Breaker Failure Protection RAICA

8
Page 1 Features Provides local back-up protection when the primary breaker fails to operate Initiates tripping of adjacent back-up breakers for disconnection of the fault, thus preventing power system instability Start verifier provides retrip or cross-trip of primary circuit-breaker for security and reliability after initiation by trip signal Very short operating times due to the fast reset time of the overcurrent detectors Evolving faults can be covered Insensitive to current transformer satura- tion and transients Accurate, consistent, short operating times and high overload capacity In case of multiple busbars tripping is normally achieved through the switching system in the bus protection Suitable as a stand-alone protection or can be integrated in a busbar protection. RAICA work together with RADSS bus protection Application This relay is required to rapidly initiate fault clearing by power circuit-breakers when, for example, a short-circuit occurs in the power system, consequently isolating the faulty sec- tion of the system. It is then important that the power circuit- breaker operates correctly, so that the fault clearing is done quickly. However, there is always a risk that the breaker will not succeed in interrupting the fault current and that the fault clearing time will be dependent on how fast the back-up protection schemes can ini- tiate clearing. A simple and secure way to verify correct operation of a power circuit-breaker is to determine that after a certain time, suffi- ciently long for the circuit-breaker to operate, there is no longer any current through the breaker. The breaker failure relay has current measur- ing detectors providing a possibility to mea- sure either phase currents or phase currents and zero sequence current. The tripping impulse of the protective relay operating the circuit-breaker simultaneously starts the breaker failure relay. (SE980072) Breaker-failure protection RAICA 1MRK 505 005-BEN Issued July 1998 Changed since June 1998 Data subject to change without notice

Transcript of Breaker Failure Protection RAICA

Page 1: Breaker Failure Protection RAICA

Page 1

(SE980072)

Breaker-failure protection RAICA

1MRK 505 005-BEN

Issued July 1998Changed since June 1998

Data subject to change without notice

Features • Provides local back-up protection when the primary breaker fails to operate

• Initiates tripping of adjacent back-up breakers for disconnection of the fault, thus preventing power system instability

• Start verifier provides retrip or cross-trip of primary circuit-breaker for security and reliability after initiation by trip signal

• Very short operating times due to the fast reset time of the overcurrent detectors

• Evolving faults can be covered

• Insensitive to current transformer satura-tion and transients

• Accurate, consistent, short operating times and high overload capacity

• In case of multiple busbars tripping is normally achieved through the switching system in the bus protection

• Suitable as a stand-alone protection or can be integrated in a busbar protection. RAICA work together with RADSS bus protection

Application This relay is required to rapidly initiate fault clearing by power circuit-breakers when, for example, a short-circuit occurs in the power system, consequently isolating the faulty sec-tion of the system.

It is then important that the power circuit-breaker operates correctly, so that the fault clearing is done quickly. However, there is always a risk that the breaker will not succeed in interrupting the fault current and that the fault clearing time will be dependent on how fast the back-up protection schemes can ini-tiate clearing.

A simple and secure way to verify correct operation of a power circuit-breaker is to determine that after a certain time, suffi-ciently long for the circuit-breaker to operate, there is no longer any current through the breaker.

The breaker failure relay has current measur-ing detectors providing a possibility to mea-sure either phase currents or phase currents and zero sequence current.

The tripping impulse of the protective relay operating the circuit-breaker simultaneously starts the breaker failure relay.

Page 2: Breaker Failure Protection RAICA

Breaker-failure protectionABB Network Partner RAICA1MRK 505 005-BEN

Page 2

Application (cont’d) If the current through the power circuit-breaker still is above the set value of the cur-rent measuring detectors after the set time, the breaker failure relay provides a tripping impulse to adjacent circuit-breakers in the same station.

In the event of a multibus-configuration, it is normal practice to arrange for the trip signal to pass the appropriate selector switch of the bus protection, in order to trip the particular bus with the faulty breaker.

Fig. 1 Operating diagram for trip at a breaker failure situation.

Design The breaker failure relay RAICA consists of (depending on the variant) a test switch, type RTXP 18, three current relays, RXIB 24, one or two time relays, RXKL 1, an impulse stor-ing device, RXTCB 1, and an output relay type RXMS 1 and auxiliary relay with flag RXME 18 or signal relay RXSF 1.

RAICA has no power consumption in auxil-iary dc circuits during normal service and the current relays can be set below load without operation until after initiation.

The relay includes static current and time measuring units with excellent measuring accuracy.

Two phase and one earth current module are recommended so that the phase modules can be set high for added security and the earth module low for sensitivity.

It is recommended that the phase modules be set below minimum load to enable operation for a trip condition.

Two phase and earth (or three phase) breaker failure relays using three individual current relays are capable of accurate and consistent

timing even during adverse CT saturation conditions, independent of current magni-tude and possible dc components.

Retrip feature after start can be included for security and reliability. Seal-in of the start signal can also be included to ensure reliable timing.

The start signal to the RAICA supplies dc auxiliary voltage to the current modules. Only if current is present above the set levels will the start verifier pick-up, seal-in, provide a trip signal to the primary breaker and start the timer.

