BOQ - MALL

17
Sr. No. Description Qty Unit Rate Amount 2.0 SITC of induced draft type cooling tower of FRP Square type multicell cooling tower complete with all acc. basin, fitting, fan, motor etc with following specification - ( 3 Working ) Cells. a Wet bulb temp : 28.3 deg C 3 Nos. 0 b Entering water temp : 37.5 deg C c Leaving water temp : 32.0 deg C d Total flow rate/cell : 225 m 3 / Hr. 2.1 CHILLED WATER PUMPS A Primary end suction pump for chilled water with drive motor and coupling with following tech specifications (3W +1S) 4 Nos. 0 a Water Qty : 136 m 3 / Hr. per Pump b Static Head : 12 Mtrs c Impeller : Bronze d Speed : NOT MORE THAN 1450 RPM e Seal : Mechanical B Secondary end suction pump WITH VFD and its accessories for chilled water with drive motor and coupling with following tech specifications (2W +1S) 3 Nos. 0 a Water Qty :205 m 3 / Hr. b Static Head :30 Mtrs c Impeller : Bronze d Speed : NOT MORE THAN 1450 RPM e Seal : Mechanical 2.2 CONDENSER WATER PUMPS End suction pump for condensr water with drive motor and coupling with following tech specifications (3W +1S) 4 Nos. 0 COOLING TOWER , CHW & COND. PUMPS & COND. WATER PIPING & FITTING CHAPTER- 6 - SCHEDULE OF QUANTITIES & PRICES Scope of work includes design, supply, erection, testing & commissioning of the complete H.V.A.C system, with complete Tech Data. PART-2 APMC - BOQ - MALL.xls

Transcript of BOQ - MALL

Page 1: BOQ - MALL

Sr. No. Description Qty Unit Rate Amount

2.0

SITC of induced draft type cooling tower of FRPSquare type multicell cooling tower complete withall acc. basin, fitting, fan, motor etc with followingspecification - ( 3 Working )

Cells.

a Wet bulb temp : 28.3 deg C 3 Nos. 0b Entering water temp : 37.5 deg Cc Leaving water temp : 32.0 deg Cd Total flow rate/cell : 225 m3 / Hr.

2.1 CHILLED WATER PUMPS

APrimary end suction pump for chilled water withdrive motor and coupling with following techspecifications (3W +1S)

4 Nos. 0

a Water Qty : 136 m3 / Hr. per Pumpb Static Head : 12 Mtrsc Impeller : Bronzed Speed : NOT MORE THAN 1450 RPMe Seal : Mechanical

B

Secondary end suction pump WITH VFD and itsaccessories for chilled water with drive motor andcoupling with following tech specifications (2W+1S)

3 Nos. 0

a Water Qty :205 m3 / Hr. b Static Head :30 Mtrsc Impeller : Bronzed Speed : NOT MORE THAN 1450 RPMe Seal : Mechanical

2.2 CONDENSER WATER PUMPSEnd suction pump for condensr water with drivemotor and coupling with following techspecifications (3W +1S)

4 Nos. 0

COOLING TOWER , CHW & COND. PUMPS & COND. WATER PIPING & FITTING

CHAPTER- 6 - SCHEDULE OF QUANTITIES & PRICESScope of work includes design, supply, erection, testing & commissioning of the completeH.V.A.C system, with complete Tech Data.

PART-2

APMC - BOQ - MALL.xls

Page 2: BOQ - MALL

a Water Qty : 225 m3 / Hr.b Static Head : 25 Mtrsc Impeller : Bronzed Speed : 1450 RPMe Seal : Mechanical

2.3 Condenser Water Piping

2.3.1

Condenser Water Piping With MS “C” Class PipeComplete With All Accessories Such As Bends,Elbow, Flanges, Nut Bolts, De-scaling Tee WithM.S. Angle & Rod Supporting Work With FRPCoating Etc.

a 300 mm dia 60 RMT 0b 250 mm dia. Rate RMTc 200 mm dia. 80 RMT 0d 100 mm dia. 10 RMT 0e 50 mm dia. 20 RMT 0

