BUILDING THE GREEN DATA CENTERTowards Best Practices and Technical Considerations
Rick Bauer, SNIA
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved. 2
SNIA Legal Notice
The material contained in this tutorial is copyrighted by the SNIA. Member companies and individuals may use this material in presentations and literature under the following conditions:
Any slide or slides used must be reproduced without modificationThe SNIA must be acknowledged as source of any material used in the body of any document containing material from these presentations.
This presentation is a project of the SNIA Education Committee.
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved. 3
Abstract
The green data center has moved from the theoretical to the realistic, with IT leaders being challenged to construct new data centers (or retrofit existing ones) with energy saving features, sustainable materials, and other environmental efficiencies in mind. This tutorial will survey the wide variety of options and issues that the data center designer must keep in mind in these matters, as well as illustrate how government regulation and certification will be affecting the data centers of the future. Analysis will include the US Green Building Council LEED standard, as well as other regulatory standards that are driving green data center construction.
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Presentation OutlineBuildings and Data Centers: Energy Drains & Gains What is the Green Data Center? Drivers for Green Data Centers Technology Options for Facilities New & Old What Facilities Folks Wish IT Folks Knew About Building ConstructionWhat IT Folks Wish Facilities Folks Knew About ITEmerging Standards
US, EU, Japan
Up Close: Green Data Center Examples Beyond Greening the Data Center: Toward Sustainable StorageBackup Slides: Bibliography, Links, Sources
4
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Drains and Gains
Our Buildings: Hungry for PowerSource: US Green Building Council, 2008
5
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Environmental Impact of Buildings
42
40
30
25
25
20
13
12
0 5 10 15 20 25 30 35 40 45
Energy Use
Atmospheric Emissions
Raw materials use
Solid Waste
Water Use
Water Effluents
Other Releases
Land Use
% of US Annual Impact
6
Systematic Evaluation and Assessment of Building Environmental Performance (SEABEP), paper for presentation to"Buildings and Environment", Paris, 9-12 June, 1997. Source: Levin, H. (1997)
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
The Impact of Buildings in the U.S.
Source: US Green Building Council, 2008
7
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Data Centers: Hungry for Power*
8
*http://www.sustainability.com/SF/home
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Concerns of Data Center Managers
9
“The Efficient Data Center: Improving Operational Economy & Availability, 2007 Data Center Users Group Conference”, p 2.
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
The Only Constant is Change
10
“The Efficient Data Center: Improving Operational Economy & Availability, 2007 Data Center Users Group Conference”, p 4.
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
U.S. 2011: $7.4 BILLION
U.S. 2006: $4.5 BILLION
11
An Inconvenient Bill:
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Storage Growth Versus Power & Cooling Cost Growth (1999-2011)
12
“The real costs to power and cool all the worlds external storage” by David Reinsel, Copyright ©2008 IDC, Framingham, MA. All rights reserved.
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Worldwide External Enterprise Storage Carbon Footprint, 2006-2011*
From “The real costs to power and cool all the worlds external storage” by David Reinsel, Copyright ©2008 IDC, Framingham, MA. All rights reserved.
*Includes HDDs effectively installed for the purpose of calculations. In other words, not all HDDs were shipped on January 1 of any given year.
13
2006 2007 2008 2009 2010 2011
HDD installed base (000)* 35,362 42,591 49,329 56,400 65,190 78,400
Average watts/HDD 12.9 12.9 12.3 10.9 9.9 8.6
HDD Billion kilowatt-hours (BkWh) 3.9 4.8 5.5 6.1 6.6 7.1
Additional non-HDD BkWh 3.9 4.8 5.5 6.1 6.6 7.1
Additional BkWh for Cooling 7.8 9.5 11.0 12.2 13.1 14.3
Total BkWh 15.5 19.0 22.0 24.3 26.2 28.5
Worldwide electricity costs/kWh ($) 0.07 0.07 0.08 0.08 0.09 0.09
Total costs of electricity ($B) 1.09 1.33 1.76 1.99 2.36 2.57
Pounds of CO2 (B) 24.1 29.5 34.1 37.7 40.7 44.2
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
EPA 2006 Report on Data CentersThe creation of standard metrics so data center operators can measure and assess their energy consumption and performance. Calling on the private-sector to conduct energy-efficiency assessments at their companies’ data centers, implement improvements and report energy performance.Distribution of “objective, credible information” on the performance of new technologies and their impact on data center energy consumption/performance.The development of standardized energy performance measures for data center equipment. More research by government and university researchers, along with utilities, to develop technologies and best practices for data center efficiency.The development of federal purchasing specifications for energy performance at outsourced data centers.Considering state and local regulations to measure data center energy consumption.Asking electric utilities to consider offering incentives to companies that run energy-efficient data centers.
