm) operating rod
Black Handle 140U-H-RM12B
Red/Yellow Handle 140U-H-RM12R
Rotary, Direct Couple Operating Mechanism
Rotary Handle — Type 1 Breaker Mounted
Black Handle 140U-H-RCB
Red/Yellow Handle 140U-H-RCR
End Cap KitProvides 3-phase connections for terminal or bolt-on connections
Metric Hardware providedQty: 1 140U-H-ECM
Phase Barriers Provides additional phase clearance when special connections are required Qty: 2 140U-H-PB
Padlock Kit Padlocking HaspLock-OFF only Qty: 1 140U-H-PL
DIN Rail Adapter Allows H-frame MCCB to mount to 35 mm DIN Rail Qty: 1 140U-H-DRA
Bulletin 140UMolded Case Circuit Breakers
44
Approximate Dimensions — 125 A, H-Frame
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Line End
.45(11.43)
4 Ð .17 (4.32) x .19 (4.83) Dia.Slot for #6 Mounting Screws
6 Ð .35 (8.90) Dia.
.72(18.29)
1.38(35.05)
1.73(43.94)
3.03(76.96)
Push toTrip Button
.17(4.32)
.15(3.81)
.17(4.32)
1.08(27.43)
.55(13.97)
.20 (5.08) Dia.Thru Conductors 1.00
(25.40)1.21
(30.73)
1.00(25.40)
.50(12.70)
.50(12.70)
3.81(96.78)
.56(14.22)
Breaker Status Dimension
A B C D E
On 2.71(68.83)
2.53(64.26)
3.46(87.88)
2.83(71.88)
2.75(69.85)
Off 1.54(39.12)
1.62(41.15)
3.46(87.88)
1.66(42.16)
1.84(46.74)
Tripped 2.33(59.18)
2.23(56.64)
3.54(89.92)
2.46(67.48)
2.45(62.23)
Reset 1.39(35.31)
1.49(37.85)
3.42(86.87)
1.52(38.61)
1.70(43.18)
.78(19.81)
.09(2.29)
.22(5.59)
AttachmentLeads SideExit Point
5.50(139.70)
2.18(55.37)
Handle
.03(0.76)
.09(2.29)
.77(19.56)
1.42(36.07)
2.77(70.36)
2.93(74.42)2.99
(75.95)C
E
D
BA
.22(5.59)
.57(14.48)
R2.13
.58(14.73)
CL
.44(11.18)
1.50(38.10)
.47(11.94)
AttachmentLeads RearExit Point
.67(17.02)
1.44(36.58)
.94(23.88)
3.00(76.20)
45
Bulletin 140UMolded Case Circuit Breakers
Product Selection — 250 A, J-Frame
Breaker Frames
Trip Units
Assembled Circuit Breakers, Thermal-Magnetic Trip Units
Assembled Circuit Breakers, Electronic Trip Units
Molded Case Switch — UL 1087
Rated Current In [A]
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz) [kA] Cat. No.Icu /Ics [kA]
220…240V 380…415V 500V 690V 240V 480V 600V
25065 65 25 25 20 12 6 3 65 25 18 140U-J2X385 85 40 40 35 20 6 3 85 35 18 140U-J3X3
100 100 70 70 42 20 7 3 100 65 25 140U-J6X3
Thermal-Magnetic ElectronicRated
CurrentIn [A]
Adjustment Range [A]Cat. No.
Rated Current In [A]
Adjustment Range [A]Protection
Type Cat. No.Thermal Trip [A] Ir = In (Fixed)
Magnetic TripIm = 5…10 x In
Thermal TripIr = 0.4…1.0 x In
Magnetic TripIm = 2…14 x In
90 90 450…900 140U-JTD3-C90 50 20…50 40…700 LS 140U-JTL3-C50100 100 500…1000 140U-JTD3-D10 50 20…50 40…700 LSI 140U-JTH3-C50125 125 600…1250 140U-JTD3-D12 100 40…100 80…1400 LS 140U-JTL3-D10150 150 750…1500 140U-JTD3-D15 100 40…100 80…1400 LSI 140U-JTH3-D10175 175 875…1750 140U-JTD3-D17 160 63…160 126…2240 LS 140U-JTL3-D16200 200 1000…2000 140U-JTD3-D20 160 63…160 126…2240 LSI 140U-JTH3-D16225 225 1125…2250 140U-JTD3-D22 250 100…250 200…3500 LS 140U-JTL3-D25250 250 1250…2500 140U-JTD3-D25 250 100…250 200…3500 LSI 140U-JTH3-D25
Rated Current In [A]400/480V
Cat. No.400/480V
Cat. No.400/480V
Cat. No.[kA] [kA] [kA]
90 25/25 140U-J2D3-C90 40/35 140U-J3D3-C90 70/65 140U-J6D3-C90100 25/25 140U-J2D3-D10 40/35 140U-J3D3-D10 70/65 140U-J6D3-D10125 25/25 140U-J2D3-D12 40/35 140U-J3D3-D12 70/65 140U-J6D3-D12150 25/25 140U-J2D3-D15 40/35 140U-J3D3-D15 70/65 140U-J6D3-D15175 25/25 140U-J2D3-D17 40/35 140U-J3D3-D17 70/65 140U-J6D3-D17200 25/25 140U-J2D3-D20 40/35 140U-J3D3-D20 70/65 140U-J6D3-D20225 25/25 140U-J2D3-D22 40/35 140U-J3D3-D22 70/65 140U-J6D3-D22250 25/25 140U-J2D3-D25 40/35 140U-J3D3-D25 70/65 140U-J6D3-D25
Rated Current In [A] Protection Type 400/480V
[kA] Cat. No. 400/480V[kA] Cat. No. 400/480V
[kA] Cat. No.
50 LS 25/25 140U-J2L3-C50 40/35 140U-J3L3-C50 70/65 140U-J6L3-C5050 LSI 25/25 140U-J2H3-C50 40/35 140U-J3H3-C50 70/65 140U-J6H3-C50100 LS 25/25 140U-J2L3-D10 40/35 140U-J3L3-D10 70/65 140U-J6L3-D10100 LSI 25/25 140U-J2H3-D10 40/35 140U-J3H3-D10 70/65 140U-J6H3-D10160 LS 25/25 140U-J2L3-D16 40/35 140U-J3L3-D16 70/65 140U-J6L3-D16160 LSI 25/25 140U-J2H3-D16 40/35 140U-J3H3-D16 70/65 140U-J6H3-D16250 LS 25/25 140U-J2L3-D25 40/35 140U-J3L3-D25 70/65 140U-J6L3-D25250 LSI 25/25 140U-J2H3-D25 40/35 140U-J3H3-D25 70/65 140U-J6H3-D25
Rated Current
In [A]
Thermal Trip Ir = In [A]
Magnetic Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz) [kA] Cat. No.Icu /Ics [kA]
220…240V 380…415V 500V 690V 240V 480V 600V250 None 2500 100 100 70 70 42 20 7 3 100 65 25 140U-J6S3-D25
• UL 489• CSA 22.2, No. 5• IEC 60947-2• CE• KEMA-KEUR (Pending)
• Terminal box lugs must be ordered separately. See page 47
Bulletin 140UMolded Case Circuit Breakers
46
Accessories — 250 A, J-Frame
Internal Control Modules — Field Installed
Internal Control Modules — Factory Installed
➊ For additional voltages, consult your local Allen-Bradley distributor.
Description Mounting Location Diagram Cat. No.
Auxiliary Contact (AX)• Electrically indicates “ON/
OFF” status of breakers
(1) 1a-1b 140U-H-EA1
(2) 1a-1b 140U-H-EA2
Alarm Contact (AL)• Electrically indicates when
the breaker is in the “TRIPPED” state
(1) 1M (make)- 1B (break) 140U-J-ER1
Auxiliary/Alarm Contact (AX/AL) Combination• Combination of auxiliary
contact and alarm contact
(1) 1a-1b(1) 1M (make)-
1B (break)140U-J-EA1R1
Shunt Trip (SNT)• Provides remote tripping of
the circuit breaker• Undervoltage trip not
available when shunt trip is used
12…60V, 50/60/DC 140U-H-SNJ
110…240V, 50/60/DC 140U-H-SND
380…600V, 50/60 140U-H-SNB
Undervoltage Release (UVT)• Automatically trips breaker
when voltage falls between preset value, 35…70%
• Shunt trip is not available when undervoltage release is used
24V50/60/DC 140U-H-UJ
110…127V, 50/60 140U-H-UD
208…240V, 50/60 140U-H-UA
380…500V, 50/60 140U-H-UB
525…600V, 50/60 140U-H-UC
Auxiliary and Alarm Contacts Suffix Shunt TripCombinations Suffix Undervoltage Release
Combinations Suffix
(1) AX - A (1) SNT only - P⊗ (1) UVT only - G⊗(2) AX - B (1) AX + (1) SNT - Q⊗ (1) AX + (1) UVT - H⊗(1) AL - D (2) AX + (1) SNT - R⊗ (2) AX + (1) UVT - J⊗
(1) AX + (1) AL - F (1) AX + (1) AL + (1) SNT - T⊗ (1) AX + (1) AL + (1) UVT - L⊗(1) AL + (1) SNT - V⊗ (1) AL + (1) UVT - N⊗
⊗ Standard Voltage Suffix Codes ➊ ⊗ Standard Voltage Suffix Codes ➊Voltage [V] 12…60 110…240 380…600 Voltage [V] 24 110…127 208…240 380…500 525…600
AC, 50/60 Hz J D B AC,
50/60 Hz J D A B C
DC J D — DC J — — — —
Left AND Right side
1b
1c
1a
I >
AX
ON
1b
1c
1a
OFF
1b
1c
1a
TRIP
Right side only
I >
ON
B
1c
M
OFF TRIP
AL B
1c
M B
1c
M
Right side only
1b
1c
1a
I >
AX
ON
B
1c
M
OFF TRIP
AL
1b
1c
1a
B
1c
M
1b
1c
1a
B
1c
M
Left side only
S1
I >
SNT
S2
Left side only
U1
I >
UVT
U2
U >
(1) Shunt Trip (SNT)or
(1) Undervoltage Release (UVT)
(1) Auxiliary contact (AX)or
(2) Auxiliary contacts (AX)or
(1) Alarm contact (AL)or
(1) Alarm contact (AL) + Auxiliary contact (AX)
Mounting LocationLeft side only Right side only
47
Bulletin 140UMolded Case Circuit Breakers
Accessories — 250 A, J-Frame, Continued
External Accessories
Description Cat. No.
Terminal Shields IP20 Ingress Protection Qty — 2 140U-J-TS
Flex-Cable Operating Mechanism
Non-Metallic — Type 1/3/12/4/4X Flange-Mount Operating Handle
3 ft. (0.9 m) Cable 140U-J-FCX03
4 ft. (1.3 m) Cable 140U-J-FCX04
6 ft. (1.8 m) Cable 140U-J-FCX06
10 ft. (3.0 m) Cable 140U-J-FCX10
Stainless Steel — Type 4/4X Flange-Mount Operating Handle
3 ft. (0.9 m) Cable 140U-J-FCS03
4 ft. (1.3 m) Cable 140U-J-FCS04
6 ft. (1.8 m) Cable 140U-J-FCS06
10 ft. (3.0 m) Cable 140U-J-FCS10
Rotary, Variable-Depth Operating Mechanism
Rotary Handle — Type 1/1212 in. (305 mm) operating rod
Black Handle 140U-J-RM12B
Red/Yellow Handle 140U-J-RM12R
Rotary, Direct Couple Operating Mechanism Rotary Handle — Type 1 Breaker Mounted
Black Handle 140U-J-RCB
Red/Yellow Handle 140U-J-RCR
Phase Barriers Provides additional phase clearance when special connections are required Qty: 2 140U-J-PB
Padlock Kit Padlocking HaspLock-OFF only Qty: 1 140U-J-PL
Terminal Lugs
Stainless Steel Box LugsCopper wire only(1) 4/0…350MCM
Qty: 1 140U-J-TLS1
Aluminum LugsAluminum or copper wire
(1) 4/0…350MCM(1) 25…185 mm2
Qty: 1 140U-J-TLA1
End Cap KitProvides 3-phase connections for terminal or bolt-on connections
Metric HardwareQty:1 140U-J-ECM
Bulletin 140UMolded Case Circuit Breakers
48
Approximate Dimensions — 250 A, J-Frame
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
5.0486.000
4.4535.642
.281 5.500
.170
ØTYP(6)
.650
3.344
Ø.198
7.0001.000
.125
.624
.1883.194
3.3443.440
3.570
.260
.125
1.541
1.771
.949
.949 .859
.173
.625
.187
REF1.906
.500
4.427
˚
TRIP
4.0˚
˚
R2.656
4.000
2.000
1.062
2.062
3.9224.938
.625
1.875R.188
.281
.500
.688
1.375
5.500
2.062
3.922
4.125
7.000
2.062
4.125
7.000
.500 Ø6 HOLES
.625ØØ
1.375
2.750
6.000
2.062
4.125
2.750
Ø.145
3.978
.203
.664
.897 2.906
.594
1.188
.688
RTYP(4)
1.375
BREAKER HANDLEH
FRONT CONNECTED DRILL PLAN
REAR CONNECTED STUDS
BREAKER HANDLE
BREAKER HANDLEK
THERMAL ADJUSTMENT
.110 X .310 DEEP
4 HOLES
.256
GNETIC ADJUSTPUSH TO TRIP
#8-32 TAP4 HOLES
49
Bulletin 140UMolded Case Circuit Breakers
Product Selection — 400 A, K-Frame
Breaker Frames
Trip Units and Rating Plugs
Assembled Circuit Breakers, Thermal-Magnetic Trip Units
Assembled Circuit Breakers, Electronic Trip Units
➊ Select proper rating plug to cover thermal trip requirement.
Molded Case Switch — UL 1087
Rated Current In [A]
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz) Cat. No.Icu /Ics [kA] [kA]
220…240V 380…415V 500V 690V 240V 480V 600V
40065 65 40 40 30 30 10 5 65 35 25 140U-K3X3100 100 65 65 50 38 13 6 100 65 35 140U-K6X3200 200 100 100 65 49 18 9 200 100 50 140U-K0X3
Thermal-Magnetic Electronic
Rated CurrentIn [A]
Adjustment Range [A]Cat. No.
Rated Current In [A]
Adjustment Range [A]Protection Type Cat. No.Thermal Trip [A]
Ir = In (Fixed)Magnetic Trip Im = 5…10 x In
Thermal Trip Ir = 1.0 x In
Magnetic Trip Im = 2…8 x In
100 100 500…1000 140U-KTD3-D10400 200…400 ➊ 400…3200
LS 140U-KTL3-D40125 125 625…1250 140U-KTD3-D12 LSI 140U-KTH3-D40150 150 750…1500 140U-KTD3-D15 LSG 140U-KTG3-D40175 175 895…1750 140U-KTD3-D17200 200 1000…2000 140U-KTD3-D20 Rating Plugs225 225 1125…2250 140U-KTD3-D22 Thermal Trip
In [A] Cat. No.Thermal Trip
In [A] Cat. No.250 250 1250…2500 140U-KTD3-D25300 300 1500…3000 140U-KTD3-D30 200 140U-KRP3-D20 300 140U-KRP3-D30350 350 1750…3500 140U-KTD3-D35 225 140U-KRP3-D22 350 140U-KRP3-D35400 400 2000…4000 140U-KTD3-D40 250 140U-KRP3-D25 400 140U-KRP3-D40
Rated CurrentIn [A]
400/480V [kA] Cat. No. 400/480V
[kA] Cat. No. 400/480V [kA] Cat. No.
100 40/35 140U-K3D3-D10 65/65 140U-K6D3-D10 100/100 140U-K0D3-D10125 40/35 140U-K3D3-D12 65/65 140U-K6D3-D12 100/100 140U-K0D3-D12150 40/35 140U-K3D3-D15 65/65 140U-K6D3-D15 100/100 140U-K0D3-D15175 40/35 140U-K3D3-D17 65/65 140U-K6D3-D17 100/100 140U-K0D3-D17200 40/35 140U-K3D3-D20 65/65 140U-K6D3-D20 100/100 140U-K0D3-D20225 40/35 140U-K3D3-D22 65/65 140U-K6D3-D22 100/100 140U-K0D3-D22250 40/35 140U-K3D3-D25 65/65 140U-K6D3-D25 100/100 140U-K0D3-D25300 40/35 140U-K3D3-D30 65/65 140U-K6D3-D30 100/100 140U-K0D3-D30350 40/35 140U-K3D3-D35 65/65 140U-K6D3-D35 100/100 140U-K0D3-D35400 40/35 140U-K3D3-D40 65/65 140U-K6D3-D40 100/100 140U-K0D3-D40
Rated CurrentIn [A]
Thermal Trip Ir = 0.5…1.0 x In
Protection Type 400/480V [kA] Cat. No. 400/480V
[kA] Cat. No. 400/480V [kA] Cat. No.
400 100…400 ➊LS 40/35 140U-K3L3-D40 65/65 140U-K6L3-D40 100/100 140U-K0L3-D40LSI 40/35 140U-K3H3-D40 65/65 140U-K6H3-D40 100/100 140U-K0H3-D40LSG 40/35 140U-K3G3-D40 65/65 140U-K6G3-D40 100/100 140U-K0G3-D40
Rated Current In [A]
Magnetic Trip 10 x In
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz) [kA] Cat. No.Icu /Ics [kA]
220…240V 380…415V 500V 690V 240V 480V 600V400 4000 100 100 65 65 50 38 13 6 100 65 35 140U-K6S3-D40
• UL 489• CSA 22.2, No. 5• IEC 157-1• KEMA-KEUR
• Terminal box lugs must be ordered separately. See page 51
Bulletin 140UMolded Case Circuit Breakers
50
Accessories — 400 A, K-Frame
Internal Control Modules — Field Installed
Internal Control Modules — Factory Installed
➊ For additional voltages, consult your local Allen-Bradley distributor.
Description Mounting Location Diagram Cat. No.
Auxiliary Contact (AX)• Electrically indicates “ON/
OFF” status of breakers
(1) 1a-1b 140U-K-EA1
(2) 1a-1b 140U-K-EA2
Alarm Contact (AL)• Electrically indicates when
the breaker is in the “TRIPPED” state
(1) 1M (make)- 1B (break) 140U-K-ER1
\
Auxiliary/Alarm Contact (AX/AL) Combination• Combination of auxiliary
contact and alarm contact
(1) 1a-1b(1) 1M (make)-
1B (break)140U-K-EA1R1
Shunt Trip (SNT)• Provides remote tripping of
the circuit breaker• Undervoltage trip not
available when shunt trip is used
12…24V, 50/60/DC 140U-K-SNJ
110…240V AC, 110…125V DC 140U-K-SND
380…440V AC, 220…250V DC 140U-K-SNN
480…600V, 50/60 Hz 140U-K-SNB
Undervoltage Release (UVT)• Automatically trips breaker
when voltage falls between preset value, 35…70%
• Shunt trip is not available when undervoltage release is used
24V,50/60 140U-K-UJ
110…127V, 50/60 140U-K-UD
208…240V, 50/60 140U-K-UA
380…500V, 50/60 140U-K-UB
Auxiliary and Alarm Contacts Suffix Shunt TripCombinations Suffix Undervoltage Release
Combinations Suffix
(1) AX - A (1) SNT only - P⊗ (1) UVT only - G⊗(2) AX - B (1) AX + (1) SNT - Q⊗ (1) AX + (1) UVT - H⊗(1) AL - D (2) AX + (1) SNT - R⊗ (2) AX + (1) UVT - J⊗
(1) AX + (1) AL - F (1) AX + (1) AL + (1) SNT - T⊗ (1) AX + (1) AL + (1) UVT - L⊗(1) AL + (1) SNT - V⊗ (1) AL + (1) UVT - N⊗
⊗ Standard Voltage Suffix Codes ➊ ⊗ Standard Voltage Suffix Codes ➊Voltage [V] 12…24 110…240 380…440 480…600 Voltage [V] 24 110…127 208…240 380…480
AC50/60 Hz J D N B AC
50/60 Hz J D A B
Voltage [V] 12…24 110…125 220…250 — Voltage [V] — — — —DC J D N — DC — — — —
Left AND Right side
1b
1c
1a
I >
AX
ON
1b
1c
1a
OFF
1b
1c
1a
TRIP
Right side ONLY
I >
ON
B
1c
M
OFF TRIP
AL B
1c
M B
1c
M
Right side ONLY
1b
1c
1a
I >
AX
ON
B
1c
M
OFF TRIP
AL
1b
1c
1a
B
1c
M
1b
1c
1a
B
1c
M
Left side ONLY
S1
I >
SNT
S2
Left side ONLY
U1
I >
UVT
U2
U >
(1) Shunt Trip (SNT)or
(1) Undervoltage Release (UVT)
(1) Auxiliary contact (AX)or
(2) Auxiliary contacts (AX)or
(1) Alarm contact (AL)or
(1) Alarm contact (AL) + Auxiliary contact (AX)
Mounting LocationLeft side only Right side only
51
Bulletin 140UMolded Case Circuit Breakers
Accessories — 400 A, K-Frame, Continued
External Accessories
Description Cat. No.
Terminal Shields IP20 Ingress Protection Qty: 1 140U-K-TS
Flex-Cable Operating Mechanism
Non-Metallic — Type 1/3/12/4/4X Flange-Mount Operating Handle
3 ft. (0.9 m) Cable 140U-K-FCX03
4 ft. (1.3 m) Cable 140U-K-FCX04
6 ft. (1.8 m) Cable 140U-K-FCX06
10 ft. (3.0 m) Cable 140U-K-FCX10
Stainless Steel — Type 4/4X Flange-Mount Operating Handle
3 ft. (0.9 m) Cable 140U-K-FCS03
4 ft. (1.3 m) Cable 140U-K-FCS04
6 ft. (1.8 m) Cable 140U-K-FCS06
10 ft. (3.0 m) Cable 140U-K-FCS10
Rotary, Variable-Depth Operating Mechanism
Rotary Handle — Type 1/1212 in. (305 mm) operating rod
Black Handle 140U-K-RM12B
Red/Yellow Handle 140U-K-RM12R
Rotary, Direct Couple Operating Mechanism Rotary Handle — Type 1 Breaker Mounted
Black Handle 140U-K-RCB
Red/Yellow Handle 140U-K-RCR
Operating Handle Extension Provides handle extension for ease of operation Qty: 1 140U-K-OHE
Phase BarriersProvides additional phase clearance when special
connections are requiredQty: 2 140U-K-PB
Padlock Kit Padlocking HaspLock-OFF only — 140U-K-PL
Terminal Lugs
Copper lugCopper wire only
(1) 250…500 MCM(1) 120…240 mm2
Qty: 1 140U-K-TLC1
Copper lugCopper wire only
(1) 3/0…250 MCM(1) 95…120 mm2
Qty: 3 140U-K-TLC2
Aluminum lugAluminum or copper wire
(1) 250…500 MCM(1) 120…240 mm2
Qty: 1 140U-K-TLA1
End Cap KitProvides 3-phase connections for terminal or bolt-on connections
Metric HardwareQty: 1 140U-K-ECM
Bulletin 140UMolded Case Circuit Breakers
52
Approximate Dimensions — 400 A, K-Frame
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
.875(22.25)
.438(11.13)
.500(12.70)
2.391(60.73)
5.490(139.43)
.188(4.77)
10.125(257.18)
8.438(214.33)
8.875(225.43)
3.563(90.50)
4.000(101.60)
2.813(71.45)
.125(3.18)
1.719(43.66)
3.438(87.32)
.625(15.88)
1.063(27.00)
.766(19.46)
2.375(60.33)
.250(6.35)
.188 R(4.77) R
.063(1.60)
1.250(31.75)
.698(17.73)
.250 R(6.35) R
Dimensions for ExtendedTerminals and Barrier StyleNos. 4212B60G02,4212B61G02 and 1492D24H01
3.812(96.82)
1.160(29.49)
.937(23.80)
.281 (7.14) Dia. Mounting Holes4 Holes for .250-20 (M6) x 1.50(38) Mounting Screws .500(12.70) Dia. C'Bore from T op2.875 (73.03) Deep Load End2.625 (66.68) Deep Line End .438(11.13) Dia C'Bore .750 (10.05)Deep from Bottom
.750 (19.05)Wide Conductorwith .391 (9.93)Dia Hole Lineand Load End
1.625(41.28)
1.625(41.28)
1.219(30.96)
7.406(112.70)
4.437(65.10)
2.563(12.70)
.375(9.52)
ContactPositionIndicatorsRed/1 - OnGreen/O - OffWhite - T rip
.500(12.70)
4.125 (104.78)
1.719(43.66)
.860 (21.84)2.063 (52.39)
.750(19.05)
.188(4.77) R
.093 R(2.36) R
ON
OFF
F
E
.500(12.70)
.062(1.57)4.062
(103.17)
39û
.547(13.89)
1.734(44.04)
.209(5.31)
.188(4.77)
.500(12.70)
.500(12.70)
.062(1.57)
1.063(27.00)
3.813(96.85)
1.000(25.40)
5.00
0(1
27.0
0)
5.96
6(1
51.5
4)
5.76
6(1
46.4
6)
43û
.694(17.63)
.500(12.70)
4.313(109.55)
D
.188 (4.77) Dia.C'Bore x .031 (.79)DP .147 (12.7) Dia.Hole x .500 DP toAccept #8 (M4)Thread CuttingScrews (8 Places)
.125 (3.18) Wide x
.750 (19.05) Slots forAttachment Leads
CB
A
Trough forAttachmentLeads
.625 (15.88)6 Holes
3.75(9.52)
.844(21.44)
.110 (2.79) Dia. x .297 (7.54)Deep, 4 Holes Accept #6(M3) Thread Cutting Screws
.250 (6.35) R.063 (1.60)
3.875 R(98.42) RHandle
CL
4.782(121.46)
2.438(61.89)
Front ViewSide View
Line End
Load End
Breaker Dimensions
Status A B C D E F
On 5.39 5.20 5.69 5.61 4.72 4.77 30 lbs.(136.9) (132.1) (144.5) (142.5) (119.9) (121.2) (13.61 kgs.)
Tripped 4.77 4.69 5.08 5.11 4.89 4.89 N/A(121.2) (119.1) (129.0) (129.8) (124.2) (124.2)
Off 4.16 4.21 4.46 4.64 4.95 4.91 25 lbs.(105.7) (106.9) (113.3) (117.9) (125.7) (124.7) (11.34 kgs.)
Reset 4.07 4.14 4.57 4.56 4.95 4.90 35 lbs.(103.4) (105.2) (116.1) (115.8) (125.7) (124.5) (15.87 kgs.)
➀ All handle forces measured approximately 0.125 (3.17) from top of handle.
HandleForce➀
53
Bulletin 140UMolded Case Circuit Breakers
Product Selection — 600 A, Q-Frame
Breaker Frames
Trip Units and Rating Plugs
Assembled Circuit Breakers, Thermal-Magnetic Trip Units
Assembled Circuit Breakers, Electronic Trip Units
➊ Select proper rating plug to cover thermal trip requirement.
Molded Case Switch — UL 1087
Rated Current In [A]
Breaking Capacity (50 Hz)Interrupting Rating (60 Hz) [kA]
Cat. No.Icu /Ics [kA]220…240V 380…415V 500V 690V 240V 480V 600V
60085 85 45 45 30 30 20 10 65 35 25 140U-Q3X3100 100 70 70 50 38 25 13 100 65 35 140U-Q6X3
Thermal-Magnetic Electronic
Rated Current In [A]
Adjustment Range [A]Cat. No.
Rated Current In [A]
Adjustment Range [A]Protection Type Cat. No.Thermal Trip
Ir = In (Fixed)Magnetic Trip Im = 5…10 x In
Thermal TripIr = 0.5…1.0 x In
Magnetic Trip Im = 2…8 x In
300 300 1500…3000 140U-QTD3-D30600 400…600 ➊ 800…4800
LS 140U-QTL3-D60350 350 1750…3500 140U-QTD3-D35 LSI 140U-QTH3-D60400 400 2000…4000 140U-QTD3-D40 LSG 140U-QTG3-D60450 450 2250…4500 140U-QTD3-D45500 500 2500…5000 140U-QTD3-D50 Rating Plugs600 600 3000…6000 140U-QTD3-D60 Thermal Trip
In [A] Cat. No.
400 140U-QRP3-D40500 140U-QRP3-D50600 140U-QRP3-D60
Rated Current In [A] Thermal TripIr = In
400/480V[kA] Cat. No. 400/480V
[kA] Cat. No.
300 300 45/35 140U-Q3D3-D30 70/65 140U-Q6D3-D30350 350 45/35 140U-Q3D3-D35 70/65 140U-Q6D3-D35400 400 45/35 140U-Q3D3-D40 70/65 140U-Q6D3-D40450 450 45/35 140U-Q3D3-D45 70/65 140U-Q6D3-D45500 500 45/35 140U-Q3D3-D50 70/65 140U-Q6D3-D50600 600 45/35 140U-Q3D3-D60 70/65 140U-Q6D3-D60
Rated Current In [A]
Thermal TripIr = 0.5…1.0 x In
Protection Type 400/480V[kA] Cat. No. 400/480V
[kA] Cat. No.
600 200…600 ➊LS 45/35 140U-Q3L3-D60 70/65 140U-Q6L3-D60LSI 45/35 140U-Q3H3-D60 70/65 140U-Q6H3-D60LSG 45/35 140U-Q3G3-D60 70/65 140U-Q6G3-D60
Rated CurrentIn [A]
Magnetic TripIm = 10 x In
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz) [kA] Cat. No.Icu /Ics [kA]
220…240V 380…415V 500V 690V 240V 480V 600V600 6000 100 100 70 70 50 38 25 13 100 65 35 140U-Q6S3-D60
• UL 489• CSA 22.2, No. 5• IEC 60947-2• CE• KEMA-KEUR
• Terminal box lugs must be ordered separately. See page 55
Bulletin 140UMolded Case Circuit Breakers
54
Accessories — 600 A, Q-Frame
Internal Control Modules — Field Installed
Internal Control Modules — Factory Installed
➊ For additional voltages, consult your local Allen-Bradley distributor.
Description Mounting Location Diagram Cat. No.
Auxiliary Contact (AX)• Electrically indicates “ON/
OFF” status of breakers
(1) 1a-1b 140U-M-EA1
(2) 1a-1b 140U-M-EA2
Alarm Contact (AL)• Electrically indicates when
the breaker is in the “TRIPPED” state
(1) 1M (make)- 1B (break) 140U-M-ER1
\
Auxiliary/Alarm Contact (AX/AL) Combination• Combination of auxiliary
contact and alarm contact
(1) 1a-1b(1) 1M (make)-
1B (break)140U-M-EA1R1
Shunt Trip (SNT)• Provides remote tripping of
the circuit breaker• Undervoltage trip not
available when shunt trip is used
12…24V, 50/60/DC 140U-M-SNJ
110…240V AC, 110…125V DC 140U-M-SND
380…440V AC, 220…250V DC 140U-M-SNN
480…600V, 50/60 Hz 140U-M-SNB
Undervoltage Release (UVT)• Automatically trips breaker
when voltage falls between preset value, 35…70%
• Shunt trip is not available when undervoltage release is used
24V,50/60 Hz 140U-M-UJ
110…127V, 50/60 Hz 140U-M-UD
208…240V, 50/60 Hz 140U-M-UA
380…500V, 50/60 Hz 140U-M-UB
Auxiliary and Alarm Contacts Suffix Shunt TripCombinations Suffix Undervoltage Release
Combinations Suffix
(1) AX - A (1) SNT only - P⊗ (1) UVT only - G⊗(2) AX - B (1) AX + (1) SNT - Q⊗ (1) AX + (1) UVT - H⊗(1) AL - D (2) AX + (1) SNT - R⊗ (2) AX + (1) UVT - J⊗
(1) AX + (1) AL - F (1) AX + (1) AL + (1) SNT - T⊗ (1) AX + (1) AL + (1) UVT - L⊗(1) AL + (1) SNT - V⊗ (1) AL + (1) UVT - N⊗
⊗ Standard Voltage Suffix Codes ➊ ⊗ Standard Voltage Suffix Codes ➊Voltage [V] 12…24 110…240 380…440 480…600 Voltage [V] 24 110…127 208…240 380…480
AC50/60 Hz J D N B AC
50/60 Hz J D A B
Voltage [V] 12…24 110…125 220…250 — Voltage [V] — — — —DC J D N — DC — — — —
Left AND Right side
1b
1c
1a
I >
AX
ON
1b
1c
1a
OFF
1b
1c
1a
TRIP
Right side ONLY
I >
ON
B
1c
M
OFF TRIP
AL B
1c
M B
1c
M
Right side ONLY
1b
1c
1a
I >
AX
ON
B
1c
M
OFF TRIP
AL
1b
1c
1a
B
1c
M
1b
1c
1a
B
1c
M
Left side ONLY
S1
I >
SNT
S2
Left side ONLY
U1
I >
UVT
U2
U >
(1) Shunt Trip (SNT)or
(1) Undervoltage Release (UVT)
(1) Auxiliary contact (AX)or
(2) Auxiliary contacts (AX)or
(1) Alarm contact (AL)or
(1) Alarm contact (AL) + Auxiliary contact (AX)
Mounting LocationLeft side only Right side only
55
Bulletin 140UMolded Case Circuit Breakers
Accessories — 600 A, Q-Frame, Continued
External Accessories
Description Cat. No.
Flex-Cable Operating Mechanism
Non-Metallic — Type 1/3/12/4/4X Flange-Mount Operating Handle
4 ft. (1.3 m) Cable 140U-M-FCX04
6 ft. (1.8 m) Cable 140U-M-FCX06
10 ft. (3.0 m) Cable 140U-M-FCX10
Stainless Steel — Type 4/4X Flange-Mount Operating Handle
4 ft. (1.3 m) Cable 140U-M-FSX04
6 ft. (1.8 m) Cable 140U-M-FSX06
10 ft. (3.0 m) Cable 140U-M-FSX10
Rotary, Variable-Depth Operating Mechanism
Rotary Handle — Type 1/1212 in. (305 mm) operating rod
Black Handle 140U-M-RM12B
Red/Yellow Handle 140U-M-RM12R
Phase BarriersProvides additional phase clearance
when special connections are required
Qty:2 140U-M-PB
Padlock Kit Padlocking HaspLock-OFF only — 140U-M-PL
Operating Handle Extension Provides handle extension for ease of operation Qty: 1 140U-M-OHE
Terminal Lugs
Copper lugCopper wire only
(2) 250…350 MCM(2) 120…250 mm2
Qty: 1 140U-Q-TLC2
Aluminum lugAluminum or Copper wire
(2) 3/0…350 MCM(2) 95…150 mm2
Qty:1 140U-Q-TLA2
Bulletin 140UMolded Case Circuit Breakers
56
Approximate Dimensions — 600 A, Q-Frame
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
.516 (13.11) Hex
.250 (6.35) Deep
.328 (8.33) Dia.Hole
9.53
1 (2
42.0
9)
/
M
ount
ing
Hol
es
6.48
9 (1
64.8
2)
5.95
8 (1
51.3
3)
5.05
2 (1
28.3
2)
4.86
4 (1
23.5
4)
12.5
00 (
317.
50)
Ove
rall
Ext
ende
d Le
ngth
Terminal Barrier Usedwith Extended T erminalsOnly (TA603LD)
Removable T erminalCover Must Be inPlace While in Service
.250(6.35) R
.250(6.35) R
.156(3.96) R
.188 R(4.77) R
Han
dle
C L
HandleCLHandleCL
1.625(41.27)
11.3
44 (
288.
14)
/
E
xten
ded
Ter
min
als
3.01
9 (7
6.68
)
.297(7.54)
1.125(28.57)
1.232(31.29)
.438 (11.12)
.875 (22.22)
.406 (10.31)Dia. .250-20(6.35)
Tap12 Holes .147(3.73) Dia Hole
.500(12.70) Deep ToAccept #8 Thread CuttingScrews 8 Places
1.142(29.00)
3.09
4 (7
8.59
)
4.00
0 (1
01.6
0).2
50(6
.35)
5.08
3 (1
29.1
0)
1.126(28.60)
9.59
4 (2
43.6
8)
/
Sta
ndar
d T
erm
inal
s
5.61
4 (1
42.5
9)
10.7
50 (2
73.0
5)
Trough ForAttachmentLeads
.125(3.17) Widex .750 (19.05)Slots ForAttachment Leads
14.7ûOn
24.2ûReset
19.2ûOff
0.2ûTripped
.616
(15.
65)
.442
(11.
23)
2.29
2 (5
8.22
)
2.750(69.85)
1.375(34.92)
7.281 (184.94)
3.641 (92.48)
5.500 (139.70)
4.125 (104.77)
2.750 (69.85)
2.062(52.37)
8.250 (209.55)
Contact PositionIndicatorsRed/I - OnGreen/O - OffWhite - T rip
4.125 (104.77)
.313 (7.95) Dia. Mounting Holes(4) for .250 (6.35) - 20 x 1.50 (38.10)Mounting Screws.531 (13.49) Dia C'Bore from Top2.625 (66.67) Deep Line End (2)2.875 (73.02) Deep Load End (2).531 (13.49) Dia. C'Bore.875 (22.22) from Bottom
1.625 (41.27)
.812 (20.62)
1.906(48.41)
1.906(48.41)
3.250 (82.55)
1.875 (47.62) WideConductor with .406(10.31) Dia. Hole Line andLoad Ends (CurrentCarrying Parts Omittedin Center Pole for 2-PoleBreaker)
1.500(38.10)
.313 R(7.95) R
.110(2.79) Dia Hole
.312(7.92) Deep ToAccept #6Thread Cutting Screws6 Places
.016(0.41)
.800(20.32)
B
3.218(81.74)2.750
(69.85)
1.000(25.40) R x1.906(48.41) Wide
.062 (1.57)
.531 (13.49)
.375 (9.52)
1.265 (32.13)
2.047 (51.99)
.219(5.56)
6.68
8 (1
69.8
7)
8.21
3 (2
08.6
1)
45û
.500(12.70)
.482(12.24)
45û
.500(12.70)
.375(9.52)
.420(10.67)
.1.151(29.23)
4.32
7 (1
09.9
0)5.
136
(130
.45)
3.62
2 (9
2.00
)
0.062 R(1.57) R
3.496 (88.80) R
A
4.062 (103.17)
4.375 (111.12)
3.812 (96.82)
.531 (13.49).375 (9.52)
1.000(25.40) Rx 1.906 (48.41)Wide
On/I On/I
Off/O Off/O
C LC L
C LC L
C LC L
Trip Unit May BeEither Thermal/Magnetic
Or Electronic
4.26
0 (1
08.2
0)
2.281(57.94) 1.594
(40.49).375
(9.52)
.750(19.05)
Front View Side View
Line End
Load End
Handle Forces ➀
On 45 lbs.
Off 50 lbs.
Reset 60 lbs.
➀ Measurements taken approximately 3/16 in.from end of handle.
57
Bulletin 140UMolded Case Circuit Breakers
Product Selection — 800 A, M-Frame
Breaker Frames
Trip Units and Rating Plugs
Assembled Circuit Breakers, Thermal-Magnetic Trip Units
Assembled Circuit Breakers, Electronic Trip Units
➊ Select proper rating plug to cover thermal trip requirement.
Molded Case Switch — UL 1087
Rated CurrentIn [A]
Breaking Capacity (50 Hz)Interrupting Rating (60 Hz) [kA]
Cat. No.Icu /Ics [kA]220…240V 380…415V 500V 690V 240V 480V 600V
80065 65 50 50 50 25 20 10 65 50 25 140U-M5X3100 100 70 70 70 50 25 13 100 65 35 140U-M6X3
Thermal-Magnetic Electronic
Rated CurrentIn [A]
Adjustment Range [A]Cat. No.
Rated Current In [A]
Adjustment Range [A]Protection
Type Cat. No.Thermal TripIr = In
Magnetic Trip Im = 5…10 x In
Thermal TripIr = 1.0 x In
Magnetic Trip Im = 2…8 x In
300 300 1500…3000 140U-MTD3-D30800 400…800 ➊ 800…6400
LS 140U-MTL3-D80350 350 1750…3500 140U-MTD3-D35 LSI 140U-MTH3-D80400 400 2000…4000 140U-MTD3-D40 LSG 140U-MTG3-D80450 450 2250…4500 140U-MTD3-D45500 500 2500…5000 140U-MTD3-D50 Rating Plugs600 600 3000…6000 140U-MTD3-D60 Thermal Trip
In [A] Cat. No.Thermal Trip
In [A] Cat. No.700 700 3500…7000 140U-MTD3-D70800 800 4000…8000 140U-MTD3-D80 400 140U-MRP3-D40 700 140U-MRP3-D70
500 140U-MRP3-D50 800 140U-MRP3-D80600 140U-MRP3-D60
Rated Current In [A]
Thermal TripIr = In
400/480V[kA] Cat. No. 400/480V
[kA] Cat. No.
300 300 50/50 140U-M5D3-D30 70/65 140U-M6D3-D30350 350 50/50 140U-M5D3-D35 70/65 140U-M6D3-D35400 400 50/50 140U-M5D3-D40 70/65 140U-M6D3-D40450 450 50/50 140U-M5D3-D45 70/65 140U-M6D3-D45500 500 50/50 140U-M5D3-D50 70/65 140U-M6D3-D50600 600 50/50 140U-M5D3-D60 70/65 140U-M6D3-D60700 700 50/50 140U-M5D3-D70 70/65 140U-M6D3-D70800 800 50/50 140U-M5D3-D80 70/65 140U-M6D3-D80
Rated Current In [A] Thermal TripIr = 0.5…1.0 x In
Protection Type 400/480V[kA] Cat. No. 400/480V
[kA] Cat. No.
800 200…800 ➊LS 50/50 140U-M5L3-D80 70/65 140U-M6L3-D80LSI 50/50 140U-M5H3-D80 70/65 140U-M6H3-D80LSG 50/50 140U-M5G3-D80 70/65 140U-M6G3-D80
Rated CurrentIn [A]
Magnetic TripIm = 10 x In
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz) [kA] Cat. No.Icu /Ics [kA]
220…240V 380…415V 500V 690V 240V 480V 600V800 8000 100 100 70 70 70 50 25 13 100 65 35 140U-M6S3-D80
• UL 489• CSA 22.2, No. 5• IEC 60947-2• CE• KEMA-KEUR
• Terminal box lugs must be ordered separately. See page 59
Bulletin 140UMolded Case Circuit Breakers
58
Accessories — 800 A, M-Frame
Internal Control Modules — Field Installed
Internal Control Modules — Factory Installed
➊ For additional voltages, consult your local Allen-Bradley distributor.
Description Mounting Location Diagram Cat. No.
Auxiliary Contact (AX)• Electrically indicates “ON/
OFF” status of breakers
(1) 1a-1b 140U-M-EA1
(2) 1a-1b 140U-M-EA2
Alarm Contact (AL)• Electrically indicates when
the breaker is in the “TRIPPED” state
(1) 1M (make)- 1B (break) 140U-M-ER1
\
Auxiliary/Alarm Contact (AX/AL) Combination• Combination of auxiliary
contact and alarm contact
(1) 1a-1b(1) 1M (make)-
1B (break)140U-M-EA1R1
Shunt Trip (SNT)• Provides remote tripping of
the circuit breaker• Undervoltage trip not
available when shunt trip is used
12…24V, 50/60/DC 140U-M-SNJ
110…240V AC, 110…125V DC 140U-M-SND
380…440V AC, 220…250V DC 140U-M-SNN
480…600V, 50/60 Hz 140U-M-SNB
Undervoltage Release (UVT)• Automatically trips breaker
when voltage falls between preset value, 35…70%
• Shunt trip is not available when undervoltage release is used
24V AC,50/60 Hz 140U-M-UJ
110…127V AC,50/60 Hz 140U-M-UD
208…240V AC,50/60 Hz 140U-M-UA
380…500V AC, 50/60 Hz 140U-M-UB
Auxiliary and Alarm Contacts Suffix Shunt TripCombinations Suffix Undervoltage Release
Combinations Suffix
(1) AX - A (1) SNT only - P⊗ (1) UVT only - G⊗(2) AX - B (1) AX + (1) SNT - Q⊗ (1) AX + (1) UVT - H⊗(1) AL - D (2) AX + (1) SNT - R⊗ (2) AX + (1) UVT - J⊗
(1) AX + (1) AL - F (1) AX + (1) AL + (1) SNT - T⊗ (1) AX + (1) AL + (1) UVT - L⊗(1) AL + (1) SNT - V⊗ (1) AL + (1) UVT - N⊗
⊗ Standard Voltage Suffix Codes ➊ ⊗ Standard Voltage Suffix Codes ➊Voltage [V] 12…24 110…240 380…440 480…600 Voltage [V] 24 110…127 208…240 380…480
AC,50/60 Hz J D N B AC,
50/60 Hz J D A B
Voltage [V] 12…24 110…125 220…250 — Voltage [V] — — — —DC J D N — DC — — — —
Left AND Right side
1b
1c
1a
I >
AX
ON
1b
1c
1a
OFF
1b
1c
1a
TRIP
Right side ONLY
I >
ON
B
1c
M
OFF TRIP
AL B
1c
M B
1c
M
Right side ONLY
1b
1c
1a
I >
AX
ON
B
1c
M
OFF TRIP
AL
1b
1c
1a
B
1c
M
1b
1c
1a
B
1c
M
Left side ONLY
S1
I >
SNT
S2
Left side ONLY
U1
I >
UVT
U2
U >
(1) Shunt Trip (SNT)or
(1) Undervoltage Release (UVT)
(1) Auxiliary contact (AX)or
(2) Auxiliary contacts (AX)or
(1) Alarm contact (AL)or
(1) Alarm contact (AL) + Auxiliary contact (AX)
Mounting LocationLeft side only Right side only
59
Bulletin 140UMolded Case Circuit Breakers
Accessories — 800 A, M-Frame, Continued
External Accessories
Description Cat. No.
Flex-Cable Operating Mechanism
Non-Metallic — Type 1/3/12/4/4X Flange-Mount Operating Handle
4 ft. (1.3 m) Cable 140U-M-FCX04
6 ft. (1.8 m) Cable 140U-M-FCX06
10 ft. (3.0 m) Cable 140U-M-FCX10
Stainless Steel — Type 4/4X Flange-Mount Operating Handle
4 ft. (1.3 m) Cable 140U-M-FSX04
6 ft. (1.8 m) Cable 140U-M-FSX06
10 ft. (3.0 m) Cable 140U-M-FSX10
Rotary, Variable-Depth Operating Mechanism
Rotary Handle — Type 1/1212 in. (305 mm) operating rod
Black Handle 140U-M-RM12B
Red/Yellow Handle 140U-M-RM12R
Terminal Lugs
Copper lugCopper wire only(3) 3/0…300MCM(3) 95…135 mm2
Qty: 1 140U-M-TLC3
Aluminum lugAluminum or Copper wire
(3) 3/0…400MCM(3) 95…185 mm2
Qty: 1 140U-M-TLA3
Phase Barriers Provides additional phase clearance when special connections are required Qty: 2 140U-M-PB
Padlock Kit Padlocking HaspLock-OFF only — 140U-M-PL
Operating Handle Extension Provides handle extension for ease of operation Qty: 1 140U-M-OHE
Bulletin 140UMolded Case Circuit Breakers
60
Approximate Dimensions — 800 A, M-Frame
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
HandlePivot
1.375(34.93)
2.750(69.85)
2.750(69.85)
5.500(139.70)
4.250(107.95)
8.250(209.55)
.375 (9.53) Dia. 4-Holes for .312 (7.92) -16 (406.40) x 1.75 (44.45) Large Mounting Screws.
16.000(406.40)
8.302(210.87)
6.052(153.72)
14.750(374.65)
7.677(195.00)
11.500(292.10)
.500 (12.70) - 13 TapThru.
Line End
Load End
CL
On/I On/I
Off/O Off/O
1.874(47.60)
3.250(82.55)
1.625(41.28)
1.625(41.28)
.813(20.65)
.547(13.89)
.531(13.49)
.500(12.70)
2.531(64.29)
4.062(103.17)
4.375(111.13)
On14.7˚
Off19.2˚
Reset24.2˚
Tripped0.2˚
.500(12.70)
1.411(35.84)Max.
HandlePivot
LC
.415(10.54)
Dim.B
Dim.A
2.018(51.26)
Breaker Status Dimension A Dimension B
On 8.72(221.49)
9.17(232.92)
Off 6.72(170.69)
7.14(181.36)
Tripped 7.86(199.64)
8.30(210.82)
Reset 6.44(163.58)
6.84(173.74)
61
Bulletin 140UMolded Case Circuit Breakers
Product Selection — 1200 A, N-Frame
Assembled Circuit Breakers, Electronic Trip Units
➊ Select proper rating plug to cover thermal trip requirement.
Rating Plugs
Molded Case Switch — UL 1087
Rated Current
In [A]
Adjustment Range Ir [A]Protection
Type
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz) [kA] Cat. No.Thermal Trip
Ir = 0.5…1.0 x In
Magnetic Trip Im = 2…8 x In
Icu /Ics [kA]220…240V 380…415V 500V 690V 240V 480V 600V
1200 600…1200 ➊ 1200…10,600 LS 85 85 50 50 40 20 20 10 65 50 25 140U-N5L3-E12
1200 600…1200 ➊ 1200…10,600LS 100 100 70 50 50 25 25 13 100 65 35 140U-N6L3-E12LSI 100 100 70 50 50 25 25 13 100 65 35 140U-N6H3-E12LSG 100 100 70 50 50 25 25 13 100 65 35 140U-N6G3-E12
1200 600…1200 ➊ 1200…10,600LS 200 100 100 50 65 33 35 18 200 100 50 140U-N0L3-E12LSI 200 100 100 50 65 33 35 18 200 100 50 140U-N0H3-E12LSG 200 100 100 50 65 33 35 18 200 100 50 140U-N0G3-E12
Rated CurrentIn [A] Cat. No.
Rated CurrentIn [A] Cat. No.
600 140U-NRP3-D60 900 140U-NRP3-D90700 140U-NRP3-D70 1000 140U-NRP3-E10800 140U-NRP3-D80 1200 140U-NRP3-E12
Rated CurrentIn [A]
Magnetic Trip 10 x In
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz) [kA] Cat. No.Icu /Ics [kA]
220…240V 380…415V 500V 690V 240V 480V 600V1200 12,000 100 100 70 50 50 25 25 13 100 65 35 140U-N6S3-E12
• UL 489• CSA 22.2, No. 5• IEC 60947-2• CE• KEMA-KEUR
• Terminal box lugs must be ordered separately. See page 63
Bulletin 140UMolded Case Circuit Breakers
62
Accessories — 1200 A, N-Frame
Internal Control Modules — Field Installed
Internal Control Modules — Factory Installed
➊ For additional voltages, consult your local Allen-Bradley distributor.
Description Mounting Location Diagram Cat. No.
Auxiliary Contact (AX)• Electrically indicates “ON/
OFF” status of breakers
(1) 1a-1b 140U-N-EA1
(2) 1a-1b 140U-N-EA2
Alarm Contact (AL)• Electrically indicates when
the breaker is in the “TRIPPED” state
(1) 1M (make)- 1B (break) 140U-N-ER1
Auxiliary/Alarm Contact (AX/AL) Combination• Combination of auxiliary
contact and alarm contact
(1) 1a-1b(1) 1M (make)-
1B (break)140U-N-EA1R1
Shunt Trip (SNT)• Provides remote tripping of
the circuit breaker• Undervoltage trip not
available when shunt trip is used
12…24V, 50/60/DC 140U-N-SNJ
110…240V AC, 110…125V DC 140U-N-SND
380…440V AC, 220…250V DC 140U-N-SNN
480…600V, 50/60 Hz 140U-N-SNB
Undervoltage Release (UVT)• Automatically trips breaker
when voltage falls between preset value, 35…70%
• Shunt trip is not available when undervoltage release is used
24V AC,50/60 Hz 140U-N-UJ
110…127V AC, 50/60 Hz 140U-N-UD
208…240V AC, 50/60 Hz 140U-N-UA
380…500V AC, 50/60 Hz 140U-N-UB
Auxiliary and Alarm Contacts Suffix Shunt TripCombinations Suffix Undervoltage Release
Combinations Suffix
(1) AX - A (1) SNT only - P⊗ (1) UVT only - G⊗(2) AX - B (1) AX + (1) SNT - Q⊗ (1) AX + (1) UVT - H⊗(1) AL - D (2) AX + (1) SNT - R⊗ (2) AX + (1) UVT - J⊗
(1) AX/ (1) AL - F (1) AX + (1) AL + (1) SNT - T⊗ (1) AX + (1) AL + (1) UVT - L⊗(1) AL + (1) SNT - V⊗ (1) AL + (1) UVT - N⊗
⊗ Standard Voltage Suffix Codes ➊ ⊗ Standard Voltage Suffix Codes ➊Voltage [V] 12…24 110…240 380…440 480…600 Voltage [V] 24 110…127 208…240 380…480
AC,50/60 Hz J D N B AC,
50/60 Hz J D A B
Voltage [V] 12…24 110…125 220…250 — Voltage [V] — — — —DC J D N — DC — — — —
Left AND Right side
1b
1c
1a
I >
AX
ON
1b
1c
1a
OFF
1b
1c
1a
TRIP
Right side ONLY
I >
ON
B
1c
M
OFF TRIP
AL B
1c
M B
1c
M
Right side ONLY
1b
1c
1a
I >
AX
ON
B
1c
M
OFF TRIP
AL
1b
1c
1a
B
1c
M
1b
1c
1a
B
1c
M
Left side ONLY
S1
I >
SNT
S2
Left side ONLY
U1
I >
UVT
U2
U >
(1) Shunt Trip (SNT)or
(1) Undervoltage Release (UVT)
(1) Auxiliary contact (AX)or
(2) Auxiliary contacts (AX)or
(1) Alarm contact (AL)or
(1) Alarm contact (AL) + Auxiliary contact (AX)
Mounting LocationLeft side only Right side only
63
Bulletin 140UMolded Case Circuit Breakers
Accessories — 1200 A, N-Frame, Continued
External Accessories
Description Cat. No.
Flex-Cable Operating Mechanism Non-Metallic — Type 1/3/12/4/4X Flange-Mount Operating Handle
4 ft. (1.3 m) Cable 140U-N-FCX04
6 ft. (1.8 m) Cable 140U-N-FCX06
10 ft. (3.0 m) Cable 140U-N-FCX10
Rotary, Variable-Depth Operating Mechanism
Rotary Handle — Type 1/1212 in. (305 mm) operating rod Black Handle 140U-N-RM12B
Phase Barriers Provides additional phase clearance when special connections are required Qty: 2 140U-N-PB
Padlock Kit Padlocking HaspLock-OFF only Qty: 1 140U-N-PL
Terminal Lugs
Copper lugCopper wire only(4) 3/0…400MCM(4) 95…185 mm2
Qty: 1 140U-N-TLC4
Aluminum lugAluminum or Copper wire
(4) 4/0…500MCM(4) 120…300 mm2
Qty:1 140U-N-TLA4
Bulletin 140UMolded Case Circuit Breakers
64
Approximate Dimensions — 1200 A, N-Frame
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Load End
Line End
ON/I
OFF/O
1.062(26.987).531(13.481)
.344(8.738) Dia. Mounting Holes
.703(17.856) Dia. C'Bore4.453(113.106) Deep from Top.594(15.088) Dia C'Bore.359(9.119) Deep from Bottom
.500-13 (12 X 1.75) Tap12-Holes
.250R(6.350)R
.062R(1.575)R
.094R(2.388)R
3.236(82.194)
7.00
0(1
77.7
74)
115.
00(2
92.0
75)
8.62
5(2
19.0
75)
14.7
50(3
74.6
50)
9.25
0(2
34.9
50)
16.0
00(4
06.4
01) .946
(24.022)
.297(7.544)
.750(19.050)
.375(9.525)
1.500(38.100)
Contact Position IndicatorRed-I/ONGreen-O/OFFWhite-TRIPPED
Removable TerminalCover Must Be inPlace While in Service
1.375(34.925)
3.187(80.950)
8.250(209.550)
4.124(104.750)
3.808(96.723)
2.798(71.057)
2.511(63.786)
.312R(7.925)R
11.431(290.348)
Removable T erminalCover Must Be inPlace While in Service
.147 (3.734) Dia. Hole
.500 (12.70) Deep toAccept a #8ThreadCutting Screw6-Places
6.375(161.925)
CL Handle
.188R(4.762)R
1.157(29.388)
.532(13.513)
.062(1.575)
Trough forAttachment Lead
.125 X .750(3.175 X 19.050)Slots forAttachment Leads
2.982(75.743)
1.034(33.281)
.353(6.331)
.375(9.525)
21û±2ûON
3.850R
HandlePivot
0û±2ûTRIPPED
15û±2ûRESET
.062(1.575)
.532(13.513)
1.095(27.813)
3.344(84.938)
5.188(131.769)
5.248(133.293)
5.500(139.687)
6.000(152.400)
7.132(181.146)
AB
13û±2û OFF
3.375(85.725)
2.750 Ref.(69.850) Ref.
2.000(50.800)2.000
(50.800)
1.688(42.863)
1.000(25.400)
1.562(39.687)
.781(19.844)
For 2-Pole Breaker Omit CurrentCarrying Parts from Center Pole
3.906(99.187)
4.875(123.799)
.062(1.588)
R
.062(1.575)
.062(1.588)
R
2.344(59.541)
2.750(69.850)
1.500 Ref(38.100) Ref
C L P
ush
To T
rip
3.819(96.723)
2.493(63.792)
6.375 Ref(161.925) Ref
DimensionsBreaker Status A B
On 7.90 (200.66) 8.30 (210.82)
Tripped 6.50 (165.10) 6.90 (175.26)
Off 5.70 (144.78) 6.10 (154.94)
Reset 5.60 (142.24) 6.00 (152.40)
Handle Forces (At Handle C)On 130 lbs. (58.97 kgs.)
Off 105 lbs. (47.63 kgs.)
Reset 160 lbs. (72.57 kgs.)
L
65
Bulletin 100-MIEC Miniature Contactors
Overview/Product Selection
Your order must include: cat. no. of the miniature contactor specified with coil voltage code and, if required, cat. no. of any accessories
Mini-Contactors
Non-Reversing Mini-Contactors 3 N.O. Power Poles/Auxiliary Contact
Reversing Mini-Contactors 3 N.O. Power Poles/Auxiliary Contact
⊗ Coil Voltage CodeThe cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no. Example: Cat. No. 100-M05N⊗ 3 becomes Cat. No. 100-M05NKD3. For other voltages, consult your local Allen-Bradley distributor.
➊ Contactors may be ordered in quantities of 1. Add the letter S to the end of the cat. no. (Example: 100-M09ND3S).➋ Not available with DC coil.
Bulletin 100-M Miniature Contactors• Compact Size• Uniform Panel Mounting Dimensions• Full Voltage Non-Reversing and Reversing Contactors• 5, 9, and 12 A Contactors• Compatible with Bulletin 193-E solid-state and 193-M bimetal Overload Relays
Allen-Bradley miniature contactors are designed for commercial and light industrial applications where panel space is at a premium. These miniature devices, while 45 mm wide, are shallower and have less panel depth requirements than standard IEC contactors.
These mini-contactors are designed with flexibility in mind. They are available in several contact configurations, offer 2- and 4-pole adder decks, and a wide variety of contact configurations. Additionally, the contactor is available with both AC or DC operating coils.
Product Selection.......... 65Accessories ................... 84Specifications................ 94Approximate Dimensions....................130
Conformity to StandardsIEC 60947-4CSA C22.2 No. 14UL 508
ApprovalsCE Marked (Per EU Low Voltage Directive 73/23/EEC 93/68/EEC)CSA Certified (File No. LR1234)UL Listed (File No. E3125;Guide No. NLDX 2nd NVYT)
Ie[A]
Ratings for switching AC motors Auxiliary Contact Configuration
Pkg. Qty. ➊ Cat. No.3∅ AC-3 kW Ratings (50 Hz) Hp (60 Hz)
AC-3 AC-1 220V/240V 400V/415V 500V1∅ 3∅
115V 230V 200V 230V 460V 575V N.O. N.C.
5.3 20 1.5 2.2 2.2 1/2 1 1-1/2 1-1/2 3 31 0 10 100-M05N⊗ 30 1 10 100-M05N⊗ 31
9 20 3 4 4 1/2 1-1/2 2 2 5 51 0 10 100-M09N⊗ 30 1 10 100-M09N⊗ 31
12 20 3 5.5 4 1/2 2 3 3 7-1/2 101 0 10 100-M12N⊗ 30 1 10 100-M12N⊗ 31
Ie[A]
Ratings for switching AC motors Auxiliary Contact Configuration
Pkg. Qty. Cat. No. ➋AC-3 kW Ratings (50 Hz) Hp (60 Hz)
AC-3 AC-1 220V/240V 400V/415V 500V1∅ 3∅
115V 230V 200V 230V 460V 575V N.O. N.C.
5.3 20 1.5 2.2 2.2 1/2 1 1-1/2 1-1/2 3 31 0 1 104-M05N⊗ 30 1 1 104-M05N⊗ 31
9 20 3 4 4 1/2 1-1/2 2 2 5 51 0 1 104-M09N⊗ 30 1 1 104-M09N⊗ 31
12 20 3 5.5 4 1/2 2 3 3 7-1/2 101 0 1 104-M12N⊗ 30 1 1 104-M12N⊗ 31
Voltage 24V 48V 110V 110…120V 220…230V 230…240V 380V50 Hz KD KH D — A — KK60 Hz KD KH — D — A KK
DC Z24 — — — — — —DC with integrated diode ZD24 — — — — — —
Bulletin 100-C/104-CIEC Contactors
66
Overview/Product Selection
Your order must include: cat. no. of the contactor specified with coil voltage code and, if required, cat. no. of any accessories and/or replacement coils.
Product Selection3-Pole AC- and DC-Operated Contactors (with or without auxiliary contacts)• 3 Main Contacts
Bulletin 100-C/104-C IEC Contactors• Compact Sizes from 4…45 kW/5…60 Hp (9…85 A)• AC and DC Coil Control• Common Accessories for All Contactor Sizes• Front and Side Mounting of Auxiliary Contacts• Electronic and Pneumatic Timing Modules• Space-Saving Coil-Mounted Control Modules• Reversible Coil Terminations (Line or Load Side)• All Devices Can Be Attached to 35 mm DIN Mounting Rail • Environmentally Friendly Materials
The Bulletin 100-C/104-C contactor family, along with a wide range of common accessories and Bulletin 193 solid-state overload relays, provides the most compact and flexible starter component system available.
Product Selection3-Pole Contactors .......... 664-Pole Contactors .......... 67Reversing Contactors .... 68
Accessories.......................85Specifications ................... 94Approximate Dimensions .....................131
Conformity to StandardsEN/IEC 60947-4-1IEC 947 Type “2” CoordinationCSA C22.2 No. 14UL 508
ApprovalsCE Marked CSA Certified (File No. LR13908)UL Listed (File No. E3125;Guide No. NLDX)
Ie[A]
Ratings for Switching AC Motors - AC-2, AC-3, AC-4 Aux. Contacts
Cat. No.3∅ kW (50 Hz) Hp (60 Hz)
AC-3 AC-1 230V 400V/415V 500V 690V1∅ 3∅
115V 230V 200V 230V 460V 575V N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/21 0 100-C09⊗ 100 1 100-C09⊗ 01
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 101 0 100-C12⊗ 100 1 100-C12⊗ 01
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 151 0 100-C16⊗ 100 1 100-C16⊗ 01
23 32 7.5 11 13 10 2 3 5 7-1/2 15 151 0 100-C23⊗ 100 1 100-C23⊗ 01
30 65 10 15 15 15 2 5 7-1/2 10 20 250 0 100-C30⊗ 001 0 100-C30⊗ 100 1 100-C30⊗ 01
37 65 11 18.5/20 20 18.5 3 5 10 10 25 300 0 100-C37⊗ 001 0 100-C37⊗ 100 1 100-C37⊗ 01
43 85 13 22 25 22 3 7-1/2 10 15 30 300 0 100-C43⊗ 001 0 100-C43⊗ 100 1 100-C43⊗ 01
60 100 18.5 32 37 32 5 10 15 20 40 500 0 100-C60⊗ 001 0 100-C60⊗ 100 1 100-C60⊗ 01
72 100 22 40 45 40 5 15 20 25 50 600 0 100-C72⊗ 001 0 100-C72⊗ 100 1 100-C72⊗ 01
85 100 25 45 55 45 7-1/2 15 25 30 60 600 0 100-C85⊗ 001 0 100-C85⊗ 100 1 100-C85⊗ 01
67
Bulletin 100-C/104-CIEC Contactors
Product Selection, Continued
⊗ Coil Voltage Code and Terminal PositionThe Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60Hz: Cat. No. 100-C09⊗ 10 becomes Cat. No.100-C09D10.
Coil Terminal Position• All contactors are delivered with the coil terminals located on the line side.• For load side coil terminations, insert a “U” prior to the coil voltage code. Ordering example:
Cat. No. 100-C09UD10.
4-Pole AC- and DC-Operated Contactors• 4 Main Contacts (without auxiliary contacts)
⊗ Coil Voltage CodeThe Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: 120V, 60 Hz: Cat. No. 100-C09⊗ 400 becomes Cat. No. 100-C09D400.
➊ Three-phase ratings only apply to contactors with at least three N.O. power poles.
12 24 32 36 42 48 100 100-110 110 120 127 200 200-
220 208 208-240
220-230 230 230-
240 240 277 347 380 380-400 400 400-
415 440 480 500 550 600
50 R K V W X Y KP — D P S KG L — — F — VA T — — — N — G B — M C —60 Q J — V — X — KP — D — — KG H L — — — A T I E — — — N B — — C
50/60 — KJ — — — KY KP — KD — — KG KL — — KL KF — KA — — — — KN — KB — — — —
DC Voltages [V] 9 12 24 36 48 60 64 72 80 110 115 125 220 230 250
100-C09…C43Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode — — DJ — — — — — — — — — — — —100-C60…C85 with Integrated Diode DR DQ DJ DW DY DZ DB DG DE DD DP DS DA DF DT
Ie[A]
Ratings for Switching AC MotorsContact Configuration,
Main PoleCat. No.
AC-2, AC-3, AC-43∅ kW (50 Hz) ➊ Hp (60 Hz)
AC-3 AC-1 230V 400V/415V 500V 690V1 ∅ 3 ∅ ➊
115V 230V 200V 230V 460V 575V N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/24 0 100-C09⊗ 4003 1 100-C09⊗ 3002 2 100-C09⊗ 200
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 104 0 100-C12⊗ 4003 1 100-C12⊗ 3002 2 100-C12⊗ 200
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 154 0 100-C16⊗ 4003 1 100-C16⊗ 3002 2 100-C16⊗ 200
23 32 7.5 11 13 10 2 3 5 7-1/2 15 154 0 100-C23⊗ 4003 1 100-C23⊗ 3002 2 100-C23⊗ 200
37 7511 18.5/20 20 18.5 3 5 10 10 25 30
4 0 100-C40⊗ 40037 65 2 2 100-C40⊗ 20085 130
25 45 55 45 7-1/2 15 25 30 60 604 0 100-C90⊗ 400
85 100 2 2 100-C90⊗ 200
12 24 32 36 42 48 100 100-110 110 120 127 200 200-
220 208 208-240
220-230 230 230-
240 240 277 347 380 380-400 400 400-
415 440 480 500 550 600
50 Hz R K V W X Y KP — D P S KG L — — F — VA T — — — N — G B — M C —60 Hz Q J — V — X — KP — D — — KG H L — — — A T I E — — — N B — — C
50/60 Hz — KJ — — — KY KP — KD — — KG KL — — KL KF — KA — — — — KN — KB — — — —
DC Voltages [V] 9 12 24 36 48 60 64 72 80 110 115 125 220 230 250
100-C09…C40Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode — — DJ — — — — — — — — — — — —100-C90 with Integrated Diode DR DQ DJ DW DY DZ DB DG DE DD DP DS DA DF DT
V
Hz
Cat. No. 100-C09⊗ 10
Line Side
Cat. No.100-C09U⊗ 10
Load Side
Cat. No. 100-C23D400
VHz
Bulletin 100-C/104-CIEC Contactors
68
Product Selection, Continued
Reversing AC- and DC-Operated Contactors• Includes Mechanical/Electrical Interlock• Includes Reversing Power Wiring
➊ The N.C. auxiliary contact is supplied as part of the mechanical/electrical interlock.
⊗ Coil Voltage Code The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V 60 Hz: Cat. No. 104-C09⊗ 22 becomes Cat. No. 104-C09D22.
Ie[A]
Ratings for Switching AC MotorsAuxiliary Contacts
Installed per ContactorCat. No.
AC-2, AC-3, AC-43∅ kW (50 Hz) Hp (60 Hz)
AC-3 AC-1 230V 400V/ 415V 500V 690V1∅ 3∅
115V 230V 200V 230V 460V 575V N.O. N.C. ➊9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 1 1 104-C09⊗ 2212 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 1 1 104-C12⊗ 2216 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 1 1 104-C16⊗ 2223 32 7.5 11 13 10 2 3 5 7-1/2 15 15 1 1 104-C23⊗ 22
30 65 10 15 15 15 2 5 7-1/2 10 20 250 1 104-C30⊗ 021 1 104-C30⊗ 22
37 65 11 18.5/20 20 18.5 3 5 10 10 25 300 1 104-C37⊗ 021 1 104-C37⊗ 22
43 85 13 22 25 22 3 7.5 10 15 30 300 1 104-C43⊗ 021 1 104-C43⊗ 22
60 100 18.5 32 37 32 5 10 15 20 40 500 1 104-C60⊗ 021 1 104-C60⊗ 22
72 100 22 40 45 40 5 15 20 25 50 600 1 104-C72⊗ 021 1 104-C72⊗ 22
85 100 25 45 55 45 7-1/2 15 25 30 60 600 1 104-C85⊗ 021 1 104-C85⊗ 22
12 24 32 36 42 48 100 100-110 110 120 127 200 200-
220 208 208-240
220-230 230 230-
240 240 277 347 380 380-400 400 400-
415 440 480 500 550 600
50 R K V W X Y KP — D P S KG L — — F — VA T — — — N — G B — M C —60 Q J — V — X — KP — D — — KG H L — — — A T I E — — — N B — — C
50/60 — KJ — — — KY KP — KD — — KG KL — — KL KF — KA — — — — KN — KB — — — —
DC Voltages 9 12 24 36 48 60 64 72 80 110 115 125 220 230 250
104-C09…C43Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode — — DJ — — — — — — — — — — — —104-C60…C85 with Integrated Diode DR DQ DJ DW DY DZ DB DG DE DD DP DS DA DF DT
Cat. No. 104-C09D22Cat. No. 104-C30ZJ22 Cat. No. 104-C85D22
V
Hz
69
Bulletin 100-DIEC Contactors
Overview/Product Selection
Bulletin 100-D IEC Contactors• 45…220 kW @500V• 60…600 Hp @460V• 75…700 Hp @575V• Electronic and Conventional Coils
AC & DCIntegrated PLC InterfaceLow Power Pick-Up & Hold-InWide Voltage Ranges
• Complete Range of Accessories• Environmentally-Friendly• Compact Dimensions
The Bulletin 100-D/104-D contactor family, along with a wide range of common accessories and Bulletin 193 electronic overload relays, provides the most compact and flexible starter component system available.
Table of ContentsProduct Selection ................70Accessories .........................90Specifications ......................94Approximate Dimensions ....................... 133
Conformity to StandardsIEC 60947-4-1IEC 947 Type “2” CoordinationCSA C22.2 No. 14UL 508
ApprovalsCE Marked CSA CertifiedUL Listed
Bulletin 100-DIEC Contactors
70
Product Selection
⊗ Voltage Suffix Codes for AC Control
➊ Conventional coils.➋ Electronic coils. ➌ Signal voltage of the Cat. No. 100-D… electronic interface: Nominal Ue: 24V DC/Ie: 15 mA
Pick-up Voltage: 13.0V DC…30.2V DCDrop-out Voltage: -3.0V DC…+5.0V DC
Ie [A] Switching of 3-phase motors — AC-2, AC-3 Auxiliary contactsNon-Reversing
Contactor Cat. No.
Reversing Contactor Cat. No.
60°C 40°C kW (50 Hz) Hp (60 Hz) N.O. N.C.
