Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way...

28
Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide

Transcript of Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way...

Page 1: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Bosch 80% AFUE Gas Furnace BGS80 Model4-Way Multipoise Category I Fan-Assisted Furnace

Troubleshooting Guide

Page 2: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

2 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide

09.2018 | BTC 770302101 AData subject to change

Page 3: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 3

BTC 770302101 A | 09.2018 Data subject to change

Table of Contents

1 Key to Symbols and Safety Instructions 4

1.1 Key to Symbols 4

1.2 Safety 4

2 Troubleshooting 6

2.1 Electrostatic Discharge (ESD) Precautions 6

2.2 Resetting From Lockout 6

3 Error Flash Codes 7

3.1 No Flash and No Fan (System Does Not Start Normally) 7

3.2 1 Flash (System Lockout - No Flame) 10

3.3 2 Flashes (Pressure Switch Stuck Closed) 12

3.4 3 Flashes (Pressure Switch Stuck Open) 14

3.5 4 Flashes (Open Limit Switch - High Temperature Limit Control) 16

3.6 5 Flashes (Open Rollout Limit Switch) 19

3.7 6 Flashes (Incorrect Polarity of L1/L2) 21

3.8 7 Flashes (Low Flame) 22

3.9 Rapid/Continuous Flashes (Flame Sensor Shorted) 24

3.10 Steady On Light (Bad Control Board) 24

Appendix A - Sequence of Operation 25

Page 4: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

4 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide

09.2018 | BTC 770302101 AData subject to change

1 Key to Symbols and Safety Instructions

1.1 Key to Symbols

Warnings

   Warnings in this document are identifi ed by a warning triangle printed against a grey background.Keywords at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.

The following keywords are defi ned and can be used in this document:

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION indicates a hazardous situation which, if not avoided, could result in minor to moderate injury.

NOTICE is used to address practices not related to personal injury.

Important information

 This symbol indicates important information wherethere is no risk to people or property.

1.2 Safety

Please read all instruction in the manual and retain all manuals for future reference.

WARNING:

Untrained personnel (homeowners) may only clean and replace filters and replace fuses as required by basic maintenance. All other operations, including installation, repair, and service must be performed by a qualified installer, service agency, or the gas supplier.

WARNING: FIRE OR EXPLOSION HAZARD

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS: — Do not try to light any appliance. — Do not touch any electrical switch; do not use any

phone in your building. — Leave the building immediately. — Immediately call your gas supplier from a

neighbor’s phone. Follow the gas supplier’s instructions.

— If you cannot reach your gas supplier, call the fire department.

Installation and service must be performed by a qualifi ed installer, service agency, or the gas supplier.

WARNING:

Do not use this furnace if any part has been under water. A fl ood-damaged furnace is extremely dangerous. Attempts to use the furnace can result in fi re or explosion. A qualifi ed service agent must inspect the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet, or the furnace if deemed necessary.

WARNING: FIRE OR EXPLOSION HAZARD

The furnace is designed and approved for use with Natural Gas and (LP) Propane Gas ONLY.

DO NOT BURN ANY LIQUID FUEL OR SOLID FUEL IN THIS FURNACE.

Burning any unapproved fuel will result in damage to the furnace's heat exchanger, which could result in Fire, Personal Injury, and/or Property Damage.

Page 5: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 5

BTC 770302101 A | 09.2018 Data subject to change

WARNING: FOLLOW ALL SAFETY CODES

Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes as well as the current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and the National Electrical Code (NEC) NFPA 70.

WARNING: FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in dangerous operation, serious injury, death, or property damage. Improper installation, adjustment,alteration, maintenance, or use could cause carbon

monoxide poisoning, explosion, fire, electrical shock,or other conditions which may cause personal injury

or property damage. Consult a qualified service agency, local gas supplier, or your distributor for information or assistance.

WARNING:

Always install furnace to operate within the furnace's intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in Section 11 of the Installation, Operation, and Maintenance Manual, or the furnace rating plate.

