Bosch Climate 5000 Water Source Heat Pump · PDF fileIntroduction to Bosch Thermotechnology...
Transcript of Bosch Climate 5000 Water Source Heat Pump · PDF fileIntroduction to Bosch Thermotechnology...
Introduction to Bosch Thermotechnology
Achieve independence, save energy and protect the environ-
ment - for a secure future
Bosch Thermotechnik GmbH is a leading supplier of resource-efficient heating products and hot water solutions in Europe. In fiscal 2013, the company generated sales of 3.1 billion Euros (68% outside Germany) and employed approximately 13,500 people. Bosch Thermotechnology has strong international and regional brands and manufactures a diversified product range in 21 plants in 11 European, North American and Asian countries. In 2013, Bosch Thermotechnology invested 129 million Euros in research and development. Intelligent networks and local systems for heating, ventilation, air-conditioning and electricity generation are fundamental technologies for the future building standard, which will generate more energy than is used.
In Southeast Asia, Bosch Thermotechnology has been established in the middle of 2011 to provide a closer support to its local customers as well as to further extend its market position. The regional headquarter office is based in Singapore, overseeing business development in the Southeast Asia region. Nowadays, Bosch Thermotechnology has successfully established
sales offices in Indonesia, Malaysia, Philippines, Singapore, Thailand and Vietnam with a representative office in Myanmar.
Bosch Thermotechnology is mostly known in Southeast Asia for its large-scale, commercial and industrial boiler systems. In 2014, the product portfolio has been extended to cooling solutions which are energy efficient, eco-friendly and high quality products for commercial and industrial applications which help our customers to increase comfort and reduce energy cost.
A comprehensive range of renewable heat pumps, chillers, fan coil units and air handling units meets almost all kinds of requirements from buildings like office, hospital, hotel, shopping mall or industrial plants.
Bosch Climate 5000 Water Source Heat Pump is a product engineered with most advanced technology which brings you great energy saving, and an ultimate quiet and comfortable indoor environment.
Higher energy prices and the increase in environmental pollution compel us to change our heating and cooling behavior and look at new forms of energy. Our future energy usage must include renewable energies for heating and cooling. Heat pumps are an excellent alternative when it comes to making efficient use of these free sources of energy. Renewable energies make you independent from oil/gas prices, protect the environment and your bank account.
Natural heat: 100% efficient, and up to 80% free of chargeAs you know, heat is our element. But did you know that heat is in nearly every element? Nature is an excellent supplier of energy and stores the heat of the sun, for instance, in the ground and surface water. With Bosch heat pumps, you simply draw this energy into your own home and, what’s more, it is practically free, up to 80% of the required heating energy is given to us by nature; you can see it in a significant reduction in your utility costs.
2 | Water Source Heat Pump
I provide the climate. You feel the comfort!
Bosch Water Source Heat Pumps
The energy of the future Everything speaks in favour of Bosch heat pumps. Not only do they have reduced running costs, but also reduced environmental pollution effects, and as they produce zero emissions, so the choice is simple.
Heat pump principleWater source heat pump is a kind of air conditioner. To explain how a heat pump works, the best place to start is the air conditioner in your house. Air conditioners remove heat from inside the room and transfer it to the outside. Heat pumps in heating mode essentially work in the same way- only in reverse. However, what is crucial here is how the heat is transported. This task
is performed by a refrigerant- a fluid with a particularly low boiling point. The refrigerant absorbs the ambient heat from the ground water, for instance, and in doing so, it evaporates. A compressor compresses this vapor and raises the pressure. This increases the temperature further until it reaches the desired level, thus producing a flow of heat. The vapor transfers the heat to indoor air and then reverts to a fluid. An expansion valve reduces the pressure to its original level – the fluid cools down and the cycle starts again: heat can be absorbed and transferred to the heating system. That is how simple heating can be. Incidentally, the heat pump does all this without producing any emissions.
Water Source Heat Pump | 3
Heat is our elementIf you are banking on renewable energy for heating and cooling, you now have a good reason to think you’re right. Using this technology you can save a lot of money and protect the environment from harmful emissions.