AC-3 AC-1 230V 400V 415V 500V 690V 1000V 200V 230V 460V 575V
95 160 25 50 50 55 80 45 25 30 60 750 0 100-D95⊗ 00 —1 1 100-D95⊗ 11 —2 4 — 104-D95⊗ 24
110 160 32 55 55 63 100 55 40 40 75 1000 0 100-D110⊗ 00 —1 1 100-D110⊗ 11 —2 4 — 104-D110⊗ 24
140 250 45 75 7580 ➊ 110 ➊
75 40 50 100 1250 0 100-D140⊗ 00 —
90 ➋ 132 ➋1 1 100-D140⊗ 11 —2 4 — 104-D140⊗ 24
180 250 55 90 10090 ➊ 132 ➊
90 50 60 150 1500 0 100-D180⊗ 00 —
110 ➋ 160 ➋1 1 100-D180⊗ 11 —2 4 — 104-D180⊗ 24
210 350 63 110 110 150 200 110 60 75 150 2000 0 100-D210⊗ 00 —1 1 100-D210⊗ 11 —2 4 — 104-D210⊗ 24
250 350 80 132 150 160 250 133 75 100 200 2500 0 100-D250⊗ 00 —1 1 100-D250⊗ 11 —2 4 — 104-D250⊗ 24
300 450 90 160 160 200 300 163 100 125 250 3000 0 100-D300⊗ 00 —1 1 100-D300⊗ 11 —2 4 — 104-D300⊗ 24
420 500 132 220 250 300 425 225 150 175 350 4000 0 100-D420⊗ 00 —1 1 100-D420⊗ 11 —2 4 — 104-D420⊗ 24
630 800 200 355 355 450 500 — 200 250 500 6000 0 100-D630⊗ 00 —1 1 100-D630⊗ 11 —2 4 — 104-D630⊗ 24
860 1000 250 500 500 560 600 — 250 300 600 7000 0 100-D860⊗ 00 —1 1 100-D860⊗ 11 —2 4 — 104-D860⊗ 24
Conventional Coil V 24 48 100 110 120 200 208 220…230 230 240 277 380…
400 415 440 480 500 550 600
100-D95…100-D18050 Hz K Y — D — — — A — T — N B G — M C —
60 Hz J X — — D — H — — A T — — N B — — C
100-D95…100-D110 50/60 Hz KJ — KP KN — KG — — KF KA — — — — — — — —
Electronic Coilw/ EI Interface ➌ V 24 42…
64 100 110…130 200 208…
277380…415
440…480 500 600
100-D95…100-D250 50/60 Hz EJ EY EP ED EG EA EN EN EN —
100-D300…100-D420 50/60 Hz — EY EP ED EG EA EN EN EN —
100-D630…100-D860 50/60 Hz — — EP ED EG EA EN EB EM EC
100-D420…
3-pole AC Contactors• Conventional and Electronic AC Coils• 3 Main Contacts• Non-Reversing or Reversing
71
Bulletin 100-DIEC Contactors
Product Selection, Continued
⊗ Voltage Suffix Codes for DC Control
➊ For conventional DC coil only. The pickup winding must be interconnected with the N.C. late-break auxiliary contact(s).➋ Conventional coils.➌ Electronic coils.➍ Signal voltage of the Cat. No. 100-D… electronic interface:Ue: 24V DC/Ie: 15 mA
Pick-Up Voltage: 13.0V DC…30.2V DCDrop-Out Voltage: -3.0V DC…+5.0V DC
Ie [A] Switching of 3-phase motors — AC-2, AC-3 Auxiliary contactsNon-reversing
Contactor Cat. No.
Reversing Contactor Cat. No.
60°C 40°C kW (50 Hz) Hp (60 Hz) N.O. N.C.
AC-3 AC-1 230V 400V 415V 500V 690V 1000V 200V 230V 460V 575V
95 160 25 50 50 55 80 45 25 30 60 75
0 0 100-D95⊗ 00 —1 1 100-D95⊗ 11 —2 1/1L 100-D95⊗ 22L ➊ —2 4 — 104-D95⊗ 242 2/2L — 104-D95⊗ 24L ➊
110 160 32 55 55 63 100 55 40 40 75 100
0 0 100-D110⊗ 00 —1 1 100-D110⊗ 11 —2 1/1L 100-D110⊗ 22L ➊ —2 4 — 104-D110⊗ 242 2/2L — 104-D110⊗ 24L ➊
140 250 45 75 75
80 ➋ 110 ➋
75 40 50 100 125
0 0 100-D140⊗ 00 —1 1 100-D140⊗ 11 —
90 ➌ 132 ➌2 1/1L 100-D140⊗ 22L ➊ —2 4 — 104-D140⊗ 242 2/2L — 104-D140⊗ 24L ➊
180 250 55 90 10090 ➊ 132 ➊
90 50 60 150 1500 0 100-D180⊗ 00 —
110 ➋ 160 ➋1 1 100-D180⊗ 11 —2 4 — 104-D180⊗ 24
210 350 63 110 110 150 200 110 60 75 150 2000 0 100-D210⊗ 00 —1 1 100-D210⊗ 11 —2 4 — 104-D210⊗ 24
250 350 80 132 150 160 250 133 75 100 200 2500 0 100-D250⊗ 00 —1 1 100-D250⊗ 11 —2 4 — 104-D250⊗ 24
300 450 90 160 185 220 300 163 100 125 250 3000 0 100-D300⊗ 00 —1 1 100-D300⊗ 11 —2 4 — 104-D300⊗ 24
420 500 132 220 250 300 425 225 150 175 350 4000 0 100-D420⊗ 00 —1 1 100-D420⊗ 11 —2 4 — 104-D420⊗ 24
630 800 200 355 355 450 500 425 200 250 500 6000 0 100-D630⊗ 00 —1 1 100-D630⊗ 11 —2 4 — 104-D630⊗ 24
860 1000 250 500 500 560 600 425 250 300 600 7000 0 100-D860⊗ 00 —1 1 100-D860⊗ 11 —2 4 — 104-D860⊗ 24
Conventional Coil V 24 48 110 125 220
100-D95…100-D140 ➊ DC ZJ ZY ZD ZS ZA
Electronic Coil w/ EI Interface ➍ V 24 48…72 110…130 200…255
100-D95…100-D300 DC EZJ EZY EZD EZA
100-D420 DC — EZY EZD EZA
100-D630…860 DC — — ED EA
100-D180…
3-pole DC Contactors• Conventional and Electronic DC Coils• 3 Main Contacts• Non-Reversing or Reversing
100-D860…100-D420…
Bulletin 100-DIEC Contactors
72
Product Selection, Continued
Auxiliary contacts with sequence numbering
Cat. Nos. 100-D95…D860 — Electronic and Conventional AC Coils
Cat. Nos. 100-D95…D860 — Electronic DC Coils
Contactor cat. nos. 100-D95…D140 — Conventional DC coils
➊ With conventional DC control, the pickup winding must be interconnected with the N.C. late-breaking auxiliary contacts.
Contact ConfigurationAuxiliary contact configurations
Left-Side MountingFor Use With
Right-Side MountingN.O. N.C. Outside Cat. No. Inside Cat. No. Inside Cat. No. Outside Cat. No.
8 0 100-DS2-20 100-DS1-20100-D…00
100-DS1-20 100-DS2-20Sequence starts with… 7/8 3/4 1/2 5/6
7 1 100-DS2-20 100-DS1-20100-D…00
100-DS1-11 100-DS2-20Sequence starts with… 7/8 3/4 1/2 5/6
6 2 100-DS2-20 100-DS1-11100-D…00
100-DS1-11 100-DS2-20Sequence starts with… 7/8 3/4 1/2 5/6
5 3 100-DS2-20 100-DS1-11100-D…00
100-DS1-11 100-DS2-11Sequence starts with… 7/8 3/4 1/2 5/6
4 4 100-DS2-11 100-DS1-11100-D…00
100-DS1-11 100-DS2-11Sequence starts with… 7/8 3/4 1/2 5/6
Contact ConfigurationAuxiliary contact configurations
Left-Side MountingFor Use With
Right-Side MountingN.O. N.C. Outside Cat. No. Inside Cat. No. Inside Cat. No. Outside Cat. No.
8 0 — —100-D…11
— —Sequence starts with… — — — —
7 1 100-DS2-20 100-DS1-20100-D…11
100-DS1-11 100-DS2-20Sequence starts with… 7/8 3/4 1/2 5/6
6 2 100-DS2-20 100-DS1-11100-D…11
100-DS1-11 100-DS2-20Sequence starts with… 7/8 3/4 1/2 5/6
5 3 100-DS2-20 100-DS1-11100-D…11
100-DS1-11 100-DS2-11Sequence starts with… 7/8 3/4 1/2 5/6
4 4 100-DS2-11 100-DS1-11100-D…11
100-DS1-11 100-DS2-11Sequence starts with… 7/8 3/4 1/2 5/6
Contact ConfigurationAuxiliary contact configurations
Left-Side MountingFor Use With
Right-Side MountingN.O. N.C. Outside Cat. No. Inside Cat. No. Inside Cat. No. Outside Cat. No.
8 0 — —100-D…11
— —Sequence starts with… — — — —
7 1 100-DS2-20 100-DS1-20100-D…11
100-DS1-L11 ➊ 100-DS2-20Sequence starts with… 7/8 3/4 1/2 5/6
6 2 100-DS2-20 100-DS1-11100-D…11
100-DS1-L11 ➊ 100-DS2-20Sequence starts with… 7/8 3/4 1/2 5/6
5 3 100-DS2-20 100-DS1-11100-D…11
100-DS1-L11 ➊ 100-DS2-11Sequence starts with… 7/8 3/4 1/2 5/6
4 4 100-DS2-11 100-DS1-11100-D…11
100-DS1-L11 ➊ 100-DS2-11Sequence starts with… 7/8 3/4 1/2 5/6
Supplied withContactor
Supplied withContactor
73
Bulletin 100-GIEC Contactors
Overview/Product Selection
Your order must include: cat. no. of the contactor selected, coil voltage code, overload relay suffix code, and, if required, cat. no. of any accessories.
Product Selection
AC and DC Control
➊ 1 N.O. contact used in control circuit.➋ No UL/cUL
⊗ Coil Voltage Code
Bulletin 100-G IEC Contactors• 315…710 kW, 400V• 350…900 Hp, 460/575V• 3-Pole Contactors• 4th Add-On Neutral Switching Pole• AC and DC Control• Horizontal and Vertical Interlocking• Mechanical Latching• Meets IEC, CE, UL, and cUL Standards and Approvals
The Bulletin 100-G contactor product family provides reliable switching of motor loads up to 1200 A. A complete range of accessories including auxiliary contacts, mechanical latches, horizontal and vertical interlocks, and 4th add-on neutral switching poles provides maximum flexibility to meet a wide variety of application requirements.
Table of ContentsProduct Selection ................73Accessories
Control Modules ...............93Renewal Parts ................286
Specifications ....................112Dimensions ........................135
Conformity to StandardsEN/IEC 60947-4IEC 947 Type “2” CoordinationCSA C22.2 No. 14UL 508
ApprovalsCE Marked UL ListedcUL
AC-1 Switching of 3-phase motors — AC-2, AC-3 Auxiliary Contacts
Cat. No.Ie (A) kW (50 Hz) Hp (60 Hz)
40°C 230V 400V 500V 690V 200V 230V 460V 575V N.O. N.C.
760 179 312 407 570 150 150 350 350 2 2 100-G550⊗ 22
1000 228 414 518 657 200 250 500 500 2 2 100-G700⊗ 22
1100 280 509 636 730 250 300 600 600 2 2 100-G860⊗ 22
1200 326 592 756 897 — — — — 2 ➊ 2 100-G1000⊗ 12➋
1350 391 710 888 1043 450 450 900 900 2 ➊ 2 100-G1200⊗ 12
For Use With: 100…110V 110…120V 200…220V 220…240V 345…380V 380…415V 400…440V 440…480V
100-G550…100-G86050/60 Hz — KD — KF — KN — KB
DC KD — KF — KN — KB —
For Use With: 110…115V 110V 220…230V 220V 240V 380…400V 440V 480V
100-G1000…100-G120050/60 Hz KD — KF — KA KN KB KU
DC — ZD — ZA — — — —
Price Adder For Type Available Control Voltages No Surcharge
Special control voltages100-G550…100-G860 24…600V 50/60 Hz, 24…440V DC
>25 pieces100-G1000…100-G1200 48…600V 50/60 Hz, 48…440V DC
Bulletin 100QCapacitor-Switching Contactors
74
Overview/Product Selection
Your order must include: cat. no. of the contactor specified with coil voltage code and, if required, cat. no. of any accessories
Product SelectionFor Applications per IEC 60947-4 (AC-6b)
For Applications per UL/CSA
⊗ Coil Voltage CodeThe cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60 Hz: Cat. No. 100Q-C16⊗ 11 becomes Cat. No.100Q-C16D11.
.
Maximum Operational Rates
Bulletin 100Q Capacitor-Switching Contactors• Compact Sizes • Limits High Inrush Currents• AC and DC Coil Control• Reversible Coil Terminals• Panel or 35 mm DIN Rail Mounting• Environmentally Friendly Materials
The Bulletin 100Q Capacitor-Switching Contactors are designed for switching banks of capacitors. The unique design uses front-mounted resistor elements that limit the severely high inrush currents seen in these applications. This reduces stress to the contactors and the capacitors, as well as allowing a more compact and economical design without the use of air-core reactors.
Product Selection ........... 74Approximate Dimensions .....................136
Conformity to StandardsIEC 60947-4CSA C22.2 No. 14UL 508
ApprovalsCE MarkedCSA CertifiedUL Listed
Ratings for Switching Capacitor Banks @ 40°C1-Phase 50 Hz (kVar) 3-Phase 50 Hz (kVar) Aux. Contacts
Cat. No.230V 240V 400V 415V 500V 690V 230V 240V 400V 415V 500V 690V N.O. N.C.
5 5 8.5 9 10.5 15 8.5 8.5 15 15.5 18.5 251 1 100Q-C16⊗ 112 0 100Q-C16⊗ 20
8 8.5 14 14.5 17.5 24 14 14 25 25 30 401 1 100Q-C37⊗ 112 0 100Q-C37⊗ 20
Ratings for Switching Capacitor Banks @ 60° C1-Phase 50 Hz (kVar) 3-Phase 50 Hz (kVar) Aux. Contacts
Cat. No.230V 240V 400V 415V 500V 690V 230V 240V 400V 415V 500V 690V N.O. N.C.
5 5 8.5 9 10.5 15 8.5 8.5 15 15.5 18.5 251 1 100Q-C16⊗ 112 0 100Q-C16⊗2 0
7 7.5 12.5 13 16 22 12.5 13 21.5 22.5 27 37.51 1 100Q-C37⊗ 112 0 100Q-C37⊗2 0
Ratings for Switching Capacitor Banks1-Phase 50 Hz (kVar) 3-Phase 50 Hz (kVar) Aux. Contacts
Cat. No.115V 230V 200V 230V 460V 600V N.O. N.C.
2.2 4.5 6.5 7.5 15 18.51 1 100Q-C16⊗ 112 0 100Q-C16⊗2 0
3.6 7.5 11 12.5 20 251 1 100Q-C37⊗ 112 0 100Q-C37⊗2 0
12 24 32 36 42 48 100 100-110 110 120 127 200 200-
220 208 208-240
220-230 230 230-
240 240 277 347 380 380-400 400 400-
415 440 480 500 550 600
50Hz R K V W X Y KP — D P S KG L — — F — VA T — — — N — G B — M C —60Hz Q J — V — X — KP — D — — KG H L — — — A T I E — — — N B — — C
50/60 Hz — KJ — — — KY KP — KD — — KG KL — — KL KF — KA — — — — KN — KB — — — —
DC Voltages 9 12 24 36 48 60 64 72 80 110 115 125 220 230 250Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode — — DJ — — — — — — — — — — — —
100Q-C16 200 operations/hour
100Q-C37 100 operations/hour
Cat. No. 100Q-C37A11
V
Hz
Bulletin 100LElectrically Held Lighting Contactors
75
Overview/Product Selection
Your order must include: Cat. No. of the contactor specified with coil voltage code and, if required, Cat. No. of any accessories
Product Selection
Ratings
➊ These contactors do not include an auxiliary hold-in contact. If a hold-in contact is required it can be ordered by adding a suffix -90 to the Cat. No. and add
$17 to the list price of the contactor. Example: Cat. No. 100L-C20NJ4-90, price $271.
➋ 20A, 250V DC max. with 3 poles in series.
⊗ Coil Voltage CodeThe Cat. No. as listed is incomplete. To complete the Cat. No., select a coil voltage code from the chart below and insert into the Cat. No.Example: Cat. No. 100L-C20N⊗ 4 becomes Cat. No. 100L-C20NJ4. For other voltages, consult Allen-Bradley Sales Office.
Wiring Diagram
Bulletin 100L Electrically Held Lighting Contactors• Electrically Held• 20 A Rating• 4-, 8-, and 12-Pole Configurations• Open or Enclosed• CSA Certified, UL Listed
Bulletin 100 Lighting Contactors have been designed to control a variety of lighting loads. The product offering includes 4-, 8-, and 12-pole contactors with or without enclosures. The Bulletin 100 line of lighting contactors has been designed with a 20 A rating for all popular lighting loads and other non-motor applications including tungsten filament lighting loads, electric discharge (fluorescent) loads, electric furnaces, and electric water heaters. In addition these contactors have been designed to meet the requirements of both CSA and UL.
Product Selection ............75Wiring Diagram ................75Modifications...................276Approximate Dimensions .....................137
Conformity to StandardsEN/IEC 60947-4CSA C22.2 No. 14UL 508
ApprovalsCE MarkedCSA Certified (File No. LR1234)UL Listed (File No. E14843;Guide No. NRNT)
Type Number of Poles ➊ Cat. No.
Open4 100L-C20N⊗ 48 100L-C20N⊗ 8
12 100L-C20N⊗ 12
IP42 (Type 1)(with lift-off cover)
4 100L-C20A⊗ 48 100L-C20A⊗ 8
12 100L-C20A⊗ 12
IP66 (Type 3/4/12)(with hinged cover)
4 100L-C20F⊗ 48 100L-C20F⊗ 8
12 100L-C20F⊗ 12
Type of Load Max (A)Max AC Volts
Poles to Load ➋
1 for 1∅ 3 for 3∅
Tungsten20 277 480/27715 347 600/347
Ballast20 277 480/27715 347 600/347
General UseResistance Heating 30 600 600
Voltage 24V 48V 110V 120V 208V 220V 240V 277V 347V 380V-400V 415V 440V 480V 500V 600V
50 Hz K Y D P — A T — — N G B — M —60 Hz J X — D H L A T I — — N B — C
A1
1
T12
3
T2
4
5
T36
7
T48
A2
4 Poles
L1 L2 L4L3
A2
1
T1
2
3
T2
4
5
T36
7
T48
A1
1
T1
2
3
T2
4
5
T36
7
T48
A28 Poles
L1 L2 L3 L4 L1 L2 L3 L4
A2 A1
1
T1
2
3
T2
4
5
T3
6
7
T4
8
1
T1
2
3
T2
4
5
T3
6
7
T4
8
1
T1
2
3
T2
4
5
T36
7
T4
8
A1 A1 A1
12 PolesL1 L2 L4L3 L1 L2 L4L3 L1 L2 L4L3
A2 A2 A2
Bulletin 100S-C/104S-CSafety Contactors
76
Overview/Product Selection
Your order must include: cat. no. of the contactor specified with coil voltage code and, if required, cat. no. of any accessories and/or replacement coils.
Product Selection3-Pole AC- and DC-Operated Contactors• 3 Main Contacts
➊ For other contact configurations, please consult your local Allen-Bradley distributor.
Bulletin 100S/104S Safety Contactors• Positively Guided/Mechanically Linked Auxiliary Contacts• Front-Mounted Auxiliary Contacts:
Permanently FixedProtective Cover to Prevent Manual OperationRed Contact Housing for Easy IdentificationIncorporates IEC 947-5-1 “Mechanically Linked” Symbol
• AC and DC Operating Coils• SUVA Third-Party Certification
Bulletin 100S-C/104S-C safety contactors provide mechanically linked, positively guided contacts, which are required in feedback circuits for modern safety applications. The positively guided N.C. auxiliary contacts will not change state when a power contact welds.
Product Selection ................76Accessories .........................85Specifications ......................94Approximate Dimensions ........................132
Conformity to StandardsEN50205CSA C22.2 No. 14UL 508EN/IEC 60947-4IEC 60947-4-1 Annex H — Mirror ContactsIEC 60947-5-1 Annex L — Mechanically Linked Contacts
ApprovalsSUVA Third-Party CertifiedCE Marked CSA Certified (Cert No. LR13908)UL Listed (File No. E3125;Guide No. NLDX)
Ie[A]
Ratings for Switching AC Motors - AC-2, AC-3, AC-4 Aux. Contacts
Cat. No. ➊3∅ kW (50 Hz) Hp (60 Hz)
AC-3 AC-1 230V 400V/415V 500V 690V
1∅ 3∅
115V 230V 200V 230V 460V 575V N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/20 5 100S-C09⊗ 05C1 4 100S-C09⊗ 14C
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 100 5 100S-C12⊗ 05C1 4 100S-C12⊗ 14C
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 150 5 100S-C16⊗ 05C1 4 100S-C16⊗ 14C
23 32 7.5 11 13 10 2 3 5 7-1/2 15 150 5 100S-C23⊗ 05C1 4 100S-C23⊗ 14C
30 65 10 15 15 15 2 5 7-1/2 10 20 250 4 100S-C30⊗ 04C1 4 100S-C30⊗ 14C
37 65 11 18.5/20 20 18.5 3 5 10 10 25 300 4 100S-C37⊗ 04C1 4 100S-C37⊗ 14C
43 85 13 22 25 22 3 7-1/2 10 15 30 300 4 100S-C43⊗ 04C1 4 100S-C43⊗ 14C
60 100 18.5 32 37 32 5 10 15 20 40 500 4 100S-C60⊗ 04C1 4 100S-C60⊗ 14C
72 100 22 40 45 40 5 15 20 25 50 600 4 100S-C72⊗ 04C1 4 100S-C72⊗ 14C
85 100 25 45 55 45 7-1/2 15 25 30 60 600 4 100S-C85⊗ 04C1 4 100S-C85⊗ 14C
77
Bulletin 100S-C/104S-CSafety Contactors
Product Selection, Continued
⊗ Coil Voltage Code and Terminal PositionThe Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60Hz: Cat. No. 100S-C09⊗ 05C becomes Cat. No.100S-C09D05C.
Coil Terminal Position• All contactors are delivered with the coil terminals located on the line side.• For load side coil terminations, insert a “U” prior to the coil voltage code. Example: Cat. No.
100S-C09UD05C.
4-Pole AC- and DC-Operated Contactors• 4 Main Contacts
➊ For other contact configurations, please consult your local Allen-Bradley distributor.➋ Three-phase ratings only apply to contactors with at least three N.O. power poles.
⊗ Coil Voltage Code The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: 120V, 60 Hz: Cat. No. 100S-C09⊗ 404C becomes Cat. No. 100S-C09D404C.
12 24 32 36 42 48 100 100-110 110 120 127 200 200-
220 208 208-240
220-230 230 230-
240 240 277 347 380 380-400 400 400-
415 440 480 500 550 600
50Hz R K V W X Y KP — D P S KG L — — F — VA T — — — N — G B — M C —60Hz Q J — V — X — KP — D — — KG H L — — — A T I E — — — N B — — C50/60 – KJ — — — KY KP — KD — — KG KL — — KL KF — KA — — — — KN — KB — — — —
DC Voltages 9 12 24 36 48 60 64 72 80 110 115 125 220 230 250
100S-C09…C43Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode — — DJ — — — — — — — — — — — —100S-C60…C85 with Integrated Diode DR DQ DJ DW DY DZ DB DG DE DD DP DS DA DF DT
Ie[A]
Ratings for Switching AC MotorsContact Configuration
Cat. No. ➊
AC-2, AC-3, AC-43∅ kW (50 Hz) ➋ Hp (60 Hz) Main Pole Auxiliary Contacts
AC-3 AC-1 230V 400V/415V 500V 690V
1 ∅ 3 ∅ ➋
115V 230V 200V 230V 460V 575V N.O. N.C. N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/24 0 0 4 100S-C09⊗ 404C3 1 0 4 100S-C09⊗ 304C
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 104 0 0 4 100S-C12⊗ 404C3 1 0 4 100S-C12⊗ 304C
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 154 0 0 4 100S-C16⊗ 404C3 1 0 4 100S-C16⊗ 304C
23 32 7.5 11 13 10 2 3 5 7-1/2 15 154 0 0 4 100S-C23⊗ 404C3 1 0 4 100S-C23⊗ 304C
12 24 32 36 42 48 100 100-110 110 120 127 200 200-
220 208 208-240
220-230 230 230-
240 240 277 347 380 380-400 400 400-
415 440 480 500 550 600
50 R K V W X Y KP — D P S KG L — — F — VA T — — — N — G B — M C —60 Q J — V — X — KP — D — — KG H L — — — A T I E — — — N B — — C
50/60 — KJ — — — KY KP — KD — — KG KL — — KL KF — KA — — — — KN — KB — — — —
DC Voltages 9 12 24 36 48 60 64 72 80 110 115 125 220 230 250
100S-C09…C23Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode — — DJ — — — — — — — — — — — —
V
Hz
Cat. No. 100S-C09⊗ 05C
Line Side
Cat. No.100S-C09U⊗ 05C
Load Side
VHz
Bulletin 100S-C/104S-CSafety Contactors
78
Product Selection, Continued
Reversing AC- and DC-Operated Contactors• 3 Main Contacts• Includes Mechanical/Electrical Interlock• Includes Reversing Power Wiring
➊ For other contact configurations, please consult your local Allen-Bradley distributor.➋ One of the N.C. auxiliary contacts is supplied as part of the mechanical/electrical interlock.
⊗ Coil Voltage Code The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: 120V 60 Hz: Cat. No. 104S-C09⊗ 210C becomes Cat. No. 104S-C09D210C.
Ie[A]
Ratings for Switching AC MotorsAuxiliary Contacts
Installed per Contactor
Cat. No. ➊
AC-2, AC-3, AC-43 ∅ kW (50 Hz) Hp (60 Hz)
AC-3 AC-1 230V 400V/415V 500V 690V
1∅ 3∅
115V 230V 200V 230V 460V 575V N.O. N.C. ➋
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/20 6 104S-C09⊗ 012C1 5 104S-C09⊗ 210C
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 100 6 104S-C12⊗ 012C1 5 104S-C12⊗ 210C
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 150 6 104S-C16⊗ 012C1 5 104S-C16⊗ 210C
23 32 7.5 11 13 10 2 3 5 7-1/2 15 150 6 104S-C23⊗ 012C1 5 104S-C23⊗ 210C
30 65 10 15 15 15 2 5 7-1/2 10 20 250 5 104S-C30⊗ 010C1 5 104S-C30⊗ 210C
37 65 11 18.5/20 20 18.5 3 5 10 10 25 300 5 104S-C37⊗ 010C1 5 104S-C37⊗ 210C
43 85 13 22 25 22 3 7.5 10 15 30 300 5 104S-C43⊗ 010C1 5 104S-C43⊗ 210C
60 100 18.5 32 37 32 5 10 15 20 40 500 5 104S-C60⊗ 010C1 5 104S-C60⊗ 210C
72 100 22 40 45 40 5 15 20 25 50 600 5 104S-C72⊗ 010C1 5 104S-C72⊗ 210C
85 100 25 45 55 45 7-1/2 15 25 30 60 600 5 104S-C85⊗ 010C1 5 104S-C85⊗ 210C
12 24 32 36 42 48 100 100-110 110 120 127 200 200-
220 208 208-240
220-230 230 230-
240 240 277 347 380 380-400 400 400-
415 440 480 500 550 600
50 Hz R K V W X Y KP — D P S KG L — — F — VA T — — — N — G B — M C —60 Hz Q J — V — X — KP — D — — KG H L — — — A T I E — — — N B — — C
50/60 Hz — KJ — — — KY KP — KD — — KG KL — — KL KF — KA — — — — KN — KB — — — —
DC Voltages 9 12 24 36 48 60 64 72 80 110 115 125 220 230 250
104S-C09…C43Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode — — DJ — — — — — — — — — — — —104S-C60…C85 with Integrated Diode DR DQ DJ DW DY DZ DB DG DE DD DP DS DA DF DT
VHz
79
Bulletin 100S-DIEC Safety Contactors
Overview/Product Selection
Product Selection
⊗ Voltage Suffix Codes for AC Control
➊ The N.C. contacts meet IEC 60947-4 Annex F requirements to mirror contact performance. The N.C. mirror contacts are wired in series or parallel and must be used as monitoring contacts with feedback to the safety circuit.
➋ Signal voltage of the Cat. No. 100S-D… electronic interface:Ue: 24V DC/Ie: 15 mAPick-Up Voltage: 13.0V DC…30.2V DCDrop-Out Voltage: -3.0V DC…+5.0V DC
➌ Higher kW rating only applies to contactors with electronic coil.
Bulletin 100S-D Safety Contactors• 45…220 kW @500V• 60…600 Hp @460V• 75…700 Hp @575V• Electronic and Conventional Coils
AC & DCIntegrated PLC InterfaceLow Power Pick-Up & Hold-InWide Voltage Ranges
• Complete Range of Accessories• Environmentally-Friendly• Compact Dimensions
Bulletin 100S-D safety contactors provide mechanically linked, positively guided contacts, which are required in feedback circuits for modern safety applications. The positively guided N.C. auxiliary contacts will not change state when a power contact welds.
Table of ContentsProduct Selection ................79Accessories .........................90Specifications ......................94Approximate Dimensions ........................134
Conformity to StandardsIEC 60947-4-1IEC 60947-4 Annex FIEC 947 Type “2” CoordinationCSA C22.2 No. 14UL 508
ApprovalsCE Marked CSA CertifiedUL ListedSUVA Certified
Ie [A] Switching of 3-phase motors — AC-2, AC-3 Auxiliary contacts
Cat. No.60°C 40°C kW (50 Hz) Hp (60 Hz) N.O. N.C. ➊
AC-3 AC-1 230V 400V 415V 500V 690V 1000V 200V 230V 460V 575V
95 160 25 50 50 55 80 45 25 30 60 75 2 2 100S-D95⊗ 22C110 160 32 55 55 63 100 55 40 40 75 100 2 2 100S-D110⊗ 22C140 250 45 75 75 80/90➌ 110/132➌ 75 40 50 100 125 2 2 100S-D140⊗ 22C180 250 55 90 100 90/110➌ 132/160➌ 90 50 60 150 150 2 2 100S-D180⊗ 22C210 350 63 110 110 150 200 110 60 75 150 200 2 2 100S-D210⊗ 22C250 350 80 132 150 160 250 133 75 100 200 250 2 2 100S-D250⊗ 22C300 450 90 160 160 200 300 163 100 125 250 300 2 2 100S-D300⊗ 22C420 500 132 220 250 300 425 225 150 175 350 400 2 2 100S-D420⊗ 22C630 800 200 355 355 450 500 425 200 250 500 600 2 2 100S-D630⊗ 22C860 1000 250 500 500 560 600 425 250 300 600 700 2 2 100S-D860⊗ 22C
Conventional Coil V 24 48 100 110 120 200 208 220…230 230 240 277 380…
400 415 440 480 500 550 600
100S-D95…100S-D18050 Hz K Y — D — — — A — T — N B G — M C —
60 Hz J X — — D — H — — A T — — N B — — C
100S-D95…100S-D110 50/60 Hz KJ — KP KN — KG — — KF KA — — — — — — — —
Electronic Coilw/ PLC Interface ➋ V 24 42…
64 100 110…130 200 208…
277380…415
440…480 500 600
100S-D95…100S-D250 50/60 Hz EJ EY EP ED EG EA EN EN EN —
100S-D300…100S-D420 50/60 Hz — EY EP ED EG EA EN EN EN —
100S-D630…100S-D860 50/60 Hz — — EP ED EG EA EN EB EM EC
100S-D860…
3-pole AC Contactors• Conventional and Electronic AC Coils• 3 Main Contacts• Non-Reversing
Bulletin 100S-DIEC Safety Contactors
80
Product Selection, Continued
⊗ Voltage Suffix Codes for DC Control
➊ The N.C. contacts meet IEC 60947-4 Annex F requirements to mirror contact performance. The N.C. mirror contacts are wired in series or parallel and must be used as monitoring contacts with feedback to the safety circuit.
➋ For conventional DC coil only. The pickup winding must be interconnected with the N.C. late-breaking auxiliary contacts.➌ Signal voltage of the Cat. No. 100S-D… electronic interface:Ue: 24V DC/Ie: 15 mA
Pick-Up Voltage: 13.0V DC…30.2V DCDrop-Out Voltage: -3.0V DC…+5.0V DC
➍ Higher kW rating only applies to contactors with electronic coil.
Ie [A] Switching of 3-phase motors — AC-2, AC-3 Auxiliary contacts
Cat. No.60°C 40°C kW (50 Hz) Hp (60 Hz) N.O. N.C. ➊
AC-3 AC-1 230V 400V 415V 500V 690V 1000V 200V 230V 460V 575V
95 160 25 50 50 55 80 45 25 30 60 753 2/1L 100S-D95⊗ 33LC ➋2 2 100S-D95⊗ 22C
110 160 32 55 55 63 100 55 40 40 75 1003 2/1L 100S-D110⊗ 33LC ➋2 2 100S-D110⊗ 22C
140 250 45 75 7580 110
75 40 50 100 1253 2/1L 100S-D140⊗ 33LC ➋
90 ➍ 132 ➍ 2 2 100S-D140⊗ 22C
180 250 55 90 10090 132
90 50 60 150 150 2 2 100S-D180⊗ 22C110 ➍ 160 ➍
210 350 63 110 110 150 200 110 60 75 150 200 2 2 100S-D210⊗ 22C250 350 80 132 150 160 250 133 75 100 200 250 2 2 100S-D250⊗ 22C300 450 90 160 160 200 300 163 100 125 250 300 2 2 100S-D300⊗ 22C420 500 132 220 250 300 425 225 150 175 350 400 2 2 100S-D420⊗ 22C630 800 200 355 355 450 500 425 200 250 500 600 2 2 100S-D630⊗ 22C860 1000 250 500 500 560 600 425 250 300 600 700 2 2 100S-D860⊗ 22C
Conventional Coil V 24 48 110 125 220 250
100S-D95…100S-D140 ➋ DC ZJ ZY ZD ZS ZA ZT
Electronic Coil w/ EI Interface ➌ V 24 48…72 110…130 200…255
100S-D95…100S-D300 DC EZJ EZY EZD EZA
100S-D420 DC — EZY EZD EZA
100S-D630…860 DC — — ED EA
100S-D420…
3-pole DC Contactors• Conventional and Electronic DC Coils• 3 Main Contacts• Non-Reversing
81
Bulletin 100DeviceNet Starter Auxiliary™
Overview/Product Selection/Specifications
Product Selection• Removable connectors• Slender 22.5 mm wide profile• Screw or DIN Rail mounting• Rotary node address switches• DeviceNet address settable via hardware or software — no need to adjust rotary node address switches
Specifications
Input Specifications
Bulletin 100 — DeviceNet Starter Auxiliary™ (DSA) Module• DeviceLogix™ Component Technology• Rotary Address Switches• Reduced Engineering, Installation, and Startup Costs• 24V DC or 120V AC Inputs• High-Capacity Transistor or Relay Outputs• Diagnostics Over Communication• ODVA Compliance v2.0 Tested
The DeviceNet Starter Auxiliary (DSA) module enables a simple integration of contactors and sensors into the DeviceNet network. Components with minimum I/O requirements (e.g., four inputs and two outputs) are predominant. The DSA has high-capacity outputs that eliminate the need for interposing relays. This makes the DSA ideal for use with motor starters, circuit breakers, contactors, motor protectors, soft starters, sensors, reed switches, tracer switches and control protectors.
The DeviceLogix component technology incorporated into the DSA allows it to be programmed with up to 48 function blocks to execute simple logic locally. This functionality can be used to solve high-speed applications, controlled shut down, or other local operations. DeviceLogix capability in the DSA module can be configured with RSNetworx 3.00 or later.
Table of ContentsProduct Selection............... 81Specifications..................... 81Conformity to StandardsIEC 60947UL 508CSA C22.2 No. 14EN50081-2, EN50082-2ApprovalsCEcULus Listed
Inputs Outputs Cat. No.4 (120V AC) 2 Relay (250V rated) 100-DNY41R4 (24V DC) 2 Relay (250V rated) 100-DNY42R4 (24V DC) 2 Solid-state (24V DC) 100-DNY42S
Electrical DataDeviceNet supply voltage 11…25V DCDeviceNet input current max. 270 mASurge current at powerup < 3 A for 5 ms
Site ConditionsAmbient temperature Operation
Storage–25…60°C (32…140°F)–40…85°C (–40…185°F)
Humidity 0…95% (without condensation)Shock Operation
Off-state30 G, peak acceleration50 G, peak acceleration
Vibration resistance 2.5 G, at 10…500 HzDeviceNet Communication
Baud rate 125, 250, 500 kBit/s
Distance maximum500 m (1640 ft.) with 125 kBit/s200 m (656 ft.) with 250 kBit/s100 m (328 ft.) with 500 kBit/s
ConnectionConnection capacity: (dependent on wire type) 0.25…2.5 mm2/0.25…2.5 mm2/24…12 AWGWire type min. 75°CTightening torque 0.5…0.6 Nm (4.4…5.3 lb-in)
Cat. Nos. 100-DNY21R, 100-DNY41R 100-DNY42R, 100-DNY42SInputs per device 4 4On-state voltage rangeOff-state voltage
80…132V AC40V, at 60 Hz
10…30V DC 5.5V DC
On-state current 1.2…2.0 mA 3 mA, at 10V (min)…11 mA, at 30VOff-state current 0.6 mA min. 1.5 mA max.
TransitionVoltage 40…79V AC 5…10V DC Current 0.6…1.2 mA 1.5…3 mA
Sensor SourceVoltage — 19…25V DCCurrent — 35 mA
Bulletin 100DeviceNet Starter Auxiliary™
82
Specifications, Continued
Output Specifications
Cat. No. 100-DNY41R, 100-DNY42R(Relay Outputs)
100-DNY42S(Transistor Outputs)
Outputs per device 2 2Voltage range max. 240V AC, 30V DC 15…30V DC, ±0.0%
Switching capacity max.3600 VA
UL: B 300IEC: AC-15: 5 A
—
Thermal continuous current per output max. 5 A —On-State voltage drop max. — 0.25V at 2 AOn-State current per output max. — 2 A Maximum off-state leakage current — 1.5 mASurge current per output — 4 A for 50 ms
External (Micro/M12) Wiring Connections Input OutputAC Voltage
Cat. Nos. 190D-XXDXXX-SA3, 191D-XXDXXX-SA3
InputPin 1: Sensor voltage (+)Pin 2: Input 1Pin 3: ReturnPin 4: Input 2Pin 5: Not used
OutputPin 1: Output APin 2: Not usedPin 3: Not usedPin 4: Return
Cat. Nos. 190D-XXDXXX-SA6, 191D-XXDXXX-SA6
InputPin 1: Input 2Pin 2: Protective EarthPin 3: Input 1Pin 4: Line
OutputPin 1: Output APin 2: Not usedPin 3: Not usedPin 4: Return
DC VoltageCat. Nos. 190D-XXNXXX-SA3 191D-XXNXXX-SA3
InputPin 1: Sensor Voltage (V+)Pin 2: Input 1Pin 3: ReturnPin 4: Input 2Pin 5: Not used
OutputPin 1: Not usedPin 2: Not usedPin 3: ReturnPin 4: Output A
Cat. Nos. 190D-XXNXXX-SA4, 191D-XXNXXX-SA4
InputPin 1: Sensor Voltage (V+)Pin 2: Input 1Pin 3: ReturnPin 4: Input 2Pin 5: Not used
OutputPin 1: V+Pin 2: Not usedPin 3: ReturnPin 4: Output A
1
5
2
43
FEMALE FEMALE
1
2
3
4
1
2
3
4
FEMALE FEMALE
1
2
3
4
1
5
2
43
FEMALE
1
2 3
4
FEMALE
1
5
2
43
FEMALE FEMALE
1
2 3
4
83
Bulletin 100DeviceNet Starter Auxiliary™
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
110
(4.33)
EN 50 022
EN 50 022
EN 50 022
22.5
(0.8
9)
0.5 (0.2)
11.25(0.43)
22.5(0.89)
4.5(0.177)
2.5 (0.1)
18 (0.7
)
18
(0.7
)
18 (0.7
)
32.8
(1.2
9)
5.5
(0.2
2)
85 (3
.35)
92.2
(3.6
3)
78 (3
.07)
38 (1
.50)
38 (1
.50)
01
INPUT
OUTPUT
23
AB
Bulletin 100-MAccessories — Field Installed
84
Accessories
➊ Must be ordered in multiples of 10.➋ Sold in quantities of 1.
Bulletin 100-M Miniature Contactors Labelling Material
Description Type For Use With Cat. No. ➊
Auxiliary Contact Adder Deck
(Top Mounted)
2 N.C.1 N.O./1 N.C.2 N.O./2 N.C
100/104-M05…M12195-MB02 195-MB11 195-MB22
Solid-State Timing Element
0.3…3 s ON-Delay, 110…250V AC or DC
100/104-M05…M12
196-MT3S1…30 s ON-Delay, 110…250V AC or DC 196-MT30S
Star-Delta Timer220V AC 196-MTSDA1110V AC 196-MTSDA2
35 mm DIN Rail Mounting Adapter for Above Timers 196-MTM
Mechanical Interlock Kit Mechanical Interlock Only 100-M05…M12 (AC Coils
Only) 199-MXM1
Power Wiring Kit For Reversing Contactors 100-M05…M12 140-KCR4➋
R-C Suppressor 24…48V AC110…280V AC
100/104-M05…M12
199-MSMA48 199-MSMA1
MOV Suppressor12…55V AC/12…77V DC
56…136V AC/78…162V DC137…277V AC/163…350V DC
199-MSMV1199-MSMV2199-MSMV3
Diode Suppressor 12…250V DC 199-MSMD1
Description Pkg. Qty. Cat. No.Labels Adhesive Paper, 105 per sheet 10 199-ID1
Marking Tags 160 per sheet 10 199-ID2Cover Transparent/Tag 100 199-ID3
Tag Carrier For Clip-On Tags 100 199-ID4
Clip-On Marking Tag Strip (10 per Strip)Tag Marking Pkg. Qty. Cat. No. Tag Marking Pkg. Qty. Cat. No. Tag Marking Pkg. Qty. Cat. No.1…10 25 199-ID5 1 25 199-ID25 G 25 199-ID4511…20 25 199-ID6 2 25 199-I26D H 25 199-ID4621…30 25 199-ID7 3 25 199-ID27 I 25 199-ID4731…40 25 199-ID8 4 25 199-ID28 J 25 199-ID4841…50 25 199-ID9 5 25 199-ID29 K 25 199-ID4951…60 25 199-ID10 6 25 199-ID30 L 25 199-ID5061…70 25 199-ID11 7 25 199-ID31 M 25 199-ID5171…80 25 199-ID12 8 25 199-ID32 N 25 199-ID5281…90 25 199-ID13 9 25 199-ID33 0 25 199-ID5391…100 25 199-ID14 0 25 199-ID34 P 25 199-ID54101…110 25 199-ID15 Unmarked 25 199-ID35 Q 25 199-ID55111…120 25 199-ID16 0…9 25 199-ID36 R 25 199-ID56121…130 25 199-ID17 + 25 199-ID37 S 25 199-ID57131…140 25 199-ID18 - 25 199-ID38 T 25 199-ID58141…150 25 199-ID19 A 25 199-ID39 U 25 199-ID59151…160 25 199-ID20 B 25 199-ID40 V 25 199-ID60161…170 25 199-ID21 C 25 199-ID41 W 25 199-ID61171…180 25 199-ID22 D 25 199-ID42 X 25 199-ID62181…190 25 199-ID23 E 25 199-ID43 Y 25 199-ID63191…200 25 199-ID24 F 25 199-ID44 Z 25 199-ID64
Cat. No. 195-MB22
85
Bulletin 100-C/104-CAccessories — Field Installed
Accessories
Auxiliary Contacts (For 100-C09…C85 contactors)
➊ Max. number of auxiliary contacts that may be mounted:AC coil contactors — max. 4 N.O. contacts on the front of the contactor, 2 N.O. contacts on the side, 4 N.C. front or side, 6 total.DC coil contactors — max. 4 N.O. contacts on the front of the contactor or max 2 N.O. contacts on the side, 4 N.C. front or side, 4 total.
➋ Double numbering — Left-side mounting only is recommended for Cat. No. 100-C09…100-C23 due to double numbering.
DescriptionN.O. N.C.
Connection Diagrams For Use With Cat. No.
Auxiliary Contact Blocks for Front Mounting ➊• 2- and 4-pole• Quick and easy mounting without tools• Electronic-compatible contacts down to 17V,
5 mA• Mutual positive guidance to the main contactor
poles (except for L types)• Models with equal function with several
terminal numbering choicesL = Late break /early make
0 2 100-C allC30⊗ 00…C85⊗ 00
100-FA02100-FB02
1 1100-C all
C30⊗ 00…C85⊗ 00C09⊗ 10…C23⊗ 10
100-FA11100-FB11100-FC11
2 0 100-C allC30⊗ 00…C85⊗ 00
100-FA20100-FB20
1L 1L C30⊗ 00…C85⊗ 00 100-FAL11100-FBL11
0 4 100-C all 100-FA04
1 3 100-C all 100-FA13
2 2100-C all
C30⊗ 00…C85⊗ 00C09⊗ 10…C23⊗ 10
100-FA22100-FB22100-FC22
3 1 100-C allC09⊗ 10…C23⊗ 10
100-FA31100-FC31
4 0 100-C all 100-FA40
1+1L 1+1L 100-C all 100-FAL22
Auxiliary Contact Blocks for Side Mounting without Sequence Terminal Designations ➊• 1- and 2-pole• Two-way numbering for right or left mounting
on the contactor• Quick and easy mounting without tools• Electronic-compatible contacts down to 17V,
5 mA• Mutual positive guidance to the main contactor
poles (except for L types)L = Late break/early make
0 1 100-C all 100-SA01
1 0 100-C all 100-SA10
0 2 100-C all 100-SA02
1 1 100-C all 100-SA11
2 0 100-C all 100-SA20
1L 1L 100-C all 100-SAL11
Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations ➊• 1- and 2-pole• Two-way numbering for right or left mounting
on the contactor• Quick and easy mounting without tools• Electronic compatible contacts down to 17V,
5 mA• Mutual positive guidance to the main contactor
poles (except for L types)L = Late break/early make
0 1 100-C all 100-SB01
1 0 100-C ➋ 100-SB10
0 2 100-C ➋ 100-SB02
1 1 100-C ➋ 100-SB11
2 0 100-C ➋ 100-SB20
1L 1L 100-C ➋ 100-SBL11
-FA02
-FB11 -FC11
-FA11
-FA20
-FBL11
-FA22 -FB22
-FC22 -FA31
-FA40 -FAL22
-FA04 -FA13
-FB02
-FB20 -FAL11
-FC31
-SA01 -SA10
-SA02 -SA11
-SA20 -SAL11
–– –
–
––
––
––
––
––
––
– –– –
– –– –
––
––
––
––
––
––
––
––
-SB01 -SB10
-SB02 -SB11
-SB20 -SBL11
Bulletin 100-C/104-CAccessories — Field Installed
86
Accessories, Continued
Control Modules (For 100-C09…C85 contactors)
⊗ Voltage Suffix CodeThe cat. no. as listed is incomplete. Select a voltage suffix code from the table below to complete the cat. no. Example: 120V, 60 Hz: Cat. No. 100-FL11⊗ becomes Cat. No. 100-FL11D.
➊ For special voltages, consult your local Allen-Bradley distributor.
Description Connection Diagrams For Use With Cat. No.
Pneumatic Timing ModulesPneumatic timing element contacts switch after the delay time. The contacts on the main contactor continue to operate without delay.• Continuous adjustment range• Repeat accuracy ± 10%
ON-Delay0.3…30 s1.8…180 s
100-C with AC coils
100-FPTA30100-FPTA180
OFF-Delay0.3…30 s1.8…180 s
100-C all 100-FPTB30100-FPTB180
Electronic Timing ModulesDelay of the contactor solenoid
100-ETA ON-Delay The contactor is energized at the end of the delay time.
ON-Delay0.1…3 s1…30 s10…180 s
110…240V,50/60 Hz110…250VDC
100-C all
100-ETA3100-ETA30100-ETA180
ON-Delay0.1…3 s1…30 s10…180 s
24…48V DC
100-C with DC coils
100-ETAZJ3100-ETAZJ30100-ETAZJ180
100-ETB OFF-Delay After interruption of the control signal, the contactor is de-energized at the end of the delay time.
OFF-Delay0.3…3 s1…30 s10…180 s
24V50/60 Hz
100-C09…C37 with AC
coils
100-ETBKJ3100-ETBKJ30100-ETBKJ180
OFF-Delay0.3…3 s1…30 s10…180 s
110…240V50/60 Hz
100-C with AC coils
100-ETB3100-ETB30100-ETB180
100-ETY Contactor K 3 (Y) is de-energized (off) and K 2 (D) is energized (on) after the end of the set Y end time. (Switching delay at 90 ms).• Continuous adjustment range• High repeat accuracy
Transition Time Y Contactor
1…30 s
110…240V50/60 Hz
100-C with AC coils 100-ETY30
Mechanical InterlocksFor interlocking of two contactors.• Common interlock for all 100-C contactor sizes• Interlocking of different sizes possible• Mechanical and electrical interlocking possible in one
module by means of integrated auxiliary contacts• 9 mm dovetail connector included
• Mechanical only• Without auxiliary contacts 100-C all 100-MCA00
• Mechanical/electrical
• With 2 N.C. auxiliary contacts 100-C all 100-MCA02
Mechanical LatchFollowing contactor latching, the contactor coil is immediately de-energized (off) by the N.C. auxiliary contact (65-66).• Electrical or manual release• 1 N.O. + 1 N.C. auxiliary contacts• Suitable for all 100-C contactor sizes, 9…85 A
100-C with AC coils 100-FL11⊗
Voltage ➊ 24V 48V 100V 110V 120V 230-240V 240V 277V 380-400V 400-415V 440V 480V50 Hz K Y KP D — VA T — N G B —60 Hz J — — — D — A T — — N B
(K1M)
K1M
(K1M)
K1M
(K1M)
K1M
87
Bulletin 100-C/104-CAccessories — Field Installed
Accessories, Continued
Control Modules (For 100-C09…C85 contactors), Continued
Assembly Components (For 100-C09…C85 contactors)
➊ Must be ordered in multiples of package quantities.
Description Connection Diagrams For Use With Cat. No.
DC Interface (electronic)Interface between the DC control signal (PLC) and the AC operating mechanism of the contactor.• Control (input) voltage
12V DC18…30V DC (24V nominal)48V DC
• Requires no additional surge suppression on the contactor coils
100-C with AC coils110…240V AC 100-JE12
100-JE100-JE48
Surge SuppressorsFor limitation of coil switching transients.• Plug-in, coil mounted• Suitable for all 100-C contactor
sizes, 9…85 A• RC, Varistor and Diode Versions
RC ModuleAC Operating Mechanism
24…48V 50/60 Hz
100-C with AC coils
100-FSC48
110…280V50/60 Hz 100-FSC280
380…480V50/60 Hz 100-FSC480
Varistor ModuleAC/DC Operating Mechanism
12…55V AC /12…77V DC
100-C all
100-FSV55
56…136V AC /78…180V DC 100-FSV136
137…277V AC /181…350V DC 100-FSV277
278…575V AC 100-FSV575
Diode Module DC Operating Mechanism
12…250V DC 100-C with DC coils 100-FSD250
Description For Use With Pkg. Qty. ➊
Cat. No.
Dovetail Connectors• For use in contactor and starter assemblies.• 10 each 100-C allSingle Connector 0 mm SpacingDual Connector 9 mm Spacing
1010
100-S0100-S9
Protective Covers• Provides protection against unintended manual operation• For contactors and front mounted auxiliary contacts, pneumatic
timers and latches
100-C all 1 100-SCCA
100-FA, FB, FC, FP, FL 10 100-SCFA
Reversing Power Wiring KitsFor Reversing Connection with a solid-state or thermal overload relay
100-C09…C23100-C30…C37
100-C43100-C60…C85
1
105-PW23105-PW37105-PW43105-PW85
35 x 7.5 mm DIN Rail (1 m) 100-C09…C85 10 199-DR1
K1M
(K1M)
Cat. No. 100-S0
Cat. No. 100-SCFA
Cat. No. 100-SCCA
Cat. No. 105-PW23
Bulletin 100-C/104-CAccessories — Field Installed
88
Cat. No. 170-PW23
Accessories, Continued
Wye-Delta Starter KitsWye-Delta power wiring kits were designed to aid in the field assembly of open-transition wye-delta starters that use Bulletin 100-C contactors. These kits include line, load, and start-point (shorting) connections. Assembling a wye-delta starter requires the use of the following additional components:
• Contactors • Overload Relay• Cat. No. 100-MCA02 Mechanical/Electrical Interlock• Cat. No. 100-ETY30 Electronic Y-∆ Timer• Cat. No. 100-S9 Base Coupler for 1M to 2M contactor (optional)
Marking Systems (For 100-C09…C85 contactors)
➊ Must be ordered in multiples of package quantities.
3-Phase RatingPkg. Qty. Cat. No.
kW (50 Hz) Hp (60 Hz) Use with Cat. No. 100-
230V 380/415V 500V 690V 200V 230V 460V 575VDelta Wye
1M 2M 1S5.5 8 8 8 5 5 10 10 C09 C09 C09 1 170-PW237.5 11 11 11 5 7.5 15 15 C12 C12 C09 1 170-PW2310 14 15 14 7.5 10 20 20 C16 C16 C12 1 170-PW2314 21 21 19 7.5 10 25 25 C23 C23 C12 1 170-PW2318 28 28 28 10 15 30 30 C30 C30 C16 1 170-PW3719 35 35 32 15 20 40 40 C37 C37 C23 1 170-PW3723 40 40 41 20 25 50 50 C43 C43 C30 1 170-PW4333 58 60 56 30 40 75 75 C60 C60 C37 1 170-PW7239 69 67 70 40 50 100 100 C72 C72 C43 1 170-PW7247 82 82 81 50 60 125 125 C85 C85 C60 1 170-PW85
Description Pkg. Qty. ➊ Cat. No.
Label Sheet• 10 sheets with 105 self-adhesive paper labels each, 6 x 17 mm 10 100-FMS
Marking Tag Sheet• 10 sheets with 160 perforated paper labels each, 6 x 17 mm• To be used with a transparent cover
10 100-FMP
Transparent Cover• 100 each• To be used with marking tag sheets
100 100-FMC
Marking Tag Adapters• 100 each• To be used with marking tag: System V4 / V5
System Bul. 1492W100100
100-FMA1100-FMA2
89
Bulletin 100-C/104-CAccessories — Field Installed
Accessories, Continued
Terminal Kits (For 100-C09…C85 contactors)
➊ Must be ordered in multiples of 100.➋ 16 mm2 max. according to IEC 60947; actual max. 25 mm2.
Description Max. Current Ratings and Wire Sizes Pkg. Qty. Cat. No.
Stab Connector Kit• Dual stab (0.250 in.) for 100-C coil terminals• For 100-C09…C85 contactors
20 199-SC2
Stab Connector Kit• Dual stab (0.250 in.) for 100-C power terminals• For 100-C09…C23 contactors
100 ➊ 199-SC10
3-Pole Terminal Lug Kit• For 100-C09…C23 (Line side)
IEC @ 40°CIEC @ 40°C
UL/CSA (Encl.)
45 A (4…16 mm2 ➋ , fine stranded w/ ferrule)45 A (4…25 mm2, coarse stranded/solid)40 A (#10…4 AWG, stranded/solid)
1 100-CTN23
• For 100-C09…C23 (Load side)IEC @ 40°CIEC @ 40°C
UL/CSA (Encl.)
45 A (4…16 mm2 ➋ , fine stranded w/ ferrule)45 A (4…25 mm2, coarse stranded/solid)40 A (#10…4 AWG, stranded/solid)
1 100-CTL23
• For 100-C30…C37 (Line side)IEC @ 40°CIEC @ 40°C
UL/CSA (Encl.)
60 A (4…16 mm2 ➋ , fine stranded w/ ferrule)60 A (4…25 mm2, coarse stranded/solid)55 A (#10…4 AWG, stranded/solid)
1 100-CT37
1-Pole Terminal Lug Kit• For 100-C43
IEC @ 40°CIEC @ 40°C
UL/CSA (Encl.)
90 A (6…35 mm2 ➋ , fine stranded w/ ferrule)90 A (6…50 mm2, coarse stranded/solid)75 A (#8…2 AWG, stranded/solid)
3 100-CT43
• For 100-C60…C85IEC @ 40°CIEC @ 40°C
UL/CSA (Encl.)
130 A (10…70 mm2 ➋ , fine stranded w/ ferrule)130 A (10…95 mm2, coarse stranded/solid)130 A (#8…2/0 AWG, stranded/solid)
3 100-CT85
3-Pole Paralleling Kit• For 100-C09…C23
IEC @ 40°CIEC @ 40°C
UL/CSA (Encl.)
100 A (35…70 mm2 ➋ , fine stranded w/ ferrule)100 A (35…95 mm2, coarse stranded/solid)100 A (#0…2/0 AWG, stranded/solid)
2 100-CP23
• For 100-C30…C37IEC @ 40°CIEC @ 40°C
UL/CSA (Encl.)
150 A (35…70 mm2 ➋ , fine stranded w/ ferrule)150 A (35…95 mm2, coarse stranded/solid)150 A (#0…2/0 AWG, stranded/solid)
2 100-CP37
Bulletin 100-DIEC Contactors
90
Accessories
Auxiliary Contacts
Labeling Material
Marking Systems (For 100-D95…D860 contactors)
➊ Must be ordered in multiples of package quantities.
DescriptionN.O. N.C.
Connection Diagram For use with Cat. No.
• Side-mounted• With IEC sequence terminal designations
1 1100-D
Left or right inside mounting
100-DS1-11
1 1
100-DLeft or right
outside mounting
100-DS2-11
1 1L100-D
Left or right inside mounting
100-DS1-L11
2 0100-D
Left or right inside mounting
100-DS1-20
2 0
100-DLeft or right
outside mounting
100-DS2-20
• Electronically compatible auxiliary contacts• Ideal for use when switching low-power control circuits• Contact ratings:
AC-1 250V, 0.1 AAC-15, DC-13 3…125V, 1…100 mA
1 1
100-DLeft or right
outside mounting
100-DS2-B11
• Uniform labeling materials for contactors, motor protection devices, timing relays, and circuit breakers.
Description Pkg. Qty. ➊ Cat. No.
Label Sheet• 10 sheets with 105 self-adhesive paper labels each, 6 x 17 mm 10 100-FMS
Marking Tag Sheet• 10 sheets with 160 perforated paper labels each, 6 x 17 mm• To be used with a transparent cover
10 100-FMP
Transparent Cover• 100 each• To be used with marking tag sheets
100 100-FMC
Marking Tag Adapters• 100 each• To be used with marking tag: System V4 / V5
System Bul. 1492W100100
100-FMA1100-FMA2
91
Bulletin 100-DIEC Contactors
Accessories, Continued
Suppressor Modules
Connecting Components
Description Circuit Diagram For use with Cat. No.
Suppressor Module for 100-D Contactors• For limiting surge voltage when coil
circuits are interrupted• Can be plugged into all 100-D
contactors• Supplied as standard on all
conventional DC coil contactors and all electronic coil contactors as part of the supply module, or delivered with separate suppressor module
RC Module (AC control)for contactors with conventional coil21…48V 50 Hz/24…55V 60 Hz95…110V 50 Hz/110…127V 60 Hz190…240V 50 Hz/220…277V 60 Hz380…550V 50 Hz/440…575V 60 Hz
100-D95…100-D180
100-DFSC48100-DFSC110100-DFSC240100-DFSC550
Varistor Modulefor contactors with conventional coil≤55V AC56…136V AC137…277V AC278…575V AC
100-D95…100-D180
100-DFSV55100-DFSV136100-DFSV277100-DFSV575
Description Cat. No.
For 100-D95…D180 Contactors — Conventional and Electronic Coils• 50 mm2 input connections — for Cat. No. 100-DL…(Lugs)• 50 mm2 input connections — for Cat. No. 100-DTB…(Terminal blocks)• 50 mm2 output connections — for Cat. No. 100-DL…(Lugs)• 50 mm2 output connections — for Cat. No. 100-DTB…(Terminal blocks)• Neutral bridge for 100-D95…100-D180 contactors
100-D180-VL100-D180-VLTB
100-D180-VT100-D180-VTTB100-D180-VYU
For 100-D210…100-D420 Contactors — Electronic Coils• 120 mm2 input connections — for 100-DL…(Lugs) contactors• 120 mm2 input connections — for 100-DTB…(Terminal blocks) contactors• 120 mm2 output connections — for 100-DL…(Lugs) contactors• 120 mm2 output connections — for 100-DTB…(Terminal blocks) contactors• Neutral bridge for 100-D210…100-D420 contactors• For Y-contactor100-D95…100-D180 contactors; 80 mm2
100-D420-VL100-D420-VLTB
100-D420-VT100-D420-VTTB100-D420-VYU100-D420-VYTB
For 100-D630…100-D860 Contactors — Electronic Coils…• 350 mm2 input connections — for 100-DL…Lugs) contactors• 350 mm2 output connections — for 100-DL…(Lugs) contactors• Neutral bridge for 100-D630…100-D860 contactors
100-D860-VL100-D860-VT
100-D860-VYU
Power Wiring Kits (for contactors using 100-DL lug kits)
For 100-D95…100-D180• Reversing• Two-speed, or changeover• Wye-Delta/Star-Delta
100-DPW180100-D180-VL100-DPY180
For 100-D210…100-D420• Reversing• Two-speed, or changeover• Wye-Delta/Star-Delta
100-DPW420100-D420-VL100-DPY420
For 100-D630…100-D860• Reversing• Two-speed, or changeover
100-DPW860100-D860-VL
Bulletin 100-DIEC Contactors
92
Accessories, Continued
Connecting Components, Continued
Interlocks
Description Cat. No.
Terminal Blocks• Set of 2• Protection class IP2X per IEC 529 and DIN 40 050
For 100-D95,100-D110For 100-D140,100-D180, 100-D95-EI…D180-EIFor 100-D210…100-D420
100-DTB110100-DTB180100-DTB420
Terminal Lugs (UL/CSA), Copper Frame• Set of 3
For 100-D95, 100-D110For 100-D140, 100-D180For 100-D210…100-D420For 100-D630, 100-D860For 100-D630, 100-D860
100-DL110100-DL180100-DL420100-DL630100-DL860
Control Circuit Terminal• 2 x 2.5 mm2
For connecting to 100-D95…D180For connecting to 100-D210…D420For connecting to 100-D630…D860
100-DAT1100-DAT2100-DAT3
Terminal Shields• Set of 2• Protection class IP10 per IEC 529 and DIN 40 050• For direct-on-line, reversing, two-speed, and wye-delta/
star-delta assemblies
For 100-D95,100-D110For 100-D140,100-D180, 100-D95-EI…D180-EIFor 100-D210…100-D420
100-DTS110100-DTS180100-DTS420
Terminal Covers• Qty: 1• Protection class IP20 per IEC 529 and DIN 40 050• For direct-on-line, reversing, two-speed, and wye-delta/
star-delta assemblies
For 100-D95…100-D180For 100-D210…100-D420For 100-D630…100-D860
100-DTC180100-DTC420100-DTC860
Phase Barriers• Set of 4 100-D630…D860 100-DPB860
Mounting Plate• Galvanized steel plate for starter combinations
For 100-D95…100-D180• Direct-on-line• Reversing, two-speed, or changeover• Y-∆ or Dahlander
100-DMS180100-DMU180100-DMY180
For 100-D210…100-D420• Direct-on-line• Reversing, two-speed, or changeover• Y-∆ or Dahlander
100-DMS420100-DMU420100-DMY420
For 100-D630…100-D860• Direct-on-line• Reversing, two-speed, or changeover• Y-∆ or Dahlander
100-DMS860100-DMU860100-DMY860
Mounting PlateFor interlocking between 100-C60…C85 and 100-D95…D180 contactors• Two-speed or changeover switches
100-DMU85
Description Circuit Diagram For use with Cat. No.
Mechanical only• No additional space required 100-D95…100-D860 100-DMA00
Dual electrical/mechanical• No additional space required• 2 N.C. auxiliary contacts
100-D95…100-D860 100-DMD02
Mechanical only• No additional space required 100-D95…100-D860 100-DMD00
Mechanical only• Provides interlocking between 100-C and 100-D contactors
100-C60…100-C85 between
100-D95…100-D180100-DMC00
22 NC 21
21 NC 22
93
Bulletin 100-GIEC Contactors
Accessories
Control Modules
⊗ Coil Voltage Codes ➊
➊ For other voltages, consult your local Allen-Bradley distributor.
Description For use with Cat. No.
Auxiliary Contact Block• For mounting between T1 & T2 or between T2 &
T3• Adjustable; provides normal, delayed or
overlapping contacts• Maximum two blocks per contactor• Alternate terminal marking tags included• 2 N.O. and 2 N.C.
100-G550…100-G860 100-EF22
Auxiliary Contact Block• For side mounting on either side of the contactor• Max. four blocks per contactor• Alternate terminal marking tags included• 1 N.O. and 1 N.C.
100-G1000…100-G1200 100-EB11
Fourth Add-On Neutral Switching Pole• Left- or right-side mountable Note: No UL/cUL
Ith AC-1 500 A
100-G550100-G700, 100-G860
100-NP500-5100-NP500-6
Note: No UL / cUL Ith AC-1 1000 A 100-G700, 100-G860100-G1000, 100-G1200
100-NP1000-6100-NP1000-7
Mechanical Latch• Mechanical life: 0.5 million operations
Direct and Impulse Contact ControlDirect and Impulse Contact Control
100-G550100-G700, 100-G860
100-FLAM5⊗100-FLAM6⊗
Mechanical Interlocks — Horizontal
100-G550/100-G550 100-MC00-5H
100-G550/100-G700, 100-G860 100-MC00-56H
100-G700, 100-G860/100-G700, 100-G860 100-MC00-6H
100-G700, 100-G860/100-G1000, 100-G1200 100-MC00-67H
100-G1000, 100-G1200/100-G1000, 100-G1200 100-MC00-7H
Mechanical Interlocks — Vertical
100-G550/100-G550 100-MC00-5V
100-G550/100-G700, 100-G860 100-MC00-56V
100-G700, 100-G860/100-G700, 100-G860 100-MC00-6V
100-G700, 100-G860/100-G1000, 100-G1200 100-MC00-67V
100-G1000, 100-G1200/100-G1000, 100-G1200 100-MC00-7V
Terminal LugsContains set of 3 lugs(2) #2…600 MCM(3) #2…600 MCM(4) #2…600 MCM
100-G550100-G700, -G860
100-G1000, 100-G1200
100-LG5100-LG6100-LG7
For use with 110…120V 220…240V 380…415V 440…480V
100-G550…100-G860 50/60 Hz KD KF KN KB
4-Pole
Standard terminal marking for mounting between T1 & T2
Alternate terminal marking for mounting between T2 & T3
2-Pole
13
14
21
22
53
54
61
62
83
84
71
72
Standard terminal marking
Alternate terminal markings
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
94
Specifications
IEC Specifications
➊ Values in ( ) with increased cross-section and cable lug➋ Power ratings: Preferred values according to IEC 60072-1
100/104-M 100/104-C, 100S/104S-C05 09 12 09 12 16 23 30 37 43 60
Coil Type : Conventional X X X X X X X X X X XElectronic — EI — — — — — — — — — — —
AC-1 Active Power Load (50 Hz)Ambient temperature 40°C
Ie ≤ 500V [A] 20 20 20 32 32 32 32 (40) ➊ 65 65 85 100690V [A] — — — 32 32 32 32 (40) ➊ 65 65 85 100
1000V [A] — — — — — — — — — — —230V [kW] 8 8 8 13 13 13 13 26 26 34 40240V [kW] 8.3 8.3 8.3 13 13 13 13 27 27 35 42400V [kW] 14 14 14 22 22 22 22 45 45 59 69415V [kW] 14 14 14 23 23 23 23 47 47 61 72500V [kW] 17 17 17 28 28 28 28 56 56 74 87690V [kW] — — — 38 38 38 38 78 78 102 120
1000V [kW] — — — — — — — — — — —Ambient temperature 60°C
Ie ≤ 500V [A] 16 16 16 32 32 32 32 65 65 80 100690V [A] — — — 32 32 32 32 65 65 80 100
1000V [A] — — — — — — — — — — —230V [kW] 6.4 6.4 6.4 13 13 13 13 26 26 25 40240V [kW] 6.7 6.7 6.7 13 13 13 13 27 27 26 42400V [kW] 11 11 11 22 22 22 22 45 45 44 69415V [kW] 12 12 12 23 23 23 23 47 47 45 72500V [kW] 14 14 14 28 28 28 28 56 56 55 87690V [kW] — — — 38 38 38 38 78 78 75 120
1000V [kW] — — — — — — — — — — —Switching of 3-phase Motors, (50Hz)Ambient temperature 60°C, AC-2, AC-3
230V [A] 6.5 12 12 12 15 20 26.5 35 38 44 62240V [A] 6.5 12 12 12 15 20 26.5 35 38 44 62400V [A] 5.3 9 12 9 12 16 23 30 37 43 60415V [A] 5.3 9 12 9 12 16 23 30 37 43 60500V [A] 4 7 7 7 10 14 20 25 30 38 55690V [A] — — — 5 7 9 12 18 21 25 34
1000V [A] — — — — — — — — — — —230V ➋ [kW] 1.5 3 3 3 4 5.5 7.5 10 11 13 18.5240V ➋ [kW] 1.5 3 3 3 4 5.5 7.5 10 11 13 18.5400V ➋ [kW] 2.2 4 5.5 4 5.5 7.5 11 15 18.5 22 32415V ➋ [kW] 2.2 4 5.5 4 5.5 7.5 11 15 20 22 32500V ➋ [kW] 2.2 4 4 4 5.5 7.5 13 15 20 25 37690V ➋ [kW] — — — 4 5.5 7.5 10 15 18.5 22 32
1000V ➋ [kW] — — — — — — — — — — —Load Carrying Capacity per UL/CSA and Lloyd’s Register of Shipping (60 Hz)General Purpose Current (enclosed)
[A] 12 12 12 25 25 30 30 55 60 63 90Rated power (enclosed)
1-phase 115V [A] 9.8 9.8 9.8 9.8 9.8 16 24 24 34 34 56230V [A] 8 10 12 10 12 17 17 28 28 40 50115V [HP] 0.5 0.5 0.5 0.5 0.5 1 2 2 3 3 5230V [HP] 1 1.5 2 1.5 2 3 3 5 5 7.5 10
3-phase 200V [A] 6.9 7.8 11 7.8 11 17.5 17.5 25.3 32.2 32.2 48.3230V [A] 6 6.8 9.6 6.8 9.6 15.2 22 28 28 42 54460V [A] 4.8 7.6 11 7.6 11 14 21 27 34 40 52575V [A] 3.9 6.1 11 9 11 17 17 27 32 32 52200V [HP] 1.5 2 3 2 3 5 5 7.5 10 10 15230V [HP] 1.5 2 3 2 3 5 7.5 10 10 15 20460V [HP] 3 5 7.5 5 7.5 10 15 20 25 30 40575V [HP] 3 5 10 7.5 10 15 15 25 30 30 50
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
95
Specifications
➌ 415 V: values in ( ) AC-3 and AC-4 lifespan -25 %➍ To be determined.
