BSRIA Isolation Rooms

34
BSRIA Isolation rooms Blanca Beato Arribas 26 February 2016

Transcript of BSRIA Isolation Rooms

Page 1: BSRIA Isolation Rooms

BSRIA

Isolation rooms

Blanca Beato Arribas

26 February 2016

Page 2: BSRIA Isolation Rooms

2Making buildings better…

BSRIA

A test, consultancy, instrument, research and market research organisation

Specialists in construction and building services

Member based association

Our values are to be authoritative, collaborative, independent and innovative

Our Mission is to

• Make Buildings Better

Page 3: BSRIA Isolation Rooms

3Making buildings better…

Turnover breakdown

Page 4: BSRIA Isolation Rooms

4Making buildings better…

Advice

Indoor air quality and thermal comfort

BIM strategy and roadmap to implementation

Life Cycle Costing and environmental assessment

Soft Landings implementation

Mock up testing and design validation

Page 5: BSRIA Isolation Rooms

5Making buildings better…

Investigations

Troubleshooting and failure investigations

Building Performance Evaluation (pre and post construction)

Maintenance audits, strategy and condition surveys

Condition monitoring

Building user guides

Page 6: BSRIA Isolation Rooms

6Making buildings better…

Mock-up testing

Page 7: BSRIA Isolation Rooms

7Making buildings better…

Mock-up testing

BSRIA’s facilities

White box chambers

– 9 m x 6 m x 4.5 m

– 8 m x 6 m x 4.5 m

“a box within a box”

– Controlled conditions

– Bigger spaces- i.e. open plan office

Page 8: BSRIA Isolation Rooms

8Making buildings better…

Isolation Rooms

Department of Health of England

PPVL and Negative P

CL4 downflow system

Department of Health, Social Services and Public Safety (DHSSPS), Northern Ireland

Intensive Care Unit (ICU)

Page 9: BSRIA Isolation Rooms

9Making buildings better…

PPVL Concept

Protection from

airborne infection

Protection to inmuno

compromised patients

Protection to staff in

room

Corridor

Isolation room

Bac

k pa

ssag

e

Ensuite

Lobby

Viewing chamber

S

E

Corridor

0.70

4.24 2.49

1.80

1.12

2.41

2.

0

2.8

4.5

8.45

6.83

All measurements in m

Internal height=3m excluding floor

Internal height lobby=2.7m excluding floor

Positively Pressurised Ventilated Lobby

Page 10: BSRIA Isolation Rooms

10Making buildings better…

Supply

220 l/s

Pressure

stabiliser

100 l/s

Extract

160 l/s

Door

60 l/s

Door

60 l/s

Door

60 l/s

Grille

100 l/s

+10 Pa0 Pa

0 Pa

-10 Pa

HBN4 Isolation room

LOBBY

ISOLATION

ROOM

EN SUITE

BATHROOM

CORRIDOR

Page 11: BSRIA Isolation Rooms

11Making buildings better…

Intensive Care Unit

CORRIDORPLANT ROOM

ISOLATION ROOM

LOBBY

Lobby to Isolation room door

Lobby to corridor door

Bed

RPS

LPS

Supply

Supply

High Extract

Low Extract

0 Pa

0 Pa

0 Pa10 Pa

0 Pa

Page 12: BSRIA Isolation Rooms

12Making buildings better…

Mock-up construction HBN4

Page 13: BSRIA Isolation Rooms

13Making buildings better…

Page 14: BSRIA Isolation Rooms

14Making buildings better…

ICU Mock-up Belfast

Page 15: BSRIA Isolation Rooms

15Making buildings better…

CL4 mock-up Bracknell

Page 16: BSRIA Isolation Rooms

16Making buildings better…

Isolation room

Validated

Smoke tests

Airtightness

Gas tracer

tests Salt tests/

bio-

aerosols*

Design

Mock-up

construction

Room air

movement

Validation process

CFD

*University of Leeds, UK

Page 17: BSRIA Isolation Rooms

17Making buildings better…

Airtightness

Differential Pressure

Flows through structure

These flows need to be

quantified

Set up the P/S and flow

under doors

Fan failure

BSRIA Standard on

airtightness of Isolation

rooms in 2016ATTMA Technical Standard 1 Issue 2 “Measuring Air Permeability of Building Envelopes”

