Building By-law Compliance Summary VCLTF Site 6 2922 East Kent Avenue South & 8588 Jellicoe St., Vancouver, BC (2900 E Kent Ave. South - Site) ISSUED FOR FULL BUILDING PERMIT GBA File #141793 November 24, 2014 Revised June 19, 2015 Prepared for: DYS Architecture 260 - 1770 Burrard Street Vancouver, BC V6J 3G7 Prepared by: Reviewed by: Lawrence Dobbs Bruce Campbell Consultant Senior Consultant Gordon Richards, Architect AIBC, FRAIC, CP Principal

Transcript of Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law...

Page 1: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building By-law Compliance Summary

VCLTF Site 62922 East Kent Avenue South &

8588 Jellicoe St., Vancouver, BC

(2900 E Kent Ave. South - Site)

ISSUED FOR FULL BUILDING PERMIT

GBA File #141793

November 24, 2014

Revised June 19, 2015

Prepared for:

DYS Architecture

260 - 1770 Burrard Street

Vancouver, BC V6J 3G7

Prepared by: Reviewed by:

Lawrence Dobbs Bruce Campbell

Consultant Senior Consultant

Gordon Richards,

Architect AIBC, FRAIC, CP

Principal

Page 2: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page i

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

TABLE OF CONTENTS

1.0 GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

1.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

1.2 Scope of Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2.0 CODE COMPLIANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2.1 Building Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2.2 Construction.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2.3 Fire Separations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2.4 Occupant Load. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.5 Spatial Separation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.6 Exit Exposures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2.7 Fire Alarm System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

2.8 Provisions for Firefighting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

2.9 Lighting and Emergency Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.10 Interconnected Floor Space. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.11 Safety Within Floor Areas. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.12 Storage Garage Security.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2.13 Exits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

2.14 Service Facilities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

2.15 Vertical Transportation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

2.16 Health Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

2.17 Barrier-Free Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Page 3: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 1

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

1.0 GENERAL

1.1 Description

The City of Vancouver is presently undertaking an initiative to provide affordable

housing for Vancouver residents, in partnership with the Community Housing Land

Trust Foundation (CHLTF). Four sites throughout Vancouver (Sites 3, 4, 5 and 6)

have been selected for the development of these projects.

The Site 6 development consists of two buildings; a 36 unit townhouse building

located at located at 2922 East Kent Avenue South, and a 54 unit apartment building

located at 8588 Jellicoe Street. Both buildings are served by a single level common

parkade.

1.2 Scope of Report

Gage-Babcock & Associates Ltd. (GBA) has been retained to review the building

permit drawings of the building for general compliance with the fire and life safety

provisions of the 2007 Vancouver Building By-law (VBBL). All references are to the

VBBL unless stated otherwise.

2.0 CODE COMPLIANCE

2.1 Building Data

Building 1 (2922 East Kent Avenue South)

Building Area: 1,419 m (15,275 ft )2 2

Building Height: 3 Storeys

Construction Type: Combustible

Major Occupancy: Group C (Residential)

Building 2 (8588 Jellicoe Street)

Building Area: 2,264 m (24,370 ft )2 2

Building Height: 3 Storeys

Construction Type: Combustible

Major Occupancy: Group C (Residential)

Page 4: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 2

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

Common Parkade

Building Area: 5,190 m (55,865 ft )2 2

Building Height: 1 Storey

Construction Type: Noncombustible

Major Occupancy: Group F-3 (Storage Garage)

2.2 Construction

The proposed buildings shall meet the requirements of the following articles

governing construction as summarized below:

Building 1 (2922 East Kent Avenue South)

3.2.2.48. Group C, up to 3 Storeys, Sprinklered

Maximum Area: 1,800 m2

Construction Type: Combustible and noncombustible permitted

Floor Assemblies: 45 min fire separations

Floor assemblies which are entirely contained within dwelling

units are required to be constructed with a fire-resistance

rating of 45 min, but need not be constructed as fire

separations [3.2.2.48.(3)]

Mezzanines: 45 min fire-resistance rating (none proposed)

Loadbearing: Rating equal to that of supporting assembly

Roof Assemblies: No fire-resistance rating required (sprinklered building)

Roof: Class A, B, or C roof covering classification

Skylights shall be glazed with wired glass, laminated safety

glass or combustible glazing as per Article 3.1.14.3.