2.3.2 Butterfly Valves & Fittingsa 300 mm dia. ( Gear operated ) 3 Nos. 0b 250 mm dia. ( Gear operated ) Rate Nos.c 200 mm dia. ( Handel operated ) 20 Nos. 0d 100 mm dia. 2 Nos. 0e 50 mm dia. 3 Nos. 0

2.3.3 Wafer swing check valvesa 250 mm dia. Rate Nos.b 200 mm dia. 4 Nos. 0

2.3.4 Pot strainera 300 mm dia. 1 Nos. 0

2.3.5 Installation of Motorised Butter Fly Valve a 250 mm dia. 4 Nos. 0b 200 mm dia. Rate Nos.

2.3.6 Balancing Valvesa 250 mm dia. Rate Nos.b 200 mm dia. 3 Nos. 0

2.3.7 Ball Valve For Draina 32 mm dia. 10 Nos. 0

2.3.8 Automatic Air Purge Valves

APMC - BOQ - MALL.xls

Page 3: BOQ - MALL

a 15 mm dia. 10 Nos. 0

2.3.9 Pressure Gauge 6" Dial (0 To 6 Kg/CM2) 14 Nos. 0

2.3.10 6" Dial Type Thermometers (0 To 50OC) 10 Nos. 0

SUB TOTAL- PART- 2 ( C.T. , COND & CHW PUMPS & COND. WATER PIPING & FITTING

) 0

APMC - BOQ - MALL.xls

Page 4: BOQ - MALL

Sr. No. Description Qty Unit Rate Amount3.0 Chilled Water Piping

3.1

Chilled Water Piping With MS “C” Class PipeComplete With All Accessories Such As Bends,Elbow, Flanges, Nut Bolts, With M.S. Angle &Rod Supporting Work Etc. Of Following Sizes

a 300 mm dia. RATE RMTb 250 mm dia. 260 RMT 0c 200 mm dia. 280 RMT 0d 150 mm dia. 200 RMT 0e 125 mm dia. 100 RMT 0f 100 mm dia. 420 RMT 0g 80 mm dia. 960 RMT 0h 65 mm dia. 760 RMT 0i 50 mm dia. 300 RMT 0j 40 mm dia. 350 RMT 0k 32 mm dia. 655 RMT 0l 25mm 300 RMT 0

m 19 mm dia. 180 RMT 0

3.2 Valves & FittingsI Butterfly Valves a 250 mm dia. RATE Nos.b 200 mm dia. 10 Nos. 0c 150 mm dia. 16 Nos. 0d 125 mm dia. 2 Nos. 0e 100 mm dia. 14 Nos. 0f 80 mm dia. 50 Nos. 0g 65 mm dia. 8 Nos. 0h 50 mm dia. 12 Nos. 0i 40 mm dia. 12 Nos. 0j 32 mm dia. 10 Nos. 0

II Wafer Swing Check Valvea 200 mm dia. 3 Nos. 0b 150 mm dia. 4 Nos. 0

III Balancing Valves a 200 mm dia. 5 Nos. 0

CHAPTER- 6 - SCHEDULE OF QUANTITIES & PRICES

Scope of work includes design, supply, erection, testing & commissioning of the completeH.V.A.C system, with complete Tech Data.

PART- 3- CHILLED WATER PIPING WITH VALVES & FITTING

APMC - BOQ - MALL.xls

Page 5: BOQ - MALL

b 80 mm dia. 12 Nos. 0c 65 mm dia. 1 Nos. 0d 50 mm dia 3 Nos. 0e 40 mm dia 3 Nos. 0

IV Ball Valvesa 40 mm dia. Rate Nos.b 32 mm dia. 284 Nos. 0c 25 mm dia. 30 Nos. 0d 12.5 mm dia 180 Nos. 0

V “Y” type strainer a 200 mm dia. 3 Nos. 0a 150 mm dia. 4 Nos. 0b 80 mm dia. 12 Nos. 0c 65 mm dia. 1 Nos. 0d 50 mm dia. 3 Nos. 0e 40 mm dia. 3 Nos. 0f 32 mm dia. 71 Nos. 0

VI Ball Valves and Ball Valves With 'Y' StrainerSet.