14
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Data Center Power Draws
15
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Power Flow in the Data Center
16
The above data center is said to be 30% efficient, based on the fraction of the input power that actually goesto the IT load. For a more detailed understanding of where the power goes and how the different types ofequipment contribute to the load, consult APC White Paper #113, “Electrical Efficiency Modeling for DataCenters.”
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Electricity & Data Center Design: Separated at Birth?
Traditionally, electrical power usage has not been a typical design criterion for data centers.Expenses for data center power have not been tightly coupled to the data center performance criteria and ROI.According to the Uptime Institute, more than 60 percent of the power used to cool equipment in the data center is completely wasted. “Data centers that used to cost $10 million now cost $100 million,” says Jonathan Koomey, staff scientist at Lawrence Berkeley National Laboratory. “That kind of expenditure gets C-level attention.”
17
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
How Did IT Get this Way?*The billed electrical costs come after the charges are incurred and are not clearly linked to any particular decisions or operating practices. Therefore they are viewed as inevitable.Tools for modeling the electrical costs of data centers are not widely available and are not commonly used during data center design.The billed electrical costs are often not within the responsibility or budget of the data center operating group.The electrical bill for the data center may be included within a larger electrical bill and may not be available separately.Decision makers are not provided sufficient information during planning and purchasing decisions regarding the electrical cost consequences.
18
*Neil Rasmussen, Implementing Energy Efficient Data Centers, American Power Conversion, used by permission
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
What is the “OSI Stack” for a Data Center? Complexity Issues
Applications andPlatforms
Applications
Application Services
Common Operating Environment
Operating Systems
Compute Platforms
Data Center
Data Storage and Retention
Switch Infrastructures
Non-Electric IT Components
Physical IT Spaces
Mechanical & Electrical Distribution
Mechanical & Electrical Supply
Building Architecture
Electrical and Telecomm Utilities
In-Country Real Estate
International Geography
19
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
What is the Green Data Center?
A green data center is a repository for the storage, management, and dissemination of data in which the mechanical, lighting, electrical and computer systems are designed for maximum energy efficiency and minimum environmental impact.
20
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Reasons to Adopt a Green Data Center Strategy
21
Source: Aberdeen Group, January 2008
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Tough Choices: Power Reduction Options?
1. Those that avoid energy consumption, but do not reduce power requirements?
2. Those that allow the reduction of installed power capacity?
22
Answer? : 2Any avoidance of energy consumption, engineered when configuring total power capacity in the design of a data center, is worth approximately twice as much as temporary consumption avoidance.
--“A watt in time saves…err…two.”
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
-2.84WReduction
A one watt reduction in a server component results in a 2.84
cascaded wattage reduction in the data center ecosystem
The Cascade Effect
Source: “Energy Logic: Reducing Data Center Energy Consumption byCreating Savings that Cascade Across Systems”, Emerson Network Power, ©2008
Servercomponent
1 Watt saved here
additional .18 Watt here
DC-DC
-1.0W
and .04Watt here
Powerdistribution
-1.49W
and .14Watt here
UPS
-1.53W
and 1.07Watt here
Cooling
-1.67W
and .10 Watt here
BuildingSwitchgear/ Transformer
-2.74W
and .31 Watt here
AC-DC
-1.18W
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Technology Options for Data Center Managers
Thermal Zone MappingUtilizing allows for heat exchange options, optimized deployment of coolingOngoing discussions of optimal temperature for equipment
24
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved. 25
Storage-specific Power/Cooling data
Each component of a Storage system has Power and Cooling requirements
Understand “Idle” (stand-by) vs. “Loaded” (R/W)Label ratings are usually peak power required
If you design using this data, your power/cooling equipment will be (grossly) over-built (Bad!), and CapEx will suffer.Operating equipment below its rated temperature offers little (no?) benefits (except for Operators!)
Some manufacturers offer better data or design infoIf you really want to know, you have to instrument in order to get real measurements.Or, you could wait to see what SNIA comes out with…
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Technology Options for Data Center Managers:
Virtualization software with power resource management features allows the administrator to power down inactive servers during non peak hours so workloads can be migrated and consolidated to fewer servers while the others remain in standby or sleep mode. As a rule of thumb, using virtualization and efficient Power & Cooling techniques and best practices can provide savings of the order of $700/year/workload. In the storage area, following some best practices like data consolidation on fewer higher capacity drives, deduplication, space efficient snapshots and thin provisioning can effectively provide savings upwards of $2250/year/TB of useable data.
