Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems...

38
Promulgated by the Texas Real Estate Commission (TREC) P.O. Box 12188, Austin, TX 78711-2188 (512) 936-3000 (http://www.trec.texas.gov). REI 7-5 (Revised 05/4/2015) Image Inspections LLC 16107 Kensington Dr. #132 Sugar Land TX 77479 832.687.3851 [email protected] - PROPERTY INSPECTION REPORT Prepared For: Sample Report (Name of Client) Concerning: 12345 Example St, Houston, TX 77035 (Address or Other Identification of Inspected Property) By: Robert Waitschies TREC#5814 01/19/2016 (Name and License Number of Inspector) (Date) PURPOSE, LIMITATIONS AND INSPECTOR / CLIENT RESPONSIBILITIES This property inspection report may include an inspection agreement (contract), addenda, and other information related to property conditions. If any item or comment is unclear, you should ask the inspector to clarify the findings. It is important that you carefully read ALL of this information. This inspection is subject to the rules (“Rules”) of the Texas Real Estate Commission (“TREC”), which can be found at www.trec.texas.gov . The TREC Standards of Practice (Sections 535.227-535.233 of the Rules) are the minimum standards for inspections by TREC licensed inspectors. An inspection addresses only those components and conditions that are present, visible, and accessible at the time of the inspection. While there may be other parts, components or systems present, only those items specifically noted as being inspected were inspected. The inspector is NOT required to turn on decommissioned equipment, systems, utility services or apply an open flame or light a pilot to operate any appliance. The inspector is NOT required to climb over obstacles, move furnishings or stored items. The inspection report may address issues that are code-based or may refer to a particular code; however, this is NOT a code compliance inspection and does NOT verify compliance with manufacturer’s installation instructions. The inspection does NOT imply insurability or warrantability of the structure or its components. Although some safety issues may be addressed in this report, this inspection is NOT a safety/code inspection, and the inspector is NOT required to identify all potential hazards. In this report, the inspector shall indicate, by checking the appropriate boxes on the form, whether each item was inspected, not inspected, not present or deficient and explain the findings in the corresponding section in the body of the report form. The inspector must check the Deficient (D) box if a condition exists that adversely and materially affects the performance of a system or component or constitutes a hazard to life, limb or property as specified by the TREC Standards of Practice. General deficiencies include inoperability, material distress, water penetration, damage, deterioration, missing components, and unsuitable installation. Comments may be provided by the inspector whether or not an item is deemed deficient. The inspector is not required to prioritize or emphasize the importance of one deficiency over another. Some items reported may be considered life-safety upgrades to the property. For more information, refer to Texas Real Estate Consumer Notice Concerning Recognized Hazards or Deficiencies below. THIS PROPERTY INSPECTION IS NOT A TECHNICALLY EXHAUSTIVE INSPECTION OF THE STRUCTURE, SYSTEMS OR COMPONENTS. The inspection may not reveal all deficiencies. A real estate inspection helps to reduce some of the risk involved in purchasing a home, but it cannot eliminate these risks, nor can the inspection anticipate future events or changes in performance due to changes in use or occupancy. It is recommended that you obtain as much information as is available about this property, including any seller’s disclosures, previous inspection reports, engineering reports, building/remodeling permits, and reports performed for or by relocation companies, municipal inspection departments, lenders, insurers, and appraisers. You should also attempt to determine whether repairs, renovation, remodeling, additions, or other such activities have taken place

Transcript of Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems...

Page 1: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Promulgated by the Texas Real Estate Commission (TREC) P.O. Box 12188, Austin, TX 78711-2188 (512) 936-3000

(http://www.trec.texas.gov). REI 7-5 (Revised 05/4/2015)

Image Inspections LLC

16107 Kensington Dr. #132

Sugar Land TX 77479

832.687.3851

[email protected]

-

PROPERTY INSPECTION REPORT

Prepared For: Sample Report

(Name of Client)

Concerning: 12345 Example St, Houston, TX 77035

(Address or Other Identification of Inspected Property)

By: Robert Waitschies TREC#5814 01/19/2016

(Name and License Number of Inspector)

(Date)

PURPOSE, LIMITATIONS AND INSPECTOR / CLIENT RESPONSIBILITIES

This property inspection report may include an inspection agreement (contract), addenda, and other information related to property

conditions. If any item or comment is unclear, you should ask the inspector to clarify the findings. It is important that you carefully

read ALL of this information.

This inspection is subject to the rules (“Rules”) of the Texas Real Estate Commission (“TREC”), which can be found at

www.trec.texas.gov.

The TREC Standards of Practice (Sections 535.227-535.233 of the Rules) are the minimum standards for inspections by TREC

licensed inspectors. An inspection addresses only those components and conditions that are present, visible, and accessible at the

time of the inspection. While there may be other parts, components or systems present, only those items specifically noted as being

inspected were inspected. The inspector is NOT required to turn on decommissioned equipment, systems, utility services or apply

an open flame or light a pilot to operate any appliance. The inspector is NOT required to climb over obstacles, move furnishings or

stored items. The inspection report may address issues that are code-based or may refer to a particular code; however, this is NOT

a code compliance inspection and does NOT verify compliance with manufacturer’s installation instructions. The inspection does

NOT imply insurability or warrantability of the structure or its components. Although some safety issues may be addressed in this

report, this inspection is NOT a safety/code inspection, and the inspector is NOT required to identify all potential hazards.

