BUILDING SERVICES BRIEF - Major Projects

44
BUILDING SERVICES BRIEF 90-102 REGENT STREET REDFERN, WEE HUR STUDENT HOUSING 02 OCTOBER 2020

Transcript of BUILDING SERVICES BRIEF - Major Projects

Page 1: BUILDING SERVICES BRIEF - Major Projects

BUILDING SERVICES BRIEF

90-102 REGENT STREET REDFERN, WEE HUR STUDENT HOUSING

02 OCTOBER 2020

Page 2: BUILDING SERVICES BRIEF - Major Projects

i

CONTACT

KAKOLI DAS National Discipline Leader

M 0428 981 326

E [email protected]

Arcadis

Level 16, 580 George Street

Sydney NSW 2000

Page 3: BUILDING SERVICES BRIEF - Major Projects
Page 4: BUILDING SERVICES BRIEF - Major Projects

iii

WEE HUR GROUP WEE HUR STUDENT VILLAGE

Building Services Brief

Author Benjamin Fogerty

Checker Kakoli Das

Approver Kakoli Das

Report No F001 - 10036797

Date 25/09/2020

Revision Text 02

This report has been prepared for Wee Hur in accordance with the terms and

conditions of appointment for Redfern Student Accommodation. Arcadis Australia

Pacific Pty Limited (ABN 76 104 485 289) cannot accept any responsibility for any

use of or reliance on the contents of this report by any third party.

REVISIONS

Revision Date Description Prepared by Approved

by

01 25/09/2020 Draft Issue BF KD

02 02/10/2020 DA Issue BF KD

Page 5: BUILDING SERVICES BRIEF - Major Projects

iv

CONTENTS 1 . EXECUTIVE SUMMARY ........................................................................................................ 6

1.1 Purpose ................................................................................................................................ 6

1.2 Description of Building ....................................................................................................... 6

1.3 Proposed Infrastructure ...................................................................................................... 6

2 ELECTRICAL SERVICES ........................................................................................................ 7

2.1 Electrical Supply .................................................................................................................. 7

2.2 Lighting ................................................................................................................................ 9

2.3 Telephone Cabling System ................................................................................................11

2.4 ACCESS CONTROL AND INTRUDER DETECTION SYSTEM...........................................11

2.5 CCTV SYSTEM ....................................................................................................................12

2.6 ENTRY INTERCOM SYSTEM ..............................................................................................12

2.7 LIGHTNING PROTECTION SYSTEM ..................................................................................12

2.8 EARTHING AND SURGE PROTECTION ............................................................................12

2.9 COMMUNICATIONS SERVICES .........................................................................................13

2.10 TYPICAL ROOM PROVISIONS .........................................................................................13

3 MECHANICAL SERVICES ...................................................................................................... 2

3.1 Scope of Works.................................................................................................................... 2

3.2 Design Conditions ............................................................................................................... 2

3.3 Description of works ........................................................................................................... 4

3.4 Hydraulic Services ............................................................................................................... 7

Page 6: BUILDING SERVICES BRIEF - Major Projects

v

3.5 Fire Services .......................................................................................................................13

3.6 Appendix A – Preliminary DA Services Spatial Requirements .......................................16

Page 7: BUILDING SERVICES BRIEF - Major Projects

6

1 . EXECUTIVE SUMMARY

1.1 Purpose

The purpose of this report is to provide a high-level overview of the Building services systems to be provided for

as part of the design.

The assessment is based on the following:

• Review of “Dial Before You Dig (DBYD)” information

• Preliminary maximum demand calculations based on initial architectural designs

• Review of architectural drawings of the proposed development

• Review of Ausgrid GIS plans and single line diagrams

• Review of Sydney Water Pressure and Flow enquiry

Further coordination and discussions will be required with other disciplines and authorities to bring design into

coordination.

This report will also provide a high-level description of the Mechanical, Electrical, Hydraulic and Fire Protection

and Lift Services proposed for the development.

This report shall not be relied upon as providing any warranty or guarantee of the project, its services or

equipment.

The report is based on architectural drawing set dated 28th September 2020, any subsequent updates and

architectural changes shall not be fully represented by this report and may require changes in the services design

requirements and provisions.

1.2 Description of Building

The development will comprise:

• 1 levels of basement

• Ground floor, entry, with lobby space

• 18 floors, inclusive of ground floor, with 14 Typical floors in tower

• Rooftop plant

The development site is located in Redfern at the intersection between Regent Street and Marian Street.

1.3 Proposed Infrastructure

For infrastructure provisions and details, please refer to Arcadis infrastructure report dated 02/10/2020 revision 02

It should be noted that where capacities are commented on, these are at the point in time when this report is

prepared and may change subject to other developments in the vicinity.

Page 8: BUILDING SERVICES BRIEF - Major Projects

7

2 ELECTRICAL SERVICES

The briefing stage of this project will involve the collection of detailed information about the areas and the

equipment to be installed so that we can detail appropriate allowances for each space.

The electrical services component of this project comprises many electrical / electronic systems.

• Establish new substations and coordinate supply arrangement – Note that the HV network and substation detailed design (ASP L3 design) is not part of this brief

• Main Switchboard

• Supply Authority Metering

• Sub-mains cabling infrastructure & Distribution Boards

• General power

• General internal and external lighting.

• Emergency and Exit Lighting.

• Coordination of telecommunications service.

• Telecommunications cabling infrastructure.

• MATV & PayTV cabling system

• Access Control & Intruder Detection system.

• Entrance CCTV System

• Entry intercom system

• Lightning Protection System & Earthing System

2.1 Electrical Supply

The building will be served by an Ausgrid HV supply and associated substations. Ausgrid should be consulted with

respect to the provision of services to the site and the street reticulation to service of the development.

Our estimated maximum demand calculation based on AS3000 recommendation and further diversification factor

for the student bedrooms obtained from a reference building in Brisbane (as directed by developer) indicated that

the development will have maximum demand of 1MVA and installation of an chamber substation on the site will be

required (Utilizing Ausgrid Standard Surface Chamber Distribution Substation Single Transformer Up to 1000KVA

Layout 1)

Consumers mains from the substation shall reticulate to the main switchboard within the main switchroom, located

on Ground Floor, from here low voltage cabling shall distribute power throughout the building. Power factor

correction equipment shall also be located within this room.

2.1.1 Main Switchboard

The site main switchboard shall be provided to serve the entire development. The main switchboards shall be

located in the main switch rooms located in a Ground Floor designated switchrooms.

The main switchboard shall be divided into separate sections for essential services, house services and retail

section. The main switchboards shall also provide power to mechanical, hydraulic, fire and vertical transportation

services. Each section of the switchboard shall be provided with multi-function meters to display and record load

information. The meters shall be also connected to the building management system.

The main switchboards shall be of the floor mounted top entry/exit, front connected cubicle type, of form 3B

separation. The main switchboards shall be designed to incorporate additional 10% spare capacity.

Provision for 25% load current growth in the main bus bars in relation to the building design load will be provided.

And overall 30% spare circuit breaker spaces will be provided.

Page 9: BUILDING SERVICES BRIEF - Major Projects

8

The main switchboard will generally feed:

• Essential fire and life safety systems (Stairwell pressurisation, stairwell lighting, emergency lifts, smoke management, fire control room, pumps etc.)

• House services lighting and power

• Air conditioning plant

• Hydraulic Services

• Main risers for accommodation floors

• Service protection devices installed within the main switchboards shall comply with Ausgrid requirements.

Main switch board room shall be constructed of 2hrs fire rated construction with 2 means of egress provided.

2.1.1.1 Power Factor Correction Equipment

Power Factor correction connection will be provided to achieve 0.95 lagging or better at the main switchboards.

2.1.1.2 Supply Authority Metering

Supply Authority meters shall be of the Ausgrid approved type, mounted within the main switch board room and

accessible by Ausgrid personnel, and located in accordance with Ausgrid standards.

The architect shall be required to specify door locking hardware keyed to Ausgrid standard keying arrangements.

Generally, supply authority metering arrangements shall be to the approval of Ausgrid however it is proposed that

electricity tariff meters be arranged and located as follows:

Meters shall be of the current transformer type. The entire building shall be metered as a single customer and no

separate meters will be provided (except for the retail space)

2.1.1.3 Retail Metering

The retail spaces shall be provided with individual single or three phase direct connected metering. Metering for

retail shall be provided in the main switch board room.

2.1.2 Distribution Boards

Distribution boards shall typically be of the surface mounted front connected, DIN circuit breaker type. All

distribution boards shall be of sheet metal construction, enclosed and complete with hinged, lockable doors.

Outgoing final circuits will be controlled by miniature moulded case circuit breakers with RCD protection as per

the requirements of AS/NZS 3000:2018, AS 2243 and BCA Section J requirements.

Circuit breakers shall be of the DIN-rail type and of minimum 10 kA rating with integral RCD for all lighting and

general power sub-circuits.

Each room is to be provided with its own Load Centre type board (NHP CSB12ST or equivalent) to allow the

interval systems in each room to be separately run.

2.1.2.1 Floor Distribution boards

Shall be of the 3-phase, minimum 160Amp rated, with separate chassis for:

• Lighting sub-circuits – for the general areas lighting

• Power sub-circuits – for the general areas power

• Rooms sub-circuits – for rooms supplies

Page 10: BUILDING SERVICES BRIEF - Major Projects

9

Energy metering for each chassis will be provided, and clarification/confirmation required from your BCA

consultant on the extend of the section J submetering provision proposed above.

House distribution boards shall be located within electrical riser cupboards.

2.1.2.2 Space Requirement

Refer to Appendixes for space requirements for key electrical infrastructure items.

2.1.3 Lightning and Surge Protection

Surge protection and a comprehensive lightning protection system in accordance with AS/NZ 1768 will be

provided. Surge protection will be provided for all power, IT & security communication cabling entering or exiting

the building. Surge protection will be equivalent to Novaris SF3200 for electrical services, and equal to Erico

HSP10/K230 for communications services.

The lightning protection system will be capable of extension to accommodate aerials & masts above the building

height.

2.1.4 Earthing

Earthing in accordance with AS/NZS 3000, AS1768 and Supply Authority requirements will be provided.

2.2 Lighting

The lighting systems will be designed to coordinate and enhance the architecture, interiors and ESD principles.

Each area shall be provided with suitable lighting to meet the requirements of the architectural concept and

energy efficiencies as required by the relevant issue National Construction Code Volume 1.

LED lights will be used wherever possible to ensure general efficiency and low maintenance of the lighting

installation. Selection of the colour rendering characteristics of the lamps is important for the ambience of the

space.

All lighting shall be designed to meet the lighting levels nominated in AS1680.

2.2.1.1 Main Entries & Lift Lobbies Lighting

Front of house corridors and lift lobbies on each floor will be provided with LED down lights, and LEP strip pelmet/coffer

mounted style lighting to compliment the interior design concept.

Special areas such as the main entry lobby will be documented as per the specialized lighting designer

requirements as applicable.

Lighting control shall be through a combination of motion detectors for lift lobbies, time switches for main

entrances. As required a level of 24-hour lighting shall be provided to all lift lobbies and main entrances.

All external lighting is to be designed and installed in a manner which prevents glare and/or spillage having an adverse

impact on occupants of adjacent properties and the landscape lighting will be provided in accordance with the landscape

planes and details.

2.2.1.2 Basements, Plant rooms, Fire stairs

These areas shall utilise surface mounted batten style linear T5 fluorescent or LED luminaires complete with

prismatic diffusers where applicable.

Page 11: BUILDING SERVICES BRIEF - Major Projects

10

Lighting control in basement areas and the car park shall be through motion detections, time switches and a 25%

of luminaires operating on a 24-hour basis.

All luminaires in all fire stairs and escape passages shall operate in 24-hour operation.

All luminaires in plant rooms shall operate through standard light switching arrangements. Lighting in utility spaces

such as store rooms and cleaners cupboards etc shall be controlled through a motion detector in each

space/cupboard.

2.2.1.3 Retail lighting

Lighting for retail will be provided for safe movement only, and final layout shall be provided and designed by the

future tenants.

Lighting control shall be through local switch provided adjacent to the retail distribution boards.

2.2.2 Lighting Controls

The following types of lighting control methods will be used:

Zone Operation

Common areas and offices Centralized lighting control system with time scheduling for normal

hours operation. Local motion sensor control for afterhours

operation. Some 24hr lighting will be provided.

Lift Lobbies and corridors Motion sensor control

Fire Stairs / Exits 24hr in accordance with AS/NZS2293 and BCA

Electrical / Communications Risers Local control.

Service Areas Local control.

Retails By the tenants

Rooms Local control.

A combination of Automated lighting control system (i.e. Dynalite) and 240V control system shall be used to

achieve the best cost/value to the client.

2.2.3 Emergency and exit lighting systems

The emergency and EXIT lighting system shall generally include single point non-maintained mode luminaires.

EXIT luminaires shall be maintained mode.

Emergency lighting testing functions shall be of the central computer monitored type utilising dedicated data

signalling. The head end computer shall be located in the main communications room. The system shall be

designed to the requirements of the Building Code of Australia (BCA) and AS2293.

Where applicable, the main entrance, lobbies and lift lobbies, corridors etc. will utilise recessed ‘spitfire’ type

recessed luminaires and ‘edge lit’ type EXIT luminaires.

Page 12: BUILDING SERVICES BRIEF - Major Projects

11

Plant rooms, fire stairs, car park, loading docks, back of house areas etc. will use integral emergency battery

packs in fluorescent fittings to match the normal light fittings within the same area and surface mounted EXIT

luminaires.

Each luminaire within fire stairs shall be complete with emergency light.

Exit luminaries will incorporate cold cathode type lamps or LED and use “running man style” green/white colour

signage.

2.3 Telephone Cabling System

A telephone cabling system shall be provided to deliver telecommunications services to the building. The facilities

for the installation of incoming telecommunications cabling shall be provided in the form of a minimum of one off

100mm diameter conduits and the main communication room.

It is anticipated that all incoming telecommunications cabling, multi-mode optical fibre and/or copper services

shall be supplied and installed by the NBN.

The client shall be required to initiate and enter into a contract between themselves and the telecommunications

carrier of their choice before any lead-in cabling infrastructure will be installed or any telecommunications services

be provided.

2.3.1.1 Reticulation

The main communications room shall be designed to house the telephone main distribution frame (MDF). In

addition to this the main communications room shall house central security and intercom system equipment with a

dedicated space for NBN equipment.

A communications cabling cupboard and riser shall be provided at each level of the building to facilitate the

reticulation of all communications services cabling throughout the building, from the main communications room

to each level of the building.

2.3.1.2 Room Provisions

It is anticipated that no communication services required inside the rooms except for a WIFI coverage which can

be provided as a part of the building network, and we would seek clarification from your client for this point.