If the primary breaker fails to trip, the timer operates to trip the back-up circuit-breakers. The filter has an RC network to absorb tran-sient energy and prevent false starting of the start verifier (caused, for example, by acci-dental earth on the initiate output).

The BFR type RAICA is suitable either as a stand-alone protection or can be integrated in the busbar protection RADSS

.

Triprelay

Setting of time relay

Operating timeof CBs Margin

Operating timeof CBs

Margin

Total trip time of breaker failure protection

Max. trip time to avoid unstability in network

Start of breaker failure protection

t

Normal tripof CBs

Trip at breakerfailure situation

Occurance of fault

Drop-out time of current relays

Normal trip time

Relay protection

(960

0020

7)

Page 3: Breaker Failure Protection RAICA

Breaker-failure protection RAICA1MRK 505 005-BEN

Page 3

ABB Network Partner

Fig. 2 Basic RAICA relay for one line.

Retrip own CBSeveral of the available versions give a retrip command to their circuit-breaker.

Two time stepsWhen very short times on three-phase or mul-tiphase faults are necessary because of system stability the two timer scheme is recom-mended so that more frequent, less critical earth faults can be cleared with greater mar-gin.

Signal flagsSignal relay of type RXSF may optionally be included in the breaker failure relay. Indica-tion may be obtained for instantaneous trip-ping or for tripping on the individual time steps.

Single-pole tripRAICA can be used for single-pole tripping if the current measuring units are set above the largest load current. At single-pole tripping, the RAICA must be supplemented with relay logic that selects the proper phase of the cir-cuit-breaker to be tripped on the first time step. This optional version may be quoted upon request.

Evolving faultsEvolving faults can be dealt with by includ-ing one optional time-lag relay per phase.

(960

0020

8)

Page 4: Breaker Failure Protection RAICA

Breaker-failure protectionABB Network Partner RAICA1MRK 505 005-BEN

Page 4

Technical data

Scale range (RXIB 24) 10-150 mA, 0,1-1,5 A, 0,2-3 A or 1-15 A

Operating value Settable (1-3) x rated scale contact IS

Operating time (RXIB 24,typical) 4-6 ms(2,5 x rated value)

Resetting time (RXIB 24, typical)Resetting ratio

5-11 ms> 70%

Rated frequency 50 or 60 Hz

Time range (RXKL 1) 20 ms-99 h

Load carrying capacityIS = 10/25/50 mAIS = 0,1/0,25/0,5 AIS = 0,2/0,5/1 mAIS = 1/2/5 A

Continuous During 1s0,3/0,7/1,2 A 4,4/12/15 A2,7/6,5/10 A 33/100/180 A6,8/11/15 A 180/230/230 A15/20/20 A 230/350/350 A

Burden per phase 5-150 mVA

Auxiliary voltage UL 48, 55, 110, 125, 220, 250 V dc-20%, +10%

Permitted ambient temperature -25 °C, +55 °C

DimensionsWeight See Ordering table

Insulation test:Dielectric test

Current circuitVoltage circuit

Impulse voltage test

50 Hz, 500 V, 2 min50 Hz, 200 V, 1 min5 kV, 1,2/50 µs, 0,5 J

Disturbance test:Normal frequency test1 MHz-testFast transient test

50 Hz, 500 V, 2 min2,5 kV, 2 s4-8 kV, 2 min

Contact data:RXME/RXSF/RXMSRXKL

see 1MRK 508 015-BENsee 1MRK 508 002-BEN

Page 5: Breaker Failure Protection RAICA

Breaker-failure protection RAICA1MRK 505 005-BEN

Page 5

ABB Network Partner

Diagrams

Fig. 3 Terminal diagram 7429 0001-CAA for RAICA, RK 651 211-CA

Fig. 4 Terminal diagram 7429 0020-BAA for RAICA, RK 651 034-BA

32

BREAKER FAILURE PROTECTION WITHONE TIME STEP, CURRENT DETECTORSIN 3 PHASES OR TWO PHASES ANDNEUTRAL

UL+

1)

2)

3)

4)

+ + + + + + -UL

-

- &

-+

7429 0001-CA RAICA3A

4A

5A

6A

7A

8A

10113A

9A

101

17A16A15A14A12A11A

2A101

1A 18A

101

331:16331:26

331:

2733

1:23

331:

1332

5:24

3

L1 L2 L3

(R)

(S)

(T)

L1 L2 L3

(R)

(S)

(T)

ALT.

2) TRIPPING OF BACK-UP CIRCUIT BREAKERS

1) TRIPPING OF PRIMARY CIRCUIT BREAKER

3) ALARM ETC.

4) TRIP RELAY IN OTHER PROTECTION

101 107 119 131

307 319 325

36C

4U331

II I

101107 119 307131319325331

RTXP 18RXIB 2RXKL 1RXTCB 1RXMS 1RXSF 1

N

131:27

+ + + + +

101

131:

16

2A13A

131:

26

UL

+ + -

101

18A

1A331:

2613

1:14

331:

16

+

10AUL+

17A16A15A14A131:23131:25

2)

3)

11A

12A

9A101

1)

& &

1

-

+

&

7429 0020-BA RAICA

3) ALARM ETC.

