Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way...
Transcript of Bosch 80% AFUE Furnace Troubleshooting Guide · Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way...
Bosch 80% AFUE Gas Furnace BGS80 Model4-Way Multipoise Category I Fan-Assisted Furnace
Troubleshooting Guide
2 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide
09.2018 | BTC 770302101 AData subject to change
Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 3
BTC 770302101 A | 09.2018 Data subject to change
Table of Contents
1 Key to Symbols and Safety Instructions 4
1.1 Key to Symbols 4
1.2 Safety 4
2 Troubleshooting 6
2.1 Electrostatic Discharge (ESD) Precautions 6
2.2 Resetting From Lockout 6
3 Error Flash Codes 7
3.1 No Flash and No Fan (System Does Not Start Normally) 7
3.2 1 Flash (System Lockout - No Flame) 10
3.3 2 Flashes (Pressure Switch Stuck Closed) 12
3.4 3 Flashes (Pressure Switch Stuck Open) 14
3.5 4 Flashes (Open Limit Switch - High Temperature Limit Control) 16
3.6 5 Flashes (Open Rollout Limit Switch) 19
3.7 6 Flashes (Incorrect Polarity of L1/L2) 21
3.8 7 Flashes (Low Flame) 22
3.9 Rapid/Continuous Flashes (Flame Sensor Shorted) 24
3.10 Steady On Light (Bad Control Board) 24
Appendix A - Sequence of Operation 25
4 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide
09.2018 | BTC 770302101 AData subject to change
1 Key to Symbols and Safety Instructions
1.1 Key to Symbols
Warnings
Warnings in this document are identifi ed by a warning triangle printed against a grey background.Keywords at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.
The following keywords are defi ned and can be used in this document:
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could result in minor to moderate injury.
NOTICE is used to address practices not related to personal injury.
Important information
This symbol indicates important information wherethere is no risk to people or property.
1.2 Safety
Please read all instruction in the manual and retain all manuals for future reference.
WARNING:
Untrained personnel (homeowners) may only clean and replace filters and replace fuses as required by basic maintenance. All other operations, including installation, repair, and service must be performed by a qualified installer, service agency, or the gas supplier.
WARNING: FIRE OR EXPLOSION HAZARD
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS: — Do not try to light any appliance. — Do not touch any electrical switch; do not use any
phone in your building. — Leave the building immediately. — Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
— If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualifi ed installer, service agency, or the gas supplier.
WARNING:
Do not use this furnace if any part has been under water. A fl ood-damaged furnace is extremely dangerous. Attempts to use the furnace can result in fi re or explosion. A qualifi ed service agent must inspect the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet, or the furnace if deemed necessary.
WARNING: FIRE OR EXPLOSION HAZARD
The furnace is designed and approved for use with Natural Gas and (LP) Propane Gas ONLY.
DO NOT BURN ANY LIQUID FUEL OR SOLID FUEL IN THIS FURNACE.
Burning any unapproved fuel will result in damage to the furnace's heat exchanger, which could result in Fire, Personal Injury, and/or Property Damage.
Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 5
BTC 770302101 A | 09.2018 Data subject to change
WARNING: FOLLOW ALL SAFETY CODES
Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes as well as the current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and the National Electrical Code (NEC) NFPA 70.
WARNING: FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, serious injury, death, or property damage. Improper installation, adjustment,alteration, maintenance, or use could cause carbon
monoxide poisoning, explosion, fire, electrical shock,or other conditions which may cause personal injury
or property damage. Consult a qualified service agency, local gas supplier, or your distributor for information or assistance.
WARNING:
Always install furnace to operate within the furnace's intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in Section 11 of the Installation, Operation, and Maintenance Manual, or the furnace rating plate.
WARNING: FIRE HAZARD
The furnaces must be kept free and clear of insulating materials. Inspect surrounding area to ensure insulation material is at a safe distance when installing furnaces or adding insulation materials. Insulation materials may be combustible.Maintain a 1 in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements.
These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, field supplied floor base MUST be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on industry standard Coil Assembly matching correct furnace width.
CAUTION: FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure. Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
CAUTION: CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
WARNING: FIRE, EXPLOSION
Check entire gas assembly for leaks after lighting this appliance.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the Installation, Operation, and Maintenance Manual.
WARNING: FIRE, EXPLOSION
See instructions for lighting/shutdown operation (as shown on a sticker directly on the inside of the furnace panel). Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
WARNING:
Furnace operation requires air for combustion and ventilation. Do not block or obstruct air openings on furnace or spacing around furnace required for supplying sufficient combustion air and ventilation.
