BORRI B500R - EficSeven

4
O F C O N T I N U O U S S E R V I C E ONLINE DOUBLE CONVERSION BORRI | B500R 6 & 10kVA UPS

Transcript of BORRI B500R - EficSeven

OF C

ONTINUOUS SERVIC

E

ONLINE DOUBLE CONVERSION

BORRI | B500R6 & 10kVA UPS

BORRI | B500R

2

Operational EfficiencyThe Borri B500R delivers 28% more useable power than other UPS in its classthanks to the 0.9 output power factor.

When positioned in rack-mount form, the Borri B500R has a capacity of 6kVA/5.4kW contained within 3Uand 10kVA/9kW contained within 5U, which includes internal batteries to provide standard runtime.This gives the user more valuable space within the rest of the rack for IT & Comms equipment.

Its online double conversion topology completely isolates the output voltage and frequency supplied tothe users valuable load from incoming mains power anomalies.

In addition, sophisticated ECO functions enable the B500R to achieve an industry leading 98% efficiency.

Borri’s B500R rotation series incorporates some of

the most technically advanced UPS components

available and as such provide superior power

resilience and operational efficiency.

Flexibility Designed to deliver maximum user flexibility, the B500R has beenbuilt with an internal static bypass switch enabling users to carry outmaintenance and battery replacements safely on the units withoutthe need to power down the load.

Additional runtime with unlimited hot swappable battery modulesmakes the Borri B500R series easily scalable.

An additional UPS unit can also be connected in parallel to share thecritical load and provide N+1 redundancy for the most resilient solution.

Expandable RuntimeUnlimited expandable runtimewith matching batterymodules allow the user toincrease the amount of timethe UPS will run the connectedcritical loads during a mainsfailure. They can be purchasedand connected after the initialinstall if required.

Hot-swap BatteriesThe internal batteries of theUPS can be "Hot Swapped"safely by the user without theneed for a power down. Thebatteries are located in aseparate internal enclosureensuring the users safety whileperforming this task.

B500R Applications:

> Small to medium sized data centres

> IT facilities

> Telecoms

> Networking

> Logistics and storage

3w w w . b o r r i . c o . u k

Online double conversion

topology

High efficiency up to 98%

Rack/tower compact

convertible design

0.9 output power factor

Smart Dot Matrix LCD display

Serial, USB, SNMP, Modbus and

Relay connectivity

Network management for alerts

and scheduled shutdown,

compatible with all major OS

including virtualisation software

Expandable runtime with

additional battery modules

Parallel capability for N+1

redundancy solutions

User-Replaceable

Hot Swappable batteries

Intelligent monitoring software

now compatible with virtualised

environments such as HyperV

and VMware

B500R Main Features

Functionality

The B500R incorporates a smart, adjustable dot matrixLCD display with an intuitive menu system so that allparameters can be viewed directly from the UPS. Alsoincluded is advanced monitoring and shutdownsoftware, which can be installed on all connected loaddevices and as such maximises battery runtime asdifferent devices can be shutdown at varying batterycapacity levels.

Borri’s software does not require any supplementarylicences and is compatible with a multitude ofoperating systems including Windows, Linux, IBM andHP and as well as virtualised platforms such as VMwareESX 3.5, 4.0, 4.1 and VMware ESXi 4.0, 4.1, 5.0, 5.1.

Dot Matrix LCD DisplayAll parameters can easily beread from a single Dot MatrixLCD screen, an intuitive menusystem allows the user to scrollthrough a multitude of historylogs, settings and currentconditions. In the event of theUPS being overloaded,overheated or any other faultoccurring, which would leavethe critical load withoutprotection, the whole displayturns red alerting the user torectify the problemimmediately.

Network Management CardThe Borri NMC option enables the UPSto be monitored and controlled overthe LAN, the UPS has its own dedicatedIP address, which can then send SNMPtraps or email warnings over thenetwork to other devices.

IEC OutletsThe B500R has a number IEC C13 andC19 outputs (model dependant) inaddition to a hardwired terminaloutput. If the user requests the plug ‘n’play option the UPS can be installedwithout the need for an electrician.

