BPG Replacing a Consumer Unit - Domestic

10
Consumer unit replacement in domestic premises 6

description

hghg

Transcript of BPG Replacing a Consumer Unit - Domestic

  • Consumer unitreplacementin domesticpremises

    6

  • page 2 The Electrical Safety Council

    The Electrical Safety Council is indebted to the followingorganisations for their contribution and/or support to thedevelopment of this Guide, and in particular to NICEICGroup Ltd for providing the initial draft:

    Published by:

    The Electrical Safety Council

    18 Buckingham Gate

    London

    SW1E 6LB

    Tel: 0870 040 0561 Fax: 0870 040 0560

    Email: [email protected]

    Website: www.esc.org.uk

    The Electrical Safety Council and other contributors believe that theguidance and information contained in this Guide is correct, but allparties must rely on their own skill and judgement when making use ofit. Neither the Electrical Safety Council nor any contributor assumes anyliability to anyone for any loss or damage caused by any error oromission in the Guide, whether such error or omission is the result ofnegligence or any other cause. Where reference is made to legislation, itis not to be considered as legal advice. Any and all such liability isdisclaimed.

    The Electrical Safety Council. July 2009

    This is one of a series of Best Practice Guides produced by theElectrical Safety Council* in association with leading industry bodiesfor the benefit of electrical contractors and installers, and theircustomers.

    BEAMA Installationwww.beamainstallation.org.uk

    British Gaswww.britishgas.co.uk

    BSI Product Serviceswww.bsigroup.com

    CORGIwww.trustcorgi.com

    City & Guildswww.cityandguilds.com

    Electrical Contractors Associationwww.eca.co.uk

    ELECSAelecsa.co.uk

    Institution of Engineering andTechnologywww.theiet.org

    NAPITwww.napit.org.uk

    NICEIC Group Ltdwww.niceic.com

    Micropower Councilwww.micropower.co.uk

    SELECT(Electrical Contractors Association ofScotland)www.select.org.uk

    SCEMEwww.sceme.org

    In electronic format, this Guide is intended to be made availablefree of charge to all interested parties. Further copies may bedownloaded from the websites of some of the contributingorganisations.

    The version of this Guide on the Electrical Safety Council website(www.esc.org.uk) will always be the latest. Feedback on any of theBest Practice Guides is always welcome email [email protected]

    The Electrical Safety Council is supported by all sectors of theelectrical industry, approvals and research bodies, consumer interestorganisations, the electrical distribution industry, professionalinstitutes and institutions, regulatory bodies, trade and industryassociations and federations, trade unions, and local and centralgovernment.

    *The Electrical Safety Council (formerly the National InspectionCouncil for Electrical Installation Contracting) is a charitablenon-profit making organisation set up in 1956 to protect users ofelectricity against the hazards of unsafe and unsound electricalinstallations.

  • 1. Aim

    1.1. The aim of this Guide is to promote best practice byproviding practical advice and guidance fordesigners, installers, verifiers and inspectors wherethe consumer unit or other main switchgear is beingreplaced in a home wired in accordance with theSixteenth Edition or earlier of the IEE WiringRegulations. The guidance is intended to protectcustomers and installers against dangeroussituations that could arise from the existinginstallation.

    1.2. The guidance recognises that the existing circuitsbeing connected to a replacement consumer unitmay not comply with the current edition ofBS 7671. In following the guidance, the installeraccepts this and must be satisfied that all new workon a particular installation addresses the risks.

    1.3. A consumer unit need not necessarily be replacedsimply because it has rewireable fuses, cartridgefuses or older-type circuit-breakers, as these devicescan provide satisfactory overcurrent protection.Similarly, a consumer unit need not be replacedbecause it does not incorporate Residual CurrentDevice (RCD) protection, as there may be otherways to provide this protection than replacing theconsumer unit.

    2. Introduction

    2.1. This Guide has been produced by the ElectricalSafety Council in association with the bodiesindicated on page 2.

    3. Limitation

    3.1. This guidance applies only to the replacement of aconsumer unit and reconnection of existing circuits.

    page 3The Electrical Safety Council

    Consumer unitreplacement indomestic premises

    Photo courtesy of NAPIT

  • 4. Legal requirements

    4.1. There is no legal requirement that calls for anexisting electrical installation to be upgraded tocurrent standards.

    4.2. However, there is a requirement under the BuildingRegulations for England and Wales to leave theinstallation and the building no worse in terms ofthe level of compliance with other applicable partsof Schedule 1 to the Building Regulations thanbefore the work was undertaken. (Schedule 1 givesthe requirements with which building work mustcomply.)