WARNING:
This product can expose you to chemicals including Lead and Lead components, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
6 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide
09.2018 | BTC 770302101 AData subject to change
2 Troubleshooting
Refer to the troubleshooting charts and associated fi gures on the following pages for assistance in determining the source of unit operational problems. The red diagnostic LED blinks to assist in troubleshooting the unit. The number of blinks refers to a specifi c code.
2.1 Electrostatic Discharge (ESD) Precautions
NOTICE:
Discharge body's static electricity before touching unit. An electrostatic discharge can adversely aff ect electrical components.
Use the following precautions during furnace installation and servicing to protect the integrated control module from damage. By putting the furnace control and the person at the same electrostatic potential these steps will help avoid exposing the integrated control module to electrostatic discharge. This procedure is applicable to both installed and uninstalled (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the integrated control module or any wire connected to the control prior to discharging your body's electrostatic charge to ground.
2. Firmly touch a clean unpainted metal surface of the furnace away from the control. Any tools held in a person's hand during grounding will be discharged.
3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e. do not move or shuffl e your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.
4. Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a furnace. Return any old or new controls to their containers before touching any ungrounded object.
2.2 Resetting From Lockout
Furnace lockout results when a furnace is unable to achieve ignition after three attempts. It is characterized by a non-functioning furnace and a one fl ash diagnostic LED code from the red LED. If the furnace is in "lockout" it will (or can be) reset in any of the following ways.
1. Automatic reset. The integrated control module will automatically reset itself and attempt to resume normal operations following a one hour lockout period.
2. Manual power interruption. Interrupt 115 volt power to the furnace for 1 - 20 seconds.
3. Manual thermostat cycle. Lower the thermostat so that there is no longer a call for heat for 1 - 20 sec.
WARNING: FIRE,EXPLOSION AND ASPHYXIATION HAZARD
Installation and service must be performed by a qualifi ed service agency or the gas supplier.
Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 7
BTC 770302101 A | 09.2018 Data subject to change
3 Error Flash Codes
3.1 No Flash and No Fan (System Does Not Start Normally)
Troubleshooting Chart
Start
Are there anyloose wires or wrong
connections?
Correctwiring
according to wiring diagram
Yes
No
Is there power to the unit?
See Figure 1No
Is the door switch working properly?
See Figure 2No
Replace the door switch
Is the transformer
working properly?See Figure 3
Is the blower access door closed or fixed properly?
No
Ensure the blower access door is closed
properly
Yes Yes
Check the incoming power
supply at connection box
No
Is the PCB Board
sending 18-31V signals?See Figure 4
No
Replace the transformer
Is there a blown fuse?No
Replace the control board
Replace the fuse
Yes, Heating
Yes, Fan Only
Is there a call for heat?See Figure 5
Is there a call for fan?
See Figure 6
Check the thermostat
settings and/or replace the thermostat
No NoReplace the control
board
Yes
Is there power to the
circulating fan motor?See Figure 7
NoReplace
the capacitor
Yes
Is thecapacitor working
properly?See Figure 8
Replacethe circulating
fan motor
No
Leave “Park” terminals unused.
Yes Yes
Yes
Yes
Yes
8 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide
09.2018 | BTC 770302101 AData subject to change
No Flash and No Fan (System Does Not Start Normally)
Figures & Tables
Figure 1
1. Check for 115Vac power supply between Line-N and Line-H with multi-meter.
Figure 2
1. Power off2. Press the door switch
3. Use a multi-meter to measure the resistance. If it is 0 Ω, then the door switch is ok.
2
3
Figure 3
1. Check for 18-31Vac power between these 2 terminals with multi-meter.
1
Figure 4
1. Check for 18-31Vac power between “R” & “C” terminals with multi-meter.
1
Figure 5
1. Check for 18-31Vac power between “W” & “C” terminals with multi-meter.
1
Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 9
BTC 770302101 A | 09.2018 Data subject to change
Figure 6
1. Check for 18-31Vac power between “G” & “C” terminals with multi-meter.
1
Figure 7
1. Check for 115Vac power supply between Cir-N and Cool-H with multi-meter.
1
Figure 8
1
1. Check values and compare to Table 1 to see if the capacitor is working normally.
Model Capacitor Value
BGS80M050A3A 25uF
BGS80M080B4A 30uF
BGS80M100C5A 50uF
BGS80M120D5A 50uF
Table 1 Capacitor Values Per Model
NOTICE:
If capacitor must be replaced, a 440 or 450 Volt field supplied capacitor will also work. Do NOT replace with a 370 Volt capacitor, it will NOT work properly.