26
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Storage Energy Efficiency Strategies
Increase disk utilizationDynamic provisioning (30-40%, or even > 60%)Reduce or eliminate hot spotsLoad balancingReduce physical resources requiredData compression (2:1 or 3:1)Eliminate redundant dataData de-duplication (up to 20:1)
Optimize cost effectiveness and reduce power requirementsTiered storage managementReduce data retention costs and power requirementsActive archive softwareDecrease power requirement densitySpin-down of inactive disks
27
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Technology Options for Data Center Managers: Available Today
28
Source: Aberdeen Group, January 2008
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Energy Savings Actions & ROI
Energy Saving Action
Savings Independent of Other Actions
Energy Savings with the Cascade Effect
ROI
Savings (kW)
Savings (%) Savings (kW) Savings (%) Cumulative
Savings (kW)
Lower power processors 111 10% 111 10% 111 12-18 months
High-efficiency power supplies 141 12% 124 11% 235 5 to 7 months
Power management features 125 11% 86 8% 321 Immediate
Blade servers 8 1% 7 1% 328 TCO reduced 38%*
Server virtualization 156 14% 86 8% 414 TCO reduced 63%**
415V AC power distribution 34 3% 20 2% 434 2 to 3 months
29*Source for blade TCO: IDC*Source for virtualization TCO: VMware
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Energy Savings Actions & ROI (cont.)
Energy Saving Action
Savings Independent of Other Actions
Energy Savings with the Cascade EffectROI
Savings (kW)
Savings (%) Savings (kW) Savings (%) Cumulative
Savings (kW)
Cooling best practices
24 2% 15 1% 449 4 to 6 months
Variable capacity cooling: variable speed fan drives
79 7% 49 4% 498 4 to 10 months
Supplementalcooling 200 18% 72 6% 570 10 to 12
months
Monitoring & optimization: Cooling units synchronized
25 2% 15 1% 585 3 to 6 months
30
Source: “Energy Logic: Reducing Data Center Energy Consumption by Creating Savings that Cascade Across Systems.” ©2008 Emerson Network Power. Used by permission.
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
DIY: The DOE Energy Profilerdcpro.ppc.com
31
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
What Facilities Folks Wish IT Folks Knew About Building Construction
We’ve got more than IT to worry about.The world does not revolve around IT.Tell us what you want, what you really, really want.Do you not think we don’t know our jobs?We really ought to talk more often.The only tool our CFO has to manage the power expenses in our facilities is the electric bill.We can’t keep doing this forever.
32
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved. 33
Facilities vs. IT in the Datacenter
Who represents IT to the Facilities staff?Right now, the whole conversation is about Servers!Try to find “Storage” mentioned in any recent article on power/cooling problems in the datacenter….Try to find “Storage” mentioned in any Utility program.Can you show that Storage is significant to the power/ cooling load (via modeling or measuring)?
Organizational differences (who owns what?)Do you talk with your Facilities managers?Do your decisions affect each other? (YES!)When will you start planning together?
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
What IT Folks Wish Facilities Folks Knew About IT
If this thing goes down, people start getting upset.There is a lot of complexity here, and it’s not like throwing a power switch.Our landscape is changing, and (confidentially) I really didn’t get a lot of training in this energy management area.We really ought to talk more often.The only tool our CIO has to manage the power expenses in our facilities is the electric bill, and then he has to meet with the CFO.We can’t keep doing this forever.
34
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
SOX and PCAOB
Basel II / GLB / FIEC
ISO
EU Guidance
NASD / NYSE
HIPAA / ARS
US IRS
US Federal Privacy
ITIL
NIST
FTC ESIGN / FISMA / FISCAM
COSO / CobiT / ISF / ISACA
Credit Card CISP/SDP
Regulatory Domains
ITIL
Basel II / GLB / FIEC
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Increasing Green RegulationsAffecting Storage and ITWorldwide Environmental Regulations:• Japan
− Law Concerning the Promotion of Procurement of Eco-friendly Goods and Services
− Energy Conservation Policy for Large Companies• China
− RoHS to regulate Hazardous substances • Europe
− WEEE to regulate waste of electronic equipment− RoHS future requirements
• United States − EPA report to Congress on datacenter energy use− AB32 law passed in California
36
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Emerging Standards: US LEED“Leadership in Energy & Environmental Design”
US Green Building Council (Private Concern)Leadership in Energy and Environmental DesignWhat types of buildings can use LEED?How does LEED work?Is LEED training available?How much does it cost to register a project?What is the average LEED certification fee?What are the strengths and weaknesses of LEED for the Data Center?