In this report, the inspector shall indicate, by checking the appropriate boxes on the form, whether each item was inspected, not

inspected, not present or deficient and explain the findings in the corresponding section in the body of the report form. The

inspector must check the Deficient (D) box if a condition exists that adversely and materially affects the performance of a system

or component or constitutes a hazard to life, limb or property as specified by the TREC Standards of Practice. General deficiencies

include inoperability, material distress, water penetration, damage, deterioration, missing components, and unsuitable installation.

Comments may be provided by the inspector whether or not an item is deemed deficient. The inspector is not required to prioritize

or emphasize the importance of one deficiency over another.

Some items reported may be considered life-safety upgrades to the property. For more information, refer to Texas Real Estate

Consumer Notice Concerning Recognized Hazards or Deficiencies below.

THIS PROPERTY INSPECTION IS NOT A TECHNICALLY EXHAUSTIVE INSPECTION OF THE STRUCTURE,

SYSTEMS OR COMPONENTS. The inspection may not reveal all deficiencies. A real estate inspection helps to reduce some of

the risk involved in purchasing a home, but it cannot eliminate these risks, nor can the inspection anticipate future events or

changes in performance due to changes in use or occupancy. It is recommended that you obtain as much information as is available

about this property, including any seller’s disclosures, previous inspection reports, engineering reports, building/remodeling

permits, and reports performed for or by relocation companies, municipal inspection departments, lenders, insurers, and appraisers.

You should also attempt to determine whether repairs, renovation, remodeling, additions, or other such activities have taken place

Page 2: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 2 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

at this property. It is not the inspector’s responsibility to confirm that information obtained from these sources is complete or

accurate or that this inspection is consistent with the opinions expressed in previous or future reports.

ITEMS IDENTIFIED IN THE REPORT DO NOT OBLIGATE ANY PARTY TO MAKE REPAIRS OR TAKE OTHER

ACTIONS, NOR IS THE PURCHASER REQUIRED TO REQUEST THAT THE SELLER TAKE ANY ACTION. When a

deficiency is reported, it is the client’s responsibility to obtain further evaluations and/or cost estimates from qualified service

professionals. Any such follow-up should take place prior to the expiration of any time limitations such as option periods.

Evaluations by qualified tradesmen may lead to the discovery of additional deficiencies which may involve additional repair costs.

Failure to address deficiencies or comments noted in this report may lead to further damage of the structure or systems and add to

the original repair costs. The inspector is not required to provide follow-up services to verify that proper repairs have been made.

Property conditions change with time and use. For example, mechanical devices can fail at any time, plumbing gaskets and seals

may crack if the appliance or plumbing fixture is not used often, roof leaks can occur at any time regardless of the apparent

condition of the roof, and the performance of the structure and the systems may change due to changes in use or occupancy, effects

of weather, etc. These changes or repairs made to the structure after the inspection may render information contained herein

obsolete or invalid. This report is provided for the specific benefit of the client named above and is based on observations at the

time of the inspection. If you did not hire the inspector yourself, reliance on this report may provide incomplete or outdated

information. Repairs, professional opinions or additional inspection reports may affect the meaning of the information in this

report. It is recommended that you hire a licensed inspector to perform an inspection to meet your specific needs and to provide

you with current information concerning this property.

TEXAS REAL ESTATE CONSUMER NOTICE CONCERNING HAZARDS OR DEFICIENCIES

Each year, Texans sustain property damage and are injured by accidents in the home. While some accidents may not be avoidable,

many other accidents, injuries, and deaths may be avoided through the identification and repair of certain hazardous conditions.

Examples of such hazards include:

Malfunctioning, improperly installed, or missing ground fault circuit protection (GFCI) devices for electrical receptacles

in garages, bathrooms, kitchens, and exterior areas;

Malfunctioning arc fault protection (AFCI) devices;

Ordinary glass in locations where modern construction techniques call for safety glass;

Malfunctioning or lack of fire safety features such as smoke alarms, fire-rated doors in certain locations, and functional

emergency escape and rescue openings in bedrooms;

Malfunctioning carbon monoxide alarms;

Excessive spacing between balusters on stairways and porches;

Improperly installed appliances;

Improperly installed or defective safety devices;

Lack of electrical bonding and grounding; and

Lack of bonding on gas piping, including corrugated stainless steel tubing (CSST).

To ensure that consumers are informed of hazards such as these, the Texas Real Estate Commission (TREC) has adopted

Standards of Practice requiring licensed inspectors to report these conditions as “Deficient” when performing an inspection for a

buyer or seller, if they can be reasonably determined.

These conditions may not have violated building codes or common practices at the time of the construction of the home, or they

may have been “grandfathered” because they were present prior to the adoption of codes prohibiting such conditions.

While the TREC Standards of Practice do not require inspectors to perform a code compliance inspection, TREC considers the

potential for injury or property loss from the hazards addressed in the Standards of Practice to be significant enough to warrant this

notice.

Contract forms developed by TREC for use by its real estate licensees also inform the buyer of the right to have the home

inspected and can provide an option clause permitting the buyer to terminate the contract within a specified time. Neither the

Standards of Practice nor the TREC contract forms require a seller to remedy conditions revealed by an inspection. The decision to

correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale or purchase of

the home.

INFORMATION INCLUDED UNDER "ADDITIONAL INFORMATION PROVIDED BY INSPECTOR", OR PROVIDED AS

AN ATTACHMENT WITH THE STANDARD FORM, IS NOT REQUIRED BY THE COMMISSION AND MAY CONTAIN

Page 3: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 3 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

CONTRACTUAL TERMS BETWEEN THE INSPECTOR AND YOU, AS THE CLIENT. THE COMMISSION DOES NOT

REGULATE CONTRACTUAL TERMS BETWEEN PARTIES. IF YOU DO NOT UNDERSTAND THE EFFECT OF ANY

CONTRACTUAL TERM CONTAINED IN THIS SECTION OR ANY ATTACHMENTS, CONSULT AN ATTORNEY.