Water source heat pump (WSHP)WSHPs are heat pumps which use water as source of heat for heating and cooling. They are always used in two kinds of heat pump systems-geothermal systems and water loop systems.
Geothermal heat pump systemGeothermal heat pump system uses the natural heat storage ability of the earth, ground water or surface water as main source for heating and cooling. It consists of water source heat pumps, ground heat exchanger, indoor air conditioning system and control systems. Typical designs for geothermal heat pumps include ground loop system (vertical loops in boreholes & horizontal loops in trenches), ground water system and surface water system. Geothermal heat pump system is one of the most energy efficient and environmentally friendly technologies available today and it’s the smart choice for saving you money and preserving our environment.
Water loop heat pump systemWater loop HP system is a decentralized system using a boiler/cooling tower as a backup heat source. The heat surplus in interior areas of building can make up heat loss in outer areas of building in this system, which leads to energy saving. Meanwhile, owners can control units of individual requirements and charge separately which equates and is convenient.
Vertical Ground Loop System Horizontal Ground Loop System
Ground-Water Heat Pump System Surface-Water Heat Pump System
Does heat come from the ground or from the water?
Bosch has the right answer for you
4 | Water Source Heat Pump
Bosch Water - Source
Heat Pump
Num
erousU
nit Options
Out
stan
ding
Tech
nolo
gy
High Perfor-
mance
Wide Prod-
uct Range
Ecological
Secure &
Convenient
40 Years Experience
Flexible
Econ
omic
al
Hig
h Q
ualit
y
No matter what your needs, Bosch has an HVAC unit
designed for you!
Expert Experience: Production since 1969, 40 years of heat pump experience.
Flexible: Provide heating, cooling and domestic hot water.
Economical: Higher efficiency which can save 40% to 60% operating cost compared with air-source heat pumps.
Ecological: Environmentally friendly refrigerant R410a, CFC free.
High Quality: Use of components from renowned brands.
Wide Product Range: Multiple configurations designed for different buildings and systems.
High Performance: High efficiency and reliable operation
Quality starts with Bosch's good design. Secure & Convenient: Intelligent unit protection
features ensure easy operation, greater comfort and reliability.
Tailor-made solutions: Numerous unit options satisfy your particular demand.
“I get twice the benefit from my new heat pump because it doesn’t just provide heat on cold days, when it gets really hot it can cool my home as well.”
Water Source Heat Pump | 5
Be in harmony with nature:
Bosch WSHP
Are you looking for a device that provides both heating and cooling for your home? Do you want a heating facility with highest efficiency? Or are you looking for a heat source for your radiant floors? You have found the right solution to these problems because Bosch water source heat pumps are what you are looking for - all you have to do is to choose.
Technical Characteristics: High efficiency
Optimized refrigerant system design plus most advanced scroll compressor and coaxial heat exchanger
Environmentally friendly refrigerant R410A, CFC free Modular design
Making it easy to enlarge capacity if needed Intelligent Self-diagnostic function Space saving and easy transportation
Occupies less space and can be moved and transported easily through doorways, elevators or hallways
Flexible Various unit sizes allow for installation in almost all