37
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Analysis of LEED
Standards around Green Data Centers just emergingOpportunity for SNIA/Green Grid, other standards orgs
Trade-Off Equations Provide Opportunities to “Game the Green” System
“PR Green” v. “Genuine Green”
Need better volunteer engagements from IT professionals (SNIA GSI/Green Grid) to incorporate intensive feedback into its ongoing development
About 250 volunteers on LEED committeesLEED continues to evolve and maintain its relevance while encouraging continuous improvement within the building industry. 38
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
European CIOs are being pulled into Green IT agenda by industry drivers
PULL
Governments and regulators seek to control spiralling power costs of IT (e.g.
DEFRA/MTP find that ICT accounts for 4% of UK CO2 and will grow by 180%
between 2008-2010)
New standards drive energy efficiency in data centre design: building standards LEED in
US and BREEM in UK, UK Market Transformation Programme (MTP)
Client concerns of power consumption of high performance IT systems (e.g. blade
servers)
Industry groups (e.g. Uptime Institute, UK’s Environmental IT Leadership, EU ) design
new IT standards for procurement evaluation such as “performance per watt”
Refresh infrastructure to replace ageing and energy-sapping systems
Government tax/power utility incentives to assist in energy efficient solutions (e.g. Pacific Gas
+ Electric Rebates with Sun)
Companies commit to carbon reduction targets to appease investor demands for
sustainable businesses
CIO’s set energy efficiency targets for IT cost avoidance
PUSH
39
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Emerging Standards: JapanTokyo Climate Change Strategy by Tokyo Metropolitan Gov’t.
CO2 Emission Reduction ProgramTargeting business
1,300 Energy intensive industries and office. Using more than 1,500kl fuel or more than 6 million kWh
Set a target; Reduction RatePlanning Stage Evaluation
Reduction Rate > 5%: AAReduction Rate > 2%: A+Full cover “TMG selected basic 12 measurement”: ACover only operational measure: BNot cover even operational measures: C
Final Stage EvaluationOutstanding case: AAAAchievement of Reduction Rate: AAFull cover operational measurement: AOthers: B, C 40
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
First US LEED Certified Data Center: Fannie Mae Technology Center
247,000 square-foot data center and office building (Urbana, MD—metro Washington DC area), first LEED certification to a data center, August 5, 2005."By forging the way for green data centers, Fannie Mae [has] pioneered a new building type for sustainability," said Max Zahniser, LEED New Construction Certification manager of the USGBC. “Designing a data center to meet LEED requirements set forth unique challenges… we had to be creative in boosting the sustainability factor in every aspect of this project from selecting only the most energy efficient systems to recycling construction waste at the project's end," said Joseph Lauro, senior project architect. "We were able to reduce overall energy consumption by 20%."
41
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Datacenter Wins Green Enterprise IT Award from Uptime Institute
360 racks @ 8 kW/rackPUE ratio = 1.37$465,000/year savings vs. 1.78 PUECO2 reduced by 7100 tons/year = emissions of 1200 cars/yearModulating dampers supply enclosed pressure-controlled roomsReduced air mixing
Reduced fan horsepowerGreater cooling capacityElimination of hot spots
Infrared shows very uniform temperaturesWarm areas from not covering empty rack space
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Best Practices
Suggested Best PracticesHot & Cold aisles
Eliminate gaps in rows
Use longer rows
Use blanking panels
Orient AC units perpendicular to hot aisles
Use 0.8m to 1.0m high floors
Seal cable cutouts
Use high/low density areas matching airflow requirements.
Deploy power efficient platforms
Enable power management features
43
Anticipated BenefitLower server/storage temperatures
Better system reliability
Better uptime
Extends life of current data centre
Increased reliability of your servers/storage
Lower TCO
Lower energy usage
Maximizes server /storage density
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Toward Sustainable Storage
Sustainable digital storage is designing, manufacturing, deploying, managing, and recycling digital information storage in a manner that meets the information needs of the present without compromising the ability of future generations to meet their own information needs.*
*Adapted from World Commission on Environment and Development, commonly known as the Bruntland Commission, 1987.
44
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Optimized benefits for
all
The Broader Perspective: Sustainable Storage
45
Uses resources
well
Ensures social equity
Runs on renewable
energy
Supports living
systems
Alignsincentives
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Sustainable Storage: A Global Perspective
Runs on clean, renewable energy. Is powered by natural, perpetual flows of energy - principally, like virtually all life on earth, from the constant energy of the sun.Uses all resources productively. Eliminates the concept of waste. Emphasizes services over products.Supports healthy living systems. Maintains and restores the health of people and natural systems.Aligns market incentives with long-term social good. Aligns structural incentives to encourage the pursuit of economic, social, and environmental ambitions. Makes economic systems honestly account for value created and lost.Ensures social equity. Generally embodies a broad definition of democracy.
46
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Closing thoughts
47
“Being green is a journey.
As technology plays an important role it is even more important that the individual be aware and be responsible of his actions.
