Breaker Failure Protection
-
Upload
tanmaybeckham07 -
Category
Documents
-
view
228 -
download
4
Transcript of Breaker Failure Protection
Breaker Failure Protection 1
Breaker Failure Protection
Breaker Failure Protection 2
Backup Protection
Local backup is the additional (or secondary, redundant) protection provided for the primary zone to assure breaker trip if the primary relaying fails.
Remote backup is the overlapping of the primary zone provided by remote (adjacent busses) protection that will operate, after a suitable coordinating time, if the primary zone breaker does not trip. Relays at 1 protecting line AB are also remote backup to relays at 3 protecting line BC.
Breaker failure is initiated when the primary and/or local backup relays have operated and the local breaker fails to trip.
Fault X
A1 2
5 6
3
7 8
4
D E
CB
Breaker Failure Protection 3
Backup: Local, Remote and Breaker Failure
Local Backup Relays
Remote Backup Relays
Primary Relays
50BF
Trip Local Breaker
Trip Local Adjacent Breakers
Trip Remote Breaker
62BF
Remote Backup Relay Time Delay
Breaker Failure Relay
Breaker Failure Protection 4
Remote Backup
Fault on line BC - Failure of breaker 3 to operate
Relays at 1,5 and 8 are backup to to relays at 3
Backup relays may not see fault due to infeed
Coordination time may be undesirably slow
Sequential remote tripping• If one remote can see the fault and clear there will be a
redistribution of fault currents reducing the effect of infeed• The second remote relay will trip eliminating infeed• The last remote relay will trip
Fault X
A1 2
5 6
3
7 8
4
D E
CB
Breaker Failure Protection 5
Breaker Failure
EHV and UHV Applications
• Greater fault currents produce more stress on power circuit breakers
• Stability demands for faster backup clearing – Critical Clearing Time
Thus, Local Breaker Failure
• Breaker failure does not preclude remote backup
Breaker Failure Protection 6
Breaker Failure and Remote Backup
Fault on line BC and relays at 1, 2 and 5 operate
Breakers 1 and 5 trip - breaker 2 fails to operate
Breaker failure at 2 trips breaker 3 and removes any infeed seen by relays at 4
Relays at 4 will operate as remote backup to clear fault
Transfer tripping of breaker 4 by breaker failure at 2 is also possible
CFault X
A
1
2
3
4
B
5
Breaker Failure Protection 7
Breaker Failure Scheme
50 - Phase and ground instantaneous overcurrent relays
52a - Breaker auxiliary contact, open when breaker is open
52T - Breaker trip coil
62X,Y - Breaker failure auxiliary (BFI)
62BF - Breaker failure timer
86BF - Breaker failure lockout relay
94 - Breaker trip relay (used for single trip coil applications)
Relay Scheme
#2
52a
94 62Y
+ dc
- dc
94Relay
Scheme #1
52a
52T
62X
+ dc
- dc
62X
+ dc
- dc
62BF
62 BF
62Y
86BF
50
Multiple 86BF
Contacts86 BF
Breaker Failure Protection 8
Breaker Failure Logic
T0
62X62Y
5086BF52a
52a86T 62BF
50 - Phase and ground instantaneous overcurrent relays
52a - Breaker auxiliary contact, open when breaker is open
62X,Y - Breaker failure auxiliary (BFI)