kinds of buildings Multiple protections
Overload protection, High/low voltage protection, Water shortage protection, Anti-freezing protection etc, make the unit more reliable
Nomenclature Bosch Climate 5000 GL S H - 35 D 3 A
Product Sequence: A Power Supply 1=220~230V/50Hz/1 Phase 3=380~400V/50Hz/3 Phase
Refrigerant:D:R410a
H:heat pump
Compressor: S:Scroll
Energy Source: WL:Water loop GW:Ground water GL:Ground loop
6 | Water Source Heat Pump
Graphic Advantage Detail
Robust structure .High strength aluminum frame inside.Stable groove+Strong connections= Professional connections
Efficient compressor .Lower pressure drop.High reliability, compliance, precise.100% volumetric efficiency.Perfect low temperature performance.Axial flexible seal.Radial flexible seal
Efficient coaxial heat exchanger
.High efficiency
.Excellent corrosion resistance
.Outstanding Anti-freezing capability
.Clean
Low noise level .Top case insulation material.Sound absorption solution.Sound insulation solution .Damping solution
User-friendly control-ler
.LED display
.Touch-sensitive button
.Intelligent self-diagnostic function
Features
Water Source Heat Pump | 7
Operating range
Explosive View
1 Compressor2 Evaporator3 Condenser4 Dry filter5 Thermostatic expansion valve6 Controller7 Controll box8 4-way valve
5
34
67
8
1
2
5
Heating
Cooling
0, 50
-5, 42
55
50
45
40
35
30
20
16
13
10
-5 5 15 25
15 20 30 40
Load
wat
er in
let/
°CLo
ad w
ater
inle
t/°C
Source water inlet/°C
Source water inlet/°C
8 | Water Source Heat Pump
08D1A 12D3A 16D3A 20D3A 25D3A
Water Loop Condition
Cooling Capacity kW 5.8 9.3 12.4 13.3 22.3
Cooling Power Input kW 1.40 2.42 3.16 3.40 5.80
EER - 4.14 3.84 3.92 3.90 3.84
Heating Capacity kW 8.0 11.7 16.3 19.6 32.9
Heating Power Input kW 1.80 2.97 3.90 4.20 7.80
COP - 4.44 3.95 4.18 4.67 4.21
Load Water Flow m3/h 1.0 1.6 2.2 2.3 4.0
LoadWaterPressureDrop kPa 25.0 25.4 21.0 20.0 21.0
Source Water Flow m3/h 1.4 1.9 2.7 2.9 4.7
SourceWaterPressureDrop kPa 14.0 39.4 12.4 25.0 23.0
Ground Water Condition
Cooling Capacity kW 6.6 10.1 13.5 14.5 24.4
Cooling Power Input kW 1.17 2.10 2.75 2.83 5.00
EER - 5.63 4.81 4.89 5.12 4.88
Heating Capacity kW 7.0 10.5 13.7 16.2 27.7
Heating Power Input kW 1.76 2.91 3.81 4.20 7.30
COP - 3.97 3.61 3.58 3.86 3.79
Load Water Flow m3/h 1.2 1.7 2.3 2.6 4.1
LoadWaterPressureDrop kPa 20.0 29.5 13.0 14.0 15.0
Source Water Flow m3/h 0.7 0.9 1.3 1.5 2.4
SourceWaterPressureDrop kPa 15.0 12.9 8.1 9.0 6.0
Ground Loop Condition
Cooling Capacity kW 6.3 9.9 12.9 13.7 23.7
Cooling Power Input kW 1.25 2.20 2.84 3.00 5.23
EER - 5.01 4.49 4.53 4.56 4.53
Heating Capacity kW 6.8 10.1 13.5 15.8 27.0
Heating Power Input kW 1.77 2.88 3.79 4.24 7.25
COP - 3.85 3.52 3.57 3.73 3.72
Load Water Flow m3/h 1.1 1.7 2.2 2.3 4.1
LoadWaterPressureDrop kPa 28.0 29.1 12.9 13.0 14.0
Source Water Flow m3/h 1.4 2.0 3.2 3.1 4.9
SourceWaterPressureDrop kPa 11.0 43.3 20.7 34.0 25.0
General
Power supply V/Ph/Hz 220/1/50 380/3/50
Refrigerant - R410A
Refrigerant Charge kg 1.6 1.7 1.8 2.5 4.7
Compressor Type Scroll Compressor
Compressor Qty unit 1 1 1 1 1
Compressor RLA - 12.8 5.8 7.3 10.7 18.6
Compressor LRA - 54 49 58 67 100
Load Water Pipe FPT Φ(mm) DN20 DN25 DN25 DN25 DN32
Source Water Pipe FPT Φ(mm) DN20 DN25 DN25 DN25 DN32
NetDimension Width mm 826 826 826 826 1168
Depth mm 692 692 692 692 711
Height mm 648 648 648 648 953
NetWeight kg 100 110 124 140 241
NoiseLevel dB(A) 50 51 51 52 53
Specification
Water Source Heat Pump | 9
Note:
- Cooling: Load Water inlet/outlet: 12oC/7oC; Source water inlet/outlet: 30oC/35oC(WaterLoop),18oC/29oC(GroundWater),
25oC/30oC(GroundLoop).