Hopefully our grandchildren will still look up and see a blue sky.”
Lee-An TanGeneral ManagerDatacraft Asia
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved. 48
Q&A / Feedback
Please send any questions or comments on this presentation to [email protected]
Many thanks to the following individuals for their contributions to this tutorial.
- SNIA Education Committee
Juergen Arnold Jeffrey Hill
Rachel Barrett Markus Ismael
Mark Carlson Richie Lary
Gene Chesser Neil Rasmussen
Tom Conroy Denise Ridolfo
Data Center User’s Group David Reinsel
James Dow Andrew Schaeffer
Shinobu Fujihara Lee An Tan
Mike Glodo Sol Squire
SNIA Green Storage TWG SW Worth
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved. 49
Other Green Tutorials at SNW
Green Storage I: Economics, Environment, Energy and EngineeringSW WorthSr. Standards Program Manager, Microsoft Corporation
Green Storage II: Metrics and Measurements Erik Riedel, PhDDirector, Seagate ResearchPatrick Chu, PhDResearch Staff Member, Seagate Research
Software Technologies for Green StorageAlan Yoder, PhDSenior Technical Staff, NetApp
BACKUP SLIDESBibliography
Additional Topics
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Bibliography
Texts & Scholarly ArticlesAbernathy, William J., and James M. Utterback. "Patterns of Innovation in Industry." Technology Review, Vol. 80, No. 7, June-July 1978, pp. 40-47.Anderson, Ray. Mid-Course Correction Towards a Sustainable Enterprise: The Interface Model Chelsea Green Publishing, 1998.Ausubel, Jesse H. "Will The Rest of the World Live Like America?" Technology in Society, Vol. 26, 2004, pp. 343-360.Benyus, Janine M. Biomimicry: Innovation Inspired by Nature. William Morrow and Company, 1997.Bash, C.E.; Patel, C.D.; Sharma, R.K.: “Dynamic Thermal Management of Air Cooled Data Centers,” Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, San Diego, California, June 2006.Billatos, Samir B., and Nadia A. Basaly. Green Technology and Design for the Environment. Washington: Taylor & Francis, 1997.Brundtland, Gro Harlem (editor). Our Common Future: The World Commission on Environment and Development. Oxford: Oxford University Press. 1987.Budnik, LeRoy, “Green Hype – Getting to the Heart of the Problem.” Posted in Untagged , at http://www.storagenetworkingnews.comChristensen, Clayton. The Innovator's Dilemma: When New Technologies Cause Great Firms To Fail. Boston: Harvard Business School Press, 1997.
51
Christensen, Clayton. The Innovator's Solution: Creating and Sustaining Successful Growth. Boston: Harvard Business School Press, 2003.Dow, Dr. James. “Understanding the Data Center.” SIFMA Data Center Panel, CS Technology.Emerson Network Power. Energy Logic: Reducing Data Center Energy Consumption by Creating Savings that Cascade Across Systems.” ©2008 Emerson Network Power.Fussier, Claude with James, Peter. Driving Eco Innovation: A Breakthrough Discipline for Innovation and Sustainabity. Pitman Publishing, 1996.Hart, Stuart L. Capitalism at the Crossroads: The Unlimited Business Opportunities in Solving the World's Most Difficult Problems. Upper Saddle River, N J: Wharton School Press, 2005.The Green Grid. 2007. Green Grid Metrics: Describing Data Center Power Efficiency. The Green Grid, Technical Committee. February 20. http://www.thegreengrid.org/downloads/Green_Grid_Metrics_WP.pdf.Hill, Jeffrey. “Green Initiatives: Lowering Costs and Increasing Efficiency in the Data Center.” ©February 2008 by Aberdeen Group. Used with permissionIMEX Research. Next Generation Data Centers: Power and Cooling Report, 2007. IMEX Research Company, 1474 Camino Robles, San Jose, CA 95120.