WARNING: FIRE HAZARD

The furnaces must be kept free and clear of insulating materials. Inspect surrounding area to ensure insulation material is at a safe distance when installing furnaces or adding insulation materials. Insulation materials may be combustible.Maintain a 1 in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements.

These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, field supplied floor base MUST be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on industry standard Coil Assembly matching correct furnace width.

CAUTION: FURNACE RELIABILITY HAZARD

Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure. Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.

CAUTION: CUT HAZARD

Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.

WARNING: FIRE, EXPLOSION

Check entire gas assembly for leaks after lighting this appliance.

Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the Installation, Operation, and Maintenance Manual.

WARNING: FIRE, EXPLOSION

See instructions for lighting/shutdown operation (as shown on a sticker directly on the inside of the furnace panel). Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.

WARNING:

Furnace operation requires air for combustion and ventilation. Do not block or obstruct air openings on furnace or spacing around furnace required for supplying sufficient combustion air and ventilation.

WARNING:

This product can expose you to chemicals including Lead and Lead components, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.

Page 6: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

6 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide

09.2018 | BTC 770302101 AData subject to change

2 Troubleshooting

Refer to the troubleshooting charts and associated fi gures on the following pages for assistance in determining the source of unit operational problems. The red diagnostic LED blinks to assist in troubleshooting the unit. The number of blinks refers to a specifi c code.

2.1 Electrostatic Discharge (ESD) Precautions

NOTICE:

Discharge body's static electricity before touching unit. An electrostatic discharge can adversely aff ect electrical components.

Use the following precautions during furnace installation and servicing to protect the integrated control module from damage. By putting the furnace control and the person at the same electrostatic potential these steps will help avoid exposing the integrated control module to electrostatic discharge. This procedure is applicable to both installed and uninstalled (ungrounded) furnaces.

1. Disconnect all power to the furnace. Do not touch the integrated control module or any wire connected to the control prior to discharging your body's electrostatic charge to ground.

2. Firmly touch a clean unpainted metal surface of the furnace away from the control. Any tools held in a person's hand during grounding will be discharged.

3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e. do not move or shuffl e your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.

4. Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a furnace. Return any old or new controls to their containers before touching any ungrounded object.

2.2 Resetting From Lockout

Furnace lockout results when a furnace is unable to achieve ignition after three attempts. It is characterized by a non-functioning furnace and a one fl ash diagnostic LED code from the red LED. If the furnace is in "lockout" it will (or can be) reset in any of the following ways.

1. Automatic reset. The integrated control module will automatically reset itself and attempt to resume normal operations following a one hour lockout period.

2. Manual power interruption. Interrupt 115 volt power to the furnace for 1 - 20 seconds.

3. Manual thermostat cycle. Lower the thermostat so that there is no longer a call for heat for 1 - 20 sec.

WARNING: FIRE,EXPLOSION AND ASPHYXIATION HAZARD

Installation and service must be performed by a qualifi ed service agency or the gas supplier.

Page 7: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 7

BTC 770302101 A | 09.2018 Data subject to change

3 Error Flash Codes

3.1 No Flash and No Fan (System Does Not Start Normally)

Troubleshooting Chart

Start

Are there anyloose wires or wrong

connections?

Correctwiring

according to wiring diagram

Yes

No

Is there power to the unit?

See Figure 1No

Is the door switch working properly?

See Figure 2No

Replace the door switch

Is the transformer

working properly?See Figure 3

Is the blower access door closed or fixed properly?

No

Ensure the blower access door is closed

properly

Yes Yes

Check the incoming power

supply at connection box

No

Is the PCB Board

sending 18-31V signals?See Figure 4

No

Replace the transformer

Is there a blown fuse?No

Replace the control board

Replace the fuse

Yes, Heating

Yes, Fan Only

Is there a call for heat?See Figure 5

Is there a call for fan?