100/104-C, 100S/104S-C 100/104-D, 100S-D72 85 95 110 140 140 180 180 210 250 300 420 630 860X X X X X — X — — — — — — —— — X X — X — X X X X X X X
100 100 160 160 250 250 250 250 350 350 450 500 800 1000100 100 160 160 250 250 250 250 350 350 450 500 800 1000— — 160 160 250 250 250 250 350 350 450 500 ➍ ➍
40 40 64 64 100 100 100 100 139 139 179 199 319 39842 42 67 67 104 104 104 104 145 145 187 208 333 41669 69 111 111 173 173 173 173 242 242 312 346 554 69372 72 115 115 180 180 180 180 252 252 323 359 575 71987 87 139 139 217 217 217 217 303 303 390 433 693 866
120 120 191 191 299 299 299 299 418 418 538 598 956 1195— — 277 277 433 433 433 433 606 606 779 866 ➍ ➍
100 100 135 135 210 210 210 210 300 300 380 425 ➍ ➍
100 100 135 135 210 210 210 210 300 300 380 425 ➍ ➍
— — 135 135 210 210 210 210 300 300 380 425 ➍ ➍
40 40 54 54 84 84 84 84 120 120 151 169 ➍ ➍
42 42 56 56 87 87 87 87 125 125 158 177 ➍ ➍
69 69 94 94 145 145 145 145 208 208 263 294 ➍ ➍
72 72 97 97 151 151 151 151 216 216 273 305 ➍ ➍
87 87 117 117 182 182 182 182 260 260 329 368 ➍ ➍
120 120 161 161 251 251 251 251 359 359 454 508 ➍ ➍
— — 234 234 364 364 364 364 520 520 658 736 ➍ ➍
72 85 95 110 140 140 180 180 210 250 300 420 630 86072 85 95 110 140 140 180 180 210 250 300 420 630 86072 85 95 110 140 140 180 180 210 250 300 420 630 86072 85 95 110 (130)➌ 140 (155)➌ 140 (155)➌ 180 180 210 (227)➌ 250 (258)➌ 300 (315)➌ 420 (425)➌ 630 86067 80 95 110 115 140 140 180 210 250 300 420 630 75342 49 95 110 115 140 140 180 210 250 300 420 ➍ ➍
— — 33 40 55 55 65 65 80 95 115 160 ➍ ➍
22 25 25 32 45 45 57 57 67 80 97 135 200 25022 25 25 32 45 45 60 60 70 83 101 141 200 25040 45 45 55 75 75 101 101 118 140 170 238 355 50040 45 45 (55)➌ 55 (75)➌ 80 (90)➌ 80 (90)➌ 105 105 122 (132)➌ 145 (150)➌ 174 (185)➌ 250 355 50045 55 55 63 80 90 98 126 150 177 213 300 450 56040 45 80 100 110 132 135 176 205 250 300 425 ➍ ➍
— — 45 55 75 75 90 90 110 132 160 225 ➍ ➍
90 100 160 160 220 220 220 220 300 300 340 420 ➍ ➍
56 80 80 100 135 135 — — — — — — — —68 68 68 110 136 136 176 176 216 — — — — —5 7.5 7.5 10 15 15 — — — — — — — —15 15 15 25 30 30 40 40 50 — — — — —
62.1 78.2 78.2 120 120 120 150 150 177 221 285 414 552 69268 80 80 104 130 130 154 154 192 248 312 420 602 72065 77 77 96 124 124 180 180 180 240 302 414 590 70262 62 77 99 125 125 144 144 192 242 289 382 562 65120 25 25 40 40 40 50 50 60 75 100 150 200 25025 30 30 40 50 50 60 60 75 100 125 175 250 30050 60 60 75 100 100 150 150 150 200 250 350 500 60060 60 75 100 125 125 150 150 200 250 300 400 600 700
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
96
Specifications
IEC Specifications
➊ Power ratings at 50 Hz: Preferred values according to IEC 60072-1
100/104-M 100/104-C, 100S/104S-C05 09 12 09 12 16 23 30 37 43 60
Coil Type : Conventional X X X X X X X X X X XElectronic — EI — — — — — — — — — — —
Switching of 3-phase Motors, (50Hz)Ambient temperature 60°C, AC-4
230V [A] 6.5 12 12 12 15 20 26.5 35 38 44 62240V [A] 6.5 12 12 12 15 20 26.5 35 38 44 62400V [A] 5.3 9 9 9 12 16 23 30 37 43 60415V [A] 5.3 9 9 9 12 16 23 30 37 43 60500V [A] 4 7 7 7 10 14 20 25 30 38 55690V [A] — — — 5 7 9 12 18 21 25 34
1000V [A] — — — — — — — — — — —230V ➊ [kW] 1.5 3 3 3 4 5.5 7.5 10 11 13 18.5240V ➊ [kW] 1.5 3 3 3 4 5.5 7.5 10 11 13 18.5400V➊ [kW] 2.2 4 4 4 5.5 7.5 11 15 18.5 22 32
415V ➊ [kW] 2.2 4 4 4 5.5 7.5 11 15 20 22 32500V ➊ [kW] 2.2 4 4 4 5.5 7.5 13 15 20 25 37690V ➊ [kW] — — — 4 5.5 7.5 10 15 18.5 22 32
1000V ➊ [kW] — — — — — — — — — — —AC-4 at approximately 200,000 operations
230V [A] 2.3 3.9 3.9 4.3 6.6 9 10 12 14 16.5 25.5240V [A] 2.3 3.9 3.9 4.3 6.6 9 10 12 14 16.5 25.5
400 / 415V [A] 2 3.3 3.3 4.3 6.6 9 10 12 14 16.5 25.5500V [A] 1.9 3.2 3.2 4.3 6.6 9 10 12 14 16.5 25.5690V [A] — — — 4.3 6.6 9 10 12 14 16.5 25.5
1000V [A] — — — — — — — — — — —230V ➊ [kW] 0.37 0.75 0.75 0.75 1.5 2.2 2.2 3 3.7 4 6.3240V ➊ [kW] 0.37 0.75 0.75 0.75 1.5 2.2 2.2 3 4 4 7.5400V ➊ [kW] 0.75 1.1 1.1 1.8 3 4 4 5.5 6.3 7.5 13415V ➊ [kW] 0.75 1.1 1.1 1.8 3 4 4 5.5 6.3 7.5 13500V ➊ [kW] 0.75 1.5 1.5 2.2 3.7 5.5 5.5 7.5 7.5 10 15690V ➊ [kW] — — — 3 5.5 7.5 7.5 10 11 15 22
1000V ➊ [kW] — — — — — — — — — — —Max. switching frequency Ops/h 250 250 250 250 250 220 200 200 200 200 120
Wye-Delta (60 Hz)200V [Hp] — — — 5 5 7½ 7½ 10 15 20 30230V [Hp] — — — 5 7½ 10 10 15 20 25 40460V [Hp] — — — 10 15 20 25 30 40 50 75575V [Hp] — — — 10 15 20 25 30 40 50 75
UL/CSA Elevator Duty200V [A] — — — 7.8 11.0 11.0 17.5 25.3 25.3 32.2 32.2230V [A] — — — 6.8 9.6 15.2 15.2 22.0 28.0 28.0 42.0460V [A] — — — 7.6 11.0 14.0 21.0 27.0 27.0 34.0 40.0575V [A] — — — 6.1 9.0 11.0 17.0 22.0 27.0 32.0 41.0200V [Hp] — — — 2 3 3 5 7½ 7½ 10 10230V [Hp — — — 2 3 5 5 7½ 10 10 15460V [Hp — — — 5 7½ 10 15 20 20 25 30575V [Hp — — — 5 7½ 10 15 20 25 30 40
Star-Delta Starting (50 Hz)≤ 230V [A] 11 21 21 21 26 35 46 61 66 76 107≤ 240V [A] 11 21 21 21 26 35 46 61 66 76 107
400V [A] 9.2 16 21 16 21 28 40 52 64 74 104415V [A] 9.2 16 21 16 21 28 40 52 64 74 104500V [A] 6.9 12 12 12 17 24 35 43 52 66 95690V [A] — — — 8.6 12 16 21 31 36 43 59
1000V [A] — — — — — — — — — — —230V ➊ [kW] 3 5.5 5.5 5.5 7.5 10 13 17 20 22 32240V ➊ [kW] 3 5.5 5.5 5.5 7.5 10 13 18.5 20 22 32400V ➊ [kW] 4 7.5 10 7.5 10 13 20 25 32 40 55415V ➊ [kW] 4 7.5 11 7.5 11 15 22 25 37 40 55500V ➊ [kW] 4 7.5 7.5 7.5 11 15 22 25 32 45 63690 V ➊ [kW] — — — 7.5 10 13 18.5 25 32 40 55
1000V ➊ [kW] — — — — — — — — — — —
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
97
Specifications
➋ 415V: Values in ( ) AC-3 and AC-4 lifespan -25 %➌ To be determined.
100/104-C, 100S/104S-C 100/104-D, 100S-D72 85 95 110 140 140 180 180 210 250 300 420 630 860X X X X X — X — — — — — — —— — X X — X — X X X X X X X
72 85 95 110 140 140 180 180 210 250 300 420 ➌ ➌
72 85 95 110 140 140 180 180 210 250 300 420 ➌ ➌
72 85 95 110 140 140 180 180 210 250 300 420 ➌ ➌
72 85 95 110 (130)➋ 140 (155)➋ 140 (155)➋ 180 180 210 (227)➋ 250 (258)➋ 300 (315)➋ 420 ➌ ➌
67 80 85 105 115 140 140 170 210 250 300 360 ➌ ➌
42 49 85 105 115 140 140 170 210 250 300 360 ➌ ➌
— — 33 45 55 55 65 65 80 95 115 160 ➌ ➌
22 25 25 34 45 45 57 57 67 80 97 135 ➌ ➌
22 25 25 36 47 47 60 60 70 83 101 141 ➌ ➌
40 45 45 61 78 78 100 100 118 140 170 238 ➌ ➌
40 45 45 (55)➋ 63 (75)➋ 80 (90)➋ 80 (90)➋ 105 (110)➋ 105 (110)➋ 125 (132)➋ 145 (150)➋ 176 (185)➋ 250 ➌ ➌
45 55 55 73 80 98 98 119 147 177 213 255 ➌ ➌
40 45 80 102 110 135 135 167 205 250 293 356 ➌ ➌
— — 45 55 75 75 90 90 110 132 160 225 ➌ ➌
31 38 43 50 60 60 67 67 85 105 140 170 ➌ ➌
31 38 43 50 60 60 67 67 85 105 140 170 ➌ ➌
31 38 43 50 60 60 67 67 85 105 140 170 ➌ ➌
31 38 43 50 60 60 67 67 85 105 140 170 ➌ ➌
31 38 43 50 60 60 67 67 85 105 140 170 ➌ ➌
— — 19 23 37 37 43 43 60 72 85 105 ➌ ➌
7.5 11 13 15 17 17 20 20 25 32 45 55 ➌ ➌
7.5 11 13 15 18.5 18.5 22 22 25 32 45 55 ➌ ➌
15 20 22 25 32 32 37 37 45 55 75 90 ➌ ➌
17 20 22 25 32 32 37 37 50 55 80 100 ➌ ➌
20 25 25 32 40 40 45 45 55 75 100 110 ➌ ➌
25 32 40 45 55 55 63 63 80 100 132 160 ➌ ➌
— — 22 30 50 50 55 55 80 100 110 150 ➌ ➌
120 120 100 100 100 100 100 100 50 50 50 50 ➌ ➌
40 50 40 60 60 60 75 75 100 125 175 250 ➌ ➌
50 60 50 60 75 75 100 100 125 175 200 250 ➌ ➌
100 125 100 125 175 175 200 200 250 350 450 600 ➌ ➌
100 125 125 150 200 200 250 250 300 450 500 650 ➌ ➌
48.3 62.1 ➌ ➌ ➌ ➌ ➌ ➌ ➌ ➌ ➌ ➌ ➌ ➌
54.0 68.0 68.0 80 ➌ 104 ➌ 130 ➌ ➌ ➌ ➌ ➌ ➌
52.0 65.0 65.0 77 ➌ 96 ➌ 124 ➌ ➌ ➌ ➌ ➌ ➌
52.0 62.0 62.0 77 ➌ 77 ➌ 99 ➌ ➌ ➌ ➌ ➌ ➌
15 20 ➌ ➌ ➌ ➌ ➌ ➌ ➌ ➌ ➌ ➌ ➌ ➌
20 25 25 30 ➌ 40 ➌ 50 ➌ ➌ ➌ ➌ ➌ ➌
40 50 50 60 ➌ 75 ➌ 100 ➌ ➌ ➌ ➌ ➌ ➌
50 60 60 75 ➌ 75 ➌ 100 ➌ ➌ ➌ ➌ ➌ ➌
125 147 147 182 242 242 294 294 364 433 520 727 ➌ ➌
125 147 147 182 242 242 294 294 364 433 520 727 ➌ ➌
125 147 147 182 242 242 294 294 364 433 520 727 ➌ ➌
125 147 147 (164)➋ 182 (225)➋ 242 (268)➋ 242 (268)➋ 294 294 364 (393)➋ 433 (447)➋ 520 (546)➋ 727 (736)➋ ➌ ➌
116 139 147 182 199 242 294 294 364 433 520 727 ➌ ➌
73 85 147 182 199 242 294 294 364 433 520 727 ➌ ➌
— — 55 65 96 96 112 112 139 165 200 277 ➌ ➌
37 45 45 55 75 75 90 90 110 132 160 220 ➌ ➌
40 50 50 63 80 80 100 100 125 150 160 250 ➌ ➌
63 80 80 100 132 132 160 160 200 250 300 425 ➌ ➌
63 80 80 (90)➋ 100 (132)➋ 132 (160)➋ 132 (160)➋ 160 160 220 250 315 (335)➋ 425 (450)➋ ➌ ➌
80 90 100 132 132 160 200 200 250 315 375 530 ➌ ➌
63 80 132 160 200 220 300 300 355 425 530 750 ➌ ➌
— — 75 90 132 132 160 160 200 220 280 400 ➌ ➌
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
98
Specifications
IEC Specifications
➊ To be determined.
100/104-M 100/104-C, 100S/104S-C05 09 12 09 12 16 23 30 37 43 60
Coil Type : Conventional X X X X X X X X X X XElectronic — EI — — — — — — — — — — —
Switching of Power Transformers, AC-6a (50 Hz)
n = 30 ≤ 230V [A] 2.9 5.4 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8≤ 240V [A] 2.9 5.4 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8≤ 400V [A] 2.4 4.1 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
415V [A] 2.4 4.1 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8≤ 500V [A] 1.8 3.2 3.2 10.9 10.9 10.9 10.9 20 20 23 40.8≤ 690V [A] — — — 10.9 10.9 10.9 10.9 20 20 23 40.8
≤ 1000V [A] — — — — — — — — — — —230V [kVA] 1.2 2.2 2.2 4.3 4.3 4.3 4.3 8 8 9.2 16240V [kVA] 1.2 2.2 2.2 4.5 4.5 4.5 4.5 8.3 8.3 10 17400V [kVA] 1.7 2.8 3.7 7.5 7.5 7.5 7.5 14 14 16 28415V [kVA] 1.7 2.9 3.9 7.8 7.8 7.8 7.8 14 14 17 29500V [kVA] 1.6 2.7 2.7 9.4 9.4 9.4 9.4 17 17 20 35690V [kVA] — — — 13 13 13 13 24 24 27 49
1000V [kVA] — — — — — — — — — — —n = 20 ≤ 690V [A] — — — 16.3 16.3 16.3 16.3 30 30 34.5 61.3n = 15 ≤ 690V [A] — — — 22 22 22 22 40 40 46 82
60 Hz Peak Inrush/peak rated transformer currentn=30 [A] ➊ ➊ ➊ 10.9 10.9 10.9 10.9 20 20 23 40.8200V [kVA] ➊ ➊ ➊ 3.8 3.8 3.8 3.8 6.9 6.9 8.0 14.1208V [kVA] ➊ ➊ ➊ 3.9 3.9 3.9 3.9 7.2 7.2 8.3 14.7240V [kVA] ➊ ➊ ➊ 4.5 4.5 4.5 4.5 8.3 8.3 9.6 17.0480V [kVA] ➊ ➊ ➊ 9.1 9.1 9.1 9.1 16.6 16.6 19.1 33.9600V [kVA] ➊ ➊ ➊ 11.3 11.3 11.3 11.3 20.8 20.8 23.9 42.4660V [kVA] ➊ ➊ ➊ 12.5 12.5 12.5 12.5 22.9 22.9 26.3 46.6
60 Hz Peak Inrush/peak rated transformer currentn=20 [A] ➊ ➊ ➊ 16.3 16.3 16.3 16.3 30 30 34.5 61.3200V [kVA] ➊ ➊ ➊ 5.6 5.6 5.6 5.6 10.4 10.4 12.0 21.2208V [kVA] ➊ ➊ ➊ 5.9 5.9 5.9 5.9 10.8 10.8 12.4 22.1240V [kVA] ➊ ➊ ➊ 6.8 6.8 6.8 6.8 12.5 12.5 14.3 25.5480V [kVA] ➊ ➊ ➊ 13.6 13.6 13.6 13.6 24.9 24.9 28.7 51.0600V [kVA] ➊ ➊ ➊ 16.9 16.9 16.9 16.9 31.2 31.2 35.9 63.7660V [kVA] ➊ ➊ ➊ 18.6 18.6 18.6 18.6 34.3 34.3 39.4 70.1
60 Hz Peak Inrush/peak rated transformer currentn=15 [A] ➊ ➊ ➊ 22 22 22 22 40 40 46 82200V [kVA] ➊ ➊ ➊ 7.5 7.5 7.5 7.5 13.9 13.9 15.9 28.4208V [kVA] ➊ ➊ ➊ 7.8 7.8 7.8 7.8 14.4 14.4 16.6 29.5240V [kVA] ➊ ➊ ➊ 9.0 9.0 9.0 9.0 16.6 16.6 19.1 34.1480V [kVA] ➊ ➊ ➊ 18.1 18.1 18.1 18.1 33.3 33.3 38.2 68.2600V [kVA] ➊ ➊ ➊ 22.6 22.6 22.6 22.6 41.6 41.6 47.8 85.2660V [kVA] ➊ ➊ ➊ 24.9 24.9 24.9 24.9 45.7 45.7 52.6 93.7
Rated transformer current
Inrush current= n
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
99
Specifications
100/104-C, 100S/104S-C 100/104-D, 100S-D72 85 95 110 140 140 180 180 210 250 300 420 630 860X X X X X — X — — — — — — —— — X X — X — X X X X X X X
40.8 40.8 53 60 70 70 85 85 105 125 150 210 ➊ ➊
40.8 40.8 53 60 70 70 85 85 105 125 150 210 ➊ ➊
40.8 40.8 53 60 70 70 85 85 105 125 150 210 ➊ ➊
40.8 40.8 53 60 70 70 85 85 105 125 150 210 ➊ ➊
40.8 40.8 53 60 70 70 85 85 105 125 150 210 ➊ ➊
40.8 40.8 53 60 70 70 85 85 105 125 150 210 ➊ ➊
— — 53 60 70 70 85 85 105 125 150 210 ➊ ➊
16 16 21 24 28 28 34 34 42 50 60 84 ➊ ➊
17 17 22 25 29 29 35 35 44 52 62 87 ➊ ➊
28 28 37 42 48 48 59 59 73 87 104 145 ➊ ➊
29 29 38 43 50 50 61 61 75 90 108 151 ➊ ➊
35 35 46 52 61 61 74 74 91 108 130 182 ➊ ➊
49 49 64 72 84 84 102 102 125 149 179 251 ➊ ➊
— — 92 104 121 121 147 147 182 217 260 364 ➊ ➊
61.3 61.3 80 90 105 105 128 128 158 188 225 315 ➊ ➊
82 82 107 120 140 140 170 170 210 250 300 420 ➊ ➊
40.8 40.8 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
14.4 14.4 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
14.7 14.7 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
17.0 17.0 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
33.9 33.9 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
42.4 42.4 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
46.6 46.6 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
61.3 61.3 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
21.2 21.2 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
22.1 22.1 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
25.5 25.5 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
51.0 51.0 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
63.7 63.7 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
70.1 70.1 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
82 82 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
28.4 28.4 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
29.5 29.5 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
34.1 34.1 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
68.2 68.2 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
85.2 85.2 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
93.7 93.7 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
100
Specifications
IEC Specifications
➊ To be determined.
100/104-M 100/104-C, 100S/104S-C05 09 12 09 12 16 23 30 37 43 60
Coil Type : Conventional X X X X X X X X X X XElectronic — EI — — — — — — — — — — —
Switching of 3-phase Capacitors, AC-6b (50 Hz)Inductance of leads between capacitors in parallel: min. 6 µH (100-C09…-C30 contactors: min. 30 µH)Single capacitor 40°C 230V [kVar] — — — 8 8 8.5 9 14 14 24 28
240V [kVar] — — — 8 8 8.5 9 14 14 25 29400V [kVar] — — — 8 8 10 12.5 20 24 35 48415V [kVar] — — — 8 8 10 12.5 20 25 35 50500V [kVar] — — — 8 8 10 12.5 20 25 35 50690V [kVar] — — — 8 8 10 12.5 20 25 35 50
1000V [kVar] — — — — — — — — — — —60°C 230V [kVar] — — — 8 8 8.5 9 12.5 12.5 18 28
240V [kVar] — — — 8 8 8.5 9 12.5 12.5 18 29400V [kVar] — — — 8 8 10 12.5 20 21.5 30 42415V [kVar] — — — 8 8 10 12.5 20 22 30 42500V [kVar] — — — 8 8 10 12.5 20 25 30 42690V [kVar] — — — 8 8 10 12.5 20 25 30 42
1000V [kVar] — — — — — — — — — — —Group capacitors 40°C 230V [kVar] — — — 5 5 8 9 12.5 14 20 28
240V [kVar] — — — 5 5 8 9 12.5 14 20 29400V [kVar] — — — 5 5 8 10 15 20 25 40415V [kVar] — — — 5 5 8 10 15 20 25 40500V [kVar] — — — 5 5 8 10 15 20 25 40690V [kVar] — — — 5 5 8 10 15 20 25 40
1000V [kVar] — — — — — — — — — — —60°C 230V [kVar] — — — 5 5 8 9 12.5 12.5 18 28
240V [kVar] — — — 5 5 8 9 12.5 12.5 18 29400V [kVar] — — — 5 5 8 10 15 20 25 40415V [kVar] — — — 5 5 8 10 15 20 25 40500V [kVar] — — — 5 5 8 10 15 20 25 40690V [kVar] — — — 5 5 8 10 15 20 25 40
1000V [kVar] — — — — — — — — — — —60 Hz Single Capacitor — 40°C
200V [kVar] ➊ ➊ ➊ 5 5 8 9 12.5 14 20 28230V [kVar] ➊ ➊ ➊ 5 5 8 9 12.5 14 20 29460V [kVar] ➊ ➊ ➊ 5 5 8 10 15 20 25 40600V [kVar] ➊ ➊ ➊ 5 5 8 10 15 20 25 40
60 Hz Group Capacitors — 40°C 200V [kVar] ➊ ➊ ➊ 5 5 8 9 12.5 12.5 18 28230V [kVar] ➊ ➊ ➊ 5 5 8 9 12.5 12.5 18 29460V [kVar] ➊ ➊ ➊ 5 5 8 10 15 20 25 40600V [kVar] ➊ ➊ ➊ 5 5 8 10 15 20 25 40
Switching of LampsGas discharge lamps AC-5a open [A] 18 18 18 22.5 25 28 29 40.5 45 77 81
closed [A] 14.5 14.5 14.5 22.5 25 28 29 37 41 57 77Individually compensated:Max. capacitance at expected Short-circuit current of 10 kA [µF] 750 750 750 1 000 1 000 1 000 1 000 2 700 2 700 3 200 4 000
20 kA [µF] 400 400 400 500 500 500 500 1 350 1 350 1 600 2 00050 kA [µF] — — — 200 200 200 200 540 540 640 800
Filament AC-5b 230/240V [A] 9.3 9.3 9.3 12 16 18 22 30 37 43 60Switching of Low Inductive Loads in Home Appliances and Similar Applications (50 Hz)AC-7a 230V [A] — — — 32 32 32 32 45 45 63 —
400V [A] — — — 32 32 32 32 45 45 63 —440V [A] — — — 32 32 32 32 45 45 63 —
Switching of Motor Load for Home Appliances (50 Hz)AC-7b 230V [A] — — — 10.5 14 19 23 30 — — —
400V [A] — — — 9 12 16 20 30 — — —440V [A] — — — 7.5 10 13.5 18 27 — — —
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
101
Specifications
100/104-C, 100S/104S-C 100/104-D, 100S-D72 85 95 110 140 140 180 180 210 250 300 420 630 860X X X X X — X — — — — — — —— — X X — X — X X X X X X X
28 28 45 45 70 70 70 70 98 98 125 139 ➊ ➊
29 29 48 48 73 73 73 73 102 102 131 145 ➊ ➊
48 48 78 78 120 120 120 120 170 170 218 242 ➊ ➊
50 50 80 80 125 125 125 125 176 176 226 252 ➊ ➊
55 60 98 98 150 150 150 150 212 212 273 303 ➊ ➊
55 60 133 133 208 208 208 208 293 293 376 418 ➊ ➊
— — 193 193 300 300 300 300 424 424 546 606 ➊ ➊
28 28 33 33 60 60 60 60 84 84 106 119 ➊ ➊
29 29 35 35 63 63 63 63 87 87 111 124 ➊ ➊
48 48 58 58 100 100 100 100 145 145 184 206 ➊ ➊
50 50 60 60 105 105 105 105 151 151 191 214 ➊ ➊
50 55 73 73 128 128 128 128 182 182 230 258 ➊ ➊
50 55 100 100 175 175 175 175 251 251 318 356 ➊ ➊
— — 145 145 253 253 253 253 364 364 461 515 ➊ ➊
28 28 45 40 70 70 70 70 98 98 125 139 ➊ ➊
29 29 47 45 73 73 73 73 102 102 131 145 ➊ ➊
48 48 58 75 98 98 120 120 170 170 218 242 ➊ ➊
50 50 60 78 98 98 123 123 170 176 226 252 ➊ ➊
50 50 60 78 100 100 123 123 172 212 273 303 ➊ ➊
50 50 60 78 100 100 123 123 174 247 356 418 ➊ ➊
— — 60 80 100 100 125 125 177 251 361 606 ➊ ➊
28 28 33 35 58 58 58 58 84 84 106 119 ➊ ➊
29 29 35 38 60 60 60 60 87 87 111 124 ➊ ➊
48 48 58 58 98 98 100 100 145 145 184 206 ➊ ➊
50 50 60 60 98 98 105 105 151 151 191 214 ➊ ➊
50 50 60 73 100 100 123 123 172 182 230 258 ➊ ➊
50 50 60 78 100 100 123 123 174 247 318 356 ➊ ➊
— — 60 80 100 100 125 125 177 251 361 515 ➊ ➊
28 28 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
29 29 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
50 50 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
50 50 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
28 28 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
29 29 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
50 50 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
50 50 ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
85 90 144 144 225 225 225 225 315 315 405 420 ➊ ➊
81 90 121.5 121.5 189 189 189 189 270 270 342 382.5 ➊ ➊
4 000 4 700 — — — — — — — — — — ➊ ➊
2 000 2 350 — — — — — — — — — — ➊ ➊
800 940 — — — — — — — — — — ➊ ➊
70 76 107 120 140 140 170 170 273 273 300 420 ➊ ➊
— — — — — — — — — — — — ➊ ➊
— — — — — — — — — — — — ➊ ➊
— — — — — — — — — — — — ➊ ➊
— — — — — — — — — — — — ➊ ➊
— — — — — — — — — — — — ➊ ➊
— — — — — — — — — — — — ➊ ➊
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
102
Specifications
Specifications
100/104-M 100/104-C, 100S/104S-C05 09 12 09 12 16 23 30 37 43 60
Coil Type : Conventional X X X X X X X X X X XElectronic — EI — — — — — — — — — — —
Switching of Hermetically Sealed Cooling Compressor Motors - manual reset of overload release (50 Hz)AC-8a 400V [A] — — — 12 16 22 32 38 45 63 72
500V [A] — — — 12 16 22 32 38 45 63 72690V [A] — — — 8 10 14 20 28 35 42 56
- automatic reset of overload release
AC-8b 400V [A] — — — 5.5 7 9.3 12 13 14 16 24
500V [A] — — — 5.5 7 9.3 12 13 14 16 24690V [A] — — — 5.5 7 9.3 12 13 14 16 24
Switching of DC LoadsNon-inductive or slightly inductive loads or resistance furnaces DC-1 at 60°C
1 pole 24V [A] 6 9 9 25 25 32 32 45 45 50 7048/60V [A] 4/1 6/1.5 6/1.5 20 20 20 20 25 25 30 40
110V [A] 0.6 1 1 6 6 6 6 8 8 9 11220V [A] 0.2 0.3 0.3 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2440V [A] 0.08 0.1 0.1 0.4 0.4 0.4 0.4 0.4 0.4 0.5 0.5
2 poles in series 24V [A] 6 9 9 25 25 32 32 45 45 50 7048/60V [A] 6 8 8 25 25 32 32 45 45 50 70
110V [A] 4 6 6 25 25 32 32 45 45 50 70220V [A] 0.8 1.2 1.2 8 8 8 10 10 10 10 15440V [A] 0.2 0.3 0.3 1 1 1 1 1 1 1 1.5
3 poles in series 24V [A] 6 9 9 25 25 32 32 45 45 63 9048/60V [A] 6 9 9 25 25 32 32 45 45 63 90
110V [A] 6 9 9 25 25 32 32 45 45 63 90220V [A] 3 4 4 25 25 32 32 45 45 50 70440V [A] 0.4 0.6 0.6 3 3 3 3 3.5 3.5 4 5
Shunt-wound MotorsStarting, reverse current braking, reversing, stepping DC-3, 60°C
3 poles in series 24V [A] 5 9 9 25 25 32 32 45 45 63 9048/60V [A] 4 6 6 25 25 32 32 45 45 50 70
110V [A] 2 3 3 20 20 25 25 30 30 35 70220V [A] 0.8 1.2 1.2 6 6 6 10 15 15 20 25440V [A] 0.15 0.2 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
Series-wound MotorsStarting, reverse current braking, reversing, stepping DC-5, 60°C
3 poles in series 24V [A] 5 9 9 25 25 32 32 45 45 63 9048/60V [A] 2 3 3 25 25 32 32 45 45 50 70
110V [A] 0.6 1 1 20 20 25 25 30 30 35 70220V [A] 0.1 0.1 0.1 6 6 6 10 15 15 20 25440V [A] — — — 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
Short Time Withstand ICW, 60°C
10 s [A] 60 96 96 170 170 170 215 300 304 375 700Resistance and Power DissipationMain current circuit resistance [mΩ] 5.5 5.5 5.5 2.7 2.7 2.7 2 2 2 1.5 0.9Power dissipation by all circuits at Ie AC-3/400V [W] 0.46 1.3 2.4 0.66 1.2 2.1 3.2 5.4 8.2 8.3 9.7
Total power dissipationat Ie AC-3/400V AC control [W] 1.9 2.7 3.8 3.3 3.8 4.7 6.2 8.4 11.2 11.5 11
DC control [W] 3.0 3.8 4.9 6.7 7.2 8.1 12.4 14.6 17.4 18.4 11LifespanMechanical AC control [Mio. operations] 10 10 10 13 13 13 13 13 13 12 10DC control [Mio. operations] 20 20 20 13 13 13 13 13 13 13 10Electrical AC-3 (400 V)[Mio. operations] 0.7 0.7 0.7 1.3 1.3 1.3 1.3 1.3 1.3 1 1Weight
AC Non-Reversing kg (lbs.) 0.16 (0.35) 0.16 (0.35) 0.16 (0.35) 0.39 (0.86) 0.39 (0.86) 0.39 (0.86) 0.39 (0.86) 0.48 (1.06) 0.49 (1.08) 0.51 (1.12) 1.45 (3.20)
Reversing kg (lbs.) — — — 0.85 (1.89) 0.85 (1.89) 0.85 (1.89) 0.85 (1.89) 1.08 (2.39) 1.08 (2.39) 1.15 (2.54) 3.14 (6.92)
DC Non-Reversing kg (lbs.) 0.16 (0.35) 0.16 (0.35) 0.16 (0.35) 0.6 (1.32) 0.6 (1.32) 0.6 (1.32) 0.73 (1.61) 0.85 (1.87) 0.85 (1.87) 1.0 (2.20) 1.47 (3.24)
Reversing kg (lbs.) — — — 1.27 (2.81) 1.27 (2.81) 1.27 (2.81) 1.53 (3.39) 1.81 (4.0) 1.81 (4.0) 2.13 (4.7) 3.22 (7.1)
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
103
Specifications
➊ Values in brackets refer to electronic coil (EI) version.➋ To be determined.
100/104-C, 100S/104S-C 100-D, 100S-D72 85 95 110 140 140 180 180 210 250 300 420 630 860X X X X X — X — — — — — — —— — X X — X — X X X X X X X
85 100 — — — — — — — — — — ➋ ➋
85 100 — — — — — — — — — — ➋ ➋
67 80 — — — — — — — — — — ➋ ➋
30 35 — — — — — — — — — — ➋ ➋
30 35 — — — — — — — — — — ➋ ➋
30 35 — — — — — — — — — — ➋ ➋
80 80 120 120 210 210 210 210 — — — — ➋ ➋
40 40 120 120 210 210 210 210 — — — — ➋ ➋
11 11 120 120 210 210 210 210 — — — — ➋ ➋
2 2 3 3 4 4 4 4 — — — — ➋ ➋
0.5 0.5 0.6 0.6 1 1 1 1 — — — — ➋ ➋
80 80 120 120 210 210 210 210 — — — — ➋ ➋
80 80 120 120 210 210 210 210 — — — — ➋ ➋
80 80 120 120 210 210 210 210 — — — — ➋ ➋
15 15 120 120 210 210 210 210 — — — — ➋ ➋
1.5 1.5 3 3 4 4 4 4 — — — — ➋ ➋
90 100 120 120 210 210 210 210 — — — — ➋ ➋
90 100 120 120 210 210 210 210 — — — — ➋ ➋
90 100 120 120 210 210 210 210 — — — — ➋ ➋
80 80 120 120 210 210 210 210 — — — — ➋ ➋
5 5 11 11 11 11 11 11 — — — — ➋ ➋
90 100 120 120 210 210 210 210 — — — — ➋ ➋
70 80 120 120 210 210 210 210 — — — — ➋ ➋
70 80 120 120 210 210 210 210 — — — — ➋ ➋
25 30 120 120 210 210 210 210 — — — — ➋ ➋
0.6 0.6 3 3 4 4 4 4 — — — — ➋ ➋
90 100 80 80 120 120 120 120 — — — — ➋ ➋
70 80 80 80 120 120 120 120 — — — — ➋ ➋
70 80 80 80 120 120 120 120 — — — — ➋ ➋
25 30 80 80 120 120 120 120 — — — — ➋ ➋
0.6 0.6 1.2 1.2 2 2 2 2 — — — — ➋ ➋
700 700 1060 1060 1 390 1 390 1 390 1 390 2 300 2 570 2 800 4 290 ➋ ➋
0.9 0.9 0.4 0.4 0.42 0.42 0.42 0.42 0.22 0.22 0.18 0.15 0.19 0.14
14 19.5 8.7 13.2 (13.8)➊ 24.6 24.6 36.3 36.3 29.4 41.7 48.6 79.5 78.4 103.2
13.8 17.5 18.2 22.7 34.5 34.5 46.5 46.5 39.4 51.7 58.6 89.5 105.4 133.213.8 17.5 16.7 20.9 32.5 32.5 44.5 44.5 37.4 49.7 56.6 87.5 105.4 133.2
10 10 10 10 10 10 10 10 10 10 10 10 2 210 10 10 10 10 10 10 10 10 10 10 10 2 21 1 1 1 1 1 1 1 1 1 1 1 ➋ ➋
1.45 (3.2) 1.45 (3.2) 3.3 (7.28)[3.8 (8.38)]➊
3.3 (7.28)[3.8 (8.38)]➊ 3.3 (7.28) 3.8 (8.38) 3.3 (7.28) 3.8 (8.38) 7.5 (16.53) 7.5 (16.53) 7.5 (16.53) 7.5 (16.53) 28.6 (63) 28.6 (63)
3.14 (6.92) 3.14 (6.92) ➋ ➋ ➋ ➋ ➋ ➋ ➋ ➋ ➋ ➋ ➋ ➋
1.47 (3.24) 1.47 (3.24) 3.3 (7.28)[3.8 (8.38)]➊
3.3 (7.28)[3.8 (8.38)]➊ 3.3 (7.28) 3.8 (8.38) 3.3 (7.28) 3.8 (8.38) 7.5 (16.53) 7.5 (16.53) 7.5 (16.53) 7.5 (16.53) 28.6 (63) 28.6 (63)
3.22 (7.1) 3.22 (7.1) ➋ ➋ ➋ ➋ ➋ ➋ ➋ ➋ ➋ ➋ ➋ ➋
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
104
Specifications
➊ Pozidriv No. 2 / Blade No. 3 screw ➋ Pozidriv No. 2 / Blade No. 4 screw➌ Hexagonal socket screw
100/104-M 100/104-C, 100S/104S-C
05 09 12 09 12 16 23 30 37 43 60 72 85
Coil Type : Conventional X X X X X X X X X X X X X
Electronic — EI — — — — — — — — — — — — —
Conductor Cross Sections - Main ContactsTerminal type
➊ ➊ ➋ ➌
(1) conductor [mm2](2) conductors [mm2]
0.75…2.50.75…2.5
1…41…4
2.5…102.5…10
2.5…162.5…10
2.5…352.5…25
(1) conductor [mm2](2) conductors [mm2]
0.75…2.50.75…2.5
1.5…61.5…6
2.5…162.5…16
2.5…252.5…16
2.5…502.5…35
b max. [mm]
c max. [mm]
s max. [mm]
Ø min. [mm]
— — — — —
— — — — —
— — — — —
— — — — —
Recommended torque [Nm] 1…1.5 1…2.5 2.5…4 2.5…4 3.5…6
Cross section per UL/CSA [AWG] 18…14 16…10 14…4 14…4 14…1
Recommended torque [lb-in] 7…15 9…22 22…35 22…35 31…53
With terminal lug kit — — — — —
Cross section per UL/CSA [AWG] — — — — —
Recommended torque [lb-in] — — — — —
With Frame Terminal Block — — — — —
top opening [mm2]bottom opening[mm2]
— — — — —
top opening [mm2]bott. opening [mm2]
— — — — —
b max. [mm]s top [mm]s bottom [mm]
— — — — —
Recommended torque [Nm] — — — — —
Cross section per UL/CSA top [AWG] — — — — —
bottom [AWG] — — — — —
Recommended torque [lb-in] — — — — —
b
c
s
c
sb
b
c
s
bs s
b
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
105
Specifications
➍ Hexagonal screw➎ 25…95 mm2 with sleeve per DIN 46228
100-D, 100S-D
95 110 140 140 180 180 210 250 300 420 630 860
X X X — X — — — — — — —
X X — X — X X X X X X X
➍ ➍ ➍ ➍
——
——
——
——
——
——
——
——
——
——
20 25 30 52 52
10 12.5 15 22 22
2 x 5 2 x 5 2 x 6 2x8 2x8
6.1 8.3 10.5 13 13
8…10 10…12 16 68 68
— — — — —
70…90 90…110 375 600 600
100-DL110 ➌ 100-DL180 ➌ 100-DL420 ➌ 100-DL630 100-DL860
6…2/0 6…250 MCM 2/0…600 MCM 2X2/0…500MCM
4X2/0…500MCM
70…90 90…110 130…150 400 400
100-DTB110 ➌ 100-DTB180 ➌ 100-DLB420 ➌ — —
16…3516…70
16…3516…95
25…240 ➎25…240 — —
16…5016…95
16…5016…120
25…30025…300 — —
163…93…12
203…93…14
254…204…20
— —
8…10 10…12 20…25 — —
6…1 / 0 AWG 6…1 / 0 AWG 4 AWG…600 MCM — —
6…3 / 0 AWG 6 AWG…250 MCM 4 AWG…600 MCM — —
70…90 90…110 180…220 — —
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
106
Specifications
Coil Data
100/104-M 100/104-C, 100S/104S-C05 09 12 09 12 16 23 30 37 43 60 72 85
Coil Type : Conventional X X X X X X X X X X X X XElectronic — EI — — — — — — — — — — — — —
Operating Limits50 Hz, 60 Hz, 50/60 Hz pick-up [x Us] 0.85…1.1 0.85…1.1 0.85….1.1
dropout [x Us] 0.35…0.65 0.3…0.6 0.3…0.6DC control pick-up [x Us] 0.85…1.1 0.8…1.1 0.8…1.1
dropout [x Us] 0.1…0.25 0.1…0.6 0.1…0.6Coil Consumption50 Hz, 60 Hz, 50/60 Hz pick-up [VA/W]
hold-in [VA/W]22/20 70/50 70/50 80/60 130/90 200/1104/1.4 8/2.6 9/3 9/3 10/3.2 16/4.5
DC control pick-up [W]hold-in [W]
2.5 6.5 9.2 9.2 10.1 2002.5 6.5 9.2 9.2 10.1 4.5
Operating TimesAC closing delay [ms]
opening delay [ms]15…40 15…30 15…30 15…30 15…30 20…4015…25 10…60 10…60 10…60 10…60 10…60
With RC module opening delay [ms] 15…25 10…60 10…60 10…60 10…60 10…60DC closing delay [ms]
opening delay [ms]18…40 40…70 40…70 50…80 50…80 20…406…12 7…15 7…15 7…15 7…15 —
With integrated diode opening delay [ms] 8…12 14…20 17…23 17…23 17…23 ≤ 220V 20…35With external diode opening delay [ms] 35…50 70…95 80…125 80…125 80…125 > 220V 80…125
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
107
Specifications
➊ Electronic coil drives are controlled for minimizing performance, but this control may shortly require (< 1ms) peak load when energizing.This must be taken into account for the proper sizing of supply devices, all-or-nothing relays and cross-sections of coil supply lines. Please contact your nearest Rockwell Automation distributor for detailed information
100/104-D, 100S/104S-D95/110 140/180 95 110 140 180 210 250 300 420 630 860
X X — — — — — — — — — —— — X X X X X X X X X X
0.85…1.1 0.85…1.1 0.8…1.10.3…0.6 0.3…0.5 0.3…0.8
0.85…1.1 0.85…1.1 0.85…1.10.3…0.6 0.3…0.5 0.3…0.8
650/310 370/243 ➊ 590/355 ➊ 1915/1720 ➊50/10 12/6 15/7 33/30540 190 ➊ 375 ➊ 1980 ➊
8 6 7 30
20…47 75…90 75…90 60…1006…12 30…60 30…60 70…1459…18 — — —
27…47 75…90 75…90 60…10012…20 30…60 30…60 70…14512…20 — — —
— — — —
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
108
Specifications
➊ To be determined.
100/104-M 100/104-C, 100S/104S-C05 09 12 09 12 16 23 30 37 43 60 72 85
Coil Type : Conventional X X X X X X X X X X X X XElectronic — EI — — — — — — — — — — — — —
Short Circuit Coordination (Max.Fuse or Circuit Breaker Rating)
Per IEC 947-4-1 (contactor and fuses only)
DIN Fuses - gG, gL 100 kA Available Fault Current Type "1" (690V) [A] 25 25 25 50 50 50 80 125 125 160 250 250 250 Type "2" (400V) [A] 16 16 16 25 35 35 40 80 80 100 160 160 160 Type "2" (690V) [A] — — — 25 35 35 40 80 80 100 160 160 160 BS88 Fuses 80 kA Available Fault Current Type "1" (690V) [A] ➊ ➊ ➊ 25 32 35 50 63 80 100 100 125 160 Type "2" (690V) [A] ➊ ➊ ➊ 25 32 35 50 63 80 100 100 125 160Per UL 508 and CSA 22.2 No. 14(contactor and fuses or circuit breaker only) UL Class K5 and RK5 Fuses 5 kA Available Fault Current UL Listed Combination (600V) [A] 40 40 40 35 40 70 90 110 125 150 200 — — UL Class K5 and RK5 Fuses 10 kA Available Fault Current UL Listed Combination (600V) [A] — — — — — — — — — — — 250 300 UL Class L Fuses 18 kA Available Fault Current UL Listed Combination (600V) [A] — — — — — — — — — — — — — UL Class L Fuses 42 kA Available Fault Current UL Listed Combination (600V) [A] — — — — — — — — — — — — — UL Class CC and CSA HRCI-MISC Fuses 100 kA Available Fault Current UL Listed Combination (600V) - "Type 2" [A] — — — 15 20 20 30 — — — — — — UL Class J and CSA HRCI-J Fuses 100 kA Available Fault Current UL Listed Combination (600V) - "Type 2" [A] — — — 15 20 20 30 40 50 50 80 100 100 UL Inverse-Time Circuit Breaker 5 kA Available Fault Current UL Listed Combination (480V) [A] — — — 30 30 50 50 125 125 125 250 — — UL Listed Combination (600V) [A] — — — — — — — 125 125 125 250 — — UL Inverse-Time Circuit Breaker 10 kA Available Fault Current UL Listed Combination (600V) [A] — — — — — — — — — — — 250 250 UL Inverse-Time Circuit Breaker 18 kA Available Fault Current UL Listed Combination (600V) [A] — — — — — — — — — — — — — UL Inverse-Time Circuit Breaker 42 kA Available Fault Current UL Listed Combination (600V) [A] — — — — — — — — — — — — —
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
109
Specifications
➊ To be determined.
100/104-D, 100S/104S-D95/110 140/180 95 110 140 180 210 250 300 420 630 860
X X — — — — — — — — — —— — X X X X X X X X X X
100 kA Available Fault Current
250 250 315 315 355 355 500 500 630 630 ➊ ➊
200 200 250 250 315 315 400 400 500 500 ➊ ➊
200 200 250 250 315 315 400 400 500 500 ➊ ➊
80 kA Available Fault Current➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
5 kA Available Fault Current— — — — — — — — — — — —
10 kA Available Fault Current225 250 350 350 450 450 500 — — — — —
18 kA Available Fault Current— — — — — — — 700 700 1000 — —
42 kA Available Fault Current— — — — — — — — — — 2500 2500
100 kA Available Fault Current— — — — — — — — — — — —
100 kA Available Fault Current➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊
5 kA Available Fault Current— — — — — — — — — — — —— — — — — — — — — — — —
10 kA Available Fault Current125 150 200 200 250 250 300 — — — — —
18 kA Available Fault Current— — — — — — — 350 400 500 — —
42 kA Available Fault Current— — — — — — — — — — 1200 1200
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
110
Specifications
Auxiliary Contacts and Auxiliary Contact Blocks
➊ Only with 100-DS2-B11
Auxiliary contact for 100-M Auxiliary contact for 100-C, 100S-C Auxiliary contact for 100-D
Internal Blocks Internal Front-mounted Side-mounted ConventionalElectronically
compatible
Switching of AC LoadsAC-12 Ith at 40 °C [A] 16 10 25 10 10 16 0.1
at 60 °C [A] 12 6 20 6 6 12 at 250 VAC-15 at rated voltage of
(1…100 mA)at
3…125 V
24 V [A] — — 10 6 6 —42 / 48 V [A] — — 10 6 6 —
110 V [A] — — 10 6 6 —230 V [A] 6 2 10 5.5 5.5 5.5240 V [A] 5 2 10 5 5 5400 V [A] 2.5 1 6 3 3 3415 V [A] 2 1 5 2.5 2.5 2.5500 V [A] 1.25 0.6 2.5 1.6 1.6 1.6690 V [A] — — 1 1 1 1
Switching of DC LoadsDC-12 L/R< 1 ms resistive loads at
24 VDC [A] 6 6 12 12 6 16 —48 VDC [A] 4 2 9 9 3.2 9 —
110 VDC [A] 0.6 0.6 3.5 3.5 0.45 3.5 —220 VDC [A] 0.2 0.2 0.55 0.55 0.18 0.55 —440 VDC [A] 0.08 0.08 0.2 0.2 0.1 0.2 —
DC-14 L/R< 15 ms inductive loads with economy resistor in series at
24 VDC [A] 4 4 9 9 2 9 —48 VDC [A] 2.5 1.2 5 5 1.6 5 —
110 VDC [A] 0.4 0.4 2 2 .3 2 —220 VDC [A] 0.12 0.12 0.4 0.4 0.12 0.4 —440 VDC [A] 0.05 0.05 0.16 0.16 0.05 0.16 —
DC-13 switching electromagnets at
(1…100 mA)at
3…125 V
24 VDC [A] 5 2 5 5 3 548 VDC [A] 0.6 0.6 2 2 1.5 2
110 VDC [A] 0.45 0.45 0.7 0.7 0.6 0.7220 VDC [A] 0.25 0.1 0.25 0.25 0.3 0.25440 VDC [A] 0.04 0.04 0.12 0.12 0.2 0.12
Fuse gGShort-circuit protection with no Welding of contacts per IEC 947-5
[A] 16 10 10 10 10 16 —
[A] 16 10 10 10 10 16 —
Safe isolation between load and auxiliary circuit 250 V
between load and auxiliary circuit 500 V
Min. switching capacity 17 V DIN 19240 [mA] 5 5 5 5 5 5 1 ➊Load Carrying Capacity per UL/CSARated voltage AC [V] max. 600 max. 600 max. 600 max. 250
Continuous rating 40 °C [A] 10 General purpose 10 10 1010 General
purpose0.1
Switching capacity AC [A] Heavy pilot duty (A 600) A 600Heavy pilot duty
(A 600)0.1
Rated voltage DC [V] max. 600 max. 600 max. 600 max. 250
Switching capacity [A] Light pilot duty (Q 600) P 600 Q 600Standard pilot duty (P 600)
0.1
Bulletins 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-DContactors
111
Specifications
General
100-M 100-C, 100S-C 100-D, 100S-D
05…09 12 09…85 95…420
Rated Isolation Voltage Ui
IEC, AS, BS, SEV, VDE 0660 [V] 500 690 1000per UL, NEMA, CSA, EEMAC [V] 600 600 600
Rated Impulse Voltage Withstand Uimp [kV]8 8 12
Rated Voltage Ue
AC 50/60 Hz [V] 230, 240, 400, 415, 500 115, 230, 400, 500, 690 230, 240, 400, 415, 500, 690, 1000DC [V] 24, 48, 110, 220, 440 24, 48, 110, 220, 440 24, 48, 110, 220, 440Insulation Class of the Coil Class «B» per IEC 85 Class «F» per IEC 85 Class «B» per VDE 0660,
Table 22Rated coil frequency AC 50/60 Hz, DC AC 50/60 Hz, DC AC 50 Hz, 50/60 Hz, DCAmbient TemperatureStorage [°C] -55…+80 -55…+80 -40…+80 Operation at rated voltage [°C] -25…+60 -25…+60 -25…+60 at 70 °C 15 % current reduction against 60 °C valuesClimatic Withstand IEC 68-2 IEC 68-2 IEC 68-2Max. Altitude of Installation Site [m] 2000 NN, per IEC 947-4 2000 NN, per IEC 947-4 2000 NN, per IEC 947-4Protection Class IP2X IP2X (in connected state) IP00 IEC 529 / DIN 40 050Single contactor cover — IP10 IEC 529 / DIN 40 050Contactor with frame terminal block — IP20 IEC 529 / DIN 40 050Auxiliary contact — IP20 IEC 529 / DIN 40 050Protection against Accidental Contact Finger and back-of-hand proof
per VDE 0106, part 100Finger and back-of-hand proof
per VDE 0106, part 100Finger and back-of-hand proof
per VDE 0106, part 100Resistance to Shock IEC 68-2 IEC 68-2 IEC 68-2Resistance to Vibration IEC 68-2 IEC 68-2 IEC 68-2
Positively Guided Contacts per SUVAContactor contacts among each other.Auxiliary contact block contacts next to
each other.But not between contactor and auxiliary
contact block.
Restricted guidance guarantees without restrictions from contactor to auxiliary
contact and auxiliary contact to contactor.
No restricted guidance 100-FL, 100-FPT
—
Standards IEC 60947; EN 60947; UL 508; CSA 22.2. No. 14
IEC 60947; EN 60947; UL 508; CSA 22.2. No. 14
IEC 60947; EN 60947; UL 508; CSA 22.2. No. 14
Approvals CE, UL Listed, CSA, Germanischer Lloyd, Bureau Veritas, Lloyd’s Register of
Shipping, Maritime Register of
Shipping
CE, UL Listed,
CSA,
CE, UL Listed, CSA, RINA,Bureau Veritas, Maritime Register of
Shipping, American Bureau of Shipping, Germanischer Lloyd, Lloyd’s Register of
Shipping, Wershe Veritas in preparation
CE, UL Listed, CSA
Bulletin 100-GIEC Contactors
112
Specifications
Electrical Data
➊ At rated voltage 415V and rated current: Life span -25%
Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
AC-1, Three-phase Switching - IECAmbient temperature: 40°C
Ie ≤ 690V [A] 760 1,000 1,100 1,200 1,350
230V [kW] 303 398 438 478 538
240V [kW] 316 416 457 499 561
400V [kW] 527 693 762 831 935
415V [kW] 546 719 791 863 970
500V [kW] 658 866 953 1,039 1,169
690V [kW] 908 1,195 1,315 1,434 1,613
Ambient temperature: 60°C
Ie ≤ 690V [A] 605 800 870 960 1,085
230V [kW] 241 319 347 382 432
240V [kW] 251 333 362 399 451
400V [kW] 419 554 603 665 752
415V [kW] 435 575 625 690 780
500V [kW] 524 693 753 831 940
690V [kW] 723 956 1,040 1,147 1,297
Continuous Current - UL/CSA [A]General Purpose Rating 40°C
520 700 810 — 1215
Switching of 3-phase Motors - IEC
AC-2, AC-3 230/240V [A] 550 700 860 1,000 1,200
50Hz/60°C 400/415V [A] 550 700 860 1,000 1,200
500V [A] 550 700 860 1,000 1,200
690V [A] 500 630 700 860 1,000
230V [kW] 179 228 280 326 391
240V [kW] 187 238 293 340 408
400V [kW] 312 414 509 592 710
415V [kW] 324 430 528 628 737
500V [kW] 407 518 636 756 888
690V [kW] 510 657 730 897 1,043
AC-4 at 200,000 operations
50Hz 230/240V [A] 140 180 210 260 300
400/415V [A] 140 180 210 260 300
230V [kW] 45 57 67 83 97
240V [kW] 47 60 70 87 101
400V [kW] 78 101 118 146 170
415V [kW] 81 105 122 151 176
AC-4, Squirrel-cage motors with reversing and jogging at 20,000 (25,000), operations
230/240V [A] 360 430 520 (630) (700)
400/415V ➊ [A] 350 420 520 (630) (700)
230V [kW] 116 139 170 (205) (228)
240V [kW] 120 151 177 (214) (245)
400V [kW] 198 238 295 (357) (414)
415V [kW] 206 247 300 (359) (424)
113
Bulletin 100-GIEC Contactors
Specifications, Continued
Electrical Data, ContinuedCat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
Switching of 3-phase Motors - UL/CSA
60Hz/60°C 200V [A] 414 552 692 — 1,185
230V [A] 360 602 722 — 1,130
460V [A] 414 590 708 — 1,062
575V [A] 336 472 576 — 864
200V [Hp] 150 200 250 — 450
230V [Hp] 150 250 300 — 450
460V [Hp] 350 500 600 — 900
575V [Hp] 350 500 600 — 900
Rated making capacity
AC-3 Ie ≤ 415V [A] 5,500 7,000 8,600 10,000 12,000
500V [A] 5,500 7,000 8,600 10,000 12,000
690V [A] 5,000 6,300 7,000 8,600 10,300
Rated breaking capacity
AC-3 Ie ≤ 240V [A] 5,500 7,000 8,000 8,000 9,600
400V [A] 4,500 5,600 6,900 8,000 9,600
415V [A] 4,500 5,600 6,900 8,000 9,600
500V [A] 4,500 5,600 6,900 8,000 9,600
690V [A] 4,000 5,700 5,600 6,900 8,000
Star-Delta Starting
50Hz 230V [A] 953 1,212 1,490 1,732 2,078
240V [A] 953 1,212 1,490 1,732 2,078
400V [A] 953 1,212 1,490 1,732 2,078
415V [A] 953 1,212 1,490 1,732 2,078
500V [A] 953 1,212 1,490 1,732 2,078
690V [A] 831 1,091 1,195 1,490 1,732
230V [kW] 310 395 485 565 677
240V [kW] 324 412 507 589 707
400V [kW] 540 717 882 1,025 1,250
415V [kW] 561 745 915 1,088 1,227
500V [kW] 705 897 1,102 1,309 1,538
690V [kW] 883 1,138 1,247 1,554 2,078
Wye-Delta Starting
60Hz 230V [Hp] 250 400 500 650 750
460V [Hp] 600 800 1,000 1,300 1,500
575V [Hp] 600 800 1,000 1,500 1,500
Short-circuit Protection of Contactors without Overload Relay
Fuse gG (aM) Type 1 coordination(per IEC 947-4-1) 500V [A] (630) 800 1,000 1,000 1,250
690V [A] (630) 800 1,000 1,000 1,000
Switching of Three-phase CapacitorInductivity of dispatching between parallel switched capacitors: min. 6 µH
Single capacitors40°C 230V [kVar] 180 220 250 290 330
240V [kVar] 200 250 300 325 360
400V [kVar] 320 400 450 500 575
415V [kVar] 350 430 500 550 630
500V [kVar] 450 520 600 660 750
690V [kVar] 580 700 800 875 1,000
55°C 230V [kVar] 150 180 220 275 325
240V [kVar] 170 200 260 300 350
400V [kVar] 280 330 400 460 550
415V [kVar] 300 360 450 500 600
500V [kVar] 360 420 540 600 720
690V [kVar] 500 580 720 800 950
Bulletin 100-GIEC Contactors
114
Specifications, Continued
Electrical Data, ContinuedCat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
Capacitor Banks 40°C 230V [kVar] 180 220 250 290 330
240V [kVar] 200 250 300 325 360
400V [kVar] 320 400 450 500 575
415V [kVar] 350 430 500 550 630
500V [kVar] 450 520 600 660 750
690V [kVar] 580 700 800 875 1,000
55°C 230V [kVar] 150 180 220 275 325
240V [kVar] 170 200 260 300 350
400V [kVar] 280 330 400 460 550
415V [kVar] 300 360 450 500 600
500V [kVar] 360 420 540 600 720
690V [kVar] 500 580 720 800 950
DC Switching
Switching of non- or slightly inductive loads, resistance furnaces DC-1 at 60°C
1-Pole 24/48V [A] 605 800 870 960 1,085
2-Poles in series 24/48V [A] 605 800 870 960 1,085
3 Poles in series 24/48V [A] 605 800 870 960 1,085
110V [A] 480 560 630 800 900
220V [A] 315 400 450 500 600
Shunt-wound Motors
Starting, plugging, reversing, plugging
DC-3 at 60°C3 Poles in series 24/48V [A] 605 800 870 960 1,085
Series-wound Motors
Starting, plugging, reversing, plugging
DC-5 at 60°C3 Poles in series 24/48V [A] 605 800 870 960 1,085
Lighting Loads
Elec. Discharge. Lamps - AC - 5a,
Non-Compensated [A] 450 570 700 850 1,000
Compensated [A] 360 460 550 660 800
Incandescent Lamps - AC - 5b, Electrical Endurance @ 100,000 ops [A] 315 440 500 560 630
Switching Power Transformers AC - 6a
Inrush = n · Ie [A]
Ie Rated transformer current [A] 259 330 405 470 570
n = 30 400V AC [kVA] 179 228 280 325 395
500V AC [kVA] 224 286 350 407 493
690V AC [kVA] 281 355 395 485 563
n = 20 [A] 389 495 608 700 850
n = 15 [A] 517 660 810 945 1130
Rated Short-time Withstand ICW, 60°C1 s [A] 5,500 7,000 8,000 10,000 12,000
4 s [A] 5,500 7,000 8,000 10,000 12,000
10 s [A] 4,400 5,600 6,900 8,000 9,600
15 s [A] 3,800 5,000 6,000 7,400 8,500
60 s [A] 2,300 2,800 3,400 4,000 4,800
240 s [A] 1,300 1,800 2,000 2,300 2,700
900 s [A] 850 1,150 1,350 1,600 1,900
Minimum cooling time at zero current [Min.] 60 60 60 60 60
Resistance and Energy Dissipation
Main circuit resistance [mW] 0.11 0.1 0.08 0.06 0.05
Total energy dissipation at Ie AC-3 [W] 99 147 177 180 216
Excess energy dissipation at Ie AC-3
AC Control [W] 110 172 202 250 286
DC Control [W] 109 169 199 240 276
115
Bulletin 100-GIEC Contactors
Specifications, Continued
Mechanical Data
➊ Quantity indicated in ( ).
Coil Data
➋ Accelerates➌ Delays
Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
Life Span in Millions of Operations
Mechanical AC Control [Mil.] 5 5 5 1 1
DC Control [Mil.] 5 5 5 1 1
Shipping Weights AC Control [kg] 13.8 26.4 28.4 50.3 53.4
[lb] 30.4 58.1 62.5 110.8 117.6
DC Control [kg] 13.8 26.4 28.4 50.3 53.4
[lb] 30.4 58.1 62.5 110.8 117.6
Terminals ➊
Terminal dimensions [mm] 6 x 40 8 x 50 8 x 50 10 x 50 10 x 60
Terminal screw hole size [mm] (1) x ø13 (1) x ø13 (1) x ø15 (2) x ø13 (2) x ø13
Terminations - PowerType Hexagonal Bolt
Direct Connection
b max.[ mm]c max. [mm]s max. [mm]∅ min. [mm]
50 60 60 60 60
20 20 25 25 25
2 x 5 2 x 5 2 x 6 2 x 6 2 x 8
12.5 13 15 2 x 13 2 x 13
Recommended Torque [Nm] 50 60 75 60 60
[ft.-lb] 37 44 55 44 44
Conductor/Wire Terminations ➊
Bus bar (width) [mm] 40 50 50 50 60
Terminal lugs 100-LG5 100-LG6 100-LG6 100-LG7 100-LG7
Wire size per IEC 60947-1 [mm2] (2) x 35…300 (3) x 35…300 (3) x 35…300 (4) x 35…300 (4) x 35…300
Wire size per UL/CSA [AWG] (2) x #2…600 MCM (3) x #2…600 MCM (3) x #2…600 MCM (4) x #2…600 MCM (4) x #2…600 MCM
Hex screw [in] 1/2 3/8 3/8 3/8 3/8
Recommended Torque [Nm] 42 62 62 56 56
[lb-in] 375 550 550 500 500
Auxiliary Contact [mm2] (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5
Coils [mm2] (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5
Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
Operating Limits
AC- 50 Hz Pick-up [x Us] 0.85…1.1
Drop-out [x Us] 0.2…0.5 0.2…0.5 0.3…0.6
AC- 60 Hz Pick-up [x Us] 0.85…1.1
Drop-out [x Us] 0.2…0.5 0.2…0.5 0.3…0.6
DC Control Pick-up [x Us] 0.85…1.1
Drop-out [x Us] 0.2…0.5 0.2…0.5 0.3…0.6
Pickup and Holding Power
AC- 50 Hz Pick-up [VA] 800…950 1,350…1,600 2,400
Hold-in [VA] 9…11 21…25 70
AC- 60 Hz Pick-up [VA] 800…950 1,350…1,600 2,400
Hold-in [VA] 9…11 21…25 70
DC Control Pick-up [W] 700…850 1,300…1,550 2,100
Hold-in [W] 8…10 18…22 60
Operating Times: Switching Delay
AC Making delay [ms] 50…100 50…100
Breaking delay [ms] 20…50 ➋ /150…200/500…1,000 ➌ 25…50
DC Making delay [ms] 50…100 50…100
Breaking delay [ms] 20…50 ➋ /150…200/500…1,000 ➌ 25…50
Bulletin 100-GIEC Contactors
116
Specifications, Continued
Auxiliary Contacts
General Data
Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
AC Switching
AC-1 Ith at 40°C [A] 16 16
at 60°C [A] 12 12
AC-15 at rated voltage
120V [A] 6 6
230V [A] 3 3
240V [A] 3 3
400V [A] 2 2
415V [A] 2 2
500V [A] 1.5 1.5
690V [A] 1 1
DC SwitchingDC-13 control of electromagnets
24V DC [A] 6 6
48V DC [A] 3 3
110V DC [A] 1 1
220V DC [A] 0.5 0.5
Back-up FuseShort-circuit protection without contact welding per IEC 60947-5
Fuse gG [A] 10 16
Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
Rated Isolation Voltage Ui
IEC, AS, BS, SEV, VDE 0660 [V]UL/CSA
1,000V600V
690V600V
Impulse Voltage Uimp
1 minute per IEC 947-4 [kV] 3,500V 2,500V
Rated Voltage - Main Control Ue
AC 50/60 Hz [V] 230, 240, 400, 415, 460, 500, 575, 690V 230, 240, 400, 415, 460, 500, 575, 690V
DC [V] 24, 48, 110, 220, 440V
Operating Frequency for AC Loads 50/60 Hz [Hz] 180/hr. for 0.25s start time – 42/hr. for 1s start time
Insulation Class of the Magnetic Coil Class B per VDE 0660, table 22
Rated Frequency of the Coil AC 50/60 Hz, DC
Ambient Temperature
Storage -40°C…+80°COperation at rated current -25°C…+60°CClimatic Withstand Damp alternating conditions cyclical, per DIN 50 016 and 40 046, Part 38, IEC 68
Altitude 2000 m above sea level, per IEC 60947-1
Type of Protection IP00 IEC 529/DIN 40 050
Certifications IEC 60947, CEI 17-2, 17-3; UTE NF C 63-110; BS 5424; VDE 0660-1; NEMA; ICS
Approvals UL, cUL, CE, Lloyd’s Register of Shipping
117
Bulletin 100/104-M, 100/104-C, 100/104-D, 100S/104S-C, 100S-D, 100-GIEC Contactors
Specifications, Continued
Electrical life in Utilization Category
Contact Life for Mixed Utilization Categories AC-3 and AC-4:In many applications, the utilization category cannot be defined as either purely AC-3 or AC-4. In those applications, the electrical life of the contactor can be estimated from the following equation:
Lmixed = Lac3/ [1+Pac4*(Lac3/Lac4-1)], where:
Lmixed Approximate contact life in operations for a mixed AC-3/AC-4 utilization category application.
Lac3 Approximate contact life in operations for a pure AC-3 utlilization category (from the AC-3 life-load curves).
Lac4 Approximate contact life in operations for a pure AC-4 utilization category (from the AC-4 life-load curves).
Pac4 Percentage of AC-4 operations.
Ie Rated operational current I Making CurrentUe Rated voltage Ic Breaking CurrentUr Recovery voltage U Off-load voltage
➊ Plugging is understood as stopping or reversing the motor rapidly by reversing motor primary connections while the motor is running.➋ Inching (jogging) is understood as energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism.
Bulletin 100-C/104-C IEC contactors are designed for superior performance in a wide variety of applications. When selecting IEC products, the user must give consideration to the specific load, utilization category and required electrical life of the application. The life-load curves shown here are based on Rockwell Automation tests according to the requirements defined in IEC 60947-4-1. Since contact life in application is dependent on environmental conditions and duty cycle, actual application contact life may vary from that indicated by the curves shown here.
To find the contactor’s estimated electrical life, follow these guidelines:1. Identify the appropriate utilization category from the table below.2. Choose the graph for the utilization category selected.3. Locate the intersection of the life-load curve for the appropriate contactor with the application’s operational current (le) found on the horizontal axis.4. Read the estimated contact life along the vertical axis.
Test Conditions Making BreakingI/Ie U/Ue cosϕ Ic/Ie Ur/Ue cosϕ
AC-1 Resistance Furnaces:Non inductive or slightly inductive loads 1 1 0.95 1 1 0.95
AC-2 Slip-ring motors:Starting and reversing 2.5 1 0.65 2.5 1 0.65
AC-3 Squirrel - cage motors:Starting and stopping of running motors
Ie < 17 AIe > 17 A
66
11
0.650.35
66
0.170.17
0.650.35
AC-4 Squirrel - cage motors:Starting, plugging ➊ , inching ➋
Ie < 17 AIe > 17 A
66
11
0.650.35
66
11
0.650.35
AC-15 Solenoids:Contactors, valves and lifting magnets 10 1 0.7 1 1 0.4
Bulletin 100-M/104-MIEC Contactors
118
Specifications
Electrical Life
100-M05
100-M09
100-M12
0.011 10 100
1
0.1
10
(AC-1)
100-M
Rated operating current Ie AC-2 [A](Dashed curves - - - - AC-1 only, open)
Con
tact
life
[mill
ions
of o
pera
tions
]
Electrical Life; Ue = 400 / 415 VACAC-3 Switching of squirrel-cage motors while startingAC-1 Non- or slightly inductive loads, resistance furnaces
0.010.1 1 10
1
0.1
10
100-M05
100-M09; 100-M12
100-M
Rated operating current Ie [A]
Con
tact
life
[mill
ions
of o
pera
tions
]
Electrical Life; Ue = 400 / 415 VACAC-4 Stepping of squirrel-cage motors
119
Bulletin 100-C/104-CIEC Contactors
Specifications, Continued
Life-Load Curves
0.1
1
10
1 10 100
C09
C12
C30
C23
C16
C85
C72
C60
C43
C37
Rated operating current Ie AC-1 [A]
Con
tact
life
[mill
ions
of o
pera
tions
]
40°C Non- or slightly inductive loads, resistance furnaces; Ue = 230…690 VAC-1
0.1
1
10
1 10 100
C09
C72
C60
C43
C37
C30
C23
C16
C12
C85
Rated operating current Ie AC-2 [A]
Con
tact
life
[mill
ions
of o
pera
tions
]
Switching of slip-ring motors; Ue = 230…400…460 VAC-2
Bulletin 100-C/104-CIEC Contactors
120
Specifications, Continued
Life-Load Curves
0.1
1
10
1 10 100
C09
C12
C23
C16
C85
C72
C60
C43
C37
C30
Rated operating current Ie AC-3 [A]
Con
tact
life
[mill
ions
of o
pera
tions
]
Switching of squirrel-cage motors while starting; Ue = 230…400…460 V
AC-3
0.1
1
10
1 10 100
C09
C23
C12
C60
C30
C16
C85
C72
C43
C37
Rated operating current Ie AC-3 [A]
Con
tact
life
[mill
ions
of o
pera
tions
]
Switching of squirrel-cage motors while starting; Ue = 500…575 V
121
Bulletin 100-C/104-CIEC Contactors
Specifications, Continued
Life-Load Curves
0.1
1
10
1 10 100
C09
C23
C85
C72
C60
C43
C37
C30
C12
C16
Rated operating current Ie AC-3 [A]
Con
tact
life
[mill
ions
of o
pera
tions
]
Switching of squirrel-cage motors while starting; Ue = 690 V
AC-3
0.1
1
10
1 10 100
C09 C43
C37
C30
C23
C16
C12
C85
C72
C60
Rated operating current Ie AC-4 [A]
Con
tact
life
[mill
ions
of o
pera
tions
]
Switching of squirrel-cage motors; Ue = 230…690 V
AC-4
Bulletin 100-C/104-CIEC Contactors
122
Specifications, Continued
Life-Load Curves
Heavy Duty Starting and Regular Short-time Operation
0.1
1
10
1 10 100
C09
C85
C72
C60
C43
C37
C30
C23
C16
C12
Rated operating current Ie AC-3/AC-4 [A]
Con
tact
life
[mill
ions
of o
pera
tions
]
10 % AC-4 Mixed operation of squirrel-cage motors; Ue = 230…400…460 V
AC-3 & AC-4
1
10
100
10 100 1000 10000
100-
C23
100-
C30
/37
100-
C43
100-
C60
/72/
85
Starting current/1Short-time current [A]
max
. Sta
rtin
g tim
e/Lo
adin
g tim
e [s
]
Bulletin 100-C Contactors
123
Bulletin 100-C/104-CIEC Contactors
Specifications, Continued
Maximum Operating Rates
0
500
1000
1500
2000
2500
3000
0 10 20 30 40 50 60 70 80 90 100
C09/C12/C16/C23
C30/C37
C43
C60/C72/C85
P/Pn [%]
Per
mis
sibl
e sw
itchi
ng r
ate
[ops
/h]
40°C Non- or slightly inductive loads, resistance furnaces; Ue = 230…690 V
AC-1
100
1000
10000
0 10 20 30 40 50 60 70 80 90 100
C09/C12/C16C23/C30/C37/C43
C60C72C85
P/Pn [%]
Per
mis
sibl
e sw
itchi
ng r
ate
[ops
/h]
Stepping of slip-ring motors; Ue = 230…460 V
AC-2
Bulletin 100-C/104-CIEC Contactors
124
Specifications, Continued
Maximum Operating Rates
100
1000
10000
0 10 20 30 40 50 60 70 80 90 100
C09/C12/C16C23/C30/C37/C43C60/C72/C85
P/Pn [%]
Per
mis
sibl
e sw
itchi
ng r
ate
[ops
/h]
Switching of squirrel-cage motors while starting; Ue = 230…460 V
Relative operating time 40 %, Starting time tA = 0.25 s
AC-3
10
100
1000
0 10 20 30 40 50 60 70 80 90 100
C09C12
C23/C30C37/C43/C60
C85
C16
C72
P/Pn [%]
Per
mis
sibl
e sw
itchi
ng r
ate
[ops
/h]
Stepping of squirrel-cage motors; Ue = 230…460 V
Starting time tA = 0.25 s
AC-4
125
Bulletin 100-C/104-CIEC Contactors
Specifications
Electrical Life
0.1
1
10
10 100 1000
420
300
250
210
180
140
110
95
(AC-1)
100-D
Rated operating current Ie AC-3 [A](Dashed curves ------ AC-1 only, open)
Con
tact
life
[mill
ions
of o
pera
tions
]
AC-3 Switching of squirrel-cage motors while startingAC-1 Non- or slightly inductive loads, resistance furnaces; Ue = 400 V
0.01
0.1
1
10
1000
420
300
250
210
180
140
110
95
100101
100-D
Rated operating current Ie AC-4 [A]
Con
tact
life
[mill
ions
of o
pera
tions
]
AC-4 Stepping of squirrel-cage motors; Ue = 400 V
Bulletin 100-C/104-CIEC Contactors
126
Specifications
Electrical Life
0.1
1
10
10 100 1000
420
300
250
210
180
140
110
95
100-D
Rated operating current Ie AC-3 / AC-4 [A]
Con
tact
life
[mill
ions
of o
pera
tions
]
AC-3 90 % & AC-4 10 % Mixed operation of squirrel-cage motors; Ue = 400 V
127
Bulletin 100-GIEC Contactors
Specifications, Continued
Electrical Life
100-G550100-G700100-G860100-G1000100-G1200
10
1
0.1
10
Con
tact
Life
(m
illio
ns o
f ope
ratio
ns)
1000 10000
Rated Operational Current Ie AC-4 [A]
0.01
0.001100
100-G550100-G700100-G860100-G1000100-G1200
10
1
100
Con
tact
Life
(m
illio
ns o
f ope
ratio
ns)
1000 10000
Rated Operational Current Ie AC-1/AC-3 [A](Curves for AC-1 only, open)
0.1
100-G550 (AC-1)100-G700 (AC-1)100-G860 (AC-1)100-G1000 (AC-1)100-G1200 (AC-1)
100-G550…100-G1200
AC-3 Switching of Running Three-phase Motors, Uz = 380…460V ACAC-1 Non or Slightly Inductive Loads, Resistance Furnaces
AC-4 Jogging of Squirrel-cage Motors, Uz = 380…460V AC
Bulletin 100-GIEC Contactors
128
Specifications, Continued
Electrical Life, Continued
Permissible Switching Rate
100-G550100-G700100-G860100-G1000100-G1200
10
1
0.1
100
Con
tact
Life
(m
illio
ns o
f ope
ratio
ns)
1000 10000
Rated Operational Current Ie AC-3/AC-4 [A]
0.01
100-G550…100-G1200AC-3 90% Switching of Running Motors, Uz = 380…460V ACAC-4 10% Jogging
100-G550100-G700100-G860100-G1000, 100-G1200100-G1200 (short time)
1000
100
100
Per
mis
sibl
e S
witc
hing
Rat
e (o
pera
tions
/hou
r)
1000 10000
Rated Operational Current Ie [A]
10
100-G550…100-G1200Switching of Running Squirrel-cage Motors AC-3, Uz = 380…460V ACStarting Time ts = 0.25 s, Relative Running Time 40%
129
Bulletin 100-GIEC Contactors
Specifications, Continued
Permissible Switching Rate, Continued
100-G550100-G700100-G860100-G1000,100-G1200100-G1200 (short-time)
1000
100
10
100
Per
mis
sibl
e S
witc
hing
Rat
e (o
pera
tions
/hou
r)
1000 10000
Rated Operational Current Ie [A]
100-G550…100-G1200Switching of Running Squirrel-cage Motors AC-3, Uz = 380…460V ACStarting Time ts = 1 s, Relative Running Time 40%
100-G550100-G700; 100-G860100-G1000,100-G1200100-G860100-G1200
1000
100
10100
Per
mis
sibl
e S
witc
hing
Rat
e (o
pera
tions
/hou
r)
1000 10000
Starting Current Is [A]
100-G550…100-G1200Switching of Starting Motors (AC-2 and AC-4), Uz = 380…460V ACStarting Time ted = 1 s (< ts)
Bulletin 100-MIEC Miniature Contactors
130
Approximate Dimensions
Bulletin 100-M Miniature Contactors and AccessoriesDimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
78(3-7/64)
48(1-29/32)
4(1/16)
10(25/64)
19.5(25/32)
22(7/8)
23.5(15/16)41
(1-41/64)
45(1-13/16)
4(1/16)
5(3/16)
31.5(1-1/4)
11(7/16)
5(3/16)
56(2-15/64)
47(1-7/8)
77(3-5/64)
74(2-59/64)
48(1-29/32)
50(1-31/32)
67(2-43/64)
4(1/16)
45(1-13/16)
5(3/16)
50(1-31/32)
56(2-15/64)
77(3-5/64
)74(2-59/64)
48(1-29/32)
4(1/16)
45(1-13/16)
120(4-51/64)
32(1-9/32)
47(1-7/8)
45(1-13/16)
4(1/16)
4(1/16)
11(7/16)
30(1-13/64)
90(3-39/64)
Mini-Contactor or Mini-Relay With Auxiliary Contact Adder Deck or Timer Mounted to Front.