- Heating: Load Water inlet/outlet: 40oC/45oC; Source water inlet: 20oC/(WaterLoop),15oC(GroundWater),10oC(GroundLoop).
samesourcewaterflowasincoolingmode.
- RLA: Rated load current; LRA: Locked Rotor current.
- Glycol will be needed when source water inlet below 3oC,Glycolconcentration:10%~20%;
- Productspecificationmightbechangedwithoutpriornoticeduetoproductengineeringevolution.plsalwaysrefertothenameplate
of equipment.
30D3A 35D3A 45D3A 67D3A 70D3A 100D3A
Water Loop Condition
Cooling Capacity kW 27.7 33.2 41.3 53.8 64.4 80.1
Cooling Power Input kW 6.39 7.55 10.04 12.52 14.79 19.67
EER - 4.34 4.40 4.11 4.30 4.35 4.07
Heating Capacity kW 37.3 44.0 55.9 72.4 85.4 108.4
Heating Power Input kW 8.10 9.60 12.37 15.87 18.81 24.24
COP - 4.60 4.58 4.52 4.56 4.54 4.47
Load Water Flow m3/h 4.7 5.4 7.2 9.2 11.1 13.8
LoadWaterPressureDrop kPa 39.3 30.4 33.3 39.5 39.2 39.6
Source Water Flow m3/h 5.5 6.4 8 10.7 12.4 15.5
SourceWaterPressureDrop kPa 48.8 27.6 28.1 57.7 60.1 71.2
Ground Water Condition
Cooling Capacity kW 30.3 35.0 46.1 58.7 67.9 89.4
Cooling Power Input kW 5.55 6.52 8.74 10.87 12.78 17.13
EER - 5.45 5.36 5.27 5.40 5.31 5.22
Heating Capacity kW 31.2 35.5 46.7 60.5 68.9 90.6
Heating Power Input kW 8.06 9.45 11.88 15.48 18.52 23.28
COP - 3.87 3.76 3.93 3.91 3.72 3.89
Load Water Flow m3/h 5.0 6.2 7.8 10.1 11.7 15.4
LoadWaterPressureDrop kPa 44 37.5 39.6 50.3 48.3 48.3
Source Water Flow m3/h 2.8 3.1 4 5.4 6 7.8
SourceWaterPressureDrop kPa 8 6.0 5.5 16.5 15.2 15.3
Ground Loop Condition
Cooling Capacity kW 29.0 33.3 43.1 56.2 64.6 83.6
Cooling Power Input kW 5.73 6.74 9.08 11.76 13.38 18.04
EER - 5.06 5.06 4.75 4.78 4.83 4.63
Heating Capacity kW 31.5 35.4 46.0 61.1 68.7 89.2
Heating Power Input kW 8.03 9.44 11.88 16.22 18.53 24.68
COP - 3.93 3.75 3.87 3.77 3.71 3.62
Load Water Flow m3/h 5.0 5.7 7.1 9.7 11.1 14.4
LoadWaterPressureDrop kPa 45 34.7 37.1 47.2 39.7 41.5
Source Water Flow m3/h 5.5 6.6 8.4 11.5 12.8 16.3
SourceWaterPressureDrop kPa 40.8 29.0 31.6 62.3 61.7 71.6
General
Power supply V/Ph/Hz 380/3/50
Refrigerant - R410A
Refrigerant Charge kg 3.6 6.0 5.9 7.0 9.5 13.0
Compressor Type Scroll Compressor
Compressor Qty unit 1 1 1 2 2 2
Compressor RLA - 20 20.7 29.3 40 41.4 58.6
Compressor LRA - 110 110 174 220 220 348
Load Water Pipe FPT Φ(mm) DN32 DN40 DN40 DN50 DN50 DN50
Source Water Pipe FPT Φ(mm) DN32 DN40 DN40 DN50 DN50 DN50
NetDimension Width mm 1168 1168 1168 1168 1168 1168
Depth mm 711 711 711 711 711 711