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Bibliography
Koomey, Jonathan, Christian Belady, Henry Wong, Rob Snevely, Bruce Nordman, Ed Hunter, Klaus-Dieter Lange, Roger Tipley, Greg Darnell, Matthew Accapadi, Peter Rumsey, Brent Kelley, Bill Tschudi, David Moss, Richard Greco, and Kenneth Brill. 2006. Server Energy Measurement Protocol. Oakland, CA: Analytics Press. November 3. http://energystar.gov/ia/products/downloads/Finalserverenergyprotocol-v1.pdf Koomey, Jonathan, Chris Calwell, Skip Laitner, Jane Thornton, Richard E. Brown, Joe Eto, Carrie Webber, and Cathy Cullicott. 2002. "Sorry, wrong number: The use and misuse of numerical facts in analysis and media reporting of energy issues." In Annual Review of Energy and the Environment 2002. Edited by R. H. Socolow, D. Anderson and J. Harte. Palo Alto, CA: Annual Reviews, Inc. (also LBNL-50499). 119-158 pp. Koomey, Jonathan, Huimin Chong, Woonsien Loh, Bruce Nordman, and Michele Blazek. 2004. Network electricity use associated with wireless personal digital assistants. The ASCE Journal of Infrastructure Systems. vol. 10, no. 3, pp. 131-137 (also LBNL-54105). September. Koomey, Jonathan G. 2007. Estimating Total Power Consumption by Servers in the U.S. and the World. February 15. http://enterprise.amd.com/Downloads/svrpwrusecompletefinal.pdf. Koomey, Jonathan, Kaoru Kawamoto, Bruce Nordman, Mary Ann Piette, and Richard E. Brown. 1999. Initial comments on 'The Internet Begins with Coal'. Berkeley, CA: Lawrence Berkeley National Laboratory. LBNL-44698. December 9. http://enduse.lbl.gov/projects/infotech.html.
52
Lawrence Berkeley National Laboratory. “High-Performance Buildings for High-Tech Industries, Data Centers. “Lawrence Berkeley National Laboratory. http://hightech.lbl.gov/datacenters.htmlLerner, Steve. Eco-Pioneers: Practical Visionaries Solving Today's Environmental Problems. MIT Press, 1998.Liedtka, Jeanne M. "If Managers Thought Like Designers." Batten Briefings (From The Darden School of Business Administration), Winter 2005, pp 2-6.Loper, Joe, and Sara Parr. 2007. Energy Efficiency in Data Centers: A New Policy Frontier. Washington, DC: Alliance to Save Energy. January. http://www.ase.org/files/3581_file_data_center_energy.pdf. Loper, Joe, Lowell Ungar, David Weitz, and Harry Misuriello. 2005. Building on Success: Policies to Reduce Energy Waste in Buildings. Washington, DC: Alliance to Save Energy. July. http://www.ase.org/images/lib/buildings/Building%20on%20Success.pdf.McDonough, William and Michael Braungart, “The Cradle-to-Cradle Alternative”, from State of the World 2004(Worldwatch / W.W. Norton, 2004)McDonough, William and Michael Braungart, “Remaking the Way We Make Things”, from The Handbook of Environmental Technology (Edward Elgar, 2004)
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Bibliography
Sharma, R.K.; Bash, C.E.; and Patel, C.D.: “Dimensionless parameters for evaluation of thermal design and performance of large-scale data centers,” 8th ASME/AIAA Joint Thermophysics and Heat Transfer Conference, AIAA-2002-3091, St. Louis, Missouri, June 2002.Speth, James Gustave. Red Sky at Morning: America and the Crisis of the Global Environment. New Haven and London: Yale University Press, 2004.Tschudi, William, Tengfang Xu, Dale Sartor, and Jay Stein. 2003. High Performance Data Centers: A Research Roadmap. Berkeley, CA: Lawrence Berkeley National Laboratory. LBNL-53483. http://hightech.lbl.gov/documents/DataCenters_Roadmap_Final.pdf.Waage, Sissel (editor). Ants, Galileo, & Gandhi: Designing the Future of Business through Nature, Genius, and Compassion. Sheffield: Greenleaf Publishing, 2003.Ziff-Davis Custom Publishing, “Data Center Power and Heat Management: Ready or Not?” Research sponsored by AMD. Available at http://enterprise.amd.com/Downloads/Ziff_Power_and_Cooling_IT_DC_survey2_en.pdf
53
Papanek, Victor. The Green Imperative: Natural Design for the Real World. Thames and Hudson, Inc., 1995.Patel, C.D.; Bash, C.E.; and Belady, C.: “Computational Fluid Dynamics Modeling of High Compute Density Data Centers to Assure System Inlet Air Specifications,” The Pacific Rim/ASME International Electronic Packaging Technical Conference and Exhibition, Kauai, Hawaii, USA, July 8–13, 2001.Patterson, M. K., A. Pratt, and P. Kumar. 2006. From UPS to Silicon: an End-to-End Evaluation of Data Center Efficiency. Santa Clara, CA: Enterprise Servers and Data Centers: Opportunities for Energy Savings Conference. January 31. http://www.energystar.gov/ia/products/downloads/MPatterson_APratt_Case_Study.pdf.Rasmussen, Neil. 2006. Electrical Efficiency Modeling of Data Centers. APC. White paper #113. http://www.apc.com.Rasmussen, Neil. “Electrical Efficiency Measurement for Data Centers” (White Paper #154). ©2007 American Power Conversion.Schmidt, Roger, and Don Beaty. 2005. ASHRAE Committee Formed to Establish Thermal Guidelines for Datacom Facilities. Electronics Cooling, February.