2.4 ACCESS CONTROL AND INTRUDER DETECTION SYSTEM

The access control and intruder detection system shall be provided to control the access of areas within the

building to appropriate persons and restrict entry of unauthorised persons into the building. The system shall

typically comprise the following:

• Door Access Control facilities.

• Interface to fire alarm system.

• Lift Access Control System interface.

• Services areas access control.

The system shall be a stand-alone system of the fully programmable, integrated type. The central control point

shall be housed in the main communications room. Space shall be provided in the main communications room to

facilitate the requirements of locating the security head end at this location. Additional active equipment shall be

located within communications cupboards on floors where required.

All building entry points shall be provided with a card reader style door access point.

Page 13: BUILDING SERVICES BRIEF - Major Projects

12

The system shall utilize proximity card style access cards with card readers. Secure doors shall incorporate

magnetic door hold devices or electric strikes and all external entrances shall utilize reed switches for monitoring of

unauthorised entry.

The system can also be interfaced to the lift control system to limit access after-hours to various floors as

programmed (TBC with the Client).

The complete security methodology shall be programmed to the client requirements to be confirmed.

2.5 CCTV SYSTEM

A separate closed circuit television (CCTV) system shall be provided to monitor the major entry and exit points of

the building only. Internal cameras shall monitor the building main entrance. No additional areas of CCTV

coverage are proposed (TBC with the Client).

The system shall be of the digital, IP based and colour type.

The system shall operate on a 24-hour basis and be capable of storage of up to 30 days of storage utilising a

networked hard drive storage device. Storage equipment shall be located in the main communications rooms.

External CCTV coverage shall not be provided.

2.6 ENTRY INTERCOM SYSTEM

An intercom system shall be provided two way communication between nominated entry points and the reception

desk. The system shall be of the fully digital type.

Entry panel shall be provided external to the front entrance. Each entry panel shall be of the recessed and vandal

proof type, colour camera will be provided to allow viewing of caller.

The system shall be interfaced with the building access control system to enable opening of the front entrance

doors and activation of appropriate lift access.

Reception desk will be provided with an intercom station complete with colour screen to view entry door call, full

duplex audio facilities, and separate buttons for opening entrance point. Intercom stations shall be of the recessed

and flush type.

2.7 LIGHTNING PROTECTION SYSTEM

A risk assessment shall be conducted based on the relevant standards to determine if a system is required. The

system shall comprise:-

• “Dynasphere” air terminations on the roof, mast extension, stay cables.

• Down conductors shall be electrically isolated from the building structure using dedicated insulated down conductors.

• Earthing of down conductors shall be achieved by earthing pits and earth electrodes in accordance with

manufacturer’s recommendations. Pits shall incorporate event counters.

• Façade earthing

2.8 EARTHING AND SURGE PROTECTION

Earthing systems shall be provided in accordance with Australian Standards and Supply Authority requirements

throughout the building. Earth bonding of structure shall be provided to the substation and building. A separate

communications earthing system will be provided. Surge diversion will be installed at the main switchboard on the

Page 14: BUILDING SERVICES BRIEF - Major Projects

13

incoming supply. Surge diversion will also be provided for copper communications cables entering building using

surge diverter modules on the MDF.

2.9 COMMUNICATIONS SERVICES

2.9.1 DESCRIPTION OF WORKS

2.9.1.1 General

A fibre to the premises telecommunications (FTTP) system in line with the National Broadband Networks

requirements shall be provided to deliver telecommunications services to the building and retail space.

Incoming telecommunications infrastructure shall be provided in the form of a minimum two off 100mm diameter

conduits. Conduits shall reticulate between existing infrastructure located adjacent the development and the

building distributor.

A pit and pipe network shall be provided by the developer for installation of the incoming telecommunications

cabling. Cabling shall be supplied and installed by a National Broadband Network provider (TBC).

The client shall be required to initiate and enter into a contract between themselves and the telecommunications

carrier of their choice before any lead-in cabling infrastructure will be installed or any telecommunications services

be provided.

2.9.1.2 Lead in telecommunications facilities.

New lead in multi-mode fibre optic cables will be provided by a National Broadband Network provider installed

within conduits, and shall terminate within the main communications room. The main communications room. The

room shall be designed to house all incoming network termination devices and carrier equipment. In addition to

this the main communications room shall house central security and intercom system equipment.

2.9.1.3 Communications Services Distribution and reticulation

A communications cabling cupboard and riser shall be provided at each third level of the building to facilitate the

reticulation of all communications services cabling throughout the building.

Telecommunications cabling shall be of the multi core optical fibre type and originate from the building

communication room and terminate within Fibre Distribution Terminals (FDTs) on each third level.

CAT 6a Cabling will be provided from each communication cupboard to the communication outlets, and we would

recommend that WIFI coverage be provided throughout the building.

It is anticipated that wired communication connections are not required within the rooms, and we would seek

clarification from your client in relation to the communication provisions.

Horizontal cabling shall be installed within ceiling voids, within flexible conduit or fixed to cable trays, in line with

NBN Co and relevant service provider requirements.

2.10 TYPICAL ROOM PROVISIONS

2.10.1.1 Supply

Each room shall be provided with a single-phase supply as described in the distribution boards section. No

separate metering will be provided for any room.

Page 15: BUILDING SERVICES BRIEF - Major Projects

1

2.10.1.2 Lighting Provisions

Room’s lighting will be typical throughout utilising LED fixtures - Typically a switched (non-dimmable) downlights

2.10.1.3 Power Provisions

Room’s load centre to be located within each room in an approved location. Final location to suit the

room fitout and the requirements of the wiring regulations.

Small power throughout the Student rooms (to suit the final layout). The numbers of GPO’s

and outlets anticipated as follows:

• 1 No. double GPO above kitchen counter for general use

• 1 No. Single GPO for hot plat

• 1 No. single GPO for range hood.

• 1 No. single GPO for microwave

• 2 No. Double GPO’s per bedroom.

• 1 No. Double GPO per bathroom

• 1 No. Double GPO per study.

The general power arrangements shall be coordinated with the Architect’s interior design for each apartment.

2.10.1.4 Security Provisions

Access to individual room can be achieved using card reader and electrical strike, and we would seek

clarification from your Client in relation to the room’s access system - (TBC).

The access control system shall also be used as an occupancy sensing device, and shall isolate all the

non-essential circuits inside each room when no one is occupying the area.

2.10.1.5 Communication Provisions

Please confirm the communication requirements for the rooms. We would propose to provide WIFI

coverage network to all spaces within the building which can be utilized by the management to grant

access to the students.

An allowance for 1 No. CAT 6A data outlet per study desk, connecting back to the floor communication rack as a

provision should the tenant requires direct connection in lieu of WIFI connection

Note: No provisions shall be made for any audio-visual system facilities such as in-ceiling speakers,

wall outlets etc… as well as MATV system

Page 16: BUILDING SERVICES BRIEF - Major Projects

2

3 MECHANICAL SERVICES

3.1 Scope of Works

The Works comprise the design, supply, delivery, installation, commissioning, testing, and placing

into service the following mechanical services:

Air conditioning to the apartments, common and retail areas, comprising typically of FCU’s

running off Reverse cycle VRF condenser units, with BS heat recovery units installed on

floors. The indoor units are to be exposed as wall mounted at the end of the room bulk head

Air Conditioning to Telecommunications room, Main Switchboard Room and Fire Control room

via air cooled condenser unit split system.

Centralised ventilation system from rooftop plant providing outside air to all SOU’s

Stair pressurisation systems.

Decentralised toilet exhaust systems for each apartment.

Ventilation for various rooms in the basement including refuse rooms.

A building management system for control of the house services

3.2 Design Conditions

Design criteria for the design of the mechanical services are as follows:

Item Design Criteria

External ambient

conditions

Cooling Calculations to be based on the following;

Summer 32oC DB, 24oC WB

Winter 7oC DB

Internal Design

Conditions

Summer 24oC DB, Maximum

Winter 21oC DB, Minimum

Humidity Design Point Nominal 60% RH, not

controlled

People Load People Sensible 70W

People Latent 60W

Other Internal Heat

Loads

Studio 500W

Common areas and reception 15 W/m2

Lighting

Apartments 7 W/m2

Lobby 10 W/m2

Common areas and reception 10 W/m2

Retail 22 W/m2

Population Studio 1 Persons

Page 17: BUILDING SERVICES BRIEF - Major Projects

3

Item Design Criteria

Lobby 1 person per 5 sqm

Reception, meeting rooms, residents

lounge and gym

Per population based on architectural

furniture layouts

Infiltration (Note 1)

Residential apartments 1 air change per hour of the area

considered the conditioned space

General Areas 0.5 air changes per hour

Ventilation / Exhaust

provisions (Note 2)

Apartment bathroom 25L/s of exhaust

Common Areas Natural ventilation to achieve 5%

openable area to floor area

Switch rooms and Comms rooms 4 L/s/m2 of outside air

Fire pump rooms To be advised by the Fire Services

Engineer (Note 4)

Retail Kitchen Exhaust 5 L/s/m2

Note 1 - Infiltration will be considered the greater of either the infiltration rates as identified in the

table or the exhausts from the space, or adjacent spaces, which impact on the conditioned space.

Infiltration rates will not be considered the sum of both infiltration rates and exhaust rates that affect

the conditioned areas. Only the largest exhaust that affects a space is to be considered for the unit

sizing.

Note 2 - The following spaces are to be considered naturally ventilated and are not allowed to be

mechanically supplied or exhausted:

• All apartments

• All retail areas

• Substations

• All gas meter rooms

• Lobby areas for retail and residential

Note 3 – The exhaust volumes listed for the kitchen exhausts are based on a general exhaust from

the kitchen area. Where range hoods are expected to be connected in lieu of general exhausts to the

kitchens, the exhaust air volumes are expected to match the flows as detailed in the architectural

package. Kitchen exhaust in residential to be via recirculating Charcoal range hoods

Page 18: BUILDING SERVICES BRIEF - Major Projects

4

3.3 Description of works

3.3.1 Ground Floor Areas

3.3.1.1 General

The Ground Floor areas include the following areas that will be provided with air conditioning:

Telecommunication room

Main Switchboard Room

Fire Control room

Retail tenancies

Common area

The gas meter and pressure regulator room and residential lobby will be naturally ventilated to the

façade.

3.3.1.2 Air Conditioning

The air conditioning to the areas on ground floor listed above is expected to be provided with VRF

indoor condenser units connected to indoor FCU’s systems to the services rooms. The ducted indoor

units are expected to be concealed in ceiling voids and connected to outdoor air intakes from louvres

located in the façade. The ceiling space is expected to be adequate to allow for the installation of

these ducted units and associated ducting. Access to these units will be required for safe regular

maintenance. The retail will be conditioned through the same system, with option to run on separate

package condenser unit.

3.3.1.3 Retail kitchen exhaust

The retail kitchen exhaust will be ceiling mounted fan discharging to the façade at the ground floor.

3.3.2 Apartments

3.3.2.1 Air Conditioning

The air conditioning for each apartment will be provided with bulk head mounted FCU’s in the rooms

connected to indoor condenser units located in a plant room on each floor. The indoor FRV

condenser units will be connected to cooling towers on the roof.

The controls for the air conditioning systems serving the apartments will be standard arrangements

as available with the units installed. A central controller option for turning off the whole area is to be

considered during the detailed design process.

The areas served by the air conditioning are expected to be provided with windows for natural

ventilation in accordance with the BCA. As these areas will be naturally ventilated they are therefore

not required to be mechanically ventilated through the air conditioning systems.

3.3.2.2 Toilet Exhaust

Exhaust systems will be provided to serve the bathrooms for all apartments. The systems shall

include ceiling space mounted fans ducted to louvres in the façade of the building.

Page 19: BUILDING SERVICES BRIEF - Major Projects

5

The exhaust louvres are expected to be detailed in the architectural drawings and included in the

building works package. Bulkheads or additional ceiling space for ducting to allow connection to the

louvres on the façade are expected to be provided where appropriate.

The operation of the exhaust fans is to be considered during the detailed design process with options

being available to interlock the fan to the lights or have a separate switch on the gang plate.

3.3.2.3 Kitchen Exhaust

The kitchens for apartments are to be provided with a range hood and will be ducted to the façade to

a louvred discharge. The specification of these rangehoods will be detailed in the architectural

package

The kitchen exhaust provided to the common areas will be a range hood system similar to the SOU’s

and will be ducted to the façade.

3.3.2.4 Power Supplies

All power supplies for mechanical services serving apartments is expected to be connected to the

house power supplies as the rooms will be unmetered, power supply to the retail area will be metred

separately.

3.3.3 Miscellaneous Ventilation Systems

Mechanical ventilation will be provided to the following areas as a minimum:

Fire control room

Hydraulics plant rooms

Garbage/refuse rooms

Comms rooms

Fire pump room

Main switchroom

3.3.4 Stair Pressurisation and Lobby Relief Systems

The stairwells in the tower will be provided with stair pressurisation. The supply fans will be located

in the roof plantroom.

3.3.5 NOISE AND VIBRATION

The construction of the development is expected to account for acoustic considerations such as

reverberant times being in accordance with AS2107 where possible and noise isolation being

adequately provided in the construction of the building elements. For instance, when the condensers

on the floor plant rooms of the tower are operating the noise transfer to the lift lobbies is adequately

minimised by sufficiently acoustically treated walls and doors.

For the residential areas, recommendations for noise levels in AS2107 are not expected to be

achievable with the air conditioning systems operating. This is due to the very low noise levels listed

such as 35dB(A) for sleeping areas near minor roads. These noise levels are only achievable with

systems with ducted units with attenuated supply and return ducting. In the case of this development,

Page 20: BUILDING SERVICES BRIEF - Major Projects

6

the ducting is expected to be very short and to have little to no attenuation of the noise from the air

conditioning systems.

For non-residential areas, noise levels are expected to be able to be addressed for the mechanical

services. The noise levels for the mechanical services are expected to be designed for compliance

with AS2107 where constraints of the development do not prohibit this.

More stringent levels of acoustic consideration than discussed above for the mechanical services will

need to be addressed with additional space allowances. For instance in the case of residential

ducted units, longer acoustically lined ducts in lowered ceiling areas would be required. Also lower

noise levels may require indoor units to operate at lower fan speeds so larger units would be

required to achieve the same cooling performance. This would affect the ceiling space requirements

as well as increasing the size of the condensers connecting to the indoor units.

External noise levels shall comply with Local Authorities requirements where possible as part of the

design of the mechanical services.