See Figure 6

Check the thermostat

settings and/or replace the thermostat

No NoReplace the control

board

Yes

Is there power to the

circulating fan motor?See Figure 7

NoReplace

the capacitor

Yes

Is thecapacitor working

properly?See Figure 8

Replacethe circulating

fan motor

No

Leave “Park” terminals unused.

Yes Yes

Yes

Yes

Yes

Page 8: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

8 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide

09.2018 | BTC 770302101 AData subject to change

No Flash and No Fan (System Does Not Start Normally)

Figures & Tables

Figure 1

1. Check for 115Vac power supply between Line-N and Line-H with multi-meter.

Figure 2

1. Power off2. Press the door switch

3. Use a multi-meter to measure the resistance. If it is 0 Ω, then the door switch is ok.

2

3

Figure 3

1. Check for 18-31Vac power between these 2 terminals with multi-meter.

1

Figure 4

1. Check for 18-31Vac power between “R” & “C” terminals with multi-meter.

1

Figure 5

1. Check for 18-31Vac power between “W” & “C” terminals with multi-meter.

1

Page 9: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 9

BTC 770302101 A | 09.2018 Data subject to change

Figure 6

1. Check for 18-31Vac power between “G” & “C” terminals with multi-meter.

1

Figure 7

1. Check for 115Vac power supply between Cir-N and Cool-H with multi-meter.

1

Figure 8

1

1. Check values and compare to Table 1 to see if the capacitor is working normally.

Model Capacitor Value

BGS80M050A3A 25uF

BGS80M080B4A 30uF

BGS80M100C5A 50uF

BGS80M120D5A 50uF

Table 1 Capacitor Values Per Model

NOTICE:

If capacitor must be replaced, a 440 or 450 Volt field supplied capacitor will also work. Do NOT replace with a 370 Volt capacitor, it will NOT work properly.

Page 10: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

1 0 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide

09.2018 | BTC 770302101 AData subject to change

3.2 1 Flash (System Lockout - No Flame)

Troubleshooting Chart

Start

Are there anyloose wires or wrong

connections?

Correct wiring according to

wiring diagramYes

No

Does the unit show 1 LED flash

after restart?

NoIs the

ignitor “glowing” red/orange?

Replace the PCB Board

Is the ignitor working properly? See

Figure 9

Is the flame sensor dirty or

broken?

Clean with steel wool or replace the

flame sensor

Properly ground the

wire

Is flame reaching the flame

sensor? (visual check)

Replace the ignitor

Is there a flame? (visual check)

NoReplace the

PCBboard

Is there a signal to the gas valve?

See Figure 11

Is the wire grounded properly?

See Figure 12

Replace the gas valve if the

pressure cannot be adjusted

Check incoming gas

supply quality

Does the manifold gas pressure meet the requirement?

See Table 2

Adjust the inlet gas pressure

Is there power to the ignitor?

See Figure 10

Check the wire connections

between ignitor and PCB Board

YesYes

Yes Yes Yes

No

Replace the PCB

board

No

Yes

Is the inlet gas pressure meeting the

requirement? See Table 3

Adjust gas valve to ensure it meets gas pressure

requirement

Yes

NoUnit should

work normally

Is gas valve switched to

“On” position?

Yes

YesTurn the gas valve switch

to “On”

No

The flame sense signal should be 1-6 microamps.

No NoYes

No

No

Yes

No

No

Remove the

blockage

Are orifices blocked or clogged?

(check burner)

No

Yes

Yes

Page 11: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 11

BTC 770302101 A | 09.2018 Data subject to change

1 Flash (System Lockout - No Flame)

Figures & Tables

Figure 9

1. Check for 9-17Ω between these two terminals with multi-meter.

1

Figure 10

1. Check for 115Vac power supply between IGN and IGN-N with multi-meter during preheating sequence. See Appendix A.

1

Input RatingKBTU/H

Manifold Gas Pressure RangeNatural Gas Propane Gas

50 4.3-4.7 in. W.C. 9.7-10.3 in. W.C.