    4.3. Similarly, the Scottish Building Standards TechnicalHandbooks, which provide guidance on achievingthe standards set in the Building (Scotland)Regulations 2004, require that any work associatedwith the replacement of a service, fitting orequipment by another of the same general type isto a standard no worse than at present.

    4.4. Replacing a consumer unit in domestic premises inEngland or Wales is notifiable work under theBuilding Regulations. Unless the work is undertakenby a person registered with an electrical self-certification scheme prescribed in the regulations,notification of the proposals to carry out the workmust be given to a building control body before thework begins, or, where the work is necessarybecause of an emergency, the building control bodyshould be notified as soon as possible.

    4.5. Installers are reminded of the need to comply withthe relevant parts of the Electricity at WorkRegulations 1989 when replacing a consumer unit.In particular, attention is drawn to:

    regulation 12, Means for cutting off the supplyand for isolation,

    regulation 13, Precautions for work onequipment made dead, and

    regulation 14, Work on or near live conductors.

    4.6. These regulations mean that it will be necessary tomake arrangements with the electricity supplier forthe cut-out fuse to be withdrawn in order todisconnect the incoming supply for the purpose ofisolation, unless a suitable isolating switch has beenprovided on the supply side of the consumer unit forthis purpose. Guidance on safe isolation proceduresis given in Best Practice Guide No 2.

    5. Requirements of BS 7671

    5.1. Replacing a consumer unit in an existing installationis an addition or alteration to that installation. Thework must therefore be designed, erected andverified in accordance with the requirements of thecurrent edition of BS 7671, and must not impair thesafety of the existing installation. (Regulations110.1(xx) and 610.4 refer.)

    5.2. BS 7671 does not require existing circuits to beupgraded to current standards in order for them tobe connected to the outgoing ways of thereplacement consumer unit.

    5.3. However, circuits that are defective or non-compliant with the requirements of BS 7671 in away that would result in real and immediate dangermust not be connected to the consumer unit.

    5.4. Where a consumer unit is being replaced, additionalprotection by means of RCDs in accordance withRegulation 415.1 should be provided to the extentrequired by the current edition BS 7671, such as for:

    socket-outlets (Regulation 411.3.3 refers),

    mobile equipment for use outdoors(Regulation 411.3.3 refers),

    cables concealed in walls or partitions, whererequired by Regulations 522.6.6 to 522.6.8, and

    circuits of locations containing a bath or shower(Regulation 701.411.3.3 refers).

    5.5. Circuits that are to be provided with RCD protectionmust be divided between a sufficient number ofRCDs or otherwise designed as necessary to avoidhazards and minimise inconvenience in the event ofa fault (Regulations 314.1 and 314.2 refer).

    5.6. The consumer unit must not be replaced until it hasbeen established that:

    the rating and condition of any existingequipment, including that of the distributor, willbe adequate for the altered circumstances, and

    the earthing and bonding arrangementsnecessary for the safety of the alteration oraddition are also adequate.

    (Regulation 131.8 refers.)

    5.7. Any defects found in the reconnected circuits mustbe recorded on the Electrical Installation Certificatecovering the replacement of the consumer unit, asrequired by Regulation 633.2

    page 4 The Electrical Safety Council

  • 6. Main earthing and bonding and meter tails

    6.1. The installer must verify, as a minimum, that:

    a) the main earthing terminal of the installation isconnected to an adequate means of earthingvia a suitably sized earthing conductor,

    b) the main protective bonding is adequate, and

    c) the meter tails and the distributors equipmenthave adequate current-carrying capacity.

    Note. Some electricity distributors have requirements regarding

    the earthing conductor, main bonding conductors and meter

    tails that exceed the requirements of BS 7671.

    6.2. If any of conditions 6.1 (a), (b) or (c) is not met, thecustomer should be informed that upgrading isrequired. If the customer refuses, the installershould not proceed with the replacement of theconsumer unit.

    7. Reason for change

    7.1. The replacement of a consumer unit could be aplanned change, as referred to in Section 7.2, or adistress change, as referred to in Section 7.3.

    7.2. Planned change

    7.2.1. The initial approach of the contractor planning thereplacement of a consumer unit should be toencourage the customer to have a periodicinspection and test of the installation carried out inadvance of the consumer unit being replaced.