1 0 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide
09.2018 | BTC 770302101 AData subject to change
3.2 1 Flash (System Lockout - No Flame)
Troubleshooting Chart
Start
Are there anyloose wires or wrong
connections?
Correct wiring according to
wiring diagramYes
No
Does the unit show 1 LED flash
after restart?
NoIs the
ignitor “glowing” red/orange?
Replace the PCB Board
Is the ignitor working properly? See
Figure 9
Is the flame sensor dirty or
broken?
Clean with steel wool or replace the
flame sensor
Properly ground the
wire
Is flame reaching the flame
sensor? (visual check)
Replace the ignitor
Is there a flame? (visual check)
NoReplace the
PCBboard
Is there a signal to the gas valve?
See Figure 11
Is the wire grounded properly?
See Figure 12
Replace the gas valve if the
pressure cannot be adjusted
Check incoming gas
supply quality
Does the manifold gas pressure meet the requirement?
See Table 2
Adjust the inlet gas pressure
Is there power to the ignitor?
See Figure 10
Check the wire connections
between ignitor and PCB Board
YesYes
Yes Yes Yes
No
Replace the PCB
board
No
Yes
Is the inlet gas pressure meeting the
requirement? See Table 3
Adjust gas valve to ensure it meets gas pressure
requirement
Yes
NoUnit should
work normally
Is gas valve switched to
“On” position?
Yes
YesTurn the gas valve switch
to “On”
No
The flame sense signal should be 1-6 microamps.
No NoYes
No
No
Yes
No
No
Remove the
blockage
Are orifices blocked or clogged?
(check burner)
No
Yes
Yes
Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 11
BTC 770302101 A | 09.2018 Data subject to change
1 Flash (System Lockout - No Flame)
Figures & Tables
Figure 9
1. Check for 9-17Ω between these two terminals with multi-meter.
1
Figure 10
1. Check for 115Vac power supply between IGN and IGN-N with multi-meter during preheating sequence. See Appendix A.
1
Input RatingKBTU/H
Manifold Gas Pressure RangeNatural Gas Propane Gas
50 4.3-4.7 in. W.C. 9.7-10.3 in. W.C.
80 3.6-4.0 in. W.C. 9.7-10.3 in. W.C.
100 4.0-4.4 in. W.C. 9.7-10.3 in. W.C.
120 4.3-4.7 in. W.C. 9.7-10.3 in. W.C.
Table 2 Manifold Gas Pressure
Figure 11
1
1. Check for 18-31Vac power between “MV” & “MV” terminals with a multi-meter.
Figure 12
1
1. Check for proper connection (green wire).
Inlet Gas Supply Pressure
Natural Gas Minimum: 5.0 in. W.C. Maximum: 10.5 in. W.C.
Propane Gas Minimum: 11.0 in. W.C. Maximum: 13.0 in. W.C.
Table 3 Inlet Gas Supply Pressure
1 2 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide
09.2018 | BTC 770302101 AData subject to change
3.3 2 Flashes (Pressure Switch Stuck Closed)
Troubleshooting Chart
Start
Are there anyloose wires or wrong
connections?
Correct wiring according to
the wiring diagram
Yes
No
Does the resistance of pressure switch show as “∞ ”
See Figure 13 &14
NoReplace the
pressure switch
Yes
Replace the PCB Board
This error could also be caused by a blocked vent. Check vent for obstructions.
Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 13
BTC 770302101 A | 09.2018 Data subject to change
2 Flashes (Pressure Switch Stuck Closed)
Figures
Figure 13
PressureSwitch
Figure 14
1. Check for ∞ resistance between these two terminals with multi-meter.
1
1 4 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide
09.2018 | BTC 770302101 AData subject to change
3.4 3 Flashes (Pressure Switch Stuck Open)
Troubleshooting Chart
Start
Yes
Is the pressure switch closed?See Figure 15
Is there blockage
in the pressure hose or is the hose loose?
See Figure 16
Are there anyloose wires or wrong
connections?
Correct wiring according to
the wiring diagram
YesReplace
the PCB Board
Yes
Remove blockage or fix
the pressure hose
No
No
Is there blockage in the exhaust pipe?
YesRemove
blockage in the exhaust pipe
No
Pull hose off the
pressure switch and put it on a monometer. The set
point is 0.55 in. WC.
NoReplace
theinducer
No
Yes
Replacethe
pressure switch
Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 15
BTC 770302101 A | 09.2018 Data subject to change
3 Flashes (Pressure Switch Stuck Open)
Figures
Figure 15
1
1. Check for 0Vac between “HL0” & ”PS” terminals with multi-meter during furnace start up sequence. See Appendix A.
Figure 16
Check pressure hose for proper operating condition.Check for proper hose connections. Check and remove any blockages in the hose.