80 3.6-4.0 in. W.C. 9.7-10.3 in. W.C.

100 4.0-4.4 in. W.C. 9.7-10.3 in. W.C.

120 4.3-4.7 in. W.C. 9.7-10.3 in. W.C.

Table 2 Manifold Gas Pressure

Figure 11

1

1. Check for 18-31Vac power between “MV” & “MV” terminals with a multi-meter.

Figure 12

1

1. Check for proper connection (green wire).

Inlet Gas Supply Pressure

Natural Gas Minimum: 5.0 in. W.C. Maximum: 10.5 in. W.C.

Propane Gas Minimum: 11.0 in. W.C. Maximum: 13.0 in. W.C.

Table 3 Inlet Gas Supply Pressure

Page 12: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

1 2 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide

09.2018 | BTC 770302101 AData subject to change

3.3 2 Flashes (Pressure Switch Stuck Closed)

Troubleshooting Chart

Start

Are there anyloose wires or wrong

connections?

Correct wiring according to

the wiring diagram

Yes

No

Does the resistance of pressure switch show as “∞ ”

See Figure 13 &14

NoReplace the

pressure switch

Yes

Replace the PCB Board

This error could also be caused by a blocked vent. Check vent for obstructions.

Page 13: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 13

BTC 770302101 A | 09.2018 Data subject to change

2 Flashes (Pressure Switch Stuck Closed)

Figures

Figure 13

PressureSwitch

Figure 14

1. Check for ∞ resistance between these two terminals with multi-meter.

1

Page 14: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

1 4 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide

09.2018 | BTC 770302101 AData subject to change

3.4 3 Flashes (Pressure Switch Stuck Open)

Troubleshooting Chart

Start

Yes

Is the pressure switch closed?See Figure 15

Is there blockage

in the pressure hose or is the hose loose?

See Figure 16

Are there anyloose wires or wrong

connections?

Correct wiring according to

the wiring diagram

YesReplace

the PCB Board

Yes

Remove blockage or fix

the pressure hose

No

No

Is there blockage in the exhaust pipe?

YesRemove

blockage in the exhaust pipe

No

Pull hose off the

pressure switch and put it on a monometer. The set

point is 0.55 in. WC.

NoReplace

theinducer

No

Yes

Replacethe

pressure switch

Page 15: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 15

BTC 770302101 A | 09.2018 Data subject to change

3 Flashes (Pressure Switch Stuck Open)

Figures

Figure 15

1

1. Check for 0Vac between “HL0” & ”PS” terminals with multi-meter during furnace start up sequence. See Appendix A.

Figure 16

Check pressure hose for proper operating condition.Check for proper hose connections. Check and remove any blockages in the hose.

PressureHose

Page 16: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

1 6 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide

09.2018 | BTC 770302101 AData subject to change

3.5 4 Flashes (Open Limit Switch - High Temperature Limit Control)

Troubleshooting Chart

Start

Are there anyloose wires or wrong

connections?

Correct wiring according to

wiring diagramYes

No

NoAre the limit

switches working properly? See

Figure 17

Is the capacitor functioning properly?

See Figure 21

Replace the circulating fan

motor

Replace the PCB Board

Replace the Limit

Switch

Are the temperatures on

the limit switches within normal operating range?

See Figure 18

Is the circulating fan

motor turning on after 45s delay?

Is there power to the

circulating fan motor?See Figure 20

Is the SW2 on PCB Board

at “On” position?See Figure 19

Clean/Replace the filter

Yes

Yes

Is there blockage on the

filter?

“SW2” is for the fan delay after burner starts.

NoReplace the

Limit Switch

Yes

Yes No

Yes

Replace the Capacitor

No

Is the circulating fan motor speed correctly set?

See Table 5

Correct the circulating fan

motor speed or replace the motor

if necessary.

Check the airflow duct for blockage

Yes

No No

Yes Yes

NoTurn it to

“On”position

No

Turn off the equipment for 10 minutes to ensure sufficient cooling

off period. Also verify the temperature rise is 40-55°F.