Page 21: BUILDING SERVICES BRIEF - Major Projects

7

3.4 Hydraulic Services

3.4.1 Scope of Work

The Hydraulic Services Works comprises the design, supply, delivery, installation, commissioning,

testing, and placing into service the following services:

Stormwater drainage and downpipes

Sanitary drainage and plumbing

Trade waste drainage

Domestic Potable and Non-potable water

Non-potable cold-water service

Hot and warm water services

Natural Gas Service

3.4.2 Hydraulic services design criteria

Generally, the Hydraulic Services systems shall be designed to provide a quality service for this type

of development that meets, the Local Authorities requirements, and represents a co-ordinated

scheme to accepted industry standards.

In particular, the systems shall be designed and installed to conform with/to the approval of:

• AS 3500 - National Plumbing Code

• National Construction Code

• Building Code of Australia.

• Sydney Water Corporation.

• Sydney Water Corporation - Trade Waste.

• Sydney City Council

• Jemena including AS 5601 - Gas Installations

• Fire Rescue NSW

• Any other authorities having jurisdiction.

3.4.3 Description of Works

3.4.4 Stormwater drainage and Downpipes

Storm water and roof water drainage will be designed and installed in accordance with the

requirements of Australian Standard AS3500.3: 2018 Part 3 Storm water Drainage and Redfern

Council.

All rainwater will be collected and discharged based on the following minimum criteria:

Box Gutters – 1 in 100-year 5-minute storm event

Page 22: BUILDING SERVICES BRIEF - Major Projects

8

Eaves Gutters – 1 in 20-year 5-minute storm event

Overflows will be provided to protect the building in the event of a system blockage.

It is intended that conventional storm water systems will drain the roof tower areas, ground floor,

planter boxes and car park.

Storm water collected from roof outlets will gravitate to the Civil On-Site Detention (OSD) located at

below Ground Level. Storm water overflow from the OSD tank will gravitate to the Authority storm

water in the Street. Note that the OSD tank design documentation and connection to Redfern

Council storm water main is by Civil.

Overflow from the fire tanks will gravitate via the Civil On-Site Detention subject to grade or

alternatively the fire tank overflow pipe will discharge to the sub-soil collection sump for pump-out to

the civil drainage system.

Storm water drainage lines and fittings will be constructed of sewer grade UPVC with solvent cement

joints where in ground and of UPVC pipes and fittings with solvent welded joints where suspended.

Downpipes cast in structural elements shall be insulation wrapped HDPE pipe and fittings with

welded joints.

3.4.5 Sub-Soil Water Drainage

The sub-soil drainage system will be installed in the basement of the building in accordance with the

requirements of Australian Standard AS3500.3: 2018 Part 3 Storm water Drainage. The sub-soil

drainage system will collect all sub-surface seepage water from around the perimeter of the site,

under the lowest slabs on ground, at the base of lift pits and trenches and gravitate to a sub-soil

collection sump.

The sump will be located away from car park spaces for convenient maintenance.

The sump will be provided with dual pumps (and control panel) that are each capable of the

calculated duty required. Pumps will be activated by 4 float switches in the collection well. The

pump control panel will automatically alternate the duty pump on a twenty-four (24) hour cycle to

ensure even wear on both pumps.

Final pump calculations to be based on geotechnical report infiltration rates.

The sub soil drainage system shall be constructed of perforated UPVC pipes and fittings with solvent

welded joints with a blue metal surround and overwrapped in filter fabric.

3.4.6 Sanitary Plumbing and Drainage

The sanitary drainage system will be designed and installed in accordance with Australian Standard

AS3500.2: 2018 Part 2 Sanitary Plumbing and Drainage and the requirements of Sydney Water

Corporation.

The sanitary drainage and vent system will be designed as a fully vented modified pipe system to

provide flexibility of the drainage installation with special consideration where pressure zones are

created at changes of direction, including the piping material used for mechanical durability and

thermal movement to serve the proposed development. Stack vents shall extend to roof and be

terminated through roof venting to atmosphere in discreet locations where possible.

Page 23: BUILDING SERVICES BRIEF - Major Projects

9

Stack offsets will be minimised where possible.

The installations will be designed and installed such that they will be entirely accessible for easy

maintenance. Horizontal pipe runs will be installed with sufficient gradients to achieve self-cleansing

velocities to avoid potential problems with blockage.

All pipework installed within noise sensitive areas will be acoustically treated.

Sanitary fixtures and tap ware will be selected to meet ESD requirements;

Plant rooms and equipment requiring drainage connections will be incorporated in the hydraulic

services design.

All exposed waste piping within habitable areas including basin or sink traps and floor waste grates

in wet areas will be chromium plated, copper or brass.

New sewer connections will be provided to the authority mains infrastructure subject to Sydney

Water Corporation approval.

The sanitary drainage system shall be fitted with overflow gullies to provide for the safe release of

sewerage in the event of a blockage.

100mm diameter sanitary drainage capped points will be provided under slab for each retail tenancy,

food court tenancies and beverage outlets.

50mm diameter branch vents will be provided in the ceiling of the tenancies, food court tenancies

and beverage outlets for connection and extension to the main vents for compliance with Code.

A sewage pump out pit will be provided in the basement of the building. Sanitary drainage that

cannot be discharged to the external sewer main by gravity including discharge from the grease

arresters and car wash facility will be collected into this pit from where dual pumps will lift the sewage

to the gravity system for disposal from the building.

Pumps will be activated by 4 float switches in the collection well. The pump control panel will

automatically alternate the duty and stand-by pumps on a twenty-four (24) hour cycle to ensure even

wear on both pumps.

Sewer drainage lines and fittings will be constructed of sewer grade UPVC with solvent cement joints

where in ground and of UPVC pipes and fittings with solvent welded joints where suspended.

3.4.7 Trade Waste Drainage

The trade waste drainage for the project shall collect effluent from the trade waste generating areas

from the retail tenancy and convey by gravity to a maximum 5,000L strategically located grease

arrestors below ground of the development to facilitate gravity discharge to the sewage pump out pit.

The numbers and total capacity of the required grease arresters will be calculated based on 1,000

litres per retail tenancies and food-court shops. (i.e. 20 shops x 1,000 Litres + 20,000 Litres)

100mm diameter grease drainage points capped off for future tenancy connection will be provided

under slab for each retail tenancy, food court tenancies and beverage outlets.

50mm diameter branch grease vents will be provided in the ceiling of the tenancies for connection of

vents for compliance with Code.

Page 24: BUILDING SERVICES BRIEF - Major Projects

10

An 80mm minimum diameter remote suction line with kamlock fitting, extending from the adjacent

walls of the grease arresters to the truck pump-out point on Ground Floor will be provided to facilitate

the cleaning of the grease arresters. All kamlock fittings shall be of stainless steel manufacture with

suction line piping being of minimum 80mm HDPE pressure rated smooth wall pipe.

The trade waste drainage shall also incorporate a system to collect effluent from the car wash bay

for pre-treatment prior to discharge to the sewage pump out pit

3.4.8 Domestic Potable Water

The domestic potable water system will be designed and installed in accordance with Australian

Standard AS3500.1: 2018 Part 1 Water Supply and the requirements of Sydney Water Corporation.

New connections for the domestic potable and fire water will be provided to the authority mains

infrastructure in George Street subject to Sydney Water approval.

The domestic potable cold-water service for the project shall comprise a 100mm incoming service

from the Sydney Water main with variable speed duty and stand-by pressurisation pumps to feed the

upper levels of the development.

Domestic potable cold-water services will be designed for a high and low-rise application.

Cold water to the top floors of the tower will be via pressurized variable speed drive pumps with the

lower floors by mains pressure. The exact amount of floors to be fed by the mains pressure will be

determined once the mains amplification to site has been conducted

The water meter set with backflow prevention devices and variable speed duty and stand-by

pressurisation pumps will be in the water meter room.

In addition to the authority meter, sub-water meters shall be installed to monitor the water use of all

major water users. These will include though not be limited to:

Retail Tenancy

Plantrooms

Fire services

The domestic potable cold-water system shall incorporate stop valves, which will be located in

readily accessible locations to enable individual area isolation for maintenance purposes. Individual

control valves will be provided to control each group of fixtures and wet areas including bathrooms,

kitchens and the like.

The domestic cold-water system will also supply the domestic hot water and fire hose reel systems.

The cold-water risers will be installed within the services ducts. Pressure limiting valves will be

installed in the cold-water supply to reduce the supply pressure on the lower levels, when required.

The domestic potable cold-water supply to the building will be reticulated in accordance with the

following design parameters:

Minimum 280kPa outlet pressure.

Maximum 500kPa outlet pressure.

Page 25: BUILDING SERVICES BRIEF - Major Projects

11

Maximum system velocity of 1.6 m / sec.

Backflow prevention devices will be installed in the system in accordance with AS3500 and the

Authority’s requirements.

Cold water pipework and fittings will be type B copper tube with silver soldered or press fit. All

exposed control valves and exposed pipework in wet areas will be chromium plated.

3.4.9 Hot and Warm Water services

Hot water service will be designed and installed in accordance with the requirements of the local

Authority having jurisdiction and Australian Standard AS3500.4:2018 Part 4 Hot Water Supply

Systems.

The following system description is based on plant option 1 in section 1.3.7 below. Option 2 in

section 1.3.8 below will provide a simplified system description, utilising metered cold water from

each apartment and a reduced plant allocation.

All heated water pipe work to be insulated in accordance with the BCA Part J.

A heat trace system shall be provided where required, to ensure any excessive ‘dead legs’ are kept

to a minimum.

Design parameters will be in accordance with the ‘Cold Water’ section.

Individual control valves will be provided to control each group of fixtures and wet areas including

bathrooms, kitchens and the like.

Hot/warm water temperatures to the toilets and amenities will be controlled by means of the

installation of tempering valves and thermostatic mixing valves in accordance with the statutory

requirements.

Hot water pipework will be constructed from type B copper tube with silver soldered joints and all

pipework and fittings insulated of a size and thermal efficiency applicable to its location.

All exposed control valves and exposed pipework in wet areas will be chromium plated.

3.4.10 Centralised Gas system

Separate gas fired plant with instantaneous heaters and storage vessels will be provided for the

generation of domestic hot water to supply hot water to the apartments, commercial floors and retail

tenancies. The hot water plant assemblies will be located in roof plant room and reticulate throughout

the building as required.

A complete flow and return systems incorporating circulating pumps will be provided to eliminate

system dead legs and associated heated water delay times;

Heated water will be circulated at 65°C and returned to the heated water plant at 60°C.

Negotiations with the preferred gas retailer will provide options for supply of major plant in

association with a long term (10yr) gas supply agreement. These negotiations can be facilitated in

the next design phase.

Page 26: BUILDING SERVICES BRIEF - Major Projects

12

3.4.11 Natural Gas services

Gas service will be designed and installed in accordance with Jemena requirements and Australian

Standard AS5601-2013 Gas Installation.

A new gas connection will be provided to the medium pressure gas main within Marian Street subject

to Jemena’s approval. Gas regulator will be installed in the ground floor gas meter room to reduce

pressure as required.

Low pressure natural gas will be brought into the building to supply the retail shops, food court

tenancies, commercial hot water plant, residential apartment hot water system and cooktops. The

gas pressure regulator and meter assembly will be located in the gas regulator/meter room in the

ground floor of the building.

In addition to the main gas meter, gas sub-meters will be installed to monitor the gas usage of all

major users. These will include though not be limited to:

Retail Tenancy;

Heated water plant (residential; retail and commercial office plant)

The gas riser will be located within the services ducts.

Emergency gas shut off device will be installed in the gas service to isolate the supply during

emergency and will be linked to the mechanical system.

All pipework will be constructed from type B copper tube with silver soldered or press fit joints.

Page 27: BUILDING SERVICES BRIEF - Major Projects

13

3.5 Fire Services

3.5.1 Scope of Services

Fire services for this building will be provided in accordance with the National Construction Code,

relevant Australian Standards, and any future fire safety engineered solution.

Services shall include:

Combined Sprinkler / Hydrant System

Smoke Detection and Alarm System

Smoke Hazard Management System

Sound System and Intercom systems for Emergency Purposes (SSISEP)

Fire Hose Reel System

Portable Fire Extinguishers

3.5.2 Design Criteria

Fire Services System BCA requirement Australian Standard

Smoke Detection and Alarm System NCC Spec E2.2a Clause 4 AS1670.1-2015

Sound System and Intercom

systems for Emergency Purposes

NCC Spec E4.9 AS1670.4-2015

Combined Sprinkler/Hydrant

System

NCC Spec E1.5 AS2118.6-2012

AS2419.1-2005

AS2118.1-2017

(secondary reference

standard)

Fire Hose Reels NCC Spec E1.4 AS2441-2005

Portable Fire Extinguishers NCC E1.6 AS2444-2001

3.5.3 Systems Description

3.5.4 Fire Detection and Alarm System

Fire detection will be provided throughout the building, with detectors selected to suit the specific

hazard of each area to minimise the possibility of false alarms.

The fire detection and alarm system will be design as analogue addressable looped detection

system, and will be connected to an approved monitoring company to notify fire brigade in the event

of a fire alarm.

Addressable smoke detection will be provided to all common areas of the building to provide smoke

hazard management.

Page 28: BUILDING SERVICES BRIEF - Major Projects

14

Addressable smoke detectors will be provided within the residential units between living and sleeping

areas, with alarm verification facility to reduce false alarms only in the class 3 area of the building

otherwise smoke alarms will be provided to all other residential units.

An analogue addressable Fire Indicator Panel will be provided in the Fire Control Room at ground

level.

A mimic fire panel will be provided at the main entry lobby if the main panel is located remotely. A

Fire Fan Control Panel (FFCP) will be provided adjacent to the Main Fire Panel and Secondary Fire

Panel to allow manual operation of the Fire Fans by the brigade.

Interface will be provided with the following building services systems;

Emergency warning system for controlled evacuation of building occupants

Mechanical services system for operation in fire mode and system shut down upon fire alarm

Combined sprinkler / hydrant system for monitoring of isolation valves, pumps, tanks, and

system activation

Security system for monitoring and release of locked doors in egress path

Facility will be provided for isolation of incoming gas supply.

3.5.5 Sound System and Intercom systems for Emergency Purposes

A Sound System and Intercommunications system for Emergency Purposes will be provided

throughout the building to allow controlled evacuation of the building during a fire condition, including

floor by floor cascading evacuation as determined through detailed fire safety engineering.

Occupant warning speakers will emit a pre-recorded verbal evacuation message and will be located

to ensure the required speech intelligibility and sound pressure level can be delivered to all occupied

areas.

An Emergency Control Panel will be provided adjacent to the Fire Panel.

Visual Alarms (Strobes) will be provided in areas with high ambient noise level, and to any areas

specified for use by hearing impaired occupants.