2) TRIPPING OF BACK-UP CIRCUIT BREAKER

1) TRIP RELAY IN ANOTHER PROTECTION

BREAKER FAILURE PROTECTION WITHONE TIME STEP, CURRENTDETECTORS

101107,119, 307131319325331

101

8A

4A

5A

6A

7A

(R)

3A

101

L1

(S)

(T)

L3L2

107 119 131

307 319 325 3314U

3 I

36C

RTXP 1 8RXIB 24RXMS 1RXTCB 1RXKL 1RXME 18

Page 6: Breaker Failure Protection RAICA

Breaker-failure protectionABB Network Partner RAICA1MRK 505 005-BEN

Page 6

Diagrams (cont’d)

Fig. 5 Terminal diagram 7429 0003-CAA for RAICA, RK 651 213-CA

32

BREAKER FAILURE PROTECTION WITHTWO TIME STEPS IN 3 PHASES ORTWO PHASES AND NEUTRAL

UL+

1)

2)

3)

+ + + + + -UL

-

- &

-+

7429 0003-CA RAICA3A

4A

5A

6A

7A

8A

10113A

9A

101

17A16A15A14A12A11A

10A

2A101

1A 18A

101

331:16331:26

337:

1333

1:23

325:

24

3

&

4) 337:16

6)

5)

L1 L2 L3

(R)

(S)

(T)

L1 L2 L3

(R)

(S)

(T)

ALT.

2 2

331:

2733

1:13

331:14331:28

++

6) EXTERNAL CONDITION FOR START OFTIME RELAY OF SHORT TIME

TRIP RELAY IN ANOTHER PROTECTION5)

ALARM ETC.4)

3) TRIPPING ETC. SHORT TIME

2) TRIPPING OF BACK-UP CIRCUIT BREAKERS

1) TRIPPING OF PRIMARY CIRCUIT BREAKER

101 107 119 131

307 319 325

42C

4U

RTXP 18RXIB 2RXKL 1RXKL 1RXTCB 1

331

RXMS 1

137

337

RXSF 1

I I

(NORMAL TIME)(SHORT TIME)

I

101107, 119, 307131137319325331 337

N

Page 7: Breaker Failure Protection RAICA

Breaker-failure protection RAICA1MRK 505 005-BEN

Page 7

ABB Network Partner

Ordering Specify:

• Quantity

• Ordering No.

• Rated frequency

• Auxiliary voltage UL

• Scale range, for each RXIB 24

• Desired wording on the lower half of the test switch face plate max. 13 lines with 14characters per line.

• RAICA is provided on apparatus bars. When additional mounting is required specify a 4U equipment frame for 19” rackmounting or a type RHGX 12 or 20 case for panel mounting.

References RXIB 24 current relay1MRK 508 018-BEN

RADSS busbar protection1MRK 505 003-BEN

Auxiliary relays1MRK 508 015-BEN

Time relays 1MRK 508 002-BEN

Further information:Description RK 651-302E

Information RF 637 375E

Current detection Description Dimensions Weight Ordering No.Circuit diagram/Terminal diagram

3I> single-phase start One time step, one flag 4U 36C 5 kg RK 651 034-BA 7429 0020-BA7429 0020-BAA

3I> or 2I> + IN> Single-phase tripping of primary circuit breaker, one time step, one flag

4U 48C 7 kg RK 651 222-AA 7429 0006-AA7429 0006-AAA

3I> or 2I> + IN> Tripping of primary circuit breaker, one time step, one flag

4U 42C 6 kg RK 651 036-BA 7429 0022-BA7429 0022-BAA

3I> or 2I> + IN> Tripping of primary circuit breaker, one time step, two flags

4U 36C 5 kg RK 651 211-CA 7429 0001-CA7429 0001-CAA

3I> or 2I> + IN> Tripping of primary circuit breaker, two time steps, external start

4U 36C 5 kg RK 651 213-AA 7429 0003-AA7429 0003-CAA

3I> or 2I> + IN> Tripping of primary circuit breaker, two time steps, external start, three flags

4U 42C 6 kg RK 651 213-CA 7429 0003-CA7429 0003-CAA

3I> + IN> Four current relays, two time steps, one flag

4U 60C 8 kg RK 651 081-DC 7431 0122-DC7431 0122-DCA

3I> + IN> Four current relays, tripping of primary circuit breaker, two time steps, two flags

4U 60C 9 kg RK 651 081-DB 7431 0122-DB7431 0122-DBA

3I> or 2I> + IN> One time step, tripping via bus protectionRADSS

4U 30C 4,5 kg RK 651 025-AA 7431 0019-BA7431 0019-BAA

Page 8: Breaker Failure Protection RAICA

Breaker-failure protectionABB Network Partner RAICA1MRK 505 005-BEN

Page 8

Manufacturer ABB Network Partner ABS-721 71 VästeråsSwedenTel: +46 21 321300Fax: +46 21 146918