a 25 mm dia. 44 Sets. 0b 19 mm dia. 36 Sets. 0

VII Installation of 2 Way On/Off Valves for AHUswith Controller & Necessary cabeling

a 200 mm dia. ( FOR VAM CHILLER ) 3 Nos. 0b 80 mm dia. Rate Nos.c 65 mm dia. 12 Nos. 0d 50 mm dia. 1 Nos. 0e 40 mm dia. 3 Nos. 0f 32 mm dia. 3 Nos. 0g 25 mm dia. 71 Nos. 0

VIII Installation of 2 Way On / OFF Valves withRoom Thermostat & Speed Controller & wiring

a 19 mm dia. 44 Nos. 0b 15 mm dia. 36 Nos. 0

IX Automatic Air Purge Valvesa 19 mm dia. Rate Nos.b 15 mm dia. 90 Nos. 0

X Pressure Gauge 6" Dial (0 To 6 Kg/CM2) 52 Nos. 0APMC - BOQ - MALL.xls

Page 6: BOQ - MALL

XI 6" Dial Type Thermometers (0 To 50OC) 40 Nos. 0

3.3

Precharged steel closed expansion tank withreplaceable heavy duty butyl rubber bladder,mounting stand with all necessary systemconnection & charging valve connection tofacilitate on site charging. Tank to meet ASMEBoiler & pressure vessel code all valve mountingetc. System to be complete with pressurizationunit and accessories like pressure reducing valve,auto air purge etc. Centrifugal air separatorSuitable for 300mm Dia pipe as shown in thedrawing and specifications(TREATED AS ONEPACKAGE)(1000ltrs)

1 Lot 0

3.4 Chilled Water Pipes/Accessories Insulation

3.4.1Chilled Water Pipe insulation Nitrile/Troceleanclosed cell rubber insulation thickness as perspecifications.

a 300 mm dia. RATE RMTb 250 mm dia. 260 RMT 0c 200 mm dia. 280 RMT 0d 150 mm dia. 200 RMT 0e 125 mm dia. 100 RMT 0f 100 mm dia. 420 RMT 0g 80 mm dia. 960 RMT 0h 65 mm dia. 760 RMT 0i 50 mm dia. 300 RMT 0j 40 mm dia. 350 RMT 0k 32 mm dia. 655 RMT 0l 25mm 300 RMT 0

m 19 mm dia. 180 RMT 0

3.4.2 Valves & FittingsI Butterfly Valves a 250 mm dia. RATE Nos. 0b 200 mm dia. 10 Nos. 0c 150 mm dia. 16 Nos.d 125 mm dia. 2 Nos.e 100 mm dia. 14 Nos. 0f 80 mm dia. 50 Nos. 0g 65 mm dia. 8 Nos. 0h 50 mm dia. 12 Nos. 0i 40 mm dia. 12 Nos. 0j 32 mm dia. 10 Nos. 0

II Wafer Swing Check ValveAPMC - BOQ - MALL.xls

Page 7: BOQ - MALL

a 200 mm dia. 3 Nos. 0b 150 mm dia. 4 Nos. 0

III Balancing Valves a 200 mm dia. 5 Nos. 0b 80 mm dia. 12 Nos.c 65 mm dia. 1 Nos. 0d 50 mm dia 3 Nos. 0e 40 mm dia 3 Nos.

IV Ball Valvesa 40 mm dia. Rate Nos.b 32 mm dia. 284 Nos. 0c 25 mm dia. 30 Nos. 0d 12.5 mm dia 180 Nos. 0

V “Y” type strainer a 200 mm dia. 3 Nos. 0a 150 mm dia. 4 Nos. 0b 80 mm dia. 12 Nos. 0c 65 mm dia. 1 Nos. 0d 50 mm dia. 3 Nos. 0e 40 mm dia. 3 Nos. 0f 32 mm dia. 71 Nos. 0

VI Ball Valves and Ball Valves With 'Y' StrainerSet.

a 25 mm dia. 44 Sets. 0b 19 mm dia. 36 Sets. 0

VII Insulation of 2 Way On/Off Valves for AHUswith controller

a 200 mm dia. ( FOR VAM CHILLER ) 3 Nos. 0b 80 mm dia. Rate Nos.c 65 mm dia. 12 Nos. 0d 50 mm dia. 1 Nos. 0e 40 mm dia. 3 Nos. 0f 32 mm dia. 3 Nos. 0g 25 mm dia. 71 Nos. 0