ADDITIONAL INFORMATION PROVIDED BY INSPECTOR

Page 4: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 4 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

PROPERTY INSPECTION AGREEMENT

Client -

Property Street Address -

In consideration of the inspection fee of $ paid by Client to Inspector, the receipt and sufficiency of which is hereby acknowledged by Inspector, and pursuant to this

Property Inspection Agreement (this “Agreement”), Image Inspections LLC. (the “Inspector”), agrees to conduct an inspection for the purpose of informing Client of major deficiencies in the condition of certain improvements located on the Property described above. The written report produced by the Inspector regarding the Property is the confidential

property of the Inspector and Client and shall not be copied, reproduced, used by, transferred to, or relied upon by any other person or company without both the Inspector’s and

Client’s prior written consent.

1. PURPOSE AND SCOPE OF INSPECTION. The purpose of this one-time inspection is to identify and disclose visually observable major deficiencies of the inspected

systems and items at the time of the inspection only. A system or component has a major defect if it is unsafe or not functioning and cannot be replaced or rendered safe or functional

for less than $1,000. The following items are not covered in the scope of the inspection: Any area that is not exposed to view, is concealed, or is inaccessible because of soil, walls,

wall coverings, floors, floor coverings, ceilings, insulation, furnishings, stored items, built-in cabinets or shelves, etc., or those areas/items that have been excluded by the TREC

standards, as well as detached buildings, fences and gates, landscaping, elevators, lifts, dumbwaiters, media equipment, telephone equipment, security equipment, intercoms, water treatment devices, thermostatic or time clock controls, radiant heat systems, solar heating systems, furnace heat exchangers, alarm systems, draperies, blinds, shutters, hardware,

formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate leaks, drains, sprinkler systems

in automatic mode or when outside temperature is below thirty-two (32) degrees, landscape lighting, sewer lines, septic systems, water wells, solar heating systems, water conditioning systems, and low voltage lighting. Regarding pools, hot tubs, saunas, steam baths, ponds, and fountains, only above-ground portions of such improvements are

inspected, provided, however, that freeze protection equipment and anti-siphon equipment are not inspected. The inspection and report do not address, and are not intended to

address, code and regulation compliance (all code references are for educational purposes only), the possible presence of or danger from asbestos, radon gas, lead paint, urea formaldehyde, soil contamination, microwave radiation, electromagnetic fields, microbiological organisms and other indoor and outdoor substances, mold, underground storage tanks,

proximity to toxic wastes, zoning ordinances, flood plain location, geological stability of soils, wood destroying insects, dry rot, fungus, or household pests. Client is urged to contact

a competent specialist if information, identification, or testing of the above is desired. Many homes have excessive moisture issues that might lead to mold growth, but the ability to detect the presence of mold is beyond the scope of this inspection. If you are concerned about the presence of mold, you are strongly urged to consult with a qualified professional

microbiologist or mold inspector prior to purchasing the Property. Inspector is not required to inspect areas which may contain, in Inspector’s sole discretion, materials hazardous to

the health and/or safety of the Inspector’s personnel.

2. NO WARRANTIES OR GUARANTIES. This inspection is not intended to be technically exhaustive, nor is it considered to be a guarantee or warranty, expressed or

implied, regarding the conditions of the property, items and systems inspected, and it should not be relied on as such. The inspection may include the use of infrared camera/digital camcorders, which can capture infrared and digital images. The use of this additional advanced equipment is for the benefit of the Client; provided, however, that latent and

concealed defects and deficiencies are excluded from the inspection and Inspector in no way purports to perform any service beyond the standard “visual inspection” of the Property.

CLIENT IS HEREBY NOTIFIED THAT THE INSPECTOR HAS NOT MADE, DOES NOT MAKE, AND HEREBY DISCLAIMS

ANY WARRANTIES OR GUARANTEES, EXPRESSED OR IMPLIED, REGARDING THE ADEQUACY, PERFORMANCE, OR

CONDITION OF ANY STRUCTURE, ITEM, COMPONENT, OR SYSTEM INSPECTED, SPECIFICALLY INCLUDING (BUT NOT

LIMITED TO), ANY IMPLIED WARRANTIES OF FITNESS, MERCHANTABILITY, HABITABILITY AND GOOD AND

WORKMANLIKE CONDUCT. Client is advised that property owner warranties are available through third-party providers if warranties are desired. The price of the

inspection does not include any such warranties, and none are offered or available through the Inspector. The Inspector shall not be held responsible or liable for any repairs or replacements with regard to the Property or the systems, components, or contents therein. Since the inspection procedure is visual only and is not intended or designed to be

diagnostically and/or technically exhaustive, an inherent risk remains that undiscovered problems exist and/or future problems will develop. Client acknowledges that the Inspector is

not an insurer and it is not the intent and/or purpose of this inspection procedure to provide client with a risk free purchase or usage of the Property.