Cat. No. 100-M or 700-M
Mini-Contactor or Mini-Relay With Surge Suppressor Mounted to Front.
Cat. No. 100-M or 700-M
Mini-Contactor or Mini-Relay With Auxiliary Contact Adder Deck Mounted to Front and Timer Mounted to Side
Cat. No. 100-M or 700-M
Surge SuppressorCat. No. 199-MSM
Reversing Mini-Contactors With Auxiliary Contact Adder DeckCat. No. 104-M
Timer With DIN Rail Mounting Adapter on 35 mm DIN RailCat. No. 196-MT
Timer With DIN Rail Mounting Adapter on 35 mm DIN RailCat. No. 196-MT
131
Bulletin 100-C/104-CIEC Contactors
Approximate Dimensions
Bulletin 100-C Contactors and AccessoriesDimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
AC Contactors
DC Contactors
Accessories
Cat. No. a b c c1 c2 ∅ d d1 d2
100-C09…100-C23 45(1-25/32)
81(3-3/16)
80.5(3-11/64)
75.5(3-3/32)
6(1/4)
2 - 4.5(2 - 3/16)
60(2-23/64)
35(1-25/64)
100-C30, 100-C37 45(1-25/32)
81(3-3/16)
97.5(4)
92.6(3-49/64)
6.5(17/64)
2 - 4.5(2 - 3/16)
60(2-23/64)
35(1-25/64)
100-C43 54(2-1/8)
81(3-3/16)
100.5(4-7/64)
95.6(3-7/8)
6.5(17/64)
2 - 4.5(2 - 3/16)
60(2-23/64)
45(1-25/32)
100-C60…100-C85 72(2-53/64)
122(4-51/64)
117(4-49/64)
111.5(4-35/64)
8.5(21/64)
4 - 5.4(4 - 7/32)
100(3-15/16)
55(2-11/64)
Cat. No. a b c c1 c2 ∅ d d1 d2
100-C09Z…100-C16Z 45(1-25/32)
81(3-3/16)
106.5(4-3/16)
101.5(4)
6(1/4)
2 - 4.5(2 -3/16)
60(2-23/64)
35(1-25/64)
100-C23Z 45(1-25/32)
81(3-3/16)
123.5(4-55/64)
119(4-43/64)
6(1/4)
2 - 4.5(2 -3/16)
60(2-23/64)
35(1-25/64)
100-C30…100-C37 45(1-25/32)
81(3-3/16)
141.5(5-37/64)
136.5(5-3/8)
6.5(17/64)
2 - 4.5(2 -3/16)
60(2-23/64)
35(1-25/64)
100-C43Z 54(2-1/8)
81(3-3/16)
144.5(5-11/16)
140(5-33/64)
6.5(17/64)
2 - 4.5(2 -3/16)
60(2-23/64)
45(1-25/32)
100-C60D…100-C85D 72(2-53/64)
122(4-51/64)
117(4-49/64)
111.5(4-35/64)
8.5(21/64)
4 - 5.4(4 -7/32)
100(3-15/16)
55(2-11/64)
Contactors with mm (inches)Auxiliary contact block for front mounting 2- or 4-pole c/c1 + 39 (c/c1 + 1-37/64)Auxiliary contact block for side mounting 1- or 2-pole a + 9 (a + 23/64)Pneumatic Timing Module c/c1 + 58 (c/c1 + 2-23/64)Electronic Timing Module on coil terminal side b + 24 (b + 15/16)Mechanical Interlock on side of contactor a + 9 (a + 23/64)Mechanical Latch c/c1 + 61 (c/c1 + 2-31/64)Interface Module on coil terminal side b + 9 (b + 23/64)Surge Suppressor on coil terminal side b + 3 (b + 1/8)Labeling with label sheet
marking tag sheet with clear covermarking tag adapter for System V4 / V5marking tag adapter for System Bul. 1492W
+ 0+ 0
+ 5.5+ 5.5
(+ 0)(+ 0)
(+ 7/32)(+ 7/32)
Terminal Lug Kit 100-C09…C23100-C30…37100-C43100-C60…C85
b + 53b + 44b + 52b + 99
(b + 2-3/32)(b + 1-47/64)
(b+ 2-3/64)(b + 3-7/8)
Paralleling Links 100-C09…C23
100-C30…C37
b + 78c + 9/5b + 85
(b + 3-1/16)(c + 3/8)
(b + 3-11/32)
c2
c
c1
➊➋
Mounting Position
DC Contactors
AC Contactors
Bulletin 100S/104SSafety Contactors
132
Approximate Dimensions
Bulletin 100S/104S Contactors and AccessoriesDimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
AC Contactors
DC Contactors
Accessories
Cat. No. a b c c1 c2 ∅ d d1 d2
100S-C09…100S-C23 45(1-25/32)
81(3-3/16)
119.5(4-3/4)
114.5(4-43/64)
6(1/4)
2 - 4.5(2 - 3/16)
60(2-23/64)
35(1-25/64)
100S-C30, 100S-C37 45(1-25/32)
81(3-3/16)
136.5(5-37/64)
131.6(5-11/32)
6.5(17/64)
2 - 4.5(2 - 3/16)
60(2-23/64)
35(1-25/64)
100S-C43 54(2-1/8)
81(3-3/16)
139.5(5-11/16)
134.6(5-29/64)
6.5(17/64)
2 - 4.5(2 - 3/16)
60(2-23/64)
45(1-25/32)
100S-C60…100S-C85 72(2-53/64)
122(4-51/64)
156(6-11/32)
150.5(6-1/8)
8.5(21/64)
4 - 5.4(4 - 7/32)
100(3-15/16)
55(2-11/64)
Cat. No. a b c c1 c2 ∅ d d1 d2
100S-C09Z…100S-C16Z 45(1-25/32)
81(3-3/16)
145.5(5-49/64)
140.5(5-37/64)
6(1/4)
2 - 4.5(2 -3/16)
60(2-23/64)
35(1-25/64)
100S-C23Z 45(1-25/32)
81(3-3/16)
162.5(6-7/16)
158(6-1/4)
6(1/4)
2 - 4.5(2 -3/16)
60(2-23/64)
35(1-25/64)
100S-C30…100S-C37 45(1-25/32)
81(3-3/16)
180.5(7-5/32)
175.5(6-61/64)
6.5(17/64)
2 - 4.5(2 -3/16)
60(2-23/64)
35(1-25/64)
100S-C43Z 54(2-1/8)
81(3-3/16)
183.5(7-17/64)
179(7-3/32)
6.5(17/64)
2 - 4.5(2 -3/16)
60(2-23/64)
45(1-25/32)
100S-C60D…100S-C85D 72(2-53/64)
122(4-51/64)
156(6-11/32)
150.5(6-1/8)
8.5(21/64)
4 - 5.4(4 -7/32)
100(3-15/16)
55(2-11/64)
Contactors with mm (inches)Auxiliary contact block for side mounting 1- or 2-pole a + 9 (a + 23/64)Electronic Timing Module on coil terminal side b + 24 (b + 15/16)Mechanical Interlock on side of contactor a + 9 (a + 23/64)Interface Module on coil terminal side b + 9 (b + 23/64)Surge Suppressor on coil terminal side b + 3 (b + 1/8)Labeling with label sheet
marking tag sheet with clear covermarking tag adapter for System V4 / V5marking tag adapter for System Bul. 1492W
+ 0+ 0
+ 5.5+ 5.5
(+ 0)(+ 0)
(+ 7/32)(+ 7/32)
c2
c
c1
➊➋
Mounting Position
AC Contactors and Control Relays
DC Contactors and Control Relays
133
Bulletin 100-DIEC Contactors
Approximate Dimensions
Bulletin 100-D Contactors and Accessories Dimensions in millimeters. Dimensions are not intended to be used for manufacturing purposes.
Mounting Position
➊ Early make and/or late break➋ Electronically suited auxiliary contact block
Cat. No. a b c c1 ød d1 d2 øe e1 e2 e3 e4
100-D95, 100-D110 120 170 156 110.5 5.2 145 100 M6 16 38.5 147 8
100-D195-EI…100-D180-EI, 100-D140, 100-D180 120 170 156 110.5 5.2 145 100 M8 20 39 160 10
100-D210-EI…100-D420-EI 155 205 180 110.5 6.5 180 130 M10 25 48 193 12.5
100-D630-EI…100D-860-EI 255 310 265 110.5 10 230 225 M12 40 70 291 22
Contactor with [mm]
Auxiliary contact block 100-DS1…100-DS2…
aa + 13.5 each
Mechanical interlock 100-DM… a + a
Frame terminal block 100-DTB110100-DTB180100-DTB420
b + 7 eachb + 7 each
b + 8.5 each
Label holder c…+ 5
d2
a c
e1
e2 c1
øe
➊
bd1 e3e4
ød
Bulletin 100S-DIEC Contactors
134
Approximate Dimensions
Bulletin 100S-D Contactors and Accessories Dimensions in millimeters. Dimensions are not intended to be used for manufacturing purposes.
Mounting Position
➊ Early make and/or late break➋ Electronically compatible auxiliary contact block
Cat. No. a b c c1 ød d1 d2 øe e1 e2 e3 e4
100S-D95, 100S-D110 120 170 156 110.5 5.2 145 100 M6 16 38.5 147 8
100S-D195-EI…100S-D180-EI, 100S-D140, 100S-D180 120 170 156 110.5 5.2 145 100 M8 20 39 160 10
100S-D210-EI…100S-D420-EI 155 205 180 110.5 6.5 180 130 M10 25 48 193 12.5
100S-D630-EI…100S-D860-EI 255 310 265 110.5 10 230 225 M12 40 70 291 22
Contactor with [mm]
Auxiliary contact block 100-DS1…100-DS2…
aa + 13.5 each
Mechanical interlock 100-DM… a + a
Frame terminal block 100-DTB110100-DTB180100-DTB420
b + 7 eachb + 7 each
b + 8.5 each
Label holder c…+ 5
d2
a c
e1
e2 c1
øe
➊
bd1 e3e4
ød
135
Bulletin 100-GIEC Contactors
Approximate Dimensions
Bulletin 100-G Contactors and AccessoriesDimensions are in millimeters. Dimensions are not intended for manufacturing purposes.
Mounting Position
Cat. No. a b b1 c c1 ød d1 d2 øe e1 e2
100-G550 220 258 228 225 164 9 220 110 12.5 40 79
100-G700 280 307 277 291 203 11 280 175 13 50 101
100-G860 280 361 325 291 203 11 280 175 15 50 101
100-G1000 334 490 434 345 231 13.5 380 120 2x13 60 100
100-G1200 334 490 434 345 231 13.5 380 120 2x13 60 100
Contactor with: [mm]
Auxiliary contact block a
side-by-side 100-G550/100-G550 a+42+a
100-G700, -860/100-G700, -860 a+32+a
Mechanical interlock 100-G1000, -1200/100-G1000, -1200 a+46+a
100-G550/100-G700, -860 a+37+a
100-G700, -860/100-G1000, -1200 a+73+a
stacked vertically 100-G550/100-G550 b+56 + b
100-G700, -860/100-G700, -860 b/2+380…480+b/2
100-G1000, -1200/100-G1000, -1200 b+120…170+b
100-G550/100-G700, -860 b/2+400+b/2
100-G700, -860/100-G1000, -1200 b/2+570+b/2
4th add-on neutral switching pole 100-G550 a+74
100-G700, -860 a+68
100-G1000, -1200 a+76
Mechanical latch 100-G550 b+59
100-G700 b+64
100-G860 b+37
d2a
d1 b1 b
c
e1
e2 c1
øeød
25° 25° 25° 25°
Bulletin 100QCapacitor-Switching Contactors
136
Approximate Dimensions
Bulletin 100Q Capacitor Switching ContactorsDimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Cat. No.AC-Operated DC-Operated
h1 h2 h1 h2
100Q-C16 120(4-23/32)
115(4-17/32)
146(5-3/4)
141(5-9/16)
100Q-C37 137(5-3/8)
132(5-3/16)
181(7-1/8)
176(6-15/16)
9 945
60
35
81.
5
105
Ø 4.5
h2
h1
137
Bulletin 100LElectrically Held Lighting Contactors
Approximate Dimensions
Bulletin 100L Lighting Contactors and AccessoriesDimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Open Type
IP42 (Type 1)
IP66 (Type 3/4/12)
Cat. No. AWide
BHigh
CDeep D E F G H J K
100L-C20F⊗ 4 200(7-7/8)
300(11-13/16)
160(6-5/16)
236(9-9/32)
76(3)
62(2-7/8)
17.5(11/16)
313(12-5/16)
105(4-1/8)
47.5(1-7/8)
100L-C20F⊗ 8 250(9-27/32)
250(9-27/32)
160(6-5/16)
186(7-5/16)
76(3)
87(3-7/16)
17.5(11/16)
263(10-3/8)
105(4-1/8)
72.5(2-7/8)
100L-C20F⊗ 12 300(11-13/16)
300(11-13/16)
160(6-5/16)
236(9-9/32)
178(7)
61(2-13/32)
17.5(11/16)
313(12-5/16)
206(8-1/8)
47(1-27/32)
81(3-3/16)
60(2-23/64)
4 Pole45
(1-49/64)35
(1-23/64)45.5
(1-25/64)45.5
(1-25/64)
4.5 (3/16) Dia.Mtg. Holes
45.5(1-25/64)
45.5(1-25/64)
91(3-19/32)
8 Pole136
(5-11/32)12 Pole
80.5(3-11/64)
6(1/4)
23.4(15/16)
B
A
D
EF7.1 (1/4) DIA.for 1/4,″or M6 Screw3 Mtg. Holes
CCat. No. A
WideB
HighC
Deep D E F
100L-C20A⊗4 140(5-1/2)
220(8-21/32)
152(5-31/32)
175(6-7/8)
95(3-3/4)
22.5(7/8)
100L-C20A⊗ 8 235(9-1/4)
220(8-21/32)
152(5-31/32)
175(6-7/8)
190(7-1/2)
22.5(7/8)
100L-C20A⊗ 12 270(10-5/8)
290(11-7/16)
152(5-31/32)
245(9-21/32)
225(8-7/8)
22.5(7/8)
A
EFG
DH
6(15/64) K J
B
4 – 5.5 (7/32) X 7.1 (1/4) Mtg. Holes
4 – 5.5 (7/32)DIA. Mtg. Holes
C7.1
(1/4)
Bulletin 193-EA/-EB/-ESE1 and E2 Solid-State Overload Relays
138
Overview/Product Selection
Your order must include 1) the Cat. No. of overload relay selected and 2) if required, Cat. No. of any accessories.
Product Selection
Bulletin 193-EA/193-ES Electronic Motor Protection Relays
Bulletin 193-EB Electronic Motor Protection Relays
Automatic/Manual Reset, Adjustable Trip Class 10, 15 or 20, Jam/Stall and Ground Fault Tripping. ➊
➊ Ground Fault Tripping and Jam/Stall is inhibited for approximately 30 seconds to eliminate the possibility of nuisance tripping during motor starting.
Bulletin 193-EA/-EB/-ES — E1 and E2 Solid-State Overload Relays193-EA/-ES• Self-Powered• Phase Loss Protection• Wide Adjustment Range (3.2:1)• 1 N.O. and 1 N.C. Isolated Auxiliary Contact• Choice of Tripping Classes — Class 10 or 20• Compact Size• Low Energy Consumption (150 mW)• Ambient Temperature Compensation
193-EB also includes:• Selectable Trip Class 10, 15 or 20• Ground Fault Tripping• Jam/Stall Protection
The Bulletin 193-EA/EB/ES is a self-powered, solid-state overload relay that provides advanced motor protection when compared to traditional bimetallic overload relays. It provides improved protection against the damage caused to motors under phase loss conditions. It also offers, as standard, a manually operated trip function, visible trip indicator, and isolated N.O. alarm contacts.
Table of ContentsProduct Selection ..............138Accessories .......................139Specifications ....................140ApproximateDimensions ........................142
Conformity to StandardsEN 60947-4-1CSA C22.2 No. 14UL 508ApprovalsCECSA CertifiedUL ListedCCC (193-EA only)
Mounts to Contactor Adjustment Range (A)Trip Class 10 Trip Class 20 Trip Class 10 Trip Class 20
Cat. No. Cat. No. Cat. No. Cat. No.Manual Reset for 3∅ Applications Automatic/Manual Reset for 3∅ Applications
100-M05…100-C29
0.1…0.32 193-EA1AB 193-EA2AB 193-EA4AB 193-EA5AB0.32…1.0 193-EA1CB 193-EA2CB 193-EA4CB 193-EA5CB1.0…2.9 193-EA1DB 193-EA2DB 193-EA4DB 193-EA5DB1.6…5.0 193-EA1EB 193-EA2EB 193-EA4EB 193-EA5EB3.7…12 193-EA1FB 193-EA2FB 193-EA4FB 193-EA5FB
100-C09…100-C23 12…32 193-EA1GB 193-EA2GB 193-EA4GB 193-EA5GB
100-C30…100-C373.7…12 193-EA1FC 193-EA2FC 193-EA4FC 193-EA5FC12…37 193-EA1HC 193-EA2HC 193-EA4HC 193-EA5HC
100-C43 14…45 193-EA1JD 193-EA2JD 193-EA4JD 193-EA5JD100-C60…100-C85 26…85 193-EA1KE 193-EA2KE 193-EA4KE 193-EA5KE
Manual Reset for 1∅ Applications Automatic/Manual Reset for 1∅ Applications
100-M05…100-C232.0…7.0 193-ES1AB 193-ES2AB 193-ES4AB 193-ES5AB5.0…15 193-ES1BB 193-ES2BB 193-ES4BB 193-ES5BB
100-C09…100-C23 12…32 193-ES1CB 193-ES2CB 193-ES4CB 193-ES5CB100-C30…100-C37 12…37 193-ES1DC 193-ES2DC 193-ES4DC 193-ES5DC
100-C43 14…45 193-ES1FD 193-ES2FD 193-ES4FD 193-ES5FD100-C60…100-C85 26…85 193-ES1HE 193-ES2HE 193-ES4HE 193-ES5HE
Mounts to Contactor Adjustment Range (A) Cat. No.
100-C09…100-C23
0.1…0.32 193-EB1AB0.32…1.0 193-EB1CB1.0…2.9 193-EB1DB1.6…5.0 193-EB1EB3.7…12 193-EB1FB12…32 193-EB1GB
100-C30…100-C37 14…45 193-EB1JC
100-C435.0…15 193-EB1SD14…45 193-EB1JD
100-C60…100-C8523…75 193-EB1ME60…85 193-EB1NE
139
Bulletin 193-EA/-EB/-ESE1 and E2 Solid-State Overload Relays
Accessories
Add-On Accessories
⊗ Voltage Suffix Code
Description For Use With Pkg. Qty. Cat. No.
DIN Rail/Panel AdapterFor separate mounting of the electronic motor protection relay, can be mounted to top-hat rail EN 50 02-35
193-EA_ _ B, -ES__B, -EA__C,
-ES__C
1
193-EPM1
193-EB__B, -EB__C, -E___D 193-EPM2
193-E___E 193-EPM3
Anti-Tamper ShieldProvides protection against inadvertent adjustment of mode selector and full load current settings.
193-E all 1 193-BC4
Current Adjustment ShieldProvides protection against inadvertent adjustment of the current setting.
193-E all 1 193-BC5
Anti-Tamper Shield for DIP Switches193-EB_ _ B193-EB_ _ C193-EB_ _D
40 193-BC7
Anti-Tamper Shield for DIP Switches 193-EB_ _ E 40 193-BC6
Remote Reset SolenoidFor remote reset of electronic overload relays 193-E all 1 193-ER1⊗
External Reset Button for Enclosed DevicesMetal construction IP66, non-illuminated with rod (Length: 142 mm, adjustment range 141…159 mm). Please consult Bulletin 800E push button selection guide for additional types.
193-E all 1 800ES-R611WTR08
Labelling MaterialUniform labelling material for contactors, motor protection devices, timing relays and circuit breakers. See page 88
Voltage 24V 48V 110V 115V 120V 220V 240V50 Hz J — D — — A —60 Hz J — — — D — A
DC Z24 Z48 — Z01 — — —
Bulletin 193-EA/-EB/-ESE1 and E2 Solid-State Overload Relays
140
Specifications
Main Circuits
Control Circuits
General
193-E1 Cat. No. 193-E_ _ _B Cat. No. 193-E_ _ _C Cat. No. 193-E_ _ _D Cat. No. 193-E_ _ _E193-E2 — Cat. No. 193-EB _ _B, 193-EB _ _C, 193-EB _ _D Cat. No. 193-EB _ _E
Rated Insulation Voltage Ui [V] 690Rated Impulse Strength Uimp [kV] 6Rated Operating Voltage Ue [V] 690
Terminal Cross-SectionsTerminal Type
Terminal Screws M4 M5 M8
Flexible with WireEnd Ferrule
[mm2] 1 x (2.5…4)2 x (2.5…4)
1 x (2.5…10)2 x (2.5…6)
1 x (2.5…16)2 x (2.5…10)
1 x (4…35)2 x (4…25)
Solid Conductor Stranded
[mm2] 1 x (2.5…6)2 x (2.5…6)
1 x (2.5…16)2 x (2.5…6)
1 x (2.5…25)2 x (2.5…10)
1 x (4…50)2 x (4…35)
Solid/Stranded Conductor [AWG] 14…8 14…8 14…6 12…2
Recommended Torque [Nm][lb-in.]
1.8 (16)
1.4 (12)
1.6 (14)
4 (35)
Pozidriv Screwdriver Size 2 2Slotted Screwdriver mm 1 x 6 —
Hexagon Socket Size [mm] — 4
Cat. No. 193-E_ _ _B Cat. No. 193-E_ _ _C Cat. No. 193-E_ _ _D Cat. No. 193-E_ _ _ERated Insulation Voltage Ui [V] 600Rated Impulse Strength Uimp [kV] 6Rated Operating Voltage Ue [V] 600
Rated Operating Current Ie /
AC-15 12…120V220…240V380…480V500…600V
[A][A][A][A]
3/21.5/1.5
0.75/0.750.6/0.6
DC-13, at L/R ≤ 15ms 24V110V220V440V
[A][A][A][A]
1.1/1.10.4/0.40.2/0.2
0.08/0.08
Conventional Thermal Current Ith [A] 5
TerminalsTerminal Type
Terminal Screws M3.5
Flexible with Wire End Ferrule
[mm2] 2 x (0.75…2.5)
Solid Conductor [mm2] 2 x (0.75…4)
Solid/Stranded Conductor [AWG] 18…12Recommended Torque [Nm]
[lb-in.]1.4 (12)
Pozidriv Screwdriver Size 2Slotted Screwdriver mm 1 x 6
Cat. No. 193-E_ _ _B 193-E_ _ _C 193-E_ _ _D 193-E_ _ _EWeight [kg (lb)] 0.14 (0.31) 0.17 (0.37) 0.21 (0.46) 0.36 (0.84)Standards IEC 947, EN 60 947, DIN VDE 0660Approvals CCC, CE, UL, CSA
Corrosion Resistance 95% relative humidity, without condensation, 30…60°C
Ambient Temperature openenclosed
–20…+60°C (–4…122°F)–20…+40°C (–4…104°F)
Temperature Compensation ContinuousShock Resistance(10 ms sinusodial shock) [G] 30Type of Protection(in connected state) IP20
N.O. N.C.
141
Bulletin 193-EA/-EB/-ESE1 and E2 Solid-State Overload Relays
Specifications, Continued
Trip Curves for 1∅ Applications (Bulletin 193-ES)
Trip Curves for 3∅ Applications (Bulletin 193-EA/EB)
Wiring Schematic
Multiple of Rated Current
.1
1
10
100
1000
1 102 3 987654
.2
.4
.6
.8
2
468
20
406080
200
400600800
Class 101000
.1
1
10
100
1 102 3 987654
.2
.4
.6
.8
2
468
20
406080
200
400600800
Class 20
App
roxi
mat
e Tr
ip T
ime
(sec
onds
)
Approximate trip time for3-phase balanced conditionfrom cold start.
Approximate trip time for3-phase balanced conditionfrom hot start.
App
roxi
mat
e Tr
ip T
ime
(sec
onds
)Multiple of Rated Current
Approximate trip time for3-phase balanced conditionfrom cold start.
.1
1
10
100
1000
1 102 864
200
800600
400
20
8060
40
2
86
4
.2
.8
.6
.4
Class 10
.1
1
10
100
1000
200
800600
400
20
8060
40
2
86
4
.2
.8
.6
.4
1 102 864
Class 20
App
roxi
mat
e Tr
ip T
ime
(sec
onds
)
Approximate trip time for3-phase balanced conditionfrom hot start.
App
roxi
mat
e Tr
ip T
ime
(sec
onds
)Class 15 (MCS-E2 only)
.1
1
10
100
1000
200
800600400
20
806040
2
864
.2
.8
.6
.4
1 102 864
App
roxi
mat
e Tr
ip T
ime
(sec
onds
)
Multiple of Rated Current Multiple of Rated Current Multiple of Rated Current
96 98
95 97
2 4 6
9795
96 98
L1/1 L2/3 L3/5
T1/2 T2/4 T3/6
Typical IEC Wiring Schematic Typical NEMA Wiring Schematic
1 3 5
2 4 6
T1 T2 T3
M
A1
A2K1
Typical Wiring for 1-Phase Applications
Bulletin 193-EA/-EB/-ESE1 and E2 Solid-State Overload Relays
142
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.Mounts to Bulletin 100-C Contactor
Individual Mounting with DIN Rail/Panel Adapter
Contactor Cat. No. a Width b Height b1 c Depth e1 e2 d1 d2 h j ∅ d
100-M05 with 193-EA or -ES 45(1-25/32)
107(4-13/64)
77.4(3-3/64)
67.2(2-41/64)
18.2(23/32)
48.5(1-29/32)
50(1-61/64) — 48.3
(1-29/32)2
(5/64)Two ∅ 4.2
(Two 11/64 ∅ )100-C09, -C12 -C16, -C23 with
193-EA or -ES45
(1-25/32)131
(5-11/64)87.8
(3-29/64)88.5
(3-1/2)18.2
(23/32)59
(2-21/64)60
(2-23/64)35
(1-3/8)85.1
(3-23/64)2
(5/64)Two ∅ 4.2
(Two 11/64 ∅ )100-C09, -C12 -C16, -C23 with
193-EB54
(2-1/8)136.5(5-3/8)
93.4(3-43/64)
90.7(3-37/64)
22.6(57-64)
59(2-21/64)
60(2-23/64)
35(1-3/8)
85.1(3-23/64)
2(5/64)
Two ∅ 4.2(Two 11/64 ∅ )
100-C30, -C37 with 193-EA or -ES
45(1-25/32)
136.5(5-3/8)
93.4(3-43/64)
92.1(3-5/8)
18.2(23/32)
59(2-21/64)
60(2-23/64)
35(1-3/8)
104.7(4-1/8)
2(5/64)
Two ∅ 4.2(Two 11/64 ∅ )
100-C30, -C37 with 193-EB 54(2-1/8)
136.5(5-3/8)
93.4(3-43/64)
92.1(3-5/8)
22.6(57/64)
59(2-21/64)
60(2-23/64)
35(1-3/8)
104.7(4-1/8)
2(5/64)
Two ∅ 4.2(Two 11/64 ∅ )
100-C43 with 193-EA, -ES or -EB 54(2-1/8)
136.5(5-3/8)
93.4(3-43/64)
92.1(3-5/8)
22.6(57/64)
59(2-21/64)
60(2-23/64)
45(1-49/64)
104.7(4-1/8)
2(5/64)
Two ∅ 4.2(Two 11/64 ∅ )
100-C60, -C72, -C85 with 193-EA, -ES or -EB
72(2-53/64)
188.5(7-27/64)
125.5(4-15/16)
120.4(4-3/4)
18.2(23/32)
83.5(3-9/32)
100(3-15/16)
55(2-11/64)
123.9(4-7/8)
2(5/64)
Four ∅ 5.5(Four 7/32 ∅ )
Cat. No. a Width b Height c Depth d e193-EPM1 45 (1-25/32) 90 (3-35/64) 75 (2-61/64) 30 (1-3/16) 75 (2-61/64)193-EPM2 55 (2-11/64) 90 (3-35/64) 96.5 (4-29/32) 40 (1-37/64) 75 (2-61/64)193-EPM3 70 (2-49/64) 120 (4-23/32) 110 (4-11/32) 55 (2-11/64) 110 (4-21/64)
a
b
c
d2
d1
hj
e2
e1
ød
b1
a
e
d
c
b
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
143
Overview/Product Selection
Your order must include 1) the Cat. No. of overload relay selected, and 2) if required, Cat. No. of any accessories.
Product OverviewThe E3 Overload Relay is available in two configurations: the E3 and E3 Plus. The following table illustrates the functional differences between the two:
➊ Inputs are rated 24V DC.
Thermal Overload
Thermal UtilizationThe E3 Overload Relay provides overload protection through true RMS current measurement of the individual phase currents of the connected motor. Based on this information, a thermal model that simulates the actual heating of the motor is calculated. Percent of thermal capacity utilization (%TCU) reports this calculated value and can be read via the DeviceNet network. An overload trip occurs when the value reaches 100%.
Adjustable SettingsThermal overload protection setup is accomplished simply by programming the motor’s full load current rating (FLA) and the desired trip class (5…30). Programming of the actual values through software programming ensures the accuracy of the protection.
Thermal MemoryThe E3 Overload Relay includes a thermal memory circuit designed to approximate the thermal decay for a trip class 30 setting. This means that the thermal model of the connected motor is maintained at all times, even if the supply power is removed.
Reset ModesFlexibility is afforded the end-user in the ability to select between manual and automatic reset for an overload trip, allowing for broad application. The point of reset is user adjustable from 1…100% TCU.
Time to TripDuring an overload condition, the E3 Overload Relay provides an estimated time to trip that is accessible via the DeviceNet network. This allows corrective action to be taken so that production may continue uninterrupted.
Time to ResetFollowing an overload trip, the E3 Overload Relay will not reset until the calculated percentage of thermal capacity utilization falls below the reset level. As this value decays, the time to reset, which is accessible via the DeviceNet network, is reported.
Thermal WarningThe E3 Overload Relay provides the capability to alert in the event of an impending overload trip. A thermal warning bit is set in the Warning Status word when the calculated percentage of thermal capacity utilization exceeds the programmed thermal warning level, which has a setting range of 0…100% TCU.
Phase LossThe E3 Overload Relay offers configurable phase loss protection in allowing the installer to enable or disable the function plus set a time delay setting, adjustable from 0.1…25.0 seconds. The trip level is factory-set at a current imbalance measurement of 100%.
Ground (Earth) FaultThe E3 Plus Overload Relay incorporates zero sequence (core balance) sensing into its design through the 90 A rating for low level (arcing) ground fault detection. Class 1 ground fault protection is provided per UL1053. Trip and warning settings are adjustable from 1.0…5.0 A. Devices rated greater than 90 A require the external core balance current transformer accessory.Note: The E3 Plus Overload Relay is not a Ground Fault Circuit-Interrupter for personnel protection as defined in article 100 of the U.S. National Electric Code.
StallStall is defined as a condition where the motor is not able to reach full-speed operation in the appropriate amount of time required by the application. This can result in motor overheating as current draw is in excess of the motor’s full load current rating.The E3 Overload Relay provides user-adjustable stall protection. The trip setting has a range of 100…600% FLA, and the enable time is adjustable up to 250 seconds.
Jam (Overcurrent)The E3 Overload Relay can respond quickly to take a motor off-line in the event of a mechanical jam, thereby reducing the potential for damage to the motor and the power transmission components.Trip adjustments include a trip setting adjustable from 50…600% FLA and a trip delay time with a range of 0.1…25.0 seconds. A seperate warning setting is adjustable from 50…600% FLA.
Underload (Undercurrent)A sudden drop in motor current can signal conditions such as• Pump cavitation• Tool breakage• Belt breakageFor these instances, rapid fault detection can help minimize damage and aid in reducing production downtime.
Bulletin 193-EC — E3 and E3 Plus Solid-State Overload Relays193-EC1• 0.4…5000 A Current Range• DeviceNet Ready (ODVA Conformance Tested)• LED Indicators• Test/Reset Button• Adjustable Trip Class 5…30• Ambient Temperature Compensation• True RMS Current Sensing (20…250 Hz)• Protection for Single- and Three-Phase motors• Integrated I/O (2 In/1 Out)• Programmable Trip and Warning Settings• Diagnostic Functions (History of Last 5 Trips)
193-EC2 also includes:• Integrated I/O (4 In/2 Out)• Low-Level (1…5 A) Ground Fault Protection• PTC Thermistor Monitoring
Table of ContentsProduct Overview ..............143Product Selection ..............145Accessories .......................146Specifications ....................148ApproximateDimensions .......................155Conformity to StandardsEN 60947-4-1CSA C22.2 No. 14UL 508ApprovalsABSCE cULPTBC-tick
Feature E3 E3 PlusInputs ➊ 2 4Outputs 1 2Thermistor Input No YesGround Fault Protection No Yes
144
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
Product Overview, Continued
Underload (Undercurrent), ContinuedAdditionally, monitoring for an underload event can provide enhanced protection for motors that are cooled by the medium handled (e.g., submersible pump that pumps water). Such motors can become overheated despite being underloaded. This can result from an absence or an insufficient amount of the medium (due to clogged filters, closed valves, etc.).
The E3 Overload Relay offers underload trip and warning settings adjustable from 10…100% FLA. The trip function also includes a trip delay time with a range of 0.1…25.0 seconds.
Over-temperature ProtectionThe E3 Plus Overload Relay provides motor over-temperature protection with the added provisions for terminating and monitoring of stator winding-embedded positive temperature coefficient (PTC) thermistors. PTC thermistors are semiconductors that exhibit a large increase in resistance when the rated response temperature is exceeded. When the monitored PTC thermistor resistance exceeds the response level of the E3 Plus Overload Relay (3400 Ω), it can be set to trip immediately or programmed to set the PTC bit of the Warning Status word.
Current Imbalance (Asymmetry)The E3 Plus Overload Relay offers current imbalance trip and warning settings adjustable from 10…100%. The trip function also includes a trip delay time with a range of 0.1…25.0 seconds.
Current Monitoring FunctionsThe E3 Overload Relay allows the user to monitor the following operational data over the DeviceNet network:• Individual phase currents (in amperes)• Individual phase currents (as a percentage of motor full load current)• Average current (in amperes)• Average current (as a percentage of motor full load current)• Percentage of thermal capacity utilized• Current imbalance percentage• Ground fault current (E3 Plus)
Diagnostic FunctionsThe E3 Overload Relay allows the user to monitor the following diagnostic information over the DeviceNet network:• Device status• Trip status• Warning status• Time to an overload trip• Time to reset after an overload trip• History of past five trips
Status IndicatorsThe E3 Overload Relay provides the following LED indicators:
Network Status: This green/red LED indicates the status of the network connection.
TRIP/WARN: This LED flashes an amber code under a warning condition and a red code when tripped.
OUT A and B: These amber LEDs illuminate when the output contacts are commanded closed.
IN 1– 4: These amber LEDs illuminate when the user-connected device contact is closed.
Note: IN 3 and 4 and OUT B are available only on the E3 Plus Overload Relay.
Inputs/OutputsInputs allow for the connection of such devices as contactor and disconnect auxiliary contacts, pilot devices, limit switches and float switches. Input status can be monitored via the network and mapped to a controller’s input image table. Inputs are rated 24V DC and are current sinking. Power for the inputs is sourced from the DeviceNet network connection with convenient customer terminations at control terminals 5 and 6.
Relay contact outputs can be controlled via the network for performing such tasks as contactor operation.
Test/Reset ButtonThe Test/Reset button located on the front of the E3 Overload Relay allows the user to perform the following:
Test: The trip relay contact will open if the E3 Overload Relay is in an un-tripped condition and the Test/Reset button is pressed for 2 seconds or longer.
Reset: The trip relay contact will close if the E3 Overload Relay is in a tripped condition, supply voltage is present, and the Test/Reset button is pressed.
Single/Three-Phase OperationThe E3 Overload Relay can be applied to three-phase as well as single-phase applications. A programming parameter is provided for selection between single- and three-phase operation. Straight-through wiring is afforded in both cases.
DeviceNet CommunicationsThe E3 Overload Relay is a Group 2 “slave only” device and supports the following:• Polled I/O messaging• Change-of-state/cyclic messaging• Explicit messaging• Group 4 - Off-line node recovery messaging• Full parameter object support• Auto-baud network rate identification• Configuration consistency value• Programming and Control Terminal (PCT) accessory• AC Input Interface Module accessoryFor more information on operation and maintenance of this product, please reference the user manual, publication 193-UM001_-EN-P.
Programming and Control Terminal (PCT) AccessoryThe PCT is a convenient tool optimized for the commissioning, programming and monitoring of E3 overload relays. It can be used where E3 overload relays are installed on a DeviceNet network or in stand-alone applications. In addition, the PCT can be used to commission other DeviceNet products.
Easy Navigation/ProgrammingThe PCT’s top row of keys provides the five familiar navigation keys (ESC,
SEL, , , and ↵ ) found on other Allen-Bradley motor control products. The PCT menu structure is straightforward and intuitive so that programming time can be minimized. Numerical keys increase ease of use.
ControlThe green and red control keys allow the PCT to operate the output relays of an E3 overload relay operating in a stand-alone application. The reset key is provided to clear E3 overload relay trips.
Password ProtectionThe PCT allows the installer to set password protection to control access to the programming menus. When logged out, the PCT will allow the monitoring of parameter values through the Display mode.
EEPROM ModeThrough the EEPROM mode, the PCT allows for the uploading, downloading and file storage of device configurations. This feature can reduce programming time in installations with multiple E3 overload relays requiring similar configuration.
Auto Connect ModeThe Auto Connect mode provides an automatic method for the PCT to establish a communication connection with a target device on power up. Additionally, the PCT is factory set to auto connect to a target device set at node address 63 - typical factory default setting. This allows for establishing an easy out-of-the-box communication connection.
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
145
Product Overview. Continued/Product Selection
AC Input Interface Module AccessoryThe AC Input Interface Module conveniently allows the E3 overload relay to be retrofitted or applied in new applications that require 110/120V AC control circuitry. This new accessory simply plugs into the E3 overload relay’s
existing input terminals, optimizing panel space utilization. The module accepts termination of up to four external devices, making it compatible with the E3 and E3 Plus versions of the E3 overload relay. Optical isolation is provided between the AC input wiring and the E3’s internal 24V circuitry.
Catalog Number Explanation
Product Selection
Bulletin 193-EC1 Electronic Motor Protection Relays – Direct Contactor Mount• 2 Inputs
• 1 Output
➊ Does not include terminal lugs. See Accessories, page 146.
Bulletin 193-EC2 Electronic Motor Protection Relay – Direct Contactor Mount• 4 Inputs
• 2 Outputs
• Built-in Ground Fault Sensor
• PTC Thermistor Input
➋ Does not include terminal lugs. See Accessories, page 146.
193 - EC1 B B
Bulletin Number
TypeEC1 E3EC2 E3 Plus
Current Rating (Amps)P 0.4…2.0A 1…5B 3…15C 5…25D 9…45E 18…90F 28…140G 42…210H 60…302J 84…420K 125…630L 172…860Z 9…5000
Bulletin 100Contactor SizeB C09…C23D C30…C43E C60…C85F D95…D180G D210…D420H D630…D860Z Panel Mount
Mounts to Contactor Adjustment Range[A] Cat. No.
100-C09…100-C23
0.4…2.0 193-EC1PB
1…5 193-EC1AB
3…15 193-EC1BB
5…25 193-EC1CB
100-C30…100-C43
1…5 193-EC1AD
3…15 193-EC1BD
5…25 193-EC1CD
9…45 193-EC1DD
100-C60…100-C859…45 193-EC1DE
18…90 193-EC1EE
100-D95…100-D18028…140 193-EC1FF ➊
42…210 193-EC1GF ➊
100-D210…100-D420
42…210 193-EC1GG ➊
60…302 193-EC1HG ➊
84…420 193-EC1JG ➊
100-D630…100-D860125…630 193-EC1KH ➊
172…860 193-EC1LH ➊
Mounts to Contactor Adjustment Range [A] Cat. No.
100-C09…100-C23
0.4…2.0 193-EC2PB
1…5 193-EC2AB
3…15 193-EC2BB
5…25 193-EC2CB
100-C30…100-C43
1…5 193-EC2AD
3…15 193-EC2BD
5…25 193-EC2CD
9…45 193-EC2DD
100-C60…100-C859…45 193-EC2DE
18…90 193-EC2EE
100-D95…100-D18028…140 193-EC2FF ➋
42…210 193-EC2GF ➋
100-D210…100-D420
42…210 193-EC2GG ➋
60…302 193-EC2HG ➋
84…420 193-EC2JG ➋
100-D630…100-D860125…630 193-EC2KH ➋
172…860 193-EC2LH ➋
146
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
Product Selection, Continued/Accessories
Panel Mount Devices for use with External Current Transformers ➊➋
➊ Current transformers supplied by customer. Refer to Specifications, page 148 for proper current transformer selection.
➋ Order panel adapter, Cat. No. 193-ECPM2, separately.➌ CT Ratio to FLA setting range correlation
Add-on Accessories
➍ The electronic motor protection relay can be mounted separately to top-hat rail EN 50 02-35.➎ Cat. No. 193-PCT ships complete with a 1 m communication cable.➏ Intended only for point-to-point configurations.➐ Used to make physical connections to other DeviceNet products.➑ Provides two physical plug connections to the E3 DeviceNet port.
Description Adjustment Range [A] ➌ Cat. No.
• 2 Inputs • 1 Output
9…5000 193-EC1ZZ
• 4 Inputs • 2 Output • Ground Fault Sensor input • PTC Thermistor Input
9…5000 193-EC2ZZ
CT Ratio FLA Setting Range (A) CT Ratio FLA Setting
Range (A) CT Ratio FLA Setting Range (A)
50:5 9…45 300:5 60…302 1200:5 240…1215100:5 18…90 500:5 84…420 2500:5 450…2250150:5 28…140 600:5 125…630 5000:5 1000…5000200:5 42…210 800:5 172…860 — —
Description For Use With Package Qty. Cat. No.
DIN Rail/Panel Adapter ➊
193-EC__B
1
193-ECPM1
193-EC__D, 193-EC__Z 193-ECPM2
193-EC__E 193-ECPM3
Programming and Control Terminal ➋ 193-EC — all592-EC — all 1 193-PCT
1 m communication cable with bare leads
193-PCT
1 2707-NC13
3 m communication cable with bare leads ➌ 1 193-C30
10 m communication cable with bare leads ➌ 1 193-C100
1 m communication cable with microconnector (female) ➍ 1 2707-NC14
1 m communication cable with microconnector (male) ➍ 1 2707-NC15
Door Mount Bezel Kit 1 2707-MVMNT
AC Input Interface Module• rated 110/120V AC, 50/60 Hz
193-EC — all592-EC — all 1 193-EIMD
Core Balance Ground Fault Sensor 193-EC2_F, 193-EC2_G, 193-EC2_H, 193-EC2_Z 1 825-CBCT
DeviceNet Tee Interface ➑ 193-EC — all592-EC — all 1 1485P-P1J5-UU5
147
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
Accessories, Continued
Add-on Accessories, Continued
Marking SystemsUniform labeling materials for contactors, motor starting equipment, timing relays and circuit breakers
➊ Must be ordered in multiples of package quantities.
Description For Use With Package Qty. Cat. No.
3-Pole Terminal Blocks• IP20 protection class
193-EC_F
1
100-DTB180
193-EC_G 100-DTB420
Terminal Lug Kits (UL/CSA)
193-EC_F
3
100-DL110
100-DL180
193-EC_G 100-DL420
193-EC_H100-DL630
100-DL860
Terminal Covers• IP20 protection class
193-EC_F
1
100-DTC180
193-EC_G 100-DTC420
193-EC_H 100-DTC860
Phase Barriers 193-EC_H 4 100-DPB860
Description Pkg. Qty. ➊ Cat. No.
Label Sheet• 10 sheets with 105 self-adhesive paper labels each, 6 x 17 mm 10 100-FMS
Marking Tag Sheet• 10 sheets with 160 perforated paper labels each, 6 x 17 mm• To be used with a transparent cover
10 100-FMP
Transparent Cover• 100 each• To be used with marking tag sheets
100 100-FMC
Marking Tag Adapters• 100 each• To be used with System Bulletin 1492W marking tag
100 100-FMA2
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
148
Specifications
Main Circuits
3-Pole Terminal Blocks
Terminal Lug Kits
Maximum Heat Dissipation (Watts)
Cat. No. 193-EC_B, 193-EC_D, 193-EC_Z Cat. No. 193-EC_E Cat. No. 193-EC_F Cat. No. 193-EC_G Cat. No. 193-EC_E
Rated Insulation Voltage (Ui) 690V AC 1000V AC
Rated Impulse Strength (Uimp) 6 kV AC 6 kV AC
Rated Operating Voltage (Ue) IEC/UL 690V AC / 600V AC 1000V AC / 600V AC
Rated Frequency 20…250 Hz 50/60 Hz
Terminal Cross-Sections
— — —
Terminal TypeTerminal Screws .M5 M8
Flexible-Stranded with FerruleSingle Conductor Torque
2.5…16 mm2
2.5 Nm4…35 mm2
4 Nm
Flexible-Stranded with FerruleMultiple Conductor Torque
6…10 mm2
3.4 Nm4…25 mm2
4 Nm
Coarse-Stranded/SolidSingle Conductor Torque
2.5…25 mm2
2.5 Nm4…50 mm2
4 Nm
Coarse-Stranded/SolidMultiple Conductor Torque
6…16 mm2
3.4 Nm4…35 mm2
4 Nm
Stranded/Solid–Single Conductor Torque
14…6 AWG22 lb-in
12…1 AWG35 lb-in
Stranded/SolidMultiple Conductor Torque
10…6 AWG30 lb-in
6…2 AWG35 lb-in
Pozidriv Screwdriver Size 2 —
Slotted Screwdriver (mm) 1 x 6 —
Hexagon Socket Size SW (mm) — 4
Cat. No. 100-DTB180 Cat. No. 100-DTB420
(A) 6…1/0 AWG, 16…50 mm2
(B) 6 AWG…250 MCM, 16…120 mm2
90…110 lb.-in., 10…12 Nm
(2) 4 AWG…600 MCM, 25…240 mm2
180…220 lb.-in., 20…25 Nm
Cat. No. 100-DL110 Cat. No. 100-DL180 Cat. No. 100-DL420 Cat. No. 100-DL630 Cat. No. 100-DL860
Lug: 6…2/0 AWG, 16…70 mm2
90…110 lb.-in., 10…12 NmTerminal: 13/32 in, 10 mm
150 lb.-in., 17 Nm
Lug: 6 AWG…250 MCM, 16…120 mm2
90…110 lb.-in., 10…12 NmTerminal: 1/2 in, 13 mm
275 lb.-in., 16 Nm
Lug: 2 AWG…350 MCM, 375 lb.-in., 42 Nm
Terminal: 11/16 in, 17 mm140 lb.-in., 16 Nm
Lug: 2/0 AWG…500 MCM, 70…240 mm2
400 lb.-in., 45 NmTerminal: 3/4 in, 19 mm
600 lb.-in., 68 Nm
Lug: 2/0 AWG…500 MCM, 70…240 mm2
400 lb.-in., 45 NmTerminal: 3/4 in, 19 mm
600 lb.-in., 68 Nm
Cat. No. 193-EC_B, 193-EC_D Cat. No. 193-EC_E Cat. No. 193-EC_F Cat. No. 193-EC_G Cat. No. 193-EC_H
E3 3.83 4.43 10.67 22.52 35.36
E3 Plus 4.53 5.13 11.37 23.22 36.06
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
149
Specifications, Continued
Control Circuits
UL Short-Circuit Ratings
IEC Short-Circuit Ratings
Control Circuits, Continued
Electromagnetic Compatibility Ratings
➊ Performance Criteria A requires the device under test (DUT) to experience no degradation or loss of performance.
Power Supply Ratings
Rated Supply Voltage (Us)24V DC (supply via DeviceNet
connection)
Operating Range 11…25V DC
Power ConsumptionE3E3 Plus
3.2 W3.9 W
Output Relay Ratings
Type of Contacts Form ASPDT–NO
Rated Insulation Voltage (Ui) 300V AC
Rated Operating Voltage (Ue) 250V AC
Rated Operating Current (Ie) 5 A
Minimum Operating Current 10 mA @ 5V DC
Switching Capacity B300AC-15
Resistive Load Rating (p.f. = 1.0) 5 A, 250V AC/5 A, 30V DC
Inductive Load Rating(p.f. = 0.4)(L/R = 7 ms)
2 A, 250V AC/2 A, 30V DC
Input Ratings
Supply Voltage 24V DC ± 10% (provided by E3)
Input Type Current Sinking
Thermistor/PTC Input Ratings
Type of Control Unit Mark A
Max. No. of Sensors in Series 6
Max. Cold Resistance of PTC Sensor Chain 1500ΩTrip Resistance 3400 Ω ± 150 ΩReset Resistance 1600Ω ± 100 ΩShort-Circuit Trip Resistance 25 Ω ± 10 Ω
Cat. No. Maximum Available Fault Current [A]
Maximum Voltage [V]
193-EC_B 5,000 600
193-EC_D 5,000 600
193-EC_E 10,000 600
193-EC_F 10,000 600
193-EC_G 18,000 600
193-EC_H 42,000 600
193-EC_Z 5,000 600
Cat. No. Maximum Available High Fault Current [A] Maximum Voltage [V]
193-EC_B 100,000 690
193-EC_D 100,000 690
193-EC_E 100,000 690
193-EC_F 100,000 1000
193-EC_G 100,000 1000
193-EC_H 100,000 1000
193-EC_Z 100,000 690
Thermistor/PTC Input Ratings, Continued
Max. Voltage @ PTC Terminals (RPTC = 4 kΩ)
7.5V DC
Max. Voltage @ PTC Terminals (RPTC = open)
30V DC
Response Time 500 ms
Sensor Characteristic
Per IEC 34-11-2
Control and DeviceNet Terminal Cross-Sections
Terminal Screws M3
Flexible-Stranded with Ferrule –Single Conductor Torque
0.25…2.5 mm2
0.55 Nm
Flexible-Stranded with Ferrule –Multiple Conductor Torque
0.5…0.75 mm2
0.55 Nm
Coarse-Stranded/Solid–Single Conductor Torque
0.2…4.0 mm2
0.55 Nm
Coarse-Stranded/Solid–Multiple Conductor Torque
0.2…1.5 mm2
0.55 Nm
Stranded/Solid–Single Conductor Torque
24…12 AWG5 lb-in
Stranded/Solid–Multiple Conductor Torque
24…16 AWG5 lb-in
Slotted Screwdriver (mm) 0.6 x 3.5
Electrostatic Discharge ImmunityTest Level
Performance Criteria
8kV Air Discharge, 6kV Contact Discharge
A ➊
RF Immunity Test LevelPerformance Criteria
10V/mA ➊
Electrical Fast Transient/Burst ImmunityTest Level
Performance Criteria
4kV (Power), 2kV (Control & Comm)
A ➊
Surge Immunity Test LevelPerformance Criteria
2kV (L-E), 1kV (L-L)A ➊
Radiated Emissions Class A
Conducted Emissions Class A
10
20
100
250
550
1330
4000
-20°C TNF-20K0°C TNF- 5K
TNF+15KTNF+ 5K
TNF
150
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
Specifications, Continued
Environmental Ratings
Current Reporting Accuracy
External Current Transformers (for use with cat. nos. 193-EC1ZZ and 193-EC2ZZThe user shall provide one current transformer (CT) for each motor phase, and shall connect the CT’s secondary leads to the appropriate E3 overload relay power terminals, as shown in current transformer’s wiring diagrams. The CT shall have the appropriate ratio (refer to the product nameplate or product description). Additionally, the CT shall be selected to be capable of providing the required VA to the secondary load, which includes the E3 overload relay burden of 0.1 VA at the rated secondary current and the wiring burden. Finally, the CT shall be rated for protective relaying to accomodate the high inrush currents associated with motor startup, and shall have an accuracy of ≤±2% over its normal operating range. Typical CT ratings include (Instrument Transformers, Inc. — Model #23 or equivalent):
General
➊ Approved by the PTB (Physikalisch-Technische Bundesanstalt, Physical Testing Institute, Federal Republic of Germany) for the protection of motors used in explosion hazard areas (EEx e).
Protection and Warning Summary
➋ Inhibit Time settings are used for both trip and warning functions.➌ Phase loss trip level is set at a current imbalance greater than or equal to 100% and is not user-adjustable.➍ Stall Protection is only applicable to the motor starting sequence.
Ambient TemperatureStorageOperating (open)Operating (closed)
-40…+85°C (-40…+185°F)-20…+55°C (-4…+131°F)-20…+40°C (-4…+104°F)
HumidityOperatingDamp Heat – Steady-State (per IEC 68-2-3)Damp Heat – Cyclic(per IEC 68-2-30)
5…95% Non-condensing92% r.h., 40°C(104°F), 56 days
93% r.h., 25°C/40°C(77°F/104°F), 21 cycles
Vibration (per IEC 68-2-6) 3G
Shock (per IEC 68-2-27) 30G
Pollution Environment Degree 2
Degree of Protection193-ECxxx592-ECxxx
1P1X1P0
Phase Currents:100% min. FLA Setting Value…720% max. FLA Setting Value50%…100% min FLA Setting Value
+/- 5%+/- 10%
Ground Current (0.5…9.0 A) +/- 10%
ANSI (USA) Class C5B0.1CSA (Canada) Class 10L5IEC (Europe) 5 VA Class 5P10
Cat. No. 193-EC_B, 193-EC_D, 193-EC_Z Cat. No. 193-EC_E Cat. No. 193-EC_F Cat. No. 193-EC_G Cat. No. 193-EC_H
Approximate Weights
0.80 kg(1.77 lb)
1.23 kg(2.71 lb)
2.95 kg(6.5 lb.)
4.43 kg(9.75 lb.)
8.63 kg(19.0 lb.)
Standards CSA C22.2 No.14, DIN VDE 0660, EN 60 947, UL 508, UL 1053
Approvals CE, PTB ➊ , C-tick, cUL
Protective Function
Trip Enable Warning Enable Trip Level Settings Trip Delay Settings Warning Level Settings Inhibit Time
Settings ➋
Factory Default
Factory Default Range Default Range
(s)Default
(s) Range Default Range(s)
Default (s)
Thermal Overload Enabled Disabled 0.4…5000 A — Trip Class5…30
Trip Class 10
0…100 %TCU 85% — —
Phase Loss Enabled — ➌ ➌ 0.1…25.0 1.0 — — 0…250 0
Ground (Earth) Fault Disabled Disabled 1.0…5.0 A 2.5 A 0.1…25.0 0.5 1.0…5.0 A 2.0 A 0…250 10
Stall (High Overload During Start)
Disabled — 100…600% FLA ➍
600% FLA ➍ 0…250 ➍ 10 ➍ — — — —
Jam (High Overload
During Run)Disabled Disabled 50…600
% FLA 250 % FLA 0.1…25.0 5.0 50…600 % FLA 150 % FLA 0…250 10
Underload Disabled Disabled 10…100% FLA 50 % FLA 0.1…25.0 5.0 10…100 %
FLA 70 % FLA 0…250 10
PTC Disabled Disabled — — — — — — — —
Current Imbalance
(Asymmetry)Disabled Disabled 10…100% 35% 0.1…25.0 5.0 10…100% 20% 0…250 10
Comm Fault Enabled Disabled — — — — — — — —
Comm Idle Disabled Disabled — — — — — — — —
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
151
Specifications, Continued
Programming and Control Terminal AC Input Interface Module
DisplayDisplay type LCD with yellow-green backlightingColumn and character 2 lines x 16 charactersCharacter size 5.56 x 2.96 mm (0.22 x 0.12 in.)Viewing area 15 x 60 mm (0.58 x 2.35 in.)
Viewing angle Horizontal: 30°Vertical: -20…+30°
Keypad
Keypad type Tactile embossed, domed keys, sealed membrane
Operation Force 453 g (16 oz.)Operational life 1 million operations
CommunicationCommunication protocol DeviceNet (selectable 125, 250, 500 kbits/s)
ElectricalInput voltage range 11…25 V DC Input power, typical 1.8 WInput current 164 mA @ 11V, 72 mA @ 25V
EnvironmentalOperating temperature 0…55°C (32…131°F)Storage temperature -20…+70°C (-4…+158°F)Humidity 5…95%, non-condensingShock:
OperatingNon-operating
30 g50 g
DimensionsHeight 129.5 mm (5.1 in.)Width 90.2 mm (3.55 in.)Depth 24.8 mm (0.975 in.)Weight 0.2 kg (0.44 lb.)
Agency ApprovalsUL, cUL
ElectricalNumber of inputs 4Voltage category 110/120V ACOperating voltage range 79…132V ACFrequency range 47…63 HzOff-state voltage (max.) 20V ACOn-state voltage (min.) 79V AC
On-state current 2.0 mA @ 79V AC (min.), 10.0 mA @ 132V A (max.)
Inrush current (max.) 150 mAOff-state current (max.) 1.0 mAHeat dissipation (max.) 0.10 W/inputIEC input compatibility Type 1
EnvironmentalOperating temperature
OpenEnclosed
-20…+55°C (-4…+131°F)-20…+40°C (-4…+104°F)
Storage temperature -40…+85°C (-40…+185°F)Humidity 5…95%, non-condensingVibration (IEC 68-2-6) 3 GShock (IEC 68-2-27) 30 G
EnvironmentalMaximum altitude 2,000 mPollution environment Pollution degree 2Terminal marking EN50012Degree of protection IP2LX
Electromagnetic CompatibilityESD Immunity (IEC 10000-4-2) 6 kV contact, 8 kV airRadiated Immunity (IEC 10000-4-3) 10V/mFast transient burst (IEC 10000-4-4) 4 kV (Power), 2 kV (Control)
Surge immunity (IEC 10000-4-5) 2 kV common mode, 1 kV differential mode
Radiated and conducted emissions Class APhysical
Weight 60 g (2.1 oz.)Agency Approvals UR, cUR, CE
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
152
Specifications, Continued
Trip Curves
E3 & E3 Plus Overload Relay Trip Class 5
1
10
100
1000
100% 1000%
Current (% FLA)
Tim
e (s
econ
ds)
Cold TripHot Trip
E3 & E3 Plus Overload Relay Trip Class 10
1
10
100
1000
100% 1000%
Current (% FLA)
Tim
e (s
econ
ds)
Cold TripHot Trip
E3 & E3 Plus Overload Relay Trip Class 20
1
10
100
1000
10000
100% 1000%
Current (% FLA)
Tim
e (s
econ
ds)
Cold TripHot Trip
E3 & E3 Plus Overload Relay Trip Class 30
1
10
100
1000
10000
100% 1000%
Current (% FLA)
Tim
e (s
econ
ds)
Cold TripHot Trip
153
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
Specifications, Continued
Typical Wiring Schematics – NEMA
Typical Wiring Schematics – IEC
Single-Phase Three-Phase
S.C.P.D.
E3 / E3 Plus
L1 L2
2/T1 4/T2 6/T3
M
T1 T2
S.C.P.D.
E3 / E3 Plus
L1 L2 L3
2/T1 4/T2 6/T3
M
T1T2
T3
M 95 96A1 A21413
Out A Trip Relay (1)E3 E3
(1) Contact shown with supply voltage applied.
Single-Phase Three-Phase
95
96
A1
A2
14
13
Out A
Trip Relay (1)
E3
E3
(1) Contact shown with supply voltage applied.
K
L1
N
M
1
2
3
4
5
6
T1 T2 T3
K1
A1
A2
M
1
2
3
4
5
6
T1 T2 T3
K1
A1
A2
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
154
Specifications, Continued
Typical Wiring Schematics – IEC
Reversing Starter Application
155
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
Approximate Dimensions
Approximate dimensions are shown in millimeters (inches). Dimensions are not to be used for manufacturing purposes.
Bulletin 109 Starter Approximate Dimensions
Overload Cat. No.
Contactor Cat. No. Width A
Height BB1 Depth C E1 E2without
193-EIMD with 193-EIMD
193-EC_ _B 100-C09, -C12 -C16, -C23
45(1-25/32)
188.3(7-13/32)
207.7(8-11/64)
145.1(5-23/32)
107(4-7/32)
11.4(29/64)
67.9(2-43/64)
193-EC_ _D 100-C30, -C37 45(1-25/32)
188.3(7-13/32)
207.7(8-11/64)
145.1(5-23/32)
107(4-7/32)
11.4(29/64)
67.9(2-43/64)
193-EC_ _D 100-C43 54(2-1/8)
188.3(7-13/32)
207.7(8-11/64)
145.1(5-23/32)
107(4-7/32)
11.4(29/64)
67.9(2-43/64)
193-EC_ _E 100-C60, -C72, -C85
72(2-53/64)
236.1(9-19/64)
255.5(10-1/16)
173.2(6-13/16)
124.6(4-29/32)
11.4(29/64)
89.8(3-17/32)
Overload Cat. No.
Contactor Cat. No. D1 D2 H J ØD
193-EC_ _B 100-C09, -C12 -C16, -C23 60(2-23/64)
35(1-3/8)
85.1(3-23/64)
2(5/64)
Ø4.2(11/64Ø)
193-EC_ _D 100-C30, -C37 60(2-23/64)
35(1-3/8)
104(4-3/32)
2(5/64)
Ø4.2(11/64Ø)
193-EC_ _D 100-C43 60(2-23/64)
45(1-25/32)
107(4-7/32)
2(5/64)
Ø4.2(11/64Ø)
193-EC_ _E 100-C60, -C72, -C85 100(3-15/16)
55(2-11/64)
125.5(4-15/16)
2(5/64)
Ø5.5(7/32Ø)
C
H J
D1
E2B
B1
E1
D2 øD
A
Bulletin 193-ECE3 and E3 Plus Solid-State Overload Relays
156
Approximate Dimensions, Continued
Approximate dimensions are shown in millimeters (inches). Dimensions are not to be used for manufacturing purposes.
Panel Mount Adapters(For Use With Cat. No. 193-EC_ _B)
(For Use With Cat. No. 193-EC_ _D, 193-EC_ZZ)
(For Use With Cat. No. 193-EC_ _E)
45(1-25/32)
159.3(6-17/64)
7.3(9/32)
135(5-5/16)
6.1(1/4)
100.5(3-31/32)
ø 4.4(11/64 ø)
11.4(29/64)
30(1-3/16)
115(4-17/32)
115(4-17/32)
11.4(29/64)
30(1-3/16)
45(1-25/32)
7.3(9-32)
135(5-5/16)
154.2(6-5/64)
ø 4.4(11/64 ø)
100.5(3-31/32)
6.1(1/4)
71.7(2-53/64)
131.2(5-11/64)
15(19/32)
77(3 - 1/32)
ø 5.5 (7/32 ø)
5 (13/64)
60(2-23/64)
11.4(29/64)
150.5(5-15/16)
130(5-1/8)
77(3-1/32)
155.1(6-7/64) w/193-EIMD
Bulletin 193-EFSolid-State Overload Relays
157
Overview/Product Selection
Features
Catalog Number Explanation
Bulletin 193-EF193-EF1• 0.5…400 A Current Range• Phase Loss/Current Imbalance Protection• LED Indicators• Digital (DIP Switch) Adjustments• Adjustable Trip Class (2…30)
193-EF2 also includes:• 0.5…630 A Current Range• Overcurrent Indication• PTC Thermistor Monitoring
Bulletin 193-EF overload relays offer precise and reliable ambient compensated overload protection for the protection of three-phase squirrel cage motors. DIP switch settings allow the Bulletin 193-EF overload relays to be closely matched to the motor characteristics to safely obtain full utilization of the motor. The wide adjustment range of the trip class setting allows the Bulletin 193-EF overload relays to be applied in a wide variety of applications. The 193-EF2 version offers enhanced motor protection with additional circuitry for monitoring motor winding embedded thermistors.
Table of ContentsProduct Overview ............. 157Cat. No. Explanation ......... 157Product Selection ............. 158Accessories....................... 158Specifications.................... 160ApproximateDimensions........................ 161Conformity to StandardsIEC 947-4CSA C22.2 No. 14UL 508ApprovalsCEPTBCSA CertifiedUL Listed
DIP switch for full-load current adjustment
Reset button
Test button for thermal overload protection
Control Voltage
Output relay contact connections
Connections for thermistor overtemperature protection
Stand-by display
Thermal overload (steady) and overcurrent (blinking) indication
Phase loss and phase imbalance indication
DIP switch for trip class adjustment
Thermistor overtemperature indication
Bulletin Number
VersionBasic 1Advanced 2
193 — EF 1 A KP — R F L
MCS PLUS Model 193-EF
Adj. Range20…180 A160…400 B160…630 C
Voltage24V AC36V AC48V AC110V AC120V AC230V AC240V AC400V AC415V AC440V AC24V DC48V DC
Factory ModificationsAutomatic ResetRemote ResetExternal Indication
RFL
KJKVKYKDKPKFKAKNKGKBZJZY
Bulletin 193-EFSolid-State Overload Relays
158
Product Selection/Accessories
Electronic Motor Protection Relays
⊗ Voltage Suffix CodeThe catalog number as listed is incomplete. Select a Voltage Suffix Code from the table below for completion. Example: Cat. No. 193-EF1A⊗ becomes Cat. No. 193-EF1AKP.
➊ 0.5…20A can be achieved by looping the motor supply cables. (Refer to the Specifications section.)
Factory Modification Options
➋ Refer to the Catalog Number Identification section for the proper suffix code sequence.➌ Device ships with the Remote Reset Module accessory (Cat. No. 193-RB1) included.➍ Device ships with the External Indication Module accessory (Cat. No. 193-CB1) included.
Add-On Modules
Mounting Materials
➎ PQ = Package Quantity➏ Only Motor connection side, on supply side use 100-DTC420
Adjustment Range (A) Cat. No. Cat. No.20…180 ➊ 193-EF1A⊗ 193-EF2A⊗160…400 193-EF1B⊗ 193-EF2B⊗160…630 — 193-EF2C⊗
VoltageSuffix Code Suffix Code
V AC V DC24 36 48 110 120 230 240 400 415 440 24 48
50/60 Hz KJ KV KY KD KP KF KA KN KG KB — —— — — — — — — — — — ZJ ZY
Description Suffix Code ➋Automatic Reset of overload and thermistor overtemperature protection -RRemote Reset ➌ -FExternal Indication ➍ -L
Description Version Cat. No. Pkg. Qty. ➊
External Indication Module• For front mounting on a control panel or MCC• 3 m connection cable with plug• Function status indication• Trips and alarms can be reset• IP54 protection
193-LB1 1
Remote Reset ModuleTrip reset from any location Operating voltage
24…48V AC/DC
with external burden resistor-8.2 kΩ, 4 W110…230V AD/DC-22 kΩ, 10 W240…440V AD/DC
193-RB1 1
Adapter for Remote Reset Module• For easy mounting of remote reset module on standard DIN Rail
(EN 50 022-35) and G-Rail196-MTM 10
Description Version PQ ➎ Cat. No.Transparent Front Cover 10 193-PA
Main Terminal Cover• Set (2 pieces) Includes mounting materials• IP 10 Protection Class
for 825-MVM/825-MVSfor 825-MVS2for 193-EF2C
2100-DTS110100-DTS180100-DTS420
Terminal Lug• Set (6 pieces) Includes terminal and fixing screws
for 193-EF1Afor 193-EF2A 6 193-HD
Terminal Blocks• Set (2 pieces)• IP 10 Protection Class•
for 825-MVM, 825-MVSfor 825-MVM2, 825-MVS2for 193-EF2C ➏
2100-DTB110100-DTB180100-DTB420
A2 A1 98 97 96 95(-) (+)
r1 r2 r3
r1 r2 r3
rt
bl
RvUs
S1R
(-)(+)
159
Bulletin 193-EFSolid-State Overload Relays
Accessories, Continued/Specifications
Connecting Components
Mounting Materials — Bus BarsSet of 3 busbars, includes terminal and fixing screws. Suitable for use with 193-EF1A and 193-EF2A overland relays.
➊ PQ - Package Quantity
Labeling MaterialsUniform labeling materials for contactors, motor starting equipment, timing relays and circuit breakers
➋ Must be ordered in multiples of package quantities.
Description Cat. No.
Terminal Lugs (UL/CSA)• Set of 3• See page XREF for conductor capacities
For 193-EF_AFor 193-EF_AFor 193-EF_B
100-DL110100-DL180100-DL420
Description PQ ➊ Cat. No.M8 connections• 4 x 16 x 100 mm (0…125 A)• Universally applicable
3 825-MVM
M8 connections• 4 x 20 x 117 mm (0…180 A)• Universally applicable
3 825-MVM2
M6 lower connections• For mounting on 100-D95 and 100-D110 contactors 3 825-MVS
M8 lower connections• For mounting on 100-D140 and 100-D180 contactors 3 825-MVS2
Description Pkg. Qty. ➋ Cat. No.
Label Sheet• 10 sheets with 105 self-adhesive paper labels each, 6 x 17 mm 10 100-FMS
Marking Tag Sheet• 10 sheets with 160 perforated paper labels each, 6 x 17 mm• To be used with a transparent cover
10 100-FMP
Transparent Cover• 100 each• To be used with marking tag sheets
100 100-FMC
Marking Tag Adapters• 100 each• To be used with System Bulletin 1492W marking tag
100 100-FMA2
160
Bulletin 193-EFSolid-State Overload Relays
Specifications
Supply Voltage FailureIn the event of a supply voltage failure, the output relay resets and the stand-by indicator goes out. The actual status is stored for 30 minutes. When the supply voltage is restored, the output relay reverts to its original state.
Reset — ManualThe reset button resets all protection functions. Resetting from any location is possible with the 193-RB1 remote reset module.
Reset — AutomaticAutomatic resetting of thermal overload and thermistor overtemperature functions is an optional feature. All other protection functions must be reset manually.
Test Button for Thermal Overload ProtectionPressing the test button will verify thermal tripping operation time at 6x/e without the motor being connected. The test button must be held for longer than the set trip time t6x/e.