High Building: No

Sprinklers: Required - system is to comply with NFPA 13R-2002

Standpipe: Not required

Fire Alarm System: Required - system is to comply with CAN/ULC-S524-01

Page 5: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 3

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

Building 2 (8588 Jellicoe Street)

3.2.2.45 Group C, up to 6 Storeys, Sprinklered

Maximum Area: 2,400 m2

Construction Type: Combustible and noncombustible permitted

Floor Assemblies: 1 h fire separation

Mezzanines: 1 h fire-resistance rating (none proposed)

Loadbearing: Rating equal to that of supporting assembly

Roof Assemblies: No fire-resistance rating required (sprinklered building)

Roof: Class A, B, or C roof covering classification

High Building: No

Sprinklers: Required - system is to comply with NFPA 13R-2002

Standpipe: Not required

Fire Alarm System: Required - system is to comply with CAN/ULC-S524-01

Common Parkade

3.2.1.2 Storage Garage Considered a Separate Building

Maximum Area: N/A

Construction Type: Noncombustible construction required

Floor / Slab over: 2 h fire separation

Loadbearing: 2 h fire-resistance rating

Sprinklers: Required - system is to comply with NFPA 13-1999

Standpipe: Not required

Fire Alarm System: Required - system is to comply with CAN/ULC-S524-01

2.3 Fire Separations

Construction: Fire separations must be constructed as continuous elements,

extending from the floor through the ceiling elements, and

horizontal service spaces to the underside of the floor or roof

deck above.

Ratings: Fire-rated assemblies are to be listed by ULC, cUL, Intertek

(WH), Appendix D of the VBBL, or other acceptable agency.

Page 6: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 4

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

Openings: Openings in a fire separation must be protected by closures,

shafts, or other means in conformance with Articles 3.1.8.4.

to 3.1.8.17. and Subsections 3.1.9.

Closures: Closures in fire separations are required to have appropriate

listed self-closing devices and latching hardware. The fire-

protection rating of a closure shall conform to Table 3.1.8.4.

of the VBBL.

TABLE 2.3A: FIRE-PROTECTION RATING of CLOSURES

Fire-Resistance Rating of Fire Separation Minimum Fire-Protection Rating of Closure

45 min 45 min

1 h 45 min

1.5 h 1 h

2 h 1.5 h

20-Minute Closures: Doors between a public corridor and suites of Group C

occupancy are permitted to have a fire-protection rating not

less than 20 min.

Temperature Rise The maximum temperature rise on the opaque portion of the

Limit: unexposed side of a door used as a closure in a fire separation

in a location shown in Table 3.1.8.15 of the VBBL, shall

conform to the Table. The relevant excerpt of Table 3.1.8.15

is as follows:

TABLE 2.3B: RESTRICTIONS on TEMPERATURE RISE/GLAZING for CLOSURES

Locations

Minimum

Required

Fire-

Protection

Rating of

Door

Maximum

Temperature

Rise on Opaque

Portion of

Unexposed Side

of Door, °C

Maximum Area

of Wired Glass in

Door, m2

Maximum

Aggregate Area

of Glass Block

and Wired Glass

Panels not in a

Door, m2

Between an exit

enclosure and the

adjacent floor area

All ratings No limit 0.8 0.8

Penetrations: Building services, such as piping, tubing, ducts, electrical

wires, and cables that penetrate a required fire separation,

must be cast in place, or the opening at the penetration must

be sealed by a listed firestopping material in conformance

with Subsection 3.1.9.

Page 7: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 5

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

Any vertical penetrations through the parkade to the buildings

above must be sealed with listed firestopping material having

an FT rating not less than 2 h.

Fire Dampers: Except as permitted by Article 3.1.8.8., a duct that penetrates

an assembly required to be a rated fire separation shall be

equipped with a fire damper. A fire damper shall have a fire-

protection rating conforming to Sentence 3.1.8.4.(2).

Fire dampers are not required for duct penetrations through a

fire separation that does not have a fire-resistance rating (0 h

fire separation).