    7.2.2. If the customer refuses, a pre-work survey should becarried out to ascertain if there are any immediateor potential dangers, or any condition that wouldcause unwanted tripping of an RCD, in the existinginstallation affected by the change. As a minimum,the survey should, include:

    making enquires with the user as to whetherthere are any known defects, faults or damage,

    an internal visual inspection of the existingconsumer unit to determine, amongst otherthings, the type and condition of the wiringsystem used for the installation,

    an external visual inspection of other readilyaccessible parts of the installation,

    a measurement of the external earth fault loopimpedance, Ze,

    a test of circuit protective conductor continuityat the end of each final circuit, and

    an insulation resistance measurement of thewhole installation at the consumer unit, betweenthe live conductors connected together and theprotective conductor connected to the earthingarrangement.

    7.2.3. If any immediate danger, potential danger orcondition that would cause unwanted tripping of anRCD is found, the customer should be informed thatremedial work is necessary to improve safety.

    7.2.4. Depending on the extent, the remedial work couldinvolve considerable additional cost, not only ininstalling new cables or accessories, but also in therenewal of decorations, unless the customer iswilling to accept surface wiring.

    page 5The Electrical Safety Council

  • 7.2.5. If the customer is unable, or not prepared, to accepteither the cost or the disruption of the remedialworks, but still requires a new consumer unit to beinstalled, the installer needs to carry out a riskassessment as described in Section 8 beforeagreeing to replace only the consumer unit.

    7.2.6. Where cables are lead or rubber sheathed thendeterioration of the cables is likely to necessitaterewiring when the consumer unit is replaced.

    7.3. Distress change

    7.3.1. A distress change occurs when the consumer unithas suffered damage, has become unusablethrough overheating, or is in a dangerous conditionwith exposed live parts. This situation usuallyrequires immediate replacement of the consumerunit. However, the installation of the consumer unitmust still comply with the requirements of thecurrent edition of BS 7671. This means, amongstother things, that requirements a), b) and c) referredto in Section 6.1 must be met.

    7.3.2. It should be explained to the occupant before theconsumer unit is replaced that:

    if an immediately dangerous condition is foundin an existing final circuit, it will not be possibleto reconnect that circuit until remedial action iscarried out, and

    it will be necessary to return to the installation tocarry out any further work that would have beenrequired if the replacement of the consumer unithad been planned. This further work, whererequired, must be carried out without delay.

    Result of a DIY home owner having wired an 10.5 kW electric

    shower circuit with 2.5 mm2 cable and a 45 A circuit-breaker.

    (Photo courtesy of British Gas)

    8. Risk assessment

    8.1. As stated in Section 7.2.5, where it is proposed toreplace a consumer unit but the customer is unableor unwilling to accept either the cost or disruption ofthe remedial works, a risk assessment should beundertaken. This is for the purpose of advising thecustomer as to the level of risk that would exist oncompletion of the proposed work. A disclaimer doesnot absolve the installer from responsibility.

    8.2. In all cases, the initial approach should be topersuade the customer that remedial actionshould be taken to correct or remove anyimmediate danger, potential danger orcondition that would cause unwanted trippingof an RCD.

    8.3. The risk assessment requires inspection and testing(except to the extent these have already beencarried out as part of the periodic inspection reportor pre-work survey mentioned in Section 7.2)

    8.4. The inspection and testing are necessary toestablish, for the circuits concerned, at least whetheror not there are:

    a) any immediate dangers (departures that wouldwarrant a code 1 recommendation according toBest Practice Guide Number 4 in a periodicinspection report),

    b) any potential dangers (departures that wouldwarrant a code 2 recommendation according toBest Practice Guide Number 4 in a periodicinspection report), or

    c) any lighting circuits that do not have a circuitprotective conductor (cpc).

    page 6 The Electrical Safety Council

  • 9. Action following risk assessment

    9.1. If any immediately dangerous conditions areindicated (see paragraph 8.4(a)), the consumer unitshould not be replaced unless the departures arecorrected or the defective circuits are leftdisconnected from the replacement consumer unit.

    9.2. If the risk assessment indicates that there are noimmediately dangerous conditions (see paragraph8.4(a)), the replacement of the consumer unit mayproceed.

    9.3. Any potential danger identified (see paragraph8.4(b)) should be explained to the customer, andwritten confirmation given. A strong writtenrecommendation should be made to the customerthat remedial action is taken to correct anypotentially dangerous conditions without delay.

    9.4. If there are any lighting circuits that do not have acpc (paragraph 8.4(c) refers), the recommendationsof Best Practice Guide Number 1 should be followed,as well as those of this guide. In some cases thismay mean that the consumer unit should not bereplaced unless the certain works, recommended inBest Practice Guide Number 1, are carried out.Alternatively the circuits should not be connected tothe replacement consumer unit.