Warden Intercom Phones (WIP) will be provided to allow direct communication with the fire warden,

and Emergency Alarms (EA) will be provided adjacent to required exits.

3.5.6 Combined Sprinkler / Hydrant System

A combined sprinkler / hydrant system will provide fire sprinkler protection and hydrant coverage

throughout the building, and will be designed to the following design;

Residential areas / Administration areas - light hazard class LH

Plant areas / Ground floor and mezzanine retail areas - ordinary hazard class 1 OH1

Fire Hydrant coverage will be provided throughout the building, ensuring all areas of the building can

be adequately reached with a 30m hose length and 10m nozzle spray from a fire hydrant outlet.

Additional hydrants will be provided where adequate coverage cannot be achieved from hydrant

outlets in the fire stairs.

Page 29: BUILDING SERVICES BRIEF - Major Projects

15

Hydrant outlets will have a minimum of 5L/sec flow and 700kPa residual pressure at the two most

disadvantaged hydrant outlets, as required for a system utilising on-site booster pumps.

3.5.6.1 System Arrangement

A Dual Supply as per AS 2118.1-2017 will be provided, comprising the following;

One fire tank (5m (W) x 8m(l) x 3.33m (H)) with a multistage diesel/electric pump located

adjacent to the fire stair on basement mezzanine which is dependent upon the available water

supply in the street water main.

The pipework system will be sectioned into individual vertical pressure zones with maximum of 35m

height (three pressure zones being -103mtr top to bottom) to ensure efficient system operation can

be achieved. Pressure reduction stations will be provided between pressure zones, and will be

located within the fire stair.

Sprinkler control valves for each level of the building will be provided within the fire stair.

3.5.6.2 Brigade Boosting

A brigade booster enclosure will be provided at ground level, within sight of the main building entry

where possible or as agreed with the fire safety engineer. The booster assembly will be provided

with the following: -

Tank suction connection

Low level boost connection

High level boost connection

Town’s main suction connections

3.5.7 Fire Hose Reels

Fire Hose Reel coverage will be provided within the non-residential areas of the building (hose reels

may not be required to residential levels as per the NCC 2019A).

Hose Reels will be provided to ensure all areas of the buildings are reached with a 36m hose and 4m

of nozzle spray, and to ensure hoses are not required to extend between fire compartments.

The Hose Reel system will be supplied from the fire hydrant system risers.

Fire Hose Reels will have a minimum of 0.33L/sec flow at the two most disadvantaged Hose Reels.

3.5.8 Portable Fire Extinguishers

Portable fire extinguishers to suit the relevant risk and associated signage will be provided

throughout all areas of the building.

Fire blankets will be provided to all kitchen areas and similar risk areas

Page 30: BUILDING SERVICES BRIEF - Major Projects

16

3.6 Appendix A – Preliminary DA Services Spatial Requirements

Page 31: BUILDING SERVICES BRIEF - Major Projects

DA3001

1

DA3001

1

TO

WE

R A

BO

VE

9 GIBBONS STREET

EXISTING RESIDENTIAL FLAT BUILDING

80-88 REGENT ST -

FUTURE 18

STOREY STUDENT

HOUSING BUILDING UNDER

CONSTRUCTION

11 GIBBONS ST - FUTURE 18 STOREY

AFFORDABLE HOUSING BUILDING UNDER CONSTRUCTION

R E G E N T S T R E E T

M A

R I A

N S

T R

E E

T

W I L L I A M L A N E

116

REGENT STREET

OUTLINE OF EXISTING

BASEMENT

FFL TO BE SET AT

22.500

41.58 m21° 41' 39"

31

.64 m

81

° 40' 4

1"

41.76 m21° 23' 36"

31.8

1 m

81° 1

7' 2

1"

EX

IST

ING

BA

SE

ME

NT

WA

LL

TRUCK TURNTABLE

SRV

SUBSTATION

RL 24.741

ESCAPE PASSAGE

BELOW

MAIN SWITCH

ROOM

FFL 24.800

FFL 24.800

VOID TO BIKE STORE

14 m²

COMMS

57 m²

WASTE

RAMP TO BASEMENT 1:121:12

206

0

8 m²

BULK WASTE

PLANT AREAS ABOVE

RL 25.000

RL 25.0001:12

DA3001

1

DA3001

1

30 m²

OSD TANK

6 m²

LIFT 2

6 m²

LIFT 1

7 m²

AIRLOCK

RL 22.800

BIKE CAPACITY 90

9 GIBBONS STREET

EXISTING RESIDENTIAL FLAT BUILDING

80-88 REGENT ST -

FUTURE 18

STOREY STUDENT

HOUSING BUILDING UNDER

CONSTRUCTION

11 GIBBONS ST - FUTURE 18 STOREY

AFFORDABLE HOUSING BUILDING UNDER CONSTRUCTION

R E G E N T S T R E E T

M A

R I A

N S

T R

E E

T

W I L L I A M L A N E

116

REGENT STREET

43 m²

FIRE RELAY

PUMP

UP 1:12

84 m²

BIKE STORE

RL 22.800

RL 22.800

INFILL OVER

EXISTING SLAB

RAMP TO LOADING DOCK

WORKSHOP

51 m²

STORAGE

RL 22.800

RL 22.800

RL 22.800

RL 23.400

UP 1:12

N

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PLO

T D

AT

E &

TIM

E:

PLO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION

1 : 200 @A110

28

/09

/202

0 1

2:4

2:3

4 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

BASEMENT & LOWERGROUND FLOOR PLAN

DA2000Wee Hur Regent

Auth

or

90 - 102 Regent Street, Redfern

19026

1 : 200

LOWER GROUND PLAN1

1 11/05/2020 Issue for Information

2 18/06/2020 Issue for Information

3 30/07/2020 Issue for Information RP BM

4 10/08/2020 Issue for Coordination RP BM

5 13/08/2020 Issue for Information RP BM

6 25/08/2020 Issue for Coordination RP BM

7 31/08/2020 Issue for Coordination RP BM

8 11/09/2020 Issue for Coordination RP BM

9 14/09/2020 Issue for Coordination RP BM

10 24/09/2020 Issue for Information RP BM

1 : 200

BASEMENT PLAN2

DRAINAGE SUBSOIL PUMP-OUT PIT (BELOW GROUND)CAPACITY = 3000Liters1800mm (Dia.)

SEWER PUMP-OUT PIT (BELOW GROUND)CAPACITY = 3000Liters1800mm (Dia.)

OIL SEPARATORFREE STANDING SEE DETAIL1410mm(L)X420mm(W)X1510mm(H)

STAIR PRESSURISATION GRILLE1800mm(L)x1000mm(H) ASSUME 50% FREE AREA,EVERY 3 LEVELS ONLY

BASEMENT EXHAUST RISER500mm(L)x500mm(W) INTERNAL DIMENSIONS

STAIR PRESSURISATION RELIEF AIR GRILLE700mm(H)x1250mm(W)

FIRE PUMP ROOM EXHAUST AND SUPPLY RISER2200mm(L)x900mm(W) INTERNAL DIMENSIONSRISER GOES UP TO THE ROOF

FH RISER AND SPRINKLER CONTROL ASSEMBLY1200mm(L)x350mm(W)ALLOWANCE FOR 1m CLEAR ZONE IN FRONT OF VALVE.THIS NEEDS TO BE LOCATED NOT MORE THAN 4M FROM FIRE EXIT STAIR

FIRE PUMP ROOM LOCATION EXTEND LENGTHOFFIRE PUMP ROOM(FIRE BRIGADE RELAY PUMP)5500mm(L)x3000mm(W)(MIN. INTERNAL DIMENSIONS)

AIRLOCK FOR OPTION 2FIRE PUMP ROOM

SUBSTATION PIT, TRENCHES AND EARTHELECTRODES

SUBSTATION TO BE FULLYLOUVRED WALL

THE SUBSTATION FOOT PRINTSHOULD BE 4200 (W) X 4600 (D)INTERNAL CLEAR DIMENSION,SEE SNIPPET

MSB ROOM4000mm(W)x4300mm(D)TWO EGRESS DOORS TOBE PROVIDED

PROPOSED LOCATION OFCOMMS ROOM5000mm(W)x3000mm(D)

HYDR RISER1200mm(L)x900mm(W) INTERNAL DIMENSIONSWITH SIDE ACCESS DOOR FROM THE WASTE ROOM

All indicated Dimension and areas are indicative and for thepurpose of initial spatial allowances, final arrangement anddimensions to be further developed during detailed designstages

FIRE PUMP ROOM DIMENSIONS:6500mm(L)x5500mm(W)x3000mm(H)

FIRE PUMP ROOM MUST HAVE FIRE ISOLATED ACCESS TOTHE FIRE STAIR, OTHERWISE, FIRE PUMP ROOM ANDTANKS NEED TO BE RELOCATED IN THE BASEMENT LEVEL.

Page 32: BUILDING SERVICES BRIEF - Major Projects

1 2 3 4 5

17 x 182 = 3,100

12345

9 x 189 = 1,700

123456789

1,

9x

98

1=

00

7

1

2

3

4

5

6

7

8

9

2,000

m29 m2 9 m2

1:20

ChamberSubstation

MainSwitch Rm

RL 25.60

RWT RWRe-useTank

24.50

RWT /

CWPump

RL 24.50

RL 24.830

RL 25.10RL26.60

Cleaner'sRoom

CommsRoom

RL 24.76 RL 24.90

RL 24.50

CC

CC

RR

RR

RR

RR

RR

R

Comm. BicycleSpaces

16 Spaces

CC

CC

RR

RR

RR

RR

RR

R

Fire ControlRoom

Pump Room

DDA

WC

Lockers

GasCupboard

Female

Male

Cond. Cond.

GasCupboard

LIFT 2

LIFT 1

FFL 25.950

DA3001

1

DA3001

1

9 GIBBONS STREET

EXISTING RESIDENTIAL FLAT BUILDING

80-88 REGENT ST -

FUTURE 18

STOREY STUDENT

HOUSING BUILDING UNDER

CONSTRUCTION

11 GIBBONS ST - FUTURE 18 STOREY

AFFORDABLE HOUSING BUILDING UNDER CONSTRUCTION

R E G E N T S T R E E T

M A

R I A

N S

T R

E E

T

W I L L I A M L A N E

116

REGENT STREET

59 m²

RETAIL

FFL 26.130

44 BIKE CAPACITY

FFL 25.700

FFL 27.000

FFL 26.997

1:14

2°FFL 24.786

1:20

FFL 24.0492°FFL 24.390

FFL 26.953FFL 25.557

FFL 26.130

211 m²

COMMON

8 m²

WC

FFL 27.000

VOID TO

LOADING DOCK

VOID TO

SUBSTATION

VOID TO

WASTE

RL 26.431 RL 26.650

FFL 26.6971225

VOID TO

SWITCH ROOM

VOID TO

COMMS

15 m²

RECEPTIONUP 1:1213 m²

FCR

69 m²

BIKE STORE

8 m²

WC

10 m²

PLANT

12 m²

PARCEL

16 m²

MANAGER

RL 27.000

31 m²

SPRINKLER

TANK16 m²

WATER

METER

RL 25.950

RL 26.130

RL 27.000

RL 26.130

15 m²

GAS METER

1:12

1:12

RL 25.800

RL 25.165

RL 25.165

RL 25.950

RL 26.697

1:40

1:14

4852

5642

38 m²

LAUNDRY

25 m²

OFFICE

DW

10 m²

KITCHEN

1:14

1:14

83 m²

GAMES

LOCKERS

2 m²

FBV

RL 25.950

DA3001

1

9 GIBBONS STREET

EXISTING RESIDENTIAL FLAT BUILDING

80-88 REGENT ST -

FUTURE 18

STOREY STUDENT

HOUSING BUILDING UNDER

CONSTRUCTION

11 GIBBONS ST - FUTURE 18 STOREY

AFFORDABLE HOUSING BUILDING UNDER CONSTRUCTION

R E G E N T S T R E E T

M A

R I A

N S

T R

E E

T

W I L L I A M L A N E

116

REGENT STREET

9m SET BACK FROM CENTRE OF

WILLIAM LANE ABOVE PODIUM

3M S

ET

BA

CK

LEV

EL 4 A

ND

AB

OV

E

CENTRE OF LOT BOUNDARY

GENERAL STREET ALIGNMENT

GE

NE

RA

L S

TR

EE

T A

LIG

NM

EN

T

5m SETBACK LEVEL 2

TOWER ABOVE

LINE OF BUILDING OVER9m

SE

T B

AC

K

LEV

EL 9 A

ND

AB

OV

E

6.5m S

ET

BA

CK

UP

TO

LEV

EL 8

TERRACE

TERRACE

TWIN STUDIO

QUEEN STUDIO

DDA

COMMON

ADMINISTRATION

DDA STUDIO

DORM OUTDOOR

GYM

KITCHEN

OUTDOOR

OUTDOORDINING

BOH

RETAIL

SERVICES

STAIR

CORRIDOR

Drinking

Fountain

Shelving Unit

152 m²

OUTDOOR

AREA

103 m²

OUTDOOR

AREA

148 m²

OUTDOOR

AREA

TV

46 m²

GYM

34 m²

KITCHEN

38 m²

COMMON

5 m²

WC

Stretching

Shelving

Weights

3000 30003000 3000

25002500

25002500

25002500

N

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PLO

T D

AT

E &

TIM

E:

PLO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION

1 : 200 @A112

28

/09

/202

0 1

2:4

2:4

0 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

GROUND & LEVEL 2FLOOR PLANS

DA2001Wee Hur Regent

CD

90 - 102 Regent Street, Redfern

19026

2 06/05/2020 Issue for Information RP BM

3 11/05/2020 Issue for Information

4 18/06/2020 Issue for Information

5 30/07/2020 Issue for Information RP BM

6 10/08/2020 Issue for Coordination RP BM

7 13/08/2020 Issue for Information RP BM

8 25/08/2020 Issue for Coordination RP BM

9 31/08/2020 Issue for Coordination RP BM

10 11/09/2020 Issue for Coordination RP BM

11 14/09/2020 Issue for Coordination RP BM

12 24/09/2020 Issue for Information RP BM

1 : 200

GROUND (L1) FLOOR PLAN1

1 : 400 @A3

1 : 200

LEVEL 22

GAS METER ROOM4000mm(L)x3000mm(W)x2400m(H) IN READILYACCESSIBLE AND UNIMPEDED ACCESS FORMAINTENANCE AND METER READING

WATER METER ROOM/DOMESTIC COLD WATERBOOSTER PUMP ROOM6000mm(L)x3000mm(W)x2400m(H)

FIRE BRIGADE BOOSTER ASSEMBLY LOCATION- MAIN ENTRANCE NEEDS TO BE ALONGREGENT ST.4000mm(L)x550mm(W)x1800m(H)FIRE BRIGADE BOOSTER SHALL BE LOCATED INTHE FOLLOWING:- ACCESSIBLE TO FIREFIGHTERS- WITHIN FIRE RATED WALL, UNOBSTRUCTEDACCESS, ADJACENT MAIN LOBBY

FCR DIMENSION SHOULD HAVE 1 SIDE ATLEAST 2500mm. LOCATION NEEDS TO BEAPPROVED BY THE BCA CONSULTANT.THERE SHOULD BE AN ALTERNATEPATHWAY THAT IS DIRECTED TO OPENSPACE.