BORRI Ltd | Systems House | Rotherside Road | Eckington | Sheffield | S21 4HLTel: +44 (0)1246 431431 | Fax: +44 (0)1246 431444 | Email: [email protected] | Web: www.borri.co.uk

BORRI Spa | Via 8 Marzo, 2 | 52010 Bibbiena | (Arezzo) | ItalyTel: +39 0575 5351 | Fax: +39 0575 561438 | Email: [email protected] | Web: www.borri.it

MODELS B500R-060-B B500R-060-C B500R-100-B B500R-100-CINPUTInput Voltage Window 120VAC-276VACTHDi <5% with full loadInput Power Factor ≥0.99(FULL LOAD)Input Frequency Range 45-55Hz / 54-66HzGenerator Set 1.3 x UPS Rating PowerOUTPUTPowerPower(kVA) max 6.0 10.0Power(kW) max 5.4 9.0Power Factor 0.9 (Default) 0.5 - 1 (Flexible)Output VoltageWaveform Pure Sine WaveNominal voltage 208VAC*/220VAC/230VAC/240VACVoltage regulation ± 1 %Transient recovery 100ms (IEC 62040-3 Non-linear load)Voltage distortion < 2% THD, linear load <5% THD, non-linear loadOutput FrequencySynchronization range 45-55Hz / 54-66Hz**Slew rate 1 Hz/sBattery mode (50/60±0.1) Hz**Transfer TimeNormal mode to Battery Mode. 0msNormal mode to Bypass Mode. 0msECO to Inverter mode <10msFull Load EfficiencyECO mode >96% >98%Overload Capability (Mains Present) 130% for 2 minutes; 150% for 30 seconds; >150% 100ms Overload Capability (Battery Mode) 130% for 10 seconds; >130% 100ms Crest Ratio 3:1Parallel 1+1 for capacity and redundancyBATTERYDC Voltage 180VDC 240VDCRating/Type 12VDC/5Ah 12VDC/9AhBack-up Time (full load) >2.5minutes >3.5minutesChargerCharging current (Normal) 1.0A 8.0A 1.7A 8.0ACharging time <3h charge to 90% Depends on the capacity of external batteries <3h charge to 90% Depends on the capacity of external batteries

FEATURES

AC Outlets IEC C13*2+ IEC C19*1+Terminal IEC C13 x 2 +IEC C19 x 2 + Terminal IEC C19 *4+Terminal IEC C13 x 4 +IEC C19 x 2 + Terminal MECHANICALWxDxH (mm) 438 x 698 x 129 (3U) 438 x 704 x 215 (5U)Net Weight 20Kg (w/o battery) 32.5Kg (w/o battery)

46Kg (w/ battery) 82.5Kg (w/ battery)Operating Temperature Range UPS: 0°C ~ 40 °C - BATTERIES: 20°C ~ 25 °CRelative Humidity 0 ~ 95% (No condensing)Audible Noise <55dB MaximumREGULATIONSESD IEC 61000-4-2 Level 4RS IEC 61000-4-3 Level 3EFT IEC 61000-4-4 Level 4Surge IEC 61000-4-5 Level 4Conduction IEC 62040-2 Category C2Radiation IEC 62040-2 Category C2Safety IEC 60950-1 / IEC 62040-1-1Transportation ETS 300019-2-2 Class 2.3Protection IP20 (static)

BORRI | B500RTechnical Specification

*Der

ate

to 9

0% d

urin

g 20

8VA

C o

utpu

t vol

tage

.**

Der

ate

to 8

0% d

urin

g Fr

eque

ncy

Conv

erte

r Mod

e .

Rear view of B500R-060-B Rear view of B500R-060-C Rear view of B500R-100-B Rear view of B500R-100-C

ECO Mode; EPO Connection; Dual Communication; Auto De-rating; Battery Capacity Calculation; Maintenance Bypass Switch; Fan Speed Control; Frequency Converter Mode**USB Connectivity; Electronic Bypass Interlock; Programmable Relay; Cold Start; Intelligent Smart slot for optional SNMP / Relay Card / MODBUS

Depends on the capacity of external batteries

19Kg 26Kg

Depends on the capacity of external batteries

UPS Communication Slot

Dry In/EPO

Dry Out

RS-232 Port Input / Output Terminal Block

USB Port

ParallelConnector

Output CircuitBreaker

OutputGround Screw

UPS Communication Slot

REPO Port

Dry Out RS-232 Port Input / Output Terminal Block

USB Port

ParallelConnector Output Circuit

Breaker OutputGround Screw

Dry In

UPS Communication Slot Dry In/EPO Dry Out RS-232 Port External Battery Connector

Terminal (Bypass, Input and Output)USB PortParallelConnector

Output CircuitBreaker

Output

UPS Communication Slot Dry In/EPO Dry Out RS-232 Port External Battery Connector

Terminal (Bypass, Input and Output)USB PortParallelConnector

Output CircuitBreaker

Output