Device Installation and CommissioningThe operating instructions enclosed with the device provide all of the information necessary to set and commission it.
Surface Mounting193-EF_A Snap-on fixing to standard DIN Rail or screw fixing193-EF_B Screw fixing193-EF_C Screw fixingMounting position: optional
Setting the Rated Current (0.5…20 A) (193-EF1A and 193-EF2A Required 193-HD)
➊ CSA, UL: for Ie = 0.5…2.5 A, only factory-assembled wound devices should be installed
➊ Type of wiring: insulated control leads, screened > 200 m (shield connected with 1T1)
➋ PTB: Approval of the Physikalisch-Technische Bundesanstalt (Germany). Requirements for motor protection in highly combustible areas (e.g., chemical and petrochemical applications). Report No. 3.53-22532/97
The motor supply cables are looped through the current transformer twice, thereby doubling the rated motor current. The setting on the Bulletin 193-EF overload relay is the product of:
Recommended for Ie [A] Motor Supply CablesCable Cross Section (Flexible Strand)
IEC [mm2] CSA, UL (AWG No.)
20…180 fed straight through 4…95 10…10 000
10…20 looped twice 2.5…25 14…10
5…10 looped 4 times 1…6 14
2.5…5 looped 8 times 0.75…2.5 14
0.5…2.5 looped 40 times 0.5…0.75 ➊
Ie [A] x…number of loops
193-
EF
4
193-
EF
2
Motor supply wire looped twice Motor supply wire looped 4 times
Rated VoltageMotor Circuit(primary circuit of current measuring device)IEC 947, EN 60947 [V] 1 000CSA, UL [V] 600Control CircuitIEC 947, EN 60947 [V] 440CSA, UL [V] 240Rated Control Voltage US
AC 50/60 Hz [V] 24, 36, 48, 110, 120, 230, 240, 400, 415, 440, (0.8…1.1US)
DC [V] 24, 48 (0.9…1.2 US)
Special Control Voltage US
AC 50/60 Hz [V] 24…440Terminal Cross-sectionControl circuit [mm2] 2 x 2.5Device Protection Fuse 10 A Type gG or 16 A Type gGOutput Relay Contact InformationContact assembly 1 N.O. and 1 N.C., galvanically separatedRated operating voltageper UL/CSA: pilot duty 240V [V] 24 110…1125 220…250 380…440
Continuous Thermal current [A] 4Rated AC operating currentAC-15 [A] 3 3 1.2Max. permissible switching current (cos = 0.3)AC-15 [A] 30 30 12Rated DC operating current(L/R = 300 ms), no protective circuit neededDC-13 [A] 2 0.3 0.2 —Max. rated back-up fuse current 10 A, 500V AC Type gGAmbient temperature
Operation -5…+60°CStorage -50…+60°CTransport -50…+85°C
Sensor Measurement CircuitMeasurement circuitCross section [mm2] 0.5 1.5Max. lead length ➊ [m] 200 600Max. cold resistance of PTC sensor chain kΩ 1.5
Max. number of PTC sensors per IEC 34-11-2 6
WeightsOverload Relay193-EF1A [g] 1 070193-EF2A [g] 1 090193-EF1B [g] 2 510193-EF2B [g] 2 530193-EF2C [g] 5 550193-LB1 indication module [g] 160193-RB1 Remote reset module [g] 160196-MTM Adapter [g] 5193-PA Front cover [g] 3193-HD Terminal lug [g] 40Bus bars825-MVM [g] 230825-MVM2 [g] 290825-MVS [g] 280825-MVS2 [g] 350Approvals
CE, UL Listed, CSA, Bureau Veritas, Lloyd’s Register of Shipping, Maritime Register of Shipping, RINA, PTB ➋
Bulletin 193-EFSolid-State Overload Relays
161
Dimensions
Dimensions in millimeters. Dimensions are not intended to be used for manufacturing purposes.
Cat. Nos. 193-EF1A, 193-EF2A
Cat. Nos. 193-EF1B, 193-EF2B
Cat. No. 193-EF2C
Cat. No. 193-LB1
➊ Terminal Cover➋ Universally applicable busbars (825-MVM)➌ Feed-through openings 19 x 19 mm➍ With 193-LB1 indication module: c = c + 29 mm➎ Can be mounted to DIN Rail EN 50 022-35➏ Universally applicable busbars (825-MVM2)
b1 e4 b
e2 e2
d2
a
ø d
a1
e3
c
➍
➌
c1
c3
d1
➎
ø e
➊
c2
➋ ➏
ø d
c
c1
d1 e4 b
a
➍
ø d
ø e
ø e1
ø d
e2e2
d2
e3
ce2
c1
d1 e4 b
e2
d2
a
ø d
ø e
ø e1
ø d
ø d ➍
e3
72
R 36
56.5 6
68
32
3
14
Dimensions 193-EF1A193-EF2A
193-EF1B193-EF2B 193-EF2C
a 120 140 155a1 105 — —b 100 142 143
b ➋ 100 — —b ➏ 117 — —b1 73 — —φd 5.4 5.8 6.5d1 55…60 75 90…93d2 100 125 135φe M8 x 12 M10 x 25 M10 x 25φe1 — M10 x 35 M10 x 25e2 38.5 48 48
e3 ➋ 16 25 25e3 ➏ 20 25 25e4 82 117 118
e4 ➋ 82 — —e4 ➏ 97 — —
c 143 148 178c1 72 117 118c2 93.5 — —c3 53.5 — —
Bulletin 193-TBimetallic Overload Relays
162
Overview/Product Selection
Product SelectionThermal Overload Relays
➊ Bulletin 193-T overload relays should not be used with DC contactors.➋ To select the setting range for use in Y-∆ Starters, multiply the rated operating current of the motor by a factor of 0.58.➌ For motors with service factor of 1.15 or greater, use motor nameplate full load current. For motors with service factor of 1.0, use 90% of the motor nameplate full
load current.
Bulletin 193-T — Bimetallic Overload Relays• Phase Failure Sensitivity• Temperature Compensation• Auxiliary Switch (1 N.O. and 1 N.C. Contact)• Test/Stop Button• Manual/Auto Reset Button• Individual Mounting• Protection of EEX Electric Motors (PTB)• “Trip Free” Construction• Trip IndicatorBulletin 193-T thermal overload relays are designed for use with Bulletin 100-C contactors and Bulletin 104-C reversing contactors. These class 10 ambient compensated thermal overload relays use integral heater elements; therefore, additional heater elements are not required. Further, the design includes a differential mechanism for sensitivity to single-phase conditions.The trip setting is adjustable over the listed motor full load current range. The overload relay can be operated in a manual or automatic reset mode. An isolated normally open contact is standard. An anti-tamper shield is available and snaps on the front of the overload relay to discourage field adjustments of the trip setting and reset mode.
Table of ContentsProduct Selection ............. 162Accessories ...................... 163Specifications ................... 164Approximate Dimensions 166Conformity to StandardsIEC 60947-4BS 5424VDE 0660IEC 60947-4 Type 2 CoordinationApprovalsUL ListedCSA CertifiedCE
Mounts on Contactor ➊ Setting Range [A] ➋➌ Cat. No.
100-C09…100-C37
0.1…0.16 193-TAA16
0.16…0.24 193-TAA24
0.24…0.4 193-TAA40
0.4…0.6 193-TAA60
0.6…1.0 193-TAB10
1.0…1.6 193-TAB16
1.6…2.4 193-TAB24
2.4…4 193-TAB40
4…6 193-TAB60
6…10 193-TAC10
100-C12…100-C37 10…16 193-TAC16
100-C23…100-C37 16…24 193-TAC24
100-C30…100-C43 18…30 193-TBC30
100-C37…100-C43 30…45 193-TBC45
100-C60…100-C85
18…30 193-TCC30
30…45 193-TCC45
45…60 193-TCC60
100-C72…100-C85 60…75 193-TCC75
Separate Mounting 70…90 193-TDC90
163
Bulletin 193-TBimetallic Overload Relays
Accessories
Add-On Modules
⊗ Voltage Suffix CodesThe catalog number as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: 120V, 60Hz: Cat. No. 193-ER1⊗ becomes Cat. No. 193-ER1D.Standard Control Voltages
Labels• Uniform labeling materials for contactors, motor starting equipment, timing relays and circuit breakers
Description For Use With Pkg. Qty. Cat. No.
DIN Rail/Panel Mounting Adapter• For separate mounting of overload relays• Snaps on to DIN Rail EN 50 022-35
193-TA… 5 193-TAPM
193-TC… 2 193-TCPM
Anti-tamper ShieldProtects against unauthorized or unintentional modification of reset mode and full-load current settings
193-T all 1 193-BC1
Current Adjustment ShieldProtects against unauthorized or unintentional adjustment of the full-load current setting
193-T all 1 193-BC3
Remote ResetFor remote resetting of overload relays• Mounts on front of overload relay• Can be operated by remote push button or PLC control
193-T all 1 193-ER1⊗
External Reset Button for Enclosed Devices• Metal type• IP66 protection• Non-illuminated• Extender included (Length: 142 mm, selectable from 141…159 mm)For additional product selection, see Bulletin 800E selection information
193-T all 1800ES-R611W
and 800E-ATR08
Voltage 24 48 110 115 120 220 240
50 Hz J — D — — A —
60 Hz J — — — D — A
DC Z24 Z48 — Z01 — — —
Description Pkg. Qty. Cat. No.
Label Sheet• Uniform labeling material for contactors, motor protection devices, timing relays and circuit-
breakers• For product information and ordering information see Bulletin 100-C accessory information
10 100-FMS
Marking Tag Sheet• 10 sheets with 160 perforated paper labels each, 6 x 17 mm• To be used with a transparent cover
10 100-FMP
Transparent Cover• To be used with marking tags 100 100-FMC
Marking Tag Sheet• To be used with label frame:
System V4/V5System Bulletin 1492W
100100
100-FMA1100-FMA2
Bulletin 193-TBimetallic Overload Relays
164
Specifications
Thermal Overload Relays
Circuit Diagrams
Trip Characteristics These trip characteristics refer to IEC 947 and are average values from cold start at an ambient temperature of 20 °C. Trip time is pictured as a function of operating current. With the device at normal operating temperature, the trip time decreases to approximately 25% of the shown value.
K1
2-phase 3-phase1-phase
Cat. No. 193-TDC90Cat. Nos. 193-TA…, 193-TB…, 193-TC…
Sec
onds
Sec
onds
Min
utes
Min
utes
3-phase
3-phase
2-phase 2-phase
Rated Current Rated Current
Bulletin 193-TBimetallic Overload Relays
165
Specifications, Continued
Thermal Overload Relays, Continued
Main Circuits Control Circuits
General
Cat. Nos. 193-TA…
193-TB…
193-TC…
193-TDC90
Rated isolation voltage Ui [V] 690 1 000
Rated surge withstand Uimp [kV] 6 8
Rated operating voltage Ue [V] 690 1 000
Overvoltage category/pollution degree III/3
Safe isolation (between main circuit and auxiliary contacts per [V]DIN, VDE 106, Part 101 and Part 101 A1
440
Current setting range 0.1…24 18…45 18…60 (75) 70…90
Direct load loss (for 3 current paths)
min. value of adjustment range [W] 2.5 3 3 (7) <16
max. value of adjustment range [W] 6 7.5 7.5 (10) <28
Wiring cross sectionType of clamp
Terminal screws M 4 M 6 M 8
multi-strand conductorwith ferrule [mm2] 2 x
(1…4)1 x 25 / 2 x
(1…10) 50
solid conductor [mm2]multi-strand conductor [mm2]solid or multi-strand [AWG]
2 x (1…6)
—14…8
2 x (1…16)—
14…2
16502
Flexible bus[mm] — — 6 x 9 x 0.8
Recommended tighteningtorque [Nm][lb-in] 1.8 (16) 3.5 (31) 6 (54)
Pozidrive screwdriver Size 2 —
Slotted screwdriver [mm] 1 x 6 —
Hex-head screw [mm] — 4
Cat. Nos. 193-TA…
193-TB…
193-TC…
193-TDC90
Rated isolation voltage Ui [V] 500
Rated surge withstand Uimp [kV] 6
Rated operating voltage Ue [V] 500
Overvoltage category/pollution degree III/3
Rated operating current Ie /
AC-15 220…240V [A]380…415V [A]500V [A]
1.5/1.50.5/0.90.5/0.8
DC-13 24V [A]60V [A]110V [A]220V [A]
0.9/0.90.75/0.75
0.4/0.40.2/0.2
Safe isolation (between auxiliary contacts) per DIN, VDE 106, [V]and Part 101 A1
240
Conventional thermal current Ith [A] 6
Short circuit withstandwithout welding, fuse gL [A] 6
Wiring cross sectionType of clamp
Terminal screw M 3.5
multi-strand conductorwith ferrule [mm2] 2 x (0.75…2.5)
solid conductor [mm2]solid or multi-strand [AWG] 2 x (0.75…4)
18…14
Recommended tightening torque [Nm(lb-in)]Pozi-driv screwdriver SizeSlotted screwdriver [mm]
1.2 (11)2
1 x 6
Cat. Nos. 193-TA… 193-TB… 193-TC… 193-TDC90
Weight [kg (lbs)] 0.130 (0.29) 0.210 (0.46) 0.210 (0.46) 1.300 (2.86)
Standards IEC 947, EN 60 947, DIN VDE 0660
Approvals CE, UL Listed, CSA, PTB, RINA
Climatic withstand humid/warm, constant, per DIN, IEC 68, Part 2-3humid/warm, cyclic, per DIN, IEC 68, Part 2-30
Ambient temperature openenclosed
–25…+50°C (–13…122°F)–25…+40°C (–13…104°F)
Temperature compensation continual
Shock withstand(Sin impact 10 ms) [G] 10
Protection class IP00IP2LX when attached
Contact protection Finger- and back of hand proof (VDE 0106, Part 100)
Bulletin 193-TBimetallic Overload Relays
166
Approximate Dimensions
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Mounted on Bulletin 100-C Contactor
Separately Mounted with DIN/Panel Adapter Separately Mounted
➊ Can be mounted on 35 mm DIN Rail EN 50 022-35➋ With reset rod, the max. action radius is 9 mm from the center of the reset knob. c3 With remote reset: 51 mm (2)c4 With auxiliary contact block: 39 mm (1-17/32)
Cat. No. With Contactor a b b1 c c1 c2 c5 ød d1 d2 e1 e2
193-TA…100-C09…100-C23 45
(1-25/32)127(5)
83(3-17/64)
96(3-25/32)
91(3-37/64)
15(19/32)
5(13/64)
2 @ 4.5(2 @ 3/16)
60(2-23/64)
35(1-25/64) ➊
16.5(21/32)
51(2)
100-C30…100-C37 45(1-25/32)
127(5)
83(3-17/64)
105(4-9/64)
99(3-37/64)
6.5(17/64)
9.5(3/8)
2 @ 4.5(2 @ 3/16)
60(2-23/64)
35(1-25/64) ➊
16.5(21/32)
51(2)
193-TB…100-C3…100-C37 60
(2-23/64)140
(5-33/64)97
(3-13/16)105
(4-9/64)99
(3-37/64)6.5
(17/64)6.5
(17/64)2 @ 4.5
(2 @ 3/16)60
(2-23/64)35
(1-25/64) ➊16.5
(21/32)57
(2-1/4)
100-C43 60(2-23/64)
140(5-33/64)
97(3-13/16)
107(4-7/32)
103(4-3/32)
6.5(17/64)
8.5(21/64)
2 @ 4.5(2 @ 3/16)
60(2-23/64)
45(1-25/32) ➊
16.5(21/32)
57(2-1/4)
193-TC… 100-C60…100-C85 72(2-53/64)
185(7-9/32)
120(4-23/32)
125(4-15/16)
120(4-23/32)
8.5(21/64)
28.5(1-1/8)
4 @ 5.4(4 @ 7/32)
100(3-15/16)
55(2-11/64) ➊
16.5(21/32)
82(3-15/64)
Cat. No. a b b1 c c1 c2 ød d1 d2 e1 e2
193-TA… 45(1-25/32)
85(3-11/32)
44(1-47/64)
95(3-47/64)
90(3-35/64)
5(13/64)
2 @ 4.5(2 @ 3/16)
60…75(2-23/64…2-61/64)
35(1-25/64) ➊
16(5/8)
3(1/8)
193-TC… 60(2-23/64)
90(3-35/64)
44(1-47/64)
117(4-49/64)
112(4-13/32)
15(19/32)
2 @ 5.4(2 @ 7/32)
75(2-61/64)
50(1-31/32) ➊
16(5/8)
0(0)
193-TDC90 100(3-15/16)
120(4-23/32) — 135
(5-5/16) — 5(13/64)
4 @ 6.2(4 @ 1/4)
74(2-29/32)
80(3-5/32)
16(5/8)
7(9/32)
193-TA…, 193-TB…, 193-TC…
⊇
⊄
193-TDC90193-TA…, 193-TC…
➊
➊
➋
167
Bulletin 193-MBimetallic Overload Relays
Overview/Product Selection/Specifications
Product Selection
SpecificationsThermal Overload Relays
Circuit Diagrams
Bulletin 193-M — Bimetallic Overload Relays• Phase Failure Sensitivity• Temperature Compensation• Optional Auxiliary Contact (1 N.O. Contact)• Manual Reset/Stop Button• Built-in Connection Between N.C. Trip Contact (95) and Contactor Coil Terminal (A2)• “Trip Free” Construction• Trip IndicatorBulletin 193-M thermal overload relays are designed for use with Bulletin 100-M contactors and Bulletin 104-M reversing contactors. These class 10 ambient compensated thermal overload relays use integral heater elements; therefore, additional heater elements are not required.The trip setting is adjustable over the listed motor full load current range. The overload relay can be operated in a manual reset mode only. An isolated normally open contact is optional.
Table of ContentsProduct Selection..............167Specifications....................168Approximate Dimensions.168Conformity to StandardsIEC 60947-1IEC 60947-4 Type 2 CoordinationApprovalsUL ListedCSA CertifiedCE
Mounts on Setting Range [A] Cat. No.Max. current rating of backup gL fuse [A]
IEC Coordination Type Type 1 Type 2
100-M Contactor
M05…M12
0.10…0.15 193-M-A15 25 10.15…0.23 193-M-A23 25 10.23…0.35 193-M-A35 25 20.35…0.55 193-M-A55 25 20.55…0.8 193-M-A80 25 20.8…1.2 193-M-B12 25 41.2…1.8 193-M-B18 25 41.8…2.7 193-M-B27 25 62.7…4 193-M-B40 25 104…6 193-M-B60 25 16
M09…M126…7.7 193-M-B77 25 207.5…9 193-M-B90 25 20
M128.8…10.5 193-M-C10 25 —
10.4…12.5 193-M-C12 25 —193-M Overload Relay(Optional N.O. Auxiliary Contact) — — 193-M-F10 — —
2-phase 3-phase1-phase
K1 K1 K1
168
Bulletin 193-MBimetallic Overload Relays
Specifications, Continued
Trip Characteristics • Time/current characteristics of thermal overload relay
Mean value of tolerance bands 3-phase heated. Full line curves relate to cold relay. Dashed curves relate to relay at operating temperature (at set current load).Tolerance trip time ±20%, ±10% for current.Function limits and temperature compensation from –25oC…+75oC.Tripping limit specified in IEC 60947-4 for –5oC…+40oC are included in the –20oC…60oC range.Specified points relative to operating temperature condition; in compliance with IEC 60947-4.
• Single phasing (phase failure):Trip limits 1.05…1.25 of set current IeF (1.05…1.32 IeF is permissible according to IEC 60947-4).For motors up to 10 kW, the 2-phase trip at 1.25 IeF max. guarantees heat buildup limitation to the value that occurs in the event of a 3-phase trip at 1.2 IeF.
Specifications Approximate Dimensions — 193-M on 100-M ContactorDimensions are in millimeters. Dimensions are not intended to be used for manufacturing purposes.
12.5 A
Main CircuitRated Insulation Voltage
IEC [V]cULus [V]
500600
Max. Wire SizeIEC Fine Stranded w/ Ferrule [mm2]
Coarse Stranded or Solid [mm2]cULus Stranded or Solid [AWG]
2 x (1…2.5)2 x (1.5…4)2 x (14…10)
Recommended Torque [Nm][lb-in]
1.4…2.012…20
Control CircuitRated Insulation Voltage
IEC [V]cULus [V]
500600
Rated Operating CurrentAC-12 [A]AC-15 220…240V [A]
380…415 [A]
—
Max. Wire SizeIEC Fine Stranded w/ Ferrule [mm2]
Coarse Stranded or Solid [mm2]cULus Stranded or Solid [AWG]
2 x (0.75…2.5)2 x (0.75…4)2 x (18…14)
Recommended Torque [Nm][lb-in]
1.211
General
Standards Compliance IEC60947, DIN VDE 0660, UL508, CSA22.2, No. 14
Approvals CE, cULusAmbient Temperature
OpenEnclosed
-20…+60°C (-4…+140°F)-20…+40°C (-4…+104°F)
169
Bulletin 190/191Eco and Compact Combination Starters
Overview/Product Selection
Your order must include: cat. no. of the starter selected and, if required, cat. no. of any accessories.
Product Line Overview
Bulletin 190 Eco and Compact Combination Starters• Power Range 0.1…45 A• Bulletin 190E/191E Modular Eco Starters• Bulletin 190S/191S Pre-wired Compact Starters• Uses Bulletin 140M Motor Protection Circuit Breakers (MPCBs) and Bulletin 100-C or
100-M Contactors 140M is UL/CSA Approved as Manual Self-Protected (Type E) Combination Starters
• Type 2 Coordination• Mounts to DIN Rail(s) or Screw Mounts
Table of ContentsProduct Selection ..............170Accessories ........................177SpecificationsFactory Options . . . . . . . . . .177
Conformity to StandardsIEC 947-1/2/4/5IEC 204-1
ApprovalsCECSA CertifiedUL Listed
Eco Starter with 100-M Miniature
Contactor
Eco Starter with 100-C IEC Contactor
Reversing Eco Starter with
100-M Miniature Contactor
Reversing Eco Starter with 100-C IEC Contactor
Compact Combination Starter (25 A)
Compact Combination Starter (45 A)
Reversing Compact
Combination Starter (25 A)
Reversing Compact
Combination Starter (45 A)
AC Coils
DC Coils — — —
Standards ComplianceUL Listed/ CSA Certified See page 176
CE
IEC 60947
Type 2 Coordination See page 176
ComponentsMPCB 140M-C 140M-C, -D 140M-C 140M-C, -D 140M-C, -D 140M-F 140M-C, -D 140M-FContactor 100-M 100-C 104-M 104-C 100-C 100-C 104-C 104-C
Bulletin 190EEco Starters
170
Product Selection
AC or DC Control Coils
⊗ Voltage Suffix Codes for AC or DC Control
➊ 1 N.O. auxiliary contact on contactor is standard. See Factory Options on page 177 for additional auxiliary contact configurations.➋ UL Pending.
IndexMotor Current Adjustment
Range[A]
Magnetic Trip Current
[A]
Max. Hp, 3-phase Non-Reversing Starter ➊Cat. No.200V 230V 460V 575V
C-Frame
➋ 0.10…0.16 2.1 — — — — 190E-MN⊗ 2-CA16X
➋ 0.16…0.25 3.3 — — — — 190E-MN⊗ 2-CA25X
➋ 0.25…0.40 5.2 — — — — 190E-MN⊗ 2-CA40X
➋ 0.40…0.63 8.2 — — — — 190E-MN⊗ 2-CA63X
➋ 0.63…1.00 13 — — 1/2 3/4 190E-MN⊗ 2-CB10X
➋ 1.00…1.60 21 — — 1 1 190E-MN⊗ 2-CB16X
➋ 1.60…2.50 33 1/2 3/4 1-1/2 2 190E-MN⊗ 2-CB25X
➋ 2.50…4.00 52 1 1 3 3 190E-MN⊗ 2-CB40X
➋ 4.00…6.30 82 1-1/2 2 5 5 190E-NN⊗ 2-CB63X
➋ 6.30…10.0 130 2 2 5 5 190E-NN⊗ 2-CC10X
Voltage 24V 48V 100V 100…120V 220…230V 230…240V 380V
50 Hz KD KH D — A — KK
60 Hz KD KH — D — A KK
DC Z24 — — — — — —
• 190E Modular Eco Starter using Bulletin 140M Motor Protection Circuit Breaker and Bulletin 100-M Mini Contactor• Mounting Options:
Snap Fixing on (1) 35 mm DIN Rail
171
Bulletin 190EEco Starters
Product Selection, Continued
AC Control Coils
➊ 1 N.O. auxiliary contact on contactor is standard. See Factory Options on page 177 for additional auxiliary contact configurations.➋ UL Pending.
⊗ Standard Voltage Suffix Codes for AC Control
IndexMotor Current Adjustment
Range[A]
Magnetic Trip Current[A]
Max. Hp, 3-phase Non-Reversing Starter ➊Cat. No.200V 230V 460V 575V
C-Frame➋ 0.10…0.16 2.1 — — — — 190E-AN⊗ 2-CA16X➋ 0.16…0.25 3.3 — — — — 190E-AN⊗ 2-CA25X➋ 0.25…0.40 5.2 — — — — 190E-AN⊗ 2-CA40X➋ 0.40…0.63 8.2 — — — — 190E-AN⊗ 2-CA63X➋ 0.63…1.00 13 — — 1/2 3/4 190E-AN⊗ 2-CB10X➋ 1.00…1.60 21 — — 1 1 190E-AN⊗ 2-CB16X➋ 1.60…2.50 33 1/2 3/4 1-1/2 2 190E-AN⊗ 2-CB25X➋ 2.50…4.00 52 1 1 3 3 190E-AN⊗ 2-CB40X➋ 4.00…6.30 82 1-1/2 2 5 5 190E-AN⊗ 2-CB63X➋ 6.30…10.0 130 2 3 7-1/2 10 190E-BN⊗ 2-CC10X➋ 10.0…16.0 208 3 5 10 10 190E-CN⊗ 2-CC16X➋ 14.5…20.0 260 5 7-1/2 15 15 190E-DN⊗ 2-CC20X➋ 18.5…25.0 325 5 7-1/2 15 15 190E-DN⊗ 2-CC25X
D-Frame➋ 1.60…2.50 33 1/2 3/4 1-1/2 2 190E-AN⊗ 2-DB25X➋ 2.50…4.00 52 1 1 3 3 190E-AN⊗ 2-DB40X➋ 4.00…6.30 82 1-1/2 2 5 5 190E-AN⊗ 2-DB63X➋ 6.30…10.0 130 2 3 7-1/2 10 190E-BN⊗ 2-DC10X➋ 10.0…16.0 208 3 5 10 10 190E-CN⊗ 2-DC16X➋ 14.5…20.0 260 5 7-1/2 15 15 190E-DN⊗ 2-DC20X➋ 18.5…25.0 325 5 7-1/2 15 15 190E-DN⊗ 2-DC25X
Voltage 12V 24V 32V 36V 42V 48V 100V 100…110V 110V 120V 127V 200V 200…
220V200…230V 208V 208…
240V
50 Hz R K V W X Y KP — D P S KG — — — —
60 Hz Q J — V — X — KP — D — — KG — H L
50/60 Hz — KJ — — — KY KP — KD — — KG — KL — —
Voltage 220…230V 230V 230…
240V 240V 277V 347V 380V 380…400V 400V 400…
415V 440V 480V 500V 550V 600V
50 Hz F — VA T — — — N — G B — M C —
60 Hz — — — A T I E — — — N B — — C
50/60 Hz — KF — KA — — — — KN — KB — — — —
• 190E Modular Eco Starter using Bulletin 140M Motor Protection Circuit Breaker and Bulletin 100-C MCS Contactor• Mounting Options:
-Snap Fixing on (1) 35 mm DIN Rail
Bulletin 190SCompact Starters
172
0Product Selection, Continued
AC or DC Control Coils
➊ 1 N.O. + 1 N.C. auxiliary contacts on 140M is standard. 1 N.O. auxiliary contact on 100C contactor is standard. See Factory Options on page 177 for additional auxiliary contact configurations.
⊗ Standard Voltage Suffix Codes for AC or DC Control
⊗ Standard Voltage Suffix Codes for DC Control
➋ For pricing information, consult the Master Price List or your local Allen-Bradley distributor.
IndexMotor Current
Adjustment Range[A]
Magnetic Trip Current[A]
Max. Hp, 3-phase Non-Reversing Starter ➊Cat. No.200V 230V 460V 575V
C-Frame1 0.10…0.16 2.1 — — — — 190S-AN⊗ 2-CA16C2 0.16…0.25 3.3 — — — — 190S-AN⊗ 2-CA25C3 0.25…0.40 5.2 — — — — 190S-AN⊗ 2-CA40C4 0.40…0.63 8.2 — — — — 190S-AN⊗ 2-CA63C5 0.63…1.00 13 — — 1/2 3/4 190S-AN⊗ 2-CB10C6 1.00…1.60 21 — — 1 1 190S-AN⊗ 2-CB16C7 1.60…2.50 33 1/2 3/4 1-1/2 2 190S-AN⊗ 2-CB25C8 2.50…4.00 52 1 1 3 3 190S-AN⊗ 2-CB40C9 4.00…6.30 82 1-1/2 2 5 5 190S-AN⊗ 2-CB63C10 6.30…10.0 130 2 3 7-1/2 10 190S-BN⊗ 2-CC10C11 10.0…16.0 208 3 5 10 15 190S-CN⊗ 2-CC16C12 14.5…20.0 260 5 7-1/2 15 15 190S-DN⊗ 2-CC20C13 18.5…25.0 325 5 7-1/2 15 15 190S-DN⊗ 2-CC25C
D-Frame14 1.60…2.50 33 1/2 3/4 1-1/2 2 190S-AN⊗ 2-DB25C16 2.50…4.00 52 1 1 3 3 190S-AN⊗ 2-DB40C18 4.00…6.30 82 1-1/2 2 5 5 190S-AN⊗ 2-DB63C20 6.30…10.0 130 2 3 7-1/2 10 190S-BN⊗ 2-DC10C22 10.0…16.0 208 3 5 10 15 190S-CN⊗ 2-DC16C24 14.5…20.0 260 5 7-1/2 15 15 190S-DN⊗ 2-DC20C26 18.5…25.0 325 5 7-1/2 15 15 190S-DN⊗ 2-DC25C
F-Frame28 6.30…10.0 130 3 3 7-1/2 10 190S-EN⊗ 3-FC10C29 10.0…16.0 208 3 5 10 15 190S-EN⊗ 3-FC16C30 14.5…20.0 260 5 7-1/2 15 20 190S-EN⊗ 3-FC20C31 18.5…25.0 325 5 10 20 25 190S-EN⊗ 3-FC25C32 23.0…32.0 416 10 10 25 30 190S-FN⊗ 3-FC32C33 32.0…45.0 585 10 15 30 30 190S-GN⊗ 3-FC45C
Voltage 12V 24V 32V 36V 42V 48V 100V 100-110V 110V 120V 127V 200V 200-
220V200-230V 208V 208-
240V
50 Hz R K V W X Y KP — D P S KG — — — —
60 Hz Q J — V — X — KP — D — — KG — H L
50/60 Hz — KJ — — — KY KP — KD — — KG — KL — —
Voltage 220-230V 230V 230-
240V 240V 277V 347V 380V 380-400V 400V 400-
415V 440V 480V 500V 550V 600V
50 Hz F — VA T — — — N — G B — M C —
60 Hz — — — A T I E — — — N B — — C
50/60 Hz — KF — KA — — — — KN — KB — — — —
190SVoltage 6…12V 12V 24V 24V w/
diode 36V 48V 60V 64V 72V 80V 110V 115V 125V 220 V230V 240V
Code ZR ZQ ZJ DJ ➋ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
• 190S Compact Combination Starter using 140M Motor Protection Circuit Breaker and 100-C Contactor • Auxiliary Contacts Wired to Terminal Block at Bottom of Starter Assembly• Mounting Options:-Screw Fixing-Snap Fixing on (1) or (2) 35 mm DIN Rails-Snap Fixing on (1) 75 mm DIN Rail
173
Bulletin 191EReversing Eco Starters
Product Selection, Continued
AC Control Coils
⊗ Standard Voltage Suffix Codes for AC Control
➊ 1 N.O. auxiliary contact on contactor is standard. See Factory Options on page 177 for additional auxiliary contact configurations.➋ UL Pending.
IndexMotor Current Adjustment
Range[A]
Magnetic Trip Current
[A]
Max. Hp, 3-phase Non-Reversing Starter ➊Cat. No.200V 230V 460V 575V
C-Frame
➋ 0.10…0.16 2.1 — — — — 191E-MN⊗ 3-CA16X
➋ 0.16…0.25 3.3 — — — — 191E-MN⊗ 3-CA25X
➋ 0.25…0.40 5.2 — — — — 191E-MN⊗ 3-CA40X
➋ 0.40…0.63 8.2 — — — — 191E-MN⊗ 3-CA63X
➋ 0.63…1.00 13 — — 1/2 3/4 191E-MN⊗ 3-CB10X
➋ 1.00…1.60 21 — — 1 1 191E-MN⊗ 3-CB16X
➋ 1.60…2.50 33 1/2 3/4 1-1/2 2 191E-MN⊗ 3-CB25X
➋ 2.50…4.00 52 1 1 3 3 191E-MN⊗ 3-CB40X
➋ 4.00…6.30 82 1-1/2 2 5 5 191E-NN⊗ 3-CB63X
➋ 6.30…10.0 130 2 2 5 5 191E-NN⊗ 3-CC10X
Voltage 24V 48V 100V 100…120V 220…230V 230…240V 380V
50 Hz KD KH D — A — KK
60 Hz KD KH — D — A KK
• 191E Modular Eco Starter using 140M Motor Protection Circuit Breaker and 104-M Reversing Mini Contactor• Mounting Options:
-Snap Fixing on (1) 35 mm DIN Rail
Bulletin 191EReversing Eco Starters
174
Product Selection, Continued
AC Control Coils
➊ 1 N.O. auxiliary contact on contactor is standard. See Factory Options on page 177 for additional auxiliary contact configurations.➋ UL Pending.
⊗ Standard Voltage Suffix Codes for AC Control
IndexMotor Current Adjustment
Range[A]
Magnetic Trip Current
[A]
Max. Hp, 3-phase Non-Reversing Starter ➊Cat. No.200V 230V 460V 575V
C-Frame➋ 0.10…0.16 2.1 — — — — 191E-AN⊗ 3-CA16X➋ 0.16…0.25 3.3 — — — — 191E-AN⊗ 3-CA25X➋ 0.25…0.40 5.2 — — — — 191E-AN⊗ 3-CA40X➋ 0.40…0.63 8.2 — — — — 191E-AN⊗ 3-CA63X➋ 0.63…1.00 13 — — 1/2 3/4 191E-AN⊗ 3-CB10X➋ 1.00…1.60 21 — — 1 1 191E-AN⊗ 3-CB16X➋ 1.60…2.50 33 1/2 3/4 1-1/2 2 191E-AN⊗ 3-CB25X➋ 2.50…4.00 52 1 1 3 3 191E-AN⊗ 3-CB40X➋ 4.00…6.30 82 1-1/2 2 5 5 191E-AN⊗ 3-CB63X➋ 6.30…10.0 130 2 3 7-1/2 10 191E-BN⊗ 3-CC10X➋ 10.0…16.0 208 3 5 10 10 191E-CN⊗ 3-CC16X➋ 14.5…20.0 260 5 7-1/2 15 15 191E-DN⊗ 3-CC20X➋ 18.5…25.0 325 5 7-1/2 15 15 191E-DN⊗ 3-CC25X
D-Frame➋ 1.60…2.50 33 1/2 3/4 1-1/2 2 191E-AN⊗ 3-DB25X➋ 2.50…4.00 52 1 1 3 3 191E-AN⊗ 3-DB40X➋ 4.00…6.30 82 1-1/2 2 5 5 191E-AN⊗ 3-DB63X➋ 6.30…10.0 130 2 3 7-1/2 10 191E-BN⊗ 3-DC10X➋ 10.0…16.0 208 3 5 10 10 191E-CN⊗ 3-DC16X➋ 14.5…20.0 260 5 7-1/2 15 15 191E-DN⊗ 3-DC20X➋ 18.5…25.0 325 5 7-1/2 15 15 191E-DN⊗ 3-DC25X
Voltage 12V 24V 32V 36V 42V 48V 100V 100…110V 110V 120V 127V 200V 200…
220V200…230V 208V 208…
240V
50 Hz R K V W X Y KP — D P S KG — — — —
60 Hz Q J — V — X — KP — D — — KG — H L
50/60 Hz — KJ — — — KY KP — KD — — KG — KL — —
Voltage 220…230 230 230…
240 240V 277V 347V 380V 380…400V 400V 400…
415V 440V 480V 500V 550V 600V
50 Hz F — VA T — — — N — G B — M C —
60 Hz — — — A T I E — — — N B — — C
50/60 Hz — KF — KA — — — — KN — KB — — — —
• 191E Modular Eco Starter using 140M Motor Protection Circuit Breaker and 104-C Reversing MCS Contactor• Mounting Options:
-Snap Fixing on (1) 35 mm DIN Rail
175
Bulletin 191SReversing Compact Starters
Product Selection, Continued
AC Control Coils
➊ 1 N.O. + 1 N.C. auxiliary contacts on 140M is standard. 1 N.O. auxiliary contact on 100C contactor is standard. See Factory Options on page 177 for additional auxiliary contact configurations.
⊗ Standard Voltage Suffix Codes for AC Control
IndexMotor Current Adjustment
Range[A]
Magnetic Trip Current[A]
Max. Hp, 3-phase Non-Reversing Starter ➊Cat. No.200V 230V 460V 575V
C-Frame1 0.10…0.16 2.1 — — — — 191S-AN⊗ 3-CA16C2 0.16…0.25 3.3 — — — — 191S-AN⊗ 3-CA25C3 0.25…0.40 5.2 — — — — 191S-AN⊗ 3-CA40C4 0.40…0.63 8.2 — — — — 191S-AN⊗ 3-CA63C5 0.63…1.00 13 — — 1/2 3/4 191S-AN⊗ 3-CB10C6 1.00…1.60 21 — — 1 1 191S-AN⊗ 3-CB16C7 1.60…2.50 33 1/2 3/4 1-1/2 2 191S-AN⊗ 3-CB25C8 2.50…4.00 52 1 1 3 3 191S-AN⊗ 3-CB40C9 4.00…6.30 82 1-1/2 2 5 5 191S-AN⊗ 3-CB63C10 6.30…10.0 130 2 3 7-1/2 10 191S-BN⊗ 3-CC10C11 10.0…16.0 208 3 5 10 15 191S-CN⊗ 3-CC16C12 14.5…20.0 260 5 7-1/2 15 15 191S-DN⊗ 3-CC20C13 18.5…25.0 325 5 7-1/2 15 15 191S-DN⊗ 3-CC25C
D-Frame14 1.60…2.50 33 1/2 3/4 1-1/2 2 191S-AN⊗ 3-DB25C16 2.50…4.00 52 1 1 3 3 191S-AN⊗ 3-DB40C18 4.00…6.30 82 1-1/2 2 5 5 191S-AN⊗ 3-DB63C20 6.30…10.0 130 2 3 7-1/2 10 191S-BN⊗ 3-DC10C22 10.0…16.0 208 3 5 10 15 191S-CN⊗ 3-DC16C24 14.5…20.0 260 5 7-1/2 15 15 191S-DN⊗ 3-DC20C26 18.5…25.0 325 5 7-1/2 15 15 191S-DN⊗ 3-DC25C
Voltage 12V 24V 32V 36V 42V 48V 100V 100-110V 110V 120V 127V 200V 200-
220V200-230V 208V 208-
240V
50 Hz R K V W X Y KP — D P S KG — — — —
60 Hz Q J — V — X — KP — D — — KG — H L
50/60 Hz — KJ — — — KY KP — KD — — KG — KL — —
Voltage 220-230V 230V 230-
240V 240V 277V 347V 380V 380-400V 400V 400-
415V 440V 480V 500V 550V 600V
50 Hz F — VA T — — — N — G B — M C —
60 Hz — — — A T I E — — — N B — — C
50/60 Hz — KF — KA — — — — KN — KB — — — —
• 191S Compact Combination Starter using 140M Motor Protection Circuit Breaker and 104-C Reversing MCS Contactor • Auxiliary Contacts Wired to Terminal Block at Bottom of Starter Assembly• Mounting Options:
-Screw Fixing-Snap Fixing on (1) or (2) 35 mm DIN Rails-Snap Fixing on (1) 75 mm DIN Rail
Bulletin 190/191ECO and Compact Combination Starters
176
Specifications
UL Listed Application Ratings
Index
Motor Current
Adjustment Range (A)
Magnetic Release
Operating Current (A)
Max. Hp, 60 Hz Max. Fault Current 480Y/277V
Max. Fault Current 600Y/347V Group Installation
200V 230V 460V 575VType 1Iq [kA]
Type 2Iq [kA]
Type EIq [kA]
Type 1Iq [kA]
Type 2Iq [kA]
Type EIq [kA]
480Y/277V Iq [kA]
600Y/347V Iq [kA]
Max. Fuse or CB per
NEC[kA]
C Frame1 0.10…0.16 2.1 — — — — 65 65 65 47 47 47 65 47 4502 0.16…0.25 3.3 — — — — 65 65 65 47 47 47 65 47 4503 0.25…0.40 5.2 — — — — 65 65 65 47 47 47 65 47 4504 0.40…0.63 8.2 — — — — 65 65 65 47 47 47 65 47 4505 0.63…1.0 13 — — 1/2 3/4 65 65 65 47 47 47 65 47 4506 1.0…1.6 21 — — 1 1 65 65 65 47 47 47 65 47 4507 1.6…2.5 33 1/2 3/4 1-1/2 2 65 65 65 10 10 — 65 10 4508 2.5…4.0 52 1 1 3 3 65 — — 10 — — 65 10 4509 4.0…6.3 82 1-1/2 2 5 5 65 — — — — — 65 — 45010 6.3…10 130 3 3 7-1/2 10 65 — — — — — 65 — 45011 10…16 208 3 5 10 15 10 — — — — — 10 — 45012 14.5…20 260 5 7-1/2 15 15 10 — — — — — 10 — 45013 18…25 325 5 7-1/2 15 15 10 — — — — — 10 — 450
D Frame14 1.6…2.5 33 1/2 3/4 1-1/2 2 65 65 65 30 — — 65 30 45015 1.6…2.5 33 1/2 3/4 1-1/2 2 65 65 65 30 30 30 65 30 45016 2.5…4.0 52 1 1 3 3 65 65 — 30 — — 65 30 45017 2.5…4.0 52 1 1 3 3 65 65 65 30 30 30 65 30 45018 4.0…6.3 82 1-1/2 2 5 5 65 65 — 30 — — 65 30 45019 4.0…6.3 82 1-1/2 2 5 5 65 65 65 30 30 30 65 30 45020 6.3…10 130 3 3 7-1/2 10 65 65 — 30 — — 65 30 45021 6.3…10 130 3 3 7-1/2 10 65 65 65 30 30 30 65 30 45022 10…16 208 3 5 10 15 65 65 — 30 — — 65 30 45023 10…16 208 3 5 10 15 65 65 65 30 30 30 65 30 45024 14.5…20 260 5 7-1/2 15 15 65 65 — — — — 65 — 45025 14.5…20 260 5 7-1/2 15 20 65 65 65 — — — 65 — 45026 18…25 325 5 7-1/2 15 15 65 65 — — — — 65 — 45027 18…25 325 7-1/2 7-1/2 15 20 65 65 65 — — — 65 — 450
F Frame28 6.3…10 130 3 3 7-1/2 10 65 65 65 30 30 30 65 30 60029 10…16 208 3 5 10 15 65 65 65 30 30 30 65 30 60030 14.5…20 260 5 7-1/2 15 20 65 65 65 30 30 30 65 30 60031 18…25 325 7-1/2 10 20 25 65 65 65 30 30 30 65 30 60032 25…32 416 10 10 25 30 65 65 65 30 30 30 65 30 60033 32…45 585 10 15 30 30 65 65 65 30 30 — 65 30 600
177
Bulletin 190Eco and Compact Combination Starters
0 Specifications
Bulletin 190E/191E/190S/191S Factory Installed ModificationsNote: For modifications change (option code ➊ ) and — add (option code ➋ ) for desired features to cat. no.
➊ Change option code X to desired auxiliary contact: 190E-MND2-CA16X
➋ Add desired option codes AFTER auxiliary contact option code: 190S-AND2-CA16X-KY
➌ 191E and 191S Reversing Eco Starters will have two of these accessories installed (one on each contactor).
Bulletin 140M Auxiliary and Trip ContactsAvailability
190E 191E 190S 191SX Without Auxiliary and Trip Contacts Standard Standard NA NAA Auxiliary Contact 1 N.C. Available Available NA NAB Auxiliary Contact 1 N.O. Available Available NA NAC Auxiliary Contact 1 N.O. + 1 N.C. Available Available Standard StandardD Auxiliary Contact 2 N.O. Available Available Available AvailableE Auxiliary Contact 2 N.C. Available Available Available AvailableR 1 N.O. Trip + 1 N.C. Auxiliary Contact Available Available Available AvailableS 1 N.O. Trip + 1 N.O. Auxiliary Contact Available Available Available Available
Modifications, AccessoriesAvailability
190E 191E 190S 191SJE ➌ Electronic Interfaces (100-C) Available Available Available AvailableR ➌ Surge Suppressor RC (100-C) Available Available Available AvailableV ➌ Surge Suppressor Varistor (100-C) Available Available Available AvailableD ➌ Surge Suppressor Diode (100-C) Available Available Available AvailableKN Lockable Twist Knob (140M) - Black Available Available Available AvailableKY Lockable Twist Knob (140M) - Red/Yellow Available Available Available AvailableTE Spacing Adapter for UL508 Type E Available Available Available Available
Additional Contactor Auxiliaries (Side Mount)S01 ➌ 1 N.C. Available Available Available AvailableS10 ➌ 1 N.O. Available Available Available AvailableS11 ➌ 1 N.O. + 1 N.C. Available Available Available AvailableS20 ➌ 2 N.O. Available Available Available Available
Additional Contactor Auxiliaries (Front Mount)F11 ➌ 1 N.O. + 1 N.C. Available Available NA NAF20 ➌ 2 N.O. Available Available NA NAF22 ➌ 2 N.O. + 2 N.C. Available Available NA NA
Additional Bulletin 140M Auxiliaries (Side Mount)A02 2 N.C. Available Available Available AvailableA20 2 N.O. Available Available Available AvailableA11 1 N.O. + 1 N.C. Available Available Available Available
Additional Bulletin 140M Trip Contacts (Side Mount)R00 1 N.O. Thermal-Mag + 1 N.O. Mag Only Available Available Available AvailableR01 1 N.O. Thermal-Mag + 1 N.C. Mag Only Available Available Available AvailableR10 1 N.C. Thermal-Mag + 1 N.O. Mag Only Available Available Available AvailableR11 1 N.C. Thermal-Mag + 1 N.C. Mag Only Available Available Available AvailableM11 1 N.O. Mag Only + 1 N.C. Mag Only Available Available Available Available
Bulletin 190Eco and Compact Combination Starters
178
Wiring Diagrams
IEC Wiring Diagram Cat. No. 190S-A…D
IEC Wiring Diagram Cat. No. 190S-E…G
190S-_ _ _ 2- _ _ _ _ C 190S-_ _ _ 2- _ _ _ _ S
190S-_ _ _ 3- _ _ _ _ S190S-_ _ _ 3- _ _ _ _ C
179
Bulletin 190Eco and Compact Combination Starters
Approximate Dimensions
Dimensions are shown in millimeters. Dimensions are not intended to be used for manufacturing purposes.
190E/191E
190S-A…D
Cat. No. a a1 b b1 b2 c c1190E Eco Starters
190E-MN…190E-NN45 (1-25/32) 0
164 (6-15/32)45 (1-25/32) —
45 (1-25/32)70 (2-49/64)
190E-AN…190E-DN 178 (7) 83.5 (3-19/64)191E Reversing Eco Starters
191E-MN…191E-NN45 (1-25/32) 0
164 (6-15/32)45 (1-25/32) —
45 (1-25/32)70 (2-49/64)
191E-AN…191E-DN 178 (7) 83.5 (3-19/64)
A[mm]
B[mm]
C[mm]
190S-AN140M-C 112
107100-FA, 100-FC
100-FPT100-FL
138157160
190S-BN190S-CN
140M-D 122190S-DN190S-ANZ
140M-C 134.5132.5 100-FA, 100-FC 163.5190S-BNZ
190S-CNZ 140M-D 144.5
190S-DNZ140M-C 157
150 100-FA, 100-FC 181140M-D 167
a1 c
c1
3 (3
/32)
aa
b1b2 b
a
b1b2 b
5.5
45
9
Ø5.4
918
9
178
Ø5.4
345.5 5.5
215
A
4
8
BC
Bulletin 190Eco and Compact Combination Starters
180
Approximate Dimensions, Continued
Dimensions are shown in millimeters. Dimensions are not intended to be used for manufacturing purposes.
190S-A…D
115˚
25˚
25
90˚ 90˚
25
Safety Clearance
yyyy25
75
135
21
15
35
101.
5
11
35
3.5
46.2
7.5
125±
1
Bulletin 190Eco and Compact Combination Starters
181
Approximate Dimensions, Continued
Dimensions are shown in millimeters. Dimensions are not intended to be used for manufacturing purposes.
190S-E and 190S-F Approximate Dimensions190S-G Approximate Dimensions
190-E…G Approximate Dimensions
A[mm]
B[mm]
C[mm]
190S-EN
140M-F135 124
100-FB100-FPT100-FL
154.5173.5176.5190S-FN
190S-ENZ179 168 100-FB 198.5
190S-FNZ
5.5
54
9
Ø5.4
918
9
200
Ø5.4
435.5 5.5
238
A
4
8
BC
A[mm]
B[mm]
C[mm]
190S-GN140M-F
135 118.5100-FB
100-FPT100-FL
157176179
190S-GNZ 179 162.5 100-FB 201
5.5
54
9
Ø5.4
918
9
200
Ø5.4
435.5 5.5
238
A
4
8
BC
90
˚
25˚
25
90˚ 90˚
25
AC
25˚
DC
Safety Clearance
35
3.5
56
7.5
125±
1
yy
25
75
145.
5
21
Bulletin 190Coordinated Starters
182
Overview
Your order must inlude the cat. no. of the manual interrupter, contactor module, trip unit, operating handle adapter, or operating shaft and, if required, the cat. no. of any accessories.
Bulletin 190 Starters• Manual Interrupter — 40 A• Interchangeable Trip Units — 11 Ranges to 40 A• Contactor Module — 40 A, 20 kW @ 415V AC, Current Limiting Contact Structure• Coordinated Protected Starter (Applicable in North America Only)• Operating Handle Indicates “ON”, “OFF” and “TRIPPED”• Visible Isolation Gap with Trip Unit Removed• Short Circuit Trip Setting Dial• Overload Trip Setting Dial• Sealable Cover for Trip Setting Dials• Operating Handle Can Be Padlocked “OFF”• Type 2 Coordination with Integrated and Coordinated Protected Starters
Bulletin 190 Coordinated Starters are a family of modular components assembled into a series of high-performance motor starters. These starters reduce machine or process down time by lessening or eliminating component damage caused by short circuit current.
Table of ContentsProduct Selection ............. 183Accessories....................... 187Specifications.................... 190ApproximateDimensions........................ 197
Conformity to StandardsIEC 947-2, 947-4-1, 204-1, 364VDE 0100, 0106 Parts 101, 0110, 0113, 0660 Parts 101, 102, 104, 107
CSA C22.2 No. 14UL 508UL Listed for Group Motor installation
ApprovalsCECSA CertifiedUL Listed
183
Bulletin 190Coordinated Starters
Product Selection
System Circuit Breaker (to IEC 947-2) for Protection of Cables and Wiring ➊Note: Not for use in North America.
⊗ Voltage Suffix CodeThe Cat. No. as listed is incomplete. Select a Voltage Suffix Code from the table below to complete the Cat. No. Example: Cat. No. 190-A40⊗ becomes Cat. No. 190-A40J.
➊ The Bulletin 190 System Circuit Breaker and Combination Circuit Breaker cannot be utilized as a short circuit protective device in Canadian and U.S. applications. In order to be utilized as a circuit breaker in Canadian and U.S. applications, the device would have to meet the breaker requirements of CSA and UL respectively. The Bulletin 190 System Combination Circuit Breaker does not meet these requirements.
Description Cat. No.
ORDER Manual Interrupter 40A Ie 690V. 190-MN
ALSOORDER
Thermal Magnetic Trip Unit for
System Protection(Short Circuit trip
= 5 – 8.5 x Iu)
Adjustable Thermal Current Range (A)
Adjustable Magnetic Trip Current Range (A)
6…10 50…80 190-P100L
10…16 80…140 190-P160L
16…25 130…210 190-P250L
24…32 160…280 190-P320L
32…40 200…350 190-P400L
ORDERContactor ModuleorCurrent Limiter Module
190-A40 ⊗
190-CL1
Schematic Symbol:
Voltage 24V 110V 120V 208V 220V 240V 380V 415V 440V 480V 600V
50 Hz K D — — A — N B B — —
60 Hz J — D H — A — — G B C
DC Z
Contactor Module orCurrent Limiter ModuleCat. No. 190-A40⊗ or
Cat. No. 190-CL1+
Combination Circuit Breaker ➊
Circuit Breaker ➊
Trip Unit for System ProtectionCat. No. 190-P100L
Manual InterrupterCat. No. 190-MN
+
=
=
13 21
A1
A214 22
Bulletin 190Coordinated Starters
184
Product Selection, Continued
Manual Motor Starter and Protector ➊
➊ UL Listed Components — The Bulletin 190 manual motor starter/protector is CSA Certified and UL Listed. Suitable for use on a circuit capable of delivering 42 kA RMS SYM/600V or 65 kA RMS SYM/480V when protected by fuses or circuit breaker selected in accordance with the U.S. National Electrical Code.
Description Cat. No.
ORDER Manual Interrupter 40 AMP Ie 690 V Ui 190-MN
ALSO ORDER Trip Unit Adjustable Thermal Current Range (A)
Adjustable Magnetic Trip
Current Range (A)0.4…0.6 5…8 190-P0060.6…1.0 8…14 190-P0101.0…1.6 14…22 190-P0161.6…2.4 20…35 190-P0242.4…4 35…55 190-P0404…6 50…80 190-P060
6…10 80…140 190-P10010…16 130…220 190-P16016…27 200…350 190-P25024…32 275…425 190-P32032…42 350…500 190-P400
OR ALSO ORDER
Trip Unit withRelay Contacts —1 N.O. and 1 N.C.
Suitable for use withBulletin 190-MN or Bulletin 190-CPS40D.
Overload condition changes contact state. Usually wired to de-energize contactor coil on overload condition. Interrupter opens on short circuit only.
Note: This trip unit not compatible with 190 RC Remote Operators, 190 RT Shunt Trip, or 190 UV Undervoltage Trip Modules.
0.4…0.6 5…8 190-P006R
0.6…1.0 8…14 190-P010R
1.0…1.6 14…22 190-P016R
1.6…2.4 20…35 190-P024R
2.4…4 35…55 190-P040R
4…6 50…80 190-P060R
6…10 80…140 190-P100R
10…16 130…220 190-P160R
16…27 200…350 190-P250R
24…32 275…425 190-P320R
32…42 350…500 190-P400R
Schematic without Relay Contacts:
Trip Unit Cat. No. 190-P_ _ _
or+
Manual InterrupterCat. No. 190-MN
Trip Unit Cat. No. 190-P_ _ _R+
Manual Motor Starter andProtector=
185
Bulletin 190Coordinated Starters
Product Selection, Continued
Integrated Starter ➊
⊗ Voltage Suffix CodeThe Cat. No. as listed is incomplete. Select a Voltage Suffix Code from the table below to complete the Cat. No. Example: Cat. No. 190-A40⊗ becomes Cat. No. 190-A40J.
➊ UL Listed Components — The Bulletin 190 Integrated Starter is CSA Certified and UL Listed. Suitable for use on a circuit capable of delivering not more than 42,000 A. RMS Symmetrical at 600V AC, or 65,000A. RMS Symmetrical at 480V AC when protected by fuses or circuit breaker selected in accordance with the requirements of the U.S. National Electrical Code.
➋ A Trip Unit with Relay Contacts (1 N.O. and 1 N.C.) may be ordered. See page 184 for Cat. No.
Description Cat. No.ORDER Manual Interrupter 190-MNORDER Contactor Module 190-A40 ⊗
ALSO ORDER Trip Unit ➋ Adjustable Thermal Current Range (A)
Adjustable Magnetic Trip Current Range
(A)0.4…0.6 5…8 190-P0060.6…1.0 8…14 190-P0101.0…1.6 14…22 190-P0161.6…2.4 20…35 190-P0242.4…4 35…55 190-P0404…6 50…80 190-P060
6…10 80…140 190-P10010…16 130…220 190-P16016…27 200…350 190-P25024…32 275…425 190-P32032…42 350…500 190-P400
Schematic without Relay Contacts:
Voltage 24V 110V 120V 208V 220V 240V 380V 415V 440V 480V 600V50 Hz K D — — A — N B B — —60 Hz J — D H — A — — G B C
DC Z
Integrated Starter
Trip Unit Cat. No. 190-P_ _ _
Manual InterrupterCat. No. 190-MN
Contactor ModuleCat. No. 190-A40⊗+
+
=
14 22
A1
A2
13 21
Bulletin 190Coordinated Starters
186
Product Selection, Continued
Coordinated Protected Starter — North American Markets Only ➊
Meets CSA and UL Requirements for a Combination Starter.
⊗ Voltage Suffix CodeThe Cat. No. as listed is incomplete. Select a Voltage Suffix Code from the table below to complete the Cat. No. Example: Cat. No. 190-CPS40⊗ becomes Cat. No. 190-CPS40J.
➊ CSA Certified and UL Listed — Suitable for use on a circuit capable of delivering 100,000 amperes RMS SYM at 240V, 65,000 amperes RMS SYM at 480V or 42,000 amperes RMS SYM at 600V. Note: Ratings above 240V are based on Power Systems as follows: 480Y/277V AC; 600Y/347V AC (up through 190-P250) to the line side of this starter.
➋ 60 Hz only.➌ A Trip Unit with Relay Contacts (1 N.O. and 1 N.C.) may be ordered. See page 184 for Cat. No. and pricing.
Description Cat. No.ORDER Coordinated protected starter less trip unit 190-CPS40⊗ ➋
OR ORDER Reversing coordinated protected starter less trip unit 190R-CPS40⊗ ➋
ALSO ORDER Trip Unit ➌ Adjustable Thermal Current Range (A)
Adjustable Magnetic Trip Current Range
(A)0.4…0.6 5…8 190-P0060.6…1.0 8…14 190-P0101.0…1.6 14…22 190-P0161.6…2.4 20…35 190-P0242.4…4 35…55 190-P0404…6 50…80 190-P060
6…10 80…140 190-P10010…16 130…220 190-P16016…27 200…350 190-P25024…32 275…425 190-P32032…42 350…500 190-P400
Voltage 24V 110V 120V 208V 220V 240V 380V 415V 440V 480V 600V50 Hz K D — — A — N B B — —60 Hz J — D H — A — — G B C
DC Z
Coordinated Protected Starter
Coordinated ProtectedStarter Less Trip Unit
Cat. No. 190-CPS40⊗
Trip Unit Cat. No. 190-P
=
+
13 21
A1
A214 22
187
Bulletin 190Coordinated Starters
Accessories
Auxiliary Contacts ➊
Trip Indicating Contacts ➊
Three Phase Commoning Link
➊ 1 N.O., 1 N.C. internal auxiliary contacts furnished standard with the contactor module.042
Mounting Configuration Pkg. Qty. Cat. No.
Manual Interrupter
1 N.O., 1 N.C., Operate with interrupter
1190-A11
2 N.O., 2 N.C., Operate with interrupter 190-A22
Integrated StarterORCoordinated Protected Starter
1 N.O., 1 N.C., Operate with interrupter
1
190-A11C
2 N.O., 2 N.C., Operate with interrupter 190-A22C
1 N.O., 1 N.C., Operate with interrupter; 1 N.O., 1 N.C., Operate with contactor
190-A11-11
Contactor(when separately mounted) ➊ 1 N.O., 1 N.C. 1 190-AC11-11
Mounting Configuration Pkg. Qty. Cat. No.
Manual Interrupter 1 N.O., 1 N.C., Indicate short circuit;1 N.O., 1 N.C., Indicate overload 1 190-T11-11
Description Pkg. Qty. Cat. No.For line side connection of adjacent manual interrupters. 100A. (Sufficient room between units for auxiliary contacts, shunt trip or undervoltage trip module is provided.)
1 190-L13
Three Phase Link Terminal — (Not shown.) For use with commoning link above. 1 190-L2
Cat. No. 190-A11
Cat. No. 190-AC11-11
Cat. No. 190-A11-11
Bulletin 190Coordinated Starters
188
Accessories, Continued
Modules/Adaptors
➊ The use of an auxiliary contact with the manual interrupter is recommended.
Description Pkg. Qty. Cat. No.
Shunt Trip Module — Trips manual interrupter from a remote location using a voltage signal. Coils available (multi-voltage):
1
—
24…48V 50/60 Hz 24…60V DC 190-RT048
110…250V 50/60 Hz 110…250V DC 190-RT250
380…600V 50/60 Hz 380…600V DC 190-RT600
Undervoltage Trip Module — Trips manual interrupter on power loss (70…35% V). Prevents undesired restart upon power resumption. (Undervoltage protection) Coils available (multi-voltage):
1
24V 50/60 Hz 190-UV024
110V 50 Hz, 120V 60 Hz 190-UV120
220V 50 Hz, 240V 60 Hz 190-UV240
415/440V 50 Hz, 480V 60 Hz 190-UV480
500V 50 Hz, 600V 60 Hz 190-UV600
208V 60 Hz 190-UV208
380V 50 Hz 190-UV380
Remote Operator Module ➊ — Operates manual interrupter from a remote location using a voltage signal. Provides “ON,” “OFF,” and “RESET” functions. Includes a lockout provision. 50,000 operations life.
1
—
Signalled and powered at same voltage —
110…120V AC/DC 190-RCE120
220…250V AC/DC 190-RCE230
380…415V AC 190-RCE400
440V AC 190-RCE440
Signalled at 24V AC or DC. Powered at separate voltages shown below.
1
—
24V AC/DC 190-RCS24
48V AC/DC 190-RCS48
110…120V AC/DC 190-RCS120
220…240V AC/DC 190-RCS230
380…415V AC 190-RCS400
440V AC 190-RCS440
Separate Mounting Base for Contactor Module — Provides line side terminals and mounting provisions. Allows panel design flexibility by offering the option of side or separate mounting of the contactor.
1 190-N2
Amplifier Module — For programmable controller interfacing.
1
—
Input: 24V DC, 15 mA 190-N3
48V DC, 10 mA 190-N4
125V DC, 10 mA 190-N5
Output: 1 N.O. and 1 N.C. contacts, 2A at 415V AC11 or 0.11A at 240V DC-DC11 —
Adaptor — Allows an integrated starter to be DIN Rail mounted. 2 190-N1
189
Bulletin 190Coordinated Starters
Accessories, Continued
Coding Pin/Surge Suppressor
External Operating Handle for Enclosure Cover Mounting ➊
➊ Not compatible with use of “Remote Operator Module”.➋ An operating shaft may be required depending on the working depth of the enclosure. Working depth is measured from the front of the enclosure to the panel on
which the Bulletin 190 starter is mounted (see drawing). This depth determines if an adapter is required and which adapter, or adapter and operating shaft, is to be used. Order an adapter and operating shaft as indicated in the table.
Description Pkg.Qty. Cat. No.
Coding Pin — Inhibits insertion of the incorrect trip unit into the manual interrupter. 5 190-N7
Surge Suppressor — Suitable for use with 120V contactor modules. 1 199-FSMA1
IP42 (Type 1) IP66 (Type 3, 3R, 4, 4X and 12)Color Cat. No.Price Color Cat. No.Black 190-HS1$ 20 Black 190-HS4
Red/Yellow 190-HS1E20 Red/Yellow 190-HS4E
Adapter and Operating ShaftWorking Depth mm (in.) Adapter Operating Shaft
Min. Max. Cat. No. Cat. No.When Cat. No. 190-N1 Mounting Plate Is Used
161 (6-11/32) 175 (6-57/64) 190-SE1$ 5 ➋
176 (6-15/16) 303 (11-15/16) 190-SE211 194R-R1305 (12) 497 (19-9/16) 190-SE211 194R-R2
When Cat. No. 190-N1 Mounting Plate Is Not Used152 (6) 166 (6-17/32) 190-SE15 ➋
167 (6-9/16) 294 (11-9/16) 190-SE211 194R-R1295 (11-5/8) 488 (19-7/32) 190-SE211 194R-R2
Operating Handle
AdapterCat. No. 190-SE-1
or+
Adapter Cat. No. 190-SE2
Operating Shaft+
Working Depth
Bulletin 190Coordinated Starters
190
Specifications
Short-Circuit Switching CapacityThe following information is not for use in Canadian and U.S. Applications.
NR = Not Required
NR = Not Required
006 010 016 024 040
Adjustable Thermal Current (A) 0.4…0.6 0.6…1.0 1.0…1.6 1.6…2.4 2.4…4.0Adjustable Magnetic Trip Range (A) 5…8 8…14 14…22 20…35 35…55
Switching Capacity (kA)
190-MN + 190-P__switching capacity Icn P-1/P-2 (kA)
220/380/415V 50 Hz ∞ ∞ ∞ ∞ ∞440V 50 Hz ∞ ∞ ∞ ∞ ∞500V 50 Hz ∞ ∞ ∞ ∞ ∞660/690V 50 Hz ∞ ∞ ∞ ∞ 4.5/3
with 190-A 40 contactor or 190-CL1 current limiter switching capacity IcnP-1/P-2 (kA)
220/380/415V 50 Hz ∞ ∞ ∞ ∞ ∞440V 50 Hz ∞ ∞ ∞ ∞ ∞500V 50 Hz ∞ ∞ ∞ ∞ ∞660/690V 50 Hz ∞ ∞ ∞ ∞ 10/7.5
Backup Fuses (A)
190-MN + 190-P__ backup fuse aM or gL required when available current Icc exceeds Icn
220/380/415V 50 Hz NR NR NR NR NR440V 50 Hz NR NR NR NR NR500V 50 Hz NR NR NR NR NR660/690V 50 Hz NR NR NR NR 63
with 190-A 40 or 190-CL1 backup fuse aM or gLrequired when available current Icc exceeds Icn
220/380/415V 50 Hz NR NR NR NR NR440V 50 Hz NR NR NR NR NR500V 50 Hz NR NR NR NR NR660/690V 50 Hz NR NR NR NR 80
060 100 160 250 320 400
Adjustable Thermal Current (A) 4…6 6…10 10…16 16…27 24…32 32…42Adjustable Magnetic Trip Range (A) 50…80 80…140 130…220 200…350 275…425 350…500
Switching Capacity (kA)
190-MN + 190-P__switching capacity Icn P-1/P-2 (kA)
220/380/415V 50 Hz ∞ R/30 R/30 30/10 30/10 30/10440V 50 Hz ∞ 10/7 10/7 10/7 10/7 10/7500V 50 Hz ∞ 7/4.5 7/4.5 7/4.5 7/4.5 7/4.5660/690V 50 Hz 4.5/3 4.5/3 4.5/3 4.5/3 4.5/3 4.5/3
with 190-A 40 contactor or 190-CL1 current limiter switching capacity Icn P-1/P-2 (kA)
220/380/415V 50 Hz ∞ ∞ ∞ ∞ ∞ ∞440V 50 Hz ∞ ∞ ∞ ∞ ∞ ∞500V 50 Hz ∞ ∞ ∞ ∞ ∞ ∞660/690V 50 Hz 10/7.5 10/7.5 10/7.5 10/7.5 10/7.5 10/7.5
Backup Fuses (A)
190-MN + 190-P__ backup fuse aM or gL required when available current Icc exceeds Icn
220/380/415V 50 Hz NR NR NR 160 160 160440V 50 Hz NR 80 100 125 160 160500V 50 Hz NR 80 100 125 160 160660/690V 50 Hz 80 80 100 125 160 160
with 190-A 40 or 190-CL1 backup fuse aM or gLrequired when available current Icc exceeds Icn
220/380/415V 50 Hz NR NR NR NR NR NR440V 50 Hz NR NR NR NR NR NR500V 50 Hz NR NR NR NR NR NR660/690V 50 Hz 80 100 100 160 160 160
190-MN+190-P___Trip Unit
Manual Interrupter
190-MN+190-P___Trip Unit
Manual Interrupter
Cat. No.
191
Bulletin 190Coordinated Starters
Specifications, Continued
Short-Circuit Protection Requirements
North American Market Only
Single Motor Application
Group Motor Applications
➊ Horsepower ratings are shown as a reference only. Selection should be based on motor full load current:• For motors with service factor of 1.15 or greater, use motor nameplate full load current to select the trip unit with the proper thermal current
range. EXAMPLE: Motor FLC = 17 A, SF = 1.15. Select Trip Unit 190-P250 which has a thermal current range of 16…25 A.• For motors with service factor less than 1.15: Multiply motor nameplate full load current by 0.9 and use the resulting figure to select the trip
unit with the proper thermal current range. EXAMPLE: Motor FLC = 17 A, SF = 1.0. 17 A x 0.9 = 15.3 A. Select Trip Unit 190-P160 which has a thermal current range of 10…16 A.
Single Motor Application, Continued
Group Motor Applications, Continued
006 010 016 024 040
Adjustable Thermal Current A 0.4…0.6 0.6…1.0 1.0…1.6 1.6…2.4 2.4…4.0Adjustable Magnetic Trip Range A 5…8 8…14 14…22 20…35 35…55
230V/60 Hz Hp — — — 1/2 1Max. 3∅ horsepower ➊ 460V/60 Hz Hp — 1/2 3/4 1 2
575V/60 Hz Hp — 1/2 1 1-1/2 3
Max. backup protection for 190-MN manual interrupter + 190-P__ trip unit
Max. Fuse A Per U.S. NEC Table 430-152(usually 175% motor full load current for time delay fuse)
Max. Circuit Breaker Size A Per U.S. NEC Table 430-152(usually 250% motor full load current for inverse time circuit breaker)
Max. backup protection for 190-MN manual interrupter + 190-P__ trip unit + 190-A40* contactor module
Max. Fuse A Per U.S. NEC Table 430-152(usually 175% motor full load current for time delay fuse)
Max. Circuit Breaker Size A Per U.S. NEC Table 430-152(usually 250% motor full load current for inverse time circuit breaker)
Max. backup protection for 190-CPS40* combination starter plus 190-P__ trip unit
Max. Fuse A None requiredMax. Circuit Breaker A None required
Max. backup protection for 190-MN manual interrupter + 190-P__ trip unit
Max. Fuse A 500 500 500 500 500Max. Circuit Breaker Size A 500 500 500 500 500
Max. backup protection for 190-MN manual interrupter + 190-P__ trip unit + 190-A40* contactor module
Max. Fuse A 2000 2000 2000 2000 2000
Max. Circuit Breaker Size A 2000 2000 2000 2000 2000
060 100 160 250 320 400
Adjustable Thermal Current A 4.0…6.0 6…10 10…16 16…27 24…32 32…42Adjustable Magnetic Trip Range A 50…80 80…140 130…220 200…350 275…425 350…500
Max. 3∅ horsepower230V/60 Hz Hp 1-1/2 3 5 7-1/2 10 15460V/60 Hz Hp 3 5 10 20 20 30575V/60 Hz Hp 5 7-1/2 10 25 30 30
Max. backup protection for 190-MN manual interrupter + 190-P__ trip unit
Max. Fuse A Per U.S. NEC Table 430-152(usually 175% motor full load current for time delay fuse)
Max. Circuit Breaker Size A Per U.S. NEC Table 430-152(usually 250% motor full load current for inverse time circuit breaker)
Max. backup protection for 190-MN manual interrupter + 190-P__ trip unit + 190-A40* contactor module
Max. Fuse A Per U.S. NEC Table 430-152(usually 175% motor full load current for time delay fuse)
Max. Circuit Breaker Size A Per U.S. NEC Table 430-152(usually 250% motor full load current for inverse time circuit breaker)
Max. backup protection for 190-CPS40* combination starter plus 190-P__ trip unit
Max. Fuse A None required
Max. Circuit Breaker A None required
Max. backup protection for 190-MN manual interrupter + 190-P__ trip unit
Max. Fuse A 500 500 500 500 500 500Max. Circuit Breaker Size A 500 500 500 500 500 500
Max. backup protection for 190-MN manual interrupter + 190-P__ trip unit + 190-A40* contactor module
Max. Fuse A 2000 2000 2000 2000 2000 2000
Max. Circuit Breaker Size A 2000 2000 2000 2000 2000 2000
190-MN+190-P___Trip Unit
Manual Interrupter
Cat. No.
190-MN+190-P___Trip Unit
Manual Interrupter
Cat. No.