Page 17: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 17

BTC 770302101 A | 09.2018 Data subject to change

4 Flashes (Open Limit Switch - High Temperature Limit Control)

Figures & Tables

Figure 17

1. Check for 0 resistance between these two terminals with multi-meter.Make sure to do this check on both limit switches.

1

Figure 18

Use thermodetector to measure the temperature of limit switch when fault is active.1. Chamber Limit switch acceptable range:160/130°F2. Fan mounted Limit switch acceptable range:120/90°F

1

2

Figure 19

1. Check to make sure “SW2” dip switch is set to “On”.

1

Figure 20

1. Check for 115Vac power supply between Cir-N and Heat-H with multi-meter

1

Page 18: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

1 8 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide

09.2018 | BTC 770302101 AData subject to change

Figure 21

1

1. Check values and compare to Table 4 to see if the capacitor is working normally.

Model Capacitor ValueBGS80M050A3A 25uF

BGS80M080B4A 30uF

BGS80M100C5A 50uF

BGS80M120D5A 50uF

Table 4 Capacitor Values Per Model

Furnace size

Return-air inlet Speed

External static pressure (in. WC)0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

50ABottom or

Sides

H 1460 1420 1370 1320 1260 1200 1120 1040 950 860

H-M 1210 1170 1140 1090 1030 970 910 840 760 780

**M-L 1080 1050 1010 960 960 870 810 750 670 550

L 780 760 730 700 670 630 580 510 390 ----

80BBottom or

Sides

H 1880 1810 1730 1650 1580 1500 1430 1330 1210 990

**H-M 1680 1620 1560 1500 1430 1350 1270 1160 1020 800

M-L 1440 1390 1340 1290 1240 1170 1080 970 810 640

L 1190 1150 1110 1070 1020 950 870 750 640 530

100CBottom or

Sides

H 2180 2070 1960 1890 1810 1720 1620 1500 1370 1230

**H-M 1760 1710 1660 1600 1520 1460 1360 1260 1140 1130

M-L 1570 1540 1490 1440 1380 1310 1240 1150 1040 910

L 1410 1370 1340 1310 1250 1200 1130 1040 940 810

120DBottom or

Sides

H 2320 2240 2160 2060 1980 1890 1780 1670 1540 1360

**H-M 1790 1750 1700 1660 1610 1540 1460 1360 1220 1060

M-L 1550 1520 1490 1450 1430 1360 1300 1210 1110 960

L 1360 1350 1330 1310 1280 1220 1160 1070 960 830

Table 5 Air Delivery - CFM (Without Filter) * **

* A fi lter is required for each return-air inlet. Airfl ow performance included 3/4-inch washable fi lter media such as contained in fi eld supplied accessory fi lter rack. To determine airfl ow performance with this fi lter, assume an additional 0.1 in. WC available external static pressure.

**  Manufacturer default speed tap for heating.

 If capacitor must be replaced, a 440 or 450 Volt fi eld supplied capacitor will also work. Do NOT replace with a 370 Volt capacitor, it will NOT work properly.

Page 19: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 19

BTC 770302101 A | 09.2018 Data subject to change

3.6 5 Flashes (Open Rollout Limit Switch)

Troubleshooting Chart

Start

Yes

Is there blockage in the

exhaust pipe and check heat exchanger for excess

grime?

Are both rollout

limit switches showing resistance of “0”?

See Figure 22& 23

Rollout limit switches require manual reset by pressing the button in.

Are there anyloose wires or wrong

connections?

Correct wiring according to

the wiring diagram

Yes

Remove blockage

in the exhaust pipe

Replace the

PCB Board

No

No

No

After manual reset of the

limit switch, is the error still present once the system

starts up?

Replacethe

rollout switchYes

Check the inducer for

proper function

Yes

No

Rollout switch set point: 250F This fault could also be caused by lack of proper NG -LP conversion.