Fire Stops in Fire stops in concealed spaces shall be provided in

Concealed Spaces: conformance with Subsection 3.1.11

The tables following provide a summary of the required fire separations and their

minimum fire-resistance rating.

TABLE 2.3C: REQUIRED FIRE SEPARATIONS (BUILDING 1)

Room / Area Fire-resistance Rating

Floor Assemblies 45 min

Dwelling Units 45 min

Vertical Service Space 45 min

TABLE 2.3D: REQUIRED FIRE SEPARATIONS (BUILDING 2)

Room / Area Fire-resistance Rating

Floor Assemblies 1 h

Dwelling Units 1 h

Exit Stair 1 h

Elevator Shaft 1 h

Main Electrical Room (sprinklered) 1 h

Main Electrical Room (not sprinklered) 2 h

Other Electrical Room No requirement

Vertical Service Space 45 min

TABLE 2.3E: REQUIRED FIRE SEPARATIONS (COMMON PARKADE)

Room / Area Fire-resistance Rating

Floor Above 2 h

Exit Stair 2 h

Elevator Shaft 2 h

Elevator Machine Room 2 h

Page 8: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 6

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

TABLE 2.3E: REQUIRED FIRE SEPARATIONS (COMMON PARKADE)

Room / Area Fire-resistance Rating

Storage Garage 1.5 h

Garbage/Recycling 1 h

Mechanical Room w/ Fuel-fired Equip 1 h

Mechanical Room w/o Fuel-fired Equip No requirement

Bike Storage No requirement

Vertical Service Space 1 h

2.4 Occupant Load

The design occupant loads are calculated based on the information provided in the

drawings and in conformance with Article 3.1.17.1. The occupant loads for each

building are as follows:

TABLE 2.4A: OCCUPANT LOAD AS PER TABLE 3.1.17.1. (COMMON PARKADE)

Level Use AreaOccupant Load

Factor (m²)

Occupant

Load (persons)

P1Parking 4,345 m 46 942

Storage/Services 384 m 46 82

TOTAL BUILDING OCCUPANT LOAD: 102

TABLE 2.4B: OCCUPANT LOAD AS PER TABLE 3.1.17.1. (BUILDING 1)

Level Use AreaOccupant Load

Factor (m²)

Occupant

Load (persons)

1-3 Residential 104 Bedrooms 2 per Bedroom 208

TOTAL BUILDING OCCUPANT LOAD: 208

TABLE 2.4C: OCCUPANT LOAD AS PER TABLE 3.1.17.1. (BUILDING 2)

Level Use Area Occupant Load

Factor (m²)

Occupant

Load (persons)

1 Residential 43 Bedrooms 2 per Bedroom 86

2 Residential 44 Bedrooms 2 per Bedroom 88

3 Residential 44 Bedrooms 2 per Bedroom 88

TOTAL BUILDING OCCUPANT LOAD: 262

2.5 Spatial Separation

Based on the worst case scenario at each building face, the spatial separation

requirements of the VBBL are listed below. As provided by Table 3.2.3.1.D., a wall

Page 9: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 7

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

having a limiting distance of 9 m or more is permitted to have 100% unprotected

openings, with no minimum construction requirements.

TABLE 2.5A: SPATIAL SEPARATION - BUILDING 1

Exposing

Building

Face

Facing Level

Limiting

Distance

(m)

Wall

Area

(m )2

Unprotected Openings Construction of

Exposing

Building FaceAllowed Proposed

North Kent Ave. South All > 9 m - 100% - No restrictions

South Building 2 All > 6 m41 m2

per unit100% - No restrictions

East Property Line All 8.4 m67 m2

per unit100% - No restrictions

West Jellicoe Street All > 9 m - 100% - No restrictions

TABLE 2.5B: SPATIAL SEPARATION - BUILDING 2

Exposing

Building

Face

Facing Level

Limiting

Distance

(m)