VIII Insulation of 2 Way On / OFF Valves with RoomThermostat & Speed Controller

a 19 mm dia. 44 Nos. 0b 15 mm dia. 36 Nos. 0

3.4.3 KITEC PIPING WITH TUBLER NITRILERUBBER INSULATION 19 MM THICK

APMC - BOQ - MALL.xls

Page 8: BOQ - MALL

a 40 mm dia RATE RMTb 32 mm dia RATE RMTa 25 mm dia RATE RMTb 19 mm dia RATE RMT

3.4.4

Insulation of Precharged steel closed expansiontank with Centrifugal air separator Suitable for300mm Dia pipe as shown in the drawing andspecifications(TREATED AS ONEPACKAGE)(1000ltrs)

1 lot 0

SUB TOTAL -PART- 3 - CHILLED WATER PIPING & INSULATION WORK 0

APMC - BOQ - MALL.xls

Page 9: BOQ - MALL

APMC - BOQ - MALL.xls

Sr. No. Description Qty Unit Rate Amount

4.0

AIR HANDLING UNITS DOUBLE SKIN TYPE: FloorMounted Double Skin Air Handling Units ( 50 mm thickPUF insulated)Comprising of DIDW forward curvedcentrifugal blower having 50 mm static pressure.Drivepackage with motor, cooling coil selection.Pre filters sectionwith 20 µ filter. All the electrical comopents like motorjunction box, etc. (Sound level of all AHU not more than 60db )

a. 16000 CFM / 35.0 TR 4 Nos.b. 14000 CFM / 32.0 TR 4 Nos.c. 13000 CFM / 30.0 TR 4 Nos.d. 10000 CFM / 24.0 TR 1 Nos.e 8000 CFM / 18.0 TR 2 Nos.f 5500 CFM / 13.0 TR 1 Nos.

4.1

Double skin low height ( 50mm thick PUF insulated) ceiling concealed units ( 30 mm static pressure) comprising of DIDW centrifugal blower, drive package with motor, cooling coil section. Pre filter section with 20 microns filters.(Sound level of all AHU not more than 60 db )

a 5000 CFM / 10.0 TR 2 Nos.b 4000 CFM / 8.0 TR 1 Nos.c 2500 CFM / 5.0 TR 17 Nos.d 2000 CFM / 4.0 TR 54 Nos.

4.2Ceiling Suspended low static fan coil units with built inTEFC drive motor from inside & outlet double layer canvassconnection.

a 2.5 TR - 1000 cfm Rate Nos.b 2.0 TR - 800 cfm 44 Nos.c 1.5 TR - 600 cfm 36 Nos.

4.3 G.I. Sheet Metal Duct Work As Per IS-655G.I. Sheet Metal Duct (Rectangular)

a 0.63 MM (24G) 3600 M²b 0.80 MM (22G) 2300 M²c 1.00 MM (20G) 900 M²d 1.20 MM (18G) RATE M²

4.3.1 Powder Coated Extruded Aluminium Diffuser Of RequiredAirflow Angles With Al. VCD as per specification. 18 M²

4.3.2 Powder Coated Extruded Aluminium Diffuser Of RequiredAirflow Angles Without Al. VCD as per specification. 18 M²

4.3.3 Powder Coated Extruded Aluminium Linear Grilles Of RequiredAirflow Angles. 220 M²

4.3.4 Al. VCD For grille 80 M²

CHAPTER- 6 - SCHEDULE OF QUANTITIES & PRICESScope of work includes design, supply, erection, testing & commissioning of the complete H.V.A.C system. Withcomplete Tech Data.

PART- 4- AHU , F.C.U & RELATED LOW SIDE WORK

AIR HANDLING UNITS

APMC - BOQ - MALL.xls

Page 10: BOQ - MALL

APMC - BOQ - MALL.xls

Sr. No. Description Qty Unit Rate Amount

CHAPTER- 6 - SCHEDULE OF QUANTITIES & PRICESScope of work includes design, supply, erection, testing & commissioning of the complete H.V.A.C system. Withcomplete Tech Data.