Bulletin 190Coordinated Starters
192
Specifications, Continued
EnvironmentalTemperature Storage
Open Enclosed Ambient temperature compensation (overload)
–25…+70° C–25…+60° C–25…+40° C–5…+60° C
Climatic Tests Damp heat to IEC 68 Pt. 2-30 Dry heat to IEC 68 part 202 85°CAltitude 3000 M
Electrical RatingsMain Contacts
Rated Insulation Voltage Ui 690VUninterrupted Current Iu 42AFrequency 50…60 HzHeat Loss Manual motor starter Integrated starter
or coordinated protected starter 14 W23 W
Electrical Life Manual interrupter Contactor module
(see curve page 193)
AC3 50000 ops at 20 kWAC3 1000000 ops at 20 kW
AC4 30000 ops at 15 kW Maximum Switching Frequency Manual Interrupter
Contactor Module(see curve page 193)
60 OPS/HR
Motor Voltage AC-3 DC-4
690V AC Max.230V DC Max.
Short Circuit Switching Capacity See page 193Contactor Module
Operating Range Pick upDrop out
85…110% nameplate voltage60…40% nameplate voltage
Power Consumption Pick up Seal
≤190 VA≤13 VA
Duty Factor 100%Operating Times ≤ 9…30 ms
≤ 4…12 ms closing delayopening delay
Making Capacity 400 A cos φ = 0.35 cos ϕ = 1Breaking Capacity 400 A cos φ = 0.35 230…690VAC 1 Duty Thermal current Ith = operating
current Ie open or enclosed 16-2/3…400 Hz
AC 3/AC 4 Duty Rated Operating Current Open or Enclosed
Voltage AC 3 Ie (A) AC 4 Ie (A)
230V AC/50 Hz 40 30415V AC/50 Hz 40 30440V AC/50 Hz 40 30500V AC/50 Hz 32 28690V AC/50 Hz 25 21
Trip UnitResidual Error Less than 5% at 40° C,Less than 10% at 60° CShort Circuit Trip Tolerance ± 20%Trip Unit for Motor Loads 11 adjustable overload trip ranges
Adjustable short circuit trip rangePhase loss sensitivity to IEC 292-1
0.4…40 A8.5…14 x Iu
Trip Unit for System Protection 5 adjustable overload trip rangesAdjustable short circuit range
6…40 A5…8.5 x Iu
193
Bulletin 190Coordinated Starters
Specifications, Continued
Electrical Ratings, Continued
Contactor Module Life Load Curves for Squirrel-Cage Motors
Contactor Module Switching Frequency Curve
Normal Switching Duty Extreme Switching Duty
Operating characteristics Starting:Stopping:
From restAfter attaining full running speed Operating characteristics Inching, plugging, reversing
Electrical characteristics Make:Break:
Up to 6x rated motor current1x rated motor current Electrical characteristics Make:
Break:6x rated motor current6x rated motor current
Utilization category 99.9% AC-3 + 0.1% AC-4 Utilization category 100% AC-4
380/415 AC3
kW330
200160
132110907555453730
2218.515
11
7.5
5.5
4
3
2.2
1.5
1.1
0.80.55
Normal switching duty
Rat
ed o
utp
ut
of
thre
e-p
has
e m
oto
rs 5
0...6
0 H
z
Component lifespan (millions of operations)0.01 0.02 0.04 0.06 0.1 0.2 0.4 0.6 1 2 3 4 5 6 8 10
380/415 AC–4
kW
375
300220
110907555
45
373022
18.51511
7.5
5.5
4
3
2.2
1.5
1.1
0.8
0.55 Extreme switching duty, squirrel-cage motors
Rat
ed o
utp
ut
of
thre
e-p
has
e m
oto
rs 5
0...6
0 H
z
0.01 0.02 0.04 0.06 0.1 0.2 0.4 0.6 1 2 3 4 5 6 8 10
0.250.37
Component lifespan (millions of operations)0.03 0.3
AC3
AC4
9000700060005000
4000
3000
2000
1500
1000800
600500400
300
200
150
1000 10 20 30 40 50 60 70 80 90 100%
Ops
/h
% Rated Load
Bulletin 190Coordinated Starters
194
Specifications, Continued
Electrical Ratings, Continued
Manual Motor Starter and Protector — Let-Through curves
Integrated Starter — Manual Starter with Current Limiter Module — Let-Through curves
Trip Curves
[kA]100
80
60
40
30
20
15
108
6
4
3
2
1.5
11 1.5 2 3 4 6 8 10 15 20 30 40 60 80100
16 A10 A
6 A
I D
Icc [kA]
32/40 A25 A
Ue = 415V
1 1.5 2 3 4 6 8 10 15 20 30 40 60 80 100
32/40 A25 A
16 A
10 A
6 A
106
86
43
2
1.5
105
86
43
21.5
104
6
4
8
2dti[A s]2
Icc kAms
Ue = 415V
[kA]100
80
60
40
30
20
15
108
6
4
3
2
1.5
11 1.5 2 3 4 6 8 10 15 20 30 40 60 80 100
16 A10 A
6 A
32/40 A25A
I D
Icc [kA]
Ue = 415V
1 1.5 2 3 4 6 8 10 15 20 30 40 60 80 100
32/40 A25 A16 A10 A
6 A
106
86
43
2
1.5
105
86
43
21.5
104
6
4
8
2dti[A s]2
Icc kAms
Ue = 415V
2h2010
5
21
40
2010
5
2
1
200
50
20
5
21.5 2 3 4 6 8 10 15 20 30
Min
utes
Sec
onds
Mill
isec
onds
x rated current
System Protection — Cat. No. 190-P___LMotor Protection — Cat. No. 190-P___
2010
5
21
402010
5
2
1
200
50
20
5
21.5 2 3 4 6 8 10 15 20 30
2h
Min
utes
Sec
onds
Mill
isec
onds
x rated current
195
Bulletin 190Coordinated Starters
Specifications, Continued
Mechanical RatingsMechanical Ratings
Impact Resistance 20 msManual motor starter 30 G
Integrated starter 8 GCoordinated protected starter 8 G
Mechanical Life Manual interrupterContactor module
100000 ops5000000 ops
Installed PositionManual motor starterIntegrated starterCoordinated protected starter
No restrictionsWithin 30° of vertical planeWithin 30° of vertical plane
Degree of Protection IP20 VDE 0106 Part 100
Terminal Capacities
Power terminals1 conductor
Solid or stranded 1.0…16 mm2 AWG 14…6Stranded with ferrule 1.5…10 mm2 AWG 14…6
Power terminals2 conductor
Solid or stranded 1.0…6 mm2 AWG 14…6Stranded with ferrule 1.5…6 mm2 AWG 14…6
Control/accessory terminals1 or 2 conductor Solid or stranded with ferrule 0.5…2.5 mm2 AWG 18…14
Approximate Shipping Weights Cat No. kg (lb)Manual Interrupter 190-MN 0.450 (1.00)Trip Unit 190-P___ 0.218 (0.48)Contactor Module 190-A40___ 0.850 (1.87)
Auxiliary Contacts
190-A11190-A22
190-AC11/11190-A11/11190-A11C190-A22C
0.087 (0.19)0.102 (0.22)0.094 (0.21)0.180 (0.40)0.180 (0.40)0.180 (0.40)
Trip Indicating Contacts 190-T11/11 0.042 (0.09)Amplifier Module 190-N3, N4, N5 0.085 (0.19)Remote Operator 190-RC___ 0.5 (1.10)Undervoltage Trip 190-UV___ 0.188 (0.41)Shunt Trip 190-RT___ 0.188 (0.41)Current Limiter Module 190-CL1 0.522 (1.15)Separate Mounting Base 190-N2 0.147 (0.32)Adaptor Plate 190-N1 0.145 (0.32)
Bulletin 190Coordinated Starters
196
Specifications, Continued
Auxiliary Contacts
Rated Insulation Voltage500V AC 600V DC
Separation from main contacts to VDE 0106 Part 100 up to 690V AC
Rated Operating Current
AC II
DC II
220/240V 50 Hz Ie = 6 A380/415V 50 Hz Ie = 3 A440/500V 50 Hz Ie = 1.5 A24V Ie = 1 A 60V Ie = 0.8 A 110V Ie = 0.7 A220V Ie = 0.3 A L/R < 200 ms
Electrical Life
190-A11190-T11/11
190-A22C, A11C, A11/11, AC11/11
A22 50 000 ops5000 ops
1 000 000 ops
Mechanical Life190-A11, A22 100000 ops190-T11/11 10000 ops190-A11C, A22C, A11/11, AC11/11 5000000 ops
Remote OperatorRated Insulation Voltage 500V AC 600V DCOperating Range AC or DC 85%…110% of nameplate voltage
Power ConsumptionACDCL/R
700 VA for 15 ms700 W for 15 ms
≤ 200 msMake Time ≤ 50 msBreak Time ≤ 50 msReset Time To Off ≤ 20 msSwitching Frequency 60 ops/hrMechanical Life 50 000 ops
Undervoltage TripRated Insulation Voltage 690V ACDrop Out 70…35% of nameplate voltage
Power Consumption Pick upSeal
5 VA AC3 VA AC
3 W DC3 W DC
Drop Out Delay 200 msShunt Trip
Operating Range AC or DC 70…110% of nameplate voltage
Power Consumption Pick upSeal
5 VA AC3 VA AC
3 W DC3 W DC
Amplifier ModuleRated Insulation Voltage 415V ACMechanical Life 10 000 000 opsOperating Range 85…110% of nameplate voltageDuty Factor 100%Uninterrupted Current 6AInput 24V 15 mA DC 48V 10 mA DC 125V 10 mA DC
Output Max. 415V ACMax. 240V DC
AC-11DC-11
AC11 2 ADC11 0.11 A
197
Bulletin 190Coordinated Starters
Approximate Dimensions
Manual Motor Starter/ProtectorDimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
45 (1-49/64)
31.5(1-16/64)
18(23/32)
68(2-11/16)
77(3-1/32)
44(1-47/64)
105(4-1/8)
18(23/32)
38
1 M1 B
2 M2 B
>
+ +
>
83105
19
38
62.5
71.5
M 4
18 62.5 36 18
105
8
68
15
45
3
4.5 39.5
109
118
(4-1/8)(3-9/32)
(3/4)
(1-1/2)
(2-7/16)
(2-25/32)
(11/16) (2-7/16) (1-13/32) (11/16)
(1/8)
(3/16) (1-9/16)
(4-21/32)
(4-19/64)
(1-49/64)
(19/32)
(2-11/16)
(4-1/8)
(5/16)
18(23/32)
(1-1/2)
Cat. No.190_A
Cat. No. 190-MNwith 190-P
Cat. No.190-RC
Cat. No.190-UV190-RT
Cat. No. 190-A22 Cat. No. 190-A11
Auxiliary Contacts Trip Indicating Contacts
Cat. No. 190-T11/11
Bulletin 190Coordinated Starters
198
Approximate Dimensions, Continued
Integrated Starter Coordinated Protected StarterDimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
105
44
109
113
(4-1/8)
(1-47/64)
(4-19/64)
(4-29/64)
18(23/32)
74
HAND
AUTO
A20
36
105
45
109118
(4-1/8)
(1-49/64)
(4-19/64)(4-21/32)
(1-27/64)
8.5
4.5 39.5
118
109
15
204
190
125
6.1 (15/64)
10 (25/64)
15 (19/32)
18.5 (23/32)
46.4
111.4
120.4135.9
145.9
150.9
8
(21/64)
(11/64) (1-35/64)
(4-21/32)
(4-19/64)
(5/16)
(8-1/32)
(7-31/64)
(4-59/64)
(1-53/64)
(4-25/64)
(4-47/64)(5-23/64)
(5-47/64)
(5-29/32)
(19/32)
19(3/4)
71.5(2-25/32)
11(7/16)
204(8-1/32)
38
62.5(1-1/2)
(2-7/16)
>
+
168
M4
C2D2
C1D1
Cat. No.
T11/11 1
Cat. No. 190-N1
190
A40 B20Control
NO
R E
72
3433
Cat. No. 190-RC_
Cat. No. 190-UVCat. No. 190-RT
Cat. No. 190-A_CCat. No. 190-A11/11
Remote OperatorCat. No. 190-RCS, RCE
Undervoltage TripCat. No. 190-UV
Shunt TripCat. No. 190-RT
199
Bulletin 190Coordinated Starters
Approximate Dimensions, Continued
Contactor ModuleDimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
19
103.5
85
44
109
38
19
100
21.8
11 (7/16)
3 65.5 77
125
53
37 (1-1/2)
(3/4)
38
62.5(1-1/2)
(2-15/32)
(4-5/64)
(3-23/64)
(1-47/64)
(4-19/64)
(1/8)
(55/64)
(2-37/64)
(3-15/16)
(4-29/32)
(2-7/64)
(3-1/32)
(1-1/2)
(3/4)
110.5
98
75
6
(4-23/64)
(3-55/64)
(2-61/64)
(15/64)
22.5(57/64)
153 (6-1/64)
77(3-1/32)
44(1-47/64)18
(23/32)18
(23/32)18
(23/32)
CS-TE
1 M1 B
1 M1 B
2 M2 B
3143
4432
1 M1 B
2M4 x 12
58
(7-31/64)190
(2-9/32)
Auxiliary Contacts
Cat. No.190-A22C
Cat. No.190-A11/11
Cat. No.190-A11C Amplifier Module
Cat. No. 190-N3, N4, N5
Separate Mounting BaseCat. No. 190-N2
Contactor ModuleCat. No. 190-A4O__
Current Limiter ModuleCat No. 190-CL1
Bulletin 141AMCS Mounting System
200
Overview
Bulletin 141A MCS Mounting System• Modularity makes Planning Easy• Simple Prefabrication of Starters• Easy Starter Exchange• Flexible in-line Assembly
DOL StartersReversing StartersStar-Delta StartersSoft StartersInverterComplete Range of Accessories
• 3 Mounting MethodsOn BusbarsOn Standard DIN RailsScrew Fixing
Table of ContentsProduct Selection
ISO Busbar Module .......201Standard Busbar Module ...........................202Mounting Module ...........204
Accessories....................... 208Specifications
Panel Mounting System .210
Conformity to StandardsUL 508CSA 22.2 No. 14EN 60947
ApprovalsCEUL Recognized
ISO Busbar Modules Standard Busbar Modules with Wires
Standard Busbar Modules with Terminals
Mounting Modules
201
Bulletin 141AMCS Mounting System
Product Selection
ISO Busbar Modules • 2-part construction
- Device adapter plate (carrying the starter) snaps onto the base of the module- Base of module remains on busbar when exchanging starters, providing isolation from live parts
• Test position with load circuit isolated• Designed for use with control plug (order separately)• Modules with current ratings supply the load current by means of wire connections matched to MCS motor protection circuit breakers• Modules can form bigger platforms using the connection clips (see accessories)• For plugging on 5 mm or 10 mm thick busbars
DescriptionRated Thermal
Current Ith Width[mm] Rails Pkg.
Qty Cat. No.
ISOTM Busbar Modules • 200 mm high• Top hat rails:
R = MCS-specific top hat rail
25 A
45
2R
1 141A-SS45RR25
54 1 141A-SS54RR25
45 A
54 1 141A-SS54RR45
63 1 141A-SS63RR45
Without electricalconnections
45
1R
1 141A-SS45R
54 1 141A-SS54R
ISO Busbar Modules • 260 mm high• Top hat rails:
R = MCS-specific top hat railS = Standard top hat rail
25 A
45
1R + 1S 1
141A-SM45RS25
54 141A-SM54RS25
45 A
54 141A-SM54RS45
63 141A-SM63RS45
Without electricalconnections
45
1S 1
141A-SM45S
54 141A-SM54S
63 141A-SM63S
Bulletin 141AMCS Mounting System
202
Product Selection, Continued
Standard Busbar Modules • Modules plug directly onto the busbar• Suitable for use with control plug• Modules with current ratings supply the load current by means of wire
connections matched to MCS motor protection circuit breakers• Modules can form bigger platforms using the connection clips (see accessories)• For plugging on 5 mm or 10 mm thick busbars
DescriptionRated Thermal
Current Ith Width[mm]
Top HatRails
Pkg. Qty. Cat. No.
Standard Busbar Module• 200 mm high• Top hat rails:
R = MCS-specific top hat railM = Metal top hat railS = Standard top hat rail
2545
2R
1 141A-GS45RR25
54 1 141A-GS54RR25
4554 1 141A-GS54RR45
63 1 141A-GS63RR45
90
90
1M 1
141A-GS90M125
162 141A-GS180M125
243 141A-GS270M125
Without electricalconnections
451R
1 141A-GS45R
54 1 141A-GS54R
721S 1
141A-GS72S
81 141A-GS81S
Standard Busbar Module• 260 mm high• Top hat rails:
R = MCS-specific top hat rail
25
45
1R + 1S 1
141A-GM45RS25
54 141A-GM54RS25
45
54 141A-GM54RS45
63 141A-GM63RS45
Without electricalconnections
45
1S 1
141A-GM45S
54 141A-GM54S
63 141A-GM63S
Standard Busbar Module with terminals• 200 mm high• With terminals for mounting various components• Top hat rails:
R = MCS-specific top hat rail
25 45
1S
1 141A-FS45S25
63
54 1 141A-FS54S63
63
1
141A-FS63S63
72 141A-FS72S63
81 141A-FS81S63
Standard Busbar Module with terminals• 260 mm high• With terminals for mounting various components• Top hat rails:
R = MCS-specific top hat rail
25 45
2S 1
141A-FM45SS25
63
54 141A-FM54SS63
63 141A-FM63SS63
72 141A-FM72SS63
81 141A-FM81SS63
203
Bulletin 141AMCS Mounting SystemProduct Selection, Continued
Standard Busbar Modules >100 A • Modules plug directly onto the busbar• For plugging on 5 mm or 10 mm thick busbars
Description For Use WithRated Thermal
Current Ith Width[mm]
Pkg. Qty. Cat. No.
Standard Busbar Module — for Mounting Bulletin 140U Circuit Breakers• Designed specifically for use with
Bulletin 140U Molded Case Circuit Breakers
140U H-Frame(Top feed)
125 A 90
1
141A-CUH125T
140U H-Frame(Bottom feed) 141A-CUH125B
140U J-Frame(Top or Bottom Feed) 250 A 105 141A-CUJ250
140U K-Frame(Top or Bottom Feed) 400 A 140 141A-CUK400
Standard Busbar Module — Universal Mounting• 222 mm high• With box terminals on top• Wire size 70 mm2
200 A 108
1
141A-FS108V200T
Standard Busbar Module• 320 mm high• With box terminals on top• Wire size 120 mm2
250 A 110 141A-FL110V250T
Standard Busbar Module — Universal Adapters• 222 mm high• With box terminals on bottom• Wire size 70 mm2
200 A 108
1
141A-FS108V200B
Standard Busbar Module — Universal Adapters• 320 mm high• With box terminals on bottom• Wire size 120 mm2
250 A 110 141A-FL110V250B
Bulletin 141AMCS Mounting System
204
Product Selection
Mounting Modules • Mounts to (2) 35 mm DIN Rails, (1) 70 mm DIN Rail, or screw mounts• Suitable for use with control plug
Description Width[mm]
Top HatRails
Pkg. Qty.
Cat. No.(Standard Module)
Cat. No.(Module with PE Terminal)
Mounting Module • 228 mm high• Top hat rails:
R = MCS-specific top hat rail• For 2-component starters
45
2R
1 141A-WS45RR 141A-WS45RRP
54 1 141A-WS54RR 141A-WS54RRP
Mounting Module • 283 mm high• Top hat rails:
R = MCS-specific top hat rail• For 3-component starters using 193-EA or -EB
overload relays
45
2R
1 141A-WM45RR 141A-WM45RRP
54 1 141A-WM54RR 141A-WM54RRP
Mounting Module • 333 mm high• Top hat rails:
R = MCS-specific top hat rail• For 3-component starters using 193-EC overload
relays
45
2R 1
141A-WL45RR 141A-WL45RRP
54 141A-WL54RR 141A-WL54RRP
205
Bulletin 141AMCS Mounting SystemProduct Selection, Continued
Busbar Components
Description Ampere Rating per IEC Height (mm) x Width (mm) Cat. No.
Busbar• 800 mm in length• Tinned copper busbar
100 12 x 5 141A-B125A
175 20 x 5 141A-B205A
230 30 x 5 141A-B305A
285 20 x 10 141A-B2010A
400 30 x 10 141A-B3010A
• 1600 mm in length• Tinned copper busbar
100 12 x 5 141A-B125B
175 20 x 5 141A-B205B
230 30 x 5 141A-B305B
285 20 x 10 141A-B2010B
400 30 x 10 141A-B3010B
• 2400 mm in length• Tinned copper busbar
100 12 x 5 141A-B125N
175 20 x 5 141A-B205N
230 30 x 5 141A-B305N
285 20 x 10 141A-B2010N
400 30 x 10 141A-B3010N
Description Busbar[mm]
Pkg. Qty. Cat. No.
Busbar Support• 60 mm pole center spacing• The busbar support can easily be adjusted to the busbar size
via the integral slide rail.
3-polewith inside mounting holes
12…30 x 5or
12…30 x 10
10 141A-TR3
4-polewith inside mounting holes 10 141A-TR4
1-pole 10 141A-TR1
Busbar End Cover• Prevents contact with the busbar ends and prevents busbars
from sliding.• The end cover can easily be clipped on the busbar support.
3-pole 10 141A-TR3E
4-pole 10 141A-TR4E
Feeder Busbar Support• For 3-pole• 60 mm pole centre spacing
16 mm2 (#6 AWG)12…30 x 5
or12…30 x 10
10 141A-TR3F16
Bulletin 141AMCS Mounting System
206
Product Selection, Continued
Busbar Components, Continued
Description Busbar[mm]
Pkg. Qty. Cat. No.
Supply Module• For 3-pole
70 mm2 (AWG 00)54 mm wide
12…30 x 5or
12…30 x 10
1
141A-VN370
Supply Module• For 3-pole
120 mm2 (AWG 250 MCM)81 mm wide 141A-VN3120
Supply Module• For 3-pole
185 mm2 (AWG 350 MCM)135 mm wide 141A-VN3185
Supply Module• For 3-pole• For round conductors
300 mm2 (AWG 600 MCM)135 mm wide 141A-VN3300R
Supply Module• For 3-pole• For flat conductors
300 mm2
135 mm wide 141A-VN3300F
Single Terminals• Single terminals for supplying busbars
2.5…16 mm2
AWG 14…612…30 x 5 25 141A-VS11612…30 x 10 25 141A-VS216
4…35 mm2
AWG 12…212…30 x 5 25 141A-VS13512…30 x 10 25 141A-VS235
16…70 mm2
AWG 6…0012…30 x 5 25 141A-VS17012…30 x 10 25 141A-VS270
Terminal Cover• Finger protection when busbars supplied with contact terminals.• Fixable on busbar with plastic lock.• (Height: 180 mm)
12…30 x 5or
12…30 x 101 141A-BK1
Busbar Connector
Distance of systems5…10 mm
12…20 x 512…20 x 10 12 141A-VC3A
13…20 mm
20…30 x 520…30 x 10
6 141A-VC3B
50…60 mm 3 141A-VC3C
100…110 mm 3 141A-VC3D
Busbar Shroud (Cat. No. 141A-BCF1) and Busbar Shroud Holder (Cat. No. 141A-BCF1H)• 200 x 1100 mm• Covers all 3 busbars
12…30 x 5 2 141A-BCF1
12…30 x 10 10 141A-BCF1H
Busbar Cover• Hollow profile of grey PVC for contact protection.• Length: 1 m, can be extended.
12…30 x 510
141A-BS5
12…30 x 10 141A-BS10
207
Bulletin 141AMCS Mounting SystemProduct Selection, Continued
Circuit Breaker Modules
Description Circuit Breaker Module Cat. No.Consists of
Mounting Module Cat. No. Circuit Breaker Cat. No.
H-Frame — Top Feed
65 kA, 15 A 3P T/M Circuit Breaker 140U-H6C3-C15-BT 141A-CUH125T 140U-H6C3-C15
65 kA, 20 A 3P T/M Circuit Breaker 140U-H6C3-C20-BT 141A-CUH125T 140U-H6C3-C20
65 kA, 65 A 3P T/M Circuit Breaker 140U-H6C3-C25-BT 141A-CUH125T 140U-H6C3-C25
65 kA, 30 A 3P T/M Circuit Breaker 140U-H6C3-C30-BT 141A-CUH125T 140U-H6C3-C30
65 kA, 35 A 3P T/M Circuit Breaker 140U-H6C3-C35-BT 141A-CUH125T 140U-H6C3-C35
65 kA, 40 A 3P T/M Circuit Breaker 140U-H6C3-C40-BT 141A-CUH125T 140U-H6C3-C40
65 kA, 45 A 3P T/M Circuit Breaker 140U-H6C3-C45-BT 141A-CUH125T 140U-H6C3-C45
65 kA, 50 A 3P T/M Circuit Breaker 140U-H6C3-C50-BT 141A-CUH125T 140U-H6C3-C50
65 kA, 60 A 3P T/M Circuit Breaker 140U-H6C3-C60-BT 141A-CUH125T 140U-H6C3-C60
65 kA, 70 A 3P T/M Circuit Breaker 140U-H6C3-C70-BT 141A-CUH125T 140U-H6C3-C70
65 kA, 80 A 3P T/M Circuit Breaker 140U-H6C3-C80-BT 141A-CUH125T 140U-H6C3-C80
65 kA, 90 A 3P T/M Circuit Breaker 140U-H6C3-C90-BT 141A-CUH125T 140U-H6C3-C90
65 kA, 100 A 3P T/M Circuit Breaker 140U-H6C3-D10-BT 141A-CUH125T 140U-H6C3-D10
65 kA, 110 A 3P T/M Circuit Breaker 140U-H6C3-D11-BT 141A-CUH125T 140U-H6C3-D11
65 kA, 125 A 3P T/M Circuit Breaker 140U-H6C3-D12-BT 141A-CUH125T 140U-H6C3-D12
H-Frame — Bottom Feed
65 kA, 15 A 3P T/M Circuit Breaker 140U-H6C3-C15-BB 141A-CUH125B 140U-H6C3-C15
65 kA, 20 A 3P T/M Circuit Breaker 140U-H6C3-C20-BB 141A-CUH125B 140U-H6C3-C20
65 kA, 65 A 3P T/M Circuit Breaker 140U-H6C3-C25-BB 141A-CUH125B 140U-H6C3-C25
65 kA, 30 A 3P T/M Circuit Breaker 140U-H6C3-C30-BB 141A-CUH125B 140U-H6C3-C30
65 kA, 35 A 3P T/M Circuit Breaker 140U-H6C3-C35-BB 141A-CUH125B 140U-H6C3-C35
65 kA, 40 A 3P T/M Circuit Breaker 140U-H6C3-C40-BB 141A-CUH125B 140U-H6C3-C40
65 kA, 45 A 3P T/M Circuit Breaker 140U-H6C3-C45-BB 141A-CUH125B 140U-H6C3-C45
65 kA, 50 A 3P T/M Circuit Breaker 140U-H6C3-C50-BB 141A-CUH125B 140U-H6C3-C50
65 kA, 60 A 3P T/M Circuit Breaker 140U-H6C3-C60-BB 141A-CUH125B 140U-H6C3-C60
65 kA, 70 A 3P T/M Circuit Breaker 140U-H6C3-C70-BB 141A-CUH125B 140U-H6C3-C70
65 kA, 80 A 3P T/M Circuit Breaker 140U-H6C3-C80-BB 141A-CUH125B 140U-H6C3-C80
65 kA, 90 A 3P T/M Circuit Breaker 140U-H6C3-C90-BB 141A-CUH125B 140U-H6C3-C90
65 kA, 100 A 3P T/M Circuit Breaker 140U-H6C3-D10-BB 141A-CUH125B 140U-H6C3-D10
65 kA, 110 A 3P T/M Circuit Breaker 140U-H6C3-D11-BB 141A-CUH125B 140U-H6C3-D11
65 kA, 125 A 3P T/M Circuit Breaker 140U-H6C3-D12-BB 141A-CUH125B 140U-H6C3-D12
J-Frame — Top or Bottom Feed
65 kA, 90 A 3P T/M Circuit Breaker 140U-J6D3-C90-BB 141A-CUJ250 140U-J6D3-C90
65 kA, 100 A 3P T/M Circuit Breaker 140U-J6D3-D10-BB 141A-CUJ250 140U-J6D3-D10
65 kA, 125 A 3P T/M Circuit Breaker 140U-J6D3-D12-BB 141A-CUJ250 140U-J6D3-D12
65 kA, 150 A 3P T/M Circuit Breaker 140U-J6D3-D15-BB 141A-CUJ250 140U-J6D3-D15
65 kA, 175 A 3P T/M Circuit Breaker 140U-J6D3-D17-BB 141A-CUJ250 140U-J6D3-D17
65 kA, 200 A 3P T/M Circuit Breaker 140U-J6D3-D20-BB 141A-CUJ250 140U-J6D3-D20
65 kA, 225 A 3P T/M Circuit Breaker 140U-J6D3-D22-BB 141A-CUJ250 140U-J6D3-D22
65 kA, 250 A 3P T/M Circuit Breaker 140U-J6D3-D25-BB 141A-CUJ250 140U-J6D3-D25
K-Frame — Top or Bottom Feed
65 kA, 100 A 3P T/M Circuit Breaker 140U-K6D3-D10-BB 141A-CUK400 140U-K6D3-D10
65 kA, 125 A 3P T/M Circuit Breaker 140U-K6D3-D12-BB 141A-CUK400 140U-K6D3-D12
65 kA, 150 A 3P T/M Circuit Breaker 140U-K6D3-D15-BB 141A-CUK400 140U-K6D3-D15
65 kA, 175 A 3P T/M Circuit Breaker 140U-K6D3-D17-BB 141A-CUK400 140U-K6D3-D17
65 kA, 200 A 3P T/M Circuit Breaker 140U-K6D3-D20-BB 141A-CUK400 140U-K6D3-D20
65 kA, 225 A 3P T/M Circuit Breaker 140U-K6D3-D22-BB 141A-CUK400 140U-K6D3-D22
65 kA, 250 A 3P T/M Circuit Breaker 140U-K6D3-D25-BB 141A-CUK400 140U-K6D3-D25
65 kA, 300 A 3P T/M Circuit Breaker 140U-K6D3-D30-BB 141A-CUK400 140U-K6D3-D30
65 kA, 350 A 3P T/M Circuit Breaker 140U-K6D3-D35-BB 141A-CUK400 140U-K6D3-D35
65 kA, 400 A 3P T/M Circuit Breaker 140U-K6D3-D40-BB 141A-CUK400 140U-K6D3-D40
Bulletin 141AMCS Mounting System
208
Product Selection, Continued/Accessories
Accessories
Description Size[mm]
Pkg. Qty. Cat. No.
Hat (DIN) Rails• Slides onto mounting modules and is then fixed
with screws• Has notches for MCS components (prevents
movement of components when used with vertical busbar)
MCS top hat rail (plastic)
45
10
141A-AHR45
54 141A-AHR54
63 141A-AHR63
72 141A-AHR72
Hat (DIN) Rails• Slides onto mounting modules and is then fixed
with screwsStandard top hat rail (plastic)
45
10
141A-AHS45
54 141A-AHS54
63 141A-AHS63
72 141A-AHS72
81 141A-AHS81
Hat (DIN) Rails• Screws directly onto mounting modules Top hat rail (metal)
90
10
141A-AHM90
171 141A-AHM171
252 141A-AHM252
Carrier for Top Hat Rail• Carrier for metal rail inclusive screws 45 10 141A-AHH45
Control Plug• Pull-apart terminal block allows fast and simple
disconnection of control wiring.
8-pole control plug 1 141A-APC8
10-pole control plug 1 141A-APC10
12-pole control plug 1 141A-APC12
Spacer module• For 9 mm spacing of mounting modules.
Connection clips (141A-AK) are included for attaching the spacer module to the mounting modules.
For ISO™ busbar modules 200
10
141A-AS9S
For standard busbar modules 200 141A-AS9B
For mounting modules 228 141A-AS9W
Connection Clip• For joining base of mounting modules 50 141A-AK
Micro Switch• Contact
• Only for ISO Modules. Automatically drops out the contactor when the device adapter plate (carrying the starter) is unplugged from the base of the ISO busbar module.
10 141A-AS
209
Bulletin 141AMCS Mounting System
Specifications
Module Data
➊ The admissible load of a complete system depends on the system topography and the application parameters. Factors of influence are ambient temperature, air circulation, busbar load, distribution of busbar load, mix of modules and switchgear components.
Supply Modules
Single Terminals
Busbar System
IsoTM ModulesStandard Modules
with Wire ConnectionsStandard Modules with Box Terminals
141A-S 141A-G 141A-F
Rated current at 60°C Ith ➊ [A] 25 45 25 45 125 25 63 200 250
stranded [mm2][AWG]
610
108
610
108 — 4
12166
6…7010…00
35…1202…4/0
solid [mm2][AWG]
610
108
610
108 — 4
12166
6…7010…00
35…1202…4/0
Laminated copper [mm] — — — — 431/0 — — — —
Insulation rating of conductors [°C] 105 105 — — — —
Supply Modules
141A-TR3F16 141A-V…70 141A-V…120 141A-V…185 141A-V…300R 141A-V…300F
stranded [mm2][AWG]
1.5…1616…6
6…7010…2/0
35…1202…4/0
95…185No. 3/0…MCM 350
150…300MCM 300…600 —
solid [mm2][AWG]
1.5…1616…6
6…7010…2/0
35…1202…4/0
95…185No. 3/0…MCM 350
150…300MCM 300…600 —
Laminated copper [mm] — — — — — 3 x 20 x 1…10 x 32 x 1
Single terminals
141A-VS116, 141A-VS216 141A-VS135, 141A-VS235 141A-VS170, 141A-VS270
Rated current at 60°C Ith [A] 180 270 400
stranded [mm2][AWG]
2.5…1614…6
4…3512…2
16…706…00
solid [mm2][AWG]
2.5…1614…6
4…3512…2
16…706…00
Laminated copper 1. Conductor [mm]
2. Conductor [mm]——
5 x 9 x 0.8—
5 x 9 x 0.85 x 9 x 0.8
Clamping area Width x Height [mm] 7.5 x 7.5 10.5 x 11 14 x 14
Tightening torque [Nm] / [lb-in] 4 / 35 6 / 53 10 / 120
Short circuit withstand
According to IEC 60439 no proof of the short circuit withstand strength is required for systems with peak short circuit levels less than 17 kA.The 140M and 140-CMN MCS circuit breakers limit the peak short circuit currents well below this level, so that the busbar support spacing does not need factor in the prospective short circuit current when using MCS starters, but may be chosen based on mechanical considerations. The diagram for busbar support spacing gives recommendations accordingly.
Support Spacing for 60 mm Busbar System
20
30
40
50
60
70
80
200 300 400 500 600 700 800 900Busbar Support Spacing [mm]
Sho
rt-c
ircui
t Cur
rent
Ipk
[kA
]
30 x
10
20 x
10
30 x
5
25 x
5
20 x
5
15 x
5
12 x
5
Bulletin 141AMCS Mounting System
210
Specifications
Busbar System, Continued
Busbars (required quality)
General Data
Main Circuits
Control Circuits
Current carrying capacity of the busbars
BarDimensions
Recommended max. busbarload at 50 / 60 Hz
The current carrying capacities of the busbars highly depend on the application (air circulation, utilization with adapters, current distribution along the rails etc.). It is not only limited by the admissible temperatures of the plastic parts, which are in contact with the busbars, but by the admissible operating temperatures of the components mounted on top of the modules.In mounting system applications the busbars act as a heatsink for the heat produced inside the starter components. The heat is flowing from the component terminals (e.g. motor protection circuit breaker) via the short wire links to the busbars. For this reason it is good practice to run busbars, which are connected to component terminals, at 65°C maximum. The recommended ampacities for copper busbar as of the table are based on this fact and taken from amendment 1 of IEC 60890, which is referred to by IEC 60439-1 for Partially Type Tested Assemblies.
tamb = 35°C tamb = 55°C
[mm] [A] [A]5 x 12 145 1005 x 15 175 1305 x 20 220 175
10 x 12 230 1855 x 25 250 2055 x 30 290 235
10 x 20 350 28510 x 30 480 400
Material E-CU blank or tinnedBusbar widths 5 or 10 mm thick [mm] 12, 15, 20, 25, 30Tolerance of thickness [mm] +0.1 / -0.3Corner radius [mm] 0.5Tolerance of center spacing [mm] 60 +0.5 / -0.5Standard DIN 46433
Rated insulation voltage UiAcc. to IEC, EN [V]Acc. to UL, NEMA, CSA, EEMAC [V]
690600
Protection class- Modules and busbars IP00
Rated impulse withstand voltage Uimp [kV] 8 -Modules and busbars mounted on plate, connected conductors and usage of busbar covers IP20
Rated frequency [Hz] 50…60 -Iso-Modules with device adapter plate removed, from front IP20 B (finger proof)
Pollution degree 3 Standards and Norms IEC/EN 60439-1Ambient temperatureOperation [°C]Transport and storage [°C]
-25…+60-50…+80
Conformity and Approvals CE, UL recognized, CSA
Control plugs For details see Wago catalog Micro switch
Rated insulation voltage UiAcc. to IEC, EN [V]Acc. to UL, NEMA, CSA, EEMAC [V]
250300
Rated insulation voltage UiAcc. to IEC, EN [V]Acc. to UL, NEMA, CSA, EEMAC [V]
250300
Rated impulse withstand voltage Uimp [kV] 4 Rated current
Suitable for switching 100-C contactors
AC-coil-voltage ≤ 250 VDC-coil-voltage ≤ 120 V
Rated current at 40°C ambient temperature Ith [A] 12 Micro switch
211
Bulletin 141AMCS Mounting System
Specifications
Weight [g] MCS IsoTM
Busbar Module[g] MCS Standard
Busbar Module [g] MCS StandardBusbar Module >100 A [g] Busbar
Components [g] Accessories [g]
141A-SS45RR25 381 141A-GS45RR25 302 141A-FS108V200T 1000 141A-TR3 203 141A-AHR45 15141A-SS54RR25 396 141A-GS54RR25 347 141A-FL110V250T 1200 141A-TR4 256 141A-AHR54 16141A-SS54RR45 472 141A-GS54RR45 358 141A-FS108V200B 1000 141A-TR1 59 141A-AHR63 16141A-SS63RR45 480 141A-GS63RR45 379 141A-FL110V250B 1200 141A-TR3E 21 141A-AHS45 15141A-SS45R 279 141A-GS90M125 781 141A-TR4E 28 141A-AHS54 16141A-SS54R 305 141A-GS171M125 1021 MCS
Mounting Module [g]141A-TR3F16 285 141A-AHS63 16
141A-SM45RS25 402 141A-GS252M125 1271 141A-VN370 360 141A-AHS72 17141A-SM54RS25 418 141A-GS45R 200 141A-WS45RR 163 141A-VN3120 485 141A-AHS81 18141A-SM54RS45 494 141A-GS54R 226 141A-WS54RR 204 141A-VN3185 1140 141A-AHM90 65141A-SM63RS45 502 141A-GS72S 268 141A-WM45RR 189 141A-VN3300R 1540 141A-AHM171 122141A-SM45S 300 141A-GS81S 289 141A-WM54RR 211 141A-VN3300F 1619 141A-AHM252 180141A-SM54S 327 141A-GM45RS25 313 141A-WL45RR 211 141A-VS116 21 141A-AHH54 19141A-SM63S 405 141A-GM54RS25 368 141A-WL54RR 222 141A-VS216 23 141A-APC8 29
141A-GM54RS45 379 141A-WS45RRP 180 141A-VS135 46 141A-APC10 35
141A-GM63RS45 400 141A-WS54RRP 221 141A-VS235 47 141A-APC12 40
141A-GM45S 211 141A-WM45RRP 212 141A-VS170 71 141A-APH 5
141A-GM54S 277 141A-WM54RRP 234 141A-VS270 74 141A-AS9B 20
141A-GM63S 298 141A-WL45RRP 240 141A-BK1 144 141A-AS9W 20
141A-FS45S25 272 141A-WL54RRP 251 141A-VC3A 185 141A-AS9S 38
141A-FS54S63 328 141A-VC3B 251 141A-AK 1
141A-FS63S63 349 141A-VC3C 565 141A-AS 75
141A-FS72S63 387 141A-VC3D 870
141A-FS81S63 408 141A-BCF1 750
141A-FM45SS25 293 141A-BCF1H 40
141A-FM54SS63 349 141A-BS5 87
141A-FM63SS63 370 141A-BS10 101
141A-FM72SS63 408
141A-FM81SS63 429
Bulletin 141AMCS Mounting System
212
Approximate Dimensions
Dimensions are in millimeters. Dimensions are not intended for manufacturing purposes.
Cat. No. 141A-S…ISO Busbar Modules
NOTES:
1. FREE SPACE REQUIRED TO GET THE DEVICE ADAPTER PLATE IN PARKING POSITION.
34
60
60
200
C
D
A
26 SEE NOTE 1 E5
B
47
10
75
CATALOG NO. A B C D E141A-SS45RR25 200 45 65 162.5 73141A-SS54RR25 200 54 65 162.5 73141A-SS54RR45 200 54 65 170 95141A-SS63RR45 200 63 65 170 95141A-SS45R 200 45 - 162.5 -141A-SS54R 200 54 - 170 -141A-SM45RS25 260 45 65 170 73141A-SM54RS25 260 54 65 170 73141A-SM54RS45 260 54 65 170 95141A-SM63RS45 260 63 65 170 95141A-SM45S 260 45 - 170 -141A-SM54S 260 54 - 170 -141A-SM63S 260 63 - 170 -
213
Bulletin 141AMCS Mounting System
Approximate Dimensions, Continued
Dimensions are in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Cat. No. 141A-GS, -GM Standard Busbar Modules with Wires
CAT. NO. APER DETAIL B C D E141A-GS45RR25 200 45 65 162.5 73141A-GS54RR25 200 54 65 162.5 73141A-GS54RR45 200 54 65 170 95141A-GS63RR45 200 63 65 170 95141A-GS45R 200 45 — 162.5 —141A-GS54R 200 54 — 170 —141A-GS72S 200 72 105 — —141A-GS81S 200 81 105 — —141A-GM45RS25 260 45 65 170 73141A-GM54RS25 260 54 65 170 73141A-GM54RS45 260 54 65 170 95141A-GM63RS45 260 63 65 170 95141A-GM45S 260 45 — 170 —141A-GM54S 260 54 — 170 —141A-GM63S 260 63 — 170 —
A
D
C
34
60
200
B
63
35
10
E
12SEE NOTE 1
60
NOTES:
1. FREE SPACE REQUIRED TO PLUG/UNPLUG MODULE INTO THE BUSBARS.
DETAIL AAAAAAAAAAAAAAAA
141A-GS90M125141A-GS171M125141A-GS252M125
BCD
———
———
———
———
———
Bulletin 141AMCS Mounting System
214
Approximate Dimensions, Continued
Dimensions are in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Cat. No. 141A-F… Standard Busbar Modules with Terminals
NOTES:
1. FREE SPACE REQUIRED TO PLUG/UNPLUG MODULE INTO THE BUSBARS.
A
D
C
34
60
60
200
B
63
35
10
E
CAT. NO. A B C D141A-FS45S25 200 45 65 — 6mm² AWG 10141A-FS54S63 200 54 65 — 16mm² AWG 6141A-FS63S63 200 63 65 — 16mm² AWG 6141A-FS72S63 200 72 65 — 16mm² AWG 6141A-FS81S63 200 81 65 — 16mm² AWG 6141A-FM45SS25 260 45 65 170 6mm² AWG 10141A-FM54SS63 260 54 65 170 16mm² AWG 6141A-FM63SS63 260 63 65 170 16mm² AWG 6141A-FM72SS63 260 72 65 170 16mm² AWG 6141A-FM81SS63 260 81 65 170 16mm² AWG 6
WIRE SIZES
12SEE NOTE 1
215
Bulletin 141AMCS Mounting System
Approximate Dimensions, Continued
Dimensions are in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Panel Mounting Modules
oben/top
A
C
152.5
E
F
64
125
D
25
B
Cat. No. A B C D E F141A-WS45RR(P) 228 45 69 166.5 210 35141A-WS54RR(P) 228 54 69 174 210 40141A-WM45RR(P) 283 45 69 166.5 265 35141A-WM54RR(P) 283 54 69 174 265 40141A-WL45RR(P) 333 45 69 166.5 315 35141A-WL54RR(P) 333 54 69 174 315 40
Bulletin 141AMCS Mounting System
216
Approximate Dimensions, Continued
Dimensions are in millimeters. Dimensions are not intended for manufacturing purposes.
Cat. No. 141A-W… Panel Mount Modules
oben/top
A
C
152.5
E
F
64
125
D
25
B
CATALOG NO. A B C D E F141A-WS45RR(P) 228 45 69 166.5 210 35141A-WS54RR(P) 228 54 69 174 210 40141A-WM45RR(P) 283 45 69 166.5 265 35141A-WM54RR(P) 283 54 69 174 265 40141A-WL45RR(P) 333 45 69 166.5 315 35141A-WL54RR(P) 333 54 69 174 315 40
217
Bulletin 141AMCS Mounting System
Approximate Dimensions, Continued
Dimensions are in millimeters. Dimensions are not intended for manufacturing purposes.
Supply Modules
Cat. No. 141A-VN370
Cat. No. 141A-VN3120
Bulletin 141AMCS Mounting System
218
Approximate Dimensions, Continued
Dimensions are in millimeters. Dimensions are not intended for manufacturing purposes.
Supply Modules, Continued
Cat. Nos. 141A-VN3185, -VN3300R, and -VN3300F
135
60
94
200194
60
27,5 32
90
184,5
82
30255
20
L33L33
L22
L11L11
219
Bulletin 141AMCS Mounting System
Approximate Dimensions, Continued
Dimensions are in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Standard Busbar Modules — Universal Adapters
30 20 20
90
80
60
50
40
30
60
50
40
30
10
0
190
180
170
160
150
140
130
110
60
50
40
30
20
10
0 L33
L1
L1L
10Nm
L2 L3L
36
36
101
73
23
50,5
14
40 30 20 30
40 30 20 30
80
80
210
70
60
50
30
10
0
70
60
50
40
30
20
10
200
190
170
160
150
140
1303031303
110110
90
80
60
40
30
20
10
000
L3L22L1
20Nm
L33
10Nm
obene
L1-60
L2L
30
20
40
50
60
80160
70
30
20
10
0
10
40
50
60
70
80
90
1001
110
1201
130 50
40
30
20
10
8NmNm
L18Nm
L2 L33
30 20 3020
30 20 3020
L3-40
L1-40
obene
45
38,5
9
108
16 44
222
109
60
oben
3020
L2L
30
20
40
50
60
80160
70
30
20
10
0
10
40
50
60
70
80
90
100
110
120
50
40
30
20
10
6-70
L22L1
8NmNm
20 3020
20
L3-40
L1-40
L3-60
45
73
73
101
38,5
108
222
35 35
16 44
60
60
101
30MAX.
60
60
60
9
30MAX.
2141
108
320
152
60
60
60
21
36
101
152
60
73
41
320
110
60
60
60
30MAX.30
MAX.
Cat. No. 141A-FS108V200B Cat. No. 141A-FS108V200T
Cat. No. 141A-FL110V250TCat. No. 141A-FL110V250B
Bulletin 141AMCS Mounting System
220
Approximate Dimensions, Continued
Dimensions are in millimeters. Dimensions are not intended for manufacturing purposes.
Busbars
Cat. Nos. 141A-BCF1, 141A-BCF1H Busbar Cover and Cover Holder
Cat. No. A B C Cat. No. A B C141A-B3010A 30 10 800 141A-B255B 25 5 1600141A-B2010A 20 10 800 141A-B205B 20 5 1600141A-B1210A 12 10 800 141A-B155B 15 5 1600141A-B305A 30 5 800 141A-B125B 12 5 1600141A-B255A 25 5 800 141A-B3010N 30 10 2400141A-B205A 20 5 800 141A-B2010N 20 10 2400141A-B155A 15 5 800 141A-B1210N 12 10 2400141A-B125A 12 5 800 141A-B305N 30 5 2400
141A-B3010B 30 10 1600 141A-B255N 25 5 2400141A-B2010B 20 10 1600 141A-B205N 20 5 2400141A-B1210B 12 10 1600 141A-B155N 15 5 2400141A-B305B 30 5 1600 141A-B125N 12 5 2400
"C" "B"
"A"
32
60
60195,4
6060
Cat. No. 141A-BCF1 Cat. No. 141A-BCF1H
221
Bulletin 141AMCS Mounting System
Approximate Dimensions, Continued
Dimensions are in millimeters. Dimensions are not intended for manufacturing purposes.
Cat. No. 141A-TR…Busbar Supports and End Covers
Cat. No. 141A-TR3 Cat. No. 141A-TR3E
Cat. No. 141A-TR4E
L3
2L
L1
L3
2L
L1
PE N
L3
2L
L1
PE N
L3
2L
L1
6,5
125
20
12
28
51
60
5 31
22660 245
60
2051
5 31
166
28
12
75
6,5
60
60
185
Cat. No. 141A-TR1
Cat. No. 141A-TR3
Cat. No. 141A-TR3F16 Cat. No. 141A-TR4
L3
2L
L1
PE N
L3
2L
L1
26
20
63 50
51
20
18575
60
6,5
125
20
12
28
51
60
60 245
60
60
202
77
28
6,5
36,5
2051
28
12
75
6,5
60
60
185
Cat. No. 141A-TR3E
L3
2L
L1
5 31
166
Bulletin 103S/107SIEC Combination Starters, Standard Busbar Mount
222
Overview/Product Selection
2-Component Starters, Type 1 Coordination
➊ These starters are UL Listed as Manual Motor Controllers and must be applied in Group Installations per NEC Article 430-53 with a max. 1000 A back-up fuse or Circuit Breaker. See page 234 for details.
⊗ Coil Voltage Codes for AC and DC Control — see page 233
Bulletin 103S/107S IEC Starters• Current Range 0.1…90 A• UL Listed Combination Motor Comtrollers
Type 1 CoordinationType 2 Coordination
• UL Listed Self-Protected Combination Motor Controllers• Assemblies consist of Bulletin 140M MPCBs and Bulletin 100-C contactors mounted on
Bulletin 141A Standard Busbar Modules• Factory installed options include:
Installation and wiring of Control Plug for auxiliary contacts.Installation of Lockable Twist Knob.Installation of Spacing Adapter for Self-Protected Starters.Electronic Interface and Surge Suppressors for coil on 100-C.Additional auxiliary contacts for 100-C.Additional auxiliary or trip contacts on 140M.
Table of ContentsProduct Selection ............. 223Factory-Installed Options. 231UL Listed Application Ratings .......... 234Accessories....................... 235Specifications.................... 102Approximate Dimensions. 131
Conformity to StandardsUL 508CSA 22.2 No. 14IEC 60947 -2, -4
ApprovalsUL ListedCSA CertifiedCE
Index
MotorCurrent
AdjustmentRange
(A)
MagneticRelease
OperatingCurrent
(A)
Max. Hp, 3-phaseMax. Fault
Current 480Y/277V
Max. Fault Current
600Y/347VStandard Bus Bar Mount
200V 230V 460V 575VType 1 Iq
[kA]Type 1 Iq
[kA]Non-ReversingStarter Cat. No.
Reversing StarterCat. No.
C Frame1 0.10…0.16 2.1 — — — — 65 47 103S-AT⊗ 2-CA16C 107S-AT⊗ 3-CA16C2 0.16…0.25 3.3 — — — — 65 47 103S-AT⊗ 2-CA25C 107S-AT⊗ 3-CA25C3 0.25…0.40 5.2 — — — — 65 47 103S-AT⊗ 2-CA40C 107S-AT⊗ 3-CA40C4 0.40…0.63 8.2 — — — — 65 47 103S-AT⊗ 2-CA63C 107S-AT⊗ 3-CA63C5 0.63…1.0 13 — — 1/2 3/4 65 47 103S-AT⊗ 2-CB10C 107S-AT⊗ 3-CB10C6 1.0…1.6 21 — — 1 1 65 47 103S-AT⊗ 2-CB16C 107S-AT⊗ 3-CB16C7 1.6…2.5 33 1/2 3/4 1-1/2 2 65 10 103S-AT⊗ 2-CB25C 107S-AT⊗ 3-CB25C8 2.5…4.0 52 1 1 3 3 65 10 103S-AT⊗ 2-CB40C 107S-AT⊗ 3-CB40C9 4.0…6.3 82 1-1/2 2 5 5 65 — 103S-AT⊗ 2-CB63C 107S-AT⊗ 3-CB63C
10 6.3…10 130 3 3 7-1/2 10 65 — 103S-BT⊗ 2-CC10C 107S-BT⊗ 3-CC10CD Frame
14 1.6…2.5 33 1/2 3/4 1-1/2 2 65 30 103S-AT⊗ 2-DB25C 107S-AT⊗ 3-DB25C16 2.5…4.0 52 1 1 3 3 65 30 103S-AT⊗ 2-DB40C 107S-AT⊗ 3-DB40C18 4.0…6.3 82 1-1/2 2 5 5 65 30 103S-AT⊗ 2-DB63C 107S-AT⊗ 3-DB63C20 6.3…10 130 3 3 7-1/2 10 65 30 103S-BT⊗ 2-DC10C 107S-BT⊗ 3-DC10C22 10…16 208 3 5 10 15 65 30 103S-CT⊗ 2-DC16C 107S-CT⊗ 3-DC16C24 14.5…20 260 5 7-1/2 15 15 65 — 103S-DT⊗ 2-DC20C 107S-DT⊗ 3-DC20C26 18…25 325 5 7-1/2 15 15 65 — 103S-DT⊗ 2-DC25C 107S-DT⊗ 3-DC25C
F Frame30 14.5…20 260 5 7-1/2 15 20 65 30 103S-ET⊗ 2-FC20C 107S-ET⊗ 3-FC20C31 18…25 325 7-1/2 10 20 25 65 30 103S-ET⊗ 2-FC25C 107S-ET⊗ 3-FC25C32 25…32 416 10 10 25 30 65 30 103S-FT⊗ 2-FC32C 107S-FT⊗ 3-FC32C33 32…45 585 10 15 30 30 65 30 103S-GT⊗ 2-FC45C 107S-GT⊗ 3-FC45C
CMN Frame ➊34 40…63 882 15 20 40 50 42 18 103S-HT⊗ 2-GC63C 107S-HT⊗ 3-GC63C35 40…63 882 20 20 50 60 42 18 103S-JT⊗ 2-GC63C 107S-JT⊗ 3-GC63C36 63…90 1260 20 25 50 60 35 10 103S-JT⊗ 2-GC90C 107S-JT⊗ 3-GC90C37 63…90 1260 25 30 60 60 35 10 103S-KT⊗ 2-GC90C 107S-KT⊗ 3-GC90C
223
Bulletin 103S/107SIEC Combination Starters, Standard Busbar Mount
Product Selection, Continued
2-Component Starters, Type 2 Coordination
➊ These starters are UL Listed as Manual Motor Controllers and must be applied in Group Installations per NEC Article 430-53 with a max. 1000 A back-up fuse or Circuit Breaker. See page 234 for details.
⊗ Coil Voltage Codes for AC and DC Control — see page 233
IndexMotor Current
Adjustment Range (A)
Magnetic Release
Operating Current (A)
Max. Hp, 3-phaseMax. Fault
Current 480Y/277V
Max. Fault Current
600Y/347VStandard Bus Bar Mount
200V 230V 460V 575V Type 2 Iq [kA] Type 2 Iq [kA] Non-Reversing Starter Cat. No.
Reversing Starter Cat. No.
C Frame1 0.10…0.16 2.1 — — — — 65 47 103S-AT⊗ 2-CA16C 107S-AT⊗ 3-CA16C2 0.16…0.25 3.3 — — — — 65 47 103S-AT⊗ 2-CA25C 107S-AT⊗ 3-CA25C3 0.25…0.40 5.2 — — — — 65 47 103S-AT⊗ 2-CA40C 107S-AT⊗ 3-CA40C4 0.40…0.63 8.2 — — — — 65 47 103S-AT⊗ 2-CA63C 107S-AT⊗ 3-CA63C5 0.63…1.0 13 — — 1/2 3/4 65 47 103S-AT⊗ 2-CB10C 107S-AT⊗ 3-CB10C6 1.0…1.6 21 — — 1 1 65 47 103S-AT⊗ 2-CB16C 107S-AT⊗ 3-CB16C7 1.6…2.5 33 1/2 3/4 1-1/2 2 65 10 103S-AT⊗ 2-CB25C 107S-AT⊗ 3-CB25C
D Frame15 1.6…2.5 33 1/2 3/4 1-1/2 2 65 30 103S-DT⊗ 2-DB25C 107S-DT⊗ 3-DB25C16 2.5…4.0 52 1 1 3 3 65 — 103S-AT⊗ 2-DB40C 107S-AT⊗ 3-DB40C17 2.5…4.0 52 1 1 3 3 65 30 103S-DT⊗ 2-DB40C 107S-DT⊗ 3-DB40C18 4.0…6.3 82 1-1/2 2 5 5 65 — 103S-AT⊗ 2-DB63C 107S-AT⊗ 3-DB63C19 4.0…6.3 82 1-1/2 2 5 5 65 30 103S-ET⊗ 2-DB63C 107S-ET⊗ 3-DB63C20 6.3…10 130 3 3 7-1/2 10 65 — 103S-BT⊗ 2-DC10C 107S-BT⊗ 3-DC10C21 6.3…10 130 3 3 7-1/2 10 65 30 103S-ET⊗ 2-DC10C 107S-ET⊗ 3-DC10C22 10…16 208 3 5 10 15 65 — 103S-CT⊗ 2-DC16C 107S-CT⊗ 3-DC16C23 10…16 208 3 5 10 15 65 30 103S-ET⊗ 2-DC16C 107S-ET⊗ 3-DC16C24 14.5…20 260 5 7-1/2 15 15 65 — 103S-DT⊗ 2-DC20C 107S-DT⊗ 3-DC20C25 14.5…20 260 5 7-1/2 15 20 65 — 103S-ET⊗ 2-DC20C 107S-ET⊗ 3-DC20C26 18…25 325 5 7-1/2 15 15 65 — 103S-DT⊗ 2-DC25C 107S-DT⊗ 3-DC25C27 18…25 325 7-1/2 7-1/2 15 20 65 — 103S-ET⊗ 2-DC25C 107S-ET⊗ 3-DC25C
F Frame28 6.3…10 130 3 3 7-1/2 10 65 30 103S-ET⊗ 2-FC10C 107S-ET⊗ 3-FC10C29 10…16 208 3 5 10 15 65 30 103S-ET⊗ 2-FC16C 107S-ET⊗ 3-FC16C30 14.5…20 260 5 7-1/2 15 20 65 30 103S-ET⊗ 2-FC20C 107S-ET⊗ 3-FC20C31 18…25 325 7-1/2 10 20 25 65 30 103S-ET⊗ 2-FC25C 107S-ET⊗ 3-FC25C32 25…32 416 10 10 25 30 65 30 103S-FT⊗ 2-FC32C 107S-FT⊗ 3-FC32C33 32…45 585 10 15 30 30 65 30 103S-GT⊗ 2-FC45C 107S-GT⊗ 3-FC45C
CMN Frame ➊34 40…63 882 15 20 40 50 42 18 103S-HT⊗ 2-GC63C 107S-HT⊗ 3-GC63C35 40…63 882 20 20 50 60 42 18 103S-JT⊗ 2-GC63C 107S-JT⊗ 3-GC63C36 63…90 1260 20 25 50 60 35 10 103S-JT⊗ 2-GC90C 107S-JT⊗ 3-GC90C37 63…90 1260 25 30 60 60 35 10 103S-KT⊗ 2-GC90C 107S-KT⊗ 3-GC90C
Bulletin 103S/107SIEC Combination Starters, Standard Busbar Mount
224
Product Selection, Continued
2-Component Starters, Self-Protected
⊗ Coil Voltage Codes for AC and DC Control — see page 233
IndexMotor Current
Adjustment Range (A)
Magnetic Release
Operating Current (A)
Max. Hp, 3-phaseMax. Fault
Current 480Y/277V
Max. Fault Current
600Y/347VStandard Bus Bar Mount
200V 230V 460V 575V Type E Iq [kA] Type E Iq [kA] Non-Reversing Starter Cat. No.
Reversing Starter Cat. No.
C Frame1 0.10…0.16 2.1 — — — — 65 47 103S-AT⊗ 2-CA16C 107S-AT⊗ 3-CA16C2 0.16…0.25 3.3 — — — — 65 47 103S-AT⊗ 2-CA25C 107S-AT⊗ 3-CA25C3 0.25…0.40 5.2 — — — — 65 47 103S-AT⊗ 2-CA40C 107S-AT⊗ 3-CA40C4 0.40…0.63 8.2 — — — — 65 47 103S-AT⊗ 2-CA63C 107S-AT⊗ 3-CA63C5 0.63…1.0 13 — — 1/2 3/4 65 47 103S-AT⊗ 2-CB10C 107S-AT⊗ 3-CB10C6 1.0…1.6 21 — — 1 1 65 47 103S-AT⊗ 2-CB16C 107S-AT⊗ 3-CB16C7 1.6…2.5 33 1/2 3/4 1-1/2 2 65 — 103S-AT⊗ 2-CB25C 107S-AT⊗ 3-CB25C
D Frame15 1.6…2.5 33 1/2 3/4 1-1/2 2 65 30 103S-DT⊗ 2-DB25C 107S-DT⊗ 3-DB25C17 2.5…4.0 52 1 1 3 3 65 30 103S-DT⊗ 2-DB40C 107S-DT⊗ 3-DB40C19 4.0…6.3 82 1-1/2 2 5 5 65 30 103S-ET⊗ 2-DB63C 107S-ET⊗ 3-DB63C21 6.3…10 130 3 3 7-1/2 10 65 30 103S-ET⊗ 2-DC10C 107S-ET⊗ 3-DC10C23 10…16 208 3 5 10 15 65 30 103S-ET⊗ 2-DC16C 107S-ET⊗ 3-DC16C25 14.5…20 260 5 7-1/2 15 20 65 — 103S-ET⊗ 2-DC20C 107S-ET⊗ 3-DC20C27 18…25 325 7-1/2 7-1/2 15 20 65 — 103S-ET⊗ 2-DC25C 107S-ET⊗ 3-DC25C
F Frame30 14.5…20 260 5 7-1/2 15 20 65 30 103S-ET⊗ 2-FC20C 107S-ET⊗ 3-FC20C31 18…25 325 7-1/2 10 20 25 65 30 103S-ET⊗ 2-FC25C 107S-ET⊗ 3-FC25C32 25…32 416 10 10 25 30 65 30 103S-FT⊗ 2-FC32C 107S-FT⊗ 3-FC32C33 32…45 585 10 15 30 30 65 — 103S-GT⊗ 2-FC45C 107S-GT⊗ 3-FC45C
225
Bulletin 103S/107SIEC Combination Starters, ISO Busbar Mount
Overview/Product Selection
2-Component Starters, Type 1 Coordination
⊗ Coil Voltage Codes for AC and DC Control — see page 233
Bulletin 103S/107S IEC Starters• Current Range 0.1…45 A• UL Listed Combination Motor Comtrollers
Type 1 CoordinationType 2 Coordination
• UL Listed Self-Protected Combination Motor Controllers• Assemblies consist of Bulletin 140M MPCBs and Bulletin 100-C contactors mounted on
Bulletin 141A ISO Busbar Modules• Installation and wiring of Control Plug for auxiliary contacts is standard on ISO Busbar
Mount starters.• Factory installed options include:
Installation of Lockable Twist Knob.Installation of Spacing Adapter for Self-Protected Starters.Electronic Interface and Surge Suppressors for coil on 100-C.Additional auxiliary contacts for 100-C.Additional auxiliary or trip contacts on 140M.
Table of ContentsProduct Selection ..............225Factory-Installed Options .231UL Listed Application Ratings...........234Accessories .......................235Specifications ....................102Approximate Dimensions .131
Conformity to StandardsUL 508CSA 22.2 No. 14IEC 60947 -2, -4
ApprovalsUL ListedCSA CertifiedCE
IndexMotor Current
Adjustment Range (A)
Magnetic Release
Operating Current (A)
Max. Hp, 3-phaseMax. Fault
Current 480Y/277V
Max. Fault Current
600Y/347VISO Bus Bar Mount
200V 230V 460V 575V Type 1 Iq [kA] Type 1 Iq [kA] Non-Reversing Starter Cat. No.
Reversing Starter Cat. No.
C Frame1 0.10…0.16 2.1 — — — — 65 47 103S-AS⊗ 2-CA16C 107S-AS⊗ 3-CA16C2 0.16…0.25 3.3 — — — — 65 47 103S-AS⊗ 2-CA25C 107S-AS⊗ 3-CA25C3 0.25…0.40 5.2 — — — — 65 47 103S-AS⊗ 2-CA40C 107S-AS⊗ 3-CA40C4 0.40…0.63 8.2 — — — — 65 47 103S-AS⊗ 2-CA63C 107S-AS⊗ 3-CA63C5 0.63…1.0 13 — — 1/2 3/4 65 47 103S-AS⊗ 2-CB10C 107S-AS⊗ 3-CB10C6 1.0…1.6 21 — — 1 1 65 47 103S-AS⊗ 2-CB16C 107S-AS⊗ 3-CB16C7 1.6…2.5 33 1/2 3/4 1-1/2 2 65 10 103S-AS⊗ 2-CB25C 107S-AS⊗ 3-CB25C8 2.5…4.0 52 1 1 3 3 65 10 103S-AS⊗ 2-CB40C 107S-AS⊗ 3-CB40C9 4.0…6.3 82 1-1/2 2 5 5 65 — 103S-AS⊗ 2-CB63C 107S-AS⊗ 3-CB63C10 6.3…10 130 3 3 7-1/2 10 65 — 103S-BS⊗ 2-CC10C 107S-BS⊗ 3-CC10C
D Frame14 1.6…2.5 33 1/2 3/4 1-1/2 2 65 30 103S-AS⊗ 2-DB25C 107S-AS⊗ 3-DB25C16 2.5…4.0 52 1 1 3 3 65 30 103S-AS⊗ 2-DB40C 107S-AS⊗ 3-DB40C18 4.0…6.3 82 1-1/2 2 5 5 65 30 103S-AS⊗ 2-DB63C 107S-AS⊗ 3-DB63C20 6.3…10 130 3 3 7-1/2 10 65 30 103S-BS⊗ 2-DC10C 107S-BS⊗ 3-DC10C22 10…16 208 3 5 10 15 65 30 103S-CS⊗ 2-DC16C 107S-CS⊗ 3-DC16C24 14.5…20 260 5 7-1/2 15 15 65 — 103S-DS⊗ 2-DC20C 107S-DS⊗ 3-DC20C26 18…25 325 5 7-1/2 15 15 65 — 103S-DS⊗ 2-DC25C 107S-DS⊗ 3-DC25C
F Frame30 14.5…20 260 5 7-1/2 15 20 65 30 103S-ES⊗ 2-FC20C 107S-ES⊗ 3-FC20C31 18…25 325 7-1/2 10 20 25 65 30 103S-ES⊗ 2-FC25C 107S-ES⊗ 3-FC25C32 25…32 416 10 10 25 30 65 30 103S-FS⊗ 2-FC32C 107S-FS⊗ 3-FC32C33 32…45 585 10 15 30 30 65 30 103S-GS⊗ 2-FC45C 107S-GS⊗ 3-FC45C
Bulletin 103S/107SIEC Combination Starters, ISO Busbar Mount
226
Product Selection, Continued
2-Component Starters, Type 2 Coordination
⊗ Coil Voltage Codes for AC and DC Control — see page 233
IndexMotor Current
Adjustment Range (A)
Magnetic Release
Operating Current (A)
Max. Hp, 3-phaseMax. Fault
Current 480Y/277V
Max. Fault Current
600Y/347VISO Bus Bar Mount
200V 230V 460V 575V Type 2 Iq [kA] Type 2 Iq [kA] Non-Reversing Starter Cat. No.
Reversing Starter Cat. No.
C Frame1 0.10…0.16 2.1 — — — — 65 47 103S-AS⊗ 2-CA16C 107S-AS⊗ 3-CA16C2 0.16…0.25 3.3 — — — — 65 47 103S-AS⊗ 2-CA25C 107S-AS⊗ 3-CA25C3 0.25…0.40 5.2 — — — — 65 47 103S-AS⊗ 2-CA40C 107S-AS⊗ 3-CA40C4 0.40…0.63 8.2 — — — — 65 47 103S-AS⊗ 2-CA63C 107S-AS⊗ 3-CA63C5 0.63…1.0 13 — — 1/2 3/4 65 47 103S-AS⊗ 2-CB10C 107S-AS⊗ 3-CB10C6 1.0…1.6 21 — — 1 1 65 47 103S-AS⊗ 2-CB16C 107S-AS⊗ 3-CB16C7 1.6…2.5 33 1/2 3/4 1-1/2 2 65 10 103S-AS⊗ 2-CB25C 107S-AS⊗ 3-CB25C
D Frame15 1.6…2.5 33 1/2 3/4 1-1/2 2 65 30 103S-DS⊗ 2-DB25C 107S-DS⊗ 3-DB25C16 2.5…4.0 52 1 1 3 3 65 — 103S-AS⊗ 2-DB40C 107S-AS⊗ 3-DB40C17 2.5…4.0 52 1 1 3 3 65 30 103S-DS⊗ 2-DB40C 107S-DS⊗ 3-DB40C18 4.0…6.3 82 1-1/2 2 5 5 65 — 103S-AS⊗ 2-DB63C 107S-AS⊗ 3-DB63C19 4.0…6.3 82 1-1/2 2 5 5 65 30 103S-ES⊗ 2-DB63C 107S-ES⊗ 3-DB63C20 6.3…10 130 3 3 7-1/2 10 65 — 103S-BS⊗ 2-DC10C 107S-BS⊗ 3-DC10C21 6.3…10 130 3 3 7-1/2 10 65 30 103S-ES⊗ 2-DC10C 107S-ES⊗ 3-DC10C22 10…16 208 3 5 10 15 65 — 103S-CS⊗ 2-DC16C 107S-CS⊗ 3-DC16C23 10…16 208 3 5 10 15 65 30 103S-ES⊗ 2-DC16C 107S-ES⊗ 3-DC16C24 14.5…20 260 5 7-1/2 15 15 65 — 103S-DS⊗ 2-DC20C 107S-DS⊗ 3-DC20C25 14.5…20 260 5 7-1/2 15 20 65 — 103S-ES⊗ 2-DC20C 107S-ES⊗ 3-DC20C26 18…25 325 5 7-1/2 15 15 65 — 103S-DS⊗ 2-DC25C 107S-DS⊗ 3-DC25C27 18…25 325 7-1/2 7-1/2 15 20 65 — 103S-ES⊗ 2-DC25C 107S-ES⊗ 3-DC25C
F Frame28 6.3…10 130 3 3 7-1/2 10 65 30 103S-ES⊗ 2-FC10C 107S-ES⊗ 3-FC10C29 10…16 208 3 5 10 15 65 30 103S-ES⊗ 2-FC16C 107S-ES⊗ 3-FC16C30 14.5…20 260 5 7-1/2 15 20 65 30 103S-ES⊗ 2-FC20C 107S-ES⊗ 3-FC20C31 18…25 325 7-1/2 10 20 25 65 30 103S-ES⊗ 2-FC25C 107S-ES⊗ 3-FC25C32 25…32 416 10 10 25 30 65 30 103S-FS⊗ 2-FC32C 107S-FS⊗ 3-FC32C33 32…45 585 10 15 30 30 65 30 103S-GS⊗ 2-FC45C 107S-GS⊗ 3-FC45C
227
Bulletin 103S/107SIEC Combination Starters, ISO Busbar Mount
Product Selection, Continued
2-Component Starters, Self-Protected
⊗ Coil Voltage Codes for AC and DC Control — see page 233
IndexMotor Current
Adjustment Range (A)
Magnetic Release
Operating Current (A)
Max. Hp, 3-phaseMax. Fault
Current 480Y/277V
Max. Fault Current
600Y/347VISO Bus Bar Mount
200V 230V 460V 575V Type E Iq [kA] Type E Iq [kA] Non-Reversing Starter Cat. No.
Reversing Starter Cat. No.