Wall

Area

(m )2

Unprotected

OpeningsConstruction of

Exposing Building

FaceAllowed Proposed

North Building 1 All > 6 m26 m2

per unit100% - No restrictions

SouthProperty

Line

Units 108,

208, 3082.5 m

36 m2

per unit

32% per

unit

31% per

unit

45 min FRR

Noncombustible

Cladding

Units 109,

209, 3092.5 m

20 m2

per unit

44% per

unit

34% per

unit

45 min FRR

Noncombustible

Cladding

All other

units> 9 m - 100% - No restrictions

EastProperty

Line

Units 107,

207, 307 3.15 m

22 m2

per unit

63% per

unit

35% per

unit45 min FRR

Units 108,

208, 3082.5 m

22 m2

per unit

41% per

unit

34% per

unit

45 min. FRR

Noncombustible

Cladding

Units 109,

209, 3092.5 m

45 m2

per unit

29% per

unit

27% per

unit

45 min FRR

Noncombustible

Cladding

WestProperty

LineAll > 9 m - 100% - No restrictions

2.6 Exit Exposures

In a case of fire exposure to an exit serving greater than 10 persons, as described in

Article 3.2.3.13., unprotected openings must be protected by:

• Glass block conforming to the requirements of Article 3.1.8.14.;

• A wired glass assembly conforming to D-2.3.14. in Appendix D; or

Page 10: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 8

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

• A closure conforming to the requirements of Subsection 3.1.8., and Articles

3.2.3.1. and 3.2.3.14.

A number of windows along Gridline E expose paths of travel from suites within the

South building. However, an exit exposure condition for an exit serving less than 10

people may be addressed by a generic alternative solution per City of Vancouver

Bulletin 2014-02-BU. This bulletin permits the 2014 VBBL provisions for water

curtain protection to be applied to buildings designed under the 2007 VBBL.

Water curtains shall be provided which meet the following requirements of Sentence

3.2.3.13.(5) of the 2014 VBBL:

• have quick response pendant type sprinklers,

• if the opening is 1.8 m or less in width, have one sprinkler head installed at

the center of the opening at a maximum distance of not more than 0.9 m from

the vertical edge of the opening,

• if the opening is more than 1.8 m in width, have multiple sprinkler heads

installed at a maximum distance of 1.8 m on center and at a maximum

distance of not more than 0.9 m from the sprinklers to the vertical edge of the

opening,

• have sprinklers located 50 mm vertically and between 150 mm and 300 mm

horizontally from the interior face of the glazing at ceiling level,

• discharge water at a minimum flow rate of 68L/min (18 USgpm),

• have sprinkler heads with an orifice size of 12.7 mm and a k factor of

nominal 5.7,

• be designed independently from the floor area coverage and be included in

the most hydraulically demanding area for the design of the adjacent floor

area sprinklers,

• have sprinkler heads protected from spray and from cold solder effects from

adjacent sprinklers (floor area or water curtain sprinkler heads) by means of

baffles in accordance with NFPA 13, and

• be provided with tempered or laminated safety glass glazed openings where

windows are permitted to be openable

See Appendix A for water curtain locations

Page 11: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 9

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

2.7 Fire Alarm System

Fire Alarm: Building 2 and the common parkade will be protected

throughout by a single stage fire alarm system per Articles

3.2.4.3. and 3.2.4.4.

Although it is not required by Sentence 3.2.1.4.(3), Building

1 will also be provided with a single stage fire alarm system

to satisfy the requirements of Clause 3.2.5.5.(3)(b) of By-law

No. 9984 which permits extended travel distance to dwelling

unit entrances (See Section 2.8 of report).

Monitoring: The fire alarm system shall be remotely monitored by a ULC

listed monitoring station in conformance with Article 3.2.4.8.

Annunciator: An annunciator shall be installed at the designated principal

entrance for each building.

Fire Alarm Zoning: The fire alarm system shall be zoned by floors. The fire alarm

zoning and sprinkler system zoning shall be consistent with

the fire alarm system operation sequence. The annunciator

shall have separate zone indication for the actuation of smoke

detectors, heat detectors, manual stations and waterflow

detecting devices.

Alarm Signal: Temporal pattern will conform to Clause 4.2 of International

Standard ISO 8201.

The sound pressure level in a sleeping room from a fire alarm

audible signal device must not be less than 75 dB.

Audible signals will provide sound pressure levels at least 10

dB above ambient noise (minimum 65 dB) in all areas within

the building.

A manual silencing switch accessible only to authorized

personnel shall be installed inside the annunciator panel.