3. LIMITATION OF LIABILITY. Since the inspection is primarily a visual inspection, it is not possible to eliminate all risks involved in the purchase and/or ownership

of the Property. CLIENT AGREES, TO THE FULLEST EXTENT PROVIDED BY LAW, THAT CLIENT’S SOLE AND EXCLUSIVE

REMEDY FOR ANY AND ALL LOSSES OR DAMAGES SUSTAINED BY CLIENT RELATING TO THIS AGREEMENT OR THE

INSPECTION OR REPORT PROVIDED PURSUANT HERETO, INCLUDING ATTORNEYS’ FEES AND COSTS AND EXPERT

WITNESS FEES AND COSTS, IS LIMITED SO THAT THE TOTAL AGGREGATE LIABILITY OF THE INSPECTOR (OR

INSPECTOR’S EMPLOYEES OR ASSIGNEES) SHALL NOT EXCEED THE AMOUNT OF THE FEE PAID BY CLIENT TO

INSPECTOR FOR THE INSPECTION AND REPORT. This limitation shall apply regardless of the cause or the legal theory pled or asserted specifically

including, but not limited to, negligence and shall control the amount of any award against the Inspector. Unless Inspector is found to be grossly negligent, Inspector shall have no liability with respect to Inspector’s obligations under this Agreement or otherwise for consequential, exemplary, special, incidental, or punitive damages even if Inspector has been

advised of the possibility of such damages.

4. NOTIFICATION OF DISPUTES REQUIRED/ARBITRATION OF DISPUTES. Client shall notify Inspector in writing of any controversy or claim related to this

Agreement, the inspection or the inspection report within ninety (90) days after the date of this Agreement, and all disputes not submitted to Inspector within such time shall be

deemed waived by Client, and Client hereby releases, acquits, and forever discharges Inspector from such claims, and all related causes of action and damages, not submitted to Inspector within said ninety (90) day period. In order to provide Inspector with an opportunity to investigate and resolve any such claim, Client shall not commence any arbitration or

other legal proceeding relating to such claim for a period of thirty (30) days after Inspector’s receipt of written notice of the claim. If, with respect to a controversy or claim related to

this Agreement, the inspection or the inspection report, Client and Inspector are unable to reach a mutually satisfactory resolution within said thirty (30) day period, such dispute shall be settled by binding arbitration administered by the American Arbitration Association under its construction industry arbitration rules; provided, however, that if such claim is made

by Client, Client shall satisfy the requirements of Section 5 hereof prior to submitting such claim to arbitration. Only TREC licensed real estate inspectors will be eligible to serve as

the arbitrator. Judgment upon the award rendered by an arbitrator may be entered in any court having jurisdiction thereof. In any arbitration or other legal action in which the Inspector is the prevailing party or is not found liable, Inspector shall recover from Client any attorney’s fees and costs incurred by Inspector in defense of the proceeding.

Page 5: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 5 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

5. CERTIFICATE OF MERIT. Client shall make no claim, including without limitation any claim of professional negligence, against Inspector unless Client has first

provided Inspector with a written certification executed by an independent Texas Licensed Professional Real Estate Inspector currently practicing in the field of residential

inspections in the Greater Houston, Texas area for homebuyers. The certification shall: a) contain the name and license number of the certifier; b) specify the acts or omissions of the Inspector that the certifier contends are not in conformance with the standard of care for a Licensed Professional Real Estate Inspector performing a home inspection under similar

circumstances; and c) state in detail the basis for the certifier’s opinion that such acts or omissions do not conform to the standard of care. This certificate shall be provided to the

Inspector not less than twenty (20) days prior to the presentation of any claim, or the institution of any arbitration or legal proceeding by Client. This certificate of merit requirement will take precedence over any existing state law in force at the time of the claim or demand for arbitration.

6. INDEMNITY.

CLIENT AGREES TO INDEMNIFY, DEFEND, AND HOLD HARMLESS INSPECTOR, ITS PARTNERS, OFFICERS,

EMPLOYEES, ATTORNEYS, AND AGENTS, AND TO DEFEND ANY ACTION BROUGHT AGAINST ANY SUCH PARTIES,

WITH RESPECT TO ANY AND ALL CLAIMS, DEMANDS, CAUSES OF ACTION, DEBTS OR LIABILITIES, INCLUDING

REASONABLE ATTORNEYS' FEES, ARISING OUT OF OR RELATING TO THIS AGREEMENT, WHETHER OR NOT

RESULTING FROM THE NEGLIGENCE OF ANY PARTY SO INDEMNIFIED, UNLESS CAUSED BY THE GROSSLY NEGLIGENT

ACTIONS OR INTENTIONAL MISCONDUCT OF INSPECTOR.

7. MISCELLANEOUS.

Any particular concern of Client regarding the Property shall be brought to the attention of the Inspector before the inspection begins. All written comments by the

Inspector shall supersede oral comments. The inspection report is valid for the date and time of the inspection only. Re-inspections charges will apply for any additional trips to the Property. Client agrees that if he/she is not in receipt of the written inspection report on this Property within 48 hours of the date and time of the inspection, Client will contact the

Inspector in writing to inform him that the inspection report has not been received. The invalidity, illegality, or unenforceability of any provision contained in this Agreement shall not

affect any other provision hereof, and this Agreement shall be construed as is such invalid, illegal or unenforceable provision has never been contained herein. THIS AGREEMENT SHALL

BE GOVERNED BY AND CONSTRUED IN ACCORDANCE WITH THE LAWS OF THE STATE OF TEXAS. VENUE FOR ANY DISPUTE ARISING IN CONNECTION

HEREWITH IS EXPRESSLY DECLARED TO BE IN HARRIS COUNTY, TEXAS. This Agreement shall be binding upon and inure to the benefit of the parties hereto and their respective

heirs, executors, administrators, legal representatives, successors and assigns where permitted by this Agreement. This Agreement may not be assigned by Client without Inspector’s prior written consent. To the extent that the inspection report issued by the Inspector conflicts with the terms of this Agreement, the terms of this Agreement shall control. This Agreement

shall be included as an addendum to the inspection report issued by the Inspector related to the Property. Any notice which is required or desired under this Agreement shall be given

in writing and may be sent by personal delivery or by mail (either a. United States mail, postage prepaid, or b. Federal Express or similar generally recognized overnight carrier), addressed as follows (subject to the right to designate a different address by notice similarly given): if to Inspector, Image Inspections LLC., 16107 Kensington Dr. #132, Sugar

Land, Texas 77479; if to Client, to the address set forth hereinbelow.