PART- 4- AHU , F.C.U & RELATED LOW SIDE WORK

4.3.5 Aluminium Aerofoil Duct Dampers asw per specifications Rate M²

4.3.6 G.I. Volume control damper for duct 20 M²

4.3.7 FIRE DAMPER WITH FUSIBLE LINK RATE M²

4.4 Insulation Work

4.4.1

Duct acoustic insulation with 12.5 mm thick rigid board ofdensity 48 Kg. /Cu. M. and covered with tissue paper and 32 Gperforated Aluminium sheets from the inside of the duct as perspecifications12.5 mm 1200 M²

4.4.2 Thermal Insulation Of Ducts with NITRILE RUBBER on ductsurface area as Per Specification

a 19 mm thick 5400 M²b 12 mm thick Rate M²

4.4.3Thermal Insulation Of Ducts with "TF" Quality Expandedpolysterene covered with sand cement plaster on duct surfacearea as Per Specification ( Exposed Duct )

a 50 mm thick RATE M²

4.4.4 False Ceiling insulation by laying fibre glass in polythene bagson false ceiling as per specifications M²

a 50 mm thick Rateb 40 mm thick Rate

4.4.1 AHU Room wall accoustic insulation & shaft insulation as perstandard specification. 100 M²

4.4.5Plant Room Accoustic Insulation with 100 MM Thick fiberglasshaving 32 kg /m3 density covered with 28 GAUGE AL.Perforated Sheet in G.I. Channel Framing of 2'x2' grid.

200 M²

4.5Exhaust chimeny for VAM unit fabricated from "C" class M.Spiping having height of 2 mt up from building / top height.Size - 350 mm dia

60 Rmt

4.5.1Insulation work of exhaust chimeny work with using 75 mm th.LRB matress having density- 150 kg with 26 gauge aluminiumclading.Size - 350 mm dia.

60 Rmt

4.6

M.S. tank fabricated from 6 mm thick sheet with drain valve, fillup valve , drain valve , over flow valve , fuel level indicator withnecessary fitting & 40 mm dia pipe fitting - tank to m/c burner .Capacity - 1000 lts. & approx piping - 40 RMT

1 lot

4.7Pressure Redusing Valve ( PRV ) for Natural gas suitablepressure range of 1.5 kg to 0.1 kg / cm2 of each VAM. Size - 50mm dia

3 Nos

APMC - BOQ - MALL.xls

Page 11: BOQ - MALL

APMC - BOQ - MALL.xls

Sr. No. Description Qty Unit Rate Amount

CHAPTER- 6 - SCHEDULE OF QUANTITIES & PRICESScope of work includes design, supply, erection, testing & commissioning of the complete H.V.A.C system. Withcomplete Tech Data.

PART- 4- AHU , F.C.U & RELATED LOW SIDE WORK

4.8 Pot Stainer for Natural gas suitable for 1.5 kg/cm2 pressure ofeach VAM. Size - 50 mm dia 3 Nos

4.9 Pressure Gauge for Natural gas suitable for 0 - 6 kg/ cm2 & 6" dial size with Ball valva 6 Nos

4.10 Pressure Switch for Natural gas suitable for 0 - 6 kg/ cm2 withnecessary wiring. 3 Nos

SUB TOTAL- PART- 4- AHU, FCU & LOW SIDE WORK

APMC - BOQ - MALL.xls

Page 12: BOQ - MALL

APMC - BOQ - MALL.xls

Sr. No. Description Qty Unit Rate Amount5.0 KITCHEN VENTILATION

5.1 BASEMENT AREA VENTILATION5.1.1 Single Skin cabinet type Exhaust Air Unit

a 30000 CFM - 65mm static - Lower Basement 2 Nos.

b 30000 CFM - 65mm static - Upper Basement 2 Nos.

5.2 G.I. Sheet Metal Duct Work As Per IS-655G.I. Sheet Metal Duct

a 0.63 MM (24 Gauge ) 500 M2

CHAPTER- 6 - SCHEDULE OF QUANTITIES & PRICES

Scope of work includes design, supply, erection, testing & commissioning of the complete H.V.A.C system.With complete Tech Data.

PART - 5- BASEMENT & W/C VENTILATION SYSTEM

APMC - BOQ - MALL.xls

Page 13: BOQ - MALL

APMC - BOQ - MALL.xls

Sr. No. Description Qty Unit Rate Amount

CHAPTER- 6 - SCHEDULE OF QUANTITIES & PRICES

Scope of work includes design, supply, erection, testing & commissioning of the complete H.V.A.C system.With complete Tech Data.