HYDR RISER1200mm(L)x900mm(W) INTERNAL DIMENSIONSWITH 600x600mmSIDE ACCESS PANELFROM THE LAUNDRY

STAIR PRESSURISATION RISER3000mm(L)x1000mm(W)INTERNAL DIMENSIONS

STAIR PRESSURISATION GRILLE1800mm(L)x1000mm(H) ASSUME 50% FREE AREAEVERY 3 LEVELS ONLY

STAIR PRESSURISATION RELIEF AIR LOUVRE3000mm(L)x800mm(H) ASSUME 50% FREE AREA

ELECTRICAL CUPBOARD1350mm(W)x400mm(D)CLEAR INTERNALDIMENSIONSWITH FULL FACE DOORS

COMMS CUPBOARD1650mm(W)x800mm(D)INTERNAL DIMENSIONSWITH FULL FACE DOORS

FH/SPRINKLER RISER1200mm(L)x350mm(W)

HYDR RISER900mm(L)x300mm(W)WITH SIDE ACCESS PANELFROM TOILETTYPICAL TO ACCOM. UNITS

OUTSIDE AIR DUCT RISER (TYPICAL TO ALL RESIDENTIAL UNITS)300mm(W)x300mm(D)INTERNAL DIMENSIONS

STAIR PRESSURISATION RELIEF AIR LOUVRE3000mm(L)x800mm(H) ASSUME 50% FREE AREA

MECHANICAL NOTES:

1. ALL ROOMS ARE PROVIDED WITH TOILET EXHAUST FANS (300MMdia.) AND 200mm x 200mm EXHAUST AIR DUCT TO FACADE.2. ALL ROOMS ARE ASSUMED TO HAVE RECIRCULATING KITCHENRANGE HOOD.3. ALL ROOMS MUST HAVE TRANSFER AIR GRILLES 200mm x 200mm,TRANSFERRING AIR FROM THE CORRIDOR TO EACH ROOM WHEN THETOILET EXHAUST FAN IS TURNED ON. TOILET DOORS MUST ALSOHAVE DOOR LOUVRES.4. THERE SHOULD BE ANOTHER STAIR PRESSURISATION SHAFT3000mm(L)x1000mm(W) INTERNAL DIMENSIONS. LOCATION CAN BEANYWHERE AROUND THE STAIRWELL.5. STAIR PRESSURISATION RELIEF AIR LOUVRES AT CORRIDOR ENDSTO BE PROVIDED, 2-OFF 1200mm(L)x800mm(H) RELIEF AIR LOUVRESPER LEVEL.6. BULKHEADS PER UNIT TO BE PROVIDED FOR FAN COIL UNITSPATIALS.7. THERE IS NO PROVISION FOR KITCHEN EXHAUST IN THE COMMONAREAS. COMMON AREAS ARE PROVIDED WITH DUCTED FAN COILUNITS FOR AIR-CONDITIONING. SIZE OF CEILING CONCEALED FANCOIL UNIT TO BE 1200mm(L)x600mm(W)x400mm(H).

All indicated Dimension and areas are indicative and for thepurpose of initial spatial allowances, final arrangement anddimensions to be further developed during detailed designstages

FIRE TANKS WITH PARTITIONMIN. EFFECTIVE CAPACITY EACH = 57.6kLTOTAL CAPACITY = 57.6x2 = 115.2kL6000mm(L)x4000mm(W)x2400mm(H)

STAIR PRESSURISATION RELIEF, BASEMENT,FCR, WASTE ROOM OUTSIDE AIR LOUVRE3200mm(L)x550mm(H) ASSUME 50% FREE AREA

RETAIL AREA TO BE PROVIDED WITH OUTSIDE AIR FAN,3-OFF CEILING CONCEALED DUCTED TYPE UNITS900mm(L)x600mm(W)x400mm(H)

OUTSIDE AIR LOUVRE FOR METER ROOM, MSBROOM, AND RETAIL AREA950mm(L)x550mm(H)

Page 33: BUILDING SERVICES BRIEF - Major Projects

LIFT 2

LIFT 1

DA3001

1

9 GIBBONS STREET

EXISTING RESIDENTIAL FLAT BUILDING

80-88 REGENT ST -

FUTURE 18

STOREY STUDENT

HOUSING BUILDING UNDER

CONSTRUCTION

11 GIBBONS ST - FUTURE 18 STOREY

AFFORDABLE HOUSING BUILDING UNDER CONSTRUCTION

R E G E N T S T R E E T

M A

R I A

N S

T R

E E

T

W I L L I A M L A N E

116

REGENT STREET

9M SETBACKFROM CENTRE OF

WILLIAM LANE LEVEL 4 AND ABOVE

3M S

ET

BA

CK

LEV

EL 4 A

ND

AB

OV

E

9M S

ET

BA

CK

LEV

EL 8 A

ND

AB

OV

E

CENTRE OF LOT BOUNDARY

4M SETBACK LEVEL 3 AND ABOVEGENERAL STREET ALIGNMENT

GE

NE

RA

L S

TR

EE

T A

LIG

NM

EN

T

TERRACE BELOW

TERRACE BELOW

6.5m S

ET

BA

CK

UP

TO

LEV

EL 8

AWNING

EXTENT

2000

1225

LANDSCAPE

ZONE FOR

CONDENSER

LOUVRED

AWNING

2250 200

595

2080

1540

208

0

1540

2080

154

0

1249

8

DA3001

1

9 GIBBONS STREET

EXISTING RESIDENTIAL FLAT BUILDING

80-88 REGENT ST -

FUTURE 18

STOREY STUDENT

HOUSING BUILDING UNDER

CONSTRUCTION

11 GIBBONS ST - FUTURE 18 STOREY

AFFORDABLE HOUSING BUILDING UNDER CONSTRUCTION

R E G E N T S T R E E T

M A

R I A

N S

T R

E E

T

W I L L I A M L A N E

116

REGENT STREET

9m SET BACK FROM CENTRE OF

WILLIAM LANE ABOVE PODIUM

3M S

ET

BA

CK

LEV

EL 3 A

ND

AB

OV

E

9m S

ET

BA

CK

CENTRE OF LANE

4m SET BACK LEVEL ABOVE PODIUMGENERAL STREET ALIGNMENT

GE

NE

RA

L S

TR

EE

T A

LIG

NM

EN

T

6.5m S

ET

BA

CK

TWIN STUDIO

QUEEN STUDIO

DDA

COMMON

ADMINISTRATION

DDA STUDIO

DORM OUTDOOR

GYM

KITCHEN

OUTDOOR

OUTDOORDINING

BOH

RETAIL

SERVICES

STAIR

CORRIDOR

1225

6205

4050

3050

8960

1246

9

154

0

2080

2080

1540

208

0

1540

2080

154

0

N

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PLO

T D

AT

E &

TIM

E:

PLO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION

1 : 200 @A111

28

/09

/202

0 1

2:4

2:4

4 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

LEVEL 3 & LOWERTYPICAL FLOOR PLANS

DA2002Wee Hur Regent

CD

90 - 102 Regent Street, Redfern

19026

1 03/04/2020 Issue for Information RP BM

2 06/05/2020 Issue for Information RP BM

3 11/05/2020 Issue for Information

4 18/06/2020 Issue for Information

5 30/07/2020 Issue for Information RP BM

6 10/08/2020 Issue for Coordination RP BM

7 13/08/2020 Issue for Information RP BM

8 25/08/2020 Issue for Coordination RP BM

9 11/09/2020 Issue for Coordination RP BM

10 14/09/2020 Issue for Coordination RP BM

11 24/09/2020 Issue for Information RP BM

1 : 2001 / DA1003

LEVEL 3 PLAN3

1 : 400 @A3

1 : 200

LEVEL 4-11 PLAN1

HYDR RISER1200mm(L)x900mm(W) INTERNAL DIMENSIONSWITH 600x600mmSIDE ACCESS PANELFROM THE LAUNDRY

STAIR PRESSURISATION RISER3000mm(L)x1000mm(W)INTERNAL DIMENSIONS

STAIR PRESSURISATION GRILLE1800mm(L)x1000mm(H) ASSUME 50% FREE AREAEVERY 3 LEVELS ONLY

STAIR PRESSURISATION RELIEF AIR LOUVRE3000mm(L)x800mm(H) ASSUME 50% FREE AREA

ELECTRICAL CUPBOARD1350mm(W)x400mm(D)CLEAR INTERNALDIMENSIONSWITH FULL FACE DOORS

COMMS CUPBOARD1650mm(W)x800mm(D)INTERNAL DIMENSIONSWITH FULL FACE DOORS

FH/SPRINKLER RISER1200mm(L)x350mm(W)

HYDR RISER900mm(L)x300mm(W)WITH SIDE ACCESS PANELFROM TOILETTYPICAL TO ACCOM. UNITS

OUTSIDE AIR DUCT RISER (TYPICAL TO ALL RESIDENTIAL UNITS)300mm(W)x300mm(D)INTERNAL DIMENSIONS

STAIR PRESSURISATIONRELIEF AIR LOUVRE3000mm(L)x800mm(H) ASSUME50% FREE AREA

REFRIGERANT PIPE RISERminimum1300mm(W)x600mm(D)INTERNAL DIMENSIONS

MECHANICAL PLANT AREA (SHOULD BE FULLYOPENED OR FULLY LOUVRED FOR SIDEDISCHARGE OF CONDENSING UNITS)TOTAL AREA = 70 m2 (3800mm(L)x12000mm(W))5-OFF 1900mm(L)x800mm(W)x1800mm(H) VRFCONDENSING UNITS SERVING LEVEL 2-6

HYDR RISER1200mm(L)x900mm(W) INTERNAL DIMENSIONSWITH 600x600mmSIDE ACCESS PANELFROM THE LAUNDRY

STAIR PRESSURISATION RISER3000mm(L)x1000mm(W)INTERNAL DIMENSIONS

STAIR PRESSURISATION GRILLE1800mm(L)x1000mm(H) ASSUME 50% FREE AREAEVERY 3 LEVELS ONLY

STAIR PRESSURISATION RELIEF AIR LOUVRE3000mm(L)x800mm(H) ASSUME 50% FREE AREA

ELECTRICAL CUPBOARD1350mm(W)x400mm(D)CLEAR INTERNALDIMENSIONSWITH FULL FACE DOORS

COMMS CUPBOARD1650mm(W)x800mm(D)INTERNAL DIMENSIONSWITH FULL FACE DOORS

FH/SPRINKLER RISER1200mm(L)x350mm(W)

HYDR RISER900mm(L)x300mm(W)WITH SIDE ACCESS PANELFROM TOILETTYPICAL TO ACCOM. UNITS

OUTSIDE AIR DUCT RISER (TYPICAL TO ALL RESIDENTIAL UNITS)300mm(W)x300mm(D)INTERNAL DIMENSIONS

REFRIGERANT PIPE RISERminimum1300mm(W)x600mm(D)INTERNAL DIMENSIONS

MECHANICAL NOTES:

1. ALL ROOMS ARE PROVIDED WITH TOILET EXHAUST FANS (300MMdia.) AND 200mm x 200mm EXHAUST AIR DUCT TO FACADE.2. ALL ROOMS ARE ASSUMED TO HAVE RECIRCULATING KITCHENRANGE HOOD.3. ALL ROOMS MUST HAVE TRANSFER AIR GRILLES 200mm x 200mm,TRANSFERRING AIR FROM THE CORRIDOR TO EACH ROOM WHEN THETOILET EXHAUST FAN IS TURNED ON. TOILET DOORS MUST ALSOHAVE DOOR LOUVRES.4. THERE SHOULD BE ANOTHER STAIR PRESSURISATION SHAFT3000mm(L)x1000mm(W) INTERNAL DIMENSIONS. LOCATION CAN BEANYWHERE AROUND THE STAIRWELL.5. STAIR PRESSURISATION RELIEF AIR LOUVRES AT CORRIDOR ENDSTO BE PROVIDED, 2-OFF 1200mm(L)x800mm(H) RELIEF AIR LOUVRESPER LEVEL.6. BULKHEADS PER UNIT TO BE PROVIDED FOR FAN COIL UNITSPATIALS.7. THERE IS NO PROVISION FOR KITCHEN EXHAUST IN THE COMMONAREAS. COMMON AREAS ARE PROVIDED WITH DUCTED FAN COILUNITS FOR AIR-CONDITIONING. SIZE OF CEILING CONCEALED FANCOIL UNIT TO BE 1200mm(L)x600mm(W)x400mm(H).