Initiating Devices: The following areas are required to be protected by alarm

initiating devices or fire detectors:

Page 12: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 10

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

Manual Pull Stations: Shall be provided near every exit and every principal

entrance. (Not required in townhouse units)

Smoke Detectors: Shall be provided in the following locations:

• At the top of exit stair enclosures.

• Within public corridors serving Group C occupancy.

• Duct-type smoke detectors are required to be provided

in an air handling system which serves more than one

storey or more than one fire compartment.

Electrical Supervisory signals shall be indicated at the annunciator

Supervision: panel for each of the following fire protection system

components:

• Sprinkler control valves including backflow

prevention devices located in the valve pit.

• Flow alarm switches.

• Low air pressure switches.

2.8 Provisions for Firefighting

Principal Entrance: The principal entrance to Building 1 shall be located at the

breezeway adjacent to East Kent Avenue South. The principal

entrance to Building 2 shall be located at the lobby adjacent

to Jellicoe Street. The distance from the principal entrances to

a hydrant shall not exceed 90 m and shall be unobstructed.

Access Route: Access for fire department vehicles shall be not more than

15 m from a principal entrance. Both principal entrances will

be designated fire department response points.

Paths of Travel: As per Clause 3.2.5.5.(3).(b) of By-law No. 9984, the

maximum path of travel from the fire department access route

to the entrance door of a dwelling unit is permitted to be

greater than 45 m but not greater than 55 m, provided the

following conditions are met:

• Not more than one dwelling unit is located above

another dwelling unit.

Page 13: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 11

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

• The path of travel to the dwelling unit entrance is

provided with an unobstructed width of 2 m.

• A strobe light connected to an internal smoke alarm is

installed outside the principal entrance to each

dwelling unit.

• The sprinkler system is monitored by the fire alarm

system.

• The sound pressure level in a sleeping room from a

fire alarm audible signal device must not be less than

75 dB.

• Emergency lighting is provided along the path of

travel.

• The fire alarm system is provided with a graphic

annunciator panel.

Fire Department The fire department connections for the automatic sprinkler

Connections: system shall be located not less than 5 m horizontally of the

principal entrances to each building and be unobstructed.

Standpipe: Given that both Buildings 1 and 2 are 3 storeys in height and

are sprinklered throughout, neither building is required to be

provided with a standpipe. The basement parkade is not

required to be provided with a standpipe.

Sprinklers: Sprinklers shall be installed throughout the building in

conformance with NFPA 13R-2002, "Installation of Sprinkler

Systems In Residential Occupancies up to and Including 4

Storeys in Height".

Sprinklers must not be omitted in any room or closet in the

storey immediately below a roof assembly.

As both buildings are of combustible construction, sprinklers

must be provided for all unenclosed exterior balconies.

Extinguishers: Portable extinguishers will be provided as per the BC Fire

Code and NFPA 10 requirements.

Page 14: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 12

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

2.9 Lighting and Emergency Power

Lighting: An average illumination level of at least 50 Lx shall be

provided at the floor level in every exit and corridor providing

access to exit.

Emergency Lighting: Emergency lighting with minimum 30 min duration shall be

provided to an average level of at least 10 Lx at the floor and

tread levels in exits, principal exit routes in open floor areas

and exit access corridors.

Emergency Power: A minimum 30 min emergency power supply shall be

provided for elevators, emergency lighting, and the fire alarm

system in conformance with Subsection 3.2.7.

2.10 Interconnected Floor Space

There are no interconnected floor spaces in any of the buildings proposed.

2.11 Safety Within Floor Areas

Corridors: Corridors will be at least 1,100 mm wide, and will not have

dead-end portions greater than 6 m long unless the area served

by the dead-end portion has a second and separate means of

egress.

Egress Doors: In a sprinklered building, two egress doors are required from

a room or area with either an occupant load exceeding 60

people, travel distance exceeding 25 m, or an area exceeding

the limits of Table 3.3.1.5.B.

Doors providing access to exit shall swing on a vertical axis

and will have a minimum clear width of 800 mm. Door

release hardware will be operable with one hand and require

only one releasing operation.

Doors within an accessible path of travel and equipped with

self-closing devices must be provided with clear and level

areas including 300 mm/600 mm latch clearances conforming

to Article 3.3.1.13.