Page 18: BSRIA Isolation Rooms

18Making buildings better…

Airtightness

Sealed plate for testing

Page 19: BSRIA Isolation Rooms

19Making buildings better…

Smoke tests

Page 20: BSRIA Isolation Rooms

20Making buildings better…

Smoke tests

Page 21: BSRIA Isolation Rooms

21Making buildings better…

Anemometer Surveys

(Room air movement)

Page 22: BSRIA Isolation Rooms

22Making buildings better…

Page 23: BSRIA Isolation Rooms

23Making buildings better…

Page 24: BSRIA Isolation Rooms

24Making buildings better…

Page 25: BSRIA Isolation Rooms

25Making buildings better…

Page 26: BSRIA Isolation Rooms

26Making buildings better…

Gas Tracer Tests

Nitrous Oxide

Release: different points

Room challenges: fan failure,

effect of doors

Page 27: BSRIA Isolation Rooms

27Making buildings better…

Gas Tracer Tests

Nitrous Oxide

Release: patient, sink,

nurse, tent

Room challenges: fan

failure, effect of doors

N2O-airborne

pathogens-studied at

the university of Leeds,

UK

Page 28: BSRIA Isolation Rooms

28Making buildings better…

Gas tracer tests

Page 29: BSRIA Isolation Rooms

29Making buildings better…

Comparison of PPVL and Neg P(Normalised Gas tracer concentration)

Model Type Test Extr.ppm 2

Bed

3

LHS

4

LHS

5

RHS

7

under bed ACR (h

-1)

Measured

1 PPVL 24 152 1.31 0.96 0.99 1.39 1.15 8.5

1 Neg P 30 174 0.95 0.86 0.90 1.14 0.44 11

Model Type Test Extr.ppm Extract Around bed 6

by nurse

2

by sink

7

under bed

ACR (h-1

)

Measured

2 PPVL 5 138 Low 1.00 0.88 0.97 0.88 12.3

2 Neg P 29 152 Low 1.18 1.18 0.98 0.86 18.2

Page 30: BSRIA Isolation Rooms

30Making buildings better…

CFD model

Model of empty room

Pressure stabiliser

Air speed

measurements- Used to

verify the predictions

Accurate modelling of

blade profile

Page 31: BSRIA Isolation Rooms

31Making buildings better…

Airtightness

Building Regulations :10 m3/hr/m2 at 50 Pa

BSRIA 1 m3/hr/m2 at a test pressure of 10 Pa = 2.62

at 50 Pa.

Model Working P Test P ALI ALI (used) Max Test Flow Rate

Max. Test Flow

Rate / unit volume

(Pa) (Pa) m3/(h.m

2) m

3/(h.m

2) (l.s

-1) (l.s

-1 per m

3)

1 10 20 3.16 3 72.5 1.01

15 30 3.87 3.9 94.3 1.31

20 40 4.47 4.5 108.8 1.51

25 50 5 5 120.8 1.68

2 10 20 3.16 3 99.2 0.75

15 30 3.87 3.9 128.9 0.98

20 40 4.47 4.5 148.8 1.13

25 50 5 5 165.3 1.25

nPkQ

Page 32: BSRIA Isolation Rooms

32Making buildings better…

Conclusions-Cat 1-3 Isolation

rooms

Successful validation: Well mixed (80%) single zone

Good comparison between GTT salt tests and

bioaerosols

Structural integrity = passive protection

Pressure differentials = protection to an extent (doors

closed)

Protection within the room = determined by internal

flows

– 0.5 to 2 of extract concentration

– Dilution strategy provides 10^3 Protection factor

Page 33: BSRIA Isolation Rooms

33Making buildings better…

Acknowledgements

The Department of Health of England

The Department of Health, Social Services and

Public Safety (DHSSPS), Northern Ireland

The University of Leeds, UK

Page 34: BSRIA Isolation Rooms

34Making buildings better…

The patient in the next bed is highly contagious- thank God for these curtains!!

Thank you for

your attention

Any questions?