All indicated Dimension and areas are indicative and for thepurpose of initial spatial allowances, final arrangement anddimensions to be further developed during detailed designstages

Page 34: BUILDING SERVICES BRIEF - Major Projects

DA3001

1

9 GIBBONS STREET

EXISTING RESIDENTIAL FLAT BUILDING

80-88 REGENT ST -

FUTURE 18

STOREY STUDENT

HOUSING BUILDING UNDER

CONSTRUCTION

11 GIBBONS ST - FUTURE 18 STOREY

AFFORDABLE HOUSING BUILDING UNDER CONSTRUCTION

R E G E N T S T R E E T

M A

R I A

N S

T R

E E

T

W I L L I A M L A N E

116

REGENT STREET

1225

4050

3050

8960

6205

14436

2000

1246

9

37 m²

COMMON

2080

1540DA3001

1

9 GIBBONS STREET

EXISTING RESIDENTIAL FLAT BUILDING

80-88 REGENT ST -

FUTURE 18

STOREY STUDENT

HOUSING BUILDING UNDER

CONSTRUCTION

11 GIBBONS ST - FUTURE 18 STOREY

AFFORDABLE HOUSING BUILDING UNDER CONSTRUCTION

R E G E N T S T R E E T

M A

R I A

N S

T R

E E

T

W I L L I A M L A N E

116

REGENT STREET

39 m²

COMMON

TWIN STUDIO

QUEEN STUDIO

DDA

COMMON

ADMINISTRATION

DDA STUDIO

DORM OUTDOOR

GYM

KITCHEN

OUTDOOR

OUTDOORDINING

BOH

RETAIL

SERVICES

STAIR

CORRIDOR

1225

4050

3050

8960

ø 1000

ø 1550

6205

1246

9

2080

1540

N

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PLO

T D

AT

E &

TIM

E:

PLO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION

1 : 200 @A112

28

/09

/202

0 1

2:4

2:4

9 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

LEVEL 9 & 15 COMMUNALFLOOR PLANS

DA2003Wee Hur Regent

CD

90 - 102 Regent Street, Redfern

19026

2 06/05/2020 Issue for Information RP BM

3 11/05/2020 Issue for Information

4 18/06/2020 Issue for Information

5 30/07/2020 Issue for Information RP BM

6 10/08/2020 Issue for Coordination RP BM

7 13/08/2020 Issue for Information RP BM

8 25/08/2020 Issue for Coordination RP BM

9 31/08/2020 Issue for Coordination RP BM

10 11/09/2020 Issue for Coordination RP BM

11 14/09/2020 Issue for Coordination RP BM

12 24/09/2020 Issue for Information RP BM

1 : 200

LEVEL 9 PLAN1 1 : 200

LEVEL 15 PLAN2

HYDR RISER1200mm(L)x900mm(W) INTERNAL DIMENSIONSWITH 600x600mmSIDE ACCESS PANELFROM THE LAUNDRY

STAIR PRESSURISATION RISER3000mm(L)x1000mm(W)INTERNAL DIMENSIONS

STAIR PRESSURISATION GRILLE1800mm(L)x1000mm(H) ASSUME 50% FREE AREAEVERY 3 LEVELS ONLY

STAIR PRESSURISATION RELIEF AIR LOUVRE3000mm(L)x800mm(H) ASSUME 50% FREE AREA

ELECTRICAL CUPBOARD1350mm(W)x400mm(D)CLEAR INTERNALDIMENSIONSWITH FULL FACE DOORS

COMMS CUPBOARD1650mm(W)x800mm(D)INTERNAL DIMENSIONSWITH FULL FACE DOORS

FH/SPRINKLER RISER1200mm(L)x350mm(W)

HYDR RISER900mm(L)x300mm(W)WITH SIDE ACCESS PANELFROM TOILETTYPICAL TO ACCOM. UNITS

OUTSIDE AIR DUCT RISER (TYPICAL TO ALL RESIDENTIAL UNITS)300mm(W)x300mm(D)INTERNAL DIMENSIONS

REFRIGERANT PIPE RISERminimum1300mm(W)x600mm(D)INTERNAL DIMENSIONS

HYDR RISER1200mm(L)x900mm(W) INTERNAL DIMENSIONSWITH 600x600mmSIDE ACCESS PANELFROM THE LAUNDRY

STAIR PRESSURISATION RISER3000mm(L)x1000mm(W)INTERNAL DIMENSIONS

STAIR PRESSURISATION GRILLE1800mm(L)x1000mm(H) ASSUME 50% FREE AREAEVERY 3 LEVELS ONLY

STAIR PRESSURISATION RELIEF AIR LOUVRE3000mm(L)x800mm(H) ASSUME 50% FREE AREA

ELECTRICAL CUPBOARD1350mm(W)x400mm(D)CLEAR INTERNALDIMENSIONSWITH FULL FACE DOORS

COMMS CUPBOARD1650mm(W)x800mm(D)INTERNAL DIMENSIONSWITH FULL FACE DOORS

FH/SPRINKLER RISER1200mm(L)x350mm(W)

HYDR RISER900mm(L)x300mm(W)WITH SIDE ACCESS PANELFROM TOILETTYPICAL TO ACCOM. UNITS

OUTSIDE AIR DUCT RISER (TYPICAL TO ALL RESIDENTIAL UNITS)300mm(W)x300mm(D)INTERNAL DIMENSIONS

REFRIGERANT PIPE RISERminimum1300mm(W)x600mm(D)INTERNAL DIMENSIONS

MECHANICAL NOTES:

1. ALL ROOMS ARE PROVIDED WITH TOILET EXHAUST FANS (300MMdia.) AND 200mm x 200mm EXHAUST AIR DUCT TO FACADE.2. ALL ROOMS ARE ASSUMED TO HAVE RECIRCULATING KITCHENRANGE HOOD.3. ALL ROOMS MUST HAVE TRANSFER AIR GRILLES 200mm x 200mm,TRANSFERRING AIR FROM THE CORRIDOR TO EACH ROOM WHEN THETOILET EXHAUST FAN IS TURNED ON. TOILET DOORS MUST ALSOHAVE DOOR LOUVRES.4. THERE SHOULD BE ANOTHER STAIR PRESSURISATION SHAFT3000mm(L)x1000mm(W) INTERNAL DIMENSIONS. LOCATION CAN BEANYWHERE AROUND THE STAIRWELL.5. STAIR PRESSURISATION RELIEF AIR LOUVRES AT CORRIDOR ENDSTO BE PROVIDED, 2-OFF 1200mm(L)x800mm(H) RELIEF AIR LOUVRESPER LEVEL.6. BULKHEADS PER UNIT TO BE PROVIDED FOR FAN COIL UNITSPATIALS.7. THERE IS NO PROVISION FOR KITCHEN EXHAUST IN THE COMMONAREAS. COMMON AREAS ARE PROVIDED WITH DUCTED FAN COILUNITS FOR AIR-CONDITIONING. SIZE OF CEILING CONCEALED FANCOIL UNIT TO BE 1200mm(L)x600mm(W)x400mm(H).

All indicated Dimension and areas are indicative and for thepurpose of initial spatial allowances, final arrangement anddimensions to be further developed during detailed designstages

Page 35: BUILDING SERVICES BRIEF - Major Projects

RL 86.300

RL 86.300

DA3001

1

9 GIBBONS STREET

EXISTING RESIDENTIAL FLAT BUILDING

80-88 REGENT ST -

FUTURE 18

STOREY STUDENT

HOUSING BUILDING UNDER

ASSESSMENT

11 GIBBONS ST - FUTURE 18 STOREY

AFFORDABLE HOUSING BUILDING UNDER ASSESSMENT

R E G E N T S T R E E T

M A

R I A

N S

T R

E E

T

W I L L I A M L A N E

116

REGENT STREET

CENTRE OF LOT BOUNDARY

GENERAL STREET ALIGNMENT

GE

NE

RA

L S

TR

EE

T A

LIG

NM

EN

T

9M SETBACKFROM CENTRE OF

WILLIAM LANE LEVEL 4 AND ABOVE

9M S

ET

BA

CK

LEV

EL 4 A

ND

AB

OV

E

3M S

ET

BA

CK

LEV

EL 4 A

ND

AB

OV

E

4M SETBACK LEVEL 3 AND ABOVE

8960

3050

6169

4050

DA3001

1

9 GIBBONS STREET

EXISTING RESIDENTIAL FLAT BUILDING

80-88 REGENT ST -

FUTURE 18

STOREY STUDENT

HOUSING BUILDING UNDER

CONSTRUCTION

11 GIBBONS ST - FUTURE 18 STOREY

AFFORDABLE HOUSING BUILDING UNDER CONSTRUCTION

R E G E N T S T R E E T

M A

R I A

N S

T R

E E

T

W I L L I A M L A N E

116

REGENT STREET

9m SET BACK FROM CENTRE OF

WILLIAM LANE ABOVE PODIUM

3M S

ET

BA

CK

LEV

EL 3 A

ND

AB

OV

E

9m S

ET

BA

CK

CENTRE OF LANE

4m SET BACK LEVEL ABOVE PODIUMGENERAL STREET ALIGNMENT

GE

NE

RA

L S

TR

EE

T A

LIG

NM

EN

T

6.5m S

ET

BA

CK

TWIN STUDIO

QUEEN STUDIO

DDA

COMMON

ADMINISTRATION

DDA STUDIO

DORM OUTDOOR

GYM

KITCHEN

OUTDOOR

OUTDOORDINING

BOH

RETAIL

SERVICES

STAIR

CORRIDOR

8960

1225

3050

14436

ø 1000

ø 1550

6205

4050

1246

9

2080

1540

N

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PLO

T D

AT

E &

TIM

E:

PLO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION

1 : 200 @A111

28

/09

/202

0 1

2:4

2:5

3 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

UPPER TYPICAL & ROOFPLAN

DA2004Wee Hur Regent

Auth

or

90 - 102 Regent Street, Redfern

19026

1 03/04/2020 Issue for Information RP BM

2 11/05/2020 Issue for Information

3 18/06/2020 Issue for Information

4 30/07/2020 Issue for Information RP BM

5 10/08/2020 Issue for Coordination RP BM

6 13/08/2020 Issue for Information RP BM

7 25/08/2020 Issue for Coordination RP BM

8 31/08/2020 Issue for Coordination RP BM

9 11/09/2020 Issue for Coordination RP BM

10 14/09/2020 Issue for Coordination RP BM

11 24/09/2020 Issue for Information RP BM

1 : 200

ROOF1

1 : 200

LEVEL 13-18 FLOOR PLAN2

HYDR RISER1200mm(L)x900mm(W) INTERNAL DIMENSIONSWITH 600x600mmSIDE ACCESS PANELFROM THE LAUNDRY

STAIR PRESSURISATION RISER3000mm(L)x1000mm(W)INTERNAL DIMENSIONS

STAIR PRESSURISATION GRILLE1800mm(L)x1000mm(H) ASSUME 50% FREE AREAEVERY 3 LEVELS ONLY

STAIR PRESSURISATION RELIEF AIR LOUVRE3000mm(L)x800mm(H) ASSUME 50% FREE AREA

ELECTRICAL CUPBOARD1350mm(W)x400mm(D)CLEAR INTERNALDIMENSIONSWITH FULL FACE DOORS

COMMS CUPBOARD1650mm(W)x800mm(D)INTERNAL DIMENSIONSWITH FULL FACE DOORS

FH/SPRINKLER RISER1200mm(L)x350mm(W)

HYDR RISER900mm(L)x300mm(W)WITH SIDE ACCESS PANELFROM TOILETTYPICAL TO ACCOM. UNITS

OUTSIDE AIR DUCT RISER (TYPICAL TO ALL RESIDENTIAL UNITS)300mm(W)x300mm(D)INTERNAL DIMENSIONS

REFRIGERANT PIPE RISERminimum1300mm(W)x600mm(D)INTERNAL DIMENSIONS

MECHANICAL NOTES:

1. ALL ROOMS ARE PROVIDED WITH TOILET EXHAUST FANS (300MMdia.) AND 200mm x 200mm EXHAUST AIR DUCT TO FACADE.2. ALL ROOMS ARE ASSUMED TO HAVE RECIRCULATING KITCHENRANGE HOOD.3. ALL ROOMS MUST HAVE TRANSFER AIR GRILLES 200mm x 200mm,TRANSFERRING AIR FROM THE CORRIDOR TO EACH ROOM WHEN THETOILET EXHAUST FAN IS TURNED ON. TOILET DOORS MUST ALSOHAVE DOOR LOUVRES.4. THERE SHOULD BE ANOTHER STAIR PRESSURISATION SHAFT3000mm(L)x1000mm(W) INTERNAL DIMENSIONS. LOCATION CAN BEANYWHERE AROUND THE STAIRWELL.5. STAIR PRESSURISATION RELIEF AIR LOUVRES AT CORRIDOR ENDSTO BE PROVIDED, 2-OFF 1200mm(L)x800mm(H) RELIEF AIR LOUVRESPER LEVEL.6. BULKHEADS PER UNIT TO BE PROVIDED FOR FAN COIL UNITSPATIALS.7. THERE IS NO PROVISION FOR KITCHEN EXHAUST IN THE COMMONAREAS. COMMON AREAS ARE PROVIDED WITH DUCTED FAN COILUNITS FOR AIR-CONDITIONING. SIZE OF CEILING CONCEALED FANCOIL UNIT TO BE 1200mm(L)x600mm(W)x400mm(H).

HEAT PUMPS1800mm(L)x800mm(W)SEE DETAIL

CENTRALISED ELECTRIC HOT WATERPLANTROOM20000mm(L)x7000mm(W)

HYDR RISER1200mm(L)x900mm(W)

ELECTRIC STORAGE TANKDIA. = 1600mm

MECHANICAL PLANT AREA (SHOULD BEOPEN TO THE ENVIRONMENT)TOTAL AREA = 80 m2

12-OFF 1900mm(L)x800mm(W)x1800mm(H) VRFCONDENSING UNITS SERVING LEVEL 7-18

REFRIGERANT PIPE RISER1300mm(W)x600mm(D)INTERNAL DIMENSIONS

OUTSIDE AIR DUCT AND FAN (TYPICALTO ALL TOILET RISERS)1200mm(L)x600mm(W)SPACE PROVISION FOR EACH RISER'SOUTSIDE AIR FAN AND DUCT

GARBAGE CHUTE EXHAUST FAN2500mm(L)x1000mm(W)

STAIR PRESSURISATION RISER3000mm(L)x1000mm(W)INTERNAL DIMENSIONS

STAIR PRESSURISATION DUCTS AND FANS8000mm(L)x5500mm(W)CAN BE PLACED ABOVE THE STAIRWELL

FIRE PUMP ROOM EXHAUST AND SUPPLY RISER2200mm(L)x900mm(W) INTERNAL DIMENSIONSRISER GOES UP TO THE ROOF

FIRE PUMP ROOM EXHAUST ANDSUPPLY FANS SPACE PROVISION6000mm(L)x3000mm(W)

2x MECHANICAL SERVICESSWITCHBOARDS TO BE LOCATED INUNDERCOVER PLANTROOM, BOARDSTO BE 800MM(D)x2000(W)X2000(H)EACH, FINAL SIZE TO BE DETERMINED

COMMS CUPBOARD1650mm(W)x800mm(D)INTERNAL DIMENSIONSWITH FULL FACE DOORS

ELECTRICAL CUPBOARD1350mm(W)x400mm(D)INTERNAL DIMENSIONSWITH FULL FACE DOORS

All indicated Dimension and areas are indicative and for thepurpose of initial spatial allowances, final arrangement anddimensions to be further developed during detailed designstages