Guards: Guards at least 1,070 mm high are to be provided at occupied

roofs and floor openings with an elevation change of more

Page 15: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 13

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

than 600 mm. Guards are to be designed in accordance with

Article 3.4.6.6.

Compartments and Residential suites within Building 1 shall be separated

Fire Separations: from each other and the remainder of the building by a 45 min

fire separation. Residential suites within Building 2 shall be

separated from each other and the remainder of the building

by a 1 h fire separation.

Resistance to The residential dwelling units will conform to Subsections

Forced Entry: 9.6.8. and 9.7.6. regarding measures to resist forced entry to

suites at the suite doors.

2.12 Storage Garage Security

Fire Separations: A storage garage shall be separated from all other occupancies

by a fire separation with a fire-resistance rating not less than

1.5 h.

Vestibules Sentence 3.3.6.7.(2) requires vestibules separating a storage

garage from a stair tower or elevator to be constructed as fire

separations with a fire-resistance rating not less than 1 h and

with wired glass to provide maximum unobstructed visual

access. Sprinkler heads shall be placed at 1,800 mm on center

parallel to the glazing, and located between 150 mm and 300

mm perpendicular to the glass.

Closures with a fire protection rating not less than 45 min

shall be provided between the storage garage and the

vestibule and between the vestibule and a stair tower.

Stair Shafts: Stair shafts serving a storage garage shall be independent

from stair shafts which serve other occupancies, as per

Sentence 3.3.6.7.(3).

Lighting A minimum illumination level of 550 Lx shall be provided in

the first 15 m of entrance roadway of the garage. A minimum

of 110 Lx shall be provided in traffic aisles, and a minimum

of 220 Lx shall be provided in pedestrian access vestibules,

stairwells and elevator lobbies.

Page 16: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 14

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

2.13 Exits

Number of Exits: A minimum of two exits will be provided for each floor area.

Multi-storey dwelling units within a sprinklered building are

permitted to be served by a single exit provided it is not

necessary to travel up or down more than two storeys to reach

an exit door, and the travel distance to an exit does not exceed

25 m (applies to townhouse units).

Distance Between The least distance between two exits need not be more than

Exits: 9 m in floor areas served by a public corridor, but shall not be

less than 9 m in all other floor areas.

If more than two exits are provided from a floor area, they are

permitted to converge if the cumulative exit capacity does not

exceed half the total required exit width for the floor area.

Width of Exits: Exit doorways will provide a minimum clear width of

800 mm.

Exit stairs require a minimum width of 1,100 mm.

Fire Separations: Exits within Building 2 must be separated from the remainder

of the floor area by a fire separation with a fire-resistance

rating not less than 1 h. At the parkade level, exits must be

separated from the remainder of the floor area by a fire

separation with a fire-resistance rating not less than 2 h.

Exterior exit passageways need not be separated form

adjacent suites by a fire separation if not less than 50% of the

exterior side is open to the outdoors and an exit stairway is

provided at each end of the passageway.

Travel Distance: Travel distance to an exit must not exceed 45 m from any

floor area. For residential suites served by a public corridor,

this distance is permitted to be measured from the suite door.

Safe paths of travel with a minimum width of 1,100 mm shall

be provided within the parkade in any area where it is

necessary to travel between parking stalls to access exit in

conformance with Article 3.2.4.5.

Page 17: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 15

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

Exits Through Exits through lobbies are permitted, provided the maximum

Lobbies: travel distance from the exit to the outdoors does not exceed

15 m.

Doors: All exit doors must swing in the direction of exit travel.

Exit Signs: Exit signs must be provided at each exit and as required to

indicate direction of travel.