Height mm 953 953 953 1778 1778 1778
NetWeight kg 252 285 315 484 560 620
NoiseLevel dB(A) 53 54 54 55 56 61
10 | Water Source Heat Pump
Coefficient table
Source water inlet
20 25 30 35 40
Chilled water outlet
Cooling capacity
Power input
Cooling capacity
Power input
Cooling capacity
Power input
Cooling capacity
Power input
Cooling capacity
Power input
5 1.039 0.775 0.984 0.884 0.930 1.003 0.872 1.138 0.810 1.302
7 1.116 0.768 1.054 0.881 1.000 1.000 0.938 1.135 0.872 1.293
10 1.233 0.765 1.171 0.878 1.105 0.997 1.039 1.129 0.969 1.280
12 1.318 0.762 1.248 0.877 1.178 0.996 1.112 1.125 1.039 1.277
15 1.457 0.759 1.380 0.876 1.302 0.995 1.225 1.125 1.147 1.270
Source water inlet
15 18 20 22 25
Chilled water outlet
Cooling capacity
Power input
Cooling capacity
Power input
Cooling capacity
Power input
Cooling capacity
Power input
Cooling capacity
Power input
5 0.948 0.929 0.920 1.007 0.899 1.060 0.864 1.074 0.843 1.208
7 1.031 0.926 1.000 1.000 0.976 1.057 0.927 1.071 0.920 1.201
10 1.147 0.915 1.112 0.993 1.084 1.046 1.024 1.067 1.021 1.191
12 1.224 0.908 1.189 0.986 1.161 1.039 1.098 1.067 1.098 1.187
15 1.357 0.898 1.315 0.975 1.287 1.028 1.210 1.067 1.210 1.177
Source water inlet
15 18 20 22 25
Chilled water outlet
Cooling capacity
Power input
Cooling capacity
Power input
Cooling capacity
Power input
Cooling capacity
Power input
Cooling capacity
Power input
5 0.951 0.929 0.923 1.007 0.867 1.148 0.811 1.307 0.748 1.491
7 1.031 0.926 1.000 1.000 0.941 1.141 0.881 1.300 0.818 1.481
10 1.147 0.915 1.112 0.993 1.045 1.131 0.983 1.290 0.916 1.466
12 1.224 0.908 1.189 0.986 1.119 1.124 1.056 1.283 0.983 1.456
15 1.357 0.898 1.315 0.975 1.245 1.117 1.168 1.272 1.091 1.445
Cooling Water Loop (oC)
Cooling Ground Water (oC)
Cooling Ground Loop (oC)
Water Source Heat Pump | 11
Source water inlet
15 17 18 20 22
Hot water outlet
Heating capacity
Power input
Heating capacity
Power input
Heating capacity
Power input
Heating capacity
Power input
Heating capacity
Power input
35 0.913 0.751 0.969 0.745 0.997 0.743 1.056 0.737 1.117 0.732
40 0.906 0.839 0.963 0.839 0.991 0.836 1.053 0.836 1.120 0.836
42 0.893 0.884 0.951 0.884 0.979 0.881 1.038 0.881 1.101 0.879
45 0.876 0.955 0.931 0.955 0.958 0.953 1.016 0.950 1.078 0.950
47 0.865 1.008 0.918 1.006 0.944 1.003 1.000 1.000 1.061 0.997
50 0.849 1.090 0.900 1.088 0.926 1.084 0.979 1.082 1.038 1.079
55 0.822 1.245 0.868 1.241 0.893 1.237 0.943 1.232 0.998 1.227
Source water inlet
12 15 18 22 25