Page 36: BUILDING SERVICES BRIEF - Major Projects

LEVEL 1 (GROUND)FFL 27.000

LEVEL 1 (GROUND)FFL 27.000

LEVEL 2FFL 31.500

LEVEL 2FFL 31.500

LEVEL 3FFL 35.300

LEVEL 3FFL 35.300

LEVEL 4FFL 38.300

LEVEL 4FFL 38.300

LEVEL 5FFL 41.300

LEVEL 5FFL 41.300

LEVEL 6FFL 44.300

LEVEL 6FFL 44.300

LEVEL 7FFL 47.300

LEVEL 7FFL 47.300

LEVEL 8FFL 50.300

LEVEL 8FFL 50.300

LEVEL 9FFL 53.300

LEVEL 9FFL 53.300

LEVEL 10FFL 56.300

LEVEL 10FFL 56.300

LEVEL 11FFL 59.300

LEVEL 11FFL 59.300

LEVEL 12FFL 62.300

LEVEL 12FFL 62.300

LEVEL 13FFL 65.300

LEVEL 13FFL 65.300

LEVEL 14FFL 68.300

LEVEL 14FFL 68.300

LEVEL 15FFL 71.300

LEVEL 15FFL 71.300

LEVEL 16FFL 74.300

LEVEL 16FFL 74.300

LEVEL 17FFL 77.300

LEVEL 17FFL 77.300

LEVEL 18FFL 80.300

LEVEL 18FFL 80.300

PlantFFL 83.300

PlantFFL 83.300

RoofSFL 86.300

RoofSFL 86.300

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

65m FROM NATURAL GROUND

BO

UN

DA

RY

BO

UN

DA

RY

1.5m SETBACK FOR FOOTPATH WIDENING

TO AVERAGE OF 3m UP TO 3 STOREYS

3m SETBACK LEVEL 4 ABOVE

NIL SETBACK TO SIDE

BOUNDARY UP TO 3 STOREYS

MARIAN LANEMARIAN LANEPROPOSED SITE

90 - 102 REGENT STREET104-116 REGENT STREET

80 - 88 REGENT STREETMARIAN LANEPROPOSED SITE

90 - 102 REGENT STREET104-116 REGENT STREET

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

3000CONTROL ENVELOPE

9000

PLANT

5250

14 m²

STAIR

OUTDOOR

AREADORM

COMMON

COMMON

43 m²

FIRE RELAY

PUMP

30 m²

OSD TANK

31 m²

SPRINKLER

TANK

8 m²

WC

38 m²

LAUNDRY83 m²

GAMES

38 m²

COMMON

8 m²

MEETING

16 m²

STUDIO

22 m²

TWIN STUDIO

16 m²

STUDIO

16 m²

STUDIO

22 m²

TWIN STUDIO

16 m²

STUDIO

22 m²

TWIN STUDIO

22 m²

TWIN STUDIO

22 m²

TWIN STUDIO

22 m²

TWIN STUDIO

22 m²

TWIN STUDIO

22 m²

TWIN STUDIO

22 m²

TWIN STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

22 m²

TWIN STUDIO

16 m²

STUDIO

16 m²

STUDIO

22 m²

TWIN STUDIO

16 m²

STUDIO

16 m²

STUDIO

22 m²

TWIN STUDIO

16 m²

STUDIO

16 m²

STUDIO

22 m²

TWIN STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

20 m²

TWIN STUDIO

22 m²

TWIN STUDIO

22 m²

TWIN STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PLO

T D

AT

E &

TIM

E:

PLO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION

As indicated@A1 4

28

/09

/202

0 1

2:4

2:5

6 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

SECTION A DA3001Wee Hur Regent

CD

90 - 102 Regent Street, Redfern

19026

1 18/06/2020 Issue for Information

2 30/07/2020 Issue for Information RP BM

3 31/08/2020 Issue for Coordination RP BM

4 28/09/2020 Issue for Information RP BM

Page 37: BUILDING SERVICES BRIEF - Major Projects

LEVEL 1 (GROUND)FFL 27.000

LEVEL 1 (GROUND)FFL 27.000

LEVEL 2FFL 31.500

LEVEL 2FFL 31.500

LEVEL 3FFL 35.300

LEVEL 3FFL 35.300

LEVEL 4FFL 38.300

LEVEL 4FFL 38.300

LEVEL 5FFL 41.300

LEVEL 5FFL 41.300

LEVEL 6FFL 44.300

LEVEL 6FFL 44.300

LEVEL 7FFL 47.300

LEVEL 7FFL 47.300

LEVEL 8FFL 50.300

LEVEL 8FFL 50.300

LEVEL 9FFL 53.300

LEVEL 9FFL 53.300

LEVEL 10FFL 56.300

LEVEL 10FFL 56.300

LEVEL 11FFL 59.300

LEVEL 11FFL 59.300

LEVEL 12FFL 62.300

LEVEL 12FFL 62.300

LEVEL 13FFL 65.300

LEVEL 13FFL 65.300

LEVEL 14FFL 68.300

LEVEL 14FFL 68.300

LEVEL 15FFL 71.300

LEVEL 15FFL 71.300

LEVEL 16FFL 74.300

LEVEL 16FFL 74.300

LEVEL 17FFL 77.300

LEVEL 17FFL 77.300

LEVEL 18FFL 80.300

LEVEL 18FFL 80.300

PlantFFL 83.300

PlantFFL 83.300

RoofSFL 86.300

RoofSFL 86.300

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

BO

UN

DA

RY

BO

UN

DA

RY

11 MARIAN STREETWILLIAM LANEPROPOSED SITE

90-102 REGENT STREETREGENT STREET131 - 133 REGENT STREET

11 MARIAN STREETWILLIAM LANEPROPOSED SITE

90-102 REGENT STREETREGENT STREET131-133 REGENT STREET

65m FROM NATURAL GROUND

4000 9000

4m SETBACK LEVEL 3 AND ABOVE

2m SETBACK TO PROVIDE THE

OPPORTUNITY FOR FOOTPATH

WIDENING

9m SETBACKFROM CENTRE

OF WILLIAM LANE LEVEL 4

AND ABOVE

COMMON

OUTDOOR

AREA Level 2 (L2). 31.500

31500

Level 3 (L3) 35.300

35300

COMMON

COMMON

16 m²

MANAGER

10 m²

KITCHEN

25 m²

OFFICE

83 m²

GAMES

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PLO

T D

AT

E &

TIM

E:

PLO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION

As indicated@A1 4

28

/09

/202

0 1

2:4

3:0

3 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

SECTION B DA3002Wee Hur Regent

AT

&JW

90 - 102 Regent Street, Redfern

19026

1 18/06/2020 Issue for Information

2 30/07/2020 Issue for Information RP BM

3 31/08/2020 Issue for Coordination RP BM

4 28/09/2020 Issue for Information RP BM

Page 38: BUILDING SERVICES BRIEF - Major Projects

LEVEL 1 (GROUND)FFL 27.000

LEVEL 1 (GROUND)FFL 27.000

LEVEL 2FFL 31.500

LEVEL 2FFL 31.500

LEVEL 3FFL 35.300

LEVEL 3FFL 35.300

LEVEL 4FFL 38.300

LEVEL 4FFL 38.300

LEVEL 5FFL 41.300

LEVEL 5FFL 41.300

LEVEL 6FFL 44.300

LEVEL 6FFL 44.300

LEVEL 7FFL 47.300

LEVEL 7FFL 47.300

LEVEL 8FFL 50.300

LEVEL 8FFL 50.300

LEVEL 9FFL 53.300

LEVEL 9FFL 53.300

LEVEL 10FFL 56.300

LEVEL 10FFL 56.300

LEVEL 11FFL 59.300

LEVEL 11FFL 59.300

LEVEL 12FFL 62.300

LEVEL 12FFL 62.300

LEVEL 13FFL 65.300

LEVEL 13FFL 65.300

LEVEL 14FFL 68.300

LEVEL 14FFL 68.300

LEVEL 15FFL 71.300

LEVEL 15FFL 71.300

LEVEL 16FFL 74.300

LEVEL 16FFL 74.300

LEVEL 17FFL 77.300

LEVEL 17FFL 77.300

LEVEL 18FFL 80.300

LEVEL 18FFL 80.300

PlantFFL 83.300

PlantFFL 83.300

RoofSFL 86.300

RoofSFL 86.300

4500

3800

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

4500

3800

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

BO

UN

DA

RY

BO

UN

DA

RY

65m FROM NATURAL GROUND

80-88 REGENT STREET MARIAN STREETPROPOSED SITE

90-102 REGENT STREET 104-116 REGENT STREET

80-88 REGENT STREET MARIAN STREETPROPOSED SITE

90-102 REGENT STREET 104-116 REGENT STREET

CONTROL ENVELOPE9000

1.5m SETBACK FOR FOOTPATH

WIDENING TO AVERAGE OF 3m

UP TO 3 STOREYS

3m SETBACK LEVEL 4 ABOVE

NIL SETBACK TO SIDE

BOUNDARY UP TO 3 STOREYS

3000

?