Exit Capacity: Exits are calculated at 6.1 mm per person for exterior doors

and ramps, and 8.0 mm per person for exit stairs

TABLE 2.13A: EXIT CAPACITY - COMMON PARKADE

Floor Exits ProvidedExit

Width

(mm)

Exit

Capacity

Factor

(mm per

person)

Floor

Exit

Capacity

(persons)

Floor

Occupant

Load

(persons)

P13 exit stairs @ 1,100 mm (clear) 3,300 8 413

1021 exit door @ 915 mm (clear) 915 6.1 150

TABLE 2.13B: EXIT CAPACITY - BUILDING 2

Floor Exits ProvidedExit

Width

(mm)

Exit

Capacity

Factor

(mm per

person)

Floor

Exit

Capacity

(persons)

Floor

Occupant

Load

(persons)

2 2 exit stairs @ 1,100 mm (clear) 2,200 8 275 88

3 2 exit stairs @ 1,100 mm (clear) 2,200 8 275 88

2.14 Service Facilities

Mechanical Room: 1 h fire separation for rooms containing fuel-fired equipment.

Main Electrical Rm: 2 h fire separation if not sprinklered.

1 h fire separation if sprinklered.

Other Electrical Rm: No fire separation required.

Garbage/Recycling: 1 h fire separation.

Water entry/sprinkler: No fire separation required.

Page 18: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 16

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

Vertical Service Fire separations with a fire resistance rating not less than

Spaces: that required by Table 3.8.3.1 for the floor assembly above.

2.15 Vertical Transportation

Elevator Separation: Vertical service spaces used for elevators shall be separated

from the remainder of the floor area by a fire separation with

a fire-resistance rating not less than that required by Table

3.5.3.1.

Elevator Car: Elevators shall conform to Appendix E of ASME A17.1/CSA

B44 "Safety Code for Elevators and Escalators".

Elevator Dimensions: At least one elevator cab is to be sized to accommodate a

stretcher 2,010 mm long and 610 mm wide. An elevator

satisfying this requirement shall be clearly indicated on the

main entrance level of the building.

2.16 Health Requirements

Plumbing Facilities: Each residential unit will be provided with its own washroom.

Room Height: The height of every room and space with dwelling units shall

conform to the requirements of Section 9.5.3 of the VBBL.

2.17 Barrier-Free Access

Parking: One parking stall for people with physical disabilities is

required for every 100 parking spaces.

Access: Barrier-free access must be provided:

• From the street to both principal entrance, and from

the principal entrance to an elevator.

• To and from parking areas containing accessible

parking stalls

All doors in a barrier-free path of travel will be provided with

clear and level areas including 300 mm/600 mm latch

clearances conforming to 3.3.1.13.(10). Where it is

impractical to provide the required latch clearances, power

operated doors may be used.

Page 19: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

Building Bylaw Compliance Summary Page 17

CHLTF Site 6 - 2922 East Kent Ave. South & 8588 Jellicoe St., Vancouver November 24, 2014

GBA File #141793 Revised June 19, 2014

As Building 2 contains greater than three dwelling units

served by an elevator and common corridor, enhanced

accessibility in conformance with Article 3.8.2.27 shall be

provided.

Ramps: Interior and exterior ramps shall comply with the

requirements of VBBL Article 3.8.3.3.

Tactile Warning: Tactile warning strips shall be provided at the top of a

stairway and should measure 725 mm to 775 mm by the full

width of the stair. The strips shall be located one tread width

back from the top riser and be slip-resistant, durable, not more

than 3 mm above or below the surrounding floor surface and

in a contrasting colour to the surrounding flooring.

This report was prepared by Gage-Babcock & Associates Ltd. (GBA) for our Client. The material herein reflects GBA's best judgment in light of

the information available to it at the time of preparation. GBA accepts no responsibility for damages, if any, suffered by any third part as a result

of use of the contents of this report without authorization from GBA. GBA shall not be held responsible for any alternative solutions stated in this

report without written acceptance of same by the applicable Authority Having Jurisdiction. It is the responsibility of the registered professionals

of record to incorporate building code measures described herein, including alternative solutions, into the design, building permit and construction

documents.

L:\Jobs_by_Year\14\141793 (gr) Site 6 2900 East Kent Ave South\8 - Analysis and Reports\1 - GBA Reports\141793 RPT 2015Jun19.wpd

Page 20: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire

APPENDIX ASketches

Page 21: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire
Page 22: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire
Page 23: Building By-law Compliance Summary VCLTF Site 6 Code Report.pdf ·  · 2016-02-03Building By-law Compliance Summary VCLTF Site 6 ... 2.5 Spatial Separation. ... Openings in a fire