C Frame1 0.10…0.16 2.1 — — — — 65 47 103S-AS⊗ 2-CA16C 107S-AS⊗ 3-CA16C2 0.16…0.25 3.3 — — — — 65 47 103S-AS⊗ 2-CA25C 107S-AS⊗ 3-CA25C3 0.25…0.40 5.2 — — — — 65 47 103S-AS⊗ 2-CA40C 107S-AS⊗ 3-CA40C4 0.40…0.63 8.2 — — — — 65 47 103S-AS⊗ 2-CA63C 107S-AS⊗ 3-CA63C5 0.63…1.0 13 — — 1/2 3/4 65 47 103S-AS⊗ 2-CB10C 107S-AS⊗ 3-CB10C6 1.0…1.6 21 — — 1 1 65 47 103S-AS⊗ 2-CB16C 107S-AS⊗ 3-CB16C7 1.6…2.5 33 1/2 3/4 1-1/2 2 65 — 103S-AS⊗ 2-CB25C 107S-AS⊗ 3CB25C
D Frame15 1.6…2.5 33 1/2 3/4 1-1/2 2 65 30 103S-DS⊗ 2-DB25C 107S-DS⊗ 3-DB25C17 2.5…4.0 52 1 1 3 3 65 30 103S-DS⊗ 2-DB40C 107S-DS⊗ 3-DB40C19 4.0…6.3 82 1-1/2 2 5 5 65 30 103S-ES⊗ 2-DB63C 107S-ES⊗ 3-DB63C21 6.3…10 130 3 3 7-1/2 10 65 30 103S-ES⊗ 2-DC10C 107S-ES⊗ 3-DC10C23 10…16 208 3 5 10 15 65 30 103S-ES⊗ 2-DC16C 107S-ES⊗ 3-DC16C25 14.5…20 260 5 7-1/2 15 20 65 — 103S-ES⊗ 2-DC20C 107S-ES⊗ 3-DC20C27 18…25 325 7-1/2 7-1/2 15 20 65 — 103S-ES⊗ 2-DC25C 107S-ES⊗ 3-DC25C
F Frame30 14.5…20 260 5 7-1/2 15 20 65 30 103S-ES⊗ 2-FC20C 107S-ES⊗ 3-FC20C31 18…25 325 7-1/2 10 20 25 65 30 103S-ES⊗ 2-FC25C 107S-ES⊗ 3-FC25C32 25…32 416 10 10 25 30 65 30 103S-FS⊗ 2-FC32C 107S-FS⊗ 3-FC32C33 32…45 585 10 15 30 30 65 — 103S-GS⊗ 2-FC45C 107S-GS⊗ 3-FC45C
Bulletin 103S/107SIEC Combination Starters, Panel Mount
228
Product Selection
2-Component Starters, Type 1 Coordination
➊ These starters are UL Listed as Manual Motor Controllers and must be applied in Group Installations per NEC Article 430-53 with a max. 1000 A back-up fuse or Circuit Breaker. See page 234 for details.
⊗ Coil Voltage Codes for AC and DC Control — see page 233
Bulletin 103S/107S IEC Starters• Current Range 0.1…90 A• UL Listed Combination Motor Comtrollers
Type 1 CoordinationType 2 Coordination
• UL Listed Self-Protected Combination Motor Controllers• Assemblies consist of Bulletin 140M MPCBs and Bulletin 100-C contactors mounted on
Bulletin 141A Panel Mount Modules• Factory installed options include:
Installation and wiring of Control Plug for auxiliary contacts.Installation of Lockable Twist Knob.Installation of Spacing Adapter for Self-Protected Starters.Electronic Interface and Surge Suppressors for coil on 100-C.Additional auxiliary contacts for 100-C.Additional auxiliary or trip contacts on 140M.
Table of ContentsProduct Selection ............. 228Factory-Installed Options. 231UL Listed Application Ratings .......... 234Accessories....................... 235Specifications.................... 102Approximate Dimensions. 131
Conformity to StandardsUL 508CSA 22.2 No. 14IEC 60947 -2, -4
ApprovalsUL ListedCSA CertifiedCE
IndexMotor Current
Adjustment Range (A)
Magnetic Release
Operating Current (A)
Max. Hp, 3-phaseMax. Fault
Current 480Y/277V
Max. Fault Current
600Y/347VPanel Mount
200V 230V 460V 575V Type 1 Iq [kA] Type 1 Iq [kA] Non-Reversing Starter Cat. No.
Reversing Starter Cat. No.
C Frame1 0.10…0.16 2.1 — — — — 65 47 103S-AW⊗ 2-CA16C 107S-AW⊗ 3-CA16C2 0.16…0.25 3.3 — — — — 65 47 103S-AW⊗ 2-CA25C 107S-AW⊗ 3-CA25C3 0.25…0.40 5.2 — — — — 65 47 103S-AW⊗ 2-CA40C 107S-AW⊗ 3-CA40C4 0.40…0.63 8.2 — — — — 65 47 103S-AW⊗ 2-CA63C 107S-AW⊗ 3-CA63C5 0.63…1.0 13 — — 1/2 3/4 65 47 103S-AW⊗ 2-CB10C 107S-AW⊗ 3-CB10C6 1.0…1.6 21 — — 1 1 65 47 103S-AW⊗ 2-CB16C 107S-AW⊗ 3-CB16C7 1.6…2.5 33 1/2 3/4 1-1/2 2 65 10 103S-AW⊗ 2-CB25C 107S-AW⊗ 3-CB25C8 2.5…4.0 52 1 1 3 3 65 10 103S-AW⊗ 2-CB40C 107S-AW⊗ 3-CB40C9 4.0…6.3 82 1-1/2 2 5 5 65 — 103S-AW⊗ 2-CB63C 107S-AW⊗ 3-CB63C10 6.3…10 130 3 3 7-1/2 10 65 — 103S-BW⊗ 2-CC10C 107S-BW⊗ 3-CC10C
D Frame14 1.6…2.5 33 1/2 3/4 1-1/2 2 65 30 103S-AW⊗ 2-DB25C 107S-AW⊗ 3-DB25C16 2.5…4.0 52 1 1 3 3 65 30 103S-AW⊗ 2-DB40C 107S-AW⊗ 3-DB40C18 4.0…6.3 82 1-1/2 2 5 5 65 30 103S-AW⊗ 2-DB63C 107S-AW⊗ 3-DB63C20 6.3…10 130 3 3 7-1/2 10 65 30 103S-BW⊗ 2-DC10C 107S-BW⊗ 3-DC10C22 10…16 208 3 5 10 15 65 30 103S-CW⊗ 2-DC16C 107S-CW⊗ 3-DC16C24 14.5…20 260 5 7-1/2 15 15 65 — 103S-DW⊗ 2-DC20C 107S-DW⊗ 3-DC20C26 18…25 325 5 7-1/2 15 15 65 — 103S-DW⊗ 2-DC25C 107S-DW⊗ 3-DC25C
F Frame30 14.5…20 260 5 7-1/2 15 20 65 30 103S-EW⊗ 2-FC20C 107S-EW⊗ 3-FC20C31 18…25 325 7-1/2 10 20 25 65 30 103S-EW⊗ 2-FC25C 107S-EW⊗ 3-FC25C32 25…32 416 10 10 25 30 65 30 103S-FW⊗ 2-FC32C 107S-FW⊗ 3-FC32C33 32…45 585 10 15 30 30 65 30 103S-GW⊗ 2-FC45C 107S-GW⊗ 3-FC45C
CMN Frame ➊34 40…63 882 15 20 40 50 42 18 103S-HW⊗ 2-GC63C 107S-HW⊗ 3-GC63C35 40…63 882 20 20 50 60 42 18 103S-JW⊗ 2-GC63C 107S-JW⊗ 3-GC63C36 63…90 1260 20 25 50 60 35 10 103S-JW⊗ 2-GC90C 107S-JW⊗ 3-GC90C37 63…90 1260 25 30 60 60 35 10 103S-KW⊗ 2-GC90C 107S-KW⊗ 3-GC90C
229
Bulletin 103S/107SIEC Combination Starters, Panel Mount
Product Selection, Continued
2-Component Starters, Type 2 Coordination
➊ These starters are UL Listed as Manual Motor Controllers and must be applied in Group Installations per NEC Article 430-53 with a max. 1000 A back-up fuse or Circuit Breaker. See page 234 for details.
⊗ Coil Voltage Codes for AC and DC Control — see page 233
IndexMotor Current
Adjustment Range (A)
Magnetic Release
Operating Current (A)
Max. Hp, 3-phaseMax. Fault
Current 480Y/277V
Max. Fault Current
600Y/347VPanel Mount
200V 230V 460V 575V Type 2 Iq [kA] Type 2 Iq [kA] Non-Reversing Starter Cat. No.
Reversing Starter Cat. No.
C Frame1 0.10…0.16 2.1 — — — — 65 47 103S-AW⊗ 2-CA16C 107S-AW⊗ 3-CA16C2 0.16…0.25 3.3 — — — — 65 47 103S-AW⊗ 2-CA25C 107S-AW⊗ 3-CA25C3 0.25…0.40 5.2 — — — — 65 47 103S-AW⊗ 2-CA40C 107S-AW⊗ 3-CA40C4 0.40…0.63 8.2 — — — — 65 47 103S-AW⊗ 2-CA63C 107S-AW⊗ 3-CA63C5 0.63…1.0 13 — — 1/2 3/4 65 47 103S-AW⊗ 2-CB10C 107S-AW⊗ 3-CB10C6 1.0…1.6 21 — — 1 1 65 47 103S-AW⊗ 2-CB16C 107S-AW⊗ 3-CB16C7 1.6…2.5 33 1/2 3/4 1-1/2 2 65 10 103S-AW⊗ 2-CB25C 107S-AW⊗ 3-CB25C
D Frame15 1.6…2.5 33 1/2 3/4 1-1/2 2 65 30 103S-DW⊗ 2-DB25C 107S-DW⊗ 3-DB25C16 2.5…4.0 52 1 1 3 3 65 — 103S-AW⊗ 2-DB40C 107S-AW⊗ 3-DB40C17 2.5…4.0 52 1 1 3 3 65 30 103S-DW⊗ 2-DB40C 107S-DW⊗ 3-DB40C18 4.0…6.3 82 1-1/2 2 5 5 65 — 103S-AW⊗ 2-DB63C 107S-AW⊗ 3-DB63C19 4.0…6.3 82 1-1/2 2 5 5 65 30 103S-EW⊗ 2-DB63C 107S-EW⊗ 3-DB63C20 6.3…10 130 3 3 7-1/2 10 65 — 103S-BW⊗ 2-DC10C 107S-BW⊗ 3-DC10C21 6.3…10 130 3 3 7-1/2 10 65 30 103S-EW⊗ 2-DC10C 107S-EW⊗ 3-DC10C22 10…16 208 3 5 10 15 65 — 103S-CW⊗ 2-DC16C 107S-CW⊗ 3-DC16C23 10…16 208 3 5 10 15 65 30 103S-EW⊗ 2-DC16C 107S-EW⊗ 3-DC16C24 14.5…20 260 5 7-1/2 15 15 65 — 103S-DW⊗ 2-DC20C 107S-DW⊗ 3-DC20C25 14.5…20 260 5 7-1/2 15 20 65 — 103S-EW⊗ 2-DC20C 107S-EW⊗ 3-DC20C26 18…25 325 5 7-1/2 15 15 65 — 103S-DW⊗ 2-DC25C 107S-DW⊗ 3-DC25C27 18…25 325 7-1/2 7-1/2 15 20 65 — 103S-EW⊗ 2-DC25C 107S-EW⊗ 3-DC25C
F Frame28 6.3…10 130 3 3 7-1/2 10 65 30 103S-EW⊗ 2-FC10C 107S-EW⊗ 3-FC10C29 10…16 208 3 5 10 15 65 30 103S-EW⊗ 2-FC16C 107S-EW⊗ 32-FC16C30 14.5…20 260 5 7-1/2 15 20 65 30 103S-EW⊗ 2-FC20C 107S-EW⊗ 3-FC20C31 18…25 325 7-1/2 10 20 25 65 30 103S-EW⊗ 2-FC25C 107S-EW⊗ 3-FC25C32 25…32 416 10 10 25 30 65 30 103S-FW⊗ 2-FC32C 107S-FW⊗ 3-FC32C33 32…45 585 10 15 30 30 65 30 103S-GW⊗ 2-FC45C 107S-GW⊗ 3-FC45C
CMN Frame ➊34 40…63 882 15 20 40 50 42 18 103S-HW⊗ 2-GC63C 107S-HW⊗ 3-GC63C35 40…63 882 20 20 50 60 42 18 103S-JW⊗ 2-GC63C 107S-JW⊗ 3-GC63C36 63…90 1260 20 25 50 60 35 10 103S-JW⊗ 2-GC90C 107S-JW⊗ 3-GC90C37 63…90 1260 25 30 60 60 35 10 103S-KW⊗ 2-GC90C 107S-KW⊗ 3-GC90C
Bulletin 103S/107SIEC Combination Starters, Panel Mount
230
Product Selection, Continued
2-Component Starters, Self-Protected
⊗ Coil Voltage Codes for AC and DC Control — see page 233
IndexMotor Current
Adjustment Range (A)
Magnetic Release
Operating Current (A)
Max. Hp, 3-phaseMax. Fault
Current 480Y/277V
Max. Fault Current
600Y/347VPanel Mount
200V 230V 460V 575V Type E Iq [kA] Type E Iq [kA] Non-Reversing Starter Cat. No.
Reversing Starter Cat. No.
C Frame1 0.10…0.16 2.1 — — — — 65 47 103S-AW⊗ 2-CA16C 107S-AW⊗ 3-CA16C2 0.16…0.25 3.3 — — — — 65 47 103S-AW⊗ 2-CA25C 107S-AW⊗ 3-CA25C3 0.25…0.40 5.2 — — — — 65 47 103S-AW⊗ 2-CA40C 107S-AW⊗ 3-CA40C4 0.40…0.63 8.2 — — — — 65 47 103S-AW⊗ 2-CA63C 107S-AW⊗ 3-CA63C5 0.63…1.0 13 — — 1/2 3/4 65 47 103S-AW⊗ 2-CB10C 107S-AW⊗ 3-CB10C6 1.0…1.6 21 — — 1 1 65 47 103S-AW⊗ 2-CB16C 107S-AW⊗ 3-CB16C7 1.6…2.5 33 1/2 3/4 1-1/2 2 65 — 103S-AW⊗ 2-CB25C 107S-AW⊗ 3-CB25C
D Frame15 1.6…2.5 33 1/2 3/4 1-1/2 2 65 30 103S-DW⊗ 2-DB25C 107S-DW⊗ 3-DB25C17 2.5…4.0 52 1 1 3 3 65 30 103S-DW⊗ 2-DB40C 107S-DW⊗ 3-DB40C19 4.0…6.3 82 1-1/2 2 5 5 65 30 103S-EW⊗ 2-DB63C 107S-EW⊗ 3DB63C21 6.3…10 130 3 3 7-1/2 10 65 30 103S-EW⊗ 2-DC10C 107S-EW⊗ 3-DC10C23 10…16 208 3 5 10 15 65 30 103S-EW⊗ 2-DC16C 107S-EW⊗ 3-DC16C25 14.5…20 260 5 7-1/2 15 20 65 — 103S-EW⊗ 2-DC20C 107S-EW⊗ 3-DC20C27 18…25 325 7-1/2 7-1/2 15 20 65 — 103S-EW⊗ 2-DC25C 107S-EW⊗ 3-DC25C
F Frame30 14.5…20 260 5 7-1/2 15 20 65 30 103S-EW⊗ 2-FC20C 107S-EW⊗ 3-FC20C31 18…25 325 7-1/2 10 20 25 65 30 103S-EW⊗ 2-FC25C 107S-EW⊗ 3-FC25C32 25…32 416 10 10 25 30 65 30 103S-FW⊗ 2-FC32C 107S-FW⊗ 3-FC32C33 32…45 585 10 15 30 30 65 — 103S-GW⊗ 2-FC45C 107S-GW⊗ 3-FC45C
231
Bulletin 103S/107SCombination Starters
Modifications
103S Factory Installed OptionsChange option code ➀ to desired auxiliary contact: 103S-AWD➀ -CA16C
Contactor Auxiliaries without “-SP” Control PlugISO Busbar Mount Standard Busbar Mount Panel Mount
Option ➀ Description 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A
2 1 N.O. NA NA NA Standard Standard Standard Standard Standard Standard3 1 N.O. + 1 N.C. NA NA NA Available Available Available Available Available Available4 2 N.O. NA NA NA Available Available Available Available Available Available6 2 N.O. + 1 N.C. NA NA NA Available NA NA Available NA NA7 2 N.O. + 2 N.C. NA NA NA NA Available Available NA Available Available8 3 N.O. + 2 N.C. NA NA NA Available NA NA Available NA NA
Change option code ➀ to desired auxiliary contact: 103S-AWD➀ -CA16C
Contactor Auxiliaries with “-SP” Control PlugISO Busbar Mount Standard Busbar Mount Panel Mount
Option ➀ Description 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A
2 1 N.O. Standard Standard NA Available Available Available Available Available Available3 1 N.O. + 1 N.C. Available Available NA Available Available Available Available Available Available4 2 N.O. Available Available NA Available Available Available Available Available Available6 2 N.O. + 1 N.C. NA NA NA NA NA NA NA NA NA7 2 N.O. + 2 N.C. NA NA NA NA NA NA NA NA NA8 3 N.O. + 2 N.C. NA NA NA NA NA NA NA NA NA
Change option code ➁ to desired auxiliary contact: 103S-AWD2-CA16➁Circuit Breaker Aux / Trip Contacts
ISO Busbar Mount Standard Busbar Mount Panel Mount
Option ➁ Description 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A
X➊ Without Aux / Trip Contacts NA NA NA Available Available Available Available Available Available
A➊ 1 N.C. Aux. NA NA NA Available Available NA Available Available NAB 1 N.O. Aux. Available Available NA Available Available NA Available Available NAC 1 N.O. + 1 N.C. Aux. Standard Standard NA Standard Standard Standard Standard Standard StandardD 2 N.O. Aux. Available Available NA Available Available Available Available Available Available
E➊ 2 N.C. Aux. NA NA NA Available Available Available Available Available Available
R➊ 1 N.O. Trip + 1 N.C. Aux NA NA NA Available Available NA Available Available NAS 1 N.O. Trip + 1 N.O. Aux Available Available NA Available Available NA Available Available NA
➊ Not available when a “-SP” Control Plug is selected.
Add option code ➂ to desired auxiliary contact: 103S-AWD2-CA16C➂Additional Circuit Breaker Aux / Trip ContactsISO Busbar Mount Standard Busbar Mount Panel Mount
Option ➂ Description 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A
Blank Without Aux / Trip Contacts Available Available Available Available Available Available Available Available Available
C➋ 1 N.O. + 1 N.C. Aux. Available Available NA Available Available NA Available Available NA
D➋ 2 N.O. Aux. Available Available NA Available Available NA Available Available NA
E➋ ,➌ 2 N.C. Aux. Available Available NA Available Available NA Available Available NAK 1 N.C. (OL) Trip + 1 N.C. (SC) Trip Available Available NA Available Available Available Available Available AvailableL 1 N.O. (OL) Trip + 1 N.O. (SC) Trip Available Available NA Available Available Available Available Available Available
M➌ 1 N.C. (OL) Trip + 1 N.O. (SC) Trip Available Available NA Available Available Available Available Available Available
N➌ 1 N.O. (OL) Trip + 1 N.C. (SC) Trip Available Available NA Available Available Available Available Available Available
Q➋ 1 N.O. (SC) Trip + 1 N.C. (SC) Trip Available Available NA Available Available NA Available Available NA
➋ Not available on 60…85 A starters.➌ Not available when a “-SP” Control Plug is selected on 60…85 A starters.
Add option code ➃ to desired auxiliary contact: 103S-AWD2-CA16C-➃Modifications / Accessories
Option ➃ Description 9…85 A
JE Electronic Interface AvailableR Surge Suppressor, RC AvailableV Surge Suppressor, Varistor AvailableD Surge Suppressor, Diode Available
KN Lockable Knob, Black AvailableKY Lockable Knob, Red/Yellow AvailableTE Spacing Adapter for UL508 Type E Available
SP Control Plug, Top Mount * See Option ➀
Bulletin 103S/107SCombination Starters
232
Modifications, Continued
107S Factory Installed OptionsChange option code ➀ to desired auxiliary contact: 107S-AWD➀ -CA16C
Contactor Auxiliaries without “-SP” Control PlugISO Busbar Mount Standard Busbar Mount Panel Mount
Option ➀ Description 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A
3 1 N.O. + 1 N.C. NA NA NA Standard Standard Standard Standard Standard Standard7 2 N.O. + 2 N.C. NA NA NA Available Available Available Available Available Available
Change option code ➀ to desired auxiliary contact: 107S-AWD➀ -CA16C
Contactor Auxiliaries with “-SP” Control PlugISO Busbar Mount Standard Busbar Mount Panel Mount
Option ➀ Description 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A
3 1 N.O. + 1 N.C. Standard Standard NA Available Available Available Available Available Available7 2 N.O. + 2 N.C. Available Available NA Available Available Available Available Available Available
Change option code ➁ to desired auxiliary contact: 107S-AWD3-CA16➁Circuit Breaker Aux / Trip Contacts
ISO Busbar Mount Standard Busbar Mount Panel Mount
Option ➁ Description 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A
X➊ Without Aux / Trip Contacts NA NA NA Available Available Available Available Available Available
A➊ 1 N.C. Aux. NA NA NA Available Available NA Available Available NAB 1 N.O. Aux. Available Available NA Available Available NA Available Available NAC 1 N.O. + 1 N.C. Aux. Standard Standard NA Standard Standard Standard Standard Standard StandardD 2 N.O. Aux. Available Available NA Available Available Available Available Available Available
E➊ 2 N.C. Aux. NA NA NA Available Available Available Available Available Available
R➊ 1 N.O. Trip + 1 N.C. Aux NA NA NA Available Available NA Available Available NAS 1 N.O. Trip + 1 N.O. Aux Available Available NA Available Available NA Available Available NA
➊ Not available when a "-SP" Control Plug is selected.
Add option code ➂ to desired auxiliary contact: 107S-AWD3-CA16C➂Additional Circuit Breaker Aux / Trip ContactsISO Busbar Mount Standard Busbar Mount Panel Mount
Option ➂ Description 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A 9…23 A 30…43 A 60…85 A
Blank Without Aux / Trip Contacts Available Available Available Available Available Available Available Available Available
C➋ 1 N.O. + 1 N.C. Aux. Available Available NA Available Available NA Available Available NA
D➋ 2 N.O. Aux. Available Available NA Available Available NA Available Available NA
E➋ ,➌ 2 N.C. Aux. Available Available NA Available Available NA Available Available NAK 1 N.C. (OL) Trip + 1 N.C. (SC) Trip Available Available NA Available Available Available Available Available AvailableL 1 N.O. (OL) Trip + 1 N.O. (SC) Trip Available Available NA Available Available Available Available Available Available
M➌ 1 N.C. (OL) Trip + 1 N.O. (SC) Trip Available Available NA Available Available Available Available Available Available
N➌ 1 N.O. (OL) Trip + 1 N.C. (SC) Trip Available Available NA Available Available Available Available Available Available
Q➋ 1 N.O. (SC) Trip + 1 N.C. (SC) Trip Available Available NA Available Available NA Available Available NA
➋ Not available on 60…85 A starters.
➌ Not available when a “-SP” Control Plug is selected on 60…85 A starters.
Add option code ➃ to desired auxiliary contact: 107S-AWD3-CA16C-➃Modifications / Accessories
Option ➃ Description 9…85 A
JE Electronic Interface AvailableR Surge Suppressor, RC AvailableV Surge Suppressor, Varistor AvailableD Surge Suppressor, Diode Available
KN Lockable Knob, Black AvailableKY Lockable Knob, Red/Yellow AvailableTE Spacing Adapter for UL508 Type E Available
SP Control Plug, Top Mount * See Option ➀
233
Bulletin 103S/107SCombination Starters
Coil Voltage Codes
⊗ Coil Voltage Codes for AC Control The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: 120V 60 Hz: Cat. No. 103S-AT⊗ 2-CA16C becomes Cat. No. 103S-ATD2-CA16C.
⊗ Coil Voltage Codes for DC ControlThe Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: 120V 60 Hz: Cat. No. 103S-AT⊗ 2-CA16C becomes Cat. No. 103S-ATZR2-CA16C.
Coil Voltages 12 24 32 36 42 48 100 100-
110 110 120 127 200 200-220 208 208-
240220-230 230 230-
240 240 277 347 380 380-400 400 400-
415 440 480 500 550 600
50 Hz R K V W X Y KP — D P S KG L — — F — VA T — — — N — G B — M C —60 Hz Q J — V — X — KP — D — — KG H L — — — A T I E — — — N B — — C
50/60 Hz — KJ — — — KY KP — KD — — KG KL — — KL KF — KA — — — — KN — KB — — — —
DC Voltages 9 12 24 36 48 60 64 72 80 110 115 125 220 230 250
103S-C09…C43Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode — — DJ — — — — — — — — — — — —107S-C60…C85 with Integrated Diode DR DQ DJ DW DY DZ DB DG DE DD DP DS DA DF DT
=
Bulletin 103S/107SIEC Combination Starters
234
Specifications
UL Listed Application Ratings
Index
Motor Current
Adjustment Range (A)
Magnetic Release
Operating Current (A)
Maximum Hp, 60 Hz Max. Fault Current 480Y/277V
Max. Fault Current 600Y/347V Group Installation
200V 230V 460V 575VType 1Iq [kA]
Type 2Iq [kA]
Type EIq [kA]
Type 1Iq [kA]
Type 2Iq [kA]
Type EIq [kA]
480Y/277V Iq [kA]
600Y/347V Iq [kA]
Max. Fuse or CB per
NEC[kA]
C Frame1 0.10…0.16 2.1 — — — — 65 65 65 47 47 47 65 47 4502 0.16…0.25 3.3 — — — — 65 65 65 47 47 47 65 47 4503 0.25…0.40 5.2 — — — — 65 65 65 47 47 47 65 47 4504 0.40…0.63 8.2 — — — — 65 65 65 47 47 47 65 47 4505 0.63…1.0 13 — — 1/2 3/4 65 65 65 47 47 47 65 47 4506 1.0…1.6 21 — — 1 1 65 65 65 47 47 47 65 47 4507 1.6…2.5 33 1/2 3/4 1-1/2 2 65 65 65 30 30 — 65 30 4508 2.5…4.0 52 1 1 3 3 65 — — 30 — — 65 30 4509 4.0…6.3 82 1-1/2 2 5 5 65 — — — — — 65 30 45010 6.3…10 130 3 3 7-1/2 10 65 — — — — — 65 25 45011 10…16 208 3 5 10 15 30 — — — — — 30 25 45012 14.5…20 260 5 7-1/2 15 15 10 — — — — — 30 30 45013 18…25 325 5 7-1/2 15 15 — — — — — — 10 10 450
D Frame14 1.6…2.5 33 1/2 3/4 1-1/2 2 65 65 65 30 — — 65 30 45015 1.6…2.5 33 1/2 3/4 1-1/2 2 65 65 65 30 30 30 65 30 45016 2.5…4.0 52 1 1 3 3 65 65 — 30 — — 65 30 45017 2.5…4.0 52 1 1 3 3 65 65 65 30 30 30 65 30 45018 4.0…6.3 82 1-1/2 2 5 5 65 65 — 30 — — 65 30 45019 4.0…6.3 82 1-1/2 2 5 5 65 65 65 30 30 30 65 30 45020 6.3…10 130 3 3 7-1/2 10 65 65 — 30 — — 65 30 45021 6.3…10 130 3 3 7-1/2 10 65 65 65 30 30 30 65 30 45022 10…16 208 3 5 10 15 65 65 — 30 — — 65 30 45023 10…16 208 3 5 10 15 65 65 65 30 30 30 65 30 45024 14.5…20 260 5 7-1/2 15 15 65 65 — — — — 65 — 45025 14.5…20 260 5 7-1/2 15 20 65 65 65 — — 30 65 — 45026 18…25 325 5 7-1/2 15 15 65 65 — — — — 65 — 45027 18…25 325 7-1/2 7-1/2 15 20 65 65 65 — — 30 65 — 450
F Frame28 6.3…10 130 3 3 7-1/2 10 65 65 65 30 30 30 65 30 60029 10…16 208 3 5 10 15 65 65 65 30 30 30 65 30 60030 14.5…20 260 5 7-1/2 15 20 65 65 65 30 30 30 65 30 60031 18…25 325 7-1/2 10 20 25 65 65 65 30 30 30 65 30 60032 25…32 416 10 10 25 30 65 65 65 30 30 30 65 30 60033 32…45 585 10 15 30 30 65 65 65 30 30 — 65 30 600
CMN Frame ➊34 40…63 882 15 20 40 50 — — — — — — 42 18 100035 40…63 882 20 20 50 60 — — — — — — 42 18 100036 63…90 1260 20 25 50 60 — — — — — — 35 10 100037 63…90 1260 25 30 60 60 — — — — — — 35 10 1000
235
Bulletin 103S/107SCombination Starters
Accessories
Auxiliary Contacts for Contactors (100-C09…C85)
➊ Up to 8 auxiliary contacts may be mountedAC coil contactors — max. 4 N.O. contacts on the front of the contactor and max. 2 N.O. contacts on the side.DC coil contactors — max. 4 N.O. contacts on the front of the contactor or max. 2 N.O. contacts on the side.
➋ Double Numbering — Left-side mounting only is recommended for Cat. No. 100-C09…100-C23 due to double numbering.
Coil Accessories (For 100-C09…C85 Contactors)
➌ Not suitable for use with 103T and 107T 3-component combination starters.
DescriptionN.O. N.C.
Connection Diagrams For Use With Cat. No.
Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations ➊• 1- and 2-pole• Two-way numbering for right or left
mounting on the contactor• Quick and easy mounting without tools• Electronic compatible contacts down to
17V, 5 mA• Mutual positive guidance to the main
contactor poles (except for L types)L = Late break/Early make
0 1 100-C all 100-SB01
1 0 100-C ➋ 100-SB10
0 2 100-C ➋ 100-SB02
1 1 100-C ➋ 100-SB11
2 0 100-C ➋ 100-SB20
L1 L1 100-C ➋ 100-SBL11
Description Connection Diagrams For Use With Cat. No. ➌
Electronic Timing ModulesDelay of the contactor solenoid
100-ETA ON-Delay The contactor is energized at the end of the delay time.
ON-Delay0.1…3 s1…30 s10…180 s
110…240V,50/60 Hz110…250VDC
100-C all 100-ETA3100-ETA30100-ETA180
ON-Delay0.1…3 s1…30 s10…180 s
24V DC
100-C with DC coils
100-ETAZJ3100-ETAZJ30100-ETAZJ180
OFF-Delay0.3…3 s1…30 s10…180 s
24V50/60 Hz
100-C09…C37 with
AC coils
100-ETBKJ3100-ETBKJ30100-ETBKJ180
100-ETB OFF-Delay After interruption of the control signal, the contactor is de-energized at the end of the delay time.
OFF-Delay0.3…3 s1…30 s10…180 s
110…240V50/60 Hz
100-C with AC coils
100-ETB3100-ETB30100-ETB180
100-ETY Contactor K 3 (Y) is de-energized (off) and K 2 (D) is energized (on) after the end of the set Y end time. (Switching delay at 90 ms).• Continuous adjustment range• High repeat accuracy
Transition Time Y Contactor
1…30 s
110…240V50/60 Hz
100-C with AC coils 100-ETY30
-SB01 -SB10
-SB02 -SB11
-SB20 -SBL11
(K1M)
K1M
(K1M)
K1M
(K1M)
K1M
Bulletin 103S/107SCombination Starters
236
Accessories, Continued
Coil Accessories (For 100-C09…C85 Contactors), Continued
⊗ Voltage Suffix CodeThe Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: 120V, 60 Hz: Cat. No. 100-FL11⊗ becomes Cat. No. 100-FL11D.
➊ For special voltages, cosult your local Allen-Bradley distributor.
Assembly Components➌ Use Discount Schedule A1.
Description Connection Diagrams For Use With Cat. No.DC Interface (electronic)Interface between the DC control signal (PLC) and the AC operating mechanism of the contactor. Requires no additional surge suppression on the contactor coils.• Control (input) voltage
100-C with AC coils 110…240V AC
12V DC18…30V DC (24V DC nominal)48V DC
100-JE12100-JE
100-JE48
Surge SuppressorsFor limitation of coil switching transients.• Plug-in, coil mounted• Suitable for all 100-C
contactor sizes, 9…85 A• RC, Varistor and Diode
Versions
RC ModuleAC Operating Mechanism
24…48V 50/60 Hz
100-C with AC coils
100-FSC48
110…280V50/60 Hz 100-FSC280
380…480V50/60 Hz 100-FSC480
Varistor ModuleAC/DC Operating Mechanism
12…55V AC /12…77V DC
100-C all
100-FSV55
56…136V AC /78…180V DC 100-FSV136
137…277V AC /181…350V DC 100-FSV277
278…575V AC 100-FSV575
Diode Module DC Operating Mechanism
12…250V DC 100-C with DC coils 100-FSD250
Voltage ➊ 24 48 100 110 120 230…240 240 277 380…400 400…415 440 48050 Hz K Y KP D — VA T — N G B —60 Hz J — — — D — A T — — N B
Description For Use With Pkg. Qty. Cat. No.
Protective Covers• Provides protection against unintended manual operation• For contactors and front mounted auxiliary contacts, pneumatic
timers and latches
100-C all 1 100-SCCA
100-FA, FB, FC, FP, FL 10 100-SCFA
K1M
(K1M)
Cat. No. 100-SCCA
Cat. No. 100-SCFA
237
Bulletin 103S/107SCombination Starters
Accessories, Continued
Auxiliary Contacts for Motor Protection Circuit Breakers (140M-C, -D, -F)
➊ X = Contact ClosedO = Contact Open
➋
Description
Connection Diagram ➋For Use
With Cat. No.
Operator Position ➊
Term. No. Description
OFF ON Tripped
Front-Mounted Auxiliary Contact• 1-pole or 2-pole• No additional space
required
O X O 13-14 N.O. Aux 140M 140M-C-AFA10
X O X 11-12 N.C. Aux 140M 140M-C-AFA01
O X O 13-14 N.O. Aux
140M 140M-C-AFA11
X O X 21-22 N.C. Aux
O X O 13-14 N.O. Aux
140M 140M-C-AFA20
O X O 23-24 N.O. Aux
X O X 11-12 N.C. Aux
140M 140M-C-AFA02
X O X 21-22 N.C. Aux
Front-MountedTrip Contact• 2-pole• Indicates tripping of
device• No additional space
required
O X O 13-14 N.O. Aux
140M 140M-C-AFAR10A10
O O X 27-28N.O. Trip
(Short-Circuit & Overload)
X O X 11-12 N.C. Aux
140M 140M-C-AFAR10A01
O O X 27-28N.O. Trip
(Short-Circuit & Overload)
I >>
13
14
I >>
11
12
13
14
21
22
I >>
I >>
13
14
23
24
I >>
11
12
21
22
13 27
14I >>
28
11
12I >>
27
28
I >>
140 M Operator
Overload (thermal) TripShort-Circuit (magnetic) Trip
Bulletin 103S/107SCombination Starters
238
Accessories, Continued
Auxiliary Contacts for Motor Protection Circuit Breakers (140M-C, -D, -F)
➊ X = Contact ClosedO = Contact Open
➋
Description
Connection Diagram ➋For Use
With Cat. No.
Operator Position ➊
Term. No. Description
OFF ON Tripped
Front-Mounted Auxiliary Contacts• Internal• 2-Pole
O X O 13-14 N.O. Aux
140-CMN
140-CA20
O X O 23-24 N.O. Aux
X O X 11-12 N.C. Aux
140-CA02
X O X 21-22 N.C. Aux
O X O 13-14 N.O. Aux
140-CA11
X O X 21-22 N.C. Aux
Front-MountedTrip Indicating Auxiliary Contacts• Internal• 2-Pole
O O X 37-38 N.O. Trip(Overload)
140-CMN
140-CT10-10
O O X 43-44 N.O. Trip(Short-Circuit)
X X O 35-36 N.C. Trip(Overload)
140-CT01-01
X X O 41-42 N.C. Trip(Short-Circuit)
X X O 35-36 N.C. Trip(Overload)
140-CT01-10
O O X 43-44 N.O. Trip(Short-Circuit)
O O X 37-38 N.O. Trip(Overload)
140-CT10-01
X X O 41-42 N.C. Trip(Short-Circuit)
13
14
23
24
I >>
140-CMN
140-CA20
I >>
21
22
11
12
140-CMN
140-CA02
I >>
13
14
21
22
140-CMN
140-CA11
37
38
43
44
I >>
140-CMN
140-CT10-10
a
b
a) Overload Tripb) Short-Circuit Trip
I >>
41
42
35
36
140-CMN
140-CT01-01
a
b
a) Overload Tripb) Short-Circuit Trip
I >>
35
36
43
44
140-CMN
140-CT01-10
a
b
a) Overload Tripb) Short-Circuit Trip
I >>
37
38
41
42
140-CMN
140-CT10-01
a
b
a) Overload Tripb) Short-Circuit Trip
I >>
140 M Operator
Overload (thermal) TripShort-Circuit (magnetic) Trip
239
Bulletin 103S/107SCombination Starters
Accessories
Auxiliary Contacts for Motor Protection Circuit Breakers (140M-C, -D, -F)
➊ X = Contact ClosedO = Contact Open
➋
Description
Connection Diagram ➋For Use
With Cat. No.
Operator Position ➊
Term. No. Desc.
OFF ON Tripped
Right Side-Mounted Auxiliary Contact• 2-pole• Adds 9 mm to the
width of the device
O X O 33-34 N.O. Aux
140M 140M-C-ASA20
O X O 43-44 N.O. Aux
X O X 31-32 N.C. Aux
140M 140M-C-ASA02
X O X 41-42 N.C. Aux
O X O 33-34 N.O. Aux
140M 140M-C-ASA11
X O X 41-42 N.C. Aux
Right Side-Mounted Trip Contact• 2-pole• Indicates tripping of
Motor Protector• Adds 9 mm to the
width of the circuit breaker
O O X 57-58N.O. Trip
(Short-Circuit & Overload)
140M 140M-C-ASAR10M10
O O X 67-68 N.O. Trip(Short-Circuit)
O O X 57-58N.O. Trip
(Short-Circuit & Overload)
140M 140M-C-ASAR10M01
X X O 65-66 N.C. Trip(Short-Circuit)
X X O 55-56N.C. Trip
(Short-Circuit & Overload)
140M 140M-C-ASAR01M10
O O X 67-68 N.O. Trip(Short-Circuit)
X X O 55-56N.C. Trip
(Short-Circuit & Overload)
140M 140M-C-ASAR01M01
X X O 65-66 N.C. Trip(Short-Circuit)
O O X 77-78 N.O. Trip(Short-Circuit)
140M 140M-C-ASAM11X X O 65-66 N.C. Trip
(Short-Circuit)
I >>
33
34
43
44
I >>
31
32
41
42
33
34
41
42
I >>
57
58
67
68
I >>
I >>
57
58
65
66
I >>
55
56
67
68
I >>
65
66
55
56
I >>
77
78
65
66
I >>
140 M Operator
Overload (thermal) TripShort-Circuit (magnetic) Trip
Bulletin 103S/107SCombination Starters
240
Accessories, Continued
Accessories for Motor Protection Circuit Breakers (140M-C, -D, -F)
Description Connection Diagram For Use With Cat. No.
Undervoltage Trip• Left-side mounted• Adds 18 mm to the width of
the circuit breaker• Trips motor protector when
voltage is removed
24V, 60 Hz24V, 50 Hz
120V, 60 Hz110V, 50 Hz
220…230V, 50 Hz240…260V, 60 Hz
277V, 60 Hz380…400V, 50 Hz
480V, 60 Hz/415V, 50 Hz600V, 60 Hz
575V, 60 Hz/500V, 50 Hz
140M
140M-C-UXJ140M-C-UXK140M-C-UXD140M-C-UXC140M-C-UXF140M-C-UXA140M-C-UXT140M-C-UXN140M-C-UXB
140M-C-UXUB140M-C-UXM
Shunt Trip• Left-side mounted• Adds 18 mm to the width of
the circuit breaker• Trips motor protector when
voltage is applied
24V, 60 Hz24V, 50 Hz
120V, 60 Hz110V, 50 Hz
220…230V, 50 Hz240…260V, 60 Hz
277V, 60 Hz380…400V, 50 Hz
480V, 60 Hz/415V, 50 Hz600V, 60 Hz
575V, 60 Hz/500V, 50 Hz
140M
140M-C-SNJ140M-C-SNK140M-C-SND140M-C-SNC140M-C-SNF140M-C-SNA140M-C-SNT140M-C-SNN140M-C-SNB
140M-C-SNUB140M-C-SNM
Description For Use With Cat. No.
Anti Tamper Shield• Provides protection against inadvertent adjustment of the current setting on the
140M-C, -D, and -F MPCBs140M 140M-C-CA
Lockable Twist Knob• For 1 padlock 4…8 mm (5/16") dia. shackle• Can be locked in OFF position
black 140M 140M-C-KN
red/yellow 140M-C/-D 140M-C-KRY
red/yellow 140M-F 140M-F-KRY
Padlockable Operating Knob• Accepts 8mm (5/16") padlock — up to three padlocks.• Permits padlocking in the off position.
black
140-CMN
140-KN
red/yellow 140-KRY
D1
D2I >>
U <
C1
C2I >>
241
Bulletin 103S/107SIEC Compact Combination Starters
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Standard and ISO Busbar MountBulletin 103S Non-Reversing Starters
34 (
b)39
(c)
6060
205.
5 (b
) /
210
.5 (
c)
236.
5 (
b) /
241
.5 (
c)45
12...
30
Circuit Breaker: 140M-C / -DContactor: 100-C09...23
(a) With additional side-mount aux. or trip contact(s)(b) Standard busbar mount with control plug(c) Iso busbar mount(d) Electronic interface
9 (d
)
31
97.5
97.5
65 (
b) /
70
(c)
54 (a)
Reference Print: D00GMD
31
97.5
97.5
65 (
b) /
70
(c)
34 (
b)39
(c)
6060
205.
5 (b
) /
210
.5 (
c)
236.
5 (
b) /
241
.5 (
c)
54
12...
30
Circuit Breaker: 140M-DContactor: 100-C30...37
(b) Standard busbar mount with control plug(c) Iso busbar mount(d) Electronic interface
9 (d
)
Reference Print: D10GMD
Bulletin 103S Busbar Mount
Bulletin 103S Busbar Mount
Bulletin 103S/107SIEC Compact Combination Starters
242
Approximate Dimensions, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Standard and ISO Busbar Mount, ContinuedBulletin 103S Non-Reversing Starters, Continued
34 (
b)39
(c)
6060
213
(b)
/ 2
18 (
c)
244
(b)
/ 2
49 (
c)
54
12...
30
Circuit Breaker: 140M-FContactor: 100-C30...37
(a) With additional side-mount aux. or trip contact(b) Standard busbar mount with control plug(c) Iso busbar mount(d) Electronic interface
9 (d
)
31
105
65 (
b) /
70
(c)
63 (a)
Reference Print: D10GMF
34 (
b)39
(c)
6060
213
(b)
/ 2
18 (
c)
244
(b)
/ 2
49 (
c)
63
12...
30
Circuit Breaker: 140M-FContactor: 100-C43
(b) Standard busbar mount with control plug(c) Iso busbar mount(d) Electronic interface
9 (d
)
31
105
65 (
b) /
70
(c)
Reference Print: D20GMF
Bulletin 103S Busbar Mount
Bulletin 103S Busbar Mount
243
Bulletin 103S/107SIEC Compact Combination Starters
Approximate Dimensions, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Standard and ISO Busbar Mount, ContinuedBulletin 103S Non-Reversing Starters, Continued
3431
6060
200 23
1 (
b)
180
12...
30
Circuit Breaker: 140-CMNContactor: 100-C60...85 (b) Standard busbar mount with control plug
105
Reference Print: D30GCM
3431
6060
200 23
1 (
b)
144
12...
30
Circuit Breaker: 140M-FContactor: 100-C60...85
(b) Standard busbar mount with control plug
105
65
Reference Print: D30GMF
Bulletin 103S Busbar Mount
Bulletin 103S Busbar Mount
Bulletin 103S/107SIEC Compact Combination Starters
244
Approximate Dimensions, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Standard and ISO Busbar Mount, ContinuedBulletin 107S Reversing Starters
34 (
b)39
(c)
6060
205.
5 (b
) /
210
.5 (
c)
236.
5 (
b) /
241
.5 (
c)
99
117 (a)
12...
30
Circuit Breaker: 140M-DContactors: 100-C09...23
(a) With additional side-mount aux. contacts(b) Standard busbar mount with control plug(c) Iso busbar mount(d) Electronic interfaces
9 (d
)
31
97.5
97.5
65 (
b) /
70
(c)
Reference Print: R00GMD
99
117 (a)
Circuit Breaker: 140M-DContactors: 100-C30...37
(a) With additional side-mount aux. contacts(b) Standard busbar mount with control plug(c) Iso busbar mount(d) Electronic interface
97.5
236.
5 (b
) /
241.
5 (c
)
205.
5 (b
) /
210.
5 (c
)
65 (b
) /
70 (c
)97
.5
12...
3034
(b)
39 (c
)60
6031
9 (d
)
Reference Print: R10GMD
Bulletin 107S Busbar Mount
Bulletin 107S Busbar Mount
245
Bulletin 103S/107SIEC Compact Combination Starters
Approximate Dimensions, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Standard and ISO Busbar Mount, ContinuedBulletin 107S Reversing Starters, Continued
213
(b)
/ 2
18 (
c)
244
(b)
/ 2
49 (
c)
99
117 (a)
Circuit Breaker: 140M-FContactors: 100-C30...37
(a) With additional side-mount aux. contacts(b) Standard busbar mount with control plug(c) Iso busbar mount(d) Electronic interface
9 (d
)
12...
3034
(b)
39 (
c)60
6031
105
65 (
b) /
70
(c)
Reference Print: R10GMF
117
135 (a)
Circuit Breaker: 140M-FContactors: 100-C43
(a) With additional side-mount aux. contacts(b) Standard busbar mount with control plug(c) Iso busbar mount(d) Electronic interface
9 (d
)
12...
3034
(b)
39 (
c)60
6031
244
(b)
/ 2
49 (
c)
213
(b)
/ 2
18 (
c)
65 (
b) /
70
(c)
105
Reference Print: R20GMF
Bulletin 107S Busbar Mount
Bulletin 107S Busbar Mount
Bulletin 103S/107SIEC Compact Combination Starters
246
Approximate Dimensions, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Standard and ISO Busbar Mount, ContinuedBulletin 107S Reversing Starters, Continued
34
31
60
60
20
0 23
1
(b)
252
261 (a)
12...3
0
Circuit Breaker: 140-CMNContactors: 100-C60...85
(a) With additional side-mount aux. contacts(b) Standard busbar mount with control plug
10
5
Reference Print: R30GCM
3431
6060
200 23
1 (
b)
225
234 (a)
12...
30
Circuit Breaker: 140M-FContactors: 100-C60...85
(a) With additional side-mount aux. contacts(b) Standard busbar adapter with control plug
105
65
Reference Print: R30GMF
Bulletin 107S Busbar Mount
Bulletin 107S Busbar Mount
247
Bulletin 103S/107SIEC Compact Combination Starters
Approximate Dimensions, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Panel Mount, ContinuedBulletin 103S Non-Reversing Starters
64
31 (
b)
125
228
54 (a)
Circuit Breaker: 140M-C/DContactor: 100-C09...23
(a) With additional side-mount aux. or trip contact(s)(b) Control plug on top OR bottom side optional
31 (
b)
210
35
6997
.5
45
40 (a)
Reference Print: D00WMD
6997
.5
64
31 (
b)
125
228
54
Circuit Breaker: 140M-DContactor: 100-C30...37 (b) Control plug on top OR bottom side optional
31 (
b)
210
40
Reference Print: D10WMD
Bulletin 103S Panel Mount
Bulletin 103S Panel Mount
Bulletin 103S/107SIEC Compact Combination Starters
248
Approximate Dimensions, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Panel Mount, ContinuedBulletin 103S Non-Reversing Starters, Continued
6910
5
64
31 (
b)
125
228
54
Circuit Breaker: 140M-FContactor: 100-C30...37
(a) With additional side-mount aux. or trip contact(b) Control plug on top OR bottom side optional
31 (
b)
210
40
Reference Print: D10WMF
6910
5
64
31 (
b)
125
228
63
Circuit Breaker: 140M-FContactor: 100-C43
(a) With additional side-mount aux. or trip contact(b) Control plug on top OR bottom side optional
31 (
b)
210
40
Reference Print: D20WMF
Bulletin 103S Panel Mount
Bulletin 103S Panel Mount
249
Bulletin 103S/107SIEC Compact Combination Starters
Approximate Dimensions, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Panel Mount, ContinuedBulletin 107S Reversing Starters
31 (
b)
210
87
6997
.5
64
31 (
b)
125
228
99
117 (a)
Circuit Breaker: 140M-C/DContactors: 100-C09...23
(a) With additional side-mount aux. contacts(b) Control plug on top OR bottom side optional
Reference Print: R00WMD
64
31 (
b)
125
228
99
117 (a)
Circuit Breaker: 140M-DContactors: 100-C30...37
(a) With additional side-mount aux. contacts(b) Control plug on top OR bottom side optional
31 (
b)
210
87
6997
.5
Reference Print: R10WMD
Bulletin 107S Panel Mount
Bulletin 107S Panel Mount
Bulletin 103S/107SIEC Compact Combination Starters
250
Approximate Dimensions, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Panel Mount, ContinuedBulletin 107S Reversing Starters, Continued
64
31 (
b)
125
228
99
117 (a)
Circuit Breaker: 140M-FContactors: 100-C30...37
(a) With additional side-mount aux. contacts(b) Control plug on top OR bottom side optional
31 (
b)
210
87
6910
5
Reference Print: R10WMF
64
31 (
b)
125
228
117
135 (a)
Circuit Breaker: 140M-FContactors: 100-C43
(a) With additional side-mount aux. contacts(b) Control plug on top OR bottom side optional
31 (
b)
210
103
6910
5
Reference Print: R20WMF
Bulletin 107S Panel Mount Bulletin 107S Panel Mount
251
Bulletin 103H/107H/140MIEC Enclosed Starters
Overview/Product Selection
Bulletin 103H/107H/140M Enclosed IEC Starters Table of ContentsProduct Selection
Reversing and Non-reversing Starters.......................... 252
Accessories .......................254Modifications .....................258Wiring Diagrams................259Enclosure Dimensions......261
Conformity to StandardsUL 489CSA 22.2 No. 5IEC 60947-2
ApprovalsUL ListedCSA CertifiedCEKEMA-KEUR
Bulletin 103H starter in enclosure size A
Bulletin 107H starter in enclosure size C
The "A" sixe box accomodates:-103H Non-Reversing Starters-Motors up to 15 Hp/480V (23 A)-2 pilot devices
The "B" sixe box accomodates:-103H Non-Reversing Starters AND 107H Reversing Starters-Motors up to 15 Hp/480V (23 A)-Control Transformer and 3 pilot devices
The "C" sixe box accomodates:-103H Non-Reversing Starters AND 107H Reversing Starters-Motors up to 30 Hp/480V (43 A)-Control Transformer and 3 pilot devices
Bulletin 103H/107H/140MIEC Enclosed Starters
252
Product Selection — 3-pole AC Contactors
• 65 kA at 480V• 30 kA at 600V• Type 2 coordination is standard for all voltages, except where noted for 575V starters
➊ 25 kA.➋ For Type 2 Coordination, change the Cat. No. to 103H-CF⊗ 2-DB40X.➌ For Type 2 Coordination, change the Cat. No. to 103H-DF⊗ 2-DB63X.➍ For Type 2 Coordination, change the Cat. No. to 103H-EF⊗ 2-DC10X.➎ For Type 2 Coordination, change the Cat. No. to 103H-EF⊗ 2-DC16X.
Line Voltage Codes — see page 258
⊗ Coil Voltage Codes — see page 258
Rated Operational
Current Ie (A)
Motor Current Adjustment Range (A)
Magnetic Trip
Current (A)
Maximum Hp, 3-phaseNon-Reversing Starter
Cat. No.Enclosure
SizeReversing Starter Cat.
No.Enclosure
Size200V 230V 460V 575V
25 A Frame Size0.16 0.10…0.16 2.1 — — — — 103S-AF ⊗ 2-CA16X A 107H-AF ⊗ 3-CA16X B0.25 0.16…0.25 3.3 — — — — 103H-AF ⊗ 2-CA25X A 107H-AF ⊗ 3-CA25X B0.40 0.25…0.40 5.2 — — — — 103H-AF ⊗ 2-CA40X A 107H-AF ⊗ 3-CA40X B0.63 0.40…0.63 8.2 — — — — 103H-AF ⊗ 2-CA63X A 107H-AF ⊗ 3-CA63X B1.0 0.63…1.0 13 — — 0.5 0.5 103H-AF ⊗ 2-CB10X A 107H-AF ⊗ 3-CB10X B1.6 1.0…1.6 21 — — 0.75 0.75 103H-AF ⊗ 2-CB16X A 107H-AF ⊗ 3-CB16X B2.5 1.6…2.5 33 0.5 0.5 1 1.5 103H-AF ⊗ 2-DB25X A 107H-AF ⊗ 3-DB25X B4.0 2.5…4.0 52 0.75 0.75 2 3 ➋ 103H-AF ⊗ 2-DB40X A 107H-AF ⊗ 3-DB40X B6.3 4.0…6.3 82 1.5 1.5 3 5 ➌ 103H-AF ⊗ 2-DB63X A 107H-AF ⊗ 3-DB63X B10 6.3…10 130 2 3 5 7.5 ➍ 103H-BF ⊗ 2-DC10X A 107H-BF ⊗ 3-DC10X B16 10…16 208 3 5 10 10 ➎ 103H-CF ⊗ 2-DC16X A 107H-CF ⊗ 3-DC16X B20 14.5…20 260 5 5 15 15 103H-DF ⊗ 2-DC20X A 107H-DF ⊗ 3-DC20X B25 18…25 325 5 7.5 15 ➊ 15 103H-DF ⊗ 2-DC25X A 107H-DF ⊗ 3-DC25X B
45 A Frame Size10 6.3…10 130 3 3 7.5 10 103H-EF ⊗ 2-FC10X C 107H-EF ⊗ 3-FC10X C16 10…16 208 3 5 10 10 103H-EF ⊗ 2-FC16X C 107H-EF ⊗ 3-FC16X C20 14.5…20 260 5 7.5 15 20 103H-EF ⊗ 2-FC20X C 107H-EF ⊗ 3-FC20X C25 18…25 325 5 10 20 20 103H-EF ⊗ 2-FC25X C 107H-EF ⊗ 3-FC25X C32 23…32 416 10 10 25 25 103H-FF ⊗ 2-FC32X C 107H-FF ⊗ 3-FC32X C45 32…45 585 10 15 30 30 103H-GF ⊗ 2-FC45X C 107H-GF ⊗ 3-FC45X C
253
Bulletin 103H/107H/140MIEC Enclosed StartersProduct Selection, Continued
➊ 25 kA
Rated Operational Current Ie (A)
Motor Current Adjustment Range (A)
Magnetic Trip Current (A)
Maximum Hp, 3-phaseCat. No. Enclosure
Size200V 230V 460V 575V
25 A Frame Size0.16 0.10…0.16 2.1 — — — — 140M-F-CA16X A0.25 0.16…0.25 3.3 — — — — 140M-F-CA25X A0.40 0.25…0.40 5.2 — — — — 140M-F-CA40X A0.63 0.40…0.63 8.2 — — — — 140M-F-CA63X A1.0 0.63…1.0 13 — — 0.5 0.75 140M-F-CB10X A1.6 1.0…1.6 21 — — 1 1 140M-F-CB16X A2.5 1.6…2.5 33 0.5 0.75 1.5 2 140M-F-DB25X A4.0 2.5…4.0 52 1 1 3 3 140M-F-DB40X A6.3 4.0…6.3 82 1.5 2 5 5 140M-F-DB63X A10 6.3…10 130 3 3 7.5 10 140M-F-DC10X A16 10…16 208 3 5 10 15 140M-F-DC16X A20 14.5…20 260 5 7.5 15 20 140M-F-DC20X A25 18…25 325 7.5 7.5 15 ➊ 20 140M-F-DC25X A
45 A Frame Size10 6.3…10 130 3 3 7.5 10 140M-F-FC10X A16 10…16 208 3 5 10 15 140M-F-FC16X A20 14.5…20 260 5 7.5 15 20 140M-F-FC20X A25 18…25 325 7.5 10 20 25 140M-F-FC25X A32 23…32 416 10 10 25 30 140M-F-FC32X A45 32…45 585 15 15 30 40 140M-F-FC45X A
Enclosed Motor Protectors• 65 kA at 480V• 30 kA at 600V
Bulletin 103H/107H/140MIEC Enclosed Starters
254
Accessories
Auxiliary Contacts for Contactors (100-C09…C85)
➊ Up to 8 auxiliary contacts may be mounted (max. 4 N.O. contacts or 6 N.C. and max. 2 N.O. contacts on the side.)➋ Double Numbering — Left-side mounting only is recommended for Cat. No. 100-C09…100-C23 due to double numbering.
Coil Accessories (For 100-C09…C85 Contactors)
➊ May be used with DC coils if no side mounted auxiliary contacts are used.
DescriptionN.O. N.C.
Connection Diagrams For Use With Cat. No.
Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations ➊• 1- and 2-pole• Two-way numbering for right or left
mounting on the contactor• Quick and easy mounting without tools• Electronic compatible contacts down to
17V, 5mA• Mutual positive guidance to the main
contactor poles (except for L types)L = Late break/Early make
0 1 100-C all 100-SB01
1 0 100-C ➋ 100-SB10
0 2 100-C ➋ 100-SB02
1 1 100-C ➋ 100-SB11
2 0 100-C ➋ 100-SB20
L1 L1 100-C ➋ 100-SBL11
Description Connection Diagrams For Use With Cat. No.
Electronic Timing ModulesDelay of the contactor solenoid
100-ETA ON-Delay The contactor is energized at the end of the delay time.
ON-Delay0.1…3 s1…30 s10…180 s
110…240V,50/60 Hz110…250V DC
100-C all 100-ETA3100-ETA30100-ETA180
ON-Delay0.1…3 s1…30 s10…180 s
24V DC
100-C with DC coils
100-ETAZJ3100-ETAZJ30
100-ETAZJ180
OFF-Delay0.3…3 s1…30 s10…180 s
24V50/60 Hz
100-C09…C37 with
AC coils
100-ETBKJ3100-ETBKJ30100-ETBKJ180
100-ETB OFF-Delay After interruption of the control signal, the contactor is de-energized at the end of the delay time.
OFF-Delay0.3…3 s1…30 s10…180 s
110…240V50/60 Hz
100-C with AC coils
100-ETB3100-ETB30100-ETB180
100-ETY Contactor K 3 (Y) is de-energized (off) and K 2 (D) is energized (on) after the end of the set Y end time. (Switching delay at 90 ms).• Continuous adjustment range• High repeat accuracy
Transition Time Y Contactor
1…30 s
110…240V50/60 Hz
100-C with AC coils 100-ETY30
-SB01 -SB10
-SB02 -SB11
-SB20 -SBL11
(K1M)
K1M
(K1M)
K1M
(K1M)
K1M
255
Bulletin 103H/107H/140MIEC Enclosed Starters
Accessories, Continued
Coil Accessories (For 100-C09…C85 Contactors), Continued
⊗ Voltage Suffix CodeThe Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: 120V, 60 Hz: Cat. No. 100-FL11⊗ becomes Cat. No. 100-FL11D.
➊ For special voltages, contact factory.
Assembly Components➌ Use Discount Schedule A1.
Description Connection Diagrams For Use With Cat. No.DC Interface (electronic)Interface between the DC control signal (PLC) and the AC operating mechanism of the contactor. Requires no additional surge suppression on the contactor coils.• Control (input) voltage
100-C with AC coils 110…240V AC
12V DC18…30V DC (24V DC nominal)48V DC
100-JE12100-JE
100-JE48
Surge SuppressorsFor limitation of coil switching transients.• Plug-in, coil mounted• Suitable for all 100-C
contactor sizes, 9…85 A• RC, Varistor and Diode
Versions
RC ModuleAC Operating Mechanism
24…48V 50/60 Hz
100-C with AC coils
100-FSC48
110…280V50/60 Hz 100-FSC280
380…480V50/60 Hz 100-FSC480
Varistor ModuleAC/DC Operating Mechanism
12…55V AC /12…77V DC
100-C all
100-FSV55
56…136V AC /78…180V DC 100-FSV136
137…277V AC /181…350V DC 100-FSV277
278…575V AC 100-FSV575
Diode Module DC Operating Mechanism
12…250VDC 100-C with DC coils 100-FSD250
Voltage ➊ 24 48 100 110 120 230…240 240 277 380…400 400…415 440 48050 Hz K Y KP D — VA T — N G B —60 Hz J — — — D — A T — — N B
Description For Use With Pkg. Qty. Cat. No.
Protective Covers• Provides protection against unintended manual operation• For contactors and front mounted auxiliary contacts, pneumatic
timers and latches
100-C all 1 100-SCCA
100-FA, FB, FC, FP, FL 10 100-SCFA
K1M
(K1M)
Cat. No. 100-SCCA
Cat. No. 100-SCFA
Bulletin 103H/107H/140MIEC Enclosed Starters
256
Accessories
Auxiliary Contacts for Motor Protectors (140M-C, -D, -F)
➊ X = Contact ClosedO = Contact Open
➋
Description
Connection Diagram ➋For Use
With Cat. No.
Operator Position ➊
Term. No. Desc.
OFF ON Tripped
Right Side-Mounted Auxiliary Contact• 2-pole• Adds 9 mm to the
width of the device
O X O 33-34 N.O. Aux
140M 140M-C-ASA20
O X O 43-44 N.O. Aux
X O X 31-32 N.C. Aux
140M 140M-C-ASA02
X O X 41-42 N.C. Aux
O X O 33-34 N.O. Aux
140M 140M-C-ASA11
X O X 41-42 N.C. Aux
Right Side-Mounted Trip Contact• 2-pole• Indicates tripping of
Motor Protector• Adds 9 mm to the
width of the circuit breaker
O O X 57-58N.O. Trip
(Short-Circuit & Overload)
140M 140M-C-ASAR10M10
O O X 67-68 N.O. Trip(Short-Circuit)
O O X 57-58N.O. Trip
(Short-Circuit & Overload)
140M 140M-C-ASAR10M01
X X O 65-66 N.C. Trip(Short-Circuit)
X X O 55-56N.C. Trip
(Short-Circuit & Overload)
140M 140M-C-ASAR01M10
O O X 67-68 N.O. Trip(Short-Circuit)
X X O 55-56N.C. Trip
(Short-Circuit & Overload)
140M 140M-C-ASAR01M01
X X O 65-66 N.C. Trip(Short-Circuit)
O O X 77-78 N.O. Trip(Short-Circuit)
140M 140M-C-ASAM11X X O 65-66 N.C. Trip
(Short-Circuit)
I >>
33
34
43
44
I >>
31
32
41
42
33
34
41
42
I >>
57
58
67
68
I >>
I >>
57
58
65
66
I >>
55
56
67
68
I >>
65
66
55
56
I >>
77
78
65
66
I >>
140 M Operator
Overload (thermal) TripShort-Circuit (magnetic) Trip
257
Bulletin 103H/107H/140MIEC Enclosed Starters
Accessories, Continued
Accessories for Motor Protectors (140M-C, -D, -F)
Description Connection Diagram For Use With Cat. No.
Undervoltage Trip• Left-side mounted• Adds 18 mm to the width of
the circuit breaker• Trips motor protector when
voltage is removed
24V, 60 Hz24V, 50 Hz
120V, 60 Hz110V, 50 Hz
220…230V, 50 Hz240…260V, 60 Hz
277V, 60 Hz380…400V, 50 Hz
480V, 60 Hz/415V, 50 Hz600V, 60 Hz
575V, 60 Hz/500V, 50 Hz
140M
140M-C-UXJ140M-C-UXK140M-C-UXD140M-C-UXC140M-C-UXF140M-C-UXA140M-C-UXT140M-C-UXN140M-C-UXB
140M-C-UXUB140M-C-UXM
Shunt Trip• Left-side mounted• Adds 18 mm to the width of
the circuit breaker• Trips motor protector when
voltage is applied
24V, 60 Hz24V, 50 Hz
120V, 60 Hz110V, 50 Hz
220…230V, 50 Hz240…260V, 60 Hz
277V, 60 Hz380…400V, 50 Hz
480V, 60 Hz/415V, 50 Hz600V, 60 Hz
575V, 60 Hz/500V, 50 Hz
140M
140M-C-SNJ140M-C-SNK140M-C-SND140M-C-SNC140M-C-SNF140M-C-SNA140M-C-SNT140M-C-SNN140M-C-SNB
140M-C-SNUB140M-C-SNM
Description For Use With Cat. No.
Anti Tamper Shield• Provides protection against inadvertent adjustment of the current setting 140M 140M-C-CA
Door Coupling Handle• For 3 padlocks 4…8 mm (5/16") in diameter• IP66 Protection/Type 1,3,3R,4,4x,13• Interlock override capability• Can be modified for locking in ON position• Ships with coupling — order extension shaft and legend plate
separately• Mounting depth (adapter-door):
140-C: 105.5 mm ± 5 mm (4.15" ± 3/16")140-D: 114.5 mm ± 5 mm (4.5" ± 3/16")140-F: 137.1 mm ± 5 mm (5.4" ± 3/16")
black 140M 140M-C-DN66
red/yellow 140M 140M-C-DRY66
Extension Shaft• Cut to required length for mounting depth (adapter-door):
140-C: 117…338 mm (4.6"…13.3")140-D: 126…347 mm (5.0"…13.7")140-F: 149…369 mm (5.4"…14.5")
140M-C-DN66140M-C-DRY66 140M-C-DS
Legend Plate• Marking: "Haupschalter" and "Main Switch"• Marking: "Not-Aus" and "Emergency Off"
140M-C-DN66 140M-C-DFCN
140M-C-DRY66 140M-C-DFCRY
Screw Adapter• For screw arrangement of a motor protector 10 pcs/pkg 140M 140M-C-N45
D1
D2I >>
U <
C1
C2I >>
Bulletin 103H/107H/140MIEC Enclosed Starters
258
Modifications
Bulletin 103H/107H Factory Installed ModificationsNote: For modifications add (option code ➊ ) for desired features to cat. no.
➊ Add desired option codes. Example: 103H-AND2-CA16X-KY
➋ 107H - One per contactor, for a total of two per option code.➌ Starters in enclosure size "A" will change to enclosure size "B" when a control
transformer is factory installed.
140M Factory Installed Modifications (Enclosed)Note: For modifications add (option code ➍ ) for desired features to cat. no.
➍ Add desired option codes. Example: 140M-F-CA16X-UVB
Line and Coil Voltage Suffix Codes
Line Voltage Suffix CodesThe Cat. No. as listed is incomplete. Select a line voltage code from the table below to complete the Cat. No. Example: 208V 60 Hz: Cat. No. 103H-AF ⊗ 2-CA16X becomes Cat. No. 103H-AFH⊗ 2-CA16X.
⊗ Coil Voltage Suffix CodesThe Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V 60 Hz: Cat. No. 103H-AFH⊗ -CA16X becomes Cat. No. 103H-AFHD-CA16X.
Coil OptionsJE ➋ Electronic Interfaces (100-C)
R ➋ Surge Suppressor RC (100-C)
V ➋ Surge Suppressor Varistor (100-C)
D ➋ Surge Suppressor Diode (100-C)Additional Contactor Auxiliaries (Side Mount)
S01 ➋ 1 N.C.
S10 ➋ 1 N.O.
S11 ➋ 1 N.O. + 1 N.C.
S20 ➋ 2 N.O.Additional 140M Auxiliaries (Side Mount)
A02 2 N.C.A20 2 N.O.A11 1 N.O. + 1 N.C.
Additional 140M Trip Contacts (Side Mount)R00 1 N.O. Thermal-Mag + 1 N.O. Mag OnlyR01 1 N.O. Thermal-Mag + 1 N.C. Mag OnlyR10 1 N.C. Thermal-Mag + 1 N.O. Mag OnlyR11 1 N.C. Thermal-Mag + 1 N.C. Mag OnlyM11 1 N.O. Mag Only + 1 N.C. Mag Only
Control Options1 Push Button — 103H Start-Stop / 107H For-Rev-Stop
1M Multifunction Push Button — 103H Start-Stop / 107H For-Rev-Stop14RM Multifunction Push Button — 103H Start-Stop-Pilot Light
3 Selector Switch — 103H Hand-Off-Auto / 107H For-Off-Rev4R Pilot Light (red, ON)
4RW Pilot Light (red—FOR, White — REV)6P Control Transformer ➌ (not available with enclosure size A)KY External Handle — Red/Yellow
ModificationsUV⊗ Undervoltage TripSN⊗ Shunt Trip
Additional 140M Auxiliaries (Side Mount)A02 2 N.C.A20 2 N.O.A11 1 N.O. + 1 N.C.
Additional 140M Trip Contacts (Side Mount)R00 1 N.O. Thermal-Mag + 1 N.O. Mag OnlyR01 1 N.O. Thermal-Mag + 1 N.C. Mag OnlyR10 1 N.C. Thermal-Mag + 1 N.O. Mag OnlyR11 1 N.C. Thermal-Mag + 1 N.C. Mag OnlyM11 1 N.O. Mag Only + 1 N.C. Mag Only
Line Voltages 208V 230V 240V 380V 400V 415V 480V 600V60 Hz H — A — — — B C50 Hz — F — N KN G — —
Standard Coil Voltages 24 110 120 208 220…230 240…260 277 380…400 415 480 600
50 Hz K C — — F — — N B — —60 Hz J — D H — A T — — B UB
259
Bulletin 103H/107H/140MIEC Enclosed Starters
Wiring Diagrams
Cat. No. 103H-AFBD2-DB40X-1-4R-6P
44
A20
33
43
2L1
2L2
2 4
L3L2L1
INCOMING LINES
L1 L2 L3
T12
1L11
L1
T24
3L2
1L2
L351L3
6T3
A2
T1T1
2
A1
L111L1
MMS
(X1) (X2)
(1-2)
1
(1-3)(1-1)
3
(1-4)
2
2L2
H1
X1
1F
H2
X2
U
2F
LINESINCOMING
(T1)(L1)
(T3)
(L2)
(L3)
1L1
1L2
1L3
L1
L2
L3
(T3)(6)
(L3)(5)
(T2)(4)
(T1)(2)
(L1)
(L2)(3)
(1)
T1
T3
MS(34)
(33)
(3)
(5)
(1) (2)
FU
MS
M
1111111
(44)
(43)
REMOTE
1
MS
R
STARTSTOP
(13) (14)
M
(A1) (A2)M
Bulletin 103H/107H/140MIEC Enclosed Starters
260
Wiring Diagrams, Continued
Cat. No. 107H-AFBD3-CA16X-1M-4RW-6P
44
A20
34
33
43
L1
2L1
2L2
22 5
3
4
1L3
L3
L3
A2A2
T1
A1A2 F
L1
L1
4 6 14
T12
L2
L2
INCOMING LINES
4T2 T3
6
13 1L1
L11
1L2
L23 5
L3
MS
(2-4) (2-3)
6 7
(3-2)
1
(1-3)(3-1)
3
(1-4)
4 5
2
(X2)
(X1) (X2)
X1 X2
LINESINCOMING
(T3)(6)
(L3)(5)
(T2)(4)
(T1)(2)
(L1)
(L2)(3)
(1)
R
(T1)(L1)
(T1)(L1)
(T3)
(L2)
(L3)
1L1
1L2
1L3
L1
L2
L3
(L2)
(T3)(L3)
T1
T3
MS(34)
(33)
(3)
(5)
(1) (2)
F
1
(3)
(5)
(1) (2)
MS
FU
(14)
REVERSE
(21) (22) (A2)R
STOPFORWARD
F
(21)
R
(A2)F
R
(44)
(43)
MS
(22)
REVERSE
W
F
(A1)
(13) (14)
(A1)
44
261
Bulletin 103H/107H/140MIEC Enclosed Starters
Enclosure Dimensions
Dimensions in mm. Dimensions are not intended to be used for manufacturing purposes.Enclosure Style A
Enclosure Style B
Enclosure Style C
Bulletin 109IEC Non-Reversing Starters
262
Overview/Product Selection
Fast Shipment of Bulletin109 IEC Products to satisfy your unexpected demands. Make your selections from any of the Cat. Nos. printed in blue and identify your order as A-B EXPRESS Fast Shipment Program.Your order must include: Cat. No. of the starter selected,coil voltage code, overload relay suffix code, and, if required, factory-installed modifications suffix code and/or Cat. No. of any accessories.
Product Selection — AC-Operated StartersEnclosed Type — Molded Plastic
Enclosed Type — Sheet Metal
⊗ Coil Voltage CodeThe Cat. No. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the Cat. No. Example: Cat. No. 109-C09A⊗ becomes Cat. No.109-C09AB .
Overload Relay CodeThe Cat. No. as listed is incomplete. Select an overload relay code from page 274 to complete the Cat. No. Bimetal and MSC-E2 overload relays are not available in molded plastic enclosed starters.
➊ When selecting a factory-installed control circuit transformer (see Modifications page 276), use the Common Control Coil Voltage Code to denote the transformer primary voltage. The starter coil and transformer secondary voltage will both be 120V by default. Example: Cat. No. 109-C09FB -6P will have a transformer with a 480V primary/120V secondary and a 120V starter coil. If a starter coil voltage other than 120V is desired, a second Coil Voltage Code must be added to denote the coil/transformer secondary voltage. Example: Cat. No. 109-C09FBJ -6P will have a transformer with a 480V primary/24V secondary and a 24V starter coil. Control Circuit transformers are not available in molded plastic enclosures
Bulletin 109 IEC Non-Reversing Starters• Impact-Resistant Molded Enclosures (9…23 A)
IP42 (Type 1)IP66 (Type 4/4X/12)
• Selection of Metal Enclosures (9…85 A)IP42 (Type 1)IP66 (Type 3/4/12)
• Bimetallic Class 10 Overload Relays• Solid-State Overload Relays• Compact Design• Meets International Standards
Bulletin 109 enclosed starters are designed using Bulletin 100 contactors (9 A…85 A) and Bulletin 193 bimetallic (Class 10) or solid-state overload relays in a metal or molded plastic enclosure. All starters include a normally open auxiliary contact as standard.