    10. Inspection, testing and certification

    10.1. The alteration or addition itself (the installation ofthe replacement consumer unit and any other newwork, such as additional final circuits) should beverified fully in accordance with the requirements ofSection 610 of BS 7671 and an ElectricalInstallation Certificate in accordance with BS 7671,detailing the work, should be given by the installer tothe customer.

    10.2. In addition, as a minimum, the following testsshould be carried out to the existing circuitsconnected to the replacement consumer unit.

    A continuity test of the protective conductor ofeach circuit, to the point or accessory electricallyfurthest from the consumer unit and to eachaccessible exposed-conductive-part.

    A continuity test of all ring final circuitconductors.

    A measurement of the combined insulationresistance of all the circuits. The measurementneed only be made between the line and neutralconductors connected together and theprotective conductor connected to the earthingarrangement.

    A test of the polarity and a test to establish theearth fault loop impedance (Zs), at eachaccessible socket-outlet and at least one point oraccessory in every other circuit, preferably thepoint or accessory electrically furthest from theconsumer unit.

    Note: Testing of each RCD using both a test instrument

    and the integral test facility in the device should have

    been carried out under Section 10.1 of this Guide.

    10.3. The Electrical Installation Certificate should identifyin the comments section any potential dangers thatexist with the reconnected circuits (code 2 items, seeparagraph 8.4(b)) and other defects that exist in thereconnected circuits, and that the installation of theconsumer unit has been carried out in accordancewith the recommendations in this guide.

    10.4. If a full periodic inspection and test of theinstallation has not been carried out as part of thework, consideration should be given by the installerto stating this on the certificate with arecommendation this should be done.

    page 7The Electrical Safety Council

  • 11. Procedure

    11.1. The procedure described in this Best Practice Guide is summarised in the flowchart on page 9.

    12. References to other Best Practice Guides

    12.1. This Best Practice Guide makes reference to thefollowing Best Practice Guides, which may bedownloaded from the websites of some of thecontributing organisations:

    Best Practice Guide No 1 Replacing aconsumer unit in domestic premises wherelighting circuits have no protective conductor.

    Best Practice Guide No 2 Guidance onmanagement of electrical safety and safeisolation procedures for low voltage installations.

    Best Practice Guide No 4 Periodic inspectionreporting recommendation codes for domesticand similar installations.

    page 8 The Electrical Safety Council

  • No

    Enquiry for consumerunit change

    7Reason for change

    7.2Planned

    7.3Distress

    6.2 Do not changeconsumer unit

    6.2 Customer agreesto upgrade?

    6.2 Customer agreesto upgrade?

    9.1 Customer agreesto remedial work?

    9.1Remedial work

    9.3 Recommendurgent remedial work

    Upgrade

    6 Main earthing,bonding & tails

    adequate ?

    6 Main earthing,bonding & tails

    adequate ?

    7.3.2 Explain tocustomer

    Change consumer unit(do not connect any

    immediately dangerous circuits)

    7.3.2 Return to installation to doany further works

    10 Finaliseinspection & testing

    10 Finaliseinspection & testing

    9.4 Customer agreesto remedial work?

    9.4 Any lightingcircuits with no CPC?

    9.4 Apply BPG1also

    9.4 Does BPG1recommend any

    work before consumerunit change?

    10 Issue EIC includingrecommendations

    10 Issue EIC includingrecommendations

    7.3.2 Customeragrees to PIR?

    7.2.1PIR

    7.2.3 Any immediateor potential dangers or

    unwanted RCD trip cause?

    7.2.2Pre-work survey

    7.2.4Remedial work

    9.4Remedial work

    7.2.5 & Section 8Risk assessment

    9.1 Any potentialdangers?

    Do not changeconsumer unit

    Changeconsumer unit

    Customer agrees toremedial work?

    Yes

    Yes

    YesYes

    Yes

    Yes

    Yes

    YesYes

    Yes

    Yes Yes

    Yes Yes

    No

    No

    No

    No

    No

    9.1 Any immediatedangers?

    NoNoNoNo

    Yes No

    No

    No

    Domestic consumer unitreplacement procedure

    page 9The Electrical Safety Council

    Note: The numbers in the boxes of this flowchart refer to the numbers of the sections in this guide

  • The latest versions of all the BestPracticeGuidesare avalable to download from www.esc.org.uk