?COMMON

OUTDOOR

AREA

COMMON TWIN STUDIO

DDASTUDIO

6500

21 m²

DDA

21 m²

DDA

21 m²

DDA

21 m²

DDA

21 m²

DDA

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

21 m²

TWIN STUDIO

21 m²

TWIN STUDIO

21 m²

TWIN STUDIO

21 m²

TWIN STUDIO

21 m²

TWIN STUDIO

21 m²

TWIN STUDIO

21 m²

TWIN STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

21 m²

TWIN STUDIO

21 m²

TWIN STUDIO

16 m²

STUDIO

43 m²

MEETING

34 m²

KITCHEN

69 m²

BIKE STORE

10 m²

PLANT 57 m²

WASTE

84 m²

BIKE STORE

30 m²

MAIN SWITCH

ROOM

0

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PL

OT

DA

TE

& T

IME

:P

LO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION16 m2 4 8

As indicated@A1 4

28

/09

/202

0 1

2:4

3:0

9 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

SECTION C DA3003Wee Hur Regent

AT

&JW

90 - 102 Regent Street, Redfern

19026

1 18/06/2020 Issue for Information

2 30/07/2020 Issue for Information RP BM

3 31/08/2020 Issue for Coordination RP BM

4 28/09/2020 Issue for Information RP BM

Page 39: BUILDING SERVICES BRIEF - Major Projects

LEVEL 1 (GROUND)FFL 27.000

LEVEL 1 (GROUND)FFL 27.000

LEVEL 2FFL 31.500

LEVEL 2FFL 31.500

LEVEL 3FFL 35.300

LEVEL 3FFL 35.300

LEVEL 4FFL 38.300

LEVEL 4FFL 38.300

LEVEL 5FFL 41.300

LEVEL 5FFL 41.300

LEVEL 6FFL 44.300

LEVEL 6FFL 44.300

LEVEL 7FFL 47.300

LEVEL 7FFL 47.300

LEVEL 8FFL 50.300

LEVEL 8FFL 50.300

LEVEL 9FFL 53.300

LEVEL 9FFL 53.300

LEVEL 10FFL 56.300

LEVEL 10FFL 56.300

LEVEL 11FFL 59.300

LEVEL 11FFL 59.300

LEVEL 12FFL 62.300

LEVEL 12FFL 62.300

LEVEL 13FFL 65.300

LEVEL 13FFL 65.300

LEVEL 14FFL 68.300

LEVEL 14FFL 68.300

LEVEL 15FFL 71.300

LEVEL 15FFL 71.300

LEVEL 16FFL 74.300

LEVEL 16FFL 74.300

LEVEL 17FFL 77.300

LEVEL 17FFL 77.300

LEVEL 18FFL 80.300

LEVEL 18FFL 80.300

PlantFFL 83.300

PlantFFL 83.300

RoofSFL 86.300

RoofSFL 86.300

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

BO

UN

DA

RY

BO

UN

DA

RY

4000

9000

2m SETBACK TO

PROVIDE THE

OPPORTUNITY FOR

FOOTPATH WIDENING

9m SETBACKFROM

CENTRE OF WILLIAM LANE

LEVEL 4 AND ABOVE

4m SETBACK LEVEL 3 AND ABOVE

65m FROM NATURAL GROUND

11 MARIAN STREET WILLIAM LANEPROPOSED SITE

90-102 REGENT STREET REGENT STREET 137-141 REGENT STREET

11 MARIAN STREET WILLIAM LANEPROPOSED SITE

90-102 REGENT STREET REGENT STREET 137-141 REGENT STREET

5250

RETAIL

DORM DORMOUTDOOR

AREA

OUTDOOR

AREA

LOADING

Level 2 (L2). 31.500

31500

STUDIOSTUDIO

31 m²

SPRINKLER

TANK

43 m²

FIRE RELAY

PUMP51 m²

STORAGE

57 m²

WASTE

25 m²

STAIR66 m²

BASEMENT

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

16 m²

STUDIO

N

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PL

OT

DA

TE

& T

IME

:P

LO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION

As indicated@A1 4

28

/09

/202

0 1

2:4

3:1

5 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

SECTION D DA3004Wee Hur Regent

Au

tho

r

90 - 102 Regent Street, Redfern

19026

1 18/06/2020 Issue for Information

2 30/07/2020 Issue for Information RP BM

3 31/08/2020 Issue for Coordination RP BM

4 28/09/2020 Issue for Information RP BM

Page 40: BUILDING SERVICES BRIEF - Major Projects

LEVEL 1 (GROUND)FFL 27.000

LEVEL 1 (GROUND)FFL 27.000

LEVEL 2FFL 31.500

LEVEL 2FFL 31.500

LEVEL 3FFL 35.300

LEVEL 3FFL 35.300

LEVEL 4FFL 38.300

LEVEL 4FFL 38.300

LEVEL 5FFL 41.300

LEVEL 5FFL 41.300

LEVEL 6FFL 44.300

LEVEL 6FFL 44.300

LEVEL 7FFL 47.300

LEVEL 7FFL 47.300

LEVEL 8FFL 50.300

LEVEL 8FFL 50.300

LEVEL 9FFL 53.300

LEVEL 9FFL 53.300

LEVEL 10FFL 56.300

LEVEL 10FFL 56.300

LEVEL 11FFL 59.300

LEVEL 11FFL 59.300

LEVEL 12FFL 62.300

LEVEL 12FFL 62.300

LEVEL 13FFL 65.300

LEVEL 13FFL 65.300

LEVEL 14FFL 68.300

LEVEL 14FFL 68.300

LEVEL 15FFL 71.300

LEVEL 15FFL 71.300

LEVEL 16FFL 74.300

LEVEL 16FFL 74.300

LEVEL 17FFL 77.300

LEVEL 17FFL 77.300

LEVEL 18FFL 80.300

LEVEL 18FFL 80.300

PlantFFL 83.300

PlantFFL 83.300

RoofSFL 86.300

RoofSFL 86.300

65m FROM NATURAL GROUND

BO

UN

DA

RY

BO

UN

DA

RY

1.5m SETBACK FOR

FOOTPATH WIDENING TO

AVERAGE OF 3m UP TO 3

STOREYS

3m SETBACK

LEVEL 3 ABOVE

NIL SETBACK TO SIDE

BOUNDARY UP TO 3 STOREYS

9m SETBACK LEVEL 4 AND ABOVE

9000 3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

104-116 REGENT STREETPROPOSED SITE

90-102 REGENT STREET MARIAN LANE 80-88 REGENT STREET

104-116 REGENT STREETPROPOSED SITE

90-102 REGENT STREET MARIAN LANE 80-88 REGENT STREET

PC1 PC2?FP2FP1?CP2CP1 WF1WF1WF2 GL2

BK1

BK2

AWF

GL1

W1

GL2

W1

GL1

ME

AWF

GL1

MS

MS

GL2

GL1WF3

COLOUR BACK GLASS BEHIND

TYPICAL FACADE

CBG1; REFER DA3006

CBG1

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PL

OT

DA

TE

& T

IME

:P

LO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION

1 : 200 @A16

28

/09

/202

0 1

2:4

3:1

9 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

EAST ELEVATION DA3005Wee Hur Regent

AT

&JW

90 - 102 Regent Street, Redfern

19026

1 18/06/2020 Issue for Information

2 30/07/2020 Issue for Information RP BM

3 31/08/2020 Issue for Coordination RP BM

4 14/09/2020 Issue for Coordination RP BM

5 22/09/2020 Issue for Information RP BM

6 28/09/2020 Issue for Information RP BM

Page 41: BUILDING SERVICES BRIEF - Major Projects

LEVEL 1 (GROUND)FFL 27.000

LEVEL 1 (GROUND)FFL 27.000

LEVEL 2FFL 31.500

LEVEL 2FFL 31.500

LEVEL 3FFL 35.300

LEVEL 3FFL 35.300

LEVEL 4FFL 38.300

LEVEL 4FFL 38.300

LEVEL 5FFL 41.300

LEVEL 5FFL 41.300

LEVEL 6FFL 44.300

LEVEL 6FFL 44.300

LEVEL 7FFL 47.300

LEVEL 7FFL 47.300

LEVEL 8FFL 50.300

LEVEL 8FFL 50.300

LEVEL 9FFL 53.300

LEVEL 9FFL 53.300

LEVEL 10FFL 56.300

LEVEL 10FFL 56.300

LEVEL 11FFL 59.300

LEVEL 11FFL 59.300

LEVEL 12FFL 62.300

LEVEL 12FFL 62.300

LEVEL 13FFL 65.300

LEVEL 13FFL 65.300

LEVEL 14FFL 68.300

LEVEL 14FFL 68.300

LEVEL 15FFL 71.300

LEVEL 15FFL 71.300

LEVEL 16FFL 74.300

LEVEL 16FFL 74.300

LEVEL 17FFL 77.300

LEVEL 17FFL 77.300

LEVEL 18FFL 80.300

LEVEL 18FFL 80.300

PlantFFL 83.300

PlantFFL 83.300

RoofSFL 86.300

RoofSFL 86.300

65m FROM NATURAL GROUND

BO

UN

DA

RY

BO

UN

DA

RY

9000

3000

3M SETBACK LEVEL 3 AND ABOVE

0.8M SETBACK TO PROVIDE

THE OPPORTUNITY FOR

FOOTPATH WIDENING

9M SETBACKFROM

CENTRE OF WILLIAM LANE

LEVEL 4 AND ABOVE

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

11 MARIAN STREETWILLIAM LANEPROPOSED SITE

90-102 REGENT STREETREGENT STREET131-133 REGENT STREET

11 MARIAN STREETWILLIAM LANEPROPOSED SITE

90-102 REGENT STREETREGENT STREET131-133 REGENT STREET

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

Level 2 (L2). 31.500

31500

Level 3 (L3) 35.300

35300

CP2?CP2CP1FP2FP1 GL1

AWF

BK1

GL1

MEGL1

ME

CP1

CP1

WF1

AP2

FP1

or FP2

or FP2

CBG1

WF1 or WF2

or AP1

Key

1. Slab Edge Panel (150mm depth); CP12. Annodized aluminium frame; WF1 or WF23. Colour back glass to top of bed datum (720mm); CBG; fixed4. Glazing (Clear finish): GL1; operable awning window5. Sunshading fin (300mm depth); SH16. Laminated glazing unit with Frit pattern interlayer; FP1 or FP27. Structural concrete slab8. Concealed frame; clear glazing above, CBG fixed below9. Slab Edge panel; Primary frame; CP1

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PL

OT

DA

TE

& T

IME

:P

LO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION

As indicated@A1 4

28

/09

/202

0 1

2:4

3:2

3 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

NORTH ELEVATION DA3006Wee Hur Regent

AT

&JW

90 - 102 Regent Street, Redfern

19026

1 : 200

NORTH ELEVATION1

Typical Facade Isometric Detail2

1

2

3

4

56

7

8

SLAB OF FLOOR ABOVE

9

1 18/06/2020 Issue for Information

2 31/08/2020 Issue for Coordination RP BM

3 22/09/2020 Issue for Information RP BM

4 28/09/2020 Issue for Information RP BM

Page 42: BUILDING SERVICES BRIEF - Major Projects

LEVEL 1 (GROUND)FFL 27.000

LEVEL 1 (GROUND)FFL 27.000

LEVEL 2FFL 31.500

LEVEL 2FFL 31.500

LEVEL 3FFL 35.300

LEVEL 3FFL 35.300

LEVEL 4FFL 38.300

LEVEL 4FFL 38.300

LEVEL 5FFL 41.300

LEVEL 5FFL 41.300

LEVEL 6FFL 44.300

LEVEL 6FFL 44.300

LEVEL 7FFL 47.300

LEVEL 7FFL 47.300

LEVEL 8FFL 50.300

LEVEL 8FFL 50.300

LEVEL 9FFL 53.300

LEVEL 9FFL 53.300

LEVEL 10FFL 56.300

LEVEL 10FFL 56.300

LEVEL 11FFL 59.300

LEVEL 11FFL 59.300

LEVEL 12FFL 62.300

LEVEL 12FFL 62.300

LEVEL 13FFL 65.300

LEVEL 13FFL 65.300

LEVEL 14FFL 68.300

LEVEL 14FFL 68.300

LEVEL 15FFL 71.300

LEVEL 15FFL 71.300

LEVEL 16FFL 74.300

LEVEL 16FFL 74.300

LEVEL 17FFL 77.300

LEVEL 17FFL 77.300

LEVEL 18FFL 80.300

LEVEL 18FFL 80.300

PlantFFL 83.300

PlantFFL 83.300

RoofSFL 86.300

RoofSFL 86.300

BO

UN

DA

RY

BO

UN

DA

RY

65m FROM NATURAL GROUND

1.5m SETBACK FOR FOOTPATH

WIDENING TO AVERAGE OF 3m UP TO 3

STOREYS

3m SETBACK LEVEL 4 ABOVE

NIL SETBACK TO SIDE

BOUNDARY UP TO 3 STOREYS

9m SETBACK LEVEL 4 AND ABOVE

90003000

80-88 REGENT STREET MARIAN STREETPROPOSED SITE

90-102 REGENT STREET 104-116 REGENT STREET

80-88 REGENT STREET MARIAN STREETPROPOSED SITE

90-102 REGENT STREET 104-116 REGENT STREET

4500

3800

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

4500

3800

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

FIRE ESCAPE

EGRESS FROM

LOADING AREA

MAIN GARAGE

DOOR

548

SUBSTATION 4988450

LOADING EGRESS1433621

LOADING DOCK DOOR76004845577

BIKE STORE7332626

DISABLED ACCESS 1:12 RAMP9957

SUBSTATION

ACCESS TO

MSB

PC1 PC2 GL1 ?FP2 FP1GL1 CP3CP2 CP1

W1

BK2

BK2

AWF

BK1

AWF

GL1

?

GL1

W1

LW

W1 ROLLER DOOR TEXTURE

?

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PL

OT

DA

TE

& T

IME

:P

LO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION

1 : 200 @A15

28

/09

/202

0 1

2:4

3:2

9 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

WEST ELEVATION DA3007Wee Hur Regent

AT

&JW

90 - 102 Regent Street, Redfern

19026

1 18/06/2020 Issue for Information

2 30/07/2020 Issue for Information RP BM

3 31/08/2020 Issue for Coordination RP BM

4 22/09/2020 Issue for Information RP BM

5 28/09/2020 Issue for Information RP BM

Page 43: BUILDING SERVICES BRIEF - Major Projects

LEVEL 1 (GROUND)FFL 27.000

LEVEL 1 (GROUND)FFL 27.000

LEVEL 2FFL 31.500

LEVEL 2FFL 31.500

LEVEL 3FFL 35.300

LEVEL 3FFL 35.300

LEVEL 4FFL 38.300

LEVEL 4FFL 38.300

LEVEL 5FFL 41.300

LEVEL 5FFL 41.300

LEVEL 6FFL 44.300

LEVEL 6FFL 44.300

LEVEL 7FFL 47.300

LEVEL 7FFL 47.300

LEVEL 8FFL 50.300

LEVEL 8FFL 50.300

LEVEL 9FFL 53.300

LEVEL 9FFL 53.300

LEVEL 10FFL 56.300

LEVEL 10FFL 56.300

LEVEL 11FFL 59.300

LEVEL 11FFL 59.300

LEVEL 12FFL 62.300

LEVEL 12FFL 62.300

LEVEL 13FFL 65.300

LEVEL 13FFL 65.300

LEVEL 14FFL 68.300

LEVEL 14FFL 68.300

LEVEL 15FFL 71.300

LEVEL 15FFL 71.300

LEVEL 16FFL 74.300

LEVEL 16FFL 74.300

LEVEL 17FFL 77.300

LEVEL 17FFL 77.300

LEVEL 18FFL 80.300

LEVEL 18FFL 80.300

PlantFFL 83.300

PlantFFL 83.300

RoofSFL 86.300

RoofSFL 86.300

BO

UN

DA

RY

BO

UN

DA

RY

65m FROM NATURAL GROUND

9000 3000

4M SETBACK LEVEL 3 AND ABOVE0.8M SETBACK TO PROVIDE THE

OPPORTUNITY FOR FOOTPATH

WIDENING

9M SETBACKFROM CENTRE OF

WILLIAM LANE LEVEL 4 AND ABOVE

11 MARIAN STREET WILLIAM LANEPROPOSED SITE

90-102 REGENT STREET REGENT STREET 137-141 REGENT STREET

11 MARIAN STREET WILLIAM LANEPROPOSED SITE

90-102 REGENT STREET REGENT STREET 137-141 REGENT STREET

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3800

4500

Level 2 (L2). 31.500

31500

Level 3 (L3) 35.300

35300

PC1 PC2 GL2

TRANSLUCENT? CP1CP2GL1PC1WF3

BK1

BK2

BK2

GL1

GL1

AWF

AWF

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PL

OT

DA

TE

& T

IME

:P

LO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION

1 : 200 @A15

28

/09

/202

0 1

2:4

3:3

9 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

SOUTH ELEVATION DA3008Wee Hur Regent

AT

&JW

90 - 102 Regent Street, Redfern

19026

1 18/06/2020 Issue for Information

2 30/07/2020 Issue for Information RP BM

3 31/08/2020 Issue for Coordination RP BM

4 22/09/2020 Issue for Information RP BM

5 28/09/2020 Issue for Information RP BM

Page 44: BUILDING SERVICES BRIEF - Major Projects

Key Client Architect Project Drawing Title Scale Drawing No. IssueRevisions

Do not scale drawings. Use figured dimensions only. Check & verify levels and dimensions on site prior to the commencement of any work, the preparation of shop drawings or the fabrication of components. This drawing is the copyright of Allen Jack + Cottier Architects and is protected under the Copyright Act 1968. Do not alter, reproduce or transmitt in any form, or by any means without the express permission of Allen Jack + Cottier Architects. Nominated Architects: Michael Heenan 5264, Peter Ireland 6661

PL

OT

DA

TE

& T

IME

:P

LO

TT

ED

& C

HE

CK

ED

BY

:R

EF

:

No. Date Description Verified Approved

Proj. No.

79 Myrtle Street Chippendale NSW 2008 AUSTRALIAph +61 2 9311 8222 fx +61 2 9311 8200ABN 53 003 782 250

Sheet Status

NOT FOR CONSTRUCTION

@A12

28

/09

/202

0 1

2:4

3:4

0 P

MC

:\U

se

rs\P

ee

ters

\Do

cum

ents

\19

026

_M

aste

r_P

ee

ters

.rvt

MATERIAL BOARD DA3011Wee Hur Regent

Au

tho

r

90 - 102 Regent Street, Redfern

19026

LGU FRIT PATTERN

DULUX ANOTEC MID BRONZE

30% PERFORATION

PRECAST CONCRETE PANEL TINT 1

KIEM 9288

PRECAST CONCRETE PANEL TINT 2

KEIM 9292

WINDOW FRAME

DULUX ANOTEC MID BRONZE

BRICK CAVITY WALL 1

PGH DRY BLACK BEAUTY

PC1

PC2

FP1

FP2

WF1

BK1

LOUVRED WALL WITH BUILT IN DOOR ACCESS

DULUX MONUMENT

LW

COLOUR BACK GLASS

DULUX PEWTER PEARLCBG1

CAPPING PLATE

DULUX ANOTEC MID BRONZE CP1

BRICK CAVITY WALL 2

PGH DRY HAWKESBURY BRONZE

BK2

PERFORATED MESH SHADE

DULUX ANOTEC MID BRONZE

30% PERFORATION

FOOTPATH AWNING

DULUX MONUMENT TO TOP AND SIDES

DULUX ELECTRO DURATE ZUES TALC TO SOFFIT

SH1 AWF

LGU FRIT PATTERN

DULUX JASPER

30% PERFORATION

WINDOW FRAME

DULUX JASPERWF2

CAPPING PLATE

DULUX JASPER

CP2

CAPPING PLATE

BASSET BROWNCP3

PODIUM WALL

DULUX MONUMENT

W1

GL1 GLAZING

CLEAR LAMINATED GLAZING

GL2 GLAZING

DARK TINT LAMINATED GLAZING

COLOUR BACK GLASS

MONUMENTCBG2

METAL EXTRUSION

DULUX MONUMENT

ME

MESH

DULUX MONUMENT

50% PERFORATION

MS

WINDOW FRAME

DULUX MONUMENTWF3

1 22/09/2020 Issue for Information RP BM

2 28/09/2020 Issue for Information RP BM

PERFORATED MESH SHADE

DULUX JASPER

30% PERFORATION

SH2

ANGLED LOUVRE

DULUX MONUMENT

LV1

ALUMINIUM PANEL

DULUX ANOTEC MID BRONZEAP1

ALUMINIUM PANEL

DULUX JASPERAP2

VENTILATION GRILLE

DULUX JASPER OR DULUX ANOTEC MID

BRONZE TO MATCH ADJOINING AP

VG1