Page 20: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

2 0 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide

09.2018 | BTC 770302101 AData subject to change

5 Flashes (Open Rollout Limit Switch)

Figures

Figure 22

1. Power off and Check for 0 resistance between these two terminals with multi-meter. Ensure that this step is completed for both rollout limit switches.

1

Figure 23

1. Rollout Switch Locations

1

Page 21: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 21

BTC 770302101 A | 09.2018 Data subject to change

3.7 6 Flashes (Incorrect Polarity of L1/L2)

Troubleshooting Chart

Start

Correct the wire connection(black

and white wire) according to

wiring diagram

Figures

Figure 24

115V FIELD-SUPPLIED

DISCONNECT

J-BOX

24VTERMINAL

BLOCKFURNACE

CONTROL

R

G

C

GND

BLOWER DOOR SWITCH

WHT

BLK

WHT

BLK W

GND

Y

Page 22: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

2 2 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide

09.2018 | BTC 770302101 AData subject to change

3.8 7 Flashes (Low Flame)

Troubleshooting Chart

Start

Is the manifold gas

pressure requirement being met? See

Table 6

Adjust the gas valve to ensure manifold gas pressure meets the required values

No

Is the PCB Board

grounded properly?See Figure 25

Replace the

PCB Board

No

Yes

Is the inlet gas

pressure requirements being met? See

Table 7

Is the flame sensor dirty

or broken?

Adjust the inlet gas pressure

Replace the gas valve if the

pressure cannot be adjustedYes

No

Clean with steel wool or replace the

Flame Sensor

Yes

No

Are orifices

blocked or clogged? (check burners)

Yes

No Yes

Properly ground the PCB Board

Removethe

blockage

Page 23: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 23

BTC 770302101 A | 09.2018 Data subject to change

7 Flashes (Low Flame)

Figures & Tables

Input RatingKBTU/H

Manifold Gas Pressure RangeNatural Gas Propane Gas

50 4.3-4.7 in. W.C. 9.7-10.3 in. W.C.

80 3.6-4.0 in. W.C. 9.7-10.3 in. W.C.

100 4.0-4.4 in. W.C. 9.7-10.3 in. W.C.

120 4.3-4.7 in. W.C. 9.7-10.3 in. W.C.

Table 6 Manifold Gas Pressure

Inlet Gas Supply Pressure

Natural Gas Minimum: 5.0 in. W.C. Maximum: 10.5 in. W.C.

Propane Gas Minimum: 11.0 in. W.C. Maximum: 13.0 in. W.C.

Table 7 Inlet Gas Supply Pressure

Figure 25

1

1. Check for proper connection (green wire).

Page 24: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

2 4 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide

09.2018 | BTC 770302101 AData subject to change

3.9 Rapid/Continuous Flashes (Flame Sensor Shorted)

Troubleshooting Chart

Figure 26

Start

If the flame sensor is not touching the sheet metal of the unit, replace the

control board

3.10 Steady On Light (Bad Control Board)

Troubleshooting Chart

Figure 27

Start

Check the power supply, if correct,

replace thePCB Board

Page 25: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 25

BTC 770302101 A | 09.2018 Data subject to change

Appendix A - Sequence of Operation

Figure 28

30s 17s 4s 17s

30/45s

30s

W signal

Inducer

Igniter

Gas valve

HEAT-H

Prepurge HEAT-H Swing flap

T. HEAT. ON T. HEAT. OFF

6543217 8

Preheating Ignite

START UPSEQUENCE

Page 26: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

2 6 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide

09.2018 | BTC 770302101 AData subject to change

Page 27: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 27

BTC 770302101 A | 09.2018 Data subject to change

Page 28: Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace Troubleshooting Guide. 2 | Bosch 80% AFUE Gas

United States

Bosch Thermotechnology Corp.65 Grove StreetWatertown, MA 02472

Tel: 866-642-3198Fax: 603-965-7581www.boschheatingandcooling.com

BTC 770302101 A | 09.2018