Hot water outlet
Heating capacity
Power input
Heating capacity
Power input
Heating capacity
Power input
Heating capacity
Power input
Heating capacity
Power input
35 0.978 0.782 1.066 0.774 1.162 0.766 1.300 0.755 1.395 0.747
40 0.944 0.887 1.038 0.880 1.180 0.871 1.300 0.863 1.387 0.856
42 0.925 0.935 1.015 0.926 1.147 0.916 1.261 0.909 1.367 0.902
45 0.917 1.012 1.000 1.000 1.128 0.988 1.241 0.981 1.342 0.974
47 0.908 1.065 0.992 1.053 1.117 1.041 1.226 1.031 1.323 1.024
50 0.899 1.151 0.979 1.137 1.100 1.122 1.202 1.110 1.300 1.103
55 0.880 1.307 0.957 1.295 1.069 1.271 1.165 1.259 1.255 1.247
Source water inlet
-3 0 3 6 10
Hot water outlet
Heating capacity
Power input
Heating capacity
Power input
Heating capacity
Power input
Heating capacity
Power input
Heating capacity
Power input
35 0.726 0.803 0.796 0.797 0.870 0.789 0.952 0.784 1.066 0.774
40 0.709 0.910 0.776 0.900 0.848 0.900 0.925 0.890 1.033 0.880
42 0.703 0.960 0.768 0.950 0.838 0.940 0.913 0.940 1.021 0.930
45 0.692 1.030 0.757 1.020 0.826 1.020 0.897 1.010 1.000 1.000
47 - - 0.750 1.080 0.820 1.070 0.890 1.060 0.990 1.050
50 - - - - 0.800 1.160 0.870 1.150 0.970 1.140
Heating Water Loop (oC)
Heating Ground Water (oC)
Heating Ground Loop (oC)
12 | Water Source Heat Pump
Dimension
Model Dimension (mm)
A B C D E F G H I Water pipe
GW/GL/WLSH-08D1A 61.5 45 390 93.5 106.5 652 692 634 648 DN20
GW/GL/WLSH-12D3A 58.5 35 384 100.5 93.5 652 692 634 648 DN25
GW/GL/WLSH-16D3A 94.5 35 305 97.5 129.5 652 692 634 648 DN25
GW/GL/WLSH-20D3A 89 34 352 65 123 652 692 634 648 DN25
Model Dimension (mm)
A B C D E F G H I J K Water pipe
GW/GL/WLSH-25D3A 1168 711 953 208 223.5 265 210 271.5 299 217 264 DN32
GW/GL/WLSH-30D3A 1168 711 953 208 202 231 287 243 367 196 282 DN32
GW/GL/WLSH-35D3A 1168 711 953 173 212 217 248 223 301 171 264 DN40
GW/GL/WLSH-45D3A 1168 711 953 174 206 219 290 219 292 174 199 DN40
GF
610
UNIT LEFT UNIT FRONT
ElECTRICALCONNECTIONS
OUT OUT
H
LOAD
IN IN
SOURCE
B
C
UNIT REAR UNIT LEFT
SOURCE OUT
SOURCE IN
LOAD OUT
LOAD IN
ElECTRICALCONNECTIONS
Water Source Heat Pump | 13
Model Dimension (mm)
A B C D E F G H Water pipe
GW/GL/WLSH-67D3A 655.5 163.5 1040 288.5 739.5 276.5 1124 151.5 DN50
GW/GL/WLSH-70D3A 660.5 125.5 1101 263.5 695.5 257 1134 118.5 DN50
GW/GL/WLSH-100D3A 623 130 1087 265 707 265.5 1171 130.5 DN50
UNIT REAR UNIT LEFT
ELECTRICALCONNECTIONSSOURCE OUT
SOURCE IN
LOAD OUT
LOAD IN
14 | Water Source Heat Pump
RLA: Rated load current; LRA: Locked Rotor current.