62BF - Breaker failure timer
86BF - Breaker failure lockout relay
86T - Transformer differential lockout
Options
Breaker Failure Protection 9
Single-line Single-breaker Bus
1 Line 1
2 Line 2
3 Line 3
N Line N
50 BF
Line Relays 62X,Y
62X,Y 50BF-1
62X,Y 50BF-2
62X,Y 50BF-3
62X,Y 50BF-N
62 BF
86 BF
Bus Arrangement Typical Logic
Breaker Failure Protection 10
Breaker-and-a-half Bus
Line 1 Line 2
50 2
50 1
50 3
Line 2 Relays
Line 1 Relays
1 2 3
4Bus L
Bus R
BreakerFailure
86 RelayOperations
1 Trip 2 and all Bus Lbreakers.Transfer trip Line 1
2 Trip 1 and 3.Transfer trip lines 1 & 2.
3 Trip 2 and all Bus Rbreakers, such as 4.Transfer trip line 2
Breaker Failure Protection 11
Ring Bus
Line 1
Relays
Relays
Line 250 1
50 2
Transformer Differential
1
2
3
4
50 3 Relays
Line 3
5
50 4
86T
Breaker Failure
86 Relay Operations
1 Trip 2 and 4 Transfer trip lines 1 & 2
2 Trip 1 and 3 Transfer trip lines 2 & 3
3 Trip 2, 4, and 5 Transfer trip line 3
4 Trip 1, 3, and 5 Transfer trip line 1
Breaker Failure Protection 12
Breaker Failure Logic
62X,Y - Breaker failure auxiliary (BFI) Include both line relay’s 62X, Y for common breaker• Breaker-and-a-half bus - center breaker• Ring bus
62X
+ dc
- dc
62BF
62 BF
62Y
86BF
50
86 BF
**
T0
62X 62Y
5086BF52a
52a86T 62BF
Options
**
Breaker Failure Protection 13
Breaker Failure Time Chart
Relay Operate
Breaker Clearing
Normal Clearing Time50
ResetMarginNormal
Clearing
Failed Breaker
62X 62Y BFI
62BF Timer Setting86 BF
TFR TRIP
Local Backup Clearing
Remote Backup Clearing
Normal ClearingLocal Backup BF Total Clearing
Remote Backup BF Total Clearing
Breaker Failure Protection 14
Breaker Failure
50BF Overcurrent Reset is affected by:• Breaker arcing contacts and shunting resistors • Fault current level prior to interruption• CT saturation• 50BF setting• Breaker-and-a-half and ring bus applications
Solid state relays have faster reset than electromechanical relays
Reset is generally assured to be within one cycle using microprocessor relays -this is dependent on sampling and computation rate
Breaker Failure Protection 15
Breaker Failure Logic
50BF - Phase and ground torque controlled instantaneous overcurrent relays
Relay cannot operate until after 62BF time
Fast pickup, 0.25 to 1.0 cycle depending on setting and fault current
Allows more sensitive setting
Control timer resets breaker failure operation
TR
62X62Y
50BF
Control Timer
T0
62BF Torque Control
86BF
Retrip
Breaker Failure Protection 16
Breaker Failure Time Chart
Relay Operate
Breaker Clearing
Normal Clearing Time
50 Pickup
MarginNormal Clearing
Failed Breaker
62X 62Y BFI
62BF Timer Setting86 BF
TFR TRIP
Local Backup Clearing
Remote Backup Clearing
Normal ClearingLocal Backup BF Total Clearing
Remote Backup BF Total Clearing
Control Timer T (Setting) R
Breaker Failure Protection 17
Critical Clearing Time
A maximum allowable time that a fault may persist before jeopardizing the integrity of the power system• System location• Loading• Fault type
Breaker failure clearing time including remote backup clearing must be less than critical clearing time
Breaker Failure Protection 18
IPO Breakers
Independent Pole Operated Breakers• Single pole tripping and reclosing• Three pole tripping
– On breaker failure • the opening of two phases on a three-phase fault will
likely clear the fault or change the fault characteristic to single-phase-to-ground.
• Increase the maximum critical clearing time.
Pole Discrepancy detection becomes increasingly important
Breaker Failure Protection 19
Pole Discrepancy
Based on auxiliary 52a and/or 52b contact positions
Based on breaker current level
Breaker Failure Protection 20
Pole Discrepancy
Auxiliary contact arrangement for three pole gang operated breaker position indication
Breaker Failure Protection 21
Pole Discrepancy
Auxiliary contact arrangement for IPO breaker position indication
Using 52a - parallel• 52a = 0 (All poles open)
• 52a = 1 (Any pole closed)
Using 52b - series• 52b = 1 (All poles open)
• 52b = 0 (Any pole closed)
CIRCUIT BREAKER
52a
A
A
A
B
B
B C
C
C
52b
Breaker Position
Breaker Position
52a
52a
52b 52b
Breaker Failure Protection 22
Pole Discrepancy
Auxiliary contact arrangement for IPO breaker position indication
Using 52a - series• 52a = 0 (Any pole open)
• 52a = 1 (All poles closed)
Using 52b - parallel• 52b = 1 (Any pole open)
• 52b = 0 (All poles closed)
CIRCUIT BREAKER
52a
A
A
A
B
B
B C
C
C
52b
Breaker Position
Breaker Position
52a52a
52b
52b
Breaker Failure Protection 23
Pole Discrepancy
Auxiliary contact arrangement at IPO breaker • Breaker position• Pole discrepancy
indication
CIRCUIT BREAKER
A
A
B
B
C
C
52a
Pole DiscrepancyFrom Breaker
52a
52a
A
B
C
52b
52b
52b
Breaker position with 52a (any pole closed)
Breaker Failure Protection 24
Pole Discrepancy
Auxiliary contact arrangement at IPO breaker • Breaker position with 52a
and 52b• Pole discrepancy logic in IED
Breaker Failure Protection 25
CIRCUIT BREAKER
A
A
B
B
C
C
52a - A
52a - B
52a - C
Pole Discrepency
ANDAND
IED Logic
OR
Pole Discrepancy
Auxiliary contact arrangement at IPO breaker • Breaker position with 52a/pole• Pole discrepancy logic in IED• Particularly suitable for SPT
Breaker Failure Protection 26
Pole Discrepancy
Auxiliary contact arrangement at IPO breaker • Breaker position with 52a and 52b
per pole• Pole discrepancy logic in IED• Particularly suitable for SPT
Breaker Failure Protection 27
Pole Discrepancy
Breaker Failure Protection 28
Questions?