PART - 5- BASEMENT & W/C VENTILATION SYSTEM

b 0.80 MM (22 Gauge ) 500 M2

c 1.00 MM (20Gauge ) 500 M2

d 1.20 MM ( 18Gauge ) 200 M2

5.2.1 G.I Duct Dampers 8 M2

5.2.2 Extruded Aluminium Griil with VCD 24 M2

5.3 Common Area Toilet Ventillation

5.3.1 Ceiling suspended Cabinet type Fresh Air Unit with DIDW Forward curved Centifugal Fan

a 1500 CFM - 40MM Static- Gr. 1st, 2nd , 3rd & 4th Floor 15 Nos.b 1000 CFM - 40MM Static- 5th & 6th floor - Auditorium 4 Nos.

5.4 G.I. Sheet Metal Duct Work As Per IS-655G.I. Sheet Metal Duct (Rectangular)

a 0.63 MM ( 24Gauge ) 850 M2

b 0.80 MM (22 Gauge ) 250 M2

5.4.1 G.I Duct Dampers 3 M2

5.4.2 Extruded Aluminium Griil for exhaust .a 6"X6" 250 Nos.

# SUB TOTAL - PART- 5 - VENTILATION SYSTEM

APMC - BOQ - MALL.xls

Page 14: BOQ - MALL

APMC - BOQ - MALL.xls

Sr. No. Description Qty Unit Rate Amount

CHAPTER- 6 - SCHEDULE OF QUANTITIES & PRICES

Scope of work includes design, supply, erection, testing & commissioning of the complete H.V.A.C system.With complete Tech Data.

PART - 5- BASEMENT & W/C VENTILATION SYSTEM

APMC - BOQ - MALL.xls

Page 15: BOQ - MALL

Sr. No. Description Qty Unit Rate

6.0 ASSOCIATED ELECTRICAL WORKFOR AIRCONDITIONING SYSTEM

6.1 MAIN HVAC Panels FOR PLANT ROOM AT GR. FL.Including following

a VAM M/C - 03 NOS - 10 hp 1 No.b Condensor Water Pumps- 04 nosc Chilled Water Pumps - Primery - 04 nosd Chilled Water Pumps - Secondery -03 nos ( With VFD )e Cooling Tower Motor - 03 nos - f Spare Feeder - 10 hp - 02 nosg Spare Feeder -MCB - 32 amp - 04 nos

6.2Electrical Cabling for the above work of followingsizes with Brass cable glands and Cu/Al. lugstermination as per Specification

a 45 Sqm. X 3.5 core Armour Aluminium Cable 125 Rmt.b 35 Sqm. X 3.5 core Armour Aluminium Cable 125 Rmt.c 4 Sqm. X 4 core- Armour Cupper cable 200 Rmt.

6.3 Control cabling for the equipments as perspecification 1 Lot

6.4 Earthing of All Equipment Motors as perspecifications RMT

b 25mm x 3mm GI strip 75c 12 SWG CU Wire 75

SUB TOTAL- PART- 6 - ELECTRICAL WORK

PART- 6- ELECTRICAL WORK

Scope of work includes design, supply, erection, testing & commissioning of the completsystem. With complete Tech Data.

CHAPTER- 6 - SCHEDULE OF QUANTITIES & PRICES

Page 16: BOQ - MALL

Amount

0

000

0

00

0

te Electrical

S

Page 17: BOQ - MALL

APMC - BOQ - MALL.xls

PART DESCRIPTION AMOUNT IN RS. REMARK

PART-1 HIGH SIDE EQUIPMENT - VAHP UNIT

PART-2 COOLING TOWER , CHW & COND. WATER PUMPS,CONDENSER WATER PIPNG

PART-3 CHILLED WATER PIPING VALVES & ITS INSULATIONWORK

PART-4 AHU's & RELATED LOW SIDE WORK

PART-5 VENTILATION SYSTEM FOR BASEMENT & W/C AREA

PART-6 ELECTRICAL WORK FOR PLANT ROOM

GRAND TOTAL

SUMMARY REPORT FOR M\s. A.P.M.C - MALL PROJECT - SURAT