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Links and Sources
Regulatory InformationUS LEED Program: http://www.usgbc.orgTokyo Municipal Government: Tokyo Environmental Finance Project; http://www.kankyo.metro.tokyo.j p/
Economic Factors in Planning• “Costing Green: A Comprehensive Database and Budgeting
Methodology” Lisa Matthiessen, Peter Morris, Davis Langdon, 2004 http://www.davislangdon.us/USA/Research/ResearchFinder/2004-Costing-Green-A-Comprehensive-Cost-Database-and-Budgeting-Methodology“LEED Cost Study” prepared for the U.S. General Services Administration, 2004 http://www.wbdg.org/newsevents/news_040105.php“The Costs and Financial Benefits of Green Buildings: A Report to California’s Sustainable Building Task Force” Greg Kats, Capital E, 2003 http://www.ciwmb.ca.gov/greenbuilding/Design/CostBenefit/Report.pdf
Publicationseco-structure Magazine—A bi-monthly magazine dedicated to improving the environmental performance of buildings and their surroundings. e design Online—The journal of the Florida Design InitiativeEnvironmental Building NewsEnvironmental Design & Construction MagazineField Guide for Sustainable Construction by the Pentagon Renovation and Construction Program Office, Department of Defense. 2004. Green Building Costs and Financial Benefits by Gregory Kats. 2003. Green Buildings—Guidelines for Creating High-Performance Green Buildings by Pennsylvania Department of Environmental Protection. 1999. Greening Federal Facilities Guide by U.S. Department of Energy. 2001. GSA LEED® Applications GuideGSA LEED® Cost StudyHigh Performance Building Guidelines by New York City Department of Design and Construction. April 1999.
54
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Links & Sources
PublicationsInnovative Workplace Strategies by U.S. General Services Administration, Office of Governmentwide Policy, Office of Real Property. Dec 2003. Managing Your Environmental Responsibilities: A Planning Guide for Construction and Development by U.S. Environmental Protection Agency. 2005. Minnesota Sustainable Design Guide by Regents of the University of Minnesota, Twin Cities Campus, College of Architecture and Landscape Architecture. Real Property Sustainable Development Guide by U.S. General Services Administration, Office of Governmentwide Policy, Office of Real Property. Sustainable Building Rating Systems SummarySustainable Building Technical Manual by U.S. Department of Energy and U.S. Environmental Protection Agency. 1996. Sustainable Development and Society by U.S. General Services Administration, Office of Governmentwide Policy, Office of Real Property. Oct 2004. Sustainable Facilities Guide by U.S. Air Force Sustainable Federal Facilities: A Guide to Integrating Value Engineering, Life-Cycle Costing, and Sustainable Developmentby Federal Facilities Council. Washington, DC: National Academy Press, 2001. UB High Performance Building Guidelines by the University at Buffalo, The State University of New York. 2004.
Relevant Codes and StandardsANSI/TIA/EIA-568 Commercial Building Telecommunications Cabling StandardANSI/TIA/EIA-569 Commercial Building Standard for Telecommunication Pathways and SpacesANSI/TIA J-STD-607-A Commercial Building Grounding (Earthing) and Bonding Requirements for TelecommunicationsFIPS PUB 174 Federal Building Telecommunications Wiring StandardFIPS PUB 175 Federal Building Standard for Telecommunication Pathways and SpacesTIA TSB72 Centralized Optical Fiber Cabling GuidelinesTIA TSB75 Additional Horizontal Cabling Practices for Open Offices
Organizations/AssociationsThe American Institute of Architects (AIA):
AIA Edges Newsletter of the TAPAIA Integrated Practice pageAIA Technology in Practice (TAP) Knowledge Community page
U.S. Department of Energy (DOE):The Building Technology Roadmaps Program: for DOE technology research into various building components and building types
55
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
The “EQ” (Energy Quotient) TestDo You Know the Following? (Self score)
1. The monthly/annual power draw of your data center(s)? [10 green points]2. I see my data center(s) power bills(s) on a regular basis [5 green points]3. Relationship of peak power your provider can supply and your current peak
levels? [10 green points]4. What your provider’s strategic plans are to address growing energy demands in
your grid(s) [15 green points]5. Had an extended discussion with senior management about power and capacity
limits in your organization? Yes [10 green points]6. Energy costs and relationship to OpEx for your organization [10 green points]7. Date when, at your current IT growth rate, you:
• Run out of space? [ 5 green points] Run out of power? [ 10 green points]• Run out of HVAC? [ 5 green points]
8. What does PUE and DCIE stand for? [5 green points each]• PUE (Power Usage Effectiveness) = Total facility power/IT equipment power• DCIE (Data Center Infrastructure Efficiency) = IT equipment power/Total facility power
9. Are there currently any technologies SELLING TODAY that can reduce my power draw? [10 green points]
56
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
The “EQ” (Energy Quotient) Test:Scoring Your “EQ”
80-100 Green Points:You are a green dynamo! Please consider submitting a tutorial for the next SNW. Furthermore, we would like you to consider joining SNIA’s Green Storage Initiative as an end-user or vendor company representative. Please take this score to your management for pay raise considerations.