The undersigned Client hereby executes this Property Inspection Agreement on this the day of , 2016.

CLIENT:

(Signature) I would like a copy of the inspection report

forwarded to my REALTOR. (Please check box, if applicable.)

(Printed Name) I would like a copy of the inspection report

forwarded to _______________________. (Please check box, if applicable.)

(Address)

Page 6: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 6 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

I. STRUCTURAL SYSTEMS

A. Foundations

Type of Foundation(s): Slab-on grade

Method of inspection: Visual inspection of exterior

Comments:

In my opinion, the foundation is performing as intended with evidence of moderate movement.

In my opinion, the amount of movement does not appear to affect the livability of the home at

this time. In my opinion, foundation repairs or leveling should be performed when the home

becomes uncomfortable or unsafe due to foundation movement. Because evidence of

foundation movement was observed further investigation of the foundation by a foundation

specialist may be desired to determine if any corrective action is needed and/or to obtain the

current elevation levels at this time to compare to at a later date. Foundation movement cannot

be determined during a one time inspection. See additional comments below.

Floor sloping, interior and exterior wall and ceiling cracking and patching and out of square

doors were observed within the home. These conditions indicate that movement within the

structure has occurred as is typical of most homes.

The height of the soil exceeds the acceptable limit around the exterior of the home. At least 4

inches of exposed foundation wall should be maintained.

Evidence of previous foundation repairs was observed. Further investigation is recommended.

The master bedroom and den appear to be additions to the original home.

The majority of the foundation was not visible due to high soil and rear deck.

Large vegetation in close proximity to the home can have an adverse effect on the performance

of the foundation if not properly maintained. Overgrown vegetation was observed along the

right side of the home.

Page 7: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 7 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

B. Grading & Drainage

Comments:

The grading and drainage should be improved around the exterior of the home to promote the

flow of storm water away from the house. The ground should slope away from the house at a

rate of one inch per foot for at least the first 6-10 feet. Ideally, at least 4-6 inches of clearance

should be maintained between soil level and the top of the foundation walls.

C. Roof Covering Materials

Type(s) of Roof Covering: Asphalt composition shingle and roll roofing

Viewed From: Walked on roof

Comments:

The roof covering appears to be older than disclosed. It was disclosed that the roof is

approximately4-6 years old. Advanced deterioration was observed on many shingles if the

stated age is correct. It is recommended that the roof be further evaluated by a reputable

roofing contractor to determine the full extent of repairs and costs associated. See additional

comments below.

Damaged shingles were observed in several locations. Loss of asphalt granules were observed

on many shingles on the roof. The fiberglass is exposed in several locations.

Heavy deterioration, cracking and is delaminating was observed at the low slope roof above

the den and skylights.

Page 8: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 8 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

The flashing at the rear edge of the low sloped roof above the den is damaged in several

locations and is higher than the sloped roof. The area between the roll roofing material and

flashing is separated. This is a likely cause for water damage (along with the gutters clogged

with debris) around the den patio doors. Repairs should be undertaken.

The lead plumbing vent jacks have been chewed by squirrels and are damaged and should be

repaired or replaced.

All exposed nail heads should be properly sealed.

The roof gutters and downspouts are damaged in several locations and are full of debris.

Page 9: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 9 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

The gutter downspout at the left rear corner of the master bedroom does not terminate into the

drain.

All debris should be removed from the roof covering.

A door sweep weather seal is attached to the siding at the right front corner of the home. This

weather seal appears to be utilized as a roof flashing. The flashing appears to be covering

water damage. Repairs should be undertaken.

A satellite dish is mounted to the roof covering. Higher than normal maintenance should be

expected in this location as the brackets is fastened directly through the roof covering.

Page 10: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 10 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

D. Roof Structures & Attics

Viewed From: Entered attic and performed a visual inspection

Approximate Average Depth of Insulation: 2-4 inches

Approximate Average Thickness of Vertical Insulation: 2-4 inches

Comments:

Soffit, gable and ridge attic ventilation was observed.

The attic access hatch is not insulated.

The attic access does not open straight and the ladder is leaning.

The attic access hatch hinge brackets are missing nails.

The attic roof structure was originally designed for a wood shingle roof. Currently the same

framing structure is now holding a decked asphalt shingle roof (which is heavier). Additional

reinforcement and additional bracing of the roof structure should have been added when the

roof type changed. This condition is very common on older homes that previously had wood

shingle roofs. Due to this condition it was found that several rafters within the attic have split

are broken and has begun to sag. It is recommended that additional bracing and reinforcement

be added to the roof structure. See addition comments below.

The rafters at the front of the home are split and the ridge board is broken. The roof is sagging

in this area.

The ridge at the rear of the home is sagging.

Page 11: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 11 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

Purlin bracing should be the same size as the rafters. Currently2x4 wooden members are being

utilized as the purlin bracing whereas the rafters are2x6 wooden members. Struts should be

attached to the purlin every 4 feet and braced to the top of the load bearing walls. The existing

purlin braces are not braced to the top of load bearing walls as the floor plan inside the home

has changed from the original.

Collar ties (horizontal members running between rafters, near their mid-span) should be

provided between every other rater. Collar ties help to resist rafter sag.

The attic insulation is missing or is extremely low in the majority of the attic space. All trash

and debris should be removed from the attic in the attic should be re-insulated.