Product Selection ...........262Accessories.....................270Modifications...................276Approximate Dimensions ....... 278 and 280
Conformity to StandardsEN/IEC 60947-4-1VDE 0660CSA C22.2 No. 14UL 508
ApprovalscULus Listed (File E3125, Guide No. NLDX)
Ratings (AC3, AC4) IP42 (Type 1)General-Purpose
Molded Plastic Enclosure
IP66 (Type 4, 4X, 12)Watertight, DusttightCorrosion Resistant
Molded Plastic EnclosureMax Ie[A]
kW Hp
3∅ 1∅ 3∅Cat. No. ➊ Cat. No. ➊
380V/ 415V 115V 230V 200V 230V 460V 575V9 4 1/2 1-1/2 2 2 5 7-1/2 109-C09B⊗ 109-C09K⊗
12 5-1/2 1/2 2 3 3 7-1/2 10 109-C12B⊗ 109-C12K⊗
16 7-1/2 1 3 5 5 10 15 109-C16B⊗ 109-C16K⊗
23 11 2 3 5 7-1/2 15 15 109-C23B⊗ 109-C23K⊗
Ratings (AC3, AC4) IP42 (Type 1) General Purpose
Sheet Metal Enclosure (Lift-off Cover)
IP66 (Type 3, 4, 12)Watertight, Dusttight
Sheet Metal Enclosure(Hinged Cover)Max Ie
[A]
kW Hp
3∅ 1∅ 3∅Cat. No. Cat. No.
380V/415V 115V 230V 200V 230V 460V 575V9 4 1/2 1-1/2 2 2 5 7-1/2 109-C09A⊗ 109-C09F⊗
12 5-1/2 1/2 2 3 3 7-1/2 10 109-C12A⊗ 109-C12F⊗
16 7-1/2 1 3 5 5 10 15 109-C16A⊗ 109-C16F⊗
23 11 2 3 5 7-1/2 15 15 109-C23A⊗ 109-C23F⊗
30 15 2 5 7-1/2 10 20 25 109-C30A⊗ 109-C30F⊗
37 18-1/2 3 5 10 10 25 30 109-C37A⊗ 109-C37F⊗
43 22 3 7-1/2 10 15 30 30 109-C43A⊗ 109-C43F⊗
60 30 5 10 15 20 40 50 109-C60A⊗ 109-C60F⊗
72 37 5 15 20 25 50 60 109-C72A⊗ 109-C72F⊗
85 45 7-1/2 15 25 30 60 60 109-C85A⊗ 109-C85F⊗
AC Voltage 24 48 110 120 208 208-240 220 240 277 380-400 400-415 440 480 500 600
Common Control ➊Coil Voltage Code
50 Hz — — — — — — A T — N G B — M —
60 Hz — — — — H L — A — — — N B — C
Separate Control (without transformer)Coil Voltage Code
50 Hz K Y D — — — — — — — — — — — —
60 Hz J X — D — — — — T — — — — — —
Cat. No. 109-C09ABA1F-1-4R-6PIP42 (Type 1) Metal
Enclosure with Lift-off Cover
Cat. No. 109-C09KDA1E-1-4R1-7
Molded Plastic Enclosure
263
Bulletin 112IEC Combination Starters
Overview/Product Selection
Fast Shipment of Bulletin112 IEC Products to satisfy your unexpected demands. Make your selections from any of the Cat. Nos. printed in blue and identify your order as A-B EXPRESS Fast Shipment Program.Your order must include: Cat. No. of the combination starter selected,coil voltage code, overload relay suffix code, and, if required, factory-installed modifications suffix code and/or Cat. No. of any accessories.
Product Selection — AC-Operated StartersFusible Disconnect Type
Non-Fusible Disconnect Type
⊗ Coil Voltage CodeThe Cat. No. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the Cat. No. Example: Cat. No. 112-C09A⊗ becomes Cat. No. 112-C09AB .
Overload Relay CodeThe Cat. No. as listed is incomplete. Select an overload relay code from page 274 to complete the Cat. No.
➊ When selecting a factory-installed control circuit transformer (see Modifications page 277), use the Common Control Coil Voltage Code to denote the transformer primary voltage. The starter coil and transformer secondary voltage will both be 120V by default. Example: Cat. No. 112-C09FB- -6P will have a transformer with a 480V primary/120V secondary and a 120V starter coil. If a starter coil voltage other than 120V is desired, a second Coil Voltage Code must be added to denote the coil/transformer secondary voltage. Example: Cat. No. 112-C09FBJ- -6P will have a transformer with a 480V primary/24V secondary and a 24V starter coil.
Bulletin 112 IEC Combination Starters• Compact Design• Can Be Modified in the Field• Selection of Enclosures
IP42 (Type 1)IP66 (Type 3/4/12)
• Bimetallic Class 10 Overload Relays• Solid-State Overload Relays• Fusible or Non-Fusible Versions• Handle with Defeater Mechanism• Padlockable Handle with up to Three Padlocks
Bulletin 112 is the first true IEC combination starter on the market, in that the enclosure and components have been designed to specific IEC standard requirements. The Bulletin 112 combination starter consists of a Bulletin 100 Contactor, Bulletin 193 bimetallic (Class 10) or solid-state overload relay and Bulletin 194R fused disconnect switch installed in a com-mon enclosure. These full-voltage combination starters are designed to provide the discon-necting means, short-circuit protection (with suitable fuses), control and overload protection for three-phase squirrel-cage motors. All starters include a normally open auxiliary contact as standard.
Product Selection........... 263Accessories .................... 270Modifications .................. 277Approximate Dimensions.......279 and 281
Conformity to StandardsEN/IEC 60947-4-1VDE 0660CSA C22.2 No. 14UL 508
ApprovalscULus Listed (File E125316, Guide No. NKJH)
Ratings (AC3, AC4) IP42 (Type 1)General Purpose
Sheet Metal Enclosure(Hinged Cover)
IP66 (Type 3/4/12)Watertight, Dusttight
Sheet Metal Enclosure(Hinged Cover)Max Ie
[A]
Hp Fuse ClipRating
Amperes/ UL Class3 ∅Cat. No. Cat. No.
200V 230V 460V 575V9 2 2 5 7-1/2 30A/Class CC 112-C09A⊗ 112-C09F⊗
12 3 3 7-1/2 10 30A/Class J 112-C12A⊗ 112-C12F⊗
23 5 7-1/2 15 15 30A/Class J 112-C23A⊗ 112-C23F⊗
30 7-1/2 10 20 25 60A/Class J 112-C30A⊗ 112-C30F⊗
43 10 15 30 30 60A/Class J 112-C43A⊗ 112-C43F⊗
60 15 20 40 50 100A/Class J 112-C60A⊗ 112-C60F⊗
72 20 25 50 60 100A/Class J 112-C72A⊗ 112-C72F⊗
Ratings (AC3, AC4) IP42 (Type 1)General Purpose
Sheet Metal Enclosure(Hinged Cover)
IP66 (Type 3/4/12)Watertight, Dusttight
Sheet Metal Enclosure(Hinged Cover)Max Ie
[A]
Hp
3 ∅Cat. No. Cat. No.
200V 230V 460V 575V9 2 2 5 7-1/2 112-C09A⊗ -DNF 112-C09F⊗ -DNF12 3 3 7-1/2 10 112-C12A⊗ -DNF 112-C12F⊗ -DNF23 5 7-1/2 15 15 112-C23A⊗ -DNF 112-C23F⊗ -DNF30 7-1/2 10 20 25 112-C30A⊗ -DNF 112-C30F⊗ -DNF43 10 15 30 30 112-C43A⊗ -DNF 112-C43F⊗ -DNF60 15 20 40 50 112-C60A⊗ -DNF 112-C60F⊗ -DNF72 20 25 50 60 112-C72A⊗ -DNF 112-C72F⊗ -DNF
Voltage 208V 230…240V 460…480V 575…600V
Common Control ➊Coil Voltage Code
60 HzH A B C
120V — Separate Control (without transformer)Coil Voltage Code AD AD CD CD
Cat. No. 112-C09FBA1F-1-7
IP66 (Type 3,4,12) Metal Enclosure with Hinged
Cover
Bulletin 113IEC Combination Starters
264
Overview/Product Selection
Your order must include: Cat. No. of the combination starter selected, coil voltage code, overload relay suffix code, and, if required, factory-installed modifications suffix code and/or Cat. No. of any accessories.
Product SelectionCircuit Breaker Type - AC Operated
⊗ Coil Voltage CodeThe Cat. No. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the Cat. No. Example: Cat. No. 113-C30A⊗ -33 becomes Cat. No. 113-C30AB -33.
Overload Relay CodeThe Cat. No. as listed is incomplete. Select an overload relay code from page 274 to complete the Cat. No.
➊ For design “E” motor applications, consult your local Allen-Bradley distributor.➋ When selecting a factory-installed control circuit transformer (see Modifications page 276), use the Common Control Coil Voltage Code to denote the transformer
primary voltage. The starter coil and transformer secondary voltage will both be 120V by default. Example: Cat. No. 113-C30FB3 -6P will have a transformer with a 480V primary/120V secondary and a 120V starter coil. If a starter coil voltage other than 120V is desired, a second Coil Voltage Code must be added to denote the coil/transformer secondary voltage. Example: Cat. No. 113-C30FBJ -6P will have a transformer with a 480V primary/24V secondary and a 24V starter coil.
Bulletin 113 IEC Combination Starters• Compact Design• Can Be Modified in the Field• Selection of Enclosures
IP42 (Type 1)IP66 (Type 3/4/12)
• Bimetallic Class 10 Overload Relays• Solid-State Overload Relays• Handle Defeater Mechanism• Padlockable Handle with up to Three Padlocks• Adjustable Instantaneous Trip Circuit Breaker
Bulletin 113 combination starter consists of a Bulletin 100 contactor, Bulletin 193 bimetallic (Class 10) or solid-state overload relay and a motor circuit protector installed in a common enclosure. These full-voltage combination starters are designed to provide the disconnect-ing means, short-circuit protection, control and overload protection for three-phase squirrel-cage motors. All starters include a normally open auxiliary contact as standard.
Product Selection ...........264Accessories.....................270Modifications...................276Approximate Dimensions ...... 279 and 281
Conformity to StandardsEN/IEC 60947-4-1VDE 0660CSA C22.2 No. 14UL 508
ApprovalscULus Listed (File E125316, Guide No. NKJH)
Ratings (AC3, AC4) IP42 (Type 1)General Purpose
Sheet Metal Enclosure(Hinged Cover)
IP66 (Type 3/4/12)Watertight, Dusttight
Sheet Metal Enclosure(Hinged Cover)
Max Ie[A]
Hp ➊
3∅
200V 230V 460V 575V Cat. No. Cat. No.
30
1/2 1/2 — — 113-C30A⊗ -33 113-C30F⊗ -33
3/4…1 3/4…1 1/2…1 — 113-C30A⊗ -35 113-C30F⊗ -35
— — — 1/2…1-1/2 113-C30A⊗ -36 113-C30F⊗ -36
1-1/2…3 1-1/2…3 1-1/2…3 2…3 113-C30A⊗ -38 113-C30F⊗ -38
5 — — — 113-C30A⊗ -39 113-C30F⊗ -39
7-1/2 5…7-1/2 5…7-1/2 — 113-C30A⊗ -40 113-C30F⊗ -40
— 10 — 5…10 113-C30A⊗ -41 113-C30F⊗ -41
— — 10 — 113-C30A⊗ -42 113-C30F⊗ -42
— — 20 15…20 113-C30A⊗ -43 113-C30F⊗ -43
— — — 25 113-C30A⊗ -44 113-C30F⊗ -44
43
7-1/2…10 10 — — 113-C43A⊗ -41 113-C43F⊗ -41
— 15 — — 113-C43A⊗ -42 113-C43F⊗ -42
— — 20…25 — 113-C43A⊗ -44 113-C43F⊗ -44
— — 30 25…30 113-C43A⊗ -45 113-C43F⊗ -45
60
15 — — — 113-C60A⊗ -42 113-C60F⊗ -42
— 15…20 — — 113-C60A⊗ -43 113-C60F⊗ -43
— — 40 40 113-C60A⊗ -46 113-C60F⊗ -46
72
15…20 — — — 113-C72A⊗ -43 113-C72F⊗ -43
— 20…25 — — 113-C72A⊗ -44 113-C72F⊗ -44
— — 40…50 — 113-C72A⊗ -47 113-C72F⊗ -47
— — — 40…60 113-C72A⊗ -48 113-C72F⊗ -48
Voltage 208V 230…240V 460…480V 575…600V
Common Control ➋Coil Voltage Code
60 HzH A B C
120V — Separate Control (without transformer)Coil Voltage Code HD AD BD CD
Cat. No. 113-C30FBA1H-4R-43IP66 (Type 3,4,12) Metal Enclosure with
Hinged Cover
265
Bulletin 105IEC Reversing Starters
Overview/Product Selection
Fast Shipment of Bulletin 105 IEC Products to satisfy your unexpected demands. Make your selections from any of the Cat. Nos. printed in blue and identify your order as A-B EXPRESS Fast Shipment Program.Your order must include: Cat. No. of the reversing starter selected,coil voltage code, overload relay suffix code, and, if required, factory-installed modifications suffix code and/or Cat. No. of any accessories.
Product SelectionAC-Operated
⊗ Coil Voltage CodeThe Cat. No. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the Cat. No. Example: Cat. No. 105-C09A⊗ becomes Cat. No. 105-C09AB .
Overload Relay Code The Cat. No. as listed is incomplete. Select an overload relay code from page 274 complete the Cat. No.
➊ For single-phase (1∅ ) applications, consult your local Allen-Bradley distributor.➋ When selecting a factory-installed control circuit transformer (see Modifications page 277), use the Common Control Coil Voltage Code to denote the transformer
primary voltage. The starter coil and transformer secondary voltage will both be 120V by default. Example: Cat. No. 105-C09FB -6P will have a transformer with a 480V primary/120V secondary and a 120V starter coil. If a starter coil voltage other than 120V is desired, a second Coil Voltage Code must be added to denote the coil/transformer secondary voltage. Example: Cat. No. 105-C09FBJ -6P will have a transformer with a 480V primary/24V secondary and a 24V starter coil.
Bulletin 105 IEC Reversing Starters• Selection of Metal Enclosures
IP42 (Type 1)IP66 (Type 3/4/12)
• Bimetallic Class 10 Overload Relays• Solid-State Overload Relays• Compact Design• Meets International Standards
Bulletin 105 enclosed starters use Bulletin 104 reversing contactors and Bulletin 193 bimetallic (Class 10) or solid-state overload relays. These reversing starters (9…85 A) incorporate a “dual” interlock that provides both mechanical and electrical interlocking in a single unit. A normally open auxiliary contact is also included on each contactor.
Product Selection........... 265Accessories .................... 235Modifications .................. 276Approximate Dimensions..................... 279
Conformity to StandardsEN/IEC 60947-4-1VDE 0660CSA C22.2 No. 14UL 508
ApprovalscULus Listed (File E3125, Guide No. NLDX)
Ratings (AC3, AC4) IP42 (Type 1)General Purpose
Sheet Metal Enclosure(Lift-off cover through 105-C72)
IP66 (Type 3/4/12)Watertight, Dusttight
Sheet Metal Enclosure(Hinged Cover)Max
Ie[A]
kW Hp
3∅ 1∅ ➊ 3∅Cat. No. Cat. No.380V/
415V 115V 230V 200V 230V 460V 575V
9 4 1/2 1-1/2 2 2 5 7-1/2 105-C09A⊗ 105-C09F⊗
12 5-1/2 1/2 2 3 3 7-1/2 10 105-C12A⊗ 105-C12F⊗
16 7-1/2 1 3 5 5 10 15 105-C16A⊗ 105-C16F⊗
23 11 2 3 5 7-1/2 15 15 105-C23A⊗ 105-C23F⊗
30 15 2 5 7-1/2 10 20 25 105-C30A⊗ 105-C30F⊗
37 18-1/2 3 5 10 10 25 30 105-C37A⊗ 105-C37F⊗
43 22 3 7-1/2 10 15 30 30 105-C43A⊗ 105-C43F⊗
60 30 5 10 15 20 40 50 105-C60A⊗ 105-C60F⊗
72 37 5 15 20 25 50 60 105-C72A⊗ 105-C72F⊗
85 45 7-1/2 15 25 30 60 60 105-C85A⊗ 105-C85F⊗
AC Voltage 24 48 110 120 208 208…240 220 240 277 380…
400400…415 440 480 500 600
Common Control ➋Coil Voltage Code
50 Hz — — — — — — A T — N G B — M —
60 Hz — — — — H L — A — — — N B — C
Separate Control (without trans-former)Coil Voltage Code
50 Hz K Y D — — — — — — — — — — — —
60 Hz J X — D — — — — T — — — — — —
Cat. No. 105-C09ABA1F-1-6PType 1 Metal Enclosure with Lift-off Cover
Bulletin 106IEC Reversing Combination Starters
266
Overview/Product Selection — Fusible Disconnect Type
Your order must include: Cat. No. of the reversing combination starter selected,coil voltage code, overload relay suffix code, and, if required, factory-installed modifications suffix code and/or Cat. No. of any accessories.
Product Selection Fusible Disconnect TypeAC Operated
⊗ Coil Voltage CodeThe Cat. No. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the Cat. No. Example: Cat. No. 106-C09A⊗ becomes Cat. No. 106-C09AB .
Overload Relay CodeThe Cat. No. as listed is incomplete. Select an overload relay code from page 274 complete the Cat. No.
➊ When selecting a factory-installed control circuit transformer (see Modifications page 277), use the Common Control Coil Voltage Code to denote the transformer primary voltage. The starter coil and transformer secondary voltage will both be 120V by default. Example: Cat. No. 106-C09FB -6P will have a transformer with a 480V primary/120V secondary and a 120V starter coil. If a starter coil voltage other than 120V is desired, a second Coil Voltage Code must be added to denote the coil/transformer secondary voltage. Example: Cat. No. 106-C09FBJ -6P will have a transformer with a 480V primary/24V secondary and a 24V starter coil.
Bulletin 106 IEC Reversing Combination Starters• Selection of Metal Enclosures
IP42 (Type 1) andIP66 (Type 3/4/12)
• Bimetallic Class 10 Overload Relays• Solid-State Overload Relays• Compact Design• Meets International Standards• Can be Modified in the Field• Handle with Defeater Mechanism• Padlockable Handle (up to three padlocks)
Bulletin 106 Combination starters use a Bulletin 104 reversing contactor, a Bulletin 193 bimetallic (Class 10) or solid-state overload relay, and a Bulletin 194R rotary disconnect switch. Reversing starters (9 A…72 A) incorporate a “dual” interlock that provides both mechanical and electrical interlocking in a single unit. A normally open auxiliary contact is also included on each contactor.
Product Selection ...........266Accessories.....................270Modifications...................276Approximate Dimensions ....... 279 and 281
Conformity to StandardsEN/IEC 60947-4-1VDE 0660CSA C22.2 No. 14UL 508
ApprovalscULus Listed (File E3125, Guide No. NLDX)
Ratings (AC3, AC4) IP42 (Type 1)General-Purpose
Sheet Metal Enclosure(Hinged Cover)
IP66 (Type 3, 4, 12)Watertight, Dusttight
Sheet Metal Enclosure(Hinged Cover)Max Ie
[A]
kW HpFuse Clip Rating
Amperes/ UL Class3∅ 3∅Cat. No. Cat. No.
380…415V 200V 230V 460V 575V9 4 2 2 5 7-1/2 30A/Class CC 106-C09A⊗ 106-C09F⊗
12 5-1/2 3 3 7-1/2 10 30A/Class J 106-C12A⊗ 106-C12F⊗
23 11 5 7-1/2 15 15 30A/Class J 106-C23A⊗ 106-C23F⊗
30 15 7-1/2 10 20 25 60A/Class J 106-C30A⊗ 106-C30F⊗
43 22 10 15 30 30 60A/Class J 106-C43A⊗ 106-C43F⊗
60 30 15 20 40 50 100A/Class J 106-C60A⊗ 106-C60F⊗
72 37 20 25 50 60 100A/Class J 106-C72A⊗ 106-C72F⊗
Voltage 208V 230…240V 460…480V 575…600V
Common Control ➊ Coil Voltage Code60 Hz
H A B C
120V — Separate Control (without transformer)Coil Voltage Code AD AD CD CD
Cat. No. 106-C30FBA1H-4RW-6PIP66 (Type 3,4,12)
Metal Enclosure with Hinged Cover
267
Bulletin 120EIEC Multi-Speed Starters
Overview/Product Selection
Fast Shipment of Bulletin 120E IEC Products to satisfy your unexpected demands. Make your selections from any of the Cat. Nos. printed in blue and identify your order as A-B EXPRESS Fast Shipment Program.Your order must include: Cat. No. of the multi-speed starter selected, coil voltage code, and, if required, factory-installed modifications suffix code and/or Cat. No. of any accessories.
Product SelectionEnclosed Type — AC Operated
2-Speed Separate Winding, Constant or Variable Torque (Constant Horsepower—Consult your local Allen-Bradley distributor.)
⊗ Coil Voltage CodeThe Cat. No. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the Cat. No. Example: Cat. No. 120E-C09A⊗ becomes Cat. No. 120E-C09AB .
Overload Relay CodeThe Cat. No. as listed is incomplete. Select (2) overload relay codes and price adder from page 274 to complete the cat. no. The first code will denote the high speed overload relay, and the second code will denote the low speed overload relay.
➊ For single-phase (1∅ ) applications, consult your local Allen-Bradley distributor. ➋ When selecting a factory-installed control circuit transformer (see Modifications page 277), use the Common Control Coil Voltage Code to denote the transformer
primary voltage. The starter coil and transformer secondary voltage will both be 120V by default. Example: Cat. No. 120E-C09FB -6P will have a transformer with a 480V primary/120V secondary and a 120V starter coil. If a starter coil voltage other than 120V is desired, a second Coil Voltage Code must be added to denote the coil/transformer secondary voltage. Example: Cat. No. 120E-C09FBJ -6P will have a transformer with a 480V primary/24V secondary and a 24V starter coil.
Bulletin 120E IEC Multi-Speed Starters• Compact Design• Selection of Enclosures
IP42 (Type 1) andIP66 (Type 3/4/12)
• Bimetallic Class 10 Overload Relays• Solid-State Overload Relays
Bulletin 120E multi-speed starters are designed to control “two-speed, separate-winding” AC squirrel-cage induction motors. These starters are available for constant torque, vari-able torque, or constant horsepower three-phase motors. Multi-speed motors are com-monly used on machine tools, fans, blowers, pumps, conveyors and many other types of equipment.
Bulletin 120E multi-speed motor starters use Bulletin 100 contactors and Bulletin 193 bime-tallic (Class 10) or solid-state overload relays. A normally open auxiliary contact is also included on each contactor. A wide variety of factory- and field-installed options are avail-able.
Product Selection........... 267Accessories .................... 270Modifications .................. 277Approximate Dimensions.......279 and 280
Conformity to StandardsEN/IEC 60947-4-1VDE 0660CSA C22.2 No. 14UL 508
ApprovalscULus Listed (File E3125, Guide No. NLDX)
Ratings (AC3, AC4) IP42 (Type 1)General Purpose
Sheet Metal Enclosure(Lift-off Cover through 120E-C72)
IP66 (Type 3/4/12)Watertight, Dusttight
Sheet Metal Enclosure(Hinged Cover)
MaxIe[A]
kW Hp
3∅ 1∅ ➊ 3∅Cat. No. Cat. No.
380V/ 415V 115V 230V 200V 230V 460V 575V9 4 1/2 1-1/2 2 2 5 7-1/2 120E-C09A⊗ 120E-C09F⊗
12 5-1/2 1/2 2 3 3 7-1/2 10 120E-C12A⊗ 120E-C12F⊗
16 7-1/2 1 3 5 5 10 15 120E-C16A⊗ 120E-C16F⊗
23 11 2 3 5 7-1/2 15 15 120E-C23A⊗ 120E-C23F⊗
30 15 2 5 7-1/2 10 20 25 120E-C30A⊗ 120E-C30F⊗
37 18-1/2 3 5 10 10 25 30 120E-C37A⊗ 120E-C37F⊗
43 22 3 7-1/2 10 15 30 30 120E-C43A⊗ 120E-C43F⊗
60 30 5 10 15 20 40 50 120E-C60A⊗ 120E-C60F⊗
72 37 5 10 20 25 50 60 120E-C72A⊗ 120E-C72F⊗
85 45 7-1/2 15 25 30 60 60 120E-C85A⊗ 120E-C85F⊗
AC Voltage 24 48 110 120 208 208…240 220 240 277 380…
400400…415 440 480 500 600
Common Control ÀCoil Voltage Code
50 Hz — — — — — — A T — N G B — M —
60 Hz — — — — H L — A — — — N B — C
Separate Control (without transformer)Coil Voltage Code
50 Hz K Y D — — — — — — — — — — — —
60 Hz J X — D — — — — T — — — — — —
Cat. No. 120E-C09FDA1FA1D-3-4RW-7IP66 (Type 3,4,12)
Metal Enclosure with Hinged Cover
Bulletin 132/133IEC Pump Control Panels
268
Overview/Product Selection
Your order must include: Cat. No. of the pump control panel, coil voltage code, overload relay suffix code, and, if required, factory-installed modifications suffix code and/or Cat. No. of any accessories.
Product SelectionFusible Disconnect Type
Circuit Breaker Type
Bulletins 132 and 133 IEC Pump Control Panel Starters• IP32 (Type 3R)• Bimetallic Class 10 Overload Relays• Solid-State Overload Relays• Enclosure with Extra Panel Space for Mounting Accessory Devices• Factory-Installed Disconnect Switch or Circuit Breaker• Handle with Defeater Mechanism• Service Entrance Rated
Bulletin 132 and 133 pump control panels are specifically designed for irrigation and similar outdoor pumping applications.The Bulletin 132 pump control panel includes a Bulletin194R IEC fusible rotary disconnect switch, a Bulletin 100 IEC contactor, a Bulletin 193 bimetallic overload relay or solid-state overload relays, a HAND-OFF-AUTO selector switch, and a START button. All starters include a normally open auxiliary contact as standard. The Bulletin 133 pump control pan-els are supplied with a motor circuit protector instead of a fusible disconnect switch.IEC pump control panels include an IP32 (Type 3R) weather-resistant enclosure with a rug-ged, outdoor finish and brackets for pole or cross-bar mounting. Conduit knockouts are located at the bottom of the enclosure. Padlock provisions are furnished on the door latches and the handle (both the ON and OFF positions).
Product Selection ...........268Accessories.....................270Modifications...................276Approximate Dimensions .....................281
Conformity to StandardsUL 508
ApprovalsUL Listed
Ratings (AC3, AC4)
Fuse Clip RatingAmperes/UL Class
IP32 (Type 3R)Sleet Resistant, OutdoorSheet Metal Enclosure
(Hinged Cover)Max. Ie
[A]
kW Hp
3∅ 3∅
380/415V 200V 230V 460V 575V Cat. No.9 4 2 2 5 7-1/2 30 A/Class CC 132-C09M⊗
12 5-1/2 3 3 7-1/2 10 30 A/Class J 132-C12M⊗
23 11 5 7-1/2 15 15 30 A/Class J 132-C23M⊗
30 15 7-1/2 10 20 25 60 A/Class J 132-C30M⊗
43 22 10 15 30 30 60 A/Class J 132-C43M⊗
60 30 15 20 40 50 100 A/Class J 132-C60M⊗
72 37 20 25 50 60 100 A/Class J 132-C72M⊗
Ratings (AC3, AC4) IP32 (Type 3R)Sleet Resistant OutdoorSheet Metal Enclosure
(Hinged Cover)Max. Ie
[A]
Hp ➊
3∅
200V 230V 460V 575V Cat. No.
30
1/2 1/2 — — 133-C30M⊗ -333/4…1 3/4…1 1/2…1 — 133-C30M⊗ -35
— — — 1/2…1-1/2 133-C30M⊗ -361-1/2…3 1-1/2…3 1-1/2…3 2…3 133-C30M⊗ -38
5 — — — 133-C30M⊗ -397-1/2 5…7-1/2 5…7-1/2 — 133-C30M⊗ -40
— 10 — 5…10 133-C30M⊗ -41— — 10 — 133-C30M⊗ -42— — 20 15…20 133-C30M⊗ -43— — — 25 133-C30M⊗ -44
43
7-1/2…10 10 — — 133-C43M⊗ -41— 15 — — 133-C43M⊗ -42— — 20…25 — 133-C43M⊗ -44— — 30 25…30 133-C43M⊗ -45
6015 — — — 133-C60M⊗ -42— 15…20 — — 133-C60M⊗ -43— — 40 40 133-C60M⊗ -46
72
15…20 — — — 133-C72M⊗ -43— 20…25 — — 133-C72M⊗ -44— — 40…50 — 133-C72M⊗ -47— — — 40…60 133-C72M⊗ -48
Cat. No. 132-C09MBA1F
269
Bulletin 132/133IEC Pump Control Panels
Product Selection, Continued
⊗ Coil Voltage CodeThe Cat. No. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the Cat. No. Example: Cat. No. 132-C12M⊗ becomes Cat. No. 132-C12MB
Overload Relay CodeThe Cat. No. as listed is incomplete. Select an overload relay code from page 274.
➊ For horsepower ratings less than those shown, consult your local Allen-Bradley distributor.➋ When selecting a factory-installed control circuit transformer (see Modifications page 277), use the Common Control Coil Voltage Code to denote the transformer
primary voltage. The starter coil and transformer secondary voltage will both be 120V by default. Example: Cat. No. 132-C09MB -6P will have a transformer with a 480V primary/120V secondary and a 120V starter coil. If a starter coil voltage other than 120V is desired, a second Coil Voltage Code must be added to denote the coil/transformer secondary voltage. Example: Cat. No. 132-C09MBJ -6P will have a transformer with a 480V primary/24V secondary and a 24V starter coil.
Voltage 208V 230…240V 460…480V 575…600VCommon Control ➋Coil Voltage Suffix Code
60 HzH A B C
120V Separate Control (without transformer)Coil Voltage Suffix Code AD AD CD CD
Bulletin 100 LineAccessories — Field Installed
270
Accessories, Continued
(For Bulletins 105, 106, 109, 112, 113, 120E, 132, and 133)
➊ Does not include legend plate. See page 11-299 for Bulletin 800E Legend Plate. Legend Plates for use on metal-hinged enclosures only.➋ Requires mounting bracket Cat. No. 198-BR1 when using metal lift-off enclosures.➌ An auxiliary contact adaptor, Cat. No. 194R-AA, is required when installing auxiliary contact, Cat. No. 195-GA10.➍ 3 required for disconnect switch.
Description For Use WithBulletin No. Enclosure Style Cat. No.
Red “ON” Pilot LightDiode Type
120V
109 Molded Plastic
198-PL13R
240V 198-PL14R
Red “ON” Pilot LightTransformer Type ➊
120V
All Metal Lift-off and Metal Hinged
198-PL21R ➋208V 198-PL25R ➋240V 198-PL22R ➋480V 198-PL23R ➋600V 198-PL24R ➋
Dual “ON” Pilot LightForward — RedReverse — White ➊
120V
105,106 Metal Hinged
198-PL21RW
240V 198-PL22RW
480V 198-PL23RW
Pilot Device Mounting Bracket(required when mounting pilot devices in metal lift-off enclosures)
105, 109, 120E Metal Lift-off 198-BR1
Control Circuit TransformerWith Top-Mounted Fuse Block All Metal Lift-off and Metal
Hinged 1497-_ _ P
Control Circuit Fuse BlockFor Class CC Rejection Type Fuses (Fuses Not Included) All Metal Lift-off and Metal
Hinged 1491-R162
Grounding Bushing Adapts to 1/2″ N.P.T., PG 16.5 & BS20 mm threads 109 Molded Plastic 198-GR1
Single Pole N.O. Auxiliary Contact for Disconnect Switch 106, 112, 132 Metal Hinged 195-GA10 ➌
Fuse Cover for Disconnect Switch
106,112,132-C09…C23
Metal Hinged
194R-FCA2
106,112,132-C30…C43 194R-FCJ60
106,112,132-C60…C72 194R-FCC1 ➍
Closing ButtonFor 22.5mm Round Panel Hole All All 198-N1
“OFF-ON” Selector Switch2-Position Maintained All
Metal Hinged &
Lift-off198-MT3
271
Bulletin 100 LineAccessories — Field Installed
Accessories, Continued
(For Bulletins 105, 106, 109, 112, 113, 120E, 132, and 133)Description For Use With Cat. No. Enclosure Style Cat. No.
“HAND-OFF-AUTO”Selector Switch3-Position Maintained, Includes Legend Plate
AllMetal Hinged
& Lift-off
198-MT1
“FORWARD-OFF-REVERSE”Selector Switch3-Position Maintained
105,106Metal Hinged
& Lift-off
198-MT2
“START” Push ButtonFlush green “I/START” 109-C09…C23 Molded Plastic 198-MS10
“STOP/RESET” Push ButtonExtended red “STOP/RESET” 109-C09…C23 Molded Plastic 198-MS11
“STOP” Push ButtonFlush red “STOP” 109-C09…C23 Molded Plastic 198-MS12
“ON” Push ButtonFlush green “ON” 109-C09…C23 Molded Plastic 198-MS19
“OFF/RESET” Push ButtonExtended red “OFF/RESET” 109-C09…C23 Molded Plastic 198-MS20
“OFF” Push ButtonExtended red “OFF” 109-C09…C23 Molded Plastic 198-MS21
“START-STOP” Push ButtonFlush green “I/START”Extended red “O/STOP”
105, 109, and 120E Metal Lift-off 198-MS3
“START” Push ButtonFlush green “START” All Metal Hinged 198-MS13
“ON-OFF” Push Button 105, 109, and 120E Metal Lift-off 198-MS6
“FORWARD, REVERSE-STOP” Push Button 105 Metal Lift-off 198-MS7
Bulletin 100 LineAccessories — Field Installed
272
Accessories, Continued
(For Bulletins 105, 106, 109, 112, 113, 120E, 132, and 133)
Description For Use WithCat. No. Enclosure Style Cat. No.
“HIGH, LOW-STOP” Push Button 120E Metal Lift-off 198-MS8
“FAST, SLOW-STOP” Push Button 120E Metal Lift-off 198-MS9
“STOP” Push ButtonExtended red “STOP” All Metal Hinged 198-MS14
“ON” Push ButtonFlush green “ON” All Metal Hinged 198-MS15
“OFF” Push ButtonExtended red “OFF” All Metal Hinged 198-MS16
“FORWARD, REVERSE-STOP”Push Buttons 105, 106 Metal Hinged 198-MS17
“HIGH, LOW-STOP” Push Buttons 120E Metal Hinged 198-MS18
“RESET” Push Button All Metal Hinged 198-MR6
“RESET” Push Button 109 Molded Plastic 198-MR5
“RESET” Push Button 105, 109, 120E Metal Lift-off 198-MR3
273
Bulletin 198EIEC Enclosures
Product Selection
IEC Enclosures
➊ Without control circuit transformer.➋ With control circuit transformer.
➌ Without control circuit transformer.➍ With control circuit transformer.
IP42 (Type 1) — General Purpose Molded Plastic Lift-Off EnclosuresBulletin No.
Cat. No.105 106 109 112 113 120E— — C09…C23 — — — 198E-AAC845
IP66 (Type 4, 4X, 12) — Raintight, Dusttight, Corrosion-Resistant Molded Plastic EnclosuresBulletin No.
Cat. No.105 106 109 112 113 120E— — C09…C23 — — — 198E-AKC845
IP42 (Type 1) — General Purpose Metal Lift-Off EnclosuresBulletin No.
Cat. No. Mounting Plate Cat. No.105 106 109 112 113 120E — — C09…C23 ➊ — — — 198E-BA966 —
C09…C23 ➊ — — — — C09…C23 ➊ 198E-BA996 —
— —C30,C37,C43 ➊C09,C12,C16 ➋
C23 ➋— — — 198E-BA1176 —
C30,C37,C43 ➊C09,C12,C16 ➋
C23 ➋— C30,C37,C43➋ — —
C30,C37,C43 ➊C09,C12,C16 ➋
C23 ➋198E-BA11116 —
— — C60…C72 ➊ — — — 198E-BA1278 —C60…C72 ➊
— C60…C72 ➋ — —C60…C72 ➊
198E-BA12138 —C30,C37,C43 ➋ C30,C37,C43➋
— — C85 ➊➋ — — — 198E-BA23108 198E-P2310
IP42 (Type 1) — General Purpose Metal Hinged EnclosuresBulletin No.
Cat. No. Mounting Plate Cat. No.105 106 109 112 113 120E— — — C09…C23 ➌➍ — — 198E-DA1488T 198E-P148T— C09…C43 ➌➍ — C30…C43 ➌➍ — — 198E-DA14168T 198E-P1416T
IP66 (Type 3/4/12) — Raintight, Dusttight, Metal Hinged Enclosures
Bulletin No.Cat. No. Mounting Plate Cat. No.
105 106 109 112 113 120E
C09…C23 ➌ — — — — C09…C23 ➌ 198E-DF10106 198E-P1010
— —C09…C43 ➌
— — — 198E-DF1286 198E-P128C09…C23 ➍
C09…C23 ➍— C30…C43 ➍ — —
C09…C23 ➍198E-DF12126 198E-P1212
C30…C43 ➌ C30…C43 ➌
— — C60…C72 ➌ — — — 198E-DF1488 198E-P148
C30…C43 ➍— C60…C72 ➍ — —
C30…C43 ➍198E-DF14168 198E-P1416
C60…C72 ➌ C60…C72 ➌
— — — C09…C23 ➌➍ — — 198E-DF1488T 198E-P148T
— C09…C43 ➌➍ — C30…C43 ➌➍ — — 198E-DF14168T 198E-P1416T
Molded Plastic Lift-Off Metal Lift-Off Metal Hinged Enclosure
Bulletin 100 LineOverload Relay Code Selection
274
Overload Relay Selection
MCS-E1 Overload Relay for 3∅ Applications: Phase Loss Protection, Class 10 or 20
➊ Starter Cat. Nos. listed have Class 10 overload relays. To order Class 20 overload relays, change the overload relay from A1_ to A2_. Example: Cat. No. 105-C09ABA1A becomes Cat. No. 105-C09ABA2A.
➋ Starter Cat. Nos. listed have Class 10 overload relays. To order Class 20 overload relays, change the overload relay from A4_ to A5_. Example: Cat. No. 105-C09ABA4A becomes Cat. No. 105-C09ABA5A.
MCS-E1 Overload Relay for 1∅ Applications: Class 10 or 20
➊ Starter Cat. Nos. listed have Class 10 overload relays. To order Class 20 overload relays, change the overload relay from S1_ to S2_. Example: Cat. No. 105-C09ABS1A becomes Cat. No. 105-C09ABS2A.
➋ Starter Cat. Nos. listed have Class 10 overload relays. To order Class 20 overload relays, change the overload relay from S4_ to S5_. Example: Cat. No. 105-C09ABS4A becomes Cat. No. 105-C09ABS5A.
MCS-E2 Overload Relay: Auto/Manual Reset, Selectable Trip Class 10, 15, 20 or 30, Phase Loss, Ground Fault, and Jam Protection
➊ Not available on Bulletin 109 Molded Plastic Enclosed Starters.
MCS E3 Overload RelayConsult your local Allen-Bradley distributor for price, availability, and dimensions.
For Use with Bulletin 105, 106, 109, 112, 113, 120E, 132 and 133
Full LoadCurrent Adjustment
Range (A)
3∅ OverloadRelay Code
Manual Reset ➊
3∅ OverloadRelay Code
Auto/Manual Reset ➋
C23 C16C12 C09
0.1…0.32 A1A A4A
0.32…1.0 A1C A4C
1.0…2.9 A1D A4D
1.6…5.0 A1E A4E
C30,C37 3.7…12 A1F A4F
12…32 A1G A4G
C30,C37 12…37 A1H A4H
C43 14…45 A1J A4J
C85 C72 C60 26…85 A1K A4K
All Sizes — No overload relay XXX XXX
For Use with Bulletin 105, 106, 109, 112, 113, 120E, 132 and 133
Full LoadCurrent Adjustment Range
(A)
1∅ OverloadRelay Code
Manual Reset ➊
1∅ OverloadRelay Code
Auto/Manual Reset ➋
C23 C16C12 C09
2….7 S1A S4A
5…15 S1B S4B
12…32 S1C S4C
C30,C37 12…37 S1D S4D
C43 14…45 S1F S4F
C85 C72 C60 26…85 S1H S4H
All Sizes - No overload relay XXX XXX
For Use with Bulletin105, 106, 109, 112, 113, 120E, 132
and 133
Full LoadCurrent
Range (A)
OverloadRelayCode
For Use with Cat. No.105, 106, 109, 112, 113, 120, 132 and 133 ➊
Full LoadCurrent Range
(A)
OverloadRelayCode
C23 C16C12 C09
0.1….32 B1A C435…15 B1S
C30, C37 14…45 B1J
0.32…1.0 B1C23…75 B1M
C85 C72 C6060…85 B1N
1.0…2.9 B1D
1.6…5.0 B1E
3.7…12 B1F
12…32 B1G
All Sizes — No overload relay XXX
275
Bulletin 100 LineOverload Relay Code Selection
Overload Relay Code Selection, Continued
Bimetallic Overload Relay: Auto/Manual Reset, Class 10
➊ Not available on Bulletin 109 Molded Plastic Enclosed Starters.
For Use With Bulletin105, 106, 109, 112, 113, 120E, 132 and 133 ➊
Full Load Current
Range (A)
Overload Relay Code
For Use With Cat. No.105, 106, 109, 112, 113, 120, 132 and 133
Full Load Current
Range (A)
Overload Relay Code
C37 C30C23
C16 C12C09
0.10…0.16 TA16
C72C60
C43 C37 30…45 TC45
0.16…0.24 TA24
C85
45…60 TC60
0.24…0.40 TA40 60…75 TC75
0.40…0.60 TA60 70…90 TC90
0.60…1.0 TB10
1.0…1.6 TB16
1.6…2.4 TB24
2.4…4.0 TB40
4…6 TB60
6…10 TC10
10…16 TC16
16…24 TC24
C60 C43 18…30 TC30
All Sizes — No Overload Relay XXX
Bulletin 100 LineModifications — Factory Installed
276
Modifications
Full Voltage Non-Reversing Starters and Lighting Contractors (Bulletins 109, 100L)Listed on this and the following pages are factory-installed modifications and special features which are available for the low voltage (600V maximum) starters listed in this catalog. To order, add a dash followed by the suffix number listed in these tables to the end of the product Cat. No. and add the price addition to the base price. Example: Cat. No. 109-C09ADA1E-1
Non-Reversing Circuit Breaker Combination Starters (Bulletin 113, 133)
A=Available OptionNA=Not Available
➊ Transformer Type.➋ When ordering in Canada, use suffix 6. Primary fusing is not required by the Canadian Electrical Code.
Description of Modification Suffix Code
Enclosure Design C09 C12 C16 100L-C20 C23 C30 C37 C43 C60 C72 C85
START-STOP Push Button 1Plastic Lift-off A A A NA A NA NA NA NA NA NAMetal Lift-off A A A NA A A A A A A AMetal Hinged A A A NA A A A A A A A
ON-OFF Push Button 1EPlastic Lift-off A A A NA A NA NA NA NA NA NAMetal Lift-off A A A A A A A A A A AMetal Hinged A A A A A A A A A A A
HAND-OFF-AUTO Selector Switch 3
Metal Lift-off A A A A A A A A A A AMetal Hinged A A A A A A A A A A A
OFF-ON Selector Switch 3E
Metal Lift-off A A A A A A A A A A AMetal Hinged A A A A A A A A A A A
Red Pilot Light ➊ 4RMetal Lift-off A A A A A A A A A A AMetal Hinged A A A A A A A A A A A
Red LED Pilot Light (120V) 4R1 Plastic Lift-off A A A NA A NA NA NA NA NA NARed LED Pilot Light (240V) 4R2 Plastic Lift-off A A A NA A NA NA NA NA NA NAControl Circuit Transformer2 Primary and 1 Secondary Fuse Provided (Standard Capacity)
6P➋Metal Lift-off A A A A A A A A A A A
Metal Hinged A A A A A A A A A A A
External Reset 7Plastic Lift-off A A A NA A NA NA NA NA NA NAMetal Lift-off A A A NA A A A A A A AMetal Hinged A A A NA A A A A A A A
Control Circuit Fuse Block2 Fuses Provided 22
Metal Lift-off A A A A A A A A A A AMetal Hinged A A A A A A A A A A A
Additional 1 N.O. – 1 N.C. (Side Mount) Auxiliary Contact on Contactor (100L only)
90Metal Lift-off NA NA NA A NA NA NA NA NA NA NA
Metal Hinged NA NA NA A NA NA NA NA NA NA NA
Additional 1 N.O. – 1 N.C. (Side Mount) Auxiliary Contact on Contactor
901Metal Lift-off A A A A A A A A A A A
Metal Hinged A A A A A A A A A A A
Additional 1 N.O. – 1 N.C. (Front Mount) Auxiliary Contact on Contactor
901TMetal Lift-off A A A A A A A A A A A
Metal Hinged A A A A A A A A A A A
Description of Modification Suffix Code
Enclosure Design C09 C12 C16 C23 C30 C37 C43 C60 C72 C85
START-STOP Push Button (113 Only) 1 ALL NA NA NA NA A NA A A A NAHAND-OFF-AUTO (113 Only) 3 ALL NA NA NA NA A NA A A A NARed Pilot Light ➊ 4R ALL NA NA NA NA A NA A A A NAControl Circuit Transformer 2 Primary and 1 Secondary Fuse Provided (Standard Capacity) 6P ➋ ALL NA NA NA NA A NA A A A NA
External Reset 7 ALL NA NA NA NA A NA A A A NAControl Circuit Fuse Block 2 Fuses Provided 22 ALL NA NA NA NA A NA A A A NAAdditional 1 N.O. - 1 N.C. (Side Mount) Auxiliary Contact on Contactor 901 ALL NA NA NA NA A NA A A A NA
Additional 1 N.O. - 1 N.C. (Front Mount)Auxiliary Contact on Contactor 901T ALL NA NA NA NA A NA A A A NA
277
Bulletin 100 LineModifications — Factory Installed
Modifications, Continued
Full Voltage Reversing and Multi-Speed Starters (Bulletins 105, 120E)
Reversing and Non-Reversing Fusible Combination Starters (Bulletins 106, 112, 132)
A=Available OptionNA=Not Available
➊ Transformer Type.➋ When ordering in Canada, use suffix 6. Primary fusing is not required by the Canadian Electrical Code.
Description of Modification Suffix Code Enclosure Design C09 C12 C16 C23 C30 C37 C43 C60 C72 C85
FOR-REV-STOP Push Buttons (105 Only) 1Metal Lift-off A A A A A A A A A NAMetal Hinged A A A A A A A A A A
HIGH-LOW-STOP Push Buttons (120E Only) 1Metal Lift-off A A A A A A A A A NAMetal Hinged A A A A A A A A A A
FOR-OFF-REV Selector Switch (105 Only) 3Metal Lift-off A A A A A A A A A NAMetal Hinged A A A A A A A A A A
HIGH-OFF-LOW Selector Switch (120E Only) 3Metal Lift-off A A A A A A A A A NAMetal Hinged A A A A A A A A A A
Red FOR/ White REV Pilot Lights ➊ (105 Only) 4RW Metal Hinged
A A A A A A A A A AA A A A A A A A A A
Red HIGH/White LOW Pilot Lights ➊(120E Only) 4RW Metal Hinged
A A A A A A A A A AA A A A A A A A A A
Control Circuit Transformer2 Primary and 1 Secondary Fuse Provided(Standard Capacity)
6P ➋ ALL A A A A A A A A A A
1 External Reset (105 Only) 7 ALL A A A A A A A A A A2 External Resets (120E Only) 7 ALL A A A A A A A A A AControl Circuit Fuse Block 2 Fuses Provided 22 ALL A A A A A A A A A AAdditional 1 N.O. – 1 N.C. (Side Mount) Auxiliary Contact on Each Contactor 901 ALL A A A A A A A A A A
Additional 1 N.O. – 1 N.C. (Front Mount) Auxiliary Contact on Each Contactor 901T ALL A A A A A A A A A A
Description of Modification Suffix Code
Enclosure Design C09 C12 C16 C23 C30 C37 C43 C60 C72 C85
START-STOP Push Button (112 Only) 1 ALL A A NA A A NA A A A NAFOR-REV-STOP Push Buttons (106 Only) 1 ALL A A NA A A NA A A A NAHAND-OFF-AUTO Selector Switch (112 Only) 3 ALL A A NA A A NA A A A NAFOR-REV-STOP Selector Switch (106 Only) 3 ALL A A NA A A NA A A A NARed Pilot Light ➊ 4R ALL A A NA A A NA A A A NARed FOR/ White REV Pilot Lights ➊ (106 Only) 4RW ALL A A NA A A NA A A A NAControl Circuit Transformer 2 Primary and 1 Secondary Fuse Provided (Standard Capacity) 6P ➋ ALL A A NA A A NA A A A NA
External Reset 7 ALL A A NA A A NA A A A NAFuse Cover For Disconnect Switch 8 ALL A A NA A A NA A A A NAControl Circuit Fuse Block 2 Fuses Provided 22 ALL A A NA A A NA A A A NA
N.O. Auxiliary Contact On Disconnect Switch 98 ALL A A NA A A NA A A A NA
Additional 1 N.O. – 1 N.C. (Side Mount) Auxiliary Contact on Contactor (112 and 132 Only) 901 ALL A A NA A A NA A A A NA
Additional 1 N.O. – 1 N.C. (Side Mount) Auxiliary Contact on each Contactor (106 Only) 901 ALL A A NA A A NA A A A NA
Additional 1 N.O. – 1 N.C. (Front Mount) Auxiliary Contact on Contactor (112 and 132 Only) 901T ALL A A NA A A NA A A A NA
Additional 1 N.O. – 1 N.C. (Front Mount) Auxiliary Contact on each Contactor (106 Only) 901T ALL A A NA A A NA A A A NA
Bulletin 100 LineIEC Enclosures and Starters
278
Approximate Dimensions
Plastic Lift-off Enclosure Type 1 (IP42)Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Plastic Lift-off Enclosure Type 12/4/4X (IP66)
Bulletin 109 Metal Lift-Off Enclosures Type 1 (IP42)
Contactor Size A Height B Width C Depth D E F GIP42 (Type 1) General Purpose Molded Plastic Enclosure for Bulletin 109 (Transformer N/A)
C09…C23 205(8-5/64)
96.6(3-47/64)
131(5-5/32)
185(7-9/32)
10(25/64)
27(1-3/64)
185(7-9/32)
Contactor Size A Height B Width C Depth D E F GIP66 (Type 4/4X) Water-Tight Corrosion-Resistant Molded Plastic Enclosure for Bulletin 109 (Transformer N/A)
C09…C23 205(8-5/64)
96.6(3-47/64)
131(5-5/32)
185(7-9/32)
10(25/64)
27(1-3/64)
185(7-9/32)
Contactor size A Height B Width C Depth D E FIP42 (Type 1) General Purpose Metal Lift-Off Enclosure for Bulletin 109 (Without Transformer)
C09…C23 220(8-21/32)
140(5-33/64)
152(5-31/32)
175(6-57/64)
95(3-3/4)
22.5(57/64)
C30…C43 290(11-27/64)
188(7-23/64)
152(5-31/32)
245(9-41/32)
140(5-33/64)
24(15/16)
C60…C72 315(12-27/64)
188(7-23/64)
203(8)
270(10-5/8)
140(5-33/64)
24(15/16)
C85 585(23-1/32)
257(10-7/64)
203(8)
540(21-17/64)
210(8-17/64)
23.5(59/64)
IP42 (Type 1) General Purpose Metal Lift-Off Enclosure for Bulletin 109 (With Transformer)
C09…C23 290(11-27/64)
188(7-23/64)
152(5-31/32)
245(9-41/64)
140(5-33/64)
24(15/16)
C30…C43 290(11-27/64)
270(10-5/8)
152(5-31/32)
245(9-41/32)
225(8-55/64)
22.5(57/64)
C60…C72 315(12-27/64)
325(12-51/64)
203(8)
270(10-5/8)
280(11-1/64)
22.5(57/64)
C85 585(23-1/32)
257(10-7/64)
203(8)
540(21-17/64)
210(8-17/64)
23.5(59/64)
B
F
D
E
Back View.272
(9/32) .212
(7/32)
A
CPilot Light K.O.
16.5(.650 dia.)
Push Button K.O.22.3
(.898 dia.)
External Reset K.O.22.13
(.898 dia.)
G G
X
.272(9/32)
.212(7/32) X
A
E
B
F
D
23.4(.921)
C
7.1 (.28) DIA.FOR 1/4 OR M6 SCREW3 MTG. HOLES
Metal Lift-Off
279
Bulletin 100 LineIEC Enclosures and StartersApproximate Dimensions, Continued
Bulletins 105 and 120E Metal Lift-Off Enclosures Type 1 (IP42)Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Bulletins 106, 112, and 113 Metal Hinged Enclosures Type 1 (IP42)
Contactor size A Height B Width C Depth D E F G (dia)
IP42 (Type 1) General Purpose Metal Lift-off Enclosure for Bulletin 105 and 120E (Without Transformer)
C09…C23 220(8-21/32)
235(9-1/4)
152(5-31/32)
175(6-57/64)
190(7-31/64)
22.5(57/64) —
C30…C43 290(11-27/64)
270(10-5/8)
152(5-31/32)
245(9-41/32)
225(8-55/64)
22.5(57/64) —
C60…C72 315(12-27/64)
325(12-51/64)
203(8)
270(10-5/8)
280(11-1/64)
22.5(57/64) —
C85 610(24)
406(16)
230(9-1/16)
572(22-1/2)
368(14-1/2)
19(3/4)
11(7-16)
IP42 (Type 1) General Purpose Metal Lift-Off Enclosure for Bulletin 105 and 120E (With Transformer)
C09…C23 290(11-7/64)
270(10-5/8)
152(5-31/32)
245(9-41/32)
225(8-55/64)
22.5(57/64) —
C30…C43 315(12-27/64)
325(12-51/64)
203(8)
270(10-5/8)
280(11-1/64)
22.5(57/64) —
Contactor Size A Height B Width C Depth D E F G (Dia.)IP42 (Type 1) General Purpose Metal Hinged Enclosure for Bulletin 106 (With and Without Transformer)
C09…C43 350(13-25/32)
400(15-3/4)
210(8-9/32)
315(12-13/32)
178(7)
111(4-3/8)
5.5(7/32)
C60…C72 610(24)
406(16)
230(9-1/06)
572(22-1/2)
368(14-1/2)
19(3/4)
11(7/16)
IP42 (Type 1) General Purpose Metal Hinged Enclosure for Bulletin 112 (With and Without Transformer)
C09…C23 350(13-25/32)
200(7-7/8)
210(8-9/32)
315(12-13/32)
76(3)
64(2-1/2)
5.5(7/32)
C30…C43 350(13-25/32)
400(15-3/4)
210(8-9/32)
315(12-13/32)
178(7)
111(4-3/8)
5.5(7/32)
C60…C72 610(24)
406(16)
230(9-1/06)
572(22-1/2)
368(14-1/2)
19(3/4)
11(7/16)
IP42 (Type 1) General Purpose Metal Hinged Enclosure for Bulletin 113 (With and Without Transformer)
C30…C72 610(24)
406(16)
230(9-1/06)
572(22-1/2)
368(14-1/2)
19(3/4)
11(7/16)
A
E
B
F
D
23.4(.921)
C
7.1 (.28) DIA.FOR 1/4 OR M6 SCREW3 MTG. HOLES
Metal Lift-Off
D
F G
B
A
E
C
Bulletin 100 LineIEC Enclosures and Starters
280
Approximate Dimensions, Continued
Bulletin 109 Metal Hinged Enclosures Type 3/4/12 (IP66)Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Bulletins 105 and 120E Metal Hinged Enclosures Type 3/4/12 (IP66)
Contactor Size A Height B Width C Depth D E F G (Dia.)IP66 (Type 3/4/12) Metal Hinged Enclosure for Bulletin 109 (Without Transformer)
C09…C43 300(11-13/16)
200(7-7/8)
160(6-5/16)
265(10-7/16)
76(3)
62(2-7/16)
5.5(7/32)
C60…C72 350(13/25/32)
200(7-7/8)
210(8-9/32)
315(12-13/32)
76(3)
64(2-1/2)
5.5(7/32)
C85 762(30)
305(12)
276(10-7/8)
724(28-1/2)
267(10-1/2)
19(3/4)
11(7/16)
IP66 (Type 3/4/12) Metal Hinged Enclosure for Bulletin 109 (With Transformer)
C09…C23 300(11-13/16)
200(7-7/8)
160(6-5/16)
265(10-7/16)
76(3)
62(2-7/16)
5.5(7/32)
C30…C43 300(11-13/16)
300(11-13/16)
160(6-5/16)
236(9-5/16)
178(7)
61(2-13/32)
5.5(7/32)
C60…C72 350(13-25/32)
400(15-3/4)
210(8-9/32)
315(12-13/32)
178(7)
111(4-3/8)
5.5(7/32)
C85 610(24)
406(16)
230(9-1/16)
572(22-1/2)
368(14-1/2)
19(3/4)
11(7/16)
Contactor Size A Height B Width C Depth D E (Mtg.) F G (Dia.)IP66 (Type 3/4/12) Metal Hinged Enclosure for Bulletins 105 and 120E (Without Transformer)
C09…C23 250(9-13/16)
250(9-13/16)
160(6-5/16)
186(7-5/16)
76(3)
87(3-13/32)
5.5(7/32)
C30…C43 300(11-13/16)
300(11-13/16)
160(6-5/16)
236(9-5/16)
178(7)
61(2-13/32)
5.5(7/32)
C60…C72 350(13-25/32)
400(15-3/4)
210(8-9/32)
315(12-13/32)
178(7)
111(4-3/8)
5.5(7/32)
C85 610(24)
406(16)
230(9-1/06)
572(22-1/2)
368(14-1/2)
19(3/4)
11(7/16)
IP66 (Type 3/4/12) Metal Hinged Enclosure for Bulletins 105 and 120E (With Transformer)
C09…C23 300(11-13/16)
300(11-13/16)
160(6-5/16)
236(9-5/16)
178(7)
61(2-13/32)
5.5(7/32)
C30…C43 350(13-25/32)
400(15-3/4)
210(8-9/32)
315(12-13/32)
178(7)
111(4-3/8)
5.5(7/32)
C60…C72 610(24)
406(16)
230(9-1/06)
572(22-1/2)
368(14-1/2)
19(3/4)
11(7/16)
C85 762(30)
610(24)
281(11-1/16)
724(28-1/2)
572(22-1/2)
19(3/4)
11(7/16)
D
F G
B
A
E
C
D
F G
B
A
E
C
281
Bulletin 100 LineIEC Enclosures and StartersApproximate Dimensions, Continued
Bulletins 106, 112 and 113 Metal Hinged Enclosures Type 3/4/12 (IP66)Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Bulletins 132 and 133 Metal Hinged Enclosures with Extra Space Type 3R (IP32)
Contactor Size A Height B Width C Depth D E (Mtg.) F G (Dia.)IP66 (Type 3/4/12) Metal Hinged Enclosure for Bulletin 106 (With and Without Transformer)
C09…C43 350(13-25/32)
400(15-3/4)
210(8-9/32)
315(12-13/32)
178(7)
111(4-3/8)
5.5(7/32)
C60…C72 610(24)
406(16)
230(9-1/06)
572(22-1/2)
368(14-1/2)
19(3/4)
11(7/16)
IP66 (Type 3/4/12) Metal Hinged Enclosure for Bulletin 112 (With and Without Transformer)
C09…C23 350(13-25/32)
200(7-7/8)
210(8-9/32)
315(12-13/32)
76(3)
64(2-1/2)
5.5(7/32)
C30…C43 350(13-25/32)
400(15-3/4)
210(8-9/32)
315(12-13/32)
178(7)
111(4-3/8)
5.5(7/32)
C60…C72 610(24)
406(16)
230(9-1/06)
572(22-1/2)
368(14-1/2)
19(3/4)
11(7/16)
IP66 (Type 3/4/12) Metal Hinged Enclosure for Bulletin 113 (With and Without Transformer)
C30…C72 610(24)
406(16)
230(9-1/06)
572(22-1/2)
368(14-1/2)
19(3/4)
11(7/16)
Contactor Size A Height B Width C Depth D E F G H J K
IP 32 (Type 3R) Rainproof Metal Hinged Enclosure for Bulletins 132 and 133 (With and Without Transformer)
C09…C43584(23)
320(12-19/32)
187(7-5/16)
711(28)
105(4-1/8)
108(4-1/4)
679(26-3/4)
667(26-1/4)
105(4-1/8)
105(4-1/8)
C60…C72864(34)
447(17-19/32)
238(9-5/16)
991(39)
105(4-1/8)
171(6-3/4)
959(37-3/4)
946(37-1/4)
105(4-1/8)
169(6-21/32)
B1101067(42)
762(30)
305(12)
1118(44)
686(27)
38(1-1/2)
1092(43)
1092(43)
— —
B180…B2501219(48)
914(36)
305(12)
1270(50)
686(27)
114(4-1/2)
1245(49)
1245(49)
— —
D
F G
B
A
E
C
JK
B
HD
A
EFG
6(15/64)
C 7.1(.28)
4 – 5.5 (.22) Dia.7.1 (.28) Mtg. Holes
4 – 5.5 (.218) Dia.Mtg. Holes
Bulletin 100-C/104-CIEC Renewal Parts
282
Renewal Parts
Coils
AC Standard Control Voltages AC Coil Code
100-C09…100-C16 100-C23…100-C37 100-C43 100-C60…100-C8550 Hz 60 Hz 50/60 Hz Cat. No. Cat. No. Cat. No. Cat. No.
12V Q TA006 TC006 TD006 TE00612V R TA404 TC404 TD404 TE404
24V J TA013 TC013 TD013 TE01324V K TA407 TC407 TD407 TE407
24V KJ TA855 TC855 TD855 TE85532V 36 V V TA481 TC481 TD481 TE48136V W TA410 TC410 TD410 TE41042V 48V X TA482 TC482 TD482 TE48248V Y TA414 TC414 TD414 TE414
48V KY TA860 TC860 TD860 TE860100V 100…110V 100V KP TA861 TC861 TD861 TE861110V 120V D TA473 TC473 TD473 TE473
110 V KD TA856 TC856 TD856 TE856120V P TA425 TC425 TD425 TE425127V S TA428 TC428 TD428 TE428200V 200…220V 200V KG TA862 TC862 TD862 TE862
208V H TA049 TC049 TD049 TE049200…220V 208…240V L TA296 TC296 TD296 TE296
200…230V KL TA864 TC864 TD864 TE864220V 240 V A TA474 TC474 TD474 TE474
220…230V F TA441 TC441 TD441 TE441230V KF TA851 TC851 TD851 TE851
230…240V VA TA440 TC440 TD440 TE440240V 277V T TA480 TC480 TD480 TE480
240V KA TA858 TC858 TD858 TE858347 V I TA065 TC065 TD065 TE065380 V E TA067 TC067 TD067 TE067
380…400V 440 V N TA071 TC071 TD071 TE071400V KN TA863 TC863 TD863 TE863
400…415V G TA457 TC457 TD457 TE457440V 480V B TA475 TC475 TD475 TE475
440V KB TA859 TC859 TD859 TE859500V M TA479 TC479 TD479 TE479550V 600V C TA476 TC476 TD476 TE476
283
Bulletin 100-C/104-CIEC Renewal Parts
Renewal Parts
Coils, Continued
➊ Voltage operating range: 0.65…1.3 x Us.➋ Voltage operating range: 0.7…1.25 x Us.
DC Standard Control Voltages DC Coil Code
100-C09…100-C16 100-C23…100-C37 100-C43 100-C60…100-C85
V DC Cat. No. Cat. No. Cat. No. Cat. No.9V➊ ZR TA766 TC766 TD766 —
9V Diode➊ DR — — — TE766M12V ZQ TA708 TC708 TD708 —
12V Diode DQ — — — TE708M24V➋ ZJ TA714 TC714 TD714 —
24V Diode➋ DJ TA714M TC714M TD714M TE714M36V ZW TA719 TC719 TD719 —
36V Diode DW — — — TE719M48V ZY TA724 TC724 TD724 —
48V Diode DY — — — TE724M60V ZZ TA774 TC774 TD774 —
60V Diode DZ — — — TE774M64V ZB TA727 TC727 TD727 —
64V Diode DB — — — TE727M72V ZG TA728 TC728 TD728 —
72V Diode DG — — — TE728M80V ZE TA729 TC729 TD729 —
80V Diode DE — — — TE729M110V ZD TA733 TC733 TD733 —
110V Diode DD — — — TE733M115V ZP TA734 TC734 TD734 —
115V Diode DP — — — TE734M125V ZS TA737 TC737 TD737 —
125V Diode DS — — — TE737M220V ZA TA747 TC747 TD747 —
220V Diode DA — — — TE747M230V ZF TA749 TC749 TD749 —
230V Diode DF — — — TE749F250V ZT TA751 TC751 TD751 —
250V Diode DT — — — TE751F
Bulletin 100-DIEC Renewal Parts
284
Accessories
Replacement coils for 100-D contactors
➊ Not available with 100-D140…D180.➋ Electronic replacement coils consist of coil bobbin, supply module, and possibly an external surge suppressor.➌ Not available with 100-D300.
AC StandardControl Voltages AC Coil
Code
100-D95…100-D180
100-D210…100-D300 100-D420 100-D630…
100-D860DC
StandardControlVoltages
DC CoilCode
100-D95…100-D140
100-D210…100-D300 100-D420 100-D630…
100-D860
50 Hz 60 Hz 50/60 Hz Cat. No. Cat. No. Cat. No. Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
Conventional AC Conventional DC24V — — K TG407 — — — 12V ZQ TG708 — — —— 24V — J TG013 — — — 24V ZJ TG714 — — —— — 24V ➊ KJ TG855 — — — 36V ZW TG719 — — —
32V 36V — V TG481 — — — 48V ZY TG724 — — —36V 42V — W TG410 — — — 60V ZZ TG774 — — —48V — — Y TG414 — — — 110V ZD TG733 — — —42V 48V — X TG482 — — — 125V ZS TG737 — — —— — 100V ➊ KP TG861 — — — 130V ZF TG738 — — —
110V 120V — D TG473 — — — 220V ZA TG761 — — —— — 110V ➊ KN TG856 — — — 240V ZL TG750 — — —— 208V — H TG049 — — — 250V ZT TG751 — — —— — 200V ➊ KG TG862 — — —— — 220V ➊ KL TG857 — — —
220…230V 240V — A TG441 — — —240V 277V — T TG480 — — —
— — 277V ➊ KT TG060 — — —— — 230V ➊ KF TG851 — — —— — 240V ➊ KA TG858 — — —
380…400V 440V — N TG071 — — —415V 480V — B TG475 — — —440V — — G TG478 — — —500V — — M TG479 — — —550V 600V — C TG476 — — —
Electronic AC ➋ Electronic DC ➋
50 Hz 60 Hz 50/60 Hz AC CoilCode Cat. No. Cat. No. Cat. No. Cat. No. DC
StandardControlVoltage
DC CoilCode Cat. No. Cat. No. Cat. No. Cat. No.— — 24V EJ TGE855 THE855 ➌ — —
— — 42…64V EY TGE864 THE864 TKE864 —— — 100V EP TGE861 THE861 TKE861 TJE861
24V EZJ TGE708 THE708 — —— — 110…130V ED TGE865 THE865 TKE865 TJE865— — 200V EG TGE862 THE862 TKE862 TJE862
48…72V EZY TGE779 THE779 TKE779 —— — 208…277V EA TGE866 THE866 TKE866 TJE866— — 380…415V EN — — — TJE867
110…130VEZD TGE780 THE780 TKE780 —
— — 380…500V EN TGE867 THE867 TKE867 —— — 440…480V EB TGE868 THE868 TKE868 TJE868 ED — — — TJE865— — 500V EM — — — TJE869
200…255VEZA TGE781 THE781 TKE781 —EA — — — TJE866
Conventional Coil
Electronic Coil
285
Bulletin 100-DIEC Renewal Parts
Renewal Parts
Description Coil For Use With Contactor Cat. No. Cat. No.
Arc Chambers for Contactors• For 3-Pole 100-D contactors
Conventional
100-D95100-D110100-D140100-D180
100-DA-95100-DA-110100-DA-140100-DA-180
Electronic
100-D95100-D110100-D140100-D180100-D210100-D250100-D300100-D420
100-DAE-95100-DAE-110100-DAE140100-DAE-180100-DAE-210100-DAE-250100-DAE-300100-DAE-420
Main Contacts for Contactors• Set for 3-Pole 100-D contactors
Conventional
100-D95100-D110100-D140100-D180
100-DC-95100-DC-110100-DC-140100-DC-180
Electronic
100-D95100-D110100-D140100-D180100-D210100-D250100-D300100-D420100-D630100-D860
100-DCE-95100-DCE-110100-DCE-140100-DCE-180100-DCE-210100-DCE-250100-DCE-300100-DCE-420100-DCE-630100-DCE-860
Terminal Hardware• Set of 6• Includes all hardware for line and load connections
100-D95…D110100-D140…D180100-D210…D420100-D630…D860
100-DTH110100-DTH180100-DTH420100-DTH860
Bulletin 100-GIEC Renewal Parts
286
Renewal Parts
Renewal Parts
Coils and Supply Modules
➊ Coils sold in pairs.
Description For use with Cat. No.
Arcing Chamber• For 3 poles
100-G550 100-AC550
100-G700, 100-G860 100-AC860
Arcing Chamber• For 1 pole 100-G1000, 100-G1200 100-AC1200
Main Contact Sets• Set for 1 pole
100-G550 100-CP550
100-G700 100-CP700
100-G860 100-CP860
100-G1000 100-CP1000
100-G1200 100-CP1200
Auxiliary Contact Block• Special two-pole design: 1 N.O. delayed make,
1 N.C.• N.O. delayed make contact used for operation of
the Feeder Group/Coil mechanism• One supplied standard with contactor
100-G1000100-G1200 100-EB11DC
AC StandardControl Voltages
DCStandardControl Voltages
Coil Code
100-G550 100-G700…100-G860 AC StandardControl Voltages
Coil Code
100-G1000…100-G1200
Coil Cat. No. ➊
Supply Module Cat.
No.
Coil Cat. No. ➊
Supply Module Cat.
No.
Coil Cat. No. ➊
Supply Module Cat. No.50/60 Hz 50/60 Hz
110…120V 100…110V KD TX734 TXS734 TY734 TYS734 110…115V KD TZ734 TZS734220…240V 200…220V KF TX747 TXS747 TY747 TYS747 220…230V KF TZ747 TZS747380…415V 345…380V KN TX779 TXS779 TY779 TYS779 380…400V KN TZ779 TZS779440…480V 400…440V KB TX780 TXS780 TY780 TYS780 440V KB TZ780 TZS780
31
32
43
44
287
Bulletin 100-GIEC Renewal Parts
Notes
Bulletin 100-GIEC Renewal Parts
288
Notes
289
Bulletin 100-GIEC Renewal Parts
Notes
Bulletin 100-GIEC Renewal Parts
290
Notes
www.rockwellautomation.com
Corporate HeadquartersRockwell Automation, 777 East Wisconsin Avenue, Suite 1400, Milwaukee, WI, 53202-5302 USA, Tel: (1) 414.212.5200, Fax: (1) 414.212.5201
Headquarters for Allen-Bradley Products, Rockwell Software Products and Global Manufacturing SolutionsAmericas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444Europe: Rockwell Automation SA/NV, Vorstlaan/Boulevard du Souverain 36-BP 3A/B, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640Asia Pacific: Rockwell Automation, 27/F Citicorp Centre, 18 Whitfield Road, Causeway Bay, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Headquarters for Dodge and Reliance Electric ProductsAmericas: Rockwell Automation, 6040 Ponders Court, Greenville, SC 29615-4617 USA, Tel: (1) 864.297.4800, Fax: (1) 864.281.2433Europe: Rockwell Automation, Brühlstraße 22, D-74834 Elztal-Dallau, Germany, Tel: (49) 6261 9410, Fax: (49) 6261 1774Asia Pacific: Rockwell Automation, 55 Newton Road, #11-01/02 Revenue House, Singapore 307987, Tel: (65) 351 6723, Fax: (65) 355 1733
Publication 100-SG003C-EN-P – February 2003 Copyright © 2003 Rockwell Automation. All rights reserved. Printed in USA.
DeviceNet is a trademark of the Open DeviceNet Vendors Association (ODVA).DeviceLogix and DeviceNet Starter Auxiliary are trademarks of Rockwell Automation.