60-80 Green Points:Acceptable score. You are aware of these issues, and have spent some time engaging with stakeholders about their impact(s). Sorry, no raise just yet!
40-60 Green Points:Glad you are with us today. We hope you will learn some useful information to take back to management. Dust off resume.
Under 40 Green Points:Okay, you get credit for honesty (unlike the others). That and $5.00 will get you a latté in the lobby.
57
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Our Buildings: The Total Impact
39% of total energy consumption
71% of electricity consumption
39% CO2 emissions
30% of raw materials use
30% of waste output
12% of potable water consumption
Source: US Green Building Council, 2008
58
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Global Impact of Facilities
17% of fresh water withdrawals
71% of the global wood harvest
39% CO2 emissions
30% material and energy use
Source: US Green Building Council, 2008
59
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
A Growing Green Perspective
89% choose brands aligned with social cause
74% listen to brands aligned with social cause
69% shop for brands aligned with social cause
66% recommend brands aligned with social cause
Source: US Green Building Council, 2008
60
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Approaches to “Greening” Challenges and Expenses: Leave Town
1. Sioux Falls, S.D. $9,684,282
2. Winston-Salem, N.C. $9,799,928
3. San Antonio, Texas $10,314,249
4. Birmingham, Ala. $10,340,534
5. Ames, Iowa $10,378,916
61
The ten least expensive cities by estimated annual operating costs*:
6. Charlotte, N.C. $10,440,123
7. Indianapolis, Ind. $10,451,796
8. Tulsa, Okla. $10,452,228 9. Des Moines, Iowa
$10,480,298 10. Columbus, Ohio
$10,499,09
*Source: SearchStorage.com, October 2007
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
How Green is the EU?
62
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved. 63
Datacenter: Proposals and Solutions
REDUCE Performance whenever possible
“Underclocking”: reducing performance-state of CPU reduces power/cooling needs for Servers
Out-of-band mgmt (BMC) = no OS tuningManagement via OS gives more granular control
What is the equivalent for Storage? TAPE or Optical? (trade-off response time vs. energy)Disk drives and RAID arrays
Slower drives where possible (Design choice vs. Dynamic)Power off selected drives: MAID (Massive Array of Idle Disks)
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Advantages in Building Green
8-9% decrease in operating costs
7.5% increase in building values
6.6% improvement in ROI
3.5% increase in occupancy
3% rent increase
Source: US Green Building Council, 2008
64
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Example: HP Dynamic Smart Cooling
• Increased available cooling capacity for additional IT loads
• Reduced cooling energy costs up to 45%
• Can retrofit or spec for new construction applications
Bridging Facilities and IT to realize Adaptive Infrastructure
65
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
Retention timeframes by industry
Life Science/Pharmaceutical
Healthcare HIPAA
Financial services
OSHA
Sarbanes - Oxley
Processing food
Developing drugs
Developing biologics
Original records
Medical records <18
Full life patient care
Financial statements
Member registration
Trading accounts
Personnel records
Financial records
2 years after commercial release
3 years after distribution
5 years after manufacturing of product
Original correspondence 4 years after financial audit
30 years from end of audit
End of account + 6 years
End-of-life of enterprise
3 years
Length of patient’s life + 2 years
From birth to 21 years
5 year minimum for all records
1 2 3 4 5 10 15 20 25 50
Regulatory Drivers: Unfunded Governmental Mandates
66
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved.
2001 2006
50 TB
500 TB
Primary data copies
Data that will NEVER be accessed
Data not accessedin last 90 days
The Real Cost of Digital Toxic Waste
67
Building the Green Data Center© 2008 Storage Networking Industry Association. All Rights Reserved. 68
Datacenter Options: (Mech, Elec, Plumbing)
Convert from AC to DC distributionCan be partial conversion (DC arrays available)
Run at higher voltage (240 vs. 120)Increase Power Supply efficiency
80 PLUS program (www.80plus.org/servers.htm)
Operate Cooling effectivelyLeverage sensors, Follow basic rules (hot/cold aisles)Computational Fluid Dynamics (get some help!)
Run Generator-testing for Peak-shavingNegotiate with your power supplier for discounts