The ridge board joints are not properly reinforced and supported.

Page 12: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 12 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

The rafters are separating from the ridge boards in several locations.

The vermin screens at the gable vents are damaged. Evidence of bird nesting and animal

activity was observed in the attic.

Today's standards require an unobstructed 24” wide attic service walkway and 30” wide

service area to all mechanical equipment in attic. Additional attic flooring should be installed.

Plywood has been laid across the attic framing but is not secured.

Water staining and damage was observed at the roof decking and attic framing in many

locations. Further investigations recommended.

Page 13: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 13 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

The master bedroom and den roof were not framed to allow overhang over the exterior walls.

Access to the attic space above the garage was not provided.

E. Walls (Interior & Exterior)

Comments:

The interior walls of the home appear to have been recently painted.

Cracking and patching was observed on the interior walls of the home in many areas.

Water damage was observed on the den rear wall above and to the sides of the back doors.

This area was wet at time of inspection. The dame appears to be caused by a damaged roof and

clogged roof gutters.

Page 14: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 14 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

Water staining or damage was observed on the master bathroom closet wall directly behind the

master bathroom tub. Organic growth was observed when the 1st access panel cover was

removed.

The rear guest bathroom wall is bulging between the shower stall and toilet.

Cracking, patching and mortar repairs were observed in many areas around the exterior brick

walls of the home.

Water damage was observed on the exterior trim, soffits and fascia in several locations around

the exterior of the home.

Page 15: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 15 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

The lintels (metal headers above the windows and doors) are rusting and should be cleaned and

painted to prevent further deterioration. The further deterioration occurs replacing the lintels

may be required to adequately support the bricks above.

Exposed framing was observed at the bottom of the master bedroom patio door.

Loose bricks were observed at the upper corners of the windows along the right side of the

home.

A damaged brick was observed at ground level on the right side of the home. Repairs should

be undertaken.

The edges of the soffits around the garage are not sealed.

Page 16: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 16 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

F. Ceilings & Floors

Comments:

Cracking and patching was observed on the ceilings in many locations.

The ceilings throughout the home appear to have been recently painted.

Water staining and damage was observed at the ceilings within the front guest bedroom closet,

front guest bathroom closet, front guest bathroom, master bedroom, rear guest bedroom. The

cause for staining and or damage should be determined and repairs should be undertaken as

necessary.

Floor sloping was observed in several locations along the right side of the home. This

condition indicates that foundation movement has likely occurred.

Staining and discoloration was observed on the floors in several locations.

Page 17: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 17 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

Separations between the wood planks were observed in several locations throughout the home.

G. Doors (Interior & Exterior)

Comments:

The laundry room patio door shows evidence of water damage at the bottom of the door and

does not seal properly at the threshold. The threshold is unlevel.

Exterior doors should not be keyed from the inside. This condition creates a fire egress

concern.

Water damage was observed at the back doors. The doors drag hard on each other and are out

of square. The door trim casing is separating from around the doors. When the doors are open

water spills out from the bottom of the doors.

Page 18: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 18 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

Missing screws were observed at the majority of the hinges of the exterior doors. Screws

should be installed where missing.

The rear guest bedroom door is out of square.

The threshold at the master bedroom patio door is loose and is not properly supported.

The door frame, casing and doorstop trim at the master bedroom door is separating.

Page 19: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 19 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

The framed opening of the rear guest bedroom/master bedroom hallway is not square.

The overhead garage door does not close and lock all the way.

Excessive gaps were observed at the bottom and sides of the overhead garage door when

closed.

H. Windows

Comments:

Single pane, single hung and fixed windows

The kitchen window has been replaced with a double pane window.

Window screens are not present at all windows.

The heights of the windows in the guest bedrooms are higher than 44 inches from the floor and

the windows do not have an adequate operable area to allow for easy escape in case of fire.

This condition creates a fire egress concern.

Page 20: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 20 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

The semicircle window within the master bedroom is in need of caulking at the interior and

exterior.

The master bedroom, den and dining room windows did not operate at time of inspection.

The window springs are loose at the middle guest bedroom and dining room windows.

Condensation was observed between the window panes of the den skylights. Repairs are

recommended.

Water staining was observed around the edges of the den skylight. Further investigations

recommended and repairs should be undertaken as necessary.

I. Stairways (Interior & Exterior)

Comments:

Page 21: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 21 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

J. Fireplaces and Chimneys

Comments:

K. Porches, Balconies, Decks, and Carports

Comments:

Cracking and displacement was observed in the driveway and rear patio.

The rear deck is installed below grade and appears to have a sump pump installed below the

deck. Repairs are recommended.

II. ELECTRICAL SYSTEMS

A. Service Entrance and Panels Comments:

General Electric Brand, 200amp electrical service panel located on the right side of the home.

The water pipes and gas pipes do not appear to be bonded to the electrical ground.

The tree limbs should be cut away from the power lines routed to the service mast.

Page 22: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 22 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

The breaker serving the 1½ air conditioner is oversized (30amp). The manufacturer indicates

that the breaker should not be larger than 20amps. This breaker should be replaced with a

20amp breaker.

The breaker knockout at the bottom of the dead front cover plate is missing and should be

properly covered to prevent electrocution.

All breakers within the electrical panel are not labeled.

Antioxidant mastic should be applied to the main service feed wire connections within the

electrical panel.

Page 23: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 23 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

Today's electrical standards now require that all breakers serving the general circuits within all

habitable areas of the home be protected with arc fault (AFCI) breakers. Updating should be

considered.

Today's electrical standards now require that the electrical system be connected to multiple

grounds to form what is known as a "grounding electrode system." Updating should be

considered. The current electrical system is connected to only a single ground.