PressureHose
1 6 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide
09.2018 | BTC 770302101 AData subject to change
3.5 4 Flashes (Open Limit Switch - High Temperature Limit Control)
Troubleshooting Chart
Start
Are there anyloose wires or wrong
connections?
Correct wiring according to
wiring diagramYes
No
NoAre the limit
switches working properly? See
Figure 17
Is the capacitor functioning properly?
See Figure 21
Replace the circulating fan
motor
Replace the PCB Board
Replace the Limit
Switch
Are the temperatures on
the limit switches within normal operating range?
See Figure 18
Is the circulating fan
motor turning on after 45s delay?
Is there power to the
circulating fan motor?See Figure 20
Is the SW2 on PCB Board
at “On” position?See Figure 19
Clean/Replace the filter
Yes
Yes
Is there blockage on the
filter?
“SW2” is for the fan delay after burner starts.
NoReplace the
Limit Switch
Yes
Yes No
Yes
Replace the Capacitor
No
Is the circulating fan motor speed correctly set?
See Table 5
Correct the circulating fan
motor speed or replace the motor
if necessary.
Check the airflow duct for blockage
Yes
No No
Yes Yes
NoTurn it to
“On”position
No
Turn off the equipment for 10 minutes to ensure sufficient cooling
off period. Also verify the temperature rise is 40-55°F.
Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 17
BTC 770302101 A | 09.2018 Data subject to change
4 Flashes (Open Limit Switch - High Temperature Limit Control)
Figures & Tables
Figure 17
1. Check for 0 resistance between these two terminals with multi-meter.Make sure to do this check on both limit switches.
1
Figure 18
Use thermodetector to measure the temperature of limit switch when fault is active.1. Chamber Limit switch acceptable range:160/130°F2. Fan mounted Limit switch acceptable range:120/90°F
1
2
Figure 19
1. Check to make sure “SW2” dip switch is set to “On”.
1
Figure 20
1. Check for 115Vac power supply between Cir-N and Heat-H with multi-meter
1
1 8 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide
09.2018 | BTC 770302101 AData subject to change
Figure 21
1
1. Check values and compare to Table 4 to see if the capacitor is working normally.
Model Capacitor ValueBGS80M050A3A 25uF
BGS80M080B4A 30uF
BGS80M100C5A 50uF
BGS80M120D5A 50uF
Table 4 Capacitor Values Per Model
Furnace size
Return-air inlet Speed
External static pressure (in. WC)0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
50ABottom or
Sides
H 1460 1420 1370 1320 1260 1200 1120 1040 950 860
H-M 1210 1170 1140 1090 1030 970 910 840 760 780
**M-L 1080 1050 1010 960 960 870 810 750 670 550
L 780 760 730 700 670 630 580 510 390 ----
80BBottom or
Sides
H 1880 1810 1730 1650 1580 1500 1430 1330 1210 990
**H-M 1680 1620 1560 1500 1430 1350 1270 1160 1020 800
M-L 1440 1390 1340 1290 1240 1170 1080 970 810 640
L 1190 1150 1110 1070 1020 950 870 750 640 530
100CBottom or
Sides
H 2180 2070 1960 1890 1810 1720 1620 1500 1370 1230
**H-M 1760 1710 1660 1600 1520 1460 1360 1260 1140 1130
M-L 1570 1540 1490 1440 1380 1310 1240 1150 1040 910
L 1410 1370 1340 1310 1250 1200 1130 1040 940 810
120DBottom or
Sides
H 2320 2240 2160 2060 1980 1890 1780 1670 1540 1360
**H-M 1790 1750 1700 1660 1610 1540 1460 1360 1220 1060
M-L 1550 1520 1490 1450 1430 1360 1300 1210 1110 960
L 1360 1350 1330 1310 1280 1220 1160 1070 960 830
Table 5 Air Delivery - CFM (Without Filter) * **
* A fi lter is required for each return-air inlet. Airfl ow performance included 3/4-inch washable fi lter media such as contained in fi eld supplied accessory fi lter rack. To determine airfl ow performance with this fi lter, assume an additional 0.1 in. WC available external static pressure.
** Manufacturer default speed tap for heating.
If capacitor must be replaced, a 440 or 450 Volt fi eld supplied capacitor will also work. Do NOT replace with a 370 Volt capacitor, it will NOT work properly.
Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 19
BTC 770302101 A | 09.2018 Data subject to change
3.6 5 Flashes (Open Rollout Limit Switch)
Troubleshooting Chart
Start
Yes
Is there blockage in the
exhaust pipe and check heat exchanger for excess
grime?
Are both rollout
limit switches showing resistance of “0”?
See Figure 22& 23
Rollout limit switches require manual reset by pressing the button in.
Are there anyloose wires or wrong
connections?
Correct wiring according to
the wiring diagram
Yes
Remove blockage
in the exhaust pipe
Replace the
PCB Board
No
No
No
After manual reset of the
limit switch, is the error still present once the system
starts up?
Replacethe
rollout switchYes
Check the inducer for
proper function
Yes
No
Rollout switch set point: 250F This fault could also be caused by lack of proper NG -LP conversion.
2 0 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide
09.2018 | BTC 770302101 AData subject to change
5 Flashes (Open Rollout Limit Switch)
Figures
Figure 22
1. Power off and Check for 0 resistance between these two terminals with multi-meter. Ensure that this step is completed for both rollout limit switches.
1
Figure 23
1. Rollout Switch Locations
1
Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 21
BTC 770302101 A | 09.2018 Data subject to change
3.7 6 Flashes (Incorrect Polarity of L1/L2)
Troubleshooting Chart
Start
Correct the wire connection(black
and white wire) according to
wiring diagram
Figures
Figure 24
115V FIELD-SUPPLIED
DISCONNECT
J-BOX
24VTERMINAL
BLOCKFURNACE
CONTROL
R
G
C
GND
BLOWER DOOR SWITCH
WHT
BLK
WHT
BLK W
GND
Y
2 2 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide
09.2018 | BTC 770302101 AData subject to change
3.8 7 Flashes (Low Flame)
Troubleshooting Chart
Start
Is the manifold gas
pressure requirement being met? See
Table 6
Adjust the gas valve to ensure manifold gas pressure meets the required values
No
Is the PCB Board
grounded properly?See Figure 25
Replace the
PCB Board
No
Yes
Is the inlet gas
pressure requirements being met? See
Table 7
Is the flame sensor dirty
or broken?
Adjust the inlet gas pressure
Replace the gas valve if the
pressure cannot be adjustedYes
No
Clean with steel wool or replace the
Flame Sensor
Yes
No
Are orifices
blocked or clogged? (check burners)
Yes
No Yes
Properly ground the PCB Board
Removethe
blockage
Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 23
BTC 770302101 A | 09.2018 Data subject to change
7 Flashes (Low Flame)
Figures & Tables
Input RatingKBTU/H
Manifold Gas Pressure RangeNatural Gas Propane Gas
50 4.3-4.7 in. W.C. 9.7-10.3 in. W.C.
80 3.6-4.0 in. W.C. 9.7-10.3 in. W.C.
100 4.0-4.4 in. W.C. 9.7-10.3 in. W.C.
120 4.3-4.7 in. W.C. 9.7-10.3 in. W.C.
Table 6 Manifold Gas Pressure
Inlet Gas Supply Pressure
Natural Gas Minimum: 5.0 in. W.C. Maximum: 10.5 in. W.C.
Propane Gas Minimum: 11.0 in. W.C. Maximum: 13.0 in. W.C.
Table 7 Inlet Gas Supply Pressure
Figure 25
1
1. Check for proper connection (green wire).
2 4 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide
09.2018 | BTC 770302101 AData subject to change
3.9 Rapid/Continuous Flashes (Flame Sensor Shorted)
Troubleshooting Chart
Figure 26
Start
If the flame sensor is not touching the sheet metal of the unit, replace the
control board
3.10 Steady On Light (Bad Control Board)
Troubleshooting Chart
Figure 27
Start
Check the power supply, if correct,
replace thePCB Board
Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 25
BTC 770302101 A | 09.2018 Data subject to change
Appendix A - Sequence of Operation
Figure 28
30s 17s 4s 17s
30/45s
30s
W signal
Inducer
Igniter
Gas valve
HEAT-H
Prepurge HEAT-H Swing flap
T. HEAT. ON T. HEAT. OFF
6543217 8
Preheating Ignite
START UPSEQUENCE
2 6 | Bosch 80% AFUE Gas Furnace Troubleshooting Guide
09.2018 | BTC 770302101 AData subject to change
Troubleshooting Guide Bosch 80% AFUE Gas Furnace | 27
BTC 770302101 A | 09.2018 Data subject to change
United States
Bosch Thermotechnology Corp.65 Grove StreetWatertown, MA 02472
Tel: 866-642-3198Fax: 603-965-7581www.boschheatingandcooling.com
BTC 770302101 A | 09.2018