Model Power input Compressor Max. fuse current (A)
RLA LRA
GW/GL/WLSH-08D1A 220V/1Ph/50Hz 12.8 54 16
GW/GL/WLSH-12D3A 380V/3Ph/50Hz 5.8 49 10
GW/GL/WLSH-16D3A 380V/3Ph/50Hz 7.3 58 10
GW/GL/WLSH-20D3A 380V/3Ph/50Hz 10.7 67 16
GW/GL/WLSH-25D3A 380V/3Ph/50Hz 18.6 100 25
GW/GL/WLSH-30D3A 380V/3Ph/50Hz 20 110 32
GW/GL/WLSH-35D3A 380V/3Ph/50Hz 20.7 110 32
GW/GL/WLSH-45D3A 380V/3Ph/50Hz 29.3 174 40
GW/GL/WLSH-67D3A 380V/3Ph/50Hz 40 220 63
GW/GL/WLSH-70D3A 380V/3Ph/50Hz 41.4 220 63
GW/GL/WLSH-100D3A 380V/3Ph/50Hz 58.6 348 80
Electrical parameters
Water Source Heat Pump | 15
Bos
ch r
eser
ves
the
righ
t to
cha
nge
any
spec
ifica
tion
, des
ign
and
info
rmat
ion
with
out
any
prio
r no
tice
for
furt
her
impr
ovem
ent
on q
ualit
y an
d pe
rfor
man
ce.
Bosch Thermotechnology in Southeast Asia
Singapore, Cambodia, Lao PDR, MyanmarRobert Bosch (SEA) Pte. Ltd.Thermotechnology Division11 Bishan Street 21, #04-05Singapore 573943Tel +65 6258 5511 Fax +65 6571 2970Email: [email protected]
Indonesia (Jakarta): Indonesia (Surabaya) PT. Robert Bosch PT. Robert BoschArkadia Office Park Tower F Plaza BRI, Suite 1203 7th Floor, Suite 703-705 Jl. Jend. Basuki Rahmat No. 122Jl. TB. Simatupang Kav.88, Surabaya 60271Jakarta 12520 IndonesiaIndonesia Tel: + 62 31 5356262Tel: +62 21 3005 5800 Fax : +62 31 5356266Fax: +62 213005 5801 Email: [email protected]: [email protected] Malaysia:Robert Bosch Sdn. BhdThermotechnology DivisionNo. 8A, Jalan 13/6,46200 Petaling Jaya, Selangor,MalaysiaTel. + 60 (3) 7966 3000Fax + 60 (3) 7958 8833Email: [email protected]
Myanmar:Representative Office of Robert Bosch (SEA) Pte. Ltd.Thermotechnology DivisionNo. 60B, Kabar Ayer Pagoda RoadMayangone TownshipYangon, MyanmarTel. + 95 1 663616Fax + 95 1 663616Email: [email protected]
Philippines:Robert Bosch Inc.Thermotechnology Division28 Floor, Fort Legend Tower3rd Ave. Cor 31st StFort Bonifacio Global CityMetro Manila 1634PhilippinesTel. +63 2 870 3888 Fax +63 2 870 3830 Email: [email protected]
Thailand:Robert Bosch LimitedThermotechnology Division287 Liberty square building, 11th floorSilom Road, BangrakBangkok 10500ThailandTel. + 66 2 639 3111Fax + 66 2 238 4783Email: [email protected]
Vietnam (Ho Chi Minh): Vietnam (Hanoi): Robert Bosch Vietnam Co., Ltd. Robert Bosch Vietnam Co., Ltd.Thermotechnology Division Thermotechnology Division194 Golden Building Unit 03C, 2nd floor, International Center473 Dien Bien Phu str. – W.25 – 17 Ngo Quyen St., Hoan Kiem Dist.,Binh Thanh Dist. - Ho Chi Minh City Ha NoiVietnam VietnamTel +84 (8) 6258 3690 Tel +84 (4) 3939 3119Fax +84 (8) 6258 3692 Fax +84 (4) 3936 2899Email: [email protected] Email: [email protected] For more information:www.bosch-industrial.com