The ground and neutral wires within the electrical panel are interconnected and should be

separated on separate bus bars.

The neutral wires within the electrical panel are doubled up on the terminals. Each neutral wire

should be connected to a single terminal.

A double tapped 15amp breaker (2 circuits connected to a single breaker) was observed within

the electrical panel. Each circuit should be served by a single breaker.

Page 24: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 24 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

B. Branch Circuits, Connected Devices, and Fixtures

Type of Wiring: Copper

Comments:

The majority of the electrical outlets throughout the home are not grounded.

Today's standards now require that all electrical outlets within the kitchen, bathrooms, garage

and exterior (wet areas) be GFCI protected. Updating is recommended.

The electrical outlets at the desk area within the front guest bedroom are wired backwards

"reversed polarity."

Smoke detectors should be installed in all bedrooms. Currently smoke detectors are only

located in the hallways outside of the bedrooms. Smoke detectors should be replaced after 10

years from the date of manufacture and should be installed in all bedrooms and directly outside

of bedrooms.

Exposed light bulbs were observed in the master bathroom closets. Today's standards now

require that light fixtures in closets be protected with a fixture cover or globe. Updating to

newer fixtures is recommended.

Page 25: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 25 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

The light fixtures within the kitchen did not operate at time of inspection. If the bulbs are not

blown the circuits should be investigated.

The kitchen light fixture is not flush at the ceiling.

The attic light switch cover plate is damaged.

Open electrical junction boxes were observed in the attic. The junction boxes should be fitted

with cover plates.

An old electrical panel is present in the attic near the furnace above the master bedroom. Inside

the electrical panel are many wire connections and splices. It is recommended that this be

further evaluated by a licensed electrician.

Open electrical wiring was observed at the front exterior wall of the home. Further

investigation is recommended by a licensed electrician.

Page 26: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 26 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

The exterior light fixtures are loose and are not sealed at the walls.

The exterior outlet cover plates are damaged in several locations.

The laundry room exterior door light fixture did not operate at time of inspection. The circuit

should be investigated.

A light fixture is not present at the den patio doors as required.

The electrical conduit is disconnected at the left side exterior wall of the master bedroom.

The electrical conduit is incomplete at the left side of the home under the soffit. The electrical

wiring is exposed to the exterior.

The light fixture at the front of the garage did not operate at time of inspection. If the bulbs are

not blown the circuit should be investigated.

Page 27: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 27 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

III. HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS

A. Heating Equipment

Type of Systems: Central Forced Air Furnace

Energy Sources: Gas

Comments:

The HVAC systems do not appear to have been installed by a professional. See additional

comments below and in the cooling and duct systems sections of this report. It is unlikely that

permits were obtained. It is recommended that both of the HVAC complete systems (furnaces

air-conditioners and duct work) be further evaluated by a reputable licensed HVAC technician

to determine the full extent of repairs or corrections needed and the costs associated with all

repairs or corrections.

Two unit system

Two 2014 Grand Aire Brand (ICP) gas furnaces were observed in the attic.

The furnace vents are improperly connected. The furnace vents should be constructed out of

Type- B double wall vent pipe sections and should be connected with slip joints and not

connected with duct tape and screws. Each section of the furnace vents is connected with

screws and duct tape. A minimum 1 inch clearance should be maintained between the furnace

vent and any combustible materials. The furnace vent is in contact with wood framing and

connected with duct tape.

The furnace vent above the master bedroom area is improperly sloped. The vent pipe slopes

downwards before it turns back up and penetrates the roof. Repairs should be undertaken.

The flexible gas lines are routed inside the furnace cabinets. Hard pipe (black iron) should be

connected within the furnace and routed to the exterior where the flexible gas line should be

connected.

Page 28: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 28 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

Sediment traps are not installed at the gas lines between the gas valve and furnace.

The furnaces did not operate at time of inspection. Malfunction indicator lights within the

furnaces indicate that a lockout was signaled the unit could not be restarted for 3 hours. Further

investigations recommended and repairs should be undertaken as necessary.

The old electrical wiring entering the furnace cabinet is not protected by a grommet.

The furnace vents should be securely strapped at the rafters.

All wire connections within the furnace should be in an enclosed junction box.

B. Cooling Equipment

Type of System: Central Forced Air System

Comments:

Two unit system

2014 Grand Aire Brand (ICP), model # WCA3184GK100, 1½ TON condenser was observed

at the right side of the home.

2014 Grand Aire Brand (ICP), model # WCA3424GKA2, 3½ TON condenser was observed at

the right side of the home.

The unit serving the guest bedrooms and front of the home operated to control and produced a

supply of 42 degrees and a return of 62 degrees. This is within test limits of 15 to 21 degrees.

The unit serving the rear of the home (master suite) did not produce cool air at time of

inspection. Further investigations recommended by a licensed HVAC technician.

The refrigerant line insulation is damaged at the exterior and within the attic (chewed by

vermin). Repairs should be undertaken

The primary condensation drain line in the attic is not insulated.

Page 29: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 29 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

The condensing units of the air conditioning systems should be installed 3 inches above the

ground (to prevent moisture and debris from collecting around the units) and should be

installed at level as possible. The units are not level and are surrounded by leaves and debris.

The electrical conduit at the air-conditioning units did not properly enter the brick wall.

The electrical conduit is not properly connected at the electrical service disconnect box located

on the right side of the home.

The smaller air conditioner serving the master bedroom area ran constantly during the

inspection and would not cut off when the thermostats were turned to the off or heat position.

Further investigation is recommended and repairs should be undertaken as necessary. The

breaker serving the air conditioner was turned off at the completion of the inspection.

Page 30: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 30 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

The primary condensation drain line connected to the front air-conditioning system is

terminating on the right side exterior of the home. The auxiliary drain line terminates next to

the primary drain line. The auxiliary drain line should terminate above a window or door or

where visible from inside the home.

The location of the rear air-conditioning system primary condensation drain line termination

could not be determined. Many air conditioner drains were observed penetrating the soffit

along the right side of the home.

C. Duct Systems, Chases, and Vents

Comments:

The return air chase is unfinished on the interior at the front guest bedroom hallway return air.

This air return is undersized.

Page 31: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 31 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

There was no air flow observed at the living room supply air vent. Further investigation is

recommended.

The return air vent within the master bedroom ceiling is poorly constructed. Replacement is

recommended. The vent does not completely cover the opening within the ceiling. The return

air duct in the attic is crushed.

Several different kinds of duct work were observed in the attic. (Some old, some new and

some damaged).

The ducts are damaged in several locations in the attic.

Balancing of the ductwork is needed to evenly distribute the conditioned air throughout the

home. The supply air temperatures were measured at all vents throughout the home and were

inconsistent.

Page 32: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 32 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

IV. PLUMBING SYSTEM

A. Plumbing Supply, Distribution Systems and Fixtures

Location of water meter: Street

Location of main water supply valve: Left side of home

Static water pressure reading: 55 PSI

Comments:

Galvanized water supply piping was observed. Galvanized piping is known for deteriorating

on the inside. The condition of the piping could not be determined. Pex and CPVC water

supply piping was also observed.

The cold water pressure is extremely low at the kitchen faucet.

The water supply pipes in the attic are not insulated.

The faucet is loose at the front guest bathroom sink.

Page 33: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 33 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

The water supply piping within the rear guest bathroom shower stall wall is loose. The faucet

and showerhead assembly moves easily.

The rear guest bathroom shower handle is damaged in turns past the designated stop.

Flexible drains were observed underneath the guest bathroom sinks. This is not a professional

installation.

Escutcheon plates should be installed where all water supply lines and drain pipes penetrates

the cabinet walls underneath the sinks.

Page 34: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 34 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

Caulking and grouting improvements are needed within the master bathroom tub tile surround.

The water diverter at the master bathroom tub faucet does not completely redirect all water to

the showerhead as designed.

The drain stopper does not seal and hold water at the master bathroom tub.

Access to the guest bathroom tub drain was not provided. The access panel was sealed and

painted shut.

Backflow preventers should be installed at all hose bibs.

Page 35: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 35 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

B. Drains, Wastes, and Vents

Comments:

The drain connections under the kitchen sink are improperly installed. The P-trap should be

installed after the connection between the left side basin drain and garbage disposal. This

condition may allow sewer gasses to vent into the kitchen from the garbage disposal. Repairs

should be undertaken.

C. Water Heating Equipment

Energy Sources: Gas

Capacity: 40 Gallons

Comments:

2008 General Electric Brand 40 gallon water heater was observed in the laundry room water

heater closet.

The water heater is not drawing combustion air from the exterior. Gas appliances should not

draw combustion air from living spaces.

Water heaters have a typical life expectancy of 7 to 12 years. The existing unit is within this

age range. One cannot predict with certainty when replacement will become necessary.

Corrosion and rusting was observed at the water supply line connections and top of the water

heater.

The temperature and pressure relief valve discharge line terminates at the floor in front of the

water heater. The temperature and pressure relief discharge should terminate outside pointing

downwards within 6-12 inches from the ground.

Page 36: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 36 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

A sediment trap is not present on the gas line serving the water heater between the gas valve

and water heater control valve.

Water staining was observed on the ceiling above the water heater.

D. Hydro-Massage Therapy Equipment Comments:

E. Other

Comments:

The gas valve in the laundry room should be capped off if not used.

V. APPLIANCES

A Dishwashers

Comments:

Maytag Brand

The dishwasher drain is not connected to an airgap device or is not configured as a "high drain

loop."

The dishwasher operated properly at time of inspection.

Page 37: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 37 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

B. Food Waste Disposers

Comments:

ISE Brand

The garbage disposal is leaking at the drain flange connection.

C. Range Hood and Exhaust Systems

Comments:

Maytag Brand ductless recirculating unit

The range vent operated properly at time of inspection.

D. Ranges, Cooktops, and Ovens

Comments:

Maytag Brand electric range

The upper oven temperature was measured at 340 degrees when set at 350 degrees which is

within acceptable limits.

The lower oven temperature was measured at 335 degrees when set at 350 degrees which is

within acceptable limits.

The range does not have an anti-tip bracket installed to prevent the unit from tipping forward.

Page 38: Building Inspection Report...formica, marble, tile floors, wall coverings, air conditioning systems when outside temperature is below sixty (60) degrees, refrigerant and condensate

Report Identification: 12345 Example St, Houston, TX 77035 I=Inspected NI=Not Inspected NP=Not Present D=Deficiency

I NI NP D

This confidential report is prepared exclusively for Sample Report Page 38 of 38

© 2016 Image Inspections LLC REI 7-5 (5/4/2015)

E. Microwave Ovens

Comments:

Maytag Brand

The microwave is loose where mounted in the provided cabinet space.

The microwave operated properly at time of inspection.

F. Mechanical Exhaust Vents and Bathroom Heaters

Comments:

The bathroom exhaust fans are not vented to the exterior of the home.

G. Garage Door Operators

Comments:

H. Dryer Exhaust Systems

Comments:

The dryer vent appeared to